To display and modify target set point; in programming mode it selects a parameter or confirm an
operation.
WING
By holding it pressed for 3s when max or min temperature is displayed it will be erased.
To see the max. stored temperature; in programming mode it browses the parameter codes or
increases the displayed value. By holding it pressed for 3s the fast freezing cycle is started.
To see the min stored temperature; in programming mode it browses the parameter codes or
XW260L decreases the displayed value.
1.2
•
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
+ To lock and unlock the keyboard.
•
+
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
To enter the programming mode.
temperature changes with high atmospheric humidity to prevent formation of condensation
• Warning: disconnect all electrical connections before any kind of maintenance.
•
•
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A..” (see
address) with a detailed description of the fault.
+ To exit the programming mode.
• Consider the maximum current which can be applied to each relay (see Technical Data).
• Ensure that the wires for probes, loads and the power supply are separated and far enough from each 4.1 USE OF LEDS
other, without crossing or intertwining.
• In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with Each LED function is described in the following table.
inductive loads could be useful. LED MODE Function
ON The compressor is running
2. GENERAL DESCRIPTION
Model XW260L, 38x185 mm format, is microprocessor based controller suitable for applications on medium or FLASHING - Programming Phase (flashing with LED )
low temperature refrigerating units. It is provided with four relay outputs to control compressor, defrost - which - Anti-short cycle delay enabled
can be either electrical or hot gas - the evaporator fans and the lights.
ON The fan is running
It is also provided with three NTC probe inputs, one for temperature control, one to control the defrost end
temperature of the evaporator and the third, optional, for the display. There are two digital inputs (free contact) FLASHING
Programming Phase (flashing with LED )
for the door switch and configurable by parameter.
The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a ModBUS- ON The defrost is enabled
RTU compatible monitoring system and to programme the parameter list with the “Hot Key”.
FLASHING Drip time in progress
An optional output for remote display “XW-REP” is available.
ON The Fast Freezing cycle is enabled
3. CONTROLLING LOADS
ON - ALARM signal
3.1 THE COMPRESSOR - In “Pr2” indicates that the parameter is also present in “Pr1”
The regulation is performed according to the temperature measured by the thermostat probe with a positive
Function of the LEDs placed on the left top side of buttons:
differential from the set point: if the temperature increases and reaches set point plus differential the compressor
is started and then turned off when the temperature reaches the set point value again.
BUTTON MODE FUNCTION
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters
“COn” and “COF”. SET FLASHING The Set point is displayed and it can be modified
SET FAST FLASHING The Energy Saving is enabled
3.2 FAST FREEZING DEFROST ON The Manual Defrost is activated
LIGHT ON The Light is ON
When defrost is not in progress, it can be activated the keypad by holding the o key pressed for about 3 ON/OFF ON The instrument is OFF
seconds. The compressor operates in continuous mode for the time set through the “CCt” parameter. The cycle
can be terminated before the end of the set time using the same activation key, o for about 3 seconds.
4.2 HOW TO SEE THE MIN TEMPERATURE
3.3 DEFROST 1. Press and release the n key.
Three defrost modes are available through the “tdF” parameter: defrost with electrical heater, hot gas or 2. The “Lo” message will be displayed followed by the minimum temperature recorded.
thermostatic defrost. The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made 3. By pressing the n key or waiting for 5s the normal display will be restored.
every “IdF” time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the
compressor is ON and the evaporator temperature is bigger than “SdF” parameter). 4.3 HOW TO SEE THE MAX TEMPERATURE
At the end of defrost the drip time is controlled through the “Fdt” parameter.
1. Press and release the o key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3.4 CONTROL OF EVAPORATOR FANS 3. By pressing the o key or waiting for 5s the normal display will be restored.
The fan control mode is selected by means of the “FnC” parameter:
FnC=C-n fans will switch ON and OFF with the compressor and not run during defrost:; 4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
FnC=C-y fans will run continuously, but not during defrost To reset the stored temperature, when max or min temperature is displayed :
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. 1. Press SET key until “rST” label starts blinking.
FnC=O-n fans will switch ON and OFF with the compressor and run during defrost;
FnC=O-y fans will run continuously also during defrost N.B. After the installation RESET the temperature stored .
An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe, above 4.5 HOW TO SEE AND MODIFY THE SET POINT
which the fans are always OFF. This can be used to make sure circulation of air only if his temperature is lower 1. Push and immediately release the SET key: the display will show the Set point value;
than set in “FSt”. 2. The SET LED start blinking;
3. To change the Set value push the o or n arrows within 10s.
4. To memorise the new set point value push the SET key again or wait 10s.
4. KEYBOARD
4.6 TO START A MANUAL DEFROST
F
C 1. Push the DEF key for more than 2 seconds and a manual defrost will start.
1. Enter the Programming mode by pressing the Set and DOWN key for few
seconds ( and start blinking).
7. INSTALLATION AND MOUNTING 10.2 UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
Instruments XW260L shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws ∅ 3 1. Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then
x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-LX). The temperature turn it ON again.
range allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations, corrosive gases, 2. When the Wing unit is ON, insert the “Hot key” and push o key; the "uPL" message appears.
excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate by the cooling 3. Push “SET” key to start the UPLOAD; the “uPL” message is blinking.
holes. 4. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages:
7.1 CUT OUT “end “ for right programming.
“err” for failed programming. In this case push “SET” key if you want to restart the programming again or
remove the not programmed “Hot key”.
165
+1
-1
11. ALARM SIGNALS
150
+0.5
-0 Message Cause Outputs
“P1” Thermostat probe failure Alarm output ON; Compressor output according to
parameters “COn” and “COF”
+0.5
“P2” Evaporator probe failure Alarm output ON; Other outputs unchanged
-0
31
“P3” Auxiliary probe failure Alarm output ON; Other outputs unchanged
“HA” Maximum temperature alarm Alarm output ON; Other outputs unchanged
“LA” Minimum temperature alarm Alarm output ON; Other outputs unchanged
Ø3 x2 “EE” Data or memory failure Alarm output ON; Other outputs unchanged
“dA” Defrost timeout alarm Alarm output ON; Other outputs unchanged
7.2 XW260L MOUNTING “dAL” Door switch alarm Alarm output ON; Other outputs unchanged
“EAL” External alarm Alarm output ON; Other outputs unchanged
“BAL” Serious external alarm Alarm output ON; Other outputs OFF
Door switch
Display
Def.
Def. Fan Light Comp rEL Software release --- --- Pr2
Ptb Map code --- --- Pr2
Prd Probes display Pb1÷Pb3 --- Pr2
Pr2 Access parameter list --- Pr2