C3-05 Controls O&M Version 3.1
C3-05 Controls O&M Version 3.1
Contents
Hardware Structure 3
Display Information 7
Networking 24
Cooling Operation 49
Heating Operation 56
Humidifier 57
Dehumidification Operation 65
Ambicool Operation 66
Combicool Operation 66
Generator Run 67
Software Upgrade 71
Hardware Structure
Connection to Denconet
Analogue Inputs 1 to 3
Analogue Outputs 1 to 4
Digital Inputs 1 to 8
Digital Outputs 14 to 18
Analogue Inputs 6 to 8
Digital Inputs 9 to 12
Expansion I/O
Connection
Digital Inputs 13 & 14
The controller, graphical displays, network and interface boards contain devices sensitive to body static
discharges. If they have to be removed and handled, follow the procedure given below:
r Discharge body static by wearing anti-static wrist straps (or similar suitable grounding straps) connected
to earthed (grounded) metal.
r Switch off at the display ON/OFF switch. Turn the unit isolator to the "OFF" position.
Base Controller
The following inputs and outputs are available on the Base Controller:
INPUTS
Digital
ID1 Unit Remote On/Off 24V AC (Open circuit = unit off)
ID2 Airflow Fail 24V AC (Open circuit = alarm condition)
ID3 Filter Blocked 24V AC
ID4 Klixon Trip 24V AC (Open circuit = alarm condition)
ID5 HP Trip Comp 1 (Or Tandem Circuit 1) 24V AC
ID6 HP Trip Comp 2 (Or Tandem Circuit 2) 24V AC
ID7 LP Trip Comp 1 (Or Tandem Circuit 1) 24V AC
ID8 LP Trip Comp 2 (Or Tandem Circuit 2) 24V AC
ID9 Water On Floor / Drip Tray Detection 24V AC
ID10 Humidifier Water Level / 24V AC (Open circuit = alarm condition)
Humidifier Global Alarm
ID11 Aux Alarm 24V AC
ID12 Generator Run 24V AC
ID13 Combicool Change-over 24V AC
ID14 Refrigerant Leak Detection 24VAC
ID15 HP Trip Comp 3 24V AC
ID16 HP Trip Comp 4 24V AC
ID17 LP Trip Comp 3 24V AC
ID18 LP Trip Comp 4 24V AC
Analogue
B1 Return Air Hum Sensor type: 0-1V
B2 Condensing Pressure 1/Suction Pressure Sensor type: 4 - 20 mA (Selectable)
B3 Condensing Pressure 2/Discharge Pressure Sensor type: 4 – 20 mA (Selectable)
B4 Return Air Temp Sensor type: NTC
B5 Supply Air Temp Sensor type: NTC
B6 Supply Air Humidity/DP Transducer Sensor type: 0-1V/4-20mA
B7 Humidifier Conductivity Sensor type: 0-1V
B8 Humidifier Current Sensor type: 0-1V
B9 Freecool / CW Temperature Sensor type: NTC
Notes:
(i) A high digital input condition will be within the voltage band –25% to +20% 50 Hz or 60 Hz. (High > 18.5V,
Low < 16.5V).
(ii) All digital inputs are opto-isolated complete with reverse voltage protection diodes.
(iii) HP / LP 3 and 4 Alarm inputs only available when C3-05 large controller fitted.
(iv) If ‘Heat Pump’ selected, B2 is configured for the Suction Pressure and B3 is configured for Discharge
Pressure.
(v) If ‘Humidifier Type’ selected for ‘Remote’, then ID10 is configured as a Humidifier Global Alarm.
OUTPUTS
Digital
NO1 Unit Fan Relay Output Normally Open Contact
NO2 Dehumidification Relay Output Normally Open Contact
NO3 Heater 1 / DODC Heat Open / Thyristor Enable Relay Output Normally Open Contact
NO4 Heater 2 / DODC Heat Close Relay Output Normally Open Contact
NO5 Compressor 1 / DODC Cool Open / Combicool Relay Output Normally Open Contact
Secondary CW Open
NO6 Compressor 2 / DODC Cool Close / Combicool Relay Output Normally Open Contact
Secondary CW Close
NO7 Compressor 3 Relay Output Normally Open Contact
NO8 Compressor 4 Relay Output Normally Open Contact
NO9 Humidifier Power Contactor Relay Output Normally Open Contact
NO10 Hum Fill Valve Relay Output Normally Open Contact
NO11 Hum Drain Valve Relay Output Normally Open Contact
NO12 Critical Alarm Relay Output Normally Closed Contact
NO13 Maintenance Alarm Relay Output Normally Closed Contact
NO14 Freecool / Combicool Primary CW DODC Open Relay Output Normally Open Contact
NO15 Freecool / Combicool Primary CW DODC Close Relay Output Normally Open Contact
NO16 Dry Cooler Fan 1 Relay Output Normally Open Contact
NO17 Dry Cooler Fan 2 Relay Output Normally Open Contact
NO18 Heat Pump Enable Relay Output Normally Open Contact
Analogue
Condenser fan control Condenser fan control Condenser fan control
disabled enabled – 1 Circuit enabled – 2 Circuits
Y1 Evaporating Fan Evaporating Fan Evaporating Fan 0 – 10 VDC
Y2 Heating Heating Heating 0 – 10 VDC
Y3 Cooling Condenser Circuit 1 Fan Condenser Circuit 1 Fan 0 – 10 VDC
Y4 Humidifier Humidifier Condenser Circuit 2 Fan 0 – 10 VDC
Y5 Cooling 0 – 10 VDC
Y6 Humidifier 0 – 10 VDC
Notes:
(i) All digital outputs are relay contacts rated at 24 VDC – 240 VAC 10A fitted with surge suppressor
network.
(ii) All PCB tracks rated to withstand let through energy of a 24 VAC control fuse (10A).
(iii) All output relay contacts common to 24 VAC (except alarm relays).
(iv) Valve open / close on heating / cooling / freecool outputs refer to drive open / drive close valves only.
(v) Drycooler fans and Freecool Valve open / close outputs only available when C3-05 large controller fitted.
(vi) The evaporating fan output is to operate concurrently with the cooling, heating, humidification and
dehumidification demands.
(vii) Cooling and heating outputs shall operate concurrently with digital / DODC outputs according to the
demand calculations.
