LV18 - 072022 - EN - ETUs 320 330 350 550etc

This document provides an overview of Siemens' SENTRON air circuit breakers and molded case circuit breakers with UL certification. It introduces the portfolio of systems and components from SIRIUS, SENTRON, SIVACON and ALPHA for power distribution and industrial controls. These solutions can be flexibly adapted to specific customer requirements. Contact information is provided to discuss customers' needs. The appendix provides additional technical specifications for molded case circuit breakers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views156 pages

LV18 - 072022 - EN - ETUs 320 330 350 550etc

This document provides an overview of Siemens' SENTRON air circuit breakers and molded case circuit breakers with UL certification. It introduces the portfolio of systems and components from SIRIUS, SENTRON, SIVACON and ALPHA for power distribution and industrial controls. These solutions can be flexibly adapted to specific customer requirements. Contact information is provided to discuss customers' needs. The appendix provides additional technical specifications for molded case circuit breakers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 156

© Siemens 2022

Catalog Edition
LV 18 07/2022

SENTRON

Air Circuit Breakers and


Molded Case Circuit Breakers
with UL Certification
siemens.com/lowvoltage
© Siemens 2022

Innovative solutions for industrial


controls and power distribution
In ensuring smooth operation of digital production environments and in the construction and
operation of industrial or commercial buildings, the underlying power distribution and industrial
controls are decisive:

SIRIUS, SENTRON, SIVACON and ALPHA provide a broad portfolio of systems and components for this
purpose that can be used for standard-compliant, requirement-based electrification.

Efficient engineering tools and cloud-based solutions are part of the portfolio, which you can flexibly
adapt to your specific requirements over the entire value-added process.

We are there when you need us


Your personal contact can be found at
www.siemens.com/lowvoltage/contact

Catalog LV 18 · 07/2022 The products and systems described in this catalog are manufactured/
distributed under application of a certified quality management system
You will find the latest edition and all future editions in accordance with EN ISO 9001 (for the Certified Registration Nos., see
in the Siemens Industry Online Support at www.siemens.com/system-certificates/ep).
www.siemens.com/lowvoltage/catalogs The certificate is recognized by all IQNet countries.
Refer to the Industry Mall for current prices Technical specifications
www.siemens.com/industrymall The technical specifications are for general information purposes only.
Always heed the operating instructions and notices on individual products
during assembly, operation and maintenance.
All illustrations are not binding.
© Siemens 2022
© Siemens 2022
SENTRON

Air Circuit Breakers and Molded Case


Circuit Breakers with UL Certification
I
Introduction I/2

1
Protecting Air Circuit Breakers 1/1

2
Molded Case Circuit Breakers 2/1

A
Appendix A/1
© Siemens 2022
Introduction | The fast route to the product

The fast route to the product


Overview of configurable products for better understanding

I
Molded Case Circuit Breakers | 3VA51 – 3VA69 new 3VA51 – 3VA69 new | Molded Case Circuit Breakers

Structure of the article numbers


Basic configuration for line protection

The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator
4 5 6 7 8 9 10 11 12 13 4 5 6 7 8 9 10 11 12 13
3VA – – AA0 3VA – – AA0
2 Trip units Thermal-magnetic 5
2
Electronic 6

3VA51
3VA52
3VA53
3VA54
3VA55
3VA57
3VA58
3VA59
3VA61
3VA62
3VA63
3VA64
3VA65
3VA66
3VA67
3VA68
3VA69
3VA51
3VA52
3VA53
3VA54
3VA55
3VA57
3VA58
3VA59
3VA61
3VA62
3VA63
3VA64
3VA65
3VA66
3VA67
3VA68
3VA69

Size 125 A ■ – – – – – – – – – – – – – – – – 1 Protective function Line protection ■■ – – – – – – – – – – – – – – – TM210 FTFM D


150 A – – – – – – – – ■ – – – – – – – – 1 thermal-magnetic ■■■■■■■■ – – – – – – – – – TM230 FTAM C
250 A – ■ – – – – – – – ■ – – – – – – – 2 ■■■■ – – – – – – – – – – – – – TM240 ATAM F
400 A – – ■ – – – – – – – ■ – – – – – – 3
600 A – – – ■ – – – – – – – ■ – – – – – 4 Protective function Line protection Without neutral conductor protection E
800 A – – – – ■ – – – – – – – ■ – – – – 5 thermal-magnetic, 100% neutral conductor protection G
1000 A – – – – – – – – – – – – – ■ – – – 6 neutral conductor
protection
1200 A – – – – – ■ – – – – – – – – ■ – – 7
1600 A – – – – – – ■ – – – – – – – – ■ – 8 Protective function Line protection H L
– – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ – ETU320 LI (N) 1)
2000 A – – – – – – – ■ – – – – – – – – ■ 9 electronic – – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ – ETU330 LIG (N) 1) H M
Max. rated current Line 15 A ■ – – – – – – – – – – – – – – – – 9 5 – – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ – ETU350 LSI (N) 1) H N
In protec- 20 A ■ – – – – – – – – – – – – – – – – 2 0
– – – – – – – – – – – – – – ■ ■ – ETU360 LSIG (N) 1) H Q
tion 25 A ■ – – – – – – – – – – – – – – – – 2 5
Line protection, – – – – – – – – ■ ■ ■ ■ ■ ■ – – – ETU550 LSI (N) 2)
J P
30 A ■ – – – – – – – – – – – – – – – – 3 0
with display – – – – – – – – ■ ■ ■ ■ ■ ■ – – – ETU556 LSI(G) (N) 2) J T
35 A ■ – – – – – – – – – – – – – – – – 3 5
40 A ■ ■ – – – – – – ■1) – – – – – – – – 4 0 – – – – – – – – ■ ■ ■ ■ ■ ■ – – – ETU560 LSIG (N) 2) J Q
45 A ■ ■ – – – – – – – – – – – – – – – 4 5 Line protection, – – – – – – – – ■ ■ ■ ■ ■ ■ – – – ETU820 LI (N) 2) K L
50 A ■ ■ – – – – – – – – – – – – – – – 5 0 with display, – – – – – – – – ■ ■ ■ ■ – – – – – ETU830 LIG (N) 2) K M
with measurement
60 A ■ ■ – – – – – – ■2) – – – – – – – – 6 0 – – – – – – – – ■ ■ ■ ■ – – ■ ■ ■ ETU850 LSI (N) 2) K P
function
70 A ■ ■ – – – – – – – – – – – – – – – 7 0
– – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ ■ ETU856 LSI(G) (N) 2) K T
80 A ■ ■ – – – – – – – – – – – – – – – 8 0
– – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ ■ ETU860 LSIG (N) 2) K Q
90 A ■ ■ – – – – – – – – – – – – – – – 9 0
100 A ■ ■ – – – – – – ■ ■ – – – – – – – 1 0 1)
Neutral conductor protection for 4-pole breakers
110 A ■ ■ – – – – – – – – – – – – – – – 1 1
2)
Neutral conductor protection for 3-pole breakers with an external neutral conductor transformer or for 4-pole breakers
125 A ■ ■ – – – – – – – – – – – – – – – 1 2
Number of poles 1-pole ■ – – – – – – – – – – – – – – – – 1
150 A – ■ – – – – – – ■ – – – – – – – – 1 5

Configurable products
175 A – ■ – – – – – – – – – – – – – – – 1 7 2-pole ■ – – – – – – – – – – – – – – – – 2
200 A – ■ ■ – – – – – – – – – – – – – – 2 0 2-pole in 3-pole – ■■■■■ – – – – – – – – – – – 6
225 A – ■ ■ – – – – – – – – – – – – – – 2 2 enclosure
250 A – ■ ■ – – – – – – ■ ■ – – – – – – 2 5 3-pole ■■■■■■■■■■ ■ ■ ■■■■■ 3

For products which are


300 A – – ■ – – – – – – – – – – – – – – 3 0 4-pole ■■■■■ – – – ■■ ■ ■ ■■ – – – 4
350 A – – ■ – – – – – – – – – – – – – – 3 5
400 A – – ■ – – – – – – – ■ ■ – – – – – 4 0 Connection Without ■■■■ – ■■■■■ ■ ■ – – ■■■ 1
450 A – – – ■ – – – – – – – – – – – – – 4 5 technology Nut keeper kit – – – – ■ – – – – – – – ■■ – – – 2

conveniently configurable
500 A – – – ■ – – – – – – – – – – – – – 5 0
600 A – – – ■ ■ – – – – – – ■ ■ – – – – 6 0 Special Standard ■■■■■■■■■■ ■ ■ ■■■■■ 0
700 A – – – – ■ – – – – – – – – – – – – 7 0 applications 100% rated – – – – – ■ ■ – ■ ■ ■1) ■2) ■ – ■ ■ – 2
800 A – – – – ■ ■ – – – – – – ■ – ■ – – 8 0 breaker

online, the structure of the


900 A – – – – – ■ – – – – – – – – – – – 9 0 1)
Only possible for 250 A
1000 A – – – – – ■ – – – – – – – ■ ■ – – 1 0 2)
Only possible for 400 A
1200 A – – – – – ■ – – – – – – – – ■ – – 1 2
1400 A – – – – – – ■ – – – – – – – – – – 1 4

article numbers is clearly


1600 A – – – – – – ■ – – – – – – – – ■ – 1 6
1800 A – – – – – – – ■ – – – – – – – – – 1 8
2000 A – – – – – – – ■ – – – – – – – – ■ 2 0

displayed. A link takes you


Short-circuit 25 kA ■ – – – – – – – – – – – – – – – – 4
breaking capacity 35 kA ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 5
at 480 V 65 kA ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 6
50/60 Hz

directly to the configurator


100 kA – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 7
150 kA – – – – – – – – ■ ■ ■ ■ – – – – – 8
200 kA – – – – – – – – ■ ■ ■ ■ – – – – – 0
1)
Available for breaking capacity classes M (35 kA), H (65 kA), C (100 kA) and L (150 kA) at 480 V ◾ Available – Not available/not present

which permits complete and


2)
Available for breaking capacity class E (200 kA) at 480 V

System overview, pages 2/8 and 2/12 System overview, pages 2/8 and 2/12
2/22 Siemens LV 18 · 07/2022 Siemens LV 18 · 07/2022 2/23

valid configuration.

I/2 Siemens LV 18 · 07/2022


© Siemens 2022
The fast route to the product | Introduction

Clickable article numbers new Search function I


Direct forwarding to the individual products in the Industry Search for new products by entering "new" in the text field of
Mall by clicking on the article number in the catalog the search function

3VA9137-0EK11

or by entering this web address incl. article number


www.siemens.com/product?Article No.

Siemens LV 18 · 07/2022 I/3


© Siemens 2022
Introduction | Overview of the key US standards

Overview of the key US standards

NSB0_01920b

IEC
UL/NFPA
IEC/UL/NFPA
CSA

UL and IEC are fundamentally different. The IEC standards for the IEC market merely define the minimum safety requirements for a
device or system. The technical details relating to how safety requirements are to be implemented are in practice a matter for the
manufacturer. Every electrical machine or system in the USA is investigated by an inspector, the so-called Authority Having
Jurisdiction (AHJ), prior to commissioning. The National Electrical Code (NEC), respective application-specific standards as well as
local standards and specifications form the basis for acceptance.

The following standards are of essential importance to mechanical engineers and panel builders:
• UL 508A for industrial control panels
• NFPA 79 (Electrical Standard for Industrial Machinery) for industrial machines
• NEC (National Electrical Code, NFPA 70) for electrical on-site installation

You will find further information at: www.siemens.com/controlpanel

I/4 Siemens LV 18 · 07/2022


© Siemens 2022
Overview of the key US standards | Introduction

Marks Applications
The UL Listing Mark is the most frequently used symbol. Products (e.g. washing machines, computers, electrical switchgear, fire
I
extinguishers, personal flotation devices, etc.) which carry this mark meet all UL's safety requirements and are allowed to be installed
universally and without further instruction or restriction of use. Our own portfolio, for example, offers contactors in accordance with
UL 508 or circuit breakers in accordance with UL 489.

C-UL Listing Mark: This mark is applied to products for the Canadian market. You will see this mark on appliances and computer
equipment, vending machines, household burglar alarm systems, lighting fixtures, and many other types of products.

C-UL US Listing Mark: Introduced in 1998, this mark indicates compliance of the products with both Canadian and U.S. requirements.
The Canada/U.S. UL mark is optional. UL encourages those manufacturers with products certified for both countries to use this combined
mark, but they may continue using separate UL marks for the United States and Canada.

Recognized Component Mark: This mark is used on components and devices that are incorporated in machines, systems or products
such as washing machines. These components may have restrictions on their performance or may be incomplete in construction. The
Component Recognition Mark is found on a wide range of products, including some switches, power supplies, printed wiring boards,
some kinds of industrial control equipment and many other products. They are allowed to be installed only by properly qualified
personnel, as the "Conditions of Acceptability (CoA)" apply to these devices in all cases. Examples of our products that bear the UR mark
include our miniature circuit breakers which meet UL 1077, our time switches which meet UL 917, and our SITOR fuses.
Canadian Recognized Component Mark (similar to the Recognized Component Mark – see above): Components approved for the
Canadian market carry this mark.

Recognized Component Mark for Canada and the United States: Components carrying this mark, which became effective in 1998,
meet the requirements of the US and Canadian markets for Recognized Components. Although UL had not originally planned to
introduce a combined Recognized Component Mark, the popularity of Canada/U.S. listing marks among clients led to the new mark.

Certifications such as u and U are issued by the so-called NRTLs (Nationally Recognized Testing Laboratories) after successful
testing. The OSHA (Occupational Safety and Health Administration) has accredited Underwriters Laboratories Inc. as an NRTL.

Siemens LV 18 · 07/2022 I/5


© Siemens 2022
Introduction | Overcurrent protection according to network standards

Overcurrent protection according to


network standards
I Overcurrent protection
The term "overcurrent" refers to the overload, short-circuit and ground-fault current when this exceeds the rated value of the
protective device. Overcurrent protection is understood to be a device designed to open a circuit when the rated current is
exceeded. The ampere rating of the device is selected for a circuit to terminate a condition where the current exceeds the rating
of conductors and equipment due to overloads, short circuits and faults to ground.

UL 508A distinguishes between straight rating and slash rating. Which of these two ratings applies depends on the existing
system type.

Slash rating Straight rating


There are two voltages (phase – phase/phase – ground) in a In the common industrial networks (see table) there is only
solidly grounded wye network. These two voltages are also one voltage. Such networks are called "straight networks".
specified along with the rating, e.g. 480 Y/277 V. A device When choosing short-circuit protection devices, attention
suitable for this network has a slash rating. must be paid to whether devices are approved for straight or
slash rating.

I201_20233

I201_20232
I201_20230

3 phases, 3 phases, 3 phases, 3 phases,


4 conductors 3 conductors 3 conductors 3 conductors
Solidly grounded wye, 3 phases, 4 conductors Corner grounded delta, Ungrounded wye, Ungrounded delta,
3 phases, 3 conductors 3 phases, 3 conductors 3 phases, 3 conductors
Notice: The PE must not carry any current.
There is no PEN conductor --> N = grounded conductor (white or gray);
separate conductors must be used for PE and N.

Usable line voltages: Usable line voltages:


600Y/347 V 1) 600 V
480Y/277 V 1) 480 V
240Y/131 V 1) 240 V
208Y/120 V 1)
1)
Y describes the "Solidly grounded circuit". The value "Y" indicates the voltage between the phases (e.g. 480 V), and the value behind the slash indicates the voltage between the phase and
the grounding or the neutral conductor (e.g. 277 V with 480 V voltage between the phases).

I/6 Siemens LV 18 · 07/2022


© Siemens 2022
Brief code comparison of UL vs. IEC standards | Introduction

Brief code comparison of


UL vs. IEC standards
Interaction of the most important US standards I

Installation NEC = IEC 60364-1


standard NFPA 70

IEC 60204-1 IEC 61439-1


Application NFPA 79 UL 508A IEC 60204-1
standard IEC 61439-1

Product
standard UL 489 UL 508 UL 98 UL 248 UL xxx IEC xxx

I201_20228
NEC = NFPA70 vs. IEC 60364-1: Electrical on-site installation

NFPA 79 vs. IEC 60204-1: Industrial machines

UL 508A vs. IEC 61439-1: Industrial control panels

Contact our Support at www.siemens.com/lowvoltage/certificates to find out which products (please specify the article number)
are approved according to which standard.

The table below contains a summary of the available products and details of the UL, CSA and IEC standards with which the 3WL5 air
circuit breaker and the 3VA5 and 3VA6 molded case circuit breakers comply. However, the table only contains product groups.
The product groups mentioned might include individual products which are not approved according to UL or CSA. It is essential
therefore to research each individual product via our Support.

UL CCN UL UL CSA IEC


Size Standard listed recognized FIle Nr. Standard File Nr. Class Nr. Standard
Air circuit breakers
ACB 3WL5 ≤5000 A UL 489 DIVQ – E231263 cULus approved IEC 60947-2
DIVQ7
Molded case circuit breakers
Circuit breaker (CB) 3VA51–3VA59 ≤2000 A UL 489 DIVQ – E364397 cULus approved IEC 60947-2 1)
DIVQ7
3VA61–3VA69 ≤2000 A UL 489 DIVQ – E364397 cULus approved IEC 60947-2 1)
DIVQ7
Motor circuit protector (MCP) 3VA51–3VA55 ≤800 A UL 489 – DKPU2 E482699 cULus approved IEC 60947-2
DKPU8
3VA61–3VA66 ≤1000 A UL 489 – DKPU2 E482699 cULus approved IEC 60947-2
DKPU8
Molded case switch (MCS) 3VA51–3VA59 ≤2000 A UL 489 WJAZ – E482701 cULus approved IEC 60947-2 1)
WJAZ7
3VA61–3VA66 ≤1000 A UL 489 WJAZ – E482701 cULus approved IEC 60947-2
WJAZ7
Circuit breaker accessories 3VA9 UL 489 DIHS DIHS2 E354102 cULus approved IEC 60947-2
DIHS7 DIHS8
1)
No IEC approval for 3VA59 and 3VA69

Siemens LV 18 · 07/2022 I/7


© Siemens 2022
Introduction | Applications

Applications

Circuit breaker for line protection/ Non-automatic circuit breaker/


I Inverse time circuit breaker for line protection Switch disconnector/Molded case switch
(CB, CCN code: DIVQ) (MCS, CCN code: WJAZ)

I201_20231

I201_19430
The trip units are designed to provide overload and short- These molded case switches can be used as feeder switches,
circuit protection for: main switches or non-automatic circuit breakers without
overload protection.
• Cables
• Leads They incorporate an integrated short-circuit self-protection
• Non-motor loads system.

Motor circuit protector/


Instantaneous trip circuit breaker/
Protective circuit breaker for motor starter
combinations (MCP, CCN-Code: DKPU2)
I201_19375

Starter combinations consist of:


Motor circuit protector + contactor + overload relay
The motor circuit protector handles short-circuit protection
and the isolating function. The task of the contactor is the
operational switching of the feeder. The overload relay
handles overload protection that can be specially matched to
the motor.
The motor circuit protector is therefore equipped with an
adjustable and instantaneous short-circuit release.

I/8 Siemens LV 18 · 07/2022


© Siemens 2022
Product approvals in control panel according to UL/NEC | Introduction

Product approvals in control panel


according to UL/NEC
Line + technical feasibility I
CCN UL Article number

Industrial Control Panel DIVQ


Circuit breaker Or WJAZ
I> Molded case switch 3VA5, 3VA6,
I >> w/o protection function 3WL5, 3LD5
UL 489

Busbar 8US

Motor circuit protector/ Circuit


Instantaneous trip circuit breaker breaker DKPU2 3VA
I >> I> DIVQ
I >>

Motor starter Manual VSD / FE


motor starter 3RV, 3RT
UL 508

Motor
disconnect 3LD
w/o
protection

I> Overload protection (Line)

I201_20195a
I >> Short-circuit protection

Diagram showing which product approvals may be used at which position in the feeder/supply line according to UL/NEC.

Siemens LV 18 · 07/2022 I/9


© Siemens 2022
Air Circuit Breakers

Reliable, versatile and perfectly


integrated

All power distribution systems rely on a secure


infeed of electrical energy. The 3WL air circuit
breakers reliably protect electrical equipment
from damage or fire resulting from short circuit,
ground fault or overload failures.

The 3WL air circuit breakers are used as incoming-


feeder, tie, and outgoing-feeder circuit breakers
in electrical installations in industry, buildings and
infrastructure applications. They have the ability
to communicate and can easily be integrated into
higher-level control and energy management
systems.

The 3WL air circuit breakers switch and protect


motors, capacitors, generators, transformers,
busbars and cables. The modular design and
standardized range of accessories enable the
circuit breakers to be adapted flexibly to different
applications. UL 489-compliant versions are
available for international use.

The 3WL air circuit breakers can optionally be


equipped with a communication module and
integrated into higher-level energy management
systems. Auxiliary, signaling and position switches
report status and fault diagnostics remotely to
higher-level control systems.
© Siemens 2022
Air Circuit Breakers

Air Circuit Breakers

All the information you need 1/2

Quick selection guide 1/4

Circuit breakers and non-automatic circuit breakers


for AC and DC 1/4

Circuit breakers and non-automatic circuit breakers


for AC 1/6

Non-automatic circuit breakers for DC 1/10

Electronic trip units ETU 1/12

Connection 1/14

Operating mechanism, auxiliary release, auxiliary switch 1/15

3WL5 1/16

System overview 1/16

Online configurator highlights 1/18

Structure of the article numbers 1/20

Accessory options 1/24

Guide frames for AC 1/34

Accessories and spare parts 1/35

Siemens LV 18 · 07/2022 1/1


© Siemens 2022
Air Circuit Breakers | All the information you need

A multitude of additional information ...

Information + ordering
1
All the important things at a glance Everything you need for your order

For information about air circuit breakers, please visit Refer to the Industry Mall for an overview of your
our website www.siemens.com/3WL products
• 3WL air circuit breakers/non-automatic air circuit
breakers for AC up to 5000 A, UL sie.ag/2ScRZK7
Siemens YouTube channel
Direct forwarding to the individual products in the
• 3WL air circuit breakers (general) Industry Mall by clicking on the article number in the
bit.ly/2ZH1rXH catalog or by entering this web address incl. article number
www.siemens.com/product?Article No.

Configurators

The configurator reduces the time and effort required in


the planning and ordering process, and allows for individ­
ual adaptations. Configure your 3WL air circuit breaker at
www.siemens.com/lowvoltage/3wl-configurator
The following are additionally available for your
configured 3WL air circuit breaker:
• 3D views
• CAD data
• Unit wiring diagrams
• Dimension drawings

The fast track to the experts

Contact persons in your region


We offer a comprehensive portfolio of services. Competent expert advice on technical questions with a wide
You can find your local contacts at range of demand-optimized services for all our products and
www.siemens.com/lowvoltage/components/contact systems.
You can find further information on services at Assistance with technical queries is provided at
www.siemens.com/service-catalog www.siemens.com/support-request

1/2 Siemens LV 18 · 07/2022


© Siemens 2022
All the information you need | Air Circuit Breakers

... can be found in our online services

Commissioning + operation

SENTRON powerconfig Manuals

The combined commissioning and service tool SENTRON Manuals are available for downloading in Siemens
powerconfig for communication-capable measuring Industry Online Support (SIOS) at
devices, circuit protection devices and circuit breakers. www.siemens.com/lowvoltage/manuals
Free download SENTRON powerconfig via • Configuration manual
www.siemens.com/powerconfig − 3WL5 air circuit breakers/ non-automatic air circuit
Free download SENTRON powerconfig mobile via breakers (109775570)
App Store and Play Store • System manual
− 3WL/3VL circuit breakers with communication
capability – Modbus (39850157)
− 3WL/3VL circuit breakers with communication
Your product in detail
capability – PROFIBUS (12560390)
• Communication manual
The Siemens Industry Online Support (SIOS) provides − 3WL air circuit breakers via COM35 – PROFINET IO,
detailed technical information Modbus TCP (109757987)
www.siemens.com/lowvoltage/product-support
• Operating instructions
• Characteristic curves Face-to-face or online training
• Certificates
Comprehensive mobile support via the Siemens Industry Our training courses can be found at
Online Support app available for download from the www.siemens.com/sitrain-lowvoltage
App Store and Play Store
• 3WL air circuit breakers, sizes 1-3 (WT-LVA3WL)
You will find further information under:
• Protection systems in low-voltage power distribution
www.siemens.com/support-app
(WT-LVAPS)
Provision of 3D data (step and u3d data formats) • Maintenance and operation of 3WL circuit breakers
• Siemens Industry Mall (LV-CBMAIN) with subsequent certification option
www.siemens.com/lowvoltage/mall (LV-CBCERT)
• Image database • Communication with SENTRON components (LV-COM)
www.siemens.com/lowvoltage/picturedb • Project planning and selection of SENTRON circuit
• Engineering data for CAD or CAE systems are available breakers (LV-CBPROJ)
in the CAx Download Manager at Video tutorial on the 3WL air circuit breaker
www.siemens.com/cax www.lowvoltage.siemens.com/wcms/3wl-tutorial

Technical overview – Air circuit breakers

The fast way to get you to our online services


This page provides you with comprehensive information and links on air circuit breakers
www.siemens.com/lowvoltage/product-support (109766020)

Siemens LV 18 · 07/2022 1/3


© Siemens 2022
Air Circuit Breakers | Quick selection guide

Circuit breakers and non-automatic circuit


breakers for AC and DC
UL 489/IEC 60947-2
AC
1

3WL51 3WL52
Basic data
Rated operational voltage Ue V 600 Υ/347 600
Rated current In A 630 … 1600 2000 … 3200
Size 1 2
Type of mounting Withdrawable Fixed-mounted Withdrawable Fixed-mounted
Number of poles 3/4-pole 3/4-pole 3/4-pole 3/4-pole
Dimensions
Width (3-pole | 4-pole) mm 320 | 410 320 | 410 460 | 590 460 | 590
Height (standard | A05, A15, A16, DC greater than 600 V) mm 465.5 434 465.5 434
Depth mm 471 291 471 291
Approvals
General product approvals VDE, UL/cULus, CE, CCC, EAC, C-Tick VDE, UL/cULus, CE, CCC, EAC, C-Tick
Breaking capacity S H
Short-circuit breaking capacity acc. to UL 489
Short-circuit breaking capacity up to 480 V AC Icu = Ics kA 65 100
Short-circuit breaking capacity up to 600 Υ V/347 V AC Icu = Ics kA 50 85 1)
Short-circuit breaking capacity up to 600 V AC Icu = Ics kA – 85
Short-circuit breaking capacity acc. to IEC 60947-2
Short-circuit breaking capacity up to 500 V AC Icu = Ics kA 65 100
Short-circuit breaking capacity Icm at 500 V AC Icu = Ics kA 143 220
Short-circuit breaking capacity up to 690 V AC Icu = Ics kA 50 85
Short-circuit breaking capacity Icm at 690 V AC Icu = Ics kA 105 187
Rated short-time withstand current Icw acc. to UL 489
Rated short-time withstand current Icw at max. delay time tsd 0.4 s kA 65 85
Rated short-time withstand current Icw acc. to IEC 60947-2
Rated short-time withstand current Icw at max. delay time tsd 0.5 s kA 65 85
1s kA 50 80
Rated short-circuit current Icc of the non-automatic air circuit breakers
Rated short-circuit current Icc at 600 V DC kA – –
Rated short-circuit current Icc at 1000 V DC kA – –
1)
Covered by 600 V AC (delta) test.

System overview, page 1/16


1/4 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Air Circuit Breakers

AC DC
1

3WL53 3WL5232
≤600 Υ/347 600
4000 … 5000 3200
3 2
Withdrawable Fixed-mounted Fixed-mounted
3/4-pole 3/4-pole 3-pole

704 | 914 704 | 914 460


465.5 434 434
471 291 291

VDE, UL/cULus, CE, CCC, EAC, C-Tick VDE, UL/cULus, CE, CCC, EAC, C-Tick
H DC

100 –
85 –
– –

100 –
220 –
85 –
187 –

85 –

85 –
80

– 25
– –

System overview, page 1/16


Siemens LV 18 · 07/2022 1/5
© Siemens 2022
Air Circuit Breakers | Quick selection guide

Circuit breakers and non-automatic circuit


breakers for AC
UL 489/IEC 60947-2
3WL51
1

Rated current In ≤1000 A 1600 A


General specifications
Isolating function acc. to EN 60947-2 Yes
Utilization category B
Permissible ambient temperature Operation °C –25 … +55
Storage °C –25 … +70
Mounting position 30° 30°

Dhmax.
= 1 mm
30° 30°

NSE0_00061a
NSE0_00062a
NSE0_00927

Degree of protection With cover IP55


Without cover (with door sealing frame) IP41
Voltage
Rated operational voltage Ue at 50/60 Hz V AC 600 Υ/347
Permissible load at 50/60 Hz
For main conductors At 40 °C A ≤1000 1600
At 55 °C A ≤1000 1600
At 60 °C A ≤1000 1600
Power loss at In
With 3-phase symmetrical load Fixed-mounted circuit breaker W 100 150
Withdrawable circuit breaker W 195 350
Switching times
Make time ms 35
Opening time ms 38
Electrical make time (through activation solenoid) 1) ms 80
Electrical opening time (through shunt trip) ms 73
Electrical opening time (instantaneous undervoltage release) ms ≤80
Opening time due to ETU, instantaneous short-circuit release ms 50
Service life/endurance
Mechanical Without maintenance Operating 10000
cycles
Electrical Without maintenance Operating 4000
cycles
Switching frequency
Mechanical / electrical 1/h 60
Minimum pauses
Between tripping by the electronic trip unit and the next closure of the circuit breaker ms 80
(only with automatic mechanical reset of the reclosing lockout)
1)
Make time through closing coil for synchronization purposes (short-time excited) 50 ms.

System overview, page 1/16


1/6 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Air Circuit Breakers

3WL52 3WL53
1

2000 A 2500 A 3000 A 3200 A 4000 A 5000 A


Yes Yes
B B
–25 … +55 –25 … +55
–25 … +70 –25 … +70
30° 30° 30° 30°
Dhmax.

Dhmax.
= 1 mm

= 1 mm
30° 30° 30° 30°

NSE0_00061a NSE0_00061a
NSE0_00062a NSE0_00062a
NSE0_00927 NSE0_00927

IP55 IP55
IP41 IP45

600 600 600 600 ≤600 Υ/347

2000 2500 3000 3200 4000 5000


2000 2500 3000 3200 4000 5000
2000 2500 3000 3200 4000 5000

180 270 410 410 520 630


320 520 710 710 810 1050

35 35
34 34
100 100
73 73
≤80 ≤80
50 50

10000 10000

4000 1000

60 60

80 80

System overview, page 1/16


Siemens LV 18 · 07/2022 1/7
© Siemens 2022
Air Circuit Breakers | Quick selection guide

Circuit breakers and non-automatic circuit


breakers for AC
UL 489/IEC 60947-2
3WL51
1

Rated current In ≤1000 A 1600 A


Connection
Main conductor minimum cross-sections
Copper bars, bare Unit, mm2 2× 6.4 × 76.2

Auxiliary conductor (Cu) max. number of auxiliary conductors × cross-section (solid/stranded)


Standard connection = screw Without end sleeve 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16);
1× 2.5 mm2 (AWG 14)
With end sleeve acc. to DIN 46228 Part 2 1) 1× 0.5 … 1× 1.5 mm2 (AWG 20 … 16)
With twin end sleeve 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16)
Screwless connection technology Without end sleeve 2× 0.5 … 2× 2.5 mm2 (AWG 20 … 14)
With end sleeve acc. to DIN 46228 Part 2 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16)
Minimum dimension of breaker compartment
Width × height × depth 3-pole mm 400 × 460 × 380
3-pole with A17 mm –
4-pole mm 500 × 460 × 380
Weights
3-pole Fixed-mounted circuit breaker kg 43
Withdrawable circuit breaker kg 45
Guide frames kg 25
4-pole Fixed-mounted circuit breaker kg 50
Withdrawable circuit breaker kg 54
Guide frames kg 30
1)
Notice: Approval of end sleeves.

