The document provides contact information for a project located at 360 West Aspen Avenue in Salt Lake City, Utah. It states that the designs in the document are proprietary and cannot be copied or commercially exploited without written permission from Method Studio Inc. The project involves an expansion for Utah State University's EVR program located at 670 East 1550 North in Logan, Utah.

Uploaded by

kksmsksk8
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
321 views167 pages

Usu Aspire Evr Bid Drawings 20230307

The document provides contact information for a project located at 360 West Aspen Avenue in Salt Lake City, Utah. It states that the designs in the document are proprietary and cannot be copied or commercially exploited without written permission from Method Studio Inc. The project involves an expansion for Utah State University's EVR program located at 670 East 1550 North in Logan, Utah.

Uploaded by

kksmsksk8
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 167

360 west aspen avenue

salt lake city, utah 84101


801 532 4422

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
Conceptual Rendering for Reference Only & Not for Actual Construction. MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.

USU EVR EXPANSION project:

USU EVR
EXPANSION
BID SET - 02.14.2023
owner structural 1600 N
utah state university | aspire arw engineers
USTAR 620
670 east 1550 north 1594 w park circle #100 670 EAST 1550 NORTH, LOGAN, UT
logan, ut 84341 ogden, ut 84404 USTAR 650
84341
(435) 797-4949 (801) 782-6008 INOVAR

contact: regan zane contact: doc moyle


INNOVATION CAMPUS 1550 N

p r o j e c t # : 21.0320
architect mechanical engineer URSURF
ASPIRE ELECTRIC VEHICLE & ROADWAY
EXPANSION
d a t e : 02.14.2023

method studio van boerum & frank associates revisions :


360 w aspen ave 40 w cache valley blvd. 1, ste b 1 Review Responses 03.06.2022

salt lake city, ut 84101 logan, ut 84341

650 E

700 E
(801) 532-4422 (435) 770-1041
contact: matt wallace contact: ray vernon

PROJECT LIMITS

civil engineer electrical engineer


title:
civil solutions group spectrum engineers
498 west 100 south
providence, ut 84332
324 s state st #400
salt lake city, ut 84111
COVER
(435) 760-2986 (801) 328-5151 1400 N
SHEET
contact: tyler munk contact: chris koybashi

landscape architect c.m.g.c.


civil solutions group gramoll construction ADD ALTERNATES DEFERRED SUBMITTALS / DELEGATED DESIGN
498 west 100 south 155 s 750 w st. 1. RTUs for the lab (base bid: swamp coolers) ● FIRE SUPPRESSION SYSTEMS June 16th, 2023 ● ATTACHMENT OF CABINETRY June 16th, 2023
providence, ut 84332 north salt lake, ut 84054 2.
3.
Paving at rooftop patio (base bid: stone ballast but structure sufficient for future paving)
Vertical sun fins at the east façade (base bid: no fins)


FIRE ALARM SYSTEMS
PATIO PAVERS & PEDESTAL SYSTEM (INCLUDES SEISMIC DESIGN)
June 16th, 2023
June 16th, 2023
● CURTAIN WALL FRAME & GLAZING
● METAL PANEL SYSTEM & ATTACHMENT
June 16th, 2023
June 16th, 2023
(435) 512-7312 (801) 295-2341 4. Overhead crane (structure in base bid is sufficient to accommodate, crane itself is the add-alt). ● MECHANICAL SEISMIC BRACING & ANCHORAGE June 16th, 2023 sheet:
5. PVC roofing in lieu of TPO (base bid: TPO) ● ELECTRICAL SEISMIC BRACING & ANCHORAGE June 16th, 2023
contact: jacob hendrickson contact: gary hansen ● EXTERIOR STEEL STUD FRAMED WALLS June 16th, 2023

DEFERRED SUBMITTALS SHALL BE SUPPLIED TO THE BUILDING OFFICIAL FOR REVIEW WITH AN ACCOMPANIED LETTER FROM THE ARCHITECT STATING THAT THE DRAWINGS ARE IN
CONFORMANCE WITH THE DESIGN. THE WORK RELATED TO THE DEFERRED SUBMITTALS IS NOT TO COMMENCE UNTIL THE BUILDING OFFICIAL HAS APPROVED THE SUBMITTAL.

G000 BID SET


ABBREVIATION SCHEDULE ABBREVIATION SCHEDULE ARCHITECTURE SYMBOLS DRAWING INDEX DRAWING INDEX GENERAL NOTES - MISCELLANEOUS
Abbrev. Description Abbrev. Description
GENERAL 1 THE PROJECT MANUAL, UNDER SEPARATE COVER, IS AN INTEGRAL PART OF THESE CONSTRUCTION DRAWINGS.
Room name ROOM NAME
0 G000 COVER SHEET ELECTRICAL
A102 101 ROOM NUMBER G001 INDEX, GENERAL NOTES, LOCATION MAP, LEGENDS EE001 SHEET INDEX, ABBREV, SCOPE MATRIX & NOTES
# NUMBER OR POUND I W WALL FINISH 2 PLANS, SECTIONS, ELEVATIONS, DETAILS AND DIMENSIONS LABELED "TYPICAL" SHALL APPLY TO ALL SITUATIONS
& AND ID INSIDE DIAMETER SHEET NUMBER SEQUENCE G003 CODE ANALYSIS & CODE PLANS EE002 SYMBOLS LEGEND OCCURRING THAT ARE THE SAME OR SIMILAR TO THOSE SPECIFICALLY KEYED ON THE DRAWINGS.
B BASE FINISH
2:1 SL 2 HORIZONTAL TO 1 VERTICAL SLOPE IE INVERT ELEVATION FLOOR FINISH G011 ADA GUIDELINES EE003 TELECOM SCHEDULES AND NOTES
SHEET TYPE F
@ AT INSUL INSULATION G012 ADA GUIDELINES CONT. EE004 BASIS OF DESIGN 3 ALL WORK, MATERIALS, AND METHODS SHALL BE IN CONFORMANCE WITH THE CODES, ORDINANCES AND REGULATIONS
DISCIPLINE G015 CODE REQUIRED SIGNAGE & DETAILS EE005 CODE SHEET OF ALL GOVERNMENTAL AGENCIES HAVING JURISDICTION AT THE PROJECT LOCATION.
[ CHANNEL INT INTERIOR
± PLUS MINUS INTX INTERSECTION G016 STEEL STUD SCHEDULES & DETAILS EE501 ELECTRICAL DETAILS
1 2 G017 STEEL STUD SCHEDULES & DETAILS EE502 ELECTRICAL DETAILS 4 UNLESS OTHERWISE INDICATED IN THE CONSTRUCTION DOCUMENTS AS BEING NOT IN CONTRACT (N.I.C.) OR EXISTING,
≤ LESS THAN OR EQUAL TO INV INVERT
G501 FIRE PENETRATION DETAILS EE503 BUSWAY SCHEDULES AND DETAILS ALL ITEMS, MATERIALS AND INSTALLATION OF SAME ARE PART OF THE CONTRACT AS DEFINED BY THE CONSTRUCTION
WALL,BASE, OR FLOOR

F CPT-01
≥ GREATER THAN OR EQUAL TO DOCUMENTS. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL ACCESSORIES, COMPONENTS AND ASSEMBLIES
J G502 TYPICAL SOUND ISOLATION DETAILS EE504 CABLE TRAY SYMBOLS & DETAILS
MATERIAL FINISH CODE REQUIRED FOR THE WORK DEPICTED OR SPECIFIED.
A JB JUNCTION BOX A EE601 GROUNDING RISER DIAGRAM
ARROWS REPRESENT EXTENT OF SCOPE CIVIL EE701 TYPICAL MOUNTING HEIGHT DETAILS 360 west aspen avenue
AB ANCHOR BOLT JCT JUNCTION A1 STARTS AT UPPER LEFT CORNER; 5 CONTRACTORS ARE RESPONSIBLE FOR ALL WORK REGARDLESS OF THE LOCATION OF THE INFORMATION ON THE
AC APSHALTIC CONCRETE JST JOIST NUMBERS ARE VERTICAL GRIDS AND LETTERS
C001 LEGEND EE702 TYPICAL LABELING DETAILS DOCUMENTS.
salt lake city, utah 84101
ACST ACOUSTIC JT JOINT ARE HORIZONTAL GRIDS (EXCLUDES LETTERS "I" C101 DEMOLITION PLAN ED101 OVERALL ELECTRICAL SITE DEMO PLAN 801 532 4422
AD AREA DRAIN AND "O") C102 SITE PLAN ED102 ENLARGED ELECTRICAL SITE DEMO PLAN 6 KEEP SITE CLEAN AND CLEAR OF DEBRIS AND IN ORDERLY CONDITION THAT DOES NOT DETRACT FROM THE
ADJ ADJUSTABLE L ?
WC-01 C201 GRADING PLAN ES101 OVERALL ELECTRICAL SITE PLAN SURROUNDING SITE AND REPAIR ANY DAMAGE CAUSED BY WORK OF THE CONTRACT.
B REFER TO FINISH LEGEND C301 UTILITY PLAN ES102 ENLARGED ELECTRICAL SITE PLAN
AFF ABOVE FINISH FLOOR L ANGLE
ALT ALTERNATE L LENGTH C302 STORMWATER BASIN ES501 SITE ELECTRICAL DETAILS 7 ALL DIMENSIONS ARE TO THE FACE OF METAL OR WOOD STUD FRAMED WALLS AND TO THE FACE OF CONCRETE AND
ALUM ALUMINUM LC LENGTH OF CURVE C303 STORMWATER CALCS EP101 LEVEL 1 POWER PLAN MASONRY WALLS AS SHOWN, UNLESS NOTED OTHERWISE.
1 DELTA MARKER 101M
ARCH ARCHITECTURAL, ARCHITECT, ARCHITECTURE LDC LEAD COVERED C501 DETAILS EP102 LEVEL 2 POWER PLAN
ASPH ASPHALT LL LIVE LOAD C502 DETAILS EP103 ROOF POWER PLAN 8 INSTALL SEALANT AT EXTERIOR SIDE OF ALL JOINTS, SEAMS, CONNECTIONS OR OPENINGS WHICH WOULD ALLOW
REVISION CLOUD MODIFIED CASEWORK TYPE
EP103A BID ALT 1 ROOF POWER PLAN WATER OR AIR INFILTRATION EXCEPT AS NOTED OTHERWISE. SEALANT COLOR TO MATCH ADJACENT SURFACE. COLOR
LLH LONG LEG HORIZONTAL AWS STANDARD CASEWORK TYPE REQUIRES ARCHITECTS APPROVAL.
LANDSCAPE EP400 ENLARGED POWER PLANS
B LLV LONG LEG VERTICAL REFER TO CASEWORK DESIGN SERIES (CDS) OF
L100 LANDSCAPE PLAN EP600 ONE-LINE DIAGRAM DETAILS AND NOTES
B BASELINE LT LIGHT THE ARCHITECTURAL WOODWORK STANDARDS
L200 IRRIGATION PLAN EP601 SKM MODEL 9 DOOR OPENINGS IN FRAME CONSTRUCTION WHICH ARE NOT DIMENSIONED ARE EITHER CENTERED IN THE WALL, FACE
B BOTTOM (AWS) FOR A FULL DESCRIPTION OF CASEWORK OF JAMB OR LOCATED 4" FROM THE FACE OF STUD TO THE FINISHED JAMB.
?
00.00 KEYNOTE TAG L300 IRRIGATION PLAN
BEJ BRICK EXPANSION JOINT M TYPES EP602 ONE-LINE DIAGRAM
BLDG BUILDING MAS MASONRY L401 DETAILS EP603 EQUIPMENT SCHEDULE UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
XX CURTAIN WALL TAG 10 ALL SPECIAL ACCESSIBLE FACILITIES SHALL BE IDENTIFIED WITH APPROVED SIGNAGE.
SIGN TYPE L402 DETAILS EP604 EQUIPMENT SCHEDULE DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
BLK BLOCK MATL MATERIAL
L403 DETAILS EP605 PANEL SCHEDULES NOT INTENDED FOR CONSTRUCTION, RECORDING
BM BEAM MAX MAXIMUM 000x DOOR TAG A 01 11 THE CONTRACTOR IS RESPONSIBLE FOR PRODUCING A WEATHER TIGHT BUILDING, DETAILS AND OMISSIONS TO PURPOSES, OR IMPLEMENTATION
BO BOARD MECH MECHANICAL EL101 LEVEL 1 LIGHTING PLAN
DRAWINGS NOTWITHSTANDING. ALL DRAWING CONFLICTS WHICH MAY NOT ALLOW A WEATHERTIGHT CONDITION SHALL
SIGN NUMBER STRUCTURAL EL102 LEVEL 2 LIGHTING PLAN BE BROUGHT TO THE ATTENTION OF THE ARCHITECT.
BRG BEARING MET METAL F1 FLOOR TAG
S001 STRUCTURAL NOTES EL400 ENLARGED LIGHTING PLANS
BSMT BASEMENT MFR MANUFACTURER
S002 STRUCTURAL NOTES EL601 LIGHTING FIXTURE SCHEDULES 12 DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT.
MH MANHOLE R1 ROOF TAG
S010 SCHEDULES EL602 LIGHTING RELAY DIAGRAMS & SCHEDULES CONTRACTOR SHALL SUBMIT SPECIFIC DISCREPANCIES FOR ARCHITECT REVIEW.
C MIN MINIMUM
S011 SCHEDULES EL603 LIGHTING CONTROL SCHEDULES
C&G CURB & GUTTER MISC MISCELLANEOUS WALL FUNCTION
S012 SCHEDULES ET101 LEVEL 1 TELECOM PLAN 13 PROVIDE FULL METAL BACKING PLATE (16 GAUGE X 6" HIGH SECURED TO 3 STUDS MIN.) OR WOOD BLOCKING AS
CAP CAPACITY MO MASONRY OPENING CORE MATERIAL
S101 FOOTING AND FOUNDATION PLAN ET102 LEVEL 2 TELECOM PLAN REQUIRED TO SECURELY ANCHOR ALL WALL MOUNTED EQUIPMENT (CABINETS, TOILET ROOM ACCESSORIES,
CEM CEMENT MTD MOUNTED
SA6 a S102 SECOND FLOOR FRAMING PLAN ET501 TELECOM DETAILS HARDWARE, ETC.). BLOCKING SHALL PROVIDE A RIGID CONNECTION CAPABLE OF SUPPORTING DESIGN LOADS. PROVIDE
CG CORNER GUARD MTG MOUNTING WALL TAGS (SEE WALL TYPE SHEET(S) FOR LEGEND)
S103 ROOF FRAMING PLAN A 16 GAUGE X 6" STL. STUD/TRACK SECURED TO 2 STUDS TO SECURELY SUPPORT ALL WALL STOPS (DOOR BUMPER).
CIP CAST IN PLACE, CAST IRON PIPE MULL MULLION ET601 ENLARGED PLANS / CONDUIT & 2-WAY RISER DIAGRAM
MODIFER S110 STAIR FRAMING PLANS EY101 LEVEL 1 AUXILIARY PLAN
CIR CIRCULATING MWP MEMBRANE WATERPROOFING CORE SIZE (ROUNDED; SEE LEGEND) 14 COORDINATE WITH ALL TRADES, SIZES AND LOCATIONS OF ALL OPENINGS FOR MECHANICAL, PLUMBING, AND
S201 TYPICAL DETAILS EY102 LEVEL 2 AUXILIARY PLAN
CJ CONTROL JOINT ELECTRICAL EQUIPMENT, EQUIPMENT PADS OR BASES, AS WELL AS ELECTRIC POWER, WATER, AND DRAIN
LEVEL NAME S202 TYPICAL DETAILS EY103 ROOF AUXILIARY PLAN
CL CENTERLINE N INSTALLATIONS, BEFORE PROCEEDING WITH WORK. CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS FOR
MAIN LEVEL S210 FOUNDATION DETAILS EY501 AUXILIARY DETAILS PROPER PLACEMENT OF ALL TRADES' WORK. ANY CONCERNS, SPACE LIMITATIONS, OR STRUCTURAL CONFLICTS, SHALL
CL CENTERLINE N NORTH
CEILING TYPE S220 FLOOR FRAMING DETAILS EY502 CCTV CAMERA DETAILS BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. A REASONABLE RESPONSE TIME SHALL BE ALLOWED AS NOTED IN
CLG CEILING NA NOT APPLICABLE 100' - 0"
S230 ROOF FRAMING DETAILS EY601 AUXILIARY RISER DIAGRAMS THE SPECIFICATIONS.
CLR CLEAR NE NORTHEAST
C1 10' - 0" LEVEL ELEVATION S301 ELEVATIONS EJ101 LEVEL 1 AV ROUGH-IN PLAN
CMU CONCRETE MASONRY UNITS NEC NATIONAL ELECTRIC CODE
S401 SCHEMATIC REFERENCE EJ102 LEVEL 2 AV ROUGH-IN PLAN 15 ALL FLOOR OR WALL OPENINGS REQUIRED FOR PIPES, DUCTS, CONDUITS,ETC. SHALL BE SEALED IN AN APPROVED
COL COLUMN NEUT NEUTRAL MANNER.
CONC CONCRETE NIC NOT IN CONTRACT CEILING HEIGHT EJ601 AV ROUGH-IN SCHEDULES
POSITION ON SHEET ARCHITECTURAL SITE EK101 LIGHTNING PROTECTION PLAN
CONN CONNECTION NO NUMBER 1 Ref
A001 SITE AND STAGING PLAN EK501 LIGHTNING PROTECTION DETAILS 16 FIRE SPRINKLER DESIGN TO BE DONE BY A CERTIFIED SUB-CONTRACTOR AND WILL REQUIRE APPROVALS BY THE CITY,
CONST CONSTRUCTION NOM NOMINAL AND STATE FIRE MARSHALS. APPROVALS BY THE FIRE MARSHAL ARE TO BE OBTAINED BY THE CONTRACTOR PRIOR TO

Ref

Ref
ROOM NAME A051 SITE DETAILS EK502 GROUNDING DETAILS
CONT CONTINUOUS NTS NOT TO SCALE SUBMITTAL TO ARCHITECT. SUBMITTAL TO THE ARCHITECT ALSO INDICATES THAT THE CONTRACTOR HAS REVIEWED AND
101 ROOM NUMBER 1 AE000 1 FA101 LEVEL 1 FIRE ALARM PLAN
CPT CARPET NW NIORTHWEST COORDINATED FIRE-SPRINKLER PIPING LOCATIONS WITH ALL TRADES.
150 SF ROOM AREA ARCHITECTURAL FA102 LEVEL 2 FIRE ALARM PLAN
CSK COUNTERSUNK SHEET NUMBER
1 Ref A101 OVERALL PLAN LEVEL 1 FA103 ROOF FIRE ALARM PLAN 17 ROOMS ENCLOSED WITH RATED WALLS REQUIRE RATED DOORS. ANY DUCTS PASSING THROUGH WALLS REQUIRE FIRE
CT CERAMIC TILE O
A102 OVERALL PLAN LEVEL 2 FA103A BID 1 ALT ROOF FIRE ALARM PLAN DAMPERS AND OR FIRE/SMOKE DAMPERS. ANY CONDUIT OR PIPING REQUIRES RATED SEALANT AT JOINTS.
CTR CENTER OA OUTSIDE AIR
A103 ROOF PLAN FA601 FIRE ALARM RISER
OA OUTSIDE AIR POSITION ON SHEET
1 Ref POSITION ON SHEET A111 LEVEL 1 SLAB PLAN 18 GENERAL STRUCTURAL NOTES GOVERN TYPICAL CONDITIONS WHETHER OR NOT SPECIFICALLY DETAILED OR NOTED.
D OC ON CENTER
SIM A112 LEVEL 2 SLAB PLAN
D DEPTH OFCI OWNER FURNISHED, CONTRACTOR INSTALLED A1

Ref

Ref
A121 LEVEL 1 DIMENSION PLAN 19 IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE AND LOCATE ELECTRICAL, DATA, AND PHONE RECEPTACLES,
DET DETAIL OFOI OWNER FURNISHED, OWNER INSTALLED A526.a 1 AE000 1 A122 LEVEL 2 DIMENSION PLAN SWITCHES, ETC. TO AVOID CASEWORK, DOORS, ETC.
DF DRINKING FOUNTAIN OPP OPPOSITE
SHEET NUMBER A131 LEVEL 1 RCP
DIA DIAMETER OVHD OVERHEAD SHEET NUMBER
1 Ref A132 LEVEL 2 RCP 20 THE DRAWINGS AND SPECIFICATIONS INDICATE THE GENERAL SCOPE OF THE PROJECT IN TERMS OF THE
DIM DIMENSION
A201 EXTERIOR ELEVATIONS ARCHITECTURAL AND STRUCTURAL DESIGN CONCEPT. THE DIMENSIONS OF THE BUILDING, THE TYPE OF STRUCTURAL,
DN DOWN P MECHANICAL, ELECTRICAL, AND UTILITY SYSTEMS AND MAJOR ARCHITECTURAL ELEMENTS OF CONSTRUCTION AS
VIEW DIRECTION A301 BUILDING SECTIONS
DS DOWNSPOUT PI POINT IF INTERSECTION HEIGHT OF ELEMENT "SCOPE" DOCUMENTS.
POSITION ON SHEET A311 WALL SECTIONS
DWG DRAWING PL PLATE
10' - 0" A312 WALL SECTIONS
PLAS PLASTER A1 SIM 21 THE DRAWINGS AND SPECIFICATIONS DO NOT NECESSARILY INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL
A401 VERTICAL CIRCULATION ENLARGED PLANS AND SECTIONS
E PLYWD PLYWOOD PERFORMANCE AND COMPLETION OF THE WORK. CONTRACTS SHALL BE LET ON THE BASIS OF SUCH DOCUMENTS, WITH
A526.a A402 VERTICAL CIRCULATION ENLARGED PLANS AND SECTIONS
E EAST PNL PANEL THE UNDERSTANDING THAT THE CONTRACTOR IS TO FURNISH ALL ITEMS REQUIRED FOR PROPER COMPLETION OF THE
A411 ENLARGED PLANS AND INTERIOR ELEVATIONS WORK WITHOUT ADJUSTMENT TO CONTRACT PRICE. IT IS INTENDED THAT THE WORK TO BE OF SOUND AND QUALITY THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
E/P EDGE OF PAVEMENT PNT PAINT SHEET NUMBER A412 ENLARGED PLANS AND INTERIOR ELEVATIONS CONSTRUCTION AND THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE INCLUSION OF ADEQUATE AMOUNTS ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
EA EACH PRELIM PRELIMINARY DRAWING NUMBER TO COVER INSTALLATION OF ALL ITEMS INDICATED, DESCRIBED, OR REASONABLY IMPLIED. MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
VIEW NAME A413 INTERIOR ELEVATIONS COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
EL ELEVATION PRESS PRESSURE
A414 INTERIOR ELEVATIONS WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
ELECT ELECTRICAL PRIM PRIMARY WRITTEN PERMISSION FROM METHOD STUDIO INC.
ELEV ELEVATOR PRTN PARTITION VIEW DIRECTION VIEW NAME A501 VERTICAL & HORIZONTAL ASSEMBLIES
EMER EMERGENCY PT POINT, POINT OF TANGENT
POSITION ON SHEET A1 1/8" = 1'-0" (REF: A1/A101)
A511 GENERAL CONSTRUCTION DETAILS
EQ EQUAL A1
SIM
A1
SIM A513
A521
STAIR AND ELEVATOR DETAILS
EXTERIOR ENVELOPE SECTION DETAILS
project:
EQUIP EQUIPMENT Q AE101 AE101 ORIGINAL SOURCE OF DETAIL
A522 EXTERIOR ENVELOPE SECTION DETAILS
EW EACH WAY QT QUARRY TILE
EWC
EXIST
ELECTRIC WATER COOLER
EXISTING R
SHEET NUMBER
DRAWING SCALE A523
A531
EXTERIOR ENVELOPE PLAN DETAILS
ROOF DETAILS USU EVR
A532 ROOF DETAILS

EXPANSION
EXP EXPANSION R RADIUS VIEW DIRECTION
A541 DOOR DETAILS
EXP JT EXPANSION JOINT RA RETURN AIR POSITION ON SHEET
A542 DOOR DETAILS
EXT EXTERIOR RB RESILIENT VINYL BASE SIM
A1 A551 EXTERIOR GLAZING DETAILS
RCP REINFORCED CONCRETE PIPE
AE101 A561 INTERIOR GLAZING DETAILS
F RD ROOF DRAIN
A571 INTERIOR DETAILS
F.V. FIELD VERIFY RECP RECEPTACLE
SHEET NUMBER A581 CASEWORK DETAILS
FD FLOOR DRAIN REINF REINFORCEMENT
A591 CEILING DETAILS
FDN FOUNDATION REQD REQUIRED
A601 DOOR SCHEDULE
FE FIRE EXTINGUISHER REV REVISION
A604 WINDOW SCHEDULE
FFE FINISHED FLOOR ELEVATION RF ROOF
A606 INTERIOR GLAZING TYPES
FH FIRE HYDRANT RFLCP REFLECTIVE CEILING PLAN
A701 LEVEL 1 FINISH PLANS
FHC FIRE HOSE CABINET RM ROOM
A702 LEVEL 2 FINISH PLANS
FIN FINISH RVT RESILIENT VINYL TILE
A703 FINISH SCHEDULE
FLR FLOOR
A704 ACCESSORY, APPLIANCE & HARDWARE SCHEDULES
FR FRAME S
A801 SIGNAGE PLAN
FTG FOOTING S SOUTH
A802 SIGNAGE PLAN
FXTR FIXTURE SCH SCHEDULE 670 EAST 1550 NORTH, LOGAN, UT
G
SD
SE
STORM DRAIN
SOUTHEAST
MATERIAL LEGEND A901
A902
LEVEL 01 FURNITURE PLAN
LEVEL 02 FURNITURE PLAN 84341
G GROUND SECT SECTION
MECHANICAL
GA GA SHT SHEET
ME001 MECHANICAL SYMBOLS LEGEND AND GENERAL NOTES
GALV GALVANIZED SIM SIMILIAR EARTH (EXISTING) CONTINUOUS WOOD ME002 MECHANICAL BASIS OF DESIGN
GL GLASS SL SLOPE
ME501 MECHANICAL DETAILS
GR GRADE SPEC SPECIFICATION
ME502 MECHANICAL DETAILS
GRD GROUND SQ SQUARE
INTERMITTENT WOOD ME503 MECHANICAL DETAILS
GWB GYPSUM WALL BOARD STL STEEL EARTH (BACKFILL) BLOCKING ME504 MECHANICAL DETAILS p r o j e c t # : 21.0320
SUSP SUSPENDED
ME505 MECHANICAL DETAILS d a t e : 02.14.2023
H
ME601 MECHANICAL SCHEDULES
HB HOSE BIBB T
HC HANDICAPPED T TOP
DRAINAGE FILL
COMPACTED FILL
SHEATHING ME602 MECHANICAL SCHEDULES revisions :
ME701 MECHANICAL SCHEMATICS
HDW HARDWARE T&B TOP AND BOTTOM 1 Review Responses 03.06.2022
MH101 LEVEL 1 MECHANICAL PLAN
HGT HEIGHT TEL TELEPHONE
MH101B LEVEL 1 MECHANICAL PLAN BID ALTERNATE NO. 1
HORZ HORIZONTAL TEMP TEMPORARY CONCRETE WOOD FINISH
CAST-IN-PLACE MH102 LEVEL 2 MECHANICAL PLAN
HR HOUR TERM TERMINAL
MH102B LEVEL 2 MECHANICAL PLAN BID ALT NO. 1
HW HOT WATER THK THICK/THICKNESS
MH103 ROOF MECHANICAL PLAN
THRSLD THRESHOLD
CONCRETE MP101 LEVEL 1 MECHANICAL PIPING PLAN
TO TOP OF HARDBOARD
PRECAST MP102 LEVEL 2 MECHANICAL PIPING PLAN
TOS TOP OF STEEL, TOP OF SLAB
TOW TOP OF WALL
PLUMBING
TYP TYPICAL
BRICK PARTICLE BOARD PE501 PLUMBING DETAILS
PE601 PLUMBING SCHEDULES
U
PE701 GAS ISOMETRIC
UNO UNLESS NOTED OTHERWISE
PE701B GAS ISOMETRIC BID ALT 1 title:
CONCRETE MASONRY BATT INSULATION
UNIT PL101 LEVEL 1 PLUMBING PLAN
V
VCT
VENT
VINYL COMPOSITION TILE
VENTILIATING
PL101B
PL102
LEVEL 1 PLUMBING PLAN BID ALT NO. 1
LEVEL 2 PLUMBING PLAN INDEX,
PL102B LEVEL 2 PLUMBING PLAN BID ALT NO. 1

GENERAL
VERT VERTICAL GROUT LOOSE FILL INSULATION
PL103 ROOF PLUMBING PLAN
VEST VESTIBULE
PL401 LARGE SCALE PLUMBING PLANS
VWC VINYL WALL COVERING

W
W WIDTH, WEST
STEEL RIGID INSULATION
NOTES,
W/
W/O
WC
WITH
WITHOUT
WATER CLOSET
ALUMINUM FIRE SPRAY LOCATION
WD
WT
WWF
WIDTH
WEIGHT
WELDED WIRE FABRIC GYPSUM BOARD
MAP,
X LEGENDS
X TRANSFORMER
sheet:

G001 BID SET


1 2 3 4 5 6
DOOR
OCC. 9
Req. 1.8"
Prov. 36"

MECH.
129
RESEARCH
130
VESTIBULE
131
CODE ANALYSIS
111.36 SF / 1 OCC 111.36 SF / 1 OCC 111.36 SF / 1 OCC

PROJECT DESCRIPTION
2 STORY EXPANSION OF THE ELECTRIC VEHICLE AND ROADWAY (EVR) RESEARCH FACILITY FOR FACULTY
DOOR
OCC. 120
Req. 24"
GRAPHIC LEGEND AND STUDENTS. THE EVR EXPANSION INCLUDES A 2 STORY OFFICE SPACE AND A FABRICATION AND
TESTING SHOP. THE OFFICE COMPONENT WILL PROVIDE 6 FACULTY OFFICES, 3 EXECUTIVE/DIRECTOR LEVEL
Prov. 72"
OFFICES, 51 OPEN WORK STATIONS SHARED BY FACULTY AND STUDENTS, AND 4 SMALL GROUP WORK
FIRE BARRIER RATING
SPACES FLEXIBLE LARGE CONFERENCE SPACES. THE SHOP SPACE INCLUDES SPECIALTY SPACES FOR
RESEARCH FLOOR 1 HOUR RATED WALL FIRE BARRIER, UL U419 FABRICATION, A LARGE FLEXIBLE WORK AREA FOR PROTOTYPE ASSEMBLY, AND FOUR SINGLE-ENTRY
126 VESTIBULE
E 4,158.39 SF / 14 OCC
HIGH-BAY TRUCK AISLES FOR TESTING AND OTHER VEHICLE WORK. THE PROJECT ALSO EXPANDS THE E
100A
PATH OF EGRESS OUTDOOR TEST TRACK FROM ONE LANE TO THREE. 360 west aspen avenue
198 SF
COMMON PATH OF EGRESS (CPE) salt lake city, utah 84101
STAIRS
ALLOWABLE DISTANCE = 100'-0" X ZONING 801 532 4422
ENTRY/RECEPTION TOTAL USED DISTANCE = 68'-0"
100C
100B as per 2015 IBC Table 1006.2.1 Utah State University - Public (PUB)
706.91 SF / 5 OCC 183 SF
TRAVEL DISTANCE (TD)
DOOR
OCC. 9 ALLOWABLE EXIT DISTANCE = 300'-0" X SOUND TRANSMISSION
Req. 1.8" ELECTRICAL EQUIPMENT CLEARANCE TOTAL USED EXIT DISTANCE = 244'-0"
Prov. 36" 108 as per 2015 IBC Table 1017.2 Sound Transmission Class (55-60 STC) at Administrative and Faculty Offices and Small Group
263.03 SF / 1 OCC UP FE FE Work rooms; (50 STC) at Conference Rooms.
1 1 POINT AT WHICH A CHOICE OF 2 EXITS BECOMES AVAILABLE
OFFICE

CONCRETE & EPOXY POURING CUTTING / GRINDING SOLDERING


LARGE CONFERENCE
114
113
PANIC HARDWARE X MAXIMUM AREA OF EXTERIOR WALL OPENINGS IBC 705.8
120.89 SF / 1 OCC
110A 110B 110D 819.40 SF / 55 OCC
353.26 SF / 2 OCC 436.56 SF / 2 OCC 229.54 SF / 1 OCC
EXIT SIGN (RE: ELECTRICAL) Based upon Fire Separation Distances:
OFFICE
115 North: 0 South: 0 East: 0 West: 0
COMPRESSOR UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
FE
121.31 SF / 1 OCC FIRE EXTINGUISHER DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
110C
DOOR
OCC. 16 16 SF
1
OFFICE FIRE EXTINGUISHER IN RECESSED CABINET
FE
1
APPLICABLE CODES NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
Req. 3.2" 117
Prov. 36" 121.31 SF / 1 OCC 2018 International Building Code NFPA 70, National Electric Code
EXIT WIDTH TAG 2018 International Mechanical Code DFCM High Performance Building Standards
OFFICE
FLEXIBLE WORK CUSTODIAL STORAGE STORAGE COFFEE 119
2018 International Plumbing Code Utah State University Design Standards
REQUIRED AND PROVIDED DOOR OPENING SIZE (IN INCHES) BASED OFF DOOR
110
122
120
118 121.31 SF / 1 OCC
NUMBER OF EXITING OCCUPANTS OCC. 10
2018 International Fire Code Utah State Fire Marshal Laws, Rules and Regulations
3,085.68 SF / 11 OCC 92.11 SF / 1 OCC
61 SF 48 SF Req. 2" 2018 International Energy Conservation Code ICC/ANSI A117.1-2009
HALLWAY as per 2018 IBC Section 1005.3.2 Prov. 36"
100E OFFICE
127 STAIR
827 SF REQUIRED AND PROVIDED STAIR OPENING SIZE (IN INCHES) BASED OFF
RESTROOM RESTROOM
FE 124 126
PRINT/COPY
121.31 SF / 1 OCC
NUMBER OF EXITING OCCUPANTS OCC.
Req.
10
2" DEFERRED SUBMITTALS
1 128 OFFICE Prov. 60"
92 SF 84 SF as per 2018 IBC Section 1005.3.1 • FIRE SUPPRESSION SYSTEMS
129
29 SF
D 121.31 SF / 1 OCC • FIRE ALARM SYSTEMS • FOLDING PANEL PARTITION D
GENERAL NOTE: SEE SHEET GI006 FOR TYPICAL FIRE PENETRATION DETAILS AND UL LISTINGS. ALSO SEE SERIES A500 • SIGNAGE & BRANDING ATTACHMENT SYSTEMS • MACHINE ROOMLESS TRACTION ELEVATORS
IT / MDF SHEETS FOR ADDITIONAL WALL TYPES AND UL LISTINGS. • PATIO PAVERS AND PEDESTAL SYSTEM
ELECTRICAL 130 OFFICE - DIRECTOR / EXEC
• ATTACHMENT OF CABINETRY
112A 209.89 SF / 1 OCC • SHORING SYSTEMS • CURTAINWALL FRAME & GLAZING
OCCUPANCY USE LEGEND
131

TRUCK BAYS
200.89 SF / 1 OCC 201.13 SF / 2 OCC • MECHANICAL SEISMIC BRACING & ANCHORAGE • EXTERIOR STOREFRONT FRAME & GLAZING
112 • ELECTRICAL SEISMIC BRACING & ANCHORAGE
4,932.52 SF / 16 OCC

MECHANICAL FLOOR AREA ALLOWANCE / OCCUPANT


112B
326.42 SF / 2 OCC OFFICE - DIRECTOR / EXEC
1 OCCUPANCY CLASSIFICATION AND USE IBC CHAPTER 3
133
Group A-3 15
STAIRS FE 247.60 SF / 2 OCC (ASSEMBLY SPACES WITH FEWER THAN 50 OCCUPANTS ARE Occupancy and Group: ____________________________________________________________
F-1, B
1 CLASSIFIED AS GROUP B)
100F
234 SF
Group B 150 N/A
Change in Use: ______ Yes
Mixed Occupancy: __________________________________
BREAK / KITCHENETTE
(ALLOWANCE OF 15 USED IN GROUP WORK ROOMS)
135 N/A
Special Use and Occupancy (e.g. High Rise, Covered Mall): ______
DOOR 733.60 SF / 49 OCC Group F 300
OCC. 19 FE
Req. 3.8"
1
2 STRUCTURAL DESIGN IBC CHAPTER 16
Prov. 36" Group S 300
Seismic Design Category: ______
D1 110 Exposure C
Design Wind Speed: ______________
DOOR DOOR
OCC. 39 OCC. 120
Req. 7.8" Req. 24"
Roof Snow Load: _____________
37 psf Ground Snow Load: ______________
46 psf
Prov. 36" Prov. 36" Risk Category: __________________
Category III
Frost Line Depth: _____________
Minimum 36"

3 TYPE OF CONSTRUCTION IBC CHAPTER 6


ENVELOPE COMCHECK VALUES
LEVEL 1 CODE PLAN
C2 1/16" = 1'-0" R- OR U-VALUES A B A B A B HT A B
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
SLAB EDGE R-15
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS

C ROOF R-30 CONTINUOUS 4 GENERAL BUILDING HEIGHTS AND AREAS IBC CHAPTER 5
C
WRITTEN PERMISSION FROM METHOD STUDIO INC.

EXTERIOR WALLS (CMU) R-18.6 (3 INCHES OF CLOSED CELL SPRAY FOAM INSULATION, MIN R-6.2 PER INCH) +
BLOCK + INTERIOR GYP. Number of Stories: 2 Above Grade + Mezzanine Building Height: 40'-0" project:
EXTERIOR WALLS (ACM) R-13 (3 INCHES OF MINERAL WOOL PANEL INSULATION + SHEATHING + INTERIOR GYP. Total Area: GROSS BUILDING AREA
GLAZING U-0.26
Level 1
Level 1
4,985 EXISTING
16,641 SF NEW (14' F.T.F.)
USU EVR
Level 2 8,321 SF NEW (14' F.T.F. + 2' PARAPET)
TOTAL AREA 29,947 (4,985 SF EXISTING + 24962 SF NEW) EXPANSION
EGRESS NOTES Allowable Area for Type II-B construction Occupancy Groups B and F-1 when surrounded by public ways
or yards not less than 60 feet in width:
Unlimited (IBC Section 507 Allowable Area with SM Sprinkler)
01. ALL EXITS ARE TO BE READILY OPENABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR
EFFORT
Required Separation of Occupancies, section 508.4 (hours)
B & F-1: 0
ROOF TERRACE
-
670.95 SF / 45 OCC 5 FIRE-RESISTANCE RATINGS AND ASSEMBLIES IBC CHAPTER 6

STAIR Fire Resistance Rating Requirements for Building Elements (hours). See A500'S for assembly listings
OCC. 39 670 EAST 1550 NORTH, LOGAN, UT
Req. 7.8" Primary Structural Frame 0 Shaft Enclosures 1 84341
Prov. 60"
STORAGE
Bearing Walls Exterior 0 Fire Walls 0
201
PERSONAL CARE
Bearing Walls Interior 0 Fire Barriers 0
STORAGE RESTROOM 22.29 SF / 1 OCC Non-Bearing Walls Exterior 0 Fire Partitions 0
204
202 203
MEZZANINE STORAGE 126.95 SF / 1 OCC Non-Bearing Walls Interior 0 Smoke Partitions 0
70 SF 111 SF
213 Floor Construction 0 Walls ≥ 30 of Adjacent 0
1,037 SF GROUP WORK
Roof Construction 0 Structure (Table 602)
PRINT / COPY 209
B 150.99 SF / 6 OCC Exterior Doors & Windows 0 B
DN RESTROOM RESTROOM 210
p r o j e c t # : 21.0320
206 208 40 SF
63 SF 97 SF 6 FIRE SEPARATION IBC CHAPTER 7 d a t e : 02.14.2023

Requirements for the Exterior Walls based on the fire separation distance (in hours): revisions :
North: 0 South: 0 East: 0 West: 0 1 Review Responses 03.06.2022

7 FIRE PROTECTION SYSTEMS IBC CHAPTER 9

Sprinklers: Fully sprinklered


Required: ______
YES Provided: ______
YES Type of Sprinkler System: ____________
NFPA 13
OPEN WORK AREA
212
3,420.46 SF / 23 OCC 8 MEANS OF EGRESS IBC CHAPTER 10

EVR Expansion
Design Occupant Load: ____________
212
title:
Exit Width Required: ____________
42.24"
PLUMBING FIXTURE ANALYSIS SUMMARY (Note: unisex restrooms provided) Exit Width Provided: ____________
288" CODE
OCCUPANT LOAD WATER CLOSETS LAVORATORIES
OCCUPANCY
GROUP MALE FEMALE MALE FEMALE MALE FEMALE
BATHTUBS/
SHOWERS
DRINKING
FOUNTAIN
SERVICE SINK CLOTHES WASHER
MISC. NOTES: ANALYSIS &
1. In case of conflict with the U.S. Department of Justice Federal Registers Parts I through V - ADA Guidelines
A-3

B
52

28
52

28
REQUIRED

REQUIRED
0.41

1.05
0.79

1.05
0.26

0.33
0.26

0.33
NA

NA
0

0
0

1
NA

NA
and specific reference to the International Building Code Accessibility Chapters, the more restrictive
requirements shall govern.
CODE PLANS
2. Additional code information shall be provided at the discretion of the Building Official for Complex Buildings.
F-1 13 13 REQUIRED 0.26 0.26 0.26 0.26 NA 2 0 NA Including, but not limited to:
GROUP WORK GROUP WORK GROUP WORK A. Atriums D. Fire Assembly Locator Sheet
A STAIR
212C
177.52 SF / 9 OCC
212B
137.72 SF / 5 OCC
212A
135.57 SF / 5 OCC
B. Performance Based Criteria E. Exterior and Interior Accessibility Route A
1 ON F. Fire Stopping, including Tested Design Number
OCC.
Req.
39
7.8"
TOTAL 93 93 PROVIDED 2 3 2 9 NA 2
LEVEL 01*
NA C. Means of Egress Analysis
Prov. 60" 3. See Code Plan sheets for additional information
Occupancy Description: 4. See GI000'S for fire penetration details
(A-3) Large Conference, Kitchen/Conference
(B) Offices, Small Group Work, Open Work, AV/IT
sheet:
LEVEL 2 CODE PLAN (F-2) Fabrication, Assembly, Testing
A2 1/16" = 1'-0" NOTES: Provided fixtures are derived from the project aggregate with multiple occupancies. The fractional numbers were first summed in project aggregate, then rounded up to the next whole number. (IBC
GENERAL NOTE: CONSTRUCTION OF NEW STATE BUILDINGS AND REMODELING OF EXISTING BUILDINGS
SHALL COMPLY WITH ALL THE REQUIREMENTS OF THE DFCM STANDARDS, INCLUDING ENHANCED

G003
2902.1.1)
ACCESSIBILITY. THE DFCM STANDARDS CAN BE FOUND AT THE FOLLOWING WEB SITE:
*SERVICE SINK LOCATED PER USU REQUEST. HOSE BIB PROVIDED ON LEVEL 02 WWW.DFCM.UTAH.GOV.

BID SET
1 2 3 4 5 6
1 2 3 4 5 6

NON ACCESSIBLE
LOCKER

1' - 0"

1' - 2"
TOP LOCKER SHELF:
46" MAX. AFF
HAND DRYER

TO TOP OF OPENING
TO DISPENSER / HANDLE

TO DISPENSER / HANDLE
4' - 0" MAX

4' - 0" MAX

4' - 0" MAX

4' - 0" MAX

4' - 0" MAX

4' - 0" MAX

4' - 0" MAX

TO TOP OF ACCESSIBLE
3'-2" MIN
TO DISPENSER
TO REFLECTIVE

LOCKER CONTROLS
E E

4' - 0"
3' - 4" MAX

SURFACE OF BED

15" MIN - 48" MAX


TO OPEN, FLAT
SURFACE

3' - 6"
360 west aspen avenue

2' - 10"
salt lake city, utah 84101

2' - 6"
15" MIN
BOT. LOCKER SHELF:

2' - 0"
15" MIN. AFF 801 532 4422

MIRROR SOAP DISPENSER PAPER TOWEL TOILET PAPER HOLDER SANITARY NAPKIN SANITARY NAPKIN BABY CHANGING TOILET SEAT COVERS WASTE RECEPTACLE FIRE TRASH CHUTE DOOR TOWEL BARS FIRE CABINET CUPS COAT HOOKS ACCESSIBLE
DISPENSER DISPOSAL DISPENSER STATION DISPENSER EXTINGUISHER LOCKER
NOTES: CABINET
1. WHERE SHOWN, 48" MAX HEIGHT SHALL BE MEASURED FROM FLOOR TO ANY HIGHEST OPERABLE PART
2. PROVIDE BLOCKING FOR ALL EQUIPMENT PER MANUFACTURER'S WRITTEN INSTRUCTIONS

TYPICAL MOUNTING HEIGHTS


E1 1/2" = 1'-0"
3/4" CDX PLYWOOD
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

2x4 TOP RAIL

2x6 CROSS ROOF SUPPORTS


4'-0" O.C. LATEX CAULK (PAINTABLE)
NOTE:
- SHOWER MIXING VALVE SHALL HAVE A TEMPERATURE CONTROL REGULATOR TO PREVENT SCOLDING AS REQUIRED BY CODE LOCTITE: POWER GRAB CONST. ADHESIVE FRAMING AS SCHEDULED
- BLOCKING MUST BE PROVIDED FOR ALL UNITS, FOR FUTURE GRAB BARS

4x4 POSTS 4'-0" O.C. CONT. FLANGE TRIM KIT KFTK125 & KXFTK125 GRAB BAR WHERE SCHEDULED

LOCTITE: POWER GRAB CONST. ADHESIVE


TOP OF TILE FOR TUB & SILICONE CAULK

8' - 5"
SHOWER HEAD 2x4 TOP EDGE MID RAIL
SHOWER ENCLOSURE
W/ 60" HOSE
D TUB/SHOWER INSERT D
5"

9' - 0" 1/2" CDX PLYWOOD SHEATHING


24" MIN NAILED TO 2x4 RAILS
RECESSED SILICONE CAULK
4" MAX CURVED SHOWER ROD
SOAP DISH BLOCKING
CONT. FLANGE TRIM KIT KFTK125 & KXFTK125
5' - 0" TILE HEIGHT
5' - 0" TILE HEIGHT

2" 24" MIN 12" MAX TUB/SHOWER INSERT


1' - 6"
3" - 6"

LATEX CAULK (PAINTABLE)


12" MIN BAR IS OMITTED IF BUILT
5/8" WATER RESISTANT TYPE 'X' GYP
IN TRANSFER SEAT IS 5/8" WATER RESISTANT TYPE 'X' GYP
2x4 MID AND BOTTOM RAIL BD
8" - 10"

8" - 10"

INSTALLED BD
8" - 10"

48" MAX
3' - 2" - 48"
1' - 6"
33" - 2' - 10"

33" - 2' - 10"


MAX

ELEVATION - TOP OF SHOWER OR TUB/SHOWER INSERT PLAN / JAMB

TRANSFER SEAT
17" - 1' - 7"
TUB SPOUT
5" MIN.

