A9-30-22 220-230V 50Hz / 230-240V
60Hz
Products Low Voltage Products and Systems Control Products Contactors Block Contactors
General Information
Extended Product Type: A9-30-22 220-230V 50Hz / 230-240V 60Hz
Product ID: 1SBL141001R8022
EAN: 3471522034809
Catalog Description: A9-30-22 220-230V 50Hz / 230-240V 60Hz Contactor
Long Description: A 9 contactors are mainly used for controlling 3-phase motors and generally for controlling
power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many oth
er applications such as isolation, capacitor switching, lighting. The A... series 2-stack 3-pol
e contactors are of the block type design. - Main poles and auxiliary contact blocks: 1st sta
ck with 3 main poles, 2nd stack with 4 built-in auxiliary contacts, side-mounted add-on auxili
ary contact blocks (The built-in auxiliary contact elements are mechanically linked) - Contro
l circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessor
ies is available.
Additional Information
ABB Industrial IT Suite: Control IT
Ambient Air Temperature: Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
Close to Contactor for Storage -60 ... +80 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C
Close to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C
BV Certificate: BV_2634H07559D0
Block Contactor Type: 3-Pole Contactor
CB Certificate: CB_FR_602227A
CCC Certificate: CCC_2013010304615753
CCC_2004010309130463
CSA Certificate: CSA_1041746
Climatic Withstand: acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Coil Consumption: Average Holding Value 50 / 60 Hz 8 V·A
Average Holding Value 50 / 60 Hz 2 W
Average Pull-in Value 50 Hz 74 V·A
Average Pull-in Value 60 Hz 70 V·A
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) °C
Coil Voltage Code: 80
Connecting Capacity Auxiliary Circuit: Flexible with Cable End 0.75 ... 2.5 mm²
Rigid Cable 1 ... 4 mm²
Connecting Capacity Main Circuit: Flexible with Cable End 0.75 ... 2.5 mm²
Rigid Cable 1 ... 4 mm²
Connecting terminals (delivered in open M 3.5 (+,-) pozidriv 2 screws with cable clamp
position) Built-in auxiliary terminals:
Connecting terminals (delivered in open M 3.5 (+,-) pozidriv 2 screws with cable clamp
position) Coils terminals:
Connecting terminals (delivered in open M 3.5 (+,-) pozidriv 2 screws with cable clamp
position) Main poles:
Conventional Free-air Thermal Current acc. to IEC 60947-4-1, Open Contactors q = 40 °C 26 A
(Ith): acc. to IEC 60947-5-1, q = 40 °C 16 A
Country of Origin: France (FR)
Customs Tariff Number: 85369085
Data Sheet, Technical Information: 1SBC100122C0202_Ch02
Declaration of Conformity - CE: 1SBD250801U1000
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Drop-out Voltage in %of Uc: Approximate 40 … 65 %
EAC Certificate: EAC_RU C-FR ME77 B01010
EAN: 3471522034809
ETIM 4: EC000066 - Magnet contactor, AC-switching
ETIM 5: EC000066 - Magnet contactor, AC-switching
ETIM 6: EC000066 - Power contactor, AC switching
Environmental Information: 1SBD250001E1004
GOST Certificate: GOST_POCCFRME77B07175
IIT Publishing Status: Level 0 - Information enabled
Industrial IT Certification Level: 0
Instructions and Manuals: FPTC407721P0001
Invoice Description: A9-30-22 220-230V 50Hz / 230-240V 60Hz Contactor
LR Certificate: LRS_9830011E4
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Maximum Electrical Switching Frequency: AC-1 600 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
Maximum Mechanical Switching 3600 cycles per hour
Frequency:
Maximum Operating Altitude Permissible: 3000 m
Mechanical Durability: 10 million
Minimum Order Quantity: 1 piece
Minimum Switching Capacity: 17 / 5 volt per milliamp
Mounted Auxiliary Contacts 1st Stack: 0 NO, 0 NC
Mounted Auxiliary Contacts 2nd Stack: 2 NO, 2 NC
