Protective Relaying
Protective Relaying
Module II
EE401 Switchgear and Protection
7th Sem. EEE
Content
• Introduction to
• electromagnetic protective relaying,
• Between the electrical power generator and electrical loads, there are several
electrical equipment and machines of various ratings which need certain
adequate protection from abnormal current, voltage and other abnormality in
working parameters.
• The protective relaying senses the abnormal conditions in a part of the power
system and give alarm to isolate that part from the remaining healthy system.
• In a protective relaying system besides circuit breakers and relays there are
several other important components in the system, this include: current and
voltage transformers, secondary circuits, trip circuits, auxiliaries and
accessories.
Contd.
• Function of protective relaying:
• For abnormal condition like over-load, under-voltage, temperature rise, under-frequency,
over-voltage, unbalanced load, reverse power, short-circuit etc. it senses and send a signal
to isolate the faulty part or energizes the trip circuit of CB.
• To isolate the faulty part immediately so as to minimize the damage to faulty part and
stable operation of rest of the healthy part of the system.
• To localize the effect of fault by disconnecting it from healthy part of the system.
• Protective zones – A part of the system protected by a certain protective
scheme is called as protective zone or zone of protection.
• Based on machine rating, its location, relative importance, probability of faults and
abnormal condition etc. each power system component is covered by a protective zone.
• The boundary of the protective zone is determined by the location of current transformer.
The current transformer are located such that the CBs are covered in the protective zones.
Contd.
• Breaker back-up – Different breakers are provided for main and back-up protection in the same station.
• Remote back-up – The main and back-up protections provided at different station and are completely independent.
• Centrally coordinated back-up – Main protection is at various stations and back-up protection for all stations is at central
control center.
• Back-up protection by time grading principle – The current is measured at various points along the current path, the
tripping time at these locations are graded in such a way that the circuit breaker/fuse nearest the fault part operate first,
giving primary protection. The CB at previous station operates only as back-up.
• Back-up protection by duplication principle – The important protective devices are duplicated. Both primary and back-up
protections are provided at the same station and are arranged to operate at the same speed.
• The possibility of failure to operate and failure of relays and circuit breaker should be considered in determining the selectivity of the relays.
• Speed – fault clearing time is the sum of relay-time and circuit breaker time.
1 1 1 1
• Fault Clearing Time = Time of operation of Relay + Time of operation of CB = 2 𝑐𝑦𝑐𝑙𝑒 𝑡𝑜 1 2 𝑐𝑦𝑐𝑙𝑒𝑠 + 2 2 𝑐𝑦𝑐𝑙𝑒𝑠 𝑡𝑜 3 2 𝑐𝑦𝑐𝑙𝑒𝑠 = 4cycles
• Though fast fault clearing is desirable, time lag is purposely provided to permit discrimination between main and back-up protection, and to prevent operation of
relay during transients. Typically, a high-speed relay can operate in the range of 10 to 30 milliseconds.
• Sensitivity – it is defined by the smallest value of actuating quantity at which the protection starts operating in relation with the minimum value
of fault current in the protected zone. Sensitivity of relay and sensitivity of system are different. S
• Discrimination - Fault/Overload, Induction Motor winding fault/Starting Current, Transformer Winding fault/Inrush current.
• Stability – by the virtue of which the protective system remains in operation and stable under certain specified condition.
• Reliability – the protective relaying should not fail to operate in the event of faults in the protected zone, and there should not be any fault in the
components of the protective system.
• Economics – the cost of protective equipment should not be more than 10% of the cost of protected device/equipment.
Relay – device by means of which an electric circuit is controlled, by change in the other
Electromechanical relay, Static Relay, Biased Relay
circuit.
Protective Relay – electrical relay used for protecting electrical devices. It closes its Power consumption of a relay – value of power consumed expressed in VA
contacts when operating quantity reaches certain predetermined magnitude/phase. (for a.c.) or watts (for d.c.)
Pick-up: Pick-up value or level is the value of operating quantity which is
Measuring Relay – Operates at a predetermined value of operating quantity by
on threshold above which the relay operates and closes its contacts.
performing the necessary measurement. (if not, then such relay is called as all-or-nothing
Reset, drop-out: the value of actuating quantity below which the relay
relay).
resets and comes back to original position.
