E291w Handout
E291w Handout
2020
1.4 Types of cathodic protection systems. There are two main types of
cathodic protection systems: galvanic and impressed current. Figure 1-1
shows these two types. Note that both types have anodes (from which
current flows into the electrolyte), a continuous electrolyte from the anode
to the protected structure, and an external metallic connection (wire).
These items are essential for all cathodic protection systems.
Figure 1-1
Galvanic (a) and impressed (b) current systems for cathodic protection
2.1.4 Short circuits. All short circuits must be eliminated from existing and
new cathodic protection systems. A short circuit can occur when one pipe
system contacts another, causing interference with the cathodic protection
system. When updating existing systems, eliminating short circuits would be
a necessary first step.
Table 2-1
Corrosivity of soils on steel based on soil resistivity
2.1.9.1 The second and third methods above can be used on both existing
and new structures.
2.1.9.3 Current requirements also can be estimated from Table 2-2. The
table gives an estimate of current, in milliamperes per square foot, required
for complete cathodic protection. That value, multiplied by the surface area
of the structure to be protected (in square feet) gives the total estimated
current required. Caution should be used when estimating, however, as
under- or overprotection may result.
Table 2-2
Typical current density requirements
for cathodic protection of uncoated steel
mA/SF
Copyright J. Paul Guyer 2017 18
CATHODIC PROTECTION DESIGN
2.1.12 The need for cathodic protection. For existing structures, the
current requirement survey (above) will verify the need for a cathodic
protection system. For new systems, standard practice is to assume a current
density of at least 2 milliamperes per square foot of bare area will be needed
to protect the structure. (However, local corrosion history may demand a
different current density.) In addition, cathodic protection is mandatory for
underground gas distribution lines and for water storage tanks with a 250,000-
gallon capacity or greater. Cathodic protection also is required for
underground piping systems located within 10 feet of steel reinforced
concrete because galvanic corrosion will occur between the steel rebar and
the pipeline.
Copyright J. Paul Guyer 2017 19
CATHODIC PROTECTION DESIGN
Figure 2-2
2.2.1.1 Review soil resistivity. The site of lowest resistivity will likely
be used for anode location to minimize anode-to-electrolyte resistivity.
In addition, if resistivity variations are not significant, the average
resistivity will be used for design calculations.
Table 2-3
Weights and dimensions of
selected high-potential
magnesium-alloy anodes for
use in soil or water
2.2.1.3.1 The potential of iron in contact with soil or water usually ranges
around -0.55 volt relative to copper-copper sulfate. When cathodic protection
is applied using magnesium anodes, the iron potential assumes some value
between -0.55 and - 1.0 volt, depending on the degree of protection provided.
In highly corrosive soils or waters, the natural potential of iron may be as high
as -0.82 volt relative to copper-copper sulfate. From this, it is evident that -
0.55 volt should not be used to calculate the net driving potential available
from magnesium anodes.
Ra = RT – RC (Equation 2-5)
(Equation 2-6)
2.2.2.3 Select anode. As with the galvanic system, the choice of anode is
arbitrary at this time; economy will determine which anode is best. Table 2-4
gives common anode sizes and specifications. The anodes used most often
are made of high-silicon chromium-bearing cast-iron (HSCBCI). When
impressed current-type cathodic protection systems are used to mitigate
corrosion on an underground steel structure, the auxiliary anodes often are
surrounded by a carbonaceous backfill. Backfill materials commonly used
include coal coke breeze, calcined petroleum coke breeze, and natural graphite
particles. The backfill serves three basic functions: (a) it decreases the anode-
to-earth resistance by increasing the anode’s effective size, (b) it extends the
system’s operational life by providing additional anode material, and (c) it
provides a uniform environment around the anode, minimizing deleterious
localized attack. The carbonaceous backfill, however, cannot be expected to
increase the groundbed life expectancy unless it is well compacted around the
anodes. In addition to HSCBCI anodes, the ceramic anode should be
considered as a possible alternative for long-term cathodic protection of water
storage tanks and underground pipes in soils with resistivities less than 5000
ohm-centimeters. The ceramic anode consumption rate is 0.0035 ounce per
ampere-year compared a 1 pound per ampere-year for HSCBCI anodes.
