Water Source VRF Installation Manual
Water Source VRF Installation Manual
WARNING Use the specified cable and connect tightly and clamp the
cable so that no external force will be acted on the
Failure to observe a warning may result in death. The terminal.
appliance shall be installed in accordance with national If connection or fixing is not perfect, it will cause heat-up or fire
wiring regulations. at the connection.
This air conditioner is a comfortable air conditioner, and it When carrying out piping connection, take care not to let
must be installed at indoor, do not place it in the places air substances go into refrigeration cycle.
such as machine room, precise instruments, Otherwise, it will cause lower capacity, abnormal high pressure
food, plants, animals or vertu etc. in the refrigeration cycle, explosion and injury.
Be sure only trained and qualified service personnel to Do not modify the length of the power supply cord or use
install, repair or service the equipment. of extension cord, and do not share the single outlet with
Improper installation, repair, and maintenance may result in other electrical appliances.
electric shocks, short-circuit, leaks, fire or other damage to the Otherwise, it will cause fire or electrical shock.
equipment.
Installation manual
1
Carry out the specified installation work after taking into Young children should be supervised to ensure that they
account strong winds, typhoons or earthquakes. do not play with the appliance.
Improper installation work may result in the equipment falling
and causing accidents. Don't install the air conditioner in the following locations:
The temperature of refrigerant circuit will be high, please There is petrolatum existing.
keep the interconnection cable away from the copper
There is salty air surrounding (near the coast). If this can't be
tube.
avoided, choose a anticorrosive model.
The power cord type designation is H07RN-F. There is caustic gas (the sulfide, for example) existing in the air
Equipment complying with IEC 61000-3-12. (near a hot spring).
If the refrigerant leaks during installation, ventilate the The Volt vibrates violently (in the factories).
area immediately. In buses or cabinets.
Toxic gas may be produced if the refrigerant comes into the
place contacting with fire. In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
After completing the installation work, check that the
refrigerant does not leak. There are inflammable materials or gas.
Toxic gas may be produced if the refrigerant leaks into the
room and comes into contact with a source of fire, such as a There is acid or alkaline liquid evaporating.
fan heater, stove or cooker. Other special conditions.
The insulation of the metal parts of the building and the air
conditioner should comply with the regulation of National
Electric Standard.
The space is too narrow. Because there isn’t enough space
CAUTION for installation and maintenance.
2. CONSTRUCTION CHECKPOINTS
main unit.
Ground the air conditioner. After the machine arrives, check whether it is damaged during
Do not connect the ground wire to gas or water pipes, lightning the shipment. If the surface or inner side of the machine is
rod or a telephone ground wire. Incomplete grounding may damaged, submit a written report to the shipping company.
result in electric shocks.
Check whether the model, specification and quantity of the
Be sure to install an earth leakage breaker. equipment conform to the contract.
Failure to install an earth leakage breaker may result in electric
shocks. After removing the outer package, please keep the operation
instructions well and count the accessories.
Connect the main unit wires , then connect the indoor unit
wires. Water pipeline connection
You are not allowed to connect the air conditioner with the
power source until wiring and piping the air conditioner is done. The pressure endurance of the water system pipelines are
1.96 MPa.
While following the instructions in this Installation manual,
install drain piping in order to ensure proper drainage and The outer conncecting pipelines of the water system should
insulate piping in order to prevent condensation. apply the stainless stell pipes, if not, that may cause corrosion.
Improper drain piping may result in water leakage and property
damage. The cooling water source of the water-ring system should prior
to prefer closed cooling tower. The installer and user should
Install the indoor and main units, power supply wiring and make sure the cool and hot water quality which inlet to the
connecting wires at least 1 meter away from televisions or water system of the unit (details please refer to Part 4-7).
radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 1 meter may not Refrigerant pipe
be sufficient enough to eliminate the noise.
Check the model and name to avoid mistaken installation.
The appliance is not intended for use by young children or
infirm persons without supervision. An additionally purchased refrigerant distributor (manifold
adapter and manifold pipe) must be used for installing the
Young children should be supervised to ensure that they refrigerant pipes.
do not play with the appliance.
Installation manual
2
The refrigerant pipes must have the specified diameter.
Nitrogen of a certain pressure must be filled into the refrigerant
3. ACCESSORIES
pipe before welding.
Table.3-1
The refrigerant pipe must undergo heat insulation treatment.