Trip Circuit – consist of mainly trip coil, relay contacts, auxiliary switch, seal in coil, Over-current relay, Earth-fault relay
battery supply, it controls the CB for opening operation.
Distance protection – protection of transmission line in which the relay
Current Transformer (CT) and Voltage or Potential transformer (PT)
measurement is based on measuring V/I ratio at relaying point.
Differential Protection – A protective system which responds to vector
Auxiliary Switch – A multipoint switch which operates in conjunction with CB and
difference (phase/magnitude) between two or more similar electrical
connects/disconnects certain protective, indicating and control circuits in each position.
quantities.
Unit Protection – Protection system in which the protective zone can be
Fault Clearing Time, Relay Time, Breaker Time clearly identified by means of CT boundaries. Such protection does not
respond to through fault, it responds only to internal faults.
Reach – the limiting distance covered by the protection, the faults beyond
Earth Fault, Phase Fault which are not within the reach.
Over-reach, Under-reach
Instantaneous relay, IDMT Relay
Relay, classifications and type
• Relay (Protective relay)
• Relays are devices that respond to signals from sensors (voltage, current, temperature, etc.) and operate contacts based on predetermined criteria.
These contacts are usually wired to the trip coil of a circuit breaker or a lockout relay. A relay can also be used as a control device to operate a
circuit breaker after a preset time interval (IEEE Std C37.90™-1989 [B42]).
• Classification based on technology
• Electromechanical relays
• Static relays
• Numerical relays.
• Classification based on speed of operation
• Instantaneous relays
• Time delay relays
• High-speed relays
• Ultra high-speed relays.
• Classification based on function
• Overcurrent relays
• Undervoltage relays
• Impedance relays
• Underfrequency relays
• Directional relays
Electromechanical Relay
• Can be used for both AC and DC , relay have fast operation and fast reset because of small length of travel and light moving parts.
• These relays are described as instantaneous, but operating time may vary with current.
• For typical relay the VS burden is of the order of 0.2 to 0.6 VA for current range 0..1 to 0.4 A.
• These relays are sensitive to starting currents, load fluctuations and current surges.
• Operating Principle: The electromagnetic force exerted on the moving element is proportional to square of the
flux in air gap. Neglecting the saturation, the force is proportional to the square of the operating current.
𝐾2
• When relay is on the verge of operation, F is zero, 𝐾1 𝐼2 = 𝐾2 , 𝐻𝑒𝑛𝑐𝑒, 𝐼 = 𝑎 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡.
𝐾1
Contd.
• Application of attracted armature type relay:
• Used for over/under current, over/under voltage for both AC and DC application.
• Over-current protection.
• Definite-time lag over-current and earth fault protection.
• Differential protection
• Auxiliary relay.
Contd.
𝐼1 𝐾2
• At the verge of operation, net torque is zero, therefore 𝐾1 × 𝐼12 = 𝐾2 × 𝐼22 , = =
𝐼2 𝐾1
𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡.
𝑉1
• If one coil is actuated by voltage (𝑉1 ) and other by current (𝐼2 ) then, the equation is, =𝐾=
𝐼2
𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡.This principle is used in impedance relay.
• Balanced beam relay is difficult to design over a wide range current because the force is
proportional to current in restraining coil.
𝒅𝝋𝟏
• 𝒆𝟏 ∝ , 𝒆𝟏 ∝ 𝝋𝒎 𝝎 𝐜𝐨𝐬 𝝎𝒕 , 𝑎𝑛𝑑 𝒆𝟐 ∝ 𝝋′𝒎 𝝎 𝐜𝐨𝐬(𝝎𝒕 + 𝜽)
𝒅𝒕
• Since the eddy current is proportional to the induced voltage, 𝒊𝟏 ∝ 𝒆𝟏 and 𝒊𝟐 ∝ 𝒆𝟐 , 𝒊𝟏 ∝ 𝝋𝒎 𝝎 𝒄𝒐𝒔 𝝎𝒕,
𝒊𝟐 ∝ 𝝋′𝒎 𝝎 𝒄𝒐𝒔(𝝎𝒕 + 𝜽).
• The flux 𝜑1 will interact with eddy current 𝑖2 and 𝜑2 will interact with 𝑖1 and since 𝜑2 is leading 𝜑1 the
torque due to 𝜑2 and 𝑖1 will be reckoned as positive whereas that due to 𝜑1 and 𝑖2 as negative.