VARIES
VARIES

VARIES

DRAIN DRAIN
TUB / SHOWER INSERT DETAIL
4' - 0"
D5 3" = 1'-0"
CONTROL VALVE CAN BE ANYWHERE IN THIS 3/4" CDX PLYWOOD
CONTROL SIDE SQUARE, COORDINATE W/ MANUF BACK WALL HEAD
INSTRUCTIONS
℄ TUB AT TYPE A UNIT
SHOWER HEAD 2x4 TOP RAIL

5' - 0"
2x6 CROSS ROOF SUPPORTS 4'-0"
12" 24" MIN 12" O.C.
MAX MAX
2' - 0" MIN BAR IS OMITTED IF
BUILT-IN TRANSFER 4x4 POSTS 4'-0" O.C.
22"-23" SEAT IS INSTALLED
1' - 9" - 24"

6" MAX THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


2' - 6"

4' - 0" MIN


14" - 15"

6" - 8" 2x4 TOP EDGE MID RAIL ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
5' - 0"
5' - 0"
5' - 0"

2' - 0" 15"-16" 2 1/2" MAX MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
4' - 0" MIN COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
PU WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
8"

2' - 5 31/32" MAX 8"

1/2" CDX PLYWOOD SHEATHING WRITTEN PERMISSION FROM METHOD STUDIO INC.
CONTROL SIDE 2' - 0" 2' - 0" SH
C NAILED TO 2x4 RAILS TO C
38" MIN

38" MIN

38" MIN
2' - 6" MAX

OP
project:
6" MAX

TUB FLOOR CLEARANCE


SPOUT EN

4' - 0" MAX


VARIES

VARIES

2' - 6" MIN


CONTROL VALVE CAN BE ANYWHERE IN THIS
LENGTH OF TUB
2x4 MID AND BOTTOM RAIL
USU EVR
CONTROL SIDE BACK WALL HEAD
SQUARE, COORDINATE W/ MANUF
INSTRUCTIONS
BLOCKING REQUIREMENTS: TUB AT TYPE A & B UNITS
TUB PLAN CR EXPANSION
PLAN ELEVATION

TUB / TUB BLOCKING LOCATIONS TYPICAL PEDESTRIANPROTECTION CORRIDOR CARD READER VIEW
C1 3/8" = 1'-0" C3 1/2" = 1'-0" C5 1/2" = 1'-0"

NOTE:
SHOWER MIXING VALVE SHALL HAVE A
TEMPERATURE CONTROL REGULATOR TO PREVENT 5' - 0"
SCOLDING AS REQUIRED BY CODE
670 EAST 1550 NORTH, LOGAN, UT
SHOWER HEAD BAR IS OMITTED IF BUILT IN TRANSFER SEAT IS ℄ 84341
SHOWER HEAD BACK
INSTALLED ℄

1 1/2" MAX
WALL BACK
12" MAX 24" MIN 12" MAX
5"

SLIDING WALL
24" MIN SHOWER
2' - 0" MIN 4" MAX RECESSED SOAP HEAD

14" - 15"
DISH CONTROL SIDE 22"-23"
RECESSED
5' - 0" TILE HEIGHT

2' - 6"
℄ ℄
1' - 9" - 24"

24" MIN
4' - 0" MIN 6" MAX ℄ SOAP DISH
24" MIN 12" MAX

12" MIN
3" - 6" 1' - 6"

SEAT CONTR
B 6" - 8" 15"-16" BACK B
5' - 0"
5' - 0"
5' - 0"

2' - 0" BAR IS OMITTED IF BUILT WALL OL WALL p r o j e c t # : 21.0320


12" MIN IN TRANSFER SEAT IS WALL
OPP
INSTALLED 2 1/2" MAX d a t e : 02.14.2023
8"

2' - 5 31/32" MAX 8"

8" - 10"

2 1/32" CONTROL
revisions :
48" MAX
3' - 2" - 48"

2' - 6"
1' - 6"
33" - 2' - 10"

33" - 2' - 10"


MAX

VALVE
38" MIN

38" MIN

38" MIN

FLOOR CLEARANCE
8" - 10"

TRANSFER SEAT
2' - 6" MAX

6" MAX

2' - 10"

BOUNDARY
TUB SPOUT

17" - 1' - 7"


FLOOR CLEARANCE
5" MIN.

EXTENTS
VARIES

VARIES

VARIES

VARIES

DRAIN
8" - 10"

DRAIN DRAIN
LENGTH OF TUB

CONTROL VALVE CAN BE CONTROL VALVE CAN BE


CONTROL SIDE BACK WALL HEAD ANYWHERE IN THIS SQUARE, TUB SPOUT
ANYWHERE IN THIS SQUARE, CONTROL SIDE BACK WALL HEAD TUB PLAN TRANSFER TYPE SHOWER PLAN BACK WALL CONTROL WALL
COORDINATE W/ MANUF COORDINATE W/ MANUF
BLOCKING REQUIREMENTS: TUB AT ACCESSIBLE AND TYPE B UNITS INSTRUCTIONS ACCESSIBLE UNIT TUB
INSTRUCTIONS ACCESSIBLE UNIT TRANSFER TYPE SHOWER
DRAIN

title:
CONTROL SIDE
ADA
5"

1 1/2" MAX
6" MAX 24" MIN
SLIDING SHOWER SLIDING SHOWER 27" MAX
GUIDELINES
6" MAX

HEAD HEAD
CONTROL VALVE
6" MAX 16" MIN BOUNDARY EXTENTS

30" MIN
12" MAX 22"-23"
24" MIN
TILE HEIGHT

6" MAX RECESSED SOAP DISH 15"-16"


6' - 4"

6' - 4"
6' - 4"

8"

8"

ABOVE GRAB BAR

48" MAX
38" - 44"
2' - 5 31/32" MAX

3' - 2" MIN

33" - 3' - 0"


2' - 6" MAX
38" MIN

38" MIN

33" - 36"

2' - 6"
33" - 36"
2' - 6" MAX

A GRAB BAR A
2' - 0" MIN

1' - 6 1/32"

SHALL NOT FLOOR CLEARANCE


EXTEND DRAIN
OVER SEAT
LENGTH OF SHOWER
END WALL BACK/CONTROL WALL SHOWER SEAT (INCLUDED IN SPECIFICATION; IF NOEND/SEAT WALL 60" MIN
END WALL BACK/CONTROL WALL END/SEAT WALL SHOWER SEAT PROVIDED, INCLUDE ADDITIONAL
GRAB BARS OVER SEAT AREA PER DRAWINGS) ROLL-IN SHOWER PLAN sheet:
BLOCKING REQUIREMENTS: ROLL-IN SHOWER AT ACCESSIBLE AND TYPE B UNITS
ACCESSIBLE UNIT ROLL-IN SHOWER

A1 SHOWER/TUB GRAB & BLOCKING LOCATION


3/8" = 1'-0"
ALL WET WALLS NEED TO COMPLY WITH ASTM #D3273 BEHIND ALL TUB/SHOWER ENCLCOSURES
G011 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

5' - 8" MIN 5' - 4" MIN 5' - 4" MIN ARM ARM
5' - 7" MIN 5' - 0" MIN

3' - 0" MIN

3' - 2" MIN

3' - 4" MIN


8" MIN

5' - 0" MIN

5' - 0" MIN

5' - 0" MIN


8" MIN
2' - 1" MAX

2' - 0" MIN

1' - 10" MIN

1' - 8" MIN

BASE
E E

BASE
10" MAX
360 west aspen avenue
salt lake city, utah 84101
801 532 4422

OVERLAP OF KNEE AND TOE OVERLAP OF KNEE AND TOE 1' - 4" MIN 3' - 0" MIN 1' - 4" MIN 11" MIN 3' - 6" MIN 11" MIN 1' - 0" MIN 3' - 4" MIN 1' - 0" MIN

CIRCULAR TURNING SPACE - CIRCULAR TURNING SPACE - T-SHAPED TURNING SPACE - T-SHAPED TURNING SPACE - T-SHAPED TURNING SPACE - T-SHAPED TURNING SPACE -
NEW BUILDINGS EXISTING BUILDINGS NEW BUILDINGS - OPTION 1 NEW BUILDINGS - OPTION 2 NEW BUILDINGS - OPTION 3 NEW BUILDINGS - OVERLAP

(ANSI 304) TURNING SPACE


E1 3/8" = 1'-0"

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

20 MAX >20-25 MAX


510 510-635 SCHEDULED WALL

CL

2' - 6" min


30 min
760

760
48 MAX
1220
15 MIN
48 MAX

48 MAX
15 MIN

46 MAX
48 MAX
380
1220

1220

44 MAX

1170
380

1220
1120

27 min
34 MAX

34 MAX

685
865

865

9 min
230

230
9
D 17 - 25 17 - 25 D
430 - 635 430 - 635
6 max 11 min CANE DETECTION

4" MAX
(b) RAILS
(a) (b) 150 280
10 MAX 10 MAX > 10-24 MAX (a) (b) (a) plan
255 elevation FIG 306.2 plan elevation FIG 306.3
255 255-610
TOE CLEARANCE KNEE CLEARANCE WHEELCHAIR
(a) (b) 1'-3" 2'-4 3/8"
ACCESSIBLE
CL CL FOUNTAIN
UNOBSTRUCTED FORWARD REACH OBSTRUCTED FORWARD REACH UNOBSTRUCTED SIDE REACH OBSTRUCTED HIGH SIDE REACH

(ANSI 308) REACH RANGES (ANSI 604) TOE / KNEE CLEARANCE CANE DETECTION AT WATER COOLER
D1 3/8" = 1'-0" D4 3/8" = 1'-0" D6 1" = 1'-0"

SCHEDULED WALL
5" MAX 1' - 3" MIN - ADULT 5" MAX

ESCUTCHEON
PLATE; FINISH
TO MATCH RAILS

X > 2' - 0"


& STANCHIONS; THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
X > 1' - 3"
2' - 6" MIN

ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &


℄ ℄ MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
CLEAR FLOOR SPACE AT WHEELCHAIR CLEAR FLOOR SPACE AT WHEELCHAIR
project:
DRINKING FOUNTAINS DRINKING FOUNTAINS - PRIMARILY FOR WHEELCHAIR DF SPOUT LOCATION STANDING US DF SPOUT LOCATION
NEW BLDGS - 4' - 4" MIN
EXISTING BLDGS - 48" MIN 5' - 0" MIN 3' - 0" MIN
CHILDRENS USE EXCEPTION
USU EVR
SIZE OF CLEAR FLOOR SPACE POSITION OF CLEAR FLOOR SPACE
FORWARD
POSITION OF CLEAR FLOOR SPACE
PARALLEL
MANUEVERING CLEARANCE IN AN ALCOVE
PARALLEL APPROACH
MANUEVERING CLEARANCE IN AN ALCOVE
FORWARD APPROACH DRINKING FOUNTAIN AND BOTTLE FILLING STATIONS EXPANSION
DRINKING FOUNTAIN AND BOTTLE FILLING STATIONS

(ANSI 305) CLEAR FLOOR SPACE (ANSI 602) DF CLEAR FLOOR SPACE (ANSI 602) DF SPOUT LOCATION ELEVATION - CANE DETECTION AT WATER COOLER
C1 3/8" = 1'-0" C4 3/8" = 1'-0" C5 3/8" = 1'-0" C6 1 1/2" = 1'-0"

5' - 0" MIN. 670 EAST 1550 NORTH, LOGAN, UT


84341
5' - 0" MIN.

5' - 0" MIN.

3' - 6" MIN.


4' - 6" MIN.

2' - 8"
4' - 0" MIN.
3' - 6" MIN.

3' - 6" MIN.

5' - 0" MIN.

MIN.

4' - 0" MIN.


4' - 0" MIN.

1' - 6" MIN.


22" MIN. 3' - 0" MIN.

8" MAX
1' - 6" MIN.
8" MAX

2' - 0" MIN.


1' - 0" MIN.

B 1' - 10" MIN. PUSH SIDE B


3' - 6" MIN.

4' - 0" MIN.

p r o j e c t # : 21.0320
12" MIN. IF DOOR 1' - 0"
HAS LATCH AND MIN. d a t e : 02.14.2023
CLOSER 12" MIN. IF DOOR
HINGE APPROACH LATCH APPROACH FRONT APPROACH
HAS LATCH AND revisions :
4' - 10" MIN. 1' - 0" CLOSER
MIN.

SWINGING DOORS SWINGING DOORS SWINGING DOORS STANDARD HARDWARE DOOR PROVIDED WITH CLOSER & LATCH

(ANSI 404) DOORS AND DOORWAYS


B1 1/4" = 1'-0"

1' - 0" HORIZONTAL RUN 1' - 0"


SLOPE MAX RISE title:
1:8* - 1:10 3"

ADA
TYPICAL

1:10 - 1:12 6"


3' - 0"

30" MAX

*SLOPE STEEPER THAN 1:8 IS NOT PERMITTED

GUIDELINES

6' - 8" MINIMUM.


1 NOTES: SCHEDULED STAIR
0' - 0 1/2"

12 RE: ENLARGED STAIR PLANS


CONT.
MAX.
MAX.

MAX.

2 2
1/2"
1/4"

1/4" - 1/2"

A. RAMP DETAILS ARE SHOWN AS CODE


SECTION VIEW 1 1 1/2" DIAMETER STEEL
MINMUM REQUIREMENTS.
5' - 0" MIN. GUARDRAIL; FINISH TO MATCH REST OF
ACTUAL CONDITIONS MAY VARY. SEE SITE
STAIR
1' - 0" 5' - 0" MIN. 30" MAX VERTICAL RISE 5' - 0" MIN. 1' - 0" PLAN AND DETAILS
BETWEEN HANDRAILS

B. CLEAR WIDTH OF LANDINGS SHALL BE AT


A LEAST AS WIDE AS THE WIDEST RAMP RUN A
3' - 0" MIN.

27" MAX
LEADING TO THE LANDING
5' - 0" MIN.

1:48 MAX SLOPE DOWN 1:12 MAX SLOPE 1:48 MAX SLOPE
(2%) (8%) (2%) C. RAMP RUNS WITH A RISE GREATER THAN 6
LANDING RAMP RUN LANDING RAMP RUN LANDING INCHES SHALL HAVE HANDRAILS
LEVEL CHANGE IN FLOOR SURFACE CARPET ON FLOOR SURFACES
1' - 0"

[A] STRAIGHT RUN sheet:


CONTINUOUS HANDRAIL ALL TRANSITIONS SHALL COMPLY WITH
DOWN
AT INSIDE CORNER OF 2009 ICC A117.1 SECTIONS 302 AND 303

G012
LANDING

[B] CHANGE IN DIRECTION REDUCED VERTICAL CLEARANCE


3' - 0" MIN.

(ANSI 405) RAMPS ACCESSIBLE FLOOR TRANSITIONS (ANSI 307) REDUCED VERTICAL CLEARANCE
A1 1/4" = 1'-0" A3 12" = 1'-0" A4 1/2" = 1'-0"
BID SET
1 2 3 4 5 6
1 2 3 4 5 6

NOTE:
SIGNAGE LEGEND
1. SEE SIGNAGE SCHEDULE AND DETAILS FOR MORE INFORMATION
PROVIDE TYPE A @ STAIRS PROVIDE TYPE L, RE: CODE PLANS FOR OCCUPANCIES
2. FABRICATOR TO COORDINATE WITH ARCHITECT FOR FINAL SIGN DESIGNS 6" PICTOGRAM (SYMBOL)
E RAISED 1/32" OFF FACE, TYP. 1'-0" WIDE E
3. PROVIDE BACK PANEL TO MATCH SIGN WHERE OCCURS ON GLASS 360 west aspen avenue
SANDBLASTED, CLEAR ANODIZED ALUMINUM PANEL salt lake city, utah 84101
801 532 4422
MAXIMUM

6"
STAIR 1" LETTERS,
TYP. UNO
3/4" HIGH LETTERING, RAISED 1/32", TYP. OCCUPANCY

8 1/2" HIGH
GRADE 2 BRAILLE APPLIED TO FACE, TYP.
NOT TO EXCEED
PROVIDE TYPE B @ UNISEX RESTROOMS

370 PERSONS
6" 2" LETTERS
PICTOGRAMS (SYMBOL)
1" LETTERS,
RAISED 1/32" OFF FACE, TYP.
TYP. UNO
SANDBLASTED, CLEAR ANODIZED

6"
ALUMINUM PANEL

8 1/2"
3/4" HIGH LETTERING, RAISED 1/32", TYP. UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
OCCUPANT LOAD SIGN DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS

2 1/2"
UNISEX NOT INTENDED FOR CONSTRUCTION, RECORDING
SETON STYLE NO. 43355 OR EQ. PURPOSES, OR IMPLEMENTATION
GRADE 2 BRAILLE APPLIED TO FACE, TYP.

PROVIDE TYPE C @ ADA UNISEX SHOWERS


PROVIDE TYPE M @ FDC LOCATIONS
6"
SANDBLASTED, CLEAR ANODIZED
ALUMINUM PANEL 1" RAISED WHITE LETTERS, ON
RED BACKGROUND
PICTOGRAMS (SYMBOL) RAISED 1'-0" WIDE

7"
1/32" OFF FACE, TYP.

9 1/2"
3/4" HIGH LETTERING, RAISED 1/32", TYP.

2 1/2"
D
UNISEX
SHOWER
FIRE D

5" HIGH
GRADE 2 BRAILLE APPLIED TO FACE, TYP.
DEPARTMENT
PROVIDE TYPE D @ NON ADA UNISEX SHOWERS CONNECTION
6"
SANDBLASTED, CLEAR ANODIZED
ALUMINUM PANEL FDC SIGN SANDBLASTED, CLEAR
ANODIZED ALUMINUM SIGN
W/ 4 EPOXY PIN ANCHORS
PICTOGRAMS (SYMBOL) RAISED

7"
1/32" OFF FACE, TYP.

9 1/2"
3/4" HIGH LETTERING, RAISED 1/32", TYP.

2 1/2"
UNISEX
SHOWER
PROVIDE TYPE N @ ELEVATOR LOCATION
GRADE 2 BRAILLE APPLIED TO FACE, TYP.

6" WIDE
PROVIDE TYPE E @ MENS RESTROOMS
3/4" HIGH LETTERING,
6" IN CASE OF RAISED 1/32", TYP.
PICTOGRAMS (SYMBOL)
RAISED 1/32" OFF FACE, TYP.
FIRE
SANDBLASTED, CLEAR ANODIZED

7" HIGH
SANDBLASTED, CLEAR ANODIZED

6"
ALUMINUM PANEL

8 1/2"
NOTE: ALUMINUM SIGN W/ 4 EPOXY
-COLOR AS SELECTED BY ARCHITECT 3/4" HIGH LETTERING, RAISED 1/32", TYP. PIN ANCHORS
-CHARACTER SIZE AND BRAILLE

2 1/2"
MEN DO NOT USE ELEVATORS
LOCATION PER ANSI A117.1, CH. 7 USE STAIRWAYS
3/8" HIGH LETTERING,
GRADE 2 BRAILLE APPLIED TO FACE, TYP. RAISED 1/32", TYP. THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
8" ± ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
OR AS REQ'D COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
PROVIDE TYPE F @ WOMENS RESTROOMS

C
ELEVATOR SIGN C
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
6"
SETON STYLE NO. 25639 OR EQ.
PICTOGRAMS (SYMBOL)
RAISED 1/32" OFF FACE, TYP. project:
2"

SANDBLASTED, CLEAR ANODIZED

USU EVR

6"
ALUMINUM PANEL

8 1/2"
3/4" HIGH LETTERING, RAISED 1/32", TYP. PROVIDE TYPE O @ STAIR EXITS
BRAILLE AREA, TYP

2 1/2"
WOMEN

GRADE 2 BRAILLE APPLIED TO FACE, TYP.


1'-4" WIDE
EXPANSION
EXIT SIGN 1-1/2" LETTERS,
TYP. UNO
PROVIDE TYPE G @ ACCESSIBLE RESTROOMS SOUTH STAIR 5" LETTERS,
6"
TYP. UNO
PICTOGRAM (SYMBOL)
RAISED 1/32" OFF FACE, TYP.

(OPTION 3) SISTER 16 GA. STL.


SANDBLASTED, CLEAR ANODIZED ALUMINUM PANEL

6"

1'-6" HIGH
8 1/2"
STUD ATTACH FIXTURE TO
SISTER STUD W/ SELF 3/4" HIGH LETTERING, RAISED 1/32", TYP.

2 1/2"
TAPPING SCREWS OR RESTROOM
STUDS SHOWN @ 16" O.C. SEE WALL TYPES ANCHORS
PROVIDE FULL VERTICAL BLOCKING AT
CENTERLINE OF URINAL (OPTION 2) INLAID FIRE GRADE 2 BRAILLE APPLIED TO FACE, TYP.
RETARDANT WOOD
BLOCKING (COMPLY WITH
FOUNTAIN 20 GA x 6" FLAT STEEL IBC 2006 2303.2) 670 EAST 1550 NORTH, LOGAN, UT
NAPKIN BLOCKING (OPTION 1) 20 GA x 6" FLAT STEEL PROVIDE TYPE H @ RESTROOMS W/ CHANGING STATION
WATER
COOLER/ BLOCKING. ATTACH W SELF TAPPING 6"
84341
20 GA x 6" FLAT STEEL
FOUNTAIN BLOCKING PAN HEAD SCREWS PICTOGRAM (SYMBOL)
20 GA x 6" FLAT STEEL GYPSUM BOARD RAISED 1/32" OFF FACE, TYP.
HAND DRYER

5 11/16"
BLOCKING SANDBLASTED, CLEAR ANODIZED ALUMINUM PANEL
TAMPON 16 GA SUPPORT STUD
ACCESSORY MOUNTED

8 1/2"
FOR STL. ANGLE
OVER FINISHED WALL 3/4" HIGH LETTERING, RAISED 1/32", TYP. PROVIDE TYPE P @ DFCM ROOF WARRANTY SIGNAGE
BRACING

2 13/16"
NOTE: CHANGING
B 1. TYPICAL BLOCKING REQUIRED STATION
1' - 2" B
BEHIND WALL MOUNTED p r o j e c t # : 21.0320
WALL CONSTRUCTION ACCESSORIES AND EQUIPMENT GRADE 2 BRAILLE APPLIED TO FACE, TYP.
1. PROVIDE A ROOF WARRANTY SIGN d a t e : 02.14.2023
PER DFCM REQUIREMENTS (METAL
PROVIDE TYPE I @ TYPICAL ROOMS
SIGN WITH VINYL LETTERING). revisions :
TYPICAL BLOCKING DETAILS 6" 2. USE APPROPRIATE FASTENERS AT

1' - 4"
EACH CORNER FOR WALL TYPE WHERE
3/4" HIGH LETTERING, RAISED 1/32", TYP. BEING INSTALLED.
ROOM
SANDBLASTED, CLEAR ANODIZED
NAME 3. 0.060 ALUMINUM SIGN WITH SCREEN
ALUMINUM PANEL

6"
315 PRINTED BACKGROUND AND
LETTERING - PROVIDE WITH RADIUSED
GRADE 2 BRAILLE APPLIED TO FACE, TYP.
CORNERS AND NO SHARP EDGES.

PROVIDE TYPE J @ TYPICAL ROOMS

6" PROVIDE TYPE Q @ ROOF ACCESS POINT


3/4" HIGH LETTERING, RAISED 1/32", TYP.
SIGN HEIGHT ABOVE THE FLOOR. TACTILE CHARACTERS SHALL BE 48 INCHES
MINIMUM ABOVE THE FLOOR. MEASURED TO THE BASELINE OF THE LOWEST TACTILE 6"
title:
315

2 1/2" 3 1/2"
CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FLOOR. MEASURED TO THE GRADE 2 BRAILLE APPLIED TO FACE, TYP. SANDBLASTED, CLEAR ANODIZED
BASELINE OF THE HIGHEST TACTILE CHARACTER. (ICC/ANSI 703.3.10)
CODE

6"
ROOF ALUMINUM PANEL

2 1/2" 3 1/2"
SANDBLASTED, CLEAR ANODIZED ALUMINUM PANEL
SIGN ACCESS
TRANSPARENT, MOLDED POLYCARBONATE

6"
TRANSPARENT, MOLDED UPDATEABLE PANEL
ACTIVE LEAF INACTIVE LEAF ACTIVE LEAF ACTIVE LEAF SIGN LOCATION. WHERE A TACTILE SIGN IS PROVIDED AT A DOOR. THE SIGN
SHALL BE ALONGSIDE THE DOOR AT THE LATCH SIDE. WHERE A TACTILE SIGN IS
POLYCARBONATE UPDATEABLE PANEL
REQUIRED
PROVIDED AT DOUBLE DOORS WITH ONE ACTIVE LEAF. THE SIGN SHALL BE
LOCATED ON THE INACTIVE LEAF. WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE PROVIDE TYPE K @ TYPICAL ROOMS
SIGNAGE &
60" MAX
48" MIN

DOORS WITH TWO ACTIVE LEAVES. THE SIGN SHALL BE TO THE RIGHT OF THE PROVIDE TYPE R @ TERRACE / PATIO DOORS
RIGHT HAND DOOR. WHERE THERE IS NO WALL SPACE ON THE LATCH SIDE OF A 9"
SINGLE DOOR, OR TO THE RIGHT SIDE OF DOUBLE DOORS. SIGNS SHALL BE ON
THE NEAREST ADJACENT WALL. SIGNS SHALL BE ON THE NEAREST SHALL BE
LOCATED SO THAT A CLEAR FLOOR AREA 18 INCHES MINIMUM BUY 18 INCHES
315 3/4" HIGH LETTERING, RAISED 1/32", TYP.
10"

3/4" HIGH LETTERING, RAISED 1/32", TYP.


DETAILS
MINIMUM, CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED BEYOND THE SANDBLASTED, CLEAR ANODIZED
A THIS DOOR TO
A

9"
ARC OF THE ANY DOOR SWING BETWEEN THE CLOSED POSITION AND 45 DEGREE

7 1/2"
ALUMINUM PANEL REMAIN UNLOCKED
WHEN THE
OPEN POSITION. (ICC/ANSI 703.311) OUTDOOR AREA IS
SANDBLASTED, CLEAR
OCCUPIED ANODIZED ALUMINUM PANEL
ROOM NAME
3/4" HIGH LETTERING, RAISED 1/32", TYP.

SIGNAGE LOCATIONS sheet:

G015 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

TSN MID WALL SCHEDULE: STANDARD TOP TRACK


MIDWALL™
Typ. Stud Spacing Max Wall Height Mid Wall to base connection Comment

250MW-24: 16"O.C. 4'-0" 1/2" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 4'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
250MW-48: 16"O.C. 7'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 5'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
362MW-24: 16"O.C. 3'-6" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck
4'-0" (2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab TYP
IC
24"O.C. 3'-0" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck STU AL
SPA D
E 4'-0" (2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab CIN E
G
362MW-48: 16"O.C. 8'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application 360 west aspen avenue
24"O.C. 7'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application salt lake city, utah 84101
600MW-24: 16"O.C. 4'-0" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck 801 532 4422
(2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab
24"O.C. 3'-6" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck
TWO ADJACENT
4'-0" (2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab MIDWALL™ SUPPORTS
600MW-48: 16"O.C. 4'-6" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck REQUIRED AT TYPICAL
10'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab STUD SPACING FOR
24"O.C. 9'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application END OF WALL

Note: Max wall height are calculated base on one 5/8" GYP BD on each side TOP TRACK SEE SPLICE POINT AT
MidWall attaches to every other stud, studs attach to MidWall=xxxS162-54. All other typ stud=xxxS137-33, typ top track=xxxT125-33 STANDARD CONTRACTOR'S
FRAMING SILL OPTION
Base connection based on concrete slab or concrete on metal deck with minimum compressive strength, f'c=3000psi WALL SCHEDULE
HEIGHT
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND

TSN MID WALL SCHEDULE (W/ HANDRAIL LOAD): #10 SCREWS TYP,
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
EACH FLANGE
Typ. Stud Spacing Max Wall Height Mid Wall to base connection Comment
STEEL COLUMN
WALL STUD EACH
250MW-24: 16"O.C. 4'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application SIDE FULL
250MW-48: 16"O.C. 7'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application 2-#10 SCREW OR HEIGHT
ENGINEER
362MW-24: 16"O.C. 4'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application APPROVED EQUAL.
24"O.C. 4'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application SPACE @ 12" O.C. #10 SCREWS TYP,
EACH SIDE EACH FLANGE
362MW-48: 16"O.C. 8'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
BOTTOM TRACK
24"O.C. 7'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application SEE PARTITION
TYPICAL WALL STUD
600MW-24: 16"O.C. 4'-0" (2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application TYPE GENERAL
24"O.C. 4'-0" (2) 3/8" dia HAS-Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application NOTES
600MW-48: 16"O.C. 10'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
D 24"O.C. 9'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
CLIP WEB AROUND D
STRUCTURAL STEEL TUBE
BASE PLATE ON BOTTOM
Note: Max wall height are calculated base on one 5/8" GYP BD on each side TRACK
MidWall attaches to every other stud, studs attach to MidWall=xxxS162-54. All other typ stud=xxxS137-33, typ top track=xxxT125-33
Handrail loads (50plf or 200lb point live load) are applied at 3'-0" above the base connection
MIDWALL SUPPORT DETAIL WALL TRACK CONNECTION TO CANTILEVER WALL SUPPORT POST
Base connection based on concrete slab or concrete on metal deck minimum compressive strength f'c=3000psi SCALE: NONE SCALE: NONE

STANDARD FRAMING JAMB STUD SCHEDULE ATTACH TO STEEL BEAM: ATTACH TO STEEL BEAM:
JAMB DEPTH MAX. JAMB HEIGHT MAX. OPENING WIDTH JAMB COMPONENTS CONFIGURATION BASE CONNECTION TOP CONNECTION
2-1/2" 12'-0" 4'-0" (2)250S162-33 & (1)250T150-33 J2 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0" (1 layer Gyp each side Max.) (2)250S162-33 & (1)250T125-54 J2 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
STEEL BEAM STEEL BEAM
12'-0" (1 layer Gyp 1 side Max.) (2)250S162-33 & (2)250T150-43 J3 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 STEEL BEAM STEEL BEAM
STEEL BEAM
STEEL BEAM
(2) HILTI X-U15
3-5/8" 10'-0" 4'-0" 362S137-33 & 362T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1 HILTI X-U15 PAF'S AT 8" HILTI X-U15 PAF'S AT 8" ANCHORS PER Z-CLIP
HILTI X-U15 PAF'S AT (2) HILTI X-U15
O.C. STAGGERED 8"O.C. STAGGERED (2) HILTI X-U15 PAF'S
8'-0" 362S137-33 & 362T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 O.C. STAGGERED 54 MIL Z-CLIP FOR AT EACH PLATE
ANCHORS PER Z-CLIP
12'-0" 362S137-33 & 362T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 54 MIL PLATE x 6" x 12" FIREPROOFING AT 32"
54 MIL PLATE x 6" x
STUD
15'-0" 4'-0" 362S137-33 & 362T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1 AT 32" O.C. MAX. SPACING
12" AT 32" O.C.
8'-0" 362S200-33 & 362T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 (2) #10 SCREWS AT
DEFLECTION TRACK 54 MIL Z-CLIP FOR FIRE
12'-0" (2)362S137-33 & (1)362T125-33 J2 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 EACH PLATE
TSN VERTICLIP SLD AT EACH
TSN VERTICLIP SLD AT EACH JAMB
PROOFING AT 32" MAX.
W/ (2) #8 SCREWS IN EACH JAMB &
16'-0" (1 layer Gyp each side Max.) (2)362S137-33 & (2)362T125-33 J3 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 STUD STUD JAMB W/ (2) #8 SCREWS IN (2) #8 SCREWS INTO TRACK AND
SPACING
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
18'-0" 4'-0" 362S162-33 & 362T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1 EACH JAMB & (2) #8 DEFLECTION TRACK
PLATE ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
SCREWS INTO TRACK
8'-0" (2)362S162-33 & (1)362T150-33 J2 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 STUD STUD STUD MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
12'-0" (2)362S200-33 & (2)362T150-33 J3 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
16'-0" (1 layer Gyp each side Max.) (3)362S200-33 & (2)362T150-33 J4 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
6" 10'-0" 4'-0" 600S137-33 & 600T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1 project:
8'-0" 600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 ATTACH TO METAL DECK: TRACK ATTACHMENT -
FIRE PROOFING IF
ATTACH TO METAL DECK:
METAL DECK SEE PARTITION TYPES
12'-0" 600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
USU EVR
GENERAL NOTES 22. REQUIRED
16'-0" 600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 TRACK ATTACHMENT - FIRE PROOFING IF TRACK
SEE PARTITION TYPES TOP TRACK. EACH SIDE OF JAMB (1) #12 SCREWS PER FLUTE
15'-0" 4'-0" 600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1 REQUIRED ATTACHMENT - CONNECTION (WHERE OCCURS). SEE (5) #12 SCREWS IN
METAL DECK
GENERAL NOTES 22.
8'-0"
12'-0"
600S137-33 & 600T125-33
600S137-33 & 600T125-33
J1
J1
(2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD)
(3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD)
Type 2
Type 2
SEE PARTITION
TYPES GENERAL
NOTES 22.
SS08 FOR DEFLECTION TRACK AND
SLOTTED TRACK INFORMATION
METAL DECK EACH FLUTE - (10)
TOTAL
DEFLECTION TRACK
EXPANSION
16'-0" 600S162-33 & 600T150-33 J1 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 TYPICAL STUD
20'-0" 4'-0" 600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1 68 MIL x 12" x 25"
DEFLECTION TRACK PLATE AT EACH TSN VERTICLIP SLD AT EACH
8'-0" (2)600S137-33 & (1)600T125-33 J2 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 68 MIL x 8" x JAMB W/ (2) #8 SCREWS IN 68 MIL x 12" x 25" JAMB STUDS
DEFLECTION TRACK JAMB PLATE AT EACH
12'-0" (2)600S137-33 & (1)600T125-33 J2 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 CONTINUOUS PLATE W/ # JAMB STUD EACH JAMB & (2) #8
10 SCREWS EACH SIDE JAMB
16'-0" (2)600S162-33 & (2)600T150-33 J3 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 STUD SCREWS INTO TRACK AND
@ 4" O.C. PLATE
25'-0" 4'-0" 600S162-33 & 600T150-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0" (2)600S137-33 & (1)600T125-33 J2 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 TRACK
12'-0" (2)600S200-33 & (1)600T200-33 J2 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 TSN VERTICLIP SLD AT EACH
PARALLEL TO PARALLEL TO PERPENDICULAR TO
16'-0" (3)600S162-33 & (2)600T150-33 J4 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2 JAMB W/ (2) #8 SCREWS IN
FLUTE AT FLUTE BETWEEN FLUTE EACH JAMB & (2) #8
FLUTE FLUTES SCREWS INTO TRACK
NOTE: SOG=SLAB ON GRADE TRACK
COMD=CONCRETE ON METAL DECK
PARALLEL TO 670 EAST 1550 NORTH, LOGAN, UT
FLUTE AT PERPENDICULAR TO 84341
FLUTE FLUTE
#10 @ 12" O.C.
TYP UNO
ATTACH TO CONCRETE SLAB ON METAL ATTACH TO CONCRETE SLAB ON METAL
DECK: DECK:
TRACK ATTACHMENT -
SEE PARTITION TYPES GENERAL
B NOTE 22. SEE DETAIL WITH
TRACK ATTACHMENT -
IF CLIP IS LOCATED PARTIALLY ON PLATE AND
B
SEE PARTITION TYPES GENERAL FIRE PROOFING IF p r o j e c t # : 21.0320
ADDITIONAL 68mil PLATE IF NOTES 22. ON CONCRETE, REPLACE SCREWS INTO (4) 3/8" DIA. HILTI KH- CONCRETE SLAB
OVERLAPPING <3" REQUIRED EZ ANCHORS W/ ON METAL DECK d a t e : 02.14.2023
CONCRETE WITH 1/4" HILTI KH-EZ ANCHORS
STRUCTURE FIRE PROOFING IF TRACK ATTACHMENT - WITH 2" MINIMUM EMBEDMENT 2-1/2" EMBEDMENT IN
J1 J2 MATCH WALL J3 J4 REQUIRED SEE PARTITION TYPES (4) 3/8" HILTI KH-EZ ANCHOR 12"
DEFLECTION TRACK EACH FLUTE. (4)
TOTAL.
12" revisions :
ONE TRACK ONE TRACK BOTTOM TRACK & TWO TRACKS TWO TRACKS GENERAL NOTES 22. W/ 2-1/2" EMBEDMENT AT DEFLECTION
EACH LOWER FLUTE TRACK
ONE STUD TWO STUDS STUD SIZE TYPICAL TWO STUDS THREE STUDS
UNO

TYPICAL STEEL STUD JAMB SECTIONS DEFLECTION TRACK TSN VERTICLIP SLD AT EACH
CONCRETE SLAB ON METAL
DECK
68 MIL x 14" x 25"
PLATE AT EACH
SCALE: NONE DEFLECTION TRACK JAMB W/ (2) #8 SCREWS IN 68 MIL x 14" x 25" JAMB TYPICAL STUD
EACH JAMB & (2) #8 PLATE AT EACH
STUD
STUD 68 MIL x 14" x CONTINUOUS PLATE W SCREWS INTO TRACK AND TSN VERTICLIP SLD AT EACH JAMB STUDS
JAMB
(1) ROWS OF HILTI X-U @ 6" O.C. PLATE
JAMB STUD JAMB W/ (2) #8 SCREWS IN
ADDITIONAL ANCHOR EACH SIDE. EMBEDMENT = 1" MIN. EACH JAMB & (2) #8
AS REQ'D. BY JAMB STUD TO FIT TIGHT SCREWS INTO TRACK AND
SCHEDULE AGAINST RADIUS OF PLATE
ADDITIONAL ANCHOR TRACK
PARALLEL TO PARALLEL TO PERPENDICULAR TO
title:
AS REQ'D. BY JAMB
PLAN VIEW PLAN VIEW SCHEDULE FLUTE AT FLUTE BETWEEN FLUTE
STEEL STUD
TRACK
SECTION
JAMB STUDS - SEE FLUTE FLUTES TRACK
A PARALLEL TO PERPENDICULAR TO
JAMB SCHEDULE
FLUTE AT FLUTE

JAMB STUDS - SEE


STUD - SEE
WALL
ATTACH TO CONCRETE
SLAB:
ATTACH TO CONCRETE
SLAB:
FLUTE SCHEDULES
SCHEDULE

JAMB BASE
JAMB SCHEDULE

JAMB BASE
TRACK
ATTACHMENT - SEE
PARTITION TYPES TYPICAL STUD
& DETAILS
ATTACHMENT - SEE ATTACHMENT - SEE
GENERAL NOTES 22 DEFLECTION TRACK
JAMB SCHEDULE JAMB SCHEDULE STURUCTURE
STUD - SEE WALL CONCRETE SLAB
SCHEDULE OPE BOTTOM TRACK -
A NIN
G SEE PARTITION
BOTTOM TRACK - A
BOTTOM TRACK SEE PARTITION
TYPE GENERAL
ATTACHMENT - TYPE GENERAL
NOTE 21.
SEE PARTITION BOTTOM TRACK NOTE 21. A
TYPE GENERAL 21. ATTACHMENT - BOTTOM TRACK NOTE:
SEE PARTITION ATTACHMENT - SEE DEFLECTION TRACK TSN VERTICLIP SLD W/ (2) SLOTS • ONLY ONE CLIP IS REQ'D FOR JAMBS AT TYPICAL
BOTTOM TRACK - TYPE GENERAL 21. PARTITION TYPE GENERAL @ EACH JAMB W/ (2) #8 SCREWS
SEE PARTITION LOCATION. WHERE JAMB CONFIG J3 AND J4 ARE
TYPE GENERAL
21.
(1) #8 SCREW @ EACH
STUD IN EACH JAMB & (2) 1/2" DIA.
HILTI HUS-EZ ANCHORS W/ 3" USED, THE CLIP MUST BE LOCATED AT THE sheet:
NOTE 21. FLANGE CENTER JAMB, OR TWO CLIPS MUST BE USE ONE
EMBEDMENT
ON EACH SIDE OF BUILT UP JAMB

JAMB BASE CONNECTIONS


SCALE: NONE
TYPICAL BOTTOM TRACK CONNECTIONS
SCALE: NONE
TOP CONNECTION TYPE 1 (DEFLECTION TRACKATTACHMENT WITHOUT VERTICLIP)
SCALE: NONE
TOP CONNECTION TYPE 2 (DEFLECTION TRACK ATTACHMENT WITH VERTICLIP)
SCALE: NONE G016 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

STANDARD FRAMING HEADER SCHEDULE


JAMB STUD DEPTH WALL HEIGHT ABOVE OPENING MAX. OPENING WIDTH HORIZONTAL HEADER COMPONENTS VERTICAL HEADER COMPONENTS CONFIGURATION TRACK CLIP TO HEADER/JAMB ATTACHMENT
2-1/2" 5'-0" 4'-0" 250T200-33 ---- H1 (2) #10 SCREWS TO HEADER/(2)#10 TO JAMB (2X2X54MIL CLIP ANGLE ONLY)
8'-0" (1)250S162-68 & (2)250T150-68 ---- H2 (4)#10 SCREWS TO HEADER/(4)#10 SCREWS TO JAMB
12'-0" (2)250S162-68 & (2)250T150-68 ---- H3 (4)#10 SCREWS TO HEADER/(4)#10 SCREWS TO JAMB

10'-0" 4'-0" (1)250S162-33 & (2)250T150-33 ---- H2 (4)#10 SCREWS TO HEADER/(4)#10 SCREWS TO JAMB

15'-0" 4'-0" (1)250S162-43 & (2)250T150-43 ---- H2 (4)#10 SCREWS TO HEADER/(4)#10 SCREWS TO JAMB L33X12GA W/4-.157" HILTI X-U PAF TO METAL DECK CONCRETE SLAB ON METAL DECK
3-5/8" 5'-0" 4'-0" 362T200-33 ---- H1 (2) #10 SCREWS TO HEADER/(2)#10 TO JAMB (2X2X54MIL CLIP ANGLE ONLY) STEEL BEAM AND 3#12 SCREW TO CFS
E 8'-0" (2)362T125-33 (2)600S137-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB BRACE E
360 west aspen avenue
12'-0" (2)362T200-43 (2)600S162-68 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB salt lake city, utah 84101
16'-0" (2)362T125-97 (2)800S137-33 H4 (8)#10 SCREWS TO HEADER/(8)#10 SCREWS TO JAMB 801 532 4422

10'-0" 4'-0" (1)362S162-33 & (2)362T150-33 ---- H2 (4)#10 SCREWS TO HEADER/(4)#10 SCREWS TO JAMB 1.5 MAX.
8'-0" (2)362T125-33 (2)600S162-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB 1
1.5 MAX.
1 MIN. .
12'-0" (2)362T150-54 (2)1000S162-68 H4 (12)#10 SCREWS TO HEADER/(12)#10 SCREWS TO JAMB M AX 1
1 -0"
CONNECT BRACING DIRECTLY
16'-0" (2)362T200-97 (2)1000S162-97 H4 (12)#10 SCREWS TO HEADER/(12)#10 SCREWS TO JAMB 10' TO ROOF FRAMING BEAM 1 MIN.
X.
362S162-33 BRACE AT 8'-0" EACH SIDE OF WEB. OR ADD L6X6X5/16 MA
1 -0" TSN STIFFCLIP CL362-68 AT EACH
WALL STAGGERED 4'-0". ALSO PROVIDE CONT BETWEEN 10'
15'-0" 4'-0" (1)362S200-33 & (2)362T200-33 ---- H2 (4)#10 SCREWS TO HEADER/(4)#10 SCREWS TO JAMB ADDITIONAL BRACING AT THE TOP OF ALL
BRACE WITH (1) 1/2" DIAMETER HILTI
STRUCTURAL SUPPORTS. KBTZ WITH 3-1/4" MIN. EMBEDMENT.
8'-0" (2)362T125-33 (2)600S162-43 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB JAMBS. IF BRACING CAN ONLY BE COPE VERT LEG & WELD TO 362S162-33 BRACE AT 8'-0" EACH SIDE OF
ATTACH TO BRACE WITH (3) #12
12'-0" (2)362T150-68 (2)1000S162-97 H4 (12)#10 SCREWS TO HEADER/(12)#10 SCREWS TO JAMB INSTALLED ON ONE SIDE, DECREASE ROOF FRAMING TOP CHORD/ WALL STAGGERED 4'-0". ALSO PROVIDE
SCREWS
SPACING TO 4'-0" FLANGE W/ 3/16" FILLED WELD ADDITIONAL BRACING AT THE TOP OF ALL
ALL AROUND JAMBS. IF BRACING CAN ONLY BE
20'-0" 4'-0" (2)362T125-33 (2)600S162-43 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB ATTACH METAL STUD INSTALLED ON ONE SIDE, DECREASE
8'-0" (2)362T125-43 (2)600S162-54 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB BRACE TO TRACK WITH SPACING TO 4'-0"
L1-1/2" x 1-1/2" x 33 MIL UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
STUD AND TRACK -SEE WALL SCHED. AND ATTACH METAL STUD DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
WITH (4) #10 SCREWS PARTITION TYPES GENERAL NOTE 20 BRACE TO TRACK WITH
STUD AND TRACK -SEE NOT INTENDED FOR CONSTRUCTION, RECORDING
INTO BRACE AND (4) L1-1/2" x 1-1/2" x 33 MIL PURPOSES, OR IMPLEMENTATION
WALL SCHED. AND
6" 5'-0" 4'-0" 600T200-33 ---- H1 (3) #10 SCREWS TO HEADER/(3)#10 TO JAMB (2X2X54MIL CLIP ANGLE ONLY) SCREWS INTO TOP WITH (4) #10 SCREWS
PARTITION TYPES
TRACK.
8'-0" (2)600T125-33 (2)600S137-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB GENERAL NOTE 20 INTO BRACE AND (4)
SCREWS INTO TOP
12'-0" (2)600T125-33 (2)600S200-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB TRACK.
16'-0" (2)600T125-43 (2)800S250-54 H4 (8)#10 SCREWS TO HEADER/(8)#10 SCREWS TO JAMB

10'-0" 4'-0" (1)600S162-33 & (2)600T125-33 ---- H2 (4)#10 SCREWS TO HEADER/(4)#10 SCREWS TO JAMB
8'-0" (2)600T125-33 (2)600S162-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB
12'-0" (2)600T125-43 (2)600S250-43 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB
16'-0" (2)600T125-43 (2)800S300-68 H4 (8)#10 SCREWS TO HEADER/(8)#10 SCREWS TO JAMB

