Flow Totalizer Manual 96
Flow Totalizer Manual 96
: Up key, move the cursor upward, and increase the value in setup menu.
: Down key, move the cursor downward, and reduce the value in setup menu.
: Left key, move the cursor leftward, and Shift the flashing digit position to left in setup menu.
: Right key, move the cursor rightward, and Shift the flashing digit position to right in setup menu.
Prompt line
1
1.1.2 Display Screen
2
1.3 Query and Export
1.3.1 Query Submenu
In main menu, press Up or Down key to select Query submenu, and then press MENU key to enter.
In Query submenu, there are records of Daily, Monthly, Year, Log read;Export date and year records and log records.
Press Up or Down key to select the inquiry record and Export records, and then press MENU key to Submenu.
1.3.2 Day Record
Press Up or Down key to select Day Record, and then press MENU key to enter, shown as below.
3.Year record 20.325 Unit with the flow total unit Down key to select the needed day.
4.log record
1.Day record Month record: Year/Month: Press Right or Left key to select
year or month, and press Up or Down key to
2.Month record 2017-12 Month consumption,
select the needed month.
3.Year record 11.325 Unit with the flow total unit
4.log record
4.log record 3
1.3.5 Log record
Press Up or Down key to select log record, and then press MENU key to enter, shown as below.
The date and time
1.Day record of meter reading
Log data:000001 Number of log records: Press Up
2.Month record Flow totalizer Time:02/12/2017 14:02:12
or Down to select the number of
The export data format is “. Csv”, There are three export documents, there are days, months, years. And the
data can be opened in the computer EXCEL software. The data is shown in the following diagram. As shown
below.
The export data format is “. Csv”, And the data can be opened in the computer EXCEL software. The data is
shown in the following diagram. As shown below.
5
1.5 Input setup
This submenu affects the performance and accuracy of instrument, please be careful when operating. Set the flow signal
parameters, temperature parameters, pressure parameters. In main menu, press Up or Down key to select Setup submenu, and
then press MENU key to enter.
1.Query and exp. Setup Password 1.Flow signals Note: The input setup submenu has password
2.Com set 2.Tempe signals protection. When inputting password, press Left key
3.Input setup 0***** 3.Press signals to shift the cursor, and press Up or Down key to
4.Output setup increase or decrease the number. The default
password is 000000, users can modify the password
according to 1.10 Password.
1.Flow signals
2.Tempe.signals
3.Press.signals
Medium select:
Liquid(volume)
6
1.5.1.2 Liquid (Volume)
In medium menu, then press Up key to select Liquid (Volume).
Press MENU key to shift cursor on density value, and then press Medium select: Coe.V-expansion
Up/Down key to change this value. Liquid (Volume) :
After set Density (20℃), press Left key to shift cursor on 0.000000
Density (20℃), press Up key to change Density (20℃) to Density(20℃):
Coe.V-expansion (Expansibility factor), press Right key to shift cursor on 1000.0000 kg/m3
factor value, and then press Up/Down key to change this value.
1.5.1.3 Liquid (Mass)
In medium menu, then press Up key to select Liquid (Mass). Medium select: Coe.V-expansion:
Press MENU key to shift cursor on density value, and then press Up/Down Liquid(mass) 0.000000
key to change this value. Density(20℃):
After set Density (20℃), press Left key to shift cursor 1000.0000 kg/m3
on Density (20℃), press Up key to change20℃ density to
Coe.V-expansion (Expansibility factor), press Right key to shift
cursor on factor value, and then press Up/Down key to change this value.
1.5.1.4 Density Compensation
In medium menu, press Left key to shift cursor on Constant density, Medium select: Constant density:
Press MENU key to shift cursor on density value, and then press Constant density 1000.0000kg/m3
Up/Down key to change this value.
1.5.1.5 Vapor (Auto)
In medium menu, Press Up key to select Vapor (Auto), press Right key to shift cursor to option content, Press MENU to enter the
temperature and pressure compensation priority selection,and then press Down key to select pressure priority or temperature
priority.