Name Qty. Outline Function
After the refrigerant pipe is installed completely, the indoor unit
cannot be powered on before performing the airtight test and
Main unit
creating a vacuum. The air-side and liquid-side pipes must 1
installation manual
undergo the airtight test and vacuum extraction.
Main unit
Trial run branch pipes 1
installation manual
Perform the trial run only after the main unit has been powered
on for over 12 hours.
Connective pipe Connect to the side
accessory 1
of liquid pipe
Installation manual
3
4. MAIN UNIT INSTALLATION 4.4 Hoisting Main Unit
Base types
Concrete base (see the figure below for the general making
method)
Main unit
780
Rubber shocking
proof mat Concrete basement
Solid ground h=200mm
Fig.4-1
or roofing
4.3 Selecting installation position 200mm
Ensure that the main unit is installed in a cool place without The master unit’s basement must be made on the solid
direct sunshine exposure or direct radiation of high-temp heat concrete ground . Refer to the structure diagram to make
source. concrete basement in detail, or make after field measurements.
Do not install the main unit in a dirty or severely polluted place, In order to ensure every point can contact equality, the
so as to avoid blockage of the heat exchanger in the main unit. basement should be on completely level.
Do not install the main unit in a place with oil pollution, salt or If the basement is placed on the roofing, the detritus layer isn’t
high content of harmful gases such as sulfurous gas. needed, but the concrete surface must be flat. The standard
concrete mixture ratio is cement 1/ sand 2/ carpolite 4, and add
Φ10 strenthen reinforcing steel bar, the surface of the cement
and sand plasm must be flat, border of the the basement must
be chamfer angle.
Installation manual
4
Centering position illustration of each connective pipe (Unit: mm)
Before construct the unit base, please ensure the base is
directly supporting the rear and front folding edges of the
bottom panel vertically, for the reason of these edges are the R
actual supported sites to the unit.
Please check the affordability of the roofing to ensure the load Electric control box
capacity.
Compressor(after electric
Double-pipe heat exchanger control box )
Fig.4-4
Fig.4-3
Table.4-2 Unit: mm
65
HP
8,10, 12
SIZE
A 650
B 780
112 70 65 80
C 518 Fig.4-5
D 550
Gas side
(8,10HP:Φ25.4;12HP:Φ31.8)
Liquid side
112 70 65 (Units accessories)
(8,10HP:Φ12.7;12HP:Φ15.9)
Oil balancer
93
Gauge point
Detect the pressure/
Refrigerant replenishment
R amplification
Fig.4-6
Installation manual
5
4.6 Main units’ placement sequence &
master and slave units’ settings
Top maintenance space
A system, which provide with more than two main units, will be
set as the followings method: The main units in this system
should place sequentially from the large to the small capacity;
the largest capacity main unit must be mounted at the first
branching site; and set the largest capacity main unit address
as the master Unit, while the other setting as the Slave Unit. ≥100 ≥100
Take 18HP (composed by 10HP, 8HP ) as an example:
Side ventilated Side ventilated
1) Place the 10HP at a side of the first branching site.
and and
2) Place the unit from the large capacity to the small (See the
maintenance maintenance
detail placement illustration).
space space
3) Set 10HP as the master unit, while the 8HP as the aux. unit.
Fig.4-9
Main unit
(18HP)
Back ventilated and Back ventilated and
maintenance space maintenance space
10HP 8HP
Fig.4-7
≥100 ≥100
Side ventilated Side ventilated
and and
4.7 Installation space for main unit maintenance maintenance
space space
Front ventilated and Front ventilated and
Ensure enough space for maintenance. The modules in the maintenance space ≥100 maintenance space
same system must be on the same height.
When installing the unit, leave a space for maintenance. Install Fig.4-10
the power supply at the side of the main unit. For installation
procedure, see the power supply device Installation manual.
≥100 ≥100
Side ventilated Side ventilated
and and
maintenance maintenance
space space
Fig.4-8
Installation manual
6
10) All low positions of the water system should be provided with
5. WATER SYSTEM INSTALLATION drainage valves, to drain water in the heat exchanger of water
side and the system completely; and all high positions should
be supplied with discharge valves, to facilitate expelling air from
5.1 Basic requirements of connection of chilled the pipeline. The discharge valves and drainage valves should
water pipes not be under heat preservation, to facilitate maintenance.
11) All possible water pipes in the system to be chilled should be
under heat preservation.