System overview, page 1/16


1/8 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Air Circuit Breakers

3WL52 3WL53
1

2000 A 2500 A 3000 A 3200 A 4000 A 5000 A

2× 6.4 × 102 2× 6.4 × 127 or 4× 6.4 × 102 4× 6.4 × 102 4× 10 × 120


4× 6.4 × 63.5

2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16); 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16);
1× 2.5 mm2 (AWG 14) 1× 2.5 mm2 (AWG 14)
1× 0.5 … 1× 1.5 mm2 (AWG 20 … 16) 1× 0.5 … 1× 1.5 mm2 (AWG 20 … 16)
2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16) 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16)
2× 0.5 … 2× 2.5 mm2 (AWG 20 … 14) 2× 0.5 … 2× 2.5 mm2 (AWG 20 … 14)
2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16) 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16)

500 × 460 × 380 500 × 460 × 380 500 × 460 × 380 500 × 460 × 380 800 × 460 × 380 800 × 460 × 380
– 560 × 570 × 500 – 560 × 570 × 500 810 × 570 × 500 –
600 × 460 × 380 600 × 460 × 380 – 560 × 570 × 500 1000 × 460 × 380 1000 × 460 × 380

56 59 64 64 82
60 63 68 – 88
31 39 45 – 60
67 71 77 77 99
72 76 82 – 106
37 47 54 – 84

System overview, page 1/16


Siemens LV 18 · 07/2022 1/9
© Siemens 2022
Air Circuit Breakers | Quick selection guide

Non-automatic circuit breakers for DC


UL 489/IEC 60947-2

3WL5232
Rated current In 3200 A
1 General specifications
Isolating function acc. to EN 60947-2 Yes
Utilization category B
Permissible ambient temperature Operation °C –25 …+55
Storage °C –25 … +70
Mounting position

Dhmax.
= 1 mm
NSE0_00927

Degree of protection With cover IP55


Without cover IP41
(with door sealing frame)
Voltage
Rated operational voltage Ue V DC 600
Permissible load
For main conductors, acc. to IEC 60947-2 At 40 °C A 3200
At 55 °C A 3200
At 60 °C A 3200
For main conductors, acc. to UL 489B At 40 °C A 3200
At 55 °C A 3200
At 60 °C A 3200
Power loss at In
With 3-phase symmetrical load Fixed-mounted circuit breaker W 410
Withdrawable circuit breaker W –
Switching times
Make time ms 35
Opening time ms 34
Electrical make time (through activation solenoid) 1) ms 100
Electrical opening time (through shunt trip) ms 73
Electrical opening time (instantaneous undervoltage release) ms ≤80
Opening time due to ETU, instantaneous short-circuit release ms 50
Service life/endurance
Mechanical Without maintenance Operating 10000
cycles
Electrical Without maintenance Operating 1000
cycles
Switching frequency
Mechanical / electrical 1/h 60
1)
Make time through activation solenoid for synchronization purposes (short-time excited) 50 ms.

System overview, page 1/16


1/10 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Air Circuit Breakers

3WL5232
Rated current In 3200 A
Connection
1
Main conductor minimum cross-sections
Copper bars, bare Unit 4× 6.4 × 102
Auxiliary conductor (Cu) max. number of auxiliary conductors × cross-section (solid/stranded)
Standard connection = strain-relief clamp Without end sleeve 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16);
1× 2.5 mm2 (AWG 14)
With end sleeve acc. to DIN 46228 Part 2 2) 1× 0.5 … 1× 1.5 mm2 (AWG 20 … 16)
With twin end sleeve 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16)
Optional connection = tension spring Without end sleeve 2× 0.5 … 2× 2.5 mm2 (AWG 20 … 14)
With end sleeve acc. to DIN 46228 Part 2 2× 0.5 … 2× 1.5 mm2 (AWG 20 … 16)
Weights
3-pole Fixed-mounted circuit breaker kg 64
Dimensions 3/4-pole
Fixed-mounted Width mm 460/590
Height mm 434
Depth mm 291
Withdrawable Height mm 465.5
Depth mm 471
2)
Notice: Approval of end sleeves.

System overview, page 1/16


Siemens LV 18 · 07/2022 1/11
© Siemens 2022
Air Circuit Breakers | Quick selection guide

Electronic trip units ETU


Available for air circuit breakers

1
ETU45B (LSI) ETU45B (LSIG)
Basic protective functions
L Overload protection Setting range of operating value Ir = In × … 0.4 | 0.45 | 0.5 | 0.55 | 0.6 | 0.4 | 0.45 | 0.5 | 0.55 | 0.6 |
(L tripping) 0.65 | 0.7 | 0.8 | 0.9 | 1 0.65 | 0.7 | 0.8 | 0.9 | 1
Switchable overload protection ■ ■
(from I2t- to I4t-dependent function)
Setting range of delay tr at I2t 2 | 3,5 | 5,5 | 8 | 10 | 14 | 17 | 2 | 3.5 | 5.5 | 8 | 10 | 14 | 17 |
(Reference point 6× In) 21 | 25 | 30 s 21 | 25 | 30 s
Setting range of delay tr at I4t 1|2|3|4|5s 1|2|3|4|5s
(Reference point 6× In)
Thermal memory can be switched on/off ■ ■
Phase failure sensitivity / asymmetry At tsd = 20 ms (M) At tsd = 20 ms (M)
S Short-time delayed short-circuit Setting range of operating value Isd = In × … 1.25 | 1.5 | 2 | 2.5 | 3 | 4 | 6 | 1.25 | 1.5 | 2 | 2.5 | 3 | 4 | 6 | 8 |
protection (ST tripping) 8 | 10 | 12 10 | 12 | OFF
Setting range of delay time tsd at I2t 100 | 200 | 300 | 100 | 200 | 300 | 400 ms
400 ms
Setting range of delay time tsd (t = const.) M (0.02 ms) | 100 | 200 | 300 | M (0.02 ms) | 100 | 200 | 300 |
400 ms 400 ms
ZSI function Via module of the CubicleBUS Via module of the CubicleBUS
I Instantaneous short-circuit protection Setting range 2 = In × … OFF | 1,5 | 2,2 | 3 | 4 | 6 | 8 | 10 | OFF | 1.5 | 2.2 | 3 | 4 | 6 | 8 | 10 |
(INST tripping) 12 | 0,8 × Ics 12 | 0.8 × Ics
N Neutral conductor protection Neutral conductor setting range IN = In × … OFF | 50 % | 100 % OFF | 50% | 100%
G Ground-fault tripping Tripping function can be switched on/off – ■
(GF tripping) Alarm function can be switched on/off – –
Detection of ground-fault current
Detection of ground-fault current through – ■
through summation current formation
external current transformer
with internal or external N conductor
transformer Setting range of the operating current – A 1) (100 / 400 A) |
Ig = In × … B 1) (300 / 600 A);
C 1) (600 / 800 A) |
D 1) (900/ 1000 A);
E 1) (1200 / 1200 A)
Setting range of the operating current Ig for – A 1) (100 / 400 A);
alarm B 1) (300 / 600 A);
C 1) (600 / 800 A);
D 1) (900/ 1000 A);
E 1) (1200 / 1200 A)
Setting range of the delay time tg – 100 | 200 | 300 | 400 | 500 ms
Switchable ground-fault protection – ■
characteristic (I2t-dependent function)
Setting range of delay time tg at I2t – 100 | 200 | 300 | 400 | 500 ms
ZSI-G function – Via module of the CubicleBUS
1) Sizes 1 and 2 / size 3

System overview, page 1/16


1/12 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Air Circuit Breakers

1
ETU45B (LSI) ETU45B (LSIG)

Parameter set changeover Switchable between parameter set A and B – –


LCD Optional Optional
Voltage tap on top/bottom Optional Optional
Measurement function Measurement function Plus Measurement function Plus

Tripping as a result of extended protective function: (including: phase asymmetry current/ ■ ■


voltage, harmonic distortion current/voltage, under/overvoltage, phase rotation direction,
active power in/opposite to normal direction, under/over-frequency, protective functions
dependent on direction of power flow)
Mode of communication
Communication PROFIBUS | PROFINET | Modbus RTU | Modbus TCP ■ ■
Output modules
Signals via relay: Overload warning, load shedding / load carrying, leading signal, overload ■ ■
tripping 200 ms, temperature alarm, phase asymmetry, instantaneous short-circuit release,
short time-delayed short-circuit release, overload trip, neutral conductor trip, auxiliary relay,
ETU faults, ground-fault protection tripping and ground-fault alarm (only with ground-fault
protection module)

System overview, page 1/16


Siemens LV 18 · 07/2022 1/13
1

1/14
NSE0_00967b NSE0_00967b

Connection
NSE0_00975b

Rear-mounted
Front-mounted

the wrong slots


the circuit breaker
NSE0_00967b NSE0_00967b
NSE0_00975b

Screw connection (standard)


NSE0_00967b NSE0_00967b

module in the guide frame


NSE0_00975b

3WL5: Withdrawable version

connector on the switch side

3WL5: Fixed-mounted version


NSE0_00970b

Siemens LV 18 · 07/2022
NSE0_00968b
Connection
Main circuit connection

NSE0_00967b NSE0_00967b
NSE0_00975b
Air Circuit Breakers | Quick selection guide

NSE0_00970b NSE0_00968b

Auxiliary circuit connections


Fixed-mounted

NSE0_00970b NSE0_00968b
1-hole

NSE0_00970b NSE0_00968b

NSE0_00967b NSE0_00967b
NSE0_00971b NSE0_00971b NSE0_009N6SE90b_00969b
NSE0_00975b

NSE0_00976b

Screwless connection
NSE0_00976b

• When fully inserted, connection with the sliding contact


• Connection of the internal auxiliary switches to the male
Vertical

(tension spring) (optional)


NSE0_00967b NSE0_00972b NSE0_00971b NSE0_00969b

Horizontal
NSE0_00967b NSE0_00979a
NSE0_00975b

Coding pins on the connectors prevent them being inserted in


• Engagement of the auxiliary supply connectors directly onto
NSE0_00976b NSE0_00970b NSE0_00968b
NSE0_00971b NSE0_00969b
NSE0_00972b
NSEN0
SE_
0_
000
099
727 aSE0_00967b
b 9N NSE0_00967b
NSE0_00975b NSE0_00979a
NSE0_00973b
NSE0_00976b
2-hole

NSE0_00970b NSE0_00968b
NSE0_00971b NSE0_00969b
© Siemens 2022

NSE0_00973b
NSE0_00976b
NSE0_00972b
NSE0_00979a NSE0_00970b NSE0_00968b

NSE0_00973b NSE0_00972b
NSE0_00971b NSE0_00969b NSE0_00967b NSE0_00979a
NSE0_00967b
NSE0_00975b
3WL5

NSE0_00976b
NSE0_00967b NSE0_00967b
NSE0_00975b
NSE0_00971b NSE0_00969b
NSE0_00972b NSE0_00973b
NSE0_00979a

NSE0_00976b
Withdrawable

NSE0_00973b NSE0_00970b NSE0_00968b


1-hole

Vertical

NSE0_00972b
NSE0_00979a
NSE0_00970b NSE0_00968b
NSE0_00973b
NSE0_00967b NSE0_00967b
NSE0_00975b

NSE0_00971b NSE0_00969b
NSE0_00973b

NSE0_00976b
NSE0_00971b NSE0_00969b
Horizontal

NSE0_00967b NSE0_00967b
NSE0_00975b
NSE0_00976b
NSE0_00972b NSE0_00970b NSE0_00968b
NSE0_00979a

NSE0_00972b
NSE0_00979a

System overview, page 1/16


2-hole

Flanges

NSE0_00970b NSE0_00973b NSE0_00968b


NSE0_00971b NSE0_00969b

NSE0_00976b NSE0_00973b

NSE0_00972b
NSE0_00979a
NSE0_00971b NSE0_00969b

NSE0_00976b

NSE0_00972b NSE0_00973b
NSE0_00979a
© Siemens 2022
Quick selection guide | Air Circuit Breakers

Operating mechanism, auxiliary release,


auxiliary switch
Operating mechanism
The circuit breakers are available with various optional operating Available for air circuit breakers
mechanisms: 3WL5 1
• Manual operating mechanism with mechanical closing Closing coils (CC) ■
(standard design) Undervoltage releases (UVR)/

shunt trips (ST)
• Manual operating mechanism with mechanical and electrical
Shunt trips (ST) ■
closing Remote reset magnets (RR) ■
• Motorized operating mechanism with mechanical and Motorized operating mechanism (MO) ■
electrical closing Mechanical operating cycles counters ■

The operating mechanisms with electrical closing are suitable for


synchronization tasks.

System overview, page 1/16


Siemens LV 18 · 07/2022 1/15
© Siemens 2022
Air Circuit Breakers | 3WL5

3WL5 system overview


UL 489 AC ..

For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator

1
Circuit breakers and
non-automatic circuit breakers

Sizes 1 to 3

Trip units Accessories

NSE0_01027a

LSI LSIG Communi­ Rating plugs Remote reset Breaker status Ground-fault
cation magnets sensors (BSS) modules
module

Main conductor connections Accessories

Fixed-mounted, Main connection vertical, Auxiliary conductor plug-in system


withdrawable versions horizontal, front, flange

Operating mechanisms and


auxiliary releases Accessories

Motorized operating mechanisms Auxiliary releases Closing coils

Note:
You will find a detailed range of accessories in the Accessories section.

1/16 Siemens LV 18 · 07/2022


© Siemens 2022
3WL5 | Air Circuit Breakers

1
Auxiliary switches Accessories

Auxiliary switches Position signaling switches

Further accessories

NSE0_01022

NSE0_01018a
Door sealing frames Shutters EMERGENCY-OFF Operating cycle Support brackets Grounding connections
pushbuttons counters

Interlocking

Interlocking sets Key operation

Note:
You will find a detailed range of accessories in the Accessories section.

Siemens LV 18 · 07/2022 1/17


© Siemens 2022
Air Circuit Breakers | 3WL5

Online configurator highlights


www.siemens.com/lowvoltage/configurators

Search function with global direct input


Searches for specific terms and jumps to MLFB based on input to the correct configurator

Product list stores multiple configurations and can transfer them collectively to the shopping cart

Recall of completed configurations for modification or additional configuration

Responsive Design

1/18 Siemens LV 18 · 07/2022


© Siemens 2022
3WL5 | Air Circuit Breakers

www.siemens.com/lowvoltage/3wl-configurator

Download an ePlan Selector for 3WL5

Mouseover display of characteristic curves to show the protection function

Direct entry of an already known MLFB or parts of an MLFB

Siemens LV 18 · 07/2022 1/19


© Siemens 2022
Air Circuit Breakers | 3WL5

Structure of the article numbers


Basic configuration for AC circuit breakers

The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 5 6 7 8 9 10 11 12 13 14 15 16
3WL5 – –

Circuit breaker and ETU


Size (SZ) 1 1
2 2
3 3
SZ 1

SZ 2

SZ 3

Max. rated current 1000 A ■ – – 1 0


In 1600 A ■ – – 1 6
2000 A – ■ – 2 0
2500 A – ■ – 2 5
3000 A – ■ – 3 0
3200 A – ■ 1) – 3 2
4000 A – – ■ 4 0
5000 A – – ■ 5 0

Short-circuit S Standard ■ – – ≤65 kA 3


breaking capacity H High – ■ ■ ≤100 kA
Icu at 480 V 4

Trip units Without electronic trip unit A A


Without ground-fault ETU45B LSIN E B
protection ETU45B (with display) LSIN F B
With ground-fault ETU45B LSING E G
protection ETU45B (with display) LSING F G

Number of poles 3-pole 3


4-pole 4

Connection
SZ 1

SZ 2

SZ 3

Type of mounting Fixed-mounted ■ ■ ■ Vertical 1


■ ■2) ■ Horizontal 2
■ ■2) ■3) Front single hole 3
■ ■2) ■3) Front double hole 4
Withdrawable ■ ■2) ■ Without frame 5
■ ■2) ■ Rear horizontal connection 6
■ ■2) ■ Rear vertical connection 7
■ ■2) ■3) Connecting flange 8
1)
For fixed-mounted versions only
2)
Not available for 3200 A
3)
Not available for 5000 A

Quick selection guide, pages 1/4 and 1/6


1/20 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

5 6 7 8 9 10 11 12 13 14 15 16 1
3WL5 – –

Motor
Stored energy Manual recharging With mechanical operation 1
mechanism of the stored energy With mechanical and electrical 110 V AC 50/60 Hz/110 … 125 V DC 2
mechanism operation, closing coil suitable 240 V AC 50/60 Hz/220 V DC
for uninterrupted duty, 3
100% OP
Motorized With mechanical and electrical 208 … 240 V AC 50/60 Hz/220 … 250 V DC 4
recharging operation, closing coil suitable 110 … 127 V AC 50/60 Hz/110 … 125 V DC 5
for uninterrupted duty,
24 V DC 6
100% OP

1st auxiliary release Without 1st auxiliary release A


With shunt trip (ST) 24 V DC B
100% OP 30 V DC C
48 V DC D
60 V DC E
110 ... 127 V AC, 110 ... 125 V DC F
208 ... 240 V AC, 220 ... 250 V DC G

2nd auxiliary Without 2nd auxiliary release A


release With shunt trip (ST) 100% OP 24 V DC B
30 V DC C
48 V DC D
60 V DC E
110 … 127 V AC 50/60 Hz/110 … 125 V DC F
208 … 240 V AC 50/60 Hz/220 … 250 V DC G
With undervoltage release (UVR), instantaneous 24 V DC J
30 V DC K
48 V DC L
60 V DC U
110 … 127 V AC 50/60 Hz/110 … 125 V DC M
208 … 240 V AC 50/60 Hz/220 … 250 V DC N
With undervoltage release (UVR), delay 0.2 … 3.2 s 48 V DC Q
110 … 127 V AC 50/60 Hz/110 … 125 V DC R
208 … 240 V AC 50/60 Hz/220 … 250 V DC S

Auxiliary switches
1st auxiliary switch block 2 NO + 2 NC 2

1st + 2nd auxiliary switch block 4 NO + 4 NC 4


6 NO + 2 NC 7
5 NO + 3 NC 8

Quick selection guide, pages 1/4 and 1/6


Siemens LV 18 · 07/2022 1/21
© Siemens 2022
Air Circuit Breakers | 3WL5

Structure of the article numbers


Basic configuration for DC non-automatic circuit breakers

The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 5 6 7 8 9 10 11 12 13 14 15 16
3WL5 – –

Non-automatic circuit breaker


and ETU
Size (SZ) 2 1) 2

Max. rated current In 3200 A 3 2

Short-circuit 25 kA at 690 V 8
breaking capacity Icu

Non-automatic air Without electronic trip unit A A


circuit breaker

Number of poles 3-pole 3

Connection
Type of mounting Fixed-mounted Vertical 1
Horizontal 2
1)
Can also be used for variable frequencies of 0 … 30 Hz.
Z option A17 must always be ordered additionally.

Quick selection guide, pages 1/4 and 1/10


1/22 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

5 6 7 8 9 10 11 12 13 14 15 16 1
3WL5 – –

Motor
Stored energy Manual recharging With mechanical operation 1
mechanism of the stored energy With mechanical and electrical 110 V AC 50/60 Hz/110 … 125 V DC 2
mechanism operation, closing coil suitable 240 V AC 50/60 Hz/220 V DC
for uninterrupted duty, 3
100% OP
Motorized With mechanical and electrical 208 … 240 V AC 50/60 Hz/220 … 250 V DC 4
recharging operation, closing coil suitable 110 … 127 V AC 50/60 Hz/110 … 125 V DC 5
for uninterrupted duty,
24 V DC 6
100% OP

1st auxiliary release Without 1st auxiliary release A


With shunt trip (ST) 24 V DC B
100% OP 30 V DC C
48 V DC D
60 V DC E
110 ... 127 V AC, 110 ... 125 V DC F
208 ... 240 V AC, 220 ... 250 V DC G

2nd auxiliary Without 2nd auxiliary release A


release With shunt trip (ST) 100% OP 24 V DC B
30 V DC C
48 V DC D
60 V DC E
110 … 127 V AC 50/60 Hz/110 … 125 V DC F
208 … 240 V AC 50/60 Hz/220 … 250 V DC G
With undervoltage release (UVR), instantaneous 24 V DC J
30 V DC K
48 V DC L
60 V DC U
110 … 127 V AC 50/60 Hz/110 … 125 V DC M
208 … 240 V AC 50/60 Hz/220 … 250 V DC N
With undervoltage release (UVR), delay 0.2 … 3.2 s 48 V DC Q
110 … 127 V AC 50/60 Hz/110 … 125 V DC R
208 … 240 V AC 50/60 Hz/220 … 250 V DC S

Auxiliary switches
1st auxiliary switch block 2 NO + 2 NC 2

1st + 2nd auxiliary switch block 4 NO + 4 NC 4


6 NO + 2 NC 7
5 NO + 3 NC 8

Quick selection guide, pages 1/4 and 1/10


Siemens LV 18 · 07/2022 1/23
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessory options

For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator

1 To specify the options, add "-Z" to the complete article number and indicate the Order code
appropriate order code(s).
3WL....-.....-.... -Z

Accessories for basic configuration


IT network capability at 690 V AC + 10% according to IEC 60947-2 Annex H
Rated operational voltage AC Size 2 3WL5225-4..31-... A17
3WL5225-4..32-... A17
3WL5232-4..31-... A17
Size 3 3WL5340-4..31-... A17
3WL5340-4..32-... A17
3WL5350-4..31-... A17
3WL5350-4..32-... A17
Rated operational voltage DC Size 2 3WL5232-8AA31-... A17
3WL5232-8AA32-... A17

Accessories for electronic trip units ETU


Rating plugs
• Only one module is possible per circuit breaker.
• As standard, the electronic trip units are equipped with a rating plug which is equal to the maximum rated circuit breaker current (In max).
The rated current of the selected rating plug must be less than In max
Module Sizes 1, 2 250 A B02
315 A B03
400 A B04
500 A B05
630 A B06
800 A B08
1000 A B10
Sizes 1, 2, 3 1250 A B12
1600 A B16
Sizes 2, 3 2000 A B20
2500 A B25
3000 A B30
3200 A B32
Size 3 4000 A B40
5000 A B50

Communication and measurement function


Breaker status sensor (BSS) For determining the statuses ON/OFF/Tripped F01
PROFIBUS DP communication port 1) Including COM15 and breaker status sensor (BSS) F02
Modbus RTU communication port 1) Including COM16 and breaker status sensor (BSS) F12
PROFINET IO/Modbus TCP Including COM35 and breaker status sensor (BSS) F35
communication port 1)
Measurement function Plus 2) Without communication module F05
1)
When ordering withdrawable circuit breaker and guide frame separately, specify order 2)
Additional voltage transformers are always required for connection of the measurement
code "F02", "F12" or "F35" only for withdrawable circuit breaker. function Plus, e.g. GE Grid Solutions Model 468.

System overview, page 1/16


1/24 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

To specify the options, add "-Z" to the complete article number and indicate the
1
Order code
appropriate order code(s).
3WL....-.....-.... -Z

Accessories for electronic trip units ETU


EMC filter
• Common-mode interference suppressor filters (e.g. in IT networks, caused by frequency converters)
• Insertion loss (asymmetric) in the range 40 kHz to 10 MHz >40 dB.
EMC filter F31

Overload and short-circuit protection for neutral conductors


• Only possible with 4-pole circuit breaker with ETU45B

Internal current transformer for Size 1 F23


N conductor Size 2 F23
Size 3 F23

Remote resetting
Automatic reset of the reclosing lockout K01
• Remote reset for displays and reset buttons including automatic reset of the reclosing lockout

Remote reset magnets 24 … 30 V DC K10


48 … 60 V DC K11
120 V AC 50/60 Hz/125 V DC K12
208 … 250 V AC 50/60 Hz/208 … 250 V DC K13

Connection
Connection technology for main connections (fixed-mounted versions)
Top:1) horizontal Size 1 ≤1600 A N11
Bottom: accessible from front, single Size 2 ≤2000 A N11
hole
≤2500 A N11
≤3200 A N11
Size 3 ≤4000 A N11

Top: vertical Size 1 ≤1600 A N20


Bottom: horizontal ≤2000 A N20
Size 2 ≤2000 A N20
≤2500 A N20
≤3200 A N20
Size 3 ≤4000 A N20
≤5000 A N20

Top: horizontal Size 1 ≤1600 A N24


Bottom: vertical ≤2000 A N24
Size 2 ≤2000 A N24
≤2500 A N24
≤3200 A N24
Size 3 ≤4000 A N24
≤5000 A N24
1)
Cannot be used for DC non-automatic air circuit breakers and circuit breakers with the Z option A17.

System overview, page 1/16


Siemens LV 18 · 07/2022 1/25
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessory options

For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator

1 To specify the options, add "-Z" to the complete article number and indicate the Order code
appropriate order code(s).
3WL....-.....-.... -Z

Connection
Connection technology for main connections (withdrawable versions)
Top and bottom: Size 1 ≤1600 A P00
accessible from front, single hole Size 2 ≤3200 A P00
Size 3 ≤4000 A P00

Top and bottom: Size 1 ≤1600 A P01


accessible from front, double hole Size 2 ≤3200 A P01
Size 3 ≤4000 A P01

Top: horizontal Size 1 ≤1600 A P07


Bottom: accessible from front, single Size 2 ≤3200 A P07
hole
Size 3 ≤4000 A P07

Connection technology for main connections (withdrawable versions)


Top: vertical Size 1 ≤1600 A P18
Bottom: horizontal Size 2 ≤3200 A P18
Size 3 ≤5000 A P18

Top: connecting flange Size 1 ≤1600 A P19


Bottom: horizontal Size 2 ≤3200 A P19
Size 3 ≤4000 A P19

Top: horizontal Size 1 ≤1600 A P23


Bottom: vertical Size 2 ≤3200 A P23
Size 3 ≤5000 A P23

Top: horizontal Size 1 ≤1600 A P28


Bottom: connecting flange Size 2 ≤3200 A P28
Size 3 ≤4000 A P28

Connection technology for auxiliary conductors


(for fixed-mounted and withdrawable circuit breakers)
Connection technology for screwless Fixed-mounted N61
terminals (tension spring) Withdrawable P61

System overview, page 1/16


1/26 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

To specify the options, add "-Z" to the complete article number and indicate the
1
Order code
appropriate order code(s).
3WL....-.....-.... -Z

Operating mechanisms and auxiliary releases


Motorized operating mechanisms Only possible if the 13th digit of the 24 ... 30 V DC M01
Article number = "1" 48 ... 60 V DC M03
110 … 127 V AC 50/60 Hz/110 … 125 V DC M05
208 … 240 V AC 50/60 Hz/220 … 250 V DC M06
Mechanical operating cycles counter, 5-digit 1)
C01
Closing coils • Suitable for uninterrupted duty, 24 V DC M21
100% OP 30 V DC M22
• Only possible if the 13th digit
48 V DC M23
of the Article number = "1"
60 V DC M24
110 … 127 V AC 50/60 Hz/110 … 125 V DC M25
208 … 240 V AC 50/60 Hz/220 … 250 V DC M26
• Not suitable for uninterrupted 24 V DC M31
duty, 5% OP, synchronizable 3) 48 V DC M33
• Only possible if the 13th digit
110 … 127 V AC 50/60 Hz/110 … 125 V DC M35
of the Article number = "1"
208 … 240 V AC 50/60 Hz/220 … 250 V DC M36
Opening coils (shunt trips) 2) 3)
Not suitable for uninterrupted duty, 24 V DC M41
5% OP, synchronizable 48 V DC M43
110 … 127 V AC 50/60 Hz/110 … 125 V DC M45
208 … 240 V AC 50/60 Hz/220 … 250 V DC M46

Auxiliary switches and signaling switches


Position signaling switches for guide frames 1 CO | 1 CO | 1 CO (connected | test | disconnected position) R15
3 CO | 2 CO | 1 CO (connected | test | disconnected position) R16
Signaling switches Ready-to-close signaling switch (S20) 1 NO C22
Spring charge signaling switch 4) (S21) 1 NO C20
For the first auxiliary release 5) (S22) 1 CO C26
For the second auxiliary release 5) (S23) 1 CO C27
1st tripped signaling switch 4) 6) (S24) 1 CO K07
2nd tripped signaling switch 4) 5) 6) (S25) 1 NO K06
1)
Only possible with motorized operating mechanism. 3)
Overexcited, i.e. switching time 50 ms (standard >80 ms). 5)
Only possible with option "K07".
2)
Only possible if the 14th digit of the Article number for the 4)
Not possible with "communication port" option, 6)
Not available for non-automatic air circuit breakers.
circuit breaker is "A", i.e. "without 1st auxiliary release". order code "F02", "F12" or "F35".

System overview, page 1/16


Siemens LV 18 · 07/2022 1/27
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessory options

For a complete and valid configuration of your air circuit breaker, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator

1 To specify the options, add "-Z" to the complete article number and indicate the Order code
appropriate order code(s).
3WL....-.....-.... -Z

Further accessories
Pushbuttons/shutdown switches/closing lockouts
EMERGENCY-OFF pushbuttons Mushroom pushbutton instead of the mechanical S24
OFF pushbutton
Electrical ON button on This prevents unauthorized electrical closing from the With sealing cap C11
operator panel 1) (S10) operator panel. Mechanical closing and remote With CES lock C12
closing remain possible. Possible only for circuit
breakers with closing coil (CC)
Motor shutdown switch on operator This prevents automatic charging of the stored energy S25
panel 2) (S12) mechanism by motorized operating mechanism

Special packaging for increased transport requirements (moisture protection)


Cardboard packaging with water-repellent coating on corrugated cardboard (moisture protection) A61

Shutters
Shutter: 2-part, lockable, with padlocks 3) 3-pole/4-pole Sizes 1, 2, 3 R21

Interlocking
Mechanical interlocking mechanism
• Interlocking module with Bowden cable 2 m
Mechanical interlock For fixed-mounted breakers S55
For withdrawable circuit breakers with guide frame R55
For guide frames (ordered separately) R56
For withdrawable circuit breakers (ordered separately) R57

Locking provisions (for fixed-mounted and withdrawable circuit breakers)


• The disconnector unit fulfills the requirements for main circuit breakers according to EN 60204-1
Locking provisions Against unauthorized closing from Made by CES S01
the operator panel Made by IKON S03
Assembly kit FORTRESS or CASTELL 4) S05
Assembly kit for padlocks 3) S07
Made by RONIS S08
Made by PROFALUX S09

Locking provisions (for fixed-mounted and withdrawable versions)


Locking provisions For charging handle with padlock 3) S33

Locking provisions (for withdrawable circuit breaker)


• The disconnector unit fulfills the requirements for main circuit breakers acc. to EN 60204-1, consisting of a lock in the guide frame,
active in the connected position, function is retained when circuit breaker is replaced.
• Not possible in combination with order code "R81", "R85" or "R86".
Locking provisions Against unauthorized closing from Made by CES R61
the operator panel Made by RONIS R68
Made by PROFALUX R60
1)
Not possible with "communication port" option, 2)
Only for breakers with motorized operating mechanism, 3)
Padlock not included in the scope of supply.
order code "F02", "F12" or "F35". not possible with order codes "C11", "C12". 4)
Locks must be ordered from the manufacturer.

