Frents Technology
Frents Technology
Compressive strength at 28 days curing time: ⚫ CEB can be pressed from humid earth.
217 psi Flexural strength at 28 days curing time: Because it is not wet, the drying time is much
11 psi shorter. Some conditions permit the block to go
straight from the press onto the wall. A single
✓ Diagonal shear strength at 28 days curing mechanical press can produce from 800 to over
time: 13 psi 5,000 blocks per day, enough to build a 110
Construction time of 8 to 9 square meter wall: square meter house in one day.
1.89 hours Shipping cost: Suitable soils are often available
✓ Direct Cost per square meter as of 1991: P at or near the construction site. Adobe and CEB
217.49 per square meter are of similar weight, but distance from a source
supply gives CEB an advantage. Also, CEB can be
✓ Frents Block came out to be the most cost- made available in places where adobe
efficient. It used the least amount of materials manufacturing operations are non- existent.
and the second least labor cost to build a 1
square meter wall. Uniformity: CEB can be manufactured to a
predictable size and has true flat sides and 90
COMPRESSED EARTH BLOCKS degree angle edges. This makes design and
costing easier. This also provides the contractor
Compressed Earth Block often referred to simply
the option of making the exterior look like
as CEB, are a type of manufactured construction
conventional stucco houses.
material formed in a mechanical press that
forms an approximate mix of dirt, non- CEB had very limited use prior to the 1980s. It
expensive clay, and an aggregate into a was known in the 1950s in South America,
compressed block. CEB blocks are installed onto where the Cinva Ram was developed by a
the wall by hand and slurry made of a soupy Colombian Engineer. The Cinva Ram is a lever-
version of the same dirt/clay mix, sand action, manual press that makes one block at a
aggregate, is spread or brushed very thinly time.
between the blocks for bonding. There is no use
of mortar in the traditional sense. During the 1980s, soil-pressing technology
became widespread. France, England, Germany
and Switzerland began to write standards. The
peace Corps, USAID, Habitat for Humanity and stucco wire/ stucco cement and or lime plaster.
other programs began to implement it into Stabilized blocks create a brick wall that if
housing projects. properly stabilized can be left exposed with no
outer plaster finish.
Construction method is simple. Less skilled
labor is required; wall construction can be done Foundations: Standards for foundations are
with unskilled labor encouraging self- sufficiency similar to those for brick walls. A CEB wall is
and community involvement. If the blocks are heavy. Footings must be at least 10" thick, with
stabilized with cement and or fly ash, they can a minimum width that is 33% greater than the
be used as bricks and assembled using standard wall width. If a stem wall is used, it shall extend
masonry techniques of brick-laying. to an elevation not less than 8" (203mm) above
the exterior finish grade. Rubble-filled
Soil mix conditions: The soil mix is 15% - 40%
foundation trench designs with a reinforced
non-expansive clay, 25%-40% silt powder, and
concrete grade beam above are allowed to
sharp sand to small gravel content of 40% -70%.
support CEB construction.
The more modem machines do not require
aggregate (rock) to make a strong soil block for The CEB code is different from the adobe code
most applications. Soil moisture content ranges in numerous aspects. For instance, the CEB code
from 4% to 12% by weight. Clay with a plasticity allows slip mortars and permit blocks ejected
index (PI) of up to 25 or 30 would be acceptable from a press to go directly to the wall.
for most applications. The Pl of the mixed soil
CEB Strength: Using ASTM D1633-00
(clay, silt and sand/gravel combined) should not
stabilization standard, a pressed and cured
exceed 12 to 15; that is the difference between
block must be submerged in water for four
the Upper and Lower Atterburg Limits, as
hours. It is then pulled from the water and
determined by laboratory testing.
immediately subjected to a compression test.
The blocks must score at least 300 pound-force
per square inch (psi) minimum. This is a higher
Other Advantages standard than for adobe, which must score an
✓ Non-toxic: materials are completely natural average minimum of 300 psi.
and do not out-gas toxic materials. It must be emphasized that the compressive
strength minimums for code compliance are
✓ Sound resistant: an important feature in high-
nothing like the true strength of CEB blocks.
density neighborhoods, residential areas
New Mexico only sought to assure that CEB
adjacent to industrial zones
would be at least as strong as adobe. The blocks
Fire resistant: earthen walls do not burn are strong. CEB can have a compressive strength
as high as 2000 psi. Blocks with compressive
Insect resistant: the walls are solid and very
strengths of 1200 psi to 1400 psi are common.
dense, discouraging insects
Thermal advantages: Also, due to the enormous
Mold resistant: there is no cellulose material
mass, these are monolithic walls CEB has
such as in wood, oriented strand board or
excellent thermal performance, reducing
drywall that can host mold. Completed walls
heating and cooling costs.
require either a reinforced bond beam or a ring
beam on top or between floors (8") and if the Thermal testing" From May 31 to June 3, 2004,
blocks are un-stabilized a plaster finish, usually the Biology Department of Southwest Texas
Junior College, Del Rio, Texas, conducted tests Use:
for thermal change on three structures:
Exterior and Interior Facing Panels
concrete blocks, adobe and compressed earth
block. Results indicate the interior temperature Wall Type:
of the adobe and CEB modules were
significantly lower than for concrete blocks. Masonry, metal framed.
With a minimum ambient temperature of 107° F •
(42°C), the interior temperatures were:
Size:
Concrete Module: 111° F (44° C) (4° F above
ambient) •
CEB Module: 91° F (33° C) 1.20 meters x 2.40 meters x 1⁄2 inch thickness
Framed or moldings.
CEMENT WOOD Type: .
Composite: Laminated Method of Attachment:
⚫ Description:
Face: Screws or nails. Back: Clips or screws
Remarks:
•
Edges of cement-bound mineral fiber board
Facing Panel: Rigid Boards or heavier gauge faced panels commonly open. Edges of metal
metal sheets laminated to an insulating core of faced panels generally closed and formed to:
various thicknesses. May be made interlock; to receive gaskets; or to fit a curtain
sufficiently rigid to function as wall panels; or wall grid system.
sufficiently thin to be used as glazing panels. NEW TECHNOLOGIES IN CONSTRUCTION
Edges may be formed or open. MATERIALS
⚫ Roofing System
Exterior Face:
Most tensile structures are supported by some Common materials for doubly-curved fabric
form of compression or bending elements, such structures are PTFE coated fiberglass and PVC
as masts (as in The O2, formerly the Millenium coated polyester. These are woven materials
Dome), compression rings or beams. with different strengths in different directions.
