0% found this document useful (0 votes)
299 views24 pages

Triton Martinique

This document provides installation and operating instructions for a Martinique electric shower. It includes important safety information, specifications for the shower, and details on electrical and plumbing connections, commissioning, operation, and maintenance. Installers should leave these instructions with the user.

Uploaded by

dani datoad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
299 views24 pages

Triton Martinique

This document provides installation and operating instructions for a Martinique electric shower. It includes important safety information, specifications for the shower, and details on electrical and plumbing connections, commissioning, operation, and maintenance. Installers should leave these instructions with the user.

Uploaded by

dani datoad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Martinique

electric shower

Installation and
operating
instructions

INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER

2180381J - November 2011


Martinique electric shower

CONTENTS Page

Important safety information........................................................... 1


Introduction.................................................................................... 2
Specifications................................................................................... 2
Advice to users................................................................................ 2
Main components........................................................................... 3
Electrical requirements..................................................................... 4
Water requirements......................................................................... 6
Siting of the shower........................................................................ 7
Fitting the shower to the wall.......................................................... 8
Plumbing connections.................................................................... 10
Electrical connections..................................................................... 11
Commissioning............................................................................... 12
Replacing the cover........................................................................ 14
Operating the shower.................................................................... 15
Operating functions........................................................................ 17
Instructions for installers and service engineers only....................... 18
Spare parts..................................................................................... 19
Fault finding................................................................................20 - 21
Guarantee, service policy, etc....................................................rear cover

To check the product suitability for commercial and multiple installations, please contact Triton’s
specification advisory service before installation.
Telephone: 0844 980 0730
Facsimile: 0844 980 0744
E mail: [email protected]
Martinique electric shower

PLEASE READ THIS IMPORTANT SAFETY INFORMATION


Products manufactured by Triton are safe and without risk provided they are installed, used and
maintained in good working order in accordance with our instructions and recommendations.
WARNING: DO NOT operate shower if frozen, or suspected of being frozen. It must thaw out
before using.
DO NOT operate the unit if the showerhead or spray hose becomes damaged.
DO NOT restrict flow out of shower by placing showerhead in direct contact with your body.
DO NOT operate the shower if water ceases to flow during use or if water has entered inside
the unit because of an incorrectly fitted cover.
WARNING: If restarting the shower immediately after stopping, be aware that a slug of
hot water will be expelled for the first few seconds.

1 GENERAL 2.2 The supply pipe must be flushed to clear debris


1.1 Isolate the electrical and water supplies before before connecting to the shower unit.
removing the cover. 2.3 DO NOT solder pipes or fittings within 300mm
1.2 Read all of these instructions and retain them of the shower unit, as heat can transfer along
for later use. the pipework and damage components.
1.3 DO NOT take risks with plumbing or electrical 2.4 DO NOT fit any form of outlet flow control as
equipment. the outlet acts as a vent for the heater can.
1.4 Isolate electrical and water supplies before 2.5 DO NOT use excessive force when making
proceeding with the installation. connections to the flexible hose or
1.5 The unit must be mounted onto the finished showerhead, finger tight is sufficient.
wall surface (on top of the tiles). DO NOT tile 2.6 All plumbing connections must be completed
up to or seal around ANY PART of the unit before making the electrical connections.
using silicone sealer after fixing to the wall.
Special care must be taken NOT TO BLOCK 3 ELECTRICAL
OR SEAL ANY PRD VENTS ON THE UNIT. 3.1 The installation must comply with BS 7671
1.6 Contact Customer Service (see back page), if ‘Requirements for electrical installations’ (IEE
any of the following occur: wiring regulations), building regulations or any
a) If it is intended to operate the shower at particular regulations as specified by the local
pressures above the maximum or below the Electrical Supply Company.
minimum stated. 3.2 This appliance MUST be earthed.
b) If the unit shows a distinct change in 3.3 In accordance with ‘The Plugs and Sockets etc.
performance. (Safety) Regulations 1994’, this appliance is
c) If the shower is frozen. intended to be permanently connected to the
fixed wiring of the electrical mains system.
1.7 If it is intended to operate the shower in areas 3.4 Make sure all electrical connections are tight to
of hard water (above 200 ppm temporary prevent overheating.
hardness), a scale inhibitor may have to be
fitted. For advice on the Scale Inhibitor, 3.5 A 30mA residual current device (RCD) MUST
contact Customer Service. be installed in all UK electric and pumped
1.8 The showerhead must be cleaned regularly shower circuits. This may be part of the
with descalent to remove scale and debris, consumer unit or a separate unit.
otherwise restrictions to the flow on the outlet 3.6 Switch off immediately at isolating switch if
of the unit will result in higher temperatures water ceases to flow during use.
and could also cause the (PRD) Pressure Relief 3.7 Other electrical equipment i.e. extractor fans,
Device in the unit to operate. pumps must not be connected to the circuits
within the unit.
1.9 This product is not suitable for mounting into
steam rooms or steam cubicles. 3.8 Switch off at isolating switch when not in use.
This is a safety procedure recommended with
2 PLUMBING all electrical appliances.
2.1 The plumbing installation must comply with
Water Regulations, Building Regulations or any 3.9 As with all electrical appliances it is
particular regulations as specified by Local recommended to have the shower and
Water Company or Water Undertakers and installation checked at least every two years by
should be in accordance with BS 6700. a competent electrician to ensure there is no
deterioration due to age and usage.

