Dixell xw260l

This document provides instructions for installing and operating a Dixell XW260L temperature controller. It has 4 relay outputs to control the compressor, defrost, evaporator fans, and lights. It uses NTC probe inputs for temperature control and defrost end detection. The LEDs indicate operating modes of the compressor, fan, defrost, and alarms. Buttons are used to display/modify setpoints, enable defrost or fast freezing, and turn lights and the controller on/off.

Uploaded by

Miftakhul Khoir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
481 views4 pages

Dixell xw260l

This document provides instructions for installing and operating a Dixell XW260L temperature controller. It has 4 relay outputs to control the compressor, defrost, evaporator fans, and lights. It uses NTC probe inputs for temperature control and defrost end detection. The LEDs indicate operating modes of the compressor, fan, defrost, and alarms. Buttons are used to display/modify setpoints, enable defrost or fast freezing, and turn lights and the controller on/off.

Uploaded by

Miftakhul Khoir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

dIXEL Installing and Operating Instructions rel.1.0 - cod.

1592009027
To display and modify target set point; in programming mode it selects a parameter or confirm an
operation.

WING
By holding it pressed for 3s when max or min temperature is displayed it will be erased.

To see the max. stored temperature; in programming mode it browses the parameter codes or
increases the displayed value. By holding it pressed for 3s the fast freezing cycle is started.

To see the min stored temperature; in programming mode it browses the parameter codes or
XW260L decreases the displayed value.

1. GENERAL WARNING By holding it pressed for 3s the defrost is started.

Switch ON and OFF the cold room light.


1.1 PLEASE READ BEFORE USING THIS MANUAL
• This manual is part of the product and should be kept near the instrument for easy and quick reference.
• The instrument shall not be used for purposes different from those described hereunder. It cannot be used Switch ON and OFF the instrument.
as a safety device.
• Check the application limits before proceeding.
KEY COMBINATIONS

1.2

SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
+ To lock and unlock the keyboard.


+
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
To enter the programming mode.
temperature changes with high atmospheric humidity to prevent formation of condensation
• Warning: disconnect all electrical connections before any kind of maintenance.


Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A..” (see
address) with a detailed description of the fault.
+ To exit the programming mode.

• Consider the maximum current which can be applied to each relay (see Technical Data).
• Ensure that the wires for probes, loads and the power supply are separated and far enough from each 4.1 USE OF LEDS
other, without crossing or intertwining.
• In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with Each LED function is described in the following table.
inductive loads could be useful. LED MODE Function
ON The compressor is running
2. GENERAL DESCRIPTION
Model XW260L, 38x185 mm format, is microprocessor based controller suitable for applications on medium or FLASHING - Programming Phase (flashing with LED )
low temperature refrigerating units. It is provided with four relay outputs to control compressor, defrost - which - Anti-short cycle delay enabled
can be either electrical or hot gas - the evaporator fans and the lights.
ON The fan is running
It is also provided with three NTC probe inputs, one for temperature control, one to control the defrost end
temperature of the evaporator and the third, optional, for the display. There are two digital inputs (free contact) FLASHING
Programming Phase (flashing with LED )
for the door switch and configurable by parameter.
The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a ModBUS- ON The defrost is enabled
RTU compatible monitoring system and to programme the parameter list with the “Hot Key”.
FLASHING Drip time in progress
An optional output for remote display “XW-REP” is available.
ON The Fast Freezing cycle is enabled
3. CONTROLLING LOADS
ON - ALARM signal
3.1 THE COMPRESSOR - In “Pr2” indicates that the parameter is also present in “Pr1”
The regulation is performed according to the temperature measured by the thermostat probe with a positive
Function of the LEDs placed on the left top side of buttons:
differential from the set point: if the temperature increases and reaches set point plus differential the compressor
is started and then turned off when the temperature reaches the set point value again.
BUTTON MODE FUNCTION
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters
“COn” and “COF”. SET FLASHING The Set point is displayed and it can be modified
SET FAST FLASHING The Energy Saving is enabled
3.2 FAST FREEZING DEFROST ON The Manual Defrost is activated
LIGHT ON The Light is ON
When defrost is not in progress, it can be activated the keypad by holding the o key pressed for about 3 ON/OFF ON The instrument is OFF
seconds. The compressor operates in continuous mode for the time set through the “CCt” parameter. The cycle
can be terminated before the end of the set time using the same activation key, o for about 3 seconds.
4.2 HOW TO SEE THE MIN TEMPERATURE
3.3 DEFROST 1. Press and release the n key.
Three defrost modes are available through the “tdF” parameter: defrost with electrical heater, hot gas or 2. The “Lo” message will be displayed followed by the minimum temperature recorded.
thermostatic defrost. The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made 3. By pressing the n key or waiting for 5s the normal display will be restored.
every “IdF” time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the
compressor is ON and the evaporator temperature is bigger than “SdF” parameter). 4.3 HOW TO SEE THE MAX TEMPERATURE
At the end of defrost the drip time is controlled through the “Fdt” parameter.
1. Press and release the o key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3.4 CONTROL OF EVAPORATOR FANS 3. By pressing the o key or waiting for 5s the normal display will be restored.
The fan control mode is selected by means of the “FnC” parameter:
FnC=C-n fans will switch ON and OFF with the compressor and not run during defrost:; 4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
FnC=C-y fans will run continuously, but not during defrost To reset the stored temperature, when max or min temperature is displayed :
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. 1. Press SET key until “rST” label starts blinking.
FnC=O-n fans will switch ON and OFF with the compressor and run during defrost;
FnC=O-y fans will run continuously also during defrost N.B. After the installation RESET the temperature stored .