12) When the unit will be not used for a long time, water inside the
unit should be drained and cut off the power. If the unit is not
CAUTION drained in winter, then the double-pipe heat exchanger and the
water pipes system of the unit might be freezing and cracking
under low temperature.
● After the unit is in place, chilled water pipes can be laid. 13) The rated water flow volume of different models are as follow:
● The relevant installation regulations should be abided with
when conducting connection of water pipes. Table.5-1
● All water pipes must conform to local rules and regulations of Model Rated water flow volume(m3/h)
pipeline engineering.
8HP 5.4
● The size of water pipe should be the same as or larger than the
10HP 6.0
connector size of the unit (DN32).
12HP 7.2
● The heat exchanger of the unit is double-pipe heat exchanger.
There are different operation and maintenance methods
between the double-pipe heat exchanger double-pipe heat
exchanger and the other heat exchangers.
WARNING
Installation manual
7
5.2 Positions of water inlet, outlet and drainage port 5.3 Installation of drainage port connecting pipes
Water inlet condensed water of the main unit out to the suitable place.
Double-pipe heat
exchanger drainage
valve
Fig.5-1
Main unit
chassis drainage port
WARNING
Installation manual
8
System main
5.4 Installation of the main unit water pipelines water return pipe
Air discharging valve
System main
System water return pipe water inlet pipe
Unit water
System water supply pipe
∽
return branch pipe
Y-shape
∽ water filter
~ ↗
∽
∽ Symbols description:
~ ↗
Water flow switch Motorized valve As the above figure 5-6, when horizontal installing the
water system main water inlet pipe and main water return
pipe, the water inlet branch pipe and water return branch
∽ Flexible connection Drainage valve
pipe which connected with the unit must be separate
connected from the vertically lower direction of main water
Fig. 5-4 Main unit side water pipelines connecting figure inlet pipe and main water return pipe; if connected from the
(Recommended) side direction and the top direction will affect the unit
performance.
Installation manual
9
3) When wiring connection is conducted, adjustment of other 6) According to the different water quality the situations of
screws except connection terminals of micro switches and double-pipe heat exchanger and water system pipelines are
ground screws is prohibited. In the meanwhile, over great different. For removing the scale, it is needed to periodically
force should not applied when wires of micro switches are clean the double-pipe heat exchanger and water system
connected, otherwise micro switches may suffer displace- pipelines. It is suggested that set isolating valves in the suitable
ment, thus leading to failure of flow switches. places during water system installation and it is convenient to
4) Special grounding screws should be used for earth connect the cleaning system for cleaning.
connection. Bolts should not be installed or removed at
will; otherwise flow switches may suffer deformation and
failure. 5.6.2 Double-pipe heat exchanger cleaning
5) Flow switches have been set at minimal flow value prior to
Gate valve of unit water return pipe Acid-resistance water pump
ex-factory. They should not be adjusted below the
ex-factory setting value, or they may suffer failure. After
Flow direction
installing flow switches, please press the flow switch lever of liquor
several times to check them. When the lever is found not
to respond with “clatter”, rotate the screw in a clockwise
direction, until “clatter” occurs.
6) Be sure to determine the model of target slice according to
the rated flow of the unit, the diameter of the outlet pipe
and the adjustment range of the target slice of the flow
Isolating valve Cleaning liquor
switch. Besides, the target slice should not contact with Double-pipe
other restrictors in the pipeline or on the inner wall of the heat exchanger
pipeline, or the flow switch cannot be reset normally.
5.5.5 Determine whether the flow switch and the system Gate valve of unit water inlet pipe
connected with it are in good operation according to the Fig.5-8 Cleaning system schematic diagram of double-pipe heat
measured value by flow meter, namely, when the exchanger
measured value on flow meter is less than 50% of rated
water flow of the unit, the water flow controller should 5.6.2.1 Preparation of cleaning liquor
be cut off and observed for 3 working periods, and it
1) The material of water side double-pipe is red copper, and
should be covered with flow switch shell timely.
for general corrosion situation it is suggested that use the
pickle liquor with 5% oxalic acid, 1.2% buffer and 0.8%
Water flow switch surfactant, and the temperature should be controlled in
Gate valve 60°C, that will has prefect cleaning effect.