(viii) If ‘Condenser Fan’ is configured for ‘Enabled’ and there are 2 cooling circuits, then a C3-05 large
controller is required for the cooling and humidifier demand 0-10VDC signals.
Display Information
Alarm Key
On/Off Key
The 8 row LCD indicates Unit Function via the icons on rows 1 and 2. The remaining rows show the selected
data, updated in real time.
The programming keys ( ↓ ↑ ← → ) have to be pressed in a coded sequence in order to enter or change the
function currently being accessed.
Current Alarm status can be reviewed by using the ← key to access the Alarm Buffer from the time-out display.
The display can be mounted upto 50 metres from the controller using the standard 6 core flat data cable.
A screened cable must be used if the display is to be mounted between 50 and 500 metres from the controller.
A separate 24Vac power supply is required when the display is to be mounted between 500 m and 1 kilometre.
A ferrite must be connected, at the display end of the cable, to reduce the risk of electrical interference.
Unit Model
D28AVH
Description
21.3°C U:01
Date
52.5%RH Unit Number
01:01:05 18:54
D28AVH
Unit ON
Time
The time-out display is the controllers' standard display at power up, during normal unit running conditions or the
default display from all software levels given that no key had been pressed for a five minute period.
When in Time Out Display, pressing the left (←) arrow key allows entry into the Alarm Buffer display. Alternatively
pressing the right (→) arrow key allows entry into the Main Menu display.
When in Time Out Display, pressing the down arrow (↓) key allows entry into four additional unit information
pages. These are set out as follows: -
Timeout Page
AMBICOOL STATUS
A.cool Demand 000.0%
Freecool Temp 00.0°C
HUMIDIFIER STATUS
Conduct. 000us/cm
Current 0.0A
COMBICOOL STATUS
Primary Cooling p
Secondary Cooling p
Changeover By DI p
Changeover By Temp p
Commissioning Date
00:00:00
Notes
1. C/M Refers to the users choice of Critical or Maintenance relay which can be selected in Level 3, Alarm
Setup.
Level 1 Password ?
5.0 deg C
21.0
Level 2 Setpoints Temp Setpoint Set Temp Setpoint 35.0 deg C
Alarm
MAIN MENU
Level 1
24 Hour Minimum
* Only Available If Enabled
25.9°c
Networking
Network Wiring
Up to a maximum of 8
units on the network
Rx+/Tx+
Rx+/Tx+
Rx+/Tx+
Rx+/Tx+
Rx-/Tx-
Rx-/Tx-
Rx-/Tx-
Rx-/Tx-
GND
GND
GND
GND
Unit 1 Unit 2 Unit 3 Unit 8 (max)
Note: The recommended cables to use for the network are any of the following:
Beldon 8761
Alpha 2401C
BICC H8082
Brand Rex BE-56761
Controller Addresses
When the C3-05 controllers are networked together, the controllers, Electronic Expansion Valve drivers and
displays must be configured with their specific addresses, as follows;
Networking (cont)
UP
DOWN
RIGHT
6. Press and keys simultaneously and switch the mains power off and back on.
7. After approximately 20 seconds a page reading “self test please wait” will appear, then release the keys.
ALARM UP
11. Press the key to move the cursor to the display address.
12. Press the key to change the display address to the required address, e.g. 25
16. Press the key once to initialise the selected controller address.
20. Press the key to adjust “Trm 1” value to the required display address, e.g. 25
Networking (cont)
Denconet Routines.
Master Temp.
If selected as "MASTER TEMP.", then the temp. sensor value is transmitted to all units on the network that are
configured as "SLAVE TEMP." (and "CHECK TEMP."). The "MASTER TEMP." controller and all the "SLAVE
TEMP." controllers (and "CHECK TEMP." controller) control to the "MASTER TEMP." sensor value.
Check Temp.
If selected as "CHECK TEMP." in addition to being a slave temp. controller, the "CHECK TEMP." will also address
the "MASTER TEMP." every 60 seconds for a sensor fail alarm or comms fail alarm.
If the sensor fail alarm is active, the "CHECK TEMP." becomes "RE-ASSIGNED MASTER TEMP." and "MASTER
TEMP." becomes re-assigned as "SLAVE TEMP." and an alarm condition is flagged on the re-assigned "SLAVE
TEMP." "RE-ASSIGNED SLAVE SENSOR FAIL".
There will be no re-assigned "CHECK TEMP." upon the sensor fail or comms fail until the system is corrected and
reset.
If the sensor fail and comms fail safe, then the "MASTER TEMP." and "CHECK TEMP." remains as assigned.
Slave Temp.
If selected as "SLAVE TEMP.", then the temp. sensor value is received from the "MASTER TEMP." or the
"RE-ASSIGNED MASTER TEMP.".
The "SLAVE TEMP." controller controls to the "MASTER/RE-ASSIGNED MASTER TEMP." sensor value.
Master Hum
If selected as "MASTER HUM", then the hum sensor value is transmitted to all units on the network that are
configured as "SLAVE HUM" (and "CHECK HUM"). The "MASTER HUM" controller and all of the "SLAVE HUM"
controllers (including "CHECK HUM") control to the "MASTER HUM" sensor value.
Check Hum
If selected as "CHECK HUM" in addition to being a "SLAVE HUM" controller, the "CHECK HUM" will also address
the "MASTER HUM" every 60 seconds for a sensor fail or comms fail alarm.
If the sensor fail alarm is active, the "CHECK HUM" becomes "RE-ASSIGNED MASTER HUM" and "MASTER
HUM" becomes "RE-ASSIGNED SLAVE HUM" and an alarm condition is flagged on the re-assigned "SLAVE
HUM" "SENSOR FAIL".
There will be no re-assigned "CHECK HUM" upon the sensor fail or the comms fail until the system is corrected
and reset.
If the sensor fail and comms fail safe, then the "MASTER HUM" and "CHECK HUM" remain as assigned.
Slave Hum
If selected as "SLAVE HUM", then the hum sensor value is received from the "MASTER HUM" or the
"RE-ASSIGNED MASTER HUM". The "SLAVE HUM" controller controls to the "MASTER HUM" or the
"RE-ASSIGNED MASTER HUM" sensor value.
Networking (cont)
NOTES
1. It must not be permissible to have two masters (temp. or hum) on the network. If this configuration is
inadvertently set, then the master unit with the lowest unit number is set as "Master".
2. It must not be permissible to have two checks (temp. or hum) on the network. If this configuration is
inadvertently set, then the check unit with the lowest unit number is set as "Check".
