DCDU16D-02 Hardware Description

The document describes a DCDU16D-02, which provides -48V DC power for telecom cabinet components. It is 1U high and can be installed in various cabinets. It has multiple DC output ports that provide power to devices like RRUs and BBUs within specific amperage limits per port. The document provides detailed specifications, diagrams, and configuration principles for the DCDU16D-02 module.

Uploaded by

Nenad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3K views7 pages

DCDU16D-02 Hardware Description

The document describes a DCDU16D-02, which provides -48V DC power for telecom cabinet components. It is 1U high and can be installed in various cabinets. It has multiple DC output ports that provide power to devices like RRUs and BBUs within specific amperage limits per port. The document provides detailed specifications, diagrams, and configuration principles for the DCDU16D-02 module.

Uploaded by

Nenad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

DCDU16D-02

Contents
6.4.3.4.17.2 DCDU16D-02

6.4.3.4.17.2 DCDU16D-02
A direct current distribution unit 16D-02 (DCDU16D-02) provides -48 V DC power for other
components in a cabinet. A DCDU16D-02 is 1 U high and can be installed in a 19-inch rack or
any of the following cabinets: APM5930, APM30H, TMC11H, BTS3900/BTS3900L,
BTS5900/BTS5900L, OMB (Ver.C), IMB03, and IMB05.

Configuration Principles
The following table describes configuration principles for the DCDU16D-02 in different
cabinets.

Table 1 DCDU16D-02 configuration principles

Base Station Cabinet Maximum Number Configuration


of Power Outputs Principle
for RRUs/AAUs

DBS3900 APM30H (Ver.D)/APM30H 3 1 DCDU16D-02


(Ver.E)/APM30H (Ver.E_B~D)/APM30H
(Ver.D_C)/APM30H (Ver.D_B)

TMC11H (Ver.E)/TMC11H 3 1 DCDU16D-02


(Ver.D)/TMC11H (Ver.E_B~D)/TMC11H
(Ver.D_B)/TMC11H (Ver.D_C)

OMB (Ver.C) DC 3 1 DCDU16D-02

IMB03 DC 3 1 DCDU16D-02

IMB05 DC 6 2 DCDU16D-02
modules

19-inch rack Depend on the site Depend on the site


configurations configurations
Table 1 DCDU16D-02 configuration principles

Base Station Cabinet Maximum Number Configuration


of Power Outputs Principle
for RRUs/AAUs

DBS5900 IMB05 DC 6 2 DCDU16D-02


modules

ILC29 (Ver.E) 9 3 DCDU16D-02


modules

APM5930(DC)/TMC11H (Ver.F_B~E) 6 2 DCDU16D-02


modules

BTS3900A APM30H (Ver.D)/APM30H 3 1 DCDU16D-02


(Ver.D_C)/APM30H (Ver.D_B)/TMC11H
(Ver.D)/TMC11H (Ver.D_B)/TMC11H
(Ver.D_C)/APM30H (Ver.E)/APM30H
(Ver.E_B~D)

TMC11H (Ver.E)/TMC11H (Ver.E_B~D) 3 1 DCDU16D-02

BTS3900 BTS3900 (Ver.D) DC 3 1 DCDU16D-02

BTS3900 (Ver.E_A~D) 3 1 DCDU16D-02

BTS5900A APM30H (Ver.E)/TMC11H (Ver.E) 3 1 DCDU16D-02

APM30H (Ver.F_B~E)/TMC11H 6 2 DCDU16D-02


(Ver.F_B~E) modules

BTS5900 BTS5900 (Ver.A) 6 2 DCDU16D-02


modules

BTS3900L BTS3900L (Ver.D) DC 3 1 DCDU16D-02

BTS3900L (Ver.E_A~D) 3 1 DCDU16D-02

BTS5900L BTS5900L (Ver.A) 6 2 DCDU16D-02


modules

BTS3900AL BTS3900AL DC/BTS3900AL AC 6 2 DCDU16D-02


modules

Exterior
The following figure shows the front and rear views of a DCDU16D-02.
Figure 1 Front and rear views of a DCDU16D-02

(1) Equipotential ground point (2) Ground point

The ground point or equipotential ground point on the DCDU16D-02 is used in the following scenarios:
 Scenario 1: A DCDU16D-02 is installed on an open rack. In this scenario, an equipotential cable connects the
equipotential ground point near the mounting ear on the DCDU16D-02 to the ground bar on the open rack.
 Scenario 2: A DCDU16D-02 is installed on a wall as a standalone power distribution device. In this scenario, the
ground point at the rear of the DCDU16D-02 is connected to the ground bar in the equipment room.

