DATA SHEET FOR LV SWITCHGEAR
XX     DD-MM-YYYY           XXX                 XXX                  XXX                                  Issued for EBOK
 REV.        DATE         ORIGINATOR          REVIEWED             APPROVED                APPROVED          DESCRIPTION
THIS DOCUMENT IS INTENDED FOR USE BY ITS NOMINATED CONSULTANTS, CONTRACTORS, MANUFACTURERS AND SUPPLIERS.
COMPANY: XXXXXXXXXXXXXXXXXXXXX
ORIGINATOR:
                                                                                          Page: 1 of 6
DATA SHEET FOR LV SWITCHGEAR
 0                                                                                                                        0
 0                                                                                                                       Page : 2 of 6
The table below is a brief summary of the most recent revisions to this document. Details of all revisions are held on
document by the issuing department.
     Sr. No.         Rev. No.                    Issue No.               Date of issue                 Description of revision
       1                 A                           1                    DD-MM-YYYY                      Issued for EBOK
DATA SHEET FOR LV SWITCHGEAR
 0                                                                                                                     0
 0                                                                                                                    Page   : 3 of 6
 1 SCOPE
   THIS DOCUMENT COVERS THE TECHNICAL AND DESIGN REQUIREMENTS IN A FORM OF DATASHEET FOR THE LV SWITCHGEAR
   INSTALLED IN PROJECT FACILITIES OF FERRUKA-HARARE PIPELINE SERIES OPERATION.
 2 GENERAL NOTES
     1) * - DATA BY VENDOR
     2) THE SWITCHGEAR SHALL BE RATED TO OPERATE SATISFACTORILY UNDER AN AMBIENT TEMPERATURE OF 37°C AND SHALL BE
         CAPABLE OF OPERATING AT 50°C FOR A PERIOD OF FOUR (4) HOURS, DURING THE FAILURE OF AIR-CONDITIONING WITHOUT
         AFFECTING ITS LIFE SPAN AS WELL AS ITS PERFORMANCE.
      3) CT, PT BURDEN & ACCURACY CLASS TO BE VERIFIED AND SELECTED BY VENDOR INCLUDING BASIS OF CALCULATION.
      4) VENDOR TO FURNISH CATALOG DETAILS OF CIRCUIT BREAKER, RELAY ETC.
      5) VENDOR TO FURNISH INSPECTION AND TEST PLAN, FACTORY ACCEPTANCE TEST PROCEDURE.
      6) VENDOR TO SUBMIT TYPE TEST CERTIFICATES FOR SWITCHGEAR, FOR PURCHASER'S REVIEW.
      7) UNIT RATES FOR ADDITION / DELETION OF VARIOUS FEEDERS SUCH AS INCOMER, OUTGOING MOTOR FEEDERS ETC. FOR DIFFERENT
         CONTINUOUS AND SHORT CIRCUIT RATING SHALL BE PROVIDED.
      8) ALL STATUS SIGNAL CONTACTS SHALL BE VOLT- FREE CONTACTS. COMMANDS AND STATUS SIGNALS SHALL BE WIRED UPTO
         MARSHALLING CABINET PROVIDED IN EACH SHIPPING SECTION. INTERPANEL WIRING SHALL BE DONE BY VENDOR.
      9) EMERGENCY TRIPPING FACILITY FROM ESD SYSTEM SHALL BE INCORPORATED IN THE WIRING DIAGRAM.
     10) LANGUAGE OF DOCUMENTS AND LANGUAGE ON EQUIPMENT SHALL BE ENGLISH.
     11) VENDOR SHALL FURNISH 230V AC NON UPS POWER REQUIREMENT FOR PANEL / MOTOR SPACE HEATER ALONG WITH BID.
     12) VENDOR SHALL FURNISH 110V AC UPS POWER REQUIREMENT FOR CLOSING COIL, TRIPPING COIL, SPRING CHARGING MOTOR,
         RELAYS, BREAKER CONTROL SUPPLY, ETC.
     13) NORMAL IDENTIFICATION LABELS SHALL BE IN WHITE BACKGROUND WITH ENGRAVED BLACK LETTER.
