Replacing The Fermator VVVF4 With The VVVF5 Plus

The VVF5+ controller is compatible with the VVVF4 motor with some connections requiring modification. The VVVF4 encoder must connect to the ASYNC plug on the VVF5+. The raised edges on the VF motor cable plug prevent it from connecting to the VVF5+, so those edges must be cut off to allow the plug to slide in. Adding a bridge from pin 7 to ground on the car top junction board can fix issues with light rays not working correctly after replacing the VVVF4 drive unit with a VVF5+.

Uploaded by

Don Luong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views2 pages

Replacing The Fermator VVVF4 With The VVVF5 Plus

The VVF5+ controller is compatible with the VVVF4 motor with some connections requiring modification. The VVVF4 encoder must connect to the ASYNC plug on the VVF5+. The raised edges on the VF motor cable plug prevent it from connecting to the VVF5+, so those edges must be cut off to allow the plug to slide in. Adding a bridge from pin 7 to ground on the car top junction board can fix issues with light rays not working correctly after replacing the VVVF4 drive unit with a VVF5+.

Uploaded by

Don Luong
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Fermator VVF5+ connection with existing VVVF4 Motor - Schindler

Fermator VVF5+ Light Ray Faults - Schindler


01/ 2021
If you are installing a new VVF5+ PCB control board with an old VVVF4 motor, please refer to
the information below. Thanks to Peter Atkinson (WA) for this information

1. Encoder Connection.

• The VVF5+ controller is fully compatible with the VVVF4 controller, so it is possible
to replace a VVVF4 with a VVF5+, but not the other way.

• The VVVF4 encoder (existing 4 wires) has to be connected to the plug marked
ASYNC.

This document contains sensitive and proprietary confidential information which is the property of Otis Elevator
Company Pty Ltd. It may not be disclosed to any third party without the consent in writing of the Director, Field
Operations-Service. Otis reserves all its legal rights in the event of any unauthorized disclosure.
Page 1 of 2
2. Motor Connection.

Due to VF motor cable plug having raised edges, it cannot be plugged in to the new VVF5+
controller.
So, it is necessary to cut the raised plastic (circled section in the following picture) at the left
side of the plug so you can slide the plug in.

3. Motor Connection.

4. VVF5+ Light Ray Fault – Schindler 3300/5300

In some cases, after replacement of the Fermator Door Drive unit VVVF4 with the VVF5+ there
are some situations where the Light Rays will not correctly.
Problems range from door reversals after several trips to permanent blocking of the light rays.
A fix is to add a bridge from 0 volt to ground on the car top junction board - The bridge can be
placed from plug SKC pin 7 to ground.