System overview, page 1/16


1/28 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

To specify the options, add "-Z" to the complete article number and indicate the
1
Order code
appropriate order code(s).
3WL....-.....-.... -Z

Interlocking
Locking provisions (for withdrawable circuit breaker)
• Safety lock for mounting onto the circuit breaker
Locking provisions To prevent movement of the Made by CES S71
withdrawable circuit breaker Made by PROFALUX S75
Made by RONIS S76

Locking mechanisms
• Not possible in combination with order code "R81", "R85" or "R86".
• R30 and R50 only possible on complete order for a circuit breaker with a guide frame or when ordering the guide frame separately
For fixed-mounted circuit breakers To prevent opening of the cabinet door in ON position S30
For withdrawable circuit breakers To prevent opening of the cabinet door in connected position R30
To prevent movement when the cabinet door is open R50

Locking mechanisms to prevent movement of the withdrawable circuit breakers in


disconnected position
• Consisting of Bowden cable and lock in the control cabinet door
• Not possible in combination with order code "R30", "R50", "R61", "R68" or "R60".
Made by CES R81
Made by PROFALUX R85
Made by RONIS R86

Seals
Door sealing frame for degree of T40
protection IP41

System overview, page 1/16


Siemens LV 18 · 07/2022 1/29
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessory options
Further technical specifications

Manual operating mechanism 3WL5


Switching on/charging energy store
Maximum force required to operate the hand lever ≤230 N

1 Required number of strokes on the hand lever 9

Closing coils 3WL5


Primary operating range
Version For continuous command 5 % OP
(100 % OP)
Primary operating range 0.85 … 1.1 × Us 0.85 … 1.1 × Us
Extended operating range for battery operation 24 … 30 V DC, 48 … 60 V DC 0.85 … 1.26 × Us 0.85 … 1.26 × Us
110 … 125 V DC
220 … 250 V DC
Rated voltage
Rated control supply voltage Us 50/60 Hz AC 110 … 127 V, 208 … 240 V
DC 24 V, 30 V, 48 V, 60 V, 110 … 125 V, 220 … 250 V
Operation
Closing power 40 W/40 VA ≤ 60 V: 200 W
≥ 110 V: 250 W
Continuous power 8 W/8 VA –
Minimum command duration at 100% Us 60 ms 60 ms
Maximum command duration at 100% Us AC/DC – 2000 ms
Make time of the circuit breaker at 100% Us 100 ms 50 ms
Fuse protection of the control circuit at Us for closing coil
Smallest permissible DIAZED fuse, gL, slow-response 24 … 30 V DC 2A 10 A
48 … 60 V DC 2A 10 A
110 … 125 V DC/110 … 127 V AC 1A 4A
220 … 250 V DC/208 … 240 V AC 1A 2A
Miniature circuit breaker with C characteristic 24 … 30 V DC 2A 10 A
48 … 60 V DC 2A 10 A
110 … 125 V DC/110 … 127 V AC 1A 4A
220 … 250 V DC/208 … 240 V AC 1A 2A
Fuse protection of the control circuit at Us for motorized operating mechanism + closing coil
Smallest permissible DIAZED fuse, gL, slow-response 24 … 30 V DC 6A 10 A
48 … 60 V DC 6A 10 A
110 … 125 V DC/110 … 127 V AC 2A 4A
220 … 250 V DC/208 … 240 V AC 2A 2A
Miniature circuit breaker with C characteristic 24 … 30 V DC 6A 10 A
48 … 60 V DC 6A 10 A
110 … 125 V DC/110 … 127 V AC 2A 4A
220 … 250 V DC/208 … 240 V AC 2A 2A

Motor 3WL5
Primary operating range
Primary operating range 0.85 … 1.1 × Us
Extended operating range for battery operation At 24 V DC, 48 V DC 0.85 … 1.26 × Us
60 V DC, 110 V DC
220 V DC
Operation
Power consumption of motor AC/DC 135 VA/135 W
Time required to charge the spring energy store at 1 × Us ≤10 s
Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/ At Us = 24 … 30 V 6A
automatic circuit breaker with C characteristic At Us = 48 … 60 V 6A
(for different rated control supply voltages) At Us = 110 ... 125 V DC/ 2A
110 ... 127 V AC
At Us = 220 ... 250 V DC/ 2A
208 ... 240 V AC

System overview, page 1/16


1/30 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

Signals of the electronic trip unit 3WL5


Signals of the electronic trip unit
Measuring accuracy of the electronic trip unit Protective functions acc. to EN 60947; current indication
≤10%; measurement function for base quantities ≤1%;
measurement function for derived quantities ≤4%
1

Undervoltage releases UVR (F3) and UVR (F4) 3WL5


Primary operating range
Response values Pickup ≥0.85 × Us (circuit breaker can be closed)
Dropout 0.35 … 0.7 × Us (circuit breaker is tripped)
Primary operating range 0.85 … 1.1 × Us
Extended operating range for battery operation At 24 V DC, 30 V DC, 0.85 … 1.26 × Us
48 V DC, 110 V DC,
220 V DC
Rated voltage
Rated control supply voltage Us Instantaneous 50/60 Hz AC 110 … 127 V, 208 … 240 V, 380 … 415 V
Instantaneous DC 24 V, 30 V, 48 V, 60 V, 110 … 125 V, 220 … 250 V
Delayed 50/60 Hz AC 110 … 127 V, 208 … 240 V, 380 … 415 V
Delayed DC 48 V, 110 … 125 V, 220 … 250 V
Operation
Power consumption (pickup/uninterrupted duty) AC 20/5 VA
DC 20/5 W
Opening time of the circuit breaker
Version UVR (F3) Instantaneous ≤80 ms
With delay 200 ms
Version UVR-td (F8) With delay, td = 0.2 ... 3.2 s 0.2 … 3.2 s
Reset through additional NC ≤100 ms
contact – direct tripping
Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/ 1 A TDz (slow)/1 A
miniature circuit breaker with C characteristic

System overview, page 1/16


Siemens LV 18 · 07/2022 1/31
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessory options
Further technical specifications
Shunt trip (ST) (F1, F2) 3WL5
Primary operating range
Version For continuous 5% OP With spring energy
command store consisting of
1 (100% OP), locks shunt trip and
out on momentary capacitor trip device
-contact
commands
Primary operating range 0.85 … 1.1 × Us 0.85 … 1.1 × Us 0.85 … 1.1 × Us
Extended operating range for battery operation 0.85… 1.26 × Us 0.85 … 1.26 × Us –
Response values Pickup >0.7 × Us >0.7 × Us –
(circuit breaker is (circuit breaker is
tripped) tripped)
Rated operational voltage
Rated control supply voltage Us 50/60 Hz AC 110 … 127 V, 208 … 240 V 230 V
DC 24 ... 30 V, 48 ... 60 V, 110 … 125 V, 220 V
220 … 250 V
Operation
Closing power DC AC/DC 40 W/40 VA ≤ 60 V: 200 W 1 VA/1 W
≥ 110 V: 250 W
Continuous power AC/DC 8 W/8 VA – –
Minimum command duration at 100% Us 60 ms 60 ms –
Maximum command duration at 100% Us – 2000 ms –
Opening time of the circuit breaker at 100% Us 80 ms 50 ms 80 ms
Storage time at Us/Recharging time at Us – – max. 5 min/min. 5 s
Fuse protection of the control circuit at Us for shunt trip
Smallest permissible DIAZED fuse, gL, slow-response 24 … 30 V DC 2A 10 A –
48 … 60 V DC 2A 10 A –
110 … 125 V DC/110 … 127 V AC 1A 4A –
220 … 250 V DC/208 … 240 V AC 1A 2A –
Miniature circuit breaker with C characteristic 24 … 30 V DC 2A 10 A –
48 … 60 V DC 2A 10 A –
110 … 125 V DC/110 … 127 V AC 1A 4A –
220 … 250 V DC/208 … 240 V AC 1A 2A –

Remote reset magnet for mechanical tripped indicator (F7) 3WL5


Primary operating range
Primary operating range 0.85 … 1.1 × Us
Extended operating range for battery operation At 24 … 30 V DC, 48 … 60 V DC 0.7 … 1.26 × Us
110 … 125 V DC, 220 … 250 V DC
Operation
Power consumption AC/DC 60 VA/60 W
Min. command duration at Us for the remote reset magnet 60 ms
Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/ 2 A TDz (slow)/2 A at Us = 24 … 60 V DC,
automatic circuit breaker with C characteristic 1 A TDz (slow)/1 A at > 100 V DC and 100 V AC

Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8) 3WL5
Rated voltage
Rated insulation voltage Ui AC/DC 500 V
Rated operational voltage Ue AC/DC 500 V
Rated impulse withstand voltage Uimp 4 kV
Contact reliability From 1 mA at 5 V DC
Breaking capacity
Alternating current 50/60 Hz Rated operational voltage Ue 24 … 230 V 380 V, 400 V
Rated operational current Ie/AC-12 10 A 10 A
Rated operational current Ie/AC-15 4A 3A
Direct current Rated operational voltage Ue 24 V 48 V 110 V 220 V
Rated operational current Ie/DC-12 10 A 8A 3.5 A 1A
Rated operational current Ie/DC-13 8A 4A 1.2 A 0.4 A
Short-circuit protection
Largest permissible DIAZED fuse (operational class gL) 10 A TDz, 10 A Dz
Largest permissible miniature circuit breaker with C characteristic 10 A

System overview, page 1/16


1/32 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

Ready-to-close signaling switches (S20)


(acc. to DIN VDE 0630) 3WL5
Breaking capacity
Alternating current 50/60 Hz Rated operational voltage Ue 250 V 1
Rated operational current Ie 8A
Direct current Rated operational voltage Ue 125 V 250 V
Rated operational current Ie 0.4 A 0.2 A
Contact reliability From 1 mA at 5 V DC
Short-circuit protection
Largest permissible DIAZED fuse (operational class gL) 2 A Dz (quick)

Tripped signaling switches (S24) and signaling switches


for auxiliary releases (S22, S23) (acc. to DIN VDE 0630) 3WL5
Breaking capacity
Alternating current 50/60 Hz Rated operational voltage Ue 250 V
Rated operational current Ie/AC-12 8A
Direct current Rated operational voltage Ue 24 V 125 V 250 V
Rated operational current Ie/DC-12 6A 0.4 A 0.2 A
Contact reliability From 1 mA at 5 V DC
Short-circuit protection
Largest permissible DIAZED fuse (operational class gL) 6 A Dz (quick)
Tripped signaling switches
Signal duration after tripping Until manual or electrical remote reset (option)

Position signaling switches on guide frame 3WL5


Type of contacts
Message "Circuit breaker in connected position" 3 CO or 1 CO
"Circuit breaker in test position" 2 CO or 1 CO
"Circuit breaker in disconnected 1 CO or 1 CO
position"
Contact reliability From 1 mA at 5 V DC
Rated operational voltage
Rated insulation voltage Ui 50/60 Hz AC 440 V
DC 250 V
Rated operational voltage Ue 250 V
Rated impulse withstand voltage Uimp 4 kV
Breaking capacity
Rated operational current Ie Ie/AC-12 24 V 10 A, 110/127 V 10 A, 220/240 V 10 A,
320/440 V 10 A
Ie/AC-15 220/240 V 4 A, 320/440 V 3 A
Ie/DC-12 24 V 10 A, 48 V 2.5 A, 220/240 V 0.2 A
Ie/DC-13 24 V 3.0 A, 220/240 V 0.1 A
A 300 (AC) 120 V 6 A, 240 V 3 A
R 300 (DC) 125 V 0.22 A, 250 V 0.11 A
Short-circuit protection
Largest permissible DIAZED fuse (operational class gL) 8 A TDz (slow)
Largest permissible automatic circuit breaker with C characteristic 8 A TDz (slow)

System overview, page 1/16


Siemens LV 18 · 07/2022 1/33
© Siemens 2022
Air Circuit Breakers | 3WL5

Guide frames for AC

The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your guide frame, please use our online configurator at
www.siemens.com/lowvoltage/3wl-configurator
1 5 6 7 8 9 10 11 12 13 14 15 16
3WL9 2 5
– – A 1

Size (SZ) 1 1
2 2
3 3
SZ 1

SZ 2

SZ 3
Max. rated current 1000 A ■ – – 1
In 1600 A ■ – – 2
2000 A – ■ – 3
2500 A – ■ – 4
3000 A – ■ – 5
4000 A – – ■ 6
5000 A – – ■ 7

Number of poles 3-pole ■ ■ ■ A


4-pole ■ ■ ■ B

Main connection Front, single hole ■ ■ ■ 1)


A
Front, double hole ■ ■ ■1) B
Horizontal ■ ■ ■ C
Vertical ■ ■ ■ D
Connecting flange ■ ■ ■1) E
1)
Not available for rated circuit breaker current 5000 A

Options
5 6 7 8 9 10 11 12 13 14 15 16
3WL9 2 5
– – A 1

Number of auxiliary Without 0


supply connectors 1 connector 1
2 connectors 2
3 connectors 3
4 connectors 4

Type of auxiliary Without 2) 0


circuit connections With screw terminals (SIGUT, standard) 1
With screwless terminals (tension spring) 2

Position signaling Without 0


switches 1 CO | 1 CO | 1 CO (connected | test | isolated position) 1
3 CO | 2 CO | 1 CO (connected | test | isolated position) 2

Shutters Without A
With shutter, 2-part, lockable B
2)
Can only be selected if the number of auxiliary supply connectors = without

System overview, page 1/16


1/34 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

Accessories and spare parts

Accessories for electronic trip units ETU


Electronic trip units ETU45B with device holder and optional measurement function
• For replacement in existing circuit breakers, please specify the circuit breaker ID No. when ordering.
Type With protective function Measurement function Article No. 1
NSE0_01610b

ETU45B (without display) LSIN(G) Without 3WL9354-5AA00-0AA1


With measurement function Plus 3WL9354-5AA20-0AA1
Rating plugs
• With the rating plug selected, the maximum rated current In max of the circuit breaker must not be
exceeded. The following applies: In ≤In max.
NSE0_00992b
Size Rated current In Article No.
1, 2 250 A 3WL9111-2AA51-0AA0
315 A 3WL9111-2AA52-0AA0
400 A 3WL9111-2AA53-0AA0
500 A 3WL9111-2AA54-0AA0
630 A 3WL9111-2AA55-0AA0
800 A 3WL9111-2AA56-0AA0
1000 A 3WL9111-2AA57-0AA0
1, 2, 3 1250 A 3WL9111-2AA58-0AA0
1600 A 3WL9111-2AA61-0AA0
2, 3 2000 A 3WL9111-2AA62-0AA0
2500 A 3WL9111-2AA63-0AA0
3000 A 3WL9111-2AA77-0AA0
3200 A 3WL9111-2AA64-0AA0
3 4000 A 3WL9111-2AA65-0AA0
5000 A 3WL9111-2AA66-0AA0
Ground-fault modules
• Alarm and tripping
• For direct metering of the ground-fault current, e.g. in the star point of the transformer,
a 1200 A/1 A current transformer, class 1, is required. The internal load of the 3WL circuit breaker is
NSE0_01027a
0.11 Ω. If the ground-fault current is to be determined using the vectorial sum of the phases,
a transformer must be installed in the neutral conductor.
Type Accessory for Article No.
GFM AT 45B ETU45B 3WL9111-2AT53-0AA0
Display
For ETU Version Article No.
NSE0_01609

ETU45B 4-line 3WL9111-1AT81-0AA0

External current transformers for N conductor


Version Size Article No.
For mounting on busbar 1 3WL9111-0AA21-0AA0
NSE0_00990a

2 3WL9111-0AA22-0AA0
3 3WL9111-0AA23-0AA0
For busbar connection 1 3WL9111-0AA31-0AA0
NSE0_00991a

2 3WL9111-0AA32-0AA0
3 3WL9111-0AA33-0AA0
EMC filter
• Common-mode interference suppressor filters
(e.g. in IT networks, caused by frequency converters)
• Insertion loss (asymmetric) in the range 40 kHz to 10 MHz >40 dB.
Types Article No.
Only for ETU release 2 3WL9111-0AK32-0AA0

System overview, page 1/16


Siemens LV 18 · 07/2022 1/35
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessories and spare parts

Accessories for electronic trip units ETU


Sealable and lockable covers
Accessory for Article No.
NSE0_00983b

1 ETU25B
ETU45B 3WL9111-0AT45-0AA0

Automatic reset of the reclosing lockout


Version Article No.
Spare part for option K01 3WL9111-0AK21-0AA0
Remote reset magnets
• For mechanical tripped indicator
• Spare part for options K10 to K13
• Note: Automatic reset of the reclosing lockout 3WL9111-0AK21-0AA0 is also required
Voltage Article No.
24 … 30 V DC 3WA9111-0EM42
NSE0_00999a
48 … 60 V DC 3WA9111-0EM44
120 V AC/125 V DC 3WA9111-0EM45
208 ... 250 V AC/208 ... 250 V DC 3WA9111-0EM46
Retrofittable internal wiring
Use Male connector Accessory for Article No.
Internal wiring of CubicleBUS for Without male connector for ETU45B 3WL9111-0AK30-0AA0
connection to terminal X8 retrofitting the communication
For connection of the external N With male connector Not for ETU Release 2 3WL9111-0AK31-0AA0
and G transformers to terminal X8

Locking provisions and interlocks


Interlocking sets for mechanical Open/Close
• Consisting of two transparent covers each for sealing or for attaching padlocks
(padlocks not included in scope of supply)
• Cover with 6.35 mm hole (for tool actuation)
• Lock mount for safety lock for key operation
Version Article No.
NSE0_00980

Without safety lock 3WL9111-0BA21-0AA0


Made by CES 3WL9111-0BA22-0AA0
Made by IKON 3WL9111-0BA24-0AA0
Locking provision against unauthorized closing from the operator panel
• The disconnector unit fulfills the requirements for main circuit breakers acc. to EN 60204-1
• Spare part for options S01 to S09
NSE0_00981

Type Scope of supply Article No.


Assembly kit FORTRESS or CASTELL Without locks, cylinders or keys 3WL9111-0BA31-0AA0
Made by RONIS Locks, cylinders and keys included 3WL9111-0BA33-0AA0
Made by KIRK-Key Without locks, cylinders or keys 3WL9111-0BA34-0AA0
Made by PROFALUX Locks, cylinders and keys included 3WL9111-0BA35-0AA0
Made by CES Locks, cylinders and keys included 3WL9111-0BA36-0AA0
Made by IKON Locks, cylinders and keys included 3WL9111-0BA38-0AA0
Assembly kit for padlocks Without padlock 3WL9111-0BA41-0AA0
Locking provision against unauthorized closing, for withdrawable circuit breakers
• The disconnector unit fulfills the requirements for main circuit breakers acc. to EN 60204-1
• Consisting of lock in the cabinet door, active in connected position, function is retained when circuit
breaker is replaced
• Spare part for option R60, R61, R68
NSE0_00982 Type Scope of supply Article No.
Made by CES Locks, cylinders and keys included 3WL9111-0BA51-0AA0
Made by IKON Locks, cylinders and keys included 3WL9111-0BA53-0AA0
Made by KIRK-Key 1) Without locks, cylinders or keys 3WL9111-0BA57-0AA0
Made by RONIS Locks, cylinders and keys included 3WL9111-0BA58-0AA0
Made by PROFALUX Locks, cylinders and keys included 3WL9111-0BA50-0AA0
1)
Locks, cylinders and keys must be ordered from the manufacturer.

System overview, page 1/16


1/36 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

Locking provisions and interlocks


Locking provisions for charging handle with padlock
Version Scope of supply Article No.
Spare part for option S33 Without padlock 3WL9111-0BA71-0AA0 1

NSE0_00984

Locking provision to prevent movement of the withdrawable circuit breaker


• Safety lock for mounting onto the circuit breaker
• Spare part for option S71, S75, S76
Type Scope of supply Article No.
NSE0_00986 Made by CES Locks, cylinders and keys included 3WL9111-0BA73-0AA0
Made by IKON Locks, cylinders and keys included 3WL9111-0BA75-0AA0
Made by PROFALUX Locks, cylinders and keys included 3WL9111-0BA76-0AA0
Made by RONIS Locks, cylinders and keys included 3WL9111-0BA77-0AA0
Made by KIRK-Key 1) Without locks, cylinders or keys 3WL9111-0BA80-0AA0
Interlocking systems
• 2 of the same keys for 3 circuit breakers
• Locking provision in OFF position
• Lock in the operator panel
• A maximum of 2 circuit breakers can be switched on
Type Article No.
Made by CES 3WL9111-0BA43-0AA0
Locking mechanisms to prevent movement of the withdrawable circuit breakers in disconnected position
• Consisting of Bowden cable and lock in the cabinet door on the circuit breaker
• Spare part for option R81, R85, R86
• Note: Not possible in combination with "Locking mechanism to prevent opening of the cabinet door"
NSE0_00987 (order code "R30") or "Locking mechanism to prevent movement with the cabinet door open"
(order code "R50").
Type Article No.
Made by CES 3WL9111-0BA81-0AA0
Made by IKON 3WL9111-0BA83-0AA0
Made by PROFALUX 3WL9111-0BA85-0AA0
Made by RONIS 3WL9111-0BA86-0AA0
Locking mechanisms to prevent opening of the cabinet door in ON position
• Fixed-mounted
• Defeatable
• Note: Not possible in combination with "Locking mechanism to prevent movement of the
NSE0_00988 withdrawable circuit breakers in disconnected position" (order codes "R81", "R85" or "R86").
Version Article No.
Spare part for option S30 3WL9111-0BB12-0AA0
Locking mechanisms to prevent opening of the cabinet door
• Guide frames
• Defeatable
• Note: Not possible in combination with "Locking mechanism to prevent movement of the
withdrawable circuit breakers in disconnected position" (order codes "R81", "R85" or "R86").
Version Article No.
Spare part for option R30 3WL9111-0BB13-0AA0
Locking mechanisms to prevent movement with the cabinet door open
• Guide frames
• Note: Not possible in combination with "Locking mechanism to prevent movement of the
withdrawable circuit breakers in disconnected position" (order codes "R81", "R85" or "R86").
Version Article No.
Spare part for option R50 3WL9111-0BB15-0AA0
1)
Locks, cylinders and keys must be ordered from the manufacturer

System overview, page 1/16


Siemens LV 18 · 07/2022 1/37
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessories and spare parts

Locking provisions and interlocks


Mechanical interlocks
• With Bowden cable 2000 mm (one required for each circuit breaker)

1 Type When ordered separately Spare part for Article No.


NSE0_00989

Fixed-mounted circuit breaker – Option S55 3WL9111-0BB21-0AA0


Module for withdrawable circuit – Option R55 3WL9111-0BB24-0AA0
breakers with guide frame
Module for guide frame ✓ Option R56 3WL9111-0BB22-0AA0
Module for withdrawable circuit breaker ✓ Option R57 3WL9111-0BB23-0AA0
Adapter for size 3 withdrawable circuit ✓ – 3WL9111-0BB30-0AA0
breaker
Couplings on the circuit breaker (with ring) for mutual interlocking
• Can be used in all circuit breakers
NSE0_01886

Article No.
3WL9112-8AH47-0AA0
Bowden cables
Length Article No.
2000 mm 3WL9111-0BB45-0AA0
3000 mm 3WL9111-0BB46-0AA0
4500 mm 3WL9111-0BB47-0AA0

Test devices
Manual tester, Release 2 for electronic trip units ETU25B to ETU45B
• For testing the Electronic Trip Unit functions of all 3WL ETUs (Release 1 and Release 2)
Article No.
3WL9111-0AT32-0AA0

Function test unit


• For testing the tripping characteristics for electronic trip units ETU15B to ETU76B
(Release 1 and Release 2)
Article No.
3WL9111-0AT44-0AA0
TD400 Kit IEC 1)
• Commissioning/Service Tool for UL 3WL5 (ETU release 1)
• With adapter, cable and case
Article No.
3VW9011-0AT41
TD400 adapter (spare part)
Version Article No.
for 3VA 3VW9011-0AT43
for 3WL ETU release 1 3VW9011-0AT44

Storage devices
Capacitor trip device
• For shunt trips
• Storage time 5 min
• Also suitable for 3VL circuit breakers
• Note: Rated control supply voltage must match the rated control supply voltage of the shunt trips.
Rated control supply voltage/rated operational voltage Article No.
50/60 Hz AC DC
220 … 240 V 220 … 250 V 3WL9111-0BA14-0AA0
1)
A country-specific radio license is required to operate the Bluetooth interface.
Before activating the Bluetooth function, ensure that the license is available:
www.siemens.com/lowvoltage/certificates

System overview, page 1/16


1/38 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

Indicators and control elements


Ready-to-close signaling switches (S20)
Version Contacts Article No.
Spare part for option C22 1 NO 3WL9111-0AH01-0AA0 1

NSE0_00993a

Signaling switch (S22 or S23)


• Not possible with communication port, order code "F02", "F12" or "F35"
• Auxiliary supply connector X7 required for circuit breakers or guide frames.
If this is not already available, please order additionally
NSE0_00994b

Version Contacts Article No.


Spare part for options C26 to C27 1st or 2nd auxiliary release 3WL9111-0AH02-0AA0

1st tripped signaling switch (S24)


• Not possible with communication port, order code "F02", "F12" or "F35"
• Auxiliary supply connector X7 required for circuit breakers or guide frames.
If this is not already available, please order additionally
Version Contacts Article No.
Spare part for option K07 1 CO 3WL9111-0AH14-0AA0
2nd tripped signaling switch (S25)
• Not possible with communication port, order code "F02", "F12" or "F35"
• Auxiliary supply connector X7 required for circuit breakers or guide frames.
If this is not already available, please order additionally
• Can only be used in combination with 1st tripped signaling switch
Version Contacts Article No.
Spare part for option K06 1 NO 3WL9111-0AH17-0AA0
Operating cycle counters
• Only in conjunction with motorized operating mechanism
Type Version Article No.
Spare part for option C01 Mechanical 3WL9111-0AH07-0AA0

NSE0_00995a

Spring charge signaling switch


• Not possible with communication port, order code "F02", "F12" or "F35".
• Auxiliary supply connector X7 required for circuit breakers or guide frames.
If this is not already available, please order additionally
Version Contacts Article No.
Spare part for option C20 1 NO 3WL9111-0AH08-0AA0
Position signaling switches for guide frames
Version Contacts Article No.
Spare part for options R15 to R16 1st block (3 CO) 3WL9111-0AH11-0AA0
2nd block (6 CO) 3WL9111-0AH12-0AA0
NSE0_00996a

Local electric close (S10) for operator panel


• Not possible with communication port, order code "F02", "F12" or "F35"
• Not possible with motor shutdown switch
• Button + wiring (Auxiliary supply connector X7 required for circuit breakers or guide frames.
If this is not already available, please order additionally)
• Note: Possible only for circuit breakers with closing coil.
NSE0_00997a Version Type Article No.
Spare part for options C11 to C12 With sealing cap C11 3WL9111-0AJ02-0AA0
With CES assembly kit C12 3WL9111-0AJ03-0AA0
With IKON assembly kit 3WL9111-0AJ05-0AA0
Motor shutdown switch (S12)
• Mounting onto operator panel
• Not possible with local electric close
Version Article No.
Spare part for option S25 3WL9111-0AJ06-0AA0

System overview, page 1/16


Siemens LV 18 · 07/2022 1/39
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessories and spare parts

Indicators and control elements


EMERGENCY-OFF pushbuttons
• Mushroom pushbutton instead of the mechanical OFF pushbutton

1 Type Article No.


Spare part for option S24 3WL9111-0BA72-0AA0

NSE
0_00
985

Auxiliary conductor connections


Male connectors for circuit breakers 1

Article No.
NSE0_00978

3WA9111-0AB01

Extension for male connector


• Male connector must be ordered separately
Version Article No.
1000 V 3WA9111-0AB02
Auxiliary supply connection for circuit breakers or guide frames 2

Version Article No.


Screw connection (SIGUT) 3WA9111-0AB03
NSE0_01268

Screwless connection (tension spring) 3WL9111-0AB04-0AA0


NSE0_01269

Coding kits 3

Version Article No.


NSE0_00974

For fixed-mounted X5 to X8 3WA9111-0AB07

Sliding contact modules for guide frames 4

Article No.
NSE0_00977a

3WA9111-0AB08

One-part sliding contact modules for guide frames 5

Version Article No.


NSE0_01586

Screw connection (SIGUT) 3WL9111-0AB18-0AA0

Blanking blocks for circuit breakers


Article No.
3WA9111-0AB12
For a complete auxiliary current connection you must order:
Fixed-mounted version:   +
1   +2    
3
Withdrawable version:   +
1   +4   2 or   +
1 5

System overview, page 1/16


1/40 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

Auxiliary releases
Closing coils/shunt trips
Version Voltage Article No.
100% OP 24 … 30 V DC 3WA9111-0AD02 1
48 … 60 V DC 3WA9111-0AD04
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AD05
0 0
E0
_0
10
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AD06
NS

Closing coil (CC)


• For momentary duty, with cut-off switch S15
Version Voltage Article No.
5 % OP 24 … 30 V DC 3WA9111-0AD12
Switching time 50 ms 48 … 60 V DC 3WA9111-0AD14
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AD15
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AD16
Shunt trip (ST)
• For momentary duty, with cut-off switch S14
Version Voltage Article No.
5 % OP 24 … 30 V DC 3WA9111-0AD22
Switching time 50 ms 48 … 60 V DC 3WA9111-0AD24
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AD25
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AD26
Undervoltage release
Version Voltage Article No.
Instantaneous 24 V DC 3WA9111-0AE02
NSE0_01001

30 V DC 3WL9111-0AE02-0AA0
48 V DC 3WA9111-0AE04
60 V DC 3WL9111-0AE07-0AA0
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AE05
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AE06
Delayed 48 V DC 3WA9111-0AE13
NSE0_01002

110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AE15


220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AE16

Operating mechanism
Motorized operating mechanisms
• Auxiliary supply connector X5 required for circuit breakers or guide frames.
If this is not already available, please order additionally
Voltage Article No.
24 ... 30 V DC 3WA9111-0AF02
NSE0_01003a

48 ... 60 V DC 3WA9111-0AF04
110 ... 125 V DC/110 ... 127 V AC 3WA9111-0AF05
220 ... 250 V DC/208 ... 240 V AC 3WA9111-0AF06

Auxiliary contacts
Auxiliary switch blocks
Contacts Article No.
NSE0_01004

2 NO + 2 NC 3WL9111-0AG01-0AA0
2 NO 3WL9111-0AG02-0AA0
1 NO + 1 NC 3WL9111-0AG03-0AA0

System overview, page 1/16


Siemens LV 18 · 07/2022 1/41
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessories and spare parts

Door sealing frames, hoods, shutters


Door sealing frames
Version Article No.

1 Spare part for option T40 3WL9111-0AP01-0AA0

Protective covers IP55


• Cannot be used in conjunction with door sealing frames
NSE0_01028a

• Hood removable and can be opened on both sides


Article No.
3WL9111-0AP03-0AA0
Shutters
Version Number of poles Size Breaking capacity
Spare part for option R21 3-pole 1 N, S, H 3WL9111-0AP04-0AA0
2 N, S, H 3WL9111-0AP06-0AA0
3 H, C 3WL9111-0AP07-0AA0
4-pole 1 N, S, H 3WL9111-0AP08-0AA0
2 N, S, H 3WL9111-0AP11-0AA0
3 H, C 3WL9111-0AP12-0AA0

Coding for withdrawable version


Coding for withdrawable version
• By customer, for 36 coding variants
Size Article No.
NSE0_01009

1 and 2 3WL9111-0AR12-0AA0
3 3WL9111-0AR13-0AA0

Support brackets
Support brackets
• For mounting fixed-mounted circuit breakers on vertical plane
NSE0_01022

• Only for sizes 1 and 2 (1 set = 2 units)


Article No.
3WL9111-0BB50-0AA0

CubicleBUS modules
• Each CubicleBUS module is supplied with a 0.2 m pre-assembled cable to connect the modules with each other.
A longer pre-assembled cable is required for connection to the circuit breaker.
• All communication components, CubicleBUS modules and measurement functions are available for the electronic trip units
ETU45B.
Modules of the CubicleBUS
Type Article No.
NSE0_01023a

Digital output module with rotary coding switch, relay outputs 3WL9111-1AT26-0AA0
Digital output module, configurable, relay outputs 3WL9111-1AT20-0AA0
Digital input module 3WL9111-1AT27-0AA0
Analog output module 3WL9111-1AT23-0AA0
ZSI module 3WL9111-1AT21-0AA0
Preassembled cables for CubicleBUS modules
For connection to 3WL Length Article No.
With COM15/COM16/COM35 0.2 m 3WL9111-0BC04-0AA0
1m 3WL9111-0BC02-0AA0
2m 3WL9111-0BC03-0AA0
Without COM15/COM16/COM35 2m 3WL9111-0BC05-0AA0

System overview, page 1/16


1/42 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

Retrofitting and spare parts


• All communication components, CubicleBUS modules and measurement functions are available for the electronic trip units
ETU45B.
COM35 PROFINET IO / Modbus TCP modules 1
Version Article No.
For electronic trip units ETU45B 3WL9111-1AT66-0AA0

COM15 PROFIBUS module


Version Article No.
For electronic trip units ETU45B 3WL9111-1AT65-0AA0

COM16 Modbus module


Version Article No.
For electronic trip units ETU45B 3WL9111-1AT15-0AA0

Breaker status sensor (BSS)


Version Article No.
For electronic trip units ETU45B 3WL9111-1AT16-0AA0

Measurement function Plus


• A measuring accuracy of 3% is achieved if retrofitted.
Version Article No.
For electronic trip units ETU45B 3WL9111-1AT03-0AA0
external voltage transformer required,
e.g. GE Grid Solutions Model 468.

