0% found this document useful (0 votes)
21 views277 pages

MI 3155 - EurotestXD ANG Ver 1.12.16 20752716

Uploaded by

Paul Chiriacescu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
21 views277 pages

MI 3155 - EurotestXD ANG Ver 1.12.16 20752716

Uploaded by

Paul Chiriacescu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 277

EurotestXD

MI 3155
Instruction manual
Version 1.12.16, Code no. 20 752 716
Distributor:

Manufacturer:

Metrel d.d.
Ljubljanska cesta 77
SI-1354 Horjul
Slovenia
https://www.metrel.si
[email protected]

DATA BACKUP AND LOSS:

It is the user’s responsibility to ensure the integrity and security of the data carrier and to
regularly backup and validate the integrity of backups of the data. METREL HAS NO
OBLIGATION OR LIABILITY FOR ANY LOSS, ALTERATION, DESTRUCTION, DAMAGE,
CORRUPTION OR RECOVERY OF USER DATA, REGARDLESS OF WHERE THE DATA IS
STORED.

Mark on your equipment certifies that it meets requirements of all subjected EU


regulations.

Hereby, Metrel d.d. declares that the MI 3155 is in compliance with Directive
2014/53/EU (RED) and all other subjected EU directive. The full text of the EU
declaration of conformity is available at the following internet address
https://www.metrel.si/DoC.

© 2022 METREL

The trade names Metrel®, Smartec®, Eurotest®, Auto Sequence® are trademarks registered in Europe and other
countries.

No part of this publication may be reproduced or utilized in any form or by any means without
permission in writing from METREL.

2
i. About the instruction manual
 This Instruction manual contains detailed information on the EurotestXD, its key
features, functionalities and use.
 It is intended for technically qualified personnel responsible for the product and its use.
 Please note that LCD screenshots in this document may differ from the actual instrument
screens in details due to firmware variations and modifications.
 Metrel reserve the right to make technical modifications without notice as part of the
further development of the product.

3
MI 3155 EurotestXD Table of Contents

Table of Contents
1 General description .......................................................................................................... 9
1.1 Warnings and notes .................................................................................................... 9
1.1.1 Safety warnings ....................................................................................................... 9
1.1.2 Markings on the instrument ................................................................................... 10
1.1.3 Warnings related to safety of batteries .................................................................. 10
1.1.4 Warnings related to safety of measurement functions ........................................... 10
1.1.5 Notes related to measurement functions ............................................................... 11
1.2 Testing potential on PE terminal ................................................................................ 14
1.3 Battery and charging of Li-ion battery pack ............................................................... 16
1.3.1 Precharge.............................................................................................................. 17
1.3.2 Li – ion battery pack guidelines ............................................................................. 19
1.4 Standards applied ..................................................................................................... 20
2 Instrument set and accessories..................................................................................... 22
2.1 Standard set MI 3155 EurotestXD ............................................................................. 22
2.1.1 Optional accessories ............................................................................................. 22
3 Instrument description ................................................................................................... 23
3.1 Front panel ................................................................................................................ 23
3.2 Connector panel ........................................................................................................ 24
3.3 Back side .................................................................................................................. 25
3.4 Carrying the instrument ............................................................................................. 27
3.4.1 Secure attachment of the strap.............................................................................. 27
4 Instrument operation ...................................................................................................... 29
4.1 General meaning of keys .......................................................................................... 29
4.2 General meaning of touch gestures........................................................................... 30
4.3 Virtual keyboard ........................................................................................................ 31
4.4 Display and sound ..................................................................................................... 32
4.4.1 Terminal voltage monitor ....................................................................................... 32
4.4.2 Battery indication ................................................................................................... 33
4.4.3 Bluetooth ............................................................................................................... 33
4.4.4 Measurement actions and messages .................................................................... 33
4.4.5 Result indication .................................................................................................... 35
4.4.6 Auto Sequence® result indication .......................................................................... 35
4.5 Instruments main menu ............................................................................................. 37
4.6 General Settings ....................................................................................................... 38
4.6.1 Language .............................................................................................................. 39
4.6.2 Power Save ........................................................................................................... 39
4.6.3 Date and time ........................................................................................................ 40
4.6.4 Workspace manager ............................................................................................. 40
4.6.5 Auto Sequences groups ..................................................................................... 40
4.6.6 User accounts ....................................................................................................... 40
4.6.7 Profiles .................................................................................................................. 45
4.6.8 Settings ................................................................................................................. 45
4.6.9 Devices ................................................................................................................. 50
4.6.10 Bluetooth initialization ........................................................................................ 50
4.6.11 Initial Settings .................................................................................................... 50
4.6.12 About ................................................................................................................. 51
4.7 Instrument profiles ..................................................................................................... 52

4
MI 3155 EurotestXD Table of Contents

4.8 Workspace Manager ................................................................................................. 53


4.8.1 Workspaces and Exports....................................................................................... 53
4.8.2 Workspace Manager main menu ........................................................................... 53
4.8.3 Operations with Workspaces ................................................................................. 54
4.8.4 Operations with Exports ........................................................................................ 54
4.8.5 Adding a new Workspace ...................................................................................... 55
4.8.6 Opening a Workspace ........................................................................................... 56
4.8.7 Deleting a Workspace / Export .............................................................................. 56
4.8.8 Importing a Workspace.......................................................................................... 57
4.8.9 Exporting a Workspace ......................................................................................... 58
4.9 Auto Sequence® groups ........................................................................................... 59
4.9.1 Auto Sequence® groups menu.............................................................................. 59
5 Memory Organizer .......................................................................................................... 61
5.1 Memory Organizer menu ........................................................................................... 61
5.1.1 Measurement statuses .......................................................................................... 61
5.1.2 Structure Objects................................................................................................... 62
5.1.3 Selecting an active Workspace in Memory Organizer ............................................ 64
5.1.4 Adding Nodes in Memory Organizer ...................................................................... 65
5.1.5 Operations in Tree menu ....................................................................................... 66
5.1.6 Searching in Memory Organizer ............................................................................ 86
6 Single tests...................................................................................................................... 90
6.1 Selection modes........................................................................................................ 90
6.1.1 Single test (measurement) screens ....................................................................... 91
6.1.2 Setting parameters, limits and comments of single tests ....................................... 93
6.1.3 Single test start screen .......................................................................................... 94
6.1.4 Single test screen during test ................................................................................ 95
6.1.5 Single test result screen ........................................................................................ 96
6.1.6 Editing graphs (Harmonics) ................................................................................... 98
6.1.7 Single test (inspection) screens ............................................................................. 99
6.1.8 Help screens ....................................................................................................... 103
6.1.9 Recall single test results screen .......................................................................... 104
7 Tests and measurements ............................................................................................. 105
7.1 Voltage, frequency and phase sequence................................................................. 105
7.2 R iso – Insulation resistance.................................................................................... 108
7.2.1 Load pretest ........................................................................................................ 110
7.3 R iso all – Insulation resistance ............................................................................... 111
7.4 The DAR and PI diagnostic ..................................................................................... 113
7.5 Varistor test ............................................................................................................. 115
7.6 R low – Resistance of earth connection and equipotential bonding ......................... 117
7.7 R low 4W................................................................................................................. 118
7.8 Continuity – Continuous resistance measurement with low current ......................... 120
7.8.1 Compensation of test leads resistance ................................................................ 121
7.9 Testing RCDs .......................................................................................................... 123
7.9.1 RCD Uc – Contact voltage .................................................................................. 124
7.9.2 RCD t – Trip-out time........................................................................................... 126
7.9.3 RCD I – Trip-out current ...................................................................................... 126
7.10 RCD Auto – RCD Auto test ..................................................................................... 128
7.11 Z loop – Fault loop impedance and prospective fault current ................................... 131
7.12 Z loop 4W – Fault loop impedance and prospective fault current............................. 134
7.13 Zs rcd – Fault loop impedance and prospective fault current in system with RCD ... 136
7.14 Z loop m – High precision fault loop impedance and prospective fault current ...... 139
7.15 Z line – Line impedance and prospective short-circuit current ................................. 142

5
MI 3155 EurotestXD Table of Contents

7.16 Z line 4W – Line impedance and prospective short-circuit current ........................... 145
7.17 Z line m – High precision line impedance and prospective short-circuit current .... 147
7.18 High Current (MI 3143 and MI 3144) ....................................................................... 150
7.19 Voltage Drop ........................................................................................................... 152
7.20 U touch – Touch voltage (MI 3143 and MI 3144) ..................................................... 155
7.21 Z auto - Auto test sequence for fast line and loop testing ........................................ 157
7.22 R line m – DC resistance measurement (MI 3144) ............................................... 159
7.23 ELR Current Injection Test (MI 3144) ...................................................................... 161
7.24 ELR Combination Time Test (MI 3144) ................................................................... 163
7.25 EVSE Diagnostic Test (A 1632) .............................................................................. 165
7.26 Earth – Earth resistance (3-wire test) ...................................................................... 168
7.27 Earth 2 clamp – Contactless earthing resistance measurement (with two current
clamps) ............................................................................................................................... 169
7.28 Ro – Specific earth resistance (A 1199) .................................................................. 170
7.29 Power ...................................................................................................................... 172
7.30 Harmonics ............................................................................................................... 174
7.31 Currents .................................................................................................................. 176
7.32 Current Clamp Meter (MI 3144) ............................................................................... 178
7.33 ISFL – First fault leakage current............................................................................. 180
7.34 IMD – Testing of insulation monitoring devices........................................................ 182
7.35 Rpe – PE conductor resistance ............................................................................... 186
7.36 Illumination .............................................................................................................. 188
7.37 Discharging time ..................................................................................................... 189
7.38 AUTO TT – Auto test sequence for TT earthing system .......................................... 192
7.39 AUTO TN (RCD) – Auto test sequence for TN earthing system with RCD............... 194
7.40 AUTO TN – Auto test sequence for TN earthing system without RCD ..................... 196
7.41 AUTO IT – Auto test sequence for IT earthing system............................................. 198
7.42 Locator .................................................................................................................... 200
7.43 Visual and Functional inspections ........................................................................... 202
7.44 Measurements using adapter MD 9273 ................................................................... 203
7.44.1 Power CLAMP ................................................................................................. 203
7.44.2 Voltage CLAMP ............................................................................................... 205
7.44.3 Current CLAMP ............................................................................................... 206
7.44.4 Inrush CLAMP ................................................................................................. 207
7.44.5 Harmonics U CLAMP ...................................................................................... 209
7.44.6 Harmonics I CLAMP ........................................................................................ 211
8 Auto Sequences® ......................................................................................................... 213
8.1 Selection of Auto Sequences® ................................................................................ 213
8.1.1 Selecting an active Auto Sequence® group in Auto Sequences® menu.............. 213
8.1.2 Searching in Auto Sequences® menu ................................................................. 214
8.1.3 Organization of Auto Sequences® in Auto Sequences® menu ........................... 216
8.2 Organization of an Auto Sequence® ....................................................................... 216
8.2.1 Auto Sequence® view menu ............................................................................... 217
8.2.2 Step by step execution of Auto Sequences® ....................................................... 219
8.2.3 Auto Sequence® result screen ............................................................................ 221
8.2.4 Auto Sequence® memory screen ........................................................................ 222
9 Communication ............................................................................................................. 224
9.1 USB and RS232 communication ............................................................................. 224
9.2 Bluetooth communication with Android devices ....................................................... 224
9.3 Communication with adapters ................................................................................. 225
9.4 Bluetooth and RS-232 communication with scanners .............................................. 226
10 Upgrading the instrument ............................................................................................ 227

6
MI 3155 EurotestXD Table of Contents

11 Maintenance .................................................................................................................. 228


11.1 Fuse replacement ................................................................................................... 228
11.2 Battery pack insertion / replacement ....................................................................... 229
11.3 Cleaning .................................................................................................................. 230
11.4 Periodic calibration .................................................................................................. 230
11.5 Service .................................................................................................................... 230
12 Technical specifications............................................................................................... 231
12.1 R iso, R iso all – Insulation resistance ..................................................................... 231
12.2 Diagnostic test......................................................................................................... 232
12.3 R low – Resistance of earth connection and equipotential bonding ......................... 232
12.4 R low 4W – Resistance of earth connection and equipotential bonding ................... 233
12.5 Continuity – Continuous resistance measurement with low current ......................... 233
12.6 RCD testing ............................................................................................................. 234
12.6.1 General data.................................................................................................... 234
12.6.2 RCD Uc – Contact voltage ............................................................................... 235
12.6.3 RCD t – Trip-out time ....................................................................................... 235
12.6.4 RCD I – Trip-out current .................................................................................. 235
12.6.5 RCD Auto ........................................................................................................ 236
12.7 Z loop, Z loop 4W – Fault loop impedance and prospective fault current ................. 236
12.8 Zs rcd – Fault loop impedance and prospective fault current in system with RCD ... 238
12.9 Z loop m – High precision fault loop impedance and prospective fault current ...... 238
12.10 U touch – Touch voltage (MI 3143 and MI 3144) ..................................................... 239
12.11 Z line, Z line 4W – Line impedance and prospective short-circuit current ................ 239
12.12 Voltage Drop ........................................................................................................... 239
12.13 Z line m – High precision line impedance and prospective fault current ................ 240
12.14 High current (MI 3143 and MI 3144) ........................................................................ 240
12.15 Z auto, AUTO TT, AUTO TN, AUTO TN (RCD), AUTO IT ....................................... 240
12.16 Rpe – PE conductor resistance ............................................................................... 241
12.17 Earth – Earth resistance (3-wire measurement) ...................................................... 241
12.18 Earth 2 clamp – Contactless earthing resistance measurement (with two current
clamps) ............................................................................................................................... 242
12.19 Ro – Specific earth resistance ................................................................................. 242
12.20 Voltage, frequency, and phase rotation ................................................................... 243
12.20.1 Phase rotation ................................................................................................. 243
12.20.2 Voltage / Online terminal voltage monitor ........................................................ 243
12.20.3 Frequency ....................................................................................................... 243
12.21 Varistor test ............................................................................................................. 243
12.22 Currents .................................................................................................................. 244
12.23 Current clamp meter (MI 3144) ............................................................................... 244
12.24 Power ...................................................................................................................... 245
12.25 Harmonics ............................................................................................................... 245
12.26 ISFL – First fault leakage current............................................................................. 246
12.27 IMD ......................................................................................................................... 246
12.28 Illumination .............................................................................................................. 246
12.29 Discharging time ..................................................................................................... 247
12.30 Auto Sequences® ................................................................................................... 247
12.31 R line mΩ - DC resistance measurement (MI 3144) ................................................ 247
12.32 ELR Current injection (MI 3144) .............................................................................. 247
12.33 ELR Combination time test (MI 3144) ...................................................................... 248
12.34 EVSE Diagnostic test (A 1632) ................................................................................ 248
12.35 Power CLAMP (MD 9273) ....................................................................................... 248
12.36 Voltage CLAMP (MD 9273) ..................................................................................... 248
12.37 Current CLAMP (MD 9273) ..................................................................................... 248

7
MI 3155 EurotestXD Table of Contents

12.38 Inrush CLAMP (MD 9273) ....................................................................................... 248


12.39 Harmonics U CLAMP (MD 9273)............................................................................. 248
12.40 Harmonics I CLAMP (MD 9273) .............................................................................. 248
12.41 General data ........................................................................................................... 249
Appendix A Profile notes ............................................................................................... 250
A.1 Profile Austria (ATAF) ............................................................................................. 250
A.2 Profile Hungary (ATAG) .......................................................................................... 251
A.3 Profile Finland (ATAH) ............................................................................................ 252
A.4 Profile France (ATAI)............................................................................................... 253
A.5 Profile Switzerland (ATAJ)....................................................................................... 254
Appendix B Commanders (A 1314, A 1401).................................................................. 255

B.1 Warnings related to safety ................................................................................ 255


B.2 Battery..................................................................................................................... 255
B.3 Description of commanders ..................................................................................... 255
B.4 Operation of commanders ....................................................................................... 256
Appendix C Locator receiver R10K ............................................................................... 257
Appendix D Structure objects ....................................................................................... 258
Appendix E Default list of Auto Sequences .................................................................. 261
Appendix F Programming of Auto Sequences on Metrel ES Manager........................ 262
F.1 Auto Sequence Editor workspace ......................................................................... 262
F.2 Managing groups of Auto Sequences ................................................................... 263
F.3 Auto Sequence® Name, Description and Image editing .......................................... 266
F.4 Search within selected Auto Sequence® group ....................................................... 267
F.5 Elements of an Auto Sequence® ............................................................................ 268
F.5.1 Auto Sequence® steps .................................................................................... 268
F.5.2 Single tests ...................................................................................................... 268
F.5.3 Flow commands .............................................................................................. 268
F.5.4 Number of measurement steps........................................................................ 268
F.6 Creating / modifying an Auto Sequence® ................................................................ 269
F.7 Description of flow commands................................................................................. 270
F.8 Custom Inspections programming ........................................................................... 272
F.8.1 Creating and editing Custom Inspections ........................................................ 272
F.8.2 Applying Custom Inspections........................................................................... 274
Appendix G Tests and Measurements with adapters .................................................. 276

8
MI 3155 EurotestXD General description

1 General description
1.1 Warnings and notes

Read before use

1.1.1 Safety warnings


In order to reach high level of operator safety while carrying out various measurements using the
EurotestXD instrument, as well as to keep the test equipment undamaged, it is necessary to
consider the following general warnings:
 Read Instruction manual carefully, otherwise the use of the instrument may be
dangerous for the operator, the instrument or for the equipment under test!
 Consider warning markings on the instrument (see next chapter for more
information).
 If the test equipment is used in a manner not specified in this user manual, the
protection provided by the equipment could be impaired!
 Do not use the instrument or any of the accessories if any damage is noticed!
 Regularly check the instrument and accessories for correct functioning to avoid
hazard that could occur from misleading results.
 Consider all generally known precautions in order to avoid risk of electric shock
while dealing with hazardous voltages!
 Always check for the presence of dangerous voltage on PE test terminal of
installation by touching the TEST key on the instrument or by any other method
before starting single test and Auto Sequence® measurements. Make sure that the
TEST key is grounded through human body resistance without any insulated
material between (gloves, shoes, insulated floors, pens,...). PE test could
otherwise be impaired and results of a single test or Auto Sequence® can mislead.
Even detected dangerous voltage on PE test terminal cannot prevent running of a
single test or Auto Sequence®. All such behaviour is regarded as misuse.
Operator of the instrument must stop the activity immediately and eliminate the
fault/connection problem before proceeding with any activity!
 Use only standard or optional test accessories supplied by your distributor!
 In case a fuse has blown follow the instructions in this manual in order to replace
it! Use only fuses that are specified!
 Service, calibration or adjustment of instruments and accessories is only allowed
to be carried out by a competent authorized person!
 Do not use the instrument in AC supply systems with voltages higher than 550
Va.c.
 Consider that protection category of some accessories is lower than of the
instrument. Test tips and Tip commander have removable caps. If they are
removed the protection falls to CAT II. Check markings on accessories!
▪ cap off, 18 mm tip: CAT II up to 1000 V
▪ cap on, 4 mm tip: CAT II 1000 V / CAT III 600 V / CAT IV 300 V
 The instrument comes supplied with rechargeable Li-Ion battery pack. The battery
pack should only be replaced with the same type as defined on the battery
compartment label or as described in this manual!

9
MI 3155 EurotestXD General description

 Hazardous voltages exist inside the instrument. Disconnect all test leads, remove
the power supply cable and switch off the instrument before removing battery
/fuse compartment cover.
 Do not connect any voltage source on C1 inputs. It is intended only for connection
of current clamps. Maximal input voltage is 3 V!

1.1.2 Markings on the instrument

 Read the Instruction manual with special care to safety operation«. The
symbol requires an action!

 Do not use the instrument in AC supply systems with


voltages higher than 550 Va.c.!

 Mark on your equipment certifies that it meets requirements of all subjected


EU regulations.

 This equipment should be recycled as electronic waste.

1.1.3 Warnings related to safety of batteries


 Use only batteries and power supply adapter delivered from the manufacturer or
distributer of the test equipment.
 Never dispose of the batteries in a fire as it may cause them to explode or generate
a toxic gas.
 Do not attempt to disassemble, crush or puncture the batteries in any way.
 Do not short circuit or reverse polarity the external contacts on a battery.
 Avoid exposing the battery to excessive shock/impacts or vibration.
 Do not use a damaged battery.
 The Li – ion battery contains safety and protection circuit, which if damaged, may
cause the battery to generate heat, rupture or ignite.
 Do not leave a battery on prolonged charge when not in use.
 If a battery has leaking fluids, do not touch any fluids.
 In case of eye contact with fluid, do not rub eyes. Immediately flush eyes
thoroughly with water for at least 15 minutes, lifting upper and lower lids, until no
evidence of the fluid remains. Seek medical attention.

1.1.4 Warnings related to safety of measurement functions


Insulation resistance (R iso, R iso – all)
 Insulation resistance measurement should only be performed on de-energized objects!
 Do not touch the test object during the measurement or before it is fully discharged! Risk
of electric shock!

Continuity functions (R low, R low 4W, Continuity)


 Continuity measurements should only be performed on de-energized objects!

10
MI 3155 EurotestXD General description

1.1.5 Notes related to measurement functions


Insulation resistance (R iso, R iso – all)
 The measuring range is decreased if using Tip commander A 1401.
 If a voltage of higher than 30 V (AC or DC) is detected between test terminals, the
measurement will not be performed.
 Load pretest detects possible connection of appliances to the system during test. Test
eliminates possible damage to the equipment that could be connected to the system
during Insulation resistance measurements.
 Load pretest is carried out between same terminals as the Insulation resistance
measurement.
 Load pretest is carried out only when Uiso ≤ 1000 V.

Diagnostic test
 If any insulation resistance values (RISO(15 s) or RISO(60 s )) are over-ranged the DAR
factor is not calculated. The result field is blank: DAR:_____!
 If any insulation resistance values (RISO(60 s) or RISO(10 min)) are over-ranged the PI
factor is not calculated. The result field is blank: PI :_____!

Continuity functions (R low, R low 4W, Continuity)


 If a voltage of higher than 10 V (AC or DC) is detected between test terminals, the
measurement will not be performed.
 Parallel loops may influence on test results.
 In some kind of PRCDs types (PRCD-3p and PRCD-S+), the protective conductor is
monitored. For protective conductor resistance measurement, a test current of 200 mA is
required. Direct application will cause tripping of PRCD, so PE conductor measurement
is not possible.
In this case use a test parameter Current set to 'ramp', where special ramp curve is
used for PE conductor resistance measurement without tripping of PRCD. If Current
parameter is set to 'normal', a standard test current curve is used.

Earth, Earth 2 clamp, Ro


 If voltage between test terminals is higher than 10 V (Earth, Earth 2 clamps) or 30 V (Ro)
the measurement will not be performed.
 Contactless earthing resistance measurement (using two current clamps) enables simple
testing of individual earthing rods in large earthing system. It is especially suitable for use
in urban areas because there is usually no possibility to place the test probes.
 For two clamps earth resistance measurement clamps A 1018 and A 1019 should be
used. Clamps A 1391 are not supported. The distance between clamps should be at
least 30 cm.
 For specific earth resistance measurements  Adaptor A 1199 should be used.

RCD t, RCD I, RCD Uc, RCD Auto


 Parameters set in one function are also kept for other RCD functions!
 Selective (time-delayed) RCDs have delayed response characteristics. As the contact
voltage pre-test or other RCD tests influence the time delayed RCD it takes a certain
period to recover into normal state. Therefore, a time delay of 30 s is inserted before
performing trip-out test by default.
 Portable RCDs (PRCD, PRCD-2p, PRCD-3p, PRCD-S, PRCD-S+ and PRCD-K) are
tested as general (non-delayed) RCDs. Trip-out times, trip-out currents and contact
voltage limits are equal to limits of general (non-delayed) RCDs.
 In some kind of PRCDs types (PRCD, PRCD-3p, PRCD-S+ and PRCD-K), the protective
conductor is monitored and carried out in the opposite direction through current sensor
circuitry. During periodic testing – when fault current flows through phase and protective

11
MI 3155 EurotestXD General description

conductor – this can cause misunderstanding, because PRCD reacts at half the tripping
fault current. In order to prevent this, use parameter Sensitivity set to 'Ipe monitoring',
where test current will be a half of selected nominal tripping current.
If Sensitivity parameter is set to 'standard', a test current with nominal tripping current
is used.
 The a.c. part of MI and EV RCDs is tested as general (non-delayed) RCDs.
 The d.c. part of MI and EV RCDs is tested with a d. c. test current The Pass limit is
between 0.5 and 1.0 IdNDC.
 The Zs rcd function takes longer to complete but offers much better accuracy of fault loop
resistance (in comparison to the RL sub-result in Contact voltage function).
 Auto test is finished without x5 tests in case of testing the RCD types A, F, B and B+ with
rated residual currents of IdN = 300 mA, 500 mA, and 1000 mA or testing the RCD type
AC with rated residual current of IdN = 1000 mA . In this case Auto test result passes if all
other results pass, and indications for x5 are omitted.
 Auto test is finished without x1 tests in case of testing the RCD types B and B+ with rated
residual currents of IdN = 1000 mA. In this case Auto test result passes if all other results
pass, and indications for x1 are omitted.
 Tests for sensitivity Idn(+) and Idn(-) are omitted for selective type RCD.
 Trip out time measurement for B and B+ type RCDs in AUTO function is made with sine-
wave test current, while trip-out current measurement is made with DC test current.

Z loop, Zloop 4W, Zs rcd


 The specified accuracy of tested parameters is valid only if the mains voltage is stable
during the measurement.
 The measurement accuracy and immunity against noise are higher if I test parameter in
Zsrcd is set to ‘Standard’.
 Fault loop impedance (Z loop) measurements will trip an RCD.
 The Zs rcd measurement does not normally trip an RCD. However, if a leakage current
from L to PE already flows or if a very sensitive RCD is installed (for example EV type)
the RCD could trip. In this case setting parameter I test to ‘Low’ can help.

Z line, Z line 4W, Voltage drop


 In case of measurement of ZLine-Line with the instrument test leads PE and N connected
together the instrument will display a warning of dangerous PE voltage. The
measurement will be performed anyway.
 Specified accuracy of tested parameters is valid only if mains voltage is stable during the
measurement.
 If the reference impedance is not set the value of ZREF is considered as 0.00 Ω.
 The lowest value of Zref, measured at different settings of the Test or Phase parameters
is used for Voltage drop (ΔU) measurement in Voltage drop single test, Zauto single test,
auto tests and Auto Sequences®.
 Measuring Zref without test voltage present (disconnected test leads) will reset Zref value
to initial value.

Power, Harmonics, Currents


 Consider polarity of current clamp (arrow on test clamp should be oriented toward
connected load), otherwise result will be negative!

Illumination
 LUXmeter type B (A 1172) and LUXmeter type C (A 1173) probes are supported by the
instrument.
 Artificial light sources reach full power of operation after a period of time (see technical
data for light sources) and should be therefore switched on for this period of time before
the measurements are taken.

12
MI 3155 EurotestXD General description

 For accurate measurement make sure that the milk glass bulb is lit without any shadows
cast by hand, body or other unwanted objects.
 Refer to the Illuminance handbook for more information.

Rpe
 The specified accuracy of tested parameters is valid only if the mains voltage is stable
during the measurement.
 Measurement will trip an RCD if the parameter RCD is set to ‘No’.
 The measurement does not normally trip an RCD if the parameter RCD is set to ‘Yes’.
However, the RCD can trip if a leakage current from L to PE already flows.

IMD
 It is recommended to disconnect all appliances from the tested supply to receive regular
test results. Any connected appliance will influence the insulation resistance threshold
test.
Discharging time
 Interpretation of the ‘Repeat’ message:
It is not possible to differentiate between a disconnection moment at very low voltage and
a machine with a very low discharging time. In both cases the reading will be 0.0 s
together with the “Repeat” warning. If after few repetitions the result is always 0.0 s with
the “Repeat” message it can be considered as a valid 0.0 s result.
A 0.0 s reading without the “Repeat” message is a valid result.
 Residual voltage is not displayed for DUTs with very low discharging time, or if detected
disconnection voltage is lower than 20 V.

Z line mΩ, Z loop mΩ


 MI 3143 Euro Z 440 V, MI 3144 Euro Z 800 V or A 1143 Euro Z 290 A adapter is required
for these measurements.

AutoTT, Auto TN(RCD), Auto TN, Auto IT, Zauto


 Voltage drop (dU) measurement in each Auto test is enabled only if ZREF is set.
 See notes related to Zline, Zloop, Zs rcd, Voltage drop, Rpe, IMD and ISFL single tests.

Auto Sequences®
 Metrel Auto Sequences® are designed as guidance to tests in order to significantly
reduce testing time, improve work scope and increase traceability of the tests performed.
METREL assumes no responsibility for any Auto Sequence® by any means. It is the
user’s responsibility, to check adequacy for the purpose of use of the selected Auto
Sequence®. This includes type and number of tests, sequence flow, test parameters and
limits.
 Auto Sequences® mode allows building custom-defined test sequences.
 See notes related to single tests in the selected Auto Sequence®.
 Compensate test leads resistance before entering Auto Sequences®.
 Zref value for Voltage drop test (ΔU) implemented in any Auto Sequence® should be set
in single test function.

13
MI 3155 EurotestXD General description

1.2 Testing potential on PE terminal


In certain instance faults on the installation's PE wire or any other accessible metal bonding
parts can become exposed to live voltage. This is a very dangerous situation since the parts
connected to the earthing system are considered to be free of potential. In order to properly

check the installation against this fault the key should be used as an indicator prior to
performing live tests.

Examples for application of PE test terminal

Figure 1.1: Reversed L and PE conductors (plug commander)

Figure 1.2: Reversed L and PE conductors (application of 3-wire test lead)

Warning!

Reversed phase and protection conductors! The most dangerous situation!


If dangerous voltage is detected on the tested PE terminal, stop all measurements
immediately and ensure the cause of the fault is eliminated before proceeding
with any activity!

14
MI 3155 EurotestXD General description

Test procedure

 Connect test cable to the instrument.


 Connect test leads to the object under test, see Figure 1.1 and Figure 1.2.

 Touch test probe for at least 1 second.


If PE terminal is connected to phase voltage the warning message is displayed, display
is yellow coloured, instrument buzzer is activated and further measurements are
disabled: RCD tests, Z loop, Zs rcd, Z auto, AUTO TT, AUTO TN, AUTO TN (rcd) and
Auto Sequences®.

Notes:
 PE test terminal is active in the Voltage, Rpe, RCD tests, Z loop, Zs rcd, Z auto, Z line,
ΔU, AUTO TT, AUTO TN, AUTO TN (rcd), AUTO IT tests and Auto Sequences only!
 In case of detection of phase voltage on PE terminal in IT earthing system, the tests can
be enabled/disabled according to setting of parameter ‘Ignore PE probe warning (IT)’.

 For correct testing of PE terminal, the key has to be touched for at least 1 second.
 Make sure that the TEST key is grounded through human body resistance without any
insulated material between (gloves, shoes, insulated floors, pens, ...). PE test could
otherwise be impaired and results of a single test or Auto Sequence® can mislead. Even
detected dangerous voltage on PE test terminal cannot prevent running of a single test or
Auto Sequence®. All such behaviour is regarded as misuse. Operator of the instrument
must stop the activity immediately and eliminate the fault/connection problem before
proceeding with any activity!

15
MI 3155 EurotestXD General description

1.3 Battery and charging of Li-ion battery pack


The instrument is designed to be powered by rechargeable Li-ion battery pack. The LCD
contains an indication of battery condition (upper right section of LCD). In case the battery is too
weak the instrument indicates this as shown in Figure 1.3.

Symbol:
Indication of low battery.

Figure 1.3: Battery test

The battery is charged whenever the power supply is connected to the instrument. The charger
socket polarity is shown in Figure 1.4. Internal circuit controls (CC, CV) charging and assures
maximum battery lifetime. Nominal operating time is declared for battery with nominal capacity of
4.4 Ah.

Figure 1.4: Charger socket polarity

The instrument automatically recognizes the connected power supply and begins charging.

Symbol:
Indication of battery charging
Figure 1.5: Charging indication
(animation)

Battery and charging characteristic Typical


Battery types 18650T22A2S2P
18650T22A2S4P (optional)
Charging mode CC / CV
Nominal voltage 7,2 V
4400 mAh (type: 18650T22A2S2P)
Rated capacity
8800 mAh (type: 18650T22A2S4P)
Max charging voltage 8,0 V
Max charging current 2,2 A (type: 18650T22A2S2P)
3,0 A (type: 18650T22A2S4P)
Max discharge current 2,5 A
3 hours (type: 18650T22A2S2P)
Typical charging time
4,5 hours (type: 18650T22A2S4P)

16
MI 3155 EurotestXD General description

Typical charging profile which is also used in this instrument is shown in Figure 1.6.

Current Regulation Voltage Regulation


VREG
Cha
Vol rge
tage

ICH

Cha
C u r rg e
re n
t

VLOWV

ICH/8

Precharge
Fastcharge Safety Time
Time

Figure 1.6: Typical charging profile

where:
VREG ................................... Battery charging voltage
VLOWV.................................. Precharge threshold voltage
ICH ...................................... Battery charging current
ICH/8 .................................... 1/8 of the charging current

1.3.1 Precharge
On power up, if the battery voltage is below the VLOWV threshold, the charger applies 1/8 of the
charging current to the battery. The precharge feature is intended to revive deeply discharged
battery. If the VLOWV threshold is not reached within 30 minutes of initiating precharge, the
charger turns off and a FAULT is indicated.

Figure 1.7: Battery fault indication Figure 1.8: Battery full indication
(charging suspended, timer fault, battery (charging completed)
absent)
Note:
 As a safety backup, the charger also provides an internal 5-hour charge timer for fast
charge.

17
MI 3155 EurotestXD General description

Typical charging time is 3 hours (Battery type: 18650T22A2S2P) in the temperature range of
5°C to 60°C.

Current
Charge Charge
Charge
Suspended Suspended
Ich

Ich/8

Temperature

TWARM
TCOOL

THTF
TLTF

Figure 1.9: Typical charging current vs temperature profile

where:
TLTF ........... Cold temperature threshold (typ. -15°C)
TCOOL ......... Cool temperature threshold (typ. 0°C)
TWARM ........ Warm temperature threshold (typ. +60°C)
THTF ........... Hot temperature threshold (typ. +75°C)
The charger continuously monitors battery temperature. To initiate a charge cycle, the battery
temperature must be within the TLTF to THTF thresholds. If battery temperature is outside of this
range, the controller suspends charge and waits until the battery temperature is within the TLTF to
THTF range.
If the battery temperature is between the TLTF and TCOOL thresholds or between the TWARM and
THTW thresholds, charge is automatically reduced to ICH/8 (1/8 of the charging current).