The warp fibers (those fibers which are
Tensile membrane structures are most often originally straight-equivalent to the starting
used as roofs as they can economically and fibers on a loom) can carry greater load than the
attractively span large distances. History weft or fill fibers, which are woven between the
This form of construction has only become well warp fibers.
understood and widespread in large structures Cables
in the latter part of the 20th century. Tensile
structures have long been used in tents, where Cables can be of mild steel, high strength
the guy ropes provide pre-tension to the fabric (drawn carbon steel), stainless steel polyester or
& allow it to withstand loads. Russian Engineer aramid fibers. Structural cables are made of a
Vladimir Shukhov was one of the first to develop series of small strands twisted or bound
practical calculations of stresses and together to form a much larger cable. Steel
deformations of tensile structures, shells and cables
membranes. Shukhov designed 8 tensile
are either spiral strand, where circular rods are
structures and thin-shell structures exhibition
twisted together and "glued" using polymer, or
pavilions for the Nizhny Novgorod Fair of 1986
locked coil stand, where individual interlocking
covering an area of 27,000 square miles. A very
steel strands form the cable (often with a spiral
early large-scale use of a membrane-covered
strand core).
tensile structure is the Sidney Myer Music Bowl,
constructed in 1958. ✓ Pretension
- Indoor or outdoor installation - Plumbing free The toilet's main features are:
n
position during installation. Does not require
Large objects like beverage cans, disposable any type of flushing mechanism, no mechanical
nappies or other objects accidentally dropped risk failure No water, no plumbing, no sewer
down the chute will not block the system. It is connections, no use of chemical
however not advisable to do this.
Features
Roof
Walls
At present, construction, renovation and Internal & Solar Heat Gain (kWh)
demolition of housing account for a large
One Floor (Bungalow)
amount of material consumption and direct or
embodied energy required to produce, or One-and-a-half Floor (split-level)
dispose of them. In addition, heating, cooling,
Two Floors (Cottage)
3011 Single Family Detached
2259 Semi-detached
1506 Rowhouse
3505 Roof
4740 1506
5209 1506
6907 1506
6907 Walls
6907 5209
10601 3261
8812 1313
6852 Doors/Windows
13257 6907
12529 6907
10085 6907
37282 Basement
12824 6852
35246 5002
12355 3156
30599 Infiltration
11754 10085
Intensive green roofs are designed for more 3. Help decentralize shelter activities and
complex planting systems. They may contain strengthen the capacity of LGUs to meet their
several feet of substrate and can support a wide sector mandates as set out in the Local
variety of vegetation, such as large shrubs or Government Code.
small trees. The benefits of green roofs range
DPUCSP is comprised of three components.
from the various ecological considerations, to
economic paybacks, as well as their contribution 1.
to the general well-being of the users and the
community. 2.
✓ Provides decent housing to low income Part C, provides capacity building and project
families ✓ Program of the National Shelter implementation support programs for the
Program national government, LGUs and other
stakeholders to improve decentralized shelter
✓ Providing loans to local government units delivery.
3.
Greater private sector involvement through c. Development of urban areas conducive to
participation of MFIs and other financing commercials and industrial activities which can
intermediaries; and generate more economic
Land Use Plan refers to the rational approach of Zonal Improvement Program or ZIP refers to the
allocating available land resources as equitably program of the National Housing Authority of
as possible among competing user groups and upgrading and improving blighted squatter
for different functions consistent with the areas within the cities and municipalities of
development plan of the area and the Program Metro Manila pursuant to existing statutes and
under this Act. pertinent
✓ Habitat houses are sold to home partner ✓ An affiliate chooses homeowners based on
families at no profit. Home partners repay their level of need, their ability to repay the loan
through affordable zero-interest, inflation- and their willingness to work in partnership with
adjusted mortgage loans. These monthly Habitat. Affiliates follow a non-discriminatory
mortgage payments are pooled into a Fund for policy of family selection. Religion is not a factor
Humanity so that the amortization of one house in choosing the families to become Habitat
will help build another. A House for a House homeowners.
principle. Funding Habitat's Work
✓ Habitat for Humanity is not a "giveaway" ✓ Donors may choose to sponsor one-third of a
program. In addition to an initial down payment home partner's house costs; the home partner
of one-third of the house cost and monthly saves up the one-third while the International
mortgage repayments, homeowners invest Habitat Community provides the rest. Thus a 25
hundreds of hours of their own labor, "sweaty to 30 sqm. concrete house that costs P 70,000
equity", into building their Habitat house and today can be built for a donation of only P
the houses of others. 25,000. This funding scheme called "Save and
Build" helps potential home partners better
✓ Additional "muscle" for construction comes
afford a house and to promote a savings culture
from volunteers from local affiliates, partner
among them.
corporations and organizations, universities,
school and youth groups. Volunteers even come Habitat Programs
from other countries as far as Europe and the
United States. Working with Others, Achieving "I've never known a Habitat volunteer who
More bought one's own tools and traveled at one's
own expense and worked hard without
✓ Habitat for Humanity's work is accomplished payment, that wasn't convinced that at the end
by affiliates; independent, locally-run, non-profit of that challenge that their sacrifice had been
volunteer groups. Each affiliate's coordinates all relatively insignificant to the blessing that they
aspects of Habitat home building in its areas. have received."-Former US President Jimmy
The affiliate selects prospective partner families Carter.
and secures suitable sites. It organizes mortgage
services, fund-raising and donations of materials
Since 1988, thousands of volunteers have joined With some schools and colleges, service with
Habitat building events. People are excited Habitat can be credited with the requirements
because they can see that they are making a of the National Service Training Program.
difference. Habitat's builds take place in over (NSTP).
100 communities across the Philippines.
Building on Faith with Families
Volunteers of all ages and backgrounds team up
for a common purpose: to provide simple, 0
decent, affordable houses for low-income
families. These builds are made possible Ever since Millard and Linda Fuller started
through the aid of sponsors, resources and building houses with the poor through a
volunteers. "partnership ministry' at Koinonia Farm, a
Christian Community in Georgia, USA, and the
✓ Youth Build work of Habitat for Humanity has been carried
out by various churches and faith-based
It is not how much you do, but how much you
communities worldwide.
