Submittal Package FTA570F

Limited Option Jockey Pump Controller


Project Information

(DRAWINGS INCLUDED IN THIS PACKAGE ARE FOR STANDARD


CONTROLLERS. ACTUAL “AS BUILT” DRAWINGS MAY DIFFER
FROM THOSE SEEN HERE).

3362 Apex Peakway


Apex, North Carolina 27502
P 919 460 5200
F 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for
damages resulting from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2023
Firetrol, Inc., All Rights Reserved.
Publication SBP570F Rev. A
Firetrol Limited Option Jockey Pump Controller
FTA570F - Full Voltage Starting
Specifications

1.0 Main Fire Pump Controller


The auxiliary jockey pump controller, if required and specified on the plans and spec-
ifications, shall be factory assembled, wired, and tested and specifically designed for
this type of service. This controller shall be of the same manufacturer as the main fire
pump controller.

1.1 Standards, Listings & Approvals


The controller shall conform to all the requirements of the latest editions of:
NFPA 70, National Electrical Code.

The controller shall be listed by:


Underwriters Laboratories, Inc., in accordance with UL508A, Standard for Industrial Controls
Canadian Standards Association CSA-C22.2, Standard for Industrial Control Equipment
(cUL)

1.2 Enclosure
The controller components shall be housed in a NEMA Type 2 (IEC IP22), painted wall
mountable enclosure.

1.3 Withstand Ratings (Short Circuit Current Ratings)


The jockey pump controller shall have standard short circuit current ratings as follows:
VOLTAGE 3-PHASE (50/60
MAX HP SHORT CIRCUIT CURRENT
HERTZ) RATING

1/4-3 HP - 65kA
-H 200 - 208V 7.5
4-7 1/2 HP - 42kA

-A 220 - 240V 10 1/4-3 HP - 65kA


4-10 HP - 42kA
1/4-5 1/2 HP - 65kA
-F 380 - 415V - WYE 15 7 1/2-15 HP - 42kA
1/4-7 1/2 HP - 65kA
-B 440 - 480V - WYE 20
10-20 HP - 42kA

-C 550 - 600V - WYE 1/4-10HP - 10kA


25
15-25 HP - 5kA
VOLTAGE 1-PHASE
MAX HP SHORT CIRCUIT CURRENT
(50/60 HERTZ) RATING

-D 110 - 120V 2 1/4 -1/2 HP- 65kA


3/4-2 HP - 42kA
1/4-2 HP - 65kA
-T 200 -208V 5 3-5 HP - 42kA
1/4-2 HP - 65kA
-E 220 - 240V 5
3-5 HP - 42kA

1.4 Construction
The jockey pump controller shall be full voltage starting, rated for wye-connected power
systems above 240V. The controller shall incorporate a horsepower rated manual cir-
cuit protector and starting contactor, control circuit transformer with 24VAC secondary,
main disconnect switch, and a 0-600 psi (0-42 bar) solid state pressure transducer.

1.5 Operator Interface


The jockey pump controller shall feature an operator interface with user keypad. The
interface shall feature a digital display. The controller shall provide indication of motor
run (manual start and automatic start), and a Hand-Off-Auto Selector Switch. User
settings such as start/stop pressure settings, timer settings and units of measure shall
be programmable from the user interface without opening the enclosure door.
1.6 Solid State Pressure Transducer
The controller shall be supplied with a solid state pressure transducer with a range of
0-600 psi (0-42 bar) ±1 psi. The solid state pressure switch shall be used for both display
of the system pressure and control of the fire pump controller. Systems using analog
pressure devices or mercury switches for operational control will not be accepted.
The START, STOP and SYSTEM PRESSURE shall be visually indicated and adjustable through
the user interface. The pressure transducer shall be mounted inside the controller to
prevent accidental damage. The pressure transducer shall be directly pipe mounted
to a bulkhead pipe coupling without any other supporting members. Field connections
shall be made externally at the controller coupling to prevent distortion of the pressure
switch element and mechanism.

1.7 Controller Operation


A digitally set On Delay (Sequential Start) timer shall be provided as standard. The
controller shall include a Minimum Run Timer to allow the motor to run for a set period
of timer after starting. The timer shall be programmable through the user interface.
The disconnect switch shall be mechanically interlocked so that the enclosure door
cannot be opened with the handle in the ON position except by a hidden tool operated
defeater mechanism. The disconnect switch shall be capable of being padlocked in
the OFF position for installation and maintenance safety.