An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe, above 4.5 HOW TO SEE AND MODIFY THE SET POINT
which the fans are always OFF. This can be used to make sure circulation of air only if his temperature is lower 1. Push and immediately release the SET key: the display will show the Set point value;
than set in “FSt”. 2. The SET LED start blinking;
3. To change the Set value push the o or n arrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
4. KEYBOARD
4.6 TO START A MANUAL DEFROST

F
C 1. Push the DEF key for more than 2 seconds and a manual defrost will start.

4.7 TO ENTER IN PARAMETERS LIST “PR1”


To enter the parameter list “Pr1” (user accessible parameters) operate as follows:

1. Enter the Programming mode by pressing the Set and DOWN key for few
seconds ( and start blinking).

1592009027 XW260L GB r1.0 15.12.2004.doc XW260L 1/4


dIXEL Installing and Operating Instructions rel.1.0 - cod. 1592009027
2. The instrument will show the first parameter present in “Pr1” rE = electrical heater (Compressor OFF)
rT = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending on the
evaporator temperature and “dtE” value.
in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode:
4.8 TO ENTER IN PARAMETERS LIST “PR2” in = interval mode. The defrost starts when the time “Idf” is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the compressor
To access parameters in “Pr2”:
is running (even non consecutively) and only if the evaporator temperature is less than the value in "SdF”
1. Enter the “Pr1” level.
(set point for SMARTFROST).
2. Select “Pr2” parameter and press the “SET” key.
SdF Set point for SMARTFROST: (-30÷30 °C/ -22÷86 °F) evaporator temperature which allows the IdF
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero.
counting (interval between defrosts) in SMARTFROST mode.
4. Use o or n to input the security code in the flashing digit; confirm the figure by pressing “SET”. The dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator
security code is “321“. probe is present) sets the temperature measured by the evaporator probe which causes the end of
5. If the security code is correct the access to “Pr2” is enabled by pressing “SET” on the last digit. defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys cycles.
within 30 seconds. MdF (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost
duration, when P2P = y, defrost end based on temperature, it sets the maximum length for defrost.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” + n. When a dFd Display during defrost:
parameter is present in “Pr1” LED is on. rt = real temperature;
it = temperature reading at the defrost start;
Set = set point;
4.9 HOW TO CHANGE THE PARAMETER VALUE dEF = “dEF” label;
1. Enter the Programming mode. dEG = “dEG” label;
2. Select the required parameter with o or n. dAd Defrost display time out: (0÷255 min) Sets the maximum time between the end of defrost and the
restarting of the real room temperature display.
3. Press the “SET” key to display its value ( and LED starts blinking). Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and the
4. Use o or n to change its value. restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops that
5. Press “SET” to store the new value and move to the following parameter. might have formed due to defrost.
To exit: Press SET + UP or wait 15s without pressing a key. dPO First defrost after start-up:
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out. y = Immediately;
n = after the IdF time
4.10 HOW TO LOCK THE KEYBOARD dAF Defrost delay after fast freezing: (0min÷23h 50min) after a Fast Freezing cycle, the first defrost will be
1. Keep the o and n keys pressed together for more than 3 s the o and n keys. delayed for this time.
2. The “POF” message will be displayed and the keyboard is locked. At this point it is only
possible the viewing of the set point or the MAX o Min temperature stored and to switch FANS
ON and OFF the light, the auxiliary output and the instrument. FnC Fan operating mode:
C-n = running with the compressor, OFF during the defrost;
TO UNLOCK THE KEYBOARD C-y = running with the compressor, ON during the defrost;
O-n = continuous mode, OFF during the defrost;
Keep the o and n keys pressed together for more than 3s. O-y = continuous mode, ON during the defrost;
Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator fans start.
FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe,
4.11 ON/OFF FUNCTION above which the fan is always OFF.
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is