1
Martinique electric shower

INTRODUCTION
Introduction ADVICE TO USERS
Advice to users
This book contains all the necessary fitting and
IMPORTANT: When first installed the unit
operating instructions for your Triton electric
will be empty. It is essential the unit should
shower. Please read them carefully.
contain water before the elements are
The shower installation must be carried out by a switched on. It is vital that the
suitably qualified person and in the sequence of I-001-A
commissioning procedure is followed.
this instruction book. Failure to carry out this operation will result
Care taken during the installation will provide a in damage to the unit and will invalidate the
long, trouble-free life from your shower. guarantee.

SPECIFICATIONS
Specifications The following points will help you understand
how the shower operates:
Electrical
a. The electric heating elements operate at a
Nominal power Nominal power
constant rate at your chosen power setting.
rating at 240V rating at 230V
It is the rate of the water passing through
9.5kW – (40A MCB rating) 8.7kW – (40A MCB rating)
the heater can which determines the water
10.5kW – (45A MCB rating) 9.6kW – (45A MCB rating)
temperature. (The slower the flow the hotter
Water the water becomes, and the faster the flow,
Inlet connection – 15 mm diameter. the cooler the water.)
Outlet connection – ½” BSP male thread. b. During winter the mains water supply will
Entry Points be cooler than in the summer, so the flow
Water – Right: bottom back, bottom. rate will vary between seasons at any one
temperature setting. At different times of the
Cable – Right: middle back, top.
year you may have to adjust the position of
Materials the temperature control to maintain your
Backplate, cover, controls, showerhead – ABS. desired temperature setting.
Sprayplate – Acetal. c. The stabiliser valve minimises variations in
Elements – Minerally insulated corrosion resistant shower temperature during mains water
metal sheathing. pressure changes. If changes in shower tem-
Dimensions perature are experienced during normal use,
Height − 338 mm it will most likely be caused by the water
Width − 208 mm pressure falling near to or below the mini-
Depth − 95 mm mum level. The drop in pressure may be due
to water being drawn off at other points in
Standards and Approvals the house whilst the shower is in use. If pres-
Splashproof rating IPX4. sure drops appreciably below the minimum,
Complies with the requirements of current British the heating elements will automatically cut
and European safety standards for household out.
and similar electrical appliances. If ever the water becomes too hot and you
Complies with requirements of the British cannot obtain cooler water, first check that
Electrotechnical Approvals Board (BEAB). the sprayplate in the showerhead has not
Meets with Compliance with European become blocked.
Community Directives (CE). Do not place items such as soap or shampoo
bottles on top of the unit. Liquid could seep
through the joint between the cover and
backplate, and possibly damage the sealing
Replacement parts can be ordered from Customer rubber.
Y-003-A
Service. See ‘spare parts’ for details and part numbers.

2
Martinique electric shower

MAIN COMPONENTS
Main components Fig.1

Inside unit (fig.1) 10 10 1

1. Top cable entry


5
2. Bottom pipe entry
6
3. Rear pipe entry area 12
4. Rear cable entry area 7
11 4
5. Wall screw fixing
6. Terminal block
13
7. Power PCB
8. Stabilising valve 5
8
9. Solenoid valve
10. Guide pockets
9
11. Can and element assembly
14
12. Thermal cut-out (main) 3
15
10 2
13. Earth connection
14. Outlet temperature regulator
15. Trimplate
Note: Not all wires have been depicted for reason of clarity
Inside cover (fig.2)
16. Cover tags Fig.2
16 16
17. Control PCB

17

16

3
Martinique electric shower

ELECTRICAL REQUIREMENTS Shepperton Park,


Triton Road, Nuneaton,
WARNING! Warwickshire, CV11 4NR
W-006-A
THIS APPLIANCE MUST BE EARTHED