Love you put into the doing that matters." -
Mother Theresa As the Articles of Incorporation of Habitat for
Humanity International state, the first purpose
of the organization is to "witness to the gospel
of Jesus Christ throughout the world by working
in cooperation with God's people in need to
✓ create a better habitat in which to live and
work."
0
In the Philippines, the involvement of churches
o
and faith-based communities with the housing
0 ministry has been called "Building on Faith with
Families." Through Habitat, churches and faith-
Youth Build is Habitat's program to involve the
based organizations can give tangible expression
youth in the ministry of ending poverty housing.
to the love of God through the work of
Through Youth Build, thousands of youth high
eliminating poverty housing, and mobilize
school and college students, out of school
families to bring hope and transform the lives of
youth, young professionals, and church youth
needy families.
groups have been helping needy Filipino
families build decent, durable and affordable What can churches and faith based
homes. organizations do?
Adopt a community. Regularly visit a Habitat Among the business corporations that have held
community to share the word of God and corporate builds with Habitat for Humanity
discuss how it applies to their everyday lives, as Philippines are ING Bank which sponsored one
persons, families, or as a community. Nurture hundred houses to mark their 15h year in the
families and help promote God-centered values. country, Dole Asia, the Ayala Group of
Designs programs for livelihood, primary health Companies, the Philippine Daily Inquirer, and
care, proper waste management, etc. Caltex Philippines. Business groups have also
held builds, such as the Makati Business Club
Coordinate volunteer efforts & donations.
and the Young Presidents Organization.
Designate someone from the church, parish or
community to handle inquiries on volunteering, Community Build
or to accept donations in Habitat's name for
0
transmittal to Habitat Philippines.
Local governments or community specific
Raise Funds. Hold a special or second collection;
associations or non-government organizations
out up a donation box; organize a fund-raising
can initiate build projects for residents or
activity to raise funds for a Habitat house.
neighbors living in poverty housing, and obtain
Educate and advocate. Raise the consciousness the assistance of Habitat for Humanity
of other people in church, parish or community, Philippines.
or even at work on the difficulties faced by the
An example is the BASECO Project, which was
poor in finding decent, durable and affordable
initiated by the local government of Manila.
shelter. Advocate the Habitat ministry as a
Another example is the Dreamland Heights
response to the problem of poverty housing in
Project, which was initiated by the Muntinlupa
your area whether it be building or renovating
Development Foundation, a non-government
homes.
organization composed of concerned citizens of
Corporate Build Muntinlupa, to resettle Muntinlupa residents
who lived in informal-settler
0
Volunteers also came from a formerly Average Floor Area: Project Type: Technology:
antagonistic community made up of a largely Balatas Relocation Housing Site
Christian indigenous people/cultural community
known as the B'laan. Today, the two Barangay Balatas, Naga City
communities are at peace with one another.
Donated by Local Government Unit of Naga City
Furthermore, with the construction skills Local Government of Naga City Fiscal Year 2007-
learned by the BUFANCO home partners, they 2008
have now found work in other construction
100 units
projects in the municipality.
8.920 square meters
Future Peace Builds: The Proposed Habitat Build
for Peace in Mindanao 50.00 square meters
While both methods achieve the objective of Because wind loads are considered horizontal
providing reserve capacity against unexpected forces, wind pressure, for design purposes,
conditions, use of load factors offers the should be assumed to be applied to the gross
advantage of greater flexibility in design of a area of the vertical projection of that portion of
system for a combination of different loading, that building above the average level of the
because a different load factor can be assigned adjoining round. Although the loads are
to each type of loading in accordance with assumed to be horizontal, they may
probability of occurrence and effects of other nevertheless apply either inward pressures or
uncertainties. suctions to inclined and horizontal surfaces. In
any case, wind loads should be considered to
Safety factors for various building systems act normal to the exposed building surfaces.
DISASTER RESISTANT BUILDINGS Furthermore, wind should be considered to be
likely to come from any direction unless it is
⚫ Wind Protection
known for a specific locality that extreme winds
may come only from one direction. As a
consequence of this assumption, each wall of a
rectangular building should be considered in the magnitude, direction, and duration of the
design to be the subject to the maximum wind maximum wind loads that may be imposed on
load. any portion of a specific building.
Although fires in buildings can be avoided, they 8. Enclose with protective materials structural
nevertheless occur. Some of the reasons for this components that may be damaged by fire
are human error, arson, faulty electrical (fireproofing).
equipment, poor maintenance of heating 9. Provide refuge areas for occupants and safe
equipment, and natural causes, such as evacuation routes to outdoors.
lightning. Consequently buildings should be
designed to minimize the probability of a fire 10. Provide means for removal of heat and
and to protect life and property damage if a fire smoke from the building as rapidly as possible
should occur. The minimum steps that should be without exposing occupants to these hazards,
taken for the purpose are as follows: with the air-conditioning system, if one is
present, assisting the removal by venting the
1. Limit potential fire loads, with respect to both building and by pressurizing smoke-proof
combustibility and ability to generate smoke towers, elevator shafts, and other exits.
and toxic gasses.
11. For large buildings, install standby so they will not spread from building to
equipment for operation in emergencies of building.
electrical system and elevators.
One way that building codes try to achieve this
Fire Loads and Resistance Ratings objective is to establish fire zones or fire limits
that restrict types of construction or occupancy
The nature and potential magnitude of fire in a
that can be used. Additional zoning regulations
building are directly related to the amount and
establish minimum distances between buildings.
physical arrangement of combustibles present,
Another way to achieve the objective is to
as contents of the building or as materials used
specify the type of construction that can be
in its construction. Because of this, all codes
used for enclosing the exterior of the building.
classify buildings by occupancy and
The distance between adjoining buildings, fire
construction, because these features are related
rating, and stability when exposed to fire of
to the amount of combustibles.
exterior walls, windows, and doors, and percent
The total amount of combustibles is called the of window area are some factors taken into
fire load of the building. Fire load is expressed in account in building codes for determination of
pounds per square foot (psf) of floor area, with construction classification of a building. The
an assumed calorific value of 7000 to 8000 prevent spread of fire from roof to roof, building
Btulb. (This Btu content applies to organic codes also often require that exterior walls
materials similar to wood and paper. Where extend as a parapet at least 3 ft. above the roof
other materials are present in large proportions, level. Parapets are also useful in shielding
the weights must be adjusted accordingly. firefighters who may be hosing a fire from roofs
of buildings adjoining the one on fire. In
National Institute of Standards and Technology addition, building should be topped with roof
burnout tests presented in Report BMS92 coverings that are fire resistant.
indicate a relation between fire load and fire
severity. The Underwriters Laboratories ✓ Fire Divisions
"Building Materials List" tabulates fire ratings for
To prevent spread of fires vertically in building
materials and assemblies it has tested. Every
interiors, building codes generally require that
building code specifies required fire-resistance
floor-ceiling and roof-ceiling assemblies be fire
ratings for structural members, exterior walls,
resistant. The fire rating of such assemblies is
fire divisions, fire separations, ceiling-floor
one of the factors considered in determination
assemblies, and any other constructions for
of the construction classification of a building.
which a fire rating is necessary.