Table 2-4
Weights and dimensions of typical selected circular high-silicon
chromium-bearing cast iron anodes
2.2.2.8 Select area for placement of anode bed. The area with the
lowest soil resistivity will be chosen to minimize anode-to-electrolyte
resistance.
(Equation 2-12)
(Equation 2-13)
(Equation 2-14)
(Equation 2-15)
(Equation 2-16)
Figure 3-1
Current Requirement Test on Pipeline
Copyright J. Paul Guyer 2015 47
4. EXAMPLES OF GALVANIC CATHODIC PROTECTION DESIGN
Figure 4-1
Copyright J. Paul Guyer 2015 49
EXAMPLES OF GALVANIC CATHODIC PROTECTION DESIGN
Underground steel storage tank
(1) Find the minimum weight of anodes required for the tank using
equation 4-I:
Equation 4-1
W= 184.8 lb.
(2) Find the number of magnesium anodes (17 pounds each) required:
Figure 4-2
4.2.2. Computations.
A = 4288 x 0.1
Table 4-1
I = 2 mA x 429 SF
I = 858 mA or 0.858 A.
W = 227 lb
(5) Find the current output to ground for a single 17-pound standard
packaged magnesium anode using equation 4-2:
Because the structure is well coated, anode spacing will be relatively large.
(6) Find the number of anodes (n) required from equation 4-3:
n = 858/26.7 = 32.1
Table 4-2
Dimensions for finding anode division
Figure 4-3
4.3.2 Computations.
(1) Find the total outside area of liquid fuel pipes serving the hydrant
refueling area from lengths and sizes of pipe = 7264 SF
(2) Some experience has shown that steel in this type soil can be
cathodically protected with approximately 1 milliampere per square foot of
uncoated surface. Thus, find the required current based on this value and
using equation 2-1:
I = (A)(I’)(1.0 - CE)
I = (7264 sq ft)(1.0 mA/sq ft)(1.0 - 0.8)
I = 726 mA.
(a) Select a 9-pound anode, 3.5 by 3.5 by 13 inches, from table 2-4.
Driving potential as provided by the manufacturer is 0.9 volt.
RT = ΔE/I
RT = 0.9/0.726 = 1.23 ohms
RC = R/N
RC = (2500 ohms/sf )/7264 sf = .345 ohm
RT = Ra + Rw + Rc
0.89 ohm = Ra
Figure 5-1
Copyright J. Paul Guyer 2015 71
EXAMPLES OF IMPRESSED CURRENT CATHODIC
PROTECTION DESIGN
Steel gas main
(10) The pipe will be coated with hot-applied coal-tar enamel and
will be holiday-checked before installation.
5.1.2 Computations.
I = (A)(I’)(1.0 - CE)
I = 10681 sq ft (2 mA/sq ft)(1.0 - 0.9)
I = 2136 mA,
which agrees with the current requirement test indicated in (13) above.
(4) Calculate the number of anodes needed to meet the anode supplier’s
current density limitations:
(5) Calculate the number of anodes required to meet the design life
requirements:
Ra = (ρK/LN) + (ρP/S)
(7) Select the number of anodes to be used. Since the last calculation
resulted in the largest number of anodes, it will be used. The groundbed
resistance, Ra, using three anodes, would equal 1.86 ohms; to insure
compliance with the manufacturer's limitations, four anodes will be used.
(8) Select an area for anode bed placement. The area of lowest
resistivity will be used, which is 100 feet from the pipeline.
Rw = (ohms/ft)(L)
(11) Select rectifier. Based on the design requirement of 6.2 volts and
2.36 amperes, a rectifier can be chosen from those marketed. After a
rectifier has been chosen, the system's cost can be calculated. A
comparison with other anode sizes and types will yield the most
economical design.
Figure 5-2
(3) Design for 4 milliamperes per square foot of bare metal heating
conduits.
(9) All conduit will be pre-coated at the factory and will not have
been holiday-checked.
5.2.2 Computations.
(1) Find the conduit's total outside area. Because the gage of the
metal from which the conduit is made ranges between 14 and
16, the pipe's outside diameter is considered the same as the
inside diameter.
