Structural Design Report for Residence
Structural Design Report for Residence
DESIGN REPORT
STRUCTURAL DESIGN & DETAILING FOR
FOUR STORIED RESIDENCE BUILDING
M A T RIX B UI L T E N G I N E E R I N G
`
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
1.0 INTRODUCTION
This report is prepared as a design workout for Short Course on Structural Design
Online course conducted by MATRIX Built, as a part of its exercises.
The design report accounts for analysis and designing of structural element of a proposed
Hostel Building which is fourstoried reinforced concrete frame building with 1015.3 m2 of
floor area.
The design report contains design calculations with respect to the analysis which was
carried out using computer aided software such as “PROKON” and “ETABS” as well as
the manual calculations in accordance with the recommendations given in BS 8110:
Part1:1997, BS 8110: Part3 : 1985, CP3: Chapter V: Part 2:1972 and BS 6399: Part
1:1996 and detailing was done according to the Standard Method of Detailing Structural
Concrete: 1989. Sizing of the structural element is carried out to fulfill the architectural
and structural requirement. This report includes designing and detailing for second floor
slab, second floor beam, column up to roof, stair case and foundation. The foundation
design was adopted according to the soil investigation report with an allowable bearing
capacity of 175kN/m2 at 1.0m depth.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
2.1 REFERENCES
Design Codes
· BS 6399: Part1: Code of practice for Dead and Imposed loads: 1996
· CP3: Chapter V: Part 2: Code of practice for Wind loads:
1972 For Detailing
Wind loading condition Speed 38 m/s(post disaster structure in wind zone 3- Kekirawa)
Imposed Load:
Roof 0.75 kN/m2
Bed room 1.5 kN/m2
Toilet area 2.0 kN/m2
2.3 ASSUMPTIONS
2. Stress in the concrete are derived from stress-strain curve in Fig 2.1 of BS
8110: Part 1 with γm = 1.5 and tensile strength of concrete is ignored.
5. Where section is design to resist only flexure, the lever arm should not be
assumed to be greater than 0.95 times the effective depth.
C nominal cover
Z Lever arm.
symbols of Slabs
symbols of beams
bv Breadth of section
symbols of columns
CHAPTER-3
DESIGN OF SECOND FLOOR SLAB
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
1. Slab thickness
Table 3.2 In the designing of slab assume the exposure condition of the
(BS8110) reinforcement as Mild and according to the fire resistance assume it has
1.5-hour fire resistance. So in order to that
Nominal cover against Fire resistance = 20 mm
Nominal cover against the exposure condition =25 mm
Considering the safety condition select the 25mm as the nominal cover
4500
3900
S3
Ly/Lx = 4500/3900 =1.15 < Since this is Two way one short edge
Table 3 ( discontinuous slab.
Design
Manual) Since this is four story housing project assume the designing imposed
load as 5 KN/m^2
2. Load Calculations
Table 1 (BS Consider imposed load = 1.5 KN/mm^2
6399) Dead load
Finishes =1KN/mm^2
Self-weight = 24 x 0.15x 1 =3.6 KN/mm^2
Moment distribution
At this stage no need to consider about the long span coefficients. Since
at this stage consider about the unit strip along the short spans.
So Similarly the same procedure was carried out for other slab panels for
find Bending moments.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Then Z =0.95d
𝑀𝑋
𝐴𝑠=
0.95 𝑥 𝑓𝑦 𝑥𝑧
4.71 𝑥 1000 𝑥 1000
𝐴𝑠=
0.95 𝑥 460 𝑥 120
=89.81 𝑚𝑚2
𝟏𝟎𝟎 As,min
= 0.13
𝟏𝟎𝟎𝟎 𝒙 𝟏𝟓𝟎
195 𝑚𝑚2
The provided spacing is =
78.58
= 2.48 bars
So then provided spacing is =1000 / 2.48 = 403 mm
But the allowable maximum spacing is =360 mm
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
The deflection check is done for Mid span, since the Mid span is critical
for deflection. Not only that deflection check is do for shorter span also,
since the shorter span is critical for deflection check.
Span
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 ≤ ×𝑀𝐹1×𝑀𝐹1
Effective depth
Span
= 26 (Continuous support)
Effective depth
(477−fs)
𝑀𝐹1= 0.55+ ≤2
120[0.9+Mbd2
fy x 2 xAs,req
𝑆𝑒𝑟𝑣𝑖𝑐𝑒𝑠 𝑠𝑡𝑟𝑒𝑠𝑠 𝑓𝑠 = 3 𝑥As,provide x βb
In this case βb = 1
𝑓𝑠=228.43
Span
×𝑀𝐹1×𝑀𝐹1 = 26 x 2 x 1 = 52 > 𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛
Effective depth
𝑀𝑥
𝑘=
𝑏𝑥𝑑 2 𝑓𝑐𝑢
Then Z =0.95d
𝑀𝑋
𝐴𝑠=
0.95 𝑥 𝑓𝑦 𝑥𝑧
=99.924 𝑚𝑚2
100As,min
=0.13
Ac
𝟏𝟎𝟎 As,min
= 0.13
𝟏𝟎𝟎𝟎 𝒙 𝟏𝟓𝟎
195 𝑚𝑚2
The provided spacing is =
78.58
= 2.48 bars
So then provided spacing is =1000 / 2.48 = 403 mm
But the allowable maximum spacing is =360 mm
Then reinforcement bars spacing is = 300 mm
Usually deflection check does not used for edge supported of the slab.
100𝐴𝑆 1 400 1
𝑣𝑐=0.79 x ( )3 𝑥 ( )4
𝑏𝑑 𝑑
= 0.643 > 𝑣
Condition is satisfying
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝑀𝑋
𝐴𝑠=
0.95 𝑥 𝑓𝑦 𝑥𝑧
5.01 𝑥 1000 𝑥 1000
𝐴𝑠=
0.95 𝑥 460 𝑥 120
=95.54 𝑚𝑚2
𝟏𝟎𝟎 As,min
= 0.13
𝟏𝟎𝟎𝟎 𝒙 𝟏𝟓𝟎
195 𝑚𝑚2
The provided spacing is =
78.58
= 2.48 bars
So then provided spacing is =1000 / 2.48 = 403 mm
But the allowable maximum spacing is =360 mm
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
The deflection check is done for Mid span, since the Mid span is critical
for deflection. Not only that deflection check is do for shorter span also,
since the shorter span is critical for deflection check.