The installation, supply cable and circuit


protection must conform with BS 7671 (IEE
wiring regulations) and be sufficient for the
amperage required.
Fig.3
The following notes are for guidance only:
1 The shower must only be connected to a
230-240V ac supply. If you are installing a
shower with a kilowatt rating above 9kW, it Fig.4 Schematic of installation circuit
is advisable to contact the local electricity
supply company. Pull cord
isolating switch
1.1 The electrical rating of the shower is shown
on the rating label (Fig.3) within the unit.
Shower
RCD unit
2 Before making any sort of electrical (can be part of
connection within the installation make sure consumer unit)
that no terminal is live. If in any doubt,
switch off the whole installation at the mains
supply and remove the correct fuse.
3 The shower must be connected to its own
independent electrical circuit. IT MUST NOT Fuse or Consumer
MCB unit Meter
be connected to a ring main, spur, socket Incoming
outlet, lighting circuit or cooker circuit. supply
80A or 100A fuse
3.1 The electrical supply must be adequate for main switch
the loading of the unit and existing circuits.
Meter
4 Check your consumer unit (main fuse box) tails
has a main switch rating of 80A or above
and that it has a spare fuse way which will
take the fuse or Miniature Circuit Breaker Table A
(MCB) necessary for the shower (Fig.4).
CIRCUIT PROTECTION
4.1 If your consumer unit has a rating below
80A or if there is no spare fuse way, then the unit cartridge
installation will not be straightforward and rating MCB fuse
may require a new consumer unit serving
7.0kW 30/32A 30A
the house or just the shower.
7.5kW 32A 35A
4.2 You will need to contact the local electricity
8.0kW 40A 35A
company. They will check the supply and
carry out what is necessary. 8.5kW 40A 45A
5 For close circuit protection DO NOT use a 9.0kW 40A 45A
rewireable fuse. Instead use a suitably rated 9.5kW 40/45A 45A
Miniature Circuit Breaker (MCB) or cartridge 10.5kW 45A 45A
fuse (see Table A).
5.1 A 30mA residual current device (RCD) must
be installed in all UK electric and pumped
shower circuits. This may be part of the
consumer unit or a separate unit.
6 A 45 amp double pole isolating switch with 4
a minimum contact gap of 3 mm in both
cabling is bunched with others, surrounded
carry out what is necessary. by thermal loft or wall insulation or placed in
5 For close circuit protection DO NOT use a areas where the ambient temperature is
rewireable fuse. Instead use a suitably rated above 30°C. Under these conditions,
Martinique
Miniature Circuit Breaker (MCB) or cartridgeelectricderating
shower factors apply and it is necessary to
fuse (see Table A). select a larger cable size.
5.1 A 30mA residual current device (RCD) must 9.2 In the majority of installations, the cable
be installed in all UK electric and pumped will unavoidably be placed in one or more
shower circuits. This may be part of the of the above conditions. This being so, it
consumer unit or a separate unit. is strongly recommended to use a
6 A 45 amp double pole isolating switch with minimum of 10mm cabling throughout
a minimum contact gap of 3 mm in both the shower installation.
poles must be incorporated in the circuit. 9.3 In any event, it is essential that individual
6.1 It must have a mechanical indicator showing site conditions are assessed by a competent
when the switch is in the OFF position, and electrician in order to determine the correct
the wiring must be connected to the switch cable size and permissible circuit length.
without the use of a plug or socket outlet. Table B
6.2 The switch must be accessible and clearly
identifiable, but out of reach of a person Twin and earth PVC insulated cable
using a fixed bath or shower, except for the Current carrying capacity
cord of a cord operated switch, and should
be placed so that it is not possible to touch Clipped direct
the switch body while standing in a bath or or buried in a
E-002-A
shower cubicle. It should be readily Installed in an In conduit non-insulated
insulated wall trunking wall
accessible to switch off after using the
shower.
6 mm² 6 mm² 6 mm²
7 Where shower cubicles are located in any 35A 38A 47A
rooms other than bathrooms, all socket 10 mm² 10 mm² 10 mm²
outlets in those rooms must be protected by 47A 52A 64A
a 30mA RCD. 16 mm² 16 mm² 16 mm²
63A 69A 85A
8 The current carrying capacity of the cable
must be at least that of the shower circuit
Note: Cable selection is dependent on
protection (see Table B).
derating factors
8.1 To obtain full advantage of the power
provided by the shower, use the shortest
cable route possible from the consumer unit
to the shower.
8.2 It is also necessary to satisfy the
disconnection time and thermal constraints
which means that for any given combination
of current demand, voltage drop and cable
size, there is a maximum permissible circuit
length.
9 The shower circuit should be separated from
other circuits by at least twice the diameter
of the cable or conduit.
9.1 The current rating will be reduced if the
cabling is bunched with others, surrounded
by thermal loft or wall insulation or placed in
areas where the ambient temperature is
above 30°C. Under these conditions,
derating factors apply and it is necessary to
select a larger cable size.
9.2 In the majority of installations, the cable
will unavoidably be placed in one or more
of the above conditions. This being so, it 5
is strongly recommended to use a
Martinique electric shower

Water
WATER requirements
REQUIREMENTS
Water requirements
Mains electric supply
(via double pole switch)
WARNING!
The shower must not be positioned
where it will be subjected to freezing
Double conditions.
pole
isolating
switch
The installation must be in accordance with
Water Regulations and Bylaws.
Shower
unit To ensure activation of the heating elements,
the shower must be connected to a mains water
Switch may
be wall supply with a minimum running pressure of
Isolating
stopvalve mounted 100kPa (1.0 bar) at a minimum flow rate of nine
in accordance
with IEE regs. litres per minute for the 9.5kW rated model.
For the 10.5kW rated shower, the minimum
running pressure must be 150kPa (1.5 bar) at a
Mains minimum flow rate of eleven litres per minute.
water
supply For all models the maximum static pressure must
be 1 000kPa (10 bar).
Note: If the stated flow rates are not available,
it may not be possible to achieve optimum
performance from the unit throughout the year.
Separate permanently
connected supply For guidance on the running and static pressures
from consumer unit
contact the local Water Authority or consult a
competent plumber.
Fig.5 Diagrammatic view (not to scale) During periods of high ambient temperatures it
may be necessary to select a low power setting
to achieve your preferred shower temperature.
The water supply can be taken from a cold water
storage cistern provided there is a minimum
head of ten metres (fifteen metres for the
10.5kW model) above the showerhead. It must
be an independent supply to the shower only.
If it is intended to operate the shower at
pressures above the maximum or below the
minimum stated, contact Customer Service for
advice.
Fig.5 shows a typical system layout.
Do not use jointing compounds on any pipe
fittings for the installation.

