0% found this document useful (0 votes)
175 views4 pages

Olex XLPE Single Core Cu 500mm2

This document provides specifications for an XLPE single core copper cable. It includes details such as: - The cable has a 500mm2 copper conductor, XLPE insulation, and PVC sheathing. - Key standards that apply are AS/NZS 1125 and AS/NZS 5000.1. - Electrical characteristics include a rated voltage of 0.6/1kV and insulation resistance of 190 MOhm.km. - Dimensional details like a nominal diameter of 37.0mm and weight of 491.0kg/100m are provided. - Current carrying capacity tables for single phase use with a copper conductor and 90C maximum temperature are included.

Uploaded by

Naufal Malbar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
175 views4 pages

Olex XLPE Single Core Cu 500mm2

This document provides specifications for an XLPE single core copper cable. It includes details such as: - The cable has a 500mm2 copper conductor, XLPE insulation, and PVC sheathing. - Key standards that apply are AS/NZS 1125 and AS/NZS 5000.1. - Electrical characteristics include a rated voltage of 0.6/1kV and insulation resistance of 190 MOhm.km. - Dimensional details like a nominal diameter of 37.0mm and weight of 491.0kg/100m are provided. - Current carrying capacity tables for single phase use with a copper conductor and 90C maximum temperature are included.

Uploaded by

Naufal Malbar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Contact

XLPE Single Core Cu OLEX CUSTOMER SERVICE - Purchase


orders, invoices, general enquiries
XLP 1X500 PC XLPPVC Phone: 1300 CABLES
[email protected]

Nexans ref.: BDBP30AA001CXNA


GTIN: 9319215277355

500mm2 XLPE / PVC Black

DESCRIPTION
• Single core, 0.6/1kV X-90 insulated,
• PVC sheathed to AS/NZS 5000.1,
• Copper or aluminium conductors, 90°C.

Mains; Submains

STANDARDS
National AS/NZS 1125; AS/
NZS 5000.1

Rated Voltage Uo/U (Um) Cable flexibility


0.6/1 kV Rigid

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 10/12/20 www.olex.com.au Page 1 / 4
Contact
XLPE Single Core Cu OLEX CUSTOMER SERVICE - Purchase
orders, invoices, general enquiries
XLP 1X500 PC XLPPVC Phone: 1300 CABLES
[email protected]

CHARACTERISTICS
Construction characteristics
Conductor material Copper
With Green/Yellow core No
Colour Black
Outer sheath PVC
Type of conductor Stranded copper
With smaller neutral conductor No
Insulation X-90
Dimensional characteristics
Nominal outer sheath thickness 2.0 mm
Nominal insulation thickness 2.2 mm
Nominal overall diameter 37.0 mm
Approximate weight 491.0 kg/100m
Conductor cross-section 500 mm²
Number of cores 1
Electrical characteristics
Max. DC resistance of the conductor at 20°C 0.037 Ohm/km
Conductor AC resistance at 50 Hz 0.051 Ohm/km
Inductive reactance at 50Hz - trefoil 0.08 Ohm/km
Inductive reactance at 50Hz - flat touching 0.095 Ohm/km
Insulation resistance at 20°C 190.0 MOhm.km
Rated Voltage Uo/U (Um) 0.6/1 kV
Mechanical characteristics
Cable flexibility Rigid

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 10/12/20 www.olex.com.au Page 2 / 4
Contact
XLPE Single Core Cu OLEX CUSTOMER SERVICE - Purchase
orders, invoices, general enquiries
XLP 1X500 PC XLPPVC Phone: 1300 CABLES
[email protected]

XLPE/PVC SINGLE CORE - CURRENT CARRYING CAPACITY TABLE SINGLE


PHASE (IN AMPS)
Copper Conductor Insulation XLPE Maximum Conductor Temperature 90C

Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu Cu Cu Cu
16 112 108 86 84 67 43 139 100 112
25 151 145 117 113 90 58 179 131 146
35 186 177 144 135 108 72 215 157 175
50 228 216 176 166 133 - 255 189 211
70 291 273 224 204 164 - 313 233 258
95 361 338 278 255 204 - 375 285 309
120 422 393 325 292 233 - 427 325 358
150 486 451 375 329 263 - 480 365 401
185 565 522 436 387 309 - 543 423 463
240 678 622 522 461 369 - 630 497 536
300 787 718 605 - - - 711 562 620
400 923 836 708 - - - 808 653 706
500 1078 966 821 - - - 913 739 800
630 1261 1113 950 - - - 1026 856 930

Unenclosed spaced Unenclosed spaced from surface Unenclosed touching

Thermal insulation, partially Thermal Insulation, completely


Enclosed conduit in air
surrounded by thermal insulation surrounded by thermal insulation

Underground ducts A - Underground Underground ducts B - Individual


Buried direct
Wiring Enclosure Wiring Enclosure

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 10/12/20 www.olex.com.au Page 3 / 4
Contact
XLPE Single Core Cu OLEX CUSTOMER SERVICE - Purchase
orders, invoices, general enquiries
XLP 1X500 PC XLPPVC Phone: 1300 CABLES
[email protected]

XLPE/PVC SINGLE CORE - CURRENT CARRYING CAPACITY TABLE THREE PHASE


(IN AMPS)
Copper Conductor Insulation XLPE Maximum Conductor Temperature 90C

Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu Cu Cu Cu
16 108 92 86 72 58 43 117 86 101
25 146 125 117 97 77 58 151 113 132
35 180 154 144 120 96 72 180 137 158
50 221 188 176 143 114 - 214 163 190
70 282 240 224 183 146 - 262 203 232
95 350 298 278 220 176 - 313 244 276
120 410 349 325 261 209 - 356 284 320
150 472 403 375 295 236 - 400 320 358
185 550 468 435 335 268 - 452 363 413
240 660 560 521 399 320 - 523 426 477
300 766 648 602 469 375 - 589 491 552
400 899 756 702 534 427 - 668 557 626
500 1051 874 812 633 506 - 752 648 707
630 1230 1010 938 714 571 - 843 727 820

Unenclosed spaced Unenclosed spaced from surface Unenclosed touching

Thermal insulation, partially Thermal Insulation, completely


Enclosed conduit in air
surrounded by thermal insulation surrounded by thermal insulation

Underground ducts A - Underground Underground ducts B - Individual


Buried direct
Wiring Enclosure Wiring Enclosure

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 10/12/20 www.olex.com.au Page 4 / 4