Span
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 ≤ ×𝑀𝐹1×𝑀𝐹1
Effective depth
Span
= 26 (Continuous support)
Effective depth
(477−fs)
𝑀𝐹1= 0.55+ ≤2
120[0.9+Mbd2
fy x 2 xAs,req
𝑆𝑒𝑟𝑣𝑖𝑐𝑒𝑠 𝑠𝑡𝑟𝑒𝑠𝑠 𝑓𝑠 = 3 𝑥As,provide x βb
In this case βb = 1
𝑓𝑠=228.43
Span
×𝑀𝐹1×𝑀𝐹1 = 26 x 2 x 1 = 52 > 𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛
Effective depth
𝑀𝑥
𝑘=
𝑏𝑥𝑑 2 𝑓𝑐𝑢
Then Z =0.95d
𝑀𝑋
𝐴𝑠=
0.95 𝑥 𝑓𝑦 𝑥𝑧
=126.24 𝑚𝑚2
100As,min
=0.13
Ac
𝟏𝟎𝟎 As,min
= 0.13
𝟏𝟎𝟎𝟎 𝒙 𝟏𝟓𝟎
195 𝑚𝑚2
The provided spacing is =
78.58
= 2.48 bars
So then provided spacing is =1000 / 2.48 = 403 mm
But the allowable maximum spacing is =360 mm
Then reinforcement bars spacing is = 300 mm
Usually deflection check does not used for edge supported of the slab.
100𝐴𝑆 1 400 1
𝑣𝑐=0.79 x ( )3 𝑥 ( )4
𝑏𝑑 𝑑
= 0.643 > 𝑣
Condition is satisfying
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
The slab S5, Ly/Lx value is greater than the 2, then the S5 slab consider
as the one-way slab.
For one-way slab used table Table 3.12 to finding the bending moment
values. But in Table 3.12 it is used to find the ultimate bending moment.
So to find the design bending moment we should go with First principal.
Using first principal bending moment was calculated. Then Maximum
bending moment was selected for further calculations. Between any two
supports energy will not dissipate. In order to that after distributing the
bending moments at supports, the mid span bending moments can find
using energy efficiency.
𝑀𝐴=𝑀𝐵=𝑞𝑙212
= (8.84×1.0) ×2.4212
=4.24 𝑘𝑁𝑚
𝑀1=𝑞𝑙224
= (8.84×1.0) ×2.4224
=2.12 𝑘𝑁𝑚
At mid span
Then Z =0.95d
𝑀𝑋
𝐴𝑠=
0.95 𝑥 𝑓𝑦 𝑥𝑧
4.24
𝐴𝑠=
0.95 𝑥 460𝑥0.95 𝑥 120
=85.12 𝑚𝑚2
195 𝑚𝑚2
The provided spacing is =
78.58
= 2.48 bars
So then provided spacing is =1000 / 2.48 = 403 mm
But the allowable maximum spacing is =360 mm
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
T10@300mmB1
The deflection check is done for Mid span, since the Mid span is critical
for deflection. Not only that deflection check is do for shorter span also,
since the shorter span is critical for deflection check.
Span
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 ≤ ×𝑀𝐹1×𝑀𝐹1
Effective depth
Span
= 26 (Continuous support)
Effective depth
(477−fs)
𝑀𝐹1= 0.55+ ≤2
120[0.9+Mbd2
fy x 2 xAs,req
𝑆𝑒𝑟𝑣𝑖𝑐𝑒𝑠 𝑠𝑡𝑟𝑒𝑠𝑠 𝑓𝑠 = 3 𝑥As,provide x βb
In this case βb = 1
𝑓𝑠=228.43
Span
×𝑀𝐹1×𝑀𝐹1 = 26 x 2 x 1 = 52 > 𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛
Effective depth
𝑀𝑥
𝑘=
𝑏𝑥𝑑 2 𝑓𝑐𝑢
Then Z =0.95d
𝑀𝑋
𝐴𝑠=
0.95 𝑥 𝑓𝑦 𝑥𝑧
=40.42 𝑚𝑚2
100As,min
=0.13
Ac
𝟏𝟎𝟎 As,min
= 0.13
𝟏𝟎𝟎𝟎 𝒙 𝟏𝟓𝟎
Bar spacing
Allowable Maximum spacing = lesser of {3d, 750 mm} =300 mm
= lesser of {3×120 ,750 mm}
= lesser of {360 mm, 750 mm}
So maximum allowable spacing = 360 mm
As = 262 𝑚𝑚2
Let’s consider the provided reinforcement bar diameter is 10 mm
T10@300mmB1
195 𝑚𝑚2
The provided spacing is =
78.58
= 2.48 bars
So then provided spacing is =1000 / 2.48 = 403 mm
But the allowable maximum spacing is =360 mm
Then reinforcement bars spacing is = 300 mm
Usually deflection check does not used for edge supported of the slab.
𝑉1=𝑉2=𝑞𝑙2
𝑉1=𝑉2= (8.84×1.0) ×2.42=10.61 𝑘𝑁
100𝐴𝑆 1 400 1
𝑣𝑐=0.79 x ( )3 𝑥 ( )4
𝑏𝑑 𝑑
= 0.643 > 𝑣
Condition is satisfy
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
The above figure shows the moments at supports and the mid span before the distribution of the bending moments. Since at the edge of the panels
moments are differ since it is need to distribute the bending moments along the short strips and the long strip to find the designing bending moments at
edges.