18
MI 3155 EurotestXD General description

1.3.2 Li – ion battery pack guidelines


Li – ion rechargeable battery pack requires routine maintenance and care in their use and
handling. Read and follow the guidelines in this Instruction manual to safely use Li – ion battery
pack and achieve the maximum battery life cycles.
Do not leave batteries unused for extended periods of time – more than 6 months (self –
discharge).
When a battery has been unused for 6 months, check the charge status see chapter 4.4.2
Battery indication. Rechargeable Li – ion battery pack has a limited life and will gradually lose
their capacity to hold a charge. As the battery loses capacity, the length of time it will power the
product decreases.

Storage
 Charge or discharge the instruments battery pack to approximately 50 % of capacity
before storage.
 Charge the instrument battery pack to approximately 50 % of capacity at least once
every 6 months.

Transportation
 Always check all applicable local, national, and international regulations before
transporting a Li – ion battery pack.

Handling Warnings

 Do not disassemble, crush, or puncture a battery in any way.


 Do not short circuit or reverse polarity the external contacts on a battery.
 Do not dispose of a battery in fire or water.
 Avoid exposing the battery to excessive shock/impacts or vibration.
 Do not use a damaged battery.
 The Li – ion battery contains safety and protection circuit, which if damaged, may
cause the battery to generate heat, rupture or ignite.
 Do not leave a battery on prolonged charge when not in use.
 If a battery has leaking fluids, do not touch any fluids.
 In case of eye contact with fluid, do not rub eyes. Immediately flush eyes
thoroughly with water for at least 15 minutes, lifting upper and lower lids, until no
evidence of the fluid remains. Seek medical attention.

19
MI 3155 EurotestXD General description

1.4 Standards applied


The EurotestXD instruments are manufactured and tested in accordance with the following
regulations:
Electromagnetic compatibility (EMC)
EN 61326-1 Electrical equipment for measurement, control and laboratory
use – EMC requirements – Part 1: General requirements
EN 61326-2-2 Electrical equipment for measurement, control and laboratory use - EMC
requirements – Part 2-2: Particular requirements - Test configurations,
operational conditions and performance criteria for portable test, measuring
and monitoring equipment used in low-voltage distribution systems
Safety (LVD)
EN 61010-1 Safety requirements for electrical equipment for measurement, control and
laboratory use – Part 1: General requirements
EN 61010-2-030 Safety requirements for electrical equipment for measurement, control and
laboratory use – Part 2-030: Particular requirements for testing and
measuring circuits
EN 61010-031 Safety requirements for electrical equipment for measurement, control and
laboratory use – Part 031: Safety requirements for hand-held probe
assemblies for electrical measurement and test
EN 61010-2-032 Safety requirements for electrical equipment for measurement, control, and
laboratory use - Part 2-032: Particular requirements for hand-held and hand-
manipulated current sensors for electrical test and measurement
Functionality
EN 61557 Electrical safety in low voltage distribution systems up to 1000 VAC and 1500
VAC – Equipment for testing, measuring or monitoring of protective measures
Part 1: General requirements
Part 2: Insulation resistance
Part 3: Loop resistance
Part 4: Resistance of earth connection and equipotential bonding
Part 5: Resistance to earth
Part 6: Residual current devices (RCDs) in TT and TN systems
Part 7: Phase sequence
Part 10: Combined measuring equipment
Part 12: Performance measuring and monitoring devices (PMD)
Part 14: Equipment for testing the safety of electrical equipment for
machinery
DIN 5032 Photometry
Part 7: Classification of illuminance meters and luminance meters
Reference standards for electrical installations and components
EN 61008 Residual current operated circuit-breakers without integral overcurrent
protection for household and similar uses
EN 61009 Residual current operated circuit-breakers with integral overcurrent
protection for household and similar uses
IEC 60364-4-41 Electrical installations of buildings Part 4-41 Protection for safety –
protection against electric shock
BS 7671 IEE Wiring Regulations (18th edition)
AS/NZS 3017 Electrical installations – Verification guidelines
IEC 62752 In-cable control and protection device for mode 2 charging of electric road
vehicles (IC-CPD)
IEC 62955 Residual direct current detecting device (RDC-DD) to be used for mode 3
charging of electric vehicles

20
MI 3155 EurotestXD General description

Li – ion battery pack


EN 62133-2 Secondary cells and batteries containing alkaline or other non-acid
electrolytes – Safety requirements for portable sealed secondary lithium cell,
and for batteries made from them, for use in portable applications – Part 2:
Lithium systems protection for household and similar uses

21
MI 3155 EurotestXD Instrument set and accessories

2 Instrument set and accessories


2.1 Standard set MI 3155 EurotestXD
 Instrument MI 3155 EurotestXD
 Soft carrying bag
 Set of carrying straps
 Earth set, 3-wire, 20 m
 Plug commander, 1.5 m + 2 batteries, size AAA
 3-wire test lead, 3 x 1.5 m
 4-wire test lead, 4 x 1.5 m
 2.5 kV test lead, 2 x 1.5 m
 Test probe, 4 pcs (black, blue, green, red)
 Crocodile clip, 6 pcs (black × 2, blue, green, red × 2)
 Current clamp 1000:1
 Current clamp (low range, leakage)
 RS232-PS/2 cable
 USB cable
 Li-ion battery pack, 7.2 V , 4400 mAh (Type: 18650T22A2S2P)
 Power supply adapter 12 V, 3 A (Type: CGSW-1203000)
 CD includes:
- PC software Metrel ES Manager
- Instruction manual
- “Guide for testing and verification of low voltage installations”
handbook
 Quick guide
 Calibration Certificate

2.1.1 Optional accessories


See the attached sheet for a list of optional accessories that are available on request from your
distributor.

22
MI 3155 EurotestXD Instrument description

3 Instrument description
3.1 Front panel

Figure 3.1: Front panel

1 4,3“ COLOR TFT DISPLAY WITH TOUCH SCREEN


SAVE key
2
Stores actual measurement result(s)
CURSOR keys
3
Navigate in menus
RUN key
Start / stop selected measurement.
4
Enter selected menu or option.
View available values for selected parameter / limit.
ON / OFF key
Switch instrument on / off.
5 The instrument automatically switches off after 10 minutes of idle
state (no key pressed or any touchscreen activity)
Press and hold the key for 5 s to switch off the instrument.
GENERAL SETTINGS key
6
Enter General settings menu.
OPTIONS key
7
Show detailed view of options.
MEMORY ORGANIZER shortcut key
8
Shortcut key to enter Memory organizer menu.
SINGLE TESTS shortcut key
9
Shortcut key to enter Single Tests menu.
AUTO SEQUENCES shortcut key
10
Shortcut key to enter Auto Sequences menu.
ESC key
11
Back to previous menu.

23
MI 3155 EurotestXD Instrument description

3.2 Connector panel

Figure 3.2: Connector panel

Test connector
L/L1 pin – In 4-wire measurements used as a current probe C1.
1 N/L2 pin – In 4-wire measurements used as a current probe C2.
PE/L3 pin – In 4-wire measurements used as a voltage probe P2.
S pin – In 4-wire measurements used as a voltage probe P1.
2 Protection cover
3 Protection cover – PS/2 communication port
Charger socket
4

USB communication port


5
Communication with PC USB (2.0) port
PS/2 communication port
Communication with PC RS232 serial port
6
Connection to optional measuring adapters
Connection to barcode / RFID reader
P/S input
7
External probe input for contact voltage measurement
C1 inputs
8
Current clamp measuring input

Warnings!
 Maximum allowed voltage between any test terminal and ground is 550 V!
 Maximum allowed voltage between test terminals on test connector is 550 V!
 Maximum allowed voltage on test terminal C1 is 3 V!
 Maximum short-term voltage of external power supply adapter is 14 V!

24
MI 3155 EurotestXD Instrument description

3.3 Back side

Figure 3.3: Back view

1 Battery / fuse compartment cover


2 Fixing screws for battery / fuse compartment cover
3 Back panel information label

Figure 3.4: Battery and fuse compartment

Type: 18650T22A2S2P
1 Li-ion battery pack
Type: 18650T22A2S4P (optional)
2 Fuse F1 M 315 mA / 250 V
3 Fuses F2 and F3 F 5 A / 500 V (breaking capacity 50 kA)

25
MI 3155 EurotestXD Instrument description

4 SD card slot

Figure 3.5: Bottom view

1 Neck belt openings


2 Stand for desktop use
3 Bottom information label
4 Serial number label

26
MI 3155 EurotestXD Instrument description

3.4 Carrying the instrument


With the neck-carrying belt supplied in standard set, various possibilities of carrying the
instrument are available. Operator can choose appropriate one on basis of his operation, see
the following examples:

The instrument hangs


around operator’s neck
only – quick placing and
displacing.

The instrument can be used even when placed in soft


carrying bag – test cable connected to the instrument
through the front aperture.

3.4.1 Secure attachment of the strap


You can choose between two methods:

Figure 3.6: First method

27
MI 3155 EurotestXD Instrument description

Figure 3.7: Alternative method

Please perform a periodical check of the attachment.

28
MI 3155 EurotestXD Instrument operation

4 Instrument operation
The EurotestXD instrument can be manipulated via a keypad or touch screen.

4.1 General meaning of keys

Cursor keys are used to:


 select appropriate option.

Run key is used to:


 confirm selected option;
 start and stop measurements;
 test PE potential.
Escape key is used to:
 return to previous menu without changes;
 abort measurements.
Option key is used to:
 expand column in control panel.
Save key is used to:
 store test results.

Auto Sequences key is used as:


 ... shortcut key to enter Auto Sequences menu.
Single Tests key is used as:
 shortcut key to enter Single Tests menu.

Memory Organizer key is used as:


 shortcut key to enter Memory Organizer menu.

General Settings key is used to:


 enter General Settings menu.

On / Off key is used to:


 switch On / Off the instrument;
 switch Off the instrument if pressed and held for 5 s.

29
MI 3155 EurotestXD Instrument operation

4.2 General meaning of touch gestures

Tap (briefly touch surface with fingertip) is used to:


 select appropriate option;
 confirm selected option;
 start and stop measurements.
Swipe (press, move, lift) up / down is used to:
 scroll content in same level;
 navigate between views in same level.
Long press (touch surface with fingertip for at least 1 s) is used to:
 select additional keys (virtual keyboard);
long  enter cross selector from single test screens.
Tap Escape icon is used to:
 return to previous menu without changes;
 abort measurements.

30
MI 3155 EurotestXD Instrument operation

4.3 Virtual keyboard

Figure 4.1: Virtual keyboard

Toggle case between lowercase and uppercase.


Active only when alphabetic characters keyboard layout selected.

Backspace
Clears last character or all characters if selected.
(If held for 2 s, all characters are selected).

Enter confirms new text.

Activates numeric / symbols layout.

Activates alphabetic characters.

English keyboard layout.

Greek keyboard layout.

Russian keyboard layout.

Returns to the previous menu without changes.

31
MI 3155 EurotestXD Instrument operation

4.4 Display and sound


4.4.1 Terminal voltage monitor
The terminal voltage monitor displays on-line the voltages on the test terminals and information
about active test terminals in the a.c. installation measuring mode.

Online voltages are displayed together with test terminal indication.


All three test terminals are used for selected measurement.

Online voltages are displayed together with test terminal indication.


L and N test terminals are used for selected measurement.
Online voltages are displayed together with test terminal indication.
L and PE are active test terminals.
N terminal should also be connected for correct input voltage condition.
L and N are active test terminals.
PE terminal should also be connected for correct input voltage condition.

Polarity of test voltage applied to the output terminals, L and N.

L and PE are active test terminals.

Polarity of test voltage applied to the output terminals, L and PE.

2.5 kV Insulation measurement terminal screen.

4-wire test terminal indication.

4-wire test terminal indication with online voltage between P1 and P2 probes.

Test terminals for Discharging time measurement.

32
MI 3155 EurotestXD Instrument operation

4.4.2 Battery indication


The battery indication indicates the charge condition of battery and connection of external
charger.
Battery capacity indication.
Battery is in good condition.
Battery is full.
Low battery.
Battery is too weak to guarantee correct result. Replace or recharge
the battery cells.
Empty battery or no battery.

Charging in progress (if power supply adapter is connected).

Charging finished.

4.4.3 Bluetooth

Bluetooth communication inactive.

Bluetooth communication active.

4.4.4 Measurement actions and messages

Conditions on the input terminals allow starting the measurement. Consider


other displayed warnings and messages.
Conditions on the input terminals do not allow starting the measurement.
Consider displayed warnings and messages.
Proceeds to next step of the measurement.

Stop the measurement.

Result(s) can be stored.

Starts test leads compensation in Rlow / Continuity measurement.


Starts Zref line impedance measurement at origin of electrical installation in
Voltage Drop measurement. Zref value is set to 0.00 Ω if pressing this touch
key while instrument is not connected to a voltage source.
Alternates between A 1507 3-Phase Active Switch and Plug/Tip Commander.
This option is available only if A 1507 is enabled in Settings menu, see
chapter 4.6.8.1 Adapters.
Use A 1199 Specific earth resistance adapter for this test.

33
MI 3155 EurotestXD Instrument operation

Use MI 3143 Euro Z 440 V, MI 3144 Euro Z 800 V or A 1143 Euro Z 290 A
adapter for this test.
Use A 1172 or A 1173 Illumination sensor for this test.

A 1507 3-Phase Active Switch not connected to the instrument.


Connect A 1507 test cable to the instrument.
Test / Measurement cannot be performed using A 1507.
A 1507 3-Phase Active Switch connected to the instrument via test cable and
Bluetooth communication.
Test / Measurement can be performed using A 1507.
Count down timer (in seconds) within measurement.

Measurement is running, consider displayed warnings.

RCD tripped-out during the measurement (in RCD functions).

Instrument is overheated. The measurement is prohibited until the


temperature decreases under the allowed limit.
High electrical noise was detected during measurement. Results may be
impaired.
Indication of noise voltage above 5 V between H and E terminals during earth
resistance measurement.
L and N are changed.
In most instrument profiles L and N test terminals are reversed automatically
according to detected voltages on input terminal. In instrument profiles for
countries where the position of phase and neutral connector is defined the
selected feature is not working.
Warning! High voltage is applied to the test terminals.
The instrument automatically discharge tested object after finished insulation
measurement.
When an insulation resistance measurement has been performed on a
capacitive object, automatic discharge may not be done immediately! The
warning symbol and the actual voltage are displayed during discharge until
voltage drops below 30 V.
Warning! Dangerous voltage on the PE terminal! Stop the activity
immediately and eliminate the fault / connection problem before proceeding
with any activity!
Continuous sound warning and yellow coloured screen is also present.
Test leads resistance in R low / Continuity measurement is not compensated.

Test leads resistance in R low / Continuity measurement is compensated.

High resistance to earth of current test probes. Results may be impaired.

34
MI 3155 EurotestXD Instrument operation

High resistance to earth of potential test probes. Results may be impaired.

High resistance to earth of potential and current test probes. Results may be
impaired.
Too small current for declared accuracy. Results may be impaired. Check in
Current Clamp Settings if sensitivity of current clamp can be increased.
In Earth 2 Clamp measurement results are very accurate for resistances
below 10 Ω. At higher values (several 10 Ω) the test current drops to few mA.
The measuring accuracy for small currents and immunity against noise
currents must be considered!
Measured signal is out of range (clipped). Results are impaired.

Single fault condition in IT system.

Fuse F1 is broken.

4.4.5 Result indication

Measurement result is inside pre-set limits (PASS).

Measurement result is out of pre-set limits (FAIL).

Measurement is aborted. Consider displayed warnings and messages.


RCD t and RCD I measurements will only be performed if the contact voltage
in the pre-test at nominal differential current is lower than the set contact
voltage limit!

4.4.6 Auto Sequence® result indication

All Auto Sequence® results are inside pre-set limits


(PASS).

One or more Auto Sequence® results are out of pre-


set limits (FAIL).

Overall Auto Sequence® result without PASS/FAIL


indication

Overall Auto Sequence® result with empty (aborted)


single tests

35
MI 3155 EurotestXD Instrument operation

Measurement result is inside pre-set limits (PASS).

Measurement result is out of pre-set limits (FAIL).

Measurement result without PASS / FAIL indication.

Measurement not performed.

36
MI 3155 EurotestXD Instrument operation

4.5 Instruments main menu


From the Main menu different main operation menus can be selected.

Figure 4.2: Main menu

Options

Single Tests
Menu with single tests, see chapter 6 Single tests.

Auto Sequences
Menu with customized test sequences, see chapter 8 Auto
Sequences®.

Memory Organizer
Menu for working with and documentation of test data, see chapter 5
Memory Organizer.

General Settings
Menu for setup of the instrument, see chapter 4.6 General Settings.

37
MI 3155 EurotestXD Instrument operation

4.6 General Settings


In the General settings menu general parameters and settings of the instrument can be
viewed or set.

Figure 4.3: General settings menu

Options

Language
Instrument language selection.

Power Save
Brightness of LCD, enabling/disabling Bluetooth communication.

Date /Time
Instruments Date and time.

Workspace Manager
Manipulation with project files. Refer to chapter 4.8 Workspace Manager
for more information.

Auto Sequences groups


Manipulation with lists of Auto Sequences®. Refer to chapter 4.9 Auto
Sequence® groups for more information.

User accounts
User accounts settings. Refer to chapter 4.6.6 User accounts for more
information.

Instrument Profile
Selection of available instrument profiles. Refer to chapter 4.7 Instrument
profiles for more information.

Settings
Refer to chapter 4.6.8 Settings for more information.

Devices
Selection of external devices. Refer to chapter 4.6.9 Devices for more
information.

38
MI 3155 EurotestXD Instrument operation

Bluetooth initialization
Reset Bluetooth settings.

Initial Settings
Factory settings.

About
Instrument info.

4.6.1 Language
In this menu the language of the instrument can be set.

Figure 4.4: Language menu

4.6.2 Power Save


In this menu different options for decreasing power consumption can be set.

Figure 4.5: Power save menu

Brightness Setting level of LCD brightness level.


Power saving at low level: approx. 15%
LCD off time Setting LCD off after set time interval. LCD is switched on after pressing
any key or touching the LCD.
Power saving at LCD off (at low level brightness): approx. 20%
Bluetooth Always On: Bluetooth module is ready to communicate.
Save mode: Bluetooth module is set to sleep mode and is not functioning.
Power saving in Save mode: 7 %

39
MI 3155 EurotestXD Instrument operation

4.6.3 Date and time


In this menu date and time of the instrument can be set.

Figure 4.6: Setting date and time

Note:
 If the batteries are removed the set date and time will be lost.

4.6.4 Workspace manager


Refer to chapter 4.8 Workspace Manager for more information.

4.6.5 Auto Sequences groups


Refer to chapter 4.9 Auto Sequence® groups for more information.

4.6.6 User accounts


The demand to sign in can prevent from unauthorized persons to work with the instrument.
In this menu user accounts can be managed:
▪ Setting if signing in to work with the instrument is required or not.
▪ Adding and deleting new users, setting their user names and passwords.

The user accounts can be managed by the administrator.


Factory set administrator password: ADMIN
It is recommended to change factory set administrator password after first use. If the custom
password is forgotten the second administrator password can be used. This password always
unlocks the Account manager and is delivered with the instrument.

If a user account is set and the user is signed in the user's name will be stored in memory for
each measurement.
Individual users can change their passwords.

40
MI 3155 EurotestXD Instrument operation

4.6.6.1 Signing in

If signing in is demanded the user must enter the password in order to work with the instrument.

Figure 4.7: Sign in menu

Options

User signing in

The user should be selected first.


The last used user is displayed in the first row.

Sign in with selected user name.

Enter the password and confirm.


The user password consists of an up to 4 digit number.

41
MI 3155 EurotestXD Instrument operation

Administrator signing in

The Account manager menu is accessed by selecting


Account manager in Sign in menu or User profile menu.

The account manager password must be entered and


confirmed first.
Administrator password consists of letters and/or
numbers. Letters are case sensitive.
The default password is ADMIN.

4.6.6.2 Changing user password, signing out

Figure 4.8: User profile menu

Options
Signs out the set user.

Enters procedure for changing the user’s password.

The user can change its password. The actual


password must be entered first followed by the new
password.

Enters the Account manager menu.

42
MI 3155 EurotestXD Instrument operation

4.6.6.3 Managing accounts

Figure 4.9: Account manager menu

Options
The Account manager menu is accessed by selecting
Account manager in Sign in menu or User profile menu.

The account manager password must be entered and


confirmed first.
The default password is ADMIN.

Field for setting if signing in is required to work with the


instrument.
Field for setting if signing is required once or at each
power on of the instrument.
Field for setting Blackbox password.

Enters procedure for changing the account manager


(administrator) password.
To change the password the actual and then the new
password should be entered and confirmed.

Enters menu for editing user accounts.

43
MI 3155 EurotestXD Instrument operation

Figure 4.10: Edit accounts menu

Options
Opens the window for adding a new user.

In the Add New window the name and initial password


of the new user account are to be set.
‘Add’ confirms the new user data.

Changes password of the selected user account.

Deletes all user accounts.


Deletes the selected user account.

44
MI 3155 EurotestXD Instrument operation

4.6.6.4 Setting Blackbox password

Blackbox password can be set by administrator from the Account manager menu. Set Blackbox
password is valid for all users. Default Blackbox password is empty (disabled).

Options

Add or edit Blackbox password. Enter to modify.

Keyboard for entering new Blackbox password is


opened. Empty string disables password.
Confirm entry.

Blackbox password is changed.

4.6.7 Profiles
Refer to chapter 4.7 Instrument profiles for more information.

4.6.8 Settings
In this menu different general parameters can be set.

Figure 4.11: Settings menu

45
MI 3155 EurotestXD Instrument operation

Available selection Description


Touch screen [ON, OFF] Enables / disables operation with touch screen.
Keys & touch [ON, OFF] Enables / disables sound when touch screen
sound or key is pressed.
Isc factor [Custom, 0.20 ... 3.00] Short circuit current Isc in the supply system is
Default value: 1.00 important for selection or verification of
protective circuit breakers (fuses, over-current
breaking devices, RCDs). The value should be
set according to local regulative.
Earthing [TN/TT, IT] Terminal voltage monitor and measuring
system functions are suited to selected earthing
system.
In some measuring functions the results and
parameters are suited to the selected system.
RCD Standard [EN 61008 / EN 61009, Used standards for RCD tests. Refer to the
IEC 60364-4-41 TN/IT, end of this chapter for more information.
IEC 60364-4-41 TT, Maximum RCD disconnection times differ in
BS 7671, various standards.
AS/NZS 3017, The trip-out times defined in individual
VDE 0664, standards are listed below.
VDE 0100-410 TN/IT,
VDE 0100-410 TT]
EV RCD/RCM [IEC 62752, IEC 62955] Used standards for EV RCD, MI RCD and EV
Standards RCM tests.
Length Unit [m, ft] Length unit for specific earth resistance
measurement.
Ch1 clamp type [A 1018, A1391] Model of current clamp adapter.
Range A 1018: [20 A] Measuring range of selected current clamp
A 1391: [40 A, 300 A] adapter.
Measuring range of the instrument must be
considered. Measurement range of current
clamp adaptor can be higher than of the
instrument.
Merge fuses [yes, no] [Yes]: Fuse type and parameters set in one
function are also kept for other functions!
[No]: Fuse parameters will be considered only
in function where they have been set.
Ignore PE [yes, no] [yes]: In IT earthing system the instrument will
warning (IT) allow to start the selected measurement
regardless of PE warning detection.
[no], In IT earthing system the instrument will
block the selected measurement if PE warning
is detected.
Uc pretest (IT) [yes, no] [yes]: In IT earthing system the instrument will
inhibit the selected measurement if result
exceed set Uc limit.
[no]: In IT earthing system the instrument will
present warning message, if result exceed set
Uc limit; operator should confirm to proceed
with selected measurement

IscMax, IscMin [yes, no] [yes]: IscMax, IscMin calculation is enabled in


calculation Z line measurement.
[no]: IscMax, IscMin calculation is disabled in Z

46
MI 3155 EurotestXD Instrument operation

line measurement.
Load pretest [yes, no] [yes]: Load pretest is enabled in Riso and
Riso-all measurements.
[no]: Load pretest is disabled.
External Device [None, Commander, [None]: This option is intended to disable the
A 1507] commander’s remote keys. In case of high EM
interfering noise the operation of the
commander can be irregular.
[Commander]: Working with commander
enabled.
[A 1507]: Working with 3-phase active switch
enabled.
Limit Uc [Custom, 12 V, 25 V, Contact voltage limit.
50 V]

4.6.8.1 Adapters

Settings menu provide selection and configuration of Metrel measuring adapters to perform
supported tests and measurements. See Appendix G for details on available Metrel adapters
and supported tests.

Available selection Description


Adapter type [none, selected adapter] Selection from list of available adapters.
Port [RS232, Bluetooth] Sets communication port of selected
measuring adapter.
See chapter 9.3 Communication with
adapters for more details.
Bluetooth Name of selected adapter After searching is finished, list of all available
device name Bluetooth devices is presented.
Pair the instrument with selected measuring
adapter.

4.6.8.2 RCD standard

Maximum RCD disconnection times differ in various standards. The trip-out times defined in
individual standards are listed below.

½IN1) IN 2IN 5IN


General RCDs
t > 300 ms t < 300 ms t < 150 ms t < 40 ms
(non-delayed)
Selective RCDs
t > 500 ms 130 ms < t < 500 ms 60 ms < t < 200 ms 50 ms < t < 150 ms
(time-delayed)
Table 4.1: Trip-out times according to EN 61008 / EN 61009

Test according to standard IEC/HD 60364-4-41 has two selectable options:


• IEC 60364-4-41 TN/IT and
• IEC 60364-4-41 TT
The options differ to maximum disconnection times as defined in IEC/HD 60364-4-41 Table
41.1.

U0 3) ½IN1) IN 2IN 5IN


TN / IT  120 V t > 800 ms t  800 ms t < 150 ms t < 40 ms

47
MI 3155 EurotestXD Instrument operation

 230 V t > 400 ms t  400 ms


 120 V t > 300 ms t  300 ms
TT
 230 V t > 200 ms t  200 ms
Table 4.2: Trip-out times according to IEC/HD 60364-4-41

½IN1) IN 2IN 5IN


General RCDs
t> 1999 ms t< 300 ms t< 150 ms t< 40 ms
(non-delayed)
Selective RCDs
t> 1999 ms 130 ms < t< 500 ms 60 ms < t< 200 ms 50 ms < t< 150 ms
(time-delayed)
Table 4.3: Trip-out times according to BS 7671

½IN1) IN 2IN 5IN


RCD type IN (mA) Note
t t t t
I  10 40 ms 40 ms 40 ms
II > 10  30 > 999 ms 300 ms 150 ms 40 ms
Maximum break time
III > 30 300 ms 150 ms 40 ms
500 ms 200 ms 150 ms
IV S > 30 > 999 ms
130 ms 60 ms 50 ms Minimum non-actuating time
Table 4.4: Trip-out times according to AS/NZS 30172)

Standard ½IN IN 2IN 5IN


EN 61008 / EN 61009 300 ms 300 ms 150 ms 40 ms
IEC 60364-4-41 1000 ms 1000 ms 150 ms 40 ms
BS 7671 2000 ms 300 ms 150 ms 40 ms
AS/NZS 3017 (I, II, III) 1000 ms 1000 ms 150 ms 40 ms
Table 4.5: Maximum test times related to selected test current for general (non-delayed)
RCD

Standard ½IN IN 2IN 5IN


EN 61008 / EN 61009 500 ms 500 ms 200 ms 150 ms
IEC 60364-4-41 1000 ms 1000 ms 150 ms 40 ms
BS 7671 2000 ms 500 ms 200 ms 150 ms
AS/NZS 3017 (IV) 1000 ms 1000 ms 200 ms 150 ms
Table 4.6: Maximum test times related to selected test current for selective (time-delayed)
RCD
1)
Minimum test period for current of ½IN, RCD shall not trip-out.
2)
Test current and measurement accuracy correspond to AS/NZS 3017 requirements.
3)
U0 is nominal ULPE voltage.

Notes:
 Trip-out limit times for PRCD, PRCD-K and PRCD-S are equal to General (non-delayed)
RCDs.
 The trip-out times of VDE 0664 are equal to trip-out times of EN 61008 / EN 61009.
 The trip-out times of VDE 0100-410 TN/IT are equal to trip-out times of IEC 60364-4-41
TN/IT.
 The trip-out times of VDE 0100-410 TT are equal to trip-out times of IEC 60364-4-41 TT.

48
MI 3155 EurotestXD Instrument operation

4.6.8.3 EV RCD/RCM standards

Supported standards:
IEC 62752:2016 In-cable control and protection device for mode 2 charging of electric road
vehicles (IC-CPD)
IEC 62955:2018 Residual direct current detecting device (RDC-DD) to be used for mode 3
charging of electric vehicles

6 mA 60 mA 200 mA 300 mA
Standard
(1  IN) (10  IN) (33  IN) (50  IN)
IEC 629551) < 10.0 s < 300 ms < 100 ms 
IEC 627522) < 10.0 s < 300 ms  < 40 ms
Table 4.7: Break times for d.c. residual currents
1) IEC 62955: Table 2 – Maximum values of break times for residual direct currents
2) IEC 62752: Table 3 – Limit values of break time for smooth d.c. residual currents

30 mA 60 mA 150 mA
Standard
(1  IN) (2  IN) (5  IN)
IEC 627523) < 300 ms < 150 ms < 40 ms
Table 4.8: Break times for a.c. residual currents
3) IEC 62752: Table 2 – Limit values of break time for a.c. residual currents at rated
frequency

Up to 30 mA 60 mA 150 mA
Standard
(1  IN) (2  IN) (5  IN)
IEC 629554) No tripping > 300 ms > 80 ms
Table 4.9: Non-operating times for a.c. residual currents
4) IEC 62955: Table 3 – Minimum values of non-operating time for alternating residual
currents (RMS values)

49
MI 3155 EurotestXD Instrument operation

4.6.9 Devices
In this menu operation with external devices is configured.

Figure 4.12: Device settings menu

Reading devices
Type Sets appropriate reading device (QR or barcode scanner, RFID
reader, via aMESM application).
Port Sets communication port of selected reading device.
Bluetooth device Goes to menu for pairing with selected Bluetooth device.
name

4.6.10 Bluetooth initialization


In this menu the Bluetooth module is reset.

Figure 4.13: Bluetooth initialization menu

4.6.11 Initial Settings


In this menu the instrument settings, measurement parameters and limits can be set to initial
(factory) values.

50
MI 3155 EurotestXD Instrument operation

Figure 4.14: Initial settings menu

Warning!
Following customized settings will be lost when setting the instruments to initial settings:
 measurement limits and parameters,
 global parameters, system settings, and Devices in General settings menu,
 opened Workspace and Auto Sequences group will be deselected,
 user will be signed out.

 If the battery pack is removed the custom-made settings will be lost.

Note:
Following customized settings will stay:
 profile settings,
 data in memory (Data in memory organizer, Workspaces, Auto Sequences groups,
Auto Sequences) and
 user accounts.

4.6.12 About
In this menu instrument data (name, serial number, firmware (FW) and hardware (HW) version,
FW profile, hardware documentation (HD) version, fuse version and date of calibration) can be
viewed.

Figure 4.15: Instrument info screen

Note:
 Adapter info is also displayed, if connected.

51
MI 3155 EurotestXD Instrument operation

4.7 Instrument profiles


In this menu the instrument profile can be selected from the available ones.

Figure 4.16: Instrument profiles menu

The instrument uses different specific system and measuring settings in regard to the scope of
work or country it is used. These specific settings are stored in instrument profiles.

By default, each instrument has at least one profile activated. Proper licence keys must be
obtained to add more profiles to the instruments.

If different profiles are available, they can be selected in this menu.

Options

Loads the selected profile. The instrument will restart


automatically with new profile loaded.

Deletes the selected profile.

Before deleting the selected profile, user is asked for


confirmation.

Opens more options in control panel / expands


column.

52
MI 3155 EurotestXD Instrument operation

4.8 Workspace Manager


The Workspace Manager is intended to manage with different Workspaces and Exports that are
stored on the SD memory card.

4.8.1 Workspaces and Exports


The works with MI 3155 EurotestXD can be organized and structured with help of Workspaces
and Exports. Exports and Workspaces contain all relevant data (measurements, parameters,
limits, structure objects) of an individual work.
Workspaces are stored on SD card on directory WORKSPACES, while Exports are stored on
directory EXPORTS. Export files can be read by METREL applications that run on other
devices. Exports are suitable for making backups of important works. To work on the instrument
an Export should be imported first from the list of Exports and converted to a Workspace. To be
stored as Export data a Workspace should be exported first from the list of Workspaces and
converted to an Export.

4.8.2 Workspace Manager main menu


In Workspace manager Workspaces and Exports are displayed in two separated lists.

Figure 4.17: Workspace manager menu

Options

List of Workspaces.

Displays a list of Exports.

Adds a new Workspace.


Refer to chapter 0
Adding a new Workspace for more information.

List of Exports.

Displays a list of Workspaces.

Opens more options in control panel / expands


column.

53
MI 3155 EurotestXD Instrument operation

4.8.3 Operations with Workspaces


Only one Workspace can be opened in the instrument at the same time. The Workspace
selected in the Workspace Manager will be opened in the Memory Organizer.

Figure 4.18: Workspaces menu

Options
Marks the opened Workspace in Memory Organizer.
Opens the selected Workspace in Memory Organizer.
Refer to chapter 4.8.6 Opening a Workspace for more information.

Deletes the selected Workspace.


Refer to chapter 4.8.7 Deleting a Workspace / Export for more information.

Adds a new Workspace.


Refer to chapter 0
Adding a new Workspace for more information.

Exports a Workspace to an Export.


Refer to 4.8.9 Exporting a Workspace for more information.

Opens more options in control panel / expands column.

4.8.4 Operations with Exports

Figure 4.19: Workspace manager Exports menu

54
MI 3155 EurotestXD Instrument operation

Options

Deletes the selected Export.


Refer to chapter 4.8.7 Deleting a Workspace / Export for more information.
Imports a new Workspace from Export.
Refer to 4.8.8 Importing a Workspace for more information.
Opens more options in control panel / expands column.

4.8.5 Adding a new Workspace


Procedure

 New Workspaces can be added from the


Workspace Manager screen.

 Enters option for adding a new


Workspace.
Keypad for entering name of a new
Workspace is displayed after selecting
New.

 After confirmation a new Workspace is


added in the list in Main Workspace
Manager menu.

55
MI 3155 EurotestXD Instrument operation

4.8.6 Opening a Workspace


Procedure

 Workspace can be selected from a list in


Workspace manager screen.

 Opens a Workspace in Workspace


manager.
The opened Workspace is marked with a
blue dot. The previously opened
Workspace will close automatically.