Also, openings in floors and roofs should be fire-
Building codes also specify the ratings required protected, although building codes do not
for interior finish of walls, ceilings and floors. usually require this for one-storey or two-storey
These are classified as to flame spread, fuel dwellings. For the purpose, an opening such as
contributed, and smoke developed, determined that for a stairway may be protected with a fire-
in standard tests performed according to ASTM resistant enclosure and fire doors. In particular,
E84 or ASTM E119. Fire and Smoke Barriers stairways and escalator and elevator shafts
should be enclosed, not only to prevent spread
A major consideration in building design is
of fire and smoke but also to provide a
safety of the community. Hence, buildings
protected means of egress from the building for
should be designed to control fires and smoke
occupants and of approach to the fire source by
firefighters.
To prevent spread of fire and smoke horizontally Openings between floors for pipes, ducts,
in building interiors, it is desirable to partition wiring, and other services should be sealed with
interiors with fire divisions. A fire division is any the equal of positive firestops. Partitions
construction with the fire-resistance rating and between each floor and a suspended ceiling
structural stability under fire conditions above are not generally required to be extended
required for the type of occupancy and to the slab above unless this is necessary for
construction of the building to bar the spread of required compartmentation. But smoke stops
fire between adjoining buildings or between should be provided at reasonable intervals to
parts of the same building on opposite sides of prevent passage f smoke to non-involved areas.
the division. A fire division may be an exterior
Height and Area Restrictions
wall, fire window, fire door, fire wall, ceiling, or
firestop. Limitations on height and floor areas included
between fire walls in an storey of a building are
given in every building code and are directly
related to occupancy and construction. From
the standpoint of fire protection, these
A fire wall should be built of incombustible provisions are chiefly concerned with safety to
material, have a fire rating of at least 4 hour, life. They endeavor to ensure this through
and extend continuously from foundations to requirements determining minimum number of
roof. Also, the wall should have sufficient exits, proper location of exits, and maximum
structural stability in a fire to allow collapse of travel distance (hence escape time) necessary to
construction on either side without the wall reach a place of refuge. The limitations are also
collapsing. Building codes restrict the size of aimed at limiting the size of fires.
openings that may be provided in a fire wall and
require the openings to be fire- protected. Unlimited height and area are permitted for the
most highly fire-resistant type of construction.
To prevent spread of fire through hollow spaces, Permissible heights are decreased with
such spaces should be fire-stopped. A firestop is decrease in fire resistance of construction.
a solid or compact, fight closure set in a hollow,
concealed space in a building to retard spread Installation of automatic sprinklers increases
of flames, smoke or hot gases. All partitions and permissible heights and areas in all classes,
walls should be firestopped at every floor level, except those allowed unlimited heights and
at the top-storey ceiling level, and at the level of areas. Permissible unlimited heights and areas
support for roofs. Also, very large unoccupied in fire-resistive buildings considered generally
attics should be subdivided by firestops into satisfactory in the past may actually not be safe.
areas of 3000 ft or less. Similarly, any large A series of fires involving loss of life and
concealed space between a ceiling and floor or considerable property damage opened the fire
roof should be subdivided. For the purpose, safety of such construction to question. As a
firestops extending the full depth of the space result, building code regulations applicable to
should be placed along the line of supports of high-rise buildings has been made more
structural members and elsewhere, if necessary stringent. Many building codes prohibit floor
to enclose areas not exceeding 1000 ft2 when areas of unlimited size unless the building is
situated between a floor and ceiling or 3000 ft2 provided with sprinklers. Without automatic
when located between a ceiling and roof. sprinklers, floor areas must be subdivided
(compartmentalized) into fire wall protected
areas and the enclosing fire walls must have a 1 2. Class B fires involve flammable liquids where
or 2 hour fire ratings, depending on occupancy smothering is effective & where a cooling agent
and construction. ("Life Protection Handbook" must be applied with care. 3. Class C fires are
and "Fire Protection Handbook," National Fire those in live electrical equipment where the
Protection Association) extinguishing agent must be non-conductive.
Since a continuing electrical malfunction will
✓ Fire-Resistance Classification of Buildings keep the fire source active, circuit protection
Although building codes classify buildings by must operate to cut off current flow, after which
occupancy and construction, there is no an electrically conductive agent can be used
universal standard for number of classes of with safety.
either occupancy or construction. For specifics, 4. Class D fires involve metals that burn such as
refer to the Philippine National Building Code, magnesium, sodium and powdered aluminum.
Chapter 4: Types of Constructions". Note
Special powders are
however, that codes do not relate life-safety
hazards to the actual fire load, but deal with
them through requirements for exit
arrangements, interior finishes, and ventilation. necessary for such fires, as well as special
training for operators. These fires should never
✓ Extinguishment of Fires be attacked by untrained personnel.
