Heat Load Calculation

The document provides calculations of the sensible heat loads and required cooling capacities for various spaces in a proposed nail spa and beauty services concession located in the basement of Terminal 3 at Singapore Changi Airport. Sensible heat load factors are listed for building elements like exposed glass, walls, roofs, and partitions. Calculations are shown for the dining area, two body massage rooms, two facial rooms, and an office space, accounting for people, lights, appliances, and outdoor air requirements. Total required and designed supply air volumes are reported for each space to maintain temperatures between 16 and 23 degrees Celsius.

Uploaded by

api-3728508
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
4K views3 pages

Heat Load Calculation

The document provides calculations of the sensible heat loads and required cooling capacities for various spaces in a proposed nail spa and beauty services concession located in the basement of Terminal 3 at Singapore Changi Airport. Sensible heat load factors are listed for building elements like exposed glass, walls, roofs, and partitions. Calculations are shown for the dining area, two body massage rooms, two facial rooms, and an office space, accounting for people, lights, appliances, and outdoor air requirements. Total required and designed supply air volumes are reported for each space to maintain temperatures between 16 and 23 degrees Celsius.

Uploaded by

api-3728508
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

ELEAD ASSOCIATES

AIR CONDITIONING HEAT LOAD CALCULATION


PROJECT PROPOSED A&A BODY CONTOURS (NAIL SPA AND BEAUTY SERVICES CONCESSION) AT BASEMENT
DESCRIPTION: 2 NORTH, TERMINAL 3, SINGAPORE CHANGI AIRPORT
PROJECT NO.: A 106
PREPARED BY: ZAW MOE
SENSIBLE HEAT LOAD
FACTORS (KWim2) COOLING
ITEMS DIRECTIONS AREA (m2)
WITH BLINDS LOAD (KVV)
N, NW - 0.3 -
S,E,NE,SE - 0.23 -
EXPOSED GLASS SW - 0.3 -
W - 0.4 -
SHADED - 0.05 -
MEDIUM
LIGHT HEAVY
CONSTRUCTI
CONSTRUCTION CONSTRUCTION
ON
N, NW - 7 x 10-3 6.42 x 10-3 4.08 x 10-3 -
EXPOSED WALLS S,E,NE,SE - 6.42 x 10-3 5.25 x 10-3 5.25 x 10-3 -
SW - 8.75 x 10 -3
7 x 10 -3
6.42 x 10 -3
-
W - 8.75 x 10-3 7.59 x 10-3 6.42 x 10-3 -
SHADED - 2.334x10-3 -
WITH
- 9.336 x 10 -3
5.84 x 10 -3
2.92 x 10 -3
-
CEILING
ROOF WITHOUT
- 2.51 x 10 -3
14.0 x 10 -3
5.84 x 10 -3
-
CEILING
GLASS - 1.75 x 10-3 -
PARTITION
WALL - 1.167 x 10- 3
-
INTERNAL SENSIBLE HEAT LOAD (DINING AREA)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 60 0.06 3.6


LIGHTS W/m 2 128.90 30 3.87
ELECT. APPLIANCES KW 6 0.5 3.00
OUTDOOR AIR 20CMH/PERSON 2.05
(1) TOTAL ROOM SENSIBLE HEAT : 12.52
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 5,364.43
TOTAL DESIGN CMH: 5,750.00
CAAS PROVIDE CMH 3,030.00
NEW ADDITIONAL AIR CON (DINING AREA) 2,720.00

INTERNAL SENSIBLE HEAT LOAD (BODY MASSAGE 1)


NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 7.43 30 0.22
ELECT. APPLIANCES W/m 2 7.43 27 0.20
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.61
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 262.22
DESIGN CMH: 270
INTERNAL SENSIBLE HEAT LOAD (BODY MASSAGE 2)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 8.20 30 0.25
ELECT. APPLIANCES W/m 2 8.20 27 0.22
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.66
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 281.03
DESIGN CMH: 320
INTERNAL SENSIBLE HEAT LOAD (FACIAL 1)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 5.50 30 0.17
ELECT. APPLIANCES W/m 2 5.50 27 0.15
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.50
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 215.07
DESIGN CMH: 220
INTERNAL SENSIBLE HEAT LOAD (FACIAL 2)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 5.55 30 0.17
ELECT. APPLIANCES W/m 2 5.55 27 0.15
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.50
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 216.29
DESIGN CMH: 220
INTERNAL SENSIBLE HEAT LOAD (OFFICE)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 2 0.06 0.12


LIGHTS W/m 2 5.50 30 0.17
ELECT. APPLIANCES W/m 2 5.50 27 0.15
OUTDOOR AIR 20CMH/PERSON 0.07
(1) TOTAL ROOM SENSIBLE HEAT : 0.50
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 215.07
DESIGN CMH: 220
INTERNAL SENSIBLE HEAT LOAD (SHOULDER MASSAGE )
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 8 0.06 0.48


LIGHTS W/m 2 10.90 30 0.33
ELECT. APPLIANCES W/m 2 10.90 27 0.29
OUTDOOR AIR 20CMH/PERSON 0.27
(1) TOTAL ROOM SENSIBLE HEAT : 1.37
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 589.13
DESIGN CMH: 600
INTERNAL SENSIBLE HEAT LOAD (FOOT SPA)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 24 0.06 1.44


LIGHTS W/m 2 35.40 30 1.06
ELECT. APPLIANCES W/m 2 35.40 27 0.96
OUTDOOR AIR 20CMH/PERSON 0.82
(1) TOTAL ROOM SENSIBLE HEAT : 4.28
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 1,833.34
DESIGN CMH: 1900
INTERNAL SENSIBLE HEAT LOAD (RECEPTION & MANICURE)
NO. OF
DESCRIPTION UNIT UNIT FACTORS
PEOPLE PERSON 8 0.06 0.48
LIGHTS W/m 2 23.80 30 0.71
ELECT. APPLIANCES W/m 2 23.80 27 0.64
OUTDOOR AIR 20CMH/PERSON 0.27
(1) TOTAL ROOM SENSIBLE HEAT : 2.11
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 904.26
DESIGN CMH: 970
INTERNAL SENSIBLE HEAT LOAD (CORRIDOR & MANICURE)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 6 0.06 0.36


LIGHTS W/m 2 15.80 30 0.47
ELECT. APPLIANCES W/m 2 15.80 27 0.43
OUTDOOR AIR 20CMH/PERSON 0.21
(1) TOTAL ROOM SENSIBLE HEAT : 1.47
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 628.11
DESIGN CMH: 710
INTERNAL SENSIBLE HEAT LOAD (PANTRY)
NO. OF
DESCRIPTION UNIT UNIT FACTORS

PEOPLE PERSON 4 0.06 0.24


LIGHTS W/m 2 6.50 30 0.2
ELECT. APPLIANCES W/m 2 6.50 27 0.18
OUTDOOR AIR 20CMH/PERSON 0.14
(1) TOTAL ROOM SENSIBLE HEAT : 0.75
TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C) 320.21
DESIGN CMH: 320
TOTAL 5,464.74
TOTAL DESIGN CMH: 5750