D D
15'-0" 4'-0" (2)600T125-33 (2)600S162-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB
8'-0" (2)600T125-33 (2)600S200-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB NOTE: IF ATTACHED TO
12'-0" (2)600T200-33 (2)800S250-43 H4 (8)#10 SCREWS TO HEADER/(8)#10 SCREWS TO JAMB TRACK CLIP: STRUCTURAL STEEL
SECTION OF 54 MIL MIN. JAMB,
16'-0" (2)600T125-54 (2)1000S300-68 H4 (12)#10 SCREWS TO HEADER/(12)#10 SCREWS TO JAMB TRACK LENGTH 1-1/4"
1.5 MAX.
REPLACE EACH SCREW
LESS THAN HEADER WITH (1) HILTI X-U15 1
DEPTH. SCREW STUDS 1 MIN. TSN STIFFCLIP CL362-68 AT EACH
20'-0" 4'-0" (2)600T125-33 (2)600S162-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB P.A.F. A X. BRACE WITH (1) 1/2" DIAMETER HILTI
8'-0" (2)600T125-33 (2)600S200-33 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB ATTACHED TO JAMB PER 1 -0 "M
SCHEDULE 10' KBTZ WITH 3-1/4" MIN. EMBEDMENT.
12'-0" (2)600T150-43 (2)600S300-68 H4 (6)#10 SCREWS TO HEADER/(6)#10 SCREWS TO JAMB HEADER (1) #8 SCREW TYP. EA. FLANGE 362S162-33 BRACE AT 8'-0" EACH SIDE OF
ATTACH TO BRACE WITH (3) #12
CONNECTION SCREWS
WALL STAGGERED 4'-0". ALSO PROVIDE
(2) #8 SCREWS @ 16" O.C. ADDITIONAL BRACING AT THE TOP OF ALL
JAMBS. IF BRACING CAN ONLY BE
JAMB STUDS - SEE
INSTALLED ON ONE SIDE, DECREASE
HORIZONTAL JAMB SCHEDULE
SPACING TO 4'-0"
SECTION - TYPICAL 54 MIL X FULL HEIGHT ATTACH METAL STUD
STUD AND TRACK -SEE BRACE TO TRACK WITH
CLOSURE TRACK @ OPEN WALL SCHED. AND
FACE OF JAMB AS REQ'D - CLIP ANGLE: L1-1/2" x 1-1/2" x 33 MIL
PARTITION TYPES WITH (4) #10 SCREWS
VERTICAL ATTACH WITH #8 SCREWS @ 2" x 2" x 54 MIL CLIP GENERAL NOTE 20 INTO BRACE AND (4)
SECTION - TYPICAL 16" O.C. EACH SIDE ANGLE 1/2" LESS THAN
STUD WIDTH. USE (3) # SCREWS INTO TOP
10 SCREWS FOR 6" TRACK.
HEADER STUDS AND TRACK -
JAMB AND (2) #10 FOR SEE JAMB AND HEADER
11/2" 2.5" AND 3.625" JAMB AT SCHEDULE
H1 H2 H3 H4 EACH LEG AS SHOWN
EQ
2" .
1 1/

TYPICAL STUD HEADER SECTIONS HEADER CONNECTION DETAIL TOP OF WALL BRACING DETAIL THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
SCALE: NONE SCALE: NONE SCALE: NONE MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

USU EVR
STANDARD FRAMING SILL SCHEDULE EXPANSION
JAMB STUD DEPTH WALL HEIGHT BELOW OPENING MAX. OPENING WIDTH SILL COMPONENTS CONFIGURATION SILL TO JAMB ANGLE
2-1/2" 5'-0" 4'-0" 250T125-33 S1 2"X2"X54MIL CLIP ANGLE
BUILT-UP JAMB OR POST,
8'-0" (1)250T250-33 & (1)250S137-33 S2 2"X2"X54MIL CLIP ANGLE EXTEND CHANNEL INTO
BRIDGING PUNCH-OUT.
1.5"x54 MIL COLD ROLLED
10'-0" 4'-0" 250T125-33 S1 2"X2"X54MIL CLIP ANGLE ATTACHMENT - SEE
CHANNEL
PLAN NOTE 2"X2"X54MIL CLIP ANGLE 1/4"
8'-0" (1)250T250-54 & (1)250S137-33 S2 2"X2"X54MIL CLIP ANGLE
SCREWS LESS THAN STUD WIDTH TO BE
PLACED AT EACH STUD.
15'-0" 4'-0" 250T125-33 S1 2"X2"X54MIL CLIP ANGLE ATTACH TO STUD WITH (4)#10
8'-0" (1)250T250-68 & (1)250S162-33 S2 2"X2"X54MIL CLIP ANGLE SCREWS.
3-5/8" 5'-0" 4'-0" 362T125-33 S1 2"X2"X54MIL CLIP ANGLE
8'-0" 362T125-33 S1 2"X2"X54MIL CLIP ANGLE
12'-0" (1)362T250-43 & (1)362S162-33 S2 2"X2"X54MIL CLIP ANGLE 670 EAST 1550 NORTH, LOGAN, UT
84341
TSN BRIDGEBAR
10'-0" 4'-0" 362T125-33 S1 2"X2"X54MIL CLIP ANGLE
8'-0" (1)362T250-33 & (1)362S137-33 S2 2"X2"X54MIL CLIP ANGLE
12'-0" (1)362T250-68 & (1)362S200-33 S2 2"X2"X54MIL CLIP ANGLE

15'-0" 4'-0" 362T125-33 S1 2"X2"X54MIL CLIP ANGLE


B 8'-0" (1)362T250-33 & (1)362S137-33 S2 2"X2"X54MIL CLIP ANGLE B
p r o j e c t # : 21.0320
12'-0" (2)362T200-54 & (1)362S200-33 S3 2"X2"X97MIL CLIP ANGLE
16'-0" (2)362T200-97 & (1)362S250-97 S3 2"X2"X97MIL CLIP ANGLE JAMB STUD - SEE
d a t e : 02.14.2023
TSN BRIDGEBAR OPTION COLD ROLL CHANNEL OPTION
HEADER AND JAMB
SCHEDULE revisions :
6" 5'-0" 4'-0" 600T125-33 S1 2"X2"X54MIL CLIP ANGLE 54 MIL CLOSURE TRACK AS
8'-0" 600T125-33 S1 2"X2"X54MIL CLIP ANGLE REQUIRED - COORDINATE WITH
12'-0" 600T200-33 S1 2"X2"X54MIL CLIP ANGLE HEADER DETAILS
43 MIL STUD BLOCKING AT 10'-0" MAX.
AND AT ENDS OF WALLS AND EACH
10'-0" 4'-0" 600T125-33 S1 2"X2"X54MIL CLIP ANGLE SIDE OF OPENINGS
8'-0" 600T125-33 S1 2"X2"X54MIL CLIP ANGLE L2 x 2 x 16 GA. x SILL WIDTH
WITH (4) #10 SCREWS INTO
12'-0" (1)600T250-33 & (1)600S137-33 S2 2"X2"X54MIL CLIP ANGLE STUD AND (4) #10 SCREWS
1-1/2" x 30 MIL STRAPPING ON
INTO 6" SILL. (3) #10 SCREWS
EACH SIDE OF WALL STUD.
15'-0" 4'-0" 600T125-33 S1 2"X2"X54MIL CLIP ANGLE INTO STUD AND (3) #10
(STRAPPING TO START, END
SCREWS INTO 3.625" SILL. (2)#
8'-0" 600T200-33 S1 2"X2"X54MIL CLIP ANGLE 10 SCREWS INTO STUD AND (2)
AND SPLICE AT SOLID
BLOCKING)
12'-0" (1)600T250-33 & (1)600S137-33 S2 2"X2"X97MIL CLIP ANGLE #10 SCREWS INTO 2.5" SILL. NG
SILL - SEE SILL SCHEDULE PACI title:
16'-0" (2)600T200-43 & (1)600S200-33 S3 2"X2"X97MIL CLIP ANGLE AX.
S
SILL TRACK SHALL BLOCKING REQUIRED 0'-0" M
STUD -SEE WALL 1
NOT EXTEND TO LAP
20'-0" 4'-0"
8'-0"
600T125-33
600T200-33
S1
S1
2"X2"X54MIL CLIP ANGLE
2"X2"X54MIL CLIP ANGLE
OVER JAMB STUDS SCHEDULE FOR TYPICAL
WALL FRAMING
ADJACENT TO ALL
OPENINGS AND END OF
WALL
L2 x 2 x 43 MIL x STUD WIDTH AT
EACH SIDE OF STUD BLOCKING.
SCREW TO STUD & BLOCKING
STEEL STUD
12'-0" (1)600T250-33 & (1)600S137-33 S2 2"X2"X97MIL CLIP ANGLE WITH (2) #8 SCREWS IN EACH
16'-0" (1)600T250-68 & (1)600S162-33 S2 2"X2"X97MIL CLIP ANGLE
(1) #8 SCREW AT EACH
REFER TO JAMB STUD
SCHEDULE FOR TRACK
ATTACHMENT
(1) #8 SCREW IN
EACH STUD FLANGE
LEG OF ANGLE - FLANGES OF
STUD BLOCKING MAY BE CUT
OFF, WEB BENT & ATTACHED
SCHEDULES
FLANGE
BOTTOM TRACK - SEE
PARTITION TYPE GENERAL
NOTES OF
TO STUDSSTUD
TYPICAL
USE (6) #10 SCREWS ON EACH SIDE OF
& DETAILS
END BLOCKING
CONCRETE
G OR
NI N
OPE LL
WA
A STRAP OPTION (ABOVE CEILING
A
SILL - SEE
SCHEDULE ONLY)
EL
G LEV
LI N
SILL TRACK - SEE SCHEDULE #8 SCREWS AT 24" CEI
O.C. NOTE:
NOTE:
S1 S2 S3
• IF SILL IS ATTACH TO
• ATTACHEMNT=BRIDGECLIP WITH (1)#10 SCREW FOR TSN CLIP, OR sheet:
STRUCTURAL STEEL, REPLACE
SUBH3.25 WITH (1)#10 SCREW AND 3/8" WASHER FOR STUD WIDTH 3.625
EACH SCREW WITH (1) HILTI X-U 15
OR ABOVE.

TYPICAL SILL SECTIONS


SCALE: NONE
SILL CONNECTION DETAIL
SCALE: NONE
BRIDGING DETAIL
SCALE: NONE
• WHEN DEEP LEG DEFLECTION TRACK IS USED, INSTALL ADDITIONAL ROW
OF BRIDGING WITHIN 12" OF TOP SLIP TRACK.
G017 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES
1. DETAILS SHOWN ARE TYPICAL DETAILS & ARE BASIS OF DESIGN. IF FIELD CONDITIONS DO NOT MATCH
REQUIREMENTS OF TYPICAL DETAILS, APPROVED ALTERNATE DETAILS SHALL BE UTILIZED. FIELD CONDITIONS AND
DIMENSIONS NEED TO BE VERIFIED FOR COMPLIANCE WITH THE DETAILS, INCLUDING BUT NOT LIMITED TO THE
FOLLOWING:
- MINIMUM AND MAXIMUM WIDTH OF JOINTS
- TYPE AND THICKNESS OF FIRE-RATED CONSTRUCTION. THE MINIMUM
ASSEMBLY RATING OF THE FIRESTOP ASSEMBLY SHALL MEET OR EXCEED THE HIGHEST RATING OF
THE ADJACENT CONSTRUCTION.

2. IF ALTERNATE DETAILS MATCHING THE FIELD CONDITIONS ARE NOT AVAILABLE, MANUFACTURER'S ENGINEERING
JUDGMENT DRAWINGS ARE ACCEPTABLE. DRAWINGS SHALL FOLLOW THE INTERNATIONAL FIRESTOP COUNCIL (IFC)
GUIDELINES FOR EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS.

3. REFERENCES:
E - 2012 UNDERWRITER'S LABORATORIES FIRE RESISTANCE DIRECTORY, E
VOLUME 2.
360 west aspen avenue
- NFPA 101 LIFE SAFETY CODE. salt lake city, utah 84101
- ALL GOVERNING LOCAL AND REGIONAL BUILDING CODES. 801 532 4422
4. FIRESTOP SYSTEM INSTALLATION MUST MEET REQUIREMENTS OF ASTM E-814 (UL 1479) TESTED ASSEMBLIES
THAT PROVIDE A FIRE RATING EQUAL TO THAT OF CONSTRUCTION BEING PENETRATED.

5. ALL RATED THROUGH-PENETRATIONS SHALL BE PROMINENTLY LABELED WITH THE FOLLOWING


INFORMATION:
- ATTENTION: FIRE RATED ASSEMBLY
- UL SYSTEM #
- PRODUCT(S) USED
- HOURLY RATING (F-RATING)
- INSTALLATION DATE

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

D D

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

USU EVR
EXPANSION

670 EAST 1550 NORTH, LOGAN, UT


84341

B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :

title:

FIRE
PENETRATION
DETAILS

A A

sheet:

1 Fire Penetration Details


12" = 1'-0"
G501 BID SET
1 2 3 4 5 6
1 2 3 4 5 6
FOR BLOCKWORK / CONC. WALLS, PIPE
MORTAR TO SLEEVE AT FULL DEPTH COVERPLATE OF 5/8" GYP. BD. MDF OR OTHER FOR BLOCKWORK / CONCRETE WALLS,
GWB (# OF LAYERS PER GWB (# OF LAYERS PER PIPE INSULATION AND CLAMP INSERTS AS
OF PARTITION APPROVED BUILDING BOARD (MIN SURFACE MASS MORTAR TO SLEEVE AT FULL DEPTH OF
SPEC'S) SPEC'S) SCHEDULED PARTITION SPECIFIED OR DETAILED ELSEWHERE
2 PSF) BEDDED IN RESILIENT SEALANT. PARTITION
COVERPLATE TO COMPRESS EXTERNAL NON-HARDENING RESILIENT SEALANT PIPE RISER CLAMP PLAN
GLASS FIBER GLASS FIBER SCHEDULED PARTITION INSULATION BUT NOT INTERRUPT INSULATION OR & FOAM CYLINDER BACKER ROD AS NEOPRENE PAD BETWEEN PIPE CLAMP ELECTRICAL BOX TO BE SEALED
INSULATION PER SPEC'S INSULATION PER SPEC'S CONTACT PIPE/DUCT. VAPOR BARRIER AIRTIGHT WITH FIRE-SAFING PUTTY
REQUIRED AND STRUCTURE TO PRECLUDE RIGID
CONTINUED UNDER COVER PLATE WHERE DUCT OR PIPE WITH INSULATION AS CONTACT
NON-HARDENING CAULK ON DUCT OR PIPE WITH INSULATION AS APPLICABLE
NON-HARDENING CAULK ON SPECIFIED
POLYETHYLENE FOAM ROD SPECIFIED
1" MAX POLYETHYLENE FOAM ROD

1" MAX

1" MAX
JUNCTION BOXES SEPARATED BY METAL

1" MAX

1" MAX
STUD

16" MIN SPACING


SECTION
STRUCTURE

DUCT (LINED) DUCT (LINED) PIPE INSULATION AND INSERTS AS


WALL AS SCHEDULED
STEEL SLEEVE SPECIFIED
E E

1" MAX
NON-HARDENING RESILIENT SEALANT FIBERGLASS 2 PCF TO 3 PCF PACKED AND NEOPRENE PAD BETWEEN PIPE CLAMP 360 west aspen avenue
& FOAM CYLINDER BACKER ROD AS STEEL SLEEVE AND STRUCTURE TO PRECLUDE RIGID
COMPRESSED TO FULL DEPTH GENERAL NOTE salt lake city, utah 84101
REQUIRED ALTERNATE - EXPANDABLE FOAM CONTACT
GLASS FIBER PACKING
FIBERGLASS 2 PCF TO 3 PCF PACKED AND 1. PURPOSE: FLANKING SOUND REDUCTION 801 532 4422
GLASS FIBER PACKING COMPRESSED TO FULL DEPTH THROUGH JUNCTION BOXES. NOT FOR
ALTERNATE - EXPANDABLE FOAM PLAN CONSTRUCTION.
FRAMING AROUND DUCT PIPE RISER CLAMP
SLEEVE BUILT INTO WALL GENERAL NOTES:
PENETRATION
GENERAL NOTES: GENERAL NOTES: NO RECESSED RECEPTACLES ALLOWED IN
ISOLATED PRACTICE/REHEARSAL/STUDIO
1. DUCT AND PIPE SUPPORTS TO BE SPACED SUFFICIENTLY FROM PARTITION LINE TO ALLOW ACCESS FOR
1. PURPOSE: TO REDUCE PIPE VIBRATION TRANSMISSION TO THE STRUCTURE IN VERTICAL RISERS. ROOMS WITH MULTILAYER GYPSUM WALLS
DUCT PENETRATION THROUGH SINGLE AND DOUBLE PIPE OR CONDUIT PENETRATION THROUGH SINGLE 1. DUCT AND PIPE SUPPORTS TO BE SPACED SUFFICIENTLY FROM PARTITION LINE TO ALLOW ACCESS FOR INSTALLATION AND SEALING.
2. DO NOT USE FOR PIPING THAT REQUIRES FIXATION TO THE STRUCTURE.
GWB/STUD NOISE CRITICAL WALL AND DOUBLE GWB/STUD NOISE CRITICAL WALL INSTALLATION AND SEALING. 2. IN BLOCKWORK PARTITIONS, THICKNESS OF STEEL SLEEVE TO BE SUFFICIENT TO SUPPORT MORTAR
3. THICKNESS OF NEOPRENE PADS SHOULD BE AT LEAST 10% OF PIPE DIAMETER.
2. THICKNESS OF STEEL SLEEVE TO BE SUFFICIENT TO SUPPORT MORTAR ABOVE. MINIMUM THICKNESS ABOVE. MINIMUM THICKNESS 1/16".
4. SHORE DUROMETER OF NEOPRENE NOT GREATER THAN 60.
1/16" 3. FOR PIPE: STEEL SLEEVE NOT REQUIRED FOR CORE -DRILLED HOLES

Duct Penetration - Single / Double Wall Pipe Penetration - Single / Double Wall Multiple Pipe / Duct Penetration Coverplates Typical Duct or Pipe Penetration Neoprene Pad Riser Junction Box Flanking Sound Isolation
E1 1N O1/2" = 1'-0"
SCALE
E2 N1O1/2" = 1'-0"
SCALE
E3 NO3" = 1'-0"
SCALE
E4 3"SCALE
NO = 1'-0" E5 1 SCALE
NO :6 E6 1 :SCALE
NO 7

MIN 1" CLEAR FILLED W/ MULTIPLE PIPEWORK UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
0' - 8" MAX 1" MIN
PENETRATIONS DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
1" MIN LOOSE FIBER BATT NOT INTENDED FOR CONSTRUCTION, RECORDING
SPACE INSULATION
MIN 1" LONG STRAND FIBERGLASS AIR DUCT COVERPLATE INSTALLED IN TWO SECTIONS. SEAL ALL PURPOSES, OR IMPLEMENTATION
0' - 0 25/32" SPACE
PIPE OF DUCT INSULATION CUT AT 1/2" MIN 'TREMCO' FYRE-SHIELD JOINTS WITH APPROVED NON-HARDENING SEALANT
FACE OF BLOCK SEALANT ACOUSTIC LIMP-MASS LAGGING EQUIVALENT
MIN 1" CLEAR FILLED W/ SET BOX FLANGES IN
ACOUSTICAL SEALANT TO KINETICS KNM-ALQ100.SECURE WITH
LOOSE FIBER BATT PLASTIC OR METAL STRAPS OR PER MFR'S
PIPE OR DUCT INSUL. CONTINUES POLYURETHANE BACKER ROD INSULATION
BEYOND ESCUTCHEON AS NEC RECOMMENDATIONS
CAP OPEN, UNUSED
SHEET CAULKING ALL AROUND KNOCKOUTS
BACK & SIDES OF BOX SEQUENCE OF INSTALLATION
SECTION 1. PIPE / DUCT WITH INSULATION
MIN ONE LAYER 5/8" GYP BD OR OVERLAP AND TAPE MASS LAYER SEAMS PER
PLASTER CONTINUOUS CLOSER MANUFACTURER'S RECOMMENDATIONS MULTIPLE DUCT 2. WALL AND MORTAR SEAL
ELECTRICAL BOX UP TO 4"x8" IN
ENCASE SLEEVE IN GYP. BD. BEHIND RECESSED BOX. BUILD FIRST PENETRATIONS 3. COVER PLATE
GROUT IF REQUIRED

6" MIN
4. THERMAL INSULATION
D STEEL PIPE D
SLEEVE ACOUSTICAL SEALANT FULL DEPTH IN
1/4" TO 1/2" JOINT ALL AROUND BOX DETAIL ALL PENETRATIONS AND JOINTS
PLASTER RING AIRTIGHT
PENETRATIONS AS DETAILED ELSEWHERE
MIN 18 GA. SHEET METAL AIR DUCT
ESCUTCHEON SET IN ACOUSTICAL SEAL ANY CONDUIT
CAP OPEN, UNUSED PENETRATING BOX BACKING
SEALANT AGAINST BLOCK AND KNOCKOUTS
PENETRATING ELEMENT MASONRY WALL FIRE RATED
WALL TYPE PER PLAN - SEE ALSO WALL TYPE PER PLAN - SEE ALSO COVERPLATE INSTALLED SECTIONS AS
AE501& AE502 FOR WALL TYPE SECURE LIMP MASS LAYER TO WALLS AT
AE501& AE502 FOR WALL TYPE NEEDED . SEAL ALL JOINTS WITH APPROVED
CONSTRUCTION PENETRATIONS WITH MECHANICAL FASTENERS AND
ACOUSTICAL SEALANT FULL DEPTH CONSTRUCTION NONHARDENING SEALANT
SECTION AT WALL TAPE
IN 1/4" TO 1/2" ANNULAR JOINTS

Resiliently Sup. Pipe, Conduit, or Duct Rated Pipe Penetration ADJUSTABLE Recessed Element Detail Duct Limp Mass Acoustic Lagging Penetration Coverplate Elevation
D1 3" = 1'-0" D2 3" = 1'-0" D3 3" = 1'-0" D4 3" = 1'-0" D5 1 1/2" = 1'-0" D6 1 1/2" = 1'-0"

EXPANSION ANCHOR SOUND BATTS WHERE


INDICATED ONE HOUR WALL, UL MIN 1" LONG STRAND FIBERGLASS
ACOUSTICAL SEALANT FULL DEPTH IN 1/4" - DESIGN NO. U465 MIN 1" LONG STRAND FIBERGLASS PIPE OF DUCT INSULATION CUT AT
1/2" JOINT 25 GA G.I. RUNNER
PIPE OF DUCT INSULATION CUT AT FACE OF BLOCK
25 GA, G.I. SLEEVE FACE OF BLOCK
PIPE OR DUCT INSUL. CONTINUES
CAULK - MIN 1/4" DIA. CONT. BEAD APPLIED TO LEADING EDGE OF 3" MIN PROVIDE MIN. 3" SOLID BEYOND ESCUTCHEON AS NEC
WRAP STRIP PRIOR TO INSERTION OF WRAP STRIP LAYER IN PROVIDE MIN. 3" SOLID
BACKING BACKING ACOUSTICAL SEALANT FULL DEPTH
ANNULAR SPACE. AFTER INSERTION OF WRAP STRIP LAYER IN
ANNULAR SPACE A NOMINAL 1/4" DIA. CONT. BEAD IS TO BE APPLIED IN 1/4" TO 1/2" ANNULAR JOINTS
TO THE WRAP STRIP/WALL INTERFACE AND TO THE EXPOSED EDGE 0' - 3"
5/8" GYP BD. OF THE STRIP LAYER APPROXIMATELY 3/4" FROM THE WALL SURFACE. THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
MINNESOTA MINING & MANUFACTURING CO. TYPES CP-25 S/L, CP-25 ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
N/S CAP OPEN, UNUSED MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
KNOCKOUTS CAP OPEN, UNUSED COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
KNOCKOUTS WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
MOLLY BOLT WRITTEN PERMISSION FROM METHOD STUDIO INC.
C ACOUSTICAL SEALANT SET IN PILOT HOLE
WRAP STRIP - 1/4" INTUMESCENT ELECTROMETRIC MATERIAL
FACED ON ONE SIDE WITH ALUMINUM FOIL, SUPPLIED IN 2" WIDE
C
BEFORE INSERTION OF DEVICE STRIPS. NOMINAL 2" WIDE STRIP TIGHTLY WRAPPED AROUND
STEEL PIPE, STEEL CONDUIT OR PIPE COVERING (FOIL SIDE OUT) GROUT FILL VOIDS BEHIND GROUT FILL VOIDS BEHIND
project:
MIN 18 GA. SHEET METAL MIN 18 GA. SHEET METAL
WITH SEAM BUTTED. WRAP STRIP LAYER SECURELY BOUND WITH AND AROUND BOXES AND AROUND BOXES
ESCUTCHEON SET IN ACOUSTICAL ESCUTCHEON SET IN ACOUSTICAL
STEEL WIRE OR ALUMINUM FOIL TAPE AND SLID INTO ANNULAR
SPACE APPROXIMATELY 1-1/4" SUCH THAT APPROX 3/4" OF THE
WRAP STRIP WIDTH PROTRUDES FROM THE WALL SURFACE.
SEALANT 1/2" TO 1" SEALANT AGAINST BLOCK AND
PENETRATING ELEMENT USU EVR
MINNESOTA MINING & MANUFACTURING CO. TYPE FS-195
GYP BOARD ESCUTCHEONS AS
REQUIRED TO REDUCE ANNULAR
GAP TO 2 1/2". FOR JOINTS OVER 1"
ACOUSTICAL SEALANT FULL DEPTH
IN 1/4" TO 1/2" ANNULAR JOINTS
EXPANSION
5/8" GYP BD. STEEL PIPE OR CONDUIT

Pennetration thru Gyp Bd. - Bolt Pipe / Conduit Penetration - Rated Wall Recessed Element Detail - Masonry Recessed Element Detail - Masonry Rigidly-Sup. Pipe, Conduit, or Duct Rigidly Sup. Pipe, Conduit, or Duct
C1 3" = 1'-0" C2 1 1/2" = 1'-0" C3 3" = 1'-0" C4 3" = 1'-0" C5 3" = 1'-0" C6 3" = 1'-0"
GYP BD. WALL SEE WALL TYPES AE501
GYP BD. BROUGHT TO METAL SLEEVE AND GYP BD. WALL SEE WALL TYPES
1/2" TO 1" ANNULAR JOINT PACKED WITH AE501
GLASS FIBER AND CAULKED A MIN. 1" DEEP
WITH ACOUSTICAL SEALANT AS SHOWN ON GYP BD. BROUGHT TO METAL SLEEVE AND
BOTH SIDES 1/2" TO 1" ANNULAR JOINT PACKED WITH
GLASS FIBER AND CAULKED A MIN. 1" DEEP
WITH ACOUSTICAL SEALANT AS SHOWN ON FRAMED OPENING AROUND CABLE TRAY,
COORDINATE SIZE WITH SCHEDULED SCHEDULED ACOUSTIC WALL
BOTH SIDES
PENETRATING ELEMENTS SEPARATED TO
TRAY 670 EAST 1550 NORTH, LOGAN, UT
GROUT ACOUSTIC SEALANT OR FIRE FACILITATE SEALING.
84341
CARRIER PUTTY TO MIN 2" DEPTH MINERAL WOOL INFILL, PACK TIGHTLY AROUND MINERAL WOOL INFILL, PACK TIGHTLY AROUND
ELECTRICAL DUCT FILLED FULL-WIDTH OF
CONSTRUCTION AFTER WIRES ARE PULLED CABLE TRAY AND CABLES AT PENETRATION CABLE TRAY AND CABLES AT PENETRATION
HANGER ROD, PIPE, OR WIRE THROUGH WALL (TYP. AT ACOUSTIC WALL THROUGH WALL (TYP. AT ACOUSTIC WALL
WITH FOAMED-IN-PLACE SILICONE. WIRES
PENETRATIONS) PENETRATIONS)
SEPARATED AS SHOWN.
ACOUSTICAL SEALANT FULL DEPTH IN 1/4" - FIRE-BARRIER PUTTY, MIN. 40-PCF DENSITY,
1/2" JOINT TO 1/4" WALL THICKNESS EACH SIDE. CABLE TRAY, REFER TO ELECTRICAL DRAWINGS

B B
p r o j e c t # : 21.0320

0' - 6" CLEAR, TYP.


MASONRY OR CONCRETE BROUGHT TO d a t e : 02.14.2023
METAL SLEEVE AND 1/2" TO 1" ANNULAR
JOINT PACKED WITH GLASS FIBER AND
CAULKED WITH ACOUSTICAL SEALANT AS
MASONRY OR CONCRETE BROUGHT TO
METAL SLEEVE AND 1/2" TO 1" ANNULAR
revisions :
5/8" GYP BD. SHOWN ON BOTH SIDES JOINT PACKED WITH GLASS FIBER AND
MASONRY OR CONCRETE SEE WALL CAULKED WITH ACOUSTICAL SEALANT AS SCHEDULED CEILING (PROVIDE ACOUSTIC BATT
TYPES AE501 SHOWN ON BOTH SIDES ABOVE ALL ACOUSTICALLY RATED ROOMS)
NOTES:
1. PROVIDE LINTELS AS REQUIRED ABOVE PENETRATIONS.
2. INTERRUPT INSULATION OUTSIDE PIPES & DUCTS AT PENETRATIONS WALL SECTION
MASONRY OR CONCRETE SEE WALL
TYPES AE501

Pennetration thru Gyp Bd. - Hanger Rigidly Sup. Pipe, Conduit, or Duct -CMU Penetration Detail Penetration Detail - Electrical Duct Penetration Detail - Cable Tray
B1 3" = 1'-0" B2 3" = 1'-0" B3 3" = 1'-0" B4 3" = 1'-0" B5 1/2" = 1'-0"

title:

TYPICAL
SOUND
ISOLATION
DETAILS
A A

sheet:

G502 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

URBAN FORESTRY SCHEDULE


SYMBOL DESCRIPTION QTY DETAIL

T-101 EXISTING TREE TO REMAIN

T-102 TREES TO BE REMOVED OR RELOCATED BY UTAH STATE


UNIVERSITY LANDSCAPE OPERATIONS AND MAINTENANCE
(LOAM)

T-103 TREE PROTECTION FENCE. (SEE TREE PROTECTION NOTE 2.)

E E
360 west aspen avenue
salt lake city, utah 84101
801 532 4422
GENERAL NOTES:
TE OF UTA
1. TWO PRESERVATION ZONES HAVE BEEN SHOWN FOR EACH TREE OF CONCERN. TA

H
S
2. ANY TREE NOT SPECIFICALLY SHOWN ON PLAN AS "TO BE REMOVED" OR "TO
E REMAIN" SHALL BE PROTECTED.
JACOB A.

HI T E C T
L IC E NS E D
D D
3. COORDINATE WITH UTAH STATE UNIVERSITY ARBORIST IN AREAS WHERE HENDRICKSON
D DISTURBANCE IS REQUIRED UNDER THE DRIPLINE OF THE TREE.
S D 10110348

RC
LA

4586
T-103 T-101 TYP 1550 NORTH ND S C A P E A
T-102 S

4588
W W W
T-103

4590
W

W
WW
UTAH STATE UNIVERSITY TREE PROTECTION
W UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
C
NOTES: DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
1. TREE PRESERVATION ZONES SHALL BE ESTABLISHED BENEATH TREES TO BE NOT INTENDED FOR CONSTRUCTION, RECORDING
SAVED. THE AREA OF A TREE PRESERVATION ZONE WILL EITHER BE THE AREA PURPOSES, OR IMPLEMENTATION
E BENEATH THE DRIP-LINE OF THE TREE'S CANOPY PLUS 10 FEET, OR AN AREA

CB
EQUAL TO THE RADIUS OF ONE FOOT FOR EVERY INCH OF TRUNK DIAMETER AT
CB
BREAST HEIGHT (DBH), WHICHEVER IS GREATER.
I 2. FENCES WILL BE INSTALLED AROUND THE TREE PRESERVATION ZONE BEFORE
ANY OTHER CONSTRUCTION ACTIVITIES BEGIN. THE FENCING MATERIAL WILL BE

88
45
WOOD, CHAIN-LINK, OR ANY OTHER EQUALLY STURDY MATERIAL. PLASTIC
NETTING IS NOT ACCEPTABLE. FENCES WILL BE SECURELY ANCHORED TO
E PREVENT THEM FROM BEING MOVED. NO DIGGING, DUMPING, STORAGE OR
E

CB
E VEHICLE TRAFFIC WILL BE PERMITTED WITHIN THE FENCED AREA. AND THERE
E
SCO
WILL BE NO ACCESS EXCEPT FOR TREE WATERING OR TREE HEALTH
E
E EVALUATION. CONTRACTOR TO COORDINATE WITH UTAH STATE UNIVERSITY
CB
T-103 ARBORIST FOR PLACEMENT AND REMOVAL OF TREE PROTECTION FENCES.
3. CONTRACTORS WILL BE REQUIRED TO WATER PROTECTED TREES WITHIN THE
T-103 E
E
CONSTRUCTION AREA ON A REGULAR BASIS DURING THE GROWING SEASON,
E
4588
T-103 T-102 AND SPECIFICATIONS WILL BE WRITTEN IN THE CONTRACT.
D E
4. ALL STAGING AREAS AND ACCESS ROUTES SHOULD BE PLACED AS FAR AWAY
FROM PROTECTED TREES AS POSSIBLE.
D
E
5. TRENCHING WILL BE PROHIBITED WITHIN A DISTANCE OF FIVES TIMES THE DBH
E
C OF A TREE. IF UTILITIES MUST BE RUN WITHIN THAT DISTANCE, THEY SHOULD BE
E
TUNNELED BENEATH THE ROOT SYSTEM AT A DEPTH OF AT LEAST 18 INCHES.
6. GRADE CHANGES WILL NOT BE MADE WITHIN THE TREE PRESERVATION ZONE.
SCO

S S
D
CB

SCO

S
E E E E E
GM
E
x
E E
E

x
T-103

x
x
x
x

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
4588

COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN

700 EAST
W WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
D BUILDING ADDITION project:
T-103
USU EVR
D
4590

E
EXPANSION
4588

TYP T-101
4586

4596
4590
4588

670 EAST 1550 NORTH, LOGAN, UT


4588

84341

S
B B
CB

p r o j e c t # : 21.0320
CB

d a t e : 02.14.2023

458
8
revisions :

CB

T-103

title:
4590

T-101

T-101

N
4592

TREE
PROTECTION
P:\2021\21-170 USU EVR\AutoCAD\Landscape\Sheet Set\21-170 LND

T-103
PLAN
A A

0 30' 60'

sheet:

THESE PLANS AND SPECIFICATIONS ARE THE PROPERTY OF CIVIL SOLUTIONS GROUP,
INC, AN SHALL NOT BE PHOTOCOPIED, RE-DRAWN, OR USED ON ANY OTHER PROJECT
OTHER THAN THE PROJECT SPECIFICALLY DESIGNED FOR, WITHOUT WRITTEN
PERMISSION. THE OWNERS AND ENGINEERS OF CIVIL SOLUTIONS GROUP, INC.
DISCLAIM ANY LIABILITY FOR ANY CHANGES OR MODIFICATIONS MADE TO THESE
PLANS OR THE DESIGN THEREON WITHOUT THEIR CONSENT. THESE PLANS ARE
DRAWN TO SCALE WHEN PLOTTED ON A 24" X 36" SHEET OF PAPER. THESE PLANS ARE
L100
BID SET
PRODUCED IN COLOR AND SHOULD BE PLOTTED AS SUCH.

1 2 3 4 5 6
1 2 3 4 5 6

REFERENCE NOTES SCHEDULE PLANT SCHEDULE


SYMBOL DESCRIPTION QTY DETAIL TREES CODE QTY BOTANICAL / COMMON NAME SIZE CAL

1 EXISTING SOLAR PANELS


MP 2 MALUS X `PRAIRIFIRE` / PRAIRIFIRE CRABAPPLE B&B 2"CAL
2 EXISTING LANDSCAPE AND IRRIGATION TO REMAIN

3 SWALE. SEE CIVIL PLANS PU 11 PICEA PUNGENS `BABY BLUE EYES` / BABY BLUE EYES COLORADO BLUE SPRUCE 6` HT

4 PROTECT EXISTING LANDSCAPE AND TREES WHERE POSSIBLE.


PLANTS AND MULCH TO REMAIN. NEW ROCKS AND PLANTS TO ZM 2 ZELKOVA SERRATA `MUSASHINO` / MUSASHINO JAPANESE ZELKOVA B&B 2"CAL
MATCH EXISTING
E E
E 5 6` TWIST TOP SELVEDGE 6 GAUGE CHAINLINK FENCE WITH 360 west aspen avenue
SHRUBS CODE QTY BOTANICAL / COMMON NAME CONT HEIGHT
KNUCKLED BOTTOM SELVEDGE. FABRIC MESH SIZE TO MATCH salt lake city, utah 84101
D D
D EXISTING. TOP RAIL SHALL BE 1-3/8". REUSE EXISTING FABRIC CB 31 CARYOPTERIS X CLANDONENSIS 'BLUE MIST' / BLUE MIST BLUEBEARD 3 GAL. 801 532 4422
S D AND TOP RAILS WHERE POSSIBLE. (ESTIMATED 330` OF NEW
FABRIC NEEDED. CONTRACTOR TO VERIFY.) NEW POSTS TO BE

6
458
6 1550 NORTH S
USED AS NEEDED. JB 9 JUNIPERUS HORIZONTALIS `BLUE CHIP` / BLUE CHIP JUNIPER 5 GAL.
TA
TE OF UTA

4588
W W W
6

H
4590
15

S
6 6 EXISTING MULCH TO REMAIN. REPAIR AS NEEDED.
W
JACOB A.

HI T E C T
L IC E NS E D
W PH 17 PINUS SYLVESTRIS 'HILLSIDE CREEPER' / HILLSIDE CREEPER SCOTCH PINE 5 GAL HENDRICKSON
WW
W 7 MOWSTRIP TO BE REMOVED
C
8
10110348
CONCRETE MOWSTRIP: 6" WIDE 10/L403 RR 29 RHAMNUS FRANGULA `FINE LINE` / FINE LINE BUCKTHORN 5 GAL.

RC
LA
E ND S C A P E A
9 CANTILEVER SLIDING GATE AND ROLLERSTO BE REMOVED AND
CB

STORED FOR RELOCATION ON THE NORTH SIDE OF THE RG 11 RHUS AROMATICA `GRO-LOW` / GRO-LOW FRAGRANT SUMAC 5 GAL.
CB
5 15 I 10 PROPERTY. FIELD VERIFY LOCATION.
2

88
45
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
10 CONCRETE PAD FOR IRRIGATION FILTER. SEE IRRIGATION PLAN. RG3 27 RIBES ALPINUM `GREEN MOUND` / GREEN MOUND ALPINE CURRANT 5 GAL. DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
E
E 5 11 EXISTING SIGN TO BE RELOCATED. SEE CIVIL PLANS. PURPOSES, OR IMPLEMENTATION
CB

E
8 E
SCO

GRASSES CODE QTY BOTANICAL / COMMON NAME CONT HEIGHT


E
E 12 GALVANIZED FENCE POST IN SLEEVE IN CONCRETE. SEE DETAIL. 9/L403
BG2 12 BOUTELOUA GRACILIS / BLUE GRAMA GRASS 1 GAL.
CB

E
E 13 RELOCATE EXISTING CANTILEVER SLIDING GATE (ONE SIDE, 11/L403
E APPROXIMATELY 24` WIDE) FROM EAST SIDE OF THE PROPERTY
4588

20 TO THIS LOCATION. THIS WILL BE A MANUAL SLIDING GATE WITH PS2 29 PANICUM VIRGATUM 'SHENANDOAH' / SHENANDOAH SWITCH GRASS 1 GAL.
E
E NO REMOTE OR CONTROL BOX. THE GATE SHALL BE INSTALLED
4 E
C
TO COMPLY WITH ASTM F2200 STANDARDS. GATE SHALL BE
E INSTALLED LEVEL. SEE A/L200 SS 39 SCHIZACHYRIUM SCOPARIUM `THE BLUES` / THE BLUES LITTLE BLUESTEM 1 GAL.
7
SCO

S
D
14 EXISTING CANTILEVER SLIDE GATE TO BE RELOCATED TO THIS 11/L403
S
CB

SCO

S LOCATION. (APPROXIMATELY 37`4" WIDE) FIELD VERIFY SIZE. PERENNIALS CODE QTY BOTANICAL / COMMON NAME CONT HEIGHT
E GATE SHALL BE INSTALLED TO COMPLY WITH ASTM F2200
D x
GM
E E E E E
7 STANDARDS AND SHALL BE INSTALLED LEVEL. HH 15 HEMEROCALLIS X 'HAPPY RETURNS' / HAPPY RETURNS DAYLILY 1 GAL. D
E E
E
15 30` X 30` SIGHT TRIANGLE (STREET/DRIVE INTERSECTION)
x

16 EXISTING CONTROL BOX TO BE RELOCATED TO THE LOCATION


SHOWN. INSTALL PER MANUFACTURERS RECOMMENDATIONS.
x

PLANTING NOTES:
5 17 GATE CONTROLLER TO BE MOUNTED ON POST PER
MANUFACTURERS RECOMMENDATIONS. 1. FOR PLANTING NOTES AND DETAILS SEE L401.
x

2. CONTRACTOR TO VERIFY QUANTITIES.


18 4" POST WITH CANTILEVER ROLLERS FOR GATE.
x

19 LANDSCAPE BY OTHERS
3
20 CONCRETE CURB AND GUTTER. SEE CIVIL PLANS.
x

21 EXISTING MOWSTRIP TO REMAIN

E
SYMBOL DESCRIPTION QTY DETAIL

ROCK MULCH, 1"-3" (COPPER CANYON CRUSHED ROCK FROM 43,515 SF 10/L403
STAKER PARSON OR APPROVED EQUAL) INSTALLED AT DEPTH
OF 3"
4588

700 EAST
W

4 COBBLE, 2-6" (SNAKE RIVER COBBLE FROM STAKER PARSONS 6,101 SF 10/L403

D
BUILDING ADDITION OR APPROVED EQUAL) INSTALLED 5" DEEP.
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
EXISTING VEGETATION AND MULCH TO REMAIN. REMOVE WEEDS, 2,234 SF MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
3 SUCKERS, AND ANY DEAD WOOD/VEGETATION. REPAIR AS COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
NEEDED WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C 8 C
D 8 9
E ROCK MULCH, PISGAH 1" FROM "STAKER PARSON" OR
APPROVED EQUAL INSTALLED AT 3" DEPTH.
744 SF 10/L403
project:

BARK MULCH (SMALL BARK MULCH FROM MILLER COMPANIES LC 8,381 SF 10/L403 USU EVR
OR APPROVED EQUAL) INSTALLED AT DEPTH OF 3" WITHOUT
4590

EXPANSION
4588

WEED BARRIER FABRIC.

7
7
GATE EXHIBIT A (OPEN POSITION)
4586

12
4596
4590
4588

1
4588

S 670 EAST 1550 NORTH, LOGAN, UT


84341
4
CB

11 17
CB
18
18
14
21
0 10' 20' 16 13
8
458

5
B B
p r o j e c t # : 21.0320

GATE EXHIBIT B (CLOSED POSITION) d a t e : 02.14.2023

CB revisions :
8 12 17

5
4590

19 18
4592

title:
18
8
14
0 10' 20' 16 13
N
LANDSCAPE
P:\2021\21-170 USU EVR\AutoCAD\Landscape\Sheet Set\21-170 LND

PLAN
A A

0 30' 60'

sheet:

THESE PLANS AND SPECIFICATIONS ARE THE PROPERTY OF CIVIL SOLUTIONS GROUP,
INC, AN SHALL NOT BE PHOTOCOPIED, RE-DRAWN, OR USED ON ANY OTHER PROJECT
OTHER THAN THE PROJECT SPECIFICALLY DESIGNED FOR, WITHOUT WRITTEN
PERMISSION. THE OWNERS AND ENGINEERS OF CIVIL SOLUTIONS GROUP, INC.
DISCLAIM ANY LIABILITY FOR ANY CHANGES OR MODIFICATIONS MADE TO THESE
PLANS OR THE DESIGN THEREON WITHOUT THEIR CONSENT. THESE PLANS ARE
DRAWN TO SCALE WHEN PLOTTED ON A 24" X 36" SHEET OF PAPER. THESE PLANS ARE
L200
BID SET
PRODUCED IN COLOR AND SHOULD BE PLOTTED AS SUCH.

1 2 3 4 5 6
1 2 3 4 5 6

IRRIGATION SCHEDULE
SYMBOL DESCRIPTION QTY DETAIL

I-101 CONNECT TO METER. SEE CIVIL PLANS FOR SIZE AND LOCATION.

I-102 REMOVE EXISTING FILTER. MINI SIGMA FILTER TO BE USED. SEE


IRRIGATION LEGEND.

I-103 CONTRACTOR TO PROVIDE POWER TO CONTROLLER

E I-104 EXISTING VALVES TO REMAIN E


360 west aspen avenue
I-105 CONNECT TO EXISTING MAINLINE PER ALL APPLICALBE salt lake city, utah 84101
PLUMBING CODES AND REGULATIONS. 801 532 4422
I-106 INSTALL SLEEVE BY BORING. NO SAW CUTTING AND PATCHING
SHALL BE ALLOWED WITHOUT THE WRITTEN APPROVAL OF THE
TE OF UTA
OWNER`S REPRESENTATIVE. TA

H
S
EXHIBIT A MAINLINE TO BE ABANDONED I-107
JACOB A.

HI T E C T
EXISTING VALVES TO BE REMOVED. CUT AND CAP PIPE.

L IC E NS E D
D D
HENDRICKSON
S D D
D
I-108
4586

S
AREA DRAIN. CONNECT MINI SIGMA FILTER OUTLET TO THIS
I-111 10110348

4586
2 3
1550 NORTH LOCATION.

RC
S
S LA

4588
ND S C A P E A
W W W
1 1550 NORTH

4588

4590
W W W 1" 2.8 1 2 " 13.1 4
1550 NORTH 5 W

4590
W
W WW
W W I-109 EXTEND EXISTING SLEEVE (FIELD VERIFY LOCATION)
3
I-102 112" 5.37 1" 3.3 W X
C

4" 1" 1" 3


4" W X X X X XX
W
E
X X
X
I-110 BALL VALVE TO BE REMOVED. CUT AND CAP PIPE.
X
C
E
I-111 UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND

X
3
I

EXISTING PIPE CONNECTED TO PROPERTY TO THE WEST TO DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
4"

88
45
1
1 4" D REMAIN. CUT AND CAP AS NEEDED. REMOVE ALL EMITTERS AND

X
E NOT INTENDED FOR CONSTRUCTION, RECORDING
HYD
1
E
E
E
I-112 D SPRINKLERS WITHIN THE PROJECT BOUNDARY. PURPOSES, OR IMPLEMENTATION

X
1 4"
SCO
E
E
E E

I-112 EXISTING MAINLINE TO BE ABANDONED

X
I

E
E

88
45
E

I-109 D I-101 458


8

X
SYMBOL DESCRIPTION QTY DETAIL
I-108 3
4"
HYD E
E

X
E
E E C
E
E D EXISTING DRIP IRRIGATION TO REMAIN. 2,265 SF

X
SCO SCO

E S S
D
I-105 E
E SCO

X
E E E E E
GM
E
E E
E E

X
E C

x
E I-106

X
4588

I-104
I-109

X
D
E
E
IRRIGATION SCHEDULE D

X
E
E
E
I-112 SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY PSI DETAIL

X
E

I-103

700 EAST
x

X
SCO

S S
D D
RAIN BIRD RD-06-U U10 SERIES
SCO
E 20 30
S E TURF SPRAY, 6IN. POP-UP. 1/2IN. NPT FEMALE THREADED

X
E
E E E E E INLET.
E E
E

X
GM
x
1 E E RAIN BIRD RD-06-U HE-VAN SERIES
E 5 30

X
I-107 1" 3.0 TURF SPRAY, 6IN. POP-UP. 1/2IN. NPT FEMALE THREADED
x

I-112

4588
E
C INLET.

X
E
W

SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY DETAIL

X
6
x

E
D

X
1" 2.9 E
E
RAIN BIRD XCZ-100-PRB-COM
WIDE FLOW DRIP CONTROL KIT FOR COMMERCIAL
4 5/L402

X
x

APPLICATIONS. 1" BALL VALVE WITH 1" PESB VALVE AND 1"

X
D
E
PRESSURE REGULATING 40PSI QUICK-CHECK BASKET
FILTER. 0.3GPM TO 20GPM.

X
x

E
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY DETAIL

X
E

700 EAST

4590
4588
RAIN BIRD EFB-CP

X
x

D
1IN., 1-1/2IN., 2IN. BRASS REMOTE CONTROL VALVE, THAT

X
E
IS CONTAMINATION PROOF W/SELF-FLUSHING FILTER 2
E
SCREEN. GLOBE CONFIGURATION, RECLAIMED WATER

X
E

4586
COMPATIBLE, AND PURPLE HANDLE COVER DESIGNATES

X
E
E I-112 NON-POTABLE WATER USE.