4.8.7 Deleting a Workspace / Export


Procedure

 Workspace / Export to be deleted should


be selected from the list of Workspaces /
Exports.
Opened workspace can’t be deleted.

 Enters option for deleting a Workspace /


Export.
Before deleting the selected Workspace /
Export the user is asked for confirmation.

56
MI 3155 EurotestXD Instrument operation

 Workspace / Export is deleted from the


Workspace / Export list.

4.8.8 Importing a Workspace

 Select an Export file to be imported from


Workspace manager Export list.

 Enters option Import.

Before the import of the selected Export


file the user is asked for confirmation.

 The imported Export file is added to the list


of Workspaces.
Note:
If a Workspace with the same name
already exists the name of the imported
Workspace will be changed (name_001,
name_002, name_003, …).

57
MI 3155 EurotestXD Instrument operation

4.8.9 Exporting a Workspace

 Select a Workspace from Workspace


manager list to be exported to an Export
file.

 Enters option Export.

Before exporting the selected Workspace


the user is asked for confirmation.

 Workspace is exported to Export file and is


added to the list of Exports.
Note:
If an Export file with the same name
already exists the name of the Export file
will be changed (name_001, name_002,
name_003 …).

58
MI 3155 EurotestXD Instrument operation

4.9 Auto Sequence® groups


The Auto Sequences® in MI 3155 EurotestXD can be organized by using lists. In a list a group
of similar Auto Sequences® is stored. The Auto Sequence® groups menu is intended to
manage with different lists of Auto Sequences® that are stored on the SD card.

Figure 4.20: Organization of Auto Sequences® on SD card

Folders with lists of Auto Sequences® are stored in Root\__MOS__\AT on the SD card.

4.9.1 Auto Sequence® groups menu


In Auto Sequence groups menu lists of Auto Sequences are displayed. Only one list can be
opened in the instrument at the same time. The list selected in the Auto Sequence groups
menu will be opened in the Auto Sequences main menu.

Figure 4.21: Auto Sequences groups menu

Operations in Auto Sequences groups menu

Opens the selected list of Auto Sequences. Previously selected list of Auto
Sequences will be closed automatically.
Refer to chapter 4.9.1.1 Selecting a list of Auto Sequences for more information.

Deletes the selected list of Auto Sequences.


Refer to chapter 4.9.1.2 Deleting a list of Auto Sequences® for more information.

Opens options in control panel / expands column.

59
MI 3155 EurotestXD Instrument operation

4.9.1.1 Selecting a list of Auto Sequences

Procedure

 A list of Auto Sequences can be selected


from the Auto Sequence groups menu.

 Enters option for selecting a list.

Selected list of Auto Sequences is


marked with a blue dot.

Note:
Previously selected list of Auto
Sequences is closed automatically.

4.9.1.2 Deleting a list of Auto Sequences®

Procedure

 A list of Auto Sequences to be deleted


can be selected from the Auto Sequence
groups menu.

 Enters option for deleting a list.

Before deleting the selected list of Auto


Sequences the user is asked for
confirmation.

 A list of Auto Sequences is removed.

60
MI 3155 EurotestXD Memory Organizer

5 Memory Organizer
Memory Organizer is a tool for storing and working with test data.

5.1 Memory Organizer menu


The data is organized in a tree structure with Structure objects and Measurements. MI 3155 –
EurotestXD Instrument has a multi-level structure. The hierarchy of Structure objects in the tree
is shown on Figure 5.1. A list of available structure objects can be seen in Appendix D –
Structure objects.

Figure 5.1: Default tree structure and its hierarchy

Figure 5.2: Example of a tree menu

5.1.1 Measurement statuses


Each measurement has:
 a status (PASS or FAIL or no status),
 a name,
 results,
 limits and parameters.

A measurement can be a Single test or an Auto Sequence. For more information refer to
chapters 7 Tests and measurements and 8 Auto Sequences®.

61
MI 3155 EurotestXD Memory Organizer

Statuses of Single tests

passed finished single test with test results


failed finished single test with test results
finished single test with test results and no status
empty single test without test results

Overall statuses of Auto Sequence®

At least one single test in the Auto sequence passed and


no single test failed
At least one single test in the Auto Sequence failed.

At least one single test in the Auto Sequence was carried


out and there were no other passed or failed single tests.
Empty Auto Sequence with empty single tests.

5.1.2 Structure Objects


Each Structure object has:
 an icon,
 a name and
 parameters.

Optionally they can have:


 an indication of the status of the measurements under the Structure object and
 a comment or a file attached.

Figure 5.3: Structure object in tree menu

Structure objects supported by the instrument are described in Appendix D – Structure


objects.

5.1.2.1 Measurement status indication under the Structure object

Overall status of measurements under each structure element /sub-element can be seen
without spreading tree menu. This feature is useful for quick evaluation of test status and as
guidance for measurements.

62
MI 3155 EurotestXD Memory Organizer

Options

There are no measurement


results under selected structure
object. Measurements should
be made.

One or more measurement


result(s) under selected
structure object has failed. Not
all measurements under
selected structure object have
been made yet.

All measurements under


selected structure object are
completed but one or more
measurement result(s) has
failed.

Note:
 There is no status indication if all measurement results under each structure element /
sub-element have passed or if there is an empty structure element / sub-element
(without measurements).

63
MI 3155 EurotestXD Memory Organizer

5.1.3 Selecting an active Workspace in Memory Organizer


Memory Organizer and Workspace Manager are interconnected so an active Workspace can be
selected also in the Memory Organizer menu.

Procedure

Press the active Workspace in Memory


 Organizer Menu.

 Select List of Workspaces in Control panel.

Choose desired Workspace from a list of


 Workspaces.

 Use Select button to confirm selection.

New Workspace is selected and displayed on


 the screen.

64
MI 3155 EurotestXD Memory Organizer

5.1.4 Adding Nodes in Memory Organizer


Structural Elements (Nodes) are used to ease organization of data in the Memory Organizer.
One Node is a must; others are optional and can be created or deleted freely.

Procedure

Press the active Workspace in Memory


 Organizer Menu.

Select Add New Structure Element in Control


 panel.

 Press “Create” to confirm.

New Structure Element (Node) is added.

 Note:
To change the name of a Node, see chapter
5.1.5.15 Rename a Structure object

65
MI 3155 EurotestXD Memory Organizer

5.1.5 Operations in Tree menu


In the Memory organizer different actions can be taken with help of the control panel at the right
side of the display. Possible actions depend on the selected element in the organizer.

5.1.5.1 Operations on measurements (finished or empty measurements)

Figure 5.4: A measurement is selected in the Tree menu

Options

Views results of measurement.


The instrument goes to the measurement memory screen. Refer to chapter 6.1.9
Recall single test results screen and 8.2.4 Auto Sequence® memory screen for
more information.

Starts a new measurement.


The instrument goes to the measurement start screen. Refer to chapter 6.1.3 Single
test start screen and 8.2.1 Auto Sequence® view menu for more information.

Saves a measurement.
Saving of measurement on a position after the selected (empty or finished)
measurement.

Clones the measurement.


The selected measurement can be copied as an empty measurement under the
same Structure object. Refer to chapter 5.1.5.8 Clone a measurement for more
information.
Copies & Paste a measurement.
The selected measurement can be copied and pasted as an empty measurement to
any location in structure tree. Multiple ‘Paste’ is allowed. Refer to chapter 5.1.5.11
Copy & Paste a measurement for more information.
Adds a new measurement.
The instrument goes to the Menu for adding measurements. Refer to chapter 5.1.5.6
Add a new measurement for more information.
Views and edit comments.
The instrument displays comment attached to the selected measurement or opens
keypad for entering a new comment.

66
MI 3155 EurotestXD Memory Organizer

Deletes a measurement.
Selected Measurement can be deleted. User is asked for confirmation before the
deleting. Refer to chapter 5.1.5.14 Delete a measurement for more information.

5.1.5.2 Operations on Structure objects

The structure object must be selected first.

Figure 5.5: A structure object is selected in the Tree menu

Options

Starts a new measurement.


Type of measurement (Single test or Auto Sequence) should be selected first.
After proper type is selected, the instrument goes to Single Test or Auto Sequence
selection screen. Refer to chapters 6.1 Selection modes and 8.1 Selection of Auto
Sequences®.
Saves a measurement.
Saving of measurement under the selected Structure object.
View / edit parameters and attachments.
Parameters and attachments of the Structure object can be viewed or edited.
Refer to chapter 5.1.5.3 View / Edit parameters and attachments of a Structure
object for more information.
Adds a new measurement.
The instrument goes to the Menu for adding measurement into structure. Refer to
chapter 5.1.5.6 Add a new measurement for more information.
Adds a new Structure object.
A new Structure object can be added. Refer to chapter 5.1.5.5 Add a new Structure
Object for more information.
Attachments.
Name and link of attachment is displayed.
Clones a Structure object.
Selected Structure object can be copied to same level in structure tree (clone). Refer
to chapter 5.1.5.7 Clone a Structure object for more information.

67
MI 3155 EurotestXD Memory Organizer

Copies & Paste a Structure object.


Selected Structure object can be copied and pasted to any allowed location in
structure tree. Multiple “Paste” is allowed. Refer to chapter 5.1.5.9 Copy & Paste a
Structure object for more information.
Cut & Paste a Structure.
Selected Structure with child items (sub-structures and measurements) can be
moved to any allowed location in structure tree. Refer to chapter 5.1.5.12 Cut &
Paste a Structure object with sub-items for more information.
Views and edit comments.
The instrument displays comment attached to the selected Structure object or opens
keypad for entering a new comment.
Deletes a Structure object.
Selected Structure object and sub-elements can be deleted. User is asked for
confirmation before the deleting. Refer to chapter 5.1.5.13 Delete a Structure
object for more information.
Renames a Structure object.
Selected Structure object can be renamed via keypad. Refer to chapter 5.1.5.15
Rename a Structure object for more information.

68
MI 3155 EurotestXD Memory Organizer

5.1.5.3 View / Edit parameters and attachments of a Structure object

The parameters and their content are displayed in this menu. To edit the selected parameter,

tap on it or press the key to enter menu for editing parameters.

Procedure

 Select structure object to be edited.

 Select Parameters in Control panel.

 Example of Parameters menu.

 In menu for editing parameters the


parameter’s value can be selected from a
dropdown list or entered via keypad.
Refer to chapter 4 Instrument operation
for more information about keypad
operation.

Note:
Some structure parameters include
custom lists. See chapter 5.1.5.4 Custom
lists of Structure parameter values for
details.

a Select Attachments in Control panel.

69
MI 3155 EurotestXD Memory Organizer

Attachments
a
The name of attachment can be seen.
Operation with attachments is not
supported in the instrument.

b Select Comments in Control panel.

b View or edit comments


Complete comment (if exists) attached
to the structure object can be seen on
this screen.

Press key or tap on screen to


open keypad for entering a new
comment.

5.1.5.4 Custom lists of Structure parameter values

Some structure parameters include option to create custom lists of values for particular
structure parameter. These custom values can be re-used easily, by selecting it from the
custom lists, and re-typing is therefore not required.

Figure 5.6: Example of Virtual keyboard with Custom list option

Procedure

70
MI 3155 EurotestXD Memory Organizer

 Select Custom list option.

 Custom list view.

 Select focused value from Custom list.

a Edit Custom list.

b Custom list Edit options.

a Add new value to the Custom list.

b Edit selected Custom list value.

c Delete selected Custom list value.

d Delete Custom list (all values).

71
MI 3155 EurotestXD Memory Organizer

5.1.5.5 Add a new Structure Object

This menu is intended to add new structure objects in the tree menu. A new structure object can
be selected and then added in the tree menu.

Procedure

 Default initial structure.

 Select Add Structure in Control panel.

 Add a new structure object menu.

a Tap on a structure type selection window.

A list of available structure items is


displayed. Select one from a list. Arrow
indicates the position where structure item
will be inserted.

Child item to the currently selected


structure item.

Structure item located in the same level.

b In menu for editing name and parameters


the parameter’s value can be selected
from a dropdown list or entered via
keypad. Refer to chapter 4 Instrument
operation for more information about
keypad operation.

 Create new structure item.

72
MI 3155 EurotestXD Memory Organizer

 New object added.

73
MI 3155 EurotestXD Memory Organizer

5.1.5.6 Add a new measurement

In this menu new empty measurements can be set and then added in the structure tree. The
type of measurement, measurement function and its parameters are first selected and then
added under the selected Structure object.

Procedure

 Select level in structure where


measurement will be added.

 Select Add measurement in Control


panel.

 Add new measurement menu.

a Type of test can be selected from this


field.
Options: (Single Tests, Auto
Sequences)

Tap on field or press the key to


modify.

b Last added measurement is offered by


default.
To select another measurement tap on

filed press the to open menu for


selecting measurements.

c

74
MI 3155 EurotestXD Memory Organizer

Select parameter and modify it as


described earlier.
Refer to chapter 6.1.2 Setting
parameters, limits and comments of
single tests for more information.

 Adds the measurement under the


selected Structure object in the tree
menu.
Returns to the structure tree menu
without changes.

 New empty measurement is added


under the selected Structure object.

75
MI 3155 EurotestXD Memory Organizer

5.1.5.7 Clone a Structure object

In this menu selected structure object can be copied (cloned) to same level in the structure tree.
Cloned structure object has the same name as the original.

Procedure

 Select the structure object to be cloned.

 Select Clone in Control panel.

 The Clone Structure object menu is


displayed. Sub-elements of the selected
structure object can be marked or un-
marked for cloning.
Refer to chapter 5.1.5.10 Cloning and
Pasting sub-elements of selected
structure object for more information.

 Selected structure object is copied (cloned)


to same level in the structure tree.
Cloning is cancelled. No changes in the
Structure tree.

 The new structure object is displayed.

76
MI 3155 EurotestXD Memory Organizer

5.1.5.8 Clone a measurement

By using this function, a selected empty or finished measurement can be copied (cloned) as an
empty measurement to the same level in the structure tree. Parameters and limits of new
measurement are the same as they are set in original measurement. Its parameters/limits can
be changed when measurement is started.

Procedure

 Select the measurement to be cloned.

 Select Clone in Control panel.

 A new empty measurement is displayed.

77
MI 3155 EurotestXD Memory Organizer

5.1.5.9 Copy & Paste a Structure object

In this menu selected Structure object can be copied and pasted to any allowed location in the
structure tree.

Procedure

 Select the structure object to be copied.

 Select Copy in control panel.

 Select location where structure element


should be copied.

 Select Paste in Control panel.

 The Paste structure object menu is


displayed.
Before copying it can be set which sub-
elements of the selected structure object
will be copied too. Refer to chapter
5.1.5.10 Cloning and Pasting sub-
elements of selected structure object for
more information.

 The selected structure object and elements


are copied (pasted) to selected position in
the tree structure.
Returns to the tree menu without changes.

78
MI 3155 EurotestXD Memory Organizer

 The new structure object is displayed.

Note
The Paste command can be executed one
or more times.

5.1.5.10 Cloning and Pasting sub-elements of selected structure object

When structure object is selected to be cloned, or copied & pasted, additional selection of its
sub-elements is needed. The following options are available:

Options
Parameters of selected structure object will be cloned /
pasted too.
Attachments of selected structure object will be cloned
/ pasted too.
Structure objects in sub-levels of selected structure
object will be cloned / pasted too.
Measurements in selected structure object and sub-
levels will be cloned / pasted too.

79
MI 3155 EurotestXD Memory Organizer

5.1.5.11 Copy & Paste a measurement

In this menu selected measurement can be copied as an empty measurement to any allowed
location in the structure tree. Selected measurement can be copied multiple times to different
locations in the structure tree. Parameters and limits of new measurement are the same as they
are set in original measurement. Its parameters/limits can be changed when measurement is
started.

Procedure

 Select the measurement to be copied.

 Select Copy in Control panel.

 Select the location where measurement


should be pasted.

 Select Paste in Control panel.

 A new (empty) measurement is displayed


in selected Structure object.

Note
The Paste command can be executed
one or more times.

80
MI 3155 EurotestXD Memory Organizer

5.1.5.12 Cut & Paste a Structure object with sub-items

In this menu selected Structure object with sub-items (sub-structures and measurements) can
be cut and pasted (moved) to any allowed location in the structure tree.

Procedure

 Select the structure item to be moved.

 Select Cut option from Control panel.

 Select new location where structure object


(with sub-structures and measurements)
should be moved.

 Select Paste option from Control panel.

 The structure object (with sub-structures


and measurements) is moved to selected
new location and deleted from previous
location in the tree structure.

81
MI 3155 EurotestXD Memory Organizer

5.1.5.13 Delete a Structure object

In this menu selected Structure object can be deleted.

Procedure

 Select the structure object to be deleted.

 Select Delete in Control panel.

 A confirmation window will appear.

Selected structure object and its sub-


elements are removed.
Returns to the tree menu without
changes.

 Structure without deleted object.

82
MI 3155 EurotestXD Memory Organizer

5.1.5.14 Delete a measurement

In this menu selected measurement can be deleted from selected location in the tree structure.

Procedure

 Select a measurement to be deleted.

 Select Delete in Control panel.

 A confirmation window will appear.

Selected measurement is deleted.

Returns to the tree menu without changes.

 Structure without deleted measurement.

83
MI 3155 EurotestXD Memory Organizer

5.1.5.15 Rename a Structure object

In this menu selected Structure object can be renamed.

Procedure

 Select the structure object to be


renamed.

 Select Rename in Control panel.

 Virtual keypad will appear on screen.


Enter new text and confirm.
Refer to chapter 4.3 Virtual keyboard for
keypad operation.

 Structure object with the modified name.

84
MI 3155 EurotestXD Memory Organizer

5.1.5.16 Recall and Retest selected measurement

Procedure

 Select the measurement to be recalled.

 Select Recall results in Control panel.

 Measurement is recalled.

a Parameters and limits can be viewed but


cannot be edited.

 Select Retest in Control panel.

 Measurement retest starting screen is


displayed.

85
MI 3155 EurotestXD Memory Organizer

a Parameters and limits can be viewed


and edited.

 Select Run in Control panel to retest the


measurement.

 Results / sub-results after re-run of


recalled measurement.

 Select Save results in Control panel.

Retested measurement is saved under


same structure object as original one.
Refreshed memory structure with the
new performed measurement.

5.1.6 Searching in Memory Organizer


In Memory organizer it is possible to search for different structure objects and parameters.
Search function is available from the active workspace directory line as presented on Figure
5.7.

Figure 5.7: Active workspace directory

86
MI 3155 EurotestXD Memory Organizer

Procedure

 Search function is available from the


active workspace directory line.

Use external device for data entry or


follow instructions below for
instrument search function.

 Select Search in control panel to open


Search setup menu.

 The parameter that can be searched


for is displayed in the search setup
menu.
Note:
 Equipment ID, Test date and
Retest date (if applicable) refer
only to the following structure
objects: Machine, EVSE and
Appliance.

a The search can be narrowed by


entering a text in the Name / Equip. ID
field.
Strings can be entered using the on-
screen keyboard.

b The search can be narrowed on base


of statuses.
If searching by status, instrument will
display all structure objects that
include one or more measurements
with searched status.

87
MI 3155 EurotestXD Memory Organizer

c The search can be narrowed on base


of test dates / retest dates (from / to).

Clears all filters.


d
Searches through the Memory
 Organizer for objects according to the
set filter.
The results are shown in the Search
results screen presented on Figure
5.8.

Figure 5.8: Search results screen (left), structure object selected (right)

Options
Next page (if available).

Previous page (if available).

Goes to location in Memory Organizer.

View / edit parameters and attachments.


Parameters and attachments of the Structure object can be viewed or edited. Refer
to chapter 5.1.5.3 View / Edit parameters and attachments of a Structure object
for more information.

Attachments.
Name and link of attachment is displayed.

88
MI 3155 EurotestXD Memory Organizer

Views comment.
The instrument displays comment attached to the selected Structure object.

Renames the selected Structure object.


Refer to chapter 5.1.5.15 Rename a Structure object for more information

Note:
 Search result page consist of up to 50 results.

89
MI 3155 EurotestXD Single tests

6 Single tests
Single tests can be selected in the main Single tests menu or in Memory organizer main
menu and sub-menus.

6.1 Selection modes


In Single test main menu four modes for selecting single tests are available.

Options

Area Group

With help of area groups it is possible to limit


the offered single tests. The instrument has
several area groups:
 the EIS group,
 the Industrial group,
 the Machine group,
 the IT Medical group,
 the IT Vehicles group,
 the EVSE group,
 the Lightning group.
In the All group all measurements are offered.

Groups

The single tests are divided into groups of


similar tests.

For the selected group a submenu with all


single tests that belongs to the selected group is
displayed.

90
MI 3155 EurotestXD Single tests

Cross selector

This selection mode is the fastest for working


with the keypad.
Groups of single tests are organized in a row.
For the selected group all single tests are
displayed and easy accessible with up /down
keys.

Last used

Last 9 made different single tests are displayed.

Expands control panel / open more options.

6.1.1 Single test (measurement) screens


In the Single test (measurement) screens measuring results, sub-results, limits and parameters
of the measurement are displayed. In addition, on-line statuses, warnings and other info are
displayed.

Figure 6.1: Single test screen organization, example of insulation resistance


measurement

91
MI 3155 EurotestXD Single tests

Single test screen organization

Header line:
 ESC touch key
 function name
 battery status
 real time clock
Control panel (available options)

Parameters (white) and limits (red)

Result field:
 main result(s)
 sub-result(s)
 PASS / FAIL indication
Voltage monitor with info and warning symbols

92
MI 3155 EurotestXD Single tests

6.1.2 Setting parameters, limits and comments of single tests


Procedure

 Select the test or measurement.


The test can be entered from:
 Single tests menu or
 Memory organizer menu once
the empty measurement was
created in selected object
structure.

 Select Parameters in Control panel.

Opens parameters and limits setting


menu.
on

 Parameters and Limits menu.


Some single tests support user
comment entry.

a Modify parameter or limit value with


touchscreen or keyboard buttons.
on or

b Select parameter to be edited or limit


/ comment to be set.
and

c Opens parameter or limit selection list


or on-screen keyboard for entering
on comment.

on

93
MI 3155 EurotestXD Single tests

a Select parameter or limit value from


the list.
Note:
Touchscreen or keyboard selection
methods can be used
interchangeably; confirm keyboard
on
selection with .

b Enter comment and confirm with


.

on

 Accepts and set selected parameters,


selected limit values and user
comments and exits Single Test
setting.

Note:
 Set parameters, set limits and entered user comments are saved to the memory. When
same Single test is used next time, settings and comments will remain the same.

6.1.3 Single test start screen

Figure 6.2: Single test start screen, example of insulation resistance measurement

Options (before test, screen was opened in Memory organizer or Single test main menu):
Starts the measurement.

Starts the continuous measurement (if applicable on


long selected single test).

long
Opens help screens.

Opens menu for changing parameters and limits.

94
MI 3155 EurotestXD Single tests

Refer to chapter 6.1.2 Setting parameters, limits


and comments of single tests for more
information.
on
Enters cross selector to select test or measurement.

long on
Expands column in control panel.

6.1.4 Single test screen during test

Figure 6.3: Single test is running, example of insulation resistance continuous


measurement

Operations when test is running:

Stops the single test measurement.

Proceeds to next step of the measurement (if measurement consists


of more steps).

Previous value.

Next value.

Stops or aborts the measurement and returns one menu back.

95
MI 3155 EurotestXD Single tests

6.1.5 Single test result screen

Figure 6.4: Single test results screen, example of insulation resistance measurement
results

Options (after measurement is finished)


Starts a new measurement.

Starts a new continuous measurement (if applicable


long on selected single test).

long
Saves the result.

A new measurement was selected and started from


a Structure object in the structure tree:
 the measurement will be saved under the
selected Structure object.
A new measurement was started from the Single
test main menu:
 saving under the last selected Structure
object will be offered by default. The user
can select another Structure object or create
a new Structure object.

 By pressing the key in Memory


organizer menu the measurement is saved
under selected location.
An empty measurement was selected in structure
tree and started:
 the result(s) will be added to the
measurement. The measurement will
change its status from ‘empty’ to ‘finished’.

An already carried out measurement was selected


in structure tree, viewed and then restarted:

96
MI 3155 EurotestXD Single tests

 a new measurement will be saved under the


selected Structure object.
Opens screen for changing parameters and limits.
Refer to chapter 6.1.2 Setting parameters, limits
and comments of single tests for more
information.

on
Adds comment to the measurement. The
instrument opens keypad for entering a comment.
Opens help screens.

Enters cross selector to select test or


measurement.
long on
Expands column in control panel.

97
MI 3155 EurotestXD Single tests

6.1.6 Editing graphs (Harmonics)

Figure 6.5: Example of Harmonics measurement results

Options for editing graphs (start screen or after measurement is finished)

Plot edit
Opens control panel for editing graphs.

Increase scale factor for y-axis.

Decrease scale factor for y-axis.

Toggle between U and I graph to set scale factor

Exits from editing graphs.

98
MI 3155 EurotestXD Single tests

6.1.7 Single test (inspection) screens


Visual and Functional inspections can be treated as a special class of tests. Items to be visually
or functionally checked are displayed. In addition on-line statuses and other information are
displayed. Type of inspection depends on type and profile of the instruments.

Figure 6.6: Inspection screen organisation

Legend
1 Overall status of the inspection
2 Selected inspection
3 Item
4 Child items
5 Status fields (for items and child items)
6 Control panel (available options)

6.1.7.1 Single test (inspection) start screen

Figure 6.7: Inspection start screen

Options (inspection screen was opened in Memory organizer or from Single test main
menu)

99
MI 3155 EurotestXD Single tests

Starts the inspection.

Opens help screens. Refer to chapter 6.1.8 Help screens for more
information.

6.1.7.2 Single test (Inspection) screen during test

Figure 6.8: Inspection screen (during inspection)

Options (during test)


Selects item.

Stops the inspection.

Applies a pass to the selected item or group of items.

Applies a fail to the selected item or group of items.

Clears status in selected item or group of items

Applies checked status to selected item or group of


items.

A status can be applied

on Multiple taps toggles between statuses.

Toggle between statuses.

Goes to the result screen.

100
MI 3155 EurotestXD Single tests

Rules for automatic applying of statuses:


 The parent item(s) can automatically get a status on base of statuses in child items.
 the fail status has highest priority. A fail status for any item will result in a fail status in all
parent items and an overall fail result.
 if there is no fail status in child items the parent item will get a status only if all child items
have a status.
 Pass status has priority over checked status.

 The child item(s) will automatically get a status on base of status in the parent item.
 All child items will get the same status as applied to the parent item.

Notes:
 Inspections and even inspection items inside one inspection can have can have different
status types. For example, some basic inspections don’t have the ‘checked’ status.
 Only inspections with overall statuses can be saved.

6.1.7.3 Single test (Inspection) result screen

Figure 6.9: Inspection result screen

Options (after inspection is finished)


Starts a new inspection.

Saves the result.


A new inspection was selected and started from a Structure object in the structure
tree:
 The inspection will be saved under the selected Structure object.
A new inspection was started from the Single test main menu:
 Saving under the last selected Structure object will be offered by default. The
user can select another Structure object or create a new Structure object. By

pressing the key in Memory organizer menu the inspection is saved


under selected location.
An empty inspection was selected in structure tree and started:
 The result(s) will be added to the inspection. The inspection will change its
status from ‘empty’ to ‘finished’.
An already carried out inspection was selected in structure tree, viewed and then
restarted:

101
MI 3155 EurotestXD Single tests

 A new measurement will be saved under the selected Structure object.

Adds comment to the measurement. The instrument opens keypad for entering a
comment.

Opens help screens. Refer to chapter 6.1.8 Help screens for more information.

6.1.7.4 Single test (inspection) memory screen

Figure 6.10: Inspection memory screen

Options
Retest
Enters screen with ‘empty’ measurement.

Enters view mode.

102
MI 3155 EurotestXD Single tests

6.1.8 Help screens


Help screens contain diagrams for proper connection of the instrument.

Figure 6.11: Examples of help screens

Options
Opens help screen.

Goes to previous / next help screen.

on

Back to test / measurement menu.

103
MI 3155 EurotestXD Single tests

6.1.9 Recall single test results screen

Figure 6.12: Recalled results of selected measurement, example of insulation resistance


recalled results

Options
Retest
Enters starting screen for a new measurement.
Refer to chapter 6.1.3 Single test start screen for
more information.
Opens menu for viewing parameters and limits.
Refer to chapter 6.1.2 Setting parameters, limits
and comments of single tests for more information.

on
Expands column in control panel.

104
MI 3155 EurotestXD Tests and measurements

7 Tests and measurements


See chapter 6.1 Selection modes for instructions on keys and touch screen functionality.

7.1 Voltage, frequency and phase sequence

Figure 7.1: Voltage measurement menu

Measurement parameters

System1) Voltage system [-, 1-phase,3-phase]


Test3) Phase to be tested [-, L1, L2, L3]
Limit type Type of limit [Voltage, %]
Earthing system Earthing system [TN/TT, IT]
Nominal voltage [Custom, 110 V, 115 V, 190 V, 200 V, 220 V, 230 V,
Nominal voltage2)
240 V, 380 V, 400 V, 415 V]
4)
Reference field Correct phase rotation [-, 1.2.3, 3.2.1]
Duration Test duration [Off, Custom, 1 s, 3 s, 5 s]
1)
There are no limits to set if System parameter is set to ‘–‘.
2)
Active only if limit type parameter is set to %.
3)
Active only when System is set to 1-phase.
4)
Active only when System is set to 3-phase; set parameter (1.2.3 or 3.2.1) to verify
correct phase sequence during Voltage test.

Measurement limits for TN/TT earthing system:

Low limit Uln5) Min. voltage [Off, Custom, 0 V … 499 V]


High limit Uln5) Max. voltage [Off, Custom, 0 V … 499 V]
Low limit Uln 6)
Min. voltage [Off, Custom, -20% … 20%]
High limit Uln6) Max. voltage [Off, Custom, -20% … 20%]
Low limit Ulpe5,6) Min. voltage [Off, Custom, 0 V … 499 V]
High limit Ulpe5,6) Max. voltage [Off, Custom, 0 V … 499 V]
Low limit Unpe 5,6)
Min. voltage [Off, Custom, 0 V … 499 V]
High limit Unpe5,6) Max. voltage [Off, Custom, 0 V … 499 V]
Low limit U127) Min. voltage [Off, Custom, 0 V … 499 V]
High limit U12 7)
Max. voltage [Off, Custom, 0 V … 499 V]
Low limit U137) Min. voltage [Off, Custom, 0 V … 499 V]
High limit U137) Max. voltage [Off, Custom, 0 V … 499 V]
Low limit U237) Min. voltage [Off, Custom, 0 V … 499 V]
High limit U23 7)
Max. voltage [Off, Custom, 0 V … 499 V]
Low limit Ull8) Min. voltage [Off, Custom, -20% … 20%]
High limit Ull8) Max. voltage [Off, Custom, -20% … 20%]
5)
In case of 1-phase voltage system and limit type set to voltage.

105
MI 3155 EurotestXD Test and measurements

6)
In case of 1-phase voltage system and limit type se to %.
7)
In case of 3-phase voltage system and limit type set to voltage.
8)
In case of 3-phase voltage system and limit type set to %.

Measurement limits for IT earthing system:

Low limit U129,11) Min. voltage [Off, Custom, 0 V … 499 V]


High limit U129,11) Max. voltage [Off, Custom, 0 V … 499 V]
Low limit U12 10)
Min. voltage [Off, Custom, -20% … 20%]
High limit U1210) Max. voltage [Off, Custom, -20% … 20%]
Low limit U1pe9,10) Min. voltage [Off, Custom, 0 V … 499 V]
High limit U1pe9,10) Max. voltage [Off, Custom, 0 V … 499 V]
Low limit U2pe9,10) Min. voltage [Off, Custom, 0 V … 499 V]
High limit U2pe9,10) Max. voltage [Off, Custom, 0 V … 499 V]
Low limit U1311) Min. voltage [Off, Custom, 0 V … 499 V]
High limit U13 11)
Max. voltage [Off, Custom, 0 V … 499 V]
Low limit U2311) Min. voltage [Off, Custom, 0 V … 499 V]
High limit U2311) Max. voltage [Off, Custom, 0 V … 499 V]
Low limit Ull 12)
Min. voltage [Off, Custom, -20% … 20%]
High limit Ull12) Max. voltage [Off, Custom, -20% … 20%]
9)
In case of 1-phase voltage system and limit type set to voltage.
10)
In case of 1-phase voltage system and limit type set to %.
11)
In case of 3-phase voltage system and limit type set to voltage.
12)
In case of 3-phase voltage system and limit type set to %.

Connection diagrams

Figure 7.2: Connection of 3-wire test lead and optional adapter in three-phase system

Figure 7.3: Connection of Plug commander and 3-wire test lead in single-phase system

106
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the Voltage function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect test leads to object under test (see Figure 7.2 and Figure 7.3).
 Start the measurement.
 Stop the measurement, if Duration is set to Off.
 Save results (optional).

Figure 7.4: Example of Voltage measurement results in single-phase system

Figure 7.5: Example of Voltage measurement results in three-phase system

Measurement results / sub-results

Single-phase TN/TT system:

Uln Voltage between phase and neutral conductors


Ulpe voltage between phase and protective conductors
Unpe voltage between neutral and protective conductors
Freq frequency

Single phase IT system:

U12 voltage between phases L1 and L2


U1pe voltage between phase L1 and PE
U2pe voltage between phase L2 and PE
Freq frequency

107
MI 3155 EurotestXD Test and measurements

Three-phase TN/TT and IT system:

U12 voltage between phases L1 and L2


U13 voltage between phases L1 and L3
U23 voltage between phases L2 and L3
Freq frequency
Field1) 3-phase rotation sequence
1)
For Pass test result, Field result must be equal to setting of Reference field parameter
(1.2.3 or 3.2.1).

7.2 R iso – Insulation resistance

Figure 7.6: Insulation resistance measurement menu

Measurement parameters / limits

Uiso Nominal test voltage [50 V, 100 V, 250 V, 500 V, 1000 V, 2500 V]
Type of test [-, L/PE, L/N, N/PE, L/L, L1/L2, L1/L3, L2/L3, L1/N, L2/N, L3/N,
Type Riso1)
L1/PE, L2/PE, L3/PE]
Limit(Riso) Min. insulation resistance [Off, Custom, 0.01 M ... 100 M]
1)
Insulation measurement depends on Type Riso parameter setting, see table below.

Type Riso 3-wire test lead and Tip commander 2.5 kV test lead
parameter measuring terminals measuring terminals
(UN ≤ 1 kV) (UN =2.5 kV)
-
L-N
Lx-N L and N
L/L
HV+ and HV-
Lx-Ly
L-PE
L and PE
Lx-PE
N-PE N and PE
Table 7.1: Insulation resistance measuring terminals and Type Riso parameter
dependency

108
MI 3155 EurotestXD Test and measurements

Connection diagrams

Figure 7.7: Connections of 3-wire test lead and Tip commander (UN ≤ 1 kV)

Figure 7.8: Connection of 2.5 kV test lead (UN =2.5 kV)

109
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the R iso function.


