fail-safe controller
with 3SK1
Siemens
SIMATIC/ SIRIUS Safety Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/81353885 Support
This entry is from the Siemens Industry Online Support. The general terms of use
(http://www.siemens.com/terms_of_use) apply.
Security Siemens provides products and solutions with industrial security functions that
informa- support the secure operation of plants, systems, machines and networks.
tion In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial security concept. Siemens’ products and solutions only
form one element of such a concept.
Customer is responsible to prevent unauthorized access to its plants, systems,
machines and networks. Systems, machines and components should only be
connected to the enterprise network or the internet if and to the extent necessary
and with appropriate security measures (e.g. use of firewalls and network
segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should be
taken into account. For more information about industrial security, please visit
http://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them
more secure. Siemens strongly recommends to apply product updates as soon
as available and to always use the latest product versions. Use of product
versions that are no longer supported, and failure to apply latest updates may
increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial
Siemens AG 2018 All rights reserved
Table of content
1 Question ............................................................................................................. 3
1.1 Answer.................................................................................................. 3
2 Introduction ........................................................................................................ 4
2.1 Application examples ........................................................................... 4
2.2 Introduction to 3SK1 safety relays ....................................................... 6
2.3 Sensor parameter assignment on 3SK1 .............................................. 7
2.4 Configuration of the safe S7 input modules ......................................... 8
2.4.1 Parameters for single-channel connection ........................................... 8
2.4.2 Parameters for two-channel connection ............................................. 10
3 Typical circuit diagrams for single-channel connection up to SIL 2/
PL d ................................................................................................................... 12
3.1 Connection via 3SK1 Standard/ Adv. transistor outputs .................... 12
3.2 Connection via 3SK1 relay outputs .................................................... 13
4 Typical circuit diagrams for two-channel connection up to SIL 3/ PL
e ......................................................................................................................... 14
4.1 Connection via 3SK1 Standard/ Adv. transistor outputs .................... 14
4.2 Connection via 3SK1 relay outputs .................................................... 15
Signal distribution to two fail-safe PLCs for SIL 3/ PL e .................................... 16
5 Contact person/Support.................................................................................. 17
1 Question
How can I multiply inputs of a fail-safe controller or read in sensors with voltages
other than 24 V DC to a failsafe PLC?
1.1 Answer
The SIRIUS 3SK1 safety relays offer such an option with their basic unit and input
expansion modules. This means you can expand the number or connectable
sensors for each F-input terminal of the fail-safe controller. This FAQ shows the
different options for using the 3SK1 device series as input expansion modules.
Siemens AG 2018 All rights reserved
2 Introduction
Figure 2-1
Higher-level sensors
Siemens AG 2018 All rights reserved
Preprocessing by
3SK1
Figure 2-2
Coupling to SIMATIC
F-modules
The 3SK1 Advanced device series is characterized by the fact that it can be
expanded by modular device connectors. This means it is possible, for example, to
expand a basic unit by up to five input expansion modules with two safe inputs
each. The connected sensors are evaluated by the input expansion module and
forwarded to the basic unit by the device connector. The basic unit combines the
enabling signals of all input expansion modules with its own input signals and
switches off the enabling circuits (relay or electronically) when a sensor is
triggered.
3SK1 Input
3SK1 Standard 3SK1 Advanced
expansion module
Siemens AG 2018 All rights reserved
- Relay outputs
- Relay outputs
- Solid-state outputs
Outputs - Solid-state outputs
- Delayed/instantaneous
- Instantaneous outputs
outputs
- 24 V AC/DC
Voltages - 24 V DC - 24 V DC
- 110 to 240 V AC/DC
-1 (on device
Enabling circuits - Up to 3 - Up to 4
connector)
- 22.5 mm
Overall width - 22.5 mm
- 17.5 mm (3SK1120-xAB40) - 17.5 mm
The 3SK1 basic units (except 3SK1111) come equipped with four DIP switches on
the front. The device parameters are set with these switches depending on the
sensor type. The parameters are explained below.
evaluation) between the sensor inputs. Depending on the required safety level,
either two separate sensors (2*1-channel) or one redundant sensor (1*2-channel)
can be evaluated.