1.8 Manufacturer
The controller shall be a Firetrol brand.

3362 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2023 Firetrol, Inc., All Rights Reserved.
Publication SP570F-01 Rev. A
Product Description FTA570F

Limited Option Jockey Pump Controllers

• Door mounted pressure display/user inter-


face.
• Rotary style door mounted disconnect handle
with door interlock

NOTE: FTA570F Jockey Pump Controllers are only


available in the voltage/horsepower com-
binations shown below. For other combina-
tions and options, see documentation for
FTA570E series Jockey Pump Controllers.

Description—Firetrol® FTA570F Jockey Pump Con-


trollers are intended for use with fire pump sys-
VOLTAGE 3-PHASE (50/60
tems. They are used for pressure maintenance HERTZ) RATING
MAX HP SHORT CIRCUIT CURRENT

in fire pump installations to prevent unnecessary 1/4-3 HP - 65kA


-H 200 - 208V 7.5
operation of the main fire pump. 4-7 1/2 HP - 42kA

-A 220 - 240V 10 1/4-3 HP - 65kA


4-10 HP - 42kA
Approvals—Firetrol jockey pump controllers are -F 380 - 415V - WYE 15 1/4-5 1/2 HP - 65kA
listed by Underwriters’ Laboratories, Inc., in ac- 7 1/2-15 HP - 42kA

cordance with UL508A, Standard for Industrial -B 440 - 480V - WYE 20 1/4-7 1/2 HP - 65kA
10-20 HP - 42kA
Controls, and CSA, Standard for Industrial Control -C 550 - 600V - WYE 25
1/4-10HP - 10kA
Equipment. They are built to meet or exceed the 15-25 HP - 5kA

requirements of the approving authorities as well VOLTAGE 1-PHASE


(50/60 HERTZ) RATING
MAX HP SHORT CIRCUIT CURRENT
as NEMA and the latest edition NFPA 70, National
1/4 -1/2 HP- 65kA
Electrical Code. -D 110 - 120V 2
3/4-2 HP - 42kA
1/4-2 HP - 65kA
-T 200 -208V 5
3-5 HP - 42kA
Standard Features—The following are included 1/4-2 HP - 65kA
as standard with each controller: -E 220 - 240V 5
3-5 HP - 42kA
• NEMA Type 2 (IEC IP22) Painted Steel Enclosure
• Type F fuseless motor starter and protector NOTE: Firetrol Brand Jockey Pump controllers DO NOT
• Suitable for use as service equipment CONTAIN MERCURY filled pressure switches.
• Hand-Off-Auto Selector Switch
• Minimum run timer
• On-Delay timer For Model # Information and Options &
• Control circuit transformer with 24VAC Modifications see Publication SD570F-01
secondary
• 0-600 psi (0-42 bar) solid state pressure
transducer
• Visual Indication, Start/Stop pressure settings
- System pressure - Motor overload

3362 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2023 Firetrol, Inc., All Rights Reserved.
Publication PD570F-01 Rev. A
Model Number FTA570F
Selection Guide

Limited Option Jockey Pump Controllers

FTA570F JOCKEY PUMP CONTROLLERS


FTA570F-A G - (Example: FTA570F-AG015B-T-BY)

FTA NUMBER OPTIONS & MODIFICATIONS


FTA570F (See other side)
TIMER OPTION
-A With Programmable VOLTAGE 3-PHASE MAX HP
Running Period Timer (50/60 Hertz)
MOTOR CURRENT PROTECTION -H 200-208 Volts 7.5
-G Manual Motor Protector -A 220-240 Volts 10
*Suitable for Use as Service Equipment* -F 380-415V - WYE 15
Short Circuit Current Rating -B 440-480V - WYE 20
See Chart -C 550-600V - WYE 20

VOLTAGE 1-PHASE MAX HP


HORSEPOWER (KW) (50/60 Hertz)
014 - 1/4 HP (.18) 004 - 4 HP (3)
013 - 1/3 HP (.23) 005 - 5 HP (3.7) -D 110-120 Volts 2
012 - 1/2 HP (.37) 006 - 5 1/2 HP (4) -T 200-208 Volts 3
034 - 3/4 HP (.56) 007 - 7 1/2 HP (5.5) -E 220-240 Volts 3
001 - 1 HP (.75) 010 - 10 HP (7.5)
011 - 1 1/2 HP (1.1) 015 - 15 HP (11)
002 - 2 HP (1.5) 020 - 20 HP (15)
003 - 3 HP (2.2) 025 - 25 HP (18.5)

(See Voltage Selection for Maximum


HP/Voltage Combinations)

VOLTAGE 3-PHASE (50/60


HERTZ) RATING
MAX HP SHORT CIRCUIT CURRENT NOTE: For requirements not listed here
(higher short circuit ratings, larger
1/4-3 HP - 65kA
-H 200 - 208V 7.5
4-7 1/2 HP - 42kA horsepowers, options not listed...
-A 220 - 240V 10
1/4-3 HP - 65kA
4-10 HP - 42kA
etc) please refer to documentation
-F 380 - 415V - WYE 15 1/4-5 1/2 HP - 65kA for FTA570E series Jockey Pump
7 1/2-15 HP - 42kA
Controllers.
1/4-7 1/2 HP - 65kA
-B 440 - 480V - WYE 20 10-20 HP - 42kA

-C 550 - 600V - WYE 1/4-10HP - 10kA


25
15-25 HP - 5kA
VOLTAGE 1-PHASE
MAX HP SHORT CIRCUIT CURRENT
(50/60 HERTZ) RATING

1/4 -1/2 HP- 65kA


-D 110 - 120V 2 3/4-2 HP - 42kA
1/4-2 HP - 65kA
-T 200 -208V 5
3-5 HP - 42kA
1/4-2 HP - 65kA
-E 220 - 240V 5
3-5 HP - 42kA
Model Number Selection Guide - Options & Modifications

SPECIAL ENCLOSURES
Option Description
--- Enclosure, NEMA Type 2 (IEC IP22), Painted Steel
-E Enclosure, NEMA Type 4 (IEC IP65), Painted Steel
-F Enclosure, NEMA Type 4X (IEC IP66), #304 Stainless Steel, Brushed Finish
-G Enclosure, NEMA Type 12 (IEC IP54), Painted Steel
-T Enclosure, NEMA Type 3R (IEC IP24), Painted Steel

ANTI-CONDENSATION SPACE HEATERS (power source by others)


Option Description
None
-J Space Heater, 120V Externally Powered with Circuit Breaker & Thermostat
-JKPX Space Heater, 120V Internally Powered with Thermostat & Humidistat in Parallel
-JX Space Heater, 120V Internally Powered with Thermostat
-K Space Heater, 120V Externally Powered with Circuit Breaker & Humidistat
-KX Space Heater, 120V Internally Powered with Humidistat

PRESSURE TRANSDUCERS
Option Description
--- Wetted Parts Including Pressure Sensor, 600 PSI (42 bar), Fresh Water
-D Wetted Parts Including Pressure Sensor, 600 PSI (42 bar), Sea Water

ALARMS
Option Description
-AC Alarm Output Contacts, Pump Operating (2 Sets)
-AM Alarm Output Contacts, Fail To Start
-BW1 Alarm Output Contacts/Visible Indication, Phase Failure/Phase Reversal
-BY Alarm Output Contacts, Pump Overload
-CPL Alarm Output Contacts, Overpressure
-EF1 Alarm Output Contacts, Controller Not In Auto (1 set)
-HV Alarm, Audible
-KH Alarm Output Contacts, Common Alarm
-PE Alarm Output Contacts, Low System Pressure

MISCELLANEOUS
Option Description
-AST Input Terminals, Automatic Start
-NZ Input Terminals, Shutdown Interlock
-S Tropicalization
*Export Packaging available for additional cost

NOTE: For requirements not listed here (higher short


circuit ratings, larger horsepowers, options not
listed...etc) please refer to documentation for
FTA570E series Jockey Pump Controllers.

3362 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2023 Firetrol, Inc., All Rights Reserved.
Publication SD570F-01
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA570F


BUILT TO THE LATEST EDITION OF THE UL 508A
A
DRAWN BY ACD 15/05/23 JOCKEY PUMP CONTROLLER DRAWING NUMBER A
© Firetrol, Inc. Not for construction.
NYC
Dpt of Building
THIRD ANGLE DD570F-001 /E
FINAL Approved
PROJECTION DWG REV. 0
Subject to change without notice. FC 15/05/23
APPROVAL SHEET 1 OF 1

B 12" [305] B

10 1/2" [267] FU1


6 3/4" [170]
Ø3/8" [Ø8] X4

MMP1
XTR1
C C

12" [305]
12 3/4" [323]

D D
C1

PT1
E E

Standard Internal Layout


S
n
C
e
n
Lg
in
osn
in
iect 1/2 " M.NPT

F F
Voltage / Power Table

Voltage Max HP
1 Phase
110 - 120 2
G 200 - 208 5 G

3 7/8" [100] 220 - 240 5

3 Phases
200 - 208 7.5

3 7/8" [100] 220 - 240 10


380 - 400 - 415 15
H H
440 - 480 20
600 25

Notes:
- Standard NEMA: NEMA 2 Drawing for information only.
- Standard Paint: Textured Red RAL 3002. Manufacturer reserves the right to modify this drawing without notice.
I - All Dimensions are in Inches [Millimeters] I
- Use Watertight Conduit and Connector Only. Contact manufacturer for "As Built" drawing.
- Protect Equipment Against Drilling Chips. *Dimensions may change depending on option required. Consult Factory for exact
- Door Swing Equal to Door Width dimensions.
0 1 2 3 4 5 6 7 8
Copyright © 2023 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA570F


DRAWN BY ACD 15/05/23
JOCKEY PUMP CONTROLLER BUILT TO THE LATEST EDITION OF THE UL 508A
A DRAWING NUMBER A
ACROSS THE LINE / 3 PHASES NYC WS570F-003 /E
© Firetrol, Inc. Not for construction. FINAL
Dpt of Building
Approved DWG REV. 0
Subject to change without notice. FC 15/05/23
APPROVAL SHEET 1 OF 1

L1 L2 L3

B G B

MMP1

FU1 XTR1
1L3 2L3 2
H2 X1
C C
1L1 2L1 H1 X2 3

7 A1 A2
N C1
6
RELAY OUT
5
IN1 4

D J11 MMP1 D
3
N
2
24VAC
EARTH
J15

J14

OUT1 OUT2
E E
GND
SIG

OUT1 OUT2 IN2


5V

J4
A1 A2 A1 A2 IN4
J12 J10 J6
MB1
White

IN3
Black
Red

J2
F F
J3
PT1
Pressure Sensor
Type 0.5 - 4.5V IN1 IN2
J1

8 10 9

G G

OFF
H A
SS1

AUTO

H HAND H

C1

I T1 T2 T3 I

P1

0 1 2 3 4 5 6 7 8
Copyright © 2023 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.
0 1 2 3 4 5 6 7 8

BY DD/MM/YY MODEL: FTA570F


DRAWN BY ACD 15/05/23
JOCKEY PUMP CONTROLLER BUILT TO THE LATEST EDITION OF THE UL 508A
A DRAWING NUMBER A
ACROSS THE LINE / 3 PHASES NYC FC570F-003 /E
© Firetrol, Inc. Not for construction. FINAL
Dpt of Building
Approved DWG REV. 0
Subject to change without notice. FC 15/05/23
APPROVAL SHEET 1 OF 1

B B

Power Connections and Motor Connections

3 Phase
Incoming Power
Bonding Ground

C C

L1 L2 L3
MMP1

C1
T1 T2 T3
D D

E E

Line Terminals (L1,L2,L3,GND)


Maximum Motor Horsepower
Wire Size Copper Only Torque Wire Size Ground Copper Only
200-208V 220-240V 380-416V 440-480V 575-600V
7.5HP 10HP 15HP 20HP 25HP #14 AWG - #8 AWG 2.5 Nm #14 AWG - #2 AWG
F F

G G

Motor Terminals (T1,T2,T3,GND)


Maximum Motor Horsepower
Wire Size Copper Only Torque Wire Size Ground Copper Only
200-208V 220-240V 380-416V 440-480V 575-600V
3HP 4HP 5.5HP 7.5HP 10HP #14 AWG - #10 AWG 1.7 Nm #14 AWG - #2 AWG
H 7.5HP 10HP 15HP 20HP 25HP #14 AWG - #8 AWG 2.5 Nm #12 AWG - #2 AWG H

I I

0 1 2 3 4 5 6 7 8
Copyright © 2023 Firetrol Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Firetrol Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Firetrol Inc.