Pres. priority: Include high temperature condensate water, pressure
Medium: Vapor auto opt: compensation priority.
Vapor (Auto) Temp.priority Temp. priority: Only measure dry saturated vapor, temperature
compensation priority.
8
1.5.2 Flowmeter type:
After set the media, press the MENU button to enter the flow sensor input type submenu. Press to up key switch the sensor type
during set.
This submenu affects the performance and accuracy of instrument, please be careful when operating.
In main menu, press Up or Down key to select Setup submenu, and then press menu key to enter.
1.Query and exp. Setup Password 1.Flow signals Medium select: Flowmeter type:
2.Com set 2.Tempe.signals Saturated stm. T Veloc. /PD
3.Input setup 0***** 3.Press.signals
4.Output setup
Before set, please confirm the meter type. The meter types are shown as below.
1. Veloc. /PD: Velocity/Volume 4. Orifice DP: Orifice plate DP 7. Elbow DP
2. Mass Flow 5. V cone DP 8. Linear: Linear current
3. DP scale: DP flow 6. Annubar DP 9.K Coe DP
9
1.5.2.1 Veloc. /PD
The meter type “Veloc. /PD” includes Volumetric flowmeters and Velocity type flow meters, shown as below.
Veloc. /PD
After set meter type, Press the MENU button to switch to the signal selection submenu. There are two parameters in Veloc. /PD:
Pulse (Volume), 4-20mA (Volume).
When choosing different signal type, the related parameters will vary, shown as below.
Pulse 4-20mA
1. Signal type 3. Coefficient linearity 1. Signal type 3. Flow unit
2. Cut-off frequency 4. Flow coefficient 2. Flow scale 4. Cut-off current
10
1.5.2.1.1 Pulse
In input setup, press Up or Down key to select flow signals submenu, press MENU key to Flowmeter type Submenu .and then
press Up/Down key to select “Veloc. /PD”.
In the signal type menu, press the up key to select the signal type (Pulse), After set the flow type, press the MENU key to switch
the options once to set the flow coefficient, cut off the frequency, frequency segmentation correction.
If you do not choose coefficient correction, just set FLOW K. When set, press the right button to set the cursor position, up and
down keys to change the value.
After the Flow k set is completed, press the MENU key to set the Cut-off fieq. value. (Cut-off pulse is set according to different
flowmeters on site)
After set Cut-off frequency, press Left key to shift cursor on Cut-off freq., and then press Up key to change Cut-off freq. to
Coefficient linearize (Coefficient linearize is used for linearity correction, default setup is “OFF”).
Cut-off fieq.: Flow coe.: Sect 0 Note: Note: If coefficient linearity is set ON, Press the MENU button
0000 Hz Freq:0000 to enter the correction factor menu, press the right key to set the
Coef. line.: ON Coe.:000000.0000 cursor position, the up and down keys to change the value.After
set, press ENTER key to enter next menu.
Flow coefficient:
When set flow coefficient, it can set by section, the number of section is 0-9.
Freq: Frequency of section, the input range is 0-9999.
Coe: Flow coefficient corresponding to different section. After calibration, input the frequency of section and flow coefficient from
section 0 to section 9. Note: If the ten sections are not all in use, for example, there are five sections in use (Section 0 to section
4), set section of frequency 5000 and flow coefficient of section 4 in section 5.
11
1.5.2.1.2 4-20Ma
In input setup, press Up or Down key to select flow signals submenu, press menu key to Flowmeter type Submenu ,and then
press Up/Down key to select “Veloc. /PD”.
In the signal type menu, press the up key to select the signal type (4-20mA), After set the flow type, press the MENU key to
switch the options once, set the flow range, cut off the current.
When set Flow scale, press the right button to set the cursor position, up and down keys to change the value (The Flow full scale
should be the same as that of flowmeters).
