Oy eSTiK- Melle (-)
BS 7671:2018+A2:2022
Updated to BS 7671:2018+A2:2022
Tate mre Uthat
O
7
”
+
D
G)
=
oO.
MPublished by the Institution of Engineering and Technology, London, United Kingdom
‘The Institution of Engineering and Technology is registered as a Charity in England & Wales (no. 211014)
and Scotland (no. SCO38698).
mz The Institution of Engineering and Technology is the institution formed by
the joining together of the IEE (The Institution of Electrical Engineers) and
| the IIE (The Institution of Incorporated Engineers).
© 1992, 1995, 1998, 2002, 2004 The Institution of Electrical Engineers
© 2008, 2011, 2015, 2018, 2022 The Institution of Engineering and Technology
First published 1992 (0 85296 537 0)
Reprinted (with amendments) May 1993
Reprinted (with amendments to Appendix 9) July 1993
Reprinted (with amendments) 1994
Revised edition (incorporating Amendment No, 1 to BS 7671:1992) 1995
Reprinted (with new cover) 1996
Revised edition (incorporating Amendment No, 2 to BS 7671:1992) 1998
‘Second edition (incorporating Amendment No. 1 t0 BS 7671:2001) 2002 (0 85296 987 2)
Reprinted (with new cover) 2003
Third edition (incorporating Amendment No. 2 to BS 7671:2001) 2004 (0 86341 374 9)
Fourth edition (incorporating 8S 7671:2008) 2008 (978-0-86341-854-8)
Reprinted (with amendments) October 2008
Fifth edition (incorporating Amendment No. 1 to BS 7671:2008) 2011 (978-1-84919-2873)
Reprinted 2012
Reprinted (with minor corrections) 2013,
Reprinted 2014
Sixth edition (incorporating Amendment No. 3 to BS 7671:2008) 2015 (878-1-84919-887-5)
Reprinted (with minor corrections) 2015,
Seventh edition (incorporating 18th Edition to BS 7671:2018) 2018 (978-1-78561-442-2)
Reprinted (with minor corrections) 2018
Eighth edition (incorporating Amendment No.2 to BS 7671-2018) 2022 (878-I-85953-227-6)
‘This publication is copyright under the Bere Convention and the Universal Copyright Convention. ll
rights reserved. Apart from any fair dealing for the purposes of research or private study, or criticism
or review, as permitted under the Copyright, Designs and Patents Act, 1988, this publication may be
reproduced, stored or transmitted, in any form or by any means, only with the prior permission in writing of
the publishers, or in the case of reprographic reproduction in accordance with the terms of licences issued
by the Copyright Licensing Agency. Enquiries concerning reproduction outside those terms should be sent,
to the publishers at The Institution of Engineering and Technology, Michael Faraday House, Six Hills Way,
Stevenage, SGI 2AY, United Kingdom,
Copies of this publication may be obtained from:
PO Box 96, Stevenage, SGI 2SD, UK
Tel: +44 (0)1438 767328
Ema:
[email protected]
https://electrica.theiet org
While the author, publisher and contributors believe that the information and guidance given in this work
are correc, all parties must rely upon their own skill and judgement when making use of them. The author,
publisher and contributors do not assume any liability to anyone for any loss or damage caused by any
error or omission in the work, whether such an error or omission is the result of negligence or any other
cause, Where reference is made to legislation itis not to be considered as legal advice. Any and all such
liability is disclaimed
Permission to reproduce extracts from British Standards is granted by BSI. No other use of this material
is permitted. British Standards can be obtained in PDF or hard copy formats from the BSI online shop:
https://shop.bsigroup.com/.
ISBN 978-1-83953-227-6 (wiro bound)
ISBN 978-1-83953-229-0 (vitalsource)
‘Typeset in the UK by the Institution of Engineering and Technology, Stevenage
Printed in the UK by A McLay and Company Ltd, Longwood Drive, Forest Farm, Cardiff, CF14 7ZBCooperating organizations
Acknowledgements
Preface
Section 1 _Introduction
1 Scope
12 Building Regulations
13 Basic information required
1.4 Intended departures from BS 7671
Section2 The electrical supply
24 General layout of equipment
2.2. Function of components
2.3 Separation of gas installation pipework from the electrical installation
2.4 Portable generators
Section3 _ Protection
31 ‘Types of protective device
3.2 Protection against overload current
3.3 Protection against short-circuit current and earth fault current
3.4 Protection against electric shock
35 Automatic disconnection
3.6 Residual current devices (RCDs)
3.7 Surge protection devices (SPDs)
3.8 Arcfault detection devices (AFDDs)
Section 4 _Earthing and bonding
4. Protective earthing
42 Legal requirements
43 Main protective bonding
44 Earthing conductor and main protective bonding conductor
cross-sectional areas
45 Main protective bonding of plastic services
46 Supplementary bonding
47 Additional protection — supplementary equipotential bonding
48 Supplementary bonding of plastic pipe installations
49 Earth electrode
4.10 ‘Types of earth electrode
4.11 Typical earthing arrangements for various types of earthing system
Onsite Guide
‘© The Institution of Engineering and Technology
x
13
13
14
7
7
19
19,
2
25
26
33
33
33
34
34
35
36
42
49
53
54
55
57
57
58
59
59
59Section 5 Isolation and switching
5.1 Isolation
5.2 Switching off for mechanical maintenance
53 Emergency switching off
54 Functional switching
55 Firefighter's switch
Section6 _—_Labelling
61 Retention of a dangerous electrical charge
62 Where the operator cannot observe the operation of switchgear and
controlgear
63 Unexpected presence of nominal voltage exceeding 230 V
64 Earthing and bonding connections
65 Purpose of switchgear and controlgear
66 Identification of protective devices
6.7 Identification of isolators
68 Isolation requiring more than one device
69 Periodic inspection and testing
610 Diagrams
6.11 Residual current devices (RCDs)
612 Waming notice: non-standard colours
6.13 Warning notice — altemative supplies
614 Warning notice — high protective conductor current
6.15 Waming notice — photovoltaic (PV) systems
6.16 Warning and user instruction labels