3. A comms error/failure will operate the communication drop out relay and flag a "Network Failure" alarm. A
global comms error - then all of the controllers will automatically revert to stand alone temp. and hum control.
4. All slave and check slave units will display the temperature and humidity sensor values of the designated
master unit.
All stand alone units will display its local sensor values.
5. When operating as a master check slave, all operating parameters/settings/alarms will function as normal. The
temp./hum alarm conditions will be generated only from the master unit (or the re-assigned master). When
operating as stand alone, the temp. and hum condition alarm will be active on the local unit. The master unit will
be running, otherwise the lowest running unit number will generate the alarm.
6. Normal alarm conditions on the controllers will have no affect upon the network irrelevant of the set
configuration.
7. The network mode will allow for only one change of unit configuration on the sensor fail or comms fail.
Sensor Averaging
Average Temp.
If selected as average temp., then the temp. sensor value is transmitted across the network. Each controller
configured as "average temp." will calculate the average temp. value and control to that value.
Average Hum
If selected as average hum, then the hum sensor value is transmitted across the network. Each controller
configured as average hum will calculate the average hum value and control to that value.
NOTES
1. A sensor failure will be flagged as an alarm condition and the sensor value will not be part of the averaged
calculation.
2. A comms failure will be flagged as an alarm condition (network failure). A global comms error - then all of the
controllers will automatically revert to stand alone temp. and hum control.
3. Any controllers on the unit in a sensor fail or comms fail mode will not form part of the averaged sensor value.
4. Normal alarm conditions will have no affect upon the network commands irrelevant of the set configuration.
5. All units configured as average temp./hum will display the averaged sensor value. All stand alone units will
display the local sensor values.
6. When operating as an averaging controller, all operating parameters/settings/alarms will function as normal.
The temp./hum alarm condition will be generated on the lowest unit number selected as averaging. When
operating as "stand alone", the temp. and hum condition alarm will be active on the local unit.
Auto Change-Over
Network
If selected as "network mode", the controllers will be automatically sequenced to equalise running hours on all
machines. The sequencing time will be set in Level 3 with movements of 168 hours standard. However, there will
be a facility in the factory configuration to reduce the sequence time down to 1 hour minimum.
The last unit number of the network is always the standby controller. After the sequence time has elapsed, the
controllers on the network are automatically sequenced.
Controller 1 2 3 4 5
Start Duty Duty Duty Duty Stand By
1 Seq. Time Stand By Duty Duty Duty Duty
2 Seq. Time Duty Stand By Duty Duty Duty
3 Seq. Time Duty Duty Stand By Duty Duty
4 Seq. Time Duty Duty Duty Stand By Duty
5 Seq. Time Duty Duty Duty Duty Stand By
REPEAT
In the event of a critical or maintenance alarm condition of any duty controller, the standby will automatically start.
The controller in an alarm condition will also run and the alarm condition will be displayed.
There will be a facility to stop the failed unit or for the failed unit to continue to run.
In the event of a power failure or a controlled shutdown, the sequence of rotation will be stored in the memory so
that the duty controllers at power down will remain the duty controllers at restart. The sequence rotation can be
reset at any time to the start sequence accepting the sequence reset in Level 3. During the sequence rotation the
duty unit is stopped before the stand-by unit runs.
Stand Alone
If selected as "stand alone", the sequence rotation command is still active but the stand alone setting will have
priority. Hence, if the stand alone is reset to "network", the controller will automatically take its position in the
sequence rotation.
NOTES
1. The Auto Change-Over Test, Time and Reset can only be configured from unit no. 1.
2. A comms failure will be flagged as an alarm condition and then all controllers on the network revert to stand
alone operation and all controllers run.
3. There will be a test/commission sequence time of 3 minutes. To prevent this sequence time inadvertently being
left set as 3 minutes, after a period of 30 minutes, the sequence rotation time as set will be installed.
4. Normal alarm conditions will have no effect upon the network commands irrelevant of the set configuration.
Monitoring Display
Master Display
Monitoring Connection
Display Details
Connection Details
*1 = Denconet Cable - Serial
*2 = Unit Display Cable
*3 = Master Display Cable
Monitoring Display
TCONN Module
*3
*1
*1
Unit No. 1
TCONN Module
Unit No. 2
Interface cards that are fitted to a controller allow exchanging variable values from one card to another, according
to the Supervisory Variable List, as detailed on page 8.
• Unit status
• Air temperature & humidity values
• Output demands
• Water temperature value
• Condensing pressures values
• Temperature & humidity setpoint adjustment
• Dead zone & proportional band adjustment
• Alarm monitoring
When any of the Serial Data Interfaces are used, there are three settings within Level 3, BMS Communication of
the controller that needs to be configured to suit the BMS requirements:
• BMS Protocol (default Carel)
• BMS Address (default 1)
• BMS Baud Rate (default 19200)
The pCOnet interface allows connection to a BACnet MS/TP network (Master/Slave/Token pass).
It is BTL™ (BACnet Test Laboratory) certified for BACnet™ protocol communication.