4596
4590
4588
X

4588
RAIN BIRD 33-DRC

X
3/4" BRASS QUICK-COUPLING VALVE, WITH
1 7/L402
E CORROSION-RESISTANT STAINLESS STEEL SPRING,

X
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
4588

E
THERMOPLASTIC RUBBER COVER, DOUBLE TRACK KEY

700 EAST
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &

X
S
E
W
LUG, AND 2-PIECE BODY. MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN

X
BRONZE BALL VALVE 2 1/L403 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS

X
SHUT OFF VALVE NIBCO T-580-S6-R-66-LL WRITTEN PERMISSION FROM METHOD STUDIO INC.
C E
D
4588

MARK II ORISEAL
C

X
E
1 2/L403
STOP AND WASTE VALVE FROM MUELLER CO. SIZE TO project:

X
E
MATCH MAINLINE.

X
MANUAL DRAIN VALVE
USU EVR

X
D 3/4" MUELLER ORSEAL DRAIN VALVE WITH INTERNAL STOP 2 8/L403
D WITH TWO INCH (2") 200 PVC SLEEVES TO VALVE IN 6"

X
I-107
E ROUND VALVE BOX.
EXPANSION

X
4590
EXISTING WEATHERTRAK CONTROLLER
C 1 5/L403

X
RELOCATE EXISTING CONTROLLER. CONTRACTOR TO

X
COORDINATE LOCATION WITH OWNER.

4592
4590

X X X X X X X X X
NETAFIM PHOTO DIODE REGISTER 1 1/2"
4588

MASTER VALVE/FLOW SENSOR WITH WATER METER AND


HYD HYDRAULIC VALVE IN A SINGLE UNIT. CAST IRON WITH 1 7/L403
C BAKED POWDER-COATED FINISH, MINIMUM WORKING
PRESSURE 14 PSI. FLANGE CONNECTION, PHOTO DIODE
SCALE: 1"=50' REGISTER, HIGH FREQUENCY.
4586

AMIAD 2-A-MSIG-STEEL SCREEN WITH 140 MESH


AMIAD 2" MINI SIGMA, ANGLED SELF-CLEANING FILTER,
4596
4590

BSPT OR NPT INLET-OUTLET. STAINLESS STEEL


1 4/L402
4588

WEAVEWIRE SCREEN ELEMENT. ADI-P BLUETOOTH RANGE


4588

CONTROLLER. MAXIMUM WORKING PRESSURE 116PSI.


INSTALL ON CONCRETE PAD THAT IS 6" GREATER THAN 670 EAST 1550 NORTH, LOGAN, UT
THE OUTER DIMENSIONS OF THE FILTER. 84341
IRRIGATION LATERAL LINE: PVC SCHEDULE 40 276.3 L.F. 1/L402

IRRIGATION LATERAL LINE: DRIP IRRIGIGATION, PVC SCH.


40, 1" 2,680 L.F. 1/L402
DISTRIBUTION TUBING, EMITTERS AND TREE WATERING
NOT SHOWN FOR GRAPHIC CLARITY. SEE DETAILS.
B IRRIGATION LATERAL LINE: IRRIGATION CONTROL WIRE IN
B
280.2 L.F. 1/L402 p r o j e c t # : 21.0320
CONDUIT.
d a t e : 02.14.2023
I-107 IRRIGATION MAINLINE: PVC SCHEDULE 40, 1-1/2" 271.5 L.F. 1/L402
revisions :
8
458

IRRIGATION MAINLINE: PVC SCHEDULE 40


164.0 L.F. 1/L402
EXISTING MAINLINE TO REMAIN. USE BUSHING FITTINGS
AS NEEDED.
PIPE SLEEVE: PVC SCHEDULE 40 121.9 L.F. 2/L402
4590

title:
I-110
4592

IRRIGATION NOTES:
1. THE SITE IS TO BE WATERED WITH ITS OWN AUTOMATIC DRIP IRRIGATION
N
SYSTEM AND ITS OWN METER.
IRRIGATION
P:\2021\21-170 USU EVR\AutoCAD\Landscape\Sheet Set\21-170 IRR

2. THE NON-POTABLE SYSTEM SHALL HAVE A MINI-SIGMA FILTER AND CONTROLLER


ACCORDING TO USU STANDARDS.
3. VALVES AND SPECIFIC IRRIGATION ZONES ARE NOT SHOWN IN THIS SCHEMATIC
DESIGN. IT IS INTENDED THAT THESE WILL BE LOCATED ALONG THE SHOWN
PROPOSED MAINLINE LOOP.
PLAN
4. A RAINBIRD (OR APPROVED EQUAL) RAIN SENSOR SHALL BE INSTALLED
ACCORDING TO MANUFACTURERS RECOMMENDATIONS.
A 5.
6.
SEE L402 FOR ADDITIONAL NOTES AND DETAILS.
WHERE EXISTING TREES ARE TO REMAIN, HAND DIG AROUND ROOTS AS NEEDED
A
TO INSTALL NEW PIPE. AVOID CUTTING ROOTS WHERE POSSIBLE.
7. NO IRRIGATION WITHIN THE PROJECT BOUNDARY IS TO BE IRRIGATED BY THE
PROPERTY TO THE NORTH.
0 30' 60'

sheet:

THESE PLANS AND SPECIFICATIONS ARE THE PROPERTY OF CIVIL SOLUTIONS GROUP,
INC, AN SHALL NOT BE PHOTOCOPIED, RE-DRAWN, OR USED ON ANY OTHER PROJECT
OTHER THAN THE PROJECT SPECIFICALLY DESIGNED FOR, WITHOUT WRITTEN
PERMISSION. THE OWNERS AND ENGINEERS OF CIVIL SOLUTIONS GROUP, INC.
DISCLAIM ANY LIABILITY FOR ANY CHANGES OR MODIFICATIONS MADE TO THESE
PLANS OR THE DESIGN THEREON WITHOUT THEIR CONSENT. THESE PLANS ARE
L300
DRAWN TO SCALE WHEN PLOTTED ON A 24" X 36" SHEET OF PAPER. THESE PLANS ARE BID SET
PRODUCED IN COLOR AND SHOULD BE PLOTTED AS SUCH.

1 2 3 4 5 6
1 2 3 4 5 6

E E
360 west aspen avenue
salt lake city, utah 84101
801 532 4422

TE OF UTA
TA

H
S
JACOB A.

HI T E C T
L IC E NS E D
HENDRICKSON
10110348

RC
LA
ND S C A P E A

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

GRAFT VISIBLE
D SET ROOTBALL CROWN 1" HIGHER ROOT FLARE SHALL
ABOVE SOIL D
LINE
WATER WELL 4" HIGH THAN SURROUNDING FINISHED BE 1-2" ABOVE
AT SHRUB, NO WATER GRADE. FINISH GRADE SOIL LINE OF THE
TOP OF ROOT BALL
LANDSCAPE CONSTRUCTION NOTES: WELL AT LAWN AREA SLOPE FINISHED GRADE AT BACKFILL
AWAY FROM ROOTBALL.
KEEP MULCH 4
INCHES WAY FROM AFTER REMOVING
TRUNK EXCESS SOIL
2" MULCH IN WATER WELL.
General Notes: SOIL SAUCER > 3
INCHES HIGH
1 TO 2 INCHES
MULCH
1. REFER TO SPECIFICATIONS FOR SOILS, PLANTING AND IRRIGATION.
2. THE CONTRACTOR SHALL LOCATE AND VERIFY ALL EXISTING UTILITY LINES PRIOR TO FINISHED GRADE.
ANY SITE WORK, IRRIGATION AND LANDSCAPE WORK; CONTRACTOR SHALL REPORT
ANY CONFLICTS TO THE OWNERS REPRESENTATIVE.
3. CONTRACTOR IS TO REVIEW PLANS, VERIFY SITE CONDITIONS AND PLANT QUANTITIES 10 INCHES EXCAVATED HOLE
PRIOR TO INSTALLATION. CONFLICTS BETWEEN THE SITE AND THESE PLANS OR TO HAVE SIDES
WITHIN THESE PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER’S PLANT FERTILIZER TABLETS AS ARTER ROOT BALL SLOPED AT 45
SPECIFIED. IS PLACED IN DEGREE ANGLES
AUTHORIZED REPRESENTATIVE PRIOR TO LANDSCAPE INSTALLATION. ANY DEVIATION
FROM THE PLANS OR SPECIFICATIONS MUST HAVE WRITTEN APPROVAL FROM THE PLANTING PIT,
BACKFILL
REMOVE ALL
OWNER'S REPRESENTATIVE. BURLAP & WIRE
4. PLANT SYMBOLS TAKE PRECEDENCE OVER PLANT QUANTITIES SPECIFIED ON PLANT BASKET DOWN TO PLACE ROOT
NATIVE SOIL MIX FIRMLY BALL ON
SCHEDULE. EXCAVATE SIDES OF 2 X ROOTBALL THE BOTTOM OF
COMPACTED AT BOTTOM OF HOLE UNDISTURBED
5. THE CONTRACTOR SHALL VERIFY PLANT QUANTITIES AND NOTIFY THE LANDSCAPE SLOPE OF THE PIT AT THE BALL
45 DEGREE ANGLE 12" AT 1 GALLON SOIL
ARCHITECT OF ANY DISCREPANCIES BETWEEN QUANTITIES AND SYMBOLS SHOWN. 22" AT 5 GALLON
6. ANY PROPOSED SUBSTITUTIONS OF PLANT SPECIES SHALL BE MADE WITH PLANTS OF 32" AT 15 GALLON
EQUIVALENT OVERALL FORM, HEIGHT, BRANCHING HABIT, FLOWER, LEAF, COLOR,
FRUIT, SOLAR NEEDS, WATER NEEDS, AND CULTURE ONLY AS APPROVED BY THE
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
PROJECT LANDSCAPE ARCHITECT AND OWNER. ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
7. PRIOR TO PLANTING, THE IRRIGATION SYSTEM SHALL BE FULLY OPERATIONAL AND ALL
PLANTING AREAS SHALL BE MOISTENED BEFORE PLANTINGS. SHRUB PLANTING TYPICAL TREE B&B PLANTING DETAIL COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN

8. SOILS SHALL BE ACCORDING TO SPECIFICATIONS. SOIL DEPTH IN PLANTER BEDS 1 NOT TO SCALE 329333.13-01
2 329343-03
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C SHALL BE A MINIMUM OF 18 INCHES AND 12 INCHES IN GRASS AREAS. C
9. ALL FINISHED GRADES SHALL BE APPROVED BY THE OWNER/OWNER'S AUTHORIZED project:
REPRESENTATIVE PRIOR TO INSTALLATION OF ANY PLANT MATERIALS. RUBBER TREE TIES.
REMOVE NURSERY STAKE. IF
10. CONTRACTOR SHALL HAVE THE OWNER'S REP. APPROVE PLANT MATERIAL SIZE
AND QUALITY PRIOR TO INSTALLATION. ANY PLANTS WHICH ARE NOT TRUE TO FORM, REMOVE ALL ROOTS
LODGE POLE
STAKES.
CENTRAL LEADER NEEDS TO BE
STRAIGHTENED OR HELD ERECT, IT
USU EVR
APPEAR STRESSED OR UNHEALTHY, INFESTED WITH PESTS, OR UNDERSIZED FOR ABOVE STRUCTURAL

11.
THEIR CONTAINERS SHALL BE REJECTED.
LANDSCAPE CONTRACTOR TO PROVIDE DETAILED AS BUILT DRAWINGS TO OWNERS
ROOTS PREVAILING
IS ACCEPTABLE TO ATTACH A 12" X
8' BAMBOO POLE TO THE
CENTRAL LEADER AND TRUNK.
EXPANSION
WIND.
REPRESENTATIVE UPON COMPLETION OF LANDSCAPE PLANTING AND IRRIGATION. THE PLANT TOP OF REMOVE ALL CIRCLING
DRAWING TO SHOW LOCATION OF: BUILDING, HARDSCAPES, AND ALL PLANT MATERIAL MODIFIED ROOTS FROM PREVIOUS
ROOT BALL
(TREES, SHRUBS, GRASSES, PERENNIALS AND OTHERS). THE AS-BUILT DRAWINGS
FLUSH WITH
CONTAINERS WITHIN THE PLAN VIEW
MUST USE THE BOTANIC NAMES OF SPECIES INSTALLED. THE CONTRACTOR MUST ROOT BALL AND ABOVE
THE SOIL LINE THE STRUCTURAL
REVIEW THE AS-BUILT DRAWINGS WITH OWNERS REPRESENTATIVE PRIOR TO 32" LONG NON - ABRASIVE RUBBER
SOIL SAUCER ROOTS. (THIS MAY
COMPLETION OF PROJECT. > 3 INCHES REQUIRE REMOVAL OF TIES.
12. THE CONTRACTOR IS RESPONSIBLE FOR MAINTENANCE OF THE TREES, PLANTER HIGH STRUCTURAL ROOTS.)
BEDS (INCLUDING WEEDING), SHRUB PRUNING, TURF MOWING/TRIMMING, WATERING TWO (2) THREE INCH LODGE POLE
THE PLANTS AND IRRIGATION SYSTEM FOR THE DURATION OF THE CONSTRUCTION PINE
PERIOD. SHAVE OUTER STAKES. INSTALL APPROXIMATELY
2"

6'
13. ALL SHRUBS AND GROUND COVERS SHALL BE GUARANTEED BY THE CONTRACTOR CIRCLING
AS TO GROWTH AND HEALTH FOR A PERIOD OF ONE (1) COMPLETE GROWING SEASON ROOTS A AWAY FROM THE EDGE OF THE
1 TO 2 INCHES MULCH ROOT
AFTER COMPLETION OF THE MAINTENANCE PERIOD AND FINAL ACCEPTANCE. ALL MINIMUM OF 1
INCH DEEP BALL. STAKE LOCATION SHALL NOT 670 EAST 1550 NORTH, LOGAN, UT
TREES SHALL BE GUARANTEED BY THE CONTRACTOR TO LIVE AND GROW IN AN INTO ROOT FOR SOIL TREATMENT INTERFERE WITH PERMANENT 84341
ACCEPTABLE UPRIGHT POSITION FOR A PERIOD OF ONE (1) COMPLETE GROWING BALL ON ALL AROUND ROOT BALL, SEE BRANCHES.
SEASON AFTER COMPLETION OF THE SPECIFIED MAINTENANCE PERIOD AND FINAL SIDES SOIL PLANS AND DETAILS
ACCEPTANCE. REMOVE ANY
LOOSE POTTING

2'
14. BIDDING LANDSCAPE CONTRACTORS SHALL PROVIDE GENERAL CONTRACTOR
MEDIUM THAT
WITH 3-5 REFERENCES OF HDPE MAINLINE INSTALLATION OF 2" PIPE SIZE OR GREATER DOES NOT
ON COMMERCIAL OR PUBLIC PROJECTS IN THE LAST 3-4 YEARS. CONTAIN ROOTS COMPACT SOIL UNDER
B 15. BIDDING LANDSCAPE CONTRACTORS SHALL ALSO PROVIDE GENERAL AT THE BOTTOM ROOT BALL TO 90 B
p r o j e c t # : 21.0320
CONTRACTOR WITH 3-5 USU REFERENCE PROJECTS COMPLETED IN THE LAST 3-4 OF THE PERCENT PROCTOR SECTION VIEW
CONTAINER d a t e : 02.14.2023
YEARS. PROJECT INFO SHALL INCLUDE SIZE OF PROJECT, LOCATION AND LANDSCAPE
CONSTRUCTION AMOUNT. revisions :
TREE CONTAINER PLANTING DETAIL TREE DOUBLE STAKING
3 NOT TO SCALE 329343-04
4 NOT TO SCALE 329343-06

title:

DETAILS
P:\2021\21-170 USU EVR\AutoCAD\Landscape\Sheet Set\21-170 DET

A A

sheet:

THESE PLANS AND SPECIFICATIONS ARE THE PROPERTY OF CIVIL SOLUTIONS GROUP,
INC, AN SHALL NOT BE PHOTOCOPIED, RE-DRAWN, OR USED ON ANY OTHER PROJECT
OTHER THAN THE PROJECT SPECIFICALLY DESIGNED FOR, WITHOUT WRITTEN
PERMISSION. THE OWNERS AND ENGINEERS OF CIVIL SOLUTIONS GROUP, INC.
DISCLAIM ANY LIABILITY FOR ANY CHANGES OR MODIFICATIONS MADE TO THESE
PLANS OR THE DESIGN THEREON WITHOUT THEIR CONSENT. THESE PLANS ARE
DRAWN TO SCALE WHEN PLOTTED ON A 24" X 36" SHEET OF PAPER. THESE PLANS ARE
L401
BID SET
PRODUCED IN COLOR AND SHOULD BE PLOTTED AS SUCH.

1 2 3 4 5 6
1 2 3 4 5 6

E E
360 west aspen avenue
salt lake city, utah 84101
801 532 4422

PAVEMENT.
TE OF UTA
FINISHED GRADE. PAVEMENT. TA

H
24" MIN.

S
PLANT DRIP EMITTER 6" MAX. FROM
BASE ROCK. JACOB A.
PLANT TRUNK.

HI T E C T
L IC E NS E D
BOTTOM OF EMITTER TO BE
HENDRICKSON
FLUSH WITH TOP OF MULCH.
10110348

RC
MINIUMUM 12" LA
OF COVER TO ND S C A P E A
MINIMUM 24" OF CLEAN BACKFILL,
TOP OF LATERAL GPH IRRIGATION GPST
COVER TO 95% RELATIVE
PIPE SPEC CHECK EMITTER
TOP OF MAIN LINE COMPACTION
PIPE MULCH

2'
UNDER PAVING OR UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
IRRIGATION NOTES PER CIVIL

6"
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS

3"
ENGINEER'S PLANS. NOT INTENDED FOR CONSTRUCTION, RECORDING
1. IRRIGATION PLAN IS DIAGRAMMATIC. ALL IRRIGATION EQUIPMENT SHALL BE LOCATED IN NON-PRESSURIZED LINE (LATERAL LINE). PURPOSES, OR IMPLEMENTATION
CONTROL WIRES, SLEEVE
PLANTING AREAS ONLY, UNLESS NOTED OTHERWISE. REFER TO THE IRRIGATION LEGEND, DIRECT BURIAL LOW UNDER PAVING. INSTALL
ROOTBALL
DETAILS, AND SPECIFICATIONS FOR EQUIPMENT AND INSTALLATION; SPECIFICATIONS SHALL ADJACENT TO PRESSURIZED

12"
VOLTAGE DETECTABLE LOCATOR TAPE. GPH DISTRIBUTION TUBING
CONTROL WIRES. MAINLINE. BUNDLE
TAKE PRECEDENCE OVER INSTALLATION DETAILS. SHALL BE NO MORE THAN 14" LONG MINIMUM
2. LANDSCAPE CONTRACTOR SHALL VERIFY LOCATION OF IRRIGATION POINT OF CONNECTION 48" LONG MAXIMUM PVC TEE (LATERAL
50% OF PIPE DIAMETER.
PRESSURIZED LINE (MAINLINE). 3" MIN. CONNECTION)
(POC) AND THE STATIC WATER PRESSURE AT THAT LOCATION PRIOR TO BEGINNING ANY NOTES:
1- MAIN LINE REQUIRED TO BE IN SEPARATE TRENCH FROM ALL LATERAL LINES. MAINLINE, SLEEVE UNDER
IRRIGATION WORK. IF THE LOCATION OR WATER PRESSURE IS DIFFERENT THAN THAT PAVING TO BE TWO TIMES
1
EXPRESSED BY THE DRAWINGS, OR IF THE PRESSURE APPEARS TO BE UNUSUALLY HIGH OR NOTES: THE DIAMETER OF THE 2"SXSXS SCH. 40 PVC TEE(S)
2- LATERAL LINES MAY BE IN SAME TRENCH IF THERE IS 6" CLEAR OUT-TO-OUT ON EACH PIPE FOR DISTRIBUTION TUBING AS PVC LATERAL LINE
LOW, THE CONTRACTOR SHALL CONTACT THE OWNER'S REP. IMMEDIATELY. TO ALLOW FOR REPAIRS. 1- SEE IRRIGATION LEGEND FOR MAINLINE SIZE AND TYPE. PRESSURIZED MAINLINE
PIPE. REQUIRED TO SUPPLY
3. CONTRACTOR SHALL KEEP THE PREMISES CLEAN AND FREE OF EXCESS EQUIPMENT, MULTIPLE PLANTS. NOTES:
2- SEE IRRIGATION LEGEND FOR MAINLINE AND LATERAL LINE PIPE SIZE AND TYPE. 2- ALL SLEEVES SHALL BE SCH. 40 PVC PIPE. NON-PRESSURIZED LINE, 1. LOCATE EMITTER ON BLDG. OR
D MATERIALS AND RUBBISH INCIDENTAL TO WORK OF THIS SECTION. SLEEVE UNDER PAVING TO 90 DEG ELL BARBED FENCE SIDE OF PLANT. D
4. CONTRACTOR TO INSTALL SYSTEM PER DRAWINGS AND SPECIFICATIONS. IF THERE IS ANY 3- DIRECT BURIAL CONTROL WIRES SHALL BE INSTALLED IN SCH. 40 PVC ELECTRICAL CONDUIT 3- ALL SLEEVES SHALL EXTEND 12" BEYOND THE EDGE OF BE TWO TIMES THE INSERT FITTING 2. (6) EMITTERS MAX. PER LATERAL
IF REQUIRED. PAVEMENT. DIAMETER OF THE LATERAL CONNECTION.
DISCREPANCY OR MISUNDERSTANDING WITH THE DRAWINGS THE LANDSCAPE CONTRACTOR
LINE. 3. INSTALL PER MANUFACTURER'S
SHALL NOTIFY THE GENERAL CONTRACTOR AND LANDSCAPE ARCHITECT IMMEDIATELY. 4- 2-WIRE IRRIGATION WIRE SHALL BE INSTALLED IN SCH. 40 PVC ELECTRICAL CONDUIT. 4- END OF SLEEVES SHALL BE LOCATED WITH A WOODEN RECOMMENDATIONS.
5. AT THE TIME OF SUBSTANTIAL COMPLETION (DEFINED AS COMPLETE INSTALLATION AND STAKE OR PVC PIPE. LOCATORS SHALL RUN 4. SEE IRRIGATION NOTE 10 FOR
5- DETECTABLE LOCATOR TAPE SHALL BE LOCATED SIX INCHES (6") ABOVE THE ENTIRE CONTINUOUSLY FROM THE END OF THE SLEEVE TO URBAN TREE FOUNDATION © 2014 EMITTER INFORMATION.
PROPER FUNCTIONING OF IRRIGATION SYSTEM, INSTALLATION OF ALL PLANT MATERIAL FINISHED GRADE. OPEN SOURCE FREE TO USE
MAINLINE RUN.
INCLUDING STAKING OF ALL TREES, AND PLACEMENT OF MULCH) THE CONTRACTOR SHALL
IRRIGATION TRENCHING DETAIL PIPE SLEEVING UNDER PAVEMENT GPH DRIP EMITTER
SCHEDULE A WALK THROUGH WITH OWNER TO REVIEW ALL WORK COMPLETED TO DATE AND
GENERATE A PUNCH LIST. AT THIS TIME THE WARRANTY PERIOD OF ONE (1) YEAR BEGINS.
1 NOT TO SCALE 328402-01
2 NOT TO SCALE 328402-02
3 1" = 1" P-CO-USU1-06

AFTER SUBSTANTIAL COMPLETION WALK THROUGH, THE CONTRACTOR HAS THIRTY (30) DAYS
TO SATISFY ALL ITEMS ON PUNCH LIST. 2 4 7 FINISH GRADE/TOP OF MULCH
RECYCLED WATER STICKER
6. IRRIGATION CONTRACTOR SHALL GUARANTEE THE ENTIRE IRRIGATION SYSTEM TO BE FREE DO NOT DRINK 1 3 6 8 10 VALVE BOX WITH COVER:
OF DEFECTS IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE (1) YEAR FROM FINAL 43 1/8" 30-INCH LINEAR LENGTH OF
ACCEPTANCE BY THE OWNER. WIRE, COILED
7. CONTRACTOR TO COORDINATE WITH OWNER'S REP. WHEN BLENDING NEW LANDSCAPE RECYCLED WATER
STRONGBOX SBBC-52AL WATERPROOF CONNECTION:
WITH EXISTING LANDSCAPE. THIS WILL ALSO INCLUDE VERIFYING SQUARE FOOTAGE OF 52"L, 30"H, XX"W RAIN BIRD DB SERIES
11
2

DO NOT DRINK

NOT USED
A
AV

GRASS AND IRRIGATION ADJUSTMENTS. 2" BRASS UNION/ NIPPLE


HP
OUT

12 ID TAG

IN
8. LANDSCAPE CONTRACTOR TO COORDINATE WITH OWNERS REP AND GENERAL 2" ON LINE MINI SIGMA UNIT
CONTRACTOR THE WATERING OF TREES AND GRASS TO KEEP PLANTS, GRASS AND TREES 2" NPT 2" NPT
REMOTE CONTROL VALVE:
2" BRASS GATE VALVE 11 RAIN BIRD PESB (INCLUCED IN
ALIVE DURING CONSTRUCTION. 1-1/2" GALVANIZED PIPE DISCHARGE
15 11
32"
XCZ-PRB-100-COM KIT)
9. USE ONLY ALL NEW MATERIALS AND EQUIPMENT ON THIS PROJECT. SALVAGED MATERIALS SECURED SWIVEL PIPE CONNECTED TO DRAIN. SEE CIVIL PLANS.
MOUNTING PLATES 22 5/8" PRESSURE REGULATING QUICK
ARE NOT ACCEPTABLE. USU STANDARD CHECK BASKET FILTER:RAIN
GALVANIZED FITTINGS BIRD PRB-QKCHK-100 THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
10. ALL TREES GET TWO ROOT WATERING UNITS. EMITTERS ARE AS FOLLOWS (1) 1 GPH LANDSCAPE (INCLUDED IN ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
EMITTER FOR 1 GALLON PLANTS, (1) 2 GPH EMITTER FOR 5 GALLON PLANTS. FINISH GRADE XCZ-PRB-100-COM KIT) MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE

OUT
IN
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
11. CONTROL WIRES SHALL BE 14 GAUGE WIRE. HOT WIRES SHALL BE GREEN IN COLOR WITH 6"X10" CONCRETE PAD NOT USED WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
ONE SPARE EACH. GROUND WIRES SHALL BE WHITE IN COLOR WITH BLUE SPARE. HOT AND 2" GALVANIZED NIPPLE LATERAL PIPE
C 3
4" CRUSHED GRAVEL 13 15 17 C
GROUND WIRES SHALL RUN TO MOST DISTANT VALVE. ALL WIRE CONNECTIONS SHALL BE 14 PVC SCH 80 NIPPLE (LENGTH AS
SOLDERED AND SEALED WATERTIGHT. WIRE CONNECTIONS SHALL BE LOCATED IN VALVE 16 REQUIRED) project:
BOXES WITH AN 18" COIL FOR EACH WIRE. CONTRACTOR SHALL LABEL ALL SPARE WIRES AT 2" SCH 40 MAINLINE PVC SCH 40 ELL
ALL VALVE BOXES THEY PASS THROUGH. PVC PIPE NOTE: SEE VALVE MANIFOLD DETAIL
PVC SCH 80 NIPPLE (2-INCH
LENGTH, HIDDEN) AND PVC
USU EVR
12. ALL IRRIGATION SLEEVES SHALL BE TWO (2) TIMES THE DIAMETER OF THE PIPE. SCH 40 ELL

MAINTENANCE AND OPERATIONAL NOTES


NATIVE SOIL
PVC SCH 40 TEE OR ELL EXPANSION
12. IF ANY SUBSURFACE DRAINAGE OR RUN-OFF IS VISIBLE AT LOW AREAS, ACROSS LANDSCAPE FABRIC MAINLINE PIPE
SIDEWALKS OR AT LOWER PORTIONS OF SLOPES, IMMEDIATELY SHUT THE VALVES OFF TO 2" GALVANIZED ELBOW 3-INCH MINIMUM DEPTH OF
3/4-INCH WASHED GRAVEL
ALLOW THE AREA TO COMPLETELY DRY OUT. IF THIS CONDITION CONTINUES AFTER 45 5/8"
PVC SCH 80 NIPPLE, CLOSE
SUBSEQUENT WATERINGS THE CONTRACTOR SHALL NOTIFY THE OWNER'S REP. 65 5/8" (INCLUDED IN
13. INSPECTIONS OF IRRIGATION SYSTEM SHALL BE MADE ON A DAILY BASIS TO OBSERVE XCZ-PRB-100-COM KIT)
AND PROVIDE REPAIRS OR REMEDIES TO THE FOLLOWING UNACCEPTABLE PROBLEMS: AMIAD 2" MINI SIGMA FILTER RAINBIRD XCZ-PRB 100 VALVE
13. A. OVER-SPRAY ON SIDEWALKS, STREETS, PAVED AREAS, PARKING AREAS, FENCES, 4 1/16" = 1'-0" P-CO-USU1-04
5 1 1/2" = 1'-0" P-UT-02
WALLS, SIGNS, BUILDINGS OR STRUCTURES.
13. B. DRAINAGE OR RUN-OFF ACROSS SIDEWALKS, PAVING OR STREETS.
13. C. DAMAGED OR IMPROPERLY OPERATING HEADS, PIPING, VALVES, CONTROLLERS OR USU STANDARD GALVANIZED UNIONS 1 30-INCH LINEAR LENGTH OF
4 WIRE COILED
OTHER IRRIGATION EQUIPMENT. 10" DIAMETER VALVE BOX. 2 WATERPROOF CONNECTION
13. D. CONTRACTOR TO PROVIDE 2 HOURS OF TRAINING TO OWNER AT END OF PROJECT HEAD BRAND "QVC" ON LID WITH 1 2 3 5 670 EAST 1550 NORTH, LOGAN, UT
3 ID TAG: RAIN BIRD VID SERIES
REGARDING OPERATION FOR IRRIGATION SYSTEM. CONTRACTOR WILL SHOW OWNER HOW 2" HIGH CHARACTERS. 84341
4 VALVE BOX WITH COVER:
TO OPERATE THE FOLLOWING: STOP AND WASTE VALVE, BACKFLOW VALVE, CONTROLLER, 6 RAIN BIRD VB-STD
AND REMOTE CONTROL VALVES. 5 FINISH GRADE/TOP OF MULCH
7
14. CONTRACTOR TO PROVIDE DETAILED DIGITAL AS BUILT OF ALL IRRIGATION EQUIPMENT 6 REMOTE CONTROL VALVE:
8 RAIN BIRD EFB-CP
INSTALLED. 12" MAX 9
15. CONTRACTOR SHALL PROVIDE A LAMINATED AS BUILT DRAWING, SIZED TO FIT, FOR 6" MIN. 7 GALVANIZED STEEL NIPPLE (CLOSE)
B B

2" MAX
1" MIN
PLACEMENT INSIDE EACH CONTROLLER, LABELING AND SHOWING THE AREA COVERED BY FINISHED GRADE. 8 GALVANIZED STEEL ELL p r o j e c t # : 21.0320
10
EACH VALVE OF THAT CONTROLLER. 9 GALVANIZED STEEL NIPPLE d a t e : 02.14.2023
(LENGTH AS REQUIRED)
FLUSH IN LAWN AREAS. 10 BRICK (1 OF 4) revisions :
2" IN SHRUB AREAS.
BIDDING: 11 HDPE MAINLINE PIPE
16. BIDDING LANDSCAPE CONTRACTORS SHALL PROVIDE GENERAL CONTRACTOR WITH 3-5 QUICK COUPLING VALVE AS SPECIFIED. SCH 80 NIPPLE (2-INCH
16 15 13 12 11 12
REFERENCES OF HDPE MAINLINE INSTALLATION OF 2" PIPE SIZE OR GREATER ON LENGTH, HIDDEN) AND
TWO STAINLESS GALV.NIPPLE, LENGTH AS REQ. SCH 40 ELL
COMMERCIAL OR PUBLIC PROJECTS IN THE LAST 3-4 YEARS. STEEL CLAMPS.
6" DEEP LAYER OF 3/4" CRUSHED ROCK. 13 PVC SCH 40 TEE OR ELL
17. BIDDING LANDSCAPE CONTRACTORS SHALL ALSO PROVIDE GENERAL CONTRACTOR WITH
3-5 USU REFERENCE PROJECTS COMPLETED IN THE LAST 3-4 YEARS. PROJECT INFO SHALL 14 NOT USED
INCLUDE SIZE OF PROJECT, LOCATION AND LANDSCAPE CONSTRUCTION AMOUNT. 3" PVC SCHEDULE 80 NIPPLE. 15 PVC LATERAL PIPE
1/2" X 36"
GALV STEEL PIPE. 16 3.0-INCH MINIMUM DEPTH OF
3/4-INCH WASHED GRAVEL
NOTE: SEE VALVE MANIFOLD DETAIL
NOTE: SOLID CAPS SHALL BE PLACED ON THE BOTTOM OF EACH WATER EMITTER TO PREVENT WATER
GOING DIRECTLY INTO GRAVEL SUBSOIL.
THREE PVC SCH 80 ELLS. title:
12" PVC SCHEDULE 80 NIPPLE.

TREE ROOT WATERING SYSTEM QUICK COUPLING VALVE IN BOX RAINBIRD EFB-CP BRASS VALVE
6 7 8
P:\2021\21-170 USU EVR\AutoCAD\Landscape\Sheet Set\21-170 DET

1" = 1" P-CO-USU1-05 1 1/2" = 1'-0" FX-IR-FX-QUIC-03 1 1/2" = 1'-0" P-UT-03 DETAILS

A A

sheet:

THESE PLANS AND SPECIFICATIONS ARE THE PROPERTY OF CIVIL SOLUTIONS GROUP,
INC, AN SHALL NOT BE PHOTOCOPIED, RE-DRAWN, OR USED ON ANY OTHER PROJECT
OTHER THAN THE PROJECT SPECIFICALLY DESIGNED FOR, WITHOUT WRITTEN
PERMISSION. THE OWNERS AND ENGINEERS OF CIVIL SOLUTIONS GROUP, INC.
DISCLAIM ANY LIABILITY FOR ANY CHANGES OR MODIFICATIONS MADE TO THESE
PLANS OR THE DESIGN THEREON WITHOUT THEIR CONSENT. THESE PLANS ARE
DRAWN TO SCALE WHEN PLOTTED ON A 24" X 36" SHEET OF PAPER. THESE PLANS ARE
L402
BID SET
PRODUCED IN COLOR AND SHOULD BE PLOTTED AS SUCH.

1 2 3 4 5 6
1 2 3 4 5 6

10" ROUND VALVE BOX 10" ROUND VALVE BOX

10" DIAMETER ROUND VALVE SET BOX 2" ABOVE GRADE AT SHRUBS. MAINLINE BELOW
BOX, SEE SPECIFICATIONS. SET BOX FLUSH TO GRADE AT LAWN. MANIFOLD LINE IRRIGATION
VALVE
E 2" PVC SCH. 40 PIPE 2" PVC SCH. 40 PIPE
E
LATERAL PIPE 360 west aspen avenue
NOTCHED OVER MAINLINE NOTCHED OVER MAINLINE
FINISH GRADE.
salt lake city, utah 84101
801 532 4422

18" BELOW GRADE


LATERAL PIPE
FLOW FLOW
PVC SCH. 80 TEE TE OF UTA
OR ELBOW TYP. TA

H
S
MATCO 2" VALVE WITH RESILIENT SEAT, MUELLER ORISEAL DRAIN VALVE WITH JACOB A.

HI T E C T
L IC E NS E D
NON-RISING STEM, AND 2" NUT INTERNAL STOP
FOUR COMMON
HENDRICKSON
PLUMB TO 40" DEEP IF WATER PLUMB TO 40" DEEP IF WATER BRICK SUPPORTS. BRASS
SUPPLY LINE IS DEEPER SUPPLY LINE IS DEEPER NOTES: 10110348
ISOLATION VALVE

RC
1. THIS DETAIL ONLY LA
SHOWS MANIFOLD TO MATCH LINE ND S C A P E A
CONFIGURATION. SIZE - SEE DETAIL
ISOLATION VALVE AS PVC MAIN LINE. REFER TO VALVE
8" MIN. LENGTH 8" MIN. LENGTH SPECIFIED. DETAILS FOR VALVE
SLIP/THREAD COUPLING. INSTALLATION.
FILTER FABRIC FILTER FABRIC UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
6" SCHEDULE 80 THREADED NOT INTENDED FOR CONSTRUCTION, RECORDING
NIPPLE. CONTROL VALVE MANIFOLD (AT VALVE CLUSTERS) PURPOSES, OR IMPLEMENTATION

NOTE: ADD VALVE BOX EXTENSIONS AS NEEDED.

12"Wx12"Wx24"D GRAVEL SUMP 12"Wx12"Wx24"D GRAVEL SUMP

MATCO 2" VALVE STOP AND WASTE VALVE BRONZE ISOLATION VALVE VALVE MANIFOLD
1 NOT TO SCALE 328406-08
2 NOT TO SCALE 328406-03
3 1 1/2" = 1'-0" P-UT-05
4 1" = 1'-0" P-UT-01

NOTE:
D DRAIN SHALL BE IN D
CENTER OF GRAVEL
SUMP
PEDISTAL MOUNT IRRIGATION
JUMBO VALVE BOX 10" DIA. ROUND
WATER PROOF WITH EXTENSIONS
CONTROLLER ON CONCRETE CONNECTIONS 2" MIN. ON TOP AS NEEDED VALVE
FOOTING. USE GALV. "J" CLEARANCE LANDSCAPE
BOX
METAL FENCE POST SURFACE

1"
BOLTS TO SECURE THE
CONTROLLER TO THE PAD. FINISH
GRADE

30" COIL OF COMMUNICATION


GFI RECEPTACLE AND WIRING FROM WIRING
LOCKING SWITCH. CONTROLLER FROM 2" CLASS 200 PVC
CONTROLLER SLEEVE
14 GA. WIRES HYDROMETER

SCH. 80 TEE
IN MAIN LINE
1" SCH. 40 CONDUIT FROM FIELD. 3" MULCH USU STANDARD
WITH SWEEP ELL FOR
120 VOLT SOURCE. 1 1/2" PVC
GALVANIZED UNIONS MAIN LINE FILTER FABRIC TO
(BOTH SIDES) SURROUND GRAVEL
SCHEDULE 40
CONDUIT WITH PVC MAINLINE
CONCRETE BASE: PIPE
6" MIN. THICKNESS, LONG SWEEP ELL.
EXTEND 6" BEYOND BRICK 3/4" SCH. 80
OUTSIDE DIMENSIONS SUPPORT THREADED NIPPLE
OF ENCLOSURE WITH CONCRETE GRAVEL
SLOPE FOR DRAINAGE. 3/4" PVC ELL (ST)
3/4" MARLEX
SYSTEM WIRES STREET ELL
IN CONDUIT

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


8 FT. COPPER GROUND 3/4" SCH. 80
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
AS PER LOCAL CODE. THREADED MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
NIPPLE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
MANUAL
C VALVE
12"x12"x24" GRAVEL
SUMP MIN.
C
project:
PEDESTAL MOUNT CONTROLLER 6' FENCE POST AND FOOTER HYDROMETER MANUAL DRAIN VALVE - MAINLINE
5 6 7 8
1" = 1'-0" 328409.16-03 NOT TO SCALE 3231-01 1 1/2" = 1'-0" P-UT-04 1 1/2" = 1'-0" 328406-04
USU EVR
EXPANSION
1
2" TOOLED EDGE.
6"

3-1/2" METAL FENCE POST


1"
1"

MULCH
5"

670 EAST 1550 NORTH, LOGAN, UT


84341
ASPHALT PAVING

CONCRETE GATE DETAIL COURTESY OF HTTPS://AMERICASGATECOMPANY.COM/HOW-TO-SELECT-YOUR-CANTILEVER-GATE/

B SUB SURFACE GRADE.


B
NOTE: p r o j e c t # : 21.0320
4" GALVANIZED METAL SLEEVE
1. INSTALL GATES AS SIMILAR TO PREVIOUS INSTALLATION. d a t e : 02.14.2023
2. FOR WIDTH SEE LANDSCAPE SITE PLAN.
CONCRETE
3. LATCH POST SHALL BE A REMOVABLE FENCE POST. SEE DETAIL
revisions :
COMPACTED SUBGRADE. 9/L403

FENCE POST WITH SLEEVE AND FOOTER 6"X6" CONCRETE MOW STRIP AT PLANTER EDGE CANTILEVER SLIDING GATE
9 NOT TO SCALE 3231-02
10 NOT TO SCALE 329413.19-21
11 NOT TO SCALE P-UT-08

title:
P:\2021\21-170 USU EVR\AutoCAD\Landscape\Sheet Set\21-170 DET

DETAILS

A A

sheet:

THESE PLANS AND SPECIFICATIONS ARE THE PROPERTY OF CIVIL SOLUTIONS GROUP,
INC, AN SHALL NOT BE PHOTOCOPIED, RE-DRAWN, OR USED ON ANY OTHER PROJECT
OTHER THAN THE PROJECT SPECIFICALLY DESIGNED FOR, WITHOUT WRITTEN
PERMISSION. THE OWNERS AND ENGINEERS OF CIVIL SOLUTIONS GROUP, INC.
DISCLAIM ANY LIABILITY FOR ANY CHANGES OR MODIFICATIONS MADE TO THESE
PLANS OR THE DESIGN THEREON WITHOUT THEIR CONSENT. THESE PLANS ARE
DRAWN TO SCALE WHEN PLOTTED ON A 24" X 36" SHEET OF PAPER. THESE PLANS ARE BID SET
L403
PRODUCED IN COLOR AND SHOULD BE PLOTTED AS SUCH.

1 2 3 4 5 6
1 2 3 4 5 6

LEGEND EXISTING LEGEND PROPOSED LEGEND DEMP


ADJACENT PROPERTY BOUNDARY PROPERTY BOUNDARY PROPERTY BOUNDARY

w CULINARY WATER LINE W CULINARY WATER LINE (SIZE SHOWN ON PLAN) CULINARY WATER LINE (SIZE SHOWN ON PLAN)
E E
360 west aspen avenue
ss SANITARY SEWER LINE SS SANITARY SEWER LINE (SIZE SHOWN ON PLAN) SS SANITARY SEWER LINE (SIZE SHOWN ON PLAN) salt lake city, utah 84101
801 532 4422
sd STORM DRAIN LINE SD STORM DRAIN LINE (SIZE SHOWN ON PLAN) SD STORM DRAIN LINE (SIZE SHOWN ON PLAN)

ir IRRIGATION LINE IR IRRIGATION LINE (SIZE SHOWN ON PLAN) IR IRRIGATION LINE (SIZE SHOWN ON PLAN)

g GAS LINE G GAS LINE G GAS LINE

e UNDERGROUND POWER LINE E UNDERGROUND POWER LINE E UNDERGROUND POWER LINE

e AERIAL POWER LINE E AERIAL POWER LINE E AERIAL POWER LINE

c UNDERGROUND COMMUNICATION LINE C UNDERGROUND COMMUNICATION LINE C UNDERGROUND COMMUNICATION LINE


UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
#### CONTOUR MINOR #### CONTOUR MAJOR #### CONTOUR MAJOR NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

#### CONTOUR MAJOR #### CONTOUR MINOR #### CONTOUR MINOR

x x FENCE X X FENCE X X FENCE

ASPHALT PAVEMENT BUILDING SETBACK BUILDING SETBACK

CLOSED FACE CURB AND GUTTER ASPHALT PAVEMENT ASPHALT PAVEMENT

OPEN FACE CURB AND GUTTER CLOSED FACE CURB & GUTTER CLOSED FACE CURB & GUTTER

D CONCRETE PAVEMENT OPEN FACE CURB & GUTTER OPEN FACE CURB & GUTTER
D

EXISTING TO BE REMOVED CURB & GUTTER TRANSITION CURB & GUTTER TRANSITION

W WATER VALVE CONCRETE PAVEMENT CONCRETE PAVEMENT

FIRE HYDRANT W WATER VALVE W WATER VALVE

W WATER METER FIRE HYDRANT FIRE HYDRANT


2/8/2023
S SEWER MANHOLE W WATER METER W WATER METER

STORM DRAIN BOX S SEWER MANHOLE S SEWER MANHOLE

STORM WATER CATCH BASIN STORM DRAIN BOX STORM DRAIN BOX

ROAD SIGN STORM WATER CATCH BASIN STORM WATER CATCH BASIN

POWER POLE ROAD SIGN ROAD SIGN

DECIDUOUS TREE

CONIFEROUS TREE
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

USU EVR
EXPANSION

670 EAST 1550 NORTH, LOGAN, UT


84341

B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :

title:

LEGEND

A A

sheet:

C001
PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6
18S

D
D

8S
C

ir
10W

12W
18S
D

D
8S
10W
ir

S
8W ir
8W ir

WW
8W ir

W
W

e
W
12W
18SD
10W

D
8S

C
g
ir

12W
ir

ir
S
8SS 8SS

D
700 EAST

6S

D
ir

8S
8SS
10W 10W

30SD
10W
E 10W 10W E

12W
360 west aspen avenue

D
ir salt lake city, utah 84101

8S
ir

c
801 532 4422

8SS
ir

D
6S
x ir

ir
x ir
x

g
x ir
x

D
x
x

8S
12W
x x
12
12

8SS

30SD
17

ir

D
ir

8S
ir 2 2 2

D
ir

g ir
6S

12W
12

S
8SS

D
ir
8SD 8SD
8SD
8SD 8SD

g
8SD 2
D

30SD
8

ir
8

12W

E
ir UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
8SS

x 15 ir 2 NOT INTENDED FOR CONSTRUCTION, RECORDING

E
sdir

15
ir

ir PURPOSES, OR IMPLEMENTATION
ir

ir
15 15
9 2
19
x
12W

7
8SS

30SD
gg

1 1

ir
15

e
1
x
ir

11 5
8SS

12W
sd

2 11
12 11

c
4
1 6
D 12 D
gg

2 6
8SS

12W

2 13
ir

ir
14 5 4
6SS 10
4SS 4SS 8
4SS 4SS
4SS
sd

4SS

S
SCO

S
13
C

SCO

c e 2 2
E
8SS

12W

1
c

SCO
10
x

15SD 10 c 2 4
g
ir

3 2
D

ir
12
ir

c 4 21
12
8SS

15 2/8/2023
12W
15SD

c
9

x
ir

ir

E
x
ir

EXISTING BUILDING

ir
ir

8SS

E
ir

12W

10
gg
15SD

ir

ir
ir

6
15

ir
W
8SS

E
2W
e
ir

ir

x
ir

g
10
E
15SD

13
1550 NORTH
12W
ir

GM

4
E E

9 4
8SS

18
E
x

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


15 ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
g

12 3 MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE


c
12W
15SD

x x COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN


8SS

e
ir

WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS


ir

10
ir

WRITTEN PERMISSION FROM METHOD STUDIO INC.


