Touch Advanced Display (TAD) Installation Guide
Part No. 24-11483-00000 Rev. B
2021-07-01
Applications Mounting
The Touch Advanced Display (TAD) is a comprehensive
series of freely programmable operator interfaces
Mounting considerations
featuring both IP and MSTP BACnet® communication The design of the TAD series allows for multiple mounting
and graphic displays with a touch-screen interface. TAD options including panel front and flush mounting on a wall
Displays feature thin-film-transistor widescreen (16:9) through utilization of the BOX0x-01 accessories. To ensure
displays of different sizes with a fully dimmable LED the front panel protection classifications as marked on
backlight and resistive touch interface. The integrated the product nameplate, you must install the TAD on a flat
HTML 5.0 web server grants remote access whenever the surface of a Type 2, 4X enclosure.
units are connected to an accessible IP network. If you wish to disregard the aforementioned front panel
protection classification, complete the steps found in
Figure 1: Touch Advanced Display Mounting the TAD on a drywall or Mounting the TAD on a
masonry wall .
Note: The equipment is not intended for continuous
exposure to direct sunlight as it accelerates the aging
process of the front panel film.
Note: The equipment is not intended for installation
Installation in contact with corrosive chemical compounds. Check
Observe these guidelines when installing the TAD: the resistance of the front panel film to a specific
compound before installation.
• Transport the display in the original container to
minimize vibration and shock damage to the unit. Note: Do not use tools of any kind to operate the
• Verify that all parts were shipped with the display. touch screen of the panel.
• Do not drop the display or subject it to physical shock.
Parts included
• One Touchscreen Advanced Display
• Fixing bracket screws
• Removable DC power terminal connector
• One installation instructions sheet
Materials and special tools needed
• Oscillating multi-tool or similar cutting tool for cutting
a hole into the panel to hold the display, if no hole is
provided
• DB-9 Serial Port Connector. See Accessories.
• 24 VDC external power supply. See Accessories.
• Small Phillips-head screwdriver
TAD0471-0, TAD0701-0, TAD1001-0
Physical features
Figure 2: TAD physical features
Table 1: Physical features callout Figure 3: TAD overall dimensions
Callout Description
1 Power supply terminal block (18-32Vdc)
2 Serial port (5V 100mA max.)
3 Ethernet port
4 USB port (version 2.0, 5V 500mA max)
Mounting dimensions
Refer to the following illustrations for the mounting
dimensions and physical features of the TAD.
Table 2: TAD overall dimensions
Model A B C D
107mm 147 mm 29 mm (1.14 5 mm (0.19
TAD0471-0
(4.21 in.) (5.78 in.) in.) in.)
147 mm 187 mm 29 mm (1.14 5 mm (0.19
TAD0701-0
(5.79 in.) (7.36 in.) in.) in.)
197 mm 282 mm 29 mm (1.14 6 mm (0.23
TAD1001-0
(7.75 in.) (11.10 in.) in.) in.)
2 Touch Advanced Display (TAD) Installation Guide
Figure 6: Mounting on the counter display
Figure 4: BOXxx-01 dimensions
Table 5: TAD counter display
Num
Description
ber
1 Assembly instructions
Side-view of the TAD correctly positioned on the
2
counter display
Table 3: BOXxx-01 dimensions
Model A B C Mounting the TAD on a drywall
102 mm (4.03 142 mm (5.61 50 mm (1.96
BOX04-01 The display can be wall-mounted using the BOXxx-01 wall
in.) in.) in.) box directly into drywall. Complete the following steps:
142 mm (5.61 182 mm (7.18 50 mm (1.96
BOX07-01 1. Use the dimensions found in Table 6 and illustrated
in.) in.) in.)
in panel 1 of Figure 7 to measure what size hole that
192 mm (7.57 277 mm (10.92 50 mm (1.96 you need to accurately draw.
BOX10-01
in.) in.) in.)
Figure 7: Mounting a TAD on a drywall
Mounting the TAD to a controls
enclosure
Figure 5: Mounting the TAD to a controls enclosure
Tighten the fixing brackets screws at 75Ncm for the
appropriate cut-out:
Table 4: Cut out dimensions
Model Cut out dimensions
136 mm x 96 mm (5.35 in. x 3.78
TAD0471-0:
in.)
176 mm x 136 mm (6.90 in. x Table 6: Cut out dimensions
TAD0701-0:
5.35 in.) Model A B
271 mm x186 mm (10.66 in. x BOX04-01 104 mm (4.09 in.) 144 mm (5.66 in.)
TAD1001-0:
7.32 in.)
BOX07-01 144 mm (5.66 in.) 184 mm (7.24 in.)
BOX10-01 194 mm (7.63 in.) 279 mm (10.98 in.)
Mounting the TAD to a counter display 2. Cut a hole in the drywall using an oscillating multi-
You can display the TAD using the DEMO-STAND07 tool or similar cutting tool.
counter display.
Touch Advanced Display (TAD) Installation Guide 3
3. Insert the box in the cutout and then route the 5. Secure the box using cement filler or a similar
wiring cables through the backplate. bonding agent.
4. Push out the tab fastners on the top, on the sides 6. Attach the wiring cables. See Wiring for further
and on the base of the box. Ensure that the box is information.
secure within the cutout. See panel 3 of Figure 7. 7. Insert the TAD into the box by pressing gently on
5. Attach the wiring cables. See Wiring for further each side of the casing until the display clicks into
information. place.
6. Insert the TAD into the box by pressing gently on
each side of the casing until the display clicks into Wiring
place.
Observe the following guidelines when wiring a TAD:
Mounting the TAD on a masonry wall
The display can be wall-mounted using the BOXxx-01 wall
box directly into a masonry wall. Complete the following CAUTION
steps:
1. Use the dimensions found in Table 7 and illustrated Risk of Electric Shock.
in panel 1 of Figure 8 to measure what size hole you
need and draw accurately. Disconnect the power supply before making electrical
connections to avoid electric shock.
Figure 8: Mounting a TAD on a masonry wall
ATTENTION
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.
Important: Do not connect supply power to the
TAD before finishing wiring and checking all wiring
connections. Short circuits or improperly connected
wires can result in damage to the controller and void
any warranty.
Important: Do not exceed the TAD electrical ratings.
Exceeding controller electrical ratings can result in
permanent damage to the controller and void any
warranty. See Technical specifications.
Important: Use copper conductors only. Make
all wiring in accordance with local, national, and
regional regulations.
Important: Electrostatic discharge can damage
Table 7: Cut out dimensions controller components. Use proper electrostatic
Model A B C discharge precautions during installation, setup, and
BOX04-01 118 mm (4.64 in.) 157 mm (6.18 in.) 60 mm (2.36 in.) servicing to avoid damaging the TAD.
BOX07-01 157 mm (6.18 in.) 198 mm (7.79 in.) 60 mm (2.36 in.) Power the TAD units with 18 to 32 VDC supply voltage. See
293 mm (11.53 Accessories for the recommended power supply. The unit
BOX10-01 207 mm (8.14 in.) 60 mm (2.36 in.) must always be grounded to earth. Use terminal 3 on the
in.)
power supply terminal block for the earth connection. See
2. If no hole is provided, cut a hole in the masonry Figure 9 for details on the correct wiring configuration.
using a concrete saw or similar cutting tool. For details on how to connect the TAD to a network of FX-
3. Insert the box in the cutout and then route the PCs devices, refer to the FX MS/TP Communications Bus
wiring cables through the backplate. Technical Bulletin (LIT-12011670). For details on connecting
4. Push out the tab fasteners on the top, on the sides the TAD to a network of Metasys devices, refer to the MS/
and on the base of the box. Ensure that the box is TP Communications Bus Technical Bulletin (LIT-12011034).
secure within the cutout. See panel 2 of Figure 8.
4 Touch Advanced Display (TAD) Installation Guide
Figure 9: Wiring configuration Table 8: Communications
Number Description
DB-9
1
• RS-485
Ethernet Port
• Upload and download
2
• Remote connection
• IP Protocols
USB
3 • Download
• Trend buffer retrieve
Serial port
The TAD serial port is used to communicate with other
field devices. The serial port standard is software
programmable. You must select RS485 for BACnet MS/TP.
Serial ports pinout: RS485
Note: Pins 3 & 4 are not internally interconnected
within the TAD. Interconnect them together on the
DB-9 Male and then connect to the FC-Bus terminal
[-]. The same is valid for pins 7 & 8 connected to the
FC-Bus terminal [+]. Pin 1 is connected to the FC-Bus
terminal COM.
Figure 11: Serial Ports Pinout: RS485
Figure 10: Communications
Once the DB-9 male connector is correctly prepared,
you can connect outputs to the FC bus connector. It
is required to wire the COM along with the + and -
connections.
Touch Advanced Display (TAD) Installation Guide 5
Figure 12: DB-9 connector Table 11: Product ordering codes
Product code Description
DB-9 Serial Port Connector,
TAD-DB9-0
required for BACnet MS/TP
Touchscreen Tailoring Tool, single
TTT0103 license key for installation on 3
computers
Touchscreen Tailoring Tool, single
TTT0110 license key for installation on 10
computers
Touchscreen Tailoring Tool, single
TTT0130 license key for installation on 30
computers
DC Power supply; Input:
ACC-PS-24VDC 100-240VAC, Output: 24VDC,2.5A;
DIN rail mounting
Table 9: Serial port: RS485
Pin Description
1 COM
3-4 -
7-8 +
The TAD uses DHCP by default. If a static IP is required,
it must be configured before connecting to the building
network.
Setup and Adjustments
Ordering information
Table 10: Product ordering codes
Product code Description
4.3 in. (109 mm) Touchscreen
TAD0471-0
Advanced Display
7.0 in. (178 mm) Touchscreen
TAD0701-0
Advanced Display
10.0 in. (254 mm) Touchscreen
TAD1001-0
Advanced Display
Accessories
Table 11: Product ordering codes
Product code Description
BOX04-01 Wall mount box for TAD04
BOX07-01 Wall mount box for TAD07
BOX10-01 Wall mount box for TAD10
Counter display structure for
DEMO-STAND07
TAD07
6 Touch Advanced Display (TAD) Installation Guide
Technical specifications
Table 12: Technical specifications
TAD0471-0: 4.3 in. (109 mm) freely programmable Touchscreen Advanced Display
Product code number TAD0701-0: 7.0 in. (178 mm) freely programmable Touchscreen Advanced Display
TAD1001-0: 10.0 in. (254 mm) freely programmable Touchscreen Advanced Display
TAD0471-0: 4.3 in. (109 mm) widescreen TFT 64k colors, 480 x 272 and LED backlight
Display TAD1001-0: 7.0 in. (178 mm) widescreen TFT 64k colors, 1024 x 600 and LED backlight
TAD0701-0: 10.0 in. (254 mm) widescreen TFT 64k colors, 800 x 480 and LED backlight
Brightness 200 cd/m2
Touch-screen Resistive
Supply voltage 18-32 VDC
Real-time clock Yes
Ethernet Port 1 – Port 0 10/100
Serial Port RS-232 / RS-422 / RS-485 software configurable
USB Port 1 – Host v. 2.0, max. 500 mA
TAD0471-0: 250 mA max @ 24 VDC
Power consumption TAD0701-0: 300 mA max @ 24 VDC
TAD1001-0: 380 mA max @ 24 VDC
Operating: 32°F to 122°F (-0°C to +50°C), 5 to 85% RH (noncondensing)
Ambient conditions
Storage: -4°F to 158°F (-20°C to +70°C), 5 to 85% RH (noncondensing)
TAD0471-0:4.21 in x 5.78 in. x 0.945 in. (107 mm x 147 mm x 24 mm)
Dimensions (H x W x D) TAD0701-0:5.79 in. x 7.36 in. x 0.945 in. (147 mm x 187 mm x 24 mm)
TAD1001-0:7.75 in. x 11.10 in. x 0.984 in. (197 mm x 282 mm x 25 mm)
TAD0471-0: 0.88 lb. (0.4 kg)
Weight TAD0701-0: 1.32 lb. (0.6 kg)
TAD1001-0: 2.2 lb. (1.0 kg)
TAD0471-0: RAM 256MB Flash, 2GB
Memory TAD0701-0: RAM 256MB Flash, 2GB
TAD1001-0: RAM 512MB Flash, 4GB
Housing Protection: IP66 front, IP20 back
United States: UL Listed, File E515649, CCN NRAQ, UL 508, Programmable controllers; FCC test report
available
Compliance
Canada: UL Listed, File E515649, CCN NRAQ7, CAN/CSA C22.2 No. 142, Programmable controllers certified
for Canada; Industry Canada Compliant.
Europe: CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages
resulting from misapplication or misuse of its products.
Touch Advanced Display (TAD) Installation Guide 7
Product warranty Single point of contact
This product is covered by a limited warranty, details APAC Europe NA/SA
of which can be found at www.johnsoncontrols.com/ JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
buildingswarranty. C/O CONTROLS PRODUCT WESTENDHOF 3 507 E MICHIGAN ST
MANAGEMENT 45143 ESSEN MILWAUKEE WI 53202
NO. 32 CHANGJIJANG RD NEW GERMANY USA
DISTRICT
Contact information WUXI JIANGSU PROVINCE 214028
CHINA
Contact your local branch office:
www.johnsoncontrols.com/locations
Contact Johnson Controls: www.johnsoncontrols.com/
contact-us
© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and
are subject to change without notice.
www.johnsoncontrols.com