The following figure shows the bending moments before the moment distribution.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
According to the above figure it is shows bending moments at support are different to
each other, so it is need to redistribute the bending moments along a considered strip
to find the relevant design bending moments at panel edges.
In this drawing mainly there are two slab panels, one is Fixed panel and the other one
is propped cantilever panel.
The stiffness for each member is depend on the member support condition. So in order
to that following table shows the relative stiffness for above two type of member.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
The ultimate shear force and the bending moment for one-way slab panel can be obtain using table 3.5
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
But usually to find the shear force we used first principal, since these slab uniformly distributed slab shear forces can obtain using (WL) /2.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
After finding the required rein-forcement area It is need to check the deflection check, check for shear and the cracking control check also.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Deflection check
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
According to the above results the deflection check is satisfying with the propose condition
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Crack control
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
According to the above results it is mentioned that the proposed condition the cracking control also satisfying.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Shear check
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Detailing
There are some few condition in detailing the slab panel. Those
are
CHAPTER 4
DESING OF SECOND FLOOR BEAM
(SPECIMEN CALCULAION FOR GRID J/1-4 BEAM)
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
In initial sizing there are several methods to follow, those are thumb
rule, bending criterial, deflection criterial and the shear criteria
Resistance.
So according to that beam width can taken as 225mm and the beam
height was selected as 350 mm
Then initial size of the beam (grid H/(1-4)) is =225mm x 350 mm .
In this design most the beams act as the continuous support bur the
J/( 2-4) beam act as simply supported beam. When considering the
simply support beam J/(2-4) beam
Loading Arrangement
There are several loading arrangements from those according to the BS
8110-1997 (BS 8110-1997 Clause 3.2.1.2.2) mainly 3 types of loading
arrangements were considered
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Load calculation
Span 1-2
Dead load along the beam Self-weight of the beam = 0.225×0.350×24 =
1.89 kN/m
Dead load (Partition walls) = 4.5×3.75 = 7.31 KN/m2 (L type flange
section = (slab width /2 + web width /2)
Total dead load =1.89+7.31
= 9.20 kN/m2
The maximum dead load induced by the beam = 1.4 Gk
= 1.4 x 9.2
= 12.88 KN /m
Minimum dead load induced by the beam =1 x Gk
= 9.2 KN /m
The induced dead load from the slab to the beam;
The load induced by the slab S4 on the beam,
Dead load from slab S4-Two adjacent discontinuous slab
Trapezoidal loading from two-way slabs on beams are taken as the shear
force acting of 0.75L center of the span (BS8110:1997-part 1 Figure 3.10)
Beam B4 along ly direction, so vs = vsx
Maximum dead load along the beam vsx = βsxnlx
= 0.30 ×{1.4×4.6+1.6×1.5}×3.9
= 10.35 kN/m
Minimum dead load along the beam vsx = βsxnlx
= 0.30 ×{1.0×4.6}×3.9
= 5.38 kN/m
Dead load of Dead load Total dead
the beam from the load
slab(S4) -
0.75L
Maximum 12.88 KN 10.35 KN /m 23.23 KN/
/m m
Minimum 9.2 KN /m 5.38 KN /m 14.58 KN
/m
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Span 2-3
Then in order to that we can find the minimum and the maximum
dead load
Maximum dead load = 1.4gk ```
= 1.4 ×12.95
= 18.13 kN/m
Minimum dead load along the beam =1.0 gk
= 1 x 12.95
=12.95 KN /m
Then in order to that we can find the minimum and the maximum dead
load
Maximum dead load = 1.4gk ```
= 1.4 ×12.95
= 18.13 kN/m
= 10.35 kN/m
Minimum dead load along the beam vsx = βsxnlx
= 0.30 ×{1.0×4.6}×3.9
= 5.38 kN/m
Dead load which is affect from the slab to beam is depend on
slab is one way or two ways. If affected slab is one way, we consider that
the affected length is equal to the beam length and also if the slab is two
ways then consider the affected length is 0.75l.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
To find out the moment values at the supports and mid spans when the
frame in equilibrium we need to go for moment distribution method and
for that purpose need to calculate the second moment of inertia for the
section to calculate the relative stiffness values.
k =4EI/L
Flange L section
(BS8110:1997 𝑏𝑓 =𝑙𝑒𝑠𝑠𝑒𝑟 𝑜𝑓 ({𝑏𝑤+0.1𝑙𝑧 or 𝐴𝑐𝑡𝑢𝑎𝑙 𝑓𝑙𝑎𝑛𝑔𝑒 𝑤𝑖𝑑𝑡ℎ)}
part 1 , Cl
3.4.1.3 , Cl
3.4.1.5)
𝑏𝑤+0.1𝑙𝑧=0.225+0.1×(0.7×𝐸𝑓𝑓𝑒𝑐𝑖𝑡𝑖𝑣𝑒 𝑠𝑝𝑎𝑛)
=0.225+0.1×(0.7×4.5)
=0.540 𝑚
The span 1 & 2 beam flange section act as a L type beam flange section.
To find the neutral axis can take the moment around the A –A axis,
using moment equilibrium method.