Design of all buildings should include provisions Automatic Sprinklers. The most widely used
for prompt extinguishment of fires. Apparatus apparatus for fire protection in buildings is the
installed for the purpose should take into automatic sprinkler system. In one or more
account the nature and amount of combustible forms, automatic sprinklers are effective
and smoke-producing materials that may be protection in all occupancy classes. Special
involved in a fire. Such apparatus may range treatment and use of additional extinguishing
from small, hand-held extinguishers for small agents, though, may be required in many high-
fires to hoses attached to a large, pressurized hazard, industrial, and storage occupancies.
water supply and automatic fire sprinklers. Also Basically, a sprinkler system consists of a
desirable are fire and smoke detectors and a network of piping installed at the ceiling or roof
protective signaling system that sounds an and supplied with water from a suitable source.
alarm to alert building occupants and calls fire On the piping at systematic intervals are placed
fighters. heat-sensitive heads, which discharge water
when a predetermined temperature is reached
. Classes of Fires. For convenience in defining
at any head. A gate valve is installed in the main
effectiveness of extinguishing media,
supply and drains are provided. AN alarm can be
Underwriter Laboratories, Inc., has developed a
connected to the system so that local and
classification that separates combustible
remote signals can be given when the water
materials into four types;
flows. Sprinkler systems are suitable for
1. Class A fires involve ordinary combustibles extinguishing all Class A fires and, in many cases,
and are readily extinguishable by water or also Class B and Class C fires. For Class B fires, a
cooling, or by coating with a suitable chemical sealed (fusible) head system may be used if the
powder. flammable liquid is in containers or is not
present in large quantity. Sprinklers have a good
record for extinguishing fires in garages, for
example. AN oil-spill can be extinguished or Foamed chemicals, mostly masses of air-filled or
contained when the water is applied in the form gas-filled bubbles, formed by chemical or
of spray, as from a sprinkler head. When an oil mechanical means, may be used to control fires
spill or process-pipe rupture can release in flammable liquids. Foam is most useful in
flammable liquid under pressure, an open-head controlling fires in flammable liquids with low
(deluge) system may be required to apply a flash points and low specific gravity, such as
large volume of water quickly and to keep gasoline. Three distinct types of foam are
surrounding equipment cool. suitable for fire control: chemical foam, air foam
(mechanical foam), and high expansion foam.
For Class C fires, water can be applied to live
electrical equipment if it is done in the form of a Chemical Foam was the first foam developed for
non-conducting fog-like spray. This is usually the fire fighting. It is formed by the reaction of
most economical way to protect outdoor oil- water with two chemical powders, usually
filled transformers and oil circuit breakers. sodium bicarbonate and aluminum sulfate. The
reaction forms carbon dioxide, which is the
Fire protection should be based on complete
content of the bubbles. This foam is the most
coverage of the building by the sprinkler system.
viscous and tenacious of the foams. It forms a
Partial coverage is rarely advisable, because
relatively tough blanket, resistant to mechanical
extinguishing capacity is based on detecting and
or heat disruption. Chemical foam is sensitive to
extinguishing fires in their incipiency, and the
the temperature at which it is formed, and the
system must be available at all times in all
chemicals tend to deteriorate during long
places. Systems are not designed to cope with
storage periods. It is not capable of being
fires that have gained headway after starting in
transported through long pipe lines.
unsprinklered areas.
Air Foam (mechanical foam) is made by
• Standpipes. Hoses supplied with water from
mechanical mixing of water and a protein-based
standpipes are the usual means of manual
chemical concentrate. Air foam can be
application of water to interior building fires.
conducted through pipes and discharged
Standpipes are usually designed for this use by
through a fixed chamber mounted in a bulk fuel
the fire department, but they can be used by
storage tank, or it can be conducted through
building fire fighters also. Standpipes are
hoses and discharged manually through special
necessary in buildings higher than those that
nozzles. This foam can also be distributed
ground-based fire department equipment can
through a sprinkler system of special design to
handle effectively. The Standard Building Code
cover small equipment, such as process vessels,
requires standpipes in buildings higher than 50
or in multi-system applications, over an entire
feet. The Uniform Building Code requirement
airplane hangar.
starts at four storeys or occupancies over 5000
ft in area and depends on whether automatic High-expansion foam was developed for use in
sprinklers are installed. coal mines, where its extremely high expansion
rate allowed it to be generated quickly in
Chemical Extinguishment. Fires involving some
sufficient volume to fill mine galleries and reach
materials may not be readily extinguished with
inaccessible fires. High-expansion foam is useful
water alone. When such materials may be
for extinguishing fires by totally flooding indoor
present in a building, provision should be made
confined spaces, as well as for local application
for application of appropriate chemicals.
to specific areas. It extinguishes by displacing air
units from the fire and by the heat-absorbing
effect of converting the foam water content into spaces where flammable liquid and/or gas
steam. The foam forms an insulating barrier for release could occur in the oil, gas,
exposed equipment or building components. petrochemical and military sectors; manned
High-expansion foam is more fragile than communication centers of the armed forces or
chemical or air foam. Also, it is not generally other places essential for national security, or
reliable when used outdoors where it is subject for the protection of spaces where there may be
to wind currents. High-expansion foam is not a risk of dispersion of radioactive material. Dry
toxic, but it has the effect or disorienting people chemical extinguishing agents were used
who may be trapped in it. originally to extinguish Class B fires. One type
consisted of sodium bicarbonate base with
Carbon dioxide is useful as an extinguishing
additives to prevent caking and to improve fluid
agent, particularly on surface fires, such as
flow characteristics. Later, multi-purpose dry
those involving flammable liquids in confined
chemicals effective on Class A, B, and C fires
spaces. It is non-conductive and is effective on
were developed. These chemical are distinctly
live electrical equipment. Because carbon
different from the dry powder extinguishing
dioxide requires agents used on combustible metals. Dry
chemicals are effective on surface fires,
especially on flammable liquids. When used on
clean-up, it is desirable on equipment such as Class A fires, they do not penetrate into the
gasoline or diesel engines. The gas can be used burning material. The major effect of dry
on Class A fires. But when a fire is deep-seated, chemical is due almost entirely the ability to
and extended discharge period is required to break the chain reaction of combustion. A minor
avoid rekindling. Carbon dioxide is not effective effect of smothering is obtained on Class A fires.
on fires involving burning metals, such as Dry chemicals can be discharged in local
magnesium, nor is it effective on oxygen- applications by hand-held extinguishers,
containing materials, such as nitrocellulose. wheeled-portable equipment, or nozzles on
Hazard to personnel is involved to the extent hose lines. These chemicals can also be used for
that a concentration of 9% will cause suffocation extinguishing fires by total flooding, when they
in a few minutes, and concentration of 20% can are distributed through a piped system with
be fatal. When used in areas where personnel special discharge nozzles. The expellant gas is
are present, a time delay before discharge is usually dry nitrogen..
necessary to permit evacuation. For use in total
flooding systems, carbon dioxide is available in Dry powder extinguishing agents are powders
either high-pressure or low-pressure effective in putting out combustible-metal fires.