     14) WARNING & DANGER LABELS SHALL BE IN RED BACKGROUND WITHENGRAVED WHITE LETTER IN ENGLISH.
     15) RATINGS SHALL BE UPDATED BY THE CONTRACTOR BASED ON FINAL VENDOR DATA DURING DETAILED ENGINEERING.
     16) MANUAL CHARGING HANDLE SHALL BE PROVIDED FOR MANUALLY CHARGING THE SPRING.
     17) VENDOR SHALL PROVIDE SUITABLE SURGE ARRESTORS IN ALL CIRCUITS WHERE REQUIRED.
     18) FOR UNIT PROTECTION (TRANSFORMER DIFFERENTIAL AND RESTRICTED EARTH FAULT) SCHEMES, SWITCHGEAR VENDOR SHALL
         CO-ORDINATE WITH EQUIPMENT SUPPLIER FOR PROPER MATCHING OF CURRENT TRANSFORMER
     19) MIMIC DIAGRAM SHALL BE SHOWN ON EACH SWITCHGEAR PANEL.
     20) VENDOR SHALL INDICATE HEAT LOAD OF THE SWITCHGEAR IN THE BID.
 3 ABBREVIATIONS
    AC   ALTERNATING CURRENT
    ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
    API  AMERICAN PETROLEUM INSTITUTE
    ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
    ATEX ATMOSPHERES EXPLOSIVE
    BS   BRITISH STANDARDS
    BSEN BRITISH STANDARDS EURO NORMES
     CT  CURRENT TRANSFORMER
     DC  DIRECT CURRENT
    EMC  ELECTRO-MAGNETIC COMPATIBILITY
    EMI  ELECTROMAGNETIC INTERFERENCE
     EN   EURO NORM
    ESD  EMERGENCY SHUT DOWN
    FAT  FACTORY ACCEPTANCE TEST
     FO  FIBER OPTIC
 HAZOP   HAZARD AND OPERABILITY
    HFI  HIGH FLASH INTERFACE
     MV  HIGH VOLTAGE
    IAC  INTERNAL ARC CLASSIFICATION
    ICS  INSTRUMENT CONTROL SYSTEM
    IEC  INTERNATIONAL ELECTROTECHNICAL COMMISSION
   IMCS  INTEGRATED MACHINE CONTROL SYSTEM
     IP  INGRESS PROTECTION
    ISO  INTERNATIONAL ORGANIZATION FOR STANDARDIZATION
     LFI LOW FLASH INTERFACE
     LV  LOW VOLTAGE
    MCB  MINIATURE CIRCUIT BREAKER
  MCCB   MOULDED CASE CIRCUIT BREAKER
  NEMA   THE NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
  NFPA   NATIONAL FIRE PROTECTION ASSOCIATION
   OEM   ORIGINAL EQUIPMENT MANUFACTURER
    PFD  PROCESS FLOW DIAGRAM
     PM  PARTITION OF METAL
    PTC  POSITIVE TEMPERATURE COEFFICIENT
    PVC  POLY VINYL CHLORIDE
    RTD  RESISTANCE TEMPERATURE DETECTOR
    SAT  SITE ACCEPTANCE TEST
 SCADA   SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM
  SCPD   SHORT CIRCUIT PROTECTIVE DEVICE
    SF6  SULFUR HEXAFLUORIDE
    SLD  SINGLE LINE DIAGRAM
  TCP/IP TRANSFER CONTROL PROTOCOL / INTERNET PROTOCOL
    TRV  TRANSIENT RECOVERY VOLTAGE
    UPS  UNINTERRUPTED POWER SUPPLY
    VCB  VACUUM CIRCUIT BREAKER
    VSC  VARIABLE SPEED COUPLING
    VSD  VARIABLE SPEED DRIVE
   XLPE  CROSS-LINKED POLYETHYLENE
   ZESA  ZIMBABWE ELECTRICITY SUPPLY AUTHORITY
DATA SHEET FOR LV SWITCHGEAR
 0                                                                                                                                             0
 0                                                                                                                                           Page      : 4 of 6
 4 REFERENCE STANDARDS
     2014/34/EU      DIRECTIVE 2014/34/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL OF 26 FEBRUARY 2014 ON THE LAWS OF THE MEMBER
                     STATES RELATING TO EQUIPMENT AND PROTECTIVE SYSTEMS INTENDED FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES
                      (RECAST) TEXT WITH EEA RELEVANCE.