Main conductor connections, fixed-mounted versions (essential accessory)


Front-accessible main connections, single hole at top
Size Rated current In Article No.
1 ≤1000 A 3WL9111-0AL01-0AA0
1250 … 1600 A 3WL9111-0AL02-0AA0
NSE0_01010

2 ≤2000 A 3WL9111-0AL03-0AA0
≤2500 A 3WL9111-0AL04-0AA0
≤3200 A 3WL9111-0AL05-0AA0
3 ≤4000 A 3WL9111-0AL06-0AA0
Front-accessible main connections, single hole at bottom
Size Rated current In Article No.
1 ≤1000 A 3WL9111-0AL51-0AA0
1250 … 1600 A 3WL9111-0AL52-0AA0
NSE0_01010

2 ≤2000 A 3WL9111-0AL53-0AA0
≤2500 A 3WL9111-0AL54-0AA0
≤3200 A 3WL9111-0AL55-0AA0
3 ≤4000 A 3WL9111-0AL56-0AA0
Front-accessible main connections according to DIN 43673, double hole at top
Size Rated current In Article No.
1 ≤1000 A 3WL9111-0AL07-0AA0
1250 … 1600 A 3WL9111-0AL08-0AA0
NSE0_01010

2 ≤2000 A 3WL9111-0AL11-0AA0
≤2500 A 3WL9111-0AL12-0AA0
≤3200 A 3WL9111-0AL13-0AA0
3 ≤4000 A 3WL9111-0AL14-0AA0

System overview, page 1/16


Siemens LV 18 · 07/2022 1/43
© Siemens 2022
Air Circuit Breakers | 3WL5

Accessories and spare parts

Main conductor connections, fixed-mounted versions (essential accessory)


Front-accessible main connections according to DIN 43673, double hole at bottom
Size Rated current In Article No.
1 1 ≤1000 A 1) 3WL9111-0AL57-0AA0
1250 … 1600 A 3WL9111-0AL58-0AA0
NSE0_01011

2 ≤2000 A 3WL9111-0AL61-0AA0
≤2500 A 3WL9111-0AL62-0AA0
≤3200 A 3WL9111-0AL63-0AA0
3 ≤4000 A 3WL9111-0AL64-0AA0
Rear vertical main connections
Size Rated current In Article No.
1 1) ≤1600 A 3WL9111-0AM01-0AA0
2 2) ≤3200 A 3WL9111-0AM02-0AA0
NSE0_01012

3 ≤6300 A 3WL9111-0AM03-0AA0

1)
In the case of vertical connection size 1 with breaking capacity N and S, up to 1000 A one 3WL9111-0AM01-0AA0 vertical connection is required up to 1600 A or
with breaking capacity H two 3WL9111-0AM01-0AA0 vertical connections are required.
2)
In the case of vertical connection size 2, up to 2500 A one 3WL9111-0AM02-0AA0 vertical connection is required up to 3200 A two 3WL9111-0AM02-0AA0 vertical connections are
required.

Main conductor connections, withdrawable versions (essential accessory)


Front-accessible main connections, single hole at top or at bottom 1)
Size Rated current In Article No.
1 ≤1000 A 3WL9111-0AN01-0AA0
1250 … 1600 A 3WL9111-0AN02-0AA0
NSE0_01013

2 ≤2000 A 3WL9111-0AN03-0AA0
≤2500 A 3WL9111-0AN04-0AA0
≤3200 A 3WL9111-0AN05-0AA0
3 ≤4000 A 3WL9111-0AN06-0AA0
Front-accessible main connections according to DIN 43673, double hole at top or at bottom 1)
Size Rated current In Article No.
1 ≤1000 A 3WL9111-0AN07-0AA0
1250 … 1600 A 3WL9111-0AN08-0AA0
NSE0_01014

2 ≤2000 A 3WL9111-0AN11-0AA0
≤2500 A 3WL9111-0AN12-0AA0
≤3200 A 3WL9111-0AN13-0AA0
3 ≤4000 A 3WL9111-0AN14-0AA0
1)
When using front-accessible main connections (withdrawable circuit breakers) supports are required

System overview, page 1/16


1/44 Siemens LV 18 · 07/2022
© Siemens 2022
3WL5 | Air Circuit Breakers

Main conductor connections, withdrawable versions (essential accessory)


Supports for front and DIN connecting bars
Number of poles Size Article No.
3-pole for 3 bars 1 3WL9111-0AN41-0AA0 1
2 3WL9111-0AN42-0AA0
NSE0_01017

3 3WL9111-0AN43-0AA0
4-pole for 4 bars 1 3WL9111-0AN44-0AA0
2 3WL9111-0AN45-0AA0
3 3WL9111-0AN46-0AA0
Rear vertical main connections
Size Rated current In Article No.
NSE0_01015

1 ≤1000 A 3WL9111-0AN15-0AA0
1250 … 1600 A 3WL9111-0AN16-0AA0
2 ≤2000 A 3WL9111-0AN17-0AA0
≤2500 A 3WL9111-0AN18-0AA0
≤3200 A 3WL9111-0AN21-0AA0
3 ≤5000 A 3WL9111-0AN22-0AA0
Rear horizontal main connections
Size Rated current In Article No.
1 ≤1000 A 3WL9111-0AN32-0AA0
1250 … 1600 A 3WL9111-0AN33-0AA0
1 ≤2000 A 3WL9111-0AN34-0AA0
≤2500 A 3WL9111-0AN35-0AA0
≤3200 A 3WL9111-0AN36-0AA0
3 ≤5000 A 3WL9111-0AN37-0AA0
Connecting flange
Size Rated current In Article No.
1 ≤1000 A 3WL9111-0AN24-0AA0
1250 … 1600 A 3WL9111-0AN25-0AA0
NSE0_01016

2 ≤2000 A 3WL9111-0AN26-0AA0
≤2500 A 3WL9111-0AN27-0AA0
≤3200 A 3WL9111-0AN28-0AA0
3 ≤4000 A 3WL9111-0AN31-0AA0

Conversion kit
Conversion kit for converting fixed-mounted circuit breakers into withdrawable circuit breakers
• Only for AC circuit breakers/non-automatic air circuit breakers
• Guide frames and sliding contact modules must be ordered separately
Number of poles Size Article No.
3-pole 1 3WL9111-0BC11-0AA0
2 3WL9111-0BC12-0AA0
3 3WL9111-0BC13-0AA0
4-pole 1 3WL9111-0BC14-0AA0
2 3WL9111-0BC15-0AA0
3 3WL9111-0BC16-0AA0

System overview, page 1/16


Siemens LV 18 · 07/2022 1/45
© Siemens 2022

One system. For all applications

Requirements for cost- and energy-efficient


operation of electrical power distribution are
on the increase. Whether in industrial plants, in
infrastructure or in buildings: As a modular, highly
adaptable system, the 3VA series of molded case
circuit breakers ensures fully reliable protection of
personnel and plant, and supports every process
phase – from planning to operation of electrical
power distribution.

Comprehensively certified. Deployable worldwide.

3VA molded case circuit breakers are available in


various ranges with IEC approval; other ranges are
available that comply with standard IEC 60947
and standard UL 489. The system is therefore
ideally suited for mechanical engineering
companies and switchgear manufacturers.
The full range of functionalities of molded
case circuit breakers can be used for plant and
equipment operating in Europe and North
America, with absolute standards compliance
assured.
© Siemens 2022

Molded Case Circuit Breakers

All the information you need 2/2

Molded case circuit breakers for all applications 2/4

Quick selection guide 2/6

Molded case circuit breakers and accessories 2/6

3VA5 molded case circuit breakers up to 2000 A 2/8

3VA6 molded case circuit breakers up to 2000 A 2/12

Trip units 2/16

Online configurator highlights 2/18

3VA51 – 3VA69 new 2/20

System overview 2/20

Structure of the article numbers 2/22

Internal accessories 2/26

Manual operators 2/28

Motor operators 2/40

Connection technology 2/42

Plug-in and withdrawable technology 2/70

Communication 2/73

Locking, blocking and interlocking 2/78

Cover frame and mounting 2/82

3VL 2/86

3VL up to 1600 A, according to UL 489 2/86

Siemens LV 18 · 07/2022 2/1


© Siemens 2022
Molded Case Circuit Breakers | All the information you need

A multitude of additional information ...

Information + ordering

All the important things at a glance Everything you need for your order
2
For information about molded case circuit breakers, Refer to the Industry Mall for an overview of your
please visit our website www.siemens.com/3VA products
• 3VA molded case circuit breakers, UL/IEC
sie.ag/2yPsA2e
Your product in detail
Direct forwarding to the individual products in the
Industry Mall by clicking on the article number in the
The Siemens Industry Online Support (SIOS) provides catalog or by entering this web address incl. article number
comprehensive information www.siemens.com/product?Article No.
www.siemens.com/lowvoltage/product-support
• Technical basic information
− 3VA molded case circuit breakers (109766672) Configurators
The relevant tender specifications can be found at
www.siemens.com/lowvoltage/tenderspecifications The configurator reduces the time and effort required in
Use our conversion tool for quick and easy conversion to the planning and ordering process, and allows for individ­
Siemens products ual adaptations. Configure your 3VA molded case circuit
www.siemens.com/conversion-tool breaker at
www.siemens.com/lowvoltage/3va-ul-configurator
The following are additionally available for your 3VA
Siemens YouTube channel molded case circuit breaker:
• 3D views
• 3VA molded case circuit breakers (general) • CAD data
bit.ly/2xNxlFA • Unit wiring diagrams
• Dimension drawings

The fast track to the experts

Contact persons in your region


We offer a comprehensive portfolio of services. Competent expert advice on technical questions with a wide
You can find your local contacts at range of demand-optimized services for all our products and
www.siemens.com/lowvoltage/components/contact systems.
You can find further information on services at Assistance with technical queries is provided at
www.siemens.com/service-catalog www.siemens.com/support-request

2/2 Siemens LV 18 · 07/2022


© Siemens 2022
All the information you need | Molded Case Circuit Breakers

... can be found in our online services

Commissioning + operation

SENTRON powerconfig Manuals

The combined commissioning and service tool SENTRON Manuals are available for downloading in Siemens
powerconfig for communication-capable measuring Industry Online Support (SIOS) at
devices, circuit protection devices and circuit breakers. www.siemens.com/lowvoltage/manuals
Free download SENTRON powerconfig via • Configuration manual
www.siemens.com/powerconfig − 3VA selectivity (109743975)
Free download SENTRON powerconfig mobile via • Communication manual
App Store and Play Store − 3VA molded case circuit breakers with IEC and UL
certification (98746267)
• Equipment manual
− 3VA molded case circuit breakers with UL and IEC
Your product in detail
certification (109758561)

The Siemens Industry Online Support (SIOS) provides


detailed technical information
www.siemens.com/lowvoltage/product-support
Face-to-face or online training
• Operating instructions
Our training courses can be found at
• Characteristic curves
www.siemens.com/sitrain-lowvoltage
• Certificates
• 3VA molded case circuit breakers (WT-LVA3VA)
Comprehensive mobile support via the Siemens Industry
• Protection systems in low-voltage power distribution
Online Support app available for download from the
(WT-LVAPS)
App Store and Play Store
• Communication with SENTRON components (LV-COM)
You will find further information under:
• Project planning and selection of SENTRON circuit
www.siemens.com/support-app
breakers (LV-CBPROJ)
Provision of 3D data (step and u3d data formats)
• Siemens Industry Mall
www.siemens.com/lowvoltage/mall
• Image database
www.siemens.com/lowvoltage/picturedb
Engineering data for CAD or CAE systems are available in
the CAx Download Manager at
www.siemens.com/cax

Technical overview – Molded case circuit breakers

The fast way to get you to our online services


This page provides you with comprehensive information and links on molded case circuit breakers
www.siemens.com/lowvoltage/product-support (109767421)

Siemens LV 18 · 07/2022 2/3


© Siemens 2022
Molded Case Circuit Breakers | Molded case circuit breakers for all applications

Molded case circuit breakers


for all applications

Ideal for standard


2
applications
The 3VA5 molded case circuit breaker is suitable for numerous
applications in infrastructure and industrial plants – and this
applies worldwide thanks to IEC and UL certification.
Its additional functionality is the perfect complement to the
circuit breaker series – and it features a consistent design and
wide range of accessories.
Special features
• Compact design
• AC/DC applications
• Universal platform of accessories
• 1, 2, 2 in 3, 3 and 4-pole version
• Also available as a molded case switch and motor circuit
3VA51 … 3VA59 protector
molded case circuit breakers • Available in different sizes with rated currents
from 1 ... 2000 A

UL certificate
• 3VA5/6 molded case circuit breaker for line protection
E364397 (CCN 1): DIVQ)
• 3VA5/6 motor circuit protector: E482699 (CCN: DKPU2)
• 3VA5/6 molded case switch: E482701 (CCN: WJAZ)
• Accessories: E354102
1)
CCN = UL Category Code Number

2/4 Siemens LV 18 · 07/2022


© Siemens 2022
Molded case circuit breakers for all applications | Molded Case Circuit Breakers

Perfect for advanced


2
applications
Whether in industry or infrastructure – the 3VA6 molded case
circuit breaker can handle all tasks with ease. It can be easily
integrated into higher-level energy management or automation
systems.
It reliably signals plant conditions and measured values, helping
you to increase plant availability and identify any potential for
savings.
Special features
• Very good selective protection response
• AC applications
• Integrated measurement function for current, voltage and
energy values
3VA61 … 3VA69 • Connection to a communication system
molded case circuit breakers • Various circuit breaker versions available as "100% rated"
(uninterrupted current carrying) and as „current limiting“
breaker according to UL 489
• Integrated DAS+ (Dynamic Arc-Flash Sentry) function in
accordance with American standard NEC 240.87 to reduce
arc flash energy in the switchboard for frame sizes
1200, 1600 and 2000 A (3VA UL Large Frame)
• Available in different sizes with rated currents
from 25 ... 2000 A

UL certificate
• 3VA5/6 molded case circuit breaker for line protection
E364397 (CCN 1): DIVQ)
• 3VA5/6 motor circuit protector: E482699 (CCN: DKPU2)
• 3VA5/6 molded case switch: E482701 (CCN: WJAZ)
• Accessories: E354102
1)
CCN = UL Category Code Number

Siemens LV 18 · 07/2022 2/5


© Siemens 2022
Molded Case Circuit Breakers | Quick selection guide

Molded case circuit breakers


and accessories

Protective functions 3VA51 3VA52 3VA53 3VA54 3VA55 3VA57 3VA58 3VA59
new new new
Size 125 A 250 A 400 A 600 A 800 A 1200 A 1600 A 2000 A
Molded case switch (MCS)
With short-circuit release for intrinsic device ■ ■ ■ ■ ■ ■ ■ ■
protection
Thermal-magnetic
Line protection ■ ■ ■ ■ ■ ■ ■ ■
Protective circuit breaker for motor starter ■ ■ ■ ■ ■ – – –
combinations, motor circuit protector (MCP)
Electronic
Line protection – – – – – – – –
Line protection, with display – – – – – – – –
Line protection, with display and measurement – – – – – – – –
function
Protective circuit breaker for motor starter – – – – – – – –
combinations, motor circuit protector (MCP)

Accessories
Size 125 A 250 A 400 A 600 A 800 A 1200 A 1600 A 2000 A
Accessories
Auxiliary switches and signaling switches ■ ■ ■ ■ ■ ■ ■ ■
Auxiliary releases ■ ■ ■ ■ ■ ■ ■ ■
Connection technology ■ ■ ■ ■ ■ ■ ■ ■
Plug-in version – – – – – – – –
Withdrawable version – – – – – – – –
Front mounted rotary operator ■ ■ ■ ■ ■ ■ ■ ■
Door mounted rotary operator ■ ■ ■ ■ ■ ■ ■ ■
Side wall mounted rotary operator ■ ■ – – – – – –
Operating unit with Bowden cable/linkage ■ ■ ■ ■ – – – –
Motor operator MO 320 (mounted on front) ■ ■ ■ ■ – – – –
Motor operator with SEO520 stored energy – ■ – – – – – –
operator
Locking, blocking and interlocking ■ ■ ■ ■ ■ ■ ■ ■
Communications interface – – – – – – – –
EFB300 – – – – – – – –
MMB300 – – – – – – – –
Testing and commissioning devices – – – – – – – –
Cover frame ■ ■ ■ ■ ■ ■ ■ ■
Mounting plate for circuit breaker – – – – – – ● ●
Assembly kit for multiple feed-in terminals – – – – – ■ ■ –
● Must be used ■ Available – Not available/not present

2/6 Siemens LV 18 · 07/2022


© Siemens 2022
Quick selection guide | Molded Case Circuit Breakers

3VA61 3VA62 3VA63 3VA64 3VA65 3VA66 3VA67 3VA68 3VA69


new new new
150 A 250 A 400 A 600 A 800 A 1000 A 1200 A 1600 A 2000 A

– – – – – – – – –

– – – – – – – – –
– – – – – – – – –

■ ■ ■ ■ ■ ■ ■ ■ –
■ ■ ■ ■ ■ ■ ■ ■ –
■ ■ ■ ■ ■ ■ ■ ■ ■

■ ■ ■ ■ ■ – – – –

150 A 250 A 400 A 600 A 800 A 1000 A 1200 A 1600 A 2000 A

■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ – – – – –
■ ■ ■ ■ – – – – –
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ – – – – – – –
■ ■ ■ ■ – – – – –
■ ■ ■ ■ – – – – –
■ ■ – – – – – – –

■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
■ ■ ■ ■ ■ ■ ■ ■ ■
– – – – – – – ● ■
– – – – – – ■ ■ –

Siemens LV 18 · 07/2022 2/7


© Siemens 2022
Molded Case Circuit Breakers | Quick selection guide

3VA5 molded case circuit breakers


up to 2000 A
Technical data

3VA51 3VA51 3VA51 3VA52


Basic data
Number of poles 1-pole 2-pole 3/4-pole 2 in 3-pole, 3/4-pole
Size A 125 125 125 250
Rated current In A 15 … 125 15 … 125 15 … 125 40 … 250
Frequency Hz 0 … 400 0 … 400 0 … 400 0 … 400
Electrical characteristics according to UL 489
Rated operational voltage Ue 50/60 Hz AC V 347 600 Y/347 and 480 600 Y/347 and 480 600
Electrical characteristics according to IEC 60947-2
Rated operational voltage Ue 50/60 Hz AC V 415 415 690 690
Rated insulation voltage Ui V 500 600 800 800
Rated impulse withstand voltage Uimp kV 8 8 8 8
Breaking capacity (line protection) S M H S M H S M H M H C
UL breaker type SEAS MEAS HEAS SEAS MEAS HEAS SEAS MEAS HEAS MFAS HFAS CFAS
Current Limiting according to UL489 – – – – – – – – – – – –
Short-circuit breaking capacity acc. to UL 489
50/60 Hz AC 120 V kA 65 85 100 – – – – – – – – –
240 V kA – – – 65 85 150 65 85 150 85 100 200
277 V kA 25 35 50 – – – – – – – – –
347 V kA 14 18 18 – – – – – – – – –
480 Y / 277 V kA – – – 25 35 65 25 35 65 35 65 100
480 V kA – – – 25 35 65 25 35 65 35 65 100
600 Y / 347 V kA – – – 14 18 25 14 18 25 18 25 35
600 V kA – – – – – – – – – 18 25 35
DC 1) 125 V kA 14 25 30 14 25 30 – – – – – –
250 V kA – – – 50 85 100 50 85 100 50 85 100
500 V kA – – – – – – 50 85 100 50 85 100
600 V kA – – – – – – 50 85 100 50 85 100
750 V kA – – – – – – – – – 50 85 100
1000 V kA – – – – – – – – – 50 85 100
Short-circuit breaking capacity acc. to IEC 60947-2
Rated ultimate short-circuit breaking 240 V kA 25 36 55 55 85 150 55 85 150 85 100 200
capacity ICU 50/60 Hz AC 2) 415 V kA 5 5 5 36 55 70 36 55 70 55 70 110 (3P)
85 (4P)
690 V kA – – – – – – 5 7 10 7 10 10
Rated service short-circuit breaking 240 V kA 25 36 55 55 85 150 55 85 150 85 100 200
capacity ICS 50/60 Hz AC 2) 415 V kA 5 5 5 36 55 70 36 55 70 55 70 110 (3P)
85 (4P)
690 V kA – – – – – – 5 5 5 7 10 10
DC 1) 125 V kA 14 25 30 14 25 30 – – – – – –
250 V kA – – – 50 85 100 50 85 100 50 85 100
500 V kA – – – – – – 50 85 100 50 85 100
600 V kA – – – – – – 50 85 100 50 85 100
750 V kA – – – – – – – – – 50 85 100
1000 V kA – – – – – – – – – 25 36 50
Dimensions
D A mm 25.4 50.8 76.2 105
A C
NSE0_01159

B mm 140 140 140 185


C mm 76.5 76.5 76.5 83
B

D mm 93.4 93.4 93.4 107

■ Available – Not available/not present 1)


For
 detailed data on DC breaking capacity, number of interrupter poles and circuit diagrams,
see FAQ www.siemens.com/lowvoltage/product-support (109775443)

System overview, page 2/20


2/8 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Molded Case Circuit Breakers

3VA53 3VA54 3VA55 3VA57 new 3VA58 new 3VA59 new

2 in 3-pole, 3/4-pole 2 in 3-pole, 3/4-pole 2 in 3-pole, 3/4-pole 2 in 3-pole, 3-pole 3-pole 3-pole
400 600 800 1200 1600 2000
200 … 400 450, 500, 600 600, 700, 800 800, 900, 1000, 1200 1400, 1600 1800, 2000
0 … 400 0 … 400 0 … 400 0 … 400 0 … 400 0 … 400

600 600 600 600 600 600

690 690 690 690 690 –


800 800 800 800 800 –
8 8 8 8 8 –
M H C M H C M H C M H C M H C M H C
MJAS HJAS CJAS MLAS HLAS CLAS MMAS HMAS CMAS MNAS HNAS CNAS MPAS HPAS CPAS MRAS HRAS CRAS
– – – – – – – – – – – ■ – – ■ – – ■

– – – – – – – – – – – – – – – – – –
85 100 200 85 100 200 85 100 200 85 100 200 85 100 200 85 100 200
– – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – –
35 65 100 35 65 100 35 65 100 35 65 100 35 65 100 35 65 100
35 65 100 35 65 100 35 65 100 35 65 100 35 65 100 35 65 100
20 25 35 20 25 35 18 25 50 25 35 65 25 35 65 25 35 65
20 25 35 20 25 35 18 25 50 25 35 65 25 35 65 25 35 65
– – – – – – – – – – – – – – – – – –
50 85 100 50 85 100 50 85 100 22 25 42 22 25 42 22 25 42
50 85 100 50 85 100 50 85 100 50 85 100 35 50 65 35 50 65
50 85 100 50 85 100 50 85 100 50 85 100 50 85 100 50 85 100
50 85 100 50 85 100 50 85 100 50 85 100 50 85 100 50 85 100
6 6 10 6 6 10 18 25 50 – – – – – – – – –

85 100 200 85 100 200 85 100 200 65 110 200 65 100 200 – – –
55 70 110 55 70 110 55 70 110 50 70 110 50 70 110 – – –

7 10 10 7 10 10 25 35 35 20 30 35 20 30 35 – – –
85 100 200 85 100 200 85 100 150 35 55 100 35 55 100 – – –
55 70 110 55 70 110 55 70 85 25 35 55 25 35 55 – – –

5 6 6 6 6 6 19 19 19 15 15 17 15 15 17 – – –
8 16 25 8 16 25 50 85 100 – – – – – – – – –
8 16 25 8 16 25 50 85 100 50 85 100 50 85 100 – – –
8 16 25 8 16 25 50 85 100 50 85 100 50 85 100 – – –
8 16 25 8 16 25 50 85 100 50 85 100 50 85 100 – – –
– – – – – – 50 85 100 50 85 100 50 85 100 – – –
– – – – – – 25 35 50 – – – – – – – – –

138 138 201 229 229 229


210 210 328 406 406 406
110 110 120 157 157 157
137 137 253 208.9 208.9 208.9
2)
I cu = rated ultimate short-circuit breaking capacity, rms value, according to IEC 60947-2.
Ics = rated service short-circuit breaking capacity, rms value, according to IEC 60947-2.

System overview, page 2/20


Siemens LV 18 · 07/2022 2/9
© Siemens 2022
Molded Case Circuit Breakers | Quick selection guide

3VA5 molded case circuit breakers


up to 2000 A
Application

3VA51 3VA51 3VA51 3VA52


Basic data
Number of poles 1-pole 2-pole 3/4-pole 2 in 3-pole, 3/4-pole
Size A 125 125 125 250
Rated current In A 15 … 125 15 … 125 15 … 125 40 … 250
Frequency Hz 0 … 400 0 … 400 0 … 400 0 … 400
3VA5 molded case circuit breakers for line protection
Service life/endurance (operating cycles)
Mechanical (OPEN-CLOSE cycles) 20000 20000 20000 20000
Electrical for Ue 480 V (UL 489)/415 V (IEC 60947) 8000 8000 8000 8000
Trip units
FTFM TM210 ■ ■ ■ ■
FTAM TM230 – – ■ ■
ATAM TM240 – – ■ ■
3VA5 motor circuit protector (protective circuit breaker for motor starter combinations)
Rated current In A – – 15 … 125 150 … 200
Breaking capacity acc. to UL 489 without contactor kA – – 65 65/100
at 480 V 1)
Approval acc. to IEC 60947-2 Annex O ICB – – ■ ■
Integrated, instantaneous short-circuit release for intrinsic device protection
AM TM120M – – ■ ■
3VA5 molded case switch
Electrical characteristics according to UL 489
Rated uninterrupted current In at 40 °C Up to 65 kA A – 100 100 150, 250
ambient temperature for short-circuit at 480 V
current rating (SCCR) 2) Up to 100 kA A – – – 100, 150, 250
at 480 V
Approval acc. to IEC 60947-2 Annex L CBI-X – ■ ■ ■
Integrated, instantaneous short-circuit release for intrinsic device protection
FM MCS110 – ■ ■ ■
Standards and specifications
Standards and specifications UL489/cULus, UL489/cULus, UL489/cULus, UL489/cULus,
IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2
Direction of power flow and infeed Top and bottom Top and bottom Top and bottom Top and bottom
Standard connection technology Without connection Without connection Without connection Without connection
technology technology technology technology

■ Available – Not available/not present


1)
Breaking capacity in combinations with contactor (SCCR rating) may differ
2)
The breaking capacity (SCCR rating) is the maximum short-circuit current permissible at the location where the MCS is installed in conjunction with a suitable overload protection device

System overview, page 2/20


2/10 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Molded Case Circuit Breakers

3VA53 3VA54 3VA55 3VA57 new 3VA58 new 3VA59 new

2 in 3-pole, 3/4-pole 2 in 3-pole, 3/4-pole 2 in 3-pole, 3/4-pole 2 in 3-pole, 3-pole 3-pole 3-pole
400 600 800 1200 1600 2000
200 … 400 450, 500, 600 600, 700, 800 800, 900, 1000, 1200 1400, 1600 1800, 2000
0 … 400 0 … 400 0 … 400 0 … 400 0 … 400 0 … 400

20000 20000 10000 3000 3000 3000


6000 3000 4800 1500 1500 500

– – – – – –
■ ■ ■ ■ ■ ■
■ ■ – – – –

250 400, 500, 600 600, 800 – – –


65/100 65/100 65/100 – – –

■ ■ ■ – – –

■ ■ ■ – – –

400 600 800 1000, 1200 1600 2000

400 600 800 1000, 1200 1600 2000

■ ■ ■ ■ ■ –

■ ■ ■ ■ ■ ■

UL489/cULus, UL489/cULus, UL489/cULus, UL489/cULus, UL489/cULus, UL 489/cULus


IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2
Top and bottom Top and bottom Top and bottom Top and bottom Top and bottom Top and bottom
Without connection Without connection Nut keeper kit Without connection Without connection Without connection
technology technology technology technology technology

System overview, page 2/20


Siemens LV 18 · 07/2022 2/11
© Siemens 2022
Molded Case Circuit Breakers | Quick selection guide

3VA6 molded case circuit breakers


up to 2000 A
Technical data

3VA61 3VA62

Basic data
Number of poles 3/4-pole 3/4-pole
Size A 150 250
Rated current In A 40 … 150 100, 250
Frequency Hz 50 … 60 50 … 60
Electrical characteristics according to UL 489
Rated operational voltage Ue 50/60 Hz AC V 600 600
Electrical characteristics according to IEC 60947-2
Rated operational voltage Ue 50/60 Hz AC V 690 690
Rated insulation voltage Ui V 800 800
Rated impulse withstand voltage Uimp kV 8 8
Breaking capacity (line protection) M H C L E M H C L E
UL breaker type MDAE HDAE CDAE LDAE EDAE MFAE HFAE CFAE LFAE EFAE

Current limiting according to UL 489 – – – – ■ – – – – ■


Short-circuit breaking capacity acc. to UL 489
50/60 Hz AC 120 V kA – – – – – – – – – –
240 V kA 100 100 200 200 – 100 100 200 200 –
277 V kA – – – – – – – – – –
347 V kA – – – – – – – – – –
480 Y / 277 V kA 35 65 100 150 200 35 65 100 150 200
480 V kA 35 65 100 150 200 35 65 100 150 200
600 Y / 347 V kA 18 22 35 50 100 18 22 35 50 100
600 V kA 18 22 35 50 100 18 22 35 50 100
Short-circuit breaking capacity acc. to IEC 60947-2
Rated ultimate short-circuit breaking 240 V kA 85 110 150 200 – 85 110 150 200 –
capacity ICU 415 V kA 55 85 110 150 150 55 85 110 150 150
50/60 Hz AC 1)
690 V kA 2.5 2.5 2.5 2.5 3 3 3 3 3 3
Rated service short-circuit breaking capacity 240 V kA 85 110 150 200 – 85 110 150 200 –
ICS 415 V kA 55 85 110 150 150 55 85 110 150 150
50/60 Hz AC 1)
690 V kA 2.5 2.5 2.5 2.5 3 3 3 3 3 3
Dimensions
D A mm 105 (3P) | 140 (4P) 105 (3P) | 140 (4P)
A C
NSE0_01159

B mm 198 198
C mm 86 86
B

D mm 107 107
■ Available – Not available/not present
1)
Icu = rated ultimate short-circuit breaking capacity, rms value, according to IEC 60947-2.
Ics = rated service short-circuit breaking capacity, rms value, according to IEC 60947-2.