Digital Variables
Index Description Type
1 BMS Unit On/Off R/W
2 Enable Unit On/Off by Time zones R/W
3 Enable Unit Temperature Set Point Adjustment by Time zones R/W
4 Enable Unit Humidity Set Point Adjustment by Time zones R/W
5 Return Air Temperature Sensor Fail Alarm R
6 Return Air Humidity Sensor Fail Alarm R
7 Condensing pressure 1 Sensor Fail Alarm R
8 Condensing pressure 2 Sensor Fail Alarm R
9 Water Temperature Sensor Fail Alarm R
10 Supply Air Temperature Sensor Fail Alarm R
11 Supply Air Humidity Sensor Fail Alarm R
12 Airflow Fail Alarm R
13 Filter Blocked Alarm R
14 Water Detection Alarm R
15 Auxiliary Alarm R
16 High Control Temperature Alarm R
17 Low Control Temperature Alarm R
18 High Control Humidity Alarm R
19 Low Control Humidity Alarm R
20 Low Supply Temperature Alarm R
21 High Supply Humidity Alarm R
22 Klixon Trip Alarm R
23 Compressor 1 High Pressure Trip Alarm R
24 Compressor 2 High Pressure Trip Alarm R
25 Compressor 3 High Pressure Trip Alarm R
26 Compressor 4 High Pressure Trip Alarm R
27 Circuit 1 (VRF) High Pressure Trip Alarm R
28 Circuit 2 (VRF) High Pressure Trip Alarm R
29 Compressor 1 Low Pressure Trip Alarm R
30 Compressor 2 Low Pressure Trip Alarm R
31 Compressor 3 Low Pressure Trip Alarm R
32 Compressor 4 Low Pressure Trip Alarm R
33 Circuit 1 (VRF) Low Pressure Trip Alarm R
34 Circuit 2 (VRF) Low Pressure Trip Alarm R
35 Denconet Comms Alarm R
36 Humidifier High Current Alarm R
37 Humidifier Lack Of Water Alarm R
38 Humidifier Low Current Alarm R
39 Clock Alarm R
Analogue Variables
Index Description Type
1 Control Temperature R
2 Control Humidity R
3 Return Air Temperature R
4 Return Air Humidity R
5 Cooling Demand R
6 Heating Demand R
7 Humidity Demand R
8 Dehum Demand R
9 Ambicool Demand R
10 Supply Air Temperature R
11 Supply Air Humidity R
12 Water Temperature R
13 Condensing Pressure 1 R
14 Condensing Pressure 2 R
15 Temperature Set Point R/W
16 Humidity Set Point R/W
17 Time Zone 1 Temperature Set Point R/W
18 Time Zone 2 Temperature Set Point R/W
19 Time Zone 3 Temperature Set Point R/W
20 Time Zone 4 Temperature Set Point R/W
21 Time Zone 1 Humidity Set Point R/W
22 Time Zone 2 Humidity Set Point R/W
23 Time Zone 3 Humidity Set Point R/W
24 Time Zone 4 Humidity Set Point R/W
25 Cooling Dead Zone R/W
26 Cooling Proportional Band R/W
27 Heating Dead Zone R/W
28 Heating Proportional Band R/W
29 Dehum Dead Zone R/W
30 Dehum Proportional Band R/W
31 Humidity Dead Zone R/W
32 Humidity Proportional Band R/W
33 Free Cool Water Set Point R/W
34 Dry Cooler Stage Differential R/W
35 Combicool Chilled Water Temperature Limit R/W
36 Temperature Alarm Band R/W
37 Humidity Alarm Band R/W
38 Tile Unit (LECU) Average Temperature (FROM THE BMS) R/W
39 LECU 1 Room Temperature R
40 LECU 1 Underfloor Temperature R
Interger Variables
Index Description Type
1 Unit Serial Number Digit 1 R
74 Month R
75 Year R
76 Hour R
77 Minute R
Proportional Control
Proportional control is the relationship between the
setpoint, proportional band and the actual control air
o
temperature. For a setpoint of 21 C, a proportional
o
band of 2 C and one stage of cooling, to enable the
cooling the control air temperature has to rise to
o
setpoint plus proportional band, i.e. 23 C ( 21 + 2 ). If
the number of cooling stages is increased to two then
the first stage would be enabled at setpoint plus (prop.
o
band/2), i.e. 22 C ( 21 + 2 / 2 ). Both stages will be
o
enabled at 23 C.
The same theory applies to chilled water outputs. For the valve to be fully open, the control air temperature has to
be at setpoint plus the full proportional band.
r A large proportional band will mean a slow system response, i.e. the control air temperature would have
to rise to a high level before full cooling is enabled, and subsequent shutting off of the cooling would also be
slower. A small or tight proportional band will bring on cooling quicker but would result in system instability or
"hunting".
r An optimum proportional band will be set for the room conditions but due to inherent heat generation
there will generally be a steady state error or "offset" from the setpoint at which the room conditions are
maintained.
The rule-of-thumb of Ziegler and Nichols is by far the simplest procedure for loop tuning. There are two methods,
both detailed below:
At this point note the cooling proportional band (Cpb) and the period of a
complete oscillation (Ti).
Once the optimum settings have been calculated set for P + I control and enter values accordingly.
2. Step Method
This method avoids the necessity of putting the control loop in oscillation.
Adjust the setpoints such that there are no cooling, heating, hum or dehum outputs, and allow conditions to
stabilise.
Manually operate 50% of the cooling capacity and plot the response in the control temperature from the logged
values. The result is normally as shown below:
Cooling Operation
Cooling is achieved by one of two methods, Direct Expansion or Chilled Water in response to a cooling demand
from the microprocessor controller. Factors that affect the cooling demand is the relationship of the control air
temperature to the temperature setpoint, cooling proportional band and cooling dead zone.
In the case of DIRECT EXPANSION (DX) one, two, three or four stages can be selected (Software Level 3
Factory Settings) to achieve the full (100%) cooling demand. Switch on points for each stage is determined as
follows "100% divided by Number of Stages". The stages can be set for automatic sequencing such that the first
stage started is the first stage to be stopped to balance running hours and minimize the number of starts.
Automatic sequencing of compressors can be disabled via the software to ensure that Cooling Stage 1 is always
energised first (used for Hot Gas Re-heat - if fitted).
• LP delay time.
When a cooling output is energised, the LP Delay Time in Level 3 (default 10 minutes) is initiated to delay the
LP alarm energising and allowing the compressor to keep running.
When the LP Delay Time has elapsed, and if there is still a LP signal, the cooling output will de-energise and
the alarm is generated. The cooling output will not re-energise until the alarm has been reset on the display
and the number of compressor starts per hour protection timer has elapsed.
For CHILLED WATER (CW), the controller drives a valve actuator to position a three-way valve to meet the
cooling demand. A unit that is configured for Chilled Water operation will use Cooling outputs 1 and 2 to run the
valve actuator, output number 1 will be used to drive the actuator open and output number 2 drive it close. For a
valve actuator with a full running time of 150 seconds from fully closed to fully open it can be seen, assuming the
valve is fully closed, if output number 1 is energised for 150 seconds the valve will be opened 100%. As the valve
actuator running time is not proportional to the amount the valve actuator moves, the controller uses an algorithm
to determine the time an output is energised in order to position the valve. Thus to open or close a valve a certain
amount the appropriate output will be energised for a certain amount of time. To enable the controller to
determine the position of the actuator on start-up (or at any time the AHU is stopped and started) it will initially
energise the drive close output for 110% of the valve running time. This ensures the valve is at the fully closed
position and any subsequent movement is from a set position. Thus at switch-on the valve may initially be seen to
close even though conditions maybe calling for a cooling demand.