After the range set is completed, press the MENU key to set the cut-off current value. (Cut-off current is set according to different
flowmeters on site)
There are two parameters in Mass Flow: Pulse (Mass), 4-20mA (Mass).
The setup method of mass flow is the same as that of Veloc. /PD.
12
1.5.2.3 DP Flow
In input setup, press Up or Down key to select flow signals submenu, press menu key to Flowmeter type Submenu ,and then
press Up/Down key to select “DP Scale”.
1.Query and exp. Setup Password 1.Flow signals Medium select: Flowmeter type:
2.Com set 0***** 2.Tempe.signals Saturated stm. T DP scale
3.Press.signals
3.Input setup
4.Output setup
Sign type: Note: Orifice plate, V-Cone, Annubar, venture tube and
4-20mA no sqrt Elbow are all belong to differential pressure flowmeter,
and the output signal is scale mass flow.
After the flowmeter type is set, press the MENU key to switch to the signal type submenu. There are two signal types: 4-20mA No
sqrt, 4-20mA sqrt. In this manual, it only introduces 4-20mA No sqrt, the others refer to 4-20mA No sqrt. Press Up key to select
different signal types.
4-20mA No sqrt: means that the output signal of differential pressure transmitter is no square root signal, this kind
signal should be extracted the square root and then can take part in computation.
4-20mA Sqrt: means that the output signal of differential pressure transmitter is linear signal, this kind signal does not
need to be extracted the square root.
After set signal type, Press MENU to switch to the scale flow range and
unit set submenu, Press the right button to move the cursor position, the up DP flow:
00000000.000
and down keys to modify the value. (The range of DP flow is 0-9999999.999) ,
Flow unit: t/h
Press Right key to shift cursor on unit t/h, and then press Up key to select
different units (t/h and Kg/h).
13
After the scale flow set is completed, press the MENU key to enter the Design Design density:
density submenu. Press the right button to move the cursor position, the up and 0000.0000 kg/m3
down keys to modify the value.
Flow coe.:
After the Design density set is completed, press the MENU key to enter
the Flow Coefficient submenu. Press the right button to move the cursor 0000.0000
position, the up and down keys to modify the value. (This parameter need not be set)
After the Flow Coefficient set is completed, press the MENU key to enter the DP scale submenu. Press the right button to move
the cursor position, the up and down keys to modify the value. Press the right button to move the cursor to DP unit (Differential
pressure unit), and then press Up/Down key to select different units (Pa, KPa and MPa).
Cut-off current:
4.0030 mA
After set the differential pressure range, press the menu button to enter the Cut-off current sub-menu. Press the right button to
move the cursor position, the up and down keys to modify the value. Cut-off current is set according to different flowmeters on site.
Generally, do not need to set this parameter.).
14
1.5.2.4 Orifice DP
In input setup, press Up or Down key to select flow signals submenu, press menu key to Flowmeter type Submenu ,and then
press Up/Down key to select “Orifice DP”.
1.Query and exp. Setup Password 1.Flow signals Medium select: Flowmeter type:
2.Com set 0***** 2.Tempe.signals Saturated stm. T Orifice DP
3.Input setup 3.Press.signals
4.Output setup
There are nine parameters in Orifice DP: Signal type, Pipe diameter, Hole diameter, Expansibility, Flow Coefficient, DP unit, DP
low scale, DP high scale and Cut-off current.
After the flowmeter type is set, press the MENU key to switch to the signal type submenu. Sign type:
There are two signal types: 4-20mA No sqrt, 4-20mA sqrt. In this manual, it 4-20mA no sqrt
only introduces 4-20mA No sqrt, the others refer to 4-20mA No sqrt. Press Up
key to select different signal types.
After set Signal type, press menu key to Pipe Diameter Submenu, Pipe diameter:
press Right key to shift cursor on Cursor position, and then 0000.0000 mm
press Up/Down key to change this value.