System overview, page 2/20


2/12 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Molded Case Circuit Breakers

3VA63 3VA64 3VA65 3VA66 3VA67 3VA68 3VA69


new new new

3/4-pole 3/4-pole 3/4-pole 3/4-pole 3-pole 3-pole 3-pole


400 600 800 1000 1200 1600 2000
250, 400 400, 600 600, 800 1000 800, 1000, 1200 1600 2000
50 … 60 50 … 60 50 … 60 50 … 60 50 … 60 50 … 60 50 … 60

600 600 600 600 600 600 600

690 690 690 690 690 690 –


800 800 800 800 800 800 –
8 8 8 8 8 8 –
M H C L E M H C L E M H C M H C M H C M H C M H C
MJAE HJAE CJAE LJAE EJAE MLAE HLAE CLAE LLAE ELAE MMAE HMAE CMAE MM- HM- CM- MNAE HNAE CNAE MPAE HPAE CPAE MRAE HRAE CRAE
NAE NAE NAE
– – – – ■ – – – – ■ – – – – – – – – ■ – – ■ – – ■

– – – – – – – – – – – – – – – – – – – – – – – – –
100 100 200 200 – 100 100 200 200 – 100 150 200 100 150 200 85 100 200 85 100 200 85 100 200
– – – – – – – – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – – – – – – – –
35 65 100 150 200 35 65 100 150 200 35 65 100 35 65 100 35 65 100 35 65 100 35 65 100
35 65 100 150 200 35 65 100 150 200 35 65 100 35 65 100 35 65 100 35 65 100 35 65 100
18 22 35 50 100 18 22 35 50 100 25 35 50 25 35 50 25 35 65 25 35 65 25 35 65
18 22 35 50 100 18 22 35 50 100 25 35 50 25 35 50 25 35 65 25 35 65 25 35 65

85 110 150 200 – 85 110 150 200 – 85 110 200 85 110 200 65 110 200 65 110 200 – – –
55 85 110 150 150 55 85 110 150 150 55 85 110 55 85 110 50 70 110 50 70 110 – – –
5 5 5 5 6 6 6 6 6 6 25 35 35 25 35 35 20 30 35 20 30 35 – – –
85 110 150 200 – 85 110 150 200 – 85 110 150 85 110 150 35 55 100 35 55 100 – – –
55 85 110 150 150 55 85 110 150 150 55 85 85 55 85 85 25 35 50 25 35 50 – – –
5 5 5 5 6 6 6 6 6 6 19 19 19 19 19 19 15 15 17 15 15 17 – – –

138 (3P) | 184 (4P) 138 (3P) | 184 (4P) 210 210 229 229 229
248 248 328 328 406 406 406
110 110 120 120 157 157 157
137 137 253 253 208.9 208.9 208.9

System overview, page 2/20


Siemens LV 18 · 07/2022 2/13
© Siemens 2022
Molded Case Circuit Breakers | Quick selection guide

3VA6 molded case circuit breakers


up to 2000 A
Application

3VA61 3VA62
Basic data
Number of poles 3/4-pole 3/4-pole
Size A 150 250
Rated current In A 40 … 150 100, 250
Frequency Hz 50 … 60 50 … 60
3VA6 molded case circuit breakers for line protection
Service life/endurance (operating cycles)
Mechanical (CLOSE-OPEN cycles) 25000 25000
Electrical for Ue 480 V (UL 489)/415 V (IEC 60947) 14000 12000
Trip units
LI ETU320 ■ ■
ETU820 ■ ■
LIG ETU330 ■ ■
ETU830 ■ ■
LSI ETU350 ■ ■
ETU550 ■ ■
ETU850 ■ ■
LSI ETU556 ■ ■
(G alarm, no integrated G protection) ETU856 ■ ■
LSIG ETU360 – –
ETU560 ■ ■
ETU860 ■ ■
Motor circuit protector (protective circuit breaker for motor starter combinations) 3VA6
Rated current In A 25 … 100 110 … 200
Breaking capacity acc. to UL 489 without contactor at 480 V 1) kA 100 100
Approval acc. to IEC 60947-2 Annex O ICB ■ ■
Integrated, instantaneous short-circuit release for intrinsic device protection
I ETU310M ■ ■
Standards and specifications
Standards and specifications UL489/cULus, UL489/cULus,
IEC 60947-2 IEC 60947-2
Direction of power flow and infeed Top and bottom Top and bottom
Standard connection technology Without connection technology Without connection technology

■ Available – Not available/not present


1)
Breaking capacity in combinations with contactor (SCCR rating) may differ

System overview, page 2/20


2/14 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Molded Case Circuit Breakers

3VA63 3VA64 3VA65 3VA66 3VA67 new 3VA68 new 3VA69 new

3/4-pole 3/4-pole 3/4-pole 3/4-pole 3-pole 3-pole 3-pole


400 600 800 1000 1200 1600 2000
250, 400 400, 600 600, 800 1000 800, 1000, 1200 1600 2000
50 … 60 50 … 60 50 … 60 50 … 60 50 … 60 50 … 60 50 … 60

20000 20000 10000 10000 3000 3000 3000


6000 4000 5100 4900 1500 1500 500

■ ■ ■ ■ ■ ■ –
■ ■ ■ ■ ■ ■ –
■ ■ ■ ■ ■ ■ –
■ ■ ■ ■ ■ ■ –
■ ■ ■ ■ ■ ■ –
■ ■ ■ ■ – – –
■ ■ – – ■ ■ ■
■ ■ ■ ■ – – –
■ ■ ■ ■ ■ ■ ■
■ ■ –
■ ■ ■ ■ – – –
■ ■ ■ ■ ■ ■ ■

200, 250 400, 500 800 – – – –


100 100 100 – – – –
■ ■ ■ – – – –

■ ■ ■ – – – –

UL489/cULus, UL489/cULus, UL489/cULus, UL489/cULus, UL 489/cULus, UL 489/cULus, UL 489/cULus


IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2 IEC 60947-2
Top and bottom Top and bottom Top and bottom Top and bottom Top and bottom Top and bottom Top and bottom
Without connection Without connection Nut keeper kit Nut keeper kit Without connection Without connection Without connection
technology technology technology technology technology

System overview, page 2/20


Siemens LV 18 · 07/2022 2/15
© Siemens 2022
Molded Case Circuit Breakers | Quick selection guide

Trip units
Protection system for 3VA molded case circuit breakers up to 2000 A
Trip units Thermal-magnetic Electronic Electronic with display Electronic with display and
measurement function

TM240 ETU350 LSI ETU550M LSI ETU860M LSIG

I201_18484
I201_18828
I201_19035

I201_19701
I r /A Ii /A /A /s /s N=X r
OFF

2 TM 2-series ETU 3-series ETU 5-series ETU 8-series


Protective function
Line protection TM210, TM230, TM240 ETU320, ETU330, ETU350, ETU550, ETU556, ETU560 ETU820, ETU830, ETU850, ETU856,
ETU360 ETU860
Starter protection TM120M ETU310M – –
Integrated functions
Parameterizing Setting and reading the Setting and reading the Setting and reading the Setting and reading the parameters
parameters parameters parameters • Via display and communication
• In A • In A and s • Via display and communi­ • Fine setting of the parameters
cation • Reading the measured values
• Fine setting of the parameters
• Reading the measured values
Status display – Indicating the ETU status via Indicating the ETU status via Indicating the ETU status via LEDs
LEDs LEDs
Interface – Interface for test devices Interface for test devices Interface for test devices
Measurement function – – – Measurement function integrated
Optional expansions
24 V module

– – 24 V module for continuous 24 V module for continuous power


power supply (also without supply (also without primary
primary current through the current through the molded case
molded case circuit breaker) circuit breaker)
External function box

– EFB300 external function box EFB300 external function box for EFB300 external function box for
for connection to the ETU connection to the ETU connection to the ETU
Maintenance mode –
box

MMB300 maintenance mode MMB300 maintenance mode box MMB300 maintenance mode box
box for connection to the ETU 1) for connection to the ETU for connection to the ETU 1)
Communication
module

– – COM060 communication module COM060 communication module 1)


Data concentrator

– – COM800/COM100 breaker data COM800/COM100 breaker data


server with interface to server with interface to
• PROFIBUS • PROFIBUS
• PROFINET • PROFINET
• Modbus RTU • Modbus RTU
• Ethernet (Modbus TCP) • Ethernet (Modbus TCP)
External display

– – DSP800 external display for DSP800 external display for


installing in the cubicle door installing in the cubicle door
Test device

– TD300/TD400/TD500 test TD300/TD400/TD500 test device TD300/TD400/TD500 test device


device
1)
For 3VA67, 3VA68 and 3VA69 (3VA UL Large Frame), this function is already integrated in the ETU

System overview, page 2/20


2/16 Siemens LV 18 · 07/2022
© Siemens 2022
Quick selection guide | Molded Case Circuit Breakers

Protective functions of the 3VA5 with thermal-magnetic trip unit


TM120M TM210 TM230 TM240
AM FTFM FTAM ATAM
Protection
Motor circuit protector ■ – – –
Line protection – ■ ■ ■
Version available with
1-pole breaker – ■ – – 2
2-pole breaker in 3-pole enclosure – ■ ■ –
3-pole breaker ■ ■ ■ ■
4-pole breaker – ■ ■ ■
Available protection parameters
Ir adjustable – – – ■
Ii adjustable ■ – ■ ■
Ir fixed – ■ ■ –
Ii fixed – ■ – –

Protective functions of the 3VA6 with electronic trip unit


ETU310M ETU320 ETU330 ETU350 ETU360 ETU550 ETU556 ETU560 ETU820 ETU830 ETU850 ETU856 ETU860
I LI LIG LSI LSIG LSI LSI LSIG LI LIG LSI LSI LSIG
(G alarm) (G alarm)
Protection
Motor circuit protector ■ – – – – – – – – – – –
Line protection – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Version available with
3-pole without external ■ ■ ■ ■ – – – – – – – – –
neutral conductor transformer
3-pole with external – – – – ■ ■ ■ ■ – – ■ ■ ■
neutral conductor transformer
4-pole with protected – ■ ■ ■ – ■ ■ ■ ■ ■ ■ ■ ■
neutral conductor transformer
Available protection parameters
Characteristic in L range I2t I2t I2 t I2 t I2 t I2 t I2t I2t I2 t I2 t I2 t I2t I2t
Ir – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
tld at 6 × Ir – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Thermal image ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Thermal image can be switched – – – – – ■ ■ ■ – – ■ ■ ■
on/off
Isd – – – ■ ■ ■ ■ ■ – – ■ ■ ■
tsd at 8 × Ir – – – ■ ■ ■ ■ ■ – – ■ ■ ■
Characteristic in S range: I2tsd – – – ■ ■ ■ ■ ■ – – ■ ■ ■
Characteristic in S range: – – – – – ■ ■ ■ – – ■ ■ ■
selectable I2tsd/tsd
Ii ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
IN 1) – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Ig – – ■ – ■ – – ■ – ■ – – ■
tg at 2 × Ig – – ■ – ■ – – ■ – ■ – – ■
Characteristic in G range: I2tg – – – – – – – ■ – ■ – – ■
Characteristic in G range: – – – – – – – ■ – ■ – – ■
selectable I2tg/tg
Ground-fault alarm function – – – – – – ■ ■ – – – ■ ■
ZSI – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Arc fault mitigation mode – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■ Available – Not available/not present
1)
Available for circuit breakers with an external current transformer for the neutral conductor and for 4-pole circuit breakers

System overview, page 2/20


Siemens LV 18 · 07/2022 2/17
© Siemens 2022
Molded Case Circuit Breakers | Quick selection guide

Online configurator highlights


www.siemens.com/lowvoltage/configurators

Search function with global direct input


Searches for specific terms and jumps to article number based on input to the correct configurator

Product list stores multiple configurations and can transfer them collectively to the shopping cart

Recall of completed configurations for modification or additional configuration

Responsive Design

2/18 Siemens LV 18 · 07/2022


© Siemens 2022
Quick selection guide | Molded Case Circuit Breakers

www.siemens.com/lowvoltage/3va-ul-configurator

Visualization of the internally mountable accessories (slot assignment)

Download of the individual edz files for 3VA

Automatic generation of the 3D model, the 2D dimension drawing and the internal circuit
diagram according to IEC

Siemens LV 18 · 07/2022 2/19


© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

System overview

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

Molded case circuit breakers


2

3VA5 for standard applications 3VA6 for applications with more stringent requirements

Trip unit Trip unit accessories

TM240 ETU350 LSI ETU860M LSIG


I201_19035

I201_18484
I201_18828

I r /A Ii /A /A /s /s N=X r
OFF

Thermal-magnetic trip Electronic trip unit Electronic trip unit (ETU) 24 V module Communica- Breaker data External Test device
unit (TMTU) (ETU) with display, and tion module server display
optionally with measure-
ment function

Type of mounting Supplementary accessories

Fixed-mounted Withdrawable unit, Plug-in unit, Auxiliary Door Position Cylinder lock Crank
complete kit complete kit circuit feedthrough signaling adapter
connector switch

Main conductor connections Connection accessories

Bus Bus connectors Circular conductor Box terminal Insulation accessories


connectors broadened terminal

Note:
You will find a detailed range of accessories in the Accessories section.

2/20 Siemens LV 18 · 07/2022


© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

Auxiliary releases/
auxiliary switches 2

Shunt trip STF/STL Universal release Undervoltage Auxiliary switch Trip alarm switch Leading changeover Electrical alarm switch
UNI release UVR AUX TAS switch LCS EAS

Mountable accessories

Manual operator Motor operator Operating unit with Bowden cable Operating unit with linkage

Additional circuit breaker


accessories

Cover frame Locking provision Cylinder lock

Mechanical interlocking
mechanisms

Sliding bar interlock Interlocking with rod Handle interlocking module with bowden cable

Note:
You will find a detailed range of accessories in the Accessories section.

Siemens LV 18 · 07/2022 2/21


© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Structure of the article numbers


Basic configuration for line protection

The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator
4 5 6 7 8 9 10 11 12 13
3VA – – AA0
2 Trip units Thermal-magnetic 5
Electronic 6
3VA51
3VA52
3VA53
3VA54
3VA55
3VA57
3VA58
3VA59
3VA61
3VA62
3VA63
3VA64
3VA65
3VA66
3VA67
3VA68
3VA69
Size 125 A ■ – – – – – – – – – – – – – – – – 1
150 A – – – – – – – – ■ – – – – – – – – 1
250 A – ■ – – – – – – – ■ – – – – – – – 2
400 A – – ■ – – – – – – – ■ – – – – – – 3
600 A – – – ■ – – – – – – – ■ – – – – – 4
800 A – – – – ■ – – – – – – – ■ – – – – 5
1000 A – – – – – – – – – – – – – ■ – – – 6
1200 A – – – – – ■ – – – – – – – – ■ – – 7
1600 A – – – – – – ■ – – – – – – – – ■ – 8
2000 A – – – – – – – ■ – – – – – – – – ■ 9

Max. rated current Line 15 A ■ – – – – – – – – – – – – – – – – 9 5


In protec- 20 A ■ – – – – – – – – – – – – – – – – 2 0
tion 25 A ■ – – – – – – – – – – – – – – – – 2 5
30 A ■ – – – – – – – – – – – – – – – – 3 0
35 A ■ – – – – – – – – – – – – – – – – 3 5
40 A ■ ■ – – – – – – ■1) – – – – – – – – 4 0
45 A ■ ■ – – – – – – – – – – – – – – – 4 5
50 A ■ ■ – – – – – – – – – – – – – – – 5 0
60 A ■ ■ – – – – – – ■2) – – – – – – – – 6 0
70 A ■ ■ – – – – – – – – – – – – – – – 7 0
80 A ■ ■ – – – – – – – – – – – – – – – 8 0
90 A ■ ■ – – – – – – – – – – – – – – – 9 0
100 A ■ ■ – – – – – – ■ ■ – – – – – – – 1 0
110 A ■ ■ – – – – – – – – – – – – – – – 1 1
125 A ■ ■ – – – – – – – – – – – – – – – 1 2
150 A – ■ – – – – – – ■ – – – – – – – – 1 5
175 A – ■ – – – – – – – – – – – – – – – 1 7
200 A – ■ ■ – – – – – – – – – – – – – – 2 0
225 A – ■ ■ – – – – – – – – – – – – – – 2 2
250 A – ■ ■ – – – – – – ■ ■ – – – – – – 2 5
300 A – – ■ – – – – – – – – – – – – – – 3 0
350 A – – ■ – – – – – – – – – – – – – – 3 5
400 A – – ■ – – – – – – – ■ ■ – – – – – 4 0
450 A – – – ■ – – – – – – – – – – – – – 4 5
500 A – – – ■ – – – – – – – – – – – – – 5 0
600 A – – – ■ ■ – – – – – – ■ ■ – – – – 6 0
700 A – – – – ■ – – – – – – – – – – – – 7 0
800 A – – – – ■ ■ – – – – – – ■ – ■ – – 8 0
900 A – – – – – ■ – – – – – – – – – – – 9 0
1000 A – – – – – ■ – – – – – – – ■ ■ – – 1 0
1200 A – – – – – ■ – – – – – – – – ■ – – 1 2
1400 A – – – – – – ■ – – – – – – – – – – 1 4
1600 A – – – – – – ■ – – – – – – – – ■ – 1 6
1800 A – – – – – – – ■ – – – – – – – – – 1 8
2000 A – – – – – – – ■ – – – – – – – – ■ 2 0

Short-circuit 25 kA ■ – – – – – – – – – – – – – – – – 4
breaking capacity 35 kA ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 5
at 480 V 65 kA ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 6
50/60 Hz 100 kA – ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ 7
150 kA – – – – – – – – ■ ■ ■ ■ – – – – – 8
200 kA – – – – – – – – ■ ■ ■ ■ – – – – – 0
1)
Available for breaking capacity classes M (35 kA), H (65 kA), C (100 kA) and L (150 kA) at 480 V ◾ Available – Not available/not present
2)
Available for breaking capacity class E (200 kA) at 480 V

System overview, pages 2/8 and 2/12


2/22 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

4 5 6 7 8 9 10 11 12 13
3VA – – AA0
2
3VA51
3VA52
3VA53
3VA54
3VA55
3VA57
3VA58
3VA59
3VA61
3VA62
3VA63
3VA64
3VA65
3VA66
3VA67
3VA68
3VA69
Protective function Line protection ■■ – – – – – – – – – – – – – – – TM210 FTFM D
thermal-­magnetic ■■■■■■■■ – – – – – – – – – TM230 FTAM C
■■■■ – – – – – – – – – – – – – TM240 ATAM F

Protective function Line protection Without neutral conductor protection E


thermal-­magnetic, 100% neutral conductor protection G
neutral conductor
protection

Protective function Line protection – – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ – ETU320 LI (N) 1) H L


electronic – – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ – ETU330 LIG (N) 1) H M
– – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ – ETU350 LSI (N) 1) H N
– – – – – – – – – – – – – – ■ ■ – ETU360 LSIG (N) 1) H Q
Line protection, – – – – – – – – ■ ■ ■ ■ ■ ■ – – – ETU550 LSI (N) 2) J P
with display – – – – – – – – ■ ■ ■ ■ ■ ■ – – – ETU556 LSI(G) (N) 2) J T
– – – – – – – – ■ ■ ■ ■ ■ ■ – – – ETU560 LSIG (N) 2) J Q
Line protection, – – – – – – – – ■ ■ ■ ■ ■ ■ – – – ETU820 LI (N) 2) K L
with display, – – – – – – – – ■ ■ ■ ■ – – – – – ETU830 LIG (N) 2) K M
with measurement
function – – – – – – – – ■ ■ ■ ■ – – ■ ■ ■ ETU850 LSI (N) 2) K P
– – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ ■ ETU856 LSI(G) (N) 2) K T
– – – – – – – – ■ ■ ■ ■ ■ ■ ■ ■ ■ ETU860 LSIG (N) 2) K Q
1)
Neutral conductor protection for 4-pole breakers
2)
Neutral conductor protection for 3-pole breakers with an external neutral conductor transformer or for 4-pole breakers

Number of poles 1-pole ■ – – – – – – – – – – – – – – – – 1


2-pole ■ – – – – – – – – – – – – – – – – 2
2-pole in 3-pole – ■■■■■ – – – – – – – – – – – 6
enclosure
3-pole ■■■■■■■■■■ ■ ■ ■■■■■ 3
4-pole ■■■■■ – – – ■■ ■ ■ ■■ – – – 4

Connection Without ■■■■ – ■■■■■ ■ ■ – – ■■■ 1


technology Nut keeper kit – – – – ■ – – – – – – – ■■ – – – 2

Special Standard ■■■■■■■■■■ ■ ■ ■■■■■ 0


applications 100% rated – – – – – ■ ■ – ■ ■ ■1) ■2) ■ – ■ ■ – 2
breaker
1)
Only possible for 250 A
2)
Only possible for 400 A

System overview, pages 2/8 and 2/12


Siemens LV 18 · 07/2022 2/23
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Structure of the article numbers


Basic configuration for motor circuit protectors and molded case switches

The structure shown below is intended as an overview of each position and its meaning.
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator
4 5 6 7 8 9 10 11 12
3VA – – 0AA0
2 Trip units Thermal-magnetic 5
Electronic 6

3VA51
3VA52
3VA53
3VA54
3VA55
3VA57
3VA58
3VA59
3VA61
3VA62
3VA63
3VA64
3VA65
Size 125 A ■ – – – – – – – – – – – – 1
150 A – – – – – – – – ■ – – – 1
250 A – ■ – – – – – – – ■ – – – 2
400 A – – ■ – – – – – – – ■ – – 3
600 A – – – ■ – – – – – – – ■ – 4
800 A – – – – ■ – – – – – – – ■ 5
1200 A – – – – – ■ – – – – – – – 7
1600 A – – – – – – ■ – – – – – – 8
2000 A – – – – – – – ■ – – – – – 9

Max. rated current Motor circuit 1A ■ – – – – – – – – – – – – 8 1


In protector 2A ■ – – – – – – – – – – – – 0 2
3A ■ – – – – – – – – – – – – 0 3
5A ■ – – – – – – – – – – – – 0 5
7A ■ – – – – – – – – – – – – 0 7
10 A ■ – – – – – – – – – – – – 9 1
15 A ■ – – – – – – – – – – – – 9 5
25 A ■ – – – – – – – ■ – – – – 2 5
30 A ■ – – – – – – – ■ – – – – 3 0
40 A ■ – – – – – – – ■ – – – – 4 0
50 A ■ – – – – – – – ■ – – – – 5 0
70 A ■ – – – – – – – ■ – – – – 7 0
80 A ■ – – – – – – – ■ – – – – 8 0
90 A ■ – – – – – – – ■ – – – – 9 0
100 A ■ – – – – – – – ■ – – – – 1 0
110 A ■ – – – – – – – – ■ – – – 1 1
125 A ■ – – – – – – – – ■ – – – 1 2
150 A – ■ – – – – – – – ■ – – – 1 5
200 A – ■ – – – – – – – ■ – – – 2 0
250 A – ■ ■ – – – – – – – ■ – – 2 5
400 A – – – ■ – – – – – – ■ ■ – 4 0
500 A – – – ■ – – – – – – – ■ – 5 0
600 A – – – ■ ■ – – – – – – – – 6 0
800 A – – – – ■ – – – – – – – ■ 8 0
Molded case 100 A ■ ■ – – – – – – – – – – – 1 0
switch 150 A – ■ – – – – – – – – – – – 1 5
250 A – ■ – – – – – – – – – – – 2 5
400 A – – ■ – – – – – – – – – – 4 0
600 A – – – ■ – – – – – – – – – 6 0
800 A – – – – ■ – – – – – – – – 8 0
1000 A – – – – – ■ – – – – – – – 1 0
1200 A – – – – – ■ – – – – – – – 1 2
1600 A – – – – – – ■ – – – – – – 1 6
2000 A – – – – – – – ■ – – – – – 2 0

Short-circuit Without, with 65 kA – ■ ■ ■ ■ – – – – – – – – 0


breaking capacity SCCR rating as a ■ – – – – – – – – – – – – 1
at 480 V combined device – – – – – ■ ■ ■ – – – – – 6
50/60 Hz
100 kA – ■ ■ ■ ■ – – – ■ ■ ■ ■ ■ 1
– – – – – ■ ■ ■ – – – – – 7
◾ Available – Not available/not present

System overview, pages 2/8 and 2/12


2/24 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

4 5 6 7 8 9 10 11 12
3VA – – 0AA0
2

3VA51
3VA52
3VA53
3VA54
3VA55
3VA57
3VA58
3VA59
3VA61
3VA62
3VA63
3VA64
3VA65
Protective Motor circuit Setting range ■ ■ ■ ■ ■ – – – – – – – – TM120M AM M H
function protector Ii high
thermal- Setting range ■ ■ ■ ■ – – – – – – – – – TM120M AM M U
magnetic Ii low

Protective Molded case switch ■■■■■■■■ – – – – – B B


function only
MCS110 –
intrinsic device
protection

Protective Motor circuit protector – – – – – – – – ■■■■■ ETU310M I M S


function
electronic

Number of Motor circuit protector ■■■■■ – – – ■■■■■ 3-pole 3


poles Molded case switch ■ – – – – – – – – – – – – 2-pole 2
– ■■■■■ – – – – – – – 2-pole in 3-pole enclosure 6
■■■■■■■■ – – – – – 3-pole 3
– ■ – – – – – – – – – – – 4-pole 4

Connection Without ■■■■ – ■■■■■■■ – 1


technology Nut keeper kit – – – – ■ – – – – – – – ■ 2

System overview, pages 2/8 and 2/12


Siemens LV 18 · 07/2022 2/25
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Internal accessories
Auxiliary and alarm switches (changeover contacts)

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

3VA61
3VA51 3VA62

2 3VA52 3VA63
3VA53 3VA64 3VA57 3VA67
3VA54 3VA65 3VA58 3VA68
3VA55 3VA66 3VA59 3VA69
Auxiliary switches AUX
• Used to signal the position of the main contacts of the molded case circuit breaker
• The contacts of the auxiliary switch and the molded case circuit breaker close in
unison
Type Width Ie Ue AC/DC Version
HQ 7 mm (1 slot) 6A 240 V/250 V Standard 3VA9978-0AA12
0.3 A 24 V/24 V Electronic-compatible 3VA9978-0AA13
HP 14 mm (2 slots) 10 A 600 V/250 V Standard 3VA9978-0AA11

Leading changeover switches LCS


• Used for load shedding, for example
• Signal the opening of the main contacts with a lead time of 20 ms in advance
of circuit breaker trips
Type Width Ie Ue AC/DC Version
HQ 7 mm (1 slot) 6A 240 V/250 V Standard 3VA9978-0AA22 –
0.3 A 24 V/24 V Electronic-compatible 3VA9978-0AA23 –
HP 14 mm (2 slots) 10 A 600 V/250 V Standard 3VA9978-0AA21 –

Trip alarm switches TAS


• Signal every circuit breaker tripping operation
• Are actuated whenever the molded case circuit breaker switches to the TRIP
position
Type Width Ie Ue AC/DC Version
HQ 7 mm (1 slot) 6A 240 V/250 V Standard 3VA9978-0AB12
0.3 A 24 V/24 V Electronic-compatible 3VA9978-0AB13
HP 14 mm (2 slots) 10 A 600 V/250 V Standard 3VA9978-0AB11

Electrical alarm switches EAS


• Are actuated as soon as the main contacts of the molded case circuit breaker
open in the event that the breaker is tripped by the ETU
Type Width Ie Ue AC/DC Version
HQ 7 mm (1 slot) 6A 240 V/250 V Standard – 3VA9978-0AB22 – Already
integrated
0.3 A 24 V/24 V Electronic-compatible – 3VA9978-0AB23 – Already
integrated

System overview, page 2/20


2/26 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

Auxiliary releases

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

3VA57
3VA58
3VA59 2
3VA51 3VA65
3VA52 3VA61 3VA66
3VA53 3VA62 3VA67
3VA54 3VA63 3VA68
3VA55 3VA64 3VA69
Shunt trips left STL
• Used for remote-controlled tripping of the molded case circuit breaker
• Have particularly low power consumption
Version Ue 50/60 Hz AC Ue DC
Standard – 12 V 3VA9978-0BL10
24 V 24 … 30 V 3VA9978-0BL30
48 … 60 V 48 … 60 V 3VA9978-0BL31
110 … 127 V 110 … 127 V 3VA9978-0BL32
208 … 277 V 220 … 250 V 3VA9978-0BL33
380 … 600 V – 3VA9978-0BL20
Shunt trips flexible STF
• Used for remote-controlled tripping of the molded case circuit breaker
• Can be flexibly installed in left-hand and right-hand accessories compartment of
molded case circuit breaker
Version Ue 50/60 Hz AC Ue DC
24 V – – 3VA9978-0BA20 –
48 … 60 V – – 3VA9978-0BA21 –
110 … 127 V – – 3VA9978-0BA22 –
208 … 277 V – – 3VA9978-0BA23 –
380 … 500 V – – 3VA9978-0BA24 –
600 V – – 3VA9978-0BA25 –
Universal releases UNI
• Combination of shunt trip and undervoltage release
Version Ue 50/60 Hz AC Ue DC
– 12 V 3VA9978-0BD11
– 24 V 3VA9978-0BD12
– 48 V 3VA9978-0BD13

Undervoltage releases UVR


• Trip the molded case circuit breaker in the event that the rated
operational voltage of a monitored circuit drops below a minimum
permissible limit or fails altogether
Version Ue 50/60 Hz AC Ue DC
– 12 V 3VA9978-0BB10
– 24 V 3VA9978-0BB11
24 V – 3VA9978-0BB20
– 48 V 3VA9978-0BB12
120 … 127 V – 3VA9978-0BB24
– 125 … 127 V 3VA9978-0BB14
208 … 230 V – 3VA9978-0BB25
– 250 V 3VA9978-0BB16
440 … 480 V – 3VA9978-0BB27
Time-delay devices for undervoltage releases
Version Ue 50/60 Hz AC Ue DC
230 V 230 V 3VA9978-0BF22
– 24 V 3VA9978-0BF23

System overview, page 2/20


Siemens LV 18 · 07/2022 2/27
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Manual operators

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2 3VA53
3VA52 3VA54
3VA61 3VA63
3VA51 3VA62 3VA64
Front mounted rotary operators
• Handle
• Degree of protection IP30
• For 3-pole and 4-pole breakers
Version Door open Illumina­tion kit Door
function interlock
Standard (gray) Without Without Without 3VA9137-0EK11 3VA9277-0EK11 3VA9447-0EK11

With 3VA9137-0EK21 3VA9277-0EK21 3VA9447-0EK21

With Without 3VA9137-0EK13 3VA9277-0EK13 3VA9447-0EK13

With 3VA9137-0EK23 3VA9277-0EK23 3VA9447-0EK23

With Without With 3VA9137-0EK31 3VA9277-0EK31 3VA9447-0EK31

With With 3VA9137-0EK33 3VA9277-0EK33 3VA9447-0EK33

EMERGENCY-OFF Without Without Without 3VA9137-0EK15 3VA9277-0EK15 3VA9447-0EK15


(red/yellow)
With 3VA9137-0EK25 3VA9277-0EK25 3VA9447-0EK25

With Without 3VA9137-0EK17 3VA9277-0EK17 3VA9447-0EK17

With 3VA9137-0EK27 3VA9277-0EK27 3VA9447-0EK27

With Without With 3VA9137-0EK35 3VA9277-0EK35 3VA9447-0EK35

With With 3VA9137-0EK37 3VA9277-0EK37 3VA9447-0EK37

Door mounted rotary operator


• Shaft 300 mm (325 mm for 1000 A)
• With mounting tolerance compensation
• Handle with masking plate 75 × 75 mm
• Degree of protection IP65
• For 3-pole and 4-pole breakers
• Enclosure types 1, 3R, 12, 4/4X
Version Door open Illumina­tion kit Door
function interlock
Standard (gray) Without Without With 3VA9137-0FK21 3VA9277-0FK21 3VA9447-0FK21

With With 3VA9137-0FK23 3VA9277-0FK23 3VA9447-0FK23

With Without With 3VA9137-0FK31 3VA9277-0FK31 3VA9447-0FK31

With With 3VA9137-0FK33 3VA9277-0FK33 3VA9447-0FK33

EMERGENCY-OFF Without Without With 3VA9137-0FK25 3VA9277-0FK25 3VA9447-0FK25


(red/yellow)
With With 3VA9137-0FK27 3VA9277-0FK27 3VA9447-0FK27

With Without With 3VA9137-0FK35 3VA9277-0FK35 3VA9447-0FK35

With With 3VA9137-0FK37 3VA9277-0FK37 3VA9447-0FK37

System overview, page 2/20


2/28 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA57
3VA58
3VA59 2
3VA55 3VA67
3VA65 3VA68
3VA66 3VA69

3VA9677-0EK11 3VA9877-0EK11 new

3VA9677-0EK21 –

– –

– –

3VA9677-0EK31 –

– –

3VA9677-0EK15 3VA9877-0EK15 new

3VA9677-0EK25 –

– –

– –

3VA9677-0EK35 –

– –

3VA9677-0FK21 3VA9877-0FK21 new

3VA9677-0FK23 –

3VA9677-0FK31 –

3VA9677-0FK33 –

3VA9677-0FK25 3VA9877-0FK25 new

3VA9677-0FK27 –

3VA9677-0FK35 –

3VA9677-0FK37 –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/29
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Manual operators

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2 3VA53
3VA52 3VA54
3VA61 3VA63
3VA51 3VA62 3VA64
Door mounted rotary operators without handle
• Degree of protection IP30
• For 3-pole and 4-pole breakers
Version Door open Illumina­tion kit Door
function interlock
With shaft stub Without Without Without 3VA9137-0GK00 3VA9277-0GK00 3VA9447-0GK00
(gray)

With shaft stub Without Without Without – – –


(gray)

Side wall mounted rotary operators without mounting plates


• Rotary operator with shaft 300 mm
• Handle with masking plate 75 × 75 mm
• Degree of protection IP65
• For 3-pole and 4-pole breakers
Version Illumination kit
Standard (gray) Without 3VA9137-0PK11 3VA9277-0PK11 –
With 3VA9137-0PK13 3VA9277-0PK13 –
EMERGENCY-OFF (red/yellow) Without 3VA9137-0PK15 3VA9277-0PK15 –
With 3VA9137-0PK17 3VA9277-0PK17 –
Side wall mounted rotary operators with mounting plates
• Rotary operator with short shaft and mounting plate for mounting directly on
the side wall
• Handle with masking plate 75 × 75 mm
• Degree of protection IP65
• For 3-pole and 4-pole breakers
Version Illumination kit
Standard (gray) Without 3VA9137-0PK51 3VA9277-0PK51 –
With 3VA9137-0PK53 3VA9277-0PK53 –
EMERGENCY-OFF (red/yellow) Without 3VA9137-0PK55 3VA9277-0PK55 –
With 3VA9137-0PK57 3VA9277-0PK57 –
Door interlock for side wall mounted rotary operators

3VA9177-0VF40 3VA9277-0VF40 –

Extended DIN rails for N/PE terminals


Version Rated current In
For mounting plate ≤250 A 3VA9987-0GL30

System overview, page 2/20


2/30 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA57
3VA58
3VA59 2
3VA55 3VA67
3VA65 3VA68
3VA66 3VA69

3VA9677-0GK00

– 3VA9877-0GK00 new

– –
– –
– –
– –

– –
– –
– –
– –

– –

– –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/31
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Manual operators

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2 3VA53
3VA52 3VA54
3VA61 3VA63
3VA51 3VA62 3VA64
Supplementary handles for door mounted rotary operators (NFPA79)
• Mandatory according to NFPA79
• For operation when cabinet door is open
Version
Standard 3VA9137-0GC01 3VA9477-0GC01 3VA9477-0GC11
(gray)
EMERGENCY-OFF 3VA9137-0GC05 3VA9477-0GC05 3VA9477-0GC15
(red/yellow)
Standard – – –
(gray)
EMERGENCY-OFF – – –
(red/yellow)

Handles
• With masking plate
Version Door open Tolerance compensation
function
Standard (gray) Without Without 8UD1721-0AB11 8UD1731-0AB11
With 8UD1721-0AB21 8UD1731-0AB21
With Without 8UD1721-0AC11 8UD1731-0AC11
With 8UD1721-0AC21 8UD1731-0AC21
EMERGENCY-OFF Without Without 8UD1721-0AB15 8UD1731-0AB15
(red/yellow) With 8UD1721-0AB25 8UD1731-0AB25
With Without 8UD1721-0AC15 8UD1731-0AC15
With 8UD1721-0AC25 8UD1731-0AC25
Handle lever extensions
• Note: The handle lever extension is already included in the scope of supply of
the breakers.