     The International Electrotechnical Commission Standards
     IEC 60038            IEC Standard Voltages
     IEC 60050            International electrotechnical vocabulary
     IEC 60051            Direct acting indicating analogue electrical measuring instruments and their accessories
     IEC 60060            High-Voltage Test Techniques
     IEC 60071            Insulation coordination
     IEC 60073            Basic and Safety Principles for Man-Machine Interface, Marking and Identification - Coding Principles for Indication Devices and
     IEC 60255            Measuring relay and protection equipment.
     IEC 60269            Low-voltage fuses.
     IEC 60417            Graphical Symbols for Use on Equipment
     IEC 60445            Basic and Safety Principles for Man-Machine Interface, Marking and Identification - Identification of Equipment Terminals and of
     IEC 60470            High-Voltage Alternating Current Contactors and Contactor-Based Motor-Starters
     IEC 60529            Degrees of protection provided by enclosures (IP code)
     IEC 60617            Graphical Symbols for Diagrams
     IEC 60644            Specification for High-Voltage Fuse-Links for Motor Circuit Applications
     IEC 60909,           short-circuit current calculations
     IEC 60947            Low-voltage switchgear and control gear
     IEC 61000            Electromagnetic Compatibility (EMC)
     IEC 61850            Communications Networks and Systems in Substations
     IEC 61869-1          Instrument transformers – General requirements
     IEC 61869-2          Instrument transformers – Additional requirements for current Transformers.
     IEC 61869-3          Instrument transformers – Additional requirements for inductive voltage Transformers.
     IEC 62208            Empty enclosures for low-voltage switchgear and control gear assemblies –General Requirements
     IEC 62271            High-Voltage Switchgear and Control gear
     IEC/TR 61641         Enclosed low-voltage switchgear and control gear assemblies - Guide for testing under conditions of arcing due to internal fault
     IEEE C37.20.7        Guide for Testing Metal-Enclosed Switchgear Rated Up to 38 kV for Internal Arcing Faults
     International Organization for Standardization
     ISO 9001             Quality management systems-Requirements
S.No                          DESCRIPTION                                             DESIGN DATA                            VENDOR DATA