After set Pipe Diameter, press menu key to Hole Diameter Submenu, Hole diameter:
press Right key to shift cursor on Cursor position, and then press Up/Down 0000.0000 mm
key to change this value.
15
Expansibility:
After set Hole diameter, press menu key to Expansibility Submenu,
0.00000
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
Flow coe.:
After set Expansibility, press menu key to Flow coe. Submenu, 0000.0000
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
After the Flow Coefficient set is completed, press the MENU key to enter the DP scale submenu. Press the right button to move
the cursor position, the up and down keys to modify the value. Press the right button to move the cursor to DP unit (Differential
pressure unit), and then press Up/Down key to select different units (Pa, KPa and MPa).
Cut-off current:
4.0030 mA
After set the differential pressure range, press the menu button to enter the Cut-off current sub-menu. Press the right button to
move the cursor position, the up and down keys to modify the value. Cut-off current is set according to different flowmeters on site.
Generally, do not need to set this parameter.).
16
1.5.2.5 V-Cone DP
In input setup, press Up or Down key to select flow signals submenu, press menu key to Flowmeter type Submenu ,and then
press Up/Down key to select “V-Cone DP”.
1.Query and exp. Setup Password 1.Flow signals Medium select: Flowmeter type:
2.Com set 0***** 2.Tempe.signals Saturated stm. T V-Cone DP
3.Input setup 3.Press.signals
4.Output setup
There are nine parameters in V-Cone DP: Signal type, Pipe diameter, Cone diameter, Expansibility f, Flow Coefficient, DP unit,
DP low scale, DP high scale and Cut-off current.
After the flowmeter type is set, press the MENU key to switch to the signal type submenu. Sign type:
There are two signal types: 4-20mA No sqrt, 4-20mA sqrt. In this manual, it 4-20mA no sqrt
only introduces 4-20mA No sqrt, the others refer to 4-20mA No sqrt. Press Up
key to select different signal types.
Pipe diameter:
After set Signal type, press menu key to Pipe Diameter Submenu, 0000.0000 mm
press Right key to shift cursor on Cursor position, and then
press Up/Down key to change this value.
Cone diameter:
After set Pipe Diameter, press menu key to Cone Diameter Submenu, 0000.0000 mm
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
17
Expansibility:
After set Cone Diameter, press menu key to Expansibility Submenu
0.00000
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
Flow coe.:
After set Expansibility, press menu key to Flow coe. Submenu, 0000.0000
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
After the Flow Coefficient set is completed, press the MENU key to enter the DP scale submenu. Press the right button to move
the cursor position, the up and down keys to modify the value. Press the right button to move the cursor to DP unit (Differential
pressure unit), and then press Up/Down key to select different units (Pa, KPa and MPa).
Cut-off current:
4.0030 mA
After set the differential pressure range, press the menu button to enter the Cut-off current sub-menu. Press the right button to
move the cursor position, the up and down keys to modify the value. Cut-off current is set according to different flowmeters on site.
Generally, do not need to set this parameter.).
18
1.5.2.6 Annubar DP
In input setup, press Up or Down key to select flow signals submenu, press menu key to Flowmeter type Submenu ,and then
press Up/Down key to select “Annubar DP”.
After the flowmeter type is set, press the MENU key to switch to the signal type submenu. Sign type:
There are two signal types: 4-20mA No sqrt, 4-20mA sqrt. In this manual, it 4-20mA no sqrt
only introduces 4-20mA No sqrt, the others refer to 4-20mA No sqrt. Press Up
key to select different signal types.
Pipe diameter:
After set Signal type, press menu key to Pipe Diameter Submenu, 0000.0000 mm
press Right key to shift cursor on Cursor position, and then
press Up/Down key to change this value.
After set Pipe Diameter, press menu key to Drag Coefficient Submenu, Drag coe.:
press Right key to shift cursor on Cursor position, and then press Up/Down 0000.0000 mm
key to change this value.