Safety relays can be connected in front of all safe input modules of the SIMATIC
S7. The modules of the ET200M, ET200S, and ET200SP series are listed below.
ET200M
24F-DI: 6ES7 326-1BK02-0AB0
ET200S
4/8 F-DI: 6ES7 138-4FA04-0AB0
2/4 F-DI; 3F-DO: 6ES7 138-4FC01-0AB0
ET200SP
8 F-DI: 6ES7 136-6BA00-0CA0
With single-channel connection of the 3SK1, the implemented safety function can
achieve a maximum of SIL 2 according to IEC 62061 or PL d according to ISO
13849-1. The shown parameters apply to the fail-safe input modules of the ET200S
and ET200M.
ET200S & ET200M in Step 7 V5.5 in connection with Distributed Safety V5.4
With two-channel connection of the 3SK1, the implemented safety function can
achieve a maximum of SIL 3 according to IEC 62061 or PL e according to ISO
13849-1. This is not the case when using the ET200S mixed module 2/4F-DI; 3F-
DO, because it is limited to SIL 2/
PL d. The shown parameters apply to the fail-safe input modules of the ET200S
and ET200M.
ET200S & ET200M in Step 7 V5.5 in connection with Distributed Safety V5.4
Behavior at
Supply 0-value
discrepancy Supply 0-value
The fail-safe input modules of the described distributed I/Os are schematically
shown in the typical circuit diagrams below. There may be deviations in the wiring
of the module supply voltage (e.g., supply by means of power module for ET200S).
This is not shown in detail for simplicity's sake. For detailed information, refer to the
respective manuals.
The parameters of the F-DI modules are assigned according to chapter 2.4.1.
Figure 3-1
Siemens AG 2018 All rights reserved
E-Stop
F-DI Modul
SET / RESET
A2 Q1 Q2 Q3 QM1
L+ (24V DC)
NOTE For SIL 2/ PL d, the control lines between the 3SK1 output (transistor) and the
input of the SIMATIC fail-safe module must be laid shielded (in the same control
cabinet or armored conduit, etc.). If this is not the case, redundant wiring (see
chapter 3.3) must be also be installed for SIL 2/ PL d.
Figure 3-2
E-Stop
F-DI Modul
SET / RESET
A2 14 24 34 42
Siemens AG 2018 All rights reserved
L+ (24V DC)
Figure 3-3
E-Stop
L/+
F-DI Modul
Autostart /
Monitored Start
A2 14 24 34 42
N/-
L+ (24V DC)
Two safe inputs in the distributed I/O are required for a two-channel design. The
channel pairs are permanently defined and cannot be changed. For an input
module with 8 fail-safe inputs, for example, one channel pair has the inputs “0” and
“4”.
Parameter assignment of the F-modules according to chapter 2.4.2.
Figure 4-1
E-Stop
F-DI Modul
SET / RESET
A2 Q1 Q2 Q3 QM1
L+ (24V DC)
Figure 4-2
E-Stop
F-DI Modul
SET / RESET
A2 14 24 34 42
Siemens AG 2018 All rights reserved
L+ (24V DC)
Figure 4-3
Figure 4-4
E-Stop
F-DI Modul
SET / RESET
A2 Q1 Q2 Q3 QM1
F-DI Modul
Siemens AG 2018 All rights reserved
L+ (24V DC)
Figure 4-5
E-Stop
VSX VSY
3SK1211-*BB40
F-DI Modul
SET / RESET
34 14
A2 14 24 34 42 A2 14 24 34
DIX DIY
SPS 2
F-DI Modul
L+ (24V DC)