Pipe Size Denco Part No. Valve Stroke Valve Run Time
½ in. (DN15) 2/293/182 8mm 60 sec.
¾ in. (DN20) 2/293/183 8mm 60 sec.
1 in. (DN25) 2/293/184 13mm 135 sec.
1¼ in. (DN32) 2/293/185 13mm 135 sec.
1½ in. (DN40) 2/293/186 19mm 200 sec.
2 in. (DN50) 2/293/187 19mm 200 sec.
The controller can also provide a 0 - 10V DC output to a chilled water valve actuator if required.
In addition to the above, the microprocessor controller has integral action which is added to the cooling demand.
On an air cooled DX system (A type), it is possible to configure, in Level 3, Factory Configuration, the control of
the condenser fans via an electronic speed controller.
A 4-20mA, 0-30bar pressure transducer is required to be fitted to the discharge line of the DX system and the
value is monitored by the C3-05 controller.
Fan Enable
If enabled, there are two types of condenser fan control, either to select the fans to continue to operate when the
setpoint is achieved at the set minimum speed or to select the fans to ‘cut-off’ when the setpoint is achieved.
Set Point
The set point is the pressure value when the fan speed is at its minimum or cut-off.
Differential
The differential is the pressure value between the set point and the point at which the fan speed is at its
maximum.
Minimum Speed
The minimum speed is the % value of the differential that dictates the fan minimum speed or cut-off point and
configures the Condenser Fan analogue output signal to suit.
E.g. If the setpoint is 18.6bar, differential is 2bar and minimum speed set to 20%, then,
20% of 2bar = 0.4bar, therefore, fan minimum speed/cut-off achieved at 19bar with an analogue
output signal of 2 volts.
Maximum Speed
The maximum speed is the % value of the differential that dictates the fan maximum speed or cut-off point and
configures the Condenser Fan analogue output signal to suit.
E.g. If the setpoint is 18.6bar, differential is 2bar and maximum speed set to 80%, then,
80% of 2bar = 1.6bar, therefore, fan maximum speed/cut-off achieved at 20.2bar with an analogue
output signal of 8 volts.
Note: Ensure that the voltage supplied to the condenser fan on minimum speed is greater than the fan
manufacturers recommended voltage. Denco recommend that the minimum voltage should not be lower
than 100 volts.
In Level 3, Factory Configuration, there is an option to select a cooling demand setpoint at which the chilled water
valve will be fully open.
This function will be used when the site requirement is to allow full chilled water cooling with the variable speed
fan(s) at the minimum speed, and as the cooling demand rises above the Chilled Water Demand Setpoint, the fan
speed would increase, depending on the maximum fan speed selected.
Example 1:
Cooling Demand Setpoint = 25%
Example 2:
Cooling Demand Setpoint = 50%
Example 3:
Cooling Demand Setpoint = 75%
p-LAN
Drive connection
Temperature
probe
Pressure probe
4-20mA COMPRESSOR
EVAPORATOR
The method to address the EV driver is achieved by setting a sequence of DIP switches using binary
configuration. The switches are accessed by removing the top cover of the EV Driver.
Address examples
Note: To ensure correct operation, select all of the DIP switches to the off position then power the unit on and
then off again. Then select the DIP switches to the required address, e.g. address number 9, and then switch the
power back on.
Suction T. Limit 20
Heating Operation
Heating is achieved in one of two ways, either with Electric Heaters or with Low Pressure Hot Water (LPHW).
In the case of Electric Heating up to a maximum of three stages of heating can be configured in software
(Software Level 3 Factory Settings) even though there are only two heating outputs. For this arrangement the
electric heaters must be of unequal size (in the ratio of 2:1, output No 1 heater being the smaller). Operation of
the outputs is in a binary manner as shown in the table below.
The LPHW output operates a Drive Open / Drive Close valve actuator via the digital outputs in response to
heating demands. The operation of the outputs is similar to that for CW control.
The heating demand is generated in the same way as the cooling demand, i.e. deviations below setpoint will
generate a heating demand relevant to the dead zone and proportional bands set, and operate the heating
outputs accordingly.
Integral action has the same effect on the heating demand, thus with no change in the Return Air Temperature
and an initial heating demand is present the demand is gradually increased so that the output increases to raise
the Return Air Temperature to its' setpoint.
The controller can also provide a 0 - 10V DC output to a LPHW valve actuator if required.
Humidifier
Humidifier Assembly
Fill cup
Cylinder
High Level Electrodes
Electrodes
Supply Hose
Fill Hose
Drain Hose
Drain Connection
Inlet Connection
Drain Pump
The above diagram shows the basic components of the humidifier assembly, while de-energised. It should be
noted that a suitable steam pipe must be used and the system should not be operated with an “open top”.
The 3 kg/hr humidifier uses a steam nozzle (typical shown below) to introduce the steam into the unit airflow,
above this capacity a sparge pipe arrangement is utilised.
The position of the nozzle / sparge pipe within the Air Handling Unit
has been selected to produce the best distribution of steam into the airflow.
The humidifier operating parameters are selected in software. Voltages, phases and the appropriate steam
cylinder size fitted are set in Software Level 3 Factory Configuration. This configuration is set up during factory
inspection and testing and will not normally need to be reset. The conductivity sensor incorporated in the design
can be used to display supply conductivity, but is primarily used for internal software calculations.
Humidifier (cont)
Humidifier (cont)
Cylinder Life
The water hardness and the humidity demand on site will determine the effective life of a steam cylinder. Units
located in areas with naturally soft water will experience the longer cylinder life, whilst areas with hard water, a
more frequent cylinder exchange must be expected as the whole purpose of the Humidifier is to produce pure
steam for humidification at the expense of the disposable steam cylinder.
The electrode boiler humidifiers are designed to cope with a very wide variety of tap waters. Tap water can be
used without water treatment, however it is recommended to put a fine filter before the water inlet valve to the
humidifier in case the water is hard or contains visible particles.
The range of acceptable water conductivity is from 125 to 1250 microSiemens/cm. The hardness of the water is
not such an important criteria because even soft water can have acceptable conductivity. However, it is not
recommended to use chemically softened water, because it may cause the water to become aggressive or cause
foam in the cylinder.