6
Martinique electric shower

sitinG
SITING OFshower
Siting of the tHe SHOWER
THE sHOWer
ImpoRTANT: If installing onto a tiled wall
always mount the unit on the surface of the
tiles. nEVER tile up to the unit. Shower unit can
be mounted either
Refer to fig.6 for correct siting of shower. side of riser rail

Position the unit where it will NOT be in direct


contact with water from the showerhead.
Position the shower unit vertically.
Leave enough room between the ceiling and the Height of
showerhead
shower to allow access to the cover top screws. and
shower
Note: Water Regulations require the showerhead to suit
be ‘constrained by a fixed or sliding attachment user's
so that it can only discharge water at a point requirement

not less than 25mm above the spill-over level Mains cold water
supply - bottom
of the relevant bath, shower tray or other fixed Soap dish and back only
retaining
appliance’. The use of the supplied retaining ring
ring/gel hanger will in most cases meet this
requirement, but if the showerhead can be Shower unit
placed within a bath, basin or shower tray, then 25 mm minimum must not
be within
a double check valve, or similar, must be fitted in an area
Spillover
the supply pipework to prevent back-flow. level 1 metre
Outline of bath from base
Pressure relief safety device or shower tray

A pressure relief device (PRD) is designed into


the shower unit which complies with European
standards. The PRD provides a level of appliance Fig.6 Diagrammatic view (not to scale)
protection should an excessive build up of
pressure occur within the shower.
DO NOT operate the shower with a damaged or IMPORTANT: The unit must be mounted on
kinked shower hose, or a blocked showerhead a flat surface which covers the full width
which can cause the PRD to operate. and length of the backplate. It is important
that the wall I-002-A
surface is flat otherwise
When commissioning, the showerhead must
difficulty may be encountered when fitting
be removed from the flexible hose, while at the
the cover and subsequent operation of the
same time the temperature control must be at
unit may be impaired.
the minimum flow position. Failure to follow this
procedure may also cause the PRD to operate.
Make sure the shower is positioned over a bath
or shower tray because if the PRD operates, then
water will eject from the bottom of the unit.
Should this happen, turn off the electricity and
water supplies to the shower at the isolating
switch and stopvalve. Contact Customer Service
for advice on replacing the PRD.

7
Martinique electric shower

FITTING THE SHOWER


Fitting the shower to the wall TO THE WALL
Fig.7
WARNING!
Check there are no hidden cables or
pipes before drilling holes for wall
W-005-A
plugs. Use great care when using power
tools near water. The use of a residual
current device (RCD) is recommended.

Note: The control knob is an integral part of the


cover – DO NOT attempt to remove it.
unscrew the two top and one bottom retaining
screws (fig.7) and lift the cover from the
backplate. To access the pipe and cable
connections, remove the two screws (fig.8) and
Fig.8 take off the trimplate.
Entry positions for the mains water are from the
bottom or from the rear. Cable entry is via the
top or rear.
Note: Deviations from the designated entry
points will invalidate product approvals.
If bottom surface entry is required for the mains
cold water, then the necessary opening will need
to be cut out in the trimplate and cover (fig.9).
If surface cable entry from the top is required
then a small area will need to be cut out in the
backplate (fig.10).
If installing a feed pipe from the rear or bottom,
the centre of the inlet valve to the wall surface is
20mm (fig.11).
Note: If entry is from the rear, the nut of the
compression fitting will be partially behind the
Fig.9 View from underneath surface of the wall (fig.11). This area MuST
be left clear when plastering over the pipework
in order to make the nut accessible for future
adjustments.
remove cover After choosing the site for the shower, use the
backplate as a template and mark the two fixing
holes (fig.12).
Drill and plug the wall.
(An appropriate drill bit should be used. If the
wall is brick, plasterboard or a soft building block,
appropriate wall plugs and screws should be fitted).

backplate

8
Martinique electric shower

Screw top fixing screw into position leaving the


base of the screw head protruding 6mm out remove
Fig.10
from the wall.
Hook the backplate over the top screw and
fit the bottom fixing screw into position. Do
not fully tighten the screws at this stage, as
the fixing holes are elongated to allow for
out of square adjustment after the plumbing
connections have been completed.

View from
rear of backplate

Fig.11

20mm

Fig.12

9
Martinique electric shower

WARNING!
PLUMBING CONNECTIONS
Plumbing connections
The outlet of the shower acts as a Plumbing to be carried out before wiring
W-004-A
vent and MUST NOT be connected to Do not use jointing compounds on any pipe
anything other than the hose and fittings for the installation.
showerhead supplied. Do not soldered fittings near the shower unit
as heat can transfer along the pipework and
damage components.
Compression fittings must be used to connect
to the inlet of the shower. (Push-on fittings must
not be used as full engagement cannot be
guaranteed.)
Note: An additional stopvalve (complying with
Water Regulations) must be fitted in the mains
water supply to the shower as an independent
means of isolating the water supply should
maintenance or servicing be necessary.
Important: Before completing the
connection of the water supply to the inlet
of the shower, flush out the pipework to
remove all swarf and system debris. This can
be achieved by connecting a hose to the
pipework and turning on the mains water
supply long enough to clear the debris to
waste.