E

C C
E

ir
ir

ir

project:
E

c
E E

9
8SS

D
15SD

ir

sd
e

USU EVR
ir

ir 4
g

5
ir

4
12W

EXPANSION
g
30SD
E
8SS

30SD
ir

ir

6 30SD

ir
ir

ir

15SD
18SD

30SD
D
ir

4W 15SD
W

E
ir

30SD
E
8SS

ir
E

15SD
6W sd 15SD
30SD
E

6W
g
W
ir

9
30SD
15SD
c

12
sd
W

6W
18SD

D
6W
W

15SD
8SS

c
2

ir
10

D
10 2
E
E

10 16

6S
g

6SS
S
ir

18SD

10 2 8 x
E
E

8
E

E
E
g
e

E
SD

E
E
8SS

12W

E
670 EAST 1550 NORTH, LOGAN, UT
30

12
SD

84341
15
E

e
10 10 10

ir
20
8SS

30SD 30SD 30SD


12W

30SD
8W

ir

15SD 15SD 15SD e


x
15SD x
18SD

x
E

x
x x 10
ir
B B
ir x
ir

ir x
8SS

ir ir
ir ir 12 e ir ir ir p r o j e c t # : 21.0320
12W

ir e ir
15SD

e
d a t e : 02.14.2023
ir ir e
ir
ir

12SD ir 12
c

12SD
revisions :
g
D
8W

8SS
ir

18SD
12W

e
ir
8SS
ir

18SD
ir
8W ir

ir
ir

GENERAL DEMOLITION PLAN NOTES: 1 DEMOLITION PLAN SHEET KEY NOTES:


ALL ITEMS CALLED OUT TO BE REMOVED SHALL BE DISPOSED OF IN AN
APPROPRIATE MANNER AND LOCATION:
title:
1. ALL ITEMS NOT INDICATED FOR REMOVAL SHOULD REMAIN IN PLACE.
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRS AND/OR REPLACEMENT
OF DAMAGED ITEMS OR SURFACES NOT INTENDED TO BE REMOVED AS
DEFINED BY THIS PLAN.
2. ALL ITEMS CALLED OUT FOR REMOVAL SHALL BE DISPOSED OF IN AN
1.
2.
3.
REMOVE CURB AND GUTTER
SAWCUT AND REMOVE EXISTING ASPHALT PAVEMENT
USU & EVR TO CORRDINATE RELOCATION AND REUSE OF SOLAR PANELS
DEMOLITION
APPROPRIATE, LEGAL MANNER AND LOCATION.
3. EXISTING UTILITY POSITIONS ON THIS PLAN ARE GENERAL LOCATIONS
BASED ON OBSERVED SURFACE FEATURES, PROVIDED MAPPING AND OTHER
4.
5.
6.
REMOVE LANDSCAPE CURBING
REMOVE STORM DRAIN BOX
REMOVE STORM DRAIN PIPE
PLAN
APPROXIMATE LOCATION INFORMATION. CONTRACTOR SHALL CONFIRM 7. REMOVE DUMPSTER ENCLOSURE AREA
LOCATION OF EXISTING UTILITIES PRIOR TO WORK WITHIN THE AREA OF ANY 8. REMOVE GRAVEL AREA
EXISTING UTILITY. 9. SEE LANDSCAPE PLANS FOR IRRIGATION DEMO
4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING CURRENT BLUE 10. SEE ELECTRICAL PLANS FOR ELECTRICAL AND COMMUNICATION DEMO
STAKE INFORMATION FOR THE ENTIRETY OF THE PROJECT SCOPE AND 11. REMOVE CONCRETE WALL.
DURATION. 12. REMOVE AND REUSE EXISTING FENCE
5. CONTRACTOR SHALL COORDINATE ANY UTILITY DISRUPTION WITH UTAH 13. REMOVE EXISTING CONCRETE PAVEMENT
STATE UNIVERSITY AND THE UTILITY OPERATOR. ADVANCED NOTICE OF 14. REMOVE AND REUSE ELECTRIC ENTRANCE GATE
PLANNED DISRUPTIONS SHALL BE PROVIDED TO ALL AFFECTED UTILITY 15. EXISTING TREE TO BE REMOVED BY LOAM
USERS 7 DAYS ADVANCED NOTICE REQUIRED. 16. RELOCATE EXISTING STRUCTURE SEE ARCHITECTURAL PLAN FOR LOCATION.
A 6. ALL ASPHALT AND CONCRETE PAVEMENT REMOVALS (INCLUDING CURB & 17. RELOCATE EXISTING GATE A
GUTTER AND SIDEWALKS) SHALL INCLUDE SAWCUTS AT APPROPRIATE 18. PRESERVE AND PROTECT EXISTING GAS METER AND SERVICE LINE IN PLACE
LOCATIONS (SEE PLAN). CONCRETE TO BE CUT AT EXISTING JOINTS. 19. EXISTING SIGN TO BE RELOCATED
7. ALL EXISTING CONCRETE NOT CALLED OUT TO BE REMOVED IS TO BE 20. ADJUST EXISTING STORM DRAIN BOX TO MATCH PROPOSED GRADE.
PROTECTED IN PLACE TO KEEP FROM FURTHER REMOVAL OF CONCRETE. 21. LANDSCAPE CURB TO REMAIN. SEE LANDSCAPE PLAN.
8. COORDINATE DEMOLITION OF EXISTING UTILITIES WITH INSTALLATION OF
REPLACEMENT UTILITIES TO MINIMIZE DISRUPTION OF SERVICE OF THESE

N
UTILITIES.
9. CONTRACTOR TO REPLACE ANY CONCRETE, ASPHALT, OR LANDSCAPING sheet:
THAT IS DISTURBED BY CONSTRUCTION ACTIVITIES. IT SHALL BE REPLACED

C101
TO MATCH PRE-CONSTRUCTION CONDITIONS AND SHALL MEET CURRENT
USU A/E DESIGN GUIDELINES.
10. PRIOR TO TRENCHING ACROSS EXISTING TRACK, COORDINATE SCHEDULE
WITH EVR.

0 20' 40'

PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6

S
WW
W
W

e
W

C
g
S
3
700 EAST

13
E 12 E
X X X 360 west aspen avenue
X
R15.5'
X X X 12 salt lake city, utah 84101
11

c
X
801 532 4422
X X X X 13
10.1' X X X 12
X

g
X X
SD X X
8 X X SD 12

X
X
10.1' X X SD
5.0' 15.5'
X
8
8
10.2'
SD 15.3'

X
g
13 14
15.6' 8

X
8

S
D
8 15.5'
8 8

SD
R134.9'

g
D

15.6'
SD

E
E
E 8 8 UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
7.0'
9 8.0' E 15.6' DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
1 14.6' NOT INTENDED FOR CONSTRUCTION, RECORDING

E
PURPOSES, OR IMPLEMENTATION

X
SD 119.2' 9

SCO
SCO
SD
R166.9' SD
11 9 SD
2

SD
SD

X
SD 4.3'
SD 20
6 R20.0'
gg

SD
R19.5'

21.0' 5
18
3 13
9.6' 8.6'
9.3' 13.8'
15

X
3
18 16.0'
2
gg

8
D 16.6' D
X

R150.4'
3 7
57.4'

R3.0'
11

S
SCO

S
SCO

c D
8S
e
R14.5'
c

SCO
SD

X
X X

c
PROPOSED BUILDING
g

8 3 8
D

8 8 2/8/2023
13 EXISTING BUILDING
1

E
X X

R165.7'

9.0'

E
gg

10 R150.2'
7.0' R134.3'

X
W

18.1'
X

E
e

g g 4.4' R118.8'
E
1550 NORTH

GM

R166.9'
E E

E
E

2
E

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


7.0' E ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
g

X
E
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
c

x x 10.0' 15.6'
8 x 10 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN

e
5.0' WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
E

WRITTEN PERMISSION FROM METHOD STUDIO INC.


X

E
C C
E

98.2'
15.5'
project:
E

SD
c
E E

SD

X
8 10

SD
R80.0'
e

USU EVR
X

50.0'
g

10.0'

E
14.4'
E

g 42.0'

E
8
EXPANSION
E

2
8 8

X
4
E

73.8'
12.0' D
X

E
1

SD
W

E
E
E

18.0'
10
E
g
W

8 13
W

D
W

16
19

SD
9
E 8
13

X
9
17
8
g
S

8
10 8
X

15.5'
8
g
e

670 EAST 1550 NORTH, LOGAN, UT

SD
84341
E

8
e 15.6'
X

SD

1 8

X
13.8'
E

X SD SD
SD
X SD
X X X X
SD SD 8
B B
SD
X X X X X X
SD SD SD 13
X e X X X X X p r o j e c t # : 21.0320
13 e X X X X e X X Xe X X d a t e : 02.14.2023
c

revisions :
g
D
e

e
g

1 SITE SHEET KEY NOTES:


GENERAL SITE NOTES:
PROVIDE, INSTALL, AND/OR CONSTRUCT THE FOLLOWING PER THE SPECIFICATIONS
GIVEN OR REFERENCED, THE DETAILS NOTED, AND/OR AS SHOWN ON THE title:
CONSTRUCTION DRAWINGS: 1. CONTRACTOR TO REPLACE ANY CONCRETE, ASPHALT, OR LANDSCAPING

SITE PLAN
THAT IS DISTURBED BY CONSTRUCTION ACTIVITIES. IT SHALL BE REPLACED
1. CONCRETE SIDEWALK, SEE 9/C502. TO MATCH PRE-CONSTRUCTION CONDITIONS AND SHALL MEET CURRENT
2. STANDARD DUTY CONCRETE PAVEMENT, SEE 7/C502. USU A/E DESIGN GUIDELINES.
3. CURB & GUTTER, SEE 8/C502
4.
5.
6.
DUMPSTER PAD LOCATION, SEE ARCHITECTURAL PLANS.
RAMP, SEE 7/C502.
CONCRETE WATERWAY, SEE 10/C502.
AND
DIMENSION
7. 4" YELLOW PAINT STRIPE (TYP)
8. ASPHALT PAVEMENT, SEE 6/C502.
9. LIGHTS SEE ELECTRICAL PLANS
10. UNDERGROUND ELECTRICAL SEE ELECTRICAL PLAN
11.
12.
13.
ADA RAMP, SEE 6/C501.
RETAINING WALL, SEE 5/C502.
FENCE, SEE LANDSCAPE PLANS.
PLAN
14. ELECTRICAL EQUIPMENT TRENCH, SEE DETAIL 4/C503.
15. INSTALL REMOVABLE FENCE POST, SEE LANDSCAPE PLANS.
A 16. RELOCATE EXISTING STRUCTURE TO THIS AREA. SEE ARCHITECTURAL PLAN
FOR LOCATION.
A
17. ELECTRICAL EQUIPMENT SEE ELECTRICAL PLAN
18. RELOCATE EXISTING SLIDE GATE AND CONTROL BOX, SEE LANDSCAPE PLANS
19. ADJUST EXISTING SUMP LID TO PROPOSED GRADE
20. RELOCATE SIGN

N
sheet:

0 20' 40' C102


PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6

4599
S
WW
W
W

e
W
93

C
g
45
700 EAST

S
TBC/ME:4591.79
TC:4591.86
TC:4591.77
TOW:4592.84 TOW:4593.56
E TBC:4591.50
TC:4591.96
459
6 E
X X X TA:4592.42 TOW:4594.55
TOW:4595.37
360 west aspen avenue
X
TC:4591.62 4593
X X TA:4593.00
X TA:4593.61 TOW:4596.09 salt lake city, utah 84101

c
X
801 532 4422
X

2%
459 BOW:4592.84 X X TA:4593.71 TOW:4596.50
FG:4591.67 2 TA:4593.35 4595
X X

-2.
X
FG:4591.61 X X TOW:4596.76 TA:4593.48

g
TA:4592.36 BOW:4593.40 BOW:4593.66
X X TOW:4596.76

%
TBC/ME:4591.35 4594 X X TOW:4596.76

.5
4592

-2.0%
X TOW:4596.00

-2
TC:4591.58 45 X

1 X
93
X X

2%
X

-2.0%
X

-2.1%

-3.
459
BOW:4593.53 TA:4593.90

-2.3%
-2.1%
BOW:4594.00
TA:4593.36

X
2%
TA:4591.54

4591

-2.
X
TA:4591.29

0%
D
%

-3.
.4

-2.0%
4590 -2

-2.0%
D

TA:4592.67 TA:4592.90

-4.0%
TC:4590.26

E
TC:4590.13 TA:4591.48 UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
TA:4592.70 4593 DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS

-4.0%
TA:4592.90 NOT INTENDED FOR CONSTRUCTION, RECORDING

-2.2%
E
TC:4590.03
PURPOSES, OR IMPLEMENTATION

X
-3.3%

SCO
TA:4592.81

SCO
TBC/ME:4589.43 FG:4590.14 TC:4592.33

-2.

%
TC:4592.50

3%
TA:4593.07

-2.9
TBC:4590.57

X
FG:4591.43 TC:4591.77
TA:4590.24 TC:4592.52 4591
gg

%
TC:4589.65

-2.4
FG:4590.30 FG/ME:4591.44 4590
TBC/ME:4590.64
TA:4589.16 TBC/ME:4590.12 TC:4591.18

-33.6%
TC:4591.77
4590 TC:4590.38 FG:4590.30 4589
92

%
TBC:4589.51
45 459

-2.6
4590 4588
2
TC:4591.08 TA:4591.79
45

TC:4590.27 4587 TA:4592.00


89

FG/ME:4586.35

X
TC:4589.75 TC:4590.42 TC:4590.63
TC:4590.82

-2.0%
-8.4% TC:4590.10 FG:4590.65
-2.
gg

-1.8%
D D
6

TC:4590.73

%
2.8%
%

TC:4590.45 -6.3%
X

-2.6
1
TBC:4588.28
-0.0% 459
TBC:4589.52 -33.3%
TA:4587.82 TC:4589.69
89
45 TC:4590.75

-2.
S
SCO

S
SCO

5%
c e TC:4590.75
c TC:4590.73

SCO
TA:4591.13
TA:4589.19
PROPOSED BUILDING

X
ADA ACCESS PATH
X X

c
g

45
FFE:4590.82

9
D

1
TBC/ME:4587.21 c MATCH EXISTING
FG:4590.05
BUILDING FFE 2/8/2023
7
458

45
X X 4588

91
EXISTING BUILDING

E
FG:4586.35 TA:4591.28
TC:4587.26

E
-2. -33.3%
3%
gg

E
TA:4590.40

X
W

TA:4588.50 E 458
8 FG/ME:4586.39 -6.6%
e

TC:4587.10
%
.9
-2
g g

4589
3%
E

-2.
1550 NORTH

4588

FG/ME:4589.95
GM

TC:4586.95
E E

4588
TC:4590.32
E

TC:4590.82
TC:4590.82 4590
TC:4590.23
E

TA:4589.87 THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING

89
TA:4589.38

87
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &

45
4587
g

4590

45
TC:4587.37

X
0
-2.0%
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
c

459
x x TC:4590.72
TC:4587.23 x -3 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN

e
3.

88
-2.2% TC:4590.20 0% WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS

45
E

-2.0% WRITTEN PERMISSION FROM METHOD STUDIO INC.


X

FG:4586.35
C TC:4590.62
C
E

45
TC:4590.62

4590

90
TC:4587.37 TC:4590.22
project:
E

-6.1%
c
E E

4589

X
4586
TA:4590.48

-5.8%
4587

TA:4588.21
-4.8
e

USU EVR

1%
FG:4586.35

-33.3%
89
X

-12.
45

-6.1%
g

g TA:4588.47

EXPANSION
TC:4588.22
E

FG:4585.00 FG:4590.00 FG:4587.20


-5.5%

X
FG:4587.00 458 4590 90
E

% 8 45
-2.1 TC:4588.17 TC:4588.26 4 5 8 9
%

-2.7%

-33.3%
4588
-1.9

D
FG:4585.00
X

4587
W

4589 4586
E

-6.1%
E

4588
FG:4590.00

6%
TC:4588.05 TA:4587.72 -2.5%
E

4588 45
g
W

-7.
TC:4587.94 TA:4587.73 85

85
c
W

45
4587 -2.5%

D
TA:4587.98 TA:4587.18
W

4587
X

87
TC:4586.97

45
TA:4586.36
6
458

0.0%

88
45X
FG:4585.00
FG:4585.00 TA:4586.18
4586 86
FG:4587.31 45
g

86
S

-3.0%
3%

45
. TA:4588.83
-1
%
FG:4587.00 -2.1
X

4585

-2.5%
TA:4585.91

-2.2%
g
e

4586 FG:4585.00
%
.9

670 EAST 1550 NORTH, LOGAN, UT


-1

458

85 84341
7
E

45
e FG:4585.00
FG:4585.00
X

4585 TA:4587.32
4587

4586 -2
TC:4586.59 TA:4587.24 .7%

X
-2.0%

TA:4586.97

-2.0%
- 2. 2% 4587 TA:4586.77

-2.0%
E

X X

4587
X X X X FG:4585.00
B B

-2
X X X FG:4585.00

.4
FG:4587.00 X X X

%
FG:4587.00 X e X
6 X p r o j e c t # : 21.0320
458
X X X
4586 e X X X FG:4587.00
4586 X e X X FG:4587.00
4586
Xe X X d a t e : 02.14.2023
4586

TA:4586.77 TA:4587.35 4587


c

4587
revisions :
g

4586
D

4586
4586
e

85
45
g

4585

title:
GRADING GENERAL NOTES:
1. ALL TBC CALLOUTS ARE AT FULL HEIGHT AT BACK OF CURB.
GRADING
2. MAINTAIN A MINIMUM OF 0.5% LONGITUDINAL SLOPE IN ALL GUTTERS.
3. MAINTAIN A MAXIMUM OF 2.0% CROSS-SLOPE ON ALL SIDEWALKS AND AT ALL
BUILDING DOORWAY ENTRANCES AND EXITS. PLAN

GRADING LEGEND:
A FG = FINISHED GRADE
EG = EXISTING GRADE
A
ME = MATCH EXISTING
TA = TOP OF ASPHALT
TC = TOP OF CONCRETE
TBC = TOP BACK OF CURB
FL = FLOW LINE

N
GB = GRADE BREAK
TOW = TOP OF WALL
BOW = BOTTOM OF WALL
sheet:
TOS = TOP OF STAIRS

C201
BOS = BOTTOM OF STAIRS

0 20' 40'

PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6
18S

D
D

8S
C

ir
10W

12W
18S
D

D
8S
10W
ir

S
8W ir
8W ir

WW
8W ir

W
W

e
W
12W
18SD
10W

D
8S

C
g
ir

12W
ir

ir
S
8SS 8SS 700 EAST

D
6S
12" NYLOPLAST DRAIN

D
ir

8S
GRATE: 4591.36
11

8SS
IE:4588.06 10W 10W

30SD
10W 10W 10W
E E

12W
X 4
360 west aspen avenue
X

D
X ir

8S
X
9 X X ir
W X
salt lake city, utah 84101

c
X X
8W 12" NYLOPLAST DRAIN

8SS
ir X
8W

D
X
8W
X 801 532 4422

6S
X ir GRATE: 4596.49

ir
8W 8W 9
X ir X X IE:4588.44
END WALL DRAIN
8W

g
X ir
SD 8W X 4

D
8W
X X
8W 75.21' of 8"Ø PIPE @-0.5

8S
12W
X
8W X SD %

X
X
8W X X SD X
10

8SS

30SD
5 .70

ir
'o 12" NYLOPLAST DRAIN
f8

D
"Ø GRATE: 4589.90

ir

8S
ir PI IE:4587.02
SD PE HYDROVAC AND LOCATE THIS CONDUIT

X
ir

g ir
@

6S
12" NYLOPLAST DRAIN TO AVOID DAMAGE TO CONDUIT

12W
1.0
% GRATE/FLOWLINE ELEV: 4590.72

X
4

8W
IE:4587.07 FLOWLINE ELEV: 4591.56

S
8SS

D
ir
8SD 8SD
8SD

SD
8SD 20.63' of 8"Ø PIPE @0.5%

%
8SD

g
8SD
D

5
30SD
12

-0.
17.33' of 8"Ø PIPE @0.3%

ir
13

@
6 SD

E
12W

PIP
E
12" NYLOPLAST DRAIN
E

I
ir
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
E
8SS

4 GRATE: 4590.11


6SS E
6SS ir DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS

f8
6SS 221.26' of 6"Ø PIPE @2.0% IE:4587.07

E
sdir

6SS
1
ir

NOT INTENDED FOR CONSTRUCTION, RECORDING

'o
6SS
4 6SS ir 110.99' of 8"Ø PIPE @0.3%

X
6SS SD 1 4 12
ir

67
SCO
6SS

ir
PURPOSES, OR IMPLEMENTATION

SCO
6SS SD
% 6SS
E @0.3

SD 92.
6SS

8W
6SS SD
63.88'
o of 8 "Ø PIP SD 6SS
43.2
f 8"Ø P
IPE @0 80.71' 6' o
f 8"
SD .3% ØP
12W

X
12" NYLOPLAST DRAIN
SD IPE
8SS

1 8

30SD
GRATE: 4591.83 SD @0
.3%
gg

1
5.00' of 6"Ø PIPE @-2.0% IE:4586.63

SD

ir
12" NYLOPLAST DRAIN
12" NYLOPLAST DRAIN 1
GRATE: 4590.20
4 GRATE: 4590.20 11
IE:4587.46
IE:4587.26 SEE MECHANICAL PLANS
ir

(NE) INV IN: 4586.50


FOR CONTINUATION
8SS

11 SEE MECHANICAL PLANS 22.02' of 8"Ø PIPE @1.5%


12W

INV: 4586.15
sd

FOR CONTINUATION

8W
INV: 4587.82 (N) INV IN: 4587.50

X
8 1
gg
8SS

D 12" NYLOPLAST DRAIN D


12W
ir

ir
X

9 GRATE: 4591.40
6SS 4 IE:4588.11
4SS 4SS 4SS 4SS

8W
4SS
sd

4SS 1

S
SCO

S
SCO

SD
c e
8SS

12W

c
1.8%

SCO
@
C

PIPE
7 SD 89.64' of 8"Ø

X
X X

15SD c
g
ir
D

ir
PROPOSED BUILDING
ir

c (S) INV IN: 4586.50' (8")


8SS

12W
15SD

8W
2/8/2023
ir

ir

E
EXISTING BUILDING
ir

X X

SEE MECHANICAL PLANS

ir
FOR CONTINUATION
ir

8SS

INV: 4587.82

E
ir

12W

(N) INV IN: 4587.50


gg
15SD

ir

ir
ir

X
18
SEE MECHANICAL PLANS
W
8SS

FOR CONTINUATION
E
2W
e

INV: 4587.82 SEE MECHANICAL PLANS


ir

ir

g FOR CONTINUATION
ir

g
INV: 4587.82
E
12" NYLOPLAST DRAIN
15SD

1550 NORTH
12W
ir

GM

GRATE: 4589.75
E E

IE:4586.00
8SS

E
4
E

SEE MECHANICAL PLANS


5.00' of 6"Ø PIPE @2.0% FOR CONTINUATION
INV: 4587.82 16.94' of 6"Ø PIPE @2.0%
E

E THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


g

ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &

X
E
c
12W
15SD

x x 4.92' of 6"Ø PIPE @2.0% MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
8SS

x 1

e
ir

COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN


ir

WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS


ir

E
X

E
REGIONAL STORM DRAIN POND WRITTEN PERMISSION FROM METHOD STUDIO INC.
E

ir
REQUIRED VOLUME: 1.10 AC-FT
C C
ir

ir

APPROXIMATE VOLUME: 1.46 AC-FT

%
E

SD
c
E E

(5,238 CF OF 15.681 CF AVAILABLE


project:

@1.3
1

SD

X
8SS

STORAGE USED)
15SD

ir

SD
17

PIPE
54.24' of 6"Ø PIPE @7.2%
e

56.92' of 6"Ø PIPE @6.9%


ir

USU EVR
ir
X
g

Ø
ir

' of 8"
SD BOX #1 (3'X3')
12W

E
E

g
17 RIM: 4585.00' SUMP:4581.50'
30SD
E
E

EXPANSION

74.99
8SS

30SD
ir

(SW) INV OUT: 4582.50' (24")


ir

X
E

30SD

ir
ir

ir

15SD
18SD

30SD
D
ir
X

E 15SD

SD
4W
W

E
ir

30SD CONNECT TO EXISTING SUMP


E
8SS

ir
13 2
E

INV APPROX: 4583.82 15SD


6W sd (CONTRACTOR TO FIELD
15SD 12
30SD
E

6W
g
W
ir

SD BOX #6 (3'X3') VERIFY LOCATION AND ELEVATION)


30SD
15SD
RIM: 4585.00' SUMP:4581.50' 1
c

sd
W

6W (SW) INV IN: 4582.50' (24")


18SD

D
6W
W

(W) INV IN: 4585.00' (8")


X

15SD
(E) INV IN: 4585.00' (8")
8SS

SD
12 E

80

ir
2 19.69' of 24"Ø PIPE @0.0% 5

.0
STORM DRAIN POND #2

7'

X
of
STORM WATER POND #4 1 REQUIRED VOLUME:1,640 CF

24
9.49' of 8"Ø PIPE @1.0%

6S
REQUIRED VOLUME:2,015 CF PROVIDED VOLUME: 1,640 CF


g

6SS
S

PROVIDED VOLUME: 2,015 CF SD BOX #5 (3'X3')

PI
RIM: 4585.00' SUMP:4577.25'

PE
1
ir

18SD

2
X

(SW) INV IN: 4578.25' (24")

@
0.
g
e

SD

(NE) INV OUT: 4582.50' (24")

0%
8SS

12W

SD BOX #7 (3'X3') 2 (E) INV OUT: 4585.09' (8")


30

SD
RIM: 4586.00' SUMP:4581.77' 670 EAST 1550 NORTH, LOGAN, UT
SD

15
(NW) INV OUT: 4582.77' (12") STORM DRAIN POND #1
15

84341
E

REQUIRED VOLUME: 1,750 CF


e 1 PROVIDED VOLUME: 1,089 CF

ir
43 14
2 .36
X

' of
8SS

1 30SD 30SD 24

SD30SD
2
12W

30SD
PIP PIPES AND SD BOX STORAGE
8W

17
ir

15SD E@
15SD
2

X
15SD REQUIRED VOLUME: 1,976 CF
0.0
15SD % PROVIDED VOLUME: 1,976 CF
1 1
18SD
E

SD
X SD 2
SD IPE @0.0%
X X SD SD
9.76' of 12"Ø PIPE @2.0% X X ir SD
4"Ø P
X X ir SD
ir

X SD
EXISTING SD BOX #1 ' of 2
X ir SD
8SS

X
B B
ir
315.61' of 24"Ø PIPE @0.0% 57.16
X X X ir SD
RIM: 4586.73' SUMP:4582.50' ir e X X X ir ir
ir X X ir
p r o j e c t # : 21.0320
12W

X ir
(SE) INV IN: 4582.50' (12") ir e X X X
15SD

ir e X X Xe
ir X
SD BOX #4 (3'X3') X
ir
ir

12SD ir
d a t e : 02.14.2023
SD BOX #2 (3'X3')
c

12SD RIM: 4586.80' SUMP:4578.25'


(S) INV IN: 4582.50' (24") RIM: 4585.00' SUMP:4581.50'
g

revisions :
D

(NE) INV IN: 4582.50' (24")


8W

(NE) INV OUT: 4578.25' (24") SD BOX #3 (3'X3')


8SS

(N) INV OUT: 4582.50' (24")


ir

RIM: 4587.14' SUMP:4581.50'


e

(S) INV IN: 4582.50' (24")


D

18SD
12W

(N) INV OUT: 4582.50' (24")


e
ir
8SS
ir

18SD
ir
8W ir

ir
ir

1 UTILITY SHEET KEY NOTES: STORM WATER PLAN GENERAL NOTES: GENERAL NOTES:
PROVIDE, INSTALL, AND/OR CONSTRUCT THE FOLLOWING PER THE title:
SPECIFICATIONS GIVEN OR REFERENCED, THE DETAILS NOTED, AND/OR AS · ALL STORM WATER PIPE SHALL BE CORRUGATED HDPE. SIZE SHOWN ON PLANS. 1. CONTRACTOR TO FIELD VERIFY ALL EXISTING UTILITY LOCATIONS AND CONTACT ENGINEER IF
SHOWN ON THE CONSTRUCTION DRAWINGS: · ALL STORM WATER PIPE SHALL BE INSTALLED PER TRENCHING DETAIL 3 ON SHEET C-601.

UTILITY
DIFFERENT FROM LOCATIONS DISPLAYED ON THESE PLANS.
· ALL 2'X3' SD CB'S SHALL BE CONSTRUCTED PER DETAIL 7 ON SHEET C-602. 2. MINIMUM 18" OF VERTICAL SEPARATION REQUIRED BETWEEN WATER MAIN AND SEWER MAIN
1. STORM DRAIN PIPE (TYP). SEE 1/C501. · 3'X3' SD CB'S SHALL BE CONSTRUCTED PER DETAIL 7 ON SHEET C-602 OR DETAIL 4 ON C-601 WHERE LINES INTERSECT.
2. STORM DRAIN CATCH BASIN. SEE 3/C501. FOR FLAT LID BOXES. 3. MINIMUM OF 10' FROM OUTSIDE-OF-PIPE TO OUTSIDE-OF-PIPE REQUIRED BETWEEN CULINARY
3.
4.
5.
NOT USED
NYLOPLAST DRAIN (TYP). SEE 2/C501.
CLASS C TRENCH DRAIN. SEE 1-4/C502.
·

·
A SNOUT SHALL BE INSTALLED IN EACH CATCH BASIN LOCATED IMMEDIATELY UPSTREAM
FROM THE DOWNSTREAM STORM DRAIN MANHOLE SUMP. SEE DETAIL 6 ON SHEET C-601.
ALL ROOF DRAINS UTILIZE NYLOPLAST INLINE DRAINS SHALL BE CONSTRUCTED PER DETAIL 8
4.
WATER LINE AND ALL OTHER WET UTILITIES.
ALL SEWER, STORM DRAIN, FIRELINES AND CULINARY WATER LINES SHALL BE INSTALLED PER
UTILITY TRENCHING DETAIL FOUND IN DETAIL 1/C501.
PLAN
6. IRRIGATION METER. SEE 4/C501 ON SHEET C-601. 5. ALL CULINARY WATER LINES SHALL BE DUCTILE IRON. ALL WATER MAINS SHALL BE INSTALLED
7. COMMUNICATIONS MANHOLE & LINES. SEE ELECTRICAL PLANS. WITH A MINIMUM OF 5.5' OF COVER.
8. SEWER CLEAN OUT SEE 2/C503 6. ALL SEWER LINES SHALL BE CONSTRUCTED OF PVC SDR-35 MATERIAL.
9. 8" WATER LINE SEE 1/C501. 7. CONTRACTOR SHALL PLACE CONCRETE THRUST BLOCKS ON ALL TEES, WYES, BENDS, ANGLES,
10. NOT USED ETC ON ALL WATER LINES AS SHOWN IN DETAIL 1/C503.
11. CONSTRUCT SWALE. 8. INSTALLATION OF 6" SDR-35 SEWER LINE AT A 1% MINIMUM.
12. LIGHT POLE - SEE ELECTRICAL PLAN 9. FOR 6" SDR-35 CONNECTION TO 8" SEWER MAIN SEE DETAIL 3/C503.
13. UNDERGROUND ELECTRICAL LINE - SEE ELECTRICAL SITE PLAN
14. ADJUST EXISTING STORM DRAIN BOX TO MATCH PROPOSED GRADE.
A 15.
16.
PROTECT ELECTRIC DUCT BANK
CONNECT TO EXISTING STORM DRAIN BOX IE 4582.50
A
17. PROTECT EXISTING STORM DRAIN BOXES DURING CONSTRUCTION
18. 2" FIRELINE DRAIN

N
sheet:

0 20' 40' C301


PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6
18S

D
D

8S
C

ir
10W

12W
18S
D

D
8S
10W
ir

S
8W ir
8W ir

WW
8W ir

W
W

e
W
12W
18SD
10W

D
8S

C
g
ir

12W
ir

ir
S
8SS 8SS 700 EAST

D
6S

D
ir

8S
8SS
10W 10W

30SD
10W 10W 10W
E E

12W
X
360 west aspen avenue
X

D
X ir

8S
X X X ir
W X
salt lake city, utah 84101

c
X X
8W

8SS
ir X
8W

D
X
8W
X 801 532 4422

6S
X ir

ir
8W 8W
X ir X X
8W

g
X ir
SD 8W X

D
8W
X X
8W

8S
12W
X
8W X SD

X
X
8W X X SD X

8SS

30SD
ir

D
ir

8S
ir SD

X
ir

g ir
6S

12W

8W
S
8SS

D
ir
8SD 8SD
8SD

SD
8SD
8SD SUB-1

g
8SD
D

30SD
SUB-9

ir
SD

12W

E
E

I
ir
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
E
8SS

6SS E
6SS 6SS ir DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS

E
sdir

6SS
ir

6SS 6SS ir NOT INTENDED FOR CONSTRUCTION, RECORDING

X
6SS SD
ir

SCO
6SS

ir
PURPOSES, OR IMPLEMENTATION

SCO
6SS 6SS SD
6SS

8W
6SS SD
SD 6SS

SD
SD
12W

X
SD
8SS

30SD
SD
gg

SD

ir
ir
8SS

12W
sd

8W

X
gg
8SS

D D
12W
ir

ir
X

6SS
4SS 4SS 4SS 4SS

8W
4SS
sd

4SS

S
SCO

S
SCO

SD
c e
SUB-2
8SS

12W

SCO
C

SD

X
X X

15SD c
g
ir
D

ir
ir

c
8SS

12W
15SD

8W
2/8/2023
ir

ir

E
ir

X X

ir
SUB-3 SUB-4
ir

8SS

E
ir

12W

gg
15SD

ir

ir
ir

X
SUB-5
W
8SS

E
2W
e
ir

ir

g
ir

g
E
15SD

1550 NORTH
12W
ir

GM
E E
8SS

E
E
E

E THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


g

ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &

X
E
c
12W
15SD

x x MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE


8SS

e
ir

COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN


ir

WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS


ir

E
X

E
REGIONAL STORM DRAIN POND WRITTEN PERMISSION FROM METHOD STUDIO INC.
E

ir
REQUIRED VOLUME: 1.10 AC-FT
C C
ir

ir

APPROXIMATE VOLUME: 1.46 AC-FT


E

SD
c
E E

(5,238 CF OF 15,681 CF AVAILABLE


project:

SD

X
8SS

STORAGE USED)
15SD

ir

SD
e
ir

USU EVR
ir
X
g
ir

12W

E
E

g
30SD
E
E

EXPANSION
8SS

30SD
ir

ir

X
E

30SD

ir
ir

ir

15SD
18SD

30SD
D
ir
X

E 15SD

SD
4W
W

E
ir

30SD
E
8SS

ir
E

15SD
6W sd 15SD
30SD
E

6W
g
W
ir

30SD
15SD
c

sd SUB-6
W

6W
18SD

D
6W
W

15SD
8SS

SD
E

ir
STORM DRAIN POND #2

X
REQUIRED VOLUME:1,640 CF

D
6S
PROVIDED VOLUME: 1,640 CF
g

6SS
S

STORM WATER POND #4


REQUIRED VOLUME:2,015 CF
ir

18SD

PROVIDED VOLUME: 2,015 CF


SUB-7
g
e

SD
8SS

12W

30

SD
670 EAST 1550 NORTH, LOGAN, UT
SD

STORM DRAIN POND #1


15

84341
E

e REQUIRED VOLUME: 1,750 CF


PROVIDED VOLUME: 1,089 CF
SUB-8

ir
X
8SS

30SD 30SD SD 30SD


12W

30SD
PIPES AND SD BOX STORAGE
8W

ir

15SD 15SD

X
15SD REQUIRED VOLUME: 1,976 CF
15SD PROVIDED VOLUME: 1,976 CF
18SD
E

X SD SD
SD
X X X ir SD SD
X X X ir SD SD
ir

X X ir SD SD
8SS

X
B B
X X X ir ir SD
ir e X X X ir ir
ir X X ir
p r o j e c t # : 21.0320
12W

ir e X X X ir
X
15SD

ir e X X Xe
ir X X
ir
ir

12SD ir
d a t e : 02.14.2023
c

12SD
g

revisions :
D
8W

8SS
ir

18SD
12W

e
ir
8SS
ir

18SD
ir
8W ir

ir
ir

title:

STORMWATER
BASIN

A A

N
sheet:

0 20' 40' C302


PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6

SUBBASIN 1 CALCULATIONS SUBBASIN 7 CALCULATIONS


SUBBASIN 2 CALCULATIONS SUBBASIN 5 CALCULATIONS SUBBASIN 6 CALCULATIONS

E E
360 west aspen avenue
salt lake city, utah 84101
801 532 4422

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

D D

2/8/2023

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
DETENTION VALUE DETENTION VALUE DETENTION VALUE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
DETENTION VALUE
DETENTION VALUE WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
SUBBASIN 8 CALCULATIONS SUBBASIN 9 CALCULATIONS project:

USU EVR
EXPANSION

STORM WATER VOLUMES


RETENTION (90TH 670 EAST 1550 NORTH, LOGAN, UT
BASIN DETENTION 84341
PERCENTILE)
SUBBASIN 1 1,364 CU-FT 806 CU-FT
SUBBASIN 2 1,285 CU-FT 634 CU-FT
B SUBBASIN 5 443 CU-FT 204 CU-FT B
p r o j e c t # : 21.0320
SUBBASIN 6 4,705 CU-FT 2,760 CU-FT d a t e : 02.14.2023
SUBBASIN 7 274 CU-FT 342 CU-FT revisions :
SUBBASIN 8 434 CU-FT 528 CU-FT
SUBBASIN 9 3,953 CU-FT 3,271 CU-FT

TOTAL REQUIRED 12,458 CU-FT 8,545 CU-FT

TOTAL PROVIDED 11,958 CU-FT 8,545 CU-FT


title:

STORMWATER
CALCS

A A

sheet:

DETENTION VALUE DETENTION VALUE 0 40' C303


PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6

E E
360 west aspen avenue
salt lake city, utah 84101
801 532 4422

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

D D

2 NYLOPLAST DRAIN
NOT TO SCALE
C501

2/8/2023

1 TRENCHING DETAIL
NOT TO SCALE
C501

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C GRATE C
project:

USU EVR
NOTE:
1. CATCH BASINS AND GRATE SHALL MEET ASTM C858
WITH AASHTO HS-20 LOADING.
EXPANSION
2. OPENINGS MAY BE LOCATED AS REQUIRED.
3. CATCH BASIN SHALL BE PRECAST OR CAST IN PLACE OF VARIES AS
3,000 PSI CONCRETE. REQ'D TO
MEET GRADE

RISER
VARIES
2'-0" VARIES
2'-0"

VARIES

CATCHBASIN 670 EAST 1550 NORTH, LOGAN, UT


84341
VARIES
2'-11"
+ RISER HT.

24" KNOCKOUTS

B
TYP. ALL 4 SIDES
4 IRRIGATION METER B
VARIES
3'-0" VARIES
3'-0" C501 NOT TO SCALE p r o j e c t # : 21.0320
d a t e : 3/6/2023
02.14.2023
5 2" WATER METER revisions :
C501 NOT TO SCALE

3 STORM DRAIN BOX


NOT TO SCALE NOTES
C501 LANDING 2%
1. DETECTABLE WARNING SURFACE DOMES SHALL BE ORIENTED SUCH THAT ROWS ARE PARALLEL WITH THE DIRECTION OF
2"
MAX. SLOPE MIN
PEDESTRIAN TRAVEL TO THE RAMP ON THE OPPOSITE SIDE OF THE STREET. CLEAR
2. THE STANDARD COLOR FOR THE DETECTABLE WARNING SURFACE SHALL BE RED OR AS DETERMINED BY THE CITY
BEGIN TAPERING CURB ENGINEER OR OTHER AUTHORIZED REPRESENTATIVE.
TO MATCH RAMP. 3. WHEN A DETECTABLE WARNING SURFACE DOME IS CUT, THE REMAINING PORTION OF THE DOME SHALL BE BEVELED TO
A MAXIMUM SLOPE OF 1:2.
RAMP 1 TO 12 SLOPE

4. AT LEAST 21 PAVER MUST BE USED (I.E. NO SMALL PIECES OR SLIVERS).


5. NO LIP IN CURB GREATER THAN 1/4-IN HIGH ALLOWED ALONG LENGTH OF RAMP.
6. LENGTHS OF RAMPS VARY AS REQUIRED TO MEET 1(V):12(H) SLOPE OR FLATTER. title:
7. ABSOLUTE MINIMUM DIMENSIONS OF LANDING TO BE 48-IN BY 48-IN.
WALL HORIZONTAL REINF.
DETAILS
8. LANDING FLARES TO BE PARALLEL WITH RAMPS. THE MAXIMUM SLOPE ON LANDING FLARES SHALL BE 1(V):12(H) SLOPE
OR FLATTER.
NOTE: PROVIDE JOINT SEALING
9. PAVER SAND TO BE UNDERLAIN WITH 3-IN THICK 4000psi CONCRETE WITH 3/4" Ø DRAIN HOLES 12-IN O.C. FILLED WITH COMPOUND AT VERTICAL JOINTS
30" OPEN FACE CURB SAND.
AND GUTTER.

FLARE FLARE
PROVIDE VERTICAL CHAMFER
STRIP (1" DEPTH) CONTINUOUS
FULL HEIGHT OF WALL. EACH
SIDE OF WALL

A A

WALL VERTICAL REINF. PROVIDE BREAK IN


HALF OF HORIZONTAL
REINF.
ADA STD. DETECTABLE CAST IRON TRUNCATED DOMES
24-IN WIDE, ALONG BACK OF CURB FOR ENTIRE
LENGTH OF CURB DROP (FOR VISION-IMPAIRED PERSONS)
sheet:

6
C501
ADA RAMP
NOT TO SCALE 7
C501
RETAINING WALL JOINTS
NOT TO SCALE
C501
PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6

E E
360 west aspen avenue
salt lake city, utah 84101
801 532 4422

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

D D

1 2 3 4
C502 C502 C502 C502
2/8/2023

FOUNDATION AND EARTHWORK:


FOUNDATION DESIGN ACCORDING TO IBC 2018 SECTION 1806

DESIGN BEARING CAPACITY = 1500 PSF


FINISH GRADE TOP SOIL
WALL SHOULD BE ESTABLISHED ON UNDISTURBED NATIVE SOILS.
8" BACKFILL SLOPE INSTALL 6" PORTLAND CEMENT CONCRETE
WRAP GEO FILTER FABRIC
AT TOP OF DRAIN 1 UNDER NO CIRCUMSTANCE SHALL WALL BE PLACED OVERLYING NON-ENGINEERED FILL, LOOSE SOIL, FROZEN
SOIL, SOIL CONTAINING FOREIGN DEBRIS, OR ANY OTHER DELETERIOUS MATERIAL. UNSUITABLE MATERIAL
2"
6" MAX

MUST BE REMOVED AND REPLACED WITH AN APPROVED STRUCTURAL FILL..


INSTALL 6 INCHES OF UNTREATED
STRUCTURAL FILL SHALL BE PLACED IN LIFTS NOT EXCEEDING 8 INCHS (LOOSE THICKNESS) AND COMPACTED
BASE COURSE
TO A MINIMUM OF 95% MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D-1557.
SIDEWALK SIDEWALK
ASSUMED SOIL LATERAL DESIGN LOADS: PROPERLY PREPARED AND STABILIZED
STEM WALL
BACKFILL SOIL FRICTION ANGLE, OR ANGLE OF FAILURE = 32° FILLS, NATURAL SUBGRADE SOILS, AND/OR
HORIZONTAL REINF. SOIL DENSITY = 120 PCF STRUCTURAL SITE GRADING FILL EXTENDING THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
TO PROPERLY PREPARED AND STABILIZED ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
FOLLOW ALL BLOCK MANUFACTURER RECOMMENDATIONS FOR INSTALLATION - INCLUDING, BUT NOT LIMITED FILLS AND/OR NATURAL SUBGRADE SOILS. MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
TO: WALL PLACEMENT, GEOGRID INSTALLATION, WALL CORNERS AND TURNING POINTS, AND DRAINAGE. SOIL PREPARATION SHALL FOLLOW THE NOTES: COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
STEM WALL DIRECTION OF THE CIVIL SOLUTIONS GROUP PREMOULD ASPHALT &
1. PORTLAND CEMENT CONCRETE SHALL HAVE A 28-DAY WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
VERTICAL REINF. REINFORCED, COMPACTED SOIL LEVELING PAD SHALL CONSIST OF ROAD BASE OR 1/2" TO 3/4" CRUSHED STONE. LEAN UNREINFORCED GEOTECHNICAL STUDY. FELT OR ASPHALT & FIBER WRITTEN PERMISSION FROM METHOD STUDIO INC.
COMPRESSIVE STRENGTH OF 4,000 POUNDS PER SQUARE INCH.
EXPANSION JOINT.
C DOWEL TO MATCH SIZE AND
CONCRETE (2000 PSI) IS AN ACCEPTABLE SUBSTITUTE AS A LEVELING PAD. LEVELING PAD SHALL BE LEVEL
FRONT-TO-BACK AND SIDE-TO-SIDE AND BE COMPACTED TO 95% STANDARD PROCTOR.
2. CONCRETE SHALL BE AIR ENTRAINED WITH APPROXIMATELY 6
PERCENT AIR.
(24' SPACING) C
5.0' MAX RETAINED HEIGHT

SPACING OF WALL VERTICAL


REINF. PROVIDE STD. HOOK
LINE OF EXCAVATION
USE ONLY HAND OPERATED COMPACTING EQUIPMENT WITHIN 4 FEET OF RETAINING WALL.
3. PROVIDE CONTRACTION JOINTS @ 10'-0" O.C.
4. PROVIDE EXPANSION JOINTS @ 50'-0" O.C.
project:
AT FOOTING AND EXTEND 1" DIA. CLEAN SECTION A-A
WRAP DRAINAGE SYSTEM WITH MIRAFI 140N GEOTEXTILE OR APPROVED EQUIVALENT.
INTO WALL MIN. LAP LENGTH
2"
DRAINAGE STONE
TOP LAYER OF GEOGRID REINFORCEMENT SHALL NEVER BE MORE THAN 2 UNITS FROM THE TOP OF THE WALL.
CONTRACTION JOINT (MINIMUM DEPTH
USU EVR
FINISH GRADE 12" DRAIN BOTTOM LAYER OF OF GEOGRID REINFORCEMENT SHALL NEVER BE MORE THAN 2 UNITS FROM THE TOP OF
LEVELING PAD. 7
STANDARD DUTY EQUALS 1/4 OF SLAB THICKNESS)
EXPANSION
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE EXTENT OF EXCAVATION AND SAFE
EXCAVATION SLOPE.
C502 CONCRETE PAVEMENT 24' O.C.
A A
NOT TO SCALE
CALL BEFORE YOU DIG! CALLING 811 BEFORE EVERY DIGGING JOB GETS YOUR UNDERGROUND UTILITY LINES
MARKED FOR FREE AND HELPS PREVENT UNDESIRED CONSEQUENCES.