All CAREL immersed-electrodes humidifiers have an algorithm that controls automatically the internal
concentration in order to respect the constraints above. The algorithm maintains the water concentration within
the working range as follows:
• When the concentration is too low, it just lets the water boil off because this will increase the internal
concentration (the fills done to restore the water level only temporarily and negligibly decrease the internal
concentration)
• When the concentration is too high, the algorithm drains part of the boiler’s water and replaces it with
mains water, thus diluting the boiler’s content of minerals: this is called “dilution drain”.
Note that the amount of water filled to restore the level after the dilution drain is greater than that filled
during the steam production; hence it has a real diluting effect on the internal concentration.
In some cases, however, the algorithm is not capable to run properly: in such situations, the manual tuning of the
dilution drains is necessary.
This is achieved by initially increasing the duration of the drain by changing the ‘Drain (resp H3)’ value
from 100% to 150%. If the problem persists then adjust the value to the maximum of 200%.
If problems are still being experienced, it is possible to decrease the frequency of the draining by
changing the ‘Evap (respH4)’ from a value of 100% to 50%.
Humidifier (cont)
Humidifier Operation
With an electrode boiler humidifier, steam is produced by boiling the water contained inside the cylinder. This
occurs by simply filling the cylinder with water and applying a voltage to the electrodes. According to the Joule
effect, the current will tend to heat the water until it boils. The current that runs through the electrodes in the
cylinder depends essentially on the voltage applied to the electrodes, the conductivity of the water inside the
cylinder and the level of the water.
The aim of the algorithm is to maintain the current that runs through the electrodes at a reference value so as to
ensure the percentage of steam production required, according to the readings of the humidity probes and the
parameters set by the user.
During evaporation, the level of the water decreases and as the current is directly proportional to the quantity of
water present in the cylinder, to keep it constant the cylinder would need to be constantly filled with minute
quantities of water. To avoid this, the current is maintained within a certain range around the reference value, by
repeated “water fill/evaporation” cycles.
As well as the level of water in the cylinder, the other factor that determines the current level is the conductivity
of the water inside the cylinder. In fact, during the fill/evaporation cycles, the conductivity of the water will tend to
increase, due to the increase in the concentration of salts in the water. The conductivity of the water inside the
cylinder is measured indirectly, by calculating the time required for a complete evaporation cycle. This time is then
compared against a reference (typical for each cylinder) and, if lower, a certain quantity of water is drained and
then the cylinder is topped up with less conductive mains water.
The humidifier also features a conductivity meter that measures the conductivity of the mains water entering the
appliance during the filling cycles. In the case of high conductivity of the supply water, the control algorithm first
signals a pre-alarm (that doesn't stop operation) and then, if necessary, an alarm (that stops operation). This is
essential to avoid the introduction of excessively conductive water into the cylinder, which may compromise the
correct operation of the humidifier.
Another fundamental element, installed at the top of the cylinder, is the high level sensor, used to detect any
water or foam.
The high level electrodes may be activated for one of the following reasons:
- over-filling of water in the boiler – when the unit is off – due to a leak in the fill valve;
- high water level when first filling the cylinder;
- high water level following the depletion of the cylinder due to fouling on the plates;
- formation of foam.
In the first case, when the high level sensor is activated, the algorithm stops operation and signals a cylinder full
alarm, while in the other three cases the humidifier responds by draining the water so as to decrease the level.
In the event of repeated activations of the high level sensor, the algorithm evaluates the possibility that the causes
may be due to the presence of foam. In this case, if after having performed a complete washing cycle (complete
emptying-complete refill-complete emptying) the high level sensor continues to be activated, the controller signals
a foam alarm (that does not stop operation).
A crucial point in the operation of the humidifier is the control of any excess current levels. In fact, whenever
voltage is applied to the electrodes in the cylinder, after a period of inactivity, there may be short but very intense
peaks in current. If the current is excessive in this initial period, the algorithm responds by immediately switching
off the electrodes and performing a drain cycle. If the excess current continues, the operation of the humidifier is
stopped and a high current alarm is signalled.
The algorithm also controls the drain cycles, signalling a drain alarm if there is no appreciable decrease in
current when the drain cycle starts. Vice-versa, a no water alarm will be signalled if there is no appreciable
increase in current when the humidifier is being filled with water.
Humidifier (cont)
The humidifier will boil off the water until 95% of the
target current is achieved.
If the rate of current drop is above the minimum
allowed time, there will be no need for a drain and the
control will open the water inlet valve and continue with
the normal operation.
The water detection system is designed to generate an alarm condition when water is detected on either the floor
sensing tape or the condensate sensor mounted in the coil drip tray.
The two sensors are wired in parallel and must have a 10kΏ resistor fitted at the end of line to operate correctly.
Note that the resistor is already fitted to the Denco floor tape (part no. 2/076/289).
The water detection sensors are wired to a Flooding Sensor Detector module that monitors the resistive value and
when water is detected energises the relay to create a digital input to the controller that generates an alarm,
energises the critical alarm relay and disables the humidifier function.
Refer to electrical schematic drawing for full wiring details.
Minimum Value - This value is the bottom range of the specific transducer selected. The default is
configured as 000.0Pa.
Maximum Value - This value is the top range of the specific transducer selected. The default is
configured as 2500.0Pa.
Offset - This value is used as a calibration offset. The default is configured as 00.0Pa.
Filter Alarm - When the measured value increases above this setpoint, the dirty filter alarm is
generated on the C3-05 controller. The default is configured as 0130.0Pa.
Flow Alarm - When the measured value decreases below this setpoint, the airflow alarm is
generated on the C3-05 controller. The default is configured as 010.0Pa.
Example of operation:
For 1 stage heat pump, i.e. 1 compressor output, the following shall apply: -
• If heating demand reaches 100% an electric heating software timer to be enabled
• If heating demand remains above 60% after 5 minutes has elapsed on timer then first stage of electric heating
shall be switched on. This switches off at 50% demand
• If heating demand remains above 75% after 10 minutes has elapsed on timer then second stage of electric
heating shall be switched on. This switches off at 60% demand
For 2 stage heat pump, i.e. 2 compressor outputs, the following shall apply: -
• If heating demand reaches 100% an electric heating software timer to be enabled
• If heating demand remains above 70% after 10 minutes has elapsed on timer then first stage of electric
heating shall be switched on. This switches off at 60% demand
• If heating demand remains above 85% after 15 minutes has elapsed on time then second stage of electric
heating shall be switched on. This switches off at 75% demand
Defrost Control
The defrost control operates by the C3-05 controller monitoring the suction and discharge pressures, via
transducers, and sending a signal to operate the heat pump reversing valve to the necessary position depending
on the values measured and the pressure and time setpoints.