Procedure
Turn off water supply either at the mains
stopvalve or the isolating stopvalve. Connect the
mains water supply to the inlet of the shower
via 15mm copper, stainless steel or plastic pipe
using a 15mm x 15mm elbow compression
fitting.
Do not use excessive force when making these
connections.
Make sure the backplate is square on the wall
and tighten the two retaining screws which hold
it to the wall.
Turn on the mains water supply and check for
leaks in the pipework connection to the shower.
IMPORTANT: Using a suitable sealant, always
seal around the incoming pipework to
prevent water entering the wall.
Note: At this stage no water can flow through
the unit.

10
Martinique electric shower

ELECTRICAL CONNECTIONS
Electrical connections Fig.13
SWItCH oFF tHE ELECtRICItY SUPPLY At
tHE MAInS. L
Fig.13 shows a schematic wiring diagram. 1
N
The cable entry points are shown in fig.1. The 6
cable can be surface clipped, hidden or via E 2
20mm conduit. 4
Note: Conduit entry can only be from rear.
Route the cable into the shower unit and 3
connect to the terminal block (fig.14) as
8
follows:

Earth cable to terminal marked


Neutral cable to terminal marked N
Live cable to terminal marked L
9

ImpoRTANT: Fully tighten the terminal


block screws and make sure that no cable
9
insulation is trapped under the screws. Loose 7 inlet
connections can result in cable overheating.
Note: The supply cable earth conductor must outlet
be sleeved. The outer sheath of the supply cable 5

must be stripped back to the minimum.


The supply cable must be secured either by 1. Terminal block 6. Thermal cut-out
routing through conduit or in trunking or by 2. Earth post (main)
3. Control PCB 7. Thermal cut-out
embedding in the wall, in accordance with 4. Power PCB (outlet)
current IEE regulations. 5. Solenoid valve 8. Connector socket
The use of connections within the unit, or other 9. Element
points in the shower circuit, to supply power to
other equipment i.e. extractor fans, pumps etc. Fig.14
will invalidate the guarantee.
Do not switch on the electricity supply until
the cover has been fitted. Terminal
At this stage, temporarily fit the cover in order to block
carry out the commissioning procedure.
The first operation of the shower is intended to
flush out any remaining unit debris and to make
sure the heater unit contains water before the
elements are switched on.
Refit the trimplate and secure with the two
screws.

Note: The elements on UK models are to 240V


specification andN-001-A
will give a lower kW rating if
the voltage supply is below 240V.

11
Martinique electric shower

COMMISSIONING
Commissioning
Fig.15
WARNING!
Before normal operation of the
shower, it isW-001-A
essential the following
commissioning procedure is completed
Valve
spindle correctly.

Turn the valve spindle fully clockwise until the


arm hits the stop (fig.15).
Turn the temperature control on the cover to
position ‘10’ (fig.16).
Offer the cover to the unit.
ImpoRTANT: Do not connect the 10-way
Fig.16 ribbon cable at this stage.
Carefully locate the cover tags into the guide
pockets on the backplate and make sure the
wires are not trapped. Guide the cover into
position so that the control spindle locates
correctly (minor adjustment may be necessary to
align the control and spindle).
Should any difficulty arise, recheck the points
above.
While applying slight pressure to the front
cover, secure in position with the three retaining
screws.
Fig.17 Fit the flexible hose to the shower outlet making
sure the outlet of the hose is directed to waste.
Temperature Check the supplied sealing washer is in place.
control at DO NOT attach the showerhead at this stage.
minimum
Before turning on the electric and mains
flow setting
water supplies to the shower, make sure the
temperature control is rotated fully clockwise to
‘10’, the minimum flow position (fig.17).
Note: Failure to rotate fully clockwise may cause
the PRD to operate.
Turn on the water supply to the shower at the
isolating stopvalve. Switch on the electricity
supply to the shower at the isolating switch.
Wait until water starts to flow from the flexible
hose.
Slowly rotate the temperature control fully anti-
clockwise, the maximum flow position (fig.18).
It will take about thirty seconds for a smooth
flow of water to be obtained while air and any
debris is being flushed from the shower. When

12
Martinique electric shower

a smooth flow of water is obtained, turn the


temperature control from minimum flow to Fig.18
maximum flow and back again several times to Temperature
release any trapped air from within the unit. control at
Once the flushing out has been completed, maximum
switch off the electricity to the shower at the flow setting
isolating switch. The water will cease to flow.
unscrew the top and bottom retaining screws
again (fig.6) and lift the cover from the
backplate.
Attached to the display PCB, inside the cover,
is a 10-way ribbon cable. The ribbon cable
connector must be plugged into the socket
located at the right of the power PCB situated
inside the unit (fig.19).
Note the cable connector can be fitted to the
Fig.19
socket only one way. The ribbon cable has
a coloured edge which is lowermost when
correctly fitted to the socket.
Note: The ribbon cable is preformed to fold flat
when the cover is fitted.

Coloured
edge

13
Martinique electric shower

REPLACING THE COVER


Replacing the cover
Fig.20
ImpoRTANT: Before finally fitting the cover,
the following steps must be taken:
a. Check plumbing connections are
Valve spindle watertight.
b. Check terminal block screws are fully
tightened.
c. Make sure the pipe and cable entering
the unit do not prevent the cover locating
correctly to the backplate.
d. Rotate the valve spindle fully clockwise
until the arm hits the stop (fig.20).
Fig.21
e. turn the temperature control on the cover
to position ‘10’ (fig.21).
Offer the cover to the unit.
Carefully locate the cover tags into the guide
pockets on the backplate and make sure the
wires are not trapped.
Guide the cover into position so that the knob
spindle locates correctly (minor adjustment may
be necessary to align the knob and spindle).
Should any difficulty arise, recheck the points
above.
While applying slight pressure to the front
cover, secure in position with the three retaining
screws.
Turn the electric supply back on at the isolating
switch. The POWER indicator will light. No
water will flow until one of the three buttons are
pressed.
Note: It is recommended that the water and
electric supplies to the shower are turned off
while the riser rail kit is being installed.
The flexible hose can be left attached to the
shower outlet. Make sure the supplied sealing
washer is fitted.