𝑏 𝑥 𝑑3 3
̅̅̅̅2 ) 𝑓𝑙𝑎𝑛𝑔𝑒 + (∑ 𝑏 𝑥 𝑑 + 𝐴𝑋
̅̅̅̅2 ) 𝑤𝑒𝑏
𝐼𝑁𝐴= (∑ + 𝐴𝑋
12 12
=112×540×1503 +540×150×62.52 +112×225 ×
2003 +225×200×112.52
=1.19×109 𝑚𝑚4
Second moment of inertia calculation in each section- Span 2-3
Flange T section
(BS8110:1997
part 1 , Cl 𝑏𝑓 =𝑙𝑒𝑠𝑠𝑒𝑟 𝑜𝑓 ({𝑏𝑤+0.1𝑙𝑧 or 𝐴𝑐𝑡𝑢𝑎𝑙 𝑓𝑙𝑎𝑛𝑔𝑒 𝑤𝑖𝑑𝑡ℎ)}
3.4.1.3 , Cl
3.4.1.5) 𝑏𝑤+0.1𝑙𝑧=0.225+0.1×(0.7×𝐸𝑓𝑓𝑒𝑐𝑖𝑡𝑖𝑣𝑒 𝑠𝑝𝑎𝑛)
=0.225+0.1×(0.7×2400)
=561 𝑚𝑚
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝑏 𝑥 𝑑3 ̅̅̅̅2
𝐼𝐼−2 = ∑ + 𝐴𝑋
12
𝑏 𝑥 𝑑3 3
̅̅̅̅2 ) 𝑓𝑙𝑎𝑛𝑔𝑒 + (∑ 𝑏 𝑥 𝑑 + 𝐴𝑋
̅̅̅̅2 ) 𝑤𝑒𝑏
𝐼𝑁𝐴= (∑ + 𝐴𝑋
12 12
=1.21×109 𝑚𝑚4
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Flange T section
̅𝑋 =230𝑚𝑚
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝑏 𝑥 𝑑3 ̅̅̅̅2
𝐼𝐼−2 = ∑ + 𝐴𝑋
12
𝑏 𝑥 𝑑3 3
̅̅̅̅2 ) 𝑓𝑙𝑎𝑛𝑔𝑒 + (∑ 𝑏 𝑥 𝑑 + 𝐴𝑋
̅̅̅̅2 ) 𝑤𝑒𝑏
𝐼𝑁𝐴= (∑ + 𝐴𝑋
12 12
𝑏 𝑥 𝑑3
𝐼𝑐𝑜𝑙𝑢𝑚𝑛 = ∑
12
225 𝑥 2253
=
12
= 2.135 𝑥108 mm
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Then it is need to find the relative stiffness of each beam and the
column section;
𝑅𝑒𝑙𝑎𝑡𝑖𝑣𝑒 𝑠𝑡𝑖𝑓𝑓𝑛𝑒𝑠 𝑜𝑓 1−2 𝑠𝑝𝑎𝑛=4𝐸𝐼/𝐿
4 𝐸 𝑋 1.19 𝑋109
=
4500
=10.6𝐸× 105
𝑅𝑒𝑙𝑎𝑡𝑖𝑣𝑒 𝑠𝑡𝑖𝑓𝑓𝑛𝑒𝑠 𝑜𝑓 1-A column section=4𝐸𝐼/𝐿
4 𝐸 𝑋 2.135 𝑥108
=
3000
= 2.85Ex 105
So in order to that we can find the relative stiffness and the
distribution factor for each and every section
Then we can relative stiff nesses were calculated and distribution
factor was found out in each element that show in below table
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
0= −24.64+32.36+(92.9x4.5/2)-4.5R2
R2 =48.17 KN
Solving two equation
R2 = 48.17 kN
R1 = 44.73 kN
Bending
(𝑑𝑀)/(𝑑𝑥)=−44.73+12.88 x
𝑑𝑚
=0
𝑑𝑥
Shear
𝑥 10.35
𝑑𝑀=24.64+12.88×x× - 44.73×𝑥 +( 𝑥 (𝑥 − 0.562))^2
2 2
10.35
(𝑑𝑀)/(𝑑𝑥)=−44.73+12.88 x + ( x2 x(x-0.562))
2
𝑑𝑚
=0
𝑑𝑥
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
That means in this range we can meet the maximum bending moment
So in order to that maximum bending moment can obtain when X=
2.17 m
𝑥
Then maximum bending moment is ; 𝑑𝑀=24.64+12.88×x× -
2
10.35
44.73×𝑥 +( 𝑥 (𝑥 − 0.562))^2
2
= -28.72
= -28.72 KNm
Shear
𝑑𝑀=24.64+12.88×𝑥×(𝑥/2)−44.73×𝑥+10.35×(0.75×4.5)(𝑥−2.25)
𝑑𝑚
=0
𝑑𝑥
Shear
𝑅1+𝑅2=26.97×2.4=64.73 𝑘𝑁
0= −17.44+27.05+(64.73 x (2.4/2))-2.4R2
R2 =36.4 KN
Solving two equation
R4 = 36.4 kN
R3 = 28.33 kN
26.97
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Bending
𝑑𝑀=17.44+26.97×𝑥×(𝑥/2)−28.33×𝑥
(𝑑𝑀)/(𝑑𝑥)=−28.33+26.97 x
𝑑𝑚
=0
𝑑𝑥
That means in this range we can meet the maximum bending moment
So in order to that maximum bending moment can obtain when X=
1.05 m
Then maximum bending moment is;
𝑑𝑀=17.44+26.97×𝑥×(𝑥/2)−28.33×𝑥
= 2.56 KNm
Shear
𝑑𝑆=28.33 -26.97x
= 0.01KN
(When X=1.05m) this means the at maximum bending moment point
the shear force is 0.01 KN
𝑑𝑆 = 0.01KN
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
0= −38.09+52.57+(156.3 x4.5/2)-4.5R6
R6 =81.9 KN
Solving two equation
R6 = 81.9 kN
R5 = 74.4 kN
Bending
Considering anticlockwise is positive
𝑥
𝑑𝑀=52.57+26.97×x× - 74.73×𝑥
2
(𝑑𝑀)/(𝑑𝑥)=−74.73+26.97 x
𝑑𝑚
=0
𝑑𝑥
Bending
𝑥 10.35
𝑑𝑀=52.57+26.97×x× – 74.4×𝑥 +( 𝑥 (𝑥 − 0.562))^2
2 2
10.35
(𝑑𝑀)/(𝑑𝑥)=−74.4+26.97 x + ( x2 x(x - 0.562))
2
𝑑𝑚
=0
𝑑𝑥
That means in this range we can meet the maximum bending moment
So in order to that maximum bending moment can obtain when X=
2.15 m
𝑥
Then maximum bending moment is ; 𝑑𝑀=52.57+26.97×x× -
2
10.35
74.4×𝑥 +( 𝑥 (𝑥 − 0.562))^2
2
= --32.65
= -32.65 KNm
Shear
Considering upward direction is positive
𝑑𝑆=74.4−26.97×𝑥− 10.35×(𝑥−0.562)
=-0.02
= -0.02
(When X=2.17 m)
𝑑𝑆 = -0.02 KN
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Bending
𝑑𝑀=52.57+26.97×𝑥×(𝑥/2)−74.4×𝑥+10.35×(0.75×4.5)(𝑥−2.25)
𝑑𝑚
=0
𝑑𝑥
Shear
𝑑𝑆=74.4−26.97× x− 10.35×(0.75×4.5)
= -27.15 KN
(When X= 2.47m)
𝑑𝑆 = - 27.15 KN
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
The same procedure can do for other load two load combinations
also, then it is need to find the bending moment diagram for the three
types of load combinations.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
(BM)
52.57
32.4
38.09
24.66 27.05
4
2.56
32.65
28.36
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
(SF)
74.4
24.64
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
75.2
60.2
58.2
46.1 36.0
25.0
16.3
44.1
59.2
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
105..5
80.1
30.2
40.4
88.3
99.2
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
49.8
43.2
34.2
30.
