SSP Relay Setting

The document provides protection settings for various relays in an electrical substation. It includes settings for overcurrent, short circuit, earth fault and overload protection for feeders, transformers and motor control centers. The settings include pickup values, time multipliers and curve types for distance and time-overcurrent protection relays from manufacturers like L&T and Siemens. Connected loads and equipment ratings are also listed to provide context for the selected settings.

Uploaded by

AkashManusmare
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
146 views

SSP Relay Setting

The document provides protection settings for various relays in an electrical substation. It includes settings for overcurrent, short circuit, earth fault and overload protection for feeders, transformers and motor control centers. The settings include pickup values, time multipliers and curve types for distance and time-overcurrent protection relays from manufacturers like L&T and Siemens. Connected loads and equipment ratings are also listed to provide context for the selected settings.

Uploaded by

AkashManusmare
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

OC & EF RELAY TRIP TIME CALCULATOR

RELAY SETTING ###


###
Input Current Set (Is) = 2500.00 ###
Input TMS = 0.02 ###
Select Curve Type = IEC S Inverse ###
###
CHARACTERISTIC ###

K ###
Trip time t = Tx +L
( I / Is ) - 1
α ###
###

INJECTION CURRENT AND RESULTANT TIME

Input Current Injected (I) = 3315.00


Calculated Trip time = 0.495 Secs
MSETCL
CTR- 200:1
OC-
IDMT 200A TMS-0.075s 100%
DMT 1000A T=0.100 s 5Times
EARTH FAULT-
IDMT 260A TMS-0.075s 30%
DMT 1000A T=0.100 s 5Times
33 KV INCOMER PROTECTION Indorama

Function Configuration CT/ VT Configuration Current Setting

Ph OC Enable Ph Curr I/P 1A Ph OC


Volt Cont OC Disable Ph CT Ratio Pri 150A 51-1 Element Enable
Cold Load Disable Ph CT Ratio Sec 1A 51-1 Setting 150 A
Derived EF Enable Earth Curr I/P 1A 51-1 Char IEC-NI
Measured EF Disable Earth CT Ratio Pri 150A 51-1 TMS 0.050 s
Restricted EF Disable Earth CT Ratio Sec 1A 50-1 Element Enable
NPS OC Disable Ph Rotation ABC 50-1 Setting 750 A
Under Curr Disable Voltage Protection 50-1 Delay 0.050 s
Thermal Disable Ph U/O Voltage Derived EF
Line Check Disable 29/57-1 Element Enable 51N-1 Element Enable
Ph U/O Volt Enable 29/57-1 Operation Over 51N-1 Setting 30 A 20% of 150