– – 3VA9487-0SC10
Shafts
Type Length
8 × 8 mm 300 mm 8UD1900-2WA00
600 mm 8UD1900-2WB00
12 × 12 mm 305 mm –
325 mm –
600 mm –
610 mm –
Adapters for shafts
Type Use
8 × 8 mm With door mounted rotary operator and 8UD1900-2DA00
side wall mounted rotary operator
12 × 12 mm With door mounted rotary operator and –
side wall mounted rotary operator
Door couplings
Type
8 × 8 mm 8UD1900-2HA00
12 × 12 mm –
Mounting tolerance compensations
Type
8 × 8 mm 8UD1900-2GA00
12 × 12 mm –

System overview, page 2/20


2/32 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA57
3VA58
3VA59 2
3VA55 3VA67
3VA65 3VA68
3VA66 3VA69

3VA9677-0GC01 –

3VA9677-0GC05 –

– 3VA9877-0GC01 new

– 3VA9877-0GC05 new

8UD1741-0AB11
8UD1741-0AB21
8UD1741-0AC11
8UD1741-0AC21
8UD1741-0AB15
8UD1741-0AB25
8UD1741-0AC15
8UD1741-0AC25

3VA9987-0SC10 3VA9877-0SC10 new

– –
– –
– –
8UD1900-4WA00 –
8UD1900-4WB00 –
– –

– –

8UD1900-4DA00

– –
8UD1900-4HA00

– –
8UD1900-4GA00

System overview, page 2/20


Siemens LV 18 · 07/2022 2/33
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Manual operators

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2 3VA61
3VA52 3VA62
3VA53 3VA63
3VA51 3VA54 3VA64
Fixing brackets for shafts

3VA9137-0GA80 3VA9477-0GA80

– – –

Variable depth adapters


Type
8 × 8 mm 3VA9487-0GB10

Interlocking module UL 508A


• Used when the handle is to remain on the circuit breaker when the door is
open

8UC9400
Labeling plates for manual operators

3VA9087-0SX10

Illumination kits for manual operators


• 24 V DC voltage
Version Rated current In
Front mounted rotary operator 125 … 250 A 8UD1900-0KA10 –
150 … 600 A – 8UD1900-0KA20
Door mounted rotary operator and 125 … 600 A 8UD1900-0KA20
side wall mounted rotary operator 600 … 1000A – – –
Cylinder locks (type Kaba), standard masking plates
Use Door open function Key
For door mounted rotary operator and Without 1 8UD1900-0MB01
side wall mounted rotary operator 2 8UD1900-0NB01
(in the masking plate),
only for locking, not for interlocking 3 8UD1900-0PB01
4 8UD1900-0QB01
With 1 8UD1900-0MC01
2 8UD1900-0NC01
3 8UD1900-0PC01
4 8UD1900-0QC01
Cylinder locks (type KABA), EMERGENCY-OFF masking plates
Use Door open function Key
For door mounted rotary operator and Without 1 8UD1900-0MB05
side wall mounted rotary operator 2 8UD1900-0NB05
(in the masking plate), 3 8UD1900-0PB05
only for locking, not for interlocking 4 8UD1900-0QB05
With 1 8UD1900-0MC05
2 8UD1900-0NC05
3 8UD1900-0PC05
4 8UD1900-0QC05

System overview, page 2/20


2/34 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA57
3VA58
3VA59 2
3VA55 3VA67
3VA65 3VA68
3VA66 3VA69

– –

3VA9677-0GA80 3VA9877-0GA80 new

– –

– –

– –

– –
– –
– –
8UD1900-0KA30 –

– –
– –
– –
– –
– –
– –
– –
– –

– –
– –
– –
– –
– –
– –
– –
– –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/35
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Manual operators

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2 3VA53
3VA52 3VA54
3VA61 3VA63
3VA51 3VA62 3VA64
Cylinder locks (type RONIS)
• Includes a lock with 2 keys
• For locking or interlocking
• For installation on the circuit breaker side in all rotary operators
• For mounting in the adapter kit for the accessories compartment
• Note: The cylinder lock adapter for rotary operators is also needed for locking
or interlocking circuit breakers via rotary operators
Key
1 3VA9980-0VL10
3 3VA9980-0VL30
4 3VA9980-0VL40
Cylinder locks (type RONIS), for 3VA9877-0EK1. front mounted rotary operators and 3VA877-0FK2. door mounted rotary operators
• Includes a lock with 2 keys
• For locking
• For installation on the circuit breaker side in all rotary operators


Cylinder lock adapters for rotary operators
• To mount the cylinder lock in the rotary operator
(also possible with door mounted rotary operator and side wall mounted
rotary operator), on circuit breaker side, NOT in masking plate

3VA9980-0LF20
Auxiliary switch modules for rotary operators
Version
1× leading to „ON“ – – –
2× leading to „ON“ 3VA9137-0GX10 3VA9477-0GX10
1× leading to „OFF“ – – –
2× leading to „OFF“ – – –
2× leading to „ON“ and – 3VA9477-0GX20
1× leading to „OFF“
Mounting adapters for side wall mounted rotary operators
Version
Necessary accessories for 3VA side wall mounted rotary operators, 3VA9137-0GX01 3VA9477-0GX01
if 3VA9...-0GX.0 auxiliary switch modules are used

Auxiliary switches for 3VA9877-0EK1. front mounted rotary operators and 3VA9877-0FK2. door mounted rotary operators
Version
1× leading to „ON“ – – –
2× leading to „ON“ – – –
1× leading to „OFF“ – – –
2× leading to „OFF“ – – –
Operating units with Bowden cable (MaxFlex operator), plastic
• Complete set, comprising:
− Switching mechanism
− Handle, plastic
− Enclosure types 1, 3, 3R, 4, 12, 12K, black = OFF, red = ON
− Bowden cable, length 36 inch (0.9 m)

3VA9137-0CK12 3VA9277-0CK12 3VA9477-0CK12

System overview, page 2/20


2/36 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA57
3VA58
3VA59 2
3VA55 3VA67
3VA65 3VA68
3VA66 3VA69

3VA9980-0VL10 –
3VA9980-0VL30 –
3VA9980-0VL40 –

– 3VA9870-0VL10 new

3VA9670-0LF20 –

– –
– –
– –
– –
– –

– –

– 3VA9877-0GX31 new
– 3VA9877-0GX32 new
– 3VA9877-0GX41 new
– 3VA9877-0GX42 new

– –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/37
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Manual operators

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2 3VA53
3VA52 3VA54
3VA61 3VA63
3VA51 3VA62 3VA64
Operating units with Bowden cable (MaxFlex operator), steel
• Complete set, comprising:
− Switching mechanism
− Handle, steel, epoxy-coated
− Enclosure types 1, 3, 3R, 4, 12, 12K, black = OFF, red = ON
− Bowden cable, length 36 inch (0.9 m)

3VA9137-0CK72 3VA9277-0CK72 3VA9477-0CK72

Switching mechanisms for operating unit with Bowden cable

3VA9137-0CB10 3VA9277-0CB10 3VA9477-0CB10

Handles for operating unit with Bowden cable


Handle Enclosure types OFF ON
Plastic 1, 3, 3R, 4, 12, 12K Black Red 3VA9977-0CH12
Steel, epoxy-coated 1, 3, 3R, 4, 12, 12K Black Red 3VA9977-0CH72
Black Black 3VA9977-0CH74
Stainless steel, 1, 2, 3, 3R, 4, 4X, 12, Black Red 3VA9977-0CH82
chrome-plated 12K, 13 Black Black 3VA9977-0CH84
Bowden cables for operating unit with Bowden cable
Length
36 inch (0.9 m) 3VA9278-0CC10 3VA9578-0CC10
48 inch (1.2 m) 3VA9278-0CC20 3VA9578-0CC20
60 inch (1.5 m) 3VA9278-0CC30 3VA9578-0CC30
72 inch (1.8 m) 3VA9278-0CC40 3VA9578-0CC40
84 inch (2.1 m) 3VA9278-0CC50 3VA9578-0CC50
96 inch (2.4 m) 3VA9278-0CC60 3VA9578-0CC60
120 inch (3.0 m) 3VA9278-0CC70 3VA9578-0CC70
144 inch (3.6 m) 3VA9278-0CC80 3VA9578-0CC80
Auxiliary switches for operating unit with Bowden cable
• Leading from On to Off
Types
1 CO 3VA9478-0CX10
2 CO 3VA9478-0CX20
Operating units with linkage
• Complete set, comprising:
− Switching mechanism
− Handle
• For mounting depths 200 … 400 mm
Handle ON
Steel, epoxy-coated Red 3VA9138-0DK72 3VA9278-0DK72 3VA9478-0DK72
Steel, chrome-plated Red 3VA9138-0DK82 3VA9278-0DK82 3VA9478-0DK82
Black 3VA9138-0DK84 3VA9278-0DK84 3VA9478-0DK84

System overview, page 2/20


2/38 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA57
3VA58
3VA59 2
3VA55 3VA67
3VA65 3VA68
3VA66 3VA69

3VA9677-0CK72 –

3VA9677-0CB10 –

– –
3VA9877-0CH72 –
3VA9877-0CH74 –
3VA9877-0CH82 –
– –

– –
3VA9877-0CC20 –
3VA9877-0CC30 –
3VA9877-0CC40 –
– –
3VA9877-0CC60 –
3VA9877-0CC70 –
3VA9877-0CC80 –

– –
– –

– –
– –
– –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/39
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Motor operators

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Motor operators without stored energy operators (MO320)
Addressable via Isolating features in Make time, typically Break time, typically Rated
control signals accordance with for 3VA5 for 3VA6 for 3VA5 for 3VA6 operational
IEC/EN 60947-1 power
■ ■ 800 … 1700 ms 1000 … 1700 ms 800 … 1400 ms 800 … 1400 ms 250 W,
max. 500 W
(60 ms)
Motor operators with stored energy operators (SEO520)
Addressable via Isolating features in Make time, typically Break time, typically Rated
control signals accordance with for 3VA5 for 3VA6 for 3VA5 for 3VA6 operational
IEC/EN 60947-1 power
■ ■ < 80 ms < 80 ms < 80 ms < 80 ms 300 W,
max. 500 W
(60 ms)

Mechanical operating cycles counters (for installation in the SEO520)


Mounting Article No.
For installation in the SEO520 3VA9987-0HX10

Cylinder lock adapters for SEO520


Mounting Article No.
For installation of cylinder locks in the SEO520 3VA9980-0LF30

Cylinder locks (type RONIS)


• Includes a lock with 2 keys
• For locking the operating mode (Manual/Auto/Lock)
Key Article No.
1 3VA9980-0VL10
3 3VA9980-0VL30
4 3VA9980-0VL40

System overview, page 2/20


2/40 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA52
3VA61 3VA53 3VA63
3VA51 3VA62 3VA54 3VA64 2
Rated control With
supply voltage communication

24 ... 60 V DC – 3VA9137-0HA10 3VA9277-0HA10 3VA9447-0HA10


110 ... 230 V AC/ – 3VA9137-0HA20 3VA9277-0HA20 3VA9447-0HA20
110 ... 250 V DC

Rated control With


supply voltage communication

24 V DC – – 3VA9277-0HC10 3VA9447-0HC10 1) new


42 ... 60 V AC/DC – – 3VA9277-0HC20 3VA9447-0HC20 1) new
110 ... 230 V AC/ – – 3VA9277-0HC30 3VA9447-0HC30 1) new
110 ... 250 V DC
24 V DC Yes – 3VA9277-0HC15 – 3VA9447-0HC15 1)
new
110 ... 230 V AC/ Yes – 3VA9277-0HC35 – 3VA9447-0HC35 1)
110 ... 250 V DC new
1)
For
 3VA53 and 3VA54 (UL/IEC) product versions < *E04* as well as for 3VA63 and 3VA64 (UL/IEC) product versions < *E03*, the SEO520 cannot be used.
It may be necessary to upgrade to a circuit breaker with a higher product version.

Reset mode
All motor operators have the following reset modes:
Reset mode 1: Automatic reset
Reset mode 2: Reset via OFF-signal

The motor operator with SEO520 stored energy operator additionally has:
Reset mode 3: Reset via OFF-signal with additional acknowledge signal

System overview, page 2/20


Siemens LV 18 · 07/2022 2/41
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Box terminals
Number of poles Connection options Scope of supply Cable cross-section, Cu stranded, class B
Min. Max.
3P ➊ ➋ – 3 single terminals AWG 14 3/0
AWG 10 3/0
AWG 4 350 kcmil
1/0 500 kcmil
4P ➊ ➋ – 4 single terminals AWG 14 3/0
AWG 10 3/0
AWG 4 350 kcmil
1/0 500 kcmil
Box terminal with control wire tap
Number of poles Connection options Scope of supply Cable cross-section, Cu stranded, class B
Min. Max.
3P ➊ ➋ – 3 single terminals AWG 10 3/0
AWG 4 350 kcmil
1/0 500 kcmil
4P ➊ ➋ – 4 single terminals AWG 10 3/0
AWG 4 350 kcmil
1/0 500 kcmil
Nut keeper kits
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
3P ➊ ➋ – 3 terminals 17 mm 0.66 inch 6.5 mm
25 mm 0.98 inch 8 mm
35 mm 1.37 inch 10 mm
50 mm 1.96 inch 28 mm
4P ➊ ➋ – 4 terminals 17 mm 0.66 inch 6.5 mm
25 mm 0.98 inch 8 mm
35 mm 1.37 inch 10 mm
50 mm 1.96 inch 28 mm
Nut keeper kits, with inch thread
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
3P ➊ ➋ – 3 terminals 50.8 mm 2.0 inch 0.6“ … 0.8“/15 … 20 mm

Nut keeper kits, with metric thread


Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
3P ➊ ➋ – 3 terminals 50 mm 1.96 inch 0.6“ … 0.8“/15 … 20 mm

1)
Maximum current-carrying capacity of cable connection 400 A
Flexible copper bar: No restrictions

System overview, page 2/20


2/42 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA53
3VA54 3VA55
3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
2
3VA51 3VA52 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69

3VA9133-0JA11 – – – – – – –
– 3VA9233-0JA11 3VA9143-0JA12 – – – – –
– 3VA9233-0JA12 3VA9243-0JA12 – – – – –
– – – 3VA9473-0JA13 1) – – – –
3VA9134-0JA11 – – – – – – –
– 3VA9234-0JA11 3VA9144-0JA12 – – – – –
– 3VA9234-0JA12 3VA9244-0JA12 – – – – –
– – – 3VA9474-0JA13 1) – – – –

– 3VA9233-0JH11 3VA9143-0JH12 – – – – –
– 3VA9233-0JH12 3VA9243-0JH12 – – – – –
– – – 3VA9473-0JH13 – – – –
– 3VA9234-0JH11 3VA9144-0JH12 – – – – –
– 3VA9234-0JH12 3VA9244-0JH12 – – – – –
– – – 3VA9474-0JH13 – – – –

3VA9133-0QA00 – – – – – – –
– 3VA9233-0QA00 3VA9243-0QA00 – – – – –
– – – 3VA9473-0QA00 – – – –
– – – – 3VA9673-0QA00 – – –
3VA9134-0QA00 – – – – – – –
– 3VA9234-0QA00 3VA9244-0QA00 – – – – –
– – – 3VA9474-0QA00 – – – –
– – – – 3VA9674-0QA00 – – –

– – – – – 3VA9873-0QA00 new –

– – – – – 3VA9803-0QA00 new –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/43
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Circular conductor terminals, 1 cable
Number of poles Connection Scope of supply Cable cross-section Cu/AL stranded, class B 1)
options Min. Max. Cu Al
3P ➊ ➋ – 3 single terminals AWG 14 AWG 8 ■ –
AWG 14 1/0 ■ ■
■ –
AWG 8 3/0 ■ ■
AWG 6 350 kcmil ■ ■
AWG 1 600 kcmil ■ ■

4P ➊ ➋ – 4 single terminals AWG 14 AWG 8 ■ –


AWG 14 1/0 ■ ■
■ –
AWG 8 3/0 ■ ■
AWG 6 350 kcmil ■ ■
AWG 1 600 kcmil ■ ■

Circular conductor terminals with control wire taps, 1 cable


Number of poles Connection Scope of supply Cable cross-section Cu/AL stranded, class B 1)
options Min. Max. Cu Al
3P ➊ ➋ – 3 single terminals AWG 14 AWG 8 ■ –
AWG 14 1/0 ■ ■

■ –
AWG 8 3/0 ■ ■
AWG 6 350 kcmil ■ ■
AWG 1 600 kcmil ■ ■
4P ➊ ➋ – 4 single terminals AWG 14 AWG 8 ■ –
AWG 14 1/0 ■ ■

■ –
AWG 8 3/0 ■ ■
AWG 6 350 kcmil ■ ■
AWG 1 600 kcmil ■ ■
1)
Al cable only tested according to UL 486 A/B 2)
Maximum current-carrying capacity of copper cables 380 A
Maximum current-carrying capacity of aluminum cables 310 A

System overview, page 2/20


2/44 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA61 3VA53 3VA54 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA62 3VA63 3VA64 3VA66 3VA67 3VA68 3VA69 2

3VA9133-0JB10 – – – – – – – –
– 3VA9233-0JB11 – – – – – – –
– – 3VA9143-0JB11 – – – – – –
3VA9133-0JB11 – – – – – – – –
– 3VA9233-0JB12 3VA9243-0JB12 – – – – – –
– – – 3VA9373-0JB13 – – – – –
2)

3VA9134-0JB10 – – – – – – – –
– 3VA9234-0JB11 – – – – – – –
– – 3VA9144-0JB11 – – – – – –
3VA9134-0JB11 – – – – – – – –
– 3VA9234-0JB12 3VA9244-0JB12 – – – – – –
– – – 3VA9374-0JB13 – – – – –
2)

3VA9133-0JG10 – – – – – – – –
– 3VA9233-0JG11 – – – – – – –
new
– – 3VA9143-0JG11 – – – – – –
3VA9133-0JG11 – – – – – – – –
– 3VA9233-0JG12 3VA9243-0JG12 – – – – – –
– – – 3VA9373-0JG13 – – – – –
3VA9134-0JG10 – – – – – – – –
– 3VA9234-0JG11 – – – – – – –
new
– – 3VA9144-0JG11 – – – – – –
3VA9134-0JG11 – – – – – – – –
– 3VA9234-0JG12 3VA9244-0JG12 – – – – – –
– – – 3VA9374-0JG13 – – – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/45
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Copper circular conductor terminals, 1 cable
Number of poles Connection options Scope of supply Cable cross-section, Cu stranded, class B
Min. Max.
3P ➊ ➋ – 3 single terminals AWG 14 AWG 8
AWG 14 2/0
AWG 14 1/0

AWG 6 350 kcmil


AWG 1 600 kcmil
4P ➊ ➋ – 4 single terminals AWG 14 AWG 8
AWG 14 2/0
AWG 14 1/0

AWG 6 350 kcmil


AWG 1 600 kcmil
Copper circular conductor terminals with control wire taps, 1 cable
Number of poles Connection options Scope of supply Cable cross-section, Cu stranded, class B
Min. Max.
3P ➊ ➋ – 3 single terminals AWG 14 AWG 8
AWG 14 2/0
AWG 14 1/0

AWG 6 350 kcmil


AWG 1 600 kcmil
4P ➊ ➋ – 4 single terminals AWG 14 AWG 8
AWG 14 2/0
AWG 14 1/0
AWG 6 350 kcmil
AWG 1 600 kcmil
Copper circular conductor terminals, 4 cables
Number of poles Connection options Scope of supply Cable cross-section, Cu stranded, class B
Min. Max.
3P ➊ ➋ – 3 single terminals 1/0 500 kcmil
long terminal cover 50 240 mm2
Control wire taps for busbars
Connection options
➊ – –

System overview, page 2/20


2/46 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA53
3VA54 3VA55
3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
2
3VA51 3VA52 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69

3VA9133-0JD10 – – – – – – –
3VA9133-0JD11 – – – – – – –
– 3VA9233-0JD11 3VA9143-0JD11 – – – – –
new
– 3VA9233-0JD12 3VA9243-0JD12 – – – – –
– – – 3VA9373-0JD13 – – – –
3VA9134-0JD10 – – – – – – –
3VA9134-0JD11 – – – – – – –
– 3VA9234-0JD11 3VA9144-0JD11 – – – – –
new
– 3VA9234-0JD12 3VA9244-0JD12 – – – – –
– – – 3VA9374-0JD13 – – – –

3VA9133-0JK10 – – – – – – –
3VA9133-0JK11 – – – – – – –
– 3VA9233-0JK11 3VA9143-0JK11 – – – – –
new
– 3VA9233-0JK12 3VA9243-0JK12 – – – – –
– – – 3VA9373-0JK13 – – – –
3VA9134-0JK10 – – – – – – –
3VA9134-0JK11 – – – – – – –
– 3VA9234-0JK11 3VA9144-0JK11 – – – – –
– 3VA9234-0JK12 3VA9244-0JK12 – – – – –
– – – 3VA9374-0JK13 – – – –

– – – – – 3VA9773-0JE43 – –
new

– 3VA9270-0WC00 3VA9470-0WC00 – – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/47
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

Note:
All bus connectors, bus connectors broadened and rear connections are Cu/Sn 6 r plated according to ISO 2093

2
Front bus connectors, with insulating plate, with phase barriers
• 3-pole and 4-pole bus connectors only permitted if used with phase barriers and insulating plate!
• Insulating plate is included in the connection technology scope of supply or can be ordered as a spare part (3VA9...-0W..0).
• Phase barriers are included in the connection technology scope of supply or can be ordered as a spare part (3VA9...-.WA00).
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
3P ➊ ➋ – 3 terminals, 22 mm 0.9 inch 8 mm 0.3 inch
2 phase barriers,
1 insulating plate

4P ➊ ➋ – 4 terminals, 22 mm 0.9 inch 8 mm 0.3 inch


3 phase barriers,
1 insulating plate

Front bus connectors, with insulating plate


• 3-pole and 4-pole bus connectors only permitted if used with phase barriers!
• Insulating plate is included in the connection technology scope of supply or can be ordered as a spare part (3VA9...-0W..0).
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
1P ➊ – – 1 terminal 22 mm 0.9 inch 8 mm 0.3 inch

3P ➊ ➋ – 3 terminals, 32 mm 1.3 inch 10 mm 0.4 inch


1 insulating plate 40 mm 1.6 inch 12.5 mm 0.5 inch

4P ➊ ➋ – 4 terminals, 32 mm 1.3 inch 10 mm 0.4 inch


1 insulating plate 40 mm 1.6 inch 12.5 mm 0.5 inch

Front bus connectors, with phase barriers


• 3-pole and 4-pole bus connectors only permitted if used with phase barriers!
• Phase barriers are included in the connection technology scope of supply or can be ordered as a spare part (3VA9...-.WA00).
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
3P ➊ ➋ – 3 terminals, 50.8 mm 2.0 inch 15.9 mm 0.63 inch
2 phase barriers

4P ➊ ➋ – 4 terminals, 50.8 mm 2.0 inch 15.9 mm 0.63 inch


3 phase barriers

Front bus connectors


Number of poles Connection options Scope of supply
3P ➊ – – 3 terminals,
1 terminal cover
Note:
The bent connection brackets shown in
the picture must be provided by the
customer

System overview, page 2/20


2/48 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

3VA9133-0QB00 – – – – – – – –

3VA9134-0QB00 – – – – – – – –

3VA9131-0QB00 – – – – – – – –

– 3VA9273-0QB00 – 3VA9273-0QB00 – – – – –
– – 3VA9473-0QB00 – 3VA9473-0QB00 – – – –

– – – 3VA9274-0QB00 – – – – –
– – 3VA9474-0QB00 – 3VA9474-0QB00 – – – –

– – – – – 3VA9673-0QB00 – – –

– – – – – 3VA9674-0QB00 – – –

– – – – – – 3VA9873-0QB00 new –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/49
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

Note:
All bus connectors, bus connectors broadened and rear connections are Cu/Sn 6 r plated according to ISO 2093

2
Front bus connectors, for 100% rated MCCB
Number of poles Connection options Scope of supply
3P ➊ – – 3 terminals,
1 terminal cover
Note:
The bent connection brackets shown in
the picture must be provided by the
customer

Front bus connectors broadened, with insulating plate


• 3-pole and 4-pole bus connectors broadened only permitted if used with insulating plate!
• Phase barriers are included in the connection technology scope of supply or can be ordered as a spare part (3VA9...-0W..0).
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
3P ➊ ➋ – 3 terminals, 60 mm 2.4 inch 12.5 mm 0.5 inch
1 insulating plate

4P ➊ ➋ – 4 terminals, 60 mm 2.4 inch 12.5 mm 0.5 inch


1 insulating plate

Front bus connectors broadened, with phase barriers


• 3-pole and 4-pole bus connectors broadened only permitted if used with phase barriers!
• Phase barriers are included in the connection technology scope of supply or can be ordered as a spare part (3VA9...-.WA00).
Number of poles Connection options Scope of supply Max. tap width Max. tap thickness
3P ➊ ➋ – 3 terminals, 60 mm 2.4 inch 12.5 mm 0.5 inch
2 phase barriers

4P ➊ ➋ – 4 terminals, 60 mm 2.4 inch 12.5 mm 0.5 inch


3 phase barriers

1)
For IEC applications up to 1000 A only. In addition, 3VA9872-0WA00 phase barriers and 3VA9803-0QA00 nut keeper kits are required.