equipment. Halon 1301 is one of a series of There are several proprietary agents effective on
halogenated hydrocarbons, several metals, but none should be used
bromotrifluoromethane (CBrF2), used with without proper attention to the manufacturer's
varying degrees of effectiveness as a fire instructions and the specific metal involved.
extinguishing agent and was included in the Fire Detection
Montreal Protocol on Substances that Deplete
the Ozone Layer signed in September 16, 1987. Every fire-extinguishing activity must start with
It is currently limited to "critical uses" and is detection. To assist in this, many types of
planned to be phased out by 2002. The types of automatic detectors are available, with a wide
uses currently defines as critical spaces are variety of sensitivity and operations that can be
performed by the detection system. It can
initiate an alarm, local or remote, visual or being disconnected when normal temperature
audible; notify a central station; actuate an is restored.
extinguishing system; start or stop fans or
Thermostatic cable consists of two sheathed
processes; perform any other operation capable
wires separated by a heat-sensitive coating
of automatic control.
which melts at high temperature, allowing the
There are five general types of detectors, each wires to contact each other. The assembly is
employing a different physical means of covered by a protective sheath. When any
operation. The types are designated fixed section has functioned, it must be replaced.
temperature, rate-of-rise, photo-electric,
Continuous detector tubing is a more versatile
combustion-products, and ultraviolet or infrared
assembly. This detector consists of a small-
detectors. A wide variety of detectors has been
diameter Inconel tube, of almost any length,
tested and reported by Underwriters
containing a central wire, separated from the
Laboratories, Inc.
tube by a thermistor element. At elevated
. Fixed-Temperature Detectors. In its approval of temperatures, the resistance of the thermistor
any detection device, UL specifies the maximum drops to a point where a current passes
distance between detectors to be used for area between the wire and the tube. The current can
coverage. This spacing should not be used be monitored, and in this way temperature
without competent judgment. In arriving at the changes over a wide range, up to 1000° F, can
permitted spacing for any device, UL judges the be detected. The detector can be assembled to
response time in comparison with that of locate temperature changes of different
automatic sprinkler heads spaced at 10 feet magnitude over the same length of detector. It
intervals. Thus, if a device is more sensitive that is self-restoring when
a sprinkler head, the permitted spacing is
increased until the response times are nearly
equal. If greater sensitivity is desired, the 0
spacing must be reduced.
0
0
normal temperature is restored. This detector is
With fixed-temperature devices, there is a useful for industrial applications, as well as for
thermal lag between the time the ambient fire detection.
temperature reaches rated temperature and the
device itself reaches that temperature. For Fusible links are the same devices used in
thermostats having a rating of 135° F, the sprinkler heads and are made to operate in the
ambient temperature can reach 260° F. same temperature range. Melting or breaking at
a specific temperature, they are used to restrain
Disk Thermostats are the cheapest and most operation of a fire door, electrical switch, or
widely used detectors. The most common type similar mechanical functions such as operation
employs the principle of unequal thermal of dampers. Their sensitivity is substantially
expansion in a bimetallic assembly to operate a reduced when installed at a distance below a
sna-action at a pre-set temperature, to close ceiling or other heat-collecting obstruction.
electrical contacts. These thermostats are
compact. The disk 1⁄2 in diameter, is mounted on Rate-of-Rise Detectors. Detectors and detector
a plastic base 1%4 inches in diameter. The systems are said to operate on the rate-of-rise
thermostats are self-resetting, the contacts principle when they function on a rapid increase
in temperature, whether the initial temperature combustion when combustion products are still
is high or low. The devices are designed to invisible. These devices are sensitive in some
operate when temperature rises at a specified degree to air currents, temperature, and
number of degrees, usually 10° or 15° F, per humidity, and should not be used without
minute. They are not affected by normal consultation with competent designers.
temperature increases and are not subject to
Flame Detectors. These discriminate between
thermal lag, as are fixed-temperature devices.
visible light and the light produced by
Photoelectric Detectors. These indicate fire combustion reactions. Ultraviolet detectors are
condition by detecting the smoke. Sensitivity responsive to flame having wavelengths up to
can be adjusted to operate when obscuration is 2850 A. The effective distance between flame
as low as 0.4% per feet. In these devices, a light and detectors is about 10 feet for a 5 inch
source is directed so that it does not infringe on diameter pan of gasoline, but a 12 inch square
a photo- electric cell. When sufficient smoke pan fire can be detected at 30 feet.
particles are concentrated in the chamber, their
Infrared detectors are also designed to detect
reflected light reaches the cell, changing its
flame. These are not designated by range of
resistance and initiating a signal.
wavelength because of the many similar sources
These detectors are particularly useful when a at and above the infrared range. To identify the
potential fire is likely to generate a substantial radiation as a fire, infrared detectors usually
amount of smoke before appreciable heat and employ the characteristic flame flicker, and have
flame erupt. A fixed-temperature, snap-action a built-in time delay to eliminate accidental
disk is usually included in the assembly. similar phenomena.
Minimum width of a passage way for normal Supervision of emergency operations can be
use is 36 inches. This is large enough to efficiently provided by personnel at a control
accommodate one-way travel for persons on center placed in a protected area. This center
crutches or in wheelchairs. For two-way travel, a may include a computer, supplemented by a
60 inch width is necessary. Building codes personnel performing scheduled maintenance,
however may require greater widths to permit and should be capable of continuously
rapid passage of the anticipated number of monitoring alarms, gate valves on automatic fire
evacuees in emergencies. This number depends sprinklers, temperatures, air and water
on a factor called the occupant load, but the pressure, and perform other pertinent
minimum width should be ample for safe, easy functions. Also the center should be capable in
passage of handicapped persons. Running slope emergencies of holding two-way
should not exceed 1:20, and cross slope, 1:50. communications with occupants and notifying
police and fire departments of the nature of the
0
emergencies.
Occupant load of a building space is the
For economical building operation, the
maximum number of persons that may be in the
emergency control center may be made part of
space at any time. The occupant load of any
a control center used for normal building
space should include the occupant load of other
operation and maintenance. Thus, the control
spaces if the occupants have to pass through
center may normally control HVAC to conserve
their space to reach an exit.
energy, tum lights on and off, and schedule
Building Operation in Emergencies building maintenance and repair. When an
emergency occurs, emergency control should be
For buildings that will be occupied by large activated in accordance with prepared plans for
number of persons, provision should be made handling each type of emergency.
for continuous services essential to safe, rapid
⚫ Lightning Protection
evacuation of occupants in event of fire or other
emergencies and for assisting safe movement of
fire fighters, medical personnel, or other aides.