2) If use hydrochloric acid as the cleaning liquor, for avoiding
to the corrosion and shorten the working life of the heat
exchanger, it should limit the
concentration of the hydrochloric acid to be 3%~5%, and
5D 5D add corrosion inhibitor with 0.2%~0.3% concentration.
When it is cleaning, pay attention to the PH value change,
Fig.5-7 when the PH=8, then stop cleaning immediately. Then
change to fresh water for cleaning.
Installation manual
10
7) After cleaning, close the isolating valve, and take down the Table.5-2
cleaning system devices and keeping properly for backup.
8) Please contact the waste liquor treating company to treat the
collected waste liquor. ITEMS CONCENTRATION (mg/L)
9) Connect the unit water system as the state before cleaning,
thoroughly check the unit and assist devices whether work ≤15,and can not
normally. Make sure there is no abnormal situation then Chromaticity
display other colors
re-operates the unit.
Turbidity NTU ≤1
Smell None
WARNING
Visible objects None
● The cleaning liquor flow direction must be correctly connected. PH Value 7.5~9
● Because different water quality and different using situations of
Total hardness
the heat exchanger, the cleaning period and method will be big ≤200
(Take CaCO3 for calculation)
different, the above method is only for reference.
● The double-pipe heat exchanger is internal thread red copper Fe <0.5
pipe, so that it can not use nitric acid as cleaning agent!
● The cleaning liquor and neutralization will be irritated and AL <0.2
corrosive to human eyes and skin, so please do well protection
Mn <0.1
measurements during the cleaning.
● It is strongly suggested that the user calls for professional Cu <0.2
cleaning company to do component analysis of the water
quality and scale, and make a effective cleaning solution and Zn ≤0.1
method, then do the cleaning. Alkalinity concentration(HCO3 ) -
70~300
2-
Sulfate radical(SO4 ) <70
- 2-
HCO3 /SO4 >1
5.7 System water quality requirements and management Conductivity 10~500 μs/cm(20°C)
NH3 <0.1
5.7.1 The unit water system must select the closed cooling -
tower. CL <100
Chlorine <1
5.7.2 Circulating Chilled Water Processing Design Standard,
other index also should meet with the Table.5.2. H2S <0.05
5.7.3 It should periodically to detect and handle the chilled Free carbon dioxide(CO2) <5
water quality in the water system. When handling the Nitrate radical(NO3-) <100
water, please make sure with the water dealing person
to confirm that use any water scale inhibitor and Suspended matter ≤20
antiseptic agent etc. will not have corrosion to the
stainless steel and copper products. Soluble solid 500~1000
Oxygen consumption
(Take O2 for calculation) ≤3
Ammonium ion(NH4+) <1
Installation manual
11
6. REFRIGERANT PIPE
Note: 1.Reduced length of the branching tube is the 0.5m of the
equivalent length of the pipe.
6.1 Length and drop height permitted of the 2. When the conditions following as table. 6-2 are all meeted,
refrigerant piping the allowable length can extened to 90m.
Table.6-1 Table.6-2
Permitted Piping No. Examples Piping
value Permitted value
L1+(L2+L3+L φ9.52→φ12.7
4+L5+L6+L7+ φ12.7→φ15.9
The size of indoor unit main pipe φ15.9→φ19.1
Total pipe length (Actual)
300m L8+L9)×2+a+ shoud be bigger than the indoor unit
L2~L9 need to increase φ19.1→φ22.2
(Note1) b+c+d+e+f+g+ aux. pipe. The indoor unit main pipe
the pipe diameter . φ22.2→φ25.4
1 needn't increase when it is equal to φ25.4→φ28.6
h+i+j main pipe . φ28.6→φ31.8
φ31.8→φ38.1
Actual length 120m L1+L5+L8 φ38.1→φ41.3
Maximum
piping (L1) +L9+j
Equivalent length 150m 2
The length of indoor unit aux. pipe is
a,b......j ≤ 40m .
no longer than 40m.
Piping (farthest from the first line
pipe branch) equivalent length(L2)
40m(90m,Note2) L5+L8+L9+j The distance difference between If the farest indoor unit is Reference Fig.6-1 .