System overview, page 2/20


2/50 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

– – – – – – 3VA9873-0QH00 new –

– – 3VA9473-0QC00 – 3VA9473-0QC00 – – – –

– – 3VA9474-0QC00 – 3VA9474-0QC00 – – – –

– – – – – 3VA9673-0QC00 3VA9603-0QC00 1) – –
new

– – – – – 3VA9674-0QC00 – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/51
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

Note:
All bus connectors, bus connectors broadened and rear connections are Cu/Sn 6 r plated according to ISO 2093

2
Rear connection studs flat
Number of poles Connection options Scope of supply
1P ➊ ➋ – 1 short connection stud flat
1 long connection stud flat

3P ➊ ➋ – 2 short connection studs flat,


1 long connection stud flat

4P ➊ ➋ – 2 short connection studs flat,


2 long connection studs flat

Rear connectors vertical


Number of poles Connection options Scope of supply
1P ➊ – – 1 rear connector

3P ➊ – – 3 rear connectors

4P ➊ – – 4 rear connectors

Rear connectors horizontal


Number of poles Connection options Scope of supply
3P ➊ – – 3 rear connectors

4P ➊ – – 4 rear connectors

Rear connection studs round


Number of poles Connection options Scope of supply
1P ➊ ➋ – 1 short connection stud round
1 long connection stud round

3P ➊ ➋ – 1 long connection stud round,


2 short connection studs round

4P ➊ ➋ – 2 long connection studs round,


2 short connection studs round

System overview, page 2/20


2/52 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

3VA9131-0QE10 3VA9231-0QE10 3VA9471-0QE10 3VA9241-0QE10 3VA9471-0QE10 – – – –


3VA9131-0QE20 3VA9231-0QE20 3VA9471-0QE20 3VA9241-0QE20 3VA9471-0QE20 – – – –

3VA9133-0QE00 3VA9233-0QE00 3VA9473-0QE00 3VA9243-0QE00 3VA9473-0QE00 – – – –

3VA9134-0QE00 3VA9234-0QE00 3VA9474-0QE00 3VA9244-0QE00 3VA9474-0QE00 – – – –

– – – – – – 3VA9773-0QE10 – –
new

– – – – – 3VA9673-0QE00 3VA9773-0QE00 – –
new new

– – – – – 3VA9674-0QE00 – – –
new

– – – – – 3VA9673-0QE60 – – –
new

– – – – – 3VA9674-0QE60 – – –
new

3VA9131-0QF10 3VA9231-0QF10 3VA9471-0QF10 3VA9241-0QF10 3VA9471-0QF10 – – – –


3VA9131-0QF20 3VA9231-0QF20 3VA9471-0QF20 3VA9241-0QF20 3VA9471-0QF20 – – – –

3VA9133-0QF00 3VA9233-0QF00 3VA9473-0QF00 3VA9243-0QF00 3VA9473-0QF00 – – – –

3VA9134-0QF00 3VA9234-0QF00 3VA9474-0QF00 3VA9244-0QF00 3VA9474-0QF00 – – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/53
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Circular conductor terminals, large, 1 cable
Number of poles Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
Min. Max. Cu Al
2P ➊ – – 2 single terminals, AWG 4 300 kcmil ■ ■
1 extended terminal cover

3P ➊ – – 3 single terminals, AWG 4 300 kcmil ■ ■


1 extended terminal cover AWG 2 350 kcmil ■ ■

4P ➊ – – 4 single terminals, AWG 4 300 kcmil ■ ■


1 extended terminal cover AWG 2 350 kcmil ■ ■

Circular conductor terminals, large with control wire taps, 1 cable


Number of poles Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
Min. Max. Cu Al
2P ➊ – – 2 single terminals, AWG 4 300 kcmil ■ ■
1 extended terminal cover

3P ➊ – – 3 single terminals, AWG 4 300 kcmil ■ ■


1 extended terminal cover AWG 2 350 kcmil ■ ■

4P ➊ – – 4 single terminals, AWG 4 300 kcmil ■ ■


1 extended terminal cover AWG 2 350 kcmil ■ ■

1)
Al cable only tested according to UL 486 A/B

System overview, page 2/20


2/54 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

3VA9132-0JJ12 – – – – – – – –

3VA9133-0JJ12 – – – – – – – –
– 3VA9233-0JJ13 – 3VA9243-0JJ13 – – – – –

3VA9134-0JJ12 – – – – – – – –
– 3VA9234-0JJ13 – 3VA9244-0JJ13 – – – – –

3VA9132-0JC12 – – – – – – – –

3VA9133-0JC12 – – – – – – – –
– 3VA9233-0JC13 – 3VA9243-0JC13 – – – – –

3VA9134-0JC12 – – – – – – – –
– 3VA9234-0JC13 – 3VA9244-0JC13 – – – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/55
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Circular conductor terminals with control wire taps, 2 cables
Number of poles Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
Min. Max. Cu Al
3P ➊ – – 3 single terminals, AWG 4 300 kcmil ■ ■
1 extended terminal cover 2/0 600 kcmil ■ ■
3 single terminals, 400 kcmil 750 kcmil ■ –
1 intermediate 250 kcmil or 750 kcmil ■ ■
terminal cover 2× 250 kcmil

3P ➊ – – 3 single terminals, 4/0 600 kcmil ■ ■


1 short terminal cover

4P ➊ – – 4 single terminals, AWG 4 300 kcmil ■ ■


1 extended terminal cover 2/0 600 kcmil ■ ■
4 single terminals, 400 kcmil 750 kcmil ■ –
1 intermediate terminal cover 250 kcmil or 750 kcmil ■ ■
2× 250 kcmil

4P ➊ – – 4 single terminals, 4/0 600 kcmil ■ ■


1 short terminal cover

Circular conductor terminals with control wire taps, 2 cables


Number of poles Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
Min. Max. Cu Al
3P ➊ – – 3 single terminals, AWG 4 300 kcmil ■ ■
1 extended terminal cover 2/0 600 kcmil ■ ■
3 single terminals, 400 kcmil 750 kcmil ■ –
1 intermediate terminal cover 250 kcmil or 750 kcmil ■ ■
2× 250 kcmil

3P ➊ – – 3 single terminals, 4/0 600 kcmil ■ ■


1 short terminal cover

4P ➊ – – 4 single terminals, AWG 4 300 kcmil ■ ■


1 extended terminal cover 2/0 600 kcmil ■ ■
4 single terminals, 400 kcmil 750 kcmil ■ –
1 intermediate 250 kcmil or 750 kcmil ■ ■
terminal cover 2× 250 kcmil

4P ➊ – – 4 single terminals, 4/0 600 kcmil ■ ■


1 short terminal cover

1)
Al cable only tested according to UL 486 A/B
2)
Up to rated current 400 A

System overview, page 2/20


2/56 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

– 3VA9233-0JJ22 – 3VA9243-0JJ22 – – – – –
– – 3VA9473-0JJ23 – 3VA9473-0JJ23 – – – –
– – – – – 3VA9673-0JJ24 – – –
– – 3VA9373-0JJ24 2) – 3VA9373-0JJ24 2) – – – –
new new

– – – – – 3VA9573-0JB23 – – –

– 3VA9234-0JJ22 – 3VA9244-0JJ22 – – – – –
– – 3VA9474-0JJ23 – 3VA9474-0JJ23 – – – –
– – – – – 3VA9674-0JJ24 – – –
– – 3VA9374-0JJ24 2) – 3VA9374-0JJ24 2) – – – –
new new

– – – – – 3VA9574-0JB23 – – –

– 3VA9233-0JC22 – 3VA9243-0JC22 – – – – –
– – 3VA9473-0JC23 – 3VA9473-0JC23 – – – –
– – – – – 3VA9673-0JC24 – – –
– – 3VA9373-0JC24 2) – 3VA9373-0JC24 2) – – – –
new new

– – – – – 3VA9573-0JG23 – – –

– 3VA9234-0JC22 – 3VA9244-0JC22 – – – – –
– – 3VA9474-0JC23 – 3VA9474-0JC23 – – – –
– – – – – 3VA9674-0JC24 – – –
– – 3VA9374-0JC24 2) – 3VA9374-0JC24 2) – – – –
new new

– – – – – 3VA9574-0JG23 – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/57
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Circular conductor terminals with control wire taps, 3 cables
Number of Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
poles Min. Max. Cu Al
2P ➊ – – 3 single terminals, 500 kcmil 750 kcmil ■ ■
1 long terminal cover 240 mm2 300 mm2

3P ➊ – – 3 single terminals, 4/0 400 kcmil ■ ■


1 short terminal cover
3 single terminals, 500 kcmil 750 kcmil ■ ■
1 extended terminal
cover
3 single terminals, 500 kcmil 750 kcmil ■ ■
1 long terminal cover 240 mm2 300 mm2
4P ➊ – – 4 single terminals, 4/0 400 kcmil ■ ■
1 short terminal cover
4 single terminals, 500 kcmil 750 kcmil ■ ■
1 extended terminal
cover

Circular conductor terminals with control wire taps, 3 cables


Number of Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
poles Min. Max. Cu Al
3P ➊ – – 3 single terminals, 4/0 400 kcmil ■ ■
1 short terminal cover

3P ➊ – – 3 single terminals, 500 kcmil 750 kcmil ■ ■


1 extended terminal
cover

4P ➊ – – 4 single terminals, 4/0 400 kcmil ■ ■


1 short terminal cover

4P ➊ – – 4 single terminals, 500 kcmil 750 kcmil ■ ■


1 extended terminal
cover

1)
Al cable only tested according to UL 486 A/B

System overview, page 2/20


2/58 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

– – – – – – 3VA9772-0JJ34 – –
new

– – – – – 3VA9673-0JB32 – – –

– – – – – 3VA9673-0JJ34 – – –

– – – – – – 3VA9773-0JJ34 – –
new
– – – – – 3VA9674-0JB32 – – –

– – – – – 3VA9674-0JJ34 – – –

– – – – – 3VA9673-0JG32 – – –

– – – – – 3VA9673-0JC34 – – –

– – – – – 3VA9674-0JG32 – – –

– – – – – 3VA9674-0JC34 – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/59
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Circular conductor terminals, 4 cables
Number of Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
poles Min. Max. Cu Al
2P ➊ – – 2 single terminals, 1/0 500 kcmil ■ ■
1 long terminal cover 50 mm2 240 mm2

3P ➊ – – 3 single terminals, 4/0 500 kcmil ■ ■


1 intermediate
terminal cover
3 single terminals, 4/0 600 kcmil ■ ■
1 extended terminal
cover
3 single terminals, 1/0 500 kcmil ■ ■
1 long terminal cover 50 mm2 240 mm2

4P ➊ – – 4 single terminals, 4/0 500 kcmil ■ ■


1 intermediate
terminal cover
4 single terminals, 4/0 600 kcmil ■ ■
1 extended terminal
cover
Circular conductor terminals with control wire taps, 4 cables
Number of Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
poles Min. Max. Cu Al
3P ➊ – – 3 single terminals, 4/0 500 kcmil ■ ■
1 intermediate
terminal cover
3 single terminals, 4/0 600 kcmil ■ ■
1 extended terminal
cover
3 single terminals, 1/0 500 kcmil ■ ■
1 long terminal cover 50 mm2 240 mm2

4P ➊ – – 4 single terminals, 4/0 500 kcmil ■ ■


1 intermediate
terminal cover
4 single terminals, 4/0 600 kcmil ■ ■
1 extended terminal
cover
Circular conductor terminals with control wire taps, 4 cables
Number of Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
poles Min. Max. Cu Al
3P ➊ – – 3 single terminals, 1/0 500 kcmil ■ ■
1 long terminal cover 50 mm2 240 mm2

1)
Al cable only tested according to UL 486 A/B

System overview, page 2/20


2/60 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

– – – – – – 3VA9772-0JJ43 – –
new

– – – – – 3VA9673-0JJ43 – – –

– – – – – 3VA9673-0JJ44 – – –
new

– – – – – – 3VA9773-0JJ43 – –
new

– – – – – 3VA9674-0JJ43 – – –

– – – – – 3VA9674-0JJ44 – – –
new

– – – – – 3VA9673-0JC43 – – –

– – – – – 3VA9673-0JC44 – – –
new

– – – – – – 3VA9773-0JC43 – –
new

– – – – – 3VA9674-0JC43 – – –

– – – – – 3VA9674-0JC44 – – –
new

– – – – – – 3VA9773-0JM43 – –
new

System overview, page 2/20


Siemens LV 18 · 07/2022 2/61
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Circular conductor terminals for mounting base, for UL applications only
• Note:
For more information, see operating instructions L1V30821788001 at www.siemens.com/lowvoltage/manuals
• Scope of supply:
− 1 single terminal
− 1 mounting screw kit
− Individually packed
Connection Connection options Cable cross-section Cu/AL stranded, class B 1)
Min. Max. Cu Al
4 cables – – ➌ 600 kcmil 750 kcmil ■ ■

5 cables – – ➌ 300 kcmil 600 kcmil ■ ■

6 cables – – ➌ 300 kcmil 600 kcmil ■ ■

Circular conductor terminals for assembly kit


Number of Connection options Scope of supply Cable cross-section Cu/AL stranded, class B 1)
poles Min. Max. Cu Al
3P ➊ – – 3 single terminals 1/0 750 kcmil ■ ■
3 mounting screws 50 mm2 300 mm2

System overview, page 2/20


2/62 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

– – – – – – – 3VA9771-0JJ44 –
new

– – – – – – – 3VA9771-0JJ53 –
new

– – – – – – – 3VA9871-0JJ63 new

– – – – – – – 3VA9773-0JJ64 –
new

System overview, page 2/20


Siemens LV 18 · 07/2022 2/63
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2
Circular conductor terminals, 6 cables
Number of Connection Scope of supply Cable cross-section Cu/AL stranded, class B 1)
poles options Min. Max. Cu Al
2P ➊ – – 2 single terminals, AWG 14 AWG 2 ■ ■
1 extended terminal
cover

3P ➊ – – 3 single terminals, AWG 14 AWG 2 ■ ■


1 extended terminal
cover

4P ➊ – – 4 single terminals, AWG 14 AWG 2 ■ ■


1 extended terminal
cover

Copper circular conductor terminals, 2 cables


Number of Connection Scope of supply Cable cross-section, Cu stranded, class B
poles options Min. Max.
3P ➊ – – 3 single terminals, 2/0 600 kcmil
1 extended terminal
cover

4P ➊ – – 4 single terminals, 2/0 600 kcmil


1 extended terminal
cover

Copper circular conductor terminals with control wire taps, 2 cables


Number of Connection Scope of supply Cable cross-section, Cu stranded, class B
poles options Min. Max.
3P ➊ – – 3 single terminals, 2/0 600 kcmil
1 extended terminal
cover

4P ➊ – – 4 single terminals, 2/0 600 kcmil


1 extended terminal
cover

1)
Al cable only tested according to UL 486 A/B

System overview, page 2/20


2/64 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA53 3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA51 3VA52 3VA54 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69 2

3VA9132-0JF60 – – – – – – – –

3VA9133-0JF60 3VA9233-0JF60 – 3VA9243-0JF60 3VA9373-0JF60 – – – –

3VA9134-0JF60 3VA9234-0JF60 – 3VA9244-0JF60 3VA9374-0JF60 – – – –

– – 3VA9473-0JE23 – 3VA9473-0JE23 – – – –

– – 3VA9474-0JE23 – 3VA9474-0JE23 – – – –

– – 3VA9473-0JL23 – 3VA9473-0JL23 – – – –

– – 3VA9474-0JL23 – 3VA9474-0JL23 – – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/65
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2 3VA51
Copper circular conductor terminals with auxiliary conductor connection, 3 cables
Number of poles Connection options Scope of supply Cable cross-section, Cu stranded,
class B
Min. Max.
3P ➊ – – 3 single terminals 4/0 400 kcmil –
1 short terminal cover
4P ➊ – – 4 single terminals 4/0 400 kcmil –
1 short terminal cover

Copper circular conductor terminals with auxiliary conductor connection, 4 cables


Number of poles Connection options Scope of supply Cable cross-section, Cu stranded,
class B
Min. Max.
3P ➊ – – 3 single terminals 4/0 500 kcmil –
1 intermediate
terminal cover
4P ➊ – – 4 single terminals 4/0 500 kcmil –
1 intermediate
terminal cover

Copper circular conductor terminals for mounting base, for UL only


Connection Connection options Scope of supply Cable cross-section, Cu stranded,
class B
Min. Max.
5 cables – – ➌
1 single terminal 300 kcmil 600 kcmil –
1 mounting screw kit
Terminal covers for fixed-mounted, plug-in and withdrawable units
Version Number of poles Mounting location
Short 1P ➊ – – 3VA9131-0WD10
3P ➊ – – 3VA9131-0WD30
4P ➊ – – 3VA9131-0WD40

Intermediate 1) 3P ➊ – – –
4P ➊ – – –

Extended 2P ➊ – – 3VA9131-0WF20
3P ➊ – – 3VA9131-0WF30

4P ➊ – – 3VA9131-0WF40

Broadened 3P ➊ – – –
4P ➊ – – –

Long 3P ➊ – – –


1)
Suitable for circular conductor terminals 2/3/4 cables

System overview, page 2/20


2/66 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA61 3VA53 3VA63 3VA65 3VA57 3VA58 3VA59
3VA52 3VA62 3VA54 3VA64 3VA66 3VA67 3VA68 3VA69 2

– – – – 3VA9673-0JK32 – – –
new
– – – – 3VA9674-0JK32 – – –
new

– – – – 3VA9673-0JL43 3VA9773-0JE43 – –
new new

– – – – 3VA9674-0JL43 – – –
new

– – – – – – 3VA9871-0JE53 new

– – – – – – – –
3VA9271-0WD30 3VA9471-0WD30 3VA9671-0WD30 3VA9871-0WD30 new
3VA9271-0WD40 3VA9471-0WD40 3VA9671-0WD40 – – –

– – – – 3VA9671-0WE30 – – –
– – – – 3VA9671-0WE40 – – –

– – – – – – – –
3VA9271-0WF30 3VA9471-0WF30 3VA9671-0WF30 – – –
new
3VA9271-0WF40 3VA9471-0WF40 3VA9671-0WF40 – – –
new
– – 3VA9471-0WG30 – – – –
– – 3VA9471-0WG40 – – – –

– – – – – 3VA9771-0WP30 – –
new
– – – – – 3VA9871-0WP30 new –
– – – – – 3VA9871-0WF30 new –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/67
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Connection technology
➊ ➊
➊ For mounting onto the circuit breaker
➋ ➋ ➋ For mounting on plug-in and withdrawable units ➌ ➌ ➌ Mounting base
For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

2 3VA51
Terminal covers for plug-in and withdrawable units (spare part)
• To provide circuit breaker touch protection
• For mounting to the molded case circuit breaker
Number of poles Mounting location
3P ➊ – – –

4P ➊ – – –

Insulating plates specially for fixed-mounted versions


Version Number of poles Mounting location
Standard 2P ➊ – – 3VA9131-0WJ20
3P ➊ – – 3VA9131-0WJ30
4P ➊ – – 3VA9131-0WJ40
Broadened 3P ➊ – – –
4P ➊ – – –

Phase barriers
Scope of supply Mounting location
2 phase barriers ➊ ➋ – 3VA9132-0WA00

System overview, page 2/20


2/68 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA55
3VA61 3VA53 3VA63 3VA65 3VA57 3VA58 3VA59
3VA52 3VA62 3VA54 3VA64 3VA66 3VA67 3VA68 3VA69 2

– 3VA9143-0KB01 – 3VA9343-0KB01 – – – –

– 3VA9144-0KB01 – 3VA9344-0KB01 – – – –

– – – – – – – –
3VA9271-0WJ30 3VA9471-0WJ30 – – – –
3VA9271-0WJ40 3VA9471-0WJ40 – – – –
– – 3VA9471-0WK30 – – – –
– – 3VA9471-0WK40 – – – –

3VA9272-0WA00 3VA9472-0WA00 3VA9672-0WA00 3VA9872-0WA00 new

System overview, page 2/20


Siemens LV 18 · 07/2022 2/69
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Plug-in and withdrawable technology


The main differences between plug-in units and withdrawable units are convenience of operation and the potential for functional
expansion.

Thanks to plug-in and withdrawable technology: Note:


• Molded case circuit breakers can be replaced quickly and easily Plug-in and withdrawable technology are only available for the
for overhauls or servicing 3VA6 molded case circuit breaker with electronic trip units. The
2 • Electrical isolation and clearly visible isolating distance plug-in and draw-out sockets of circuit breaker sizes 250 A to
• The socket can be interlocked to prevent the 3VA molded case 400 A (3VA61, 3VA62 and 3VA63) can be equipped with all
circuit breaker from being plugged in or moved in available terminal types.
• Identical connection technology for all molded case circuit
For circuit breaker size 600 A (3VA64), special plug-in and
breakers, whether they are plug-in, withdrawable or
withdrawable bases are available. Broadened connecting bars are
fixed-mounted units
supplied for this purpose. For temperature reasons, only this
In addition, withdrawable technology offers: connection technology can be used for this size of circuit
breaker. 100% rated breakers can never be used with plug-in or
• Transmission of the position of the molded case circuit breaker withdrawable technology for temperature reasons.
via communication (CONNECT, TEST, DISCONNECT)
• The ability to test the auxiliary and control circuit connections
in the test position of the withdrawable unit, without
contacted main conducting paths
• Transmission of the state of the molded case circuit breaker
(ON, OFF, TRIP) via the COM060 communication module

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

3VA61
3VA62 3VA63 3VA64
Withdrawable unit, complete kits
• Scope of supply:
− Draw-out socket
− Withdrawable unit, conversion kit
− Mounting screw kit
• Note: The crank for the withdrawable unit must be
ordered separately.
Number of poles
3P 3VA9143-0KD00 3VA9343-0KD00 3VA9443-0KD00
4P 3VA9144-0KD00 3VA9344-0KD00 3VA9444-0KD00
Withdrawable units, conversion kits
• Scope of supply:
− Screw-fastened terminal covers for molded case
circuit breakers
− Side panels
− Plug-in contacts
− Cable cages
− Autotrip plunger
Number of poles
3P 3VA9143-0KD10 3VA9343-0KD10
4P 3VA9144-0KD10 3VA9344-0KD10
Plug-in units, complete kits
• Scope of supply:
− Plug-in base
− Plug-in unit, conversion kit
− Mounting screw kit
Number of poles
3P 3VA9143-0KP00 3VA9343-0KP00 3VA9443-0KP00
4P 3VA9144-0KP00 3VA9344-0KP00 3VA9444-0KP00

System overview, page 2/20


2/70 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA61
3VA62 3VA63 3VA64
Plug-in units, conversion kits
• Scope of supply:
− Screw-fastened terminal covers for molded case
circuit breakers
− Plug-in contacts
− Cable cages 2
− Autotrip plunger
Number of poles
3P 3VA9143-0KP10 3VA9343-0KP10
4P 3VA9144-0KP10 3VA9344-0KP10
Cable cages for plug-in/withdrawable units
• Cable duct for routing of the required cables from the
internal accessories on the back of the circuit breaker
Number of poles
3P/4P 3VA9167-0KB02 – –
Door feedthroughs
Number of poles
3P/4P 3VA9147-0KT00 3VA9347-0KT00

Spare part autotrip plunger


Version
Plug-in unit 3VA9267-0KP81 3VA9457-0KP81
Withdrawable unit 3VA9267-0KD81 3VA9457-0KD81

Accessories
Communication links for withdrawable unit
Scope of supply Article No.
Set of cables with three special position signaling switches, 3VA9977-0KC00
3VA9987-0KC10 connecting cables

Position signaling switches for withdrawable unit and plug-in unit


Article No.
3VA9977-0KB00

Connecting cables
Use Article No.
Connection of position signaling switches for communication with COM060 3VA9987-0KC10

Cranks for withdrawable units


Version Scope of supply Article No.
Insulated Including crank holder 3VA9987-0KD81
Auxiliary circuit connectors
• Each auxiliary circuit connector is designed for 4 cables.
Version Article No.
For all withdrawable units 3VA9977-0KD80
For all plug-in units 3VA9977-0KP80

System overview, page 2/20


Siemens LV 18 · 07/2022 2/71
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Plug-in and withdrawable technology

For a complete and valid configuration of your molded case circuit breaker, please use our online
configurator at www.siemens.com/lowvoltage/3va-ul-configurator

Cylinder locks
• Scope of supply: 1 lock with 2 keys

2 • For locking or interlocking


• For installation in all rotary operators with a shaft stub
• For mounting in the adapter kit for the accessories compartment
Key Lock number Article No.
1 1 3VA9980-0VL10
3 3 3VA9980-0VL30
4 4 3VA9980-0VL40
Cylinder lock adapters for withdrawable units
• To prevent unauthorized withdrawal or insertion of the circuit breaker into the withdrawable unit
• Circuit breaker can be locked in the CONNECT, TEST and DISCONNECT positions
Use Article No.
For fitting a cylinder lock in the right-hand 3VA9970-0LF40
side wall of the withdrawable unit

System overview, page 2/20


2/72 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

Communication

powermanager power powerconfig


monitoring software software

2
PROFIBUS

I201_19498a
Ethernet (Modbus TCP)

SIMATIC S7

PROFINET

3VA-line

T-Connector T-Connector T-Connector

COM800 DSP800
breaker data server display

3VA6 molded case 3VA6 molded case 3VA6 molded case


circuit breaker circuit breaker circuit breaker
Large Frame
7KM PAC Switched 7KM PAC 7KM PAC RS485
Ethernet PROFINET PROFIBUS (Modbus RTU)
expansion module expansion module expansion module
COM060
communication module

System overview, page 2/20


Siemens LV 18 · 07/2022 2/73
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Communication

Communication
ETU ETU Display Display COM800/
Measurement function 1)
5-series 8-series in ETU DSP800 COM100
Current
Phase and neutral conductor currents I1, I2, I3, IN A ■ ■ □ □ ■
Residual current to ground Ig A ■ ■ □ □ ■

2 Phase with highest load A ■ ■ □ □ ■


Average value over the three phase currents Ileading axis= (I1 + I2 + I3)/3 A – ■ – □ ■
Asymmetry of the phase currents Inba % – ■ – □ ■
THD of the 3 phases THDI1, THDI2, THDI3 % – ■ – □ ■
Voltage
Phase voltages incl. average value U12, U23, U31, Uphavg V – ■ □ □ ■
Voltages to N conductor incl. average value U1N, U2N, U3N, UNavg V – ■ – □ ■
Voltage unbalance % – ■ – □ ■
THD phase/phase and phase/N THDI1, THDI2, THDI3 % – ■ – □ ■
Power
Active power, total and per phase P1, P2, P3, Ptot kW – ■ □ (Ptot) □ ■
Apparent power, total and per phase S1, S2, S3, Stot kVA – ■ – □ ■
Reactive power, total and per phase Q1, Q2, Q3, Qtot kVAr – ■ □ □ ■
Power factor of the fundamental PF1, PF2, PF3, PFavg – ■ □ (PFavg) □ ■
Energy
Active energy, infeed and feedback Ep kWh – ■ □ □ ■
Reactive energy, infeed and feedback Eq kVArh – ■ – □ ■
Apparent energy Es kVAh – ■ – □ ■
Frequency
Present frequency f Hz – ■ □ □ ■
Maximum pointer function
Min./max. current, voltage, power With time stamp – – – – – ■
Condition monitoring 2)
Operating cycles counter ON/OFF cycle ■ ■ – – ■
Operating hours h ■ ■ – – ■
Trip counter Differentiated in ■ ■ – – ■
trip reasons
Health indicator 3) Incl. contact state % ■ ■ ■ – ■
Remaining life time 3) Time ■ ■ – – ■

■ Available □ Displayable – Not available

1)
Depending on ETU version
2)
Only available with continuous external power supply and COM060 and COM800/100 communication interfaces
3)
Firmware 4.4 or higher of ETU, COM060 and COM800/100 required. Not for the 3VA57, 3VA58, 3VA59, 3VA67, 3VA68 and 3VA69

3VA63
3VA64 3VA67
3VA61 3VA65 3VA68
3VA62 3VA66 3VA69
COM060 communication modules
• For mounting in the right-hand accessories compartment of the 3VA6 molded
case circuit breaker (including ETU power supply)
• Including a T-connector
Use
Communication to the COM800/COM100 breaker data server via 3VA line 3VA9177-0TB10 3VA9377-0TB10 Already
integrated

24 V modules
• 24 V DC
• For mounting in the right-hand accessories compartment of the 3VA6
Use
Optional energy supply for the ETU, also includes continuous operation of the ETU 3VA9177-0TB50 3VA9377-0TB50 Already
display and the measurement function of the ETU 8-series integrated

System overview, page 2/20


2/74 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

Breaker data server


COM800 breaker data servers
Version Article No.
Central communication module for connection of up to eight 3VA6 molded case circuit breakers via the 3VA 3VA9977-0TA10
line, Ethernet 10/100 Mbps interface, module socket for inserting an optional PROFIBUS DP, PROFINET or
RS485 module, 2 terminating resistors
2
COM100 breaker data servers
Version Article No.
Central communication module for connection of a 3VA6 molded case circuit breaker via the 3VA line, 3VA9977-0TA20
Ethernet 10/100 Mbps interface, module socket for inserting an optional PROFIBUS DP, PROFINET or RS485
module, 2 terminating resistors

7KM PAC PROFIBUS DP expansion modules


Use Article No.
Used for connecting the COM800/COM100 breaker data server, and the 3VA molded case circuit breakers 7KM9300-0AB01-0AA0
connected to it, to PROFIBUS DPV1. Supplies the state and measured variables of the 3VA molded case circuit
breaker for the PROFIBUS DP master. Receives information (e.g. commands) from the PROFIBUS DP master
and transmits them to the 3VA molded case circuit breaker.
7KM PAC Switched Ethernet PROFINET expansion modules
Use Article No.
Used for connecting the COM800/COM100 breaker data server, and the connected 3VA molded case circuit 7KM9300-0AE02-0AA0
breakers, to PROFINET via two Ethernet interfaces. Supplies the state and measured variables of the 3VA
molded case circuit breakers to PROFINET via the PROFINET IO, PROFIenergy and Modbus TCP protocols.

7KM PAC RS485 Modbus RTU expansion modules


Use Article No.
Used for connecting the COM800/COM100 breaker data server, and the 3VA molded case circuit breakers 7KM9300-0AM00-0AA0
connected to it, to Modbus RTU. Supplies the state and measured variables of the 3VA molded case circuit
breaker for the Modbus RTU master. Receives information (e.g. commands) from the Modbus RTU master
and transmits them to the 3VA molded case circuit breaker.

System overview, page 2/20


Siemens LV 18 · 07/2022 2/75
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Communication

Accessories for communication


T-connectors (spare part)
Use Article No.
Provides a stub connection to the COM060 and loops through to the next circuit breaker. 3VA9987-0TG10
Including connection adapter for mounting on the 3VA6 circuit breaker enclosure
DIN-rail adapters
2 Use Article No.
For snapping the T-connector onto a DIN rail 3VA9987-0TG11

Prefabricated connecting cables, T-connector – T-connector or T-connector – COM800/COM100


Length Article No.
0.4 m 3VA9987-0TC10
1m 3VA9987-0TC20
2m 3VA9987-0TC30
4m 3VA9987-0TC40
Prefabricated connecting cables for extending the COM060 – T-connector stub connection
Length Article No.
0.4 m 3VA9987-0TF20
0.8 m 3VA9987-0TF10

Additional bus terminating resistors


Article No.
3VA9987-0TE10

Voltage tap to external N conductors


Use Article No.
Cable for connection of the star point for the measurement function of the 8-series ETU, length 1.5 m 3VA9987-0UC10

External current transformers as straight-through transformers


Use Rated current In Article No.
Connection of an external current transformer for the neutral conductor 25 … 150 A 3VA9077-0NA10
for 3-pole 3VA6 molded case circuit breakers for 5-series and 8-series ETUs 160 … 350 A 3VA9177-0NA10
(ETU850, ETU856, ETU860), including connecting cables
400 … 600 A 3VA9377-0NA10

600 … 1200 A 3VA9677-0NA10


1600/2000 A 3VA9877-0NA10 new

Display
Display DSP800 for connection to COM800/COM100
Use Article No.
For displaying status, measured values and parameters 3VA9977-0TD10
of up to 8 3VA6 molded case circuit breakers.
Connection to the COM800/COM100 via Ethernet
for displaying the information of the COM800/COM100
and the connected 3VA6 molded case circuit breakers.