19
Expansibility:
After set Drag Coefficient, press menu key to Expansibility Submenu
0.00000
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
Flow coe.:
After set Expansibility, press menu key to Flow coe. Submenu, 0000.0000
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
After the Flow Coefficient set is completed, press the MENU key to enter the DP scale submenu. Press the right button to move
the cursor position, the up and down keys to modify the value. Press the right button to move the cursor to DP unit (Differential
pressure unit), and then press Up/Down key to select different units (Pa, KPa and MPa).
Cut-off current:
4.0030 mA
After set the differential pressure range, press the menu button to enter the Cut-off current sub-menu. Press the right button to
move the cursor position, the up and down keys to modify the value. Cut-off current is set according to different flowmeters on site.
Generally, do not need to set this parameter.).
20
1.5.2.7 Elbow DP
In input setup, press Up or Down key to select flow signals submenu, press menu key to Flowmeter type Submenu ,and then
press Up/Down key to select “Elbow DP”.
After the flowmeter type is set, press the MENU key to switch to the signal type submenu. Sign type:
There are two signal types: 4-20mA No sqrt, 4-20mA sqrt. In this manual, it 4-20mA no sqrt
only introduces 4-20mA No sqrt, the others refer to 4-20mA No sqrt. Press Up
key to select different signal types.
Pipe diameter:
After set Signal type, press menu key to Pipe Diameter Submenu,
0000.0000 mm
press Right key to shift cursor on Cursor position, and then
press Up/Down key to change this value.
After set Pipe Diameter, press menu key to Bend Radius Submenu,
press Right key to shift cursor on Cursor position, and then press Up/Down Bend radius:
key to change this value. 000.00000
21
Expansibility:
After set Bend Radius, press menu key to Expansibility Submenu
0.00000
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
Flow coe.:
After set Expansibility, press menu key to Flow coe. Submenu, 0000.0000
press Right key to shift cursor on Cursor position, and then press Up/Down
key to change this value.
After the Flow Coefficient set is completed, press the MENU key to enter the DP scale submenu. Press the right button to move
the cursor position, the up and down keys to modify the value. Press the right button to move the cursor to DP unit (Differential
pressure unit), and then press Up/Down key to select different units (Pa, KPa and MPa).
Cut-off current:
4.0030 mA
After set the differential pressure range, press the menu button to enter the Cut-off current sub-menu. Press the right button to
move the cursor position, the up and down keys to modify the value. Cut-off current is set according to different flowmeters on site.
Generally, do not need to set this parameter.).
22
1.5.2.8 Linear current
In input setup, press Up or Down key to select flow signals submenu, press menu key to Flowmeter type Submenu ,and then
press Up/Down key to select “Linear current”.
After the flowmeter type is set, Press the menu button to enter the current and the corresponding range set.
Linear I: Sect 0
I: 00.0000 mA
Flow:00000000.000
Flow unit: m3/h
Linear current:
Set the segment current and the corresponding range, can be set in segments, section number is 0-9.
I: Segment current value, input range 00.0000-99.9999.
Flow: The flow value corresponding to different current segments. Input range 0000000.000-9999999.999. Press the right button
to set the cursor position, up and down keys to change the value. Set the unit according to the display unit
23
1.5.2.9 Damping and log interval
After set all the flow signals, press the MENU button to enter the Damping Time and Log interval Time sets submenu.
Damping: 00 sec
Log interval:
00:00:05
Press Right key to shift cursor, and press Up/Down key to change time value, damping time range is 0-30s.
Log record preservation interval, Hours / minutes / seconds. set parameters press Right key to shift cursor, and then press
Up/Down key to set the values.
Press the right button to move the cursor, press the up / down button to change the flow cut-off value, the set range is
0-99999.999, the unit is the same as the display unit. Low Flow Cutoff is set according to different flowmeters on site. Generally,
do not need to set this parameter.