14
Martinique electric shower

OPERATING THE SHOWER


Operating the shower Fig.22
WARNING!
Before normal operation of the
shower, it isW-001-A
essential the following
commissioning procedure is completed Stop
correctly. button

When the electricity supply to the shower is


switched on at the isolating switch, the POWER
indicator will light.

to start the shower


Water will flow by pressing any of the three
buttons – COLD, ECONOMY or HIGH.

to stop the shower High

Press the STOP button and the phased shutdown


will begin. Water will cease to flow after about Cold
four seconds.
Economy
to use the control buttons
There are three control buttons – HIGH, COLD
and ECONOMY (fig.22).
The upper button – red symbol is a HIGH
power setting which allows the highest flow
achievable for your preferred temperature. This
setting should normally be regarded as optimum
shower performance throughout the year. Temperature
Temperature adjustment at this setting is via the control
temperature control.
The centre button – blue symbol is for COLD
water only. Adjusting the temperature control
at this setting will only increase or decrease the
force of the water from the showerhead. (It will
not alter the water temperature).
The lower button – red symbol is an
ECONOMY setting for using less energy when
the ambient mains water temperature is high
during hot months. Temperature adjustment at Note: In normal use, it is in order to leave the
this setting is via the temperature control. water supply permanently on to the shower
Note: If the stated flow rate required for the unit unit, but as with most electrical appliances,
cannot be met due to low water pressure, it will the unit must be switched off at the
be necessary to operate the unit on this setting isolating switch when not in use.
during the warmer months because of flow rate
limitations entering the unit.

15
Martinique electric shower

To adjust the shower temperature


WARNING!
After any servicing of mains water The water temperature is altered by increasing
or decreasing the flow rate of the water through
supply, always flush out the pipework
the shower via the temperature control (fig.22).
W-002-A
to remove any debris.
Always make sure the unit is started After finding a suitable showering temperature,
the number can left as the normal setting and
on COLD in order to purge any air in
should only need altering to compensate for
the pipework.
seasonal changes in ambient water temperature.
Note: The preferred number on ‘economy’ will
Warning give a different temperature to the same number
position on ‘high’.
This appliance is not intended for use
by persons (including children) with To decrease the shower temperature
reduced physical, sensory or mental Turn the temperature control anti-clockwise;
capabilities, or lack of experience this will increase the flow of water through the
and knowledge, unless they have shower and is indicated by lower numbers.
been given supervision or instruction
To increase the shower temperature
concerning use of the appliance by a
person responsible for their safety. Turn the temperature control clockwise; this will
decrease the flow of water through the shower
Children should be supervised to and is indicated by higher numbers.
ensure that they do not play
Note: It is advisable to be certain that the
with the appliance. showering temperature is satisfactory by testing
with your hand before stepping under the
showerhead. There will always be a time delay of
a few seconds between selecting a flow rate and
the water reaching the stable temperature for
that flow rate.
Caution: It is recommended that persons
who may have difficulty understanding or
operating the shower controls should not
be left unattended while showering. Special
consideration should be given to young
children and the less able bodied.

16
Martinique electric shower

OPERATING FUNCTIONS (fig.23)


Operating functions Fig.23
Power on indicator
When the electricity supply to the shower is
switched on at the isolating switch, the POWER
indicator will light.

Low pressure indicator


If this indicator lights, this means the water
pressure has fallen below the minimum required
for correct operation of the shower, resulting in
the low pressure cut-out operating. This switches Power on
off power to the heating elements preventing
any undue temperature rises (water will continue Low pressure
to flow). Power will automatically be restored
when adequate water pressure returns.

selector mode indicators Selector


mode
Next to each control button there is an indicator
indicators
that lights when the button is pressed, indicating
which shower mode is in operation.

Phased shutdown
In use, when the stop button is pressed, power is
switched off to the elements. Water will continue
to flow for a few seconds, flushing out any
remaining hot water. This makes sure the next
immediate user will not receive a slug of hot
water if standing under the showerhead when
starting the shower.

temperature regulator
During normal operation if an overheat
temperature is sensed, power to the elements
will be reduced. Water will continue to flow.
When the temperature has cooled sufficiently
power to the elements will be automatically
restored to the setting at the time of
interruption.

safety cut-out
The unit is fitted with a non-resettable
thermal cut-out safety device. In the event of
abnormal operation which could cause unsafe
temperatures within the unit, the device will
disconnect the heating elements. It will require a
visit from a qualified engineer to determine the
nature of the fault and replace the safety device,
once the unit has been repaired.

