The document is a request for approval of addressable control relay modules to be used for the Adani DC1 Data Center Phase 2 project in Chennai. It includes a technical submittal with specifications of the proposed Simplex brand modules matching the project and tender requirements. Comments provided by Adani Connex ask for confirmation that the specifications meet project needs and that accessories are included, and request separate submittals if control module and relay module part codes are different.

Uploaded by

rajinirk4664
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views9 pages

Control Relay Model

The document is a request for approval of addressable control relay modules to be used for the Adani DC1 Data Center Phase 2 project in Chennai. It includes a technical submittal with specifications of the proposed Simplex brand modules matching the project and tender requirements. Comments provided by Adani Connex ask for confirmation that the specifications meet project needs and that accessories are included, and request separate submittals if control module and relay module part codes are different.

Uploaded by

rajinirk4664
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

REQUEST FOR APPROVAL OF MATERIAL

PROJECT : Date : 17-08-2022


Submittal No:
ADANI DC1 DATA CENTER PHASE 2, CHENNAI.
ACXDC1-JCI-PH2-FAS-TDS-003
To:
Reply Required By
M/s. ADANI CONNEX PVT LTD  New Submittal
Attention: Alternative
23-Aug-22
Mr. Malcolm Resubmittal

Ref. Doc. No.:


Contract Drawing No. (if applicable)
Description of Item Submitted Contract Specification / Supplier Proposed Specification / Supplier
Contract spec: Proposed Spec:
Addressable control relay modules as per Addressable control relay modules as per technical
technical specifications specifications

Addressable Control Relay Module

Approved make list: Proposed make list:

Submitted by: Premkumar V, JCI Simplex Simplex

Comments

The material / equipment submitted is hereby transmitted with actions as indicated.


Approved
✔ Approved Rejected resubmission
required

Approved with comments Approved with comments


no submission required Re-submission required
ACX COMMENT:
1. It should be complied project requirement.
Signature: 2. It should be inclusive of all required accessories.
3. Please confirm whether part code for CM and
CRM are same. If not then TDS for both the items
Name: Date: 26/08/2022
shall be submitted separately.
Distribution :

EPSILON ADANI

Page 1 of 9
TECHNICAL SUBMITTAL

CONTRACTOR CLIENT CONSULTANT

JCI ADANI CONNEX EPSILON

PROJECT : M/s. ADANI DC1 DATA CENTER PHASE 2 AT CHENNAI. DATE : 17-08-2022

DOCUMENT NO : ACXDC1-JCI-PH2-FAS-TDS-003 REVISION : 00

MATERIAL DESCRIPTION : Addressable Control Relay Module

TENDER MAKE : Simplex

SL.NO PARAMETERS SPEC. AS PER PROPOSED MAKE REMARKS

1 Proposed Make Simplex

2 BOQ Ref No FAS BOQ_Part 1 A.1.10 & 1.11

3 Model Number 4090-9002

4 Communications IDNet communications, 1 address per device

5 Relay IAM Power Supplied by IDNet communications

6 Contact Type Form C, SPDT

7 Contact Rating Power-Limited 2 A @ 24 VDC, resistive

Screw terminals for in/out wiring,


8 Wire Connections
18 to 14 AWG wire (0.82 to 2.08 mm2)
4 ⅛” H x 4 ⅛” W x 1 ⅜” D
9 Dimensions
(105 mm x 105 mm x 35 mm)

10 Housing Material Black thermoplastic

11 Temperature Range 32° to 120° F (0° to 49° C), intended for indoor operation

12 Humidity Range Up to 93% RH at 100° F (38° C)

13 Approvals UL, ULC, CSFM Listed; FM Approved

Enclosures:

1 BOQ Attached

2 Tech Spec Attached

3 Approved Make List Attached

4 Catalogue Attached

5 Sample Nil

COMMENTS (If any):