2
0.87
35.7
29.2
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
70.0
56.2
42.1
44.1
60.2
63.2
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
52.57
32.36
38.07
26.64
2.56
57.48
41.22
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
74.4
44.73
48.17
48.17
74.4
81.9
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Span 3
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Bending
Shear
𝑴𝒙
K=
𝒃𝒅𝟐 𝒇𝒄𝒖
𝟐𝟒.𝟔𝟒 𝒙 𝟏𝟎𝟔
=
𝟐𝟐𝟓 𝒙 𝟑𝟎𝟒𝟐 𝒙 𝟐𝟓
0.05
Z= [0.5 + √0.25 − ]d
0.9
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 013
225 𝑥 350
𝐴𝑠𝑚𝑖𝑛 = 102.4 𝑚𝑚2
Then 𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑝𝑟𝑜𝑣𝑖𝑑𝑒
Provided reinforcement area is 2T16
Then the required condition is satisfying. But in this case we need
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Design beam for flexure for span 1-2 mid span (flange L beam)
Maximum moment at span 1-2 = 57.48 kNm
Assume that main bar was 20 mm and stirrups was 6 mm bars and
assume that neutral axis is in the flange
𝐸𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ=350−30−6−20/2=304 𝑚𝑚
𝑴𝒙
K=
𝒃𝒅𝟐 𝒇𝒄𝒖
𝟓𝟕.𝟒𝟖 𝒙 𝟏𝟎𝟔
=
𝟐𝟐𝟓 𝒙 𝟑𝟎𝟒𝟐 𝒙 𝟐𝟓
0.11
Z= [0.5 + √0.25 − ]d
0.9
57.48 x 𝟏𝟎𝟔
As =
0.95x 460x 0.85 x304
As = 509.02 𝑚𝑚2
Then we can provide the 2T16 + 1T12, but we need to check the
required minimum reinforcement area
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18 (BS8110:1997 part 1 Table 3.25)
𝐴𝐶
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18
225 𝑥 350
𝐴𝑠𝑚𝑖𝑛 = 141.75 𝑚𝑚2
Then 𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑝𝑟𝑜𝑣𝑖𝑑𝑒 Then all the condition is satisfying
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝑴𝒙
K=
𝒃𝒅𝟐 𝒇𝒄𝒖
𝟑𝟐.𝟑𝟔 𝒙 𝟏𝟎𝟔
=
𝟐𝟐𝟓 𝒙 𝟑𝟎𝟒𝟐 𝒙 𝟐𝟓
0.06
Z= [0.5 + √0.25 − ]d
0.9
32.36 x 𝟏𝟎𝟔
As =
0.95x 460x 0.92 x304
As = 264.8 𝑚𝑚2
Then we can provide the 2T16, but we need to check the required
minimum reinforcement area.
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18
225 𝑥 350
𝐴𝑠𝑚𝑖𝑛 = 141.75 𝑚𝑚2
Then 𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑝𝑟𝑜𝑣𝑖𝑑𝑒 Then all the condition is satisfying
𝑴𝒙
K=
𝒃𝒅𝟐 𝒇𝒄𝒖
𝟐.𝟓𝟔 𝒙 𝟏𝟎𝟔
=
𝟐𝟐𝟓 𝒙 𝟑𝟎𝟒𝟐 𝒙 𝟐𝟓
0.004
Z= [0.5 + √0.25 − ]d
0.9
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18
225 𝑥 350
𝐴𝑠𝑚𝑖𝑛 = 141.75 𝑚𝑚2
Then 𝐴𝑠𝑚𝑖𝑛 > 𝐴𝑝𝑟𝑜𝑣𝑖𝑑𝑒
Then we need to provide the minimum reinforcement area
𝐸𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ=350−30−6−202=304 𝑚𝑚
𝑴𝒙
K=
𝒃𝒅𝟐 𝒇𝒄𝒖
𝟓𝟐.𝟓𝟕 𝒙 𝟏𝟎𝟔
=
𝟐𝟐𝟓 𝒙 𝟑𝟎𝟒𝟐 𝒙 𝟐𝟓
0.10
Z= [0.5 + √0.25 − ]d
0.9
As = 454.85 𝑚𝑚2
Then need to check the minimum reinforcement area to select the
provided reinforcement area
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18 (BS8110:1997 part 1 Table 3.25)
𝐴𝐶
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18
225 𝑥 350
𝐴𝑠𝑚𝑖𝑛 = 141.75 𝑚𝑚2
Then 𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑝𝑟𝑜𝑣𝑖𝑑𝑒 All required condition satisfy
𝐸𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ=350−30−6−202=304 𝑚𝑚
𝑴𝒙
K=
𝒃𝒅𝟐 𝒇𝒄𝒖
𝟒𝟏.𝟐𝟐 𝒙 𝟏𝟎𝟔
=
𝟐𝟐𝟓 𝒙 𝟑𝟎𝟒𝟐 𝒙 𝟐𝟓
0.08
Z= [0.5 + √0.25 − ]d
0.9
41.22 x 𝟏𝟎𝟔
As =
0.95x 460x 0.90 x304
As = 304 𝑚𝑚2
Then need to check the minimum reinforcement area to select the
provided reinforcement area
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18 (BS8110:1997 part 1 Table 3.25)
𝐴𝐶
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18
225 𝑥 350
𝐴𝑠𝑚𝑖𝑛 = 141.75 𝑚𝑚2
Then 𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑝𝑟𝑜𝑣𝑖𝑑𝑒 All required condition is satisfying
𝐸𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑑𝑒𝑝𝑡ℎ=350−30−6−202=304 𝑚𝑚
𝑴𝒙
K=
𝒃𝒅𝟐 𝒇𝒄𝒖
𝟑𝟖.𝟎𝟗 𝒙 𝟏𝟎𝟔
=
𝟐𝟐𝟓 𝒙 𝟑𝟎𝟒𝟐 𝒙 𝟐𝟓
0.073
Z= [0.5 + √0.25 − ]d
0.9
100 𝑥 𝐴𝑠𝑚𝑖𝑛
= 0.18
225 𝑥 350
𝐴𝑠𝑚𝑖𝑛 = 141.75 𝑚𝑚2