                                                                         GENERAL
  1    MANUFACTURER NAME                                     *
  2    COUNTRY OF ORIGIN                                     *
  3    GOVERNING MANUFACTURING STANDARD                      *
  4    SWIITCHGEAR SERIES NAME                               *
  5    TYPE TESTED SWITCHBOARD ( YES / NO)                   Yes
  6    LIST OF TYPE TEST WITH DATE OF VALIDITY               *
  7    NAME OF TESTING AUTHORITY                             *
  8                                                          APPLICABLE REFERENCE DOCS
  9    SPECIFICATION                                          SPECIFICATIONFOR LV SWITCHGEAR Doc. No. XXXXX
 10    MANUFACTURING STANDARD                                IEC 60947
 11    SWITCHGEAR SLD                                        REFER SLD
 12    SWITCHGEAR TAG                                        REFER SLD
 13                                                            SERVICE / SITE CONDITIONS
 14    SERVICE/APPLICATION                                   ELECTRICAL LOADS
 15    ALTITUDE IF > 1000 m                                  XXX
 16    MAXIMUM AMBIENT TEMPERATURE                           XXX°C
 17    DESIGN AMBIENT TEMPERATURE                            XXX°C
 18    MAXIMUM HUMIDITY                                      XX% APPROX.
 19    SPECIAL CONDITIONS (TROPICALISATION, etc.)            TROPICALISATION
 20                                                              AREA CLASSIFICATION
 21    SAFE / HAZARDOUS                                      SAFE
 22    INDOOR / OUTDOOR                                      INDOOR
 23                                                            SYSTEM CHARACTERISTICS
 24    TYPE                                                  SINGLE FRONT
       ASSEMBLY EXTERNAL DESIGN (ENCLOSED, CUBICLE, MULTI-
 25                                                        ENCLOSED MULTICUBICLE
       CUBICLE, BOX, MULTI-BOX)
 26    INTERNAL SEPARATION (FORM 1, FORM 2, …) & TYPE      FORM 3A
 27    WITHDRAWABLE / PLUG-IN FIXED / ...                  WITHDRAWABLE
 28    MOUNTING                                            FLOOR MOUNTED
 29    ACCESS                                              FRONT
 30    CABLES ENTRY                                        BOTTOM
 31    FOOT PLINTH                                         YES
 32                                                                   NETWORK
 33    VOLTAGE                                             400 V ± 10 %
 34    FREQUENCY                                             50 Hz ± 1 %
 35    VOLTAGE VARIATION                                     +10% /-10%
 36    SHORT CIRCUIT RATING                                  50kA / 1Sec
 37    NEUTRAL EARTHING SYSTEM                               TN-S
 38                                                                     SWITCHGEAR
 39    RATED OPERATIONAL VOLTAGE                             400 V± 10 %
 40    RATED CURRENT                                         600 A (HOLD)
 41    RATED SHORT-TIME WITHSTAND CURRENT FOR 1 SECONDS      50kA / 1Sec
                                                             Approximately 1.6 to 1.8 times the Rated Short time withstand
 42    RATED PEAK WITHSTAND CURRENT
                                                             current (IEC 60909)
       INTERNAL ARC FAULT PROTECTION FOR 0.3 SECONDS
 43                                                          YES
       (Y / N) FOR RATED SHORT CIRCUIT CURRENT
 44    VECTOR ROTATION                                          Clockwise
 45    COLOUR                                                   RAL 7035
 46                                                                       MAIN BUSBAR
 47    RATING AT SITE CONDITION                                 800A (HOLD)
 48    BUSBAR SYSTEM                                            SINGLE & INSULATED
 49    BUSBAR CONFIGURATION                                     3Ph + N
 50                                                                      EARTH BUSBAR
 51    CONDUCTOR                                                BARE OR TINNED COPPER
 52    BUSBAR SYSTEM                                            THROUGHOUT THE SWITCHGEAR LENGTH
 53                                                                   AUXILIARY VOLTAGES
 54    INTERNAL (I) / EXTERNAL (E) VOLTAGE SUPPLY               INTERNAL 240 V AC / EXTERNAL 110 V AC
 55    CONTROL SYSTEM                                           110V AC ± 10 %
 56    CIRCUIT BREAKER COILS                                    110V AC ± 10 %
 57    PROTECTION RELAYS                                        110V AC ± 10 %
 58    AUXILIARY RELAYS                                         110V AC ± 10 %
 59    SIGNALISATION                                            110V AC ± 10 %
 60    CONTACTOR COILS                                          240V AC
 61                                                     INCOMER CUBICLE TECHNICAL CHARACTERISTICS
 62                                                                    BREAKING DEVICE
 63    ISOLATING DEVICE & BREAKING DEVICE                       MOTORIZED MCCB
 64    RATINGS OF BREAKING DEVICES                              600A (HOLD)
 65                                                                      MEASUREMENT
                                                                Y / (MIN. A, V, W, VA, VAr, f, PF, kWh,
 66    SEPARATE DIGITAL MULTIFUNCTIONAL METER (DMM)
                                                                KVArh)
 67    REMOTE MONITORING FROM DCS                               YES