Port and Terminal


The following figure shows the ports and terminals on a DCDU16D-02.
Figure 2 Ports and terminals on a DCDU16D-02

The following table describes the ports and terminals on a DCDU16D-02.

Table 2 Ports and terminals on a DCDU16D-02

No. Port and Silkscreen Connector and Cable Description


Terminal

(1) DC input  NEG(-) Two one-hole OT  Negative power input


terminals  RTN(+) terminals (M6). One terminal
group of power cables  Positive power input
with a maximum cross- terminal
sectional area of 35
mm2 (0.054 in.2) or two
groups of power cables
with a maximum cross-
sectional area of 25
mm2 (0.039 in.2) are
supported.

(2) Circuit LOAD0 to LOAD2 Bare wires. The For the specifications of DC
breaker output supported cable cross- outputs, see Table 3.
portsa sectional area ranges
from 6 mm2 to 16.7
mm2 (0.0093 in.2 to
0.026 in.2).

(3) Fuse blocksb LOAD3 to LOAD6 - It controls the LOAD3 to


LOAD6 ports, and therefore
controls the power supply to
modules such as BBUs,
Table 2 Ports and terminals on a DCDU16D-02

No. Port and Silkscreen Connector and Cable Description


Terminal

transmission equipment, and


fan assemblies.

(4) DC output LOAD3 to LOAD6 EPC4 connectorsc are For the specifications of DC
ports used for the LOAD3 to outputs, see Table 3.
LOAD6 ports. Figure 3
shows the exterior. The
supported cable cross-
sectional area ranges
from 1.5 mm2 to 4 mm2
(0.0023 in.2 to 0.0062
in.2).

(5) Spare fuse box - - It contains two 30 A spare


fuses.

a: The wiring terminals of circuit breakers must be connected to cables onsite.


b: The indicator on the fuse block indicates the status of the fuse. When the indicator is steady on, the
fuse is faulty and must be replaced. When the indicator is steady off, the fuse is working properly.
c: EPC4 connectors must be connected to cables onsite.

 Do not connect cables less than 6 mm2 (0.0093 in.2) to the LOAD0 to LOAD2 output ports.
 Do not install modules with ports on a DCDU16D-02 panel vertically facing upwards or
downwards.

A fuse block and a DC output terminal are jointly called a fuse terminal block.

Figure 3 Exterior of an EPC4 connector

The following table describes the power distribution of the DC output terminals on a DCDU16D-
02.
Table 3 Power distribution of the DC power output terminals on a DCDU16D-02

DC Output Terminal Power-Consuming Equipment Circuit Breaker/Fuse


Specifications

LOAD0 to LOAD2 RRU 3x50 Aa

LOAD3 to LOAD6 Transmission equipment, BBU, 4x30 Ab


or FAN

a: Each power output is less than or equal to 50 A.


b: Each power output is less than or equal to 25 A, and the total power output is less than or equal to 60
A.

Technical Specifications
The following table lists the technical specifications of a DCDU16D-02.

Table 4 Technical specifications of a DCDU16D-02

Item Specifications

Dimensions (H x W x D) A DCDU16D-02 is 1 U high with a case structure and can be


installed in a 19-inch cabinet or rack. The DCDU16D-02
dimensions are as follows:
 43.6 mm x 442 mm x 150 mm (1.72 in. x 17.40 in. x 5.91
in.) (without mounting ears)
 43.6 mm x 482.6 mm x 150 mm (1.72 in. x 19 in. x 5.91 in.)
(with mounting ears)

Weight 2 kg (4.41 lb)

Input voltage and current Input voltage: -48 V DC


Input current: 200 A

-48 V output power  3x50 A circuit breakers are used for the power distribution.
(The output current of one circuit cannot exceed 50 A.)
 4x30 A fuses are used for the power distribution. (The
output current of one circuit cannot exceed 25 A, and the
total current cannot exceed 60 A.)

Operating temperature -40°C to +60°C (-40°F to +140°F)

Ingress protection rating IP20

Surge protection specifications Surge voltage on the -48 V DC power port


Table 4 Technical specifications of a DCDU16D-02

Item Specifications

 Differential mode: 2 kV (1.2/50 μs)


 Common mode: 4 kV (1.2/50 μs)

Surge current on the -48 V DC power port


 Differential mode: 10 kA (8/20 μs)
 Common mode: 20 kA (8/20 μs)

Parent Topic: DCDU