Then 𝐴𝑠𝑚𝑖𝑛 < 𝐴𝑝𝑟𝑜𝑣𝑖𝑑𝑒 All required condition is satisfying
Bar diameter = 20 mm
Minimum bar spacing > hagg + 5 mm = 19.05 + 5 = 25 mm (the used
aggregate size is ¾ inch)
(BS8110:1997 Cl 3.12.11.1
Bar spacing at most critical location with bars 1T12+ 2T16
Clear distance = (225 – 30 -30 – (6 x2) – 12-(16 x 2)/3 = 54.5 mm
Upper portion
𝑣𝑐 =0.56 N/mm2
𝒗𝒄+𝟎.𝟒=0.56+0.4=0.96 N/mm2
𝑣𝑐 = 0.62 𝑚𝑚2
𝒗𝒄+𝟎.𝟒=0.62+0.4=1.02 N/𝑚𝑚2
Shear force = 1.02 x 225 x 304 =69.8 KN
.𝟓𝒗𝒄=0.5×0.62=0.31 N/𝑚𝑚2
Shear force = 0.31 x 225 x 304 =21.2 KN
So then shear links are provided according to the following figure.
According to the BS8110:1997 Table 3.7
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
62
𝑆𝑣 ≤0.95×460×{2×(𝜋× )}/
4
(0.4×225)
≤275 𝑚𝑚
Upper portion
𝑣𝑐 =0.62 N/mm2
𝒗𝒄+𝟎.𝟒=0.62+0.4=1.02 N/mm2
Lower portion
𝑣𝑐 = 0.74 𝑚𝑚2
𝒗𝒄+𝟎.𝟒=0.74+0.4=1.14 N/𝑚𝑚2
Shear force = 1.14 x 225 x 304 =77.98 KN
.𝟓𝒗𝒄=0.5×0.74=0.37 N/𝑚𝑚2
Shear force = 0.37 x 225 x 304 =25.3 KN
Consider span 3-4
Upper portion
𝑣𝑐 =0.65 N/mm2
𝒗𝒄+𝟎.𝟒=0.65+0.4=1.05 N/mm2
Lower portion
𝑣𝑐 = 0.63 𝑚𝑚2
𝒗𝒄+𝟎.𝟒=0.63+0.4=1.03 N/𝑚𝑚2
Shear force = 1.03 x 225 x 304 =70.45 KN
.𝟓𝒗𝒄=0.5×0.63=0.32 N/𝑚𝑚2
Shear force = 0.32 x 225 x 304 =21.9 KN
Spacing for span 3-4
Design R/F
62
≤(0.95×460×{2×(𝜋× )} / (225×(1.19−0.65))
4
≤ 203.4 𝑚𝑚
62
𝑆𝑣 ≤0.95×460×{2×(𝜋× )}/
4
(0.4×225)
≤275 𝑚𝑚
62
≤(0.95×460×{2×(𝜋× )} / (225×(1.19−0.65))
4
≤ 203.4 𝑚𝑚
Span
=26
Effective depth
477− 𝑓𝑠
𝑀𝐹1=0.55+ ( 𝑀 )≤2
120 𝑥 [0.9+ ]
𝑏𝑑2
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝛽𝑏=1
1
𝑓𝑠=(2/3)×460×(509.02/515)×
1
= 303.1
MF1 =1.5 <2
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 =26 𝑥 1.5 𝑥 1
= 39
Then we can find the actual deflection as follows;
Span 4500
=
Effective depth 304
= 14.8
𝐴𝑐𝑡𝑢𝑎𝑙 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛<𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 So condition
satisfied. Therefore, safe under deflection
Consider span 2-3
In deflection check it is considering about the sagging moment which
is happened at the mid span of the beam
DeflectionActual ≤ Deflection𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 Condition should be satisfied
to safe under deflection
Span
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 = 𝑥 𝑀𝐹1 𝑋 𝑀𝐹2
Effective depth
Span
=26
Effective depth
477− 𝑓𝑠
𝑀𝐹1=0.55+ ( 𝑀 )≤2
120 𝑥 [0.9+ ]
𝑏𝑑2
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝛽𝑏=1
1
𝑓𝑠=(2/3)×460×(20.28/226)×
1
= 27.5
MF1 =4.4 > 2 But MF1 should less than the 2, therefore we select
MF1 as 2
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 =26 𝑥 2 𝑥 1
= 52
Then we can find the actual deflection as follows;
Span 2100
=
Effective depth 304
= 6.91
𝐴𝑐𝑡𝑢𝑎𝑙 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛<𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 So condition
satisfied. Therefore, safe under deflection
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Span
=26
Effective depth
477− 𝑓𝑠
𝑀𝐹1=0.55+ ( 𝑀 )≤2
120 𝑥 [0.9+ ]
𝑏𝑑2
2
𝑆𝑒𝑟𝑣𝑖𝑐𝑒𝑠 𝑠𝑡𝑟𝑒𝑠𝑠 𝑓𝑠 = (𝑓 1 𝐴𝑠,𝑅𝑒𝑞𝑢𝑖𝑟𝑒𝑑
3 𝑦)𝑥(βb ) 𝑥 𝐴
𝑠,𝑃𝑟𝑜𝑣𝑖𝑑𝑒𝑑
𝛽𝑏=1
1
𝑓𝑠=(2/3)×460×(304/402)×
1
= 231.91
MF1 = 1.98 < 2
𝐴𝑙𝑙𝑜𝑤𝑎𝑏𝑙𝑒 𝑑𝑒𝑓𝑙𝑒𝑐𝑡𝑖𝑜𝑛 =26 𝑥 1.98 𝑥 1
= 51.8
Then we can find the actual deflection as follows;
Span 4500
=
Effective depth 304
= 14.8
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
CHAPTER 5
DESING OF COLUMN
(SPECIMEN CALCULAION FOR THE COLUMN)
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
H-1
Dead load
Let’s consider this as a commercial building, then dead laod for the
residential building taken as = 18 KN /𝑚2
First of all it is need to decide the size of the column, for that purpose
consider this building section as the commercial building.