 Set test parameters / limits.
 Disconnect tested installation from mains supply and discharge installation as required.
 Connect test cable to the instrument.
 Connect test leads to object under test (see Figure 7.7 and Figure 7.8).
Different test cable must be used for testing with nominal test voltage UN ≤ 1000 V and
UN= 2500 V. Also, different test terminals are used.
The standard 3-wire test lead, Schuko test cable or Plug / Tip commanders can be used
for the insulation test with nominal test voltages ≤ 1000 V.
For the 2500 V insulation test the two-wire 2.5 kV test lead should be used.

 Start the measurement. A longer press on key or a longer press on ‘Start test’
option on touch screen starts a continuous measurement.
 Stop the measurement. Wait until object under test is fully discharged.
 Save results (optional).

Figure 7.9: Examples of Insulation resistance measurement result

Measurement results / sub-results

Riso Insulation resistance


Um Actual test voltage

7.2.1 Load pretest


High Insulation voltage can potentially damage the connected appliances during the Insulation
measurement. This misuse can be prevented by enabling Load pretest functionality in Settings
menu. Load pretest measures the impedance on test terminals with low and safe a.c. voltage. If
impedance lower than 50 kΩ is detected, warning message is displayed, allowing to disconnect
the appliances before test voltage is applied (see Figure 7.10). Insulation measuring voltage is
applied to the test terminals only after YES is selected. NO will abort the measurement.
If impedance higher than 50 kΩ is measured during the Load pretest, Insulation test will follow
automatically.

110
MI 3155 EurotestXD Test and measurements

Load pretest terminals


Test Type Riso 3-wire test lead and Tip 2.5 kV test lead
function parameter commander measuring terminals measuring terminals
(UN ≤ 1 kV) (UN =2.5 kV)
Riso -
L/N
Lx/N L-N ×
L/L
Lx/Ly
L/PE
L-PE ×
Lx/PE
N/PE N-PE ×
Riso - all L-N, L-PE, N-PE ×
×. ......................................................not applicable
Table 7.2: Insulation resistance measuring terminals and Load pretest dependency

Figure 7.10: Load pretest warning message

7.3 R iso all – Insulation resistance

Figure 7.11: R iso - all measurement menu

Measurement parameters / limits

Uiso Nominal test voltage [50 V, 100 V, 250 V, 500 V, 1000 V]


Limit Min. insulation resistance [Off, Custom, 0.01 M ... 100 M]
Insulation is always measured between all three test leads.

111
MI 3155 EurotestXD Test and measurements

Connection diagrams

Figure 7.12: Connection of 3-wire test lead and Tip commander

Measurement procedure

 Enter the R iso - all function.


 Set test parameters / limits.
 Disconnect tested installation from mains supply and discharge installation as required.
 Connect test cable to the instrument.
 Connect test leads to object under test (see Figure 7.12).
The standard 3-wire test lead, Schuko test cable or Plug / Tip commanders can be used.
 Start the measurement.
 Wait until object under test is fully discharged.
 Save results (optional).

Figure 7.13: Examples of R iso - all measurement result

Measurement results / sub-results

L-N Insulation resistance between L and N terminals


Riso L-PE Insulation resistance between L and PE terminals
N-PE Insulation resistance between N and PE terminals
L-N Actual test voltage between L and N terminals
Um L-PE Actual test voltage between L and PE terminals
N-PE Actual test voltage between N and PE terminals

112
MI 3155 EurotestXD Test and measurements

7.4 The DAR and PI diagnostic


DAR (Dielectric Absorption Ratio) is ratio of insulation resistance values measured after 15
seconds and after 1 minute. The DC test voltage is present during the whole period of the
measurement.

𝑅𝐼𝑆𝑂 (1 min)
𝐷𝐴𝑅 =
𝑅𝐼𝑆𝑂 (15 s)

PI (Polarization Index) is the ratio of insulation resistance values measured after 1 minute and
after 10 minutes. The DC test voltage is present during the whole period of the measurement

𝑅𝐼𝑆𝑂 (10 min)


𝑃𝐼 =
𝑅𝐼𝑆𝑂 (1 min)

For additional information regarding PI and DAR diagnostic, please refer to Metrel’s handbook
Modern insulation testing.

Figure 7.14: Diagnostic test menu

Measurement parameters / limits

Uiso Nominal test voltage [500 V, 1000 V, 2500 V]

Connection diagrams

Figure 7.15: Connection of 3-wire test lead and Tip commander (UN ≤ 1 kV)

113
MI 3155 EurotestXD Test and measurements

Figure 7.16: Connection of 2.5 kV test lead (UN = 2.5 kV)

Measurement procedure

 Enter the Diagnostic test function.


 Set test parameters / limits.
 Disconnect tested installation from mains supply and discharge installation as required.
 Connect test cable to the instrument.
 Connect test leads to object under test (see Figure 7.15 and Figure 7.16).
Different test cable must be used for testing with nominal test voltage UN ≤ 1000 V and
UN= 2500 V. Also, different test terminals are used.
The standard 3-wire test lead, Schuko test cable or Plug / Tip commanders can be used
for the diagnostic test with nominal test voltages ≤ 1000 V. For the 2500 V diagnostic
test the two-wire 2.5 kV test lead should be used.
 Start the measurement. Internal timer begins to increment. When internal timer reaches
1 min R60 and DAR factor are displayed and short beep is generated. Measurement
can be interrupted at any time.
 When internal timer reaches 10 min also PI factor is displayed and measurement is
completed. Wait until object under test is fully discharged.
 After the measurement is finished wait until tested item is fully discharged.
 Save results (optional).

Figure 7.17: Examples of Diagnostic test result

Measurement results / sub-results


Riso Insulation resistance
Um Actual test voltage
R60 Resistance after 60 seconds
DAR Dielectric absorption ratio
PI Polarization index

114
MI 3155 EurotestXD Test and measurements

7.5 Varistor test


Measuring principle

A voltage ramp starts from 50 V and rises with a slope of 100 V/s (Range parameter set to 1000
V) or 350 V/s (Range parameter set to 2500 V). The measurement ends when the defined end
voltage is reached or if the test current exceeds the value of 1 mA.

Figure 7.18: Varistor test main menu

Measurement parameters / limits

I lim Current limit [1.0 mA]


System System [-, TT, TN, TN-C, TN-S]
Range Test voltage range [1000 V, 2500 V]
Low limit (Uac) Low breakdown limit value
1000 V range [Off, 50 V … 620 V]
2500 V range [Off, 50 V … 1550 V]
High limit (Uac) High breakdown limit value
1000 V range [Off, 50 V … 620 V]
2500 V range [Off, 50 V … 1550 V]

Test circuit for Varistor test

Figure 7.19: Connection of 3-wire test lead and Tip commander (Range: 1000 V)

115
MI 3155 EurotestXD Test and measurements

Figure 7.20: Connection of 2.5 kV test lead (Range: 2500 V)

Measurement procedure

 Enter the Varistor test function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect test leads to object under test (see Figure 7.19 and Figure 7.20).
Different test cable must be used if testing at Range: 1000 V or 2500 V. Also, different
test terminals are used.
The standard 3-wire test lead, or Tip commander can be used for the Varistor test when
testing at Range: 1000 V. If Range: 2500 V is selected, the two-wire 2.5 kV test lead
should be used for the Varistor test.
 Start the measurement.
The measurement ends when the defined end voltage is reached or if the test current
exceeds the value of 1 mA.
 After the measurement is finished wait until tested item is fully discharged.
 Save results (optional).

Figure 7.21: Examples of Varistor test result

Measurement results / sub-results

Uac Calculated a.c. breakdown voltage


Udc Breakdown voltage

Meaning of the Uac voltage


Protection devices intended for a.c. network are usually dimensioned approx. 15 % above peak
value of the nominal mains voltage. The relation between Udc and Uac is following:

116
MI 3155 EurotestXD Test and measurements

𝑈𝑑𝑐
𝑈𝑎𝑐 ≈
1.15 × √2
Uac voltage may be directly compared with the voltage declared on tested protection
device.

7.6 R low – Resistance of earth connection and


equipotential bonding

Figure 7.22: R low measurement menu

Measurement parameters / limits

Output1) [LPE, LN]


Bonding [Rpe, Local]
Current [standard, ramp]
Limit(R) Max. resistance [Off, Custom, 0.1 Ω ... 20.0 Ω]
1)
R low measurement depends on Output parameter setting, see table below.

Output Test terminals


LN L and N
LPE L and PE

Connection diagram

Figure 7.23: Connection of 3-wire test lead plus optional Extension lead

117
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the R low function.


 Set test parameters / limits.
 Connect 3-wire test lead to the instrument.
 Compensate the test leads resistance, if necessary, see section 7.8.1 Compensation
of test leads resistance.
 Disconnect tested installation from mains supply and discharge insulation as required.
 Connect test leads, see Figure 7.23.
 Start the measurement.
 Save results (optional).

Figure 7.24: Examples of R low measurement result

Measurement results / sub-results

R Resistance
R+ Result at positive test polarity
R- Result at negative test polarity

7.7 R low 4W

Figure 7.25: R low 4W measurement menu

Measurement parameters / limits

Bonding [Rpe, Local]


Limit(R) Max. resistance [Off, Custom, 0.05 Ω … 20.0 Ω]

118
MI 3155 EurotestXD Test and measurements

Connection diagram

Figure 7.26: Connection of 4-wire test lead plus optional extension leads

Measurement procedure

 Enter the R low 4W function.


 Set test parameters / limits.
 Connect 4-wire test lead to the instrument.
 Disconnect tested installation from mains supply and discharge insulation as required.
 Connect test leads to device under test, see Figure 7.26. Use extension leads if
necessary.
 Start the measurement.
 Save results (optional).

Figure 7.27: Examples of R low 4W result

Measurement results / sub-results

R Resistance
R+ Result at positive test polarity
R- Result at negative test polarity

119
MI 3155 EurotestXD Test and measurements

7.8 Continuity – Continuous resistance measurement


with low current

Figure 7.28: Continuity resistance measurement menu

Measurement parameters / limits

Sound [On*, Off]


Limit(R) Max. resistance [Off, Custom, 0.1 Ω ... 20.0 Ω]
*Instrument sounds if resistance is lower than the set limit value.

Connection diagrams

Figure 7.29: Tip commander and 3-wire test lead applications

120
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the Continuity function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Compensate the test leads resistance, if necessary, see section 7.8.1 Compensation
of test leads resistance.
 Disconnect device under test from mains supply and discharge it as required.
 Connect test leads to device under test, see Figure 7.29.
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

Figure 7.30: Examples of Continuity resistance measurement result

Measurement results / sub-results

R Resistance

7.8.1 Compensation of test leads resistance


This chapter describes how to compensate the test leads resistance in R low and Continuity
functions. Compensation is required to eliminate the influence of test leads resistance and the
internal resistances of the instrument on the measured resistance. The lead compensation is
therefore a very important feature to obtain correct result.
symbol is displayed if the compensation was carried out successfully.

Connections for compensating the resistance of test leads

Figure 7.31: Shorted test leads

121
MI 3155 EurotestXD Test and measurements

Compensation of test leads resistance procedure

 Enter R low or Continuity function.


 Connect test cable to the instrument and short all test leads together, see Figure 7.31.
 Touch the key to compensate leads resistance.

Figure 7.32: Result with old and new calibration values

122
MI 3155 EurotestXD Test and measurements

7.9 Testing RCDs


Various test and measurements are required for verification of RCD(s) in RCD protected
installations. Measurements are based on the EN 61557-6 standard.
The following measurements and tests (sub-functions) can be performed:

 Contact voltage,
 Trip-out time,
 Trip-out current and
 RCD Auto test.

Figure 7.33: RCD menus

Test parameters / limits

I N Rated RCD residual current sensitivity [10 mA, 15 mA, 30 mA,


100 mA, 300 mA, 500 mA, 1000 mA]
I N/ I Ndc Rated RCD residual current sensitivity for special RCDs types
[30 mA / 6 mA d.c., - / 6 mA d.c.] 1)
RCD type RCD type [AC, A, F, B, B+, EV RCD1), MI RCD1), EV RCM1)]
Use RCD / PRCD selection [fixed, PRCD, PRCD-2p, PRCD-3p, PRCD-S,
PRCD-S+, PRCD-K, other]
Selectivity Characteristic [G, S]
x IN Multiplication factor for test current [0.5, 1, 2, 5]
x IN d.c. Multiplication factor for d.c. test current [0.5, 1, 10, 33.33, 50] 1)
Phase Starting polarity [(+), (-), (+,-)]
Test Test [-, L/PE, L1/PE, L2/PE, L3/PE]
Test Test current shape [a.c., d.c.] 2)
Sensitivity Sensitivity [standard, Ipe monitoring] 3)
Uc (P) Contact voltage, external probe [On, Off]
Limit Uc Conventional touch voltage limit [Custom, 12 V, 25 V, 50 V]
RCD Standard Refer to chapter 4.6.8.2 RCD standard for more information.
EV RCD/RCM Standard Refer to chapter 4.6.8.3 EV RCD/RCM standards for more

123
MI 3155 EurotestXD Test and measurements

information.
Earthing system Refer to chapter 4.6.8 Settings for more information.
1)
Parameter is available only when parameter Use is set to other (for Electrical Vehicle
(EV) RCDs/RCMs and Mobile installations (MI) RCDs).
2)
Parameter is available only when RCD I or RCD t test is selected and parameter Use is
set to ‘other’.
3)
Parameter is available only when parameter ‘Use’ is set to PRCD, PRCD-3p, PRCD-S+
or PRCD-K.

Connection diagrams

Figure 7.34: Connecting the Plug commander and the 3-wire test lead

Figure 7.35: Connection for Uc(P) measurement

7.9.1 RCD Uc – Contact voltage


1
Measuring current up to 3 of nominal residual current is used for measurement of contact
voltage.

Contact voltage measurement is performed before trip-out time/current tests. If limit voltage
(e.g. 50 V) is reached during this pre-test, trip-out test is aborted for safety reason.

7.9.1.1 RCD Uc(P) – Contact voltage with external probe

Contact voltage measurement can also be performed using external test probe. Place external
probe to reference earth potential.
For connection see Figure 7.35 Connection for Uc(P) measurement.

124
MI 3155 EurotestXD Test and measurements

Before the contact voltage measurement make sure that Uc(P) parameter is set to On.

Test procedure

 Enter the RCD Uc function.


 Set test parameters / limits.
 Connect test cables to the instrument.
 Connect L, N and PE of 3-wire test lead or Plug commander to the object under test,
see Figure 7.34.
 Connect test lead to P/S terminal and external earthed point (optional, see Figure
7.35).
 Start the measurement.
 Save results (optional).

The contact voltage results Uc and Uc(P) relate to the rated nominal residual current of the
RCD and are multiplied by an appropriate factor (depending on RCD type and type of test
current). The 1.05 factor is applied to avoid negative tolerance of result. See Table 7.3 for
detailed contact voltage calculation factors.

Contact voltages Uc and Uc(P)


RCD type Rated IN
proportional to
AC, EV, MI (a.c. part) G 1.05IN any
AC S 21.05IN
A, F G 1.41.05IN  30 mA
A, F S 21.41.05IN
A, F G 21.05IN < 30 mA
A, F S 221.05IN
B, B+ G 21.05IN any
B, B+ S 221.05IN
Table 7.3: Relation between Uc, Uc(P) and IN

Fault Loop resistance is indicative and calculated from Uc result (without additional proportional
𝑈
factors) according to: 𝑅𝐿 = 𝐼 𝐶 .
∆𝑁

Figure 7.36: Examples of Contact voltage measurement result

Test result / sub-results

Uc Contact voltage
Uc(P) – if selected Contact voltage, external probe
Rl Fault loop resistance

125
MI 3155 EurotestXD Test and measurements

7.9.2 RCD t – Trip-out time


Test procedure

 Enter the RCD t function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object
under test, see Figure 7.34.
 Start the measurement.
 Save results (optional).

Figure 7.37: Examples of Trip-out time measurement result

Test results / sub-results

t ∆N Trip-out time
Uc Contact voltage for rated IN

7.9.3 RCD I – Trip-out current


The instrument increases the test current in small steps through appropriate range as follows:

Slope range
RCD type Waveform
Start value End value
AC 0.2IN 1.1IN Sine
IEC 62752:
0.2IN 1.0IN Sine
EV RCD, EV RCM, MI RCD (a.c. part)
IEC 62955:
0.2IN 1.0IN Sine
EV RCD, EV RCM, MI RCD (a.c. part)
A, F (IN 30 mA) 0.2IN 1.5IN
Pulsed
A, F (IN = 10 mA) 0.2IN 2.2IN
B, B+ 0.2IN 2.2IN DC
IEC 62752:
1.2 mA 6.0 mA DC
EV RCD, EV RCM, MI RCD (d.c. part)
IEC 62955:
1.2 mA 6.0 mA DC
EV RCD, EV RCM, MI RCD (d.c. part)
Table 7.4: Relation between RCD type, slope range and test current

Maximum test current is I (trip-out current) or end value in case the RCD didn’t trip-out.

126
MI 3155 EurotestXD Test and measurements

Test procedure

 Enter the RCD I function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object under test, see Figure 7.34.
 Start the measurement.
 Save results (optional).

Figure 7.38: Examples of Trip-out current measurement result

Test results / sub-results

I∆ Trip-out current
Uc Contact voltage
Uc I∆ Contact voltage at trip-out current I∆ or no value if the RCD didn’t trip
t I∆ Trip-out time at trip-out current I∆

127
MI 3155 EurotestXD Test and measurements

7.10 RCD Auto – RCD Auto test


RCD Auto test function performs a complete RCD test (trip-out time at different residual
currents, trip-out current and contact voltage) in one set of automatic tests, guided by the
instrument.

RCD Auto test procedure

RCD Auto test steps Notes


 Enter the RCD Auto function.
 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the
object under test, see Figure 7.34
 Start the measurement. Start of test
Test with IN d.c., (+) positive polarity (step 1) 1). RCD should trip-out
 Re-activate RCD.
Test with IN d.c., (-) negative polarity (step 2) 1). RCD should trip-out
 Re-activate RCD.
Test with IN, (+) positive polarity (step 3) 2). RCD should trip-out
RCD should not trip-out during
non-operating time for a.c.
residual current (IEC 62955).
 Re-activate RCD if required.
Test with IN, (-) negative polarity (step 4) 2). RCD should trip-out
RCD should not trip-out during
non-operating time for a.c.
residual current (IEC 62955).
 Re-activate RCD if required.
Test with 5IN, (+) positive polarity (step 5) 2). RCD should trip-out
 Re-activate RCD.
Test with 5IN, (-) negative polarity (step 6) 2). RCD should trip-out
 Re-activate RCD.
Test with ½IN, (+) positive polarity (step 7) 2). RCD should not trip-out
Test with ½IN, (-) negative polarity (step 8) 2). RCD should not trip-out
2)
Trip-out current test, (+) positive polarity (step 9) . RCD should trip-out
 Re-activate RCD.
Trip-out current test, (-) negative polarity (step 10) 2). RCD should trip-out
 Re-activate RCD1).
Trip-out current test for d.c. part, (+) polarity (step 11). RCD should trip-out
1)
 Re-activate RCD .
Trip-out current test for d.c. part, (-) polarity (step 12). RCD should trip-out
 Re-activate RCD.
Save results (optional). End of test
1) Steps 1, 2 11 and 12 are performed only when parameter Use is set to ‘other’ and parameter Type
is set to ‘EV RCD’, ‘EV RCM’ or ‘MI RCD’. Trip-out times are measured according to IEC 62752 or
IEC 62955.
2) When parameter Use is set to ‘other’ and parameter Type is set to ‘EV RCD’, ‘EV RCD’ or ‘MI

RCD’, trip-out times or non-operating times for a.c. residual current are measured according to IEC
62752 or IEC 62955.

128
MI 3155 EurotestXD Test and measurements

Step 1 Step 2

Step 3 Step 4

Step 5 Step 6

Step 7 Step 8

129
MI 3155 EurotestXD Test and measurements

Step 9 Step 10

Step 11 Step 12

Figure 7.39: Individual steps in RCD Auto test, example on testing EV RCD

Test results / sub-results


t I∆N d.c. x1, (+) 1) Step 1 trip-out time (I=IN d.c., (+) positive polarity)
t I∆N d.c. x1, (-) 1) Step 2 trip-out time (I=IN d.c., (-) negative polarity)
t I∆N x1, (+) Step 3 trip-out time (I=IN, (+) positive polarity)
Non-operating time for a.c. current (IEC 62955).
t I∆N x1, (-) Step 4 trip-out time (I=IN, (-) negative polarity)
Non-operating time for a.c. current (IEC 62955).
t I∆N x5, (+) Step 5 trip-out time (I=5IN, (+) positive polarity)
t I∆N x5, (-) Step 6 trip-out time (I=5IN, (-) negative polarity)
t I∆N x0.5, (+) Step 7 trip-out time (I=½IN, (+) positive polarity)
t I∆N x0.5, (-) Step 8 trip-out time (I=½IN, (-) negative polarity)
I∆ (+) Step 9 trip-out current ((+) positive polarity)
I∆ (-) Step 10 trip-out current ((-) negative polarity)
I∆ d.c. (+) 1) Step 11 trip-out current ((+) positive polarity)
I∆ d,c, (-) 1) Step 12 trip-out current ((-) negative polarity)
Uc Contact voltage for rated IN
1) Result is displayed only when parameter Use is set to ‘other’ and parameter Type to ‘EV RCD’,
‘EV RCM’ or ‘MI RCD’.

130
MI 3155 EurotestXD Test and measurements

7.11 Z loop – Fault loop impedance and prospective fault


current

Figure 7.40: Z loop menu

Measurement parameters / limits

Fuse Type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
Isc factor Isc factor [Custom, 0.20 … 3.00]
Test1) Selection of test [-, L/PE, L1/PE, L2/PE, L3/PE]
Uc (P) Contact voltage measurement with external probe [Off, On]
Earthing system Refer to chapter 4.6.8 Settings for more information.
Ia(Ipsc) Minimum fault current for selected fuse or custom value
Limit Uc Contact voltage Uc (P) limit [Custom, 12 V, 25 V, 50 V]
1)
With Plug test cable or Plug commander Z loop is measured in the same way regardless
of the setting. The parameter is meant for documentation.

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagrams

Figure 7.41: Connection of Plug commander and 3-wire test lead

131
MI 3155 EurotestXD Test and measurements

Figure 7.42: Connection for Uc(P) measurement

Measurement procedure

 Enter the Z loop function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object under test, see Figure
7.41.
 Connect test lead P/S to external earthed point (optional), see Figure 7.42.
 Start the measurement.
 Save results (optional).

Figure 7.43: Examples of Loop impedance measurement result

Measurement results / sub-results

Z Loop impedance
Ipsc Prospective fault current
Ulpe Voltage L-PE
R Resistance of loop impedance
XL Reactance of loop impedance
Uc (P) Contact voltage at prospective fault current (external probe)

Prospective fault current 𝐼PSC is calculated from measured impedance as follows:

𝑈n ∙ 𝑘sc
𝐼PSC =
𝑍

132
MI 3155 EurotestXD Test and measurements

where:
𝑈n ......... Nominal UL-PE voltage (see table below),
𝑘sc ........ Correction factor (Isc factor) for 𝐼PSC . Refer to chapter 4.6.8 Settings for more
information.
Uc(P) .... Voltage between external earthed point and main earthing point (P/S and PE terminals),
see calculation below

Un Input voltage range (L-PE)


110 V (93 V  UL-PE  134 V)
230 V (185 V  UL-PE  266 V)
Table 7.5: Relation between Input voltage – UL-PE and nominal voltage – Un used for
calculation

Uc(P) calculation
𝑈C (P) = 𝑍PE−P/S × 𝐼PSC

133
MI 3155 EurotestXD Test and measurements

7.12 Z loop 4W – Fault loop impedance and prospective


fault current

Figure 7.44: Z loop 4W menu

Measurement parameters / limits

Fuse Type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
Isc factor Isc factor [Custom, 0.20 … 3.00]
Test Selection of test [-, L-PE, L1-PE, L2-PE, L3-PE]
Ia (Ipsc) Minimum short circuit current for selected fuse or custom value

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagram

Figure 7.45: Connection of 4-wire test lead

Measurement procedure

 Enter the Z loop 4W function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 4-wire test lead to the object under test, C1, P1 terminals to
phase and C2, P2 terminals to PE; see Figure 7.45.
 Start the measurement.
 Save results (optional).

134
MI 3155 EurotestXD Test and measurements

Figure 7.46: Example of Z loop 4W measurement result

Measurement results / sub-results

Z Loop impedance
Ipsc Prospective fault current
Ulpe Voltage L-PE
R Resistance of loop impedance
XL Reactance of loop impedance

Prospective fault current 𝐼PSC is calculated from measured impedance as follows:

𝑈n ∙ 𝑘sc
𝐼PSC =
𝑍
where:
𝑈n ......... Nominal UL-PE voltage (see table below),
𝑘sc ........ Correction factor (Isc factor) for 𝐼PSC . Refer to chapter 4.6.8 Settings for more
information.

Un Input voltage range (L-PE)


110 V (93 V  UL-PE  134 V)
230 V (185 V  UL-PE  266 V)
Table 7.6: Relation between Input voltage – UL-PE and nominal voltage – Un used for
calculation

135
MI 3155 EurotestXD Test and measurements

7.13 Zs rcd – Fault loop impedance and prospective fault


current in system with RCD
Zs rcd measurement prevents trip-out of the RCD in systems with the RCD.

Figure 7.47: Zs rcd menu

Measurement parameters / limits

Protection Protection type [TN, TTrcd]


Fuse Type1) Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]
Fuse I1) Rated current of selected fuse
Fuse t1) Maximum breaking time of selected fuse
Ia(Ipsc)1) Minimum fault current for selected fuse or custom value
Isc factor Isc factor [Custom, 0.20 … 3.00]
Test 3) Selection of test [-, L-PE, L1-PE, L2-PE, L3-PE]
I ∆N 2) Rated RCD residual current sensitivity [10 mA, 15 mA, 30 mA, 100 mA, 300
mA, 500 mA, 1000 mA]
RCD type2) RCD type [AC, A, F, B, B+]
Selectivity2) Characteristic [G, S]
Uc (P) Contact voltage measurement with external probe [On, Off]
I test Test current [Standard, Low]
Limit Uc2) Contact voltage limit [Custom, 12 V, 25 V, 50 V]
1)
Parameter or limit is considered if Protection is set to TN.
2)
Parameter or limit is considered if Protection is set to TTrcd.
3)
With Plug test cable or Plug commander Zs rcd is measured in the same way regardless
of the setting. The parameter is meant for documentation.

Refer to Fuse tables guide for detailed information on fuse data.

136
MI 3155 EurotestXD Test and measurements

Connection diagrams

Figure 7.48: Connection of Plug commander and 3-wire test lead

Figure 7.49: Connection for Uc(P) measurement

Measurement procedure

 Enter the Zs rcd function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object under test, see Figure 7.48.
 Connect test lead P/S to external earthed point (optional), see Figure 7.49.
 Start the measurement.
 Save results (optional).

Figure 7.50: Examples of Zs rcd measurement result

137
MI 3155 EurotestXD Test and measurements

Measurement results / sub-results

Z Loop impedance
Ipsc Prospective fault current
Ulpe Voltage L-PE
Uc 1) Contact voltage at nominal residual current
Uc (P) Contact voltage at prospective fault current (external probe) 2)
Contact voltage at nominal residual current (external probe) 3)
R Resistance of loop impedance
XL Reactance of loop impedance
1)
Result is presented only if Protection is set to TTrcd.
2)
Protection type parameter set to TN.
3)
Protection type parameter set to TTrcd.

Prospective fault current 𝐼PSC is calculated from measured impedance as follows:

𝑈n ∙ 𝑘sc
𝐼PSC =
𝑍
where:
𝑈n ......... Nominal UL-PE voltage (see table below),
𝑘sc ........ Correction factor (Isc factor) for IPSC. Refer to chapter 4.6.8 Settings for more
information.
Uc(P) .... Voltage between external earthed point and main earthing point (P and PE terminals),
see calculation below

Un Input voltage range (L-PE)


110 V (93 V  UL-PE  134 V)
230 V (185 V  UL-PE  266 V)
Table 7.7: Relation between Input voltage – UL-PE and nominal voltage – Un used for
calculation

Uc(P) calculation

𝑍PE−P/S × 𝐼∆N , Protection = TTrcd


𝑈C (P) = {
𝑍PE−P/S × 𝐼PFC, Protection = TN

138
MI 3155 EurotestXD Test and measurements

7.14 Z loop m – High precision fault loop impedance and


prospective fault current

A 1143 MI 3143 or MI 3144


Figure 7.51: Z loop mΩ menu

Measurement parameters / limits

Fuse Type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
Ia(Ipsc) Minimum fault current for selected fuse or custom value
Test1) Test [-, L/PE, L1/PE, L2/PE, L3/PE]
Un2) Nominal voltage [Custom, 110 V, 115 V, 127 V, 220 V, 230 V, 240 V, 290 V,
400 V, 460 V]
2)
Tolerance MI 3143 & MI 3144: Nominal voltage tolerance [6 %, 10 %]
Test Load2) MI 3143: Test Load [33.3 %, 66.6 %, 100 %]
MI 3144: Test Load [16.6 %, 33.3 %, 50.0 %, 66.6 %, 83.3 %, 100 %]
Average2) MI 3143 & MI 3144: Average [Off, 2, 4, 6]
2)
Isc factor Isc factor [Custom, 0.2 ... 3]
1)
The measurement doesn’t depend on the setting. The parameter is meant for
documentation.
2)
Parameter is available only if MI 3143 or MI 3144 Euro Z instrument is selected.

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagram

Connection of A 1143 Connection of MI 3143 and MI 3144

Figure 7.52: High precision loop impedance measurement

139
MI 3155 EurotestXD Test and measurements

Figure 7.53: Contact voltage measurement

Measurement procedure

 Connect MI 3155 instrument with A 1143, MI 3143 or MI 3144 Euro Z adapter /


instrument via serial RS232 or pair them using Bluetooth communication. See
chapter 4.6.8.1 Adapters.
 Enter the Z loop m function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if MI 3143 or MI 3144 Euro Z instrument
is connected to MI 3155 instrument via Bluetooth communication.
 Connect test leads to A 1143, MI 3143 or MI 3144 Euro Z adapter / instrument.
 Connect test leads to the object under test, see Figure 7.52 and Figure 7.53.

 Start the measurement using or button.


 Save results (optional).

Result screen using A 1143 Result screen using MI 3143 or MI 3144


Figure 7.54: Examples of high precision Loop impedance measurement result

Measurement results / sub-results

Z Loop impedance
Ipsc Standard prospective fault current
Imax Maximal prospective fault current
Imin Minimal prospective fault current
Ub Contact voltage at maximal prospective fault current (contact voltage measured against
Probe S if used)
R Resistance of loop impedance
XL Reactance of loop impedance

Voltage monitor using A 1143:

140
MI 3155 EurotestXD Test and measurements

Ulpe Voltage L-PE


Freq Frequency

Voltage monitor using MI 3143 or MI 3144:


Up1p2 Voltage P1-P2
Uc1c2 Voltage C1-C2
Freq Frequency

Refer to A 1143 – Euro Z 290 A, MI 3143 – Euro Z 440 V and MI 3144 – Euro Z 800 V
Instruction manuals for detailed information.

141
MI 3155 EurotestXD Test and measurements

7.15 Z line – Line impedance and prospective short-circuit


current

Figure 7.55: Z line measurement menu

Measurement parameters / limits

Fuse Type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
Isc factor Isc factor [Custom, 0.20 … 3.00]
Test1) Test [-, L/N, L/L, L1/N, L2/N, L3/N, L1/L2, L1/L3, L2/L3]
Earthing system Refer to chapter 4.6.8 Settings for more information.
Ia(Ipsc) Minimum short-circuit current for selected fuse or custom value
1)
With Plug test cable or Plug commander Z line is measured in the same way regardless
of the setting. The parameter is meant for documentation.

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagram

Figure 7.56: Phase-neutral or phase-phase line impedance measurement – connection of


Plug commander and 3-wire test lead

142
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the Z line function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object under test, see Figure
7.56.
 Start the measurement.
 Save results (optional).

Figure 7.57: Examples of Line impedance measurement result

Measurement results / sub-results

Z Line impedance
Ipsc Prospective short-circuit current
Uln Voltage measured between L and N test terminals
R Resistance of line impedance
XL Reactance of line impedance
Imax3p Maximal three-phases prospective short-circuit current
Imin3p Minimal three-phases prospective short-circuit current
Imax2p Maximal two-phases prospective short-circuit current
Imin2p Minimal two-phases prospective short-circuit current
Imax Maximal single-phase prospective short-circuit current
Imin Minimal single-phase prospective short-circuit current

Prospective short circuit current 𝐼PSC is calculated as follows:

𝑈n ∙ 𝑘sc
𝐼PSC =
𝑍
where:
𝑈n ......... Nominal UL-N or UL-L voltage (see table below),
𝑘sc ........ Correction factor (Isc factor) for 𝐼PSC . Refer to chapter 4.6.8 Settings for more
information.

Un Input voltage range (L-N or L-L)


110 V (93 V  UL-N  134 V)
230 V (185 V  UL-N  266 V)
400 V (321 V  UL-L  485 V)
Table 7.8: Relation between Input voltage – UL-N(L) and nominal voltage – Un used for
calculation

143
MI 3155 EurotestXD Test and measurements

The prospective short-circuit currents IMin, IMin2p, IMin3p and IMax, IMax2p, IMax3p are calculated as
follows:

2
𝐶min 𝑈n(L−N) 𝑍(L−N)hot = √(1.5 × 𝑅(L−N) )2 + 𝑋(L−N)
𝐼min = where
𝑍(L−N)hot 0.95; 𝑈n(L−N) = 230 V ± 10 %
𝐶min = {
1.00; otherwise

2 2
𝐶max 𝑈n(L−N) 𝑍(L−N) = √𝑅(L−N) + 𝑋(L−N)
𝐼max = where
𝑍(L−N) 1.05; 𝑈n(L−N) = 230 V ± 10 %
𝐶max = {
1.10; otherwise

2
𝐶min 𝑈n(L−L) 𝑍(L−L)hot = √(1.5 × 𝑅(L−L) )2 + 𝑋(L−L)
𝐼min2p = where
𝑍(L−L)hot 0.95; 𝑈n(L−L) = 400 V ± 10 %
𝐶min = {
1.00; otherwise

2 2
𝐶max 𝑈n(L−L) 𝑍(L−L) = √𝑅(L−L) + 𝑋(L−L)
𝐼max2p = where
𝑍(L−L) 1.05; 𝑈n(L−L) = 400 V ± 10 %
𝐶max = {
1.10; otherwise

2
𝐶min × 𝑈n(L−L) 2 𝑍(L−L)hot = √(1.5 × 𝑅(L−L) )2 + 𝑋(L−L)
𝐼min3p = where
√3 𝑍(L−L)hot 0.95; 𝑈n(L−L) = 400 V ± 10 %
𝐶min = {
1.00; otherwise

2 2
𝐶max × 𝑈n(L−L) 2 𝑍(L−L) = √𝑅(L−L) + 𝑋(L−L)
𝐼max3p = where
√3 𝑍(L−L) 1.05; 𝑈n(L−L) = 400 V ± 10 %
𝐶max = {
1.10; otherwise

144
MI 3155 EurotestXD Test and measurements

7.16 Z line 4W – Line impedance and prospective short-


circuit current

Figure 7.58: Z line 4 W measurement menu

Measurement parameters / limits

Fuse Type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
Isc factor Isc factor [Custom, 0.20 … 3.00]
Test1) Test [-, L/N, L/L, L1/N, L2/N, L3/N, L1/L2, L1/L3, L2/L3]
Earthing system Refer to chapter 4.6.8 Settings for more information.
Ia (Ipsc) Minimum short circuit current for selected fuse or custom value
1)
The measuring results (for phase – neutral or phase – phase line) are set according to
the setting. The parameter is meant for documentation.