[the main unit to the farthest in- N10, the nearest indoor u-
3 nit is N1, i.e.(L1+L5+L8+
door unit] and [the main unit to
Indoor unit- Main unit up H=50m the nearest indoor unit] is ≤40m. L9+j)-(L1+L2+L3+a)
main unit ≤40m.
drop height Main unit down H=40m
N1
Drop height between indoor unit and main unit H≤50m
N2
Main unit
(one or more main units)
a b
C
Indoor unit
L5 (From the first line branch pipe) Maximum piping equivalent length L2≤40m
N5 N6
e f
L6
E F G N7
L7 g
L8
L9 I
H
h i j
N8 N9
N10
Fig.6-1
>300mm
>300mm Fig.6-2
CAUTION
1. Indoor units should be placed as equally as possible at the both sides of the U-shape branch pipe.
2. When the main unit is over 20m from the above places, it is recommended to set a return oil bending every 10m of the air
pipe in the main pipe, the return oil bending specification is as Fig. 6-2.
Installation manual
12
6.2 Select the refrigerant piping type
N1 N2
(71) (71)
a b
C
L3
B D
L4 d
c
G1 L2 N3 N4
M L A (71) (71)
M L1
g1 g2 g3
N5 N6
L5 (71) (71)
e f
L6
E F G N7
L7
L8 g (71)
L9 I
W3 W2 W1 H
i j
(8) (8) (10) h
N8 N9 N10
(140) (56) (71)
Fig.6-3
Table.6-3
6.4 Size of joint pipes for main unit
Pipe name Code (As per the Fig. 6-2) Base on the following tables, select the diameters of the main unit
Main pipe connective pipes. In case of the main accessory pipe large than
L1
the main pipe, take the large one for the selection.
Indoor unit main pipe L2~L9
Example: parallel connect with the three main units 10+10+8 (the
Indoor unit aux. pipe a, b, c, d, e, f, g, h, i, j total capacity is 28HP), all indoor units total capacity is 812,
provided that the equivalent length of all pipes are ≥90m, accord-
Indoor unit branching pipe assembly A, B, C, D, E, F, G, H, I ing to the Table 6-6 the main pipe diameter areΦ31.8/Φ22.2; in
according to all indoor unit capacity 1360, we could find out the
Main unit branching pipe assembly L, M master unit diameter isΦ31.8/Φ19.1 base on Table 6-3. Take the
large one for the selection, we final confirm the main pipe diameter
Main unit connective pipe g1, g2, g3, G1 isΦ38.1/Φ22.2.
6.3 Size of joint pipes for indoor unit When the equivalent length of all liquid
Model pipes < 90m, the size of main pipe(mm)
Table.6-4 Size of joint pipes for 410A indoor unit Gas side Liquid side The 1st branching pipe
Installation manual
13
Table.6-6 Size of joint pipes for 410A main unit Table.6-9 Main unit multi-connective pipe assembly
6) The main pipe L9 with N9, N10 downstream indoor units that
total capacity is 56×2=112, the pipe L9 diameter is Φ15.9/Φ9.5,
thus select FQZHN-01D for the branching pipe I.
Installation manual
14
7) The main pipe L8 with N8~N10 downstream indoor units that 6.9 Gas tight test
total capacity is 112+56×2=224 the pipe L8 diameter isΦ19.1/Φ
9.5, thus select FQZHN-01D for the branching pipe H.
1) Upon set up the indoor unit pipeline, please connect the
8) The main pipe L5 with N5~N10 downstream indoor units that Hi-pressure pipe with shut-off valve firstly.
total capacity is 112+56×3+71×2=366, the pipe L5 diameter isΦ
28.6/Φ12.7, thus select FQZHN-03D for the branching pipe E. 2) Weld the pipe at the low pressure side to the meter
connector.
9) The main pipe A with N1~N10 downstream indoor units that
total capacity is 56×3+71×6+112=706, thus select FQZHN-03D 3) Use the vacuum pump discharging air inside the liquid side
for the branching pipe A. shut-off valve and meter connecter, until to the -0.1MPa.
C Main pipe (Refer to Table 6-4, Table 6-5, Table 6-6): 4) Close the vacuum pump, charge 3.9MPa nitrogen gas from
Main pipe L1 in the Fig.6-2, which upstream main units total the piston of shut-off valve and from the meter connector.
capacity is 10+8+8=26HP, base on table 6-5, the gas/liquid pipe Pressure inside should be maintained at there no less than
diameter areΦ38.1/Φ22.2, total capacity of the downstream 24 hrs.
indoor unit is 56×3+71×6+112=706, base on table 6-4, the
gas/liquid pipe diameter areΦ31.8/Φ19.1, take the large one for
your selection, final confirm the main pipe diameter is: gas/liquid Gas pipe Indoor unit
pipeΦ38.1/Φ22.2.