When the pressure is lower than the Minimum Setpoint for a period of the Minimum Time, the defrost mode is
initiated. The unit status on the time out display will change to ‘Defrost Mode’, the cooling demand is forced to
100% and the heating demand is forced to 0% demand. The condenser fan 0-10VDC signal will be forced to
maximum speed during a defrost cycle (if enabled).
The Defrost Mode is ended when either the pressure has risen above the Maximum Setpoint or the Maximum
Time has elapsed. The unit will then operate based on the normal calculated temperature demands.
• Minimum Setpoint – the value that the pressure will decrease to initiate the defrost function.
• Maximum Setpoint – the value that the pressure needs to increase to disable the defrost function.
• Minimum Time – the amount of time that the pressure must be below the minimum setpoint to initiate a
defrost cycle.
• Maximum Time – the maximum time that the defrost function could be enabled for, irrelevant of the pressure.
Note: Defrost is disabled when a two circuit unit is configured, i.e. VRF with 4 compressors or non VRF with 2
compressors.
Dehumidification Operation
The Dehumidification demand is calculated in a similar way to that of the initial cooling demand.
For Dehum with modulating cooling when the demand reaches 100% the controller will run the CW valve for a
predetermined amount of time for the % CW Cooling assigned to Dehumidification (set in Software Level 3).
Dehum with DX cooling when the demand reaches 100% the total number of DX stages assigned to
dehumidification will energise. Note if two stages are assigned to dehumidification then the stage delay will be
applied to prevent both stages energising simultaneously.
The Dehum output can be disabled in several ways even though the Return Air %RH may indicate that
dehumidification is required. The disable functions are as follows:
All these interlocks allow dry bulb control to have priority over humidity.
Refer to Engineering Manual for relevant airflows and external static values.
Ambicool Operation
Ambicool is the use of low ambient temperatures cooling a freecooling liquid (typically glycol / water solution) to
effect heat extraction from an air conditioned space. Should the ambient temperature rise to a level at which no
duty can be achieved by freecooling then DX stages will cool the room air in order to do the cooling duty.
There is a 1°C hysteresis control band that will allow the freecooling liquid temperature to equal the return air
temperature setpoint before disabling the Ambicool function (closing the freecooling control valve).
To ensure correct and effective operation of the Ambicool system, it is recommended to configure the
Control Strategy to Proportional only control.
The Ambicool valve position is determined by the cooling demand multiplied by four.
e.g. 15% cooling demand = 60% valve position
20% cooling demand = 80% valve position
25% cooling demand = 100% valve position
The DX stages of cooling are enabled depending on the number of cooling stages and the demand. The following
table illustrates this.
Combicool Operation
A Combicool unit consists of two separate cooling circuits. Normally the primary cooling circuit will be chilled water
and the secondary circuit a DX system, however, the option for two chilled water circuits is available in Level 3,
Factory Configuration.
The cooling function would change from one system to another in one of two ways;
r If the chilled water temperature rises above the Combicool CW Limit, configured in Level 2.
If the interlock is enabled then the cooling output is reduced by a reduction factor, where;
If the interlock function is enabled then the humidifier output demand will start to decrease when the supply air
humidity is Alarm Setpoint minus 10%. Should the supply air humidity reach the alarm setpoint then the humidifier
output would be 0%.
With option (2) or (3) selected, the interlock remains active even if the software output forcing routines are
applied.
Generator Run
If the control 24VAC is present on Digital Input 12 (ID12) then the controller will operate in a cooling only mode,
i.e. Heating and humidifier outputs are disabled. This is normally controller via a volt free contact supplied from
the generator or UPS.
This function is designed to reduce the power consumption to a minimum in the event of a mains power failure.
Sensor adjustment (monitored with a calibrated instrument) can be made in Software Level 3 Calibration.
+VDC G 24V DC
GND M 0V DC
NTC
B4 NTC Temp Signal
B1 H Hum Signal
G NTC NTC M H
Note: please refer to "Handling Static Sensitive Devices" prior to servicing the controller and its
associated modules.
1. Ensure that the Mains supply is isolated.
3. Switch all MCB's, except the single phase Controls power supply MCB, to the "OFF” position.
5. Switch on the mains supply. Check the liquid crystal display illuminates. The liquid crystal display will show the
Time Out display.
6. Use the programming keys to select Software Level 3. Using the appropriate coded key presses, enter
Software Level 3 Factory Settings.
7. Using the Factory Settings table, set the values as appropriate to the Air Handling Unit, as identified in 2.
8. If any operating parameters are different to default values enter the appropriate Software Level and change as
required. For explanation of time-out displays, input / output status and control types see the previous sections.
9. Switch unit "ON" and reset any alarms. Switch on fan(s) with the fan MCBs. Check the rotation of fan(s) and set
airflow switch as required. Using the software H/O/A switches test the function of individual output stages.
Remember to reset MCBs as they are used. On completion reset all H/O/A switches to "AUTO".
(1) Switch off Air Handling Unit at the display ON/OFF switch. Enter Software Levels and note any parameters
that are different to default settings, also check the Factory Settings. If for any reason access to the Software
Levels cannot be made check the electrical drawing configuration tables, commissioning sheets or contact the
contracts engineer.
(3) Remove all inputs and output connections by unplugging the terminals from controller.
(7) Switch on mains supply. Set software Factory Settings as appropriate, see Software Level 3. Also set up any
parameters as noted previously.
(8) Switch on Air Handling Unit using the display ON/OFF switch, and check operation of the unit.
(1) Switch off Air Handling Unit at the display ON/OFF switch.
(7) Switch on Air Handling Unit using the display ON/OFF switch, and check operation of the unit.
Software Upgrade
The Denco application software can be upgraded using a Smartkey, as follows;-
Due attention should be paid to the notes on servicing the microprocessor. Any servicing is to be carried out by a
QUALIFIED CONTROLS ENGINEER.
Always fault find with relevant schematic wiring diagrams and panel layouts at hand. Always modify diagrams if
any modifications are made (subject to confirmation with the Denco Technical Department).
Always replace relays, contactors or any other components with those of the same make, type and rating. Failure
to do so may invalidate the warranty.