switched ON. ALARMS
During the OFF status, all the relays are switched OFF and the regulations are stopped; if a ALC Temperature alarm configuration
monitoring system is connected, it does not record the instrument data and alarms. rE = High and Low alarms related to Set Point
N.B. During the OFF status the Light button is active. Ab = High and low alarms related to the absolute temperature.
ALU High temperature alarm setting:
4.12 TO SEE THE PROBE VALUES ALC= rE, 0 ÷ 50°C or 90°F
1. Enter in “Pr2” level. ALC= Ab, ALL ÷ 110°C or 230°F
when this temperature is reached and after the ALd delay time the HA alarm is enabled.
2. Select “Prd” parameter with o or n.
ALL Low temperature alarm setting:
3. Press the “SET” key to display “Pb1” label alternate with Pb1 value. ALC = rE , 0 ÷ 50 °C or 90°F
4. Use o and n keys to display the other probe values. ALC = Ab , - 50°C or -58°F ÷ ALU
5. Press “SET” to move to the following parameter. when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.
AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature
alarm set point and fan regulation set point, always positive.
5. PARAMETER LIST ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the
corresponding alarm signalling.
REGULATION
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of the
Hy Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor temperature alarm condition after the instrument power on and the alarm signalling.
Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set EdA Alarm delay at the end of defrost: (0÷255 min) Time interval between the detection of the temperature
point. alarm condition at the end of defrost and the alarm signalling.
LS Minimum set point limit: (-50,0°C÷SET; -58°F÷SET) Sets the minimum acceptable value for the set dot Delay of temperature alarm after closing the door : (0÷255 min) Time delay to signal the temperature
point. alarm condition after closing the door.
US Maximum set point limit: (SET÷110°C; SET÷230°F) Set the maximum acceptable value for set point. doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the alarm signalling: the flashing message “dA” is displayed.
instrument and inhibits any output activation for the period of time set in the parameter. (Light can work) nPS Pressure switch number: (0 ÷15) Number of activation of the pressure switch, during the “did” interval,
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart. before signalling the alarm event (I2F= PAL).
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used,
for instance, when the room is filled with new products. PROBE INPUTS
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the
of faulty thermostat probe. With COn=0 compressor is always OFF. thermostat probe.
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in case of OE Evaporator probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the
faulty thermostat probe. With COF=0 compressor is always active. evaporator probe.
O3 Auxiliary probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the evaporator
DISPLAY probe.
P2P Evaporator probe presence:
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is
n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and time.
changed the SET point and the values of some parameters have to be modified.
P3P Auxiliary probe presence: n= not present; y= present.
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display.
HES Temperature increase during the Energy Saving cycle : (-30,0°C ÷ 30,0°C / -22÷86°F) sets the
de = 0,1°C
increasing value of the set point during the Energy Saving cycle.
in = 1 °C
Lod Local display : select which probe is displayed by the instrument: DIGITAL INPUTS
P1 = Thermostat probe odc Compressor and fan status when open door:
P2 = Evaporator probe no = normal;
P3 = auxiliary probe Fan = Fan OFF;
1r2 = difference between P1 and P2 (P1-P2) CPr = Compressor OFF;
Red Remote display : select which probe is displayed by the remote display (XW-REP) F_C = Compressor and fan OFF.
P1 = Thermostat probe I1P Door switch input polarity:
P2 = Evaporator probe CL : the digital input is activated by closing the contact;
P3 = auxiliary probe OP : the digital input is activated by opening the contact.
1r2 = difference between P1 and P2 (P1-P2) I2P Configurable digital input polarity:
CL : the digital input is activated by closing the contact;
DEFROST OP : the digital input is activated by opening the contact
tdF Defrost type: I2F Digital input operating mode: configure the digital input function:

1592009027 XW260L GB r1.0 15.12.2004.doc XW260L 2/4


dIXEL Installing and Operating Instructions rel.1.0 - cod. 1592009027
EAL = generic alarm;
bAL = serious alarm mode;
PAL = Pressure switch;
dFr = Start defrost; AUS = Not used;
Es = Energy Saving;
onF = remote On/OFF.
did Time interval/delay for digital input alarm:(0÷255 min.) Time interval to calculate the number of the
pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines 1
the time delay between the detection and the successive signalling of the alarm.
2
SAA Set Point for anti-condensing heater: (-50,0÷110,0°C; -58÷230°F) defines the room temperature
setpoint to switch on the anti-condensing heater.
4
OTHER 3
Adr RS485 serial address (1÷247): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
Rel Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map.
Prd Probes display: (read only) display the temperature values of the evaporator probe Pb2 and the auxiliary
probe Pb3.
Pr2 Access to the protected parameter list (read only).
1
6. DIGITAL INPUTS
The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the
3 2
second is programmable in seven different configurations by the “I2F” parameter.
RG-LX gascke
(optional)
6.1 DOOR SWITCH INPUT 4
It signals the door status and the corresponding relay output status through the “odc” parameter:
no = normal (any change);
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF. 8. ELECTRICAL CONNECTIONS
Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is enabled and the The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm2 for
display shows the message “dA”. The alarm stops as soon as the external digital input is disabled again. During the digital and analogue inputs. Relays and power supply have a Faston connection (6,3mm). Heat-resistant
this time and then for the delay “dot” after closing the door, the high and low temperature alarms are disabled. cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the power
connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable
6.2 CONFIGURABLE INPUT - GENERIC ALARM (EAL) external relay.
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm N.B. Maximum current allowed for all the loads is 20A.
message. The outputs status don’t change. The alarm stops just after the digital input is de-activated.

8.1 PROBE CONNECTIONS


6.3 CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is
When the digital input is activated, the unit will wait for “did” delay before signalling the “BAL” alarm message. recommended to place the thermostat probe away from air streams to correctly measure the average room
The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated. temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice
is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.

6.4 CONFIGURABLE INPUT - PRESSURE SWITCH (PAL)


If during the interval time set by “did” parameter, the pressure switch has reached the number of activation of 9. TTL SERIAL LINE
the “nPS” parameter, the “PAL” pressure alarm message will be displayed. The compressor and the regulation The TTL connector allows, by means of the external module TTL/RS485, to connect the unit to a network line
are stopped. When the digital input is ON the compressor is always OFF. ModBUS-RTU compatible as the dIXEL monitoring system XJ500 (Version 3.0).
The same TTL connector is used to upload and download the parameter list of the “HOT KEY“.

6.5 CONFIGURABLE INPUT - START DEFROST (DFR)


It executes a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 10. USE OF THE PROGRAMMING “HOT KEY “
restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is expired. The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the “Hot
Key” and vice-versa.

6.6 CONFIGURABLE INPUT - ENERGY SAVING (ES)


The Energy Saving function allows to change the set point value as the result of the SET+ HES (parmeter) sum. 10.1 DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)
This function is enabled until the digital input is activated. 1. Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert
the “Hot Key” and then turn the Wing ON.
6.7 CONFIGURABLE INPUT - REMOTE ON/OFF (ONF) 2. Automatically the parameter list of the “Hot Key” is downloaded into the Wing memory, the “DoL”
This function allows to switch ON and OFF the instrument. message is blinking. After 10 seconds the instrument will restart working with the new parameters.
3. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages:
6.8 DIGITAL INPUTS POLARITY “end “ for right programming. The instrument starts regularly with the new programming.
“err” for failed programming. In this case turn the unit off and then on if you want to restart the download again
The digital inputs polarity depends on “I1P” and “I2P” parameters.
or remove the “Hot key” to abort the operation.
CL : the digital input is activated by closing the contact.
OP : the digital input is activated by opening the contact

7. INSTALLATION AND MOUNTING 10.2 UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
Instruments XW260L shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws ∅ 3 1. Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then
x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-LX). The temperature turn it ON again.
range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations, corrosive gases, 2. When the Wing unit is ON, insert the “Hot key” and push o key; the "uPL" message appears.
excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate by the cooling 3. Push “SET” key to start the UPLOAD; the “uPL” message is blinking.
holes. 4. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages:
7.1 CUT OUT “end “ for right programming.
“err” for failed programming. In this case push “SET” key if you want to restart the programming again or
remove the not programmed “Hot key”.