Table 5-1
Dimensions for finding steam conduit area: heat distribution system
Table 5-2
Dimensions for finding condensate return conduit area:
heat distribution system
A=21,481 x 0.2
A = 4296 sq ft.
I = 4296 x 4
I = 17,184 mA or 17.2 A.
(4) Compute the maximum weight of anode material needed for 15 years'
life.
W = YSI/E
W = (15)(2.0)(17.2)/(0.50) = 1032 lb
Rv = PK/L
Table 5-3
Conduit area: heat distribution system
A = 21,481/41
A = 524 sq ft/anode.
Table 5-4
Anode division: heat distribution system
Figure 5-3
Cathodic protection for
black iron hot water storage tank
5.3.2 Computations.
Figure 5-4
Fringe factor for stub anodes
Copyright J. Paul Guyer 2015 101
EXAMPLES OF
IMPRESSED CURRENT CATHODIC PROTECTION DESIGN
Black iron hot water storage tank
(6) Find the resistance of a three-anode group using an equation
based on equation 2-11:
Rn = (1/N)Rv + ρP/S, where
Rn = total anode-to-electrolyte resistance, N = number of
anodes, Rv = anode-to-electrolyte resistance of a single
anode, P = electrolyte resistivity, P paralleling factor from
manufacturer’s data, and S = spacing between anodes
(feet). Thus,
Rn = (1/3)(98.2) + ((8600)(0.00289))/4 = 38.94 ohms
(8) Locate the rectifier adjacent to tank for the following reasons:
Figure 5-5
Dimensions for an
elevated steel water tank
(1) Find the minimum weight of button anode material required for the tank:
W = YSI/E, where
Y = 15 yr, S = 1.0 lb/ampere-yr, I = 7.0 amperes and E = 0.50, thus
W = ((15)(1.0)(7.0))/0.50 = 210 lb
(2) Compute the number of tank anodes needed (button anodes weight 55 lb):
N = 210/55 = 3.82 (use 4 anodes)
(3) Find the minimum weight of riser anode material required for the
riser:
W = YSI/E, where
Y = 15 yr, S = 1.32X10-5 lb/ampere-yr, I = 1.0 ampere, and
E = 0.50
W = ((15)(1.32X10-5)(1.0))/0.50 3.96 x 10-4 lb
(4) Find the number of riser anodes needed. Platinized titanium wire,
0.1-in diameter, 3-ft long, with 0.001-in thick platinum over titanium
will be used for each anode. The weight of platinum on each anode
is 8.8 x 10-5 pound. Thus,
N = (3.96)(10-4)/(8.8)(10-5) = 4.5 (use 5 anodes)
(5) Locate anodes as shown in figure 5-6.
Copyright J. Paul Guyer 2015 109
EXAMPLES OF
IMPRESSED CURRENT
CATHODIC PROTECTION
DESIGN
Elevated water tank (ice
is expected)
Figure 5-6
Cathodic protection for tanks
using rigid-mounted, button-type
anodes and platinized titanium
wire
• Each button anode has its own No.8 AWG 7-strand copper cable
(HMWPE) run in conduit to a resistor box mounted at eye level on a
tank leg. The riser anode’s one No.4 AWG 7-strand cable is run in
conduit to the resistor box. If required to get proper current output, a
resistor must be installed in the riser anode circuit at the time of
rectifier sizing. The rectifier must be sized after the anodes are
installed and must be mounted at eye level adjacent to the resistor
box.
This impressed current design is for a tank that has not been built;
thus, it is not possible to measure current requirements and other
factors. Calculated estimates are used.
5.5.2 Computations.
(1) Find the area of wetted surface or tank bowl (figure 5-7).
A = 2πrx (approximately), T
where r = 28 feet (tank radius), x = 10 feet. Thus,
A =2 x 3.1416 x 28 ft x 10 ft T
A= 1759 sq ft.
A =2 πrh
where r = 28 feet (tank radius) and h = 11 feet. Thus,
A = 2 x 3.1415 x 28 ft x 11 ft c
A = 1935 sq ft.