Lightning, a high voltage, high-current electrical
Standby electric power, for example, should be discharge between clouds and the ground, may
made available in all buildings to replace the strike and destroy life and property anywhere
basic power source if it should fail. The standby thunderstorms have occurred in the past.
system should be equipped with a generator Buildings and their occupants, however, can be
protected against this hazard by installation of a electrical and communication systems. Lightning
special electrical system. Because an incomplete protection usually requires installation of
or poor installation can cause worse damage or electrical conductors that extend from points
injuries than no protection at all, a lightning- above the roof of a building to the ground, for
protection system should be designed and the purpose of conducting to the ground
installed by experts. lightning that would otherwise strike the
building. Such an installation, however,
As an addition to other electrical systems
possesses the potential hazard that, if not done
required for a building, a lightning-protection
properly, lightning may flash from the lightning
system increases the construction cost of a
conductors to other building components.
building. A building owner therefore has to
Hence, the system must ensure that the
decide whether potential losses justify the
lightning distance is diverted away from the
added expenditure. Also the owner should
building and its contents
compare the cost of insurance to cover losses
with the cost of the protection system. The key element in diverting lightning away
⚫ Characteristics of Lightning
from a building is an air terminal or lightning
rod, a conductor that projects into the air at
least 12 inches above the roof. Air terminals
Lightning strikes are associated with should be spaced at intervals not exceeding 25
thunderstorms. In such storms, the base of the feet. Alternatively, a continuous wire conductor
clouds generally develops a negative or a grid of such conductors may be placed
along the highest points of a roof. If the tallest
object on a roof is a metal mast, it can act as an
air terminal. A metal roof also can serve as an
electrical charge, which includes a positive
air terminal, but only if all joints are made
charge in the earth directly below. As the clouds
electrically continuous by soldering, welding, or
moves, the positive charges, being attracted by
interlocking. Arranged to provide a cone of
the negative charges, follow along the surface of
protection over the entire building, all the air
the earth and climb up buildings, antennas,
terminals should be connected by conductors to
trees, power transmission towers, and other
each other and, by the same or other
conducting or semi-conducting objects along
conductors, to the ground along at least two
the path. Current flows in the form of a lightning
separate paths.
flash, when the voltage becomes great enough
to overcome the electrical resistance of the air Protection Against Intruders
between the clouds and the ground or an object
on it. Thus the probability of a building being Prevention of illegal entry into buildings by
struck by lightning depends not only on the professional criminals determined to break in is
frequency of occurrence of thunderstorms but not practical. Hence, the prime objective of
also on building height relative to nearby security measures is to make illegal entry
objects and the intensity of cloud and charges. difficult. If this is done, it will take an intruder
longer to gain entry or will compel the intruder
Methods for Protection against Lightning to make noise, thus increasing the chances of
detection and apprehension. Other objectives
Objectives of lightning protection are life safety,
of security measures are detection of break- in
prevention of property damage, and
attempts and intruders, alarming intruders so
maintenance of essential services, such as
that they leave the premises before they cause
a loss or injury, and alerting building occupants For most types of occupancy, control at the
and the police of the break-in attempt. Also, an entrance may often be provided by receptionist
objective is to safeguard valuable assets by who records names of visitors and persons
placing them in a guarded, locked, secure visited notify the latter and can advise the
enclosure with access limited only to approved police of disturbances. When necessary, the
personnel. receptionist can be augmented by a guard at the
control point or in a security center and, in very
•
large or high-rise buildings, by a roving guard
Security Measures available for emergencies. If a large security
force is needed, facilities should be provided in
Basic security for a building is provided by the building for an office for the security
commonly used walls and roofs with openings administrator and staff, photographic
protected by doors with key-operated locks or identification, and squad room and lockers, all in
windows with latches. The degree of protection or adjoining a security center.
required for a building and its occupants beyond
basic security and privacy needs depends on the Security Center
costs of insurance and security measures
The security center may be equipped with or
relative to potential losses from burglary and
connected to electronic devices that do the
vandalism. For a small building not housing
following:
small items of great value, devices for detecting
break-in attempts are generally the most 1. Detect a break-in attempt and sound an
practical means of augmenting basic security. alarm.
Bells, buzzers, or sirens should be installed to
2. Identify the point of intrusion.
sound an alarm and automatic telephone or
wireless dialer should be used to alert a 3.
monitoring service to notify the police when an
⚫ Flood-proofing
of earth adjoining foundations are the only
forces available to prevent the horizontal
A flood occurs when a river rises above an
elevation, called flood stage, and is not
loads from overtuming the building. Also, as for prevented by enclosures from causing damage
wind loads, the roof should be firmly anchored beyond its banks. Buildings constructed in a
to the superstructure framing, which, in tum, flood plain, an area that can be inundated by a
should be securely attached to the foundations. flood, should be protected against a flood with a
Furthermore, individual footing, especially pile mean recurrence interval of 100 years.
and caisson footing should be tied to each other
to prevent relative movement. Major objectives of flood-proofing are to
protect fully building and contents from damage
Building codes often limit the drift per floor from a 100-year flood, reduce losses from more
under the equivalent static seismic load. devastating floods, and lower flood insurance
Connections and intersections of curtain walls premiums. Flood-proofing, however, would be
and partitions with each other or with the unnecessary if buildings were not constructed in
structural framing should allow for a relative flood prone areas. Building in flood prone areas
movement of at least twice the calculated drift should be avoided unless the risk to life is
in each floor. Such allowances for displacement acceptable and construction there can be
may be larger than those normally required for economically and socially justified.
dimensional changes caused by temperature
variations. Some sites in flood prone areas posses some
ground high enough to avoid flood damage. If
PROTECTION AGAINST WATER: Typhoon such sites must be used, buildings should be
Resistant Construction clustered on the high areas. Where such areas
Whether thrust against and into a building by a are not available, it may be feasible to build up
flood, driven into the interior by a heavy rain, an earth fill, with embankments protected
leaking from plumbing, storm surge, or seeping against erosion by water, to raise structures
through the exterior enclosure, water can costly above flood levels.