Page 2 of 9
ADANI CONNEX DC1 PHASE 2-SIRUSERI CHENNAI

Document number: ACXDC1-JCI-PH2-FAS-TDS-003 Rev no: 0

BOQ DESCRIPTION: -

FAS BOQ Part 1


1. FIRE ALARM & DETECTION SYSTEM
S.No. Item Description Qty Unit
Network Repeater panel (NRP) with minimum 168 character back lit
super twist LCD display with system function keys like system reset.
Alarm acknowledge, Alarm Silence, Trouble Acknowledge etc. The
NRP shall be networkable with main FAS panel & shall seat on
1.5 3 Nos.
dedicated FAS Ring network as per specifcation.

Also, all Phase-2 NRP Panel shall communicate with existing NRP
Panel.

1.9 Addressable monitor module as per technical specifications. 296 Nos.

1.10 Addressable control modules as per technical specifications 165 Nos.

1.11 Addressable control relay modules as per technical specifications 194 Nos.

Supply installation Testing & commissioning of Zone Monitor Modules


1.12 53 Nos.
with all mounting accessories
Modular type Duct detectors ideally suitable for smoke detection
application within the confined space of ventilation ducts. Detectors
shall be “UL” listed. It shall possible to provide early warning to prevent
1.16 smoke from circulating through out the building. Detectors shall 7 Nos.
continuously sample air flow in the HVAC duct and initiate an alarm
whenever smoke detected The duct detector shall be as per technical
specification. The detectors shall be of UL listed.
Addressable type Manual dual action (Push IN-Pull DOWN) Flush or
surface mounted addressable Manual Call Point in manufacturers
1.17 prescribed matching red enamel outlet box complete with key 83 Nos.
operated test-reset lock. The word FIRE shall appear in front of station
as per technical specifications
Surface mounted addressable type fully solid state circuitory dual tone
1.18 Electronic loud speakers with strobe lights of 110 Cd intensity as per 214 Nos.
technical specifications
1.20 Addressable Fault Isolation Module as per specifications 189 Nos.

1.22 Fire fighters Telephone jack as per technical specifications. 9 Nos.


Ceiling Mounted Speakers / Cold Asile Area Speakers of 2W rating
1.23 with multiple wattage tapping of 2 / 1 / 0.5W with all necessary 111 Nos.
mounting accessories complete as required.
Fire fighters Telephone Handset as per technical specifications.
1.26 9 Nos.
(used while during the Fire case).

1.27 Weather Proof MCP for External Area 3 Nos.

RI Mimic Panel For Dc Hall False Floor Devices With Enclosure For
1.29 3 Nos.
Concealed Installation

Page 3 of 9
ADANI CONNEX DC1 PHASE 2-SIRUSERI CHENNAI

Document number: ACXDC1-JCI-PH2-FAS-TDS-003 Rev no: 0

TECHNICAL SPECIFICATION: -

Page 4 of 9
ADANI CONNEX DC1 PHASE 2-SIRUSERI CHENNAI

Document number: ACXDC1-JCI-PH2-FAS-TDS-003 Rev no: 0

Page 5 of 9
ADANI CONNEX DC1 PHASE 2-SIRUSERI CHENNAI

Document number: ACXDC1-JCI-PH2-FAS-TDS-003 Rev no: 0

Page 6 of 9
ADANI CONNEX DC1 PHASE 2-SIRUSERI CHENNAI

Document number: ACXDC1-JCI-PH2-FAS-TDS-003 Rev no: 0

APPROVED MAKE LIST:

Page 7 of 9
Multi-Application Peripherals
UL, ULC, CSFM Listed; FM Approved; IDNet Communicating Devices
MEA (NYC) Acceptance* Model 4090-9002 Relay IAM