Figure 5-7
Segmented elevated
tank for area
calculations
AT + AC + AB = 7588 sf
Ar = 2πrRhR, where rR =riser radius = 2.5 ft, hR = riser height = 115 ft.
W = YSI/E, where
W = ((10)(1.0)(15.2))/0.50 = 304 lb
W = YSI/E, where
W = ((10)(1.0)(3.62))/0.50 = 72.4 lb
Figure 5-8
Anode spacing for
elevated steel water tank
Copyright J. Paul Guyer 2015 120
EXAMPLES OF
IMPRESSED CURRENT CATHODIC PROTECTION DESIGN
Elevated Steel Water Tank
(b) The minimum number of anode units per anode string (N),
based on a required weight of 304 pounds and 10 anode
strings, is computed as follows:
N = 304/(10 x 1)
N = 30.4, use 31 units per string.
This number is not practical for the bowl since the distance
between the anode hanger and tank bottom is only 28 feet. Table
5-5 shows the maximum recommended current discharge per
anode for various types of anodes to insure a 10-year minimum life.
Using a type B anode, three anodes per string are required. The
manufacturer does not recommend more than two type B anodes
per string assembly because the strings are fragile. Therefore, the
best choice of anode for the main anode strings is type C or CDD.
Type CDD is recommended because the lead wire connection is
protected longer by the thicker wall of the enlarged ends. Two type
CDD anodes per string provide a current capacity of 2 amperes 10
strings = 20 amperes. These anodes are spaced as shown in figure
5-9.
Table 5-5
Commonly Used HSCBCI anodes
Figure 5-9
Anode Suspension Arrangement for
Elevated Steel Water Tank
Copyright J. Paul Guyer 2015 125
EXAMPLES OF
IMPRESSED CURRENT CATHODIC PROTECTION DESIGN
Elevated Steel Water Tank
Figure 5-10
Equivalent Diameter Factor for Anodes in a Circle in Water Tank
Copyright J. Paul Guyer 2015 127
EXAMPLES OF
IMPRESSED CURRENT CATHODIC PROTECTION DESIGN
Elevated Steel Water Tank
L/d = (2 x 60)/1.5
R = 3.03 ohms.
(11) In designing an elevated water tank, the need for stub anodes
must be justified.
(a) The main anode radius has been calculated to be 22 feet. The
main anodes are spaced to provide approximately the same
distance from the sides and the bottom of the tank. The main
anodes will protect a length along the tank bottom equal to 1½
times the spacing of the anode from the bottom.
(b) The anode suspension arrangement for the tank being considered
is shown in figure 5-9. It can be seen that stub anodes are required
for this design. Ten stub anodes are spaced equally on a
circumference with a radius of 8 feet in a way shown in figure 5-8.
For smaller diameter tanks, stub anodes may not be required.
Is = 2.0 x 511.3
Is = 1022.6 milliamperes or 1.02 amperes.
(c) The maximum current for the tank bowl is 15.2 amperes.
(a) The electrical conductor to the main anode is wire size No.2 AWG,
rated at 0.159 ohm per 1000 feet, and has an estimated length of 200
feet. Thus, the resistance of the wire, R, is:
R = (200 ft/1000 ft) x .0159 ohm = 0.032 ohm
(a) The electrical conductor to the stub anodes is wire size No. 2
AWG, rated 0.159 ohm/1000 ft, and has an estimated length of 200
ft. Thus –
(d) Find the voltage drop through the stub anodes given that
the rectifier output is 80 volts, the anode current (I) is 1.02
amperes, and the resistance (R) is 9.54 ohms:
E = IR
E = 1.02 A x 9.54 ohms
E = 9.73 V.
(e) Find the total voltage drop in the stub anode circuit.
ET = 0.033 + 9.73
ET = 9.76 V.
P = I2R
P = (1.02)2 x 147.4 = 153.4 W.
R = (0.012P)(log (D/d))/L
L = (0.012P)(log(D/d))/R
L = (0.012)(4000)(log(5/0.166))/12 = 5.92 ft
For proper current distribution in the riser pipe, the anode units
should not be placed too far apart. It is generally considered that
each anode unit protects a length along the riser pipe equal to 1½
times the spacing of the anode from the riser pipe wall. Therefore,
for a riser height of 115 feet, spacing (center of anode to tank wall)
should be 2.5 feet. The riser length protected by one anode is 1.5 x
2.5 = 3.75 feet, so the number of units required is 115/3.75=30.7 or
31 units. To satisfy the maximum anode discharge current for a G-2
anode–
Copyright J. Paul Guyer 2015 140
EXAMPLES OF
IMPRESSED CURRENT CATHODIC PROTECTION DESIGN
Elevated Steel Water Tank
The L/d ratio for the riser anode string is 324/2 or 162; thus
no fringe factor correction is used.
E = IR,
(c) Find the voltage drop in the riser anode suspension cables
for wire No. 2 AWG, 0.159 ohm per 1000 ft rating, and
estimated length 130 ft.
(e) Find the total voltage drop in the riser anode circuit:
(a) Criteria for the variable resistor are the same as given
for the stub anode resistor.
(d) The commercially available resistor that nearest meets the size
requirements is a 750-watt, 50-ohm, 3.87-ampere model. This
rheostat is 10 inches in diameter and 3 inches deep and is fairly
expensive. It will not fit into most rectifier cases. In addition, the
rheostat consumes large amounts of power. This power
generates heat that can damage components inside the rectifier
case unless good ventilation is provided. The problems found
with using a large rheostat can be overcome by using a
separate rectifier for the riser anodes. Although initial cost may
be slightly high, power savings will be substantial and heat
damage will be avoided.
Copyright J. Paul Guyer 2015 145
EXAMPLES OF
IMPRESSED CURRENT CATHODIC PROTECTION DESIGN
Elevated Steel Water Tank
(22) Size the rectifier for the riser.
(23) Find the rectifier d.c. rating for the bowl. Voltage output has been
determined to be 80 volts. Current rating is 15.2 amperes. The
commercially available rectifier that nearest meets the above
requirements is 80 volts, 16 amperes.
(24) Determine wire sizes and types. All positive feeder and suspension
cables (rectifier to anodes) must be No.2 AWG HMWPE insulated copper
cable. To avoid complication, the negative rectifier cable (rectifier to
structure) must be the same size and type (fig 5-11).
Figure 5-11
Elevated Steel Tank Showing
Rectifier and Anode Arrangement
Copyright J. Paul Guyer 2015 147
(25) Discussion of design.
THE QUIZ
a. potentiometer
b. catalyst
c. corrosimeter
d. corrosion cell
a. 0 – 2000 ohm-cm
b. 2000 – 10000 ohm-cm
c. 10000 – 30000 ohm-cm
d. above 30000 ohm-cm
5. The typical range of current density (in mA/sq ft) required for
cathodic protection of an uncoated steel tank in well aerated
neutral soil is:
a. 0.4 to 1.5
b. 2 to 3
c. 1 to 6
d. 3 to 15
a. 0.25
b. 0.5
c. 1
d. 2
a. impressed current
b. sacrificial anode
c. cathode-anode couple
d. any of the above
a. 6
b. 7
c. 8
d. 9
a. 10
b. 11
c. 12
d. 13
a. – 1.45 volts
b. – 1.55 volts
c. – 1.65 volts
d. – 1.75 volts
a. – 1.45 volts
b. – 1.55 volts
c. – 1.65 volts
d. – 1.75 volts
a. copper or zinc
b. zinc or magnesium
c. magnesium or copper
d. any of the above
a. 0 to 5,000
b. 5,000 to 10,000
c. 10,000 to 30,000
d. 30,000 to 100,000
a. cathode
b. ground rod
c. button anode
d. rectifier
a. cathode
b. rectifier
c. electrolyte
d. ground wire
a. rectifiers
b. electrolytes
c. short circuits
d. galvanic cells
a. coating
b. cathode
c. anode
d. electrolyte
20. Studying the corrosion history in the area can prove very
________ when designing a cathodic protection system.
a. helpful
b. misleading
c. difficult
d. easy
a. current
b. voltage
c. pH
d. AIC
a. iron
b. carbon
c. magnesium
d. manganese
a. permanently
b. for 5 years
c. for 25 years
d. for a given number of years
a. -0.85
b. +0.85
c. -1.85
d. +1.85