An alternative to elevating a building on fill is windows and doors, impervious water-stops in
raising it on stilts (columns in an enclosed joints, or calking of cracks and other openings.
space). In that case, utilities and other services Methods of preventing seepage, however,
should be protected against damage from flood depend on the type of materials used in the
flows. The space at ground level between the exterior enclosure.
stilts may be used for parking automobiles, if
Definitions of Terms Related to Water
the risk of water damage to them is acceptable
Resistance
or if they will be removed before flood waters
reach the site. Buildings that cannot be elevated . Permeability. Quality or state of permitting
above flood stage should be fumished with an passage of water and water vapor into, through
impervious exterior. Windows should be above and from pores and interstices, without causing
flood stage, and doors should seal tightly rupture, or displacement.
against their frames. Doors and other openings
may also be protected with a flood shield, such Pervious of leaky. Cracks, crevices, leaks, or
as a wall. Openings in the wall for access to the holes larger than capillary pores which permit a
building may be protected with a movable flood flow or leakage of water, are present. The
shield, which for normal conditions can be material may or may not contain capillary pores.
stored out of sight and then positioned in the
wall opening when a flood is imminent.
Most of these solutions contained not more The cementitious coatings absorb moisture and
than 10% of solid matter. These treatments are of the breather type, permitting passage of
reduced the rate of leakage but did not stop all water vapor. Addition of water repellents to
leakage through the walls. The test data shows these coatings does not greatly affect their
that colorless coating materials applied to water resistance but does reduce the soiling of
permeable walls of brick or concrete masonry the surface from the absorption of dirt-laden
may not provide adequate protection against water. If more than one coating is applied, as in
leakage of wind-driven rain. a two-coat paint or stucco facing job, the
repellent is preferably added only to the finish
Solutions containing oils and waxes tended to
coat, thus avoiding the difficulty of bonding a
seal the pores exposed in the faces of the
cementitious coating to a water repellent
mortar joints and masonry units, thereby acting
surface. The technique used in applying the
more or less as vapor barriers, but did not seal
cementitious coatings is highly important. The
the larger openings, particularly those in the
backing should be thoroughly dampened. Paints
joints.
and grouts should be scrubbed into place with
Silicone water-repellent solutions greatly stiff fiber brushes and the coatings should be
reduced leakage through the walls as long as properly cured by wetting. Properly applied, the
the treated wall faces remained water- grouts are highly durable; some grout coatings
repellent. After and exposure period of 2 or 3 applied to concrete masonry test walls aere
hour, the rate of leakage gradually increased as found to be as water-resistant after 10 years
the water repellency of the wall face out-of-doors exposure as when first applied to
diminished. Coatings of the water-repellent, the walls.
breather type, such as silicone and "soap
Pigmented Organic Coatings. These include
solutions, may be of value in reducing
textured coatings, mastic coatings, conventional
absorption of moisture into the wall surface.
paints, and aqueous dispersions. The thick-
They may be of special benefit in reducing the
textured and mastic coatings are usually spray-
soiling and disfiguration of stucco facings and
applied but may be applied by trowel.
light-colored masonry surfaces. They may be
Conventional paints and aqueous dispersions
applied to precast-concrete panels to reduce
are usually applied by brush or spray. Most of
volume changes that may otherwise result from
these coatings are vapor barriers but some
changes in moisture content of the concrete.
textured coatings, conventional paints, and
aqueous dispersions are breathers. Except for
the aqueous dispersions, all the coatings are
recommended for use with a primer.
Cementitious Coatings. Coatings of Portland- Applied as continuous coating without pinholes,
cement paints, grouts, and stuccos and of the pigmented organic coatings are highly
pneumatically applied mortars are highly water- water-resistant. They are most effective when
resistant. They are preferred above all other applied over a smooth backing. When they are
types of surface coatings for use as water- applied with paintbrush or spray by
conventional methods to rough-textured walls, Mid-rise housing, as defined, is an aggregation
it is difficult to level the surface and obtain a of dwelling units in buildings ranging from
continuous water-resistant coating free from approximately four to fifteen storeys. These
holes. A scrubbed-on cementitious grout used buildings require elevator access; but they are
as a base coat on such walls will prevent leakage generally broader than they are high.
through the masonry without the use of a
Flats in these building configurations may be
pigmented organic coating. The pigmented
organized along a single-loaded corridor (a row
organic coatings are highly decorative but may
of flats opening off one side of the corridor) or a
not be so water-resistant, economical, or
double-loaded corridor (a row of flats opening
durable as the cementitious coatings.
off both sides of the corridor).
Bituminous Coatings. Bituminous cutbacks,
The double-loaded approach is more efficient in
emulsions, and plastic cements are usually
terms of circulation and space; but single loaded
vapor barriers and are sometimes applied as
schemes are appropriate where an exterior
"damp proofers" on the inside faces of masonry
access corridor is feasible, where views make
walls. Plaster is often applied directly over these
one side of the building more desirable, where
coatings, the bond of the plaster to the masonry
the site is narrow, or where the units wrap
being only of a mechanical nature. Test show
around another structure such as parking.
that bituminous coatings applied to the inside
Whether the building plan is single-loaded or
faces of highly permeable masonry walls, not
double-loaded, elevators generally will be
plastered, will readily blister and permit leakage
centrally located, with egress stairs at the
of water through the coating. It is advisable not
corridor ends.
to depend on such coatings to prevent the
leakage of wind-driven rain unless they are The units created typically have only one
incorporated in the masonry or held in place exterior exposure. The interior zone that
with a rigid self-sustaining backing. parallels the corridor is used for entry,
circulation, kitchen, bathrooms, and storage.
Even though the walls are resistant to wind-
The exterior zone, with its exterior windows, is
driven rain, but are treated on their inner faces
reserved for living and dining areas, bedrooms,
with a bituminous coating, water may not be
and a possible study.
condensed on the warm side of the coating and
damage to the plaster may result, whether the Units at the building's ends, comers, and
walls are furred or not. However, the setbacks can take advantage of multi exposures.
bituminous coating may be of benefit as a vapor Balconies related to living and dining areas,
barrier in furred walls, if no condensation occurs whether recessed into the building mass or
on the warm inside. projecting from it, are a desirable feature.
Exterior Treatment