17
Martinique electric shower

INSTRUCTIONS
Instructions FOR INSTALLERS
for installers and service engineers only AND SERVICE ENGINEERS ONLY
CLEANING THEinlet
Cleaning the INLET
filter FILTER
Fig.24
It is recommended that the filter is periodically
cleaned in order to maintain the performance of
the shower. It is essential that this operation is
carried out by a competent person.
SWItCH oFF tHE ELECtRICItY SUPPLY At
tHE MAInS.
The inlet filter is situated in the inlet pipe which
is part of the solenoid valve (fig.24).
Inlet To gain access to the filter, remove the trimplate
filter then disconnect and remove the compression
fitting. Also, depending on the incoming
pipework arrangements, if there is not enough
slack in the pipework, it could mean removing
the unit from the wall.
When cleaning the wire mesh filter DO NOT
use a sharp object, as it will cause damage. It is
preferable to use an old toothbrush or similar.

18
Martinique electric shower

Spare parts SPARE PARTS


ref. Description Part no.

1. Power PCB.................................. 7073333


2. Terminal block & wires
9.5kW....................................... 82200900
10.5kW..................................... 82200920
1
2
3. Heater can assembly
9.5kW....................................... 84500290 6
10.5kW..................................... 84500670
4. Stabiliser valve assembly
9.5kW....................................... 82600700
10.5kW..................................... 82600810
3
5. Solenoid valve assembly ........... 83304130
6. Thermal cut-out........................ 22009860
7. PRD & ‘O’ ring ......................... 83301330 4
8. Outlet pipe assembly ................ 85000130
c/w wires
– Trimplate ................................. 7051656
5
− Control PCB ............................ 7073492
− TCO shield .............................. 7052871
9. Cover assembly ........................ 85100350 7 8

19
Martinique electric shower

FAULT FINDING
IMPORTANT: Switch off the electricity at the mains supply and remove the circuit fuse before
attempting any fault finding inside the unit.
Fault finding
Problem/Symptom Cause Action/Cure

1 Shower 1.1 Interrupted 1.1.1 Blown fuse or circuit breaker. Check


inoperable, no power supply. supply. Renew or reset fuse or circuit
water flow. breaker. If it fails again, consult a
qualified electrician.
1.1.2 Power cut? Check other appliances and if
necessary, contact local Electricity Supply
Company.
1.2 No mains water 1.2.1 Check if isolating valves are fully open.
supply to Check for a blockage in inlet filter or in
shower. pipework.
1.3 Unit 1.3.1 Have unit checked. Ring Customer
malfunction. Service.

2 Water too hot. 2.1 Not enough 2.1.1 Increase flow rate via temperature
water flowing control.
through the 2.1.2 Blocked showerhead — clean or replace
shower. blocked sprayplate in showerhead.
2.2 Blockage in 2.2.1 Check if stop valves are fully open. Check
supply. if blockage in inlet filter.
2.3 Increase in 2.3.1 Readjust flow rate to give increased flow.
ambient water 2.3.2 Select ‘economy’ power.
temperature.

3 Water temperature 3.1 Heater cycling 3.1.1 See 'Water too hot' causes 2.1, 2.2 and
cycling hot/cool at on outlet 2.3 and their appropriate action/cures. If
intervals. thermal cut-out. it continues, contact Triton Customer
Service.

4 Water too cool or 4.1 Too much flow. 4.1.1 Reduce flow rate via temperature control.
cold.
4.2 Water pressure 4.2.1 Is water supply mains or tank fed ?
below minimum 4.2.2 If tank fed, replumb to mains water
required (see supply or see 4.2.4.
rating label). 4.2.3 If mains fed, make sure that the mains
stopvalve is fully open and there are no
other restrictions in the supply while
X-004-A shower is in use, or see 4.2.4.
4.2.4 Fit pump to give minimum pressure (see
rating label). Contact Customer Service
for advice.
4.3 Reduction in 4.3.1 Readjust flow rate to give reduced flow.
ambient water 4.3.2 Select ‘high’ power.
temperature.
4.4 Electrical 4.4.1 Have unit checked by suitably qualified
malfunction or electrician or contact Triton Customer
safety cut-out Service.
operated.
20
required (see supply or see 4.2.4.
rating label). 4.2.3
If mains fed, make sure that the mains
stopvalve is fully open and there are no
other restrictions in the supply while
Martinique electric shower
X-004-A shower is in use, or see 4.2.4.
4.2.4 Fit pump to give minimum pressure (see
rating label). Contact Customer Service
FAULT FINDINGfor advice.
4.3 Reduction in 4.3.1 Readjust flow rate to give reduced flow.
Problem/Symptom Cause ambient water Action/Cure
4.3.2 Select ‘high’ power.
temperature.

4.4 Electrical 4.4.1 Have unit checked by suitably qualified


malfunction or electrician or contact Triton Customer
safety cut-out Service.
operated.

5 Shower varies from 5.1 Water pressure 5.1.1 Wait until the water pressure resumes to
normal has dropped normal.
temperature to below minimum
cold during use. required.

6 Pressure relief 6.1 Blocked 6.1.1 Clean or replace blocked sprayplate in


device has showerhead. showerhead and then fit new PRD.
operated (water
ejected from PRD 6.2 Twisted/blocked 6.2.1 Check for free passage through hose.
tube). flexible shower Replace the hose if necessary and fit new
hose. PRD.
6.3 Showerhead not 6.3.1 Fit new PRD. Commission unit with
removed while showerhead removed.
commissioning.
6.4 Water pressure 6.4.1 Fit pressure reducing valve to inlet and
above specified then fit new PRD.
maximum for
unit (see rating
label).