165
+1
-1
11. ALARM SIGNALS
150
+0.5
-0 Message Cause Outputs
“P1” Thermostat probe failure Alarm output ON; Compressor output according to
parameters “COn” and “COF”
+0.5

“P2” Evaporator probe failure Alarm output ON; Other outputs unchanged
-0
31

“P3” Auxiliary probe failure Alarm output ON; Other outputs unchanged
“HA” Maximum temperature alarm Alarm output ON; Other outputs unchanged
“LA” Minimum temperature alarm Alarm output ON; Other outputs unchanged
Ø3 x2 “EE” Data or memory failure Alarm output ON; Other outputs unchanged
“dA” Defrost timeout alarm Alarm output ON; Other outputs unchanged
7.2 XW260L MOUNTING “dAL” Door switch alarm Alarm output ON; Other outputs unchanged
“EAL” External alarm Alarm output ON; Other outputs unchanged
“BAL” Serious external alarm Alarm output ON; Other outputs OFF

1592009027 XW260L GB r1.0 15.12.2004.doc XW260L 3/4


dIXEL Installing and Operating Instructions rel.1.0 - cod. 1592009027
Message Cause Outputs
“PAL” Pressure switch alarm Alarm output ON; Other outputs OFF 14. DEFAULT SETTING VALUES
The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. Label Name Range Default Level
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is displayed for REGULATION °C/°F XW260L
about 3s. Set Set point LS÷US -5 Pr1
Hy Differential 0,1÷25,5 °C / 1÷45°F 2 Pr1
11.1 SILENCING BUZZER LS Minimum set point -50,0°C÷SET / -58°F÷SET -30 Pr2
Once the alarm signal is detected the buzzer can be silenced by pressing any key. US Maximum set point SET ÷ 110°C / SET ÷ 230°F 20 Pr2
OdS Outputs activation delay at start up 0÷255 min. 1 Pr2
11.2 “EE” ALARM AC Anti-short cycle delay 0÷30 min. 1 Pr1
The dIXEL instruments are provided with an internal check for the data integrity. Alarm “EE” flashes when a CCt Compressor ON time during fast freezing 0 ÷ 23h 50 min. 0 Pr2
failure in the memory data occurs. In such cases the alarm output is enabled. COn Compressor ON time with faulty probe 0÷255 min. 15 Pr2
COF Compressor OFF time with faulty probe 0÷255 min. 30 Pr2
11.3 ALARM RECOVERY DISPLAY
Probe alarms : “P1” (probe1 faulty), “P2” and “P3”; they automatically stop 10s after the probe restarts normal CF Temperature measurement unit °C ÷ °F °C Pr2
operation. Check connections before replacing the probe. rES Resolution (integer/decimal point) in ÷ de de Pr1
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal Lod Local display P1 ÷ 1r2 P1 Pr2
values or when the defrost starts.
Red Remote display P1 ÷ 1r2 P1 Pr2
Door switch alarm “dA” stop as soon as the door is closed.
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled “PAL” alarm is recovered by DEFROST
switching OFF the instrument. tdF Defrost type rE, rT, in rE Pr1
EdF Defrost mode In, Sd In Pr2
12. TECHNICAL DATA SdF Set point for SMART DEFROST -30 ÷ +30°C / -22÷+86°F 0 Pr2
Housing: self extinguishing ABS. dtE Defrost termination temperature (1°Evaporator) -50,0÷110°C/ -58÷230°F 8 Pr1
Case: facia 38x185 mm; depth 76mm IdF Interval between defrost cycles 1÷120h 6 Pr1
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws. ∅ 3 x 2mm. MdF (Maximum) length for 1° defrost 0÷255 min. 30 Pr1
Distance between the holes 165mm dFd Displaying during defrost rt, it, SEt, dEF, dEG it Pr2