Installation
plate of valve Liquid pipe
D Parallel connect the main units
Nitrogen
1) The main unit linked by Pipe g1 is 8HP, parallel connects with Nitrogen
main unit. the connective pipe diameter to be selected accord-
ing to its connector size isΦ25.4/Φ12.7, Gas side of
The main unit linked by Pipe g2 is 8HP, parallel connects with shut-off valve
main unit. the connective pipe diameter to be selected accord- Liquid side of
ing to its connector size isΦ25.4/Φ12.7, shut-off valve
The main unit linked by Pipe g3 is 10HP, parallel connects with
main unit. the connective pipe diameter to be selected accord- Fig.6-5
ing to its connector size isΦ25.4/Φ12.7.
N1 N2
(71)
(71)
a b
C
L3
B D
L4 d
c
G1 L2 N3 N4
M L A (71) (71)
M L1
g1 g2 g3
N5 N6
L5 (71) (71)
e f
L6
E F G N7
L7
L8 g (56)
W3 W2 W1 L9
H I
(8) (8) (10) i j
h
N8 N9 N10
(112) (56) (56)
Fig.6-4
Installation manual
15
6.10 Vacuum with vacuum pump 6.12 The Installation key points of connective
pipes between main units
1) Use the vacuum pump which vacuum level lower than
-0.1MPa and the air discharge capacity above 40L/min. 1) Connect the pipes between main units, the pipes should
place horizontally (Fig.6-7,Fig.6-8), it is not allow the concave
2) The main unit is not necessary to vacuum, don’t open the at junction site and set longer than 200mm bending pipes for
main unit gas and liquid pipe shut-off valves. saving oil.
3) Make sure the vacuum pump could result as -0.1MPa or 2) All connective pipes between the main units are not allowed
below after 2 hrs or above operation. If the pump operated 3 to over than the height of every outlets of the pipes(Refer to
hrs or above could not achieve to -0.1MPa or below, please Fig.6-9, Fig.6-10).
check whether water mix or gas leak inside of the pipe.
At least 200mm
Connect with vacuum pump
Connect to
Perform the pump (last for 2 hrs or above) the indoor unit
CAUTION
Don’t mix up the different refrigerants or abuse the tools and √ Correct way Fig.6-8
measurements which directly contact with refrigerants.
Table.6-11
Pipe size on Refrigerant to
Down slope the
liquid side be Added per meter pipeline connection
Φ6.4 0.022kg
Connect to
Φ9.5 0.057kg the indoor unit
Φ12.7 0.110kg
Φ15.9 0.170kg
Φ19.1 0.260kg
Φ22.2 0.360kg
Φ25.4 0.520kg
Φ28.6 0.680kg × Wrong way Fig.6-10
Installation manual
16
3) The branching pipe must be installed horizontally, error angle 7. ELECTRIC WIRING
of it should not large than 10°. Otherwise, malfunction will be
caused. 7.1 Sw1 query instructions
Table.7-1
A 1 0,1,2,3
Main unit address
17 Actual value
Current 2 of inverter compressor
26 -- Check end
Installation manual
17
The display contents as followings:
1) Normal display:When in standby, it displays the qty. of indoor
units that can communicate with the main unit .When it is
operating , it will display the rotation frequency of the L1 L2 L3
compressor.
2)Operation mode: 0—OFF/Fan, 2—Cooling, 3—Heating(Cooling
only type without), 4—Constraint cooling.
3)Water flow switch state: 0—Open,1—Close.
4) Priority mode : 0—Heating Priority Mode, 1—Cooling Priority XT1 Powerline terminal
220V 3~ 60Hz
Mode, 2—Priority Mode, 3—Only Respond The Heating Mode, Fig.7-2
4—Only Respond The Cooling Mode.
5) EXV opening angle: pulse count=display value×8.
6) ENC1: Main unit address setting switch,
ENC2: Main unit capacity setting switch,
ECN3: Network address setting switch,
S10, ENC4: combination setting the qty. of the installed indoor
units.
SW1:Query button;SW2:Constraint cooling.