Mounting Position: Position 1 to 5 -Ambient temperature =<55°C and control voltage 0.85 - 1.1 Uc, Ambient temp
erature 55 - 70°C and control voltage equal to Uc, Position 6 - Ambient temperature =<55°C
and control voltage 0.95 - 1.1 Uc, Ambient temperature >55°C unauthorised
Non-overlapping Time Between N.O. and >= 2 ms
N.C. Contacts:
Number of Auxiliary Contacts NC: 2
Number of Auxiliary Contacts NO: 2
Number of Main Contacts NC: 0
Number of Main Contacts NO: 3
Object Classification Code: Q
Operate Time: Between Coil Energization and NO Contact Closing 10 ... 26 ms
Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil De-energization and NC Contact Closing 9 ... 16 ms
Between Coil Energization and NC Contact Opening 7 ... 21 ms
Order Multiple: 1 piece
Package Level 1 EAN: 3471522034809
Package Level 1 Gross Weight: 0.4 kg
Package Level 1 Height: 46 mm
Package Level 1 Length: 110 mm
Package Level 1 Units: 1 piece
Package Level 1 Width: 78 mm
Package Level 2 Units: 48 piece
Package Level 3 Units: 576 piece
Power Loss: at Rated Operating Conditions per Pole 0.1 W
at Rated Operating Conditions per Pole 0.8 W
at Rated Operating Conditions per Pole 0.1 W
at Rated Operating Conditions per Pole 0.1 W
Product Main Type: A9
Product Name: Block Contactor
Product Net Depth: 107 mm
Product Net Height: 74 mm
Product Net Weight: 0.400 kg
Product Net Width: 44 mm
RINA Certificate: RINA_ELE128713XG001
RMRS Certificate: RMRS_0507015250
Rated Breaking Capacity AC-3 acc. to IEC 8 x Ie AC-3
60947-4-1:
Rated Breaking Capacity acc. to IEC 10 x Ie AC-15
60947-5-1:
Rated Control Circuit Voltage (Uc): 50 Hz 220 … 230 V
60 Hz 230 … 240 V
Rated Frequency (f): Supply Circuit 50 Hz
Supply Circuit 60 Hz
Rated Frequency Limits: 25 … 400 Hz
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Insulation Voltage (U):
i acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
acc. to UL/CSA 600 V
Rated Making Capacity AC-3 acc. to IEC 10 x Ie AC-3
60947-4-1:
Rated Making Capacity acc. to IEC 60947- 10 x Ie AC-15
5-1:
Rated Operational Current AC-1 (Ie): (690 V) 40 °C 25 A
(690 V) 55 °C 22 A
(690 V) 70 °C 18 A
Rated Operational Current AC-15 (Ie): (220 / 240 V) 4 A
(24 / 127 V) 6 A
(380 / 440 V) 3 A
(500 V) 2 A
(690 V) 2 A
Rated Operational Current AC-3 (Ie): (220 / 230 / 240 V) 55 °C 9 A
(380 / 400 V) 55 °C 9 A
(415 V) 55 °C 9 A
(440 V) 55 °C 9 A
(500 V) 55 °C 9 A
(690 V) 55 °C 7 A
Rated Operational Current DC-13 (Ie): (125 V) 0.55 / 69 A
(24 V) 6 / 144 A
(250 V) 0.3 / 75 A
(48 V) 2.8 / 134 A
(72 V) 1 / 72 A
Rated Operational Power AC-3 (Pe): (220 / 230 / 240 V) 2.2 kW
(380 / 400 V) 4 kW
(415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
Rated Operational Voltage: Main Circuit 690 V
Rated Short-time Withstand Current (Icw): at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 100 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 26 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 50 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 60 A
for 0.1 s 140 A
for 0.1 s 140 A
for 1 s 100 A
RoHS Date: 20050501
RoHS Information: 1SBD350061R1000
RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
Selling Unit of Measure: piece
Short Description: A9-30-22 220-230V 50Hz / 230-240V 60Hz Contactor
Short-Circuit Protective Devices: Auxiliary Circuit - gG Type Fuses 10 A
gG Type Fuses 25 A
Standards: Devices complying with international standards IEC 947-1 / 947-4-1, and European standard
s EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to I
EC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1
Terminal Type: Screw Terminals
UL Certificate: UL_20160205-E312527-10-2
UL Listing Card: UL_E312527
UNSPSC: 39121529
DNV GL Certificate: DNV-GL_TAE00000TX