It is necessary to ensure that all isolators are in the "OFF" position before any covers are removed.
Any repeated faults in the initial warranty period should be relayed to the contractor and consultant.
Plant settings should not be altered as the balance of the complete system can be affected resulting in a costly re-
balancing operation. Re-balancing should only be carried out by a COMPETENT ENGINEER.
Carrying out maintenance as described in the servicing sections can cut down significantly nuisance fault finding
problems, however maintenance should be carried out by competent and trained staff - bad maintenance is often
worse than no maintenance all.
The fault finding tables have been prepared in logical sequence, with the most likely faults first.
Ensure that the person(s) fault finding are competent in attending to all aspects of the equipment and that they
know the location of all items of plant.
3. Sensor calibration incorrect. Refer to Service section for sensor values. Use
Sensor Trim in Software Level 3 to adjust value.
6. Earth screen on sensor cable The sensor wiring must be screened and fully
ineffective. segregated from wiring carrying mains potential.
The screen should be terminated to earth at one
end only.
3. Cooling demand greater than Ensure that this is not a design feature before
dehum demand. disabling interlock in Software Level 3.
(I) Cooling not 1. Supply air temperature Ensure that this is not a design feature before
functioning with a interlock enabled. When the disabling supply air temperature interlock in
cooling demand supply air temperature interlock is Software Level 3 Factory Settings.
enabled cooling is disabled or
reduced if the supply air
temperature falls below a
predetermined value.
(J) Cooling DX stages 1. HP or LP alarm / trip. Check for cause. Reset as required.
not
energising
(K) Logged averages 1. Alteration of sample frequency. Always register all required samples before
of temperature and setting/re-setting sample frequency.
humidity display 0° C
and 0 %RH
respectively. No
recorded samples on
any of the logging
channels.
(L) Heating outputs 1. Heater Klixon activated. Investigate why Klixon has operated. Reset via
not energised with a display keys. The Klixon is an auto-reset device.
demand for heating
2. Fan Failure Alarm Investigate why fan(s) have failed. Reset via
display keys.
3. Hum prevents Heat Interlock. Ensure that this is not a design feature before
disabling interlock in Software Level 3 Factory
Settings.
(M) Outputs remain 1. Software Hand/Off/Auto Ascertain reason why output is in HAND or OFF
constantly energised switches not set to AUTO. before setting to AUTO control.
or de-energised
3. Fan Failure Alarm. Investigate why fan(s) failed. Reset via display
keys.
(O) Auxiliary alarms: 1. Alarm text message altered or Set alarm text message as required.
displaying irregular set to customers requirements in
alarm messages Software Level 3.
when activated
(P) Auxiliary alarm(s) 1. Mode of operation set to Ensure that this is not a customer requirement
fail to activate critical activate alarm relay in Software before setting to operate the critical alarm relay.
alarm relay Level 3.
(Q) 0 - 10V DC 1. 24V AC supply to valve lost. Check / replace cabling to valve.
modulating output not
operating 2. Valve running time incorrect. Check VRT and adjust if required.
correctly(CW cooling
/ LPHW heating 3. Incorrectly set for cool / heat / Set for correct output.
/remote humidifier) hum output in Software Level 3
Factory Settings
(R) Drive Open / 1. Digital cooling set in Software Set to DODC cooling
Drive Close Level 3 Factory Settings.
modulating cooling
not operating 2. 24V AC supply to valve lost. Check / replace cabling to valve.
correctly
3. Digital outputs damaged Check outputs for 24V AC when operated.
(Cool 1/2)
(S) Drive Open / 1. Digital heating set in Software Set to DODC heating
Drive Close Level 3 Factory Settings.
modulating heating
not operating 2. 24V AC supply to valve lost. Check / replace cabling to valve.
correctly
If technical support is required after the preceding fault finding section, contact the nearest GEA Denco service
department for assistance.
The combined sensor uses an NTC resistive element for temperature and a voltage-based signal for humidity, proportional to relative humidity levels. By providing real-time data, it enables precise environmental control, crucial for maintaining desired conditions within the system's operational range .
In chilled water systems, the valve actuator positions a three-way valve to meet cooling demands by using outputs to open or close the valve. The controller calculates the required actuation time to achieve the desired cooling level, ensuring the valve starts from a known closed position for accuracy .
When commissioning or replacing a controller, factors such as ensuring all operational parameters meet site requirements, setting factory configuration specifically for the AHU type, and managing static sensitive devices are important. Proper configuration ensures compatibility and optimal performance of the AHU .
The 'valve opening at start-up' parameter ensures the valve begins at a suitable position, critical for preventing low-pressure shutdowns if set too low. Incorrect settings could prevent the valve from fulfilling its cooling role effectively, necessitating recalibration or adjustment to match the rated capacity of the system components .
Appropriate configuration of LOP protection is crucial to prevent damage from operating under low pressure. Ensuring effectiveness involves setting the LOP integration time greater than zero, calibrating the threshold at the correct saturated evaporation temperature, and decreasing the integration time to prevent premature triggering .
Incorrect solenoid valve operations can be diagnosed by checking if the solenoid opens correctly and confirming reliable electrical connections. If the movement is reversed, reversing the connections can solve the issue. If the solenoid is blocked or stuck, manual control operation should be attempted, and the valve might need replacement if problems persist .
The control air temperature must be measured and compared to the temperature setpoint, which dictates how much cooling is needed. The cooling proportional band influences how aggressively the cooling system responds to deviations, while the cooling dead zone defines a range where no cooling changes occur despite temperature discrepancies. Together, these factors determine how the system calculates and responds to cooling demand .
Automatic sequencing ensures balanced running hours and minimal starts by making the first stage to start also the first to stop. This process maximizes efficiency and lifespan of compressors. It can be deactivated for scenarios requiring consistent use of a specific stage, such as Hot Gas Re-heat configurations .
Heating and humidifier functions might be exclusive when electrical supply limits the simultaneous operation of both. This is managed through software configurations that prioritize one function over the other, ensuring only one operates at any time, thus reducing power consumption and maintaining system balance .
The cooling system utilizes a software timer that delays re-energizing the cooling output for six minutes after activation to prevent excessive compressor starts. Additionally, a Low Pressure (LP) delay timer is triggered when the cooling output is active, initially set at 10 minutes, to allow the system to operate within safe parameters before any LP alarms de-energize the output .