Concealed floor
standing unit
Bluevolution
FNA-A / RXM-R
Designed to be concealed in walls
› C
ombination with split outdoor › Its low height (620mm) enables
units is ideal for small retail, offices the unit to fit perfectly beneath
or residential applications a window
› Ideal for installation in offices, › R
equires very little installation space
FNA-A
hotels and residential applications as the depth is only 200mm
› B
lends unobtrusively with any › High ESP allows flexible installation
interior décor: only the suction
and discharge grills are visible
RXM50-60R
I
W I- F O L
TR
CO N A P P
V IA
Madoka
BRC1H52W
WI-FI ADAPTOR
BRC4C65 AVAILABLE AS
(optional) AN OPTION
FNA-A / RXM-R
Indoor Units FNA25A9 FNA35A9 FNA50A9 FNA60A9
Capacity UK Total Cooling kW 2.54 3.32 4.89 5.86
UK Sensible Cooling kW 1.89 2.26 3.66 4.11
Nominal Cooling kW 2.6 3.4 5.0 6.0
Nominal Heating kW 3.2 4.0 5.8 7.0
Seasonal Efficiency Energy Label A+ A+ A+ A
(EN14825) Pdesign kW 2.6 3.4 5.0 6.0
COOLING SEER 5.68 5.7 5.77 5.56
Annual Energy Consumption kWh 160 209 303 378
Seasonal Efficiency Energy Label A+ A+ A+ A+
(EN14825) Pdesign kW 2.8 2.9 4.0 4.6
HEATING SCOP 4.24 4.05 4.09 4.16
Annual Energy Consumption kWh 924 1002 1369 1547
Air Flow Rate (Cooling) High / Nom / Low m3/sec 0.145 / 0.133 / 0.122 0.145 / 0.133 / 0.122 0.267 / 0.247 / 0.225 0.267 / 0.247 / 0.225
External Static Pressure High / Nom Pa 48 / 30 48 / 30 49 / 40 49 / 40
Dimensions Height mm 620 620 620 620
Width mm 790 790 1190 1190
Depth mm 200 200 200 200
Weight kg 23 23 30 30
Sound Pressure (Cooling) High / Med / Low dBA 33 / 31 / 28 33 / 31 / 28 36 / 33 / 30 36 / 33 / 30
Sound Pressure (Heating) High / Med / Low dBA 33 / 31 / 28 33 / 31 / 28 36 / 33 / 30 36 / 33 / 30
Sound Power (Cooling) dBA 53 53 56 56
Outdoor Units RXM25R9 RXM35R9 RXM50R RXM60R
Dimensions Height x Width x Depth mm 550 x 765 x 285 550 x 765 x 285 734 x 870 x 373 734 x 870 x 373
Weight kg 32 32 49 49
Electrical Details Power Supply 1ph 1ph 1ph 1ph
Maximum Input Current (MCA) A 11.17 11.17 14.43 15.09
Max Fuse Size A 13 13 16 16
Interconnection Wiring Core / Cable Size 3+E / 1.5 3+E / 1.5 3+E / 1.5 3+E / 1.5
Piping Connections Liquid / Gas inches (mm) 1/4 (6.4) / 3/8 (9.5) 1/4 (6.4) / 3/8 (9.5) 1/4 (6.4) / 1/2 (12.7) 1/4 (6.4) / 1/2 (12.7)
Pipework Maximum Length m 20 20 30 30
Maximum Vertical Rise m 15 15 20 20
Precharged to m 10 10 10 10
Additional charge g/m 20 20 20 20
Holding charge kg 0.76 0.76 1.15 1.15
Sound Pressure (Cooling) Nominal dBA 46 49 48 48
Sound Pressure (Heating) Nominal dBA 47 49 49 49
Sound Power (Cooling) dBA 58 61 62 63
Operating Range (Cooling) Min / Max °CDB -10 / 50 -10 / 50 -10 / 50 -10 / 50
Operating Range (Heating) Min / Max °CWB -15 / 18 -15 / 18 -15 / 18 -15 / 18
Air Flow Rate (Cooling) Nominal m3/sec 0.472 0.600 0.777 0.777
Accessories:
Accessory Ref Description Accessory Ref Description
BRP069C81 Wifi adaptor for connection to on-line controller K.RSS Wireless room mounted temperature sensor and receiver
BRC1H52W Wired touch screen remote controller - White (Included as standard) KLIC-DI KNX Interface for Sky Air and VRV systems
BRC1H52S Wired touch screen remote controller - Silver KRCS01-4 Remote room mounted temperature sensor
BRC1H52K Wired touch screen remote controller - Black KRP4A53 and UK.FB2 Unit/group adaptor PCB for remote on/off, status indication and
BRC2E52C Wired simplified remote controller (without auto swing) temperature setting
BRC4C65 Wireless remote controller RS-SE Service and configuration tool for K.RSS
K.CGM Condensing unit guard (1150 x 1150 x 650) RTD-10 and UK.FB2 Enhanced function PCB for Sky Air and VRV. Duty rotation, Lead Lag
K.CGS Condensing unit guard (750 x 1050 x 460) control and heating interlock
K.CWB90-2 Wall bracket (90kg, 500mm support arm) RTD-20 and UK.FB2 Energy control PCB for Sky Air and VRV
K.DT1 Condensate drip tray for use with K.CWB90-2 RTD-NET and UK.FB2 Modbus interface PCB for Sky Air and VRV
UKEPLEN21-993B / 12.21 / Copyright 2021 Daikin
The present leaflet is drawn up by way of information only and
does not constitute an offer binding upon Daikin UK. Daikin UK has
compiled the content of this leaflet to the best of its knowledge.
No express or implied warranty is given for the completeness,
accuracy, reliability or fitness for particular purpose of its content FSC
and the products and services presented therein. Specifications are
subject to change without prior notice. Daikin UK explicitly rejects
any liability for any direct or indirect damage, in the broadest sense, Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC),
arising from or related to the use and/or interpretation of this leaflet. Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing
All content is copyrighted by Daikin UK. validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com
Daikin Airconditioning UK Limited The Heights Brooklands Weybridge Surrey KT13 0NY Tel 01932 879000 daikin.co.uk