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagram

Figure 7.59: Phase-phase or phase-neutral 4-wire line impedance measurement

145
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the Z line 4W function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 4-wire test lead to the object under test, see Figure 7.59.
 Start the measurement.
 Save results (optional).

Figure 7.60: Examples of Z line 4W measurement result

Measurement results / sub-results

Z Line impedance
Ipsc Prospective short-circuit current
Uln Voltage measured between C1 and C2 terminals
R Resistance of line impedance
XL Reactance of line impedance

Prospective short circuit current 𝐼PSC is calculated as follows:

𝑈n ∙ 𝑘sc
𝐼PSC =
𝑍
where:
𝑈n ......... Nominal L-N or L-L voltage (see table below),
𝑘sc ........ Correction factor for Isc. Refer to chapter 4.6.8 Settings for more information.

Un Input voltage range (L-N or L-L)


110 V (93 V  UL-N 134 V)
230 V (185 V  UL-N 266 V)
400 V (321 V  UL-L 485 V)
Table 7.9: Relation between Input voltage – UL-N(L) and nominal voltage – Un used for
calculation

146
MI 3155 EurotestXD Test and measurements

7.17 Z line m – High precision line impedance and


prospective short-circuit current

A 1143 MI 3143 or MI 3144


Figure 7.61: Z line mΩ menu

Measurement parameters / limits

Fuse Type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
Ia(Ipsc) Minimum short circuit current for selected fuse or custom value
Test1) Test [-, L-N, L/L, L1-N, L2-N, L3-N, L1-L2, L1-L3, L2-L3]
Un2) Test=[-, L/N, L1/N, L2/N, L3/N]:
Nominal voltage [Custom, 110 V, 115 V, 127 V, 220 V, 230 V, 240 V,
290 V, 400 V, 460 V]
Test=[L/L, L1/L2, L1/L3, L2/L3]:
Nominal voltage [Custom, 190 V, 200 V, 220 V, 380 V, 400 V, 415 V,
500 V, 690 V, 800 V]
Tolerance2) MI 3143 & MI 3144: Nominal voltage tolerance [6 %, 10 %]
Test Load2) MI 3143: Test Load [33.3 %, 66.6 %, 100 %]
MI 3144: Test Load [16.6 %, 33.3 %, 50.0 %, 66.6 %, 83.3 %, 100 %]
2)
Average MI 3143 & MI 3144: Average [Off, 2, 4, 6]
Isc factor2) Isc factor [Custom, 0.20 ... 3.00]
1)
The measuring results (for phase – neutral or phase – phase line) are set according to
the setting. The parameter is meant for documentation.
2)
Parameter is available only if MI 3143 or MI 3144 Euro Z instrument is selected.

Refer to Fuse tables guide for detailed information on fuse data.

147
MI 3155 EurotestXD Test and measurements

Connection diagram

Connection of A 1143 Connection of MI 3143 or MI 3144


Figure 7.62: Phase-neutral or phase-phase high precision Line impedance measurement

Measurement procedure

 Connect MI 3155 instrument with A 1143, MI 3143 or MI 3144 Euro Z adapter /


instrument via serial RS232 or pair them using Bluetooth communication. See
chapter 4.6.8.1 Adapters.
 Enter the Z line m function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if MI 3143 or MI 3144 Euro Z instrument
is connected to MI 3155 instrument via Bluetooth communication.
 Connect test leads to A 1143, MI 3143 or MI 3144 Euro Z adapter / instrument.
 Connect test leads to the object under test, see Figure 7.62.

 Start the measurement using or button.


 Save results (optional).

Result screens using A 1143

Result screens using MI 3143 or MI 3144


Figure 7.63: Examples of high precision Line impedance measurement result

148
MI 3155 EurotestXD Test and measurements

Measurement results / sub-results

Z Line impedance
Ipsc Standard prospective short-circuit current
Imax Maximal prospective short-circuit current
Imin Minimal prospective short-circuit current
Imax2p Maximal two-phases prospective short-circuit current
Imin2p Minimal two-phases prospective short-circuit current
Imax3p Maximal three-phases prospective short-circuit current
Imin3p Minimal three-phases prospective short-circuit current
R Resistance of line impedance
XL Reactance of line impedance

Voltage monitor using A 1143:


Uln Voltage L-N or L-L
Freq Frequency

Voltage monitor using MI 3143 or MI 3144:


Up1p2 Voltage P1-P2
Uc1c2 Voltage C1-C2
Freq Frequency

Refer to A 1143 – Euro Z 290 A, MI 3143 – Euro Z 440 V and MI 3144 – Euro Z 800 V
Instruction manuals for detailed information.

149
MI 3155 EurotestXD Test and measurements

7.18 High Current (MI 3143 and MI 3144)

Figure 7.64: High Current menu

Measurement parameters / limits

Test Load MI 3143: Test load [33.3 %, 66.6 %, 100 %]


MI 3144: Test load [16.6 %, 33.3 %, 50.0 %, 66.6 %, 83.3 %, 100 %]
Clamp Type1) Clamp type [A 1227, A 1281, A 1609]
Clamp Range1) Range @ A 1227, A 1609 [30 A, 300 A, 3000 A]
Range @ A 1281 [0.5 A, 5 A, 100 A, 1000 A]
Average Average [Off, 2, 4, 6]
Limit (R) Limit [Off, Custom, 0.01  … 19 ]
1)
Measurement with current clamps is supported by MI 3144 – Euro Z 800 V instrument
only.

Connection diagram

Figure 7.65: High Current resistance measurement

Measurement procedure

 Connect MI 3155 instrument with MI 3143 or MI 3144 Euro Z adapter / instrument


via serial RS232 or pair them using Bluetooth communication. See chapter 4.6.8.1
Adapters.
 Enter the High Current function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if MI 3143 or MI 3144 Euro Z instrument
is connected to MI 3155 instrument via Bluetooth communication.

150
MI 3155 EurotestXD Test and measurements

 Connect test leads to MI 3143 or MI 3144 Euro Z instrument.


 Connect test leads to the object under test. See Figure 7.65.
 Refer to MI 3143 – Euro Z 440 V or MI 3144 – Euro Z 800 V Instruction manual for
detailed information.

 Start the measurement using or button.


 Save results (optional).

Figure 7.66: Example of High Current measurement result

Measurement results / sub-results

R Resistance
Rsel1) Resistance (calculated from Clamp current)
Itest Test current
Ic1) Clamp current
U Voltage
f Frequency
U Voltage dip
U% Voltage dip in percentage [ΔU (%) = (ΔU / U_unloaded) x 100 %]

1)
Measurement with current clamps is supported by MI 3144 – Euro Z 800 V instrument only.

Voltage monitor:
Up1p2 Voltage P1-P2
Uc1c2 Voltage C1-C2
Freq Frequency

Refer to MI 3143 – Euro Z 440 V and MI 3144 – Euro Z 800 V Instruction manuals for
detailed information.

151
MI 3155 EurotestXD Test and measurements

7.19 Voltage Drop


The voltage drop is calculated based on the difference of line impedance at connection points
(sockets) and the line impedance at the reference point (usually the impedance at the
switchboard).

Figure 7.67: Voltage drop menu

Measurement parameters / limits

Fuse Type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
I (U) 1)
Rated current for U measurement (custom value)
Isc factor Isc factor [Custom, 0.20 … 3.00]
Test 2) Test [-, L/N, L/L, L1/N, L2/N, L3/N, L1/L2, L1/L3, L2/L3]
Earthing system Refer to chapter 4.6.8 Settings for more information.
Limit(U) Maximum voltage drop [Off, Custom, 3.0 % … 9.0 %]
1)
Applicable if Fuse type is set to Off or Custom
2)
With Plug test cable or Plug commander Voltage drop is measured in the same way
regardless of the setting. The parameter is meant for documentation.

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagram

Figure 7.68: Voltage drop measurement – connection of Plug commander and 3-wire test
lead

152
MI 3155 EurotestXD Test and measurements

Measurement procedure

STEP 1: Measuring the impedance Zref at origin

 Enter the Voltage Drop function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead to the origin of electrical installation, see Figure 7.68.
 Touch or select the icon to initiate Zref measurement.

 Press the button to measure Zref.

STEP 2: Measuring the Voltage drop

 Enter the Voltage Drop function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the tested points, see Figure 7.68.
 Start the measurement.
 Save results (optional).

Figure 7.69: Example of Zref measurement result (Step 1)

Figure 7.70: Examples of Voltage drop measurement result (Step 2)

153
MI 3155 EurotestXD Test and measurements

Measurement results / sub-results

U Voltage drop
Ipsc Prospective short-circuit current
Uln Voltage L-N
Zref Reference line impedance
Z Line impedance

Voltage drop is calculated as follows:

(𝑍 − 𝑍𝑅𝐸𝐹 ) ⋅ 𝐼𝑁
𝛥𝑈[%] = ⋅ 100
𝑈𝑁
where:

ΔU Calculated Voltage drop


Zref Impedance at reference point (at origin)
Z Impedance at test point
Un Nominal voltage
In Rated current of selected fuse (Fuse I) or custom value I (U)

Un Input voltage range (L-N or L-L)


110 V (93 V  UL-N  134 V)
230 V (185 V  UL-N  266 V)
400 V (321 V  UL-L  485 V)
Table 7.10: Relation between Input voltage – UL-N(L) and nominal voltage – Un used for
calculation

154
MI 3155 EurotestXD Test and measurements

7.20 U touch – Touch voltage (MI 3143 and MI 3144)

Figure 7.71: Touch voltage menu

Measurement parameters / limits

Test Load MI 3143: Test load [33.3 %, 66.6 %, 100 %]


MI 3144: Test load [16.6 %, 33.3 %, 50.0 %, 66.6 %, 83.3 %,
100 %]
I fault Fault current [Custom, 10 A … 200 kA]
Limit(Utouch) Limit [Off, Custom, 25 V, 50 V]

Connection diagram

Figure 7.72: Touch voltage measurement – Connection of MI 3143 or MI 3144

Refer to MI 3143 – Euro Z 440 V and MI 3144 – Euro Z 800 V Instruction manual for detailed
information.

Measurement procedure

 Connect MI 3155 instrument with MI 3143 or MI 3144 Euro Z instrument via serial
RS232 or pair them using Bluetooth communication. See chapter 4.6.8.1 Adapters.
 Enter the U touch function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if MI 3143 or MI 3144 Euro Z instrument
is connected to MI 3155 instrument via Bluetooth communication.
 Connect test leads and A 1597 adapter to MI 3143 or MI 3144 Euro Z instrument.
 Connect test leads to the object under test.
Refer to MI 3143 Euro Z 440 V or MI 3144 Euro Z 800 V Instruction manual for
detailed information.

 Start the measurement using or button.

155
MI 3155 EurotestXD Test and measurements

 Save results (optional).

Figure 7.73: Example of Touch voltage measurement result

Measurement results / sub-results

Utouch Calculated touch voltage


Um Measured voltage drop
Itest Test current

Voltage monitor:
Up1p2 Voltage P1-P2
Uc1c2 Voltage C1-C2
Freq Frequency

Refer to MI 3143 Euro Z 440 V and MI 3144 Euro Z 800 V Instruction manuals for detailed
information.

156
MI 3155 EurotestXD Test and measurements

7.21 Z auto - Auto test sequence for fast line and loop
testing
Tests / measurements implemented in Z auto test sequence

Voltage
Z line
Voltage Drop
Zs rcd
Uc

Figure 7.74: Z auto menu

Measurement parameters / limits


Protection Protection type [TN, TNrcd, TTrcd]
Fuse type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]
Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
I (U) 1) Rated current for U measurement (custom value)
Isc factor Isc factor [Custom, 0.20 … 3.00]
RCD Type RCD type [AC, A, F, B, B+]
I N Rated RCD residual current sensitivity [10 mA, 15 mA, 30 mA, 100 mA, 300
mA, 500 mA, 1000 mA]
Selectivity Characteristic [G, S]
Phase2) Selection of test [-, L1, L2, L3]
I test Test current [Standard, Low]
Limit(∆U) Maximum voltage drop [Off, Custom, 3.0 % ... 9.0 %]
Ia(Ipsc (LN) Minimum short circuit current for selected fuse or custom value
Ipsc (LPE))3)
Limit Uc Conventional touch voltage limit [Custom, 12 V, 25 V, 50 V]
1)
Applicable if Fuse type is set to Off or Custom.
2)
With Plug test cable or Plug commander RCD tests are measured in the same way
regardless of the setting. The parameter is meant for documentation.
3)
Ipsc (LPE) is considered if Protection is set to TNrcd. Ipsc(LN) is always considered.

Refer to Fuse tables guide for detailed information on fuse data.

157
MI 3155 EurotestXD Test and measurements

Connection diagram

Figure 7.75: Z auto measurement

Measurement procedure

 Enter the Z auto function.


 Set test parameters / limits.
 Measure the impedance Zref at origin (optional), see chapter 7.19 Voltage Drop.
 Connect test cable to the instrument.
 Connect 3 wire test lead or Plug commander to the object under test, see Figure
7.75.
 Start the Auto test.
 Save results (optional).

Figure 7.76: Examples of Z auto measurement results

Measurement results / sub-results

Uln Voltage between phase and neutral conductors


∆U Voltage drop
Z (LN) Line impedance
Z (LPE) Loop impedance
Zref Reference line impedance
Ipsc (LN) Prospective short-circuit current
Ipsc (LPE) Prospective fault current
Uc Contact voltage

158
MI 3155 EurotestXD Test and measurements

7.22 R line m – DC resistance measurement (MI 3144)

Figure 7.77: R line mΩ menu

Measurement parameters / limits

Limit (R) Limit [Off, Custom, 0.01  … 19 ]

Connection diagram

Figure 7.78: R line mΩ – Connection of MI 3144

Measurement procedure

 Connect MI 3155 instrument with MI 3144 Euro Z 800 V instrument via serial RS232
or pair them using Bluetooth communication. See chapter 4.6.8.1 Adapters.
 Enter the R line m function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if MI 3144 Euro Z 800 V instrument is
connected to MI 3155 instrument via Bluetooth communication.
 Connect test leads to MI 3144 Euro Z 800 V instrument.
 Connect test leads to the object under test.
Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

 Start the measurement using or button.


 Save results (optional).

159
MI 3155 EurotestXD Test and measurements

Figure 7.79: Example of R line mΩ measurement result

Measurement results / sub-results

R Line resistance
Itest Test current
Udc Voltage
U Voltage drop
U% Voltage drop in percentage

Voltage monitor:
Up1p2 Voltage P1-P2
Uc1c2 Voltage C1-C2
Freq Frequency

Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

160
MI 3155 EurotestXD Test and measurements

7.23 ELR Current Injection Test (MI 3144)

Figure 7.80: ELR Current Injection Test menu

Measurement parameters / limits

Current Waveform Current waveform [Alternating, Pulsating, DC]


Number of turns Number of turns [1 … 10]
I gen Current [3 mA, 5 mA, 6 mA, 10 mA, 15 mA, 30 mA, 50 mA, 100 mA, 150
mA, 250 mA, 300 mA, 500 mA]
Phase Phase [(+), (-)]
I set Current limit for selected generated current and number of turns.

Connection diagram

Figure 7.81: ELR Current Injection Test / Combination Time Test connection

Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

Measurement procedure

 Connect MI 3155 instrument with MI 3144 Euro Z 800 V instrument via serial
RS232 or pair them using Bluetooth communication. See chapter 4.6.8.1
Adapters.
 Enter the ELR Current Injection Test function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if MI 3144 Euro Z 800 V instrument is
connected to MI 3155 instrument via Bluetooth communication.
 Connect test leads to MI 3144 Euro Z 800 V instrument.
 Connect test leads to the object under test. See Figure 7.81.

161
MI 3155 EurotestXD Test and measurements

Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

 Start the measurement using or button.


 Use to select PASS / FAIL / NO STATUS indication.

 Press or the key to confirm selection and complete the measurement.


 Save results (optional).

Figure 7.82: Examples of high precision Line impedance measurement result

Measurement result

I Current

Voltage monitor:
Up1p2 Voltage P1-P2
Uc1c2 Voltage C1-C2
Freq Frequency

Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

162
MI 3155 EurotestXD Test and measurements

7.24 ELR Combination Time Test (MI 3144)

Figure 7.83: ELR Combination Time Test menu

Measurement parameters / limits

Current Waveform Current waveform [Alternating, Pulsating, DC]


Number of turns Number of turns [1 … 10]
I gen Current [3 mA, 5 mA, 6 mA, 10 mA, 15 mA, 30 mA, 50 mA, 100 mA, 150
mA, 250 mA, 300 mA, 500 mA]
Phase Phase [(+), (-)]
Test duration Duration [0.3 s, 0.5 s, 1 s, 2 s, 5 s, 10 s, 20 s]
I set Current limit for selected generated current and number of turns.

Connection diagram

See Figure 7.81.


Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

Measurement procedure

 Connect MI 3155 instrument with MI 3144 Euro Z 800 V instrument via serial RS232
or pair them using Bluetooth communication. See chapter 4.6.8.1 Adapters.
 Enter the ELR Combination Time Test function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if MI 3144 Euro Z 800 V instrument is
connected to MI 3155 instrument via Bluetooth communication.
 Connect test leads to MI 3144 Euro Z 800 V instrument.
 Connect test leads to the object under test. See Figure 7.81.
Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

 Start the measurement using or button.


 Use to select PASS / FAIL / NO STATUS indication.

 Press or the key to confirm selection and complete the measurement.


 Save results (optional).

163
MI 3155 EurotestXD Test and measurements

Figure 7.84: Example of ELR Combination Time Test result

Measurement result

t Time

Voltage monitor:
Up1p2 Voltage P1-P2
Uc1c2 Voltage C1-C2
Freq Frequency

Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

164
MI 3155 EurotestXD Test and measurements

7.25 EVSE Diagnostic Test (A 1632)


EVSE Diagnostic Test should be performed with A 1632 eMobility Analyser connected with MI
3155 instrument via Bluetooth communication.

Figure 7.85: Diagnostic Test (EVSE) start screens – EV simulator, Errors and Monitor

Measurement parameters / limits


With selection of the Test parameter on the start screen, three diagnostic sub-tests can be set.

Test Test [EV simulator, Monitor, Errors]


EV simulator - Simulation of Electrical Vehicle
Monitor - Monitoring of EVSE – EV interconnection and signalling
Errors - Simulation of CP Errors
Toff Simulated CP errors [C->E1, C->E2, C->E3, D->E1, D->E2, D->E3]
Simulator CP CP (control pilot) state setting [nc, A, B, C, D]
Simulator PP PP (proximity pilot) state setting [nc, 13 A, 20 A, 32 A, 63 A, 80 A]
Duration Test duration [Off, 2 s, 3 s, 5 s, 10 s, 30 s, 60 s, 90 s, 120 s, 180 s]
Control Analyser control [Remote (Bluetooth), Manual (A 1632)]

Connection diagrams

Refer to A 1632 – eMobility Analyser Instruction manual for detailed information.

Figure 7.86: Diagnostic test - EV simulator and Errors sub-tests - connection to EVSE

Figure 7.87: Diagnostic test - EV simulator and Errors sub-tests - connection to Mode 2
charging cable powered from Analyser

165
MI 3155 EurotestXD Test and measurements

Figure 7.88: Diagnostic test (EVSE) - Monitor sub-test - connection to EVSE or charging
cable

Diagnostic test procedure

 Pair and connect MI 3155 with A 1632 eMobility Analyzer instrument via Bluetooth
communication. See chapter 4.6.8.1 Adapters.
 Enter the Diagnostic test (EVSE) function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if A 1632 eMobility Analyzer is
connected to MI 3155 instrument via Bluetooth communication.
 Connect the charging cable / station to A 1632 eMobility Analyzer adapter. See
Figure 7.86, Figure 7.87 and Figure 7.88.
Refer to A 1632 eMobility Analyzer Instruction manual for detailed information.

 Start the measurement using or button.


 Manually apply status (optional).
 Save results (optional).

Figure 7.89: Examples of Diagnostic Test (EVSE) measurement results – EV simulator,


Errors and Monitor

Measurement results / sub-results

CP+ Maximal value of CP (control pilot) signal


CP- Minimal value of CP (control pilot) signal
D Duty cycle of CP (control pilot) signal
Freq Frequency of CP (control pilot) signal
Ievse Charging current available by charging cable / EVSE
U1N Voltage UL1-N on the output of charging cable / EVSE
U2N Voltage UL2-N on the output of charging cable / EVSE
U3N Voltage UL3-N on the output of charging cable / EVSE
Field 1.2.3 – correct connection – CW rotation sequence

166
MI 3155 EurotestXD Test and measurements

3.2.1 – invalid connection – CCW rotation sequence


toff Disconnection time of charging cable / EVSE
State System state

Refer to A 1632 eMobility Analyzer Instruction manual for detailed information.

167
MI 3155 EurotestXD Test and measurements

7.26 Earth – Earth resistance (3-wire test)

Figure 7.90: Earth menu

Measurement parameters / limits


Limit(Re) Maximum resistance [Off, Custom, 1  ... 5 k]

Connection diagrams

Figure 7.91: Resistance to earth, measurement of main installation earthing and lighting
protection system

Measurement procedure
 Enter the Earth function.
 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead to the object under test, see Figure 7.91.
 Start the measurement.
 Save results (optional).

Figure 7.92: Examples of Earth resistance measurement result

168
MI 3155 EurotestXD Test and measurements

Measurement results / sub-results

Re Earth resistance
Rc Resistance of H (current) probe
Rp Resistance of S (potential) probe

7.27 Earth 2 clamp – Contactless earthing resistance


measurement (with two current clamps)

Figure 7.93: Earth 2 clamps menu

Measurement parameters / limits

Limit(Re) Maximum resistance [Off, Custom, 1  ... 30 ]

Connection diagram

Figure 7.94: Contactless earthing resistance measurement

Measurement procedure

 Enter the Earth 2 clamp function.


 Set test parameters / limits.
 Connect test cable and clamps to the instrument.
 Clamp on object under test, see Figure 7.94.
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

169
MI 3155 EurotestXD Test and measurements

Figure 7.95: Examples of Contactless earthing resistance measurement result

Measurement results / sub-results

Re Earth resistance

7.28 Ro – Specific earth resistance (A 1199)

Figure 7.96: Earth Ro menu

Measurement parameters / limits

Length Unit Length unit [m, ft]


Distance Distance between probes [Custom, 0.1 m ... 29.9 m or 1 ft ... 100 ft]

Connection diagram

Figure 7.97: Specific earth resistance measurement

170
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the Ro function.


 Set test parameters / limits.
 Connect A 1199 adapter to the instrument.
 Connect test leads to earth probes, see Figure 7.97.
 Start the measurement.
 Save results (optional).

Figure 7.98: Example of Specific earth resistance measurement result

Measurement results / sub-results

 Specific earth resistance


Rc Resistance of H, E (current) probe
Rp Resistance of S, ES (potential) probe

171
MI 3155 EurotestXD Test and measurements

7.29 Power

Figure 7.99: Power menu

Measurement parameters / limits

Ch1 clamp type Current clamp adapter [A1018, A1391]


Range Range for selected current clamp adapter
A1018 [20 A]
A1391 [40 A, 300 A]

Connection diagram

Figure 7.100: Power measurement

Measurement procedure

 Enter the Power function.


 Set parameters / limits.
 Connect the 3-wire test lead and current clamp to the instrument.
 Connect the 3-wire test lead and current clamp to the item to be tested (see Figure
7.100).
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

172
MI 3155 EurotestXD Test and measurements

Figure 7.101: Example of Power measurement result

Measurement results / sub-results

P Active power
S Apparent power
Q Reactive power (capacitive or inductive)
PF Power factor (capacitive or inductive)
THDu Voltage total harmonic distortion

173
MI 3155 EurotestXD Test and measurements

7.30 Harmonics

Figure 7.102: Harmonics menu

Measurement parameters / limits

Ch1 clamp type Current clamp adapter [A1018, A1391]


Range Range for selected current clamp adapter
A1018 [20 A]
A1391 [40 A, 300 A]
Limit(THDu) Max. THD of voltage [Off, Custom, 3 % ... 10 %]

Connection diagram

Figure 7.103: Harmonics measurement

Measurement procedure

 Enter the Harmonics function.


 Set parameters / limits.
 Connect 3-wire test lead and current clamp to the instrument.
 Connect 3-wire test lead and current clamp to the item to be tested, see Figure
7.103.
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

174
MI 3155 EurotestXD Test and measurements

Figure 7.104: Examples of Harmonics measurement results

Measurement results / sub-results

U:h(i) TRMS voltage of selected harmonic [h0 ... h11]


I:h(i) TRMS current of selected harmonic [h0 ... h11]
THDu Voltage total harmonic distortion
THDi Current total harmonic distortion

175
MI 3155 EurotestXD Test and measurements

7.31 Currents

Figure 7.105: Current menu

Measurement parameters / limits

Ch1 clamp type Current clamp adapter [A1018, A1391]


Range Range for selected current clamp adapter
A1018 [20 A]
A1391 [40 A, 300 A]
Limit(I1) Max. PE leakage or load current [Off, Custom, 0.1 mA ... 100 mA]

Connection diagram

Figure 7.106: PE leakage and load current measurements

Measurement procedure

 Enter the Currents function.


 Set parameters / limits.
 Connect the current clamp to the instrument.
 Connect the clamp to the object under test, see Figure 7.106.
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

176
MI 3155 EurotestXD Test and measurements

Figure 7.107: Examples of Current measurement result

Measurement results / sub-results

I1 PE leakage or load current

177
MI 3155 EurotestXD Test and measurements

7.32 Current Clamp Meter (MI 3144)

Figure 7.108: Current Clamp Meter menu

Measurement parameters / limits

Clamp Type Clamp type [A 1227, A 1281, A 1609]


Clamp Range Range
Clamp type A 1227, A 1609: [30 A, 300 A, 3000 A]
Clamp type A 1281: [0.5 A, 5 A, 100 A, 1000 A]

Connection diagram

Figure 7.109: Current Clamp Meter measurement

Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

Measurement procedure

 Connect MI 3155 instrument with MI 3144 Euro Z instrument via serial RS232 or pair
them using Bluetooth communication. See chapter 4.6.8.1 Adapters.
 Enter the Current Clamp Meter function.
 Set test parameters / limits.
 Check Bluetooth communication active sign if MI 3144 Euro Z 800 V instrument is
connected to MI 3155 instrument via Bluetooth communication.
 Connect current clamp to MI 3144 Euro Z 800 V instrument.
 Wrap the object under test with the measuring clamp. See Figure 7.109.
Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

 Start the continuous measurement using or button.


 Stop the measurement.

178
MI 3155 EurotestXD Test and measurements

 Save results (optional).

Figure 7.110: Example of Current Clamp Meter measurement result

Measurement results / sub-results

I Current
f Frequency

Refer to MI 3144 Euro Z 800 V Instruction manual for detailed information.

179
MI 3155 EurotestXD Test and measurements

7.33 ISFL – First fault leakage current

Figure 7.111: ISFL measurement menu

Measurement parameters / limits

Imax(Isc1, Isc2) Maximum first fault leakage current [Off, Custom, 3.0 mA ... 19.5 mA]

Connection diagrams

Figure 7.112: Measurement of highest First fault leakage current with 3-wire test lead

Figure 7.113: Measurement of First fault leakage current for RCD protected circuit with 3-
wire test lead

180
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the ISFL function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead to the object under test, see Figure 7.112 and Figure
7.113.
 Start the measurement.
 Save results (optional).

Figure 7.114: Examples of First fault leakage current measurement result

Measurement results / sub-results

Isc1 First fault leakage current at single fault between L1/PE


Isc2 First fault leakage current at single fault between L2/PE

181
MI 3155 EurotestXD Test and measurements

7.34 IMD – Testing of insulation monitoring devices


This function checks the alarm threshold of insulation monitor devices (IMD) by applying a
changeable resistance between L1/PE and L2/PE terminals.

Figure 7.115: IMD test menu

Test parameters / limits

Test Test mode [MANUAL R, MANUAL I, AUTO R, AUTO I]


Rstart Starting insulation resistance [Auto, 5 k ... 640 k]
Istart Starting fault current [Auto, 0.1 mA ... 19.9 mA]
t step Timer (AUTO R and AUTO I test modes) [1 s ... 99 s]
Rmin(R1,R2) Min. insulation resistance (RLIMIT) [Off, 5 k ... 640 k]
Imax(I1,I2) Max. fault current (ILIMIT) [Off, 0.1 mA ... 19.9 mA]
Time limit (t1, t2) Max. activation / disconnection time limit [Off, 1 s]

Connection diagram

Figure 7.116: Connection with 3-wire test lead

182
MI 3155 EurotestXD Test and measurements

Test procedure (MANUAL R, MANUAL I)

 Enter the IMD function.


 Set test parameter to MANUAL R or MANUAL I.
Set other test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead to the object under test, see Figure 7.116.
 Start the measurement.

 Use the or keys to change insulation resistance1) until IMD


alarms an insulation failure for L1.

 Press or the key to change line terminal selection to L2.


(If IMD switches off voltage supply, instrument automatically changes line
terminal selection to L2 and proceeds with the test when supply voltage is
detected.)

 Use the or keys to change insulation resistance1) until IMD


alarms an insulation failure for L2.

 Press the or the key.


(If IMD switches off voltage supply, instrument automatically proceeds to the
PASS / FAIL / NO STATUS indication.)
 Use to select PASS / FAIL / NO STATUS indication.

 Press or the key to confirm selection and complete the


measurement.
 Save results (optional).

Test procedure (AUTO R, AUTO I)

 Enter the IMD function.


 Set test parameter to AUTO R or AUTO I.
 Set other test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead to the object under test, see Figure 7.116.
 Start the measurement.
Insulation resistance between L1-PE is decreased automatically according to limit
value1) every time interval selected with timer. To speed up the test press the

or keys until IMD alarms an insulation failure for L1.

 Press or the key to change line terminal selection to L2.


(If IMD switches off voltage supply, instrument automatically changes line

183
MI 3155 EurotestXD Test and measurements

terminal selection to L2 and proceeds with the test when supply voltage is
detected.)
 Insulation resistance between L2-PE is decreased automatically according to limit
value1) every time interval selected with timer. To speed up the test press the

or keys until IMD alarms an insulation failure for L2.

 Press the or the key.


If IMD switches off voltage supply, instrument automatically proceeds to the
PASS / FAIL / NO STATUS indication.
 Use to select PASS / FAIL / NO STATUS indication.

 Press or the key to confirm selection and complete the


measurement.
 Save results (optional).
*)
Starting and ending insulation resistances are determined by selection of IMD test sub-
function and test parameters. See tables below:

Sub-function Rstart parameter Starting insulation Ending insulation


resistance value resistance value
Auto 𝑅𝑆𝑇𝐴𝑅𝑇 ≅ 1.5 × 𝑅𝐿𝐼𝑀𝐼𝑇 -
MANUAL R
[5 k ... 640 k] 𝑅𝑆𝑇𝐴𝑅𝑇 = 𝑅𝑠𝑡𝑎𝑟𝑡 -
Auto 𝑅𝑆𝑇𝐴𝑅𝑇 ≅ 1.5 × 𝑅𝐿𝐼𝑀𝐼𝑇 𝑅𝐸𝑁𝐷 ≅ 0.5 × 𝑅𝐿𝐼𝑀𝐼𝑇
AUTO R
[5 k ... 640 k] 𝑅𝑆𝑇𝐴𝑅𝑇 = 𝑅𝑠𝑡𝑎𝑟𝑡 𝑅𝐸𝑁𝐷 ≅ 0.5 × 𝑅𝑆𝑇𝐴𝑅𝑇
Table 7.11: Starting / ending insulation resistance values for MANUAL R and AUTO R
sub-functions

Sub-function Istart parameter Starting insulation Ending insulation


resistance value resistance value
𝑈𝐿1−𝐿2 -
Auto 𝑅𝑆𝑇𝐴𝑅𝑇 ≅ 1.5 ×
𝐼𝐿𝐼𝑀𝐼𝑇
MANUAL I 𝑈𝐿1−𝐿2 -
[0.1 mA ... 19.9 mA] 𝑅𝑆𝑇𝐴𝑅𝑇 ≅
𝐼𝑠𝑡𝑎𝑟𝑡
𝑈𝐿1−𝐿2 𝑈𝐿1−𝐿2
Auto 𝑅𝑆𝑇𝐴𝑅𝑇 ≅ 1.5 × 𝑅𝐸𝑁𝐷 ≅ 0.5 ×
𝐼𝐿𝐼𝑀𝐼𝑇 𝐼𝐿𝐼𝑀𝐼𝑇
AUTO I 𝑈𝐿1−𝐿2 𝑈𝐿1−𝐿2
[0.1 mA ... 19.9 mA] 𝑅𝑆𝑇𝐴𝑅𝑇 ≅ 𝑅𝐸𝑁𝐷 ≅ 0.5 ×
𝐼𝑠𝑡𝑎𝑟𝑡 𝐼𝑠𝑡𝑎𝑟𝑡
Table 7.12: Starting / ending insulation resistance values for MANUAL I and AUTO I
sub-functions

184
MI 3155 EurotestXD Test and measurements

Figure 7.117: Examples of IMD test result

Test results / sub-results

R1 Threshold insulation resistance between L1-PE


I1 Calculated first fault leakage current for R1
t1 Activation / disconnection time of IMD for R1
R2 Threshold insulation resistance between L2-PE
I2 Calculated first fault leakage current for R2
t2 Activation / disconnection time of IMD for R2

𝑈𝐿1−𝐿2
Calculated first fault leakage current at threshold insulation resistance is given as 𝐼1(2) = 𝑅1(2)
,
where UL1-L2 is line-line voltage. The calculated first fault current is the maximum current that
would flow when insulation resistance decreases to the same value as the applied test
resistance, and a first fault is assumed between opposite line and PE.