 68                                               CURRENT TRANSFORMER FOR MEASUREMENTS AND PROTECTION
 69    RATIO / QTY                                              *
 70    CLASS                                                    *
 71    BURDEN                                                   *
 72                                                           SWITCHGEAR STATUS (AS A MINIMUM)
 73    CIRCUIT BREAKER OPEN/CLOSED                              YES
 74    CIRCUIT BREAKER READY FOR CLOSE                          YES
 75    CIRCUIT BREAKER SERVICE / TEST / ISOLATATED              YES
 76    LOCAL/REMOTE                                             YES
 77                                                       SWITCHGEAR ALARM AND TRIP (AS A MINIMUM)
 78    INST OVERCURRENT TRIP                                    YES
 79    INST EARTHFAULT TRIP                                     YES
 80    IDMT OVER CURRENT                                        YES
 81    TRIP CIRCUIT FAULTY                                      YES
 82    CIRCUIT BREAKER LOCKOUT                                  YES
 83    UNDER VOLTAGE ALARM                                      YES
 84    INTER-TRIP RECEIVE                                       YES
 85    TRANSFORMER TRIP STATUS SIGNAL                           YES
 86                                                                VOLTAGE TRANSFORMERS
 87    RATIO / QTY                                               *
 88    DRAWOUT FIXED TYPE                                       DRAWOUT
 89                                                                SWITCHBOARDS CONTROLS
 90    CLOSED / OPEN (Y / N)                                    YES
 91    TRIPPED (Y / N)                                          YES
Datasheet for LV Switchgear                                                                                                                5 of 6
S.No                           DESCRIPTION                                          DESIGN DATA            VENDOR DATA
 92    MECHANICAL (Y / N) / ELECTRICAL (Y / N)                 YES / YES
 93    REMOTE CONTROL (Y / N) FROM DCS (CLOSE AND OPEN)        YES (HARDWIRED)
 94                                                         INTELLIGENT PROTECTION RELAYS
 95    FEEDING DIRECT, BY CT OR VT                             BY CT & VT
 96    LIST OF ANSI DEVICE CODE NUMBERS                        AS PER SLD
                                                               MICROPROCESSOR BASED WITH SELF DIAGNOSTIC
 97    TYPE
                                                               FACILITIES & SERIAL COMMUNICATION DRAWOUT
       VOLTAGE / CURRENT TEST TERMINAL, BOXES AND SOCKETS (Y /
 98                                                            YES
       N)
 99                                                            OUTGOING FEEDER (REFER SLD)
 100                                                  OUTGOING CUBICLE TECHNICAL CHARACTERISTICS
 101   ISOLATING DEVICE & BREAKING DEVICE RATING               AS PER SLD
 102   DISCONNECTING SWITCH (Y / N)                            YES
 103   FUSES (Y / N)                                           NO
 104   START/STOP FROM DCS                                      NO
 105                                                             MOTOR STARTER FEEDERS
 106   ISOLATING DEVICE & BREAKING DEVICE                      MCCB OR ACB (NOTE-8)
 107   PLUG BUSHING CONTACTS (Y / N)                           ***
 108   DISCONNECTING SWITCH (Y / N)                            NO
 109   SWITCH (Y / N)                                          NO
 110   CONTACTOR (Y / N)                                       YES
 111   FUSES (Y / N)                                           NO
 112   CIRCUIT BREAKER (Y / N)                                 YES
 113   START/STOP FROM IMCS & DCS                              YES
 114   TRIP COMMAND FROM ESD                                   YES
 115   MOTOR RUNNING INDICATION IMCS & DCS                     YES
 116   FOR CRITICAL & NON-CRITICAL MOTOR                       YES
 117                                                                      LABELS
 118   LANGUAGE ON DOCUMENTS                                   ENGLISH
 119   LANGUAGE ON LABELS/EQUIPMENT                            DUTCH
 120   MAIN LABEL (FRONT / BACK)                               FRONT
 121   FUNCTIONAL UNIT LABELS (FRONT / BACK)                   FRONT
 122   COLOUR                                                  WHITE BACKGROUND BLACK LETTERING
 123                                                            SWITCHGEAR ARRANGEMENT
 124   LENGTH / WIDTH / HEIGHT                                 *
 125   TOTAL WEIGHT                                            *
 126   HEAT LOSS                                               *
 127   NUMBER & SIZE OF UNITS                                  *
 128                                                        ACCESSORIES AND MISCELLANOUS
 129   MOUNTING CHANNELS & FIXING ACCESSORIES (Y / N)          YES
 130   LIFTING EYEBOLTS (Y / N)                                YES
 131   HANDLING TRUCK (Y / N)                                   NO
 132   SET OF SAFETY DEVICES (Y / N)                           NO
 133   DOOR LOCKING                                            YES
 134   PADLOCKING FACILITIES                                   YES
 135   GLAND PLATE                                             YES
 136   INTERNAL MAINTENANCE LIGHT WITH DOOR SWITCH             YES
 137   SPACE HEATER WITH THERMOSTAT                            YES
Datasheet for LV Switchgear                                                                                              6 of 6