System overview, page 2/20


2/76 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

External function box


EFB300 external function boxes
• 4 digital outputs for information output
• 1 digital input
• ZSI functionality
• S0 interface
• Including cable 1.5 m in length
Use Article No. 2
For connection to the ETU of 3VA6 molded case circuit breakers 3VA9977-0UA10
Connecting cables for EFB300
Length Use Article No.
1.5 m 3VA9987-0UB10
3.0 m 3VA9987-0UB20

Maintenance mode box


MMB300 maintenance mode boxes
• 2 digital outputs
• 1 digital input
• 1 3VA-line interface
• Including cable 1.5 m in length
Use Article No.
Series connection of up to eight 3VA6 molded case circuit breakers to one MMB300 maintenance mode box 3VA9977-0UF10
for activating the Dynamic Arc Sentry Mode (DAS Mode) of the molded case circuit breaker

Test devices
TD300 test devices
Use Connection Article No.
For activation of the ETU and On the front interface of the ETU 3VA9977-0MA10
initiation of a test tripping operation

TD400 test devices 1)


• Energy supply via batteries or the USB-C interface
• USB-C interface for connecting a PC with powerconfig
• Bluetooth interface for connection to a PC, smartphone or tablet
• ETU parameterization
• Including adapter and connecting cable to 3VA2 molded case circuit breaker and IEC 3WL
(ETU Release 2)
• Including case
Use Connection Article No.
Initiation of a test tripping operation On the front interface of the ETU (3VA and IEC 3WL ETU Release 2) 3VW9011-0AT40
TD500 test devices
• USB interface for connecting a PC with powerconfig
• Including external power supply
• Including connecting cable to 3VA2 molded case circuit breaker
Use Connection Article No.
Initiation of various test tripping On the front interface of the ETU 3VA9977-0MB10
operations (LSING), ETU parameterization
External power supplies for TD500 (spare part)
Voltage Article No.
110 … 240 V AC 3VA9987-0MX10

Connecting cables for connecting TD500 to 3VA6 molded case circuit breakers (spare part)
Article No.
3VA9977-0MY10

1)
A country-specific radio license is required to operate the Bluetooth interface.
Before activating the Bluetooth function, ensure that the license is available:
www.siemens.com/lowvoltage/certificates

System overview, page 2/20


Siemens LV 18 · 07/2022 2/77
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Locking, blocking and interlocking

3VA53
3VA54
3VA61 3VA63
3VA51 3VA52 3VA62 3VA64
2 Locking
• The locking provisions make it possible to lock the 3VA molded case
circuit breakers in either the OFF or the ON operating position.
Version

Cylinder lock Key 1 (lock number 1) 3VA9980-0VL10


Key 3 (lock number 3) 3VA9980-0VL30
Key 4 (lock number 4) 3VA9980-0VL40

Adapter kit for mounting the cylinder lock (type RONIS) in the 3VA9137-0LF10 3VA9237-0LF10 3VA9147-0LF10 3VA9347-0LF10
accessories compartment of the molded case circuit breaker

Blocking device for handle 3VA9038-0LB10 3VA9378-0LB10

Locking provision for handle – – –

System overview, page 2/20


2/78 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA57
3VA58
3VA59
3VA55 3VA67
3VA65 3VA68
3VA66 3VA69
Locking 2

Use in Locking in OFF Locking in ON Front Rear Interlocked breakers


position position mounting mounting
3VA9980-0VL10 – Breakers, motor ■ ■ ■ – –
3VA9980-0VL30 – operators, manual
operators, withdrawable
3VA9980-0VL40 –
technology

3VA9577-0LF10 – Circuit breaker ■ ■ ■ – –

3VA9578-0LB10 3VA9877-0LB10 Circuit breaker ■ ■ ■ – –


new

– 3VA9877-0LB11 Circuit breaker ■ ■ ■ – –


new

System overview, page 2/20


Siemens LV 18 · 07/2022 2/79
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Locking, blocking and interlocking

3VA53
3VA54
3VA61 3VA63
3VA51 3VA52 3VA62 3VA64
2 Interlocking
• Using interlocking technology, it is possible to mutually interlock
two or more molded case circuit breakers.
• The interlock system is designed to ensure that no more than one
molded case circuit breaker can be operated at a time.
• The following methods of interlocking can be used on 3VA molded
case circuit breakers:
− Front interlock
− Rear interlock
Version

Cylinder lock Key 1 (lock number 1) 3VA9980-0VL10


Key 3 (lock number 3) 3VA9980-0VL30
Key 4 (lock number 4) 3VA9980-0VL40

Sliding bar interlock for 3VA9138-0VF30 3VA9238-0VF30 3VA9148-0VF30 3VA9348-0VF30


interlocking 2 circuit breakers

Module for handle interlock One module for handle interlock is 3VA9137-0VF10 3VA9237-0VF10 3VA9147-0VF10 3VA9347-0VF10
with Bowden cable required for each circuit breaker.
A Bowden cable must be ordered
separately.

Bowden cable Length 0.6 m 3VA9980-0VC10


Length 1.0 m 3VA9980-0VC20
Length 1.5 m 3VA9980-0VC30

Rear interlock with rod Circuit breaker, fixed-mounted 3VA9078-0VM10


Plug-in/withdrawable technology 3VA9078-0VM30

Circuit breaker, fixed-mounted – – – –

Mounting frame for rear Profile rails (2 units) 3VA9078-0VK10


interlock with rod for
fixed-mounted version
Mounting plate 3VA9138-0VK20 3VA9238-0VK20 3VA9248-0VK20 3VA9448-0VK20

1)
Contains mounting plate and profile rails

System overview, page 2/20


2/80 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA57
3VA58
3VA59
3VA55 3VA67
3VA65 3VA68
3VA66 3VA69
Interlocking 2

Use in Locking in OFF Locking in ON Front Rear Interlocked breakers


position position mounting mounting
3VA9980-0VL10 – Breakers, motor ■ ■ ■ – Unlimited
3VA9980-0VL30 – operators, manual
operators, withdrawable
3VA9980-0VL40 –
technology

– – Circuit breaker – – ■ – 3

3VA9577-0VF10 3VA9877-0VF10 Circuit breaker – – ■ – 3


new

3VA9980-0VC10 –
3VA9980-0VC20
3VA9980-0VC30

3VA9578-0VM10 1) – Circuit breaker, – – – ■ 2


– – fixed-mounted,
Plug-in/withdrawable
technology
– 3VA9873-0VM10 Circuit breaker, – – – ■ 2
new fixed-mounted

– – Fixed-mounted – – – ■

– –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/81
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Cover frames and mounting

3VA51
Cover frames for door cut-outs for molded case circuit breakers, with access to TMTU/ETU
Number of poles
2 3P 3VA9033-0SB20
4P 3VA9034-0SB20

Cover frames for door cut-outs for molded case circuit breakers, with access to TMTU/ETU and connection area
Number of poles
3P –

Cover frames for door cut-outs for molded case circuit breakers, without access to TMTU/ETU
Number of poles
3P 3VA9033-0SB10
4P 3VA9034-0SB10

Cover frames for door cutout for circuit breaker handle only, without access to TMTU/ETU
Number of poles
3P –

Cover frames for MO320 motor operators


Use
MO320 motor operator 3VA9033-0SB10
Motor operator with SEO520 stored energy operator –

Cover frames for front mounted rotary operators

3VA9033-0SB10

Cover frames for door feedthroughs

System overview, page 2/20


2/82 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA53
3VA54 3VA55 3VA57 3VA67
3VA61 3VA63 3VA65 3VA58 3AV68
3VA52 3VA62 3AV64 3VA66 3VA59 3VA69

3VA9233-0SB20 3VA9143-0SB20 3VA9343-0SB20 3VA9583-0SB20 3VA9877-0SB20 new 2


3VA9234-0SB20 3VA9144-0SB20 3VA9344-0SB20 3VA9584-0SB20 – –

– – – – 3VA9877-0SB60 new

3VA9143-0SB10 3VA9373-0SB10 3VA9583-0SB10 – –


3VA9144-0SB10 3VA9374-0SB10 3VA9584-0SB10 – –

– – – – 3VA9877-0SB10 new

3VA9237-0SB30 3VA9377-0SB30 – – –
3VA9147-0SB30 – – – –

3VA9143-0SB10 3VA9373-0SB10 3VA9583-0SB50 – –

– – – – 3VA9877-0SB30 new

3VA9233-0SB20 3VA9333-0SB20 – – –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/83
© Siemens 2022
Molded Case Circuit Breakers | 3VA51 – 3VA69 new

Cover frames and mounting

3VA51
Labeling plates for cover frame, not for 3VA9877-0SB10 and 3VA9877-0SB30

2 3VA9087-0SX10

Adapters for 60 mm busbar system (8US)


• Busbar adapter systems with 60-mm spacing between busbars
• For mounting on the busbar adapter, box terminals for the line side must be ordered separately.
• The connection technology for the outgoing side can be chosen freely
Number of poles
3P 8US1211-4SS00
4P –

Mounting screw kits with metric thread


Use Number of poles
For fixed-mounted breakers 1P 3VA9151-0SS10
3P 3VA9126-0SS10
4P 3VA9124-0SS10
3P and 4P –
For plug-in and withdrawable – –
technology
Mounting screw kits with inch thread
Version Scope of supply
1/4-20 UNC × 4.0 4 screws and 4 nuts, inch thread –

Mounting base
Use
For front connection –

For rear connection –

Assembly kit for multiple feed-in terminals and busbars


Use Number of poles
For busbars and multiple feed-in 3P –
terminals

System overview, page 2/20


2/84 Siemens LV 18 · 07/2022
© Siemens 2022
3VA51 – 3VA69 new | Molded Case Circuit Breakers

3VA53
3VA54 3VA55
3VA61 3VA63 3VA65 3VA57 3VA58 3VA59
3VA52 3VA62 3VA64 3VA66 3VA67 3VA68 3VA69

3VA9087-0SX10 2

8US1213-4AP03 8US1213-4AH04 – – –
8US1313-4AH03 new 8US1313-4AM04 – – –
new

– – – – – –
3VA9126-0SS10 – – 3VA9874-0SS10 new
3VA9124-0SS10 – – – –
– – 3VA9328-0SS10 – – –
– 3VA9124-0SS10 3VA9328-0SS10 – – –

– – – – 3VA9874-0SS00 new

– – – – – 3VA9873-0WM00 new

– – – – – 3VA9873-0WN00 new

– – – – 3VA9873-0WL00 new –

System overview, page 2/20


Siemens LV 18 · 07/2022 2/85
© Siemens 2022
Molded Case Circuit Breakers | 3VL

3VL up to 1600 A, according to UL 489

2 Product Discontinuation
The 3VL molded case circuit breaker up to 1600 A UL can only be
ordered as a spare part since 10/2021 and will be removed from
the order portfolio from 10/2025 onwards.
Documents available for downloading:
You can find comprehensive information on the 3VL molded case
circuit breaker in the catalog extract
3VL molded case circuit breakers according to UL 489
www.siemens.com/lowvoltage/catalogs (109778213)

3VL molded case circuit breakers

VL150X UL, VL150 UL, VL250 UL,


CG frame DG frame FG frame
Number of poles 3-pole 3-pole 3-pole
Rated current In 1) 20 A … 150 A 50 A … 150 A 100 A … 250 A
Frequency 50/60 Hz 50/60 Hz 50/60 Hz
Electrical characteristics according to UL 489
Rated operational voltage Ue 50/60 Hz AC 480 V, 600 V/347 V 480 V, 600 V/347 V 480 V, 600 V/347 V
DC 2) 250 V 500 V 500 V
Breaking capacity N H L N H L N H L
Breaking capacity Up to 240 V AC kA 65 100 – 65 100 200 65 100 200
Up to 480 V AC kA 35 65 – 35 65 100 35 65 100
Up to 600 V AC kA – – – – – – – – –
Up to 600 Y/347 V AC kA 10 10 – 18 18 18 18 18 18
Up to 250 V DC 3) kA 30 30 – 30 30 30 30 30 30
Up to 500 V DC 3) 4) kA – – – 18 18 18 18 25 30
Breaking capacity Icu/Ics Up to 240 V AC kA 65/65 10/75 – 65/65 100/75 200/150 65/65 100/75 200/150
rms value according to IEC 60947-2 Up to 415 V AC kA 40/40 70/70 – 40/40 70/70 100/75 40/40 70/70 100/75
Up to 690 V AC kA 8/4 5) 10/5 5) – 12/6 12/6 12/6 12/6 12/6 12/6
Up to 250 V DC 3) kA 30/30 30/30 – 30/30 30/30 30/30 30/30 30/30 30/30
Dimensions
D A mm 105 105 105
A C
NSE0_01159

B mm 157 175 175


C mm 81 81 81
B

D mm 107 107 107


1)
80% rated current applications acc. to UL 489, 4)
500 V DC nominal/600 V DC max. for use in ungrounded UPS DC applications
100% rated current applications acc. to IEC 60947-2. (acc. to UL 489, Supplement SC)
2)
Rated operational DC voltage applies only to molded case circuit breakers with 5)
Rated current In ≥25 A.
a thermal-magnetic trip unit.
3)
For switching DC, the maximum permissible direct voltage per conducting path must be
considered.

2/86 Siemens LV 18 · 07/2022


© Siemens 2022
3VL | Molded Case Circuit Breakers

VL400 UL, VL400X UL, VL800 UL, VL1200 UL, VL1600 UL,
JG frame LG frame MG frame NG frame PG frame
3-pole 3-pole 3-pole 3-pole 3-pole
250 A … 400 A 400 A … 600 A 600 A … 800 A 800 A … 1200 A 1200 A … 1600 A
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz

600 V 600 V 600 V 600 V 600 V


500 V 500 V 500 V 500 V 500 V
N H L N H L N H L N H L N H L
65 100 200 65 100 200 65 100 200 65 100 200 65 100 200
35 65 100 35 65 100 35 65 100 35 65 100 35 65 100
25 25 25 18 18 18 25 35 50 25 35 65 25 35 65
– – – – – – – – – – – – – – –
30 30 30 30 30 30 22 25 42 22 25 42 22 25 42
25 35 35 25 35 35 35 50 65 35 50 65 35 50 65
65/65 100/75 200/150 65/65 100/75 200/150 65/65 100/75 200/150 65/35 100/50 200/100 65/35 100/50 200/100
45/45 70/70 100/75 45/45 70/70 100/75 50/50 70/70 100/75 50/25 70/35 100/50 50/25 70/35 100/50
12/6 15/8 15/8 12/6 15/8 15/8 20/10 20/10 20/10 20/10 30/15 35/17 20/10 30/15 35/17
30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30 30/30

139 139 190 229 229


279 279 406 406 406
102 102 118 157 157
138 138 151 209 209

Siemens LV 18 · 07/2022 2/87


© Siemens 2022
Appendix
© Siemens 2022
Appendix

Appendix

Link directory A/2

Conditions of sale and delivery A/4

Article number index A/6

Index A/7

Notes A/8

Siemens LV 18 · 07/2022 A/1


© Siemens 2022
Appendix | Link directory

Link directory
Catalog LV 18

General information
Information on low-voltage power distribution and electrical www.siemens.com/lowvoltage
installation technology
Tender specifications www.siemens.com/lowvoltage/tenderspecifications
Conversion tool www.siemens.com/conversion-tool
Image database www.siemens.com/lowvoltage/picturedb
CAx download manager www.siemens.com/cax
Newsletter system www.siemens.com/lowvoltage/newsletter
Siemens YouTube channel www.youtube.com/Siemens
Catalog LV 10 www.siemens.com/lv10
Catalog LV 18 www.siemens.com/lv18
Brochures/catalogs www.siemens.com/lowvoltage/catalogs
Operating instructions/manuals www.siemens.com/lowvoltage/manuals
Siemens Industry Online Support (SIOS) www.siemens.com/lowvoltage/product-support
Siemens Industry Online Support app www.siemens.com/support-app
My Documentation Manager (MDM) www.siemens.com/lowvoltage/mdm
Configurators www.siemens.com/lowvoltage/configurators
Siemens Industry Mall – product catalog and www.siemens.com/lowvoltage/mall
online ordering system
Direct forwarding to the Industry Mall www.siemens.com/product?Article No.
Training www.siemens.com/sitrain-lowvoltage
Local contacts www.siemens.com/lowvoltage/contact
www.siemens.com/lowvoltage/components/contact
www.siemens.com/lowvoltage/systems/contact
www.siemens.com/lowvoltage/software/contact
Technical Support www.siemens.com/support-request
Information on services www.siemens.com/service-catalog
Control panels for the North American market www.siemens.com/northamerican-standards
Control panel building www.siemens.com/controlpanel
Energy savings and amortization www.automation.siemens.com/sinasave
SIMATIC Energy Suite www.siemens.com/energysuite
SITOP power supplies www.siemens.com/sitop
Power distribution with Totally Integrated Power www.siemens.com/tip

A/2 Siemens LV 18 · 07/2022


© Siemens 2022
Link directory | Appendix

Information + ordering
Technical overviews
Air circuit breakers www.siemens.com/lowvoltage/product-support (109766020)
Molded case circuit breakers www.siemens.com/lowvoltage/product-support (109767421)
All the important things at a glance
Air circuit breakers www.siemens.com/3WL
Molded case circuit breakers www.siemens.com/3VA
Your product in detail
Technical basic information – 3VA molded case circuit breakers www.siemens.com/lowvoltage/product-support (109766672)
Siemens YouTube channel
3WL air circuit breakers (general) bit.ly/2ZH1rXH
3VA molded case circuit breakers (general) bit.ly/2xNxlFA
Everything you need for your order
3WL air circuit breakers/non-automatic air circuit breakers for sie.ag/2ScRZK7
AC up to 5000 A, UL
3VA molded case circuit breakers, UL/IEC sie.ag/2yPsA2e
Configurators
3WL air circuit breakers www.siemens.com/lowvoltage/3wl-configurator
3VA molded case circuit breakers www.siemens.com/lowvoltage/3va-ul-configurator

Commissioning + operation
Tools/software
SENTRON powerconfig www.siemens.com/powerconfig
Manuals
Communication manual – 3VA molded case circuit breakers with www.siemens.com/lowvoltage/manuals (98746267)
IEC and UL certification
Communication manual – 3WL air circuit breakers via COM35 – www.siemens.com/lowvoltage/manuals (109757987)
PROFINET IO, Modbus TCP
Configuration manual – 3VA selectivity www.siemens.com/lowvoltage/manuals (109743975)
Configuration manual – 3WL5 air circuit breakers/non-automatic www.siemens.com/lowvoltage/manuals (109775570)
air circuit breakers
Equipment manual – 3VA molded case circuit breakers with UL www.siemens.com/lowvoltage/manuals (109758561)
and IEC certification
System manual – 3WL/3VL circuit breakers with communication www.siemens.com/lowvoltage/manuals (39850157)
capability – Modbus
System manual – 3WL/3VL circuit breakers with communication www.siemens.com/lowvoltage/manuals (12560390)
capability – PROFIBUS
Face-to-face or online training
Video tutorial on the 3WL air circuit breaker www.lowvoltage.siemens.com/wcms/3wl-tutorial
Protection systems in low-voltage power distribution www.siemens.com/sitrain-lowvoltage (WT-LVAPS)
3WL air circuit breakers, sizes 1-3 www.siemens.com/sitrain-lowvoltage (WT-LVA3WL)
3VA molded case circuit breakers www.siemens.com/sitrain-lowvoltage (WT-LVA3VA)
Communication with SENTRON components www.siemens.com/sitrain-lowvoltage (LV-COM)
Maintenance and operation of 3WL circuit breakers www.siemens.com/sitrain-lowvoltage (LV-CBMAIN) A
with subsequent certification option www.siemens.com/sitrain-lowvoltage (LV-CBCERT)
Project planning and selection of SENTRON circuit breakers www.siemens.com/sitrain-lowvoltage (LV-CBPROJ)

Siemens LV 18 · 07/2022 A/3


© Siemens 2022
Appendix | Conditions of sale and delivery

Conditions of sale and delivery

1. General Provisions 1.2 For customers with a seat or registered office outside
By using this catalog you can purchase products (hardware, European Union
software and services) described therein from Siemens Aktien­ For customers with a seat or registered office outside European
gesellschaft subject to the following Terms and Conditions of Union, the following terms and conditions apply subordinate to
Sale and Delivery (hereinafter referred to as „T&C“). Please note T&C:
that the scope, the quality and the conditions for supplies and
• for products, which include specific terms and conditions in
services, including software products, by any Siemens entity
the description text, these specific terms and conditions shall
having a registered office outside Germany, shall be subject
apply and subordinate thereto,
exclusively to the General Terms and Conditions of the respective
• for consulting services the „Standard Terms and Conditions for
Siemens entity. The following T&C apply exclusively for orders
Consulting Services of the Division DF for Customers with a
placed with Siemens Aktiengesellschaft, Germany.
Seat or Registered Office Outside of Germany“1) and/or
1.1 For customers with a seat or registered office in • for other services the „International Terms & Conditions for
European Union Services“1) supplemented by „Software Licensing Conditions“1)
For customers with a seat or registered office in European Union, and/or
the following terms and conditions apply subordinate to T&C: • for other supplies of hard- and software the „International
Terms & Conditions for Products“1) supplemented by „Software
• for products, which include specific terms and conditions in Licensing Conditions“1)
the description text, these specific terms and conditions shall
apply and subordinate thereto, 1.3 For customers with master or framework agreement
• for stand-alone software products and software products To the extent our supplies and/or services offered are covered by
forming a part of a product or project, the „General License an existing master or framework agreement, the terms and
Conditions for Software Products for Automation and Drives conditions of that agreement shall apply instead of T&C.
for Customers with a Seat or registered Office in Germany“1)
2. Additional Terms and Conditions
and/or
The dimensions are in mm. In Germany, according to the German
• for consulting services the “Allgemeine Geschäftsbedingungen
law on units in measuring technology, data in inches apply only
für Beratungsleistungen der Division DF – Deutschland”
to devices for export.
(available only in German) and/or
• for other services, the „Supplementary Terms and Conditions Illustrations are not binding.
for Services (“BL”)1) and/or
Insofar as there are no remarks on the individual pages of this
• for other supplies the „General Conditions for the Supply of
catalog – especially with regard to data, dimensions and weights
Products and Services of the Electrical and Electronics
given – these are subject to change without prior notice.
Industry“1).
In case such supplies should contain Open Source Software,
the conditions of which shall prevail over the „General
Conditions for the Supply of Products and Services of the
Electrical and Electronics Industry“1), a notice will be contained
in the scope of delivery in which the applicable conditions for
Open Source Software are specified. This shall apply mutatis
mutandis for notices referring to other third party software
components.

1)
The text of the Terms and Conditions of Siemens AG can be downloaded at
https://mall.industry.siemens.com/legal/ww/en/ terms_of_trade_en.pdf

A/4 Siemens LV 18 · 07/2022


© Siemens 2022
Conditions of sale and delivery | Appendix

3. Export Regulations
We shall not be obligated to fulfill any agreement if such Prior to any transfer of goods, works and services provided by us
fulfillment is prevented by any impediments arising out of to a third party you shall in particular check and guarantee by
national or international foreign trade or customs requirements appropriate measures that
or any embargoes and/or other sanctions. • there will be no infringement of an embargo imposed by the
Export may be subject to license. We shall indicate in the delivery European Union, by the United States of America and/or by the
details whether licenses are required under German, European United Nations by such transfer, by brokering of contracts
and US export lists. concerning those goods, works and services or by provision of
other economic resources in connection with those goods,
Our products are controlled by the U.S. Government (when works and services, also considering the limitations of
labeled with „ECCN“ unequal „N“) and authorized for export only domestic business and prohibitions of by-passing those
to the country of ultimate destination for use by the ultimate embargos;
consignee or end-user(s) herein identified. They may not be • such goods, works and services are not intended for use in
resold, transferred, or otherwise disposed of, to any other connection with armaments, nuclear technology or weapons,
country or to any person other than the authorized ultimate if and to the extent such use is subject to prohibition or
consignee or end-user(s), either in their original form or after authorization, unless required authorization is provided;
being incorporated into other items, without first obtaining • the regulations of all applicable Sanctioned Party Lists of the
approval from the U.S. Government or as otherwise authorized European Union and the United States of America concerning
by U.S. law and regulations. Products labeled with „AL“ unequal the trading with entities, persons and organizations listed
„N“ are subject to European/national export authorization. therein are considered.
The export indications can be viewed in advance in the descrip­ If required to enable authorities or us to conduct export control
tion of the respective goods on the Industry Mall, our online checks, you, upon request by us, shall promptly provide us with
catalog system. Only the export labels „AL“ and „ECCN“ indicated all information pertaining to the particular end customer, the
on order confirmations, delivery notes and invoices are authori- particular destination and the particular intended use of goods,
tative. works and services provided by us, as well as any export control
restrictions existing.
Products without label, with label „AL:N“/„ECCN:N“, or label
„AL:9X9999“/„ECCN: 9X9999“ may require authorization from You acknowledge that under the EU embargo regulations against
responsible authorities depending on the final end-use, or the Iran, Syria and Russia respectively the sale of certain listed goods
destination. and related services is subject to authorization by the competent
export control authorities of the European Union. If (1) the goods
If you transfer goods (hardware and/or software and/or technolo- or services ordered by you are destined for Iran, Syria or Russia,
gy as well as corresponding documentation, regardless of the and (2) the contract for our supplies and/or services is subject to
mode of provision) delivered by us or works and services prior authorization of the competent export control authorities of
(including all kinds of technical support) performed by us to a the European Union, the contract between you and us shall
third party worldwide, you shall comply with all applicable come into force in this respect only upon granting of such
national and international (re-)export control regulations. In any authorization.
event of such transfer of goods, works and services you shall
comply with the (re-) export control regulations of the Federal The products listed in this catalog may be subject to European/
Republic of Germany, of the European Union and of the United German and/or US export regulations. Any export requiring
States of America. approval is therefore subject to authorization by the relevant
authorities. Errors excepted and subject to change without prior
notice.

Siemens LV 18 · 07/2022 A/5


© Siemens 2022
Appendix | Article number index

Article number index

Article No. Page

3V
3VA90 2/34, 2/76, 2/78, 2/80, 2/82, 2/84–2/85
3VA91 I/3, 2/28, 2/30, 2/32, 2/34, 2/36, 2/38, 2/41, 2/43, 2/45,
2/47, 2/49, 2/53, 2/55, 2/65–2/66, 2/68–2/71, 2/74, 2/76,
2/78, 2/80, 2/83–2/85
3VA92 2/28, 2/30, 2/36, 2/38, 2/41, 2/43, 2/45, 2/47, 2/49, 2/53,
2/55, 2/57, 2/65, 2/67, 2/69, 2/71, 2/78, 2/80, 2/83
3VA93 2/45, 2/47, 2/57, 2/65, 2/69–2/71, 2/74, 2/76, 2/78, 2/80,
2/83, 2/85
3VA94 2/28, 2/30, 2/32, 2/34, 2/36, 2/38, 2/41, 2/43, 2/47, 2/49,
2/51, 2/53, 2/57, 2/65, 2/67, 2/69–2/71, 2/80
3VA95 2/38, 2/57, 2/79, 2/81, 2/83
3VA96 2/29, 2/31, 2/33, 2/35, 2/37, 2/39, 2/43, 2/49, 2/51, 2/53,
2/57, 2/59, 2/61, 2/67, 2/69, 2/76
3VA97 2/47, 2/53, 2/59, 2/61, 2/63, 2/67
3VA98 2/29, 2/31, 2/33, 2/35–2/37, 2/39, 2/43, 2/49–2/51, 2/63,
2/67, 2/69, 2/76, 2/79, 2/81, 2/83–2/85
3VA99 2/26–2/27, 2/30, 2/33, 2/36–2/38, 2/40, 2/71–2/72,
2/75–2/81
3VW90 1/38, 2/77

3W
3WA91 1/36, 1/40–1/41
3WL52 1/5, 1/10–1/11, 1/24
3WL53 1/24
3WL91 1/35–1/45
3WL93 1/35

7K
7KM93 2/75

8U
8UC94 2/34
8UD17 2/32–2/33
8UD19 2/32–2/35
8US12 2/84–2/85
8US13 2/85

A/6 Siemens LV 18 · 07/2022


© Siemens 2022
Index | Appendix

Index

Keyword Page Keyword Page


Operating mechanism, auxiliary release, auxiliary switch 1/15
0–9 Overcurrent protection according to network standards I/6
3VA5 molded case circuit breakers 2/8–2/11 Overview of the key US standards I/4–I/5
3VA51–3VA69 2/20–2/41, 2/48–2/85
3VA6 molded case circuit breakers 2/12–2/15 P
3VL up to 1600 A, according to UL 489 2/86–2/87 Plug-in and withdrawable technology 2/7–2/72
3WL5 1/16–1/45 Product approvals in control panel according to UL/NEC I/9

A Q
Accessories and spare parts 1/35–1/45 Quick selection guide 1/4–1/15, 2/6–2/19
Accessory options 1/24–1/33
Air Circuit Breakers 1/1–1/45 S
All the information you need 1/2–1/3, 2/2–2/3 Structure of the article numbers 1/20–1/23, 2/22–2/25
Appendix A/1–A/8 System overview 2/20
Applications I/8
Article number index A/6 T
The fast route to the product I/2–I/3
B Trip units 2/16
Brief code comparison of UL vs. IEC standards I/7

C
Circuit breakers and non-automatic circuit 1/4–1/9
Communication 2/73–2/77
Conditions of sale and delivery A/4–A/5
Connection 1/14
Connection technology 2/42–2/69
Cover frames and mounting 2/82–2/85

E
Electronic trip units ETU 1/12

G
Guide frames for AC 1/34

I
Index A/7
Internal accessories 2/26
Introduction I/2–I/9

L
Link directory A/2–A/3
Locking, blocking and interlocking 2/78–2/81

M
Manual operators 2/28–2/39
Molded Case Circuit Breakers 2/1–2/87 A
Molded case circuit breakers for all applications 2/4–2/5
Motor operators 2/40

N
Non-automatic circuit breakers for DC 1/10
Notes A/8

O
Online configurator highlights 1/18, 2/18

Siemens LV 18 · 07/2022 A/7


© Siemens 2022
Appendix | Notes

Notes

A/8 Siemens LV 18 · 07/2022


© Siemens 2022

Catalogs and further information

LV 10 ET D1
Low-Voltage Power Distribution and Switches and Socket Outlets
Electrical Installation Technology DELTA
SENTRON • SIVACON • ALPHA
Catalog
LV 10
Edition
04/2022

PDF
Protection, Switching, Measuring and
SENTRON • SIVACON • ALPHA

Low-Voltage Power
Distribution and Electrical DELTA
Installation Technology

Monitoring Devices, Switchboards and


Switches and Socket
Protection, Switching, Measuring and Monitoring
Devices, Switchboards and Distribution Systems Outlets
siemens.com/lowvoltage Catalog Version
ET D1 2018/19 siemens.com/delta

Distribution Systems
PDF (E86060-K8280-A101-B5-7600)

LV 18 Industry Mall
Air Circuit Breakers and Molded Case Information and Ordering Platform
Circuit Breakers with UL Certification on the Internet:
SENTRON
Catalog Edition
www.siemens.com/industrymall
PDF (E86060-K8280-E347-A9-7600)
LV 18 07/2022

SENTRON

Air Circuit Breakers and


Molded Case Circuit Breakers
with UL Certification
siemens.com/lowvoltage

IC 10 SITRAIN
© Siemens 2022

Industrial Controls Digital Industry Academy


SIRIUS
www.siemens.com/sitrain
PDF (E86060-K1010-A101-B3-7600)
SIRIUS

Industrial Controls
Catalog Edition
IC �� ���� siemens.com/sirius

Siemens TIA Selection Tool


for the selection, configuration and
ordering of TIA products and devices
www.siemens.com/tst

The catalogs listed above and additional catalogs are Further information on low-voltage power distribution
available in PDF format at Siemens Industry Online Support and electrical installation technology is available on the
www.siemens.com/lowvoltage/catalogs Internet at www.siemens.com/lowvoltage
© Siemens 2022

Get more information Security information


www.siemens.com/lowvoltage Siemens provides products and solutions with
industrial security functions that support the
secure operation of plants, systems, machines
Published by and networks.
Siemens AG
In order to protect plants, systems, machines and
networks against cyber threats, it is necessary to
Smart Infrastructure implement – and continuously maintain – a
Electrical Products holistic, state-of-the-art industrial security concept.
Siemensstraße 10 Siemens’ products and solutions constitute one
93055 Regensburg, Germany element of such a concept.
Customers are responsible for preventing unautho-
For the U.S. published by rized access to their plants, systems, machines and
Siemens Industry Inc. networks. Such systems, machines and compo-
nents should only be connected to an enterprise
100 Technology Drive network or the Internet if and to the extent such a
Alpharetta, GA 30005 connection is necessary and only when appropriate
United States security measures (e.g. firewalls and/or network
segmentation) are in place.
For additional information on industrial security
PDF (E86060-K8280-E347-A9-7600) measures that may be implemented, please visit
KG 0722 152 En https://www.siemens.com/industrialsecurity .
Produced in Germany
© Siemens 2022 Siemens’ products and solutions undergo contin­
uous development to make them more secure.
Siemens strongly recommends that product
updates are applied as soon as they are available
and that the latest product versions are used. Use
of product versions that are no longer supported,
and failure to apply the latest updates may increase
customer‘s exposure to cyber threats.
To stay informed about product updates, subscribe
to the Siemens Industrial Security RSS Feed under
https://www.siemens.com/cert .

Subject to changes and errors. The information


given in this document only contains general
descriptions and/or performance features which
may not always specifically reflect those described,
or which may undergo modification in the course
of further development of the products. The
requested performance features are binding only
when they are expressly agreed upon in the
concluded contract.
All product designations may be trademarks or
other rights of Siemens AG, its affiliated companies
or other companies whose use by third parties for
their own purposes could violate the rights of the
respective owner.