7 Water flowing 7.1 Debris in 6.1.1 Replace solenoid valve.


from showerhead solenoid valve.
when unit is
turned off. 7.2 Unit 6.2.1 Have unit checked. Ring Customer
malfunction. Service.

Note: Identify cause of operation before fitting new PRD unit.


When fitting a new PRD, follow the commissioning procedure.
N-003-A
It is advised all electrical maintenance/repairs to the shower
should be carried out by a suitably qualified person.

In the unlikely event of unit failure other than detailed in the fault finding page,
Y-001-A
please contact Customer Service for advice.

21
uK SErVICE PoLICY TrITon STandard GuaranTEE
In the event of a product fault or complaint occurring, the following Triton guarantee this product against all
procedure should be followed: mechanical and electrical defects arising from
1. Telephone Customer Service on 0844 980 0750 having available, faulty workmanship or materials for a period of
your details including post code, the model number and power two years for domestic use only, from the date of
rating of the product, together with the date of purchase and, where
applicable, details of the particular fault. purchase, provided that it has been installed by
2. If required, the Customer Service Advisor will arrange
a competent person in full accordance with the
for a qualified engineer to call. fitting instructions.
3. All products attended to by a Triton service engineer must be Any part found to be defective during this
installed in full accordance with the Triton installation guide guarantee period we undertake to repair or replace
applicable to the product. (Every product pack contains an installation at our option without charge so long as it has been
guide, however, they can also be bought via our Customer Service Spares properly maintained and operated in accordance
Department).
with the operating instructions, and has not been
4. Our engineer will require local parking and if a permit is required this
must be available to the engineer on arrival at the call. subject to misuse or damage.
5. It is essential that you or an appointed representative (who must This product must not be taken apart, modified or
be over 18 years of age) is present for the duration of the service repaired except by a person authorised by Triton.
engineer's visit. If the product is in guarantee you must produce This guarantee applies only to products installed
proof of purchase. within the United Kingdom and does not apply to
6. Where a call under the terms of guarantee has been booked and products used commercially. This guarantee does
the failure is not product related (i.e. scaling and furring, incorrect not affect your statutory rights.
water pressure, pressure relief device operation or electrical/plumbing
installation fault) a charge will be made. A charge will also be issued What is not covered:
if nobody is at home when the service engineer calls or adequate
parking/permit is not available. 1. Breakdown due to: a) use other than domestic
7. If the product is no longer covered by the guarantee an up front use by you or your resident family; b) wilful act
fixed fee will be charged before the site visit. or neglect; c) any malfunction resulting from the
8. Should proof of purchase not be available on an “in-guarantee” call, incorrect use or quality of electricity, gas or water
or should the service engineer find that the product is no longer or incorrect setting of controls; d) failure to install
under guarantee, the engineer will charge the same fixed price and in accordance with this installation guide.
the customer will be expected to pay the engineer before he leaves.
If payment is not made on the day an administration charge will be 2. Repair costs for damage caused by foreign
added to the fixed charge. objects or substances.
9. If a debt is outstanding from a previous visit, or from any other Triton 3. Total loss of the product due to non-availability
purchase. Triton reserves the right to withhold service until the debt of parts.
has been settled. 4. Compensation for loss of use of the product or
10. Triton takes the health, safety and wellbeing of its employees very consequential loss of any kind.
seriously and expects customers to treat all staff members with respect.
Should any employee feel threatened or receive abuse, either verbally 5. Call out charges where no fault has been found
or physically, Triton reserves the right to withhold service and will with the appliance.
support the employee with a legal prosecution. 6. Call out charges where the water supply cannot
replacement Parts Policy be isolated, this includes consequential losses
It is the policy of Triton Showers to maintain parts availability for the arising from unserviceable supply valves.
duration of production and a period of 5 years thereafter in accordance 7. The cost of repair or replacement of pressure
with industry standards. In the event of a spare part not being available a relief devices, showerheads, hoses, riser rails
substitute part will be supplied. and/or wall brackets, isolating switches,
Spare parts can be ordered via our online spare parts store, or by electrical cable, fuses and/or circuit breakers or
telephoning Triton Spares Department. Payment should be made by any other accessories installed at the same time.
credit/debit card (excluding American Express or Diners Card). Payment
can also be made by pre-payment of a pro-forma invoice, by cheque or 8. The cost of routine maintenance, adjustments,
postal order. overhaul modifications or loss or damage arising
Telephone orders are based on information given during of the call. therefrom, including the cost of repairing
Before contacting Triton, please verify your requirements using the damage, breakdown, malfunction caused by
information contained in the user guide. Triton cannot accept liability for corrosion, furring, pipe scaling, limescale,
incorrect part identification. system debris or frost.

Customer Service: % 0844 980 0750


Triton Showers
Triton Road Trade Installer Hotline: %
0844 980 0730
Nuneaton Fax: 0844 980 0744
Warwickshire CV11 4NR www.tritonshowers.co.uk
Triton is a division of Norcros Group (Holdings) Limited E-mail: [email protected]

Extended Warranty AVAILABLE NOW. Call 0844 980 0740 for more details.
3-1-2012 TRITON reserve the right to change product specification without prior notice. E&OE. © TRITON SHOWERS 2012

You might also like