U/O Freq Disable 29/57-1 Setting 126.5 V 115% of 110 V 51N-1 Char IEC-NI
Trip Ckt Supervision Enable 29/57-1 Delay 2s 51N-1 TMS 0.050 s
29/57-1 U/V Guarded Yes 50N-1 Element Enable
29/57-3 Element Enable 50N-1 Setting 433 A
29/57-3 Setting 77.0 V 85% of 110 V 50N-1 Delay 0.050 s
29/57-3 Delay 2s
29/57-3 U/V Guarded Yes
Transformer feeder Protection 1,2 & 3
Function Configuration CT/ VT Configuration TRAFO RELAY- 1, OC & EF TRAFO REALY- 2,STANDBY EARTH FAULT
Ph OC Enable Ph Curr I/P 1A Curr Protection Measured EF
Volt Cont OC Disable Ph CT Ratio Pri 75A Ph OC 51G-1 Element
Cold Load Disable Ph CT Ratio Sec 1.00A 51-1 Element Enable 51G-1 Setting 400 A
Derived EF Enable Earth Curr I/P 1A 51-1 Setting 58 A 51G-1 Char IEC-NI
Measured EF Disable Earth CT Ratio Pri 2000A 51-1 Char IEC-NI 51G-1 TMS 0.050 s
Restricted EF Disable Earth CT Ratio Sec 1.00A 51-1 TMS 0.050 s 50G-1 Element Enable
NPS OC Disable Ph Rotation ABC 50-1 Element Enable 50G-1 Setting 5.7 KA
Under Curr Disable TRAFO PRI AMP 43.73 50-1 Setting 750 A 50G-1 Delay 0s
Thermal Disable 50-1 Delay 0s
Line Check Disable Derived EF
Ph U/O Volt Enable 51N-1 Element Enable
U/O Freq Disable 51N-1 Setting 15 A 15% of 58
HT AMP- 58A
Trip Ckt Supervision Enable 51N-1 Char IEC-NI LT AMP- 4450A
51N-1 TMS 0.050 s TRAFO RATED-3333 A
50N-1 Element Enable 1.3 TIMES OVERLOAD On HT SIDE
50N-1 Setting 167 A
50N-1 Delay 0s
Restricted EF
64H Element DISABLE
64H Setting
64H Delay
LT TRAFO INCOMER PROTECTION
Feeder Protection Type L&T Release Siemens Relay
Overload 4000 A T-0.500 S 4000A TMS-0.200 S
Trafo 1,2&3 Short Circuit 32000 A TMS- 0.020 S (I2T ON) 30000 A TMS-0.075 S
(Short Ckt-44 KA) Earth Fault 800 A TMS- 0.100 S (I2T OFF) 400 A TMS-0.050 S 10 % OF 4000
Instanteneous 40000A T-0 S 40000 A T-0 S
Overload 800 A TMS- 0.500 S HT AMP- 52A
Short Circuit 4800 A TMS- 0.020 S (I2T ON) LT AMP- 4000A
MCC-1 315 KW CONNECTED LOAD
Earth Fault 160 A TMS- 0.100 S (I2T OFF) TRAFO RATED-3333 A
Instanteneous 4800 A T-0 S 1.2 TIMES OVERLOAD On LT Side
Overload 800 A TMS- 0.500 S

Short Circuit 4000 A TMS- 0.020 S (I2T ON) FOR L&T RELEASE EARTH FAULT MIN SETTING IS 0.2 XIn
MCC-2 315 KW CONNECTED LOAD
Earth Fault 160 A TMS- 0.100 S (I2T OFF)

Instanteneous 4800 A T-0 S


Overload 1600 A TMS- 0.500 S

MCC-3 (Short Short Circuit 8000 A TMS- 0.020 S (I2T ON)


720 KW CONNECTED LOAD
Ckt-26 KA) Earth Fault 320 A TMS- 0.100 S (I2T OFF)

Instanteneous 9600 A T-0 S


Overload 800 A TMS- 0.500 S

Short Circuit 4000 A TMS- 0.020 S (I2T ON)


MCC-4 193 KW CONNECTED LOAD
Earth Fault 160 A TMS- 0.100 S (I2T OFF)

Instanteneous 4800 A T-0 S


Overload 1600 A TMS- 0.500 S

Short Circuit 8000 A TMS- 0.020 S (I2T ON)


MCC-5 560 KW CONNECTED LOAD
Earth Fault 320 A TMS- 0.100 S (I2T OFF)

Instanteneous 9600 A T-0 S


Overload 800 A TMS- 0.500 S

Short Circuit 4000 A TMS- 0.020 S (I2T ON)


HCC 375 KW CONNECTED LOAD
Earth Fault 160 A TMS- 0.100 S (I2T OFF)

Instanteneous 4800 A T-0 S


Overload 2500 A TMS- 0.500 S

MCC-7 (UTILITY) Short Circuit 12500 A TMS- 0.100 S (I2T ON)


845 KW CONNECTED LOAD (APPROX)
(Short Ckt-24 KA) Earth Fault 500 A TMS- 0.100 S (I2T OFF)

Instanteneous 15000 A T-0 S


Overload 2500 A TMS- 0.500 S

Short Circuit 12500 A TMS- 0.100 S (I2T ON)


MCC-8 (UTILITY) 595KW CONNECTED LOAD (APPROX)
Earth Fault 500 A TMS- 0.100 S (I2T OFF)

Instanteneous 15000 A T-0 S