Protection: IP20. dAd MAX display delay after defrost 0÷255 min. 30 Pr2
Frontal protection: IP65 with frontal gasket mod RG-L. (optional) Fdt Draining time 0÷60 min. 0 Pr2
Connections: Screw terminal block ≤ 2,5 mm2 heat-resistant wiring and 6,3mm Faston
dPO First defrost after start up n÷y n Pr2
Power supply: 230Vac or. 110Vac ± 10%
Power absorption: 7VA max. dAF Defrost delay after fast freezing 0 ÷ 23h 50 min. 2 Pr2
Display: 3 digits, red LED, 14,2 mm high. FANS
Inputs: 3 NTC probes FnC Fans operating mode C-n, C-y, O-n, O-y O-n Pr2
Digital inputs: 2 free voltage Fnd Fans delay after defrost 0÷255 min. 10 Pr2
Relay outputs: Total current on loads MAX. 20A FSt Fans stop temperature -50,0÷110°C/ -58÷230°F 2 Pr2
compressor: relay SPST 20(8) A, 250Vac ALARMS
light: relay SPST 16(3) A, 250Vac ALC Temperature alarms configuration rE÷Ab rE Pr2
fans: relay SPST 8(3) A, 250Vac ALU MAXIMUM temperature alarm -50,0÷110°C/ -58÷230°F 10 Pr1
defrost: relay SPST 8(3) A, 250Vac
ALL minimum temperature alarm -50,0÷110°C/ -58÷230°F 10 Pr1
Other output : alarm buzzer
Serial output : TTL standard AFH Temperature alarm and fan differential 0,1÷25,5 °C / 1÷45°F 2
Communication protocol: Modbus - RTU ALd Temperature alarm delay 0÷255 min. 15 Pr2
Data storing: on the non-volatile memory (EEPROM). dAO Delay of temperature alarm at start up 0 ÷ 23h 50 min. 1,3 Pr2
Kind of action: 1B. EdA Alarm delay at the end of defrost 0÷255 min. 30 Pr2
Pollution grade: normal dot Delay of temperature alarm after closing the door 0÷255 min. 15 Pr2
Software class: A. dOA Open door alarm delay 0÷255 min. 15 Pr2
Operating temperature: 0÷60 °C. nPS Pressure switch activation number 0÷15 0 Pr2
Storage temperature: -25÷60 °C. ANALOGUE INPUTS
Relative humidity: 20÷85% (no condensing)
Ot Thermostat probe calibration -12,0÷12,0°C / -21÷21°F 0 Pr1
Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F)
OE Evaporator probe calibration -12,0÷12,0°C / -21÷21°F 0 Pr2
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit O3 Auxiliary probe calibration -12,0÷12,0°C / -21÷21°F 0 Pr2
P2P Evaporator probe presence n÷y y Pr2
13. CONNECTIONS P3P Auxiliary probe presence n÷y n Pr2
HES Temperature increase during the Energy Saving -30÷30°C / -22÷86°F 0 Pr2
cycle
13.1 XW260L
DIGITAL INPUTS
Odc Open door control no, Fan, CPr, F_C Fan Pr2
I1P Door switch polarity CL÷OP CL Pr2
I2P Configurable digital input polarity CL÷OP CL Pr2
8A 8A 16A 20A
XW260L i2F Digital input configuration EAL, bAL, PAL, dFr, EAL Pr2
250Vac 250Vac 250Vac 250Vac MAX AUS, ES, OnF
20A
dId Digital input alarm delay 0÷255 min. 5 Pr2
SAA Set point for anti-condensing heater -50,0÷110°C/ -58÷230°F ---
5 6 7 8 9 10 11 12 13 14 17 18 19 20 21 22 23 OTHER 1
Room
Digital inp.
Common

Door switch

Display

Adr Serial address 0÷247 1.0 Pr1


Neutral
Line

Def.

Def. Fan Light Comp rEL Software release --- --- Pr2
Ptb Map code --- --- Pr2
Prd Probes display Pb1÷Pb3 --- Pr2
Pr2 Access parameter list --- Pr2

Dixell S.p.A. Via dell’Industria, 27


32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail:[email protected] - http://www.dixell.com

1592009027 XW260L GB r1.0 15.12.2004.doc XW260L 4/4