• The resultant torque is 𝑻 ∝ 𝝋𝟐 𝒊𝟏 − 𝝋𝟏 𝒊𝟐 , 𝑻 ∝ 𝝋𝒎 𝝋′𝒎 𝐬𝐢𝐧 𝜽. So the torque is maximum when the two
fluxes are displaced by 90𝑜 .
• The shading ring is a copper band or coil. The effect of the shading ring is to displaced the flux in
phase and space from the flux produced by unshaded pole.
• Since 𝜑2 leads the 𝜑1 , the rotation of the disc under the poles will be from unshaded pole towards the
shaded pole.
• Since the torque is of constant magnitude, therefore, there is no possibility of vibration.
Contd.
• The watt-hour meter structure has two separate coils on two different magnetic
circuits, each of which produces one of the two necessary fluxes for driving the disc
of the relay. The operating principle is same as that of shaded pole type.
Induction cup relay
• This relay has two, four or more electromagnets, in stator. A stationary iron core is placed
between these electromagnets. The rotor consists if a hollow metallic cylindrical cup. The
rotor is free to rotate in the gap between the stationary iron and the electromagnets.
• The electromagnets are energized by the relay coils. The eddy currents are produced in the
metallic cup. These currents interact with the flux produced by the other electromagnet and
torque is produced.
• The operating principle is same as that of disc type relay.
• A control spring and moving contacts are carried on an arm attached to the spindle of the
cup.
• The relay can be responsive to voltage or current.
• The relays have inverse time characteristic.
Contd.
• For simple protective functions and for protection of simple low power
equipment, electromechanical relays are preferred.
• Electromechanical relays are also used as components of static relay, e.g.
for auxiliary relay function, output function.
• For complex protective functions requiring accurate characteristics for
various protective functions and for protection of costly, large equipment,
static relays are preferred.
• For integrated protection and monitoring systems programmable
microprocessor-controlled relays are preferred.
Operating Characteristics
• Determine the time of operation of a relay of rating 5 amps, 2.2 sec IDMT and having a relay setting of
125% TMS = 0.6. It is connected to a supply circuit through a CT 400/5 ratio. The fault current is
4000A.
• 𝑇ℎ𝑒 𝑝𝑖𝑐𝑘 −
𝑢𝑝 𝑣𝑎𝑙𝑢𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑟𝑒𝑙𝑎𝑦 𝑖𝑠 5𝐴 𝑏𝑢𝑡 𝑠𝑖𝑛𝑐𝑒 𝑡ℎ𝑒 𝑟𝑒𝑙𝑎𝑦 𝑠𝑒𝑡𝑡𝑖𝑛𝑔 𝑖𝑠 125%, 𝑡ℎ𝑒𝑟𝑒𝑓𝑜𝑟𝑒, 𝑡ℎ𝑒 𝑜𝑝𝑒𝑟𝑎𝑡𝑖𝑛𝑔 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 𝑜𝑓 𝑡ℎ𝑒 𝑟𝑒𝑎𝑙𝑦 𝑖𝑠
𝑆𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 𝐶𝑢𝑟𝑟𝑒𝑛𝑡
• 5 × 1.25 = 6.25𝐴, 𝑡ℎ𝑒 𝑝𝑙𝑢𝑔 𝑠𝑒𝑡𝑡𝑖𝑛𝑔 𝑚𝑢𝑙𝑡𝑖𝑝𝑙𝑖𝑒𝑟 𝑜𝑓 𝑡ℎ𝑒 𝑟𝑒𝑙𝑎𝑦, 𝑃𝑆𝑀 =
𝑅𝑒𝑙𝑎𝑦 𝑐𝑢𝑟𝑟𝑒𝑛𝑡 𝑠𝑒𝑡𝑡𝑖𝑛𝑔
• 𝑆𝑖𝑛𝑐𝑒 𝑡ℎ𝑒 𝑇𝑀𝑆 𝑖𝑠 0.6, 𝑡ℎ𝑒 𝑎𝑐𝑡𝑢𝑎𝑙 𝑜𝑝𝑒𝑟𝑎𝑡𝑖𝑛𝑔 𝑡𝑖𝑚𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑟𝑒𝑙𝑎𝑦 𝑖𝑠 1.92 𝑠𝑒𝑐.