Press the right button to move the cursor, press the up / down button to change the flow cut-off value,
24
1.5.2.12 Temperature signals
This submenu affects the performance and accuracy of instrument, please be careful when operating. Set the flow signal
parameters, temperature parameters, pressure parameters. In main menu, press Up or Down key to select temperature signals
submenu, and then press ENTER key to enter. In input setup, press Up or Down key to select Temperature signals submenu,
then press the menu button to enter.
There are five temperature sensor types: Pt100, Pt1000,4-20mA, 0-10mA, setup (set temperature).
T scale:
When the T sensor is selected 4-2mA or 0-10mA signal, it needs to corresponding temperature range. 4mA:+0000.00 ℃
Press the menu key to enter the upper and lower 20mA:+0000.00℃
temperature limit sets, set parameters press Right key to shift cursor, and then press
Up/Down key to set the values.
T zero:
After set the temperature sensor and range, press the MENU key to enter the +00.000 ℃
temperature zero set, set parameters press Right key to shift cursor, and
then press Up/Down key to set the values.
After set the zero temperature, press the MENU key to enter the upper and T Upper/lower:
lower temperature limit set submenu, If the temperature is out of the range, Lower:-0050.00℃
Upper:+0050.00℃
it will set temperature to compensate.
25
1.5.2.13 Pressure signals
This submenu affects the performance and accuracy of instrument, please be careful when operating. Set the flow signal
parameters, temperature parameters, pressure parameters. In main menu, press Up or Down key to select pressure signals
submenu, and then press menu key to enter. In input setup, press Up or Down key to select Pressure signals submenu, then
press the menu button to enter.
P Upper/lower (kP
After set the pressure zero, press the MENU key to enter the upper and
Lower: +00000.00
lower pressure limit set submenu, If the pressure is out of the range, Upper: +02000.00
it will use set pressure to compensate.
26
1.6 Output setup
In the main menu, press the up or down arrow key to select the output set menu, then press the MENU key to enter.
In the "Output sets" submenu, there are current output, frequency output, alarm output. Press Up or Down to select Set Output
Type and press the Menu key to enter the submenu.
After entering the current output menu, right-click to move the cursor to the output variable type. There are 7 output variables:
Flow rate, Temperature, Gauge pressure, DP, Differential pressure, KPa, Thermal enthalpy KJ / kg), Power (MJ / h), press the up
key to switch the output variable type. Then press the MENU button to enter the variable output range upper and lower limits, set
parameters press Right key to shift cursor, and then press Up/Down key to set the values.
27
1.6.2 Frequency output
In the output setup menu, press the up and down keys to move the cursor to the frequency output, then press the menu key to
enter the frequency output channel sets.
28
1.6.3 alarm output
In the output setup menu, press the up and down keys to move the cursor to the alarm output, then press the menu key to enter
the alarm output, channel sets. (Noted: Normally the alarm channel defaults to only one channel)
Alarm: Quantity
Value: m3
00000001.000
29
1.7 Total reset
In the main menu, press the up or down arrow key to select the Total reset menu, then press the MENU key to enter.
2.Com set Reset passwd: Total reset: Note: The Total reset submenu has password
3.Input setup 0***** 00000000.000 m3 protection. When inputting password, press Left key
4.Output setup to shift the cursor, and press Up or Down key to
5.Total reset increase or decrease the number. The default
password is 000000, users can modify the password
1.7.1 Total reset according to 1.10 Password.
Enter the password to enter the total clear menu, by modifying the value of zero and modify the cumulative flow.
set parameters press Right key to shift cursor, and then press Up/Down key to set the values.
1.7.2 Log reset
Log reset: No
After the accumulated flow rate clear set is completed, press the MENU key to enter the log record clear.
When clearing the log, press the up key to change "ON" to "yes", then press the MENU key, the log record will be cleared
completely, and the meter will save the log record again.
30
1.8 Calibration
This submenu is used to calibrate the internal analog signal, and it affects the accuracy of instrument. If there are no resistance
box, standard current source, multimeter and other calibration equipment’s, please do not use this submenu!