592.65 x 103
=
0.35 𝑥 24
= 70.55 𝑥 103 𝑚𝑚2
Then can obtain the size of the column as = √ 70.55 103 𝑚𝑚2
= 265.61mm
Then the column size is approximately = 250 x 250 𝑚𝑚2
.X-X direction
Y-Y direction
then
X –X direction
𝐿𝑒𝑥 = ᵝ𝑥 𝐿0𝑒
Y–Y direction
𝐿𝑒𝑦 = ᵝ𝑦 𝐿0𝑒
𝐿𝑒𝑦 4275
= = 17.1 > 10
𝑏 250
Axial Load
Dead load
Imposed load
The imposed load can reduce according to the floor vise also. the
BS 6399- proposed building is four story building so then reduction in total
Table 2 distributed imposed floor load is 30%.
30
Then total live load reduction = 26.34 KN x
100
= 7.902 KN
Then total imposed load = 26.34 -7.902
= 18.438 KN
100Asc
Minimum reinforcement area ; = 0.4
Ac
100Asc
= 0.4
250 x 250
Asc =6T12
Asc = 250 𝑚𝑚2 > 𝑝𝑟𝑜𝑣𝑖𝑑𝑒𝑑 𝑟𝑒𝑖𝑛𝑓𝑜𝑟𝑐𝑒𝑚𝑒𝑛𝑡 𝑎𝑟𝑒𝑎
57 KNm
. 24 KNm
𝑀1 = 24𝐾𝑁𝑚
𝑀2 = 57 𝐾𝑁𝑚
𝑀𝑖 = 0.4𝑀1 + 0.6 𝑀2 >=0.4 𝑀2
= 0.4 x 24 +0.6 x 57 = 43.8 KNm
𝑀𝑎𝑑𝑑 = 𝑁𝑎𝑢
N =255.15 𝐾𝑁
1 𝑙𝑒𝑥
ᵝ𝑒 = 𝑥 ( ′ )2
2000 𝑏
12
𝑏 ′ = 250 − 30 − ( ) −6
2
= 208 mm
1 3180 2
ᵝ𝑒 = 𝑥( )
2000 208
ᵝ𝑒 = 0.116
𝑀𝑎𝑑𝑑 = 𝑁𝑎𝑢
= 255.15 x 0.029 = 7.39 𝐾𝑁𝑚
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝑁 255.15 𝑥 103
= = 4.08
𝑏ℎ 250 𝑥 250
𝑀 64.39 𝑥 106
= = 4.12
𝑏ℎ2 250 𝑥 250 𝑥 250
Then k is approximately = 1
BS 8110 -
100 𝑥 𝐴𝑠
part 3 = 2.4
𝑏𝑥ℎ
100 𝑥 𝐴𝑠
= 2.4
250 𝑥 250
𝐴𝑠 =
4T20 +2T16
𝐴𝑠 = 1500 𝑚𝑚2
100Asc
Minimum reinforcement area ; = 0.4
Ac
100Asc
= 0.4
250 x 250
Deflection of column
Clause 3.8.5
Since the end condition is 1 at top and the bottom and the design
column is unbraced column then
𝑙𝑒 ᵝ𝑙0 1.2 x 3000
BS 8110- Then = = =14.4 mm < 30
ℎ ℎ 250
1997- Table
3.20 Then no need to check for the deflection
Crack control
N > 0.2𝑓𝑐𝑢𝐴𝑐
𝑁 300 𝑥 103
= = 4.8
𝑏ℎ 250 𝑥 250
𝑀 64.39 𝑥 106
= = 4.12
𝑏ℎ2 250 𝑥 250 𝑥 250
100 𝑥 𝐴𝑠
= 2.8
250 𝑥 250
𝐴𝑠 = 6T20
𝐴𝑠 = 1750 𝑚𝑚2
G-2
Dead load
Let’s consider this as a commercial building, then dead laod for the
residential building taken as = 18 KN /𝑚2
First of all it is need to decide the size of the column, for that purpose
consider this building section as the commercial building.