CONCRETE:
30" MIN FROST DEPTH

SLOPE TO
2% MIN.
FOOTING LONG. BARS EXPANSION

CURB
ALL CONCRETE CONSTRUCTION SHALL CONFORM TO THE LATEST, ADOPTED EDITIONS OF THE STANDARD EXPANSION JOINT
VARIES
AND MATERIAL SPECIFICATIONS REFERENCED BELOW JOINT
INSTALL 4 INCHES STANDARD ASPHALT
ACI 117 - SPECIFICATIONS FOR TOLERANCES OF CONCRETE CONSTRUCTION
INSTALL 8 INCHES OF UNTREATED
ACI 301 - SPECIFICATIONS FOR STRUCTURAL CONCRETE
BASE COURSE
ACI 304 - GUIDE FOR MEASURING, MIXING, TRANSPORTING AND PLACING CONCRETE
2" ACI 305 - HOT WEATHER CONCRETING
ACI 306 - COLD WEATHER CONCRETING INSTALL 8 INCHES OF 3" MINUS
ACI 308 - GUIDE FOR CURING OF CONCRETE GRAVEL SUBBASE COURSE
GEO FILTER FABRIC ACI 309 - GUIDE FOR CONSOLIDATION OF CONCRETE
1'-0" ACI 315 - DETAILS AND DETAILING OF CONCRETE REINFORCEMENT 670 EAST 1550 NORTH, LOGAN, UT
ACI 318 - BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE PROPERLY PREPARED AND STABILIZED NOTE: 7" CONCRETE SECTION THROUGH DRIVEWAYS.
4" PERFORATED DRAIN PIPE. DRAINAGE PIPE SHALL MAINTAIN POSITIVE ACI 347 - GUIDE TO FORMWORK FOR CONCRETE FILLS, NATURAL SUBGRADE SOILS, AND/OR 5" CONCRETE SECTION THROUGH ALL OTHER AREAS. 84341
STRUCTURAL SITE GRADING FILL EXTENDING NOTES:
DRAINAGE. INSTALL DRAINPIPE TO STORM DRAIN SYSTEM OR DAYLIGHT.
TO PROPERLY PREPARED AND STABILIZED 1. PAVEMENT SECTION SHALL CONFORM TO THE SITE
PROVIDE DAYLIGHT DRAINAGE PIPE EVERY 30 FEET AND AT ENDS OF WALL. CONCRETE SHALL BE PLACED MONOLITHICALLY BETWEEN CONTROL JOINTS. PROTECT ALL CONCRETE GEOTECHNICAL STUDY.
3" FROM PREMATURE DRYING, AND EXCESSIVE HOT OR COLD TEMPERATURE FOR SEVEN DAYS AFTER FILLS AND/OR NATURAL SUBGRADE SOILS.
SOIL PREPARATION SHALL FOLLOW THE
PLACING.
FOOTING TRANS. BARS DIRECTION OF THE CIVIL SOLUTIONS GROUP
GEOTECHNICAL STUDY.
1'-6" 2'-0" CONCRETE STRENGTH SHALL MEET THE FOLLOWING 28-DAY COMPRESSIVE STRENGTH (f'c) UNLESS
OTHERWISE NOTED IN THE DRAWINGS.

B 3'-6"
CONCRETE STRENGTH AND MIX REQUIRMENTS STANDARD DUTY B
p r o j e c t # : 21.0320
28 DAY WATER 6
REINFORCING STEEL: STANDARD HOOK GEOMETRY
MEMBER COMPRESSIVE
STRENGTH
CEMENT
RATIO
AIR
ENTRAINMENT
SLUMP
EXP.
CLASS
C502
ASPHALT PAVEMENT d a t e : 3/6/2023
02.14.2023

ALL CONCRETE REINFORCEMENT SHALL BE PLACED IN ACCORDANCE WITH ACI DETAILING MANUAL
BAR INSIDE 90° 180° STRUCTURAL 1
NOT TO SCALE
5" SUB GRADE, MINIMUM COMPACTION
REQUIRED = 95% STD. PROCTOR
revisions :
MNL-66(20) AND CONCRETE REINFORCING STEEL INSTITUTE (CRSI) MANUAL OF STANDARD PRACTICE. 4500 PSI 0.45 6% ± 1 2% 4" ± 1" F2
BAR SIZE DIAMTER, BEND HOOK HOOK WALLS
CONCRETE REINFORCEMENT SHALL CONFORM TO THE FOLLOWING STANDARDS AND MATERIAL db DIAMETER LENGTH LENGTH EXTERIOR
4500 PSI 0.45 6% ± 1 21% 4" ± 1" F2
PROPERTIES: STAIRS
#3 3/8 2 1/4 6 2 1/2
DEFORMED BARS ASTM615 GRADE 60 #4 1/2 3 8 2 1/2 USE TYPE II PORTLAND CEMENT.

REINFORCEMENT SHALL HAVE THE FOLLOWING CONCRETE PROTECTION (CLEAR COVER) PER ACI 318: #5 5/8 3 3/4 10 2 1/2
CEMENT TO CONFORM TO ASTM C150.

CONDITION COVER
#6 3/4 4 1/2 12 3
FINE AND COARSE AGGREGATE TO BE CLEAN, HARD, DURABLE, AND FREE OF DELETERIOUS SUBSTANCES 9 CONCRETE SIDEWALK
CAST AGAINST EARTH 3" AND SHALL CONFORM TO ASTM C33. NOT TO SCALE
FORMED AND EXPOSED TO EARTH OR WEATHER 2"
STANDARD HOOK DETAILS
C502
WALL EXPOSED TO WEATHER 2" MAXIMUM AGGREGATE SIZE TO BE 3/4".
IN ACCORDANCE WITH ACI 318 TABLE 25.3.1
ALL REINFORCEMENT SHALL BE SECURELY TIED OR HELD IN PLACE WITH PROPER ACCESSORIES. DO NOT WATER SHALL BE POTABLE.
USE WOOD OR BRICK TO SUPPORT REINFORCEMENT. CHAIRS OR SPACERS SHALL BE PLASTIC WHEN
RESTING ON EXPOSED SURFACES.
db 90° WATER REDUCING AGENTS SHALL CONFORM TO ASTM C494.
title:
ALL BARS SHALL BE KEPT CLEAN AND FREE OF RUST. AIR ENTRAINMENT ADMIXTURE SHALL CONFORM TO ASTM C260.

ALL SPLICES SHALL LAP THE MINIMUM LISTED LAP LENGTH.


HOOK
LENGTH
DIAMETER
CONCRETE TO BE READY-MIXED AND DELIVERED IN COMPLIANCE WITH ASTM C94. DETAILS
STAGGER HORIZONTAL WALL REINFORCEMENT SO THAT NO TWO BARS IN THE SAME OR OPPOSITE MAT DOWELS IN WALL FOOTINGS TO MATCH SIZE AND SPACING OF WALL VERTICAL BARS. DOWELS MUST BE
ARE SPLICED AT THE SAME LOCATION. SECURED IN PLACE PRIOR TO PLACEMENT OF CONCRETE. EXTEND MINIMUM DEVELOPMENT LENGTH INTO
MEMBER ABOVE AND BELOW. WHERE MINIMUM DEVELOPMENT LENGTH CANNOT BE ACHIEVED, PROVIDE
EMBEDMENT OF STANDARD HOOKS SHALL MEET THE MINIMUM EMBEDMENT DEPTH SPECIFIED IN ACI 318. STANDARD 90° HOOK.
2 FEET 2 FEET
CONCRETE REINFORCEMENT DEVELOPMENT AND LAP SPLICE LENGTH SCHEDULE PROVIDE 3/4" CHAMFER AT EXTERIOR CONCRETE CORNERS AND EDGES OF PERMANENTLY EXPOSED REINFORCEMENT
CONCRETE.
S = O.0521 #4 @ 24" O.C.
1 1/4" (4) #4 @ 12" O.C.
CONCRETE RETAINING WALL SCHEDULE ALL CONCRETE SURFACES AGAINST WHICH NEW CONCRETE IS TO BE PLACED SHALL BE CLEANED AND
ROUGHENED TO AN AMPLITUDE OF 1/4". 9"
FOOTING STEM WALL
MAXIMUM GEOMETRY REINFORCEMENT REINFORCEMENT 4" 3"
CONCRETE IS TO BE MECHANICALLY VIBRATED AND CONSOLIDATED DURING PLACEMENT PER ACI
TYPE RETAINED
A HEIGHT TOE HEEL TOTAL
LONGITUDINAL TRANSVERSE WALL
WIDTH
STANDARDS.
8" BASE COURSE
A
DEPTH VERT. HORIZ.
LENGTH LENGTH WIDTH TOP BOTT. TOP BOTT. NO ALUMINUM ITEMS SHALL BE IN OR PLACED IN CONTACT WITH CONCRETE.
RW-1 5'-0" 1'-0" 1'-0" 1'-10" 2'-10" (3) #4 (3) #4 #4 AT 18" #4 AT 18" 8" #4 AT 14" #4 AT 14" 4' - 0"
DEVELOPMENT AND LAP SPLICE LENGTH SCHEDULE
RETAINING WALL NOTES: NORMAL WEIGHT CONCRETE, f'c = 4000PSI
-WALL DESIGN ASSUMES DRY, COMPACTED STRUCTURAL FILL. IF INTRODUCTION OF WATER TO THE RETAINED SOIL IS A POSSIBILITY, CONTACT THE ENGINEER OF
HORIZONTAL BARS WITH MORE
4' - 0" WATERWAY
RECORD FOR ADDITIONAL REQUIREMENTS.
- SOIL IS TO BE PLACED AND COMPACTED AT FRONT OF WALL PRIOR TO PLACING AND COMPACTING SOIL AT RETAINED FACE.
- PROVIDE VERTICAL CONTROL JOINTS WITH SPACING NOT TO EXCEED 20 FEET ON CENTER. AT VERTICAL CONTROL JOINT, PROVIDE DISCONTINUITY FOR HALF OF ALL
BAR SIZE
THAN 12" OF CONCRETE CAST
BELOW
OTHER BARS CONCRETE AREA = 2.583 SQ. FT.
sheet:
HORIZONTAL REINFORCEMENT.

C502
DEVELOPMENT LAP SPLICE DEVELOPMENT LAP SPLICE

#3 1'-8" 2'-2" 1'-3" 1'-8"

RETAINING WALL
#4 2'-1" 2'-9" 1'-7" 2'-1"
CATCH CURB & 10
4' WATERWAY
5 NOTES: TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE LENGTHS ARE
8 NOT TO SCALE
C502 NOT TO SCALE
CALCULATED PER ACI 318 CHAPTER 25 SECTION 4. LENGTHS ARE BASED ON GR. 60
UNCOATED BARS WITH CASE 1 DEVELOPMENT AND CLASS B SPLICE. LENGTHS SHOWN
IN SCHEDULE ARE MINIMUM LENGTHS, PROVIDING A LONGER LENGTH THAN SHOWN IS C502 GUTTER C502
NOT DETRIMENTAL AND MAY BE ADVANTAGEOUS FOR CONSTRUCTIBILITY PURPOSES.
NOT TO SCALE PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6

E E
360 west aspen avenue
salt lake city, utah 84101
801 532 4422

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

D D

2/8/2023
1 THRUST BLOCK DETAILS
C503 NOT TO SCALE 2 6" SEWER TWO WAY CLEANOUT
C503
3 6" SEWER TWO WAY CLEANOUT
C503

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

USU EVR
EXPANSION
0.5% LOW POINT 0.5%

670 EAST 1550 NORTH, LOGAN, UT


84341

NOTES:
1. SEE CONCRETE STRENGTH AND MIX REQUIREMENT ON SEE C502.
TRENCH TO COMPLY WITH STRUCTURAL WALL MIX DESIGN.
B B
p r o j e c t # : 21.0320
d a t e : 3/6/2023
02.14.2023

revisions :

4 UTILITY TRENCH
C503

title:

DETAILS

A A

sheet:

C503
PERMIT SET
1 2 3 4 5 6
1 2 3 4 5 6
STRUCTURAL NOTES :

A. GENERAL E. CONCRETE H. SUSPENDED CONCRETE SLABS / SLABS ON METAL DECK J. STRUCTURAL STEEL

1. THE STRUCTURAL NOTES ARE INTENDED TO COMPLEMENT THE PROJECT SPECIFICATIONS W HICH ARE 1. ALL CONCRETE MIX DESIGNS SHALL COMPLY W ITH THE PROJECT SPECIFICATIONS AND THE 1. UNLESS NOTED OTHERW ISE, ALL CONCRETE SLABS ON METAL DECK SHALL BE 5-1/2" TOTAL 1. STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE W ITH THE LATEST EDITION
PART OF THE CONSTRUCTION DOCUMENTS. SPECIFIC NOTES AND DETAILS ON THE DRAW INGS SHALL REQUIREMENTS LISTED BELOW : THICKNESS NORMAL W EIGHT CONCRETE W ITH A W EIGHT LESS THAN 145 POUNDS PER CUBIC FOOT, OF THE FOLLOW ING:
GOVERN OVER THE STRUCTURAL NOTES AND TYPICAL DETAILS. a. FOOTINGS, GRADE BEAMS, FOUNDATION W ALLS : REINFORCED W ITH 6 X 6 - W 1.4 X W 1.4 W ELDED W IRE FABRIC. REINFORCING STEEL SHALL BE CHAIRED a. ANSI/AISC 360-16 “SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS”, W ITH “COMMENTARY” AND
2. THESE DRAW INGS (AND, W HERE APPLICABLE, ACCOMPANYING W RITTEN SPECIFICATIONS) ARE THE 1. W HERE THE TOP OF THE ELEMENT IS EXPOSED OR IS LOCATED W ITHIN 30” OF THE LOW EST TO 1” TOP COVER AT ALL BEAM LOCATIONS. EXCEPT W HERE SPECIFICALLY DETAILED, FIBER MESH MAY “SUPPLEMENTS” AS REQUIRED BY BUILDING CODE.
ONLY CONTRACT DOCUMENTS PROVIDED BY ARW ENGINEERS FOR THE PROJECT REPRESENTED ADJACENT GRADE (EXPOSURE CATEGORY F2) : BE USED IN PLACE OF REINFORCEMENT IN SLABS ON DECK W HEN USED IN ACCORDANCE W ITH AN b. AISC 303-16 “CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES” EXCLUDING THE
HEREIN. NOTHING IN ANY DIGITAL MODEL OR DIGITAL FILE RELATED TO THIS PROJECT SHALL BE a. 28 DAY COMPRESSIVE STRENGTH : 4500 PSI APPROVED ICC RESEARCH REPORT AND W HERE APPROVED BY THE ENGINEER. W HERE THE SLAB FOLLOW ING SECTIONS: 4.4, 4.4.1, AND 4.4.2.
TAKEN TO SUPERSEDE ANY INFORMATION SHOW N IN THESE DRAW INGS (INCLUDING, BUT NOT LIMITED b. MAXIMUM W /C RATIO : 0.45 CONSTRUCTION IS USED TO OBTAIN A UL FIRE RATING, THE PROPOSED FIBER MESH SHALL HAVE UL c. AISI “SPECIFICATIONS FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS”.
TO, DIMENSIONS, SIZES, ETC). c. MAXIMUM AGGREGATE SIZE : 1” ACCEPTANCE AS AN APPROVED ALTERNATIVE TO W ELDED W IRE FABRIC. d. AISC “SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH STRENGTH BOLTS”.
3. THE ARCHITECTURAL DRAW INGS ARE THE PRIME CONTRACT DRAW INGS. THE STRUCTURAL DRAW INGS d. AIR CONTENT : SEE SCHEDULE BELOW 2. AROUND OPENINGS IN SUSPENDED CONCRETE SLABS, ADD REINFORCING BARS EQUIVALENT TO BARS e. AW S D1.1 AND 1.3, “STRUCTURAL W ELDING CODE” (EXCEPT SPECIFIC ITEMS DO NOT APPLY IF THEY
ARE SUPPLEMENTARY TO AND MUST BE USED IN CONJUNCTION W ITH THE ARCHITECTURAL DRAW INGS 2. W HERE THE TOP OF THE ELEMENT IS NOT EXPOSED OR IS NOT LOCATED W ITHIN 30” OF THE CUT BY OPENING W ITH HALF ON EACH SIDE OF OPENING. BARS PARALLEL TO PRINCIPAL REINFORCING CONFLICT W ITH AISC).
AND OTHER CONSULTANTS DRAW INGS. ALL OMISSIONS OR CONFLICTS BETW EEN THE VARIOUS LOW EST ADJACENT GRADE (EXPOSURE CATEGORY F0) : SHALL RUN FULL LENGTH OF SPAN. BARS PARALLEL TO TEMPERATURE REINFORCING SHALL RUN 24” f. ANSI/AISC 341-16 “SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS”.
ELEMENTS OF THE W ORKING DRAW INGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE 3. 28 DAY COMPRESSIVE STRENGTH : 3000 PSI BEYOND OPENING. g. AW S D1.8, "STRUCTURAL W ELDING CODE - SEISMIC".
ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER BEFORE PROCEEDING W ITH ANY W ORK b. INTERIOR SLABS ON GRADE (EXPOSURE CATEGORY F0) : 3. SLAB PENETRATIONS LESS THAN 6” IN ALL DIRECTIONS W ITH A CLEAR SPACING OF AT LEAST 3 TIMES 2. STRUCTURAL STEEL SHALL COMPLY W ITH THE FOLLOW ING:
E INVOLVED. IN CASE OF CONFLICT, FOLLOW THE MOST STRINGENT REQUIREMENT AS DIRECTED BY THE 1. 28 DAY COMPRESSIVE STRENGTH : 4000 PSI THE LONGEST DIMENSION, DO NOT REQUIRE SUPPLEMENTAL REINFORCING. OTHERW ISE, THE a. W IDE FLANGE SHAPES, CHANNELS, AND W T SHAPES - ASTM A992 (Fy = 50 ksi) E
ARCHITECT AT NO ADDITIONAL COST TO THE OW NER. c. INTERIOR SUSPENDED SLABS (EXPOSURE CATEGORY F0) : PENETRATIONS SHALL BE FRAMED ON 4 SIDES W ITH STEEL ANGLES OR BENT PLATES (SEE TYPICAL b. OTHER SHAPES, PLATES, ANGLES, AND BARS - ASTM 572 (Fy = 50 ksi) (UNO) 360 west aspen avenue
4. SEE SPECIFICATIONS FOR REQUIRED SUBMITTALS. SUBMITTALS SHALL BE MADE IN A TIMELY MANNER 1. 28 DAY COMPRESSIVE STRENGTH : 3000 PSI DETAIL) UNLESS NOTED OTHERW ISE. c. HOLLOW STRUCTURAL SECTIONS (HSS) - ASTM A-500, GRADE C (Fy = 50 ksi)
salt lake city, utah 84101
AS INDICATED IN SPECIFICATIONS. REVIEW OF SUBMITTALS BY ARW ENGINEERS IS FOR GENERAL d. TOTAL AIR CONTENT FOR CONCRETE EXPOSED TO CYCLES OF FREEZING AND THAW ING SHALL BE 4. EVERY EFFORT SHALL BE MADE TO PROVIDE A LEVEL FINISHED FLOOR W HILE MAINTAINING THE d. STAINLESS STEEL SHAPES, PLATES, AND FASTENERS – ASTM 304
COMPLIANCE ONLY AND IS NOT INTENDED AS APPROVAL. CONTRACTOR IS RESPONSIBLE FOR DETERMINED IN ACCORDANCE W ITH THIS SCHEDULE. TOLERANCE ON AIR CONTENT AS MINIMUM INDICATED SLAB THICKNESS. e. DEFORMED BAR ANCHORS (DBA) - ASTM A-496, W ELDED IN ACCORDANCE W ITH AW S D1.1 801 532 4422
VERIFYING ALL SIZES, DIMENSIONS, AND ELEVATIONS ON SUBMITTALS AS RELATED TO DESIGN DELIVERED SHALL BE +/- 1.5 PERCENT. 5. CONTROL JOINTS IN SUSPENDED CONCRETE SLABS AND CONCRETE SLABS ON DECK SHALL NOT BE f. HEADED STUD ANCHORS (HSA) - ASTM A-108, GRADE 1015 STEEL AND W ELDED IN ACCORDANCE
DOCUMENTS. PREPARATION OF SHOP DRAW INGS FOR STRUCTURAL ELEMENTS W ILL REQUIRE NOMINAL MAXIMUM TARGET AIR CONTENT, PERCENT USED UNLESS SPECIFICALLY APPROVED AND DETAILED BY THE ENGINEER. W ITH AW S D1.1 FOR TYPE “B”. USE 3/4” DIAMETER STUDS, UNLESS NOTED OTHERW ISE.
INFORMATION (I.E. DIMENSIONS, ETC.) FOUND IN THE ARCHITECTURAL, STRUCTURAL, AND OTHER AGGREGATE SIZE, IN. F1 F2 AND F3 6. SEE TYPICAL DETAILS W HEN SLABS ARE MADE COMPOSITE W ITH STEEL BEAMS. g. THREADED ROD - ASTM A-449.
CONSULTANTS DRAW INGS. 3/8 6 7.5 7. ANY CONDUIT PLACED IN SLABS ON DECK SHALL BE SPACED NOT CLOSER THAN 18”O.C. CONDUIT h. NON-SHRINK GROUT - ASTM C110. NON-SHRINK GROUT SHALL BE PRE-PACKAGED, NON-METALLIC,
5. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE SITE. IF ACTUAL 1/2 5.5 7 LARGER THAN 3/4” DIAMETER SHALL BE PLACED IN DECK FLUTES, BUT MAY NOT BE PLACED IN FLUTES W ITH A 28-DAY COMPRESSIVE STRENGTH OF 6,000 PSI.
CONDITIONS DIFFER FROM THOSE SHOW N ON CONTRACT DOCUMENTS, CONTRACTOR SHALL NOTIFY 3/4 5 6 W ITH REINFORCING STEEL OR HSA’S. A 1” MINIMUM CLEARANCE SHALL BE MAINTAINED BETW EEN THE 3. CONNECTIONS SHALL COMPLY W ITH THE STRUCTURAL DRAW INGS UNLESS W RITTEN APPROVAL TO
ARCHITECT PRIOR TO FABRICATION OR CONSTRUCTION OF ANY AFFECTED ELEMENTS. 1 4.5 6 CONDUIT AND THE DECK. NO CONDUIT LARGER THAN 1” DIAMETER OR 1/3 THE THICKNESS OF THE CHANGE IS GIVEN BY THE STRUCTURAL ENGINEER.
6. THE CONTRACTOR SHALL COORDINATE AND VERIFY ALL LOCATIONS AND SIZES OF MECHANICAL 1-1/2 4.5 5.5 CONCRETE OVER THE DECK FLUTE SHALL BE PLACED IN SLABS ON DECK. CONDUIT CROSSOVERS ARE 4. ALL SHOP FABRICATIONS SHALL BE PERFORMED BY AN APPROVED FABRICATOR IN ACCORDANCE
EQUIPMENT OR OTHER EQUIPMENT BEFORE FABRICATING AND ERECTING STRUCTURAL ELEMENTS. 2 4 5 NOT ALLOW ED. W ITH SECTIONS 1702 AND 1704 OF THE IBC OR W ITH SHOP INSPECTION BY AN INDEPENDENT AGENCY
SIZES AND LOCATIONS THAT DIFFER FROM THOSE SHOW N ON THE CONTRACT DOCUMENTS SHALL BE 3 3.5 4.5 8. W HERE CONDUIT IS CLUSTERED TOGETHER TO RISE ABOVE SLAB OR PENETRATE SLAB, PENETRATION IN ACCORDANCE W ITH SECTION 1704.2.5 OF THE IBC.
REPORTED TO THE ARCHITECT. 2. W ATER USED IN MIXING CONCRETE SHALL CONFORM TO ASTM C1602. IN SLAB MUST BE SUPPORTED AS NOTED IN NOTE H.3 ABOVE. 5. W ELDING
7. THE CONTRACTOR SHALL SUBMIT A W RITTEN REQUEST TO THE ARCHITECT FOR ARCHITECT AND/OR 3. NO PIPES, DUCTS, SLEEVES, ETC. SHALL BE PLACED IN STRUCTURAL CONCRETE UNLESS 9. CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING, BRACING, AND GUYING AS REQUIRED a. ALL W ELDING AND CUTTING SHALL BE PERFORMED BY AW S QUALIFIED W ELDERS IN ACCORDANCE
ENGINEER APPROVAL BEFORE PROCEEDING W ITH ANY CHANGES, MODIFICATIONS, OR SPECIFICALLY DETAILED OR APPROVED BY THE STRUCTURAL ENGINEER. NO ALUMINUM PRODUCTS DURING ERECTION AND PLACEMENT OF SUSPENDED CONCRETE SLABS ON METAL DECK. W ITH ANSI/AW S D1.1 (LATEST EDITION).
SUBSTITUTIONS. SHALL BE EMBEDDED IN CONCRETE. PENETRATIONS THRU STRUCTURAL CONCRETE ELEMENTS MUST b. USE E-70XX ELECTRODES UNLESS NOTED OTHERW ISE. E-60XX MAY BE USED FOR W ELDING STEEL
8. OBSERVATION VISITS TO THE SITE BY ARW ENGINEERS FIELD REPRESENTATIVES SHALL NEITHER BE BE APPROVED BY THE ENGINEER AND SHALL BE BUILT INTO THE ELEMENT PRIOR TO CONCRETE I. REINFORCING STEEL DECKS.
CONSTRUED AS INSPECTION NOR APPROVAL OF CONSTRUCTION. PLACEMENT. c. ALL INTERSECTING STEEL SHAPES W HICH ARE NOT CONNECTED W ITH BOLTS SHALL BE W ELDED UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
TOGETHER W ITH A FILLET W ELD ALL AROUND UNLESS NOTED OTHERW ISE. W HERE W ELD SIZES DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
9. DURING AND AFTER CONSTRUCTION, BUILDER AND/OR OW NER SHALL KEEP LOADS ON STRUCTURE 4. REFER TO ARCHITECTURAL DRAW INGS FOR MOLDS, GROOVES, ORNAMENTS, ETC. TO BE CAST IN TO 1. REINFORCING BAR STRENGTH REQUIREMENTS:
NOT INTENDED FOR CONSTRUCTION, RECORDING
W ITHIN THE LIMITS OF DESIGN LOADS AS NOTED IN THESE DOCUMENTS. CONCRETE, AND FOR EXTENT AND LOCATION OF DEPRESSIONS, CURBS, RAMPS, ETC. a. ALL REINFORCING BARS (EXCEPT REINFORCING INDICATED IN NOTE B) SHALL CONFORM TO ASTM ARE NOT SHOW N, USE THE FOLLOW ING: PURPOSES, OR IMPLEMENTATION
10. TYPICAL OR SIMILAR DETAILS AND SECTIONS SHALL APPLY W HERE SPECIFIC DETAILS ARE NOT 5. UNLESS NOTED OTHERW ISE, MINIMUM REINFORCING IN ALL CONCRETE FOUNDATION W ALLS SHALL BE STANDARD A-615 GRADE 60 AND ALL W ELDED W IRE FABRIC SHALL CONFORM TO ASTM STANDARD 1. W HERE THE THICKNESS OF THE CONNECTED PARTS IS EQUAL TO OR THICKER THAN 1/4”, W ELD
SHOW N. TYPICAL OR SIMILAR DETAILS REFER TO THE CONDITION ADDRESSED AND ARE NOT AS FOLLOW S: A-1064 AND SHALL BE SUPPLIED IN FLAT SHEETS. ADEQUATELY TIE AND SUPPORT ALL SIZE SHALL BE 1/16” LESS THAN THE THICKNESS OF THE THINNEST PART.
NECESSARILY DETAILS LABELED “TYPICAL” OR “SIMILAR” IN THE PLANS AND DOCUMENTS. TOP & REINFORCING STEEL AS SPECIFIED BY ACI 117, TO MAINTAIN EXACT REQUIRED POSITION. 2. W HERE ANY OF THE CONNECTED PARTS IS LESS THAN 1/4” THICK, W ELD SIZE SHALL BE THE
11. DRAW INGS AND DETAILS HAVE BEEN PREPARED W ITH THE INTENT TO VISUALLY REPRESENT THICKNESS BOTTOM BARS VERTICAL HORIZONTAL b. ALL FRP (FIBER REINFORCED POLYMER) REINFORCING BARS SHALL CONFORM TO ASTM STANDARD SAME AS THE THICKNESS OF THE THINNEST PART.
INFORMATION PROVIDED IN SCALED FORM; HOW EVER CONTRACTOR/SUPPLIERS SHOULD NOT SCALE 8” (2) #5 #4 AT 16”O.C. #4 AT 12”O.C. D7957. d. W ELDING OF HSA’S (HEADED STUD ANCHORS) AND DBA’S (DEFORMED BAR ANCHORS) SHALL
PLANS OR DETAILS FOR DIMENSIONAL INFORMATION. 12” (2) #5 #4 AT 16”O.C. EA FACE #4 AT 16”O.C. EA FACE 2. HEADED SHEAR STUD ASSEMBLIES SHALL CONFORM TO ASTM A1044. CONFORM TO THE MANUFACTURER’S SPECIFICATIONS AND AW S D1.1 REINFORCING BARS SHALL
12. THE CONTRACTOR SHALL PROVIDE ADEQUATE TEMPORARY SHORING AND BRACING FOR ALL 6. UNLESS NOTED OTHERW ISE, CONCRETE SLABS ON EARTH SHALL BE UNREINFORCED. 3. STEEL DISCONTINUOUS FIBER REINFORCEMENT SHALL BE DEFORMED AND CONFORM TO ASTM A820 NOT BE SUBSTITUTED FOR HSA'S OR DBA'S.
STRUCTURAL ELEMENTS UNTIL THE ENTIRE STRUCTURAL SYSTEM IS COMPLETED. DESIGN OF ALL 7. UNLESS NOTED OTHERW ISE, FOR NON-DETAILED OPENINGS IN CONCRETE W ALLS LARGER THAN 12” AND SHALL HAVE A LENGTH TO DIAMETER RATIO NOT SMALLER THAN 50 AND NOT GREATER THAN 100. e. W HEREVER POSSIBLE, W ELDS SHALL BE SHOP W ELDS. SPECIAL CONSIDERATIONS, SUCH AS ITEMS
SHORING AND BRACING IS BY OTHERS AT NO ADDITIONAL COST TO THE OW NER. AND SMALLER THAN 24” IN ANY DIRECTION ADD (2) #5 BARS ON ALL SIDES IN ADDITION TO REGULAR 4. HEADED DEFORMED BARS SHALL CONFORM TO ASTM A970. OBSTRUCTIONS OR INTERRUPTIONS OF W HICH MAY NEED ADJUSTMENT AT THE SITE, REQUIRE THAT SOME W ELDS BE FIELD W ELDS.
13. ENGINEER SHALL NOT BE RESPONSIBLE FOR ACTIVITIES UNDER CONTROL OF THE CONTRACTOR SUCH W ALL REINFORCING AND EXTEND 24” EACH W AY BEYOND OPENING. IF 24” IS NOT AVAILABLE ON EVERY THE BAR DEFORMATIONS, IF ANY, SHALL NOT EXTEND MORE THAN 2 BAR DIAMETERS FROM THE W HERE QUESTIONS OR DISCREPANCIES OCCUR THE CONTRACTOR SHALL COORDINATE THE
AS CONSTRUCTION SITE SAFETY, MEANS, METHODS AND SEQUENCING OF CONSTRUCTION. ENGINEER SIDE, NOTIFY STRUCTURAL ENGINEER FOR FURTHER DIRECTION. OPENINGS SHALL HAVE A MINIMUM BEARING FACE OF THE HEAD. W ORK BETW EEN THE SHOP FABRICATOR AND THE STEEL ERECTOR.
SHALL NOT BE RESPONSIBLE FOR FABRICATION, ERECTION AND CONSTRUCTION REQUIREMENTS AS OF 12" OF CONCRETE ABOVE THE OPENING, TYP. 5. ALL REINFORCING STEEL SHALL BE TIED IN PLACE AND ADEQUATELY SUPPORTED PRIOR TO PLACING f. SPECIAL PROVISIONS FOR SFRS (SEISMIC FORCE RESISTING SYSTEM):
PRESCRIBED BY OSHA OR OTHER REGULATORY AGENCIES REGARDLESS OF INDICATIONS IN THESE 8. CONSTRUCTION JOINTS NOT SHOW N ON THE PLANS SHALL BE MADE AND LOCATED SO AS TO NOT CONCRETE. W ET STABBING OF ANY REINFORCING STEEL IS NOT PERMITTED, UNLESS SPECIFICALLY 1. ALL W ELDS DESIGNATED AS DEMAND CRITICAL W ELDS SHALL BE MADE W ITH FILLER METALS
DOCUMENTS. IMPAIR THE STRENGTH OF THE STRUCTURE AND AS APPROVED BY THE STRUCTURAL ENGINEER. DETAILED OTHERW ISE OR APPROVED BY THE ENGINEER. MEETING THE REQUIREMENTS SPECIFIED IN CLAUSES 6.1, 6.2, AND 6.3 OF AW S D1.8.
14. NOTICE OF COPYRIGHT: THESE STRUCTURAL DRAW INGS ARE HEREBY COPYRIGHTED BY ARW PROVIDE 2 X 4 (SHAPED) KEYW AY IN ALL VERTICAL AND HORIZONTAL JOINTS UNLESS NOTED OR 6. ALL FIELD BENT DOW ELS SHALL BE GRADE 40 W ITH SPACING INDICATED REDUCED BY 1/3. 2. ALL OTHER W ELDS THAT ARE PART OF THE SFRS SHALL BE MADE W ITH FILLER METALS
D ENGINEERS, ALL RIGHTS RESERVED. THESE DOCUMENTS DEFINE A STRUCTURE AND ARE DETAILED OTHERW ISE. ALL STEEL REINFORCING SHALL BE CONTINUOUS THROUGH COLD JOINTS 7. UNLESS NOTED OTHERW ISE, REINFORCEMENT SHALL HAVE THE FOLLOW ING CONCRETE COVERAGE : MEETING THE REQUIREMENTS SPECIFIED IN CLAUSE 6.1 OF AW S D1.8. D
INSTRUMENTS OF SERVICE, FOR ONE USE ONLY. REPRODUCTION AND DISTRIBUTION OF THESE UNLESS NOTED OTHERW ISE. SEE TYPICAL DETAILS FOR COLD/CONSTRUCTION JOINTS FOR SLABS ON a. CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ….. 3” 3. BUTT W ELDS IN MEMBERS W ITH DIFFERENT THICKNESSES, SUCH AS COLUMN SPLICES, SHALL
DRAW INGS IS ONLY ALLOW ED AS REQUIRED FOR REGULATORY AGENCIES AND FOR CONVEYANCE OF GRADE. b. EXPOSED TO EARTH OR W EATHER : BE TAPERED AND MADE IN SUCH A MANNER THAT THE TRANSITION DOES NOT EXCEED 1 IN
INFORMATION TO PARTIES INVOLVED IN THE CONSTRUCTION OF THIS PROJECT. THESE DOCUMENTS 9. W HERE NEW CONCRETE IS PLACED AGAINST PREVIOUSLY HARDENED CONCRETE, THE JOINT SHALL 1. #6 & LARGER ….. 2” 2-1/2 INCHES. THE TRANSITION SHALL BE ACCOMPLISHED BY CHAMFERING THE THICKER PART,
SHALL NOT BE REPRODUCED OR COPIED, IN PART OR W HOLE BY ANY PARTY FOR USE IN BE CLEAN AND FREE OF LAITANCE. IMMEDIATELY BEFORE NEW CONCRETE IS PLACED, CONSTRUCTION 2. #5 & SMALLER …..1-1/2” TAPERING THE W IDER PART, SLOPING THE W ELD METAL OR BY A COMBINATION OF THESE
PREPARATION OF SHOP DRAW INGS OR OTHER SUBMITTALS. JOINTS SHALL BE PREW ETTED AND STANDING W ATER REMOVED. c. NOT EXPOSED TO W EATHER OR EARTH : 6. BOLTING
15. W HERE THE W ORD "SHALL" OCCURS IN THESE DRAW INGS AND ANY ACCOMPANYING SPECIFICATIONS, 1. SLABS, W ALLS, JOISTS, #11 & SMALLER ….. 3/4” a. UNLESS NOTED OTHERW ISE, ALL STRUCTURAL STEEL TO STEEL CONNECTIONS SHALL USE HIGH
IT IS CONSIDERED A MANDATORY OBLIGATION AND SYNONYMOUS W ITH THE PHRASE "HAS DUTY TO". F. ANCHOR BOLTS/EMBEDDED BOLTS 2. BEAMS, COLUMNS: MAIN REINFORCING OR TIES ….. 1-1/2” STRENGTH BOLTS CONFORMING TO ASTM F3125 GR. A325.
d. SLAB ON GRADE : b. UNLESS NOTED OTHERW ISE, ALL BOLTING IS CLASSIFIED AS NON-SLIP CRITICAL BEARING TYPE
B. STATEMENT OF SPECIAL INSPECTIONS AND SPECIAL INSPECTIONS 1. ALL ANCHOR BOLTS SHALL HAVE ASTM A-563 HEAVY HEX NUT AND ASTM F-436 W ASHERS AT 1. PLACE REINFORCING AT CENTER OF SLAB UNLESS INDICATED OTHERW ISE. CONNECTIONS W ITH THREADS INCLUDED IN SHEAR PLANE. TIGHTEN BOLTS TO A SNUG TIGHT
STANDARD OR OVERSIZED HOLES PER AISC SPECIFICATION TABLE J3.3. W HERE HOLE SIZES DO NOT 8. EXCEPT W HERE NOTED ON PLANS OR DETAILS CONTINUOUS REINFORCEMENT SHALL BE SPLICED AT CONDITION, W ITH ALL PLIES OF THE JOINT IN FIRM CONTACT.
1. THE DESIGNATED SEISMIC/W IND SYSTEMS AND SEISMIC/W IND-FORCE-RESISTING SYSTEMS THAT ARE COMPLY W ITH THE LIMITATIONS FOR OVERSIZED HOLES THE STRUCTURAL ENGINEER SHALL BE POINTS OF MINIMUM STRESS BY LAPPING PER THE REBAR LAP SCHEDULE. c. W HERE OVERSIZED OR SLOTTED HOLES OCCUR IN THE OUTER PLY, AN ASTM F436 W ASHER OR
SUBJECT TO SPECIAL INSPECTIONS IN ACCORDANCE W ITH IBC SECTION 1705.11 AND 1705.12 ARE NOTIFIED TO DETERMINE STEEL PLATE W ASHER REQUIREMENTS. ANCHOR BOLTS SHALL COMPLY 9. REINFORCING STEEL MAY BE SPLICED W ITH MECHANICAL COUPLERS THAT HAVE A TENSION CAPACITY 5/16” THICK COMMON PLATE W ASHER SHALL BE USED AS REQUIRED TO COMPLETELY COVER THE
IDENTIFIED ON THESE DOCUMENTS W ITH A CIRCLE “L”. ALL OTHER ITEMS REQUIRING SPECIAL W ITH THE FOLLOW ING : OF AT LEAST 125% OF THE STRENGTH OF THE BAR. MECHANICAL COUPLERS SHALL BE A POSITIVE HOLE.
INSPECTION ARE IDENTIFIED IN THE SPECIAL INSPECTION SCHEDULE ON SHEETS S010 AND S012. a. AT ALL ANCHOR BOLTS (UNLESS NOTED OTHERW ISE) - ASTM F1554 GRADE 36 HEADED BOLTS. CONNECTING TYPE COUPLER, AND SHALL BE INSTALLED IN ACCORDANCE W ITH AN APPROVED ICC d. BOLTS SHALL BE CENTERED IN SLOTTED HOLES, UNLESS NOTED OTHERW ISE.
2. SPECIAL INSPECTIONS AND TESTING ARE TO BE PROVIDED AS REQUIRED BY IBC SECTIONS 1704 (ASTM A36 THREADED ROD MAY BE USED W ITH DOUBLE NUT AND W ASHER.) RESEARCH REPORT. W HERE THESE ARE USED, SPLICES ON ADJACENT BARS SHALL BE STAGGERED e. W HERE A STEEL BEAM TO BEAM CONNECTION IS NOT SHOW N, PROVIDE AN AISC STANDARD
THROUGH 1705 AND OTHER APPLICABLE SECTIONS OF THE IBC. THE TYPE AND FREQUENCY OF 2. EMBEDDED BOLTS IN MASONRY SHALL BE (UNLESS NOTED OTHERW ISE) ASTM A-307 GRADE HEADED AT LEAST 24 INCHES ALONG THE LENGTH OF THE BARS. FRAMED CONNECTION SIZED FOR 1/2 OF THE TOTAL LOAD CAPACITY OF THE BEAM FOR THE SPAN
TESTING AND SPECIAL INSPECTIONS SHALL BE AS NOTED IN THE SPECIAL INSPECTION SCHEDULE, JOB BOLTS. 10. ALL VERTICAL REINFORCING IN STRUCTURAL ELEMENTS ABOVE SHALL BE SPLICED W ITH MATCHING AND STEEL SPECIFIED.
SPECIFICATIONS, AND ACCORDANCE W ITH IBC SECTION 110 AND CHAPTER 17. CONTRACTOR SHALL 3. SEE TYPICAL ANCHOR BOLT DETAIL FOR DEFINITIONS OF EMBEDMENT LENGTH, ETC. DOW ELS EMBEDDED W ITHIN THE FOOTINGS OR STRUCTURE BELOW . SPLICE LENGTHS SHALL COMPLY 7. METAL DECKING
COORDINATE AND COOPERATE W ITH REQUIRED INSPECTIONS. 4. FURNISH TEMPLATES AND OTHER DEVICES AS NECESSARY FOR PRESETTING ALL BOLTS PRIOR TO W ITH REBAR LAP SCHEDULE. DOW ELS INTO FOOTINGS SHALL TERMINATE W ITH A STANDARD HOOK, a. UNLESS NOTED OTHERW ISE, METAL ROOF DECK SHALL BE 22 GAUGE TYPE "B". STEEL DECK. SEE
3. ALL TESTING AND SPECIAL INSPECTION SHALL BE PROVIDED BY A QUALIFIED INDEPENDENT SPECIAL PLACING CONCRETE AND/OR GROUT. AND SHALL EXTEND TO W ITHIN 4” OF THE BOTTOM OF THE FOOTING, BUT NEED NOT EXTEND MORE ROOF DECK SCHEDULE FOR ATTACHMENTS.
INSPECTION AGENCY IN ACCORDANCE W ITH IBC 1704 AND AS OUTLINED IN THE JOB SPECIFICATIONS. 5. IF THREADED RODS ARE USED AS PERMITTED ABOVE, THEY SHALL BE CLEAR OF SOIL AND DIRT. THAN 20” INTO FOOTING. FOR MASONRY CONSTRUCTION SEE STRUCTURAL NOTE N.6.A. b. UNLESS NOTED OTHERW ISE, METAL FLOOR DECK SHALL BE 20 GAUGE TYPE "W 2" COMPOSITE,
REPORTS OF FINDINGS OR DISCREPANCIES SHALL BE NOTED AND FORW ARDED TO THE CONTRACTOR, 6. W HERE REQUIRED FOR ERECTION, HOLES LARGER THAN OVERSIZED MAY BE PERMITTED W ITH THE 11. DO NOT W ELD REINFORCING EXCEPT AS NOTED ON PLANS, W HERE REINFORCING IS W ELDED, USE UNVENTED STEEL DECK. UNLESS NOTED OTHERW ISE, ATTACH TO SUPPORTING STRUCTURE W ITH
ARCHITECT, ENGINEERS, AND BUILDING OFFICIAL IN A TIMELY MANNER. USE OF STEEL PLATE W ASHERS AT THE DISCRETION OF THE STRUCTURAL ENGINEER. ASTM A-706 REINFORCING. 3/4” DIAMETER W ELDS AT 12" MAXIMUM SPACING. ATTACH SIDE SEAMS W ITH BUTTON PUNCH OR
4. STRUCTURAL OBSERVATION VISITS SHALL BE PERFORMED BY A REPRESENTATIVE FROM ARW 12. REINFORCING BARS, TIES, AND TENDONS SHALL BE SUPPORTED BY NYLON CONES, PLASTIC-COATED SIDE SEAM SCREW S AT 24" MAXIMUM SPACING. AN HSA FIELD-W ELDED THROUGH THE DECK MAY
ENGINEERS IN ACCORDANCE W ITH THE CONTRACT AS NEEDED TO OBSERVE THE CONSTRUCTION OF G. ADHESIVE/MECHANICAL ANCHORS TIE-W IRES, OR PLASTIC-COATED CHAIRS. REINFORCING IN FOOTINGS IS PERMITTED TO BE SUPPORTED SUBSTITUTE FOR A PUDDLE W ELD.
CRITICAL BUILDING ELEMENTS (I.E. FOOTINGS, BRACED FRAMES, MOMENT FRAMES, DRAG STRUTS AND ON CONCRETE DOBIES. c. ALL DECK SHALL BE CONTINUOUS OVER 3-SPANS. W HERE NOT POSSIBLE, THE DECK
THEIR CONNECTIONS, COLLECTORS, AND ROOF AND FLOOR DIAPHRAGMS). STRUCTURAL 1. W ITHOUT W RITTEN APPROVAL OF THE ENGINEER, CONTRACTOR SHALL NOT SUBSTITUTE POST- 13. UNLESS NOTED OTHERW ISE, HOOKS, STIRRUPS, TIES, AND OTHER BENDS IN REINFORCING STEEL SUPPLIER/CONTRACTOR SHALL PROVIDE HEAVIER GAUGE DECK AS NEEDED TO PROVIDE THE
OBSERVATION REPORTS FOR EACH VISIT SHALL BE SENT DIRECTLY TO THE ARCHITECT FOR INSTALLED ANCHORS W HERE CAST-IN-PLACE ANCHORS ARE SPECIFIED IN THE DRAW INGS. SHALL MEET THE STANDARDS SET FORTH IN ACI 318/318R-14. UNLESS OTHERW ISE PERMITTED BY THE EQUIVALENT PERFORMANCE OF THE SPECIFIED DECK W ITH 3-SPAN CONTINUITY.
DISTRIBUTION TO THE CONTRACTOR AND BUILDING OFFICIAL. STRUCTURAL OBSERVATION VISITS 2. W HERE STRUCTURAL DETAILS SPECIFY SPECIFIC BRANDS AND/OR TYPES OF ADHESIVES OR ENGINEER, ALL REINFORCEMENT SHALL BE BENT COLD. REINFORCEMENT PARTIALLY EMBEDDED IN d. SEE TYPICAL DETAILS FOR SUPPORT OF DECK AT OPENINGS.
SHALL NEITHER BE CONSTRUED AS SPECIAL INSPECTION NOR APPROVAL OF COMPLETED ANCHORS, SUBSTITUTIONS OF OTHER BRANDS AND/OR TYPES IS NOT ALLOW ED, W ITHOUT W RITTEN CONCRETE SHALL NOT BE FIELD BENT, EXCEPT AS SHOW N ON THESE DRAW INGS OR OTHERW ISE e. PROVIDE L2”x2”x3/16” FOR DECK SUPPORT AT LOCATIONS W HERE COLUMNS EXTEND THROUGH
CONSTRUCTION. APPROVAL OF THE ENGINEER. PERMITTED BY THE ENGINEER. DECK.
5. IN ACCORDANCE W ITH IBC 1704.4, THE CONTRACTOR SHALL SUBMIT A W RITTEN CONTRACTOR’S 3. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS SHALL BE APPROVED IN W RITING BY THE 14. UNLESS SPECIFICALLY NOTED AND/OR DETAILED IN THE STRUCTURAL DRAW INGS CONDUIT SHALL NOT f. PAINTED STEEL DECK SHALL CONFORM TO EITHER ASTM A1008 OR A1039, GRADE 50 STEEL AND THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND OW NER. THE STATEMENT SHALL BE BE IN CONTACT W ITH REINFORCING STEEL. GALVANIZED STEEL DECK SHALL CONFORM TO EITHER ASTM A653 OR A1063, GRADE 50 STEEL, ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. SUBSTITUTION REQUESTS SHALL INCLUDE AN
W ITH A ZINC COATING DESIGNATION OR G60. MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
SUBMITTED PRIOR TO THE CONSTRUCTION OF ANY SEISMIC/W IND-FORCE-RESISTING SYSTEM, ICC ESR OR IAPMO REPORT AND SUPPORTING CALCULATIONS INDICATING COMPLIANCE W ITH DESIGN
g. BUILDING ELEMENTS MAY BE SUPPORTED BY HANGING DIRECTLY FROM METAL DECKING, COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
DESIGNATED SEISMIC/W IND SYSTEM, OR COMPONENT IDENTIFIED IN THESE DOCUMENTS W ITH A INTENT. WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
CIRCLE “L”. 4. ALL ADHESIVE/MECHANICAL ANCHORS SHALL BE INSTALLED, INCLUDING HOLE DRILLING AND PROVIDED THAT THE TOTAL W EIGHT PER CONNECTION IS LESS THAN 50 LBS AND THAT THE WRITTEN PERMISSION FROM METHOD STUDIO INC.
PREPARATION, IN ACCORDANCE W ITH AN APPROVED INDEPENDENT EVALUATION REPORT (ICC-ES, ATTACHMENT TO THE DECKING IS DISTRIBUTED ACROSS AT LEAST TW O RIBS AND SPACED AT
C C. BASIS OF DESIGN IAPMO, OR APPROVED EQUAL), AS INDICATED BELOW , AND IN ACCORDANCE W ITH ALL LEAST 6 FEET APART IN ANY DIRECTION. C
1. GOVERNING BUILDING CODE : INTERNATIONAL BUILDING CODE (IBC) 2018 5.
MANUFACTURER’S PRINTED INSTALLATION INSTRUCTIONS (MPII).
INSTALLERS SHALL BE, AT A MINIMUM, TRAINED FOR THE SPECIFIC APPLICATION INSTALLATION
8. ALL COLUMNS EMBEDDED IN OR LOCATED AT THE END OF MASONRY W ALLS SHALL HAVE (2) 1/2”
DIAMETER X 24” LONG DBA EXTENDING EACH W AY AT ALL W ALL BOND BEAMS.
project:
RISK CATEGORY : II TECHNIQUE FOR THE SPECIFIC PRODUCT BY THE PRODUCT MANUFACTURERS FIELD EMPLOYEE OR 9. PROVIDE FULL DEPTH W EB STIFFENER PLATES AT EACH SIDE OF STEEL BEAMS AT ALL BEARING
(EXCEPT SECONDARY FRAMING) POINTS. STIFFENER PLATES SHALL BE THICKNESS SHOW N UNLESS
2. SUSPENDED FLOOR LOADS
a. LIVE LOAD = 80 PSF UNREDUCED (125 PSF AT STORAGE)
b. DEAD LOAD = 70 PSF
6.
SHALL POSSESS A TRAINING CARD OBTAINED BY THE MANUFACTURERS ONLINE TRAINING PROGRAM.
ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT TIME
OF ANCHOR INSTALLATION. ADHESIVE ANCHORS SHALL NOT BE FULLY LOADED UNTIL CONCRETE HAS
NOTED OTHERW ISE AND SHALL BE W ELDED BOTH SIDES W ITH FILLET W ELDS ALL AROUND.
FLANGE W IDTH
< 8 1/4”
STIFFENER THICKNESS
1/4”
W ELD THICKNESS
3/16”
USU EVR
3. ROOF LOADS REACHED DESIGN STRENGTH.
a. FLAT-ROOF SNOW LOAD, P f : 31 PSF
1. GROUND SNOW LOAD, P g : 44 PSF
2. SNOW EXPOSURE FACTOR, C e : 1.0
7.