In main menu, press Up or Down key to select Calibrate submenu, and then press MENU key to enter.
Note: The Total reset submenu has password
protection. When inputting password, press Left key
3.Input setup Calib passwd: 1.I output cali. to shift the cursor, and press Up or Down key to
4.Output setup 0***** 2.I input calib.
increase or decrease the number. The default
5.Total reset 3.Temper. calib.
6.Calibration password is 000000, users can modify the password
according to 1.10 Password.
The meter adopts two-point calibration. When calibrating, the meter prompts 4mA, then the output current is about 4mA. Input the
value of the multimeter into the meter, then press the MENU key to enter the next point. At this moment, it indicates 20mA, then
the output current is about 20mA. Multimeter to detect the value entered into the meter, and then press the menu button, the
meter prompts to modify successfully. And then return to calibrate submenu. set parameters press Right key to shift cursor, and
then press Up/Down key to set the values.
31
1.8.2 Current input calibrate
In calibrate submenu, press Up or Down key to select Current Input, and then press MENU key to enter. When calibrating, it
needs standard current source to input current to instrument according to “Input” prompt. For example, of calibrating Flow Current,
select Flow Current, and press MENU key to calibrate. Input 4mA for zero-scale, the instrument will display a measuring value
mea. I approximating 4mA, and then press MENU key to enter full-scale. Input 20mA for full-scale, the instrument will display a
mea. I approximating 20mA, and then press MENU key to finish calibration. After calibration, the instrument will display
“Successful”, and then return to calibrate submenu.
1.I output cali. 1.Flow current I input: I input: I input:
2.I input calib. 2.Temp. current Std. I:04.0000mA Std. I:20.0000mA Std. I:20.0000mA
3.Temper. calib. 3.Pres. current Mea.I:03.9790mA Mea.I:20.0100mA Mea.I:20.0100mA
Successful!
The calibration method of temperature and pressure is the same as that of Flow current.
1.I output cali. Calib. Temp.: L Calib. Temp.: H Calib. Temp.: H Calib. Temp.: H
2.I input calib. Std. v: Std. v: Std. v: Std. v:
3.Temper. calib. +0000.0℃ +0000.0℃ +0400.0℃ +0400.0℃
Mea.v:+0000.0℃ Mea.v:+0001.2℃ Mea.v:+0397.3℃ Mea.v:+0397.3℃
Successful!
After calibration, the instrument will display “Successful”, and then return to calibrate submenu. set parameters press Right key to
shift cursor, and then press Up/Down key to set the values.
32
1.9 Display unit
In the main menu, press the up or down arrow key to select the output set menu, then press the MENU key to enter.
In the "Display unit" submenu, there are display unit and display param. Press Up or Down to select Set Output Type and press
the Menu key to enter the submenu. 4.Output setup 1.Display unit
5.Total reset 2.Display Parma
6.Calibration
7.Display unit
In calibrate submenu, press Up or Down key to select Display unit, and then press MENU key to enter.
Set parameters Press the right button to move the cursor, and then press the up button to switch units.
33
1.10 Password
In the main menu, press the up or down arrow key to select the Password menu, then press the MENU key to enter.
5.Total reset 1.Input Ch. pwd 1.Input ch. pwd 1.Input ch. pwd
6.Calibration 2.Para. rst pwd Old pwd: 0***** Old pwd: ******
7.Display unit 3.Cali. Ch. pwd New pwd: ****** New pwd: *****1
8.Password Successful!
Press Right key to shift cursor on Input channel, press MENU key to enter setup password menu, input old and new passwords,
and then press MENU key, it will display “Successful!”. set parameters press Right key to shift cursor, and then press Up/Down
key to set the values.
The setup method of calibrate and total reset password is the same as that of Input channel password.
34
Part 2 Wirings
2.1 Wiring Terminals 2.2 Terminals Definition
No. Definition N Definition
o.
1 Current output + 14 Public GND
10 Pt100, B 23 GND
35