Section 7 Final circuits
a Final circuits
72 Standard final circuits
73 Installation considerations
74 Proximity to electrical and other services
75 Earthing requirements for the installation of equipment having
high protective conductor current
76 Electrical supplies to furniture
7 Trunking installations
78 Additions and alterations
79 Installation and use of non-standard cables
7.10 EMC Directive and compatibility
7.11 Wiring systems in escape routes
Section 8
81 ‘Summary of requirements
82 Shower cubicle in a room used for other purposes
83 Underfloor heating systems
Section 9 —_ Inspection and testing
91 Inspection and testing
92 Inspection
93 Testing
Section 10 Guidance on initial testing of installations
10.1 Safety and equipment
4 | OnSite Guide
© The institution of Engineering and Technology
61
él
62
62
63
63
65
65
65
65
66
66
66
66
66
67
67
68
68
69
70
70
7
B
86
91
8
95
98
98
99
100
100
101
103
103
106
106
107
107
107
109
m
Mm10.2 Sequence of tests
103 Test procedures
Section 11 Operation of RCDs
11.1 General test procedure
112 General-purpose RCCBs to BS 4293 and RCD protected socket-outlets
and fused connection units to editions of 8S 7288 earlier than 2018
113 General-purpose RCCBs to BS EN 61008 or RCBOs to BS EN 61009
and BS EN 62423
114 RCD protected socket-outlets and fused connection units
(FCU) to BS 7288:2016
115 Additional protection
11.6 Integral test device
11.7 Multipole RCDs
Section 12 Prosumer’s electrical installations
121 Prosumer's installations
122 Types of prosumers electrical installation
123 Operating modes
Appendix A Maximum demand and diversity
Appendix B Maximum permissible measured earth fault loop
impedance
Appendix __ Selection of types of cable for particular uses and
external influences
Appendix D Methods of support for cables, conductors and
wiring systems
AppendixE Cable capacities of conduit and trunking
Appendix F _Current-carrying capacities and voltage drop for copper
conductors
Appendix G Certification and reporting
Appendix H Standard circuit arrangements for household and
similar installations
Resistance of copper and aluminium conductors
Selection of devices for isolation and switching
Identification of conductors
Degrees of protection provided by enclosures (IP code)
12
2
127
128
128
128
128
129
129
129
131
131
133
133
135
139
147
153
161
167
179
209
217
221
225
233
235
On-Site Guide | 5
‘© The institution of Engineering and Technologybet TTT Lalit 4
eee
The Institution of Engineering and Technology acknowledges the invaluable contribution
made by the following individuals in the preparation of this Guide:
Institution of Engineering and Technology
J. Bradley BSc CEng FIET FCIBSE
M. Coles BEng(Hons) MIET
G.D. Cronshaw CEng FIET
R. Giddings IEng MIET ACIBSE
We would like to thank the following organi:
British Cables Association (BCA)
BEAMA
British Gas
British Standards Institution (BSI)
Certsure trading as NICEIC
Department for Levelling Up, Housing and
‘Communities (DLUHC)
ECA
Electrical Contractors’ Association of
Scotland (SELECT)
Revised, compiled and edited
M. Doughton lEng MIET LCG!
6 | OnSite Guide
‘© The Institution of Engineering and Technology
G. Gundry MIET
M. Peace CEng MIET MCIBSE
Eur Ing L. Markwell MSc BSc(Hons) CEng
MIET MCIBSE LCG!
S. Devine IEng MIET
ions for their continued support:
NEC Ltd
RINA Tech UK Ltd
Electrical Safety First
Health and Safety Executive (HSE)
NAPIT
The Safety Assessment Federation
(SAFed)ee ri eh
TN-C-S arrangement — 0.35 Q, (see Figure 2.1(i)); and
> TN-S arrangement ~ 0.8 Q, (see Figure 2.1(ii))
NOTE: The values of 0.35 0 and 0.8 © are typical maximum values as quoted by distributors of
electricity upon enquiry which will ad, for example, designs for new-build installations.
Onsite Guide | 13
‘© The Institution of Engineering and Technology1
Table 41.5
542.24
Appx E
For a TT arrangement, 21 © is the usual stated maximum resistance of the
distributor's earth electrode at the supply transformer. The resistance of the
consumer's installation earth electrode should be as low as practicable and
an earth electrode resistance or Z, measurement exceeding 200 may not
be stable due to environmental changes, such as drying out in summer and
freezing in winter.
This Guide also contains information that may be required in general installation work,
for example, conduit and trunking capacities and the bending radi of cables, etc.
‘The Guide introduces the use of standard circuits, which are discussed in Section 7.
However, due to simplification, this Guide may not give the most economical result.
This Guide is not a replacement for BS 7671, which should always be consulted.
Defined terms according to Part 2 of BS 7671 are used.
In compliance with the definitions in BS 7671, throughout this Guide the term line
conductor is used instead of phase conductor and live part is used to refer to a
conductor or conductive part intended to be energized in normal use, including a neutral
conductor.
The terminals of electrical equipment are identified by the letters L, N and E (or PE).
Further information is available in the series of Guidance Notes published by the IET:
> GN 1 Selection & Erection
GN 2 Isolation & Switching
GN 3 Inspection & Testing
GN 4 Protection Against Fire
GN 5 Protection Against Electric Shock
GN 6 Protection Against Overcurrent
GN 7 Special Locations
GN 8 Earthing & Bonding
vvvvvvy
NOTES:
For dlatiication:
> the distributor of electricity is deemed to be: “A party that distributes electricity to consumers
using electrical lines and equipment they own or operate” and
> the supplier of electricity is the organisation from whom electricity is purchased.
1.2 Building Regulations
Refer to the IET publication Electrician's Guide to the Building Regulations for more
in-depth guidance on electrical installations in dwellings.
1.2.1 England: the Building Regulations 2010
Persons carrying out electrical work in dwellings must comply with the Building
Regulations of England, in particular Part P (Electtical safety ~ dwellings).
OnSite Guide
© The institution of Engineering and Technology1
Persons responsible for work within the scope of Part P of the Building Regulations may
also be responsible for ensuring compliance with other Parts of the Building Regulations,
where relevant, particularly if there are no other parties involved with the work. Building
Regulations requirements relevant to installers carrying out electrical work include the
following:
Part Title
A structure
B Fire safety
c Site preparation
and resistance to
contaminants and
moisture
D Toxic substances
Resistance to the
passage of sound
F Ventilation
G Sanitation, hot water
safety and water
efficiency
K Protection from falling,
collision and impact
L Conservation of fuel
‘and power
M Access to and use of
buildings
Pp Electrical safety —
‘dwellings
R Physical infrastructure
for high speed
electronic
communications
networks
Regulation 7 Materials and
‘workmanship.
Examples of relevance to
electrical installers
Depth of chases in walls, sizes of holes and notches in floor
and roof joists
Fire safety of certain electrical installations; provision of
fire alarm and fire detection systems; fire resistance of
penetrations through floors and walls
Moisture resistance of cable penetrations through extemal
walls
Cable jointing compounds, gavaftoid paint, use of solvents
Penetrations through floors, ceilings and walls
Ventilation rates for dwellings
Electic water heating
Electrical means of opening windows
Energy efficient lighting
Mounting heights of switches, socket-outlets ete. and
‘consumer units
All electrical work within dwellings, of which some is notifiable
Installation of data networks and equipment
Implementation of European Regulation 305/2011/EU-CPR
‘covering construction products, referred to as the Construction
Products Regulation (CPR).
NOTE: Guidance is available for each part of the Building Regulations in the form of approved
documents which can be freely downloaded from the Department for Levelling Up, Housing
‘and Communities (OLUHC) website: http://wmw.gov.uk/planning-permission-england-wales
Onsite Guide | 15
‘© The Institution of Engineering and Technology1
1.2.2 The Building (Scotland) Regulations 2004
(as amended)
The detailed requirements are given in the Technical Standards for compliance with the
Building (Scotland) Regulations.
Guidance on how to achieve compliance with these Standards is given in two Scottish
Building Standards Technical Handbooks ~ Domestic and Non-domestic.
These handbooks contain recommendations for electrical installations, covering the
following:
(a) compliance with 8S 7671;
(b) the minimum number of socket-outlets in dwellings;
(©) the minimum number of lighting points in dwellings;
@ the minimum illumination levels in common areas of domestic buildings, for
example, blocks of flats;
(€) the range of mounting heights of switches and socket-outlets, etc.;
(f) separate switching for concealed socket-outlets, for example, behind white
goods in kitchens; and
(8) conservation of fuel and power in buildings.
With regard to electrical installations in Scotland, the requirements of the above are
deemed to be satisfied by compliance with BS 7671
NOTE: The handbooks are available in electronic format only from the Building Standards Division of
the Scottish Government from website: www scotland gov.uk/bsd
1.2.3 The Building Regulations of Northern Ireland
The Building Regulations (Northern Ireland) 2000 (as amended) apply.
NOTE: Information can be obtained from the website: www.buildingcontro-ni.com
1.2.4 The Building Regulations of Wales
On 31st December 2011 the power to make building regulations for Wales was transferred
to Welsh ministers. This means Welsh ministers make any new building regulations or
publish any new building regulations guidance applicable in Wales from that date.
The Building Regulations 2010 and related guidance for England and Wales, including
approved documents as at that date, will continue to apply in Wales until Welsh ministers
make changes to them. The latest update was published July 2018 and information can
be obtained from their website: https://gov wales/building-regulations
16 | OnSite Guide
© The institution of Engineering and Technology3131
5441
312
132.16
1203
I
1.3. Basic information required
Before starting work on an installation that requires a new electrical supply, the installer
should establish the following information with the local electricity distributor:
(a) the number of live conductors required by the design
(b) the distributor's requirement for cross-sectional atea (sa) and maximum
length of the consumer's tails (see NOTE below)
(@) the maximum prospective fault current (Ip) at the supply terminals
(d) the typical maximum earth fault loop impedance (Z,) of the earth fault path
outside the consumer's installation
(€) the type and rating of the distributor's fusible cut-out or protective device
(f) the distributor's requirements regarding the size of main protective bonding
conductors
(g) the conductor arrangement and system earthing; and
(h) the arrangements for the incoming cable and metering.
NOTE: Some distributors will specify a maximum permitted length for consumer's tail. The distributor
may also apply particular requirements for isolation or protection.
For additions and alterations to existing installations, installers should satisfy themselves
as to the suitability of the supply, the distributor's equipment and the earthing and
bonding arrangements.
1.4 Intended departures from BS 7671
Where the designer decides to depart from the requirements of BS 7671, the resulting
degree of safety must not be less than that obtained by compliance with the Regulations.
The designer is responsible for the safety of the design. Any intended departure from the
requirements of BS 7671, although the designer is confident regarding safety, must be
recorded on the Electrical Installation Certificate (EIC). There is a difference between an
intended departure and a non-compliance. Note the following distinction:
(@) an intended departure must be recorded on the EIC
(b) an intended departure not recorded on the EIC is unacceptable, as itis simply
a non-compliance and the certificate would, therefore, be worthless.
Onsite Guide | 17
‘© The Institution of Engineering and Technology18 | OnSite Guide
‘© The Institution of Engineering and TechnologyThe electrical 79
TY
2.1 General layout of equipment
The general layout of the equipment at the service position is shown in Figures 2.1(i) to
2.10), including typical protective conductor cross-sectional areas.
The following scenarios are considered:
(a) Figure 2.1(i) TN-C-S (protective multiple earthing — PME) earthing arrangement;
(b) Figure 2.1(i) TN-S earthing arrangement (cable sheath earth); and
() Figure 2.1(ji) TT earthing arrangement (no distributor's earth provided/used).
V Figure 2.1(i) TN-CS (PME) earthing arrangement
circuit protective _ metal water metal gas
conductors pipe pipe
consumer's tails
notice (see Figure 6.4)
‘gas meter
NOTE: An electricity isolator switch may not always be installed by the distributor.
Onsite Guide | 19
‘© The Institution of Engineering and Technology2
Y Figure 2.1 (ii) TN-S earthing arrangement (cable sheath earth)
rcuitprotecive metalwater metal gs
fonductors "pipe pe
consumer tals
notice (see Figure 6.)
i a
teh
“ST
NOTE: An electricity isolator switch may not always be installed by the distributor.
Y Figure 2.1 iii) TT earthing arrangement (no distributor's earth provided/used)
rcut protective metaluater metal gas
fonducon pipe Pipe
ratce Gee Figue 6)
ON
decry
Testor main swich
‘teh
(ouradand not
protected
LABEL (segue 55)
NOTES:
1 Anelectrcity isolator switch may not always be installed by the distributor.
502.51 2 See Table 4.4(ii for further information regarding the sizing ofthe earthing conductor for a TT
earthing arrangement.
3 See 2.26 for requirements for consumer unit enclosures.
20 | OnSite Guide
‘© The Institution of Engineering and Technology2
2.2. Function of components
2.2
Distributors cut-out
This will be sealed to prevent the fuse being withdrawn by unauthorized persons. When
the consumer's tails and consumer unit are installed in accordance with the requirements
of the distributor, the cut-out may be assumed to provide protection against fault current
up to the consumer's main switch.
As the cut-out is the property of the distributor, installers must not cut seals and withdraw
cut-out fuses without permission. Where removal of the cut-out for isolation is required,
the supplier of electricity should be contacted to arrange disconnection and subsequent
reconnection. Should an installer encounter a distributors seal which has already been
broken or removed it is recommended that this is notified to the person ordering the
work before work commences.
NOTE: The supplier of electricity may not be the same organization as the distributor; (see 1.1).
2.2.2 Electricity meter
The terminals will be sealed by the meter owner to prevent interference by unauthorized
persons,
2.2.3 Meter tails
s2io.1 Meter tails fall into two categories, consumer's tails and suppliers tails. There is a need
to differentiate between the two.
V Figure 2.2.3 Meter tails
consumer's tails
3):
U4
supplier's
tai electricity
isolator main switch
i i switch
OnSite Guide | 21
‘© The instution of Engineering and Technology2
51431
434.30)
522.6,202,
522.6.203,
536.4.201
22
2.2.3.1 Consumer's tails
The cables between the electricity meter and the consumer unit, known as the
consumer's tails, are part of the consumer's installation and should be insulated and
non-metallic sheathed or insulated and enclosed within containment, for example,
conduit or trunking. Consumer's tails are provided by the installer and are the
responsibility of the owner of the electrical installation.
Polarity should be indicated by the colour of the insulation and the minimum cable size
should be 25 mm? The distributor may specify the maximum length of tails between
the meter and the consumer unit in addition to the minimum cross-sectional area
Gee 1.3). In some cases, the distributor may require an electricity isolator switch (ee 2.2.4),
Where the consumer's tails are protected against fault current by the distributor's cut-out,
the method of installation, maximum length and minimum cross-sectional area of the
tails must comply with the requirements of the distributor.
2.2.3.2. Supplier's tails
The cables between the distributor's cut-out and the electricity meter, known as the
supplier's tails, are part of the supplier's equipment.
Where tails are buried in walls or enclosed within the fabric of the building, further
protection is required (Gee 7.3.2).
Itis important that both supplier's and consumer's tails are sufficiently protected from
mechanical damage and disturbance by the use of trunking and/or cable clips; see 2.2.6
of this Guide
2.2.4 Electricity isolator switch
Distributors may provide and install an electricity isolator switch between the meter and
the consumer unit, labelled as ‘electricity isolator switch’ in Figures 2.1()) to 2.1(ii)
and Figure 2.2.3. This double-pole switch permits the supply to the installation to be
interrupted without withdrawing the distributor's cut-out fuse. Where this is the case the
tails between the meter and the electricity isolator are part of the supplier's equipment.
2.2.5 Consumer's controlgear
A consumer unit assembly (to BS EN 61439-3:2012) is for use on single-phase
installations up to 100 A and may include the following components:
(a) a double-pole isolator;
(b) fuses, circuit-breakers or residual current circuit-breakers (with overcurrent
protection) (RCBOs) for protection against overload and fault currents;
(© residual current devices (RCDs) for additional protection against electric shock
(d) RCDs for fault protection;
(e) arc fault detection devices (AFDDs) for additional protection against fire; and
(f) surge protection device(s) (SPDs) where required.
OnSite Guide
© The institution of Engineering and Technology421.1.201
421.1.201
531.3.5.3.2.201
2
Alternatively, a separate main switch and distribution board may be provided.
All devices and components shall only be those declared suitable according to the
assembly manufacturer's instructions or literature. The scope of BS EN 61439-3 includes
distribution boards with an incoming rated current not exceeding 250 A and outgoing
circuits not exceeding 125 A. They are intended to be operated by ordinary persons.
They can be used in domestic and commercial single and three-phase installations up to
100 A within the scope of this Guide.
See IET Guidance Note | and the BEAMA guide: Overload protection of an RCCB or
switch in an LV assembly to BS EN 61439-3.
2.2.6 Consumer unit assemblies
Where a consumer unit assembly is installed in domestic (household) premises one of
the following applies:
» the enclosure is to be manufactured from non-combustible material; or
» the consumer unit is to be enclosed in a cabinet constructed from.
non-combustible material.
Ferrous metal, i.e. steel, is deemed to be an example of a non-combustible material.
Plastic enclosures manufactured from 960 °C degree glow-wire rated material would
not be classified as ‘non-combustible’ in the context of this Regulation.
Where a steel consumer unit is installed in an installation forming part of a TT system, the
earth fault loop impedance, Za, is likely to be much higher than the maximum permitted
for use of the overcurrent protective device (OCPD), i. cut-out, in order to provide fault
protection. Should the consumer's tails become loose or damaged and make contact
with the metal enclosure, it is likely that the overcurrent device will not operate within
the maximum permitted time of 1 s.
The IET's Wiring Regulations Policy Committee, therefore, advises the following:
(@) a Class | metal consumer unit is installed and each outgoing circuit is protected
by an RCBO; and
(b) a split, Class | metal consumer unit is installed, where the double-pole main
switch of the consumer unit should incorporate an S-type (time-delayed)
residual current circuit-breaker (RCCB), for example 100 mA S-type RCCB.
NOTE: in cases where RCBOs protect each outgoing circuit, the risk of the solid busbar (connecting
the supply side of each RCBO) making contact with the ferrous enclosure is minimal. In
split consumer units, where two or three RCCBs protect multiple circuits through individual
circuit-breakers, the risk of the single-insulated conductors (connecting the load side of the
double-pole main switch to the supply side of the RCCBs) making contact with the ferrous
enclosure due to vibration and/or abrasion or being damaged is far higher. In essence, where
the construction and layout of the consumer units such that the risk of live conductors making
contact with the ferrous enclosure is minimal, then the double-pole main switch need not
incorporate an S-type RCCB.
OnSite Guide | 23
‘© The instution of Engineering and Technology2|
Inall cases:
ara24a (a) the consumer's tails need to meet the requirements for the protective measure
sasss220) of double or reinforced insulation throughout their length. This can be achieved
by the use of single-core insulated and non-metallic sheathed cable with the
sheath being kept on the right up to the terminals of the incoming device
(main switch or RCD) of the consumer unit.
522.8.1 (B) the consumer's tails need to be protected to avoid mechanical damage and
disturbance at the incoming terminals in the consumer unit in order to avoid:
(i) the line conductor becoming disconnected and making contact with the
metal enclosure; and
(ii) the incoming terminals becoming loose, which may give rise to arcing
and/or fire.
This can be achieved by, for example, clipping or clamping the consumer's tails,
or by installing them in trunking and the use of a suitable cable entry gland. In all
cable entry arrangements, the enclosure shall not have sharp edges that could
damage cables.
V Figure 2.2.6 Example of clipping tails to arrest movement
Cables dipped at relevant postions ‘cult protective. metal water metal gas
searestmovemers — cnsumer tas conductors. pipe pipe
notice (see Figure 64)
lectricty
Bolter |
‘witch
“TT
supplier’ tlls
42221 (© the cable installation entry method shall, so far as is reasonably practicable,
416.22 maintain the fire containment of the enclosure. It is essential that account is.
taken of the manufacturer's instructions, if any.
This can generally be achieved by the installer ensuring that cable access holes
made in the enclosure do not leave gaps greater than:
(1.0 mm for the horizontal top surface; and
(ii) 2.5 mm for all other surfaces of the enclosure that are accessible after
installation.
24 | OnSite Guide
‘© The Institution of Engineering and Technology522.81
521.5.1
12
The installer could for example, select (as they deem appropriate) trunking,
conduit, cable gland or cable entry accessories to minimize the opening
around the cables.
(d) the consumer's tails also need to be protected to avoid any foreseeable
damage and, where entering a ferrous enclosure, need to do so through the
same entry point.
Anon-combustible enclosure includes the base, cover, door and any components, such
as the hinges, covers, screws and catches necessary to maintain fire containment. Devices
and blanks are contained within the non-combustible enclosure and, therefore do not
have to be manufactured from a non-combustible material, such as steel. However, the
use of non-combustible blanks is not precluded, Any unused ways in the consumer unit
must be closed off using blanks to provide at least IP XXB protection
NOTE: This information on consumer units has been kindly provided by BEAMA. Further information
can be found at: http://www.beama.orguk/en/publications/technical-bulletins.cfm,
Where the consumer unitis to be located in an external, non-habitable building, such as
a garage or shed, which is not in close proximity to a dwelling, consideration could stil
be given to installing a consumer unit of non-ferrous construction. The term ‘not in close
proximity’ is always a moot point and the decision to install a non-ferrous enclosure must
be supported by a documented risk assessment by a skilled person (electticelly), which
must be appended to the Electrical Installation Certificate (EIC).
2.3 Separation of gas installation pi
from the electrical installation
pework
Where gas installation pipework is not separated from electrical equipment or cables
by an insulating enclosure, dividing barrier, trunking, or conduit, the following separation
distances shall be observed:
(a) at least 150 mm away from electricity supply equipment, such as metering
equipment and main service cut-outs or supplier (main) isolation switches and
distribution boards or consumer units; and
(b) at least 25 mm away from electrical switches, sockets and electricity supply
and distribution cables.
The installation pipework shall not be positioned in a manner that prevents the operation
of any electrical accessory, ie. a switch or socket-outlet
NOTE: — Where these spacing requirements are impracticable the pipework should either be sheathed
with an electric insulating material rated at 230 V or more, of a panel of electrical insulating
material should be interposed.
The cited distances are quoted within Clause 8.4.2 of BS 6891:2015+A1:2019
Specification for the installation and maintenance of low pressure gas installation
pipework of up to 35 mm (R1'/.) on premises.
Onsite Guide | 25
‘© The Institution of Engineering and Technology2
©2834 Figure 2.3 Separation from the gas installation
= JE Separation of atleast 25 mm from switches,
' | socket-outlets and supply or distribution cables
‘© Supply cable or
‘dstribution cable
Minima
= distance
150mm
Separation of at least 150 mm from electricity supply equipment.
‘eg. metering equipment, main service cut ots or supplier (main)
‘solation switches and distribution boards or consumer units
°144 2.4 Portable generators
It is recognized that generators will be used occasionally as a temporary or short-term
means of supplying electricity for use, for example:
(a) ona construction site;
(b) on stalls at a street market; or
(©) atan external gathering or function attended by the general public, such as a
country show.
This Guide considers three scenarios relating to the use of portable generators: see 2.4.1
to 2.4.3.
For information relating to the permanent use of generators see IET Guidance Notes
5 and 7 and Section 551 of BS 7671. Further information on the use of temporary
generators is available in the IET Practitioner's Guide to Temporary Power.
Where generators are used to supply mobile or transportable units such as catering vans
or temporary buildings, see also Section 717 Mobile and Transportable Units of BS 7671
and IET Guidance Note 7.
26 | OnSite Guide
‘© The Institution of Engineering and Technology55144
413
anas
2
2.4.1 Electrically separated generator systems
‘The windings of smaller portable generators are often isolated from the mass of Earth
and the protective conductor, i.e. there is no connection between the chassis and/or
earth connection of the socket-outlet(s) of the unit and either of the live conductors
of the generator winding. The ends of the generator winding are brought out to one or
more three-pin socket-outlets which should preferably conform to BS EN 60309-2. The
protective conductor of the socket-outlet(s) is usually connected internally to the frame
of the generator only (see Figure 2.4.1).
The electrical system connected to this type of earthing arrangement is a form of
electrical separation, where basic protection is provided by basic insulation of live
parts or by bartiers and enclosures, and fault protection is provided by simple separation
of the separated circuit from other circuits and from Earth. The requirements for electrical
separation can be found in Section 413 of BS 7671 where one item of equipment is
supplied and Regulation 418.3 where more than one item of equipment is supplied
by the separated circuit. However, the requirements of Regulation 418.3 could prove
difficult or impracticable to meet in a typical application of a portable generator.
It is extremely important to note that a portable generator isolated from earth should
only be used to supply equipment in the following permutations:
a) one or more items of Class Il equipment;
(b) one item of Class | equipment; or
() one or more items of Class Il and one item of Class I equipment.
The supply of only Class Il equipment, however, is preferable.
No more than one item of Class | equipment should be supplied at any time unless
further measures are put in place. This is because first faults will go undetected, putting
users at risk of shock in the event of a second fault (as the users can provide a path for
current flowing between exposed-conductive-parts of faulty electrical equipment).
OnSite Guide | 27
‘© The instution of Engineering and Technology2
Y Figure 2.4.1 Portable generator using electrical separation as the protective measure
=,
TO oad Current-using
ae equipment
Socket-outlet
with overcurrent
protection
Generator
55144 2.4.2 Portable generator used without an Earth electrode
Where a generator is used for a short duration, or is powering a simple system
(eg. a mobile unit), and providing the connecting cables are adequately protected
from mechanical damage, it may not be necessary to connect the system to the mass
of Earth. It is important to ensure that the protective conductor connections of the
socket-outlets at the generator are connected to the neutral of the generator winding in
addition to the chassis or frame of the generator (see Figure 2.4.2). This arrangement is
described as a ‘floating earth’ as the source of supply is not connected to the mass of
Earth.
Such a configuration will provide a retum path for any fault current caused by contact
between live parts and exposed-conductive-parts of the connected equipment, enabling
automatic disconnection of supply (ADS) to be used as the protective measure, as is
common with most installations. If this arrangement is used and the system is not
connected to the mass of Earth, it constitutes a departure from BS 7671 Regulation
4114.1 as Earth does not form part of the fault path.
With this configuration, neither of the live conductors of the generator are connected to
the conductive mass of the Earth. If this method of supply is used, care should be taken
to ensure that there is no intended or casual interconnection with any other electrical
system, such as extraneous conductive-parts or exposed-conductive-parts from other
electrical systems.
As an additional protective measure, distribution circuits supplied from the generator
output should be protected by an RCD operating at no more than 100 mA with a time
delay not more than 200 ms. This is to provide detection of faults caused by unintentional
earthing of the system, such as may occur with Class | equipment in contact with the
mass of Earth (e.g. a metal-framed distribution unit on the ground). The settings will
allow selectivity with other 30 mA RCDs providing Additional Protection on final circuits.
28 | OnSite Guide
© The institution of Engineering and Technology2
Y Figure 2.4.2 Generator with floating earth arrangement
Generator
Line 3
Exposed-conductive-parts
Main protective
bonding conductor(s)
Extraneous-conductive-parts
2.4.3 Portable generator with Earth Electrode
For longer term use, or if there are several circuits supplied by the generator a reliable
connection with Earth is required. Connecting the system to Earth allows for detection
of insulation faults in the distribution - see Figure 2.4.3.
Note that this does not create a TT system; the system will be TN-S from the generator,
with the neutral or star point being connected to the conductive mass of the Earth.
Where an earth electrode is supplied it will need to be tested by the standard method
using a proprietary earth electrode resistance tester; (see 10.3.5.2). Note that an earth
fault loop impedance tester cannot be used for this test as the earth electrode does not
form part of the earth fault loop path
The required value of electrode resistance is determined by the protective devices
on the output of the generator. For example, if a single-phase 8 kVA generator has a
Type C 32 A circuit breaker on the output, in order to disconnect following a distribution
cable insulation fault of negligible impedance to the mass of Earth, a current of
320 A must flow to meet the required disconnection time. At a supply voltage of 230 V
(ote Cmin does not apply) this requires an electrode value of 0.72 Ohms or less. In
practice such a value will be very hard to achieve for a temporary system and so it is
common to use RCDs or Residual Current Monitors to provide ADS.
On-Site Guide | 29
‘© The instution of Engineering and Technology2
In practice the installation of an earth electrode for a temporary system is unlikely to
produce a sufficiently low resistance to enable overcurrent protective devices to operate.
Because of this it is most common to use RCDs or Residual Current Monitors to provide ADS.
choptersa The requirements of BS 7671 Chapter 54 apply. For generator fault currents,
manufacturers advice should be complied with as the ability of a generator to sustain
high fault currents varies.
Y Figure 2.4.3 Generator using earth electrode
Generator
Equipment
<——— Exposed-conductive-parts ———>
Protective conductor
Where restrictions, such as concreted/paved areas or where the portable generator is
being used some distance above ground level, make it impossible to install an earth
electrode and it is not suitable to operate the system un-earthed as described in 2.4.1,
other earthed metalwork may be used, such as metal fencing or structural steelwork.
Connections to street furniture with an electrical installation such as street lighting or
other electrical systems of buildings should be avoided.
«2 2.4.4 Inverter generators
Because traditional engine/alterator generators can suffer stability issues when
powering low-energy loads such as LED lighting, the use of electronic inverter generators
are increasingly common. These have the appearance of being centre-tapped to earth
Gee Figure 2.4.4) and test equipment may not function correctly.
30 | OnSite Guide
© The institution of Engineering and Technology2
Y Figure 2.4.4 Inverter generator configuration,
Inverter Generator
<—— Exposed conductive-parts
Line
Equipment
Main protective
bonding conductor's)
AZNZNZNN
Extraneous conductive-parts
Such arrangements should be treated in the same way as those in 2.4.2 or 2.4.3, though
they may not sustain high fault currents and the requirements of BS 7671 regulation
group 419 may apply.
Onsite Guide | 31
‘© The Institution of Engineering and Technology32 | OnSite Guide
‘© The Institution of Engineering and TechnologyProtection
Types of protective device
The consumer unit (or distribution board) may contain devices providing:
433 (a) protection against overload current;
434 (b) protection against short-circuit current and earth fault current;
au32 (© automatic disconnection in case of a fault (fault protection);
ais (d) additional protection (electric shock protection) by means of 30 mA residual
current devices (RCD(S));
aaag (©) additional protection against fire may also be included (arc fault detection
devices (AFDDs)); and
aa (8) protection against transient overvoltage may be included (surge protection
devices (SPDs)).
Functions (@) and (b) are usually carried out by one device, ie. a fuse or circuit-breaker.
ssa Function (© is usually carried out by the device performing function (b), except where
a high value of earth fault loop impedance makes the use of a fuse or circuit- breaker for
function (©) impracticable (such as a TT system), in which case an RCD has to be used.
sou A residual current circuit-breaker with integral overcurrent protection (RCBO), being a
“unit with a combined circuit-breaker and RCD, will carry out functions (@) to (d).
spends 3.2 Protection against overload current
533.1
Protection against overload current will be provided by the use of any of the following
devices:
{a) fuses to BS 88-2 (BS EN 60269-2), BS 88-3, BS 88-6, BS 136] or BS 3036;
(b) circuit-breakers to BS 3871-1 types 1, 2 and 3;
(©) circuit-breakers to BS EN 60898 types B, C and D; and
(d) RCBOs to the BS EN 61009 series and to BS EN 62423.
NOTE: 8S 5871-1 has been withdrawn and is replaced by BS EN 60898-1:2019; however, these
devices are likely to be present in older installations.
Onsite Guide | 33
‘© The Institution of Engineering and Technology3
3.3 Protection against short-circuit current and
earth fault current
When a consumer unit to BS EN 61439-3:2012 or BS 5486: Part 13 or a fuseboard
having fuse links to BS 88-2 (BS EN 60269-2) or BS 88-6 or BS 1361 is used, protection
against short-circuit current and earth fault current will be provided by that particular
overcurrent protective device (OCPD).
NOTE: BS 5486: Part 13 has been withdrawn; however, consumer units to this standard may still be
found in older installations.
For other protective devices the breaking capacity must be adequate for the prospective
fault current at their point of installation.
3.4 Protection against electric shock
3.4.1 Automatic disconnection of supply (ADS)
411 ADSis the most the common method of protection against electric shock. There are two
“01 elements to ADS: basic protection and fault protection.
912 3.4.1.1 Basic protection
20) Basic protection is the physical barrier between persons/livestock and a live part.
"© Examples of basic protection are:
mea (a) electrical insulation; and
ai62 (b) enclosures and barriers.
s2i01 It follows that single-core non-sheathed insulated conductors must be protected by
conduit or trunking and be terminated within a suitable enclosure.
495.11 A 30 mA RCD may be provided to give additional protection against contact with live
“15.12 parts but must not be used as primary protection.
213 3.4.1.2 Fault protection
0) Fault protection comprises:
aga (a) protective earthing;
asia (b) protective equipotential bonding; and
ana (© automatic disconnection in case of a fault.
Fault protection works by limiting the magnitude and duration of voltages that may appear
under earth fault conditions between simultaneously accessible exposed-conductive-
parts of equipment and between them and extraneous-conductive-parts or Earth.
34 | OnSite Guide
© The institution of Engineering and Technology10.3.3
a4
amas
44a
41444
44a
44s
any
3
3.4.2 Other methods of protection against electric shock
In addition to ADS, BS 7671 recognizes other methods of protection against electric shock.
3.4.3 SELV and PELV
SELV
Separated extra-low voltage (SELV) systems:
(a) are supplied from isolated safety sources such as a safety isolating transformer
to BS EN 61558-2-6 or BS EN 61558-2-8;
(b) have no live part connected to earth or the protective conductor of another
system;
(©) have basic insulation from other SELV and protective extra-low voltage (PELV)
circuits;
(d) have double or reinforced insulation or basic insulation plus earthed metallic
screening from LV circuits; and
(@) have no exposed-conductive-parts connected to earth or to exposed-
conductive-parts or protective conductors of another circuit.
PELV
Protective extra-low voltage (PELV) systems must meet all the requirements for SELV,
except that the circuits are not electrically separated from earth.
For SELV and PELV systems, basic protection need not be provided if voltages do not
exceed those given in Table 3.4.3.
Y Table 3.4.3 SELV and PELV basic protection voltage limits
eeu) Baud
Dry areas 25 VAC or 60V DC
Locations containing a bath or shower, Further protection required at all voltages
‘swimming pools, saunas
3.5 Automatic disconnection
3.5.1 Standard circuits
For the standard final circuits given in Section 7 of this Guide, the correct disconnection
time is obtained for the protective devices by limiting the maximum circuit lengths.
Onsite Guide | 35
‘© The Institution of Engineering and Technology3
Table 41.1
4n5.22
4113.23
Table 41.1
4u.3.22
43.24
5313.3
3.5.2 Disconnection times: TN systems
A disconnection time of not more than 0.4 s is required for final circuits not exceeding:
> 63 Awith one or more socket-outlets; and
> 32 Awhen supplying only fixed equipment.
A disconnection time of not more than 5 s is permitted for:
> final circuits exceeding 32 A, (excluding circuits with socket outlets); and
> distribution circuits.
3.5.3 Disconnection times - TT systems
The required disconnection times for installations forming part of a TT system can,
except in the most exceptional circumstances outside the scope of this Guide, only be
achieved by protecting every circuit with an RCD, hence, a time of not more than 0.2 s
is required for final circuits not exceeding
> 63 Awith one or more socket-outlets; and
> 32 Awhen supplying only fixed equipment.
A disconnection time of not more than 1 s is permitted for:
> final circuits exceeding 32 A, (excluding circuits with socket outlets); and
> distribution circuits.
3.6 Residual current devices (RCDs)
RCD is the generic term for a device that operates when the residual current in the circuit
reaches a predetermined value. The RCD is, therefore, the main component in an RCCB
(residual current operated circuit-breaker without integral overcurrent protection) or
one of the functions of an RCBO (residual current operated circuit-breaker with integral
overcurrent protection).
3.6.1 Types of RCD
Different types of RCD are manufactured and they vary depending on their behaviour in
the presence of DC components and frequencies. The appropriate type of RCD shall be
selected from the following:
(a) RCD Type AC: RCD tripping on alternating sinusoidal residual current, suddenly
applied or smoothly increasing. Type AC RCDs shall only be used to serve
fixed equipment, where it is known that the load contains no DC components.
Examples of fixed equipment containing no DC components include electric
heating appliances and simple filament lighting which does not include
electronic transformers or dimmer controls.
(b) RCD Type A: RCD tripping on alternating sinusoidal residual current and on
residual pulsating direct current, suddenly applied or smoothly increasing.
OnSite Guide
© The institution of Engineering and Technologyana
aus
ass
Appendix 5
4113.30)
ansa
701.4133
701.411.3.3
3
(©) RCD Type F: RCD for which tripping is achieved as for Type A, and in addition:
(i) for composite residual currents, whether suddenly applied or slowly rising,
intended for a citcuit supplied between line and neutral or line and earthed
middle conductor; and
(ii) for residual pulsating direct currents superimposed on a smooth direct
current.
(d) RCD Type B: RCD for which tripping is achieved as for Type F, and in addition:
(i) for residual sinusoidal alternating currents up to 1 kHz;
for residual alternating currents superimposed on a smooth direct current;
for residual pulsating direct currents superimposed on a smooth direct
current;
(iv) for residual pulsating rectified direct current which results from two or
more phases; and
(W) for residual smooth direct currents, whether suddenly applied or slowly
increased, independent of polarity.
For general purposes, only Type A RCDs may be used.
For further guidance on the correct use of RCDs for household and similar use, see
PD IEC/TR 62350 Guidance for the correct use of residual current operated protective
devices (RCDs) for household and similar use.
3.6.2 Protection by RCDs
RCDs are required for:
(@) fault protection where the earth fault loop impedance is too high to meet
the required disconnection time, for example, where the distributor does not
provide a connection to a means of earthing, i.e. TT earthing arrangement,
(b) In AC systems, additional protection by means of an RCD with a rated residual
operating current not exceeding 30 mA shall be provided for:
(i) socket-outlets with a rated current not exceeding 32 A in locations where
they are liable to be used by persons of capability BAI, BA3 or children
(BA2, BA3);
(ii) additional protection for socket-outlets not exceeding 32 A in other
locations; and
(iii) mobile equipment with a rated current not exceeding 32 A for use outdoors
Note 2 to Regulation 411.3.3: RCD protection of all socket-outlets is
recommended.
(© additional protection for lighting circuits in domestic (household) premises;
(d) additional protection for all low voltage circuits serving locations containing a
bath or shower;
(©) additional protection for all low voltage circuits passing through zones 1 and 2
of locations containing a bath or shower but not serving equipment within the
location;
OnSite Guide | 37
‘© The instution of Engineering and Technology3
522.6.202
522.6.203
ans
ana
aus
ans
ass
Note 5
Appendix 2
Item 11
(6) additional protection for cables without earthed metallic covering installed in
walls or partitions at a depth of less than 50 mm and not protected by earthed
steel conduit, earthed trunking or earthed ducting: and
(g) additional protection for cables without earthed metallic covering installed in
walls or partitions with metal parts (not including screws or nails) and not
protected by earthed steel conduit or the like.
Note 4 to Regulation 411.3.3 clarifies those means of connection which are not
considered to be a socket outlet as: “A lighting distribution unit complying with
BS 5733, shaver supply unit complying with BS EN 61558-2-5, luminaire track
system, installation coupler, LSC or DCL is not regarded as a socket-outlet for
‘the purposes of this regulation”.
3.6.3 Omission of RCD protection
3.6.3.1 Specific cases
RCDs for additional protection for socket-outlets not exceeding 32 A in locations other than:
> socket-outlets with a rated current not exceeding 32 A in locations where
they are liable to be used by persons of capability BAI, BA3 or children (BA2,
BAS); and/or
> mobile equipment with a rated current not exceeding 32 A for use outdoors
can be omitted, where @ documented risk assessment determines that RCD protection
is not necessary. The risk assessment must be appended to the certificate issued for the
work. See 3.6.3.2.
Cables installed on the surface do not specifically require RCD protection; however, RCD
protection may be required for other reasons, for example, for fault protection where the
earth fault loop impedance is such that the disconnection time for an overcurrent device
cannot be met.
3.6.3.2 Risk assessment and the omission of additional requirements by
RCDs for socket-outlets
As identified above, BS 7671 permits RCDs, where usually provided for additional
Protection to socket-outlets, to be omitted where a documented risk assessment
determines that the risk to users and those in the vicinity is sufficiently low and, hence,
that RCD protection is not necessary.
The Management of Health and Safety at Work Regulations 1999 puts the responsibility
for carrying out risk assessments onto (as applicable) the persons responsible for the
operations or work activity.
For this situation, the risk assessment needs to be carried out by a skilled person
(lectrically) together with the responsible person and must be appended to the
appropriate Electrical Installation Certificate (EIC).
OnSite Guide
© The institution of Engineering and Technology314
3
The risk assessment should consider the frequency of use, the environment, the
equipment to be connected, the skill level of the person using the equipment and the
socket-outlet and the persons who will have access to the area when the equipment is
in operation, amongst many other factors.
The intention is that the omission of RCDs for additional protection to socket-outlets
should be only as a last resort and certainly not for implementation in domestic premises.
Note that the risk assessment, like all risk assessments, will need to be revisited at
pertinent intervals to assess any change in circumstances, such as change of use, change
of ownership or when a periodic inspection is undertaken and must be appended to the
Electrical Installation Condition Report (EICR).
3.6.4 Applications of RCDs
Installations are required to be divided into circuits to avoid hazards and minimize
inconvenience in the event of a fault and to take account of danger that might arise from
the failure of a single circuit, such as a lighting circuit.
The following scenarios show different methods of providing RCD protection within
installations. Note that, for clarity, earthing and bonding connections are not shown.
3.6.4.1. Examples of RCDs within installations
In each case, refer to 2.2.6 of this Guide.
Y Figure 3.6.4(i) Consumer unit with RCBOs, suitable forall installations (TN and TT)
final circuits
‘30 mA RCBOs:
labelled main switch
“Main switch’ (isolator)
Onsite Guide | 39
‘© The Institution of Engineering and Technology