Communication
switching plate
Main units Digital Indoor units Indoor units Main units
XT1 powerline central monitor kilowatthour central communi- communi-
terminal meter monitor cation bus cation bus
Fig.7-5
Grounding
terminal
WARNING
Installation manual
18
7.3 Explanation of main board
Fig.7-6
Installation manual
19
Explanation of main board S1 definition
S1 Starting time is set about 10
Table.7-2 ON
minutes
No. Content
1
1 Reserve S1 Starting time is set about 12
2 Reserve ON
minutes (Default the Factory
3 Air discharge temp. sensed port 2 of inverter compressor
1 Set)
4 Air discharge temp. sensed port 1 of inverter compressor
28 Reserve S6 definition
29 ON/OFF singnal input port for water flow switch
30 Input port of water outlet temp. sensor 1 and sensor 2 Automatic search address.
31 C phase power supply
Reserve
Fig.7-7
Reserve
Installation manual
20
S10 definition
S10
CAUTION
Combined with ENC4 to set the qty.of
Set refrigerant piping system, signal wires between
the indoor unit to be 1-15 indoor-indoor unit, and that between main-main unit into one
system.
S10
Combined with ENC4 to set the qty.of Power must unified supply to all indoor units in the same
the indoor unit to be 16-31 system.
S10 Please do not put the signal wire and power wire in the
Combined with ENC4 to set the qty.of same wire tube; keep distance between the two tubes.
the indoor unit to be 32-47 (Current capacity of power supply: less than 10A--300mm,
less than 50A--500mm.)
S10
Combined with ENC4 to set the qty.of Make sure to set address of main unit in case of parallel
the indoor unit to be 48-63 multi-main units.
S11 definition
Reserve
NOTE
Please shut off the power when setting the switch.
Fig.7-8
Indoor power supply
Indoor power
Leakage protector
1 2 3 4 5 6 7 8
Indoor unit
9 10 11 12 13 14 15 16
Fig.7-9
Installation manual
21
7.6 Electric parameter form of outdoor unit
Table.7-3
Notes:
1.The current value of combination unit is the total value of each basic model(refer to Table.7-3)
2. RLA is based on the following conditions, Indoor temp. 27°C DB/19°C WB, Outdoor temp. 35°C DB
5. Voltage range units are suitable for use on electrical systems where voltage supplied to unit terminals
8. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth circuit breaker).
Remark:
MCA: Min. Current Amps. (A) TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A) MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A) OFM:Outdoor Fan Motor.
FLA: Full Load Amps. (A) KW: Rated Motor Output (KW)
Installation manual
22
7-9-2 Water pump ON/OFF signal wiring
7.7 Control system and Installation
Each unit has configured a dry contact terminal for central
The control line should be shielded wire. Using other wiring control of the water pump (see Fig.7-13),this terminal can
not be connected to power terminal of the water pump
shall create signal interference.
directly, only should be connected to the control terminal of
the water pump stater.
When the water pump ON/OFF signal wire has been
The shielded nets at the two sides of shielded wires are
connected to strong current, it shoud be wired the signal
either grounded to the earth, or connected with each other wires along with other strong current wires; when it has been
and jointed to the sheet metal along to the earth. connected to week current, it shoud be wired the signal
wires along with the week current wires.
Control wire could not be bound together with refrigerant When the water pipeline has a single system, the water
pipeline and power wire. When power wire and control wire pump ON/OFF signal wire should be connected
is distributed in parallel form, keep gap between them above to the XT3 terminals in the main unit electric control box.
300mm so as to preventing signal interference. When the water pipeline has several systems, the
water pump ON/OFF signal should be controlled by the main
Control wire could not form closed loop. unit centralized controller. The wiring of main unit centralized
controller see the Fig.7-15.
Control wire has polarity, so be careful when connecting.
NOTE
The shield net should be grounded at the wiring terminal
of main unit. The inlet and outlet wire net of indoor
communication wire should be connected directly and
could not be grounded, and form open circuit at the shield
net of final indoor unit.
XT2 XT3
XT2 XT3
Installation manual
23
Main unit Main unit Main unit
(master unit) (slave unit) (slave unit)
(H1 H2 E)
(P Q E)
(H1 H2 E) (H1 H2 E)
(P Q E)
Signal wire of
indoor/main units
group control
matching
P
resisitor
Q (open)
Fig.7-12
Installation manual
24
Main unit Main unit Main unit
(master unit) (slave unit) (slave unit)
(K1 K2 E)
(K1 K2 E) (K1 K2 E)
P P amplification
PUMP
(K1 K2 E)
~
Water pump starter
Fig.7-13
L
Water pump
N
CAUTION
2
The signal wire of the main unit centralized controller should apply three-core shielding wire (larger or equal to 0.75mm ), and has
polarity. It should be correctly connected.
