EEE3100S 2023 Tutorials 6-7
EEE3100S 2023 Tutorials 6-7
Question 1
Give three main reasons why we need to control frequency in power system.
Question 2
Two generators are supplying power to a power system. Their power ratings are
P1 = 50 MW and P2 = 500 MW. The frequency is 60 Hz and the generators are
half-loaded. The system load increases by 110 MW and as a result, the frequency
drops to 59.5Hz. What must the individual regulations (Sg) be, if the ratio of the
change in output of the two generators is same as the ratio of their rating?
Question 3
a) What does a 5% speed droop mean?
b) Assuming a two-area power system has one generator in each area, with a total system
demand of 250 MW (Table Q3). Generator A and B contribute 150 MW and 100 MW,
respectively, to meet the load demand. Following a sudden load increase, the system
frequency dropped from the nominal value to 49.5 Hz. What is the magnitude of this
load increase and the new power output from generator A and generator B?
Table Q3
Network specifications
Gen A Gen B
Generator droop characteristic (p.u.) 0.1 0.05
Rated power output (MW) 200 150
Pre-contingency scheduled power (MW) 150 100
Nominal frequency (Hz) 50
Question 4
Question 5
State TRUE/FALSE for the following
Question 6
Discuss the relationship between voltage magnitude and the reactive power flow. How does
SIL relates to reactive power?
Question 7
Due to contingencies in the power system, certain points in the network may experience over
voltage or under voltages. When such occurs, the system operator is tasked with
implementation certain measures to curb the problem. List three of that a system operator can
use to curb:
a) Under Voltages
b) Over Voltages
Question 8
List the three different voltage control schemes. Discuss each of these control schemes and
what it entails.
Question 9
List three devices that can be used to provide static reactive power compensation and three
devices for dynamic reactive power compensation. For each of these categories, state the main
characteristic of each.
Question 10
According to the South African grid code, what is voltage Ride Through Capability of RPP?
University of Cape Town EEE3100S, 2023
Department of Electrical Eng. Tutorials 6- 7 – Frequency and Voltage
ControlPower Control