8.
ADHESIVE ANCHORS SHALL CONSIST OF REINFORCING BAR OR THREADED RODS AS INDICATED IN
THESE DOCUMENTS.
UNLESS APPROVED BY THE ENGINEER OF RECORD, CONCRETE AND DRILLED ANCHOR HOLES SHALL 10.
8 1/4” < BF < 12 1/2”
12 1/2” < BF < 18”
3/8”
1/2”
1/4”
5/16”
FABRICATORS AND SUPPLIERS SHALL COORDINATE PAINT/FINISHES W ITH REQUIREMENTS FOR DIRECT
EXPANSION
3. SNOW LOAD IMPORTANCE FACTOR, Is : 1.0 BE DRY AND FREE OF W ATER FOR 14 DAYS PRIOR TO ADHESIVE INSTALLATION. CONTACT THE APPLIED INSULATION, FIREPROOFING, ETC. AS NOTED IN THE PROJECT SPECIFICATIONS.
4. THERMAL FACTOR, C t : 1.0 ENGINEER OF RECORD FOR GUIDANCE IF THE CONTRACTOR CHOOSES TO INSTALL IN DAMP, W ATER- 11. W HEN DETERMINING THE FIRE RESISTANCE OF ASSEMBLIES, USE THE FOLLOW ING: STEEL ROOF
5. SLOPE FACTOR, C S : 1.0 SATURATED, OR W ATER-FILLED HOLES. MEMBERS ARE CONSIDERED UN-RESTRAINED AND STEEL FLOOR FRAMING MEMBERS ARE
6. SNOW DRIFT : SHOW N ON PLANS W HERE APPLICABLE. 9. CONCRETE TEMPERATURE AT THE TIME OF INSTALLATION SHALL BE MONITORED BY THE CONSIDERED RESTRAINED.
b. LIVE LOAD = 20 PSF CONTRACTOR. CONTRACTOR SHALL COMPLY W ITH ALL MANUFACTURER'S PRINTED INSTALLATION 12. UNLESS NOTED OTHERW ISE, ALL HORIZONTAL FRAMING MEMBERS SHALL BE ERECTED W ITH THE
c. DEAD LOAD = 20 PSF INSTRUCTIONS (MPII) RELATIVE TO SUBSTRATE TEMPERATURE. NATURAL CROW N UP.
d. SPECIAL LOADS, IE. PHOTOVOLTAIC PANEL SYSTEMS, ETC. = 5 PSF 10. INSTALLATION OF ADHESIVE ANCHORS HORIZONTALLY OR UPW ARDLY INCLINED TO SUPPORT 13. UNLESS OTHERW ISE SHOW N OR DETAILED IN THE PLANS, ALL STEEL COLUMNS, BEAMS, BRACES,
4. W IND DESIGN SUSTAINED TENSION LOADS SHALL BE PERFORMED BY PERSONNEL CERTIFIED BY AN APPLICABLE STRUTS, ETC. SHALL BE CONTINUOUS BETW EEN CONNECTIONS OR SUPPORTS. SPLICES IN MEMBERS
a. BASIC W IND SPEED (3 SECOND GUST) : 103 MPH CERTIFICATION PROGRAM. CERTIFICATION SHALL INCLUDE W RITTEN AND PERFORMANCE TESTS IN SHALL NOT BE PERMITTED W ITHOUT W RITTEN APPROVAL BY THE ENGINEER OF RECORD.
b. W IND EXPOSURE : C ACCORDANCE W ITH THE ACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION PROGRAM, OR
c. INTERNAL PRESSURE COEFFICIENT, G CPI : 0.18 EQUIVALENT IN ACCORDANCE W ITH ACI 318-11 D.9.2.2. PROOF OF CURRENT CERTIFICATION SHALL BE
d. COMPONENT AND CLADDING DESIGN W IND PRESSURE SHALL BE AS REQUIRED PER ASCE 7-16. SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO INSTALLATION. CONTINUOUS SPECIAL
5. SEISMIC DESIGN : INSPECTION SHALL BE PROVIDED FOR THESE ANCHORS.
a. SEISMIC IMPORTANCE FACTOR, IE : 1.0 11. UNLESS NOTED OTHERW ISE, ALL ADHESIVE ANCHORS INTO CONCRETE SHALL BE:
b. SITE CLASS : D-DEFAULT a. HILTI HIT-RE 500V3 (ESR-3814), OR HILTI HIT-HY 200-A (ESR-3187).
c. MAPPED SPECTRAL RESPONSE ACCELERATIONS : S S = 1.042 , S 1 = 0.347 b. SIMPSON SET-3G (ESR-4057), OR AT-XP (ER-0263).
d. SPECTRAL RESPONSE COEFFICIENTS : S DS = 0.834 , S D1 = .452 c. DEW ALT PURE 110+ (ESR-3298), OR AC200+ GOLD (ESR-4027-COLD W EATHER). 670 EAST 1550 NORTH, LOGAN, UT
e. SEISMIC DESIGN CATEGORY : D 12. UNLESS NOTED OTHERW ISE, ALL ADHESIVE ANCHORS INTO GROUTED MASONRY (CMU) SHALL BE:
f. BASIC SEISMIC-FORCE-RESISTING SYSTEM : SPECIAL REINFORCED MASONRY SHEAR W ALLS
84341
a. HILTI HIT-HY 270 (ESR-4143).
g. DESIGN BASE SHEAR : V = 283 K b. SIMPSON SET-XP (ER-0265), OR AT-XP (ER-0281).
h. SEISMIC RESPONSE COEFFICIENT, C S : .167 c. DEW ALT AC100+ GOLD (ESR-3200).
i. RESPONSE MODIFICATION FACTOR, R : 5 13. UNLESS NOTED OTHER W ISE, ALL MECHANICAL ANCHORS INTO CONCRETE SHALL BE:
j. ANALYSIS PROCEDURE : EQUIVALENT LATERAL FORCE a. HILTI KW IK BOLT-TZ2 (ESR-4266).
b. SIMPSON STRONG-BOLT 2 (ESR-3037).
D. FOUNDATION 14. UNLESS NOTED OTHERW ISE, ALL MECHANICAL ANCHORS INTO GROUTED MASONRY (CMU) SHALL BE:
a. HILTI KW IK BOLT-TZ2 (ESR-4561).
B 1. GENERAL b. SIMPSON STRONG BOLT 2 W EDGE ANCHOR (ER-0240). B
a. DESIGN SOIL PRESSURE : 2500 PSF c. DEW ALT SCREW BOLT+ (ESR-4042). p r o j e c t # : 21.0320
b. SOILS REPORT BY : GSH 15. UNLESS NOTED OTHERW ISE, ALL SCREW ANCHORS INTO CONCRETE SHALL BE:
REPORT # : 1964-005-21 a. SIMPSON TITEN HD (ESR-2713). d a t e : 02.14.2023
DATED : NOVEMBER 29,2021 b. DEW ALT SCREW BOLT+ (ESR-3889).
c. SOIL PREPARATION UNDER FOUNDATIONS AND SLABS-ON-GRADE SHALL BE IN ACCORDANCE W ITH c. HILTI KW IK HUS-EZ (ESR-3027). revisions :
THE SOILS REPORT. 16. UNLESS NOTED OTHERW ISE, ALL SCREW ANCHORS INTO GROUTED MASONRY (CMU) SHALL BE:
d. TOP OF FOOTING ELEVATIONS SHOW N ON THE FOOTING AND FOUNDATION PLAN ARE BASED ON a. SIMPSON TITEN HD (ESR-1056).
PRELIMINARY GRADING INFORMATION AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION. STEPS b. DEW ALT SCREW BOLT+ (ESR-1678).
W HERE SHOW N ARE AT APPROXIMATE LOCATIONS. ACTUAL STEP LOCATIONS SHALL BE AT THE c. HILTI KW IK HUS EZ (ESR-3056).
CONTRACTOR’S DISCRETION BASED UPON FIELD CONDITIONS. ALL EXTERIOR FOUNDATIONS SHALL 17. ALL MASONRY CELLS W ITHIN 8” OF THE ANCHOR SHALL BE SOLID GROUTED.
BEAR A MINIMUM OF 30 INCHES BELOW LOW EST ADJACENT FINAL GRADE. 18. THE TESTING LABORATORY W ILL PERFORM VISUAL INSPECTION OF ANCHORS AND DOW ELS AS
e. ALL W ALLS (EXCEPT CANTILEVERED RETAINING W ALLS) SHALL BE ADEQUATELY BRACED AGAINST SPECIFIED IN THE SPECIAL INSPECTION SCHEDULE AND THE APPROVED INDEPENDENT EVALUATION
LATERAL MOVEMENT PRIOR TO BACKFILLING. DESIGN AND ERECTION OF BRACING/SHORING SHALL REPORT. TENSION TESTING CAN BE REQUIRED AT THE DIRECTION OF THE STRUCTURAL ENGINEER OF
BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. BRACING SHALL REMAIN IN PLACE UNTIL RECORD OR THE SPECIAL INSPECTOR.
SUPPORTING STRUCTURAL ELEMENTS ARE IN PLACE AND HAVE ATTAINED FULL STRENGTH. 19. IF REINFORCEMENT IS ENCOUNTERED DURING DRILLING, ABANDON THAT HOLE AND SHIFT THE
f. UNLESS NOTED OTHERW ISE, ALL FOOTINGS AT COLUMNS SHALL BE CENTERED BELOW COLUMNS. ANCHOR LOCATION TO AVOID THE REINFORCEMENT. PROVIDE A MINIMUM SPACE OF (2) ANCHOR HOLE
g. UNLESS NOTED OTHERW ISE, ALL FOOTINGS SHALL HAVE VERTICAL FACES FORMED W ITH DIAMETERS OR 2 INCHES, W HICH EVER IS LARGER, OF SOUND CONCRETE/MASONRY BETW EEN THE
STANDARD FORMING MATERIALS (W OOD, METAL, ETC.). W ITH PRIOR APPROVAL OF ARCHITECT AND ANCHOR AND THE ABANDONED HOLE. FILL THE ABANDONED HOLE W ITH NON-SHRINK GROUT OR AN
ENGINEER, CONCRETE FOR FOOTINGS CAN BE PLACED IN EXCAVATED SOIL “FORMS” PROVIDED APPROVED ANCHORING ADHESIVE. AT CONTRACTORS OPTION, LOCATE EXISTING REINFORCEMENT
THAT THE DIMENSIONS ARE INCREASED 3” ON ALL SIDE. PRIOR TO DRILLING/CORING. IF THE ANCHOR OR DOW EL CANNOT BE SHIFTED AS NOTED ABOVE, THE

20.
ENGINEER W ILL DETERMINE A NEW LOCATION.
LOCATE REINFORCEMENT AND CONFIRM FINAL ANCHOR LOCATIONS PRIOR TO FABRICATING PLATES,
title:
MEMBERS, OR OTHER STEEL ASSEMBLIES ATTACHED W ITH MECHANICAL ANCHORS.

STRUCTURAL
NOTES
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

Structural Sheet Index


SHEET
NUMBER SHEET NAME
S001 STRUCTURAL NOTES
S002 STRUCTURAL NOTES
A S010 SCHEDULES A
S011 SCHEDULES
S012 SCHEDULES
S101 FOOTING AND FOUNDATION PLAN
S102 SECOND FLOOR FRAMING PLAN
S103 ROOF FRAMING PLAN
S110 STAIR FRAMING PLANS sheet:
S201 TYPICAL DETAILS
S202 TYPICAL DETAILS

S001
S210 FOUNDATION DETAILS
S220 FLOOR FRAMING DETAILS
S230 ROOF FRAMING DETAILS
S301 ELEVATIONS
S401 SCHEMATIC REFERENCE

BID SET
1 2 3 4 5 6
1 2 3 4 5 6

M. OPEN WEB JOISTS AND GIRDERS S. STRUCTURAL DELEGATED DESIGNS AND DEFERRED SUBMITTALS

1. ALL OPEN W EB STEEL JOISTS AND GIRDERS SHALL BE FABRICATED AND ERECTED IN ACCORDANCE 1. STRUCTURAL DELEGATED DESIGNS AND SUBSEQUENT DEFERRED SUBMITTALS ARE FOR ELEMENTS,
W ITH THE LATEST EDITION OF “STANDARD SPECIFICATIONS AND CODE OF STANDARD PRACTICE” OF PARTS, OR PORTIONS OF THE OVERALL STRUCTURAL SYSTEM THAT ARE INDICATED OR REFERRED TO
THE STEEL JOIST INSTITUTE. ON THESE DRAW INGS AND THAT ARE CRITICAL TO THE PERFORMANCE OF THE OVERALL STRUCTURAL
2. (###/###) DENOTES APPLIED TOTAL AND LIVE UNIFORMLY DISTRIBUTED LOADS IN POUNDS PER LINEAR SYSTEM. DESIGN CRITERIA HAS BEEN PROVIDED FOR THESE ITEMS IN THE STRUCTURAL NOTES,
FOOT OF JOIST, RESPECTIVELY. PLANS, AND DETAILS.
3. SEE JOIST LOAD PROFILES FOR SPECIALLY LOADED JOISTS. 2. STRUCTURAL DEFERRED SUBMITTALS ARE COMPLETE PACKAGES TO BE SUBMITTED FOR REVIEW
4. CONCENTRATED POINT LOADS, NOT SPECIFICALLY SHOW N ON THE PLANS, OF LESS THAN 100 POUNDS THAT INCLUDE DRAW INGS AND CALCULATIONS FOR ALL DELEGATED DESIGN ITEMS AND THEIR
FOR MECHANICAL UNITS, FIRE SPRINKLER MAINS, AND OTHER EQUIPMENT SHALL BE ALLOW ED CONNECTIONS. DEFERRED SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF THE DESIGN
W ITHOUT REQUIRING ADDITIONAL W EB MEMBERS TO BE INSTALLED. W HERE THE LOAD EXCEEDS 100 PROFESSIONAL RESPONSIBLE FOR THEIR DESIGN.
POUNDS, THE LOAD SHALL BE SUPPORTED W ITHIN 6" OF A CHORD PANEL POINT. SUPPORT BEYOND 6" 3. ARW ENGINEERS W ILL REVIEW STRUCTURAL DEFERRED SUBMITTALS TO VERIFY DESIGN CRITERIA IS
FROM PANEL POINTS CAN BE PROVIDED BY ADDING (2) L2 x 2 x 1/4 DIAGONALS TO THE NEAREST COMPLIANT W ITH THE APPROVED CONSTRUCTION DOCUMENTS.
OPPOSITE CHORD PANEL POINT PER THE TYPICAL DETAIL. CONNECTIONS SHALL BE MADE 4. STRUCTURAL DELEGATED DESIGN COMPONENTS SHALL NOT BE INSTALLED UNTIL APPROVED BY THE
CONCENTRIC TO THE CHORD ANGLES. BEAM CLAMPS, OR SIMILAR ECCENTRIC ATTACHMENTS, ARE BUILDING OFFICIAL.
E NOT ALLOW ED, EXCEPT AS INDICATED BELOW . LOADS SHALL BE SPACED AT LEAST 6 FEET APART 5. STRUCTURAL DELEGATED DESIGN ITEMS REQUIRING DEFERRED SUBMITTALS INCLUDE, BUT ARE NOT E
W ITH NO MORE THAN 4 PER JOIST. BEAM CLAMPS, OR SIMILAR ATTACHMENTS THAT ARE NOT LIMITED TO : 360 west aspen avenue
CENTERED ON THE CHORD ANGLES MAY ONLY BE USED FOR LOADS LESS THAN 10 POUNDS. SEE a. OPEN W EB JOISTS & GIRDERS, BRIDGING, BRACING, CONNECTIONS, AND RELATED COMPONENTS. salt lake city, utah 84101
JOIST SUBMITTAL FOR ADDITIONAL REQUIREMENTS. ALL LOADS PROVIDED FOR IN THIS NOTE SHALL
BE ACCOUNTED FOR IN THE SPECIFIED DESIGN LOADS. A. NON-STRUCTURAL DELEGATED DESIGNS AND DEFERRED SUBMITTALS
801 532 4422
5. ANY BRACING REQUIRED FOR MISCELLANEOUS ITEMS (I.E. DUCTW ORK, PIPING, ETC.) MUST CONNECT
TO THE TOP CHORD OF THE JOIST OR GIRDER. BRACING TO THE BOTTOM CHORD IS NOT ALLOW ED 1. NON-STRUCTURAL DELEGATED DESIGNS AND SUBSEQUENT DEFERRED SUBMITTALS ARE FOR ITEMS
UNLESS SPECIFICALLY DETAILED THAT W AY ON THE PLANS. NOT INCLUDED IN THE STRUCTURAL DELEGATED DESIGN SECTION. THESE ARE ITEMS THAT ARE NOT
6. PROVIDE SPECIAL BEARING ENDS AS REQUIRED AT SLOPED BEARING CONDITIONS. CONTRACTOR CRITICAL TO THE OVERALL PERFORMANCE OF THE STRUCTURAL SYSTEM BUT THAT IMPART LOADS
SHALL COORDINATE W ITH OTHER STRUCTURAL ELEMENTS. AND FORCES TO THE STRUCTURAL SYSTEM.
7. ALL JOISTS SHALL BE CAMBERED PER SJI SPECIFICATIONS, UNLESS NOTED OTHERW ISE. 2. NON-STRUCTURAL DEFERRED SUBMITTALS SHALL BEAR THE STAMP AND SIGNATURE OF THE DESIGN
8. FIELD MODIFICATIONS (INCLUDING HOLES IN THE CHORD OR W EB MEMBERS) SHALL NOT BE MADE TO PROFESSIONAL RESPONSIBLE FOR THE DESIGN.
ANY JOIST OR GIRDER W ITHOUT PRIOR APPROVAL BY THE MANUFACTURER. 3. ARW ENGINEERS W ILL REVIEW NON-STRUCTURAL DEFERRED SUBMITTALS TO VERIFY DESIGN
9. FABRICATORS AND SUPPLIERS SHALL COORDINATE PAINT/FINISHES W ITH REQUIREMENTS FOR DIRECT CRITERIA IS COMPLIANT W ITH THE APPROVED CONSTRUCTION DOCUMENTS.
APPLIED INSULATION, FIREPROOFING, ETC. AS NOTED IN THE PROJECT SPECIFICATIONS. 4. IF THE STRUCTURAL DRAW INGS INCLUDE LOADS TO ACCOMMODATE NON-STRUCTURAL ELEMENTS,
10. JOIST BRIDGING SHALL BE PROVIDED AS REQUIRED BY THE JOIST MANUFACTURER AND SJI THE CONTRACTOR SHALL SUBMIT DOCUMENTATION INDICATING THAT THE NON-STRUCTURAL
STANDARDS. BRIDGING W HERE SHOW N ON THE STRUCTURAL DRAW INGS IS A SCHEMATIC ELEMENTS COMPLY W ITH THE LOADING CRITERIA PROVIDED HEREIN. SUCH DOCUMENTATION SHALL
REPRESENTATION ONLY. SEE JOIST MANUFACTURER FOR BRIDGING SIZE, CONNECTIONS, TYPE AND BEAR THE STAMP AND SIGNATURE OF THE DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN.
QUANTITY. 5. W HEN THE NON-STRUCTURAL DEFERRED SUBMITTAL INDICATES THAT THE ELEMENT W ILL IMPART
11. W HERE ADDED LOADS ARE SHOW N ON THE JOISTS BUT NOT SPECIFICALLY DIMENSIONED, THE JOIST FORCES IN EXCESS OF LOADS THAT ARE INDICATED ON THE STRUCTURAL DRAW INGS, THE
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DESIGNER SHALL PLACE THOSE LOADS ON THE JOIST AT A LOCATION THAT RESULTS IN THE HIGHEST CONTRACTOR SHALL SUBMIT A DETAILED GRAPHICAL REPRESENTATION OF THOSE DESIGN LOADS, DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
STRESS IN THE MEMBERS. THE DESIGNER MAY ASSUME THAT THE LOAD OCCURS W ITHIN 10 FEET OF A INCLUDING MAGNITUDE, AND LOCATION. THE GRAPHIC SHALL BE ACCOMPANIED BY DOCUMENTATION NOT INTENDED FOR CONSTRUCTION, RECORDING
SCALED DIMENSION. INDICATING THAT THE NON-STRUCTURAL ELEMENT DESIGN COMPLIES W ITH THE LOADING CRITERIA PURPOSES, OR IMPLEMENTATION
12. FABRICATOR MUST SUBMIT A CERTIFICATE OF COMPLIANCE TO THE BUILDING OFFICIAL PER IBC 2207.5 PROVIDED HEREIN. THE LETTER SHALL BEAR THE STAMP AND SIGNATURE OF THE DESIGN
STATING THAT W ORK W AS PERFORMED IN ACCORDANCE W ITH APPROVED CONSTRUCTION PROFESSIONAL RESPONSIBLE FOR THE DESIGN.
DOCUMENTS AND W ITH SJI SPECIFICATIONS. 6. NON-STRUCTURAL DELEGATED DESIGN ITEMS REQUIRING DEFERRED SUBMITTALS SHALL INCLUDE,
13. UNLESS NOTED OTHERW ISE, ROOF JOISTS AND GIRDERS SHALL BE DESIGNED FOR A NET W IND UPLIFT BUT ARE NOT LIMITED TO :
OF 11 PSF (ASD). a. COLD FORMED STEEL STUDS / JOISTS / HEADERS / JAMBS / TRUSSES.
14. ALL ROOF JOISTS BEARING ON EXTERIOR W ALLS SHALL BE DESIGNED TO TRANSFER 4.0 KIPS b. SEISMIC BRACING OF ALL ARCHITECTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL ITEMS
(ULTIMATE) TOP CHORD AXIAL FORCE THROUGH THE BEARING SHOE. W HERE REQUIRED BY THE MOST RECENT VERSION OF ASCE 7 AND THE PROJECT CONTRACT
15. ALL JOISTS AT GRID LINES SHALL BE DESIGNED TO RESIST A 8 KIP TOP CHORD AXIAL FORCE DOCUMENTS.
(ULTIMATE).
16. ALL STANDARD AND NON STANDARD SJI JOISTS SHALL BE DESIGNED FOR THE FOLLOW ING A. EXISTING BUILDING NOTES
DEFLECTION CRITERIA :
a. LIVE LOAD : L/240 TOTAL LOAD : L/180 1. ARW ENGINEERS EXPRESSLY DISCLAIMS RESPONSIBILITY FOR ANY PORTION OF THE EXISTING
17. JOIST MANUFACTURER SHALL APPLY ADDITIONAL POINT OR LINE LOAD AS REQUIRED TO SUPPORT BUILDING NOT SPECIFICALLY ADDRESSED IN THESE DRAW INGS.
FIRE PROTECTION MAINLINES 4" DIAMETER OR GREATER. JOIST MANUFACTURER SHALL COORDINATE 2. DRAW INGS AND DETAILS HAVE BEEN PREPARED TO REFLECT THE EXISTING CONDITIONS AND
W ITH GENERAL CONTRACTOR TO OBTAIN LOCATIONS AND W EIGHTS OF THESE LINES. SEISMIC CONFIGURATIONS OF STRUCTURAL ELEMENTS. HOW EVER, THE CONTRACTOR IS ULTIMATELY
D BRACING LOADS FOR FIRE PROTECTION MAINLINES SHALL ALSO BE ACCOUNTED FOR IN THE JOIST RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITIONS AND ALERTING THE ENGINEER OF ANY D
MANUFACTURER'S DESIGN. DISCREPANCIES FOUND PRIOR TO FABRICATING OR INSTALLING STRUCTURAL ELEMENTS.
3. THE CONTRACTOR IS RESPONSIBLE FOR MAKING SURE THAT THE BUILDING AND ELEMENTS W ITHIN
N. MASONRY THE BUILDING REMAIN STABLE UNTIL CONSTRUCTION IS COMPLETE. AT NO ADDITIONAL COST TO THE
OW NER, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING SHORING OR OTHER
1. ALL HOLLOW MASONRY UNITS SHALL CONFORM TO ASTM C-90. TEMPORARY SUPPORT OF STRUCTURAL MEMBERS UNTIL THE FINAL CONFIGURATION HAS BEEN
f’m (MINIMUM, FACTORED) 2,000 PSI COMPLETED.
MINIMUM UNIT STRENGTH 2,000 PSI (TESTED IN ACCORDANCE W ITH ASTM C-140)
ACCEPTABLE RANGE OF UNIT W EIGHT : 105 PCF TO 125 PCF
2. ALL GROUT (SITE MIXED OR PRE-MIXED) SHALL CONFORM TO ASTM C-476 OR SECTION 2.2A OF TMS
602-16. GROUT SHALL BE PLACED W ITH SUFFICIENT W ATER FOR POURING W ITHOUT SEGREGATION. DO
NOT USE MORTAR FOR GROUT. MECHANICALLY VIBRATE ALL GROUT.
3. GROUT STOPS SHALL BE AN APPROVED PRODUCT DESIGNED AND MANUFACTURED FOR USE AS A
GROUT STOP. GROUT STOP SUBMITTALS SHALL BE SUBMITTED TO THE ARCHITECT AND ENGINEER
FOR REVIEW . OTHER GROUT STOP MATERIALS SUCH AS ASPHALT IMPREGNATED MATERIALS ARE NOT
PERMITTED.
4. MORTAR SHALL BE TYPE S AND SHALL CONFORM TO ASTM C 270.
5. ALL MASONRY W ORK SHALL CONFORM TO CHAPTER 21 OF THE IBC.
6. UNLESS NOTED OTHERW ISE, MINIMUM REINFORCING IN ALL 8” MASONRY W ALLS SHALL BE AS
FOLLOW S :
a. VERTICAL : #5 BARS IN GROUTED CELLS ADJACENT TO ALL OPENINGS GREATER THAN 24 INCHES
W IDE, ON EACH SIDE OF CONTROL JOINTS, AT ENDS OF W ALL, AND AT A MAXIMUM SPACING OF 32"
THROUGHOUT THE W ALL. AT CORNERS, PROVIDE A MINIMUM OF (4) VERTICAL BARS AT "T" JOINTS
AND (3) VERTICAL BARS AT "L" JOINTS. SEE THE TYPICAL DETAIL / SCHEDULE FOR MORE
INFORMATION. ALL VERTICAL REINFORCEMENT SHALL BE DOW ELED INTO THE FOUNDATION W ALL
UNLESS SPECIFICALLY DETAILED OTHERW ISE.
b. HORIZONTAL : (2) #4 BARS IN 8” DEEP “H” BLOCK BOND BEAM UNITS AT 48”O.C. AND AT FLOORS,
ROOF, BELOW OPENINGS, AND TOP OF W ALL. BOND BEAMS AT ROOF SHALL SLOPE TO MATCH
SLOPING ROOF. SEE THE MASONRY REINFORCING SCHEDULE FOR MASONRY BEAMS ABOVE
OPENINGS.
7. SEE THE MASONRY REINFORCING SCHEDULE FOR OPENINGS W HICH EXCEED 32 INCHES IN EITHER
DIRECTION.
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
8. ALL BLOCK CELLS CONTAINING REINFORCING, BOLTS, OR ANCHORS SHALL BE GROUTED SOLID.
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
9. PROVIDE (1) #5 (MINIMUM), IN GROUTED SPACE, ON ALL SIDES AND ADJACENT TO EVERY OPENING MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
W HICH EXCEEDS 24” IN EITHER DIRECTION. HORIZONTAL BARS SHALL EXTEND 24” BEYOND THE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
CORNERS OF THE OPENING AND VERTICAL BARS SHALL EXTEND TO TOP OF W ALL. VERTICAL WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
REINFORCING SHALL BE PROVIDED AT ENDS, CORNERS AND EACH SIDE OF CONTROL JOINTS. SEE WRITTEN PERMISSION FROM METHOD STUDIO INC.
C TYPICAL DETAILS FOR OPENINGS W HICH EXCEED 32” IN EITHER DIRECTION. C
10. SOLID GROUTING OF MASONRY IS UNACCEPTABLE EXCEPT AS SPECIFICALLY NOTED ON PLANS AND

11.
SCHEDULES.
W HERE W ALLS ARE NOT GROUTED SOLID, EACH GROUT POUR SHALL TERMINATE FLUSH W ITH THE
project:
TOP OF THE UPPERMOST UNIT EXCEPT AT CELLS W ITH VERTICAL REINFORCING W HERE GROUT SHALL

12.
BE 1-1/2” BELOW TOP OF UNIT TO PROVIDE CONSTRUCTION KEY. W HERE W ALLS ARE GROUTED SOLID,
EACH GROUT POUR SHALL TERMINATE 1-1/2” BELOW TOP OF UNIT.
GROUT POURS SHALL NOT EXCEED 5’-0” UNLESS HIGH LIFT GROUTING PROCEDURES ARE FOLLOW ED.
USU EVR
13. THE USE OF HIGH LIFT GROUTING PROCEDURES REQUIRE THE APPROVAL OF THE ARCHITECT AND
ENGINEER AND SHALL NOT EXCEED THE MAXIMUM HEIGHTS GIVEN IN TABLE 3.2.1 OF TMS 402-16.
GROUT DEMONSTRATION PANELS, AS PRESCRIBED BY THE ARCHITECT AND ENGINEER, SHALL BE
REQUIRED W HERE REQUESTED GROUTING PROCEDURES DO NOT MEET THE LIMITS OF TABLE 3.2.1.
EXPANSION
ADDITIONALLY, ALL HIGH LIFT GROUTING SHALL REQUIRE SPECIAL INSPECTION PROCEDURES NEEDED
TO VERIFY GROUT PLACEMENT DURING CONSTRUCTION. DURING THE SUBMITTAL FOR APPROVAL
PROCESS, SUBMITTAL SHALL INCLUDE, BUT NOT BE LIMITED TO: STATEMENT OF PROCEDURE FOR
MECHANICAL VIBRATION OF HIGH LIFT GROUT; NEW MIX DESIGNS FOR HIGH SLUMP, HIGH LIFT GROUT;
FOR SELF-CONSOLIDATING GROUT, SUBMIT MIX DESIGNS, SLUMP FLOW RATES, VISUAL STABILITY
INDEX (VSI), AND QUANTITIES OF ADMIXTURES BEING USED.
14. ALL MASONRY BEAMS SHALL BE BUILT INTEGRAL W ITH SUPPORT. NO TOOTHING OR DOW ELING
PERMITTED. UNITS W ITH ONE END OPEN SHALL BE USED FOR ALL MASONRY BEAMS.
15. PROVIDE VERTICAL CONTROL JOINTS AT MAXIMUM SPACINGS NOTED BELOW UNLESS NOTED
OTHERW ISE IN THE SPECIFICATIONS AND/OR ON ARCHITECTURAL ELEVATIONS AND AT ALL CHANGES
IN W ALL ELEVATION AND MASONRY THICKNESS. CONTROL JOINTS SHALL NOT BE LOCATED DIRECTLY
OVER OR CLOSER THAN 24” TO W ALL OPENINGS (DOORS, W INDOW S, MECHANICAL OPENINGS, ETC.),
OR W ITHIN MASONRY JAMBS.
REINFORCED MASONRY : 40 FT
16. HORIZONTAL REINFORCEMENT SHALL TERMINATE AT EACH SIDE OF CONTROL JOINTS EXCEPT AT
FLOOR AND ROOF LEVEL BOND BEAMS AND AT TOP OF PARAPET.
17. CONTROL JOINTS SHALL BE PROVIDED AT THE MASONRY SIDE OF EMBEDDED STEEL COLUMNS TO 670 EAST 1550 NORTH, LOGAN, UT
CONTROL CRACKING OF FACE SHELLS. 84341
18. SUPPORT NON-BEARING, NON-STRUCTURAL W ALLS AT TOP OF MASONRY AS PER TYPICAL DETAILS AT
LOCATIONS W HERE INTERSECTING OR PERPENDICULAR W ALLS ARE 12’-0” OR MORE APART OR W HERE
END OF W ALL OCCURS 6’-0” OR MORE FROM INTERSECTING W ALL.
19. EMBED CHANNELS AND PLATES TO BE PLACED SO AS TO CREATE FLUSH SURFACE W ITH FACE OF
MASONRY. FLANGES ON CHANNEL EMBEDS SHALL BE HORIZONTAL.
20. ALL VERTICAL REINFORCING SHALL BE SECURED IN PLACE PRIOR TO GROUTING USING W IRE
POSITIONERS OR OTHER ACCEPTABLE DEVICES. REINFORCING SHALL BE SECURED AT BAR-SPLICE
LOCATIONS AND AT A SPACING NOT MORE THAN 120 BAR DIAMETERS.
B 21. UNLESS NOTED OTHERW ISE, MASONRY W ALLS SHALL BE CONSTRUCTED UTILIZING COMMON B
RUNNING-BOND W ITH FULLY MORTARED BED JOINTS AROUND GROUTED CELLS. p r o j e c t # : 21.0320
22. ELECTRICAL CONDUIT SHALL NOT BE PLACED IN CELLS THAT CONTAIN REBAR. CONDUIT IS ALLOW ED
d a t e : 02.14.2023
TO PASS THROUGH REINFORCED CELLS W HEN IT OCCURS PERPENDICULAR TO THE REBAR. CONDUIT
SHALL NOT CONTACT REBAR AS IT PASSES. THERE SHALL BE 1” CLEAR BETW EEN CONDUIT AND
REBAR. revisions :

title:

STRUCTURAL
NOTES
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

A A

sheet:

S002 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

2018 IBC CONCRETE REBAR LAP SPLICE SCHEDULE LEGEND OF SYMBOLS AND ABBREVIATIONS
FOR CONCRETE APPLICATIONS (ACI 318 - 14)
AB = ANCHOR BOLT FOOTING MARK
ABV = ABOVE
ARCH = ARCHITECT TOP OF FOOTING ELEVATION
FACE OF JOINT OR FACE OF JOINT OR COUPLER OR BLW = BELOW
CRITICAL SECTION CRITICAL SECTION W ELDED SPLICE BN = BOUNDARY NAILING SECTION MARK
BS = BOUNDARY SCREW SHEET NUMBER
BRB = BUCKLING RESTRAINED BRACE
BRBF = BUCKLING RESTRAINED BRACE FRAME TOP OF FOUNDATION W ALL OR
CJP = COMPLETE JOINT PENETRATION COLUMN PIER ELEVATION
CL = CENTERLINE
CMU = CONCRETE MASONRY UNIT SHEAR W ALL - SEE SCHEDULE
ℓd ℓs ℓdh 2' - 0"
COL = COLUMN
DEVELOPMENT LENGTH LAP SPLICE LENGTH HOOK DEVELOPMENT CLEAR CONC = CONCRETE MIN. LENGTH OF SHEAR W ALL
LENGTH CP = CONCRETE PIER
E DC = DEMAND CRITICAL S S FOOTING STEP E
DIA / Ø = DIAMETER 360 west aspen avenue
CONCRETE REINFORCING & SPLICE LENGTHS (IN) DBA = DEFORMED BAR ANCHOR MASONRY W ALL salt lake city, utah 84101
DBE = DECK BEARING ELEVATION
CONCRETE BAR SIZE ELEV = ELEVATION
801 532 4422
BAR LOCATION DEPRESS FDN./W ALL AND POUR
#3 #4 #5 #6 #7 #8 #9 #10 #11 COMMENTS EN = EDGE NAILING
TYPE STRENGTH EOD = EDGE OF DECK FLOOR SLAB OVER AT MASONRY
ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh FDN = FOUNDATION FOUNDATION W ALL
FTG = FOOTING
VERT. W ALL BARS, DEPRESS FDN./W ALL AND POUR
NW C 3000 PSI 17 22 8 22 29 8 28 36 10 33 43 12 48 62 13 55 72 15 62 81 17 69 90 19 76 99 30 FFE = FINISHED FLOOR ELEVATION
FILL ON METAL DECK FLOOR SLAB OVER AT CONCRETE
GB = CONCRETE GRADE BEAM
HORIZ. W ALL BARS, HSA = HEADED STUD ANCHOR FOUNDATION W ALL
NW C 3000 PSI 17 22 8 22 29 8 28 36 10 33 43 12 48 62 13 55 72 15 62 81 17 69 90 19 76 99 30
FOOTING TOP BARS JBE = JOIST BEARING ELEVATION
KB = KICKER BRACE MASONRY BEAM
BEAM BOTTOM BARS, NW C 3000 PSI 17 22 8 22 29 11 28 36 14 33 43 16 48 62 19 55 72 22 62 81 25 69 90 27 76 99 30 MAX = MAXIMUM
COLUMN BARS CONCRETE BEAM
MB = MASONRY BEAM
FOOTING BOTTOM MC = MASONRY COLUMN
NW C 3000 PSI 12 16 8 14 18 8 17 22 10 20 26 12 29 38 13 33 43 15 37 48 17 42 55 19 46 60 30

"
BARS MECH = MECHANICAL

"A
HD - SIMPSON HOLDOW N SIZE
MEZZ = MEZZANINE
BEAM TOP BARS NW C 3000 PSI 22 29 8 29 38 11 36 47 14 43 56 16 63 82 19 72 94 22 81 105 25 90 117 27 98 127 30 POST - SIZE OF END POST
MIN = MINIMUM

D
H
CONNECTED TO HOLDOW N UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND

ST
MJ = MASONRY JAMB

PO
"A" - PLAN CONFIGURATION AT DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
SLAB ON GRADE NW C 3000 PSI 12 16 8 14 18 8 17 22 10 20 26 12 32 42 13 42 55 15 53 69 17 69 90 19 76 99 30 MW = MASONRY W ALL NOT INTENDED FOR CONSTRUCTION, RECORDING
HOLDOW N AT FOUNDATION
NS, FS = NEAR SIDE, FAR SIDE PURPOSES, OR IMPLEMENTATION
OAE = OR APPROVED EQUAL ELEVATION
CONCRETE REINFORCING & SPLICE LENGTHS (IN) OPP = OPPOSITE
CONCRETE BAR SIZE PAF = POW DER ACTUATED FASTENER
L FRAMING ANGLE SEE TYPICAL DETAIL
BAR LOCATION PL = PLATE
#3 #4 #5 #6 #7 #8 #9 #10 #11 COMMENTS
TYPE STRENGTH REINF = REINFORCING
REQ'D = REQUIRED C FRAMING CHANNEL SEE TYPICAL
ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh ℓd ℓs ℓdh
SIM = SIMILAR DETAIL
VERT. W ALL BARS, SSH = STEEL STUD HEADER
NW C 4500 PSI 14 18 7 18 23 6 23 30 8 27 35 9 40 52 11 45 59 13 51 66 14 56 73 16 62 81 25 ITEMS, DETAILS, & SYSTEMS W HICH
FILL ON METAL DECK SSJ = STEEL STUD JAMB
SSS = STEEL STUD SILL L ARE PART OF THE LATERAL FORCE
HORIZ. W ALL BARS, RESISTING SYSTEM.
NW C 4500 PSI 14 18 7 18 23 6 23 30 8 27 35 9 40 52 11 45 59 13 51 66 14 56 73 16 62 81 25 SSW = STEEL STUD W ALL
FOOTING TOP BARS
TOB = TOP OF BEAM ELEVATION
BEAM BOTTOM BARS, TOC = TOP OF CONCRETE SLAB MOMENT RESISTING CONNECTIONS -
NW C 4500 PSI 14 18 7 18 23 9 23 30 11 27 35 13 40 52 16 45 59 18 51 66 20 56 73 22 62 81 25 SEE DETAIL
COLUMN BARS TOF = TOP OF FOOTING
TOG = TOP OF GIRDER ELEVATION
D FOOTING BOTTOM
BARS
NW C 4500 PSI 12 16 7 12 16 6 14 18 8 17 22 9 24 31 11 27 35 13 31 40 14 34 44 16 37 48 25 TOM = TOP OF MASONRY MOMENT RESISTING CANTILEVER D
TOS = TOP OF STEEL ELEVATION CONNECTIONS - SEE DETAIL
BEAM TOP BARS NW C 4500 PSI 18 23 7 24 31 9 30 39 11 35 46 13 51 66 16 59 77 18 66 86 20 73 95 22 80 104 25 TYP = TYPICAL KB
UNO = UNLESS NOTED OTHERW ISE KICKER BRACE

SLAB ON GRADE NW C 4500 PSI 12 16 7 12 16 6 14 18 8 17 22 9 27 35 11 34 44 13 44 57 14 56 73 16 62 81 25

NOTES :
1. MECHANICAL COUPLERS MAY BE USED IN LIEU OF LAP SPLICES SHOW N. SEE STRUCTURAL NOTES FOR MINIMUM COUPLER CAPACITY. W HERE MECHANICAL COUPLERS ARE USED, STAGGER ADJACENT SPLICES A MINIMUM OF 24" AS FOOTING SCHEDULE
INDICATED ABOVE.
2. LENGTHS INDICATED IN THIS SCHEDULE SHALL BE INCREASED BY 50% FOR STRAIGHT BAR DEVELOPMENT AND 20% FOR HOOKED BARS W HERE EPOXY COATING IS USED. LENGTHW ISE REINF. CROSSW ISE REINF.
MARK W IDTH LENGTH THICK REMARKS
3. W HEN SPLICING BARS OF DIFFERENT SIZES, USE LAP SPLICE LENGTH OF LARGER BARS UNO. NO. SIZE NO. SIZE SPA.
4. SPLICE BARS LARGER THAN #11 USING MECHANICAL COUPLERS.
FC2 2'-0" CONT. 12" (2) #5 -- -- --
FC3 3'-0" CONT. 12" (3) #5 -- -- --
FC4 4'-0" CONT. 12" (4) #5 (4) #5 --
SPECIAL INSPECTION SCHEDULE 1, 2
ROOF DECK SCHEDULE
F3 3'-0" 3'-0" 12" (3) #5 (3) #5 --
ESTABLISHED PER 2015 IBC SECTION 110 AND CHAPTER 17 ATTACHMENT
DECK F3.5 3'-6" 3'-6" 12" (3) #5 (3) #5 --
SUPPORTS SIDE SEAMS MIN. SHEAR MIN. SHEAR
AREA SUPPORTS PARALLEL F4 4'-0" 4'-0" 12" (4) #5 (4) #5 --
DIA. WELD CAPACITY STIFFNESS COMMENTS
ITEM CONTINUOUS 3 PERIODIC 3 REFERENCE COMMENTS #12 TEK TOP SEAM PUNCH TO FLUTES
DEPTH TYPE GA. @ INTERIOR PATTERN (LRFD) G' (kip/in)
SCREWS WELD LOCK (1) F4.5 4'-6" 4'-6" 12" (4) #5 (4) #5 --
FLUTES Ø W ELD SPA.
P 1. SPECIAL INSPECTION IS NOT REQUIRED W HERE THE WORK IS DONE ON THE PREMISES OF A FABRICATOR REGISTERED AND APPROVED F5 5'-0" 5'-0" 12" (5) #5 (5) #5 --
TO PERFORM SUCH W ORK W ITHOUT SPECIAL INSPECTION, PROVIDED THE FABRICATOR COMPLIES WITH IBC. A 1 1/2 PLB 22 3/4" 36/7/4 --- --- 12"o.c. 3/4" 12"o.c. 1354 plf 136 ---
F5.5 5'-6" 5'-6" 14" (5) #6 (5) #6 --
PRE-FAB CONSTRUCTION (IBC 1704.2) REFERENCE NOTES P1 & P2 P 2. INSPECTION FOR PREFABRICATED CONSTRUCTION SHALL BE THE SAME AS IF THE MATERIAL USED IN THE CONSTRUCTION TOOK PLACE
ON SITE. SPECIAL INSPECTION W ILL NOT BE REQUIRED DURING PREFABRICATION IF THE APPROVED AGENCY CERTIFIES THE F6 6'-0" 6'-0" 16" (6) #6 (6) #6 --
CONSTRUCTION AND FURNISHES EVIDENCE OF COMPLIANCE. (SEE NOTE 2).
F6.5 6'-6" 6'-6" 16" (6) #6 (6) #6 --
CONCRETE CONSTRUCTION (IBC 1705.3) SEE IBC TABLE 1705.3 - REF. NOTE C1 C 1. SPECIAL INSPECTION IS NOT REQUIRED FOR CONC. ISOLATED SPREAD FOOTINGS, CONTINUOUS FOOTINGS, NON-STRUCTURAL SLABS, F7 7'-0" 7'-0" 18" (7) #6 (7) #6 -- THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
FOUNDATION WALLS, PATIOS, DRIVEWAYS, AND SIDEW ALKS PROVIDED THE REQUIREMENTS OF IBC 1705.3 ARE MET. ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
REINFORCING STEEL PLACEMENT
C 2. PERIODIC SPECIAL INSPECTION IS ALLOWED FOR VERIFICATION OF THE W ELDABILITY OF REINFORCING STEEL RESISTING FLEXURAL AND F7.5 7'-6" 7'-6" 18" (7) #6 (7) #6 -- MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
W ELDING OF REINFORCING STEEL REFERENCE NOTE C2 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
AXIAL FORCES IN INTERMEDIATE AND SPECIAL MOMENT FRAMES, BOUNDARY ELEMENTS OF SPECIAL REINFORCED CONCRETE SHEAR F8 8'-0" 8'-0" 20" (8) #6 (8) #6 -- WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
EMBEDDED BOLTS & PLATES W ALLS, AND SHEAR REINFORCEMENT. PERIODIC SPECIAL INSPECTION IS ALLOW ED FOR W ELDING OF OTHER ASTM A 706 REINFORCING FASTENING PATTERNS WRITTEN PERMISSION FROM METHOD STUDIO INC.
STEEL NOT INCLUDED IN THE CONTINUOUS SPECIAL INSPECTION REQUIREMENTS NOTED ABOVE.
C VERIFYING REQUIRED DESIGN MIX C 3. PERFORM AIR, SLUMP AND TEMP. TESTS WHEN CONCRETE SAMPLES ARE CAST. C
F358 3'-6" 8'-0" 14" (4) #6 (8) #6 --
CONCRETE PLACEMENT / SAMPLING REFERENCE NOTE C3
C 4. PERIODIC SPECIAL INSPECTION IS REQUIRED FOR VERIFICATION OF IN-SITU CONCRETE STRENGTH FOR POST-TENSIONED CONCRETE
PRIOR TO TENSIONING TENDONS OR REMOVING SHORING OR FORMS. (6) project:
CURING TEMPERATURE / TECHNIQUES C 5. EPOXY AND EXPANSION ANCHORS INTO MASONRY OR CONCRETE MAY BE USED ONLY W HEN APPROVED BY ARCHITECT. AND/OR
ENGINEER USING AN APPROVED PRODUCT W ITH CURRENT PUBLISHED ICC RESEARCH REPORT NUMBERS. COORDINATE 3" CLEAR 3" CLEAR 3" CLEAR
USU EVR
EQ. EQ. EQ. EQ. EQ. EQ. 3" CLEAR
ERECTION OF PRECAST MEMBERS CONTINUOUS/PERIODIC SPECIAL INSPECTION REQUIREMENTS WITH ICC REPORT.
VERIFICATION OF IN-SITU STRENGTH REFERENCE NOTE C4 W ELD PATTERN : 36/7 (6)
2" CLEAR
36/4 @ INTERIOR PANEL SUPPORTS
EPOXY / EXPANSION ANCHOR PLACEMENT

MASONRY CONSTRUCTION (IBC 1705.4)


REFERENCE NOTE C5

SEE TMS 402/ACI 550 TABLE M 1. PERIODIC SPECIAL INSPECTION IS ALLOW ED FOR VERIFICATION OF THE WELDABILITY OF REINFORCING STEEL OTHER THAN ASTM A 706 IN
ACCORDANCE WITH ANSI / AW S D1.4. CONTINUOUS SPECIAL INSPECTION IS REQUIRED FOR REINFORCING STEEL RESISTING FLEXURAL
W ELD PATTERN : 36/7/4
36/7 @ END PANEL SUPPORTS

3" CLEAR 3" CLEAR


EXPANSION
1.19.2 (NON-ESSENTIAL)
AND AXIAL FORCES IN INTERMEDIATE AND SPECIAL MOMENT FRAMES, BOUNDARY ELEMENTS OF SPECIAL REINFORCED CONCRETE
AS MASONRY CONSTRUCTION BEGINS, VERIFY: SHEAR WALLS, AND SHEAR REINFORCEMENT. PERIODIC SPECIAL INSPECTION IS ALLOW ED FOR W ELDING OF OTHER ASTM A 706 TYPICAL FOOTING REINFORCING
REINFORCING STEEL NOT INCLUDED IN THE CONTINUOUS SPECIAL INSPECTION REQUIREMENTS NOTED ABOVE.
SITE PREPARED MORTAR
M 2. CONTINUOUS SPECIAL INSPECTION IS REQUIRED FOR ESSENTIAL FACILITIES (TMS 402/ACI 530 TABLE 1.19.3). TYP. FOOTING SECTION
MORTAR JOINTS M 3. EPOXY AND EXPANSION ANCHORS INTO MASONRY OR CONCRETE MAY BE USED ONLY WHEN APPROVED BY ARCHITECT AND/OR NOTES : TYP. FOOTING SECTION
ENGINEER USING AN APPROVED PRODUCT W ITH CURRENT PUBLISHED ICC RESEARCH REPORT NUMBERS. COORDINATE 1. ALL ROOF DECKING TO BE SUPPLIED BY VERCO, OR APPROVED EQUAL. ALTERNATE DECKING SHALL BE SUBMITTED W ITH CURRENT ICC APPROVAL W / TOP & BOTTOM REINF.
REINFORCEMENT / CONNECTORS TO ENGINEER FOR REVIEW AND APPROVAL. ALTERNATE DECKING SYSTEMS SHALL MEET OR EXCEED THE MINIMUM SHEAR CAPACITY AND SHALL
CONTINUOUS/PERIODIC SPECIAL INSPECTION REQUIREMENTS W ITH ICC REPORT.
GRADE & SIZE OF TENDONS & ANCHORAGES PROVIDE LESS THAN OR EQUAL TO THE MINIMUM SHEAR STIFFNESS LISTED IN THE SCHEDULE.
2. TOP SEAM W ELDS SHALL BE 1-1/2" LONG AND SHALL BE ACCORDING TO SDI STANDARDS.
INSPECTION SHALL VERIFY: 3. USE NESTABLE (OVERLAPPING) SIDE SEAMS AT SCREW ATTACHMENTS AND INTERLOCKING SIDE SEAMS AT W ELDS.
4. IF N DECK IS NOT NESTABLE, N DECK END BUTT JOINTS OVER STEEL JOISTS SHALL USE 16 GA. x 6" CONTINUOUS SHEET BETW EEN DECK AND JOIST STANDARD HOOK & BEND SCHEDULE
SIZE & LOCATION OF STRUCTURAL ELEMENTS
TOP CHORD ANGLES. DECK W ELDS TO PENETRATE SHEET AND ENGAGE JOIST CHORD.
TYPE, SIZE, & LOCATION OF ANCHORS REFERENCE NOTE M2 5. ALL DECK W ITH A PROFILE DEPTH OF 2" OR LESS SHALL HAVE NESTED OR TELESCOPED END LAPS. DETAILING
6. A 1 1/4" x 5/8" EFFECTIVE ARC SEAM W ELD IS REQUIRED AT SUPPORTS ADJACENT TO SIDELAPS. DIMENSIONS
SIZE, GRADE & TYPE OF REINFORCEMENT DETAILING DETAILING
DIMENSIONS HOOK A DIMENSIONS
W ELDING OF REINFORCING BARS REFERENCE NOTE M1
D 90° 670 EAST 1550 NORTH, LOGAN, UT
J
HOT OR COLD W EATHER PROTECTION A CANOPY D
A
84341
J 180° 6db OR 2 1/2" MIN. D
MEASUREMENT OF PRE-STRESSING FORCE REFERENCE NOTE M2 135°

C
FROM POINT OF
PRIOR TO GROUTING, VERIFY: NOTE: PATIO IS CONCRETE TANGENCY
D = 6d b FOR #3 THROUGH #8
CLEAN GROUT SPACE REFERENCE NOTE M2
EXISTING SLAB ON DECK PER D = 8d b FOR #9 THROUGH #11
STRUCTURAL NOTES 4 d b OR 2 1/2" MIN.
C = FOR BARS IN CMU:
PLACEMENT OF REINFORCEMENT CONNECTORS, #6 AND LARGER, PROVIDE 12d b
TENDONS AND ANCHORS. FROM POINT OF TANGENCY D = 4d b FOR #3 THROUGH #5
A D = 6d b FOR #3 THROUGH #8
#5 AND SMALLER, PROVIDE 6d b D = 6d b FOR #6 THROUGH #8
D = 8d b FOR #9 THROUGH #11
B PROPORTIONS OF SITE PREPARED GROUT FROM POINT OF TANGENCY D = 8d b FOR #9 THROUGH #11 B
(2 1/2" MINIMUM) p r o j e c t # : 21.0320
CONSTRUCTION OF MORTAR JOINTS
A NOTE: d b = BAR DIAMETER d a t e : 02.14.2023
GROUT PLACEMENT
GROUTING OF PRE-STRESSING BONDED TENDONS DIMENSION OF STANDARD 180° DIMENSION OF STANDARD revisions :
PREPARATION OF TEST SPECIMENS / PRISMS BAR SIZE HOOKS, ALL GRADES 90° HOOKS, ALL GRADES

COMPLIANCE W / CONST. DOCS. / SUBMITTALS A J A


CANOPY
EPOXY / EXPANSION ANCHOR PLACEMENT REFERENCE NOTE M3 A #3 5" 3" 6"
VERIFICATION OF f'm AND f'aac #4 6" 4" 8"
A
SELF CONSOLIDATING GROUT: #5 7" 5" 10"
VERIFY SLUMP FLOW AND VSI #6 8" 6" 1'-0"

SOILS (IBC 1705.6) REFERENCE NOTE F1 F 1. SPECIAL INSPECTION OF SOILS SHALL REFERENCE THE APPROVED SOILS REPORT TO DETERMINE COMPLIANCE. #7 10" 7" 1'-2"
VERIFY ADEQUATE MATERIALS BELOW FOOTINGS REFERENCE NOTE F1 F 2. W HERE SOILS REPORT IS NOT PROVIDED SPECIAL INSPECTIONS ARE REQUIRED TO VERIFY THAT THE IN-PLACE DRY DENSITY OF THE #8 11" 8" 1'-4"
COMPACTED FILL IS NOT LESS THAN 90 PERCENT OF THE MAXIMUM DRY DENSITY AT OPTIMUM MOISTURE CONTENT DETERMINED IN
EXCAVATIONS EXTEND TO PROPER DEPTH AND
REFERENCE NOTE F2
ACCORDANCE WITH ASTM D 1557. KEY PLAN #9 1'-3" 11 3/4" 1'-7"
REACH PROPER MATERIAL #10 1'-5" 1'-1 1/4" 1'-10"
CLASSIFY & TEST CONTROLLED FILL MATERIALS REFERENCE NOTE F2 #11 1'-7" 1'-2 3/4" 2'-0" title:
PERFORM MATERIALS, DENSITIES, AND LIFT
THICKNESSES DURING PLACEMENT AND
COMPACTION OF CONTROLLED FILL.
REFERENCE NOTE F1
SCHEDULES
PROPERLY PREPARED SITE AND SUB-GRADE PRIOR
REFERENCE NOTE F1
TO FILL.
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

GENERAL SPECIAL INSPECTION NOTES :


1. THE ITEMS MARKED WITH A " " IN THE SPECIAL INSPECTION SCHEDULE SHALL BE INSPECTED IN ACCORDANCE W ITH IBC CHAPTER 17 BY A CERTIFIED SPECIAL INSPECTOR FROM AN ESTABLISHED TESTING AGENCY. FOR MATERIAL SAMPLING AND TESTING REQUIREMENTS, REFER TO THE
MATERIAL SAMPLING AND TESTING SECTION, THE PROJECT SPECIFICATIONS, AND THE SPECIFIC GENERAL NOTES SECTIONS. THE TESTING AGENCY SHALL SEND COPIES OF ALL STRUCTURAL TESTING AND INSPECTION REPORTS DIRECTLY TO THE ARCHITECT, ENGINEER, CONTRACTOR, AND
BUILDING OFFICIAL. ANY ITEMS W HICH FAIL TO COMPLY WITH THE APPROVED CONSTRUCTION DOCUMENTS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF DISCREPANCIES ARE NOT CORRECTED, THEY SHALL BE BROUGHT TO THE ATTENTION
OF THE BUILDING OFFICIAL, ARCHITECT, AND ENGINEER PRIOR TO COMPLETION OF THAT PHASE OF W ORK. SPECIAL INSPECTION TESTING REQUIREMENTS APPLY EQUALLY TO ALL BIDDER DESIGNED COMPONENTS.
2. ANY CONSTRUCTION OR MATERIAL THAT HAS FAILED INSPECTION SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT.
3. CONTINUOUS SPECIAL INSPECTION MEANS THE FULL-TIME OBSERVATION OF W ORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR W HO IS PRESENT IN THE AREA WHERE THE W ORK IS BEING PERFORMED. PERIODIC SPECIAL INSPECTION MEANS THE PART-TIME OR
INTERMITTENT OBSERVATION OF W ORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR W HO IS PRESENT IN THE AREA W HERE THE WORK HAS BEEN OR IS BEING PERFORMED AND AT THE COMPLETION OF THE WORK. (IBC SECTION 1702)
A A

sheet:

S010 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

2018 IBC MASONRY REBAR LAP SPLICE SCHEDULE TYPICAL MASONRY / JAMB REINFORCING SCHEDULE
FOR MASONRY APPLICATIONS (TMS 402/602 - 16)

JAMB STEEL TO
SLOPE BOND BEAM W HERE
EXTEND TO
OCCURS - SEE ARCH.
ROOF/FLOOR
BOND BEAM REQ'D @ ROOF DOW ELS TO MATCH BOND
CASE #1 = SINGLE BAR, CENTERED IN CELL ELEVATION STEP AS REQ'D BOND BEAM BEAM REINFORCING. SEE
TO MATCH SLOPING ROOF AT PARAPET SCHEDULE FOR LAP

2"

2"
SEE ARCH.

E CASE #2 = W HEN REINFORCING BAR IS PLACED ADJACENT TO FACE SHELL E


SEE REBAR
360 west aspen avenue
MASONRY REINFORCING & SPLICE LENGTHS (IN) (f'm = 1500psi)
salt lake city, utah 84101
LAP SCHED.

BEAM DEPTH
801 532 4422

BEAM DEPTH

SEE PLAN
BAR SIZE

SEE PLAN
BAR LOCATION #3 #4 #5 #6 #7
CASE # CASE # CASE # CASE # CASE #
1 2 1 2 1 2 1 2 1 2

BEAM / W ALL 26" 32"


19" 38" 45"
HORIZONTAL
W ALL VERTICAL 12" 16" 14" 29" 22" 45" 43" 54" 59" 63"
COLUMN AND JAMB 24"
OPEN OPEN
MASONRY REINFORCING & SPLICE LENGTHS (IN) (f'm = 2000psi) OPEN

BAR SIZE
BAR LOCATION #3 #4 #5 #6 #7 OPENING SIZE UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
CASE # CASE # CASE # CASE # CASE # SEE ARCH. PLANS DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
1 2 1 2 1 2 1 2 1 2 TOP OF PURPOSES, OR IMPLEMENTATION
FOUNDATION/
BEAM / W ALL
19" 26" 32" 38" 45" FTG.
HORIZONTAL TYPICAL W ALL BOND BEAM REINFORCING
W ALL VERTICAL W HERE BOND BEAM LAYOUT DOES NOT
12" 14" 12" 25" 19" 40" 37" 54" 51" 63" COINCIDE W ITH BOTTOM OF OPENING
COLUMN AND JAMB
NOTES:
MASONRY REINFORCING & SPLICE LENGTHS (IN) (f'm = 2500psi)
1. USE OPEN-END UNITS AT INTERSECTIONS OF BEAMS AND JAMBS.
BAR SIZE 2. TYPICAL HORIZONTAL BOND BEAMS MAY BE ADJUSTED UP OR DOW N BY ONE COURSE PROVIDED THE OVERALL NUMBER OF REQUIRED BOND BEAMS ARE INSTALLED.
3. TYPICAL HORIZONTAL AND VERTICAL W ALL REINFORCING NOT SHOW N FOR CLARITY, SEE PLAN AND SCHEDULE FOR TYPICAL W ALL REINFORCING.
BAR LOCATION #3 #4 #5 #6 #7 4. JAMB REINFORCING SHOW N IS SCHEMATIC. SEE SCHEDULE & DETAILS FOR ACTUAL JAMB REINFORCING.
CASE # CASE # CASE # CASE # CASE # 5. ALL VERTICAL W ALL REINFORCING SHALL BE CONTINUOUS BETW EEN THE LEVELS IN W HICH THE W ALL OCCURS.

1 2 1 2 1 2 1 2 1 2

D BEAM / W ALL
HORIZONTAL
19" 26" 32" 38" 45" MASONRY BEAM SCHEDULE MASONRY JAMB SCHEDULE D
W ALL VERTICAL NOMINAL BOTTOM TOP VERTICAL MIN. GROUT OPENING 1 NOMINAL VERTICAL OPENING 1
12" 12" 22" 17" 36" 33" 54" 46" 63" MARK COMMENTS MARK TIES CONFIG. COMMENTS
COLUMN AND JAMB THICKNESS REINF. REINF. REINF. DEPTH SIZE THICKNESS REINF. SIZE

NOTES : MB-8A 8" (2) #5 (2) #4 #4 AT 16"o.c. 16" UP TO 4'-0" MJ-1 8" (2) #5 --- A 2'-8" TO 4'-0"
1. MECHANICAL COUPLERS MAY BE USED IN LIEU OF LAP SPLICES SHOW N. SEE STRUCTURAL NOTES FOR MINIMUM MB-8B 8" (2) #5 (2) #4 #4 AT 8"o.c. 24" 4'-0" TO 9'-0" MJ-2 8" (4) #5 --- B 4'-1" TO 9'-0"
COUPLER CAPACITY. W HERE MECHANICAL COUPLERS ARE USED, STAGGER ADJACENT SPLICES A MINIMUM OF 24"
AS INDICATED ABOVE. MB-8C 8" (4) #5 (2) #5 #4 AT 8"o.c. 60" SEE PLAN MJ-3 8" (6) #5 --- C SEE PLAN
2. DEVELOPMENT LENGTHS SHALL BE INCREASED BY 50% W HERE EPOXY COATED REBAR IS USED. MB-12A 12" (2) #5 (2) #5 #4 AT 16"o.c. 16" UP TO 4'-0" MJ-4 12" (2) #6 --- A 2'-8" TO 10'-0"
3. W HEN SPLICING BARS OF DIFFERENT SIZES, USE LAP SPLICE LENGTH OF LARGER BARS UNO.
4. ALL REBAR #8 AND LARGER IN MASONRY SHALL BE SPLICED USING MECHANICAL SPLICES. SEE STRUCTURAL MB-12B 12" (2) #5 (2) #5 #4 AT 24"o.c. 32" 4'-1" TO 10'-0" MJ-5 12" (6) #6 --- C SEE PLAN
NOTES FOR MINIMUM COUPLER CAPACITY.
MB-12C 12" (4) #5 (2) #5 #4 AT 24"o.c. 60" SEE PLAN

BEAM CONNECTION SCHEDULE AT MASONRY W ALL


NOTES: NOTES:
1. W HERE SPECIFIC BEAMS ARE NOT NOTED ON THE PLANS - REFER TO OPENING SIZE FOR REQUIRED BEAM 1. W HERE SPECIFIC JAMBS ARE NOT NOTED ON THE PLANS - REFER TO OPENING SIZE FOR REQUIRED
DEPTH AND REINFORCING. REINFORCING AND CONFIGURATION.
2. FIRST VERTICAL BAR TO BE W ITHIN 8" OF END OF BEAM. 2. ALL VERTICAL REINFORCING SHALL HAVE MATCHING DOW ELS CAST INTO FOUNDATIONS.
3. SEE TYPICAL ELEVATION - VIEW OF BEAM. 3. HORIZONTAL REINFORCING NOT SHOW N.
TYP. BOTH ANGLES 4. VERTICAL REINFORCING SHALL HAVE HOOKS TOP AND BOTTOM. 4. JAMBS TO BE GROUTED SOLID.
"A" SEE SCHED
W ELD @ BOTTOM,
TOE, AND 1/2"
RETURN ON TOP VERTICAL REINFORCING -
SEE W ALL REINF. SCHEDULE
SEE W ALL REINF. SEE SCHEDULE
FOR TYPICAL REINF. SIZE AND
A325 BOLTS AS PER SCHEDULE
MASONRY W ALL W / W ASHERS THAT COMPLETELY
SPACINGS - CONTINUE SCHEDULE FOR TYP. USE UNITS W / ONE CONFIGURATION 'A'
TYPICAL W ALL HORIZONTAL VERTICAL REINF. OPEN END CELL AT
COVER THE SLOTS PER THE
AND VERTICAL REINF. IN SIZE AND SPACINGS ALL LINTELS/BEAMS
2 1/4" STRUCTURAL NOTES
BEAM SECTION SOLID GROUT THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
2" TYP. 1/2" (DO NOT USE TC BOLTS) ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &

MIN. GROUT DEPTH


VERTICAL REINFORCING -
EQUAL PLACE REINFORCING IN 24" OF JAMB SEE SCHEDULE
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
W BEAM - SEE PLAN COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
SPACING EXCESS OF (2) CONT. IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
NEXT COURSES

2"
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C CONFIGURATION 'B' C
SPACING

EMBED VERTICAL BEAM REINF.


2" TYP.
EQUAL

2"
HORIZ. BEAM REINFORCING -
CHANNEL 3" TYP. W / 180 DEG. HOOK TOP & 90
DEG. HOOK BOTTOM
SEE SCHEDULE FOR SIZES - VERTICAL BEAM project:
EXTEND 24" BEYOND OPENING REINF. W / HOOKS SOLID GROUT
PARALLEL TO BOTTOM BARS TOP & BOTTOM
1 1/2" TYP. TYP. EACH SIDE, SEE 24" OF JAMB
ELEVATION - AT INTERSECTING
W ALLS, HOOK INTO W ALL PER USU EVR

2"
U-BLOCK
TYP. H.S.A. TYPICAL DETAIL
CONFIGURATION 'C'

4" MAX.
3" MIN.
(2) L 3 x 5 W / 1 1/2" SLOTTED
PATTERN LAYOUT 12" W IDE 8" W IDE
EXPANSION

2"
HOLES SEE SCHEDULE

CHANNEL EMBED W / 3/4"DIA x 5" SOLID GROUT


SECTION PLAN VERTICAL REINFORCING -
H.S.A.'s SEE SCHED. NOTE: SEE TYPICAL DETAIL FOR 32" OF JAMB SEE SCHEDULE
LINTELS W / BRICK VENEER

MASONRY W ALL SCHEDULE MASONRY COLUMN SCHEDULE


VERT. REINF. HORIZ. BOND BEAM REINF. NOMINAL VERT.
MARK TIES CONFIGURATION
DIMENSIONS REINF.
ANGLE SIZE EMBED # OF H.S.A. MARK THICK. COMMENTS
BEAM SIZE W ELD 'A' BOLTS SIZE SPACE NO. SIZE SPACE @ ROOF @ ELEVATED
(EA. SIDE) CHANNEL H.S.A. PATTERN FLOOR MC-1 12" x 32" (8) #6 #3 AT 8"o.c. C
CONFIGURATION 'A'
W 6, W 8, C8 3 x 5 x 1/4" x 0'-4" 3/16" (2) 3/4"Ø C8 x 13.75 x 0'-8" 4 MW-8A 8" #5 32"o.c. (2) #4 48"o.c. (4) #5 (4) #5 MC-2 8" x 16" (4) #5 #3 AT 8"o.c. A
W 10, C10 3 x 5 x 5/16" x 0'-7" 1/4" (2) 3/4"Ø C12 x 20.7 x 1'-4" 6 HOOK HORIZ. W ALL REINFORCING AROUND VERTICAL
MW-8B 8" #5 32"o.c. (2) #4 32"o.c. (4) #5 (4) #5
W 12, C12 3 x 5 x 5/16" x 0'-9" 1/4" (3) 3/4"Ø C12 x 20.7 x 1'-4" 6 BARS AT ENDS OF W ALL SEGMENTS
W 14 3 x 5 x 5/16" x 0'-10" 1/4" (3) 3/4"Ø C15 x 33.9 x 2'-0" 12 MW-12A 12" #5 24"o.c. (2) #5 48"o.c. (4) #5 -- CONFIGURATION 'B' 670 EAST 1550 NORTH, LOGAN, UT
W 16 3 x 5 x 5/16" x 1'-0" 1/4" (4) 3/4"Ø C15 x 33.9 x 2'-0" 12 MW-6A 6" #4 16"o.c. (1) #4 16"o.c. -- -- SOLID GROUT
GROUT 84341
W 18 3 x 5 x 5/16" x 1'-3" 1/4" (5) 3/4"Ø (2) C12 x 20.7 x 2'-0" 12 MW-10A 10" #5 24"o.c. (1) #5 24"o.c. -- -- SOLID GROUT SOLID

1. AT THE CONTRACTORS OPTION, (2) C8 x 13.7 MAY BE SUBSTITUTED FOR THE C15 x 33.9. HSA PATTERN SHALL BE
RECONFIGURED & EQUALLY DISTRIBUTED BETW EEN THE TW O CHANNELS. CONFIGURATION 'C'
2. DOUBLE CHANNELS SHALL BE W ELDED TOGETHER W ITH A 2" STITCH W ELD EVERY 4" AT THE FLANGE TOE.
3. AT 6" MASONRY W ALL LOCATIONS USE (2) C8x13.75 CHANNELS IN LIEU OF C15x33.9 SPECIFIED IN TABLE. USE NOTES:
CONFIGURATION 'D'
3/4" DIA. x 3" HSAs RECONFIGURED AND EQUALLY DISTRIBUTED BETW EEN THE TW O CHANNELS. 1. AT BEAM/GIRDER BEARING LOCATIONS SEE
B NOTES:
TYPICAL DETAILS.
B
1. FOR ANY CMU W ALLS NOT SPECIFICALLY CALLED OUT IN PLANS, USE MW 1 p r o j e c t # : 21.0320
2. VERTICAL REINFORCING TO BE @ CENTERLINE OF W ALL UNLESS OTHERW ISE NOTED. 2. ALL HORIZONTAL W ALL REINFORCING (NOT
CONFIGURATION 'E' SHOW N FOR CLARITY) SHALL BE d a t e : 02.14.2023
3. SOLID GROUTING OF W ALLS IS UNACCEPTABLE EXCEPT W HERE SPECIFICALLY NOTED.
4. SEE STRUCTURAL NOTES FOR ADDITIONAL INFORMATION. CONTINUOUS THROUGH COLUMN
5. A BOND BEAM SHALL BE LOCATED IN THE FIRST COURSE ABOVE THE FOUNDATION IF VERTICAL DOW ELS HAVE 3. ALL VERTICAL BARS SHALL BE PLACED 2 1/2" revisions :

2 1/2"
BEEN BENT TO ALIGN W ITH VERTICAL CELLS, W HETHER OR NOT MASONRY W EBS HAVE BEEN CUT. FROM FACE OF CELL.
2 1/2"

title:

SCHEDULES
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

A A

sheet:

S011 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

STRUCTURAL STEEL SPECIAL INSPECTION SCHEDULE


ESTABLISHED PER 2018 IBC SECTION 1705.2.1
FABRICATOR SPECIAL INSPECTOR
INSPECTION TASKS PRIOR TO W ELDING (TABLE N5.4-1) QUALITY CONTROL QUALITY ASSURANCE NOTES INSPECTION TASKS PRIOR TO BOLTING (TABLE N5.6-1) CONTINUOUS PERIODIC CONTINUOUS PERIODIC NOTES
CONTINUOUS PERIODIC CONTINUOUS PERIODIC
W ELDER QUALIFICATION RECORDS AND CONTINUITY RECORDS MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS 1. PERIODIC - OBSERVE THESE ITEMS ON A RANDOM BASIS.
W ELDING PROCEDURE SPECIFICATIONS (W PSs) AVAILABLE FASTENERS MARKED IN ACCORDANCE W ITH ASTM REQUIREMENTS OPERATIONS NEED NOT BE DELAYED PENDING THESE
INSPECTIONS.
MANUFACTURER CERTIFICATIONS FOR W ELDING CONSUMABLES AVAILABLE 1. PERIODIC - OBSERVE THESE ITEMS ON A RANDOM BASIS. 2. CONTINUOUS - PERFORM THESE TASKS FOR EACH BOLTED
PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT
OPERATIONS NEED NOT BE DELAYED PENDING THESE CONNECTION.
MATERIAL IDENTIFICATION (TYPE / GRADE) LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE)
INSPECTIONS. 3. QUALITY CONTROL (QC) SHALL BE PROVIDED BY THE FABRICATOR
W ELDER IDENTIFICATION SYSTEM 1 2. CONTINUOUS - PERFORM THESE TASKS FOR EACH W ELDED JOINT PROPER BOLTING PROCEDURES SELECTED FOR JOINT DETAIL AND ERECTOR.
OR MEMBER. 4. QUALITY ASSURANCE (QA) SHALL BE PROVIDED BY OTHERS W HEN
E FIT-UP OF GROOVE W ELDS (INCLUDING JOINT GEOMETRY) 3. QUALITY CONTROL (QC) SHALL BE PROVIDED BY THE FABRICATOR CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE CONDITION REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ), E
* JOINT PREPARATION
AND ERECTOR. AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS APPLICABLE BUILDING CODE (ABC), PURCHASER, OW NER, OR 360 west aspen avenue
4. QUALITY ASSURANCE (QA) SHALL BE PROVIDED BY OTHERS W HEN ENGINEER OF RECORD (EOR). NONDESTRUCTIVE TESTING (NDT) salt lake city, utah 84101
* DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ), PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL SHALL BE PERFORMED BY THE AGENCY OR FIRM RESPONSIBLE
APPLICABLE BUILDING CODE (ABC), PURCHASER, OW NER, OR 801 532 4422
* CLEANLINESS (CONDITION OF STEEL SURFACES) OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED FOR QUALITY ASSURANCE, EXCEPT AS PERMITTED IN
ENGINEER OF RECORD (EOR). NONDESTRUCTIVE TESTING (NDT) ACCORDANCE W ITH SECTION N7.
* TACKING (TACK W ELD QUALITY AND LOCATION) SHALL BE PERFORMED BY THE AGENCY OR FIRM RESPONSIBLE PROPER STORAGE PROVIDED FOR BOLTS, NUTS, W ASHERS AND OTHER FASTENER 5. FOR SNUG-TIGHT JOINTS, PRE-INSTALLATION VERIFICATION
FOR QUALITY ASSURANCE, EXCEPT AS PERMITTED IN COMPONENTS TESTING AS SPECIFIED IN TABLE N5.6-1 AND MONITORING OF THE
* BACKING TYPE AND FIT (IF APPLICABLE) ACCORDANCE W ITH SECTION N6. INSTALLATION PROCEDURES AS SPECIFIED IN TABLE N5.6-2 ARE
5. QC AND QA INSPECTORS SHALL BE QUALIFIED IN ACCORDANCE NOT APPLICABLE. THE QCI AND QAI NEED NOT BE PRESENT
FIT-UP OF CJP GROOVE W ELDS OFHSS T-, Y-, AND K-JOINTS
W ITH AISC 360-16 CHAPTER N4. INSPECTION TASKS DURING BOLTING (TABLE N5.6-2) CONTINUOUS PERIODIC CONTINUOUS PERIODIC
W ITHOUT BACKING (INCLUDING JOINT GEOMETRY) DURING THE INSTALLATION OF FASTENERS IN SNUG-TIGHT JOINTS.
6. NONDESTRUCTIVE TESTING PERSONNEL SHALL BE QUALIFIED IN 6. FOR PRETENSIONED JOINTS AND SLIP-CRITICAL JOINTS, W HEN THE
FASTENER ASSEMBLIES, PLACED IN ALL HOLES AND W ASHERS (IF REQUIRED) ARE
* JOINT PREPARATIONS ACCORDANCE W ITH AISC 360-16 CHAPTER N4.3. INSTALLER IS USING THE TURN-OF-NUT METHOD W ITH
POSITIONED AS REQUIRED
7. NONDESTRUCTIVE TESTING OF W ELDED JOINTS SHALL COMPLY MATCHMARKING TECHNIQUES, THE DIRECT-TENSION-INDICATOR
* DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) W ITH AISC 360-16 CHAPTER N5.5a AND b.
JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONING METHOD, OR THE TW IST-OFF-TYPE TENSION CONTROL BOLT
* CLEANLINESS (CONDITION OF STEEL SURFACES) 8. OBSERVATION OF W ELDING OPERATIONS AND VISUAL INSPECTION METHOD, MONITORING OF BOLT PRETENSIONING PROCEDURES
OF IN-PROCESS AND COMPLETED W ELDS SHALL BE THE PRIMARY OPERATION
SHALL BE AS SPECIFIED IN TABLE N5.6-2. THE QCI AND QAI NEED
* TACKING (TACK W ELD QUALITY AND LOCATION) METHOD TO CONFIRM THAT THE MATERIALS, PROCEDURES AND NOT BE PRESENT DURING THE INSTALLATION OF FASTENERS
FASTENER COMPONENT NOT TURNED BY THE W RENCH PREVENTED FROM ROTATING
W ORKMANSHIP ARE IN CONFORMANCE W ITH THE CONSTRUCTION W HEN THESE METHODS ARE USED BY THE INSTALLER.
CONFIGURATION AND FINISH OF ACCESS HOLES
DOCUMENTS. FOR STRUCTURAL STEEL, ALL PROVISIONS OF AW S 7. FOR PRETENSIONED JOINTS AND SLIP-CRITICAL JOINTS, W HEN THE
D1.1 / D1.1M STRUCTURAL W ELDING CODE - STEEL FOR FASTENERS ARE PRETENSIONED IN ACCORDANCE W ITH THE RCSC SPECIFICATION, UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
FIT-UP OF FILLET W ELDS INSTALLER IS USING THE CALIBRATED W RENCH METHOD OR THE
STATICALLY LOADED STRUCTURES SHALL APPLY. PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOW ARD THE FREE DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
* DIMENSIONS (ALIGNMENT, GAPS AT ROOT) EDGES TURN-OF-NUT METHOD W ITHOUT MATCHMARKING, MONITORING NOT INTENDED FOR CONSTRUCTION, RECORDING
9. THERMALLY CUT SURFACES OF ACCESS HOLES SHALL BE TESTED OF BOLT PRETENSIONING PROCEDURES SHALL BE AS SPECIFIED PURPOSES, OR IMPLEMENTATION
* CLEANLINESS (CONDITION OF STEEL SURFACES) BY QA USING MT OR PT, W HEN THE FLANGE THICKNESS EXCEEDS IN TABLE N5.6-2. THE QCI AND QAI SHALL BE ENGAGED IN THEIR
2 IN. (50mm) FOR ROLLED SHAPES, OR W HEN THE W EB THICKNESS INSPECTION TASKS AFTER BOLTING (TABLE N5.6-3) CONTINUOUS PERIODIC CONTINUOUS PERIODIC ASSIGNED INSPECTION DUTIES DURING INSTALLATION OF
* TACKING (TACK W ELD QUALITY AND LOCATION) EXCEEDS 2 IN. (50mm) FOR BUILT-UP SHAPES. ANY CRACK SHALL FASTENERS W HEN THESE METHODS ARE USED BY THE INSTALLER.
BE DEEMED UNACCEPTABLE REGARDLESS OF SIZE OR LOCATION. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS
CHECK W ELDING EQUIPMENT 8. OBSERVATION OF BOLTING OPERATIONS SHALL BE THE PRIMARY
10. W HEN REQUIRED BY APPENDIX 3, TABLE A-3.1, W ELDED JOINTS METHOD USED TO CONFIRM THAT THE MATERIALS, PROCEDURES
1 THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY W HICH A WELDER W HO HAS WELDED A REQUIRING W ELD SOUNDNESS TO BE ESTABLISHED BY AND W ORKMANSHIP INCORPORATED IN CONSTRUCTION ARE IN
JOINT OR MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL BE THE LOW -STRESS TYPE. RADIOGRAPHICS OR ULTRASONIC INSPECTION SHALL BE TESTED CONFORMANCE W ITH THE CONSTRUCTION DOCUMENTS AND THE
BY QA AS PRESCRIBED. REDUCTION IN THE RATE OF UT IS PROVISIONS OF THE RCSC SPECIFICATION.
INSPECTION TASKS DURING W ELDING (TABLE N5.4-2) CONTINUOUS PERIODIC CONTINUOUS PERIODIC PROHIBITED.
11. REDUCTION OF RATE OF ULTRASONIC TESTING - THE RATE OF UT
CONTROL AND HANDLING OF W ELDING CONSUMABLES IS ONLY PERMITTED TO BE REDUCED IF APPROVED BY THE EOR GENERAL STEEL SPECIAL INSPECTION NOTES :
AND THE AHJ PER AISC 360-16 CHAPTER N5.5e.
* PACKAGING
12. FOR STRUCTURES IN RISK CATEGORY II, W HERE THE INITIAL RATE 1. QUALITY ASSURANCE (QA) INSPECTION OF FABRICATED ITEMS SHALL BE MADE AT THE FABRICATOR'S PLANT. THE QUALITY ASSURANCE INSPECTOR (QAI) SHALL SCHEDULE THIS W ORK TO MINIMIZE
* EXPOSURE CONTROL FOR UT IS 10%, THE NDT RATE FOR AN INDIVIDUAL W ELDER OR INTERRUPTION TO THE W ORK OF THE FABRICATOR.
W ELDING OPERATOR SHALL BE INCREASED TO 100% SHOULD THE 2. QA INSPECTION OF THE ERECTED STEEL SYSTEM SHALL BE MADE AT THE PROJECT SITE. THE QAI SHALL SCHEDULE THIS W ORK TO MINIMIZE INTERRUPTION TO THE W ORK OF THE ERECTOR.
D NO W ELDING OVER CRACKED TACK W ELDS REJECT RATE, THE NUMBER OF W ELDS CONTAINING 3. W HERE A TASK IS NOTED TO BE PERFORMED BY BOTH QC AND QA, IT IS PERMITTED TO COORDINATE THE INSPECTION FUNCTION BETW EEN THE QCI AND QAI SO THAT THE INSPECTION FUNCTIONS ARE
D
ENVIRONMENTAL CONDITIONS UNACCEPTABLE DEFECTS DIVIDED BY THE NUMBER OF W ELDS PERFORMED BY ONLY ONE PARTY. W HERE QA RELIES UPON INSPECTION FUNCTIONS PERFORMED BY QC, THE APPROVAL OF THE ENGINEER OF RECORD AND THE AUTHORITY HAVING JURISDICTION IS
COMPLETED, EXCEEDS 5% OF THE W ELDS TESTED FOR THE REQUIRED.
* W IND SPEED W ITHIN LIMITS W ELDER OR W ELDING OPERATOR. A SAMPLING OF AT LEAST 20 4. THE FABRICATOR'S QCI SHALL INSPECT THE FABRICATED STEEL TO VERIFY COMPLIANCE W ITH THE DETAILS SHOW N ON THE SHOP DRAW INGS, SUCH AS PROPER APPLICATION OF JOINT DETAILS AT EACH
* PRECIPITATION AND TEMPERATURE COMPLETED W ELDS FOR A JOB SHALL BE MADE PRIOR TO CONNECTION. THE ERECTOR'S QCI SHALL INSPECT THE ERECTED STEEL FRAME TO VERIFY COMPLIANCE W ITH THE DETAILS SHOW N ON THE ERECTION DRAW INGS, SUCH AS BRACES, STIFFENERS,
IMPLEMENTING SUCH AN INCREASE. W HEN THE REJECT RATE FOR MEMBER LOCATIONS AND PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION.
W PS FOLLOW ED THE W ELDER OR W ELDING OPERATOR, AFTER A SAMPLING OF AT 5. THE QAI SHALL BE ON THE PREMISES FOR INSPECTION DURING THE PLACEMENT OF ANCHOR RODS AND OTHER EMBEDMENTS SUPPORTING STRUCTURAL STEEL FOR COMPLIANCE W ITH THE
* SETTINGS ON W ELDING EQUIPMENT LEAST 40 COMPLETED W ELDS, HAS FALLEN TO 5% OR LESS, THE CONSTRUCTION DOCUMENTS. AS A MINIMUM, THE DIAMETER, GRADE, TYPE AND LENGTH OF THE ANCHOR ROD OR EMBEDDED ITEM, AND THE EXTENT OR DEPTH OF EMBEDMENT INTO THE CONCRETE,
RATE OF UT SHALL BE RETURNED TO 10%. FOR EVALUATING THE SHALL BE VERIFIED PRIOR TO PLACEMENT OF THE CONCRETE.
* TRAVEL SPEED REJECT RATE OF CONTINUOUS W ELDS OVER 3 FT (1M) IN LENGTH 6. THE QAI SHALL INSPECT THE FABRICATED STEEL OR ERECTED STEEL FRAME, AS APPROPRIATE, TO VERIFY COMPLIANCE W ITH THE DETAILS SHOW N ON THE CONSTRUCTION DOCUMENTS, SUCH AS
W HERE THE EFFECTIVE THROAT IS 1 IN. (25mm) OR LESS, EACH 12 BRACES, STIFFENERS, MEMBER LOCATIONS AND PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION.
* SELECTED W ELDING MATERIALS
IN. (300mm) INCREMENT OR FRACTION THEREOF SHALL BE 7. QUALITY ASSURANCE (QA) INSPECTIONS, EXCEPT NONDESTRUCTIVE TESTING (NDT), MAY BE W AIVED W HEN THE W ORK IS PERFORMED IN A FABRICATING SHOP OR BY AN ERECTOR APPROVED BY THE
* SHIELDING GAS TYPE / FLOW RATE CONSIDERED AS ONE W ELD. FOR EVALUATING THE REJECT RATE AUTHORITY HAVING JURISDICTION (AHJ) TO PERFORM THE W ORK W ITHOUT QA. NDT OF W ELDS COMPLETED IN AN APPROVED FABRICATOR'S SHOP MAY BE PERFORMED BY THAT FABRICATOR W HEN
ON CONTINUOUS W ELDS OVER 3 FT (1M) IN LENGTH W HERE THE APPROVED BY THE AHJ. W HEN THE FABRICATOR PERFORMS THE NDT, THE QA AGENCY SHALL REVIEW THE FABRICATOR'S NDT REPORTS.
* PREHEAT APPLIED EFFECTIVE THROAT IS GREATER THAN 1 IN. (25mm), EACH 6 IN. 8. AT COMPLETION OF FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE AHJ STATING THAT THE MATERIALS SUPPLIED AND W ORK PERFORMED BY THE
* INTERPASS TEMPERATURE MAINTAINED (MIN. / MAX) (150mm) OF LENGTH OR FRACTION THEREOF SHALL BE FABRICATOR ARE IN ACCORDANCE W ITH THE CONSTRUCTION DOCUMENTS. AT COMPLETION OF ERECTION, THE APPROVED ERECTOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE AHJ STATING
CONSIDERED ON W ELD. THAT THE MATERIALS SUPPLIED AND W ORK PERFORMED BY THE ERECTOR ARE IN ACCORDANCE W ITH THE CONSTRUCTION DOCUMENTS.
* PROPER POSITION (F, V, H, OH) 13. ALL NDT PERFORMED SHALL BE DOCUMENTED. FOR SHOP 9. IDENTIFICATION AND REJECTION OF MATERIAL OR W ORKMANSHIP THAT IS NOT IN CONFORMANCE W ITH THE CONSTRUCTION DOCUMENTS, SHALL BE PERMITTED AT ANY TIME DURING THE PROGRESS OF
W ELDING TECHNIQUES FABRICATION, THE NDT REPORT SHALL IDENTIFY THE TESTED THE W ORK. HOW EVER, THIS PROVISION SHALL NOT RELIEVE THE OW NER OR THE INSPECTOR OF THE OBLIGATION FOR TIMELY, IN-SEQUENCE INSPECTIONS. NONCONFORMING MATERIAL AND
W ELD BY PIECE MARK AND LOCATION IN THE PIECE. FOR FIELD W ORKMANSHIP SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE FABRICATOR OR ERECTOR, AS APPLICABLE.
* INTERPASS AND FINAL CLEANING W ORK, THE NDT REPORT SHALL IDENTIFY THE TESTED W ELD BY 10. NONCONFORMING MATERIAL OR W ORKMANSHIP SHALL BE BROUGHT INTO CONFORMANCE, OR MADE SUITABLE FOR ITS INTENDED PURPOSE AS DETERMINED BY THE ENGINEER OF RECORD.
* EACH PASS W ITHIN PROFILE LIMITATIONS LOCATION IN THE STRUCTURE, PIECE MARK, AND LOCATION IN THE 11. CONCURRENT W ITH THE SUBMITTAL OF SUCH REPORTS TO THE AHJ, EOR OR OW NER, THE QA AGENCY SHALL SUBMIT TO THE FABRICATOR AND ERECTOR:
PIECE. W HEN A W ELD IS REJECTED ON THE BASIS OF NDT, THE (1) NONCONFORMANCE REPORTS
* EACH PASS MEETS QUALITY REQUIREMENTS NDT RECORD SHALL INDICATE THE LOCATION OF THE DEFECT AND (2) REPORTS OF REPAIR, REPLACEMENT OR ACCEPTANCE OF NONCONFORMING ITEMS.
THE BASIS OF REJECTION
PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS
14. DEMAND CRITICAL W ELDS SHALL MEET THE PROVISION FOUND IN
INSPECTION TASKS AFTER W ELDING (TABLE N5.4-3) CONTINUOUS PERIODIC CONTINUOUS PERIODIC AISC 341-16 AND W ELDING METHODS, PROCEDURES AND QUALITY
CONTROL SHALL COMPLY W ITH AW S D1.1 AND THE FOLLOW ING:
W ELDS CLEANED a. ARC STRIKES, GOUGES AND OTHER IMPERFECTIONS W ITHIN
OR ADJACENT TO THE JOINT, SHALL BE REPAIRED OR
SIZE, LENGTH AND LOCATION OF W ELDS REMOVED.
W ELDS MEET VISUAL ACCEPTANCE CRITERIA b. PREHEAT AND INTER-PASS REQUIREMENTS AS OUTLINED IN
SECTION 3.5. THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
* CRACK PROHIBITION c. UNREPAIRED CRACKS, GOUGES, AND NOTCHES W ILL NOT BE ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
* W ELD / BASE-METAL FUSION PERMITTED IN THE JOINT AREA.
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
d. USE ELECTRODES W ITH CHARPY V-NOTCH ABSORBED WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
* CRATER CROSS SECTION ENERGY EQUAL TO OR GREATER THAN 20 FT-LBS AT 20 WRITTEN PERMISSION FROM METHOD STUDIO INC.
DEGREES FAHRENHEIT UNDER AW S A5 CLASSIFICATION TEST
C * W ELD PROFILES
METHODS, AND 40 FT-LBS AT 70 DEGREES FAHRENHEIT USING
C
* W ELD SIZE TEST PROCEDURES PRESCRIBED IN APPENDIX X OF AISC 358.
ACCEPTABLE ELECTRODES INCLUDE E70TG-K2, E71 T-1.
project:
* UNDERCUT
* POROSITY
ARC STRIKES USU EVR
K-AREA 1

W ELD ACCESS HOLES IN ROLLED HEAVY SHAPES AND BUILT-UP


HEAVY SHAPES 2
EXPANSION
BACKING REMOVED AND W ELD TABS REMOVED (IF REQUIRED)
REPAIR ACTIVITIES
DOCUMENT ACCEPTANCE OR REJECTION OF W ELDED JOINT OR MEMBER

NO PROHIBITED W ELDS HAVE BEEN ADDED W ITHOUT THE


APPROVAL OF THE EOR

1 WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA,
VISUALLY INSPECT THE W EB K-AREA FOR CRACKS WITHIN 3 IN. (75mm) OF THE W ELD)
2 AFTER ROLLED HEAVY SHAPES (SEE SECTION A3.1c) AND BUILT-UP HEAVY SHAPES (SEE SECTION A3.1d) ARE W ELDED,

VISUALLY INSPECT THE W ELD ACCESS HOLE FOR CRACKS.

670 EAST 1550 NORTH, LOGAN, UT


EXTENDED PLATE BOLTED CONNECTION SCHEDULE BEAM CONNECTION SCHEDULE 84341
FULL DEPTH STIFFENER PLATES SHEAR PLATE INFORMATION
BETW EEN COLUMN FLANGES AT BOLTS
PL. DIMENSIONