Metasol+MCCB E

This document provides information on Meta Solution's upgraded low voltage circuit breakers. It summarizes the key upgrades and specifications of Meta Solution's Molded Case Circuit Breaker (MCCB) and Earth Leakage Circuit Breaker (ELCB) product lines. The upgrades include increased breaking capacities, compatibility with existing products, standardized dimensions, and a wider range of installable accessories. Technical specifications like voltage ratings, breaking capacities, and dimensions are also presented.

Uploaded by

dan.gonzalez2573
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views140 pages

Metasol+MCCB E

This document provides information on Meta Solution's upgraded low voltage circuit breakers. It summarizes the key upgrades and specifications of Meta Solution's Molded Case Circuit Breaker (MCCB) and Earth Leakage Circuit Breaker (ELCB) product lines. The upgrades include increased breaking capacities, compatibility with existing products, standardized dimensions, and a wider range of installable accessories. Technical specifications like voltage ratings, breaking capacities, and dimensions are also presented.

Uploaded by

dan.gonzalez2573
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 140

Meta Solution

Low voltage circuit breakers

Meta Solution
Green Innovators of Innovation

Upgraded for the global


best worth!

Molded case circuit breaker / Earth leakage circuit breaker

Marking and configuration 16


External configuration 18
Quick selection table (Molded Case Circuit Breakers) 20
Quick selection table (Earth Leakage Circuit Breakers) 30
Ratings 34
Accessories 74
Type numbering system 98
Characteristics curves 99
Dimensions 106
Technical Information 123
Meta solution

MCCB = ELCB
4
4II
Metasol
Molded case circuit breaker / Earth leakage circuit breaker

Upgrade of Meta-MEC series


… Low voltage circuit breaker
•Ics = 100%×Icu
•Ui = 750V
•Uimp = 8kV

•Compatible and differentiated design • Upgrade breaking capacity


- Compatible with the Meta-MEC - N100AF : 10  18kA
- Outlook differentiated design - S125AF : 25  37kA
- S250AF : 25  37kA
•Same External dimension with - H250AF : 35  50kA
MCCB and ELCB - N400AF : 25  37kA
•Upgrade the coordination - S400AF : 35  50kA
- S800AF : 50  65kA
- Upgrade the coordination with Susol /
Meta-MEC mass capacity • Ics = 100% Icu

I5
MCCB/ELCB

Metasol MCCB
Upgrade breaking capacity

460V
85kA
ABL400c ABL800c
85kA 85kA
75kA

65kA
ABH400c ABS800c
50 65kA 50 65kA
50kA
ABH50c ABH125c ABH250c ABS400c
25 50kA 35 50kA 35 50kA 35 50kA
37kA
ABS125c ABS250c ABN400c ABN800c
25 37kA 25 37kA 25 37kA 35 37kA
26kA
ABN250c
18 26kA
18kA
ABS50c ABS60c ABN100c
10 18kA 10 18kA 1018kA
14kA
ABS30c ABN50c ABN60c
5 14kA 5 14kA 5 14kA

30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF

6I
Short-circuit breaking capacity

Upgrade breaking capacity


● N100AF : ● S125AF : ● S250AF : ● H250AF :
10  18kA 25  37kA 25  37kA 35  50kA

● N400AF : ● S400AF : ● S630AF : ● S800AF :


25  37kA 35  50kA 50  65kA 50  65kA

Metasol ELCB
Upgrade breaking capacity
460V
85kA
EBL400c EBL800c
85kA 85kA
75kA

65kA
EBH400c EBS800c
5065kA 5065kA
50kA
EBH50c EBH125c EBH250c EBS400c
2550kA 3550kA 3550kA 3550kA
37kA
EBS125c EBS250c EBN400c EBN800c
2537kA 2537kA 2537kA 3537kA
26kA
EBN250c
1826kA
18kA
EBS50c EBS60c EBN100c
1018kA 1018kA 1018kA
14kA
EBS30c EBN50c EBN60c
514kA 514kA 514kA

30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF

I7
MCCB/ELCB Compatible and Standard
● 100% compatible with Meta-MEC Series.

● Standardized dimension (Depth, Cutout) when the panel is made.

105×165×60mm 90×155×60mm 75×130×60mm

Metasol MCCB

AF
30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF
Type
ABN50c ABN60c ABN100c ABN250c ABN400c ABN800c
ABN 14kA 14kA 18kA 26kA 37kA 37kA

ABS30c ABS50c ABS60c ABS125c ABS250c ABS400c ABS800c


ABS 14kA 18kA 18kA 37kA 37kA 50kA 65kA

ABH50c ABH125c ABH250c ABH400c


ABH 50kA 50kA 50kA 65kA

ABL400c ABL800c
ABL 85kA 85kA

Note) Dimension is for 3 pole and breaking capacity is for AC460V.

8I
● Same external dimension with MCCB and ELCB.

60mm

50mm

75×130×60mm 90×155×60mm 105×165×60mm

Metasol ELCB

AF
30AF 50AF 60AF 100AF 125AF 250AF 400AF 800AF
Type
EBN50c EBN60c EBN100c EBN250c EBN400c EBN800c
EBN 14kA 14kA 18kA 26kA 37kA 37kA

EBS30c EBS50c EBS60c EBS125c EBS250c EBS400c EBS800c


EBS 14kA 18kA 18kA 37kA 37kA 50kA 65kA

EBH50c EBH125c EBH250c EBH400c


EBH 50kA 50kA 50kA 65kA

EBL400c EBL800c
EBL 85kA 85kA

Note) Dimension is for 3 pole and breaking capacity is for AC460V.

I9
MCCB/ELCB System overview

Various installable Accessories


● Wider range of installable accessories compared to Meta MEC series.
● Composed of User Friendly Method.
System overview
 Breaker
 Internal auxiliaries
 Plug-in kit (ELCB only)

 Rotary handle (direct)
 Rotary handle (direct, key lock)
 Rotary handle (extended)
 Rear terminal
 Terminal cover (Short, Long)
  Insulation barrier
 Handle Lock






I11
MCCB/ELCB Internal accessories

● ●


Internal Accessories
Internal Accessories can be commonly used in all Metasol MCCB and ELCB
(Notice: Exception of SHT, UVT in ELCB)
Internal accessories

Common use to all Metasol MCCBs and ELCBs

Alarm Switch (AL)


Alarm switches offer provisions for immediate audio or visual indication of a tripped
breaker due to overload, short-circuit, operation of shunt trip, or undervoltage trip
conditions, operation of push button.
They are particularly useful in automated plants where operators must be signaled
about changes in the electrical distribution system. This switch features a closed
contact when the circuit breaker is tripped automatically. In other words, this switch
does not function when the breaker is operated manually. Its contact is open when
the circuit breaker is reset.

Auxiliary Switch (AX)


Auxiliary switch is for applications requiring remote “ON” and “OFF” indication.
Each switch contains two contacts having a common connection. One is open and
the other closed when the circuit breaker is open, and vice-versa.

Undervoltage trip (UVT)


The undervoltage trip automatically opens a circuit breaker when voltage drops to a
value ranging between 35% to 70% of the line voltage. The operation is
instantaneous, and the circuit breaker cannot be reclosed until the voltage returns
to 85% of line voltage.
Continuously energized, the undervoltage trip must be operating be fore the circuit
breaker can be closed.

Shunt Trip (SHT)


The shunt trip opens the mechanism in response to an externally applied voltage
signal. LS shunt trips include coil clearing contacts that automatically clear the
signal circuit when the mechanism has tripped.contact with live parts and thereby
guarantee protection against direct contacts.

AX AL AL AX AX AL AL AX

SHT/UVT SHT/UVT
AX AL AL AX

SHT/UVT

53 103 203 I13


MCCB/ELCB External accessories

External Accessories
Designed for various mount and user safety.
External accessories

Front and rear connection


Several kinds of terminals can be equipped with ELCBs as well as MCCBs.
­- Terminals for front connection
- ­Rear connection terminals

Plug-in base
It makes to extract and/or rapidly replace the circuit breaker without having to touch
connections.(Easy replacement and maintenance)

Direct & Extended Rotary Handle


There are two types of rotary handles.
­- Direct rotary handle(with or w/o key lock device)
- ­Extended rotary handle

Locking device
- ­Fixed padlock
­- Removable padlock
- ­Key lock device on direct handle

Insulation barrier
These allow the insulation characteristics between the phases at the connections
to be increased.

Insulation terminal cover


The terminal covers are applied to the circuit-breaker to prevent accidental contact
with live parts and thereby guarantee protection against direct contacts.

I15
Marking and configuration

MCCB

MCCB model
•ABN: Economic type
•ABS: Standard type
•ABH: High capacity type

Standardized characteristics
­Ui: Rated insulation voltage
­Uimp: Impulse withstand
voltage
­Ue: Rated operational voltage
­Icu: Ultimate breaking
capacity
­Ics: S
 ervice breaking capacity

Rated frequency Utilization Manufacturer Standard


category

Symbol indicating
suitability for isolation
as defined by IEC 947-2

MCCB
Upstream connections
Fixing hole

Product name

Brand name

Operating handle

Indication of closed (I/ON) position


Indication of open (O/OFF) position

Certification mark

Company logo

"push to trip" button

Fixing hole
Downstream connections

16
ELCB

ELCB model
•EBN: Economic type
•EBS: Standard type
•EBH: High capacity type

Rated frequency Standard Manufacturer Utilization category

Symbol indicating
suitability for isolation
as defined by IEC 947-2

ELCB
Upstream connections

Fixing hole
Brand name

Indication of closed (I/ON) position


Indication of open (O/OFF) position

Product name

Trip indication by earth fault

Operating handle
Residual current(I▵n) setting

"push to trip" button for earth fault

"push to trip" button for overcurrent trip

Company logo

Certification mark

Fixing hole

Downstream connections

17
External configuration

MCCB
① Handle
•Function of indications
- “ON” “OFF” “TRIP”
•Resetting Handle
When the handle indicates "tripped" position it
must first be reset by moving the handle to
the “OFF” position and then closing is
possible
Terminal
•Trip-Free even if the handle is held at “ON”,
the breaker will trip if an over current flows
•Suitable for Verification of the main contact
position under abnormal conditions because Arc-Extinguishing
unit
the handle doesn’t indicate open position

② Arc-Extinguishing unit
LS patent technique PASQ Contact
Arc-Extinguishing unit
PASQ : Puffer Assisted Self-Quenching
•Reduction of arc voltage for a short time Mechanism

Hybrid Grid
chamber Ass’y

Trip

③ Trip button (push to trip)


•Enables tripping mechanically from outside, Trip button

for confirming the operation of the accessory


switches and the manual resetting function.

A Application of PASQ Arc Extinguishing A Application of Current limiting structure

•The reduction of breaking •Current limiting repulsion structure


time by applying PASQ arc (U fixed structure)
extinguishing for inhibition •Toggle structure
of arc voltage for a short - When the operating unit repulses by short circuit
time. current, repulsion structure at bigger angle.

18
ELCB

① Residual
indication LED

① Residual indication LED


•Normal situation is yellow , trio situation
is red

② Residual test Button


•Special design for Upgrade to prohibit
resistance accident

③ Residual detection unit


② Residual test (ZCT + Main board)
Button •For upgrade the design is selected the 3
phase input power method and in case
of Voltage problem, it can break residual
current safely.

③ Residual
detection unit
(ZCT + Main board)

Upgrade coil operation by special design 3 phase power supply method

•Sliding structure application •In case of 1 phase loss


of Trip lever residual operation upgrade
•Trip special design by •New IEC standard
applying design Button
method.
•Upgrade the testing unit

19
Quick selection table
Molded Case Circuit Breakers

MCCBs
AF 30AF 50AF 60AF

Type E-Type S-Type N-Type S-Type H-Type N-Type S-Type


Type and Pole 2-pole ABE32b ABS32c ABN52c ABS52c ABH52c ABN62c ABS62c
3-pole ABE33b ABS33c ABN53c ABS53c ABH53c ABN63c ABS63c
4-pole - ABS34c ABN54c ABS54c ABH54c ABN64c ABS64c
Rated current, In A 15, 20, 30,
(3, 5, 10) Note)
­ 1, 15, 20, 30 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60
40, 50
Rated operational AC(V) 460 690 690 690 690 690 690
voltage, Ue DC(V) - 500 500 500 500 500 500
Rated insulation voltage, Ui V 460 750 750 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 6 8 8 8 8 8 8

Rated short-circuit breaking capacity(Icu) kA (Sym), IEC 60947-2


AC 690V - 2.5 2.5 5 10 2.5 5
480/500V - 7.5 (5) 7.5 10 35 7.5 10
415/460V 2.5 14 (10) 14 18 50 14 18
380V 2.5 18 (14) 18 22 50 18 22
220/250V 5 30 (25) 30 35 100 30 35
DC 500V(3P) - 5 5 10 30 5 10
250V(2P) - 5 5 10 30 5 10
Ics=%×Icu 50 100 100 100 100 100 100
Dimensions (mm) W×H×D 75×96×60mm 75×130×60mm 75×130×60mm 90×155×60mm 75×130×60mm
(3-pole) (Fig. 1) (Fig. 1) (Fig. 2) (Fig. 1)
More info. Ratings 34 page 36 page 38 page 38 page 40 page
Curves 98 page 98 page 98 page 99 page 98 page
Drawings 105 page 106 page 106 page 107 page 106 page
Note) 1.The short-circuit breaking capacities in ( ) are applied to the rated current in (3, 5, 10A) 3.Standard type is designed on the basis of 40℃ of ambient temperature.
Metasol
2. MCCBs MCCB
can be applied to both 50 and 60Hz. 4.There are certain products for hot areas.(30~250AF on the basis of 55℃, 400~800AF on the basis of 50℃)
Ø7.4

AF
Type 30AF 50AF 60AF 100AF 125AF 250AF 50
Ø4.5
130

ABN50c ABN60c ABN100c


115

ABN250c
84

ABN
50

14kA 14kA 18kA 26kA

ABS30c ABS50c ABS60c ABS125c ABS250c


ABS 14kA 18kA 18kA 37kA 37kA

22 58
60
50
ABH50c ABH125c ABH250c
ABH 50kA 50kA 50kA 75
64
68
82
(Fig. 1)
20
100AF 125AF 250AF

N-Type S-Type H-Type N-Type S-Type H-Type


ABN102c ABS102c ABH102c ABN202c ABS202c ABH202c
ABN103c ABS103c ABH103c ABN203c ABS203c ABH203c
ABN104c ABS104c ABH104c ABN204c ABS204c ABH204c
15, 20, 30, 40,
15, 20, 30, 40, 50, 60, 75, 100, 125 100, 125, 150, 175, 200, 225, 250
50, 60, 75, 100
690 690 690 690 690 690
500 500 500 500 500 500
750 750 750 750 750 750

8 8 8 8 8 8

5 8 10 8 8 10
10 26 35 18 26 35
18 37 50 26 37 50
22 42 50 30 42 50
35 85 100 65 85 100
10 20 30 10 20 30
10 20 30 10 20 30
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
42 page 44 page 46 page
98 page 99 page 100 page
106 page 107 page 108 page
Ø8.2

50
Ø8.2
Ø5

47
Ø4.5
100
50

155
135

59.4

102
126
144
165
50

60 58
60 60
90 35
64
70 64
68
105 68.5
82
(Fig. 2) (Fig. 3) 86.85

21
Quick selection table
Molded Case Circuit Breakers

MCCBs
AF 400AF

Type N-Type S-Type H-Type L-Type

Type and Pole 2-pole ABN402c ABS402c ABH402c ABL402c


3-pole ABN403c ABS403c ABH403c ABL403c
4-pole ABN404c ABS404c ABH404c ABL404c
Rated current, In A 250, 300, 350, 400
Rated operational AC(V) 690 690 690 690
voltage, Ue DC(V) 500 500 500 500
Rated insulation voltage, Ui V 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 8 8 8 8

Rated short-circuit breaking capacity(Icu)


kA (Sym), IEC 60947-2
AC 690V 5 8 10 14
480/500V 18 35 50 65
415/460V 37 50 65 85
380V 42 65 70 100
220/250V 50 75 85 125
DC 500V(3P) 10 20 40 40
250V(2P) 10 20 40 40
Ics=%×Icu 100 100 100 75
Dimensions (mm) W×H×D 140×257×109mm
(3-pole) (Fig. 4)
More info. Ratings 48 page
Curves 101 page
Drawings 109 page
Note) 1.The short-circuit breaking capacities in ( ) are applied to the rated current in (3, 5, 10A) 3.There are certain products for hot areas. (30~250AF on the basis of 55℃, 400~800AF on the basis of 50℃)
2.Standard type is designed on the basis of 40℃ of ambient temperature.

AF
Type 400AF 800AF 1000AF 1200AF
Ø13

Ø8

ABN400c ABN800c
ABN 37kA 37kA 52.5
48
257
225
215
150

41
48

ABS400c ABS800c ABS1000b ABS1200b


ABS 50kA 65kA 65kA 65kA

ABH400c
ABH 65kA 95
105
109
ABL400c ABL800c ABL1000b ABL1200b
ABL 85kA 85kA 85kA 85kA 113
145

(Fig. 4)
22
800 AF 1000 AF 1200 AF
N-Type S-Type L-Type S-Type L-Type S-Type L-Type

ABN802c ABS802c ABL802c - - - - -

ABN803c ABS803c ABL803c ABS1003b ABL1003b ABS1203b ABS1203bE ABL1203b


ABN804c ABS804c ABL804c ABS1004b ABL1004b ABS1204b - ABL1204b
500, 630, 700, 800 1000 1200
690 690 690 600 600 600 600 600
500 500 500 - - - - -
750 750 750 690 690 690 690 690

8 8 8 6 6 6 6 6

8 10 14 - - - - -

25 45 65 50 75 50 50 75

37 65 85 65 85 65 65 85

45 75 100 65 85 65 65 85

50 85 125 100 125 100 100 125

10 20 40 - - - - -

10 20 40 - - - - -

100 100 75 50 50 50 50 50

210×280×109mm 220×400×105mm 220×400×105mm

(Fig. 5) (Fig. 6) (Fig. 6)

50 page 52 page 52 page 53 page 52 page

101 page 102 page 102 page 102 page 102 page

110 page 111 page 111 page 112 page 111 page

93
48.5
17
Ø13.5

116

56
90
Ø8

53
25

21.4
280
243
150
96

25

400
110

98.5

95
105
90
40

109
113 17
44 48.5
20

145 70 70 102.5
220 105
122.5
159
(Fig. 5) (Fig. 6) 230
23
Quick selection table
Motor protection Molded Case Circuit Breakers

MCCBs
AF 30AF 50AF 60AF

Type S-Type N-Type S-Type H-Type N-Type S-Type


Type and Pole 3-pole ABS33cM ABN53cM ABS53cM ABH53cM ABN63cM ABS63cM

Rated current, In A 16, 24 16, 24, 32, 45 60

Rated operational AC(V) 690 690 690 690 690 690


voltage, Ue DC(V) 500 500 500 500 500 500
Rated insulation voltage, Ui) V 750 750 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 8 8 8 8 8 8

Rated short-circuit breaking capacity(Icu) kA (Sym), IEC 60947-2


AC 690V 2.5 2.5 5 10 2.5 5
480/500V 7.5 7.5 10 35 7.5 10
415/460V 14 14 18 50 14 18
380V 18 18 22 50 18 22
220/250V 30 30 35 100 30 35
DC 500V(3P) 5 5 10 30 5 10
Ics=%×Icu 100 100 100 100 100 100
Dimensions (mm) W×H×D 75×130×60mm 75×130×60mm 90×155×60mm 75×130×60mm
(3-pole) (Fig. 1) (Fig. 1) (Fig. 2) (Fig. 1)
More info. Ratings 36 Page 38 Page 38 Page 40 Page
Curves 103 Page 103 Page 104 Page 103 Page
Drawings 106 Page 106 Page 107 Page 106 Page
Note) 1. Same electrical and physical specification with MCCB.
2. Accessory : Same application with MCCB
3. MCCBs can be applied to both 50 and 60Hz.
Metasol MCCB
Ø7.4

AF 50
30AF 50AF 60AF 100AF 125AF 250AF
Ø4.5

Type
130
115
84
50

ABN50cM ABN60cM ABN100cM ABN250cM


ABN 14kA 14kA 18kA 26kA

ABS30cM ABS50cM ABS60cM ABS125cM ABS250cM


ABS 14kA 18kA 18kA 37kA 37kA

22 58
60
ABH50cM ABH125cM
50
ABH250cM
ABH 50kA 50kA 50kA 75
64
68
82
(Fig. 1)

24
100AF 125AF 250AF

N-Type S-Type H-Type N-Type S-Type H-Type


ABN103cM ABS103cM ABH103cM - ABS203cM ABH203cM

60, 75, 90 60, 75, 90 125, 150, 175, 225

690 690 690 690 690 690


500 500 500 500 500 500
750 750 750 750 750 750

8 8 8 8 8 8

5 8 10 8 8 10
10 26 35 18 26 35
18 37 50 26 37 50
22 42 50 30 42 50
35 85 100 65 85 100
10 20 30 10 20 30
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
42 Page 44 Page 46 Page
103 Page 104 Page 104 Page
106 Page 107 Page 108 Page
Ø8.2

Ø8.2

50 47
Ø5

Ø4.5
59.4
100
50

102
126
144
165
155
135

50

60 58
60
60 35
90
64 70 64
68 105 68.5
82 86.85

(Fig. 2) (Fig. 3)

25
Quick selection table
ZCT Molded Case Circuit Breakers

MCCBs
AF 30AF 50AF 60AF

Type S-Type N-Type S-Type H-Type N-Type S-Type

Type and Pole 2-pole - - - ABH52c - -

3-pole ABS33c ABN53c ABS53c ABH53c ABN63c ABS63c

4-pole ABS34c ABN54c ABS54c ABH54c ABN64c ABS64c

Rated current, In A
15, 20, 30 15, 20, 30, 40, 50 15, 20, 30, 40, 50, 60

Rated operational
AC(V) 690 690 690 690 690 690
voltage, Ue

Rated insulation voltage, Ui V 750 750 750 750 750 750

Rated impulse withstand


kV 8 8 8 8 8 8
voltage, Uimp

Rated short-circuit breaking capacity(Icu) kA (Sym), IEC 60947-2


AC 690V 2.5 2.5 5 10 2.5 5

480/500V 7.5 7.5 10 35 7.5 10

415/460V 14 14 18 50 14 18

380V 18 18 22 50 18 22

220/250V 30 30 35 100 30 35

Ics=%×Icu 100 100 100 100 100 100

Dimensions (mm) W×H×D 75×130×60mm 75×130×60mm 90×155×60mm 75×130×60mm

(3-pole) (Fig. 1) (Fig. 1) (Fig. 2) (Fig. 1)

More info. Ratings 36 page 38 page 38 page 40 page

Curves 98 page 98 page 99 page 98 page

Drawings 106 page 106 page 107 page 106 page

Note) 1. Same electrical and physical specification with MCCB.


2. Accessory : Same application with MCCB
3. MCCBs can be applied to both 50 and 60Hz.
4. Marking ZCT on the Aux. cover right side
5. Dimension
Metasol of ABH52c, ABS102c and ABH102, which have a built-in ZCT, is 60(W) X 155(H) X 60(D) mm
MCCB
6. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
Ø7.4

AF 50
Type 30AF 50AF 60AF 100AF 125AF 250AF
Ø4.5
130
115
84

ABN50c ABN60c ABN100c ABN250c


50

ABN 14kA 14kA 18kA 26kA

ABS30c ABS50c ABS60c ABS125c ABS250c


ABS 14kA 18kA 18kA 37kA 37kA

22 58
60
ABH50c ABH125c ABH250c 50
ABH 50kA 50kA 50kA 64
75
68
(Fig. 1) 82

26
100AF 125AF 250AF
N-Type S-Type H-Type N-Type S-Type H-Type
- ABS102c ABH102c - - -
ABN103c ABS103c ABH103c ABN203c ABS203c ABH203c
ABN104c ABS104c ABH104c ABN204c ABS204c ABH204c
15, 20, 30, 40, 50
15, 20, 30, 40, 50, 60, 75, 100, 125 100, 125, 150, 175, 200, 225, 250
60, 75, 100

690 690 690 690 690 690

750 750 750 750 750 750

8 8 8 8 8 8

5 8 10 8 8 10
10 26 35 18 26 35
18 37 50 26 37 50
22 42 50 30 42 50
35 85 100 65 85 100
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
42 page 44 page 46 page
98 page 99 page 100 page
106 page 107 page 108 page
Ø8.2

Ø8.2

50 47
Ø5

Ø4.5
59.4
100
50

102
126
144
165
155
135

50

60 58
60
60 35
90 64
64 70
68 105 68.5
82 86.85
(Fig. 2) (Fig. 3)

27
Quick selection table
ZCT Molded Case Circuit Breakers

MCCBs
AF 400AF

Type N-Type S-Type H-Type L-Type

Type and Pole 2-pole - -


3-pole ABN403c ABS403c ABH403c ABL403c
4-pole ABN404c ABS404c ABH404c ABL404c
Rated current, In A 250, 300, 350, 400
Rated operational
AC(V) 690 690 690 690
voltage, Ue
Rated insulation voltage, Ui V 750 750 750 750
Rated impulse withstand
voltage, Uimp kV 8 8 8 8

Rated short-circuit breaking capacity(Icu)


kA (Sym), IEC 60947-2
AC 690V 5 8 10 14
480/500V 18 35 50 65
415/460V 37 50 65 85
380V 42 65 70 100
220/250V 50 75 85 125
Ics=%×Icu 100 100 100 75
Dimensions (mm) W×H×D 140×257×109mm
(3-pole) (Fig. 4)
More info. Ratings 48 page
Curves 101 page
Drawings 109 page
Note) 1. Same electrical and physical specification with MCCB.
2. Accessory : Same application with MCCB
3. MCCBs can be applied to both 50 and 60Hz.
4. Marking ZCT on the Aux. cover right side
5. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

AF
Type 400AF 800AF

ABN400c ABN800c
ABN 37kA 37kA

ABS400c ABS800c
ABS 50kA 65kA

ABH400c
ABH 65kA

ABL400c ABL800c
ABL 85kA 85kA

28
800 AF
N-Type S-Type L-Type

- - -
ABN803c ABS803c ABL803c
- - -
500, 630, 700, 800

690 690 690

750 750 750

8 8 8

8 10 14
25 45 65
37 65 85
45 75 100
50 85 125
100 100 75
210×280×109mm
(Fig. 5)
50 page
101 page
110 page
Ø13.5
Ø13

56
Ø8
Ø8

52.5 53
25
48
257
225
215

280
243
150
150

96
41
48

95
95
105
105
109 109
113 113
145 145
(Fig. 4) (Fig. 5)

29
Quick selection table
Earth Leakage Circuit Breakers

ELCBs
AF 30AF 50AF 60AF

Type S-Type N-Type S-Type H-Type N-Type S-Type


Type and Pole 2-pole - EBN52c - - - -
3-pole EBS33c EBN53c EBS53c EBH53c EBN63c EBS63c
4-pole EBS34c - EBS54c EBH54c - EBS64c
Protective function Overload, Short-circuit Overload, Short-circuit Overload, Short-circuit Overload, Short-circuit
and Ground fault and Ground fault and Ground fault and Ground fault
Rated current, In A (5, 10) , 15, 20, 30
Note) 3
15, 20, 30, 40, 50 15, 20, 30, 40, 50 60
Rated residual current, I▵n mA 30, 100/200/500mA 30, 100/200/500mA 30, 100/200/500mA 30,100/200/500mA
Rated operational voltage, Ue AC(V) 220/460 220/460 220/460 220/460
Rated impulse withstand
kV 6 6 6 6
voltage, Uimp
Residual current off-time at I▵n sec ≤0.1 sec ≤0.1 sec ≤0.1 sec ≤0.1 sec

Rated short-circuit breaking capacity (Icu) kA (Sym), IEC 60947-2


AC 415/460V 14 (10) 14 18 50 14 18
220/250V 30 (25) 30 35 100 30 35
Ics=%×Icu 100 100 100 100 100 100 100
Dimensions (mm) W×H×D 75×130×60mm 75×130×60mm 90×155×60mm 75×130×60mm
(3-pole) (Fig. 1) (Fig. 1) (Fig. 2) (Fig. 1)
More info. Ratings 56 page 58 page 58 page 60 page
Curves 98 page 98 page 99 page 98 page
Drawings 113 page 113 page 114 page 113 page
Note) 1. MCCBs can be applied to both 50 and 60Hz.
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. The short-circuit breaking capacities in ( ) are applied to the rated current in (5, 10A)
Ø7.4

AF
Ø4.5

Type 30AF 50AF 60AF 100AF 125AF 250AF

EBN50c EBN60c EBN100c EBN250c


EBN 14kA 14kA 18kA 26kA

EBS30c EBS50c EBS60c EBS125c EBS250c


EBS 37kA
14kA 18kA 18kA 37kA

EBH50c EBH125c EBH250c


EBH 50kA 50kA 50kA

(Fig. 1)

30
100AF 125AF 250AF

N-Type S-Type H-Type N-Type S-Type H-Type


EBN102c - - EBN202c - -
EBN103c EBS103c EBH103c EBN203c EBS203c EBH203c
EBN104c EBS104c EBH104c - EBS204c EBH204c
Overload, Short-circuit Overload, Short-circuit Overload, Short-circuit
and Ground fault and Ground fault and Ground fault
60, 75, 100 15, 20, 30, 40, 50, 60, 75, 100, 125 100, 125, 150, 175, 200, 225, 250
30, 100/200/500mA 30,100/200/500mA 30,100/200/500mA
220/460 220/460 220/460

6 6 6

≤0.1 sec ≤0.1 sec ≤0.1 sec

18 37 50 26 37 50
35 85 100 65 85 100
100 100 100 100 100 100
75×130×60mm 90×155×60mm 105×165×60mm
(Fig. 1) (Fig. 2) (Fig. 3)
62 page 64 page 66 page
98 page 99 page 100 page
113 page 114 page 115 page
Ø8.2

Ø8.2
Ø5

50
Ø4.5

47
100

102

144

165
135
155
50

50
7
4.7

60 58 60
60 35
90 64
64 70
66.5
68 105
68.5
82
86.85
(Fig. 2) (Fig. 3)

31
Quick selection table
Earth Leakage Circuit Breakers

ELCBs
AF 400AF

Type N-Type S-Type H-Type L-Type


Type and Pole 3-pole EBN403c EBS403c EBH403c EBL403c
4-pole EBN404c EBS404c EBH404c EBL404c
Protective function Overload, Short-circuit and Ground fault
Rated current, In A 250, 300, 350, 400
Rated residual current, I▵n mA 30, 100/200/500mA
Rated operational voltage, Ue AC(V) 220/460 220/460 220/460 220/460
Rated impulse withstand
kV 6 6 6 6
voltage, Uimp
Residual current off-time at I▵n sec 0.1 sec 0.1 sec 0.1 sec 0.1 sec


Rated short-circuit breaking capacity (Icu) kA (Sym), IEC 60947-2
AC 415/460V 37 50 65 85
220/250V 50 75 85 125
Ics=%×Icu 100 100 100 75
Dimensions (mm) W×H×D 140×257×109mm
(3-pole) (Fig. 4)
More info. Ratings 68 page
Curves 101 page
Drawings 116 page
Note) 1. MCCBs other than 1000/1200AF can be applied to both 50 and 60Hz.
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
Ø13

AF
400AF 800AF 1000AF 1200AF
Ø8

Type

EBN400c EBN800c
EBN 37kA 37kA
257
225

215

150

EBS400c EBS800c EBS1000b EBS1200b


EBS 50kA 65kA 65kA 65kA

EBH400c
EBH 65kA 95
105
109
EBL400c EBL800c
EBL 85kA 85kA 113
145

(Fig. 4)

32
800 AF 1000 AF 1200 AF

N-Type S-Type L-Type S-Type S-Type


EBN803c EBS803c EBL803c EBS1003b EBS1203b
- - - - -
Overload, Short-circuit and Ground fault Overload, Short-circuit and Ground fault

500, 630, 700, 800 1000 1200


30, 100/200/500mA 100/200/500mA 100/200/500mA
220/460 220/460 220/460 220/460 220/460

6 6 6 - -

0.1 sec 0.1 sec 0.1 sec 0.1 sec 0.1 sec

37 65 85 85 85

50 85 125 125 125


100 100 75 - -
210×280×109mm 220×565×105mm
(Fig. 5) (Fig. 6)
70 page 70 page
101 page 102 page
117 page 118 page

93
48.5
17
116
90
Ø13.5

Ø8

21.4
206
25

400
360
110
280
243

98.5
150
96

525
165
165

95
105
90
40

109 17
44 48.5
20

113 70 70 102.5
220 105
122.5
145 159
(Fig. 5) (Fig. 5) 231

33
30AF MCCB
ABE30b

Ratings

Frame size 30AF


Type and Pole E-Type
2-pole ABE32b
3-pole ABE33b
4-pole -
Rated current, In 3-5-10-15-20-30A
Rated operational voltage, Ue AC : 460V
-
Rated insulation voltage, Ui AC : 460V
ABE32b
Rated impulse withstand voltage, Uimp 6kV

Rated short-circuit breaking E-Type


capacity, Icu AC 690V -
IEC 60947-2 (lcu) 480/500V -
460V
2.5kA
415V 2.5kA
380V 2.5kA
220/250V
5kA
DC 500V (3P) -
ABE33b
250V (2P) -
lcs=%×Icu 50%

Protective function Overload, Short-circuit


Type of trip unit Hydraulic-Magnetic
Magnetic trip range 12In
Endurance Mechanical 8500 operations
Electrical 1500 operations
Connection Standard Front connection
Optional -
-
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p


a
d 50 75
c2
a c1
b 96 96
c1 Note) 60 60
b

c2 Note) - -
For more information d 80 80
•Drawings ▶ 105 page Weight, kg Standard 0.5 0.7
•Trip curves ▶ 98 page
•Accessories ▶ 74 page Certification Pole 2p 3p
•Connection and mounting ▶ 123 page CE marking ○ ○
Note) Depth by door cut size : c1 for large cut, c2 for small cut

34
Ordering types

Breaker types Accessories


ABE type (2.5kA/460V)

Rated current, In 2-pole 3-pole


3A ABE32b/3 ABE33b/3
5A ABE32b/5 ABE33b/5
10 A ABE32b/10 ABE33b/10
15 A ABE32b/15 ABE33b/15
20 A ABE32b/20 ABE33b/20
Electrical auxiliaries
30 A ABE32b/30 ABE33b/30
AX Auxiliary Switch
AL Alarm Switch
R T
SHT Shunt Trip

Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL
Note) For more detail see 74 page

External accessories
ABE30b Name

B-03B Insulation barrier


TBS23 Short type
Note) For more detail see 82 page

35
30AF MCCB
ABS30c

Ratings

Frame size 30AF


Type and Pole S-Type
2-pole ABS32c
3-pole ABS33c
4-pole ABS34c
Rated current, In (3-5-10)-15-20-30A
Rated operational voltage, Ue AC: 690V
DC: 500V

ABS32c Rated insulation voltage, Ui AC: 750V


Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking S-Type


capacity, Icu AC 690V 2.5 kA
480/500V 7.5 (5)kA
IEC 60947-2 (lcu) 460V 14 (10)kA
415V 14 (10)kA
380V 18 (14)kA
220/250V
30 (25)kA
DC 500V(3P) 5 kA
ABS33c
250V(2P) 5 kA
lcs=%×Icu 100%

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 400A
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection

ABS34c Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p


a
d 50 75 100
c2
a c1
b 130 130 130
c1 Note) 2 60 60 60
b

c2 Note) 2 64 64 64
For more information d 82 82 82
•Drawings ▶ 106 page Weight, kg Standard 0.5 0.7 0.9
•Trip curves ▶ 98 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○ ○
Note) 1. The short-circuit breaking capacities in ( )are applied to the rated current in (3, 5, 10A)
2. Depth by door cut size : c1 for large cut, c2 for small cut
3. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

36
Ordering types

Breaker types Accessories


ABS type (10kA/460V)
Rated current, In 2-pole 3-pole 4-pole
3A ABS32c/3 ABS33c/3 ABS34c/3
5A ABS32c/5 ABS33c/5 ABS34c/5
10 A ABS32c/10 ABS33c/10 ABS34c/10

Electrical auxiliaries

ABS type (14kA/460V) AX Auxiliary Switch


AL Alarm Switch
Rated current, In 2-pole 3-pole 4-pole
AX+AL Combination switch R T
15 A ABS32c/15 ABS33c/15 ABS34c/15
SHT Shunt Trip
20 A ABS32c/20 ABS33c/20 ABS34c/20
UVT Undervoltage trip
30 A ABS32c/30 ABS33c/30 ABS34c/30

Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page

External accessories
ABS30c Name

IB13 Insulation barrier


Terminal cover (Long)
TCL13
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS13
- Inde type, D-Handle type, N-Handle type
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

37
50AF MCCB
ABN50c, ABS50c, ABH50c

Ratings

Frame size 50AF


Type and Pole N-Type S-Type H-Type
2-pole ABN52c ABS52c ABH52c
3-pole ABN53c ABS53c ABH53c
4-pole ABN54c ABS54c ABH54c
Rated current, In 15-20-30-40-50A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
ABS52c
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type S-Type H-Type


capacity, Icu AC 690V 2.5kA 5kA 10kA
480/500V 7.5kA 10kA 35kA
IEC 60947-2 (lcu) 460V 14kA 18kA 50kA
415V 14kA 18kA 50kA
380V 18kA 22kA 50kA
220/250V
30kA 35kA 100kA
DC 500V(3P) 5kA 10kA 30kA
ABS53c 250V(2P) 5kA 10kA 30kA
lcs=%×Icu 100% 100% 100%

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
ABS54c
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p


a
d 50 75 100 50 75 100 60 90 120
c2
b
a c1 130 130 155
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 82 82 82
•Drawings ▶ 106, 107 page Weight, kg Standard 0.5 0.7 0.9 0.5 0.7 0.9 0.7 1 1.2
•Trip curves ▶ 98, 99 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

38
Ordering types

Breaker types Accessories


ABN type (14kA/460V)
Rated current, In 2-pole 3-pole 4-pole
15 A ABN52c/15 ABN53c/15 ABN54c/15
20 A ABN52c/20 ABN53c/20 ABN54c/20
30 A ABN52c/30 ABN53c/30 ABN54c/30
40 A ABN52c/40 ABN53c/40 ABN54c/40
50 A ABN52c/50 ABN53c/50 ABN54c/50
Electrical auxiliaries
ABS type (18kA/460V) AX Auxiliary Switch
Rated current, In 2-pole 3-pole 4-pole AL Alarm Switch
AX+AL Combination switch R T
15 A ABS52c/15 ABS53c/15 ABS54c/15
20 A ABS52c/20 ABS53c/20 ABS54c/20 SHT Shunt Trip
30 A ABS52c/30 ABS53c/30 ABS54c/30 UVT Undervoltage trip
40 A ABS52c/40 ABS53c/40 ABS54c/40
50 A ABS52c/50 ABS53c/50 ABS54c/50 Maximum possibilities
T-position One of above auxiliaries
ABH type (50kA/460V) R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page
Rated current, In 2-pole 3-pole 4-pole
15 A ABH52c/15 ABH53c/15 ABH54c/15
20 A ABH52c/20 ABH53c/20 ABH54c/20
30 A ABH52c/30 ABH53c/30 ABH54c/30
40 A ABH52c/40 ABH53c/40 ABH54c/40
50 A ABH52c/50 ABH53c/50 ABH54c/50

External accessories
ABN50c
ABH50c Name
ABS50c

IB13 IB23 Insulation barrier


Terminal cover (Long)
TCL13 TCL23
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS13 TCS23
- Inde type, D-Handle type, N-Handle type
DH100 DH125 Rotary handle (Direct)
DHK100 DHK125 Rotary handle (Direct, Key lock)
EH100 EH125 Rotary handle (Extended)
- RTB2 Rear terminal (Bar)
RTR1 RTR2 Rear terminal (Round)
PB-A3 PB-C3 Plug-in kit
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

39
60AF MCCB
ABN60c, ABS60c

Ratings

Frame size 60AF


Type and Pole N-Type S-Type
2-pole ABN62c ABS62c
3-pole ABN63c ABS63c
4-pole ABN64c ABS64c
Rated current, In 15-20-30-40-50-60A
Rated operational voltage, Ue AC: 690V
DC: 500V

ABS62c
Rated insulation voltage, Ui AC: 750V
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type S-Type


capacity, Icu AC 690V 2.5kA 5kA
480/500V 7.5kA 10kA
IEC 60947-2 (lcu) 460V 14kA 18kA
415V 14kA 18kA
380V 18kA 22kA
220/250V
30kA 35kA
DC 500V(3P) 5kA 10kA
ABS63c
250V(2P) 5kA 10kA
lcs=%×Icu 100% 100%

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
ABS64c
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p


a
d 50 75 100 50 75 100
c2
b
a c1 130 130
c1 Note) 60 60
b

c2 Note) 64 64
For more information d 82 82
•Drawings ▶ 106 page Weight, kg Standard 0.5 0.7 0.9 0.5 0.7 0.9
•Trip curves ▶ 98 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

40
Ordering types

Breaker types Accessories


ABN type (14kA/460V)
Rated current, In 2-pole 3-pole 4-pole
15 A ABN62c/15 ABN63c/15 ABN64c/15
20 A ABN62c/20 ABN63c/20 ABN64c/20
30 A ABN62c/30 ABN63c/30 ABN64c/30
40 A ABN62c/40 ABN63c/40 ABN64c/40
50 A ABN62c/50 ABN63c/50 ABN64c/50
60 A ABN62c/60 ABN63c/60 ABN64c/60
Electrical auxiliaries
AX Auxiliary Switch
ABS type (18kA/460V) AL Alarm Switch
Rated current, In 2-pole 3-pole 4-pole AX+AL Combination switch R T

15 A ABS62c/15 ABS63c/15 ABS64c/15 SHT Shunt Trip


20 A ABS62c/20 ABS63c/20 ABS64c/20 UVT Undervoltage trip
30 A ABS62c/30 ABS63c/30 ABS64c/30
40 A ABS62c/40 ABS63c/40 ABS64c/40 Maximum possibilities
50 A ABS62c/50 ABS63c/50 ABS64c/50 T-position One of above auxiliaries
60 A ABS62c/60 ABS63c/60 ABS64c/60 R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page

External accessories
ABS60c
Name
ABN60c
IB13 Insulation barrier
Terminal cover (Long)
TCL13
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS13
- Inde type, D-Handle type, N-Handle type
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

41
100AF MCCB
ABN100c

Ratings

Frame size 100AF


Type and Pole N-Type
2-pole ABN102c
3-pole ABN103c
4-pole ABN104c
Rated current, In 15-20-30-40-50-60-75-100A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
ABN102c
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type


capacity, Icu AC 690V 5kA
480/500V 10kA
IEC 60947-2 (lcu) 460V 18kA
415V 18kA
380V 22kA
220/250V
35kA
DC 500V(3P) 10kA
ABN103c 250V(2P) 10kA
lcs=%×Icu 100%

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 400A
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
ABN104c
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p


a
d 50 75 100
c2
b
a c1 130 130 130
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 82 82 82
•Drawings ▶ 106 page Weight, kg Standard 0.5 0.7 0.9
•Trip curves ▶ 98 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

42
Ordering types

Breaker types Accessories


ABN type (14kA/460V)
Rated current, In 2-pole 3-pole 4-pole
15 A ABN102c/15 ABN103c/15 ABN104c/15
20 A ABN102c/20 ABN103c/20 ABN104c/20
30 A ABN102c/30 ABN103c/30 ABN104c/30
40 A ABN102c/40 ABN103c/40 ABN104c/40
50 A ABN102c/50 ABN103c/50 ABN104c/50
Electrical auxiliaries
60 A ABN102c/60 ABN103c/60 ABN104c/60
75 A ABN102c/75 ABN103c/75 ABN104c/75 AX Auxiliary Switch
100 A ABN102c/100 ABN103c/100 ABN104c/100 AL Alarm Switch
AX+AL Combination switch R T
SHT Shunt Trip
UVT Undervoltage trip

Maximum possibilities
T-position One of above auxiliaries
R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page

External accessories
ABN100c Name

IB13 Insulation barrier


Terminal cover (Long)
TCL13
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS13
- Inde type, D-Handle type, N-Handle type
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
PB-A3 Plug-in kit
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

43
125AF MCCB
ABS103c, ABH103c

Ratings

Frame size 125AF


Type and Pole S-Type H-Type
2-pole ABS102c ABH102c
3-pole ABS103c ABH103c
4-pole ABS104c ABH104c
Rated current, In 15-20-30-40-50-60-75-100-125A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
ABS102c Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking S-Type H-Type


capacity, Icu AC 690V 8kA 10kA
480/500V 26kA 35kA
IEC 60947-2 (lcu) 460V 37kA 50kA
415V 37kA 50kA
380V 42kA 50kA
220/250V
85kA 100kA
DC 500V(3P) 20kA 30kA
250V(2P) 20kA 30kA
lcs=%×Icu 100% 100%
ABS103c
Protective function Overload, Short-circuit
Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p


ABS104c
a
d 60 90 120 60 90 120
c2
a c1
b 155 155
c1 Note) 60 60
b

c2 Note) 64 64
For more information d 82 82
•Drawings ▶ 107 page Weight, kg Standard 0.7 1 1.2 0.7 1 1.2
•Trip curves ▶ 99 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

44
Ordering types

Breaker types Accessories


ABS type (37kA/460V)
Rated current, In 2-pole 3-pole 4-pole
15 A ABS102c/15 ABS103c/15 ABS104c/15
20 A ABS102c/20 ABS103c/20 ABS104c/20
30 A ABS102c/30 ABS103c/30 ABS104c/30
40 A ABS102c/40 ABS103c/40 ABS104c/40
50 A ABS102c/50 ABS103c/50 ABS104c/50
60 A ABS102c/60 ABS103c/60 ABS104c/60
Electrical auxiliaries
75 A ABS102c/75 ABS103c/75 ABS104c/75 AX Auxiliary Switch
100 A ABS102c/100 ABS103c/100 ABS104c/100 AL Alarm Switch
125 A ABS102c/125 ABS103c/125 ABS104c/125 AX+AL Combination switch R T
SHT Shunt Trip
ABH type (50kA/460V) UVT Undervoltage trip
Rated current, In 2-pole 3-pole 4-pole
15 A ABH102c/15 ABH103c/15 ABH104c/15 Maximum possibilities
20 A ABH102c/20 ABH103c/20 ABH104c/20 T-position One of above auxiliaries
30 A ABH102c/30 ABH103c/30 ABH104c/30 R-position Option of AX or AL or AX+AL
40 A ABH102c/40 ABH103c/40 ABH104c/40 Note) For more detail see 74 page

50 A ABH102c/50 ABH103c/50 ABH104c/50


60 A ABH102c/60 ABH103c/60 ABH104c/60
75 A ABH102c/75 ABH103c/75 ABH104c/75
100 A ABH102c/100 ABH103c/100 ABH104c/100
125 A ABH102c/125 ABH103c/125 ABH104c/125

External accessories
ABS125c
Name
ABH125c
IB23 Insulation barrier
Terminal cover (Long)
TCL23
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS23
- Inde type, D-Handle type, N-Handle type
DH125 Rotary handle (Direct)
DHK125 Rotary handle (Direct, Key lock)
EH125 Rotary handle (Extended)
RTB2 Rear terminal (Bar)
RTR2 Rear terminal (Round)
PB-C3 Plug-in kit
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

45
250AF MCCB
ABN250c, ABS250c, ABH250c

Ratings

Frame size 250AF


Type and Pole N-Type S-Type H-Type
2-pole ABN202c ABS202c ABH202c
3-pole ABN203c ABS203c ABH203c
4-pole ABN204c ABS204c ABH204c
Rated current, In 100-125-150-175-200-225-250A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
ABS202c
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type S-Type H-Type


capacity, Icu AC 690V 8kA 8kA 10kA
480/500V 18kA 26kA 35kA
IEC 60947-2 (lcu) 460V 26kA 37kA 50kA
415V 26kA 37kA 50kA
380V 30kA 42kA 50kA
220/250V
65kA 85kA 100kA
DC 500V(3P) 10kA 20kA 30kA
250V(2P) 10kA 20kA 30kA
ABS203c lcs=%×Icu 100% 100% 100%

Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Plug-in
Mounting Standard Screw fixing

ABS204c Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p


a
d 105 105 140 105 105 140 105 105 140
c2
a c1
b 165 165 165
c1 Note) 60 60 60
b

c2 Note) 64 64 64
For more information d 87 87 87
•Drawings ▶ 108 page Weight, kg Standard 1.1 1.2 1.6 1.1 1.2 1.6 1.1 1.2 1.6
•Trip curves ▶ 100 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

46
Ordering types

Breaker types Accessories


ABN type (25kA/460V)
Rated current, In 2-pole 3-pole 4-pole
100 A ABN202c/100 ABN203c/100 ABN204c/100
125 A ABN202c/125 ABN203c/125 ABN204c/125
150 A ABN202c/150 ABN203c/150 ABN204c/150
175 A ABN202c/175 ABN203c/175 ABN204c/175
200 A ABN202c/200 ABN203c/200 ABN204c/200
225 A ABN202c/225 ABN203c/225 ABN204c/225
Electrical auxiliaries
250 A ABN202c/250 ABN203c/250 ABN204c/250 AX Auxiliary Switch
AL Alarm Switch
ABS type (37kA/460V) R T
AX+AL Combination switch
Rated current, In 2-pole 3-pole 4-pole SHT Shunt Trip
100 A ABS202c/100 ABS203c/100 ABS204c/100 UVT Undervoltage trip
125 A ABS202c/125 ABS203c/125 ABS204c/125
150 A ABS202c/150 ABS203c/150 ABS204c/150 Maximum possibilities
175 A ABS202c/175 ABS203c/175 ABS204c/175 T-position One of above auxiliaries
200 A ABS202c/200 ABS203c/200 ABS204c/200 R-position Option of AX or AL or AX+AL
225 A ABS202c/225 ABS203c/225 ABS204c/225 Note) For more detail see 74 page
250 A ABS202c/250 ABS203c/250 ABS204c/250

ABH type (50kA/460V)


Rated current, In 2-pole 3-pole 4-pole
100 A ABH202c/100 ABH203c/100 ABH204c/100
125 A ABH202c/125 ABH203c/125 ABH204c/125
150 A ABH202c/150 ABH203c/150 ABH204c/150
175 A ABH202c/175 ABH203c/175 ABH204c/175
200 A ABH202c/200 ABH203c/200 ABH204c/200 External accessories
225 A ABH202c/225 ABH203c/225 ABH204c/225
ABH250c Name
250 A ABH202c/250 ABH203c/250 ABH204c/250
B33 Insulation barrier
Terminal cover (Long)
TCL33
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS33
- Inde type, D-Handle type, N-Handle type
DH250 Rotary handle (Direct)
DHK250 Rotary handle (Direct, Key lock)
EH250 Rotary handle (Extended)
RTB3 Rear terminal (Bar)
RTR3 Rear terminal (Round)
PBA250C Plug-in kit
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

47
400AF MCCB
ABN400c, ABS400c, ABH400c, ABL400c

Ratings

Frame size 400AF


Type and Pole N-Type S-Type H-Type L-Type
2-pole ABN402c ABS402c ABH402c ABL402c
3-pole ABN403c ABS403c ABH403c ABL403c
4-pole ABN404c ABS404c ABH404c ABL404c
Rated current, In 250-300-350-400A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V
Rated impulse withstand voltage, Uimp 8kV
ABS403c
Rated short-circuit breaking N-Type S-Type H-Type L-Type
capacity, Icu AC 690V 5kA 8kA 10kA 14kA
480/500V 18kA 35kA 50kA 65kA
IEC 60947-2 (lcu) 415/460V 37kA 50kA 65kA 85kA
380V 42kA 65kA 70kA 100kA
220/250V
50kA 75kA 85kA 125kA
DC 500V(3P) 10kA 20kA 40kA 40kA
250V(3P) 10kA 20kA 40kA 40kA
lcs=%×Icu 100% 100% 100% 75%
ABL404c Protective function Overload, Short-circuit
Type of trip unit Thermal-Magnetic
Magnetic trip range 8~12In
Endurance Mechanical 4000 operations
Electrical 1000 operations
Connection Standard Front connection
Optional Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p 2p 3p 4p


a
d 140 140 184 140 140 184 140 140 184 140 140 184
c2
a c1
b 257 257 257 257
c1 Note) 109 109 109 109
b

c2 Note) 113 113 113 113


For more information d 145 145 145 145
•Drawings ▶ 109 page Weight, kg Standard 5.2 6.2 7.8 5.2 6.2 7.8 5.2 6.2 7.8 5.2 6.2 7.8
•Trip curves ▶ 101 page
•Accessories ▶ 75 page Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 124 page CE marking ○ ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

48
Ordering types

Breaker types Accessories


ABN type (37kA/460V)
Rated current, In 2-pole 3-pole 4-pole
250 A ABN402c/250 ABN403c/250 ABN404c/250
300 A ABN402c/300 ABN403c/300 ABN404c/300
350 A ABN402c/350 ABN403c/350 ABN404c/350
400 A ABN402c/400 ABN403c/400 ABN404c/400

ABS type (50kA/460V)


Rated current, In 2-pole 3-pole 4-pole
250 A ABS402c/250 ABS403c/250 ABS404c/250
300 A ABS402c/300 ABS403c/300 ABS404c/300
Electrical auxiliaries
350 A ABS402c/350 ABS403c/350 ABS404c/350
400 A ABS402c/400 ABS403c/400 ABS404c/400 AX Auxiliary Switch
AL Alarm Switch
R T
SHT Shunt Trip
ABH type (65kA/460V)
UVT Undervoltage trip
Rated current, In 2-pole 3-pole 4-pole
250 A ABH402c/250 ABH403c/250 ABH404c/250
Maximum possibilities
300 A ABH402c/300 ABH403c/300 ABH404c/300
T-position Option of 2AX, 2AL and SHT or UVT
350 A ABH402c/350 ABH403c/350 ABH404c/350
R-position Option of 2AX, 2AL and SHT or UVT
400 A ABH402c/400 ABH403c/400 ABH404c/400
Note) For more detail see 75 page

ABL type (85kA/460V)


Rated current, In 2-pole 3-pole 4-pole
250 A ABL402c/250 ABL403c/250 ABL404c/250
300 A ABL402c/300 ABL403c/300 ABL404c/300
350 A ABL402c/350 ABL403c/350 ABL404c/350
400 A ABL402c/400 ABL403c/400 ABL404c/400

E-70U N-70

External accessories
IBL400 Insulation barrier
T1-43A Terminal cover (Long) - 2, 3pole
T1-44A Terminal cover (Long) - 4pole
N-70 Rotary handle (Direct)
E-70U Rotary handle (Extended)
MI-43 Mechanical interlock - 2, 3pole
MI-44 Mechanical interlock - 4pole
PB-I3-FR Plug-in kit
Note) For more detail see 82 page

49
800AF MCCB
ABN800c, ABS800c, ABL800c

Ratings

Frame size 800AF


Type and Pole N-Type S-Type L-Type
2-pole ABN802c ABS802c ABL802c
3-pole ABN803c ABS803c ABL803c
4-pole ABN804c ABS804c ABL804c
Rated current, In 500-630-700-800A
Rated operational voltage, Ue AC: 690V
DC: 500V
Rated insulation voltage, Ui AC: 750V

ABS803c
Rated impulse withstand voltage, Uimp 8kV

Rated short-circuit breaking N-Type S-Type L-Type


capacity, Icu AC 690V 8kA 10kA 14kA
480/500V 25kA 45kA 65kA
IEC 60947-2 (lcu) 415/460V 37kA 65kA 85kA
380V 45kA 75kA 100kA
220/250V 50kA 85kA 125kA
DC 500V(3P) 10kA 20kA 40kA
250V(3P) 10kA 20kA 40kA
lcs=%×Icu 100% 100% 75%

ABL804c Protective function Overload, Short-circuit


Type of trip unit Thermal-Magnetic
Magnetic trip range 8~12In
Endurance Mechanical 2500 operations
Electrical 500 operations
Connection Standard Front connection
Optional Plug-in
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p


d
a
c2 210 210 280 210 210 280 210 210 280
a c1
b 280 280 280
c1 Note) 109 109 109
b

c2 Note) 113 113 113


For more information d 145 145 145
•Drawings ▶ 110 page Weight, kg Standard 11 11.5 18.2 11 11.5 18.2 11 11.5 18.2
•Trip curves ▶ 101 page
•Accessories ▶ 75 page Certification Pole 2p 3p 4p 2p 3p 4p 2p 3p 4p
•Connection and mounting ▶ 124 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

50
Ordering types

Breaker types Accessories


ABN type (37kA/460V)
Rated current, In 2-pole 3-pole 4-pole
500 A ABN802c/500 ABN803c/500 ABN804c/500
630 A ABN802c/630 ABN803c/630 ABN804c/630
700 A ABN802c/700 ABN803c/700 ABN804c/700
800 A ABN802c/800 ABN803c/800 ABN804c/800

ABS type (65kA/460V)


Rated current, In 2-pole 3-pole 4-pole
500 A ABS802c/500 ABS803c/500 ABS804c/500
630 A ABS802c/630 ABS803c/630 ABS804c/630 Electrical auxiliaries
700 A ABS802c/700 ABS803c/700 ABS804c/700 AX Auxiliary Switch
800 A ABS802c/800 ABS803c/800 ABS804c/800 AL Alarm Switch
R T
SHT Shunt Trip
ABL type (85kA/460V) UVT Undervoltage trip

Rated current, In 2-pole 3-pole 4-pole


Maximum possibilities
500 A ABL802c/500 ABL803c/500 ABL804c/500
630 A ABL802c/630 ABL803c/630 ABL804c/630 T-position Option of 2AX, 2AL and SHT or UVT
700 A ABL802c/700 ABL803c/700 ABL804c/700 R-position Option of 2AX, 2AL and SHT or UVT
800 A ABL802c/800 ABL803c/800 ABL804c/800 Note) For more detail see 75 page

E-80U N-80

External accessories
IBL800 Insulation barrier
T1-63A Terminal cover (Long) - 2, 3pole
T1-64A Terminal cover (Long) - 4pole
N-80 Rotary handle (Direct)
E-80U Rotary handle (Extended)
MI-83S Mechanical interlock - 2, 3pole
MI-84S Mechanical interlock - 4pole
PB-J3-FR Plug-in kit
Note) For more detail see 82 page

51
1000/1200AF MCCB
ABS1000b/1200b, ABL1000b/1200b

Ratings

Frame size 1000AF 1200AF


Type and Pole S-Type L-Type S-Type L-Type
2-pole - - - -
3-pole ABS1003b ABL1003b ABS1203b ABL1203b
4-pole ABS1004b ABL1004b ABS1204b ABL1204b
Rated current, In 1000A 1200A
Rated operational voltage, Ue AC: 600V
Rated insulation voltage, Ui 690V
Rated impulse withstand voltage, Uimp 6kV

Rated short-circuit breaking S-Type L-Type S-Type L-Type


capacity, Icu AC 690V 45kA 65kA 45kA 65kA
480/500V 50kA 75kA 50kA 75kA
IEC 60947-2 (lcu) 415/460V 65kA 85kA 65kA 85kA
380V 65kA 85kA 65kA 85kA
220/250V
100kA 125kA 100kA 125kA
lcs=%×Icu 50% 50% 50% 50%
① Adjustable instantaneous
for each phase Protective function Overload, Short-circuit
Type of trip unit Thermal-Magnetic
Magnetic trip range 3~6×In ...①
Endurance Mechanical 2500 operations
Electrical 500 operations
Connection Standard Front connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 4p 3p 4p


d
a
c2 220 290 220 290
a c1
b 400 400 400 400
c 105 105 105 105
b

d 159 159 159 159


Weight, kg Standard 19.6 25.7 19.6 25.7

Certification Pole 3p 4p 3p 4p
CE marking ABS1003b ABS1004b ABS1203b ABS1204b

For more information ○ × ○ ×

•Drawings ▶ 111 page ABL1003b ABL1004b ABL1203b ABL1204b


•Trip curves ▶ 102 page × × × ×
Note) 1. Please specify the frequency when ordering.
2. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.

52
Ordering types

Breaker types Contact operation for Auxiliary and Alarm Switches


ABS type (65kA/460V) MCCB ON OFF TRIP
Rated current, In 3-pole 4-pole
1000 A ABS1003b/1000 ABS1004b/1000
AX
1200 A ABS1203b/1200 ABS1204b/1200

ABL type (85kA/460V)


Rated current, In 3-pole 4-pole
AL
1000 A ABL1003b/1000 ABL1004b/1000
1200 A ABL1203b/1200 ABL1204b/1200

Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AX2 Auxiliary Switch (2c) Voltage Current (A) Voltage Current (A)
Alarm Switch (1c) R T
AL1 (V) Resistive load Inductive load (V) Resistive load Inductive load
AL2 Alarm Switch (2c) 125 20 20 30 6 5
AX1+AL Auxiliary (1c) + Alarm (1c) Switch 250 20 20 125 0.4 0.05
AX2+AL Auxiliary (2c) + Alarm (1c) Switch 500 10 5 250 0.2 0.03

Option of below items for R-position


SHT Shunt Trip Rating for Shunt trip (SHT)
UVT Undervoltage trip Control voltage Time rating Operational voltage
100~110V Continuous 85~110% of control voltage
125V
AC 200~220V
380~440V
480~550V
24V 75~125% of control voltage
48V
DC 100~110V
125V
200~220V

Rating for Undervoltage release (UVT)


Control voltage Time rating Operational voltage Trip voltage
100~110V Continuous 85~110% of 20~70% of
125V control voltage control voltage
AC
200~220V
380~440V

53
1200AF Electronic MCCB
ABS1203bE

Ratings

Frame size 1200AF


Type and Pole S-Type
2-pole -
3-pole ABS1203bE
4-pole) -
Rated current, In 1200A
Rated operational voltage, Ue AC: 600V
Rated insulation voltage, Ui AC: 600V
Rated impulse withstand voltage, Uimp 6kV

Type Long time Current, IR (0.5-0.6-0.7-0.8-0.9-1.0)×In, adjustable...①


pick-up time 5sec ± 20% at 6×Ir, fixed
Short time Current, Im (2-3-4-5-6-8-10)×ln, adjustable...②
pick-up time 0.1-0.2-0.3 sec, adjustable...③
Instantaneous Current, It 11×ln, fixed
pick-up time within 0.03 sec, fixed
⑤ LED Pre-Alarm between 70 to 110% of set current Ir: LED flickering
over 110% of set current Ir: stays on
④ Rated frequency 50-60Hz selectable by the switch of the trip unit

Rated short-circuit breaking S-Type


capacity, Icu AC 690V 45kA
480/500V 50kA
415/460V
65kA
380V 65kA
220/250V
100kA
lcs=%×Icu 50%
Protective function Overload, Short-circuit
Type of trip unit Electronic type
Endurance Mechanical 2500 operations
Electrical 500 operations
Connection Standard Front connection
Mounting Standard Screw fixing
Dimensions (mm) Pole 3p
d
a
a
c2
c1 220
b 400
c 105
b

For more information


•Drawings ▶ 112 page d 159
•Trip curves ▶ 102 page Weight, kg Standard 21

54
Ordering types

Breaker types Contact operation for Auxiliary and Alarm Switches


ABS type (65kA/460V) MCCB ON OFF TRIP
Rated current, In 3P
1200 A ABS1203bE
AX

AL

Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AX2 Auxiliary Switch (2c) Voltage Current (A) Voltage Current (A)
R T
AL1 Alarm Switch (1c) (V) Resistive load Inductive load (V) Resistive load Inductive load
AL2 Alarm Switch (2c) 125 20 20 30 6 5
AX1+AL Auxiliary (1c) + Alarm (1c) Switch 250 20 20 125 0.4 0.05
AX2+AL Auxiliary (2c) + Alarm (1c) Switch 500 10 5 250 0.2 0.03

Option of below items for R-position


SHT Shunt Trip Rating for Shunt trip (SHT)
UVT Undervoltage trip Control voltage Time rating Operational voltage
100~110V Continuous 85~110% of control voltage
125V
AC 200~220V
380~440V
480~550V
24V 75~125% of control voltage
48V
DC 100~110V
125V
200~220V

Rating for Undervoltage release (UVT)


Control voltage Time rating Operational voltage Trip voltage
100~110V Continuous 85~110% of 20~70% of
125V control voltage control voltage
AC
200~220V
380~440V

55
30AF ELCB
EBS30c

Ratings

Frame size 30AF


Type and Pole S-Type
2-pole(2-sensor) -
3-pole(3-sensor) EBS33c
4-pole(3-sensor) EBS34c
Rated current, In (5-10) Note) 4 -15-20-30A
Rated residual current, I▵n 30, 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV
EBS33c Wiring system 2-pole(2-sensor) -
3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W
4-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W

Rated short-circuit breaking S-Type


capacity, Icu AC 460V 14 (10)kA
IEC 60947-2 (lcu) 415V 14 (10)kA
220/250V
30 (25)kA
lcs=%×Icu 100%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 400A
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 4p


a
d 75 100
c2
a c1
b 130 130
c1 Note) 2 60 60
b

c2 Note) 2 64 64
For more information d 82 82
•Drawings ▶ 113 page Weight, kg Standard 0.7 0.9
•Trip curves ▶ 98 page
•Accessories ▶ 74 page Certification Pole 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. The short-circuit breaking capacities in ( ) are applied to the rated current in (5, 10A)
4. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
5. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

56
Ordering types

Breaker types Accessories


EBS type (14kA/460V)
Rated residual current, I▵n: 30mA
Rated current, In
3-pole 4-pole
5A EBS33c/5/30 EBS34c/5/30
10 A EBS33c/10/30 EBS34c/10/30
15 A EBS33c/15/30 EBS34c/15/30
20 A EBS33c/20/30 EBS34c/20/30
30 A EBS33c/30/30 EBS34c/30/30
Electrical auxiliaries

AX Auxiliary Switch
AL Alarm Switch R T
EBS type (14kA/460V) AX+AL Combination switch
Rated residual current, I▵n: 100/200/500mA
Rated current, In
3-pole 4-pole Maximum possibilities
5A EBS33c/5/100 EBS34c/5/100 T-position Not available
10 A EBS33c/10/100 EBS34c/10/100 R-position Option of AX or AL or AX+AL
15 A EBS33c/15/100 EBS34c/15/100 Note) For more detail see 74 page
20 A EBS33c/20/100 EBS34c/20/100
30 A EBS33c/30/100 EBS34c/30/100

External accessories
EBS30c Name

IB13 Insulation barrier


Terminal cover (Long)
TCL13
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS13
- Inde type, D-Handle type, N-Handle type
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTR1 Rear terminal (Round)
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

57
50AF ELCB
EBN50c, EBS50c, EBH50c

Ratings

Frame size 50AF


Type and Pole N-Type S-Type H-Type
2-pole(2-sensor) EBN52c - -
3-pole(3-sensor) EBN53c EBS53c EBH53c
4-pole(3-sensor) - EBS54c EBH54c
Rated current, In 15-20-30-40-50A
Rated residual current, I▵n 30, 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV

EBN53c Wiring system 2-pole(2-sensor) 1Ø2W


3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W
4-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W

Rated short-circuit breaking N-Type S-Type H-Type


capacity, Icu AC 460V 14kA 18kA 50kA
IEC 60947-2 (lcu) 415V 14kA 18kA 50kA
220/250V
30kA 35kA 100kA
lcs=%×Icu 100% 100% 100%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
EBS53c Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 3p 4p 3p 4p


a
d 75 75 75 100 90 120
c2
a c1
b 130 130 155
c1 Note)1 60 60 60
b

c2 Note)1 64 64 64
For more information d 82 82 82
•Drawings ▶ 113, 114 page Weight, kg Standard 0.5 0.7 0.7 0.9 1 1.2
•Trip curves ▶ 98, 99 page
•Accessories ▶ 74 page Certification Pole 2p 3p 3p 4p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : C1 for large cut, C2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

58
Ordering types

Breaker types Accessories


EBN type (14kA/460V)
Rated residual current, Rated residual current,
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In
2-pole 3-pole 2-pole 3-pole
15 A EBN52c/15/30 EBN53c/15/30 EBN52c/15/100 EBN53c/15/100
20 A EBN52c/20/30 EBN53c/20/30 EBN52c/20/100 EBN53c/20/100
30 A EBN52c/30/30 EBN53c/30/30 EBN52c/30/100 EBN53c/30/100
40 A EBN52c/40/30 EBN53c/40/30 EBN52c/40/100 EBN53c/40/100
Electrical auxiliaries
50 A EBN52c/50/30 EBN53c/50/30 EBN52c/50/100 EBN53c/50/100 AX Auxiliary Switch
AL Alarm Switch R T
AX+AL Combination switch
EBS type (18kA/460V)
Rated residual current, Rated residual current,
Rated Maximum possibilities
I▵n: 30mA I▵n: 100/200/500mA
current, In T-position Not available
3-pole 4-pole 3-pole 4-pole
R-position Option of AX or AL or AX+AL
15 A EBS53c/15/30 EBS54c/15/30 EBS53c/15/100 EBS54c/15/100
Note) For more detail see 74 page
20 A EBS53c/20/30 EBS54c/20/30 EBS53c/20/100 EBS54c/20/100
30 A EBS53c/30/30 EBS54c/30/30 EBS53c/30/100 EBS54c/30/100
40 A EBS53c/40/30 EBS54c/40/30 EBS53c/40/100 EBS54c/40/100
50 A EBS53c/50/30 EBS54c/50/30 EBS53c/50/100 EBS54c/50/100

EBH type (37kA/460V)


Rated residual current, Rated residual current,
Rated
I▵n: 30mA I▵n: 100/200/500mA External accessories
current, In
3-pole 4-pole 3-pole 4-pole
EBN50c
15 A EBH53c/15/30 EBH54c/15/30 EBH53c/15/100 EBH54c/15/100 EBH50c Name
EBS50c
20 A EBH53c/20/30 EBH54c/20/30 EBH53c/20/100 EBH54c/20/100
30 A EBH53c/30/30 EBH54c/30/30 EBH53c/30/100 EBH54c/30/100 IB13 IB23 Insulation barrier
40 A EBH53c/40/30 EBH54c/40/30 EBH53c/40/100 EBH54c/40/100 Terminal cover (Long)
TCL13 TCL23
50 A - Inde type, D-Handle type, N-Handle type
EBH53c/50/30 EBH54c/50/30 EBH53c/50/100 EBH54c/50/100
Terminal cover (Short)
TCS13 TCS23
- Inde type, D-Handle type, N-Handle type
DH100 DH125 Rotary handle (Direct)
DHK100 DHK125 Rotary handle (Direct, Key lock)
EH100 EH125 Rotary handle (Extended)
- RTB2 Rear terminal (Bar)
RTR1 RTR2 Rear terminal (Round)
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

59
60AF ELCB
EBN60c, EBS60c

Ratings

Frame size 60AF


Type and Pole N-Type S-Type
2-pole(2-sensor) - -
3-pole(3-sensor) EBN63c EBS63c
4-pole(3-sensor) - EBS64c
Rated current, In 60A
Rated residual current, I▵n 30, 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV
EBN63c Wiring system 2-pole(2-sensor) -
3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W
4-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W

Rated short-circuit breaking N-Type S-Type


capacity, Icu AC 460V 14kA 18kA
IEC 60947-2 (lcu) 415V 14kA 18kA
220/250V
30kA 35kA
lcs=%×Icu 100% 100%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In
Endurance Mechanical 25000 operations
EBS63c
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 3p 4p


d
ac2 75 75 100
a c1
b 130 130 130
c1 Note)1 60 60 60
b

c2 Note)1 64 64 64
For more information d 82 82 82
•Drawings ▶ 113 page Weight, kg Standard 0.7 0.7 0.9
•Trip curves ▶ 98 page
Certification Pole 3p 3p 4p
•Accessories ▶ 74 page
•Connection and mounting ▶ 123 page CE marking ○ ○
Note) 1. Depth by door cut size : C1 for large cut, C2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

60
Ordering types

Breaker types Accessories


EBN type (14kA/460V)
Rated residual current, Rated residual current,
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In
3-pole 3-pole
60 A EBN63c/60/30 EBN63c/60/100

EBS type (18kA/460V) Electrical auxiliaries


Rated residual current, Rated residual current, AX Auxiliary Switch
Rated
I▵n: 30mA I▵n: 100/200/500mA AL Alarm Switch R T
current, In
3-pole 4-pole 3-pole 4-pole AX+AL Combination switch
60 A EBS63c/60/30 EBS64c/60/30 EBS63c/60/100 EBS64c/60/100
Maximum possibilities
T-position Not available
R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page

External accessories
EBS60c
Name
EBN60c
IB13 Insulation barrier
Terminal cover (Long)
TCL13
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS13
- Inde type, D-Handle type, N-Handle type
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

61
100AF ELCB
EBN100c

Ratings

Frame size 100AF


Type and Pole N-Type
2-pole(2-sensor) EBN102c
3-pole(3-sensor) EBN103c
4-pole(3-sensor) EBN104c
Rated current, In 60-75-100A
Rated residual current, I▵n 30, 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV
EBN103c
Wiring system 2-pole(2-sensor) 1Ø2W
3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W
4-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W

Rated short-circuit breaking N-Type


capacity, Icu AC 460V 18kA
IEC 60947-2 (lcu) 415V 18kA
220/250V
35kA
lcs=%×Icu 100%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In
Endurance Mechanical 25000 operations
Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 4p


d
ac2 75 75 100
a c1
b 130 130 130
c1 Note)1 60 60 60
b

c2 Note)1 64 64 64
For more information d 82 82 82
•Drawings ▶ 113 page Weight, kg Standard 0.5 0.7 0.9
•Trip curves ▶ 98 page
•Accessories ▶ 74 page Certification Pole 2p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

62
Ordering types

Breaker types Accessories


EBN type (18kA/460V)
Rated residual current, I▵n: 30mA
Rated current, In
2-pole 3-pole 4-pole
60 A EBN102c/60/30 EBN103c/60/30 EBN104c/60/30
75 A EBN102c/75/30 EBN103c/75/30 EBN104c/75/30
100 A EBN102c/100/30 EBN103c/100/30 EBN104c/100/30

Electrical auxiliaries
Rated residual current, I▵n: 100/200/500mA
Rated current, In
2-pole 3-pole 4-pole AX Auxiliary Switch
60 A EBN102c/60/100 EBN103c/60/100 EBN104c/60/100 AL Alarm Switch R T
75 A EBN102c/75/100 EBN103c/75/100 EBN104c/75/100 AX+AL Combination switch
100 A EBN102c/100/100 EBN103c/100/100 EBN104c/100/100
Maximum possibilities
T-position Not available
R-position Option of AX or AL or AX+AL
Note) For more detail see 74 page

External accessories
EBN100c Name

IB13 Insulation barrier


Terminal cover (Long)
TCL13
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS13
- Inde type, D-Handle type, N-Handle type
DH100 Rotary handle (Direct)
DHK100 Rotary handle (Direct, Key lock)
EH100 Rotary handle (Extended)
RTB1 Rear terminal (Bar)
RTR1 Rear terminal (Round)
Handle Lock
Note) For more detail see 82 pageNote) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

63
125AF ELCB
EBS103c, EBH103c

Ratings

Frame size 125AF


Type and Pole S-Type H-Type
2-pole(2-sensor) - -
3-pole(3-sensor) EBS103c EBH103c
4-pole(3-sensor) EBS104c EBH104c
Rated current, In 15-20-30-40-50-60-75-100-125A
Rated residual current, I▵n 30, 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV

EBS103c Wiring system 2-pole(2-sensor) -


3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W
4-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W

Rated short-circuit breaking S-Type H-Type


capacity, Icu AC 460V 37kA 50kA
IEC 60947-2 (lcu) 415V 37kA 50kA
220/250V
85kA 100kA
lcs=%×Icu 100% 100%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 12×In (30A and under: 400A)
Endurance Mechanical 25000 operations
EBH103c Electrical 10000 operations
Connection Standard Front connection
Optional Rear connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 4p 3p 4p


ad
c2
90 120 90 120
a c1
b 155 155 155 155
c1 Note)1 60 60 60 60
b

c2 Note)1 64 64 64 64
For more information d 82 82 82 82
•Drawings ▶ 114 page Weight, kg Standard 1 1.2 1 1.2
•Trip curves ▶ 99 page
•Accessories ▶ 74 page
Certification Pole 3p 4p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

64
Ordering types

Breaker types Accessories


EBS type (37kA/460V)
Rated residual current, Rated residual current,
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In
3-pole 4-pole 3-pole 4-pole
15 A EBS103c/15/30 EBS104c/15/30 EBS103c/15/100 EBS104c/15/100
20 A EBS103c/20/30 EBS104c/20/30 EBS103c/20/100 EBS104c/20/100
30 A EBS103c/30/30 EBS104c/30/30 EBS103c/30/100 EBS104c/30/100
40 A EBS103c/40/30 EBS104c/40/30 EBS103c/40/100 EBS104c/40/100
Electrical auxiliaries
50 A EBS103c/50/30 EBS104c/50/30 EBS103c/50/100 EBS104c/50/100 AX Auxiliary Switch
60 A EBS103c/60/30 EBS104c/60/30 EBS103c/60/100 EBS104c/60/100 AL Alarm Switch R T
75 A EBS103c/75/30 EBS104c/75/30 EBS103c/75/100 EBS104c/75/100 AX+AL Combination switch
100 A EBS103c/100/30 EBS104c/100/30 EBS103c/100/100 EBS104c/100/100
125 A EBS103c/125/30 EBS104c/125/30 EBS103c/125/100 EBS104c/125/100 Maximum possibilities
T-position Not available
EBH type (50kA/460V) R-position Option of AX or AL or AX+AL
Rated residual current, Rated residual current, Note) For more detail see 74 page
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In
3-pole 4-pole 3-pole 4-pole
15 A EBH103c/15/30 EBH104c/15/30 EBH103c/15/100 EBH104c/15/100
20 A EBH103c/20/30 EBH104c/20/30 EBH103c/20/100 EBH104c/20/100
30 A EBH103c/30/30 EBH104c/30/30 EBH103c/30/100 EBH104c/30/100
40 A EBH103c/40/30 EBH104c/40/30 EBH103c/40/100 EBH104c/40/100
50 A EBH103c/50/30 EBH104c/50/30 EBH103c/50/100 EBH104c/50/100
60 A EBH103c/60/30 EBH104c/60/30 EBH103c/60/100 EBH104c/60/100
75 A EBH103c/75/30 EBH104c/75/30 EBH103c/75/100 EBH104c/75/100
100 A EBH103c/100/30 EBH104c/100/30 EBH103c/100/100 EBH104c/100/100
125 A
External accessories
EBH103c/125/30 EBH104c/125/30 EBH103c/125/100 EBH104c/125/100
EBS125c
Name
EBH125c

IB23 Insulation barrier


Terminal cover (Long)
TCL23
- Inde type, D-Handle type, N-Handle type
Terminal cover (Short)
TCS23
- Inde type, D-Handle type, N-Handle type
DH125 Rotary handle (Direct)
DHK125 Rotary handle (Direct, Key lock)
EH125 Rotary handle (Extended)
RTB2 Rear terminal (Bar)
RTR2 Rear terminal (Round)
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

65
250AF ELCB
EBN250c, EBS250c, EBH250c

Ratings

Frame size 250AF


Type and Pole N-Type S-Type H-Type
2-pole(2-sensor) EBN202c - -
3-pole(3-sensor) EBN203c EBS203c EBH203c
4-pole(3-sensor) - EBS204c EBH204c
Rated current, In 100-125-150-175-200-225-250A
Rated residual current, I▵n 30, 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue AC: 220/460V
Rated impulse withstand voltage, Uimp 6kV
EBN203c
Wiring system 2-pole(2-sensor) 1Ø2W
3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W
4-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W

Rated short-circuit breaking N-Type S-Type H-Type


capacity, Icu AC 460V 26kA 37kA 50kA
IEC 60947-2 (lcu) 415V 26kA 37kA 50kA
lcs=100%Icu 220/250V 65kA 85kA 100kA
lcs=%×Icu 100% 100% 100%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
EBS203c
Magnetic trip range 12×In
Endurance Mechanical 20000 operations
Electrical 5000 operations
Connection Standard Front connection
Optional Rear connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 2p 3p 3p 4p 3p 4p


d
ac2 105 105 105 140 105 140
a c1
b 165 165 165
c1 Note)1 60 60 60
b

c2 Note)1 64 64 64
For more information d 87 87 87
•Drawings ▶ 115 page Weight, kg Standard 1.1
1.2 1.2
1.5 1.2
1.5
•Trip curves ▶ 100 page
•Accessories ▶ 74 page Certification Pole 2p 3p 3p 4p 3p 4p
•Connection and mounting ▶ 123 page CE marking ○ ○ ○
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

66
Ordering types

Breaker types Accessories


EBN type (25kA/460V)
Rated residual current, Rated residual current,
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In
2-pole 3-pole 2-pole 3-pole
100 A EBN202c/100/30 EBN203c/100/30 EBN202c/100/100 EBN203c/100/100
125 A EBN202c/125/30 EBN203c/125/30 EBN202c/125/100 EBN203c/125/100
150 A EBN202c/150/30 EBN203c/150/30 EBN202c/150/100 EBN203c/150/100
175 A EBN202c/175/30 EBN203c/175/30 EBN202c/175/100 EBN203c/175/100
Electrical auxiliaries
200 A EBN202c/200/30 EBN203c/200/30 EBN202c/200/100 EBN203c/200/100 AX Auxiliary Switch
225 A EBN202c/225/30 EBN203c/225/30 EBN202c/225/100 EBN203c/225/100 AL Alarm Switch R T
250 A EBN202c/250/30 EBN203c/250/30 EBN202c/250/100 EBN203c/250/100 AX+AL Combination switch

EBS type (37kA/460V) Maximum possibilities

Rated residual current, Rated residual current, T-position Not available


Rated R-position Option of AX or AL or AX+AL
I▵n: 30mA I▵n: 100/200/500mA
current, In Note) For more detail see 74 page
3-pole 4-pole 3-pole 4-pole
100 A EBS203c/100/30 EBS204c/100/30 EBS203c/100/100 EBS204c/100/100
125 A EBS203c/125/30 EBS204c/125/30 EBS203c/125/100 EBS204c/125/100
150 A EBS203c/150/30 EBS204c/150/30 EBS203c/150/100 EBS204c/150/100
175 A EBS203c/175/30 EBS204c/175/30 EBS203c/175/100 EBS204c/175/100
200 A EBS203c/200/30 EBS204c/200/30 EBS203c/200/100 EBS204c/200/100
225 A EBS203c/225/30 EBS204c/225/30 EBS203c/225/100 EBS204c/225/100
250 A EBS203c/250/30 EBS204c/250/30 EBS203c/250/100 EBS204c/250/100
External accessories
EBH type (50kA/460V) EBN250c
EBS250c Name
Rated residual current, Rated residual current, EBH250c
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In IB23 Insulation barrier
3-pole 4-pole 3-pole 4-pole
Terminal cover (Long)
100 A EBH203c/100/30 EBH204c/100/30 EBH203c/100/100 EBH204c/100/100 TCL33
- Inde type, D-Handle type, N-Handle type
125 A EBH203c/125/30 EBH204c/125/30 EBH203c/125/100 EBH204c/125/100
Terminal cover (Short)
150 A EBH203c/150/30 EBH204c/150/30 EBH203c/150/100 EBH204c/150/100 TCS33
- Inde type, D-Handle type, N-Handle type
175 A EBH203c/175/30 EBH204c/175/30 EBH203c/175/100 EBH204c/175/100
DH250 Rotary handle (Direct)
200 A EBH203c/200/30 EBH204c/200/30 EBH203c/200/100 EBH204c/200/100
DHK250 Rotary handle (Direct, Key lock)
225 A EBH203c/225/30 EBH204c/225/30 EBH203c/225/100 EBH204c/225/100
EH250 Rotary handle (Extended)
250 A EBH203c/250/30 EBH204c/250/30 EBH203c/250/100 EBH204c/250/100
RTB3 Rear terminal (Bar)
RTR3 Rear terminal (Round)
Handle Lock
Note) For more detail see 82 page
• Inde type: This cover is used without auxiliary Handle.
• D-Handle type: This cover is used with D-Handle.
• N-Handle type: This cover is used with N-Handle.

67
400AF ELCB
EBN400c, EBS400c, EBH400c, EBL400c

Ratings

Frame size 400AF


Type and Pole N-Type S-Type H-Type L-Type
3-pole(3-sensor) EBN403c EBS403c EBH403c EBL403c
4-pole(3-sensor) EBN404c EBS404c EBH404c EBL404c
Rated current, In 250-300-350-400A
Rated residual current, I▵n 30, 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue 220/460V
Rated impulse withstand voltage, Uimp 6kV

EBS403c Wiring system 3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W


4-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W, 3Ø4W

Rated short-circuit breaking N-Type S-Type H-Type L-Type


capacity, Icu AC 415/460V 37kA 50kA 65kA 85kA
IEC 60947-2 (lcu) 220/250V 50kA 75kA 85kA 125kA
lcs=%Icu 100% 100% 100% 75%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 8~12In
Endurance Mechanical 4000 operations
EBL404c
Electrical 1000 operations
Connection Standard Front connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p 4p 3p 4p 3p 4p 3p 4p


d
ac2 140 184 140 184 140 184 140 184
a c1
b 257 257 257 257
c1 Note)1 109 109 109 109
b

c2 Note)1 113 113 113 113


For more information d 145 145 145 145
•Drawings ▶ 116 page Weight, kg Standard 7 8.4 7 8.4 7 7
•Trip curves ▶ 101 page
•Accessories ▶ 75 page Certification Pole 3p 4p 3p 4p 3p 3p
•Connection and mounting ▶ 124 page CE marking - - - -
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. 4-Pole product’s ampacity on neutral conductor is equal to or less than 50% of the rated current.
4. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

68
Ordering types

Breaker types Accessories


EBN type (25kA/460V)
Rated residual current, Rated residual current,
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In
3-pole 4-pole 3-pole 4-pole
250 A EBN403c/250/30 EBN404c/250/30 EBN403c/250/100 EBN404c/250/100
300 A EBN403c/300/30 EBN404c/300/30 EBN403c/300/100 EBN404c/300/100
350 A EBN403c/350/30 EBN404c/350/30 EBN403c/350/100 EBN404c/350/100
400 A EBN403c/400/30 EBN404c/400/30 EBN403c/400/100 EBN404c/400/100

EBS type (50kA/460V)


Electrical auxiliaries
Rated residual current, Rated residual current,
Rated Auxiliary Switch
I▵n: 30mA I▵n: 100/200/500mA AX
current, In Alarm Switch
3-pole 4-pole 3-pole 4-pole AL R T
250 A EBS403c/250/30 EBS404c/250/30 EBS403c/250/100 EBS404c/250/100 SHT Shunt Trip
300 A EBS403c/300/30 EBS404c/300/30 EBS403c/300/100 EBS404c/300/100 UVT Undervoltage trip
350 A EBS403c/350/30 EBS404c/350/30 EBS403c/350/100 EBS404c/350/100
400 A EBS403c/400/30 EBS404c/400/30 EBS403c/400/100 EBS404c/400/100 Maximum possibilities
T-position Not available
EBH type (65kA/460V) R-position Option of 2AX, 2AL and SHT or UVT
Note) For more detail see 75 page
Rated residual current, Rated residual current,
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In
3-pole 4-pole 3-pole 4-pole
250 A EBH403c/250/30 EBH404c/250/30 EBH403c/250/100 EBH404c/250/100
300 A EBH403c/300/30 EBH404c/300/30 EBH403c/300/100 EBH404c/300/100
350 A EBH403c/350/30 EBH404c/350/30 EBH403c/350/100 EBH404c/350/100
400 A EBH403c/400/30 EBH404c/400/30 EBH403c/400/100 EBH404c/400/100

EBL type (85kA/460V)


Rated residual current, Rated residual current,
Rated
I▵n: 30mA I▵n: 100/200/500mA
current, In
3-pole 4-pole 3-pole 4-pole
E-70U N-70
250 A EBL403c/250/30 EBL404c/250/30 EBL403c/250/100 EBL404c/250/100
External accessories
300 A EBL403c/300/30 EBL404c/300/30 EBL403c/300/100 EBL404c/300/100
IBL400 Insulation barrier
350 A EBL403c/350/30 EBL404c/350/30 EBL403c/350/100 EBL404c/350/100
T1-43A Terminal cover (Long) - 2, 3pole
400 A EBL403c/400/30 EBL404c/400/30 EBL403c/400/100 EBL404c/400/100
T1-44A Terminal cover (Long) - 4pole
N-70 Rotary handle (Direct)
E-70U Rotary handle (Extended)
MI-43 Mechanical interlock - 2, 3pole
MI-44 Mechanical interlock - 4pole
Note) For more detail see 82 page

69
800AF ELCB
EBN803c, EBS803c, EBL803c

Ratings

Frame size 800AF


Type and Pole N-Type S-Type L-Type
3-pole(3-sensor) EBN803c EBS803c EBL803c
4-pole(3-sensor) - - -
Rated current, In 500-630-700-800A
Rated residual current, I▵n 30, 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue 220/460V
Rated impulse withstand voltage, Uimp 6 kV
Wiring system 3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W
EBS803c 4-pole(3-sensor) -

Rated short-circuit breaking N-Type S-Type L-Type


capacity, Icu AC 415/460V 37kA 65kA 85kA
IEC 60947-2 (lcu) 220/250V 50kA 85kA 125kA
lcs=%Icu 100% 100% 75%

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 8~12In
Endurance Mechanical 2500 operations
Electrical 500 operations
Connection Standard Front connection
Mounting Standard Screw fixing

Dimensions (mm) Pole 3p


d
ac2 210
a c1
b 280
c1 Note)1 109
b

c2 Note)1 113
For more information d 145
•Drawings ▶ 117 page Weight, kg Standard 11.5
•Trip curves ▶ 101 page
•Accessories ▶ 75 page Certification Pole 3p
•Connection and mounting ▶ 124 page CE marking -
Note) 1. Depth by door cut size : c1 for large cut, c2 for small cut
2. Do not test withstand voltage or insulation resistance test between poles to avoid the damage of the PCB.
3. Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

70
Ordering types

Breaker types Accessories


EBN type (37kA/460V)

Rated residual current, Rated residual current, I▵n:


Rated I▵n: 30mA 100/200/500mA
current, In
3p 3p
500 A EBN803c/500/30 EBN803c/500/100
630 A EBN803c/630/30 EBN803c/630/100
700 A EBN803c/700/30 EBN803c/700/100
800 A EBN803c/800/30 EBN803c/800/100

EBS type (65kA/460V)


Electrical auxiliaries
Rated residual current, Rated residual current, I▵n:
Rated I▵n: 30mA 100/200/500mA AX Auxiliary Switch
current, In Alarm Switch
3p 3p AL R T
SHT Shunt Trip
500 A EBS803c/500/30 EBS803c/500/100
UVT Undervoltage trip
630 A EBS803c/630/30 EBS803c/630/100
700 A EBS803c/700/30 EBS803c/700/100
800 A EBS803c/800/30 EBS803c/800/100 Maximum possibilities
T-position Not available
R-position Option of 2AX, 2AL and SHT or UVT
EBL type (85kA/460V)
Note) For more detail see 75 page
Rated residual current, Rated residual current, I▵n:
Rated I▵n: 30mA 100/200/500mA
current, In
3p 3p
500 A EBL803c/500/30 EBL803c/500/100
630 A EBL803c/630/30 EBL803c/630/100
700 A EBL803c/700/30 EBL803c/700/100
800 A EBL803c/800/30 EBL803c/800/100

E-80U N-80

External accessories
IBL800 Insulation barrier
T1-63A Terminal cover (Long) - 2, 3pole
T1-64A Terminal cover (Long) - 4pole
N-80 Rotary handle (Direct)
E-80U Rotary handle (Extended)
MI-83S Mechanical interlock - 2, 3pole
MI-84S Mechanical interlock - 4pole
Note) For more detail see 82 page

71
1000/1200AF ELCB
EBS1003b, EBS1203b

Ratings

Frame size 1000AF 1200AF


Type and Pole S-Type S-Type
3-pole(3-sensor) EBS1003b EBS1203b
4-pole(4-sensor) - -
Rated current, In 1000A 1200A
Rated residual current, I▵n 100/200/500mA (Adjustable)
Residual current off-time at I▵n ≤0.1 sec
Rated operational voltage, Ue AC: 460V
Wiring system 3-pole(3-sensor) 1Ø2W, 1Ø3W, 3Ø3W

Rated short-circuit breaking S-Type S-Type


capacity, Icu AC 415/460V 85kA
IEC 60947-2 (lcu) 220/250V 125kA

Protective function Overload, Short-circuit and Ground fault


Type of trip unit Thermal-Magnetic
Magnetic trip range 3~6×In ...①
Endurance Mechanical 2500operations
Electrical 500operations
Connection Standard Front connection
① Adjustable instantaneous
Mounting Standard Screw fixing
for each phase
Dimensions (mm) Pole 3p
d
ac2 220
a c1
b 565
c 105
b

For more information


•Drawings ▶ 118 page
d 159
•Trip curves ▶ 102 page Weight, kg Standard 27.1
Note) Rated non-trip current sensitivity is equal to or less than 50% of the rated current sensitivity.

72
Ordering types

Breaker types Contact operation for Auxiliary and Alarm Switches


EBS type (85kA/460V ) MCCB ON OFF TRIP
Rated current, In 3p
1000 A EBS1003b/1000/100
AX
1200 A EBS1203b/1200/100

AL

Option of below items for T-position Contact rating for Auxiliary and Alarm Switches
AX1 Auxiliary Switch (1c) AC DC
AL1 Alarm Switch (1c) Voltage Current (A) Voltage Current (A)
R T (V) Resistive load Inductive load (V) Resistive load Inductive load
AX1+AL1 Auxiliary (1c) + Alarm (1c) Switch
Note) R-position is not available. 125 20 20 30 6 5
250 20 20 125 0.4 0.05
500 10 5 250 0.2 0.03

73
Accessories

SHT

Shunt Trip

AX

Auxiliary UVT
Switch

Undervoltage
trip

AL
Left-hand seat Right-hand seat

Alarm Switch

AX
Auxiliary
Switch

AX+AL
AL
Alarm
Combination switch Switch

Option of connecting AX or AL or AX+AL


This seat is not available for 2-pole MCCB. AX+AL Combination
switch

Option of connecting SHT or UVT


or AX or AL or AX+AL
This seat is not available for ELCB.

Maximum possibilities
ABN100c ABH125c ABH250c EBN100c EBH125c EBH250c
Position Type
2p 3/4p 2p 3/4p 2/3/4p 2/3/4p 3/4p 2/3/4p

AX - 1 - 1 1 1 1 1
Left-hand
AL - 1 - 1 1 1 1 1
seat
AX+AL - 1 - 1 1 1 1 1
AX 1 1 1 1 1 - - -
Right-hand AL 1 1 1 1 1 - - -
seat AX+AL 1 1 1 1 1 - - -
SHT/UVT 1 1 1 1 1 - - -

74
Electrical auxiliaries of 400~800AF

AL AL AL AL

Alarm Switch Alarm Switch

SHTSHT SHTSHT

Shunt Trip Shunt Trip

UVTUVT UVTUVT

Undervoltage trip Undervoltage trip

AX AX AX AX

Auxiliary Switch Auxiliary Switch

Option of connecting Option of connecting


AX or AL or AX+AL SHT or UVT or AX or AL or AX+AL
This seat is not available for 2-pole breakers. This seat is not available for ELCB.

Maximum possibilities
MCCB ELCB
Position Type
(400~800AF) (400~800AF)
AX 2 2
Left-hand
AL 2 2
seat
SHT/UVT 1 1
AX 2 -
Right-hand
AL 2 -
seat
SHT/UVT 1 -

75
Accessories

Combinations of accessories
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker

Series MCCB (30~250AF) MCCB (400~800AF) MCCB (1000~1200AF)


ABN 53c/54c
ABN 52c
ABN 63c/64c ABN 402c/403c/404c
N-Type ABE 32b ABE 33b ABN 62c -
ABN 103c/104c, ABN 103d/104d ABN 802c/803c/804c
ABN 102c/102d
ABN 202c/203c/204c
ABS 33c/34c ABS 1003b
ABS 32c
ABS 53c/54c ABS 1004b
ABS 52c ABS 402c/403c/404c
S-Type - - ABS 63c/64c ABS 1203b
ABS 62c ABS 802c/803c/804c
ABS 103c/104c ABS 1204b
Type ABS 102c
ABS 202c/203c/204c ABS 1203bE
ABH 53c/54c
ABH 52c
H-Type - - ABH 103c/104c ABH 402c/403c/404c -
ABH 102c
ABH202c/203c/204c
ABL 1003b
ABL 402c/403c/404c ABL 1004b
L-Type - - - -
ABL 802c/803c/804c ABL 1203b
ABL 1204b
Pole 2 Pole 3 Pole 2 Pole 2, 3, 4 Pole 2, 3, 4 Pole 3, 4 Pole
AX

AX2

AX3 (4)

AL

AL2

AL3(4)

SHT(UVT)

SHT(UVT)2

AX+AL

AX+AL2

AX+AL3(4)

AX2+AL

AX2+AL2

AX2+AL3(4)

AX3(4)+AL

AX3(4)+AL2

AX3(4)+AL3(4)

AX+SHT(UVT)

76
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker

Series MCCB (30~250AF) MCCB (400~800AF) MCCB (1000~1200AF)


ABN 53c/54c
ABN 52c
ABN 63c/64c ABN 402c/403c/404c
N-Type ABE 32b ABE 33b ABN 62c -
ABN 103c/104c ABN 802c/803c/804c
ABN 102c
ABN 202c/203c/204c
ABS 33c/34c ABS 1003b
ABS 32c
ABS 53c/54c ABS 1004b
ABS 52c ABS 402c/403c/404c
S-Type - - ABS 63c/64c ABS 1203b
ABS 62c ABS 802c/803c/804c
ABS 103c/104c ABS 1204b
ABS 102c
Type ABS 202c/203c/204c ABS 1203bE
ABH 53c/54c
ABH 52c
H-Type - - ABH 103c/104c ABH 402c/403c/404c -
ABH 102c
ABH202c/203c/204c
ABL 1003b
ABL 402c/403c/404c ABL 1004b
L-Type - - - -
ABL 802c/803c/804c ABL 1203b
ABL 1204b
Pole 2 Pole 3 Pole 2 Pole 2, 3, 4 Pole 2, 3, 4 Pole 3, 4 Pole
AX+SHT(UVT)2

AX2+SHT(UVT)

AX2+SHT(UVT)2

AX3(4)+SHT(UVT)

AX3(4)+SHT(UVT)2

AL+SHT(UVT)

AL+SHT(UVT)2

AL2+SHT(UVT)

AL2+SHT(UVT)2

AL3(4)+SHT(UVT)

AL3(4)+SHT(UVT)2

AX+AL+SHT(UVT)

AX+AL+SHT(UVT)2

AX2+AL2+SHT(UVT)

AX2+AL2+SHT(UVT)2

AX3(4)+AL3(4)+SHT(UVT)

AX3(4)+AL3(4)+SHT(UVT)2

77
Accessories

Combinations of accessories
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage
Main breaker
Left-hand Right-hand Auxiliary switch (AX)
seat seat
Alarm switch (AL) Shunt trip (SHT) / Undervoltage trip (UVT)
Main breaker

Series ELCB (30~250AF) ELCB (400~800AF) ELCB (1000~1200AF)


EBN 52c/53c/54c
EBN 63c EBN 403c/404c
N-Type -
EBN 102c/103c/104c EBN 803c
EBN 202c/203c
EBS 33c/34c
EBS 53c/54c
EBS 403c/404c EBS 1003b
S-Type EBS 63c/64c
EBS 803c EBS 1203b
EBS 103c/104c
Type EBS 203c/204c
EBH 53c/54c
H-Type EBH 53c/54c EBH 403c/404c -
EBH 103c/104c

L-Type EBL 403c/404c
- -
EBL 803c
Test lead wire (30~250AF)
Pole 3, 4 Pole 3 Pole 3 Pole
AX

AX2

Test button AL

AL2

SHT(UVT)
Note) 1. When you touch the lead wire under energized condition,
you will be in danger of electric shock.
2. Do not energize on both ends of lead wire. AX+AL
3. Do not pull out the lead wire excessively or impact on the
product.
AX+AL2

AX2+AL

AX2+AL2

Terminal block type AX+SHT(UVT)

AX2+SHT(UVT)

AL+SHT(UVT)

AL2+SHT(UVT)

AX+AL+SHT(UVT)

AX2+AL2+SHT(UVT)

78
Auxiliary and Alarm switch

Auxiliary switch (AX)


Auxiliary switch is for applications requiring remote “ON” and “OFF” indication.
Each switch contains two contacts having a common connection.
One is open and the other closed when the circuit breaker is open, and viceversa.

Alarm switch (AL)


Alarm switches offer provisions for immediate audio or visual indication of a tripped breaker due to overload,
short circuit, shunt trip, or undervoltage release conditions.
They are particularly useful in automated plants where operators must be signaled about changes in the
electrical distribution system. This switch features a closed contact when the circuit breaker is tripped
automatically. In other words, this switch does not function when the breaker is operated manually.
Its contact is open when the circuit breaker is reset.

Combination switch (AX+AL)


It consists of one auxiliary switch (AX) and one alarm switch (AL) in a body to connect into the same position of
the breaker.

Contact (AX+AL)
MCCB ON OFF TRIP

AX

AL

Rating (AX+AL)
Conventional thermal current, Ith 5A

Rated operational current, Ie Current, Ie


Voltage, Ue Resistive Inductive Minimum Applicable
load load laod current MCCB/ELCB
AC 50/60Hz 125V 5 3
250V 3 2
500V - - 5V DC 160mA Metasol MCCB/ELCB
DC 30V 4 3 30V DC 30mA 30~800AF
125V 0.4 0.4
250V 0.2 0.2

79
Accessories

Shunt trip, SHT

The shunt trip opens the mechanism in response to an externally applied voltage signal. The releases include
coil clearing contacts that automatically clear the signal circuit when the breaker has tripped. This is not
available for ELCBs of 30~250AF .

Rating for 30~250AF

Power consumption
Control voltage, Ue MCCB/ELCB
AC (VA) DC (W)

DC 12V - 1.5

AC/DC 24~30V 1.5 1.5

AC/DC 48~60V 1.5 1.5

Voltage AC/DC 100~130V 1.5 1.5 Metasol MCCB


ABN100c
Terminal block type (TBT) AC/DC 200~250V 1.5 1.5
ABH125c
AC 380~450V 1.5 -
ABH250c
AC 440~500V 1.5 -
Max.opening time 50ms (max.)
Tightening torque of
terminal screw 8.2 kgf·cm
Note: 1. Range of operational voltage: 0.7 ~ 1.1Vn
Lead wire type (LWT) Frequency (Only AC): 45Hz ~ 65Hz

Rating for 400~800AF


Power consumption
Control voltage, Ue
V mA W

AC/DC 24~48 AC 24 14 0.3


AC 100~240/DC 100~220 DC 24 15.4 0.4
AC 380~550 AC 48 14 0.7
Lead wire type (LWT)
Note: Range of operational voltage DC 48 16 0.8
AC: 0.85 ~ 1.1Vn
DC: 0.75 ~ 1.25Vn AC 110 6 0.7
DC 110 6.6 0.7
AC 220 6.8 1.5
DC 200 7.6 1.5
AC 440 4.3 1.9
AC 480 4.4 3.3
AC 550 4.6 2.4

80
Undervoltage release, UVT

The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between
20% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be
re-closed again until the voltage returns to 85% of line voltage.
Continuously energized, the undervoltage release must be operating before the circuit breaker can be closed.
This is not available for ELCBs of 30~250AF .

- Range of tripping voltage: 0.2 ~ 0.7Vn


- Reset and closing of a breaker is possible when the control voltage is over 0.85Vn
- Frequency (Only AC): 45Hz ~ 65Hz

Rating for 30~250AF


Power consumption
Control voltage, Ue
AC (VA) DC (W) mA

AC/DC 24V 0.64 0.65 27


AC/DC 48V 1.09 1.1 23
AC/DC 100~110V 0.73 0.75 5.8
Voltage
AC/DC 200~220V 1.21 1.35 5.4
AC 380~440V 1.67 - 3.8
AC 440~480V 1.68 - 3.5
Max.opening time 50ms (max.)
Tightening torque of terminal screw 8.2 kgf·cm
Operating Trip 20~70% Vn
voltage range Reset/Closing ≥ 0.85Vn

Rating for 400~800AF


Control voltage, Ue Trip voltage Reset/closing voltage Time rating

AC/DC 48
AC/DC 100~125
·AC: 85~1.1Vn ·AC: 0.2~0.7Vn
AC 200~240 / DC 200~240 Continuous
·DC: 85~1.25Vn ·DC: 0.2~0.7Vn
AC 380~440
AC 440~480

Terminal numbering
Auxiliary Switch (AX) Alarm Switch (AL) Shunt Trip (SHT) Undervoltage trip (UVT)

81
Accessories

External accessories

Wide range of external accessories provides user-friendly solution for mounting, cable connection, insulation, safety lock and remote control.

Insulation barrier

Terminal cover

Rear terminal

Breaker
Rotary handle (Direct)

Rotary handle
(Direct, Key lock)

Rear terminal

Plug-in kit Rotary handle


(Extended)

Terminal cover

Insulation barrier Pad Handle Lock

82
Rotary handles
Direct type
The rotary handle operating mechanism is available in either the direct version or in the extended version on the
compartment door. It is always fitted with a compartment door lock and on a request it can be supplied with a
key lock in the open position.

Direct type , D-handle and N-handle


-D-Handle : Directly mountable to a circuit breaker. Trip button is built as standard. Key lock type is optional.
Direct type -N-Handle : Directly mountable to a circuit breaker. Door is locked in the Off state. Handle size is greater than D-Handle.
(DH 30~250AF) Extended type, E-Handle
It is used in case direct type handle can not be applied because of the longer distance between the breaker and
the panel door.

Type
Key lock
(DH 30~250AF) Direct type Breaker type
Direct type Extended type
(Key lock) MCCB ELCB

N-30c - - ABN50c/60c/100c EBN50c/60c/100c


DH100 DHK100 EH100 ABS30c/50c/60c EBS30c/50c/60c
N-40c - - ABS125c EBS125c
DH125 DHK125 EH125 ABH50c/125c EBH50c/125c
(N 30~250AF) N-50c - -
ABN/S/H250c EBN/S/H250c
DH250 DHK250 EH250
N-70 - E-70U ABN/S/H/L400c EBN/S/H/L400c
N-80 - E-80U ABN/S/L630c/800c EBN/S/L630c/800c
Note: Padlock type for N-handle
- On or OFF state type - Only OFF state type

(N 400~800AF)

Extended type

Type suffix according to the mounting position


S-Type L-Type R-Type
LINE
LINE LOAD LOAD LINE

(30~250AF)

LOAD

ON ON

(400~800AF)

83
Accessories

D-handle

MCCB and D-handle


ABN100c ABH125c ABH250c

Tripping MCCB & Install type

Tripped

Push to trip

L-Type S-Type R-Type

LINE

LINE LOAD LOAD LINE

LOAD
ON ON ON

84
Installing the D-handle

ABN100c, EBN100c ABH125c, EBH125c ABH250c, EBH250c

Cutting Panel

D-Handle A (mm) B (mm) C (mm) D (mm) E (mm) Breaker

DH100 110.5 78 90 92 103.4 100AF


DH125 132 94 105 108 120 125AF
DH250 126 108 121 110 122 250AF

85
Accessories
LOCKED

D-handle
UNLOCKED

Operating
OFF position Test
Remove
CAUTIONthe key if you operate the handle.
If the door is opened with
much pressure when the ON
position of handle is ON or
TRIP, the handle lock lever
will be demaged.

TRIP position : Panel door


can’t be opened

Reset Panel door not open

PUSH TO
OFF Tripped TRIP

Panel door open &


close availa ble

Locking System

Releasing (at ON position) Locking (ON, OFF position)

Open Panel Door KEY LOCK

LOCKED

UNLOCKED

OFF position

Releasing Remove the key if you operate the handle.

86
E-handle

MCCB and E-handle


ABN100c ABH125c ABH250c

Tripping MCCB & Install type

Tripped

Push to trip

L-Type S-Type R-Type


LINE

LINE LOAD LOAD LINE

LOAD
ON ON ON

87
Accessories

E-handle

Installing the E-handle

ABN100c, EBN100c ABH125c, EBH125c ABH250c, EBH250c

Cutting Panel

E-Handle A (mm) B (mm) C (mm) Breaker

EH100 min 150, max 573.5 (SHAFT469mm) 47 Ø53 100AF


EH125 min 150, max 573.5 (SHAFT469mm) 47 Ø53 125AF
EH250 min 150, max 571.5 (SHAFT469mm) 47 Ø53 250AF
Note: An extension shaft that must be adjusted to the distance between back of circuit breaker and door

88
LOCKED

UNLOCKED

Operating
OFF position Test
Remove
CAUTIONthe key if you operate the handle.
If the door is opened with
much pressure when the Reset ON
position of handle is ON or
TRIP, the handle lock lever
will be demaged.

TRIP position : Panel door


can’t be opened

Panel door not open

OFF

Panel door open &


close availa ble

Locking System

Releasing (at ON position) Locking (ON, OFF position)

Open Panel Door

Releasing

89
Accessories

N-handle

How to mount
1) Drilling on the panel door (N-30c, 40c, 50c) (N-70, N-80)
① All the N handles require the same size of
mounting hole.
② Drill the holes according to the Fig. 1

Mounting base
Dimension A
* S : Vertical mounting N-30c :103
N-40c : 103
<Fig 1> N-50c : 103

(2) Mounting base


① Prepare a mounting base according to the Fig. 2 . (N-30c, 40c, 50c) (N-70, N-80)
The distance between the door panel and the
mounting base should be A+2. Dimension A Mounting base Mounting base
is shown in the Fig. Dimension A
② In the case of horizontal mounting turn the N-30c :103
N-40c : 103
breaker mounting holes by 90 degrees N-50c : 103

<Fig 2>

Mounting base
(3) Fixing
① Fixing a breaker and a handle at the same (N-30c, 40c, 50c) (N-70, N-80)
time.
a) As shown in the Fig. 3 a breaker and
a handle can be fixed at the same time
on a mounting base with the 4 (long)
screws enclosed.

<Fig 3>

b) Have the breaker handle and the


lever of N handle be located in the
position shown in Fig. 4.
lever of lever of
N handleN handle
breaker breaker
handle handle

(N-30c, 40c, 50c) (N-70, N-80)

<Fig 4>

90
② Fixing a handle and a breaker step by step
a) Check if there is any thin membrane in the mounting hole
of the breaker cover and remove it, If exists.
b) Have the breaker handle and the lever of N handle be
located in the position shown in Fig. 4.
c) Fix the N handle on the breaker with the 2 (short) screws
enclosed.
d) Fix the breaker on a mounting base with the 2 (long)
<Fig 5>
screws
locking plate
(4) Fixing front plate and lock plate
① Set the front plate and the locking plate on the door as door

front plate
shown in Fig. 6 fix them with screws.

<Fig 6>

② Adjust if front plate or handle is at tilt against the breaker .

Bad-tilt

<Fig 7>

③ Verify that locking plate and locking lever interact on each


other properly when the panel door is closed.
If necessary adjust them by following instructions.

<Fig 8>

a) In the event the panel door is not fully closed


This happens if the distance between the door panel and
the mounting base the panels of the door is short.
Loosen the adjusting screw in the lock plate and move the adjusting screw

platein the direction of the arrow as shown in Fig. 9.


locking lever

<Fig 9>

b) In the event the door does not lock after closing the door
This happens if the distance between the door panel and
the mounting base the panels of the door is long.
Loosen the adjusting screw in the lock plate and move the
plate in the direction of the arrow as shown in Fig. 10.

<Fig 10>

91
Accessories

N-handle

­­(1) Operation in the door closed


① To have the breaker ON turn the handle to be vertical. <Fig. 11>
② To have the breaker OFF turn the handle to be horizontal. <Fig. 12>
③ If the breaker is tripped, the handle points to the TRIP position.
④ To reset the breaker turn the handle to Reset position.

<Fig 11>
(2) Unlocking the panel door
① The door is locked and will not open at ON, OFF and TRIP status.
② To unlock the door from OFF or TRIP status turn the handle toward OPEN
direction. (Unlocked after taking the hand off the handle.)
③ To unlock the door from ON state turn the Release screw clockwise <Fig. 13>

<Fig 12>
(3) Operation of the breaker in the door open
① When the door is open the breaker will not be ON as the lock lever operates.
② To release the locking pull the lock lever to be nearly horizontal position. Then
the breaker can be closed. <Fig. 14>
③ If the door is closed the lock lever will be reset automatically.
Release screw
Release screw

<Fig 13>

Padlocking
① Lockable at ON or OFF state with a padlock. (Padlock is not supplied)
(N-30, 40, 50)
- Lockable at OFF state with a padlock is an optional spec.
② Pull the lock plate on the front of the handle and fasten the lock. <Fig. 15>
③ If the breaker is tripped after padlocking at ON state, the handle will point to
the TRIP.
④ Padlock diameter should be 3.5 ~ 6mm

(N-70, N-80)

<Fig 14>

<Fig 15>

92
Terminal covers

The terminal covers are applied to the circuit-breaker to prevent accidental contact with live parts and thereby guarantee protection
against direct contacts.
Two types by length are available and provide IP20 degree of protection.
Also, covers ara classified in to 2 different type: Independent, Attachable and detachable with D or N Handle

•Short type covers, TCS:


For fixed circuit-breakers with rear terminals and for moving parts of plug-in.

•Long type covers, TCL:


For fixed circuit-breakers with front, front extended, front for cables terminals.

Terminal covers Size extended(A),


Applied breaker
Short Type Long Type Pole mm
Inde D-Handle N-Handle Inde D-Handle N-Handle MCCB ELCB Short Type Long Type

TBS22 - - - - - 2P
ABE30b - 10 -
TBS23 - - - - - 3P
TCS12 - - TCL12 - - 2P
ABN50c/60c/100c EBN50c/60c/100c
TCS13 TCS13 TCS13 TCL13 TCL13 TCL13 3P 5.5 30
ABS30c/50c/60c EBS30c/50c/60c
TCS14 TCS14 TCS14 TCL14 TCS14 TCS14 4P
TCS22 - - TCL22 - - 2P
ABS125c EBS125c
TCS23 TCS23 TCL23 TCL23 3P 5.5 40
ABH50c/125c EBH50c/125c
TCS24 TCS24 TCL24 TCL24 4P
TCS33 TCS33 TCL33 TCL33 2, 3P ABN250c, ABS250c EBN250c, EBS250c
5.5 50
TCS34 TCS34 TCL34 TCL34 4P ABH250c EBH250c
- - - T1-43A - - 2, 3P
ABN/S/H/L400c EBN/S/H/L400c - 120
- - - T1-44A - - 4P
- - - T1-63A - - 2, 3P
ABN/S/L/800c EBN/S/L/800c - 141
- - - T1-64A - - 4P
Note: Terminal covers for 400AF and 800AF MCCBs are in acrylic.

TCS(Short type)
A

TCL(Long type) Short type construction Long type construction

93
Accessories

Insulation barriers

Insulation barrier allows the insulation characteristics between the phases at the connections to be increased.
They are mounted from the front, even with the circuit-breaker already installed, inserting them into the
corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side by side.

Breaker
Type
MCCB ELCB

ABN50c/60c/100c EBN50c/60c/100c
IB-13
ABS30c/50c/60c EBS30c/50c/60c
ABS125c EBS125c
ABH50c/125c EBH50c/125c
IB-23
ABN250c, ABS250c EBN250c, EBS250c
ABH250c EBH250c

IBL400 ABN/S/H/L400c EBN/S/H/L400c


IBL800 ABN/S/L800c EBN/S/L800c


Insulation barriers for line side are provided as standard.

94
Rear connection terminals

Rear connection terminals are used to adapt the circuit breakers to switchboards or
other applications that require rear connection.
There are two kinds of rear connection terminals.

- Flat type
- Round type

Round type terminals

Breaker For 2-pole For 3-pole For 4-pole

ABN100c 50AF RTR1-52 RTR1-53 -


ABN100c 100AF RTR1-102 RTR1-103 RTR1-104
ABH125c RTR2-102 RTR2-103 RTR2-104
ABH250c RTR3-202 RTR3-203 RTR3-204

CL

Flat type terminals

Breaker For 2-pole For 3-pole For 4-pole

ABN100c RTB1-102 RTB1-103 RTB1-104


ABH125c RTB2-102 RTB2-103 RTB2-104
ABH250c RTB3-202 RTB3-203 RTB3-204

CL CL

95
Accessories

Mechanical interlock
The mechanical interlock is installed on the front of two breakers mounted side by side, in either the 3-pole or 4-pole version
and prevents simultaneous closing of the two breakers. So it is suitable for consisting of manual sourcechangeover system.

Type numbering system

MI 4 3

Type AF Pole
Mechanical 1 100AF 3 3P
interlock 2 125AF 4 4P
3 250AF
4 400AF
8 800AF

Types and applicable breakers


Type MCCB ELCB

MI-13, 14 ABS30c, ABS50c, ABS60c, ABN50c, ABN60c, ABN100c EBS30c, EBS50c, EBS60c, EBN50c, EBN60c, EBN100c
MI-23, 24 ABS100c, ABH50c, ABH100c EBS100c, EBH50c, EBH100c
MI-33, 34 ABN/S/H200c EBN/S/H200c
MI-43, 44 ABN/S/H/L400c EBN/S/H/L400c
MI-83, 84 ABN/S/L600c, 800c EBN/S/L600c, 800c
Note) MI is not applicable to 2-pole version breakers of 100AF and 125AF.

Layout

Padlock dimensions

* Padlock is not supplied.

MCCB panel cutting MCCB panel drilling


Narrow cutting Narrow cuttingWide cutting Wide cutting
C E C
B B B B
A

A
A

( Unit in: mm) ( Unit in: mm)

MI-13, 14 MI-23, 24 MI-33, 34 MI-43, 44 MI-83, 84 C D E


Cutting Breaker
A B A B A B A B A B 3P 4P 3P 4P 3P 4P
Narrow 52 66 52 66 52 66 100 111 100 111 100AF 25 25 110.5 110.5 70 95
Wide 86 62 102 62 104 62 152 97 152 97 125AF 30 30 132 132 84 114
250AF 35 35 126 126 99 134
400AF 44 44 215 215 166 210
800AF 70 70 243 243 210 280
96
Plug-in devices
Plug-in device makes it possible to extract and/or rapidly replace the circuit breaker without having to touch
connections for ship and important installations.
The plug-in base is the fixed part of the plug-in version of the circuit-breaker.
It will be installed directly on the back plate of panel.
The circuit-breaker is racked out by unscrewing the top and bottom fixing screws.

Normal type Plug-in MCCB


Plug-in base
- MCCB current rating upto 250A
- generally used in switchgears

Double-row type Plug-in MCCB


- For 125AF MCCB
- generally used in branch circuits

Type names of blocks


Breaker Arrangement P lug-in block Remark

Normal PB-A3-FR
Single-row PB-A3-1DB
Plug-in type MCCB ABN100c
(plug-in terminal built) Double-row PB-A3-2DB
Line-only PB-A3-FRL
Normal PB-C3-FR
Single-row PB-C3-1DB
ABH125c
Double-row PB-C3-2DB
Line-only PB-C3-FRL
ABH250c Normal PB-D3-FR
400AF Normal/Line-only PB-I3-FR/PB-I3-FRL
800AF Normal PB-J3-FR
ABH103c plug-in type

Normal Double-row

ABH203c plug-in type

97
Type numbering system

MCCB
AB S 10 3 C M / 100A AX T SHT=220V

MCCB Type Ampere Frame Pole Series Application Rated current Position & Type Control voltage
General of accessory
N N-Type 3 30AF 2 2-pole Right
-
S S-Type 5 50AF 3 3-pole purpose T LWT Side SHT
Motor Lead
H H-Type 6 60AF 4 4-pole Mounting AC/DC 12V
M Wire
L L-Type 10 100/125AF protection Left AC/DC 24V
Type
20 225/250AF R LWT Side AC/DC 48V
40 400AF Mounting AC/DC 60V
80 800AF Right AC/DC
100 1000AF Rated current Accessory T TBT side 100V~130V
Terminal
120 1200AF 3A 150A AX Auxiliary Switch mounting AC/DC
Block
5A 175A AL Alarm Switch Left 200V~250V
Type
10A 200A SHT Shunt Trip R TBT side AC 380V~450V
15A 225A Undervoltage mounting AC 440V~500V
UVT UVT
20A 250A trip
30A 300A Rotary handle AC/DC 24V
DH AC/DC 48V
40A 350A (Direct)
50A 400A Rotary handle AC/DC
EH 100V~110V
60A 500A (Extended)
75A 630A RTR AC/DC
Rear terminal 200V~220V
100A 700A RTB
125A 800A AC 380V~440V
150A 1200A AC 440V~480V

* Warning: Mounting accessories is not available at the left side of 2pole MCCB (Up to 125AF)

ELCB

EB S 10 3 C / 100A 30mA AX R

ELCB Type Ampere Frame Pole Series Rated residual Accessory


N N-Type 3 30AF 2 2-pole current AX Auxiliary Switch
S S-Type 5 50AF 3 3-pole 30mA AL Alarm Switch
H H-Type 6 60AF 4 4-pole 100/200/500mA Rotary handle
DH
L L-Type 10 100/125AF (Direct)
20 225/250AF Rated current Rotary handle
EH
40 400AF 15A 225A (Extended)
80 800AF 20A 250A RTR
Rear terminal
100 1000AF 30A 300A RTB
120 1200AF 40A 350A
50A 400A
Position & Type
60A 500A
75A 630A Left Lead
100A 700A R LWT Side Wire
125A 800A Mounting Type
150A 1000A Left Terminal
175A 1200A R TBT Side Block
200A Mounting Type
* Warning: Mounting accessories is not available at the right side ELCB (Up to 250AF)

98
Characteristics curves

Breaker types Compensation curves Rated current: 3~30A (ABE)


MCCB ABE30b
Rated current compensation rate (%)

ABE30b

Min.
Ambient temp. 40℃
Max.

Operational time
Min.

Breaker types Compensation curves


Sec.

MCCB ABN/S, EBN/S


Rated current compensation rate (%)

Magnetic trip range


ABN50c/60c/100c/100d
ABS30c/50c/60c
ELCB Max. breaking time

EBN50c/60c/100c
EBS30c/50c/60c
Ambient temp. 40℃ Rated current

Rated current: 3~30A (ABN/S,EBN/S) Rated current: 40~100A (ABN/S,EBN/S)


Min.
Min.

Max. Max.
Operational time
Operational time

Min. Min.
Sec.
Sec.

Magnetic trip range Magnetic trip range

Max. breaking time Max. breaking time

Rated current Rated current

99
Characteristics curves

Breaker types Rated current: 15~30A, 40~100A


MCCB
ABS125c
ABH50c/125c

Min.
ELCB
EBS125c
EBH50c/125c

Max.

Operational time

Min.
Sec.

Magnetic trip range

Max. breaking time

Rated current

Compensation curves Rated current: 125A


Rated current: 15~100A
Rated current compensation rate (%)

Min.

Max.
Operational time

Ambient temp. 40℃

Min.

Rated current: 125A


Sec.
Rated current compensation rate (%)

Magnetic trip range

Max. breaking time

Rated current
Ambient temp. 40℃

100
Breaker types Rated current: 100~225A
MCCB
ABN250c, ABS250c
ABH250c
ELCB

Min.
EBN250c, EBS250c
EBH250c

Max.

Operational time
Sec. Min.

Magnetic trip range

Max. breaking time

Rated current

Compensation curves Rated current: 250A


Rated current: 100~225A 240
Rated current compensation rate (%)

180
150 150
120
100
80
60
40
Min.

20
100
10
8
6
4

50 2
0 10 20 30 40 50 Max.
1
Ambient temp. 40℃
Operational time

40

20

10
8
6 Min.
4

Rated current: 250A 2


Rated current compensation rate (%)

150
Sec.

1
0.8
0.6
0.4
Magnetic trip
0.2
range
100 (960~1440%)
0.1
0.08
0.06
0.04
Max. breaking time

0.02
50
0 10 20 30 40 50 0.01
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100
Ambient temp. 40℃
Rated current

101
Characteristics curves

Breaker types Rated current: 250~400A


MCCB
ABN400c, ABS400c, ABH400c, ABL400c
ABN800c, ABS800c, ABL800c
ELCB

Min.
EBN400c, EBS400c, EBH400c, EBL400c
EBN800c, EBS800c, EBL800c
Max.

Operational time

Min.
Sec.

Magnetic trip range

Max. breaking time

Rated current

Compensation curves Rated current: 500~800A


Rated current: 250~400A
Rated current compensation rate (%)

240
150 180
120

60
40

100
Min.

20

10
8
6
4
Max.
50 2
0 10 20 30 40 50
1
Ambient temp. 40℃
Operational time

40

20

10
8
6
Min.
4

Rated current: 500~800A 2


Rated current compensation rate (%)

150 1
Sec.

0.8
0.6
0.4

0.2
100 Magnetic trip range
0.1
0.08 (800~1200%)
0.06
0.04 Max. breaking time
0.02
50
0 10 20 30 40 50 0.01
1 1.25 2 3 4 5 6 7 8 9 10 15 20 30 40 50 70 100
Ambient temp. 40℃
Rated current

102
Breaker types Rated current: 1000~1200A
MCCB
ABS1000b, ABL1000b
ABS1200b, ABL1200b
ELCB

Min.
EBS1003b, EBS1203b
Max.

Min. Rated Ranges of instantaneous trip


current
Min Max

Operational time
Compensation curves

Rated current compensation rate (%)


Rated current: 1000~1200A
Rated current compensation rate (%)

Sec.

Max. breaking time

Ambient temp. 40ŭ

Rated current

Breaker types Rated current: 1200A


MCCB
ABS1200bE
Hou.
Min.
Operational time
Sec.

Rated current

103
Characteristics curves
Motor Protection type

Breaker types Rated current: 16~32A

Min.
MCCB
ABN50cM/60cM/100cM/100dM
ABS30cM/50cM/60cM

Min.
Max.

Operational time
Min. Max.

Operational time
Sec.
Min. trip range
Magnetic
Sec.

Max. breaking time

Magnetic trip range

Rated current
Max. breaking time

Rated current

Compensation curves Rated current: 45~90A


Rated current: 16~32A
(%)(%)
rate

16A~32A
rate

16A~32A
compensation
compensation

Min.
current
current
Rated

Max.
Min.
Rated

Ambient temp . 40℃


Operational time

Ambient temp . 40℃

Max.
Min.
Operational time

Rated current: 45~90A


(%)(%)

Sec.
rate
rate

Min.Magnetic trip range


compensation
compensation

45A~90A
Sec.

45A~90A Max. breaking time


current
current

Magnetic trip range


Rated
Rated

Ambient temp . 40℃ Rated current


Ambient temp . 40℃ Max. breaking time

104
Rated current
Breaker types Rated current: 16~90A
MCCB 240
180
150
120
ABS125cM 100
80
60
ABH50cM/125cM 40

Min.
20

10
8
6
4

2
Max.
1
40

Operational time
20

10
8

Compensation curves 6
4
Min.

2
Rated current: 16~90A
Rated current compensation rate (%)

1
Sec.

0.8
16A~32A 0.6
0.4
Magnetic trip range
0.2

45A~90A 0.1
0.08
0.06
0.04 Max. breaking time

0.02

0.01
1 1.5 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 100
Ambient temp . 40℃
Rated current

Breaker types Rated current: 125~225A


MCCB
ABN250cM, ABS250cM
ABH250cM

Compensation curves
Rated current: 125~225A
Rated current compensation rate (%)

Ambient temp. 40ŭ

105
Dimensions

MCCB
ABE30b

(mm)

Terminal cover
Insulation barrier Insulation
Terminal cover barrier
Terminal cover
Fixing hole

Terminal cover
Insulation barrier Insulation
Terminal cover barrier
Terminal cover
Fixing hole
DIN-Rail

Terminal cover
Insulation barrier Insulation
Terminal cover barrier DIN-Rail
Terminal cover
Fixing hole

Trip test button Trip test button DIN-Rail

2P 3P
Trip test button Trip test button

Trip test button Trip test button

Terminal details

(Screw) (Screw)

(Screw) (Screw)

Panel drilling Front panel cutting

(Screw) (Screw)

(Holder) (Holder)

(Holder) (Holder)

(Holder) (Holder)
3P 3극

106
MCCB ABN50c ABS30c
ABN60c ABS50c
ABN100c/100d ABS60c

(mm)

25 25 25 56

Insulation barrier Insulation barrier Insulation barrier

50
50

50

Ø7.4
50

Ø4.5
22 22 22
115
130

115
130

115
130
50
84

50
84

50
84
19
19

19
13.3 13.3 13.3

58
25 50 25
Trip test button Trip test button Trip test button 60
50 75 75
64
100
68
82
2P 3P 4P

Terminal details Connecting


8.2

12.5

M5×14
5

Ø9
5.
Ø

15
7.5

18 24 7 7

(≤ 50A) (≤ 50A) (≥60A)


8.2

M8×14
7.5

18 24

(≥60A)

Panel drilling Front panel cutting


M4 or Ø5 M4 orØ5 M4 orØ5
110.5

110.5

110.5

52

52

52

25 25 52 77 102

2P 3P 4P 2P 3P 4P

107
Dimensions

MCCB ABS125c ABH50c


ABH125c

(mm)
30 30 30

Insulation barrier Insulation barrier Insulation barrier

80
80

80

50
Fixing hole
50

Fixing hole
50
Fixing hole

5
50

8.2
22 22 22
16.5

16.5
16.5

155

155

155
135
100
135
100

135
100
50

50
50

37 37 37

4
8
8

30 60 30 58
10

10

10

Trip test button Trip test button Trip test button 8 60


60 90 90
120 82

2P 3P 4P

Terminal details Connecting


M8×14
8

9
Ø
16

18 24 8
10

Panel drilling Front panel cutting


M4 orØ5 M4 orØ5 M4 orØ5
132
132

52

52

52
132

30 30 62 92 122

2P 3P 4P 2P 3P 4P

108
MCCB ABN250c ABS250c ABH250c

(mm)

Insulation barrier
Insulation barrier

Fixing hole Fixing hole

Trip test button Trip test button

2,3P 4P

Terminal details Connecting

Panel drilling Front panel cutting


M4 orØ5 M4 orØ5

2,3P 4P 2,3P 4P

109
Dimensions

MCCB ABN400c ABS400c ABH400c ABL400c

(mm)

In
Fixing hole Fixing hole Fixing hole

Trip test button Trip test button Trip test button

2P 3P 4P

Terminal details Connecting

Panel drilling Front panel cutting

"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M6 orØ6 M6 orØ6

Slot "A"

Slot "B"

Slot "C"
142(3p) 142(3p)
187(4p) 187(4p)

2, 3P 4P 2, 3, 4P 3, 4P 3, 4P

110
MCCB ABN630c ABS630c ABL630c
ABN800c ABS800c ABL800c

(mm)

34.5
7
73.5

73.5
73.5

73.5

Trip test button Trip test button Trip test button

2P 3P 4P

630AF : 7
800AF : 10

Connecting
Terminal details

Panel drilling Front panel cutting

<Handle Only> <Handle & Test Button> <AUX.Cover>


A B C
Panel
Cover A

Panel
Cover B
Panel
Cover C
212(3P) 212(3P)
282(4P) 282(4P)

2, 3P 4P 2, 3, 4P 3, 4P 3, 4P

111
Dimensions

MCCB ABS1000b ABL1000b


ABS1200b ABL1200b

(mm)

Mounting hole Mounting hole

Mounting hole Mounting hole


Auxiliary handle

Auxiliary handle

3P 4P

or or

Panel drilling Front panel cutting


or or

3P 4P 3P 4P

112
MCCB
ABS1203bE

(mm)

Mounting hole

Mounting hole
Auxiliary handle

Auxiliary handle

or

Panel drilling Front panel cutting

or

113
Dimensions

ELCB EBN50c EBS30c


EBN60c EBS50c
EBN100c EBS60c

(mm)
56
25 Insulation barrier 25 25
Insulation barrier

50
50

Ø7.4
Trip indication Trip indication
by earth fault by earth fault 50

Ø4.5
Residual current Residual current
2.2

(I△n) setting (I△n) setting


115
130

84
50

130
115
84
50
29.2 29.2
19

Trip test button 19 Trip test button


13.3 for earth fault 13.3 for earth fault

Trip test button 25 Trip test button


58
50 75
75 100 60
64
2,3P 4P
66.5

68

82
Terminal details Connecting

(≤ 50A)
(≤ 50A) (≥60A)

(≥60A)

Panel drilling Front panel cutting

M4 orØ5 M4 orØ5

2, 3P 4P 2P 3P 4P

114
ELCB EBS125c EBH50c
EBH125c

(mm)
30 30

Insulation barrier Insulation barrier

80
80
50

50
Fixing hole Fixing hole

5
Trip indication Trip indication 50

8.2
22 22 by earth fault
by earth fault
37.8 37.8
Residual current Residual current
(I△n) setting
16.5

(I△n) setting

16.5
100

100
50

50
155

135

155
135
4.7

4.7
37
2.5
Trip test button
Trip test button for earth fault 4
for earth fault
8

Trip test button


Trip test button
60 58
30
10

10

8 60
90 90
82
120

3P 4P

Terminal details Connecting

Panel drilling Front panel cutting

M4 orØ5 M4 orØ5

3P 4P 3P 4P

115
Dimensions

ELCB EBN250c EBS250c EBH250c

(mm)

Insulation barrier Insulation barrier


80

80
Fixing hole Fixing hole

Trip indication Trip indication


by earth fault by earth fault
22 22
Residual current Residual current
(I△n) setting (I△n) setting
14.5 14.5
CL
59.4

59.4
165
144
126
102

165
144
126
102
50

50

7
7

19.6
19.6

Trip test button Trip test button


44.5 for earth fault 44.5 for earth fault

Trip test button Trip test button

70 105 35
105 140

2, 3P 4P

Terminal details Connecting

Panel drilling Front panel cutting


M4 orØ5 M4 orØ5

2, 3P 4P 2, 3P 4P

116
ELCB EBN400c EBS400c EBH400c EBL400c

(mm)

56.5 56.5 52.5 52.5 52.5


44 44
44 44 44
.5
12
Ø
41.5
26.5

Trip indication Trip indication


by earth fault by earth fault

57.9 57.9
48

48
46.9 46.9
16.5 23.9

23.9
257
225
215
150

257
225
215
150
41.4

41.4
48

48
Trip test button 16.5 Trip test button
for earth fault for earth fault
Residual current Residual current
(I△n) setting (I△n) setting

25 Trip test button Trip test button

51.1 184
140
3P 4P

Terminal details Connecting

Panel drilling Front panel cutting

"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)
M6 orØ6 M6 orØ6

Slot "A"

Slot "B"

Slot "C"
142(3p) 142(3p)
187(4p) 187(4p)

2, 3P 4P 2, 3, 4P 3, 4P 3, 4P

117
Dimensions

ELCB EBN630c EBS630c EBL630c


EBN800c EBS800c EBL800c

(mm)
210
70 34.5 34.5
44 7 10
15

73.5
37

Ø13.5

Ø13.5
8

Ø8

Ø8
56 Earthleakage trip indicator

Trip test button - earthleakage


90.6
77.6

280
243

280

280
150
96

17
25

23.9
16.5

Residual current selector


54.1 Trip test button - mechanical
73.5

70 70 95 95
109 109
113 113
145 145
3P

Terminal details Connecting 630AF : 7


800AF : 10

Panel drilling Front panel cutting

(Handle only) (Handle and Test Button) (AUX. Cover)


A B C

Panel
cover A

Panel
cover B

Panel
cover C

3P

118
ELCB EBS1000b
EBS1200b

(mm)

Mounting hole

Mounting hole

Auxiliary handle

Reset

Auxiliary handle

Trip test button

Residual current
Reset
(I△n) setting
Trip test button
for earth fault
Trip test button

Residual current
(I△n) setting
Trip test button
for earth fault
3P

Panel drilling Front panel cutting


60

60

3P 3P

119
Dimensions

Rear connection terminals

Bar type

C C

B
A

A
L L

D
Ø
E E E

MCCB A B C D E

ABN100c 115 37 87 Ø8.5 25


ABH125c 135 37 87 Ø8.5 30
ABH250c 144 57.5 93.5 Ø8.5 35

Round type

C
B
A

L
B
C

C
D
Ø

E E E E E E

MCCB A B C D E

ABN100c 50AF 115 42 92 M6 25


ABN100c 100AF 115 52 102 M8 25
ABH125c 135 52 102 M8 30
ABH250c 144 70 106 M8 35

120
Rotary handles

Direct mounting type (D-Handle, 30~250AF)


t1.2~3.2
t1.2~3.2 2-Ø6
4-Ø5

A

D
E
B
60
104 B A
C

Type A (mm) B (mm) C (mm) D (mm) E (mm) Remarks

DH100 110.5 78 90 92 103.4 100AF


DH125 132 94 105 108 120 125AF
DH250 126 108 121 110 122 250AF

Direct mounting type (N-Handle, 30~250AF)


N-30c, 40c, 50c
t1.2~3.2
t1.2~3.2
52.552.5 52.552.5 Panel
Panel
doordoor
105
105

105105

43 43

N-Handle N-30c N-40c N-50c

Note 100AF 125AF 250AF


A (mm) 103 103 103

Direct mounting type (N-Handle, 400~800AF)


N-70, N-80
150

t1.2~3.2
75
113

51

121
Dimensions

Rotary handles

Extended mounting type (E-Handle) (30~250AF)

t1.2~3.2
~3.2 2-Ø6
4-Ø5

B
D
E

B A
C

Type A (mm) B (mm) C (mm) Remarks

EH100 min 150, max 573.5 (SHAFT469mm) 47 Ø53 100AF


EH125 min 150, max 573.5 (SHAFT469mm) 47 Ø53 125AF
EH250 min 150, max 571.5 (SHAFT469mm) 47 Ø53 250AF

Extended mounting type (N-Handle, 400~800AF)

E-70U (400AF)

E-80U (800AF)
158.8
243

122
Technical Information

Standard accessories

The following accessories for mounting, connection and insulation are standard
items and are packed with Metasol series circuit breakers.

Item 100AF 125AF 250AF 400AF 800AF

Fixing
screw
2P: 2EA (M4×60) 2P: 2EA (M4×60) 2P: 2EA (M4×55) 2P: 4EA (M6×100) 2P: 4EA (M6×100)
3P: 2EA (M4×60) 3P: 2EA (M4×60) 3P: 2EA (M4×55) 3P: 4EA (M6×100) 3P: 4EA (M6×100)
4P: 4EA (M4×60) 4P: 4EA (M4×60) 4P: 4EA (M4×55) 4P: 4EA (M6×100) 4P: 4EA (M6×100)

3~50A
Terminal 2P: 4EA (M5×14)
bolt 3P: 6EA (M5×14)
2P: 4EA (M8×14) 2P: 4EA (M8×20) 2P: 4EA (M10×30) 2P: 4EA (M12×35)
4P: 8EA (M5×14)
3P: 6EA (M8×14) 3P: 6EA (M8×20) 3P: 6EA (M10×30) 3P: 6EA (M12×35)
60~100A
4P: 8EA (M8×14) 4P: 8EA (M8×20) 4P: 8EA (M10×30) 4P: 8EA (M12×35)
2P: 4EA (M8×14)
3P: 6EA (M8×14)
4P: 8EA (M8×14)

IB-23 IB-13 IB-23 IB-13 IB-23 IB-13

Insulation
barrier
2P: 1EA 2P: 1EA 2P: 1EA 2P: 1EA 2P: 1EA
3P: 2EA 3P: 2EA 3P: 2EA 3P: 2EA 3P: 2EA
4P: 3EA 4P: 3EA 4P: 3EA 4P: 3EA 4P: 3EA

Fixing screws for rotary handles


Handle type N-30c N-40c N-50c N-70 N-80

ABN 50c/60c/100c
ABS 125c ABN 250c ABN 400c ABN 800c
ABS 30c/50c/60c
ABH 50c ABS 250c ABS 400c ABS 800c
Applied MCCB
ABH 125c ABH 250c ABH 400c ABL 800c
ABL 400c
EBN 50c/60c/100c EBS 125c EBN 250c EBN 400c EBN 800c
EBS 30c/50c/60c EBH 50c EBS 250c EBS 400c EBS 800c
Applied ELCB
EBH 125c EBH 250c EBH 400c EBL 800c
EBL 400c
Fixing screw(short) - - - M6×16 M6×16
Fixing screw(long) M4×85 M4×85 M4×85 M6×110 M6×110

Handle type DH/EH100 DH/EH125 DH/EH250

Fixing screw M4×70 M4×70 M4×70

123
Technical Information

Connection

Terminal Tightening torque Conductor


MCCB
(mm) (kgf·cm) (mm)

[3~50A] M5 : 23 ~ 28 [3~50A]
M8 : 55 ~ 75
8.2

M5×14
8.2

M5×14 Ø 5.5
Ø 5.5
8.28.2

M5×14
Ø 5.5 Ø 5.5
M5×14
Ø 5.5
8.2

M5×14 Ø 5.5 ≤11.


8.2
7.5

18 M5×14 24 Ø 5.5 Ø 5.5 7 ≤11


7.5

18 24 Ø≤5.5 7 Ø 5.5
≤11.5 11.5
7.57.5

18 24 7 7
≤11.5 ≤11.5
18 24 7 7
8.2

M5×14 ≤11.5 ≤11.5


7.5

18 24 7 7Ø 5.5 ≤Ø11.5
5.5
7.5

18 24 7
100AF
8.2

M5×14 [60~100A] [60~100A] ≤11.5


7.5

18 24 Ø 5.5 Ø 5.5 7 7
8.2

M8×14 Ø9
8.2

M8×14 Ø9
≤11.5Ø9 ≤11.5
8.28.2

Ø9
7.5

18 M8×14 24 7 7
Ø9 Ø9
M8×14 Ø9 ≤16
8.2

M8×14 Ø9 7 ≤16
Ø9
8.2
7.5

18 M8×14 24 Ø≤916 7
7.5

18 24 ≤16
7 7 ≤16
7.57.5

18 24 ≤16
7 7 ≤16
18 24 ≤16 Ø9
8.2

M8×14 7 7Ø 9 ≤16
7.5

18 24 7
7.5

18 24

Ø9 ≤16
8.2

M8×14 Ø9 7 7
M8 : 55 ~ 75
7.5

18 24

≤16 ≤16
M8×14 7 7
M8×14
7.5

24
88

18
M8×14 Ø9
Ø9
8 8

M8×14
Ø9 Ø9
M8×14
M8×14 Ø9 Ø9
8

≤18
8

18 24 Ø9 Ø9 8 ≤ 18
1010

18 24 Ø9 8 Ø9
≤18 ≤18
18 24 8 8 ≤18
10 10

18 125AF 24
M8×14
8
≤18
8 ≤18
8

18 24 ≤18
8 8Ø9 Ø9
≤18
10

18 24 8
10

M8×14
8

18 24 Ø9 Ø9 ≤18
8 8
10

≤18 ≤18
18 24 8 8
10

M8×20 Ø9
M8×20 M8 : 80 ~ 130 Ø9
M8×20 Ø9 Ø9
M8×20 Ø9 Ø9
2121

M8×20 Ø9 Ø9 ≤25
M8×20 10 25
≤Ø9
Ø9 10
21 21

≤25 ≤ 25
10 10 ≤ 25
28 24 ≤25
28 24 10 10
21

≤25 ≤ 25
21

28 24 M8×20 10 10Ø9 Ø9
≤25
10
28 24
28 24
28 24
21

250AF M8×20 Ø9 Ø9 ≤25 10


10

28 24
21

≤25 ≤ 25
10 10

28 24

124
Connection

Terminal Tightening torque Conductor


MCCB
(mm) (kgf·cm) (mm)

M10 : 240~300 (Terminal)


M10 : 240~300 (Busbar)

30 37 .5
30 37 M10×30 .5 10
M10×30 10 Ø
Ø

29.5
400AF
13

29.5
13

29
29

12.5
12.5

M12 : 400~500
(Terminal, Busbar)

44 M12×35 34.5
44 M12×35 34.5 4
Ø1 4
Ø1
44
29

800AF
44
29
11
11

10.5
10.5

125
Technical Information

Safety clearance

When installing a circuit breaker, safety clearances must be kept between the breaker and panels, bars and
other protection devices installed nearby. These safety clearances are depend on the ultimate breaking capacity
and are defined by tests carried out in accordance with standard IEC 60947-2.
When a short circuit interruption occur, high temperatures pressures are present in and above the arc chambers
of the circuit-breaker. In order to allow the pressure to be distributed and to prevent fire and arcing or short-
circuit currents, safety clearances are required.

A: Minimum distance to metallic top panels


Frame A(mm)
Description
size 460V 250V

ABN50c 40 25
ABN60c 40 25
ABN100c 50 30
100AF
ABS30c 30 25
ABS50c 40 30
ABS60c 40 30
ABS125c 50 40
125AF ABH50c 50 40
ABH125c 100 80
ABN250c 100 80
250AF ABS250c 100 80
ABH250c 100 80
A

A
ABN400c 100 80
F

ABS400c 100 80
400AF
ABH400c 100 80
ABL400c 100 80
ABN800c 100 80
800AF ABS800c 100 80
ABL800c 100 80

126
B: Minimum distance between the lower and the upper breakers
•C1: Minimum distance between the lower breaker and the bare terminal of the upper breaker
•C: C1+ the dimension of bare part of conductor

Frame C1 (mm)
Description C (mm)
size 460V 250V

ABN50c 40 25
ABN60c 40 25
ABN100c 50 30
100AF ABS30c 30 25
ABS50c 40 30

The dimension of bare conduct + C1


ABS60c 40 30
ABS125c 50 40
125AF ABH50c 50 40
ABH125c 100 80
ABN250c 100 80
250AF ABS250c 100 80
ABH250c 100 80
ABN400c 100 80

C
C

C
C1

C1

C1

ABS400c 100 80 C1

C1

C1
400AF

C1

C1

C1
ABH400c 100 80
ABL400c 100 80
ABN800c 100 80
800AF ABS800c 100 80
ABL800c 100 80
Direct Connection Connection
connection by using a by using a
of cable crimp-type crimp-type
terminal lug terminal lug to
the extended
terminal

127
Technical Information

Safety clearance

Insulated length of main terminal of circuit breaker


•D1: Connection by solerless terminal with taping
•D2: Connection by busbar with taping
•D3: Connection by solderless terminal and using insulation barrier
•D4: Connection by busbar and using insulation barrier

Frame D1 D2 D3 D4
Description
size (mm) (mm) (mm) (mm)

ABN50c 40 40
ABN60c 40 40
ABN100c 50 50
100AF ABS30c 30 30
ABS50c 40 40
ABS60c 40 40
The dimension of bare conduct + 20

The dimension of bare conduct + 20

ABS125c 50 50
125AF ABH50c 50 50
ABH125c 50 50
ABN250c 50 50
250AF ABS250c 50 50
ABH250c 50 50

D4
D3
D1

D2

ABN400c 100 100


ABS400c 100 100
400AF
ABH400c 100 100
ABL400c 100 100
ABN800c 150 150
800AF ABS800c 150 150
ABL800c 150 150

128
Minimum distance to metallic side panels
Frame E(mm)
Description
size 460V 250V

ABN50c 25 15
ABN60c 25 15
ABN100c 25 15
100AF ABS30c 20 15
ABS50c 25 15
ABS60c 25 15
ABS125c 25 15
125AF ABH50c 25 15
E E
ABH125c 50 20
ABN250c 50 15
250AF ABS250c 50 15
ABH250c 50 15
ABN400c 80 40
ABS400c 80 40
400AF
ABH400c 80 40
ABL400c 80 40
ABN800c 80 40
800AF ABS800c 80 40
ABL800c 80 40

129
Technical Information

Safety clearance

Distance of bare cables or busbars


Frame
Description F(mm)
size

ABN50c 10
ABN60c 10
ABN100c -
100AF ABS30c 5
ABS50c 10
ABS60c 10
ABS125c -
125AF ABH50c 10
ABH125c 20
ABN250c -
250AF ABS250c -
ABH250c -
F

ABN400c 10
ABS400c 10
400AF
ABH400c 10
ABL400c 10
ABN800c 10
800AF ABS800c 10
ABL800c 10

130
Minimal distance between two adjacent breakers (With terminal covers)
Frame
Description G(mm)
size

ABN50c 0
ABN60c 0
ABN100c 0
100AF ABS30c 0
ABS50c 0
ABS60c 0
ABS125c 0
125AF ABH50c 0
ABH125c 0
ABN250c 0
G
250AF ABS250c 0
ABH250c 0
ABN400c 0
ABS400c 0
400AF
ABH400c 0
ABL400c 0
ABN800c 0
800AF ABS800c 0
ABL800c 0

131
Technical Information

Standards & Approval

Metasol series circuit breakers and auxiliaries comply with the following
international standard:
•IEC 60947-1
Low-voltage switchgear and controlgear - Part 1: General rules

•IEC 60947-2
Low-voltage switchgear and controlgear - Part 2: Circuit-breakers

The following certificates are available on a request.