Static Relay
• Static relay is an electrical relay in which the response is developed by
electronic/magnetic/optical or other components, without mechanical
motion of components.
Contd.
• A static relay generally has several functional units.
• A static relay may have one or more programmable units such as a microprocessor. Such relays are
called as programmable relays or microprocessor-controlled relay.
• Advantages of static relays
• Low power consumption, Low burden
• No moving contacts
• Fast response
• Less maintenance
• Single relay for several functions
• Compact
• Precise and accurate
• Interface with SCADA and EMS
• Logic circuit can be used for complex protective scheme.
• Disadvantages of static relays
• Auxiliary voltage requirement
• Temperature sensitive
• Sensitive to voltage transients
Contd.
• Phase Comparator – it compare the two (or more) input quantities vectorially. There are two kinds
of phase comparators
• One which recognises only phase angle between the input waveforms
• Other, which recognises the vector product (or division) between two (or more) input quantities.
• Let A and B be two vectors and φ be the phase difference between the two, then 𝜑 = 0 𝑖𝑓 𝐴 + 𝐵 =
𝐴 − 𝐵 , 𝜑 < 900 𝑖𝑓 𝐴 + 𝐵 > 𝐴 − 𝐵 , 𝑎𝑛𝑑 𝜑 > 900 if 𝐴 + 𝐵 < 𝐴 − 𝐵 .
Contd.
https://crushtymks.com/sv/protection/1405
B. Osorno, "Application of Microprocessor Based Protective Relays in Power Systems," -the-essentials-of-numerical-relays-their-features-and-important-considerations.html
2009 IEEE Industry Applications Society Annual Meeting, Houston, TX, USA, 2009, pp. 1-8, doi: 10.1109/IAS.2009.5324898.
Thermal Relay
• Used to protect device/equipment from overloading.
• The electromechanical thermal relay uses heat sensitive material like
bimetallic strip. The bimetallic strip open/close the contacts
mechanically.
• The solid state or static relay monitors the current for operation.
• Some relays use thermistor or other such transducer to sense the heat
developed due to overloading.
Overcurrent Relay
• Over current relays sense fault currents and over-load currents.
• OC relays are connected to the system, normally by means of CTs.
• The instantaneous relay is more effective where the impedances between the source and the relay is small compared with the impedance of the section to be protected.
• These are normally more inverse near the pick-up value and become less inverse as it is increased.
• Directional unit
• Directional unit
• It is a four-pole induction cup unit. Two opposite poles are fed with voltage and other two poles are fed with current. The voltage is
taken as polarizing unit.
• The polarizing quantity is one which produces one of the two fluxes required for production of torque and this quantity is taken as
reference.
• Now if due to certain abnormality the current flow in opposite direction, the relay will develop positive torque and will operate.
Contd.
• If 𝜃 is greater than +90𝑜 and less than −90𝑜 the torque will be negative. The cup or disc will rotate in negative
direction, the movement will be hindered by backstop.
• When fault occurs, the angle between V & I varies between 70 to 90 (depends on fault location)
• 𝑇 ∝ 𝑉𝐼 cos 𝜃, 𝜃 → 70𝑜 𝑡𝑜 90𝑜 . The directional relay should be designated for maximum torque angle, decided based
on relay location from source.
• Most of the differential relays are current differential relays in which vector difference between the current entering the
winding and current leaving the winding is used for sensing and relay operation.
• Differential protection is generally unit protection. The protected zone is exactly determined by location of CTs or PTs.
• Application
• Protection of generator and generator-transformer
• Protection of transformer
• Bus-zone protection
• The ratio of the differential operating current to the average restraining current is a
fixed percentage. That is why it is called as percentage differential relay.
Contd.
Distance Relay
• Background – During a fault on a transmission line the fault current increases and the voltage at
fault point reduces. The voltage at PT location depends on the distance between PT and the
fault. If fault is nearer, measured voltage is lesser. If the fault is farther, measured voltage will
be more. Hence, assuming constant fault resistance each value of the ratio 𝑉Τ𝐼 measured from
relay location corresponds to distance between the relaying point and the fault along the line.
Hence such protection is called as distance protection.
• It is used for non-unit type protection.
• It includes following types of relay:
• Impedance relay
• Reactance relay
• MHO relays
• Angle impedance relays
• Quadrilateral relays
• Elliptical and other conic section relays.
Contd.