If any of the activation / disconnection time result (t1, t2) is out of set limit, overall status of the
test is “failed” and cannot be modified manually. Otherwise, overall status can be user defined.
If activation of IMD device is visual indication and/or audio alert, without voltage disconnection,
Time limit (t1,t2) parameter should be set to “Off” to disable timing limitation.

185
MI 3155 EurotestXD Test and measurements

7.35 Rpe – PE conductor resistance

Figure 7.118: PE conductor resistance measurement menu

Measurement parameters / limits

Bonding [Rpe, Local]


RCD [Yes, No]
Limit(Rpe) Max. resistance [Off, Custom, 0.1  ... 20.0 ]

Connection diagram

Figure 7.119: Connection of Plug commander and 3-wire test lead

186
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the Rpe function.


 Set test parameters / limits.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object under test, see Figure 7.119.
 Start the measurement.
 Save results (optional).

Figure 7.120: Examples of PE conductor resistance measurement result

Measurement results / sub-results

Rpe PE conductor resistance

187
MI 3155 EurotestXD Test and measurements

7.36 Illumination

Figure 7.121: Illumination measurement menu

Measurement parameters / limits

Limit(E) Minimum illumination [Off, Custom, 0.1 lux ... 20 klux]

Probe positioning

Figure 7.122: LUXmeter probe positioning

Measurement procedure

 Enter the Illumination function.


 Set test parameters / limits.
 Connect illumination sensor A 1172 or A 1173 to the instrument.
 Take the position of LUXmeter probe, see Figure 7.122.
Make sure that LUXmeter probe is turned on.
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

188
MI 3155 EurotestXD Test and measurements

Figure 7.123: Examples of Illumination measurement result

Measurement results / sub-results

E Illumination

7.37 Discharging time

Figure 7.124: Discharging time measurement menu

Measurement parameters / limits

Limit U Voltage limit [34 V, 60 V, 120 V]


Limit (t) Time limit [1 s, 5 s]

Measuring principle

The measuring principle of the discharging time function is as following:

Step 1: The DUT is connected to supply voltage via an external socket.


The instrument monitors the voltage (on supply or internal connections) and
internally stores the peak voltage, r.m.s. voltage and frequency values.
Step 2: The DUT is disconnected from the supply and the voltage at the test terminals
starts to fall. Once the rms voltage falls for 10 V the instrument starts to measure
discharging time.
Step 3: After the voltage drops below an internally calculated voltage value the timer is
stopped. The instrument re-calculates the measured time and residual voltage to
values as they would be, if the disconnection occurred at the maximum voltage
value.

189
MI 3155 EurotestXD Test and measurements

(1) peak voltage (5) moment of disconnection


(2) voltage at disconnection time (6) discharging time @ ULIM
(3) calculated voltage value (7) residual voltage @ tLIM = 1 s (5 s)
(4) Voltage limit - ULIM (34 V, 60 V or 120 V)
Figure 7.125: Discharging time measuring principle

Connection diagram

Figure 7.126: Discharging time measurement

Measurement procedure

 Enter the Discharging time function.


 Set test parameters / limits.
 Connect 3-wire test lead to the instrument and on the DUT, see Figure 7.126.
 Connect DUT to the mains supply and Switch it ON, see Figure 7.126.
 Start the measurement.
 Measurement will stop automatically when disconnecting DUT from mains supply.
 Save results (optional).

190
MI 3155 EurotestXD Test and measurements

Figure 7.127: Discharging time results

Measurement results / sub-results


t Discharging time
Ures Residual voltage
Up Peak value of supply voltage at disconnection time
U RMS voltage
Freq Frequency

191
MI 3155 EurotestXD Test and measurements

7.38 AUTO TT – Auto test sequence for TT earthing


system
Tests / measurements implemented in AUTO TT sequence

Voltage
Z line
Voltage Drop
Zs rcd
RCD Uc

Figure 7.128: AUTO TT menu

Measurement parameters / limits

I ΔN Rated RCD residual current sensitivity [10 mA, 15 mA, 30 mA, 100 mA,
300 mA, 500 mA, 1000 mA]
RCD type RCD type [AC, A, F, B, B+]
Selectivity Characteristic [G, S]
Fuse type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]
Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
I (U) 1) Rated current for U measurement (custom value)
Isc factor Isc factor [Custom, 0.20 … 3.00]
I test Test current [Standard, Low]
Limit(ΔU) Maximum voltage drop [Off, Custom, 3.0 % ... 9.0 %]
Limit Uc Conventional touch voltage limit [Custom, 12 V, 25 V, 50 V]
Ia(Ipsc (LN)) Minimum short circuit current for selected fuse or custom value
1)
Applicable if Fuse type is set to Off or Custom.

Refer to Fuse tables guide for detailed information on fuse data.

192
MI 3155 EurotestXD Test and measurements

Connection diagram

Figure 7.129: AUTO TT measurement

Measurement procedure

 Enter the AUTO TT function.


 Set test parameters / limits.
 Measure the impedance Zref at origin (optional), see chapter 7.19 Voltage Drop.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object under test, see Figure
7.129.
 Start the Auto test.
 Save results (optional).

Figure 7.130: Examples of AUTO TT measurement results

Measurement results / sub-results

Uln Voltage between phase and neutral conductors


∆U Voltage drop
Z (LN) Line impedance
Z (LPE) Loop impedance
Uc Contact voltage
Zref Reference line impedance
Ipsc (LN) Prospective short-circuit current
Ipsc (LPE) Prospective fault current

193
MI 3155 EurotestXD Test and measurements

7.39 AUTO TN (RCD) – Auto test sequence for TN earthing


system with RCD
Tests / measurements implemented in AUTO TN (RCD) sequence

Voltage
Z line
Voltage Drop
Zs rcd
Rpe rcd

Figure 7.131: AUTO TN (RCD) menu

Measurement parameters / limits

Fuse type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
I (U) 1) Rated current for U measurement (custom value)
Isc factor Isc factor [Custom, 0.20 … 3.00]
I test Test current [Standard, Low]
Limit(∆U) Maximum voltage drop [Off, Custom, 3.0 % ... 9.0 %]
Ia(Ipsc (LN), Ipsc (LPE)) Minimum short circuit current for selected fuse or custom
value
Limit (Rpe) Max. resistance [Off, Custom, 0.1  ... 20.0 ]
1)
Applicable if Fuse type is set to Off or Custom.

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagram

Figure 7.132: AUTO TN (RCD) measurement

194
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the AUTO TN (RCD) function.


 Set test parameters / limits.
 Measure the impedance Zref at origin (optional), see chapter 7.19 Voltage Drop.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object under test, see Figure
7.132.
 Start the Auto test.
 Save results (optional).

Figure 7.133: Examples of AUTO TN (RCD) measurement results

Measurement results / sub-results

Uln Voltage between phase and neutral conductors


ΔU Voltage drop
Z (LN) Line impedance
Z (LPE) Loop impedance
Rpe PE conductor resistance
Zref Reference Line impedance
Ipsc (LN) Prospective short-circuit current
Ipsc (LPE) Prospective fault current

195
MI 3155 EurotestXD Test and measurements

7.40 AUTO TN – Auto test sequence for TN earthing


system without RCD
Tests / measurements implemented in AUTO TN sequence

Voltage
Z line
Voltage Drop
Z loop
Rpe

Figure 7.134: AUTO TN menu

Measurement parameters / limits

Fuse type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
I (U) 1) Rated current for U measurement (custom value)
Limit(∆U) Maximum voltage drop [Off, Custom, 3.0 % ... 9.0 %]
Limit(Rpe) Max. resistance [Off, Custom, 0.1  ... 20.0 ]
Ia(Ipsc (LN), Ipsc (LPE)) Minimum short circuit current for selected fuse or custom
value
Isc factor Isc factor [Custom, 0.20 … 3.00]
1)
Applicable if Fuse type is set to Off or Custom.

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagram

Figure 7.135: AUTO TN measurement

196
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the AUTO TN function.


 Set test parameters / limits.
 Measure the impedance Zref at origin (optional), see chapter 7.19 Voltage Drop.
 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the object under test, see Figure
7.135.
 Start the Auto test.
 Save results (optional).

Figure 7.136: Examples of AUTO TN measurement results

Measurement results / sub-results

Uln Voltage between phase and neutral conductors


∆U Voltage drop
Z (LN) Line impedance
Z (LPE) Loop impedance
Rpe PE conductor resistance
Zref Reference Line impedance
Ipsc (LN) Prospective short-circuit current
Ipsc (LPE) Prospective fault current

197
MI 3155 EurotestXD Test and measurements

7.41 AUTO IT – Auto test sequence for IT earthing system


Tests / measurements implemented in AUTO IT sequence

Voltage
Z line
Voltage Drop
ISFL
IMD

Figure 7.137: AUTO IT menu

Measurement parameters / limits

Fuse type Selection of fuse type [Off, Custom, gG, NV, B, C, D, K, Z, L, U]


Fuse I Rated current of selected fuse
Fuse t Maximum breaking time of selected fuse
I (U) 1) Rated current for U measurement (custom value)
Test Test mode [MANUAL R, MANUAL I, AUTO R, AUTO I]
t step Timer (AUTO R and AUTO I test modes) [1 s … 99 s]
Isc factor Isc factor [Custom, 0.20 … 3.00]
Limit(∆U) Maximum voltage drop [Off, Custom, 3.0 % ... 9.0 %]
Rmin(R1,R2) Min. insulation resistance [Off, 5 k … 640 k],
Imax(I1,I2) Max. fault current [Off, 0.1 mA ... 19.9 mA]
Imax(Isc1,Isc2) Maximum first fault leakage current [Off, Custom, 3.0 mA ... 19.5 mA]
Ia(Ipsc (LN)) Minimum short circuit current for selected fuse or custom value
1)
Applicable if Fuse type is set to Off or Custom.

Refer to Fuse tables guide for detailed information on fuse data.

Connection diagram

Figure 7.138: AUTO IT measurement

198
MI 3155 EurotestXD Test and measurements

Measurement procedure

 Enter the AUTO IT function.


 Set test parameters / limits.
 Measure the impedance Zref at origin (optional), see chapter 7.19 Voltage Drop.
 Connect test cable to the instrument.
 Connect 3-wire test lead to the object under test, see Figure 7.138.
 Start the Auto test.
 Save results (optional).

Figure 7.139: Examples of AUTO IT measurement results

Measurement results / sub-results

Uln Voltage between phases L1 and L2


ΔU Voltage drop
Isc1 First fault leakage current at single fault between L1/PE
Isc2 First fault leakage current at single fault between L2/PE
R1 Threshold insulation resistance between L1-PE
R2 Threshold insulation resistance between L2-PE
I1 Calculated first fault leakage current for R1
I2 Calculated first fault leakage current for R2
Z (LN) Line impedance
Zref Reference Line impedance
Ipsc (LN) Prospective short-circuit current

199
MI 3155 EurotestXD Test and measurements

7.42 Locator
This function is intended for tracing mains installation, like:
 Tracing lines,
 Finding shorts, breaks in lines,
 Detecting fuses.

The instrument generates test signals that can be traced with the handheld tracer receiver
R10K. See Appendix C – Locator receiver R10K for additional information.

Figure 7.140: Locator main screen

Typical applications for tracing electrical installation

Figure 7.141: Tracing wires under walls and in cabinets

Figure 7.142: Locating individual fuses

200
MI 3155 EurotestXD Test and measurements

Line tracing procedure

 Select Locator function in Other menu.


 Connect test cable to the instrument.
 Connect 3-wire test lead or Plug commander to the tested object (see Figure
7.141 and Figure 7.142).

 Press the key.


 Trace lines with receiver (in IND mode) or receiver plus its optional accessory.

 To stop tracing press the key again.

Figure 7.143: Locator active

201
MI 3155 EurotestXD Test and measurements

7.43 Visual and Functional inspections

Figure 7.144: Examples of Visual / Functional inspection menu

Inspection

Figure 7.145: Visual / Functional inspection test circuit

Visual / Functional inspection procedure

 Select the appropriate inspection test from Visual or Function menu.


 Start the inspection.
 Perform the inspection of the item under test.
 Apply appropriate ticker(s) to items of inspection.
 End inspection.
 Save results (optional).

Figure 7.146: Examples of Visual / Functional inspection results

202
MI 3155 EurotestXD Test and measurements

7.44 Measurements using adapter MD 9273


Clamp MD 9273 can be used as an adapter connected via Bluetooth® communication with
EurotestXD in manner to expand it Power quality Test range. Supported test measurements
and signal recordings are:
• P – Power CLAMP
• U – Voltage CLAMP
• I – Current CLAMP
• Imax – Inrush CLAMP
• hn – Harmonics U CLAMP
• hn – Harmonics I – CLAMP

Required test is selected from the CLAMP section of the Single Tests menu, see Figure 7.147
below. Menu is available only when Adapter MD 9273 is set, see chapters 4.6.8 Settings and
9.3 Communication with adapters for details.

Figure 7.147: CLAMP single test selection menu

Selected test is configured from EurotestXD. Adapter MD 9273 acquires test signals, process
measurements and send results to the EurotestXD. Results are presented on the instrument
screen and can be saved to the Workspace memory for later use.

7.44.1 Power CLAMP

Figure 7.148: Power CLAMP menu

Measurement parameters
There are no parameters to be set.

Connection diagram

203
MI 3155 EurotestXD Test and measurements

Figure 7.149: Power CLAMP connection

Measurement procedure
 Connect MD 9273 to the item to be tested and set Bluetooth® mode.
 Enter the Power CLAMP function and wait for active Bluetooth® communication sign.
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

Figure 7.150: Power CLAMP results

Measurement results / sub-results


P Active power
S Apparent power
Q Reactive power (capacitive or inductive)
PF Power factor (capacitive or inductive)
Φ Phase displacement between voltage and current in degrees

Note:
Voltage test terminals connection and current flow toward load should be taken into account;
the red voltage terminal should be connected to the Line terminal and the jaw should be
correctly oriented, to obtain positive sign of Power test result. If Power test result has negative
sign, connection of voltage terminal or jaw orientation are opposite and the result of phase
displacement angle has opposite sign too. Consequently, load character determination
(capacitive or inductive) is mismatched.

204
MI 3155 EurotestXD Test and measurements

7.44.2 Voltage CLAMP

Figure 7.151: Voltage CLAMP menu

Measurement parameters
h Harmonic setup [1 to 19, 1st is fundamental frequency]

Connection diagram

Figure 7.152: Voltage CLAMP connection

Measurement procedure
 Connect MD 9273 to the item to be tested and set Bluetooth® mode.
 Enter the Voltage CLAMP function and wait for active Bluetooth® communication sign.
 Set test parameter.
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

Figure 7.153: Voltage CLAMP results

205
MI 3155 EurotestXD Test and measurements

Measurement results / sub-results


Uac Effective ac voltage value – last obtained result
Uac min Minimum effective ac voltage value during measurement time duration
Uac max Maximum effective ac voltage value during measurement time duration
Udc DC voltage value
THDu [V] Effective voltage value of all harmonics (without voltage value at fundamental
frequency)
THDu [%] Total harmonic distortion
Uh Effective voltage value of set harmonic
CFu Voltage Crest factor – peak voltage to effective ac voltage ratio
Freq Fundamental frequency

7.44.3 Current CLAMP

Figure 7.154: Current CLAMP menu

Measurement parameters
h Harmonic setup [1 to 19, 1st is fundamental frequency]

Connection diagram

Figure 7.155: Current CLAMP connection

Measurement procedure
 Connect MD 9273 to the item to be tested and set Bluetooth® mode.
 Enter the Current CLAMP function and wait for active Bluetooth® communication sign.
 Set test parameter.
 Start the continuous measurement.
 Stop the measurement.

206
MI 3155 EurotestXD Test and measurements

 Save results (optional).

Figure 7.156: Current CLAMP results

Measurement results / sub-results


Iac Effective ac current value – last obtained result
Iac min Minimum effective ac current value during measurement time duration
Iac max Maximum effective ac current value during measurement time duration
THDi [A] Effective current value of all harmonics (without current value at fundamental
frequency)
THDi [%] Total harmonic distortion
Ih Effective current value of set harmonic
CFi Current Crest factor – peak current to effective current ratio
Freq Fundamental frequency

7.44.4 Inrush CLAMP


Inrush CLAMP function records current and voltage transients that occur when load is turned
on. Recorded values are presented on the screen of the instrument in separate charts. Two
event triggers can be set, Voltage dip or Inrush current. Only one trigger can be active at the
same time; when one is set, the other is switched off automatically. Voltage dip trigger is
effective only if MD 9273 Voltage input is connected to supply circuit. Minimum effective circuit
voltage is calculated during recorded transient and compared with set voltage threshold. Inrush
current trigger is effective only if the wire with flowing current is embraced with MD 9273 jaws.
Maximum effective ac circuit current is calculated during recorded transient and compared with
set Inrush threshold.
After Inrush Test is started, MD 9273 starts to record signals and waits for trigger event to
occur, which is symbolised with sign on the bottom right of the screen. Displayed chart is
divided in Pre-trigger area, presenting first second of total set chart duration time and transient
event area – rest of the chart duration time.
Trigger event occur automatically, when one of the recorder signals achieve set threshold level
or can be initiated manually by tapping on the icon within command menu on the right of the
screen, see right screen picture of the figure below.

207
MI 3155 EurotestXD Test and measurements

Figure 7.157: Inrush CLAMP menu – setup on the left, waiting for trigger on the right

Test parameters
Inrush threshold Inrush current threshold setting [Off, 5 mA … 90 A]
Voltage threshold Voltage dip threshold setting [Off, 50 V … 500 V]
Duration Recording duration [3 s, 10 s]

Connection diagram

Figure 7.158: Inrush CLAMP connection

Test procedure
 Connect MD 9273 to the item to be tested and set Bluetooth® mode.
 Enter the Inrush CLAMP function and wait for active Bluetooth® communication sign.
 Set test parameters.
 Set charts Y value range1) within expected values (optional; could be set later, after
the test)
 Start the test.
 Initiate set threshold event or manually trigger test recording.
 Save results (optional) after test is finished and results and recorded charts are
presented on the screen.
1)
Chart range selection:
 Voltage range [100 mV/div … 100 V/div]
 Current range [10 mA/div … 200 A/div]

208
MI 3155 EurotestXD Test and measurements

Figure 7.159: Inrush CLAMP results

Test results / sub-results


I: Inrush current chart 2) range
Recorded effective ac current value at cursor position
Relative time of recorded data at cursor position
U: Circuit voltage chart 2) range
Recorded effective ac voltage value at cursor position
Relative time of recorded data at cursor position
Imax Inrush current maximum value of recorded data
Umin Circuit voltage dip minimum value of recorded data
Uac Effective ac voltage (within the measurement)
Iac Effective ac current (within the measurement)
Start Inrush test start recording time (from Master Instrument)
2)
Tap on chart area or drag graph line cursor to present chart value at chosen time. Use
left / right arrow keys for smooth setting.

7.44.5 Harmonics U CLAMP


Harmonics (1 through to 19) are measured and displayed in the chart as an absolute magnitude
of the signal or as a percentage of the signal value at the fundamental frequency (the 1st
harmonic h1). Absolute magnitude or percent value display is chosen by Type parameter
setting.

Figure 7.160: Harmonics U CLAMP menu

Measurement parameters
Type [%, V]
% – harmonics and distortion are displayed as relative value
V – harmonics and distortion are displayed as absolute value

Connection diagram

209
MI 3155 EurotestXD Test and measurements

Figure 7.161: Harmonics U CLAMP connection

Measurement procedure
 Connect MD 9273 to the item to be tested and set Bluetooth® mode.
 Enter the Harmonics U CLAMP function and wait for active Bluetooth®
communication.
 Set Type parameter.
 Set charts Y value range3) within expected values (optional; could be set later, after
the test).
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).
3)
Chart Voltage range selection: [100 mV/div … 100 V/div]

Figure 7.162: Harmonics U CLAMP results

Measurement results / sub-results


U: Harmonics chart range
Uac Effective ac voltage value
THDu [%] Total harmonic distortion
THDu [V] Effective voltage value of all harmonics (without voltage value at fundamental
frequency)
U:h5 [%] Relative value of 5th harmonic 4)
U:h5 [V] Absolute voltage of 5th harmonic 4)
4)
Tap on chart area at chosen harmonic to present its value.

210
MI 3155 EurotestXD Test and measurements

7.44.6 Harmonics I CLAMP


Harmonics (1 through to 19) are measured and displayed in the chart as an absolute magnitude
of the signal or as a percentage of the signal value at the fundamental frequency (the 1st
harmonic h1). Absolute magnitude or percent value display is chosen by Type parameter
setting.

Figure 7.163: Harmonics I CLAMP menu

Measurement parameters
Type [%, A]
% – harmonics and distortion are displayed as relative value
A – harmonics and distortion are displayed as absolute value

Connection diagram

Figure 7.164: Harmonics I CLAMP connection

Measurement procedure
 Connect MD 9273 to the item to be tested and set Bluetooth® mode.
 Enter the Harmonics I CLAMP function and wait for active Bluetooth® communication.
 Set Type parameter.
 Set charts Y value range within expected values (optional; could be set later, after the
test).
 Start the continuous measurement.
 Stop the measurement.
 Save results (optional).

211
MI 3155 EurotestXD Test and measurements

Figure 7.165: Harmonics I CLAMP results

Measurement results / sub-results


I Harmonics chart
Iac Effective ac current value
THDi [%] Total harmonic distortion
THDi [A] Effective current value of all harmonics (without current value at fundamental
frequency)
I:h3 [%] Relative value of 3rd harmonic 5)
I:h3 [A] Absolute current value of 3rd harmonic 5)
5)
Tap on chart area at chosen harmonic to present its value.

212
MI 3155 EurotestXD Auto Sequences

8 Auto Sequences®
Pre-programmed sequences of measurements can be carried out in Auto Sequences® menu.
The sequence of measurements, their parameters and flow of the sequence can be
programmed. The results of an Auto sequence® can be stored in the memory together with all
related information.
Auto Sequences® can be pre-programmed on PC with the Metrel ES Manager software and
uploaded to the instrument. Refer to chapter Appendix F Programming of Auto Sequences
on Metrel ES Manager for detailed information on programming Auto Sequences.

On the instrument parameters and limits of individual single test in the Auto Sequence® can be
changed / set.

8.1 Selection of Auto Sequences®


The Auto Sequence® list from Auto Sequence® groups menu should be selected first. Refer to
chapter 4.9 Auto Sequence® groups for more details.

8.1.1 Selecting an active Auto Sequence® group in Auto


Sequences® menu
Auto Sequences® and Auto Sequence® group menus are interconnected so an active Auto
Sequence® group can be selected also in the Auto Sequences® menu.

Procedure

 Tap on the active Auto Sequence® group


header in Auto Sequences® Menu.

 Opens a list of Auto Sequence® groups


in Control panel.

 Selects desired Auto Sequence® group


from a list of groups.

 Confirms a new selection.

213
MI 3155 EurotestXD Auto Sequences

 New Auto Sequence® group is selected


and all Auto Sequences® within that
group are displayed on the screen.

8.1.2 Searching in Auto Sequences® menu


In Auto Sequence® menu it is possible to search for Auto Sequences® on base of their Name
or Short code.

Procedure

 Search function is available from the


active Auto Sequence® group header
line.

 Select Search in control panel to open


Search setup menu.

 The parameters that can be searched


for are displayed in the Search setup
menu.

a The parameters that can be searched


for are displayed in the Search setup
menu.
The search can be narrowed by
entering a text in the Name and Short
code fields.

214
MI 3155 EurotestXD Auto Sequences

Strings can be entered by using the


on-screen keyboard.

b Clears all filters. Sets filters to default


value.

 Searches through the active Auto


Sequence® group according to the set
filters.
The results are shown in the Search
results screen presented on Figure
8.1.

Figure 8.1: Search results screen (left), Auto Sequence selected (right)

Options

Next page.

Previous page.

Goes to location in Auto Sequences® menu.

Goes to Auto Sequence® view menu.

Starts the selected Auto Sequence®.

Note:
 Search result page consist of up to 50 results.

215
MI 3155 EurotestXD Auto Sequences

8.1.3 Organization of Auto Sequences® in Auto Sequences®


menu
The Auto Sequences® to be carried out can be selected from the Main Auto Sequences®
menu. This menu can be organized in a structural manner with folders, sub-folders and Auto
Sequences®. Auto Sequence® in the structure can be the original Auto Sequence® or a
shortcut to the original Auto Sequence®.
Auto Sequences® marked as shortcuts and the original auto Sequences® are coupled.
Changing of parameters or limits in any of the coupled Auto Sequences® will influence on the
original Auto Sequence® and all its shortcuts.

Figure 8.2: Examples of organized Auto Sequences® in main Auto Sequences® menu

Options

The original Auto Sequence®.

A shortcut to the original Auto Sequence®.

Enters menu for more detail view of selected Auto sequence®.


This option should also be used if the parameters / limits of the
selected Auto Sequence® have to be changed. Refer to chapter
8.2.1 Auto Sequence® view menu for more information.

Starts the selected Auto Sequence®.


The instrument immediately starts the Auto sequence®.

Searches within the Auto Sequences® menu. Refer to chapter


8.1.2 Searching in Auto Sequences® menu for more
information.

8.2 Organization of an Auto Sequence®


An Auto Sequence® is divided into three phases:
 Before starting the first test the Auto Sequence® view menu is shown (unless it was
started directly from the Main Auto Sequences® menu). Parameters and limits of
individual measurements can be set in this menu.

216
MI 3155 EurotestXD Auto Sequences

 During the execution phase of an Auto Sequence®, pre-programmed single tests are
carried out. The sequence of single tests is controlled by pre-programmed flow
commands.
 After the test sequence is finished the Auto Sequence® result menu is shown. Details of
individual tests can be viewed and the results can be saved to Memory organizer.

8.2.1 Auto Sequence® view menu


In the Auto Sequence® view menu, the header and the single tests of selected Auto
Sequence® are displayed. The header contains Name, Short code and description of the Auto
Sequence®. Before starting the Auto Sequence®, test parameters / limits of individual
measurements can be changed.

Note:
 Once fuse and RCD parameters are changed in active Auto Sequence®, the new
settings are distributed through all single tests within the active Auto Sequence® and
stored for next use of the same Auto Sequence®.

8.2.1.1 Auto Sequence® view menu (Header is selected)

Figure 8.3: Screen organization in Auto Sequence® view menu – Header selected

Legend
1 Short code
2 Auto Sequence® name
3 Header
4 Single tests
5 Description
6 Control panel (available options)

Option

Starts the Auto Sequence®.

217
MI 3155 EurotestXD Auto Sequences

8.2.1.2 Auto Sequence® view menu (measurement is selected)

Figure 8.4: Screen organization in Auto Sequence® view menu – measurement selected

Legend
1 Auto Sequence® name
2 Header
3 Single tests
4 Parameters / limits of selected single test
5 Control panel (available options)

Options
Selects single test.

Opens menu for changing parameters and


limits of selected measurements.

Refer to chapter 6.1.2 Setting parameters,


limits and comments of single tests for more
information how to change measurement
parameters and limits.

on

218
MI 3155 EurotestXD Auto Sequences

User must decide whether the changes in


global parameter(s) apply to all single tests
within the selected Auto Sequence® containing
the modified parameter(s), or only for the
edited one.

Starts the Auto Sequence®.

Opens help screens. Refer to chapter 6.1.8


Help screens for more information.

8.2.1.3 Indication of Loops

The attached ‘x3’ at the end of a single test name indicates that a loop of single tests is
programmed. This means that the marked single test will be carried out as many times as the
number behind the ‘x’ indicates. It is possible to exit the loop before, at the end of each
individual measurement.

8.2.2 Step by step execution of Auto Sequences®


While the Auto Sequence® is running, it is controlled by pre-programmed flow commands.
Examples of actions controlled by flow commands are:
▪ pauses during the Auto Sequence®,
▪ buzzer/ PASS/FAIL sound after the tests,
▪ proceeding of test sequence in regard to measured results,
▪ etc.
The actual list of flow commands is available on chapter F.7 – Description of flow commands.

Figure 8.5: Auto Sequence® – Example of a pause with message

219
MI 3155 EurotestXD Auto Sequences

Figure 8.6: Auto Sequence® – Example of a finished measurement with options for
proceeding

Options (during execution of an Auto Sequence®):

Proceeds to the next step in the test sequence.

Repeats the measurement.


Displayed result of a single test will not be stored.

Ends the Auto Sequence® and goes to Auto Sequence® result screen.
Refer to chapter 8.2.3 Auto Sequence® result screen for more information.

Exits the loop of single tests and proceeds to the next step in the Auto Sequence®.

The offered options in the control panel depend on the selected single test, its result and the
programmed test flow.

Notes:
 During Auto Sequences® the popup Warning messages are displayed only before the
single test inside one Auto Sequence®. This default setting can be changed with
appropriate flow command. For more information about programming Auto Sequences®
refer to chapter Appendix F – Programming of Auto Sequences on Metrel ES
Manager.

220
MI 3155 EurotestXD Auto Sequences

8.2.3 Auto Sequence® result screen


After the Auto Sequence® is finished the Auto Sequence® result screen is displayed.
On the left side of the display the single tests and their statuses in the Auto Sequence® are
shown.
In the middle of the display the header of the Auto Sequence® with Short code and description
of the Auto Sequence® is displayed. At the top the overall Auto Sequence® result status is
displayed. Refer to chapter 5.1.1 Measurement statuses for more information.

Figure 8.7: Auto Sequence® result screen

Legend
1 Overall PASS / FAIL status
2 Short code
3 Auto Sequence® name
4 Single tests with individual PASS / FAIL statuses
5 Description
6 Control panel (available options)

Options

Starts a new Auto Sequence®.

View results of individual measurements.


The instrument goes to the menu for viewing details of the Auto
Sequence®.

Saves the Auto Sequence® results.


A new Auto Sequence® was selected and started from a Structure
object in the structure tree:
▪ The Auto Sequence® result will be saved under the selected
Structure object.

221
MI 3155 EurotestXD Auto Sequences

A new Auto Sequence® was started from the Auto Sequence® main
menu:
▪ Saving under the last selected Structure object will be offered by
default. The user can select another Structure object or create a

new Structure object. By pressing in Memory organizer


menu the Auto Sequence result is saved under selected location.
An empty measurement was selected in structure tree and started:
▪ The result(s) will be added to the Auto Sequence®. The Auto
Sequence® will change its overall status from ‘empty’ to
‘finished’.
An already carried out Auto Sequence® was selected in structure tree,
viewed and then restarted:
▪ A new Auto Sequence result will be saved under the selected
Structure object.

Adds comment to the Auto Sequence®. The instrument opens keypad


for entering a comment.

Options (menu for viewing details of Auto Sequence® and single test results)

Details of a selected single test in Auto Sequence® are displayed.

View parameters and limits of selected single test.

Adds comment to the selected single test in Auto Sequence®. The instrument opens
keypad for entering a comment.

Figure 8.8: Details of menu for viewing details of Auto Sequence® results

8.2.4 Auto Sequence® memory screen


In Auto Sequence® memory screen details of the Auto Sequence® results can be viewed and a
new Auto Sequence® can be restarted.

222
MI 3155 EurotestXD Auto Sequences

Figure 8.9: Auto Sequence® memory screen

Options

Retest the Auto Sequence®.


Enters menu for a new Auto Sequence®.

Enters menu for viewing details of the Auto Sequence®. Refer to chapter 8.2.3 Auto
Sequence® result screen for more information.

223
MI 3155 EurotestXD Communication

9 Communication
The instrument can communicate with the Metrel ES Manager PC software and aMESM
android application. The following action is supported:
 Saved results and Tree structure from Memory organizer can be downloaded and stored
to a PC or android device.
 Tree structure from Metrel ES Manager PC software or aMESM android aplication can
be uploaded to the instrument.
 Custom Auto Sequences® can be uploaded to the instrument or downloaded and stored
to a PC.
Metrel ES Manager is a PC software running on Windows 8.1, Windows 10 and Windows 11.
There are three communication interfaces available on the instrument:
 RS-232
 USB
 Bluetooth.
Instrument can also communicate to various external devices (test adapters, scanners …).

9.1 USB and RS232 communication


The instrument automatically selects the communication mode according to detected interface.
USB interface has priority.

Figure 9.1: Interface connection for data transfer over PC COM port

How to establish an USB or RS-232 link

 RS-232 communication: connect a PC COM port to the instrument PS/2 connector


using the PS/2 - RS232 serial communication cable;
 USB communication: connect a PC USB port to the instrument USB connector using
the USB interface cable.
 Switch on the PC and the instrument.
 Run the Metrel ES Manager software.
 Select communication port (COM port for USB communication is identified as
‘Measurement Instrument USB VCom Port’.
 The instrument is prepared to communicate with the PC.

9.2 Bluetooth communication with Android devices


The internal Bluetooth module enables easy communication via Bluetooth with Android devices.

How to configure a Bluetooth link between instrument and an Android device

 Switch on the instrument.


 Some Android applications automatically carry out the setup of a Bluetooth connection.
It is preferred to use this option if it exists. This option is supported by Metrel's Android
applications.

224
MI 3155 EurotestXD Communication

If this option is not supported by the selected Android application, then configure a
Bluetooth link via Android device’s Bluetooth configuration tool. Usually, no code for
pairing the devices is needed.
 The instrument and Android device are ready to communicate.

Notes
 Sometimes there will be a demand from the Android device to enter the code. Enter
code ‘1234’ to correctly configure the Bluetooth link.
 The name of correctly configured Bluetooth device must consist of the instrument type
plus serial number, e.g. MI 3155-12240429I. If the Bluetooth module got another name,
the configuration must be repeated.
 In case of serious troubles with the Bluetooth communication it is possible to reinitialize
the internal Bluetooth module. The initialization is carried out during the Initial settings
procedure. In case of a successful initialization “INITIALIZING… OK!” is displayed at the
end of the procedure. See chapter 4.6.11 Initial Settings.
 Metrel android application aMESM is available for download from Google play store:

9.3 Communication with adapters


EurotestXD can communicate with Metrel test and measurement adapters through wired RS232
port or wireless Bluetooth communication port.
Adapter can be selected from the list of adapters from General Settings / Settings / Adapters
section menu, see Figure 9.2 below.

Figure 9.2: Adapters section menu

When adapter is selected from the list, supported communication port is automatically offered.
To establish Bluetooth communication, adapter must be paired with EurotectXD.