•CE Declaration of conformity
•Certificate of conformance test (CB) - IEC 60947
•Full type test report issued by KEMA

CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the
manufacturer, as regards his products, by virtue of the European Community directives providing
for the affixing of the CE marking.
When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of
his authorized representative that the product in question conforms to all the applicable provisions
including the conformity assessment procedures.

132
Standard Use Environment

Standard Use Environment for Molded Case Circuit Breaker


The operation characteristic of Molded Case Circuit Breaker including short-circuit, overload, endurance and
insulation is often influenced largely by external environment and thus should be applied appropriately with
conditions of the place where it is used taken into consideration. In particular, the operation characteristic of the
circuit breaker with a thermal magnetic trip element (FTU, FMU, ATU) applied changes a bit with the ambient
temperature so you have to adjust the value of power rating accordingly when it is actually in use.

1) Ambient Temperature: Within the range of -5℃~+40℃ (However, the average for the duration of 24 hours
must not exceed 35℃.)
2) Relative Humidity: Within the range of 45~85%
3) Altitude: 2,000m or less (However, if it exceeds 1,000m, atmosphere correction through humidity test and
withstand voltage test can be considered.)
4) Atmosphere where excessive steam, oil steam, smoke, dust, salt and other corrosive materials do not exist

■ If a standard circuit breaker is used in high temperature


exceeding 40℃, you are advised to use it according to the
current corrected for each level of ambient temperature in
catalog.
■ If used in conditions of highly humidity, the dielectric strength or
electric performance may be degraded.

■ There is no problem in conduction switch, trip or short circuit


isolation in the temperature of -20℃. 
■ Passing or storage in stone-cold area is allowed in the
temperature of 40℃.
■ The operating characteristic of the breaker with a thermal
magnetic trip element changes as the base ambient
temperature is adjusted to 40℃.

■ It is highly recommended to use a dust cover or anti-humid


agent if it is used in dusty and humid conditions.
■ Excessive vibration may cause a trip break such as connection
fault or flaw on mechanical parts.

■ If it is left ON or OFF for a long time, it is recommended to


switch load current on a regular basis.
■ It is recommend to put it in the sealed protection if corrosive gas
is prevalent.

133
Technical Document

Special Use Environment

Environment where Ambient Temperature Exceeds 40℃


The temperate of each module of a Molded Case Circuit Breaker is the sum of temperature increase by
conduction and ambient temperature and if the ambient temperature exceeds 40℃ the passing current needs
to be reduced so that the temperature of such element as internal insulator of MCCB exceed the maximum
allowable temperature.
The base ambient temperature of Metasol breaker is set as 40℃ so if it has to be used in conditions with higher
temperature than this, the rated current is required to be reduced a little as described in the table below.

Table of Rated Current for Metasol MCCB Corrected


according to Ambient Temperature
Ampere Rated Rated Table of Rated Current Corrected according to Ambient Temperature (A)
Model Name of Breaker
Frame current current 10℃ 20℃ 30℃ 40℃ 45℃ 50℃ 55℃

3 3 3 3 3 3 3 3 3
5 5 5 5 5 5 5 5 4
10 10 10 10 10 10 10 9 9
30 ABS30c
15 15 15 15 15 15 15 14 13
20 20 20 20 20 20 19 19 18
30 30 30 30 30 30 29 28 27
40 40 40 40 40 40 39 38 36
50 ABN50c, ABS50c
50 50 50 50 50 50 49 47 45
60 60 ABN60c, ABS60c 60 60 60 60 60 58 56 55
75 75 75 75 75 75 73 71 68
100 ABN100c
100 100 100 100 100 100 97 94 91
125 125 ABH50c, ABS125c, ABH125c 125 125 125 125 125 121 116 107
150 150 150 150 150 150 145 140 128
175 175 175 175 175 175 169 163 150
ABN200c, ABS200c,
250 200 200 200 200 200 200 193 186 171
ABH250c
225 225 225 225 225 225 217 209 193
250 250 250 250 250 250 241 233 214
250 250 250 250 250 250 246 242 238
300 ABN400c, ABS400c 300 300 300 300 300 295 291 287
400
350 ABH400c, ABL400c 350 350 350 350 350 345 339 332
400 400 400 400 400 400 394 388 381
500 500 500 500 500 500 492 485 477
630 ABN800c, ABS800c 630 630 630 630 630 621 611 602
800
700 ABL800c 700 700 700 700 700 689 679 668
800 800 800 800 800 800 788 776 764

134
Special Use Environment

Table of Rated Current for Metasol ELCB Corrected


according to Ambient Temperature
Ampere Rated Rated Table of Rated Current Corrected according to Ambient Temperature (A)
Model Name of Breaker
Frame current current 10℃ 20℃ 30℃ 40℃ 45℃ 50℃ 55℃

15 15 15 15 15 15 15 15 15
30 20 EBS30c 20 20 20 20 20 19 19 18
30 30 30 30 30 30 29 28 27
40 40 40 40 40 40 39 38 36
50 EBN50c, EBS50c
50 50 50 50 50 50 49 47 45
60 60 EBN60c, EBS60c 60 60 60 60 60 58 56 55
75 75 75 75 75 75 73 71 68
100 EBN100c
100 100 100 100 100 100 97 94 91
125 125 EBH50c, EBS125c, EBH125c 125 125 125 125 125 121 116 107
150 150 150 150 150 150 145 140 128
175 175 175 175 175 175 169 163 150
EBN200c, EBS200c,
250 200 200 200 200 200 200 193 186 171
EBH250c
225 225 225 225 225 225 217 209 193
250 250 250 250 250 250 241 233 214
250 250 250 250 250 250 246 242 238
300 EBN400c, EBS400c 300 300 300 300 300 295 291 287
400
350 EBH400c, EBL400c 350 350 350 350 350 345 339 332
400 400 400 400 400 400 394 388 381
500 500 500 500 500 500 492 485 477
630 EBN800c, EBS800c 630 630 630 630 630 621 611 602
800
700 EBL800c 700 700 700 700 700 689 679 668
800 800 800 800 800 800 788 776 764

135
Technical Document

Special Use Environment

Environment where Ambient Temperature is -5℃ or less


Molded Case Circuit Breaker is subject to the effect of low temperature brittle of metal part inside and insulator,
or changes in viscosity of lubricating oil in device, extra care should be taken not to have the temperature drop
extremely with the use of such device as space heater. In addition, in case of using a thermal magnetic trip
element (FTU, FMU, ATU), the operating characteristic changes toward the difficult direction, so you should
identify the relationship of protection and correct accordingly.
Although MCCB is not affected by conduction switch, trip, or short circuit isolation in the temperature of - 20℃, it
is highly recommended to use a temperature maintaining device such as space heater. In addition,
transportation and passing in stone-cold area in the temperature as low as -40℃ is allowed but it is recommend
to leave the status of MCCB off or tripped in order to minimize the effect of brittle due to a low temperature.

High Humidity Condition (Relative Humidity 85% or more)


Using Molded Case Circuit Breaker in a place of high humidity requires a rigorous maintenance including
installation of anti-humidity agent within the structure in order to prevent the insulation sag of insulator or
corrosion of mechanical parts as a result of high humidity. Also, in case of installing MCCB within the enclosed
equipment, a space heater needs to be installed as well to prevent dew condensation that might occur due to a
drastic temperature change.

Environment where Petrochemical Gas Exists


The contact material of Molded Case Circuit Breaker is silver or silver alloy which develops creation of
petrochemical coat that might cause a poor connection if it gets in contact with petrochemical gas.
However, it is easy for petrochemical coat to be mechanically taken off so it is no problem if make-and break
operation occurs frequently but it needs to be switched back and forth between make and break if the operation
rarely occurs.
The lead wire of moving contact of Molded Case Circuit Breaker can be disconnected as it is corroded or
hardened by petrochemical gas. The silver coating is effective to prevent this from occurring and there is a need
to increase durability of MCCB with the use of silver coated lead wire if it is used in environment with thick
petrochemical gas.

Environment where Potentially Explosive Gas Exists


It is advised, in principle, not to install a Molded Case Circuit Breaker that switches and inhibits current in a
dangerous place such as this one.

Impact of Altitude
If an MCCB is used in an elevated area higher than 2000m sea level, its operating performance is subject to
dramatic drop in atmospheric pressure and temperature. For example, the air pressure is reduced to 80% of
ordinary pressure at 2,200m and further 50% at 5,500m although the short-circuit performance is not affected. If
it is used in areas of high sea level, you can do correction based on the correction parameter table in high
altitude environment, as described below.
[Correction Parameter Table for Altitude]
* Refer to the correction parameter table in high altitude Voltage Current
environment (ANSI C37. 29-1970) Altitude Correction Correction
1) How to Correct Voltage: Parameter Parameter
- If the rated voltage is AC 600V at 4,000m above sea level, 2,000m 1.00 1.00
600V (rated voltage) × 0.82 (correction parameter) = 492V. 3,000m 0.91 0.98
2) How to Correct Current: 4,000m 0.82 0.96
- If the rated voltage is AC 800A at above 4,000m sea level, 5,000m 0.73 0.94
800A (rated current) × 0.96(correction parameter) = 768A.
6,000m 0.65 0.92

136
Environment with Vibration and Impulse Exercised

Impact of Vibration and Impulse


An excessive vibration and impulse may cause damage on breaker or other security problems including
dynamic strength. An appropriate consideration is required to select a right MCCB for an adverse environmental
stress such as this one. Moreover, this stress may incur from vibration during transportation, magnetic impulse
while manipulating a switch or may be affected by equipment in surrounding area.
There is a standard call [Vibration Testing Method for Small Electric Appliances] for vibration and impulse test
for electric equipment and the seismic and endurance tests of Molded Case Circuit Breaker are conducted in
accordance with this standard, considering the circumstance mentioned above.

Vibration
The magnitude of vibration is measured by double amplitude and frequency with the following equation with
accelerator.
αg=0.002×frequency(Hz)×double amplitude (mm)
* αg: multiple of gravitational acceleration (g=9.8m/sec2)
There are three types of vibration tests including resonance test, vibration endurance test, and malfunction test
as described below.
1) Resonant Test
Alter the frequency of sinusoidal wave within the range of 0~55Hz gradually with 0.5~1mm of double
amplitude applied to see if there is any occurrence of vibration on a specific part of MCCB.
2) Vibration Endurance Test
A sinusoidal wave with double amplitude of 0.5~1mm and frequency of 55Hz(resonant frequency obtained in
previous clause if there is a resonant point) is manually created to check the operational status.
3) Malfunction Test
Apply vibration for 10 minutes for each condition of altering double amplitude and frequency to check if there
is any malfunction in MCCB.

Impulse
The magnitude of impulse is denoted by the multiple of gravitational acceleration imposed on the equipment
and part. The test is conducted through a drop impulse test.

Impact of High Frequency


In case of high frequency current, you are required to reduce the rated current of the breaker with a thermal
magnetic trip element embedded due to heat incurred by the skin effect of conductor and/or core less of
structure. The reduction rate varies according to the Frame Size and rated current and decreases down to
70~80% at 400Hz. In addition, the core loss decreases attractive force, which leads to increase of
instantaneous trip current.
* Core loss: It refers to the electrical loss in a transformer caused by magnetization of the core that changes
over time and is categorized into hysteresis loss and eddy current loss.
* Hysteresis loss: It takes up the majority portion of no-load loss of electric equipment and is calculated like this.
Ph = σfBmn
Bm: maximum value of magnetic flux density, n: constant(1.6~2.0), f: frequency, σ: hysteresis constant
* Eddy current: It refers to an induced electric current formed within the body of a conductor when it moves
through a non-uniform or changing magnetic field. The eddy current that incurs at winding of
transformer or core is considered as one of the transformer losses as a part of exciting current. It
is also called ‘eddy current loss’.

137
Technical Document

Use Environment with Vibration and Impulse Applied

[Table of Seismic Performance and Internal Impulse Performance]

Test Internal Impulse

Test Mounting ● Vertical mounting ● Picture 1, 2, 3, 4

Condition Vibration, ● Top-down, Left-right, Front-back (→ represents the direction of drop)


Direction
Picture 1 Picture
Picture 1 2 Picture 2
of impulse Left-right, Left-right,
Front-back Front-back

Top-down Top-down ON ON

ON ON

Line Connection
Line Connection Picture 3 Picture34
Picture Picture 4

Status of (1) Non-conduction (ON or OFF status) Non-conduction (ON or OFF status)
MCCB (2) Status where rated current is conducted
until the temperature of MCCB becomes
constant and keeps being conducted
Test Judgment ● If it is ON, it should not be OFF

Result Condition ● If it is OFF, it should not be ON

●N
 o abnormal status such as damage,

transformation, or annealing of nut part


●C
 haracteristics of switch and trip after the test

must be normal

138
Cerfications

MCCB ELCB
Type Approvals Certificates Type Approvals Certificates Type Approvals Certificates
Cerficate Safet certi IEC KEMA Cerficate Safet certi IEC KEMA Cerficate Safet certi IEC KEMA

Mark Mark Mark


and and and
name CE KEMA name CE KEMA name CE KEMA
Type Korea Europe Netherlands Type Korea Europe Netherlands Type Korea Europe Netherlands
ABS32c ● ● ● ABP104c ● ● ● EBS33c ● ● ●
ABS33c ● ● ● ABH102c ● ● ● EBS34c ● ● ●
ABS34c ● ● ● ABH103c ● ● ● EBN52c ● ● ●
ABN52c ● ● ● ABH104c ● ● ●
EBN53c ● ● ●
ABN53c ● ● ● ABN202c ● ● ●
EBS53c ● ● ●
ABN54c ● ● ● ABN203c ● ● ●
MCCB 30~250AF

EBS54c ● ● ●
ABS52c ● ● ● ABN204c ● ● ●
ABS53c ABS202c EBN63c ● ● ●
● ● ● ● ● ●
ABS54c ● ● ● ABS203c ● ● ● EBS63c ● ● ●
ABN62c ● ● ● ABS204c ● ● ● EBS64c ● ● ●
ABN63c ● ● ● ABP202c ● ● ● EBN102c ● ● ●
ABN64c ● ● ● ABP203c ● ● ● EBN103c ● ● ●
ABS62c ● ● ● ABP204c ● ● ● EBN104c ● ● ●
ABS63c ● ● ● ABH202c ● ● ●
EBS33d ● ● ●
ABS64c ● ● ● ABH203c ● ● ●
EBS34d ● ● ●
ABN102c ● ● ● ABH204c ● ● ●
EBN52d ● ● ●
ABN103c ● ● ● ABN402c ● ● ●
ABN104c ● ● ● ABN403c ● ● ● EBN53d ● ● ●
ABS32d ● ● ● ABN404c ● ● ● EBS53d ● ● ●
ELCB 30~250AF

ABS33d ● ● ● ABS402c ● ● ● EBS54d ● ● ●


ABS34d ● ● ● ABS403c ● ● ● EBN63d ● ● ●
ABN52d ABS404c
MCCB 30~250AF

● ● ● ● ● ● EBS63d ● ● ●
ABN53d ● ● ● ABH402c ● ● ●
EBS64d ● ● ●
ABN54d ● ● ● ABH403c ● ● ●
EBN102d ● ● ●
ABS52d ● ● ● ABH404c ● ● ●
EBN103d ● ● ●
ABS53d ● ● ● ABL402c ● ● ●
ABS54d ABL403c EBN104d ● ● ●
● ● ● ● ● ●
ABN62d ● ● ● ABL404c ● ● ● EBP53c ● ● ●
ABN63d ● ● ● ABN602c ● ● EBP54c ● ● ●
MCCB 400~800AF

ABN64d ● ● ● ABN603c ● ● EBH53c ● ● ●


ABS62d ● ● ● ABN604c ● ● EBH54c ● ● ●
ABS63d ● ● ● ABS602c ● ● EBS103c ● ● ●
ABS64d ● ● ● ABS603c ● ●
EBS104c ● ● ●
ABN102d ● ● ● ABS604c ● ●
EBP103c ● ● ●
ABN103d ● ● ● ABL602c ● ●
EBP104c ● ● ●
ABN104d ● ● ● ABL603c ● ●
ABP52c ● ● ● ABL604c ● ● EBH103c ● ● ●
ABP53c ● ● ● ABN802c ● ● EBH104c ● ● ●
ABP54c ● ● ● ABN803c ● ● EBN202c ● ● ●
ABH52c ● ● ● ABN804c ● ● EBN203c ● ● ●
ABH53c ● ● ● ABS802c ● ● EBS203c ● ● ●
ABH54c ● ● ● ABS803c ● ●
EBS204c ● ● ●
ABS102c ● ● ● ABS804c ● ●
EBP203c ● ● ●
ABS103c ● ● ● ABL802c ● ●
EBP204c ● ● ●
ABS104c ● ● ● ABL803c ● ●
ABP102c ● ● ● ABL804c ● ● EBH203c ● ● ●

ABP103c ● ● ● EBH204c e ● ● ●

Note: ●(Completion)

139
LSMS

<Android>

<IOS>
This application is selection
guide of motor starter,
overload relays and MCCBs

•For your safety, please read user's manual thoroughly before operating.
•Contact the nearest authorized service facility for examination, repair, or adjustment.
•Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions •Any maintenance and inspection shall be performed by the personnel having expertise concerned.

ⓒ 2009.10 LSIS Co.,Ltd. All rights reserved. www.lsis.com

■ HEAD OFFICE ■ GLOBAL NETWORK


LS-ro 127 (Hogye-dong) Dongan-gu, Anyang-si,
Gyeonggi-Do Korea Overseas Subsidiaries
Tel. 82-2-2034-4902, 4684, 4429 •LSIS USA Inc. ≫ Chicago, America
2000 Millbrook Drive, Lincolnshire, Chicago, IL 60069, United States of America
Fax. 82-2-2034-4555 Tel: 1-847-941-8240 Fax: 1-847-941-8259 E-mail: [email protected]
•LSIS (Middle East) FZE ≫ Dubai, U.A.E.
LOB 19-205, JAFZA View Tower, Jebel Ali Free Zone, Dubai, United Arab Emirates
Tel: 971-4-886-5360 Fax: 971-4-886-5361 E-mail: [email protected]
•LSIS Europe B.V. ≫ Schiphol-Rijk, Netherlands
1st Floor, Tupoleviaan 48, 1119NZ, Schiphol-Rijk, The Netherlands
Tel: 31-20-654-1420 Fax: 31-20-654-1429 E-mail: [email protected]
•LSIS Japan Co., Ltd. ≫ Tokyo, Japan
Tokyo Club Building 13F, 2-6, Kasumigaseki 3-chome, Chiyoda-ku, Tokyo, 100-0013
Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-mail: [email protected]
•LSIS(Dalian) Co., Ltd. ≫ Dalian, China
No. 15, Liaohexi 3-Road, Economic and Technical Development Zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 E-mail: [email protected]
• LS IS(Wuxi) Co., Ltd. ≫ WUxi, China
102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 E-mail: [email protected]
•LS-Vina Co., Ltd. ≫ Hanoi, Vietnam
Nguyen Khe, Dong Anh, Hanoi, Vietnam
Tel: 84-4-6275-8055 Fax: 84-4-3882-0220 E-mail: [email protected]

Overseas Branches
•LSIS Co., Ltd. Rep. Office, Vietnam
Gema Dept Tower 18F, 6 Le Thanh Ton, District 1, HCM, Vietnam
Tel: 84-8-3823-7890 E-mail: [email protected]
•LSIS Moscow Office, Russia
Specifications in this catalog are subject to change without notice due to 123610, Krasnopresnenskaya, nab, 12, building1, office No.1005, Moscow, Russia
continuous product development and improvement. Tel: 7-495-258-1466, 1467 Fax: 7-495-258-1466, 1467 E-mail: [email protected]

2016. 05 Low voltage circuit breakers (E) 2009. 10/(18) 2016. 05 Printed in Korea STAFF