Features
Individual Addressable Relay Module (Relay IAM):
 IDNet addressable control for use with Simplex® fire
alarm control panel models 4007ES, 4008, 4010,
4010ES, 4100ES, and 4100U
 A single addressable point provides control and status
tracking of a Form “C” contact
 Low power latching relay design allows IDNet
communications to supply both data and module power
 Relay is set to OFF on initial power up and upon loss of
IDNet communications
Compact, sealed construction:
 Enclosed design minimizes dust infiltration
 Mounts in standard 4” (102 mm) square electrical box, 4090-9002 IDNet Relay IAM Package
(shown approximately 1/2 size)
optional adapter bracket is available to mount in a
4 11⁄16” (119 mm) square electrical box Specifications
 Screw terminals for wiring connections
 Visible LED flashes to indicate communications IDNet communications, 1 address per
Communications
 Optional covers are available to allow LED to be device
viewed after installation Relay IAM Power Supplied by IDNet communications

UL listed to Standard 864 Contact Ratings* (not rated for incandescent switching)
Type Form C, SPDT
Description 2 A @ 24 VDC, resistive from listed
Power-Limited fire alarm
IDNet Relay IAMs allow fire alarm control panels to 1 A @ 24 VDC, inductive supply
control a remotely located Form “C” contact using IDNet
addressable communications for both data and module Nonpower-Limited 0.5 A @ 120 VAC, resistive
power. Typical applications would be for switching local * Provide circuit fusing and transient suppression as
power for control functions such as elevator capture, or required per application. DC inductive loads can typically
control of HVAC components, pressurization fans, be diode suppressed; 120 VAC loads may require RC
networks or varistors, depending on device type. Refer to
dampers, etc. Relay status is also communicated requiring
the installation instructions for additional information.
only one device address.
Screw terminals for in/out wiring,
Wire Connections
18 to 14 AWG wire (0.82 to 2.08 mm2)
Product Selection
Up to 2500 ft (762 m) from control
Model Description panel
4090-9002 Relay IAM IDNet
Up to 10,000 ft (3048 m) total wiring
Communications
distance (including T-Taps)
Optional Adapter and Trim Plates Wiring Reference
Compatible with Simplex 2081-9044
Model Description Overvoltage Protectors
Adapter plate to fit 4 11⁄16” (119 mm) square 4 ǩ” H x 4 ǩ” W x 1 Ǫ” D
4090-9813 Dimensions
electrical box (105 mm x 105 mm x 35 mm)
For semi-flush Trim Plate, galvanized Housing Material Black thermoplastic
4090-9801
mounted box steel, with LED viewing Mounting Plate Sheet metal, galvanized
For surface window; includes
4090-9802 mounting screws Temperature 32° to 120° F (0° to 49° C),
mounted box
Range intended for indoor operation
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to Humidity Range Up to 93% RH at 100° F (38° C)
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7300-0026:223 for allowable values and/or conditions concerning material presented in this Installation
574-184
document. Accepted for use – City of New York Department of Buildings – MEA35-93E. Instructions
Additional listings may be applicable; contact your local Simplex product supplier for the
latest status. Listings and approvals under Simplex Time Recorder Co. are the property of
Tyco Fire Protection Products.

S4090-0002-10 11/2014
Page 8 of 9
Relay IAM Mounting Information

Address setting under


resealable label

4" (102 mm) square box, 2-1/8"


(54 mm) minimum depth, RACO
232 or equal (supplied by others)

4090-9002 Relay IAM

Double gang blank cover plate and mounting screws, for


use when LED is not required to be externally viewed
(supplied by others)

Mounting Reference, Double Gang Blank Cover Plate

Light pipe for LED viewing

4-9/16" 4-5/16"
(116 mm) (109 mm)

4-9/16" (116 mm) 4-5/16" (109 mm)

4090-9801, Trim plate for 4090-9802, Trim plate for


semi-flush mounted box surface mounted box

Optional Trim Plates for Visible LED

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4090-0002-10 11/2014


www.simplex-fire.com
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Page 9 of 9