1543.39 x 103
=
0.35 𝑥 24
= 183.74 𝑥 103 𝑚𝑚2
Then can obtain the size of the column as = √ 183.74 𝑥 103 𝑚𝑚2
= 428.64mm
Then the column size is approximately = 450 x 450 𝑚𝑚2
450
.X-X direction
Y-Y direction
then
X –X direction
𝐿𝑒𝑥 = ᵝ𝑥 𝐿0𝑒
Y–Y direction
𝐿𝑒𝑦 = ᵝ𝑦 𝐿0𝑒
𝐿𝑒𝑥 3975
= = 8.8 < 10
ℎ 450
𝐿𝑒𝑦 4275
= = 9.5 < 10
𝑏 450
Axial Load
Dead load
Imposed load
The imposed load can reduce according to the floor vise also. the
proposed building is four story building so then reduction in total
distributed imposed floor load is 30%.
30
Then total live load reduction = 80.70 KN x
100
= 24.21 KN
Then total imposed load = 80.70 -24.21
= 56.49 KN
100Asc
Minimum reinforcement area ; = 0.4
Ac
100Asc
= 0.4
450 x 450
Asc =
Asc = 810 𝑚𝑚2 < 𝑝𝑟𝑜𝑣𝑖𝑑𝑒𝑑 𝑟𝑒𝑖𝑛𝑓𝑜𝑟𝑐𝑒𝑚𝑒𝑛𝑡 𝑎𝑟𝑒𝑎 4T20
20
𝑏 ′ = ℎ′ = 450 − 30 − ( ) − 10
2
= 400 mm
Biaxial bending
𝑀𝑥 57.43 𝑥 103
= = 143.575
h′ 400
𝑀𝑦 4.3 𝑥 103
= = 10.75
b′ 400
𝑀𝑥 𝑀𝑦
>
h′ b′
h′
𝑀𝑥′=𝑀𝑥+𝛽 𝑀𝑦
b′
Then it is need to find the ᵝ′ value
𝑁 656.915 KN
= = 0.14
𝑏ℎ𝑓𝑐𝑢 450 𝑥450 𝑥 24
ᵝ = 0.836
400′
𝑀𝑥′=57.43kNm +0.836 𝑥 𝑥 4.3 kNm
400
=61.025 kNm
h′
𝑀y′=𝑀y+𝛽 𝑀x
b′
400′
𝑀𝑥′=4.3 kNm +0.836 𝑥 𝑥 57.43 kNm
400
= 52.31 kNm
𝑀
=(61.025 x 106 )/( 450 𝑥 4502 )
𝑏ℎ2
=0. 7
𝑁 656.9 𝑥 103
= = 3.24
𝑏ℎ 450 𝑥 450
.
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝐴𝑠 = 810 𝑚𝑚2
100Asc
Minimum reinforcement area ; = 0.4
Ac
100Asc
= 0.4
450 x 450
Deflection of column
Since the end condition is 1 at top and the bottom and the design
column is unbraced column then
𝑙𝑒 ᵝ𝑙0 1.2 x 3000
Then = = =8 mm < 30
ℎ ℎ 450
Crack control
N > 0.2𝑓𝑐𝑢𝐴𝑐
𝑁 972 𝑥 103
= = 4.8
𝑏ℎ 450 𝑥 450
𝑀 61.0 𝑥 106
= = 0.72
𝑏ℎ2 450 𝑥 450 𝑥 450
100 𝑥 𝐴𝑠
= 0.4
450 𝑥 450
CHAPTER 6
DESING OF FOUNDATION
(SPECIMEN CALCULAION FOR THE FOUNDATION)
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Axial Load
Dead load
Imposed load
The imposed load can reduce according to the floor vise also. the
proposed building is four story building so then reduction in total
distributed imposed floor load is 30%.
30
Then total live load reduction = 114.325 KN x
100
= 34.29 KN
Then total imposed load = 114.325 -34.29
= 80.03 KN
Let’s consider the imposed load (Live load) as 300 KN and let’s
consider the bearing capacity of soil is 200 KN / 𝑚𝑚2
𝑆𝑒𝑟𝑣𝑖𝑐𝑒 𝑙𝑜𝑎𝑑
𝐵𝑎𝑠𝑒 𝑎𝑟𝑒𝑎 =
ớ𝑏𝑐
858.316 + 300
𝐵𝑎𝑠𝑒 𝑎𝑟𝑒𝑎 =
250
= 4.63 𝑚2
X 4.63 𝑚2
X
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
d > 10√𝑁𝑢𝑙𝑡
= 1681.64 KN
3
d > 10√1681.64 𝑥 10
d > 410 mm
1158.316+55.47
Bearing pressure =
2.4 𝑥 2.4
1158.316+55.47
Bearing pressure =
2.4 𝑥 2.4
Reinforcement design
N = 1.4 𝐺𝑘 + 1.6𝑄𝑘
= 1681.64 KN
𝑀
𝑘=
𝑏𝑑2 𝑓𝑐𝑢
333.042 𝑥 106
𝑘=
450 𝑥 4502 𝑥 24
= 0.152 < 0.156 then this is satisfying for singly reinforcement
condition.
𝑀
𝐴𝑠 =
0.95𝑓𝑦 𝑧
333.042 𝑥 106
𝐴𝑠 = = 1823.23 𝑚𝑚2
0.95 𝑥 460 𝑥 418
Then provided reinforcement area is;
𝑉
v=
𝑏𝑑
374.86 𝑥 103
v=
2400 𝑥 440
= 0.355 N / 𝑚𝑚2
𝑉𝑐 = 0.34
𝑆𝑣 <= 38.86
Then minimum shear links spacing = 35 mm
S< 0.75d
S < 0.75x 440
S < 330 mm
𝑉
V=
𝐶𝑜𝑙𝑢𝑚𝑛 𝑝𝑒𝑟𝑖𝑚𝑒𝑡𝑒𝑟 𝑋 𝑑
1681.64 𝑥 103
V=
450 𝑥 4 𝑥 440
So then it is satisfying
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
Punching shear
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
𝑉
v=
𝑏𝑑
767.83 𝑥 103
v=
2400 𝑥 440
= 0.25 N / 𝑚𝑚2
𝑉𝑐 = 0.34
3d = 3 x 440 =1320 mm
Anchoring
Detailing
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190
JAYASEKARA J M P L M BSC.ENG (HONS), REG NO : 190