Procedure:
1. Adapter: switch it ON and select BT mode, if not already automatically selected.
2. EurotestXD: Open General Settings / Settings menu and navigate to the Adapters
section.
3. Adapter type: select adapter by using left / right arrows or tap on the field and select it

225
MI 3155 EurotestXD Communication

from the list of adapters


4. Port: Bluetooth or RS232, which one is supported by the adapter, is automatically
offered. Connect serial cable or proceed with pairing procedure
5. Bluetooth device name: select field and instrument start searching for Bluetooth
devices; when finished, list of available devices is presented on the screen
6. Select Adapter name from the list: pairing procedure is finished.

When test supported by the adapter is selected on EurotestXD, active BT communication is


indicated with sign on the right – top of the screen.

Note:
Pairing between same Metrel adapter and same EurotestXD is necessary only when adapter is
first time used. If communication is not established when supported test is selected, adapter is
probably switched OFF or Bluetooth link is out of range.

9.4 Bluetooth and RS-232 communication with scanners


EurotestXD instrument can communicate with supported Bluetooth and serial scanners. Serial
scanner should be connected to the instrument via PS/2 serial port. Contact Metrel or your
distributor which external devices and functionalities are supported. See chapter 4.6.9 Devices
for details how to set the external Bluetooth or serial device.

226
MI 3155 EurotestXD Upgrading the instrument

10 Upgrading the instrument


The instrument can be upgraded from a PC via the RS232 or USB communication port. This
enables to keep the instrument up to date even if the standards or regulations change. The
firmware upgrade requires internet access and can be carried out from the Metrel ES Manager
software with a help of special upgrading software – FlashMe which will guide you through the
upgrading procedure. For more information refer to Metrel ES Manager Help file.

227
MI 3155 EurotestXD Maintenance

11 Maintenance
Unauthorized persons are not allowed to open the EurotestXD instrument. There are no user
replaceable components inside the instrument, except the battery and fuses under back cover.

Figure 11.1: Position of screws to open battery / fuse compartment

11.1 Fuse replacement


There are three fuses under back cover of the EurotestXD instrument.

F1 M 0.315 A / 250 V, 205 mm


This fuse protects internal circuitry for continuity functions if test probes are connected
to the mains supply voltage by mistake during measurement.
F2, F3 F 5 A / 500 V, 326.3 mm (breaking capacity: 50 kA)
General input protection fuses of test terminals L/L1 and N/L2.

228
MI 3155 EurotestXD Maintenance

Figure 11.2: Fuses

Warnings:
 Disconnect all measuring accessory and switch off the instrument before opening battery
/ fuse compartment cover, hazardous voltage inside!
 Replace blown fuse with original type only, otherwise the instrument or accessory may
be damaged and / or operator’s safety impaired!

11.2 Battery pack insertion / replacement


Procedure:

 Remove the battery pack from battery


compartment.

 Remove foam if were inserted under the


battery pack.

 Press to unlock the connector (1) and pull the


wires (2) to disconnect the battery pack from
the instrument.

 Connect the new battery pack to the


instrument.

 For standard capacity pack use a foam (2) to


fill empty space.

 Insert the battery pack in battery


compartment and close the battery / fuse
compartment cover.
Note:

229
MI 3155 EurotestXD Maintenance

When placing high-capacity battery pack


make sure that protection circuit module of
the battery pack is placed at top inner side of
the compartment.

Warnings:
 Disconnect all measuring accessory and switch off the instrument before opening battery
/ fuse compartment cover, hazardous voltage inside!
 Replace battery pack with original type only, otherwise the instrument may be damaged
and / or operator’s safety impaired!
 Ensure batteries are used and disposed of in accordance with Manufacturers guidelines
and in accordance with Local and National Authority guidelines.

11.3 Cleaning
No special maintenance is required for the housing. To clean the surface of the instrument or
accessory use a soft cloth slightly moistened with soapy water or alcohol. Then leave the
instrument or accessory to dry totally before use.

Warnings:
 Do not use liquids based on petrol or hydrocarbons!
 Do not spill cleaning liquid over the instrument!

11.4 Periodic calibration


It is essential that the test instrument is regularly calibrated in order that the technical
specification listed in this manual is guaranteed. We recommend an annual calibration. Only an
authorized technical person can do the calibration. Please contact your dealer for further
information.

11.5 Service
For repairs under warranty, or at any other time, please contact your distributor.

230
MI 3155 EurotestXD Technical specifications

12 Technical specifications
12.1 R iso, R iso all – Insulation resistance
Uiso: 50 V, 100 V and 250 V (R iso, R iso all)
Riso – Insulation resistance (R iso)
R L-N, R L-PE, R N-PE – Insulation resistance (R iso all)
Measuring range according to EN 61557 is 0.15 M … 199.9 M.
Measuring range (M) Resolution (M) Accuracy
0.00 ... 19.99 0.01 (5 % of reading + 3 digits)
20.0 ... 99.9 (10 % of reading)
0.1
100.0 ... 199.9 (20 % of reading)

Uiso: 500 V (R iso, R iso all)


Riso – Insulation resistance (R iso)
R L-N, R L-PE, R N-PE – Insulation resistance (R iso all)
Measuring range according to EN 61557 is 0.15 M … 999 M.
Measuring range (M) Resolution (M) Accuracy
0.00 ... 19.99 0.01 (5 % of reading + 3 digits)
20.0 ... 199.9 0.1 (5 % of reading)
200 ... 999 1 (10 % of reading)

Uiso: 1000 V (R iso, R iso all)


Riso – Insulation resistance (R iso)
R L-N, R L-PE, R N-PE – Insulation resistance (R iso all)
Measuring range according to EN 61557 is 0.15 M … 199.9 M.
Measuring range (M) Resolution (M) Accuracy
0.00 ... 19.99 0.01 (5 % of reading + 3 digits)
20.0 ... 199.9 0.1 (5 % of reading)
200 ... 999 1 indicative

Uiso: 2500V (R iso)


Riso – Insulation resistance
Measuring range () Resolution () Accuracy
0.00 M ... 19.99 M 0.01 M (5 % of reading + 3 digits)
20.0 M ... 199.9 M 0.1 M (5 % of reading)
200 M ... 999 M 1M (10 % of reading)
1.00 G ... 19.99 G 0.01 G (10 % of reading)

Um – Voltage (Riso, Riso all)


Measuring range (V) Resolution (V) Accuracy
0 ... 2700 1 (3 % of reading + 3 digits)

Nominal voltages Uiso ............................50 VDC, 100 VDC, 250 VDC, 500 VDC, 1000 VDC,
2500 VDC
Open circuit voltage ................................-0 % / +20 % of nominal voltage
Measuring current...................................min. 1 mA at RN = UN  1 k/V
Short circuit current ............................... max. 3 mA
Load pretest voltage .............................. < 20 VAC, 125 Hz
Load pretest warning ............................. < 50 k
The number of possible tests

231
MI 3155 EurotestXD Technical specifications

(R iso, Riso all) ...................................... up to 1000, with a fully charged battery (type:
18650T22A2S2P)
up to 2000, with a fully charged battery (type:
18650T22A2S4P)

Auto discharge after test.

Specified accuracy is valid if 3-wire test lead is used while it is valid up to 100 M if Tip
commander is used.
Specified accuracy is valid up to 100 M if relative humidity is > 85 %.
In case the instrument gets moistened, the results could be impaired. In such case, it is
recommended to dry the instrument and accessories for at least 24 hours.
The error in operating conditions could be at most the error for reference conditions (specified in
the manual for each function) 5 % of measured value.

12.2 Diagnostic test


Uiso: 500V, 1000 V, 2500 V

DAR – Dielectric absorption ratio


Measuring range Resolution Accuracy
0.01 ... 9.99 0.01 (5 % of reading + 2 digits)
10.0 ... 100.0 0.1 (5 % of reading)

PI – Polarization index
Measuring range Resolution Accuracy
0.01 ... 9.99 0.01 (5 % of reading + 2 digits)
10.0 ... 100.0 0.1 (5 % of reading)

For Riso, R60 and Um sub-results technical specifications defined in chapter 12.1 R iso, R iso
all – Insulation resistance apply.

12.3 R low – Resistance of earth connection and


equipotential bonding
Measuring range according to EN 61557 is 0.12  ... 1999 .

R – Resistance
Measuring range () Resolution () Accuracy
0.00 ... 19.99 0.01 (3 % of reading + 3 digits)
20.0 ... 199.9 0.1
(5 % of reading)
200 ... 1999 1

R+, R – Resistance
Measuring range () Resolution () Accuracy
0.0 ... 199.9 0.1
(5 % of reading + 5 digits)
200 ... 1999 1

Open-circuit voltage ................................6.5 VDC ... 18 VDC


Measuring current...................................min. 200 mA into load resistance of 2 
Test lead compensation (Rlow) ..............up to 5 
The number of possible tests:

232
MI 3155 EurotestXD Technical specifications

(Rlow (Current = standard), Rlow 4W) ....up to 1700, with a fully charged battery (type:
18650T22A2S2P)
up to 3400, with a fully charged battery (type:
18650T22A2S4P)
Rlow (Current = ramp) ............................up to 1000, with a fully charged battery (type:
18650T22A2S2P)
up to 2000, with a fully charged battery (type:
18650T22A2S4P)

Automatic polarity reversal of the test voltage.

12.4 R low 4W – Resistance of earth connection and


equipotential bonding
Measuring range according to EN 61557 is 0.100  ... 1999 .
R – Resistance
Measuring range () Resolution () Accuracy
0.000 ... 0.049 0.001 (30 digits)
0.050 ... 19.999 0.001 (3 % of reading + 10 digits)
20.00 ... 199.99 0.01
(5 % of reading)
200.0 ... 1999.9 0.1

R+, R – Resistance
Measuring range () Resolution () Accuracy
0.00 ... 19.99 0.01
20.0 ... 199.9 0.1 (5 % of reading + 5 digits)
200 ... 1999 1

Open-circuit voltage ................................6.5 VDC ... 18 VDC


Measuring current...................................min. 200 mA into load resistance of 2 
The number of possible tests: ................up to 1700, with a fully charged battery (type:
18650T22A2S2P)
up to 3400, with a fully charged battery (type:
18650T22A2S4P)
Automatic polarity reversal of the test voltage.

12.5 Continuity – Continuous resistance measurement


with low current
R – Continuity resistance
Measuring range () Resolution () Accuracy
0.0 ... 19.9 0.1
(5 % of reading + 3 digits)
20 ... 1999 1

Open-circuit voltage ................................6.5 VDC ... 18 VDC


Short-circuit current ................................max. 8.5 mA
Test lead compensation..........................up to 5 

233
MI 3155 EurotestXD Technical specifications

12.6 RCD testing


12.6.1 General data
Nominal residual current (A,AC) .............10 mA, 15 mA, 30 mA, 100 mA, 300 mA, 500 mA,
1000 mA
Nominal residual current accuracy ..........-0 / +0.1I; I = IN, 2IN, 5IN
-0.1I / +0; I = 0.5IN
AS/NZS 3017 selected: ± 5 %

Sensitivity parameter supported .............PRCD, PRCD-3p, PRCD-2p, PRCD-S+, PRCD-K

Nominal residual current accuracy by using parameter Sensitivity:


Sensitivity: standard................................-0 / +0.1I; I = IN, 2IN, 5IN
-0.1I / +0; I = 0.5IN
Sensitivity: Ipe monitoring .......................-0 / +0.1I; I = 0.5IN, 20.5IN, 50.5IN
-0.1I / +0; I = 0.50.5IN

AS/NZS 3017 selected: ± 5 %

Test current shape..................................Sine-wave (AC), pulsed (A, F), smooth DC (B, B+)
DC offset for pulsed test current .............< 2 mA (typical)
RCD type ................................................(non-delayed), S (time-delayed), PRCD, PRCD-2p,
PRCD-3p, PRCD-S, PRCD-S+, PRCD-K, EV RCD,
EV RCM, MI RCD
Test current starting polarity ...................0º or 180º
Voltage range .........................................93 V ... 134 V (16 Hz … 400 Hz)
185 V ... 266 V (16 Hz … 400 Hz)

RCD test current in relation to RCD type, nominal RCD current and multiplication factor
IN × 1/2 IN × 1 IN × 2 IN × 5 RCD I
(mA) (mA) (mA) (mA)
IN (mA) AC A, F B, B+ AC A, F B, B+ AC A, F B, B+ AC A, F B, B+ AC A, F B, B+
10 5 3.5 5 10 20 20 20 40 40 50 100 100 ✓ ✓ ✓
15 7.5 5.3 7.5 15 30 30 30 60 60 75 150 150 ✓ ✓ ✓
30 15 10.5 15 30 42 60 60 84 120 150 212 300 ✓ ✓ ✓
100 50 35 50 100 141 200 200 282 400 500 707 1000 ✓ ✓ ✓
300 150 105 150 300 424 600 600 848 × 1500 × × ✓ ✓ ✓
500 250 175 250 500 707 1000 1000 1410 × 2500 × × ✓ ✓ ✓
1000 500 350 500 1000 1410 × 2000 × × × × × ✓ ✓ ×

×. ............................................................not applicable
✓.............................................................applicable
AC type...................................................sine wave test current
A, F types…… ........................................pulsed current
B, B+ types .............................................smooth DC current

RCD test current in relation to MI / EV RCD type and multiplication factor


IN × 1/2 IN × 1 IN × 2 IN × 5 IN × 10 IN × 33.33 IN × 50 RCD I
(mA) (mA) (mA) (mA) (mA) (mA) (mA)
IN MI / EV MI / EV MI / EV MI / EV MI / EV MI / EV MI / EV MI / EV MI / EV
(mA) a.c., d.c. a.c., d.c. a.c. a.c. d.c. d.c. d.c. a.c. d.c.
(IEC 62955) (IEC 62752)

234
MI 3155 EurotestXD Technical specifications

30 15 30 60 150 × × × ✓ ×
a.c.
6 3 6 × × 60 200 300 × ✓
d.c.

×. ............................................................not applicable
✓.............................................................applicable
MI / EV type (a.c. part) ............................sine wave test current
MI / EV type (d.c. part) ............................smooth DC current

12.6.2 RCD Uc – Contact voltage


Measuring range according to EN 61557 is 20.0 V ... 31.0 V for limit contact voltage 25 V
Measuring range according to EN 61557 is 20.0 V ... 62.0 V for limit contact voltage 50 V

Uc – Contact voltage, Uc(P) – Contact voltage, external probe


Measuring range (V) Resolution (V) Accuracy
0.0 ... 19.9 (-0 % / +15 %) of reading ±
0.1
10 digits
20.0 ... 99.9 0.1 (-0 % / +15 %) of reading
The accuracy is valid if mains voltage is stabile during the measurement and PE terminal is free
of interfering voltages. Specified accuracy is valid for complete operating range.

Test current ........................................... max. 0.5IN


Limit contact voltage (Uc, Uc(P)) ........... Custom, 12 V, 25 V, 50 V

12.6.3 RCD t – Trip-out time


Complete measurement range corresponds to EN 61557 requirements.
Maximum measuring times set according to selected reference for RCD testing.

t N –Trip-out time
Measuring range (ms) Resolution (ms) Accuracy
0.0 ... 40.0 0.1 1 ms
0.0 ... max. time* 0.1 3 ms
* For max. time see normative references in chapter 4.6.8.2 RCD standard. This specification
applies to max. time >40 ms.

Test current ........................................... ½IN, IN, 2IN, 5IN


5IN is not available for IN=1000 mA (RCD type AC) or IN  300 mA (RCD types A, F, B, B+).
2IN is not available for IN=1000 mA (RCD types A, F) or IN  300 mA (RCD types B, B+).
1IN is not available for IN=1000 mA (RCD types B, B+).
Specified accuracy is valid for complete operating range.

12.6.4 RCD I – Trip-out current


Complete measurement range corresponds to EN 61557 requirements.

I – Trip-out current
Measuring range Resolution I Accuracy
0.2IN ... 1.1IN
0.05IN 0.1IN
(AC type)
0.2IN ... 1.0IN 0.05IN 0.1IN

235
MI 3155 EurotestXD Technical specifications

(IEC 62752: EV RCD, EV RCM, MI RCD (a.c. part))


0.2IN_d.c. ... 1.0IN_d.c.
0.05IN_d.c. 0.1IN_d.c.
(IEC 62752: EV RCD, EV RCM, MI RCD (d.c. part))
0.2IN ... 1.0IN
0.05IN 0.1IN
(IEC 62955: EV RCD, EV RCM, MI RCD (a.c. part))
0.2IN_d.c. ... 1.0IN_d.c
0.05IN_d.c. 0.1IN_d.c.
(IEC 62955: EV RCD, EV RCM, MI RCD (d.c. part))
0.2IN ... 1.5IN
0.05IN 0.1IN
(A type, IN≥30 mA)
0.2IN ... 2.2IN
0.05IN 0.1IN
(A type, IN<30 mA)
0.2IN ... 2.2IN
0.05IN 0.1IN
(B type)

t I – Trip out-time
Measuring range (ms) Resolution (ms) Accuracy
0 ... 300 1 3 ms

Uc, Uc I – Contact voltage


Measuring range (V) Resolution (V) Accuracy
(-0 % / +15 %) of reading 
0.0 ... 19.9 0.1
10 digits
20.0 ... 99.9 0.1 (-0 % / +15 %) of reading

Limit contact voltage (Uc, Uc I) ............ Custom, 12 V, 25 V, 50 V

The accuracy is valid if mains voltage is stabile during the measurement and PE terminal is free
of interfering voltages. Specified accuracy is valid for complete operating range.
Trip-out measurement is not available for IN=1000 mA (RCD types B, B+).

12.6.5 RCD Auto


For technical specification refer to chapter 12.6 RCD testing for technical specification of
individual RCD tests.

12.7 Z loop, Z loop 4W – Fault loop impedance and


prospective fault current
Z – Fault loop impedance
Measuring range according to EN 61557 is 0.12  ... 9.99 k.
Measuring range () Resolution () Accuracy
0.00 ... 9.99 0.01
(3 % of reading + 3 digits)
10.0 ... 99.9 0.1
100 ... 999 1
 10 % of reading
1.00 k ... 9.99 k 10

Ipsc – Prospective fault current


Measuring range (A) Resolution (A) Accuracy
0.00 ... 9.99 0.01
10.0 ... 99.9 0.1 Consider accuracy of fault
100 ... 999 1 loop resistance measurement
1.00 k ... 9.99 k 10

236
MI 3155 EurotestXD Technical specifications

10.0 k ... 23.0 k 100

Ulpe – Voltage
Measuring range (V) Resolution (V) Accuracy
0 ... 550 1 (2 % of reading + 2 digits)

Uc(P) – Contact voltage at Ipsc, external probe


Measuring range (V) Resolution (V) Accuracy
(-0 % / +15 %) of reading 
0.0 ... 99.9 0.1
0.02   Ipsc

The accuracy is valid if mains voltage is stabile during the measurement.

Test current (at 230 V) ........................... 20 A (10 ms)


Nominal voltage range ............................93 V ... 134 V (16 Hz … 400 Hz)
185 V ... 266 V (16 Hz … 400 Hz)
R and XL values are indicative.

237
MI 3155 EurotestXD Technical specifications

12.8 Zs rcd – Fault loop impedance and prospective fault


current in system with RCD
Z – Fault loop impedance
Measuring range according to EN 61557 is 0.46  ... 9.99 k for I test = standard and 0.48  ...
9.99 k for I test = low.
Measuring range () Resolution () Accuracy Accuracy
I test = standard I test = low
0.00 ... 9.99 0.01 (5 % of reading + 10 (5 % of reading + 12
10.0 ... 99.9 0.1 digits) digits)
100 ... 999 1
 10 % of reading  10 % of reading
1.00 k ... 9.99 k 10
Accuracy may be impaired in case of heavy noise on mains voltage.

Ipsc – Prospective fault current


Measuring range (A) Resolution (A) Accuracy
0.00 ... 9.99 0.01
10.0 ... 99.9 0.1
Consider accuracy of fault
100 ... 999 1
loop resistance measurement
1.00 k ... 9.99 k 10
10.0 k ... 23.0 k 100

Ulpe – Voltage
Measuring range (V) Resolution (V) Accuracy
0 ... 550 1 (2 % of reading + 2 digits)

Uc(P) – Contact voltage at Ipsc (Protection = TN), external probe


Measuring range (V) Resolution (V) Accuracy
(-0 % / +15 %) of reading 
0.0 ... 99.9 0.1
0.02   Ipsc

Uc(P) – Contact voltage at IΔN (Protection = TT rcd), external probe


Measuring range (V) Resolution (V) Accuracy
(-0 % / +15 %) of reading 
0.0 ... 99.9 0.1
10 digits

Uc – Contact voltage
Refer to chapter 12.6.2 RCD Uc – Contact voltage for detailed technical specification.

Nominal voltage range ............................93 V ... 134 V (16 Hz … 400 Hz)


185 V ... 266 V (16 Hz … 400 Hz)
No trip out of RCD.
R, XL values are indicative.

12.9 Z loop m – High precision fault loop impedance and


prospective fault current
This test is performed in combination with an external test adapter / instrument.
For technical specification refer to A 1143 Euro Z 290 A, MI 3143 Euro Z 440 V and MI 3144
Euro Z 800 V Instruction manual.

238
MI 3155 EurotestXD Technical specifications

12.10U touch – Touch voltage (MI 3143 and MI 3144)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MI 3143 Euro Z 440 V and MI 3144 Euro Z 800 V
Instruction manual.

12.11 Z line, Z line 4W – Line impedance and prospective


short-circuit current
Z – Line impedance
Measuring range according to EN 61557 is 0.12  ... 9.99 k.
Measuring range () Resolution () Accuracy
0.00 ... 9.99 0.01
(3 % of reading + 3 digits)
10.0 ... 99.9 0.1
100 ... 999 1
 10 % of reading
1.00 k ... 9.99 k 10

Ipsc – prospective short-circuit current


Imax – Maximal single-phase prospective short-circuit current
Imax2p – Maximal two-phases prospective short-circuit current
Imax3p – Maximal three-phases prospective short-circuit current
Measuring range (A) Resolution (A) Accuracy
0.00 ... 0.99 0.01
1.0 ... 99.9 0.1
Consider accuracy of line
100 ... 999 1
resistance measurement
1.00 k ... 99.99 k 10
100 k ... 199 k 1000

Uln – Voltage
Measuring range (V) Resolution (V) Accuracy
0 ... 550 1 (2 % of reading + 2 digits)

Test current (at 230 V) ........................... 20 A (10 ms)


Nominal voltage range ............................93 V ... 134 V (16 Hz … 400 Hz)
185 V ... 266 V (16 Hz … 400 Hz)
321 V ... 485 V (16 Hz … 400 Hz)
R, XL, Imin, Imin2p, Imin3p values are indicative.

12.12Voltage Drop
∆U – Voltage drop
Measuring range (%) Resolution (%) Accuracy
Consider accuracy of line
0.0 ... 99.9 0.1
impedance measurement(s)*

Uln, Ipsc, Zref, Z


Refer to chapter 12.13 Z line m – High precision line impedance and prospective fault
current for technical specification.

ZREF measuring range .............................0.00 Ω ... 20.0 Ω

239
MI 3155 EurotestXD Technical specifications

Test current (at 230 V) ........................... 20 A (10 ms)


Nominal voltage range ............................93 V ... 134 V (16 Hz … 400 Hz)
185 V ... 266 V (16 Hz … 400 Hz)
321 V ... 485 V (16 Hz … 400 Hz)
*See chapter 7.19 Voltage Drop for more information about calculation of voltage drop result.

12.13 Z line m – High precision line impedance and


prospective fault current
This test is performed in combination with an external test adapter / instrument.
For technical specification refer to A 1143 Euro Z 290 A, MI 3143 Euro Z 440 V and MI 3144
Euro Z 800 V Instruction manual.

12.14 High current (MI 3143 and MI 3144)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MI 3143 Euro Z 440 V and MI 3144 Euro Z 800 V
Instruction manual.

12.15 Z auto, AUTO TT, AUTO TN, AUTO TN (RCD), AUTO


IT
Refer to following chapters for detailed technical specification:

12.6.2 RCD Uc – Contact voltage,

12.7 Z loop, Z loop 4W – Fault loop impedance and prospective fault current,

12.8 Zs rcd – Fault loop impedance and prospective fault current in system with RCD,

12.11 Z line, Z line 4W – Line impedance and prospective short-circuit current,

12.12 Voltage Drop,

12.16 Rpe – PE conductor resistance,

12.26 ISFL – First fault leakage current and

12.27 IMD.

240
MI 3155 EurotestXD Technical specifications

12.16 Rpe – PE conductor resistance


RCD: No
R – PE conductor resistance
Measuring range () Resolution () Accuracy
0.00 ... 19.99 0.01
(5 % of reading + 5 digits)
20.0 ... 99.9 0.1
100.0 ... 199.9 0.1
 10 % of reading
200 ... 1999 1

Measuring current...................................min. 200 mA into PE resistance of 2 

RCD: Yes, no trip out of RCD


R – PE conductor resistance
Measuring range () Resolution () Accuracy
0.00 ... 19.99 0.01
(5 % of reading + 10 digits)
20.0 ... 99.9 0.1
100.0 ... 199.9 0.1
 10 % of reading
200 ... 1999 1

Accuracy may be impaired in case of heavy noise on mains voltage.

Measuring current................................... < 15 mA


Nominal voltage range ............................93 V ... 134 V (16 Hz … 400 Hz)
185 V ... 266 V (16 Hz … 400 Hz)

12.17 Earth – Earth resistance (3-wire measurement)


Re – Earth resistance
Measuring range according to EN61557-5 is 0.20  ... 1999 .
Measuring range () Resolution () Accuracy
0.00 ... 19.99 0.01
20.0 ... 199.9 0.1 (5 % of reading + 5 digits)
200 ... 9999 1

Max. auxiliary earth electrode resistance RC ...........100RE or 50 k (whichever is lower)


Max. probe resistance RP .......................................100RE or 50 k (whichever is lower)
RC and RP values are indicative.

Additional probe resistance error at RCmax or RPmax. .(10 % of reading + 10 digits)

Additional error at 3 V voltage noise (50 Hz) ...........(5 % of reading + 10 digits)


Open circuit voltage ................................................< 30 VAC
Short circuit current ................................................< 30 mA
Test voltage frequency ...........................................125 Hz
Test voltage shape .................................................sine wave
Noise voltage indication threshold ..........................1 V (< 50 , worst case)

Automatic measurement of auxiliary electrode resistance and probe resistance.


Automatic measurement of voltage noise.

241
MI 3155 EurotestXD Technical specifications

12.18 Earth 2 clamp – Contactless earthing resistance


measurement (with two current clamps)
Re – Earth resistance
Measuring range () Resolution () Accuracy*)
0.00 ... 19.99 0.01 (10 % of reading + 10 digits)
20.0 ... 30.0 0.1 (20 % of reading)
30.1 ... 39.9 0.1 (30 % of reading)
*)
Distance between current clamps > 30 cm.

Additional error at 3 V voltage noise (50 Hz) ...........10 % of reading


Test voltage frequency ...........................................125 Hz
Noise current indication ..........................................yes
Low clamp current indication ..................................yes
Additional clamp error has to be considered.

12.19 Ro – Specific earth resistance


 – Specific earth resistance
Measuring range (m) Resolution (m) Accuracy
0.0 ... 99.9 0.1
100 ... 999 1
1.00 k ... 9.99 k 0.01 k See accuracy note
10.0 k ... 99.9 k 0.1 k
100 k ... 9999 k 1k

 – Specific earth resistance


Measuring range (ft) Resolution (ft) Accuracy
0.0 ... 99.9 0.1
100 ... 999 1
1.00 k ... 9.99 k 0.01 k See accuracy note
10.0 k ... 99.9 k 0.1 k
100 k ... 9999 k 1k

RC and RP values are indicative.

Principle:
= 2··d·Re,
where Re is a measured resistance in 4-wire method and d is distance between the probes.

Accuracy note:
Accuracy of the specific earth resistance result depends on measured earth resistance Re as
follows:

Re – Earth resistance
Measuring range () Accuracy
1.00 ... 1999 5 % of measured value
2000 ... 19.99 k 10 % of measured value
>20 k 20 % of measured value

Additional error:
See Earth resistance three-wire method.

242
MI 3155 EurotestXD Technical specifications

12.20 Voltage, frequency, and phase rotation


12.20.1 Phase rotation
Nominal system voltage range............... 100 VAC ... 550 VAC
Nominal frequency range ....................... 14 Hz ... 500 Hz
Result displayed .................................... 1.2.3 or 3.2.1

12.20.2 Voltage / Online terminal voltage monitor


Measuring range (V) Resolution (V) Accuracy
0 ... 550 1 (2 % of reading + 2 digits)

Result type ............................................ True r.m.s. (TRMS)


Nominal frequency range ....................... 0 Hz, 14 Hz ... 500 Hz

12.20.3 Frequency
Measuring range (Hz) Resolution (Hz) Accuracy
0.00 ... 9.99 0.01
(0.2 % of reading + 1 digit)
10.0 ... 499.9 0.1

Nominal voltage range ........................... 20 V ... 550 V

12.21 Varistor test


Udc – DC voltage
Measuring range (V) Resolution (V) Accuracy
0 … 2500 1 (3 % of reading + 3 digits)

Uac – AC voltage
Measuring range (V) Resolution (V) Accuracy
0 … 1562 1 Consider accuracy of DC
voltage

Measurement principle .......................... d.c. voltage ramp


Test voltage slope ................................. Nominal test voltage 1000 V: 100 V/s
Nominal test voltage 2500 V: 350 V/s
Threshold current .................................. 1 mA

243
MI 3155 EurotestXD Technical specifications

12.22 Currents
Maximum voltage on C1 measuring input ........ 3 V
Nominal frequency ................................. ......... 0 Hz, 40 Hz ... 500 Hz

Ch1 clamp type: A1018


Range: 20 A
I1 – Current
Measuring range (A) Resolution (A) Accuracy*
0.0 m ... 99.9 m 0.1 m (5 % of reading + 5 digits)
100 m ... 999 m 1m (3 % of reading + 3 digits)
1.00 ... 19.99 0.01 (3 % of reading)

Ch1 clamp type: A1391


Range: 40 A
I1 – Current
Measuring range (A) Resolution (A) Accuracy*
0.00 ... 1.99 0.01 (3 % of reading + 3 digits)
2.00 ... 19.99 0.01 (3 % of reading)
20.0 ... 39.9 0.1 (3 % of reading)

Ch1 clamp type: A1391


Range: 300 A
I1 – Current
Measuring range (A) Resolution (A) Accuracy*
0.00 ... 19.99 0.01
indicative
20.0 ... 39.9 0.1
40.0 ... 299.9 0.1 (3 % of reading + 5 digits)

* Accuracy at operating conditions for instrument and current clamp is given.

12.23 Current clamp meter (MI 3144)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MI 3144 Euro Z 800 V Instruction manual.

244
MI 3155 EurotestXD Technical specifications

12.24 Power
Measurement characteristics
Function symbols Class according to Measuring range
IEC 61557-12
P – Active power 2.5 5 % ... 100 % INom*)
S – Apparent power 2.5 5 % ... 100 % INom*)
Q – Reactive power 2.5 5 % ... 100 % INom*)
PF – Power factor 1 - 1 ... 1
THDu 2.5 0 % ... 20 % UNom
*)
INom depends on selected current clamp type and selected range as follows:
A 1018:[20 A]
A 1391: [40 A, 300 A]

Function Measuring range


Power (P, S, Q) 0.00 W (VA, Var) ... 99.9 kW (kVA, kVar)
Power factor -1.00 ... 1.00
Voltage THD 0.1 % ... 99.9 %

Error of external voltage and current transducers is not considered in this specification.

12.25 Harmonics
Measurement characteristics
Function symbols Class according to Measuring range
IEC 61557-12
Uh 2.5 0 % ... 20 % UNom
THDu 2.5 0 % ... 20 % UNom
Ih 2.5 0 % ... 100 % INom*)
THDi 2.5 0 % ... 100 % INom*)
*)
INom depends on selected current clamp type and selected range as follows:
A 1018: [20 A]
A 1391: [40 A, 300 A]

Function Measuring range


Voltage harmonics 0.1 V ... 500 V
Voltage THD 0.1 % ... 99.9 %
Current harmonics and Current THD 0.00 A ... 199.9 A

Error of external voltage and current transducers is not considered in this specification.

245
MI 3155 EurotestXD Technical specifications

12.26 ISFL – First fault leakage current


Isc1, Isc2 – First fault leakage current
Measuring range (mA) Resolution (mA) Accuracy
0.0 ... 19.9 0.1 ±(5 % of reading + 3 digits)

Measuring resistance.................................. approx. 390 


Nominal voltage ranges .............................. 93 V  UL1-L2  134 V
185 V  UL1-L2  266 V

12.27 IMD
R1, R2 – Threshold insulation resistance
R (kΩ) Resolution (kΩ) Note
5 ... 640 5 up to 128 steps

I1, I2 – First fault leakage current at threshold insulation resistance


I (mA) Resolution (mA) Note
0.0 ... 19.9 0.1 calculated value*)

t1, t2 – Activation / disconnection time of IMD


t1,t2 (s) Resolution (s) Accuracy
0.00 ... 19.99 0.01 ± 0.02 s
20.0 … 99.9 0.1 ± 0.1 s

Nominal voltage ranges .............................. 93 V  UL1-L2  134 V


185 V  UL1-L2  266 V
*)See chapter 7.34 IMD – Testing of insulation monitoring devices for more information
about calculation of first fault leakage current at threshold insulation resistance.

12.28 Illumination
E – Illumination (A 1172)
Specified accuracy is valid for complete operating range.
Measuring range (lux) Resolution (lux) Accuracy
0.01 ... 19.99 0.01 (5 % of reading + 2 digits)
20.0 ... 199.9 0.1
200 ... 1999 1 (5 % of reading)
2.00 k ... 19.99 k 10

Measurement principle ...........................silicon photodiode with V() filter


Spectral response error ..........................< 3.8 % according to CIE curve
Cosine error ............................................< 2.5 % up to an incident angle of  85O
Overall accuracy .....................................matched to DIN 5032 class B standard

E – Illumination (A 1173)
Specified accuracy is valid for complete operating range.
Measuring range (lux) Resolution (lux) Accuracy
0.01 ... 19.99 0.01 (10 % of reading + 3 digits)
20.0 ... 199.9 0.1
(10 % of reading)
200 ... 1999 1

246
MI 3155 EurotestXD Technical specifications

2.00 k ... 19.99 k 10

Measurement principle ...........................silicon photodiode


Cosine error ............................................< 2.5 % up to an incident angle of  85O
Overall accuracy .....................................matched to DIN 5032 class C standard

12.29 Discharging time


t – Discharging time
Measuring range according to EN 61557-14 is 0.8 s ... 9.9 s.
Range (s) Resolution (s) Accuracy
0.0 s ... 9.9 0.1 (5 % of reading + 2 digits)

Ures – Residual voltage


Range (V) Resolution (V) Accuracy
0.0 ... 99.9 0.1
(5 % of reading + 3 digits)
100 … 372 1

Up – Peak voltage
Range (V) Resolution (V) Accuracy
0 ... 372 1 (5 % of reading + 3 digits)

U – RMS voltage
Range (V) Resolution (V) Accuracy
70.0 ... 99.9 0.1
(2 % of reading + 2 digits)
100 … 263 1

Freq – Frequency
Range (Hz) Resolution (Hz) Accuracy
45.0 ... 65.0 0.1 (0.2 % of reading + 1 digits)

Nominal frequency range ................................. d.c.,45 Hz – 65 Hz


High limits ........................................................ 1 s, 5 s
Threshold voltage ............................................ 34 V, 60 V, 120 V
Input resistance ............................................... 20 M

12.30 Auto Sequences®


Refer to each individual test (measurement) for detailed technical specification.