Installation manual
25
7.10 Example for power wire connection
7.10.1 A water circuit for single system wiring
L1 L2 L3
Branch box
Main unit (master unit) Main unit (slave unit) Main unit (slave unit)
L N P Q E A B C D E L N P Q E A B C D E L N P Q E A B C D E
Fig.7-14
Installation manual
26
7.10.2 A water circuit for several systems wiring
L1 L2 L3
Branch box
Branch box
Main unit (master unit) Main unit (slave unit) Main unit (slave unit)
Signal wires
between main unit
Connect to water flow Connect to water flow switch terminals Connect to water flow switch terminals
switch terminals
Signal wires between indoor unit and main unit
L N P Q E A B C D E L N P Q E A B C D E L N P Q E A B C D E
Branch box
main unit
Main unit (master unit) Main unit (slave unit) Main unit (slave unit) centralized controller
L N P Q E A B C D E L N P Q E A B C D E L N P Q E A B C D E
connecting wires
Branch Branch Branch betwee indoor units
box box box and wired controllers
power wires
between indoor units
A B C D E A B C D E A B C D E
Fig.7-15
Installation manual
27
8. TRIAL RUN 8.3 Fill the name of connected system
8.1 Inspection and confirmation before To clearly identify the connected systems between two or
commissioning more indoor units and main unit, select names for every
system and record them on the nameplate on the main
1) Check and confirm that refrigeration pipe line and
electric control box cover.
communication wire with indoor and main unit have been
connected to the same refrigeration system. Otherwise,
operation troubles shall happen.
6) Confirm whether the system to debugging has been carried 1) This air conditioner adopts R410A as refrigerant, which is
out vacuum drying and packed with refrigeration as safe and noncombustible.
required.
2) The room for air conditioner should be big enough that
7) Make sure all the water pipelines are correct, including the refrigerant leakage can not reach the critical thickness.
installation directions of water filter and water flow switch. Besides this, you can take some action on time.
8) Check whether the water filter has been blocked, and clean 3) Critical thickness-----the max thickness of Freon without
the filter screen. If it is seriously blocked, then it should be any harm to person. R410A critical thickness:0.3 [ kg/m3]
checked whether the water quality has meet the
requirements.
10) Check whether the pressure meters in the water inlet and
Indoor unit
water return pips of the unit, thermometer, water flow Main unit
switch etc. work normally, and make sure the water
pipelines system operate normal, and the water flow is
Room full of leaking refrigerant
suitable.
(All the refrigerant has leaked)
8.2 Preparation before debugging
Fig.8-2
4) Record the setting address code on the system plan. Calculate the indoor cubage (B[m3]) (as the minimum
cubage)
5) Turn on power switches main unit in advance, and keep
connected for above 12 hours so that heater heating up Calculate the refrigerant thickness.
refrigerant oil in compressor.
A [ kg]
6) Turn on air pipe stop valve, liquid pipe stop valve, oil B [ m3] ≤ Critical thickness:0.3 [kg/m3]
balance valve and air balance valve totally. If the above
valves do not be turned on totally, the unit should be 5) Countermeasure against overhigh thickness
damaged.
Install mechanical ventilator to reduce the refrigerant
7) Check whether the power phase sequence of main unit is thickness under critical level. (ventilate regularly)
correct.
Install leakage detector alarming device related to
8) All dial switch to indoor and main unit have been set mechanical ventilator if you can not regularly ventilate.
according to the Technical Requirement of Product.
Installation manual
28
b. Leakage detector alarming device
related to mechanical ventilator
Indoor unit
OA
a:Ventilation peristome
Fig.8-3
Installation manual
29
9. CUSTOMER DETAILS
……………………………………………………………
……………………………………………………………
Telephone : ……………………………………………………………
……………………………………………………………
……………………………………………………………
Telephone : ……………………………………………………………
……………………………………………………………
In all correspondence/communication state your name, address, the serial number of your air
conditioning unit, date of purchase and dealer’s name (include address), location of unit and
description of problem, for prompt and immediate attention
Address : ……………………………………………………………
……………………………………………………………
……………………………………………………………
Invoice No : ……………………………………………………………
Installation manual
30
2020001C1098 V1.0