12.31 R line mΩ - DC resistance measurement (MI 3144)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MI 3144 Euro Z 800 V Instruction manual.

12.32 ELR Current injection (MI 3144)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MI 3144 Euro Z 800 V Instruction manual.

247
MI 3155 EurotestXD Technical specifications

12.33 ELR Combination time test (MI 3144)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MI 3144 Euro Z 800 V Instruction manual.

12.34 EVSE Diagnostic test (A 1632)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to A 1632 eMobility Analyzer Instruction manual.

12.35 Power CLAMP (MD 9273)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MD 9273 Leakage Clamp meter with Bluetooth®
Communication Instruction manual.

12.36 Voltage CLAMP (MD 9273)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MD 9273 Leakage Clamp meter with Bluetooth®
Communication Instruction manual.

12.37 Current CLAMP (MD 9273)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MD 9273 Leakage Clamp meter with Bluetooth®
Communication Instruction manual.

12.38 Inrush CLAMP (MD 9273)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MD 9273 Leakage Clamp meter with Bluetooth®
Communication Instruction manual.

12.39 Harmonics U CLAMP (MD 9273)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MD 9273 Leakage Clamp meter with Bluetooth®
Communication Instruction manual.

12.40 Harmonics I CLAMP (MD 9273)


This test is performed in combination with an external test adapter / instrument.
For technical specification refer to MD 9273 Leakage Clamp meter with Bluetooth®
Communication Instruction manual.

248
MI 3155 EurotestXD Technical specifications

12.41General data
Power supply ......................................... Li-Ion battery pack 7.2 V,
4400 mAh (type: 18650T22A2S2P)
8800 mAh (type: 18650T22A2S4P) optional
Operation............................................... Typical 16 h (type: 18650T22A2S2P)
Typical 32 h (type: 18650T22A2S4P)
Charger socket input voltage ................. 12 V  10 %
Charger socket input current.................. 3000 mA max.
Battery charging current ........................ up to 2200 mA (Battery type: 18650T22A2S2P)
up to 3000 mA (Battery type: 18650T22A2S4P)
Measuring category ............................... 600 V CAT III
300 V CAT IV
Protection classification ......................... double insulation
Pollution degree..................................... 2
Protection degree .................................. 56 (with protective covers on USB, Charger and
PS/2 terminals)
Altitude .................................................. ≤ 2000 m
Display .................................................. 4.3 inch (10.9 cm) 480x272 pixels TFT colour display
with touch screen
Dimensions (w  h  d) .......................... 252 mm  111 mm  165 mm
Weight ................................................... 1.78 kg, with battery pack (type: 18650T22A2S2P)
Reference conditions
Reference temperature range ................ 10 C ... 30 C
Reference humidity range ...................... 40 %RH ... 70 %RH
Operation conditions
Working temperature range ................... 0 C ... 40 C
Maximum relative humidity .................... 95 %RH (0 C ... 40 C), non-condensing
Operation............................................... Indoor use
Storage conditions
Temperature range ................................ -10 C ... +70 C
Maximum relative humidity .................... 90 %RH (-10 C ... +40 C)
80 %RH (40 C ... 60 C)
Locator
Locator .................................................. supports inductive mode
Maximum operation voltage ................... 440 V a.c.
Communication ports, memory
RS 232 .................................................. 115200 bits/s, 8N1 serial protocol
USB ....................................................... USB 2.0 Hi speed interface
with USB type B receptacle connector
Data storage capacity ............................ 8 GB SD memory card
Bluetooth module................................... Class 2
EMC
Emission ................................................ Class B
Immunity ................................................ Basic electromagnetic environment
(Portable test and measurement equipment)
The error in operating conditions could be at most the error for reference conditions (specified in
the manual for each function) +1 % of measured value + 1 digit, unless otherwise specified in
the manual for particular function.

249
MI 3155 EurotestXD Appendix A – Profile notes

Appendix A Profile notes


Instrument supports working with multiple Profiles. This appendix contains collection of minor
modifications related to particular country requirements. Some of the modifications mean
modified listed function characteristics related to main chapters and others are additional
functions. Some minor modifications are related also to different requirements of the same
market that are covered by various suppliers.

A.1 Profile Austria (ATAF)


Testing special delayed G type RCD supported.

Modifications in chapter 7.9 Testing RCDs.

Special delayed G type RCD selection added in the Selectivity parameter in Test Parameters /
Limits section as follows:

Selectivity Characteristic [--, S, G]

Time limits are the same as for general type RCD and contact voltage is calculated the same as
for general type RCD.

Selective (time delayed) RCDs and RCDs with (G) - time delayed characteristic demonstrate
delayed response characteristics. They contain residual current integrating mechanism for
generation of delayed trip out. However, contact voltage pre-test in the measuring procedure
also influences the RCD and it takes a period to recover into idle state. Time delay of 30 s is
inserted before performing trip-out test to recover S type RCD after pre-tests and time delay of 5
s is inserted for the same purpose for G type RCD.

Table 7.3: Relation between Uc, Uc(P) and IN changed as follows:

Contact voltages Uc and Uc(P)


RCD type Rated IN
proportional to
-- any
AC, EV, MI (a.c. part) 1.05IN
G
AC S 21.05IN
A, F
--  30 mA
1.41.05IN
G
A, F S 21.41.05IN
-- < 30 mA
A, F 21.05IN
G
A, F S 221.05IN
B, B+ -- 21.05IN any
B, B+ S 221.05IN

Technical specifications unchanged.

250
MI 3155 EurotestXD Appendix A – Profile notes

A.2 Profile Hungary (ATAG)


Fuse type gR added to the fuse tables. Refer to Fuse tables guide for detailed information on
fuse data.

New Single test function Visual Test added.

Figure A.1: Visual Test menu

Measurement parameters / limits

Protection type [No, Automatic disconnection, Class II,


Protection type
Electrical separation, SELV,PELV]

Measurement procedure

 Enter the Visual Test function.


 Set test parameters / limits.
 Perform the visual inspection on tested object.

 Use to select PASS / FAIL / NO STATUS indication.


 Save results (optional).

Figure A.2: Examples of Visual Test result

Modifications in chapter 7.10 RCD Auto – RCD Auto test

Added tests with multiplication factor 2.

Modification of RCD Auto test procedure

251
MI 3155 EurotestXD Appendix A – Profile notes

RCD Auto test inserted steps Notes


 Re-activate RCD.
Test with 2IN, (+) positive polarity (new step 5). RCD should trip-out
 Re-activate RCD.
Test with 2IN, (-) negative polarity (new step 6). RCD should trip-out

Inserted new Step 5 Inserted new Step 6

Figure A.3: Example of individual steps in RCD Auto test – Inserted 2 new steps

Test results / sub-results


t I∆N d.c. x1, (+) 1) Step 1 trip-out time (I=IN d.c., (+) positive polarity)
t I∆N d.c. x1, (-) 1) Step 2 trip-out time (I=IN d.c., (-) negative polarity)
t I∆N x1, (+) Step 3 trip-out time (I=IN, (+) positive polarity)
Non-operating time for a.c. current (IEC 62955).
t I∆N x1, (-) Step 4 trip-out time (I=IN, (-) negative polarity)
Non-operating time for a.c. current (IEC 62955).
t I∆N x2, (+) Step 5 trip-out time (I=2IN, (+) positive polarity)
t I∆N x2, (-) Step 6 trip-out time (I=2IN, (-) negative polarity)
t I∆N x5, (+) Step 7 trip-out time (I=5IN, (+) positive polarity)
t I∆N x5, (-) Step 8 trip-out time (I=5IN, (-) negative polarity)
t I∆N x0.5, (+) Step 9 trip-out time (I=½IN, (+) positive polarity)
t I∆N x0.5, (-) Step 10 trip-out time (I=½IN, (-) negative polarity)
I∆ (+) Step 11 trip-out current ((+) positive polarity)
I∆ (-) Step 12 trip-out current ((-) negative polarity)
I∆ d.c. (+)1) Step 13 trip-out current ((+) positive polarity)
I∆ d,c, (-)1) Step 14 trip-out current ((-) negative polarity)
Uc Contact voltage for rated IN
1) Result
is displayed only when parameter Use is set to ‘other’ and parameter Type to ‘EV RCD’, ‘EV
RCM’ or ‘MI RCD’.

A.3 Profile Finland (ATAH)


Ia(Ipsc) limit modified in fuse types gG, NV, B, C, D and K.
Refer to Fuse tables guide for detailed information on fuse data.

252
MI 3155 EurotestXD Appendix A – Profile notes

A.4 Profile France (ATAI)


Modifications in chapters:
7.9 Testing RCDs;
7.13 Zs rcd – Fault loop impedance and prospective fault current in system with RCD;
7.21 Z auto - Auto test sequence for fast line and loop testing;
7.38 AUTO TT – Auto test sequence for TT earthing system.

650 mA added in the I N parameter in Test Parameters / Limits section as follows:

I N Rated RCD residual current sensitivity [10 mA, 15 mA, 30 mA, 100 mA, 300
mA, 500 mA, 650 mA, 1000 mA]

Modifications in chapter 12.6 RCD testing

Nominal residual current (A,AC) .............10 mA, 15 mA, 30 mA, 100 mA, 300 mA, 500 mA,
650 mA, 1000 mA

RCD test current in relation to RCD type, nominal RCD current and multiplication factor
IN × 1/2 IN × 1 IN × 2 IN × 5 RCD I
(mA) (mA) (mA) (mA)
IN AC A, F B, AC A, FB, AC A, F B, AC A, B, AC A, B,
(mA) B+ B+ B+ F B+ F B+
10 5 3.5 5 10 20 20 20 40 40 50 100 100 ✓ ✓ ✓
15 7.5 5.3 7.5 15 30 30 30 60 60 75 150 150 ✓ ✓ ✓
30 15 10.5 15 30 42 60 60 84 120 150 212 300 ✓ ✓ ✓
100 50 35 50 100 141 200 200 282 400 500 707 1000 ✓ ✓ ✓
300 150 105 150 300 424 600 600 848 × 1500 × × ✓ ✓ ✓
500 250 175 250 500 707 1000 1000 1410 × 2500 × × ✓ ✓ ✓
650 325 227.5 250 650 916.5 1300 1300 × × × × × ✓ ✓ ✓
1000 500 350 500 1000 1410 × 2000 × × × × × ✓ ✓ ×

×. ............................................................not applicable
✓.............................................................applicable
AC type...................................................sine wave test current
A, F types…… ........................................pulsed current
B, B+ types .............................................smooth DC current

Other technical specifications remain unchanged.


;
7.38 AUTO TT – Auto test sequence for TT earthing system.

650 mA added in the I N parameter in Test Parameters / Limits section as follows:

I N Rated RCD residual current sensitivity [10 mA, 15 mA, 30 mA, 100 mA, 300
mA, 500 mA, 650 mA, 1000 mA]

Modifications in chapter 12.6 RCD testing

Nominal residual current (A,AC) .............10 mA, 15 mA, 30 mA, 100 mA, 300 mA, 500 mA,
650 mA, 1000 mA

253
MI 3155 EurotestXD Appendix A – Profile notes

RCD test current in relation to RCD type, nominal RCD current and multiplication factor
IN × 1/2 IN × 1 IN × 2 IN × 5 RCD I
(mA) (mA) (mA) (mA)
IN AC A, F B, AC A, FB, AC A, F B, AC A, B, AC A, B,
(mA) B+ B+ B+ F B+ F B+
10 5 3.5 5 10 20 20 20 40 40 50 100 100 ✓ ✓ ✓
15 7.5 5.3 7.5 15 30 30 30 60 60 75 150 150 ✓ ✓ ✓
30 15 10.5 15 30 42 60 60 84 120 150 212 300 ✓ ✓ ✓
100 50 35 50 100 141 200 200 282 400 500 707 1000 ✓ ✓ ✓
300 150 105 150 300 424 600 600 848 × 1500 × × ✓ ✓ ✓
500 250 175 250 500 707 1000 1000 1410 × 2500 × × ✓ ✓ ✓
650 325 227.5 250 650 916.5 1300 1300 × × × × × ✓ ✓ ✓
1000 500 350 500 1000 1410 × 2000 × × × × × ✓ ✓ ×

×. ............................................................not applicable
✓.............................................................applicable
AC type...................................................sine wave test current
A, F types…… ........................................pulsed current
B, B+ types .............................................smooth DC current

Other technical specifications remain unchanged.

A.5 Profile Switzerland (ATAJ)


Modifications in chapter 4.4.1 Terminal voltage monitor
In the Terminal voltage monitor the positions of L and N indications are opposite to standard
version.

Voltage monitor example:

Online voltages are displayed together with test terminal indication. All three
test terminals are used for selected measurement.

254
MI 3155 EurotestXD Appendix B – Commanders

Appendix B Commanders (A 1314, A 1401)


B.1 Warnings related to safety
Measuring category of commanders

Plug commander A 1314 ............... 300 V CAT II

Tip commander A 1401


(cap off, 18 mm tip) ....................... 1000 V CAT II / 600 V CAT II / 300 V CAT II
(cap on, 4 mm tip) ......................... 1000 V CAT II / 600 V CAT III / 300 V CAT IV

 Measuring category of commanders can be lower than protection category of the


instrument.
 If dangerous voltage is detected on the tested PE terminal, immediately stop all
measurements, find and remove the fault!
 When replacing battery cells or before opening the battery compartment cover,
disconnect the measuring accessory from the instrument and installation.
 Service, repairs or adjustment of instruments and accessories is only allowed to be
carried out by competent authorized personnel!

B.2 Battery
The commander uses two AAA size alkaline or rechargeable Ni-MH battery cells.
Nominal operating time is at least 40 h and is declared for cells with nominal capacity of 850
mAh.

Notes:
 If the commander is not used for a long period of time, remove all batteries from the
battery compartment.
 Alkaline or rechargeable Ni-MH batteries (size AAA) can be used. Metrel recommends
only using rechargeable batteries with a capacity of 800 mAh or above.
 Ensure that the battery cells are inserted correctly otherwise the commander will not
operate and the batteries could be discharged.

B.3 Description of commanders

Figure B.1: Front side Tip commander (A 1401)

255
MI 3155 EurotestXD Appendix B – Commanders

Figure B.2: Front side Plug commander (A 1314)

Figure B.3: Back side

1 TEST Starts measurements.


TEST
Acts also as the PE touching electrode.
2 LED Left status RGB LED
3 LED Right status RGB LED
4 LEDs Lamp LEDs (Tip commander)
5 Function selector Selects test function.
6 MEM Store / recall / clear tests in memory of instrument.
7 BL Switches On / Off backlight on instrument
8 Lamp key Switches On / Off lamp (Tip commander)
9 Battery cells Size AAA, alkaline / rechargeable Ni-MH
10 Battery cover Battery compartment cover
11 Cap Removable CAT IV cap (Tip commander)

B.4 Operation of commanders


Both LED yellow Warning! Dangerous voltage on the commander’s PE
terminal!
Right LED red Fail indication
Right LED green Pass indication
Left LED blinks blue Commander is monitoring the input voltage.
Left LED orange Voltage between any test terminals is higher than 50 V.
Both LEDs blink red Low battery
Both LEDs red and switch off Battery voltage too low for operation of commander

256
MI 3155 EurotestXD Appendix C – Locator receiver R10K

Appendix C Locator receiver R10K


The highly sensitive hand-held receiver R10K detects the fields caused by the currents in
the traced line. It generates sound and visual output according to the signal intensity. The
operating mode switch in the head detector should always be set in IND (inductive) mode.
The CAP (capacitive) operating mode is intended for operating in combination with other
Metrel measuring equipment.
The built in field detector is placed in the front end of the receiver. External detectors can be
connected via the rear connector.
Traced object must be energized when working with the EurotestXD.

Detectors Operation
In built inductive sensor (IND) Tracing hidden wires.
Current clamp (optional) Connected through the rear connector.
Locating wires.
Selective probe Connected through the rear connector.
Locating fuses in fuse cabinets.

Figure C.1: Receiver R10K

The user can choose between three sensitivity levels (low, middle and high). An extra
potentiometer is added for fine sensitivity adjustment. A buzzer sound and 10-level LED bar
graph indicator indicates the strength of the magnetic field e.g. proximity of the traced object.

Note:
 The field strength can vary during tracing. The sensitivity should always be adjusted
to optimum for each individual tracing.

257
MI 3155 EurotestXD Appendix D – Structure objects

Appendix D Structure objects


Structure elements used in Memory Organizer are instrument’s Profile dependent.

Symbol Default name Description


Node Node

Object Object

Dist. board Distribution board

Sub D. Board Sub Distribution board

Local bonding Local equipotential bonding

Water Service Protective conductor for Water service

Oil service Protective conductor for Oil service

Lightn. protect. Protective conductor for Lightning protection

Gas service Protective conductor for Gas service

Struct. steel Protective conductor for Structural steel

Other service Protective conductor for Other incoming service

Earthling cond. Earthing conductor

Circuit Circuit

Connection Connection

Socket Socket

Connection 3-ph Connection - 3 phase

Light Light

Socket 3-ph Socket - 3 phase

RCD RCD

MPE MPE

258
MI 3155 EurotestXD Appendix D – Structure objects

Symbol Default name Description


Foundation gr. Protective conductor for Foundation ground

Equip. bond. rail Equipotential bonding rail

House water m. Protection conductor for House water meter

Main water p. Protection conductor for Main water pipes

Main gr. cond. Main grounding conductor

Inter. gas inst. Protective conductor for Interior gas installation

Heat.inst. Protective conductor for Heating installation

Air cond. inst. Protective conductor for Air conditioning installation

Lift inst. Protective conductor for Lift installation

Data proc. Inst. Protective conductor for Lift Data processing installation

Teleph. Inst. Protective conductor for Telephone installation

Lightn. prot. syst. Protective conductor for Lightning protection system

Antenna inst. Protective conductor for Antenna installation

Build. Constr. Protective conductor for Building construction

Other conn. Other connection

Earth electrode Earth electrode

Lightning Sys. Lightning System

Lightning. electr. Lightning electrode

Inverter Inverter

String String array

Module Module

EVSE Electro-Vehicle supply Equipment

259
MI 3155 EurotestXD Appendix D – Structure objects

Symbol Default name Description


Level 1 Level 1

Level 2 Level 2

Level 3 Level 3

Varistor Varistor

LS connection LS connection

Machine Machine

Appliance Appliance (PRCD)

260
MI 3155 EurotestXD Appendix E – Default list of AutoSequences

Appendix E Default list of Auto Sequences


Default list of Auto Sequences® for MI 3155 – Eurotest XD instrument is available on Metrel
home page www.metrel.si.

261
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

Appendix F Programming of Auto Sequences


on Metrel ES Manager
The Auto Sequence® editor is a part of the Metrel ES Manager software. In Auto Sequence®
editor Auto Sequence® can be pre-programmed and organized in groups, before uploaded
to the instrument.

F.1 Auto Sequence Editor workspace

To enter Auto Sequence® editor’s workspace, select in Home Tab of Metrel


ES Manager PC SW. Auto Sequence® editor workspace is divided in four main areas. On

the left side ,structure of selected group of Auto Sequence® is displayed. In the middle

part of the workspace , the elements of the selected Auto Sequence® are shown. On the

right side, list of available Single tests (measurements and inspections) and list of Flow

commands are shown.


Single test area contain three tabs: Measurements, Inspections and Custom Inspections tab.
Custom Inspections and their tasks are programmed by user, see chapter F.8 Custom
Inspections programming for procedure.

Figure F.1: Auto Sequence® Editor workspace

262
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

An Auto Sequence® begins with Name, Description and Image, followed by the first step
(Header), one or more measuring steps and ends with the last step (Result). By inserting

appropriate Single tests (measurements and inspections) and Flow commands and
setting their parameters, arbitrary Auto Sequences® can be created.

Figure F.2: Example of an empty Auto


Sequence® header

Figure F.3: Example of a measurement step

Figure F.4: Example of an Auto Sequence®


result

F.2 Managing groups of Auto Sequences


The Auto Sequences® can be divided into different user defined groups of Auto
Sequences®. Each group of Auto Sequences® is stored in a file. More files can be opened
simultaneously in Auto Sequence® editor.
Within Group of Auto Sequences®, tree structure can be organized, with folders / subfolders
containing Auto Sequences®. The three structure of currently active Group of Auto
Sequences® is displayed on the left side of the Auto Sequence® Editor workspace, see
Figure F.5.

Figure F.5: Group of Auto Sequences® tree organization

263
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

Operation options on Group of Auto Sequences® are available from menu bar at the top of
Auto Sequence® Editor workspace.
File operation options:

Opens a file (Group of Auto Sequences®).

Creates a new file (Group of Auto Sequences®).

Saves / Saves as the opened Group of Auto sequences® to a file.

Closes the file (Group of Auto Sequences®).

Group of Auto Sequences® view options:

Expand all folders / subfolders / Auto Sequences®.

Collapse all folders / subfolders / Auto Sequences®.

Toggle between Search by name within Auto Sequence® group and normal
view. See chapter F.4 Search within selected Auto Sequence® group for
details.

Group of Auto Sequences® operation options (also available by right clicking on Folder or
Auto Sequence®):

Adds a new folder / subfolder to the group

Adds a new Auto Sequence® to the group.

Deletes:
- the selected Auto Sequence®
- the selected folder with all subfolders and Auto Sequences®

Right click on the selected Auto Sequence® or Folder opens menu with additional
possibilities:

Auto Sequence®: Edit Name, Description and Image (see Figure F.6.)
Folder: Edit folder name

Auto Sequence®: Copy to clipboard


Folder: Copy to clipboard including subfolders and Auto Sequences®

264
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

Auto Sequence®: Paste it to selected location


Folder: Paste it to selected location

Auto Sequence®: Creates shortcut to selected Auto Sequence®

Double click on the object name allows it name edit:

Auto Sequence® name: Edit Auto Sequence® name

DOUBLE CLICK
Folder name: Edit folder name

Drag and drop of the selected Auto Sequence® or Folder / Subfolder moves it to a new
location:

‘Drag and drop’ functionality is equivalent to ‘cut’ and ‘paste’ in a


single move.
DRAG & DROP
move to folder
insert

265
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

F.3 Auto Sequence® Name, Description and Image editing


When EDIT function is selected on Auto Sequence®, menu for editing presented on Figure
F.6 appear on the screen. Editing options are:
Name: Edit or change the name of Auto Sequence®.
Description: Any text for additional description of Auto Sequence® can be entered.
Image: Image presenting Auto sequence® measuring arrangement can be entered or
deleted.

Enters menu for browsing to Image location.

Deletes the Image from Auto Sequence®.

Figure F.6: Editing the Auto Sequence® Name, Description and Image

266
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

F.4 Search within selected Auto Sequence® group

When function is selected, Search menu as presented on Figure F.7 appear on the
screen. By entering the text into search box, found results are automatically highlighted with
yellow background. Search functionality is implemented in Folders, Subfolders and Auto
Sequences® of selected Auto Sequence® Group. Search text can be cleared by selecting
the Clear button.

Figure F.7: Example of Search result within Auto Sequence® group

267
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

F.5 Elements of an Auto Sequence®


F.5.1 Auto Sequence® steps
There are three kinds of Auto Sequence® steps.

Header
The Header step is empty by default.
Flow commands can be added to the Header step.

Measurement step
The Measurement step contains a Single test and the Operation after end of test flow
command by default. Other Flow commands can also be added to the Measurement step.

Result
The Result step contains the Result screen flow command by default. Other Flow commands
can also be added to the Result step.

F.5.2 Single tests


Single tests are the same as in Metrel ES Manager Measurement menu.
Limits and parameters of the measurements can be set. Results and sub-results can’t be set.

F.5.3 Flow commands


Flow commands are used to control the flow of measurements. Refer to chapter F.7
Description of flow commands for more information.

F.5.4 Number of measurement steps


Often the same measurement step has to be performed on multiple points on the device
under test. It is possible to set how many times a Measurement step will be repeated. All
carried out individual Single test results are stored in the Auto Sequence® result as if they
were programmed as independent measuring steps.

268
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

F.6 Creating / modifying an Auto Sequence®


If creating a new Auto Sequence® from scratch, the first step (Header) and the last step
(Result) are offered by default. Measurement steps are inserted by the user.

Options

Adding a measurement step By double clicking on a Single test a new


measurement step will appear as the last of
measurement steps. It can also be dragged and
dropped on the appropriate position in the Auto
Sequence®.

Adding flow commands Selected flow command can be dragged from the list
of Flow Commands and dropped on the appropriate
place in any Auto Sequence® step.

Changing position of flow command By a click on an element and use of and keys.
within measurement step

Viewing / changing parameters of By a double click on the element.


flow commands or single tests.

Setting number of measurement


step repetitions. By setting a number in the field.

Touch pre-test disable / enable


By setting True / False in the field.
(not available in all functions)
(Default value is False – Touch pre-test is enabled)

Right click on the selected measurement step / flow command:

Copy – Paste before


A measurement step / flow command can be
copied and pasted above selected location on
the same or on another Auto Sequence®.

Copy – Paste after


A measurement step / flow command can be
copied and pasted under selected location on
the same or on another Auto Sequence®.

Delete
Deletes the selected measurement step / flow
command.

269
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

F.7 Description of flow commands


Double click on inserted Flow Command opens menu window, where text or picture can be
entered, external commands can be activated and parameters can be set.
Flow commands Operation after end of test and Results screen are entered by default,
others are user selectable from Flow Commands menu.

Pause
A Pause command with text message or picture can be inserted anywhere in the measuring
steps. Warning icon can be set alone or added to text message. Arbitrary text message can
be entered in prepared field Text of menu window.

Parameters

Pause type Show text and/or warning ( check to show warning icon).
Show picture ( browse for image path).

Duration Number in seconds, infinite (no entry).

Buzzer mode
Passed or failed measurement is indicated with beeps.
 Pass – double beep after the test
 Fail – long beep after the test
Beep happens right after single test measurement.

Parameters

State On – enables Buzzer mode


Off – disables Buzzer mode

270
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

Operation after end of test


This flow command controls the proceeding of the Auto Sequence® in regard to the
measurement results.

Parameters

Operation after end of test The operation can be individually set for the case the
measurement passed, failed or ended without a status.
 pass
 fail Manual: The test sequence stops and waits for
appropriate command (RUN key, external
 no status
command …) to proceed.

Auto: The test sequence automatically proceeds.

Result screen
This flow command controls the proceeding after the Auto Sequence® has ended.

Parameters

 Auto save Auto Sequence® results are stored in the momentary workspace.
A new Node with the current month and year will be created. Under the
Node Auto Sequence® results will be stored.
Up to 100 Auto Sequence® results can be automatically stored under the
same node. If more results are available, they are split to multiple nodes.
Auto Save Flow setting is disabled by default.
Note
 This flow command is active only if Auto Sequence® is started from
the Auto Sequence® Main menu (not from the Memory organizer).

271
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

F.8 Custom Inspections programming


Arbitrary set of tasks dedicated to specific user defined Inspections can be programmed with
application of Custom Inspection Editor Tool, accessible from Auto Sequence® Editor
workspace. Custom Inspections are stored in dedicated file *.indf with user defined name.
For application of Custom Inspections as a single test within Auto Sequence® group,
appropriate file containing specific Custom Inspection should be opened first.

F.8.1 Creating and editing Custom Inspections

Custom Inspection Editor workspace is entered by selecting icon from Auto


Sequences® main menu. It is divided in two main areas, as presented on Figure F.8:

Custom Inspection Name and Scope of inspection (Visual or Functional)

Name of Custom Inspection Item tasks and Type of Item Pass / Fail checkbox marking

Figure F.8: Custom Inspection Editor workspace

Custom Inspection Editor Main menu options:


Opens existing Custom Inspection Data file.
By selecting, menu for browsing to location of *.indf file containing one or more
Custom Inspections data appear on the screen. Selected file is opened in
dedicated tab marked with file name.

Creates a new Custom Inspection Data file.


New tab with empty workspace is opened. Default name of the new tab is
Inspection Data File; it could be renamed during Save procedure.

Saves / Saves as Custom Inspection Data file opened on active tab.


Menu for browsing to the folder location and editing of file name is opened.

272
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

Browse to the location, confirm overwriting, if file already exists or edit file name to
save it as a new Custom Inspection Data file.

Add New Custom Inspection.


New inspection with default name Custom Inspection and default scope Visual
appear on the editor workspace. It contains one Item task with default name
Custom Inspection and default Type Pass_Fail_Checked_Empty. Default Name
and Type can be edited – changed.

Remove selected custom inspection.


To select inspection, click to the inspection Name field. To remove it, select icon
from editor main menu. Before removal, user is asked to confirm deletion.

Edit Name and Scope of Inspection


Inspection Name edit:
Click to the Inspection Name field to start editing it.
Drag cursor, with left mouse button pressed, to select letters and words.
Position cursor and double-click to select word of the name. Actions
could be performed with keyboard also.
Press right mouse button to activate Edit menu and select appropriate
action as presented on the left figure. Menu is case sensitive; options
currently not available are greyed out.

Inspection Scope edit:


Click to Inspection Scope field to open selection menu presented on left
figure. Options:
Visual is intended for observation of test object
Functional allows functional test of observed object

Edit Item task structure of Inspection


Item tasks of the selected Inspection are listed in Name column on
the right side of Editor workspace.
Each Item task can have Child Item tasks, Child Item can have its
own Child Item tasks and so on.
Arbitrary tree structure of Item tasks and subtasks can be built as
presented on left figure.

ADD New Item task procedure:


Position cursor above Item task Name and apply right mouse click
to select Item task and open menu with options:
Add New: new Item task is added on the top tree level
Add New Child: new child Item task is added under selected Item
Remove selected: delete selected Item task with all subtasks
Default Name of New Item task is Custom Inspection, default Type
Pass_Fail_Checked_Empty and both can be edited – changed.

273
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

Item tasks containing Child Item tasks are marked with triangle in
front of their Name.
Click on triangle mark:

collapse Item task tree structure


expands Item task tree structure

Edit Name and Type of Item task

Edit Name of Item task:


Click to the Item task Name field to start editing it.
Drag cursor, with left mouse button pressed, to select letters and
words. Position cursor and double-click to select word of the name.
Actions could be performed with keyboard also.
Press right mouse button to activate Edit menu and select
appropriate action as presented on the left figure. Menu is case
sensitive; options currently not available are greyed out.

Edit Type of Item task:


Click to Item Type field to open selection menu presented on left
figure. Selectable checkbox status assignment options are:
Pass_Fail_Checked_Empty: Pass, Fail, Checked, Empty (default)
Pass_Fail_Empty: Pass, Fail selection, Empty (default) value

F.8.2 Applying Custom Inspections


Custom inspections can be applied in Auto Sequences®. Direct assignment of Custom
inspection to the Metrel ES manager structure objects is not possible.
After custom created Inspection Data file is opened, available inspections are listed in
Custom Inspections tab of Single test area of Auto Sequence® Editor, see chapter F.1 Auto
Sequence Editor workspace for details.
Custom Inspection is added to Auto sequence as a Single test, see chapter F.6 Creating /
modifying an Auto Sequence® for details.

Opening / changing Inspection Data File

274
MI 3155 EurotestXD Appendix F – Programming of AutoSequences
on Metrel ES Manager

Position cursor within Custom inspections List area and


apply mouse right click to open Option menu:
Refresh: Refresh content of already opened Inspection
Data file
Browse for custom Inspection file:
Menu for browsing to folder location of new Inspection
Data file is opened.

After confirmation of selection, new Inspection Data file is


opened and list of available Custom Inspections is
changed.
Note:
 If Metrel ES Manager Work scope is changed,
opened Inspection Data file remains active and
available Custom Inspections remains the same.

275
MI 3155 EurotestXD Appendix G – Tests and Measurements with adapters

Appendix G Tests and Measurements with


adapters

A 1507 3-phase active switch

A 1632 eMobility Analyser

MD 9273 Leakage Clamp


MI 3143 Euro Z 440 V

MI 3144 Euro Z 800 V

meter with Bluetooth


A 1143 Euro Z 290 A

Voltage 1-phase (TN/TT) • - - - - -


1-phase (IT) - - - - - -
3-phase • - - - - -
Socket test basic(live) - - - - - -
Riso 50V – 1000V • - - - - -
2500 V - - - - - -
Riso all - - - - - -
Diagnostic 50V – 1000V - - - - - -
test 2500 V - - - - - -
Varistor - - - - - -
R low • - - - - -
Rlow 4W - - - - - -
Continuity - - - - - -
Ring Continuity - - - - - -
Socket - - - - - -
Rpe • - - - - -
RCD Auto • - - - - -
RCD Uc • - - - - -
RCD t • - - - - -
RCD I • - - - - -
Zs rcd • - - - - -
Z loop • - - - - -
Z loop 4W - - - - - -
Z loop mOhm - • • • - -
Z line mOhm - • • • - -
High Current - - • • - -
Current clamp Meter - - - • - -
Rline mOhm - - - • - -
ELR Current Injection Test - - - • - -
ELR Combination Time Test - - - • - -
Utouch - - • • - -
Z auto • - - - - -

276
MI 3155 EurotestXD Appendix G – Tests and Measurements with adapters

A 1507 3-phase active switch

A 1632 eMobility Analyser

MD 9273 Leakage Clamp


MI 3143 Euro Z 440 V

MI 3144 Euro Z 800 V

meter with Bluetooth


A 1143 Euro Z 290 A
Z line • - - - - -
Z line 4W - - - - - -
Voltage Drop • - - - - -
Earth 3W - - - - - -
Earth 2 clamps - - - - - -
Ro - - - - - -
Power - - - - - -
Harmonics - - - - - -
Currents - - - - - -
IMD - - - - - -
ISFL - - - - - -
Locator - - - - - -
Discharging Time - - - - - -
Illumination - - - - - -
Diagnostic Test (EVSE) - - - - • -
Power CLAMP - - - - - •
Voltage CLAMP - - - - - •
Current CLAMP - - - - - •
Inrush CLAMP - - - - - •
Harmonics U CLAMP - - - - - •
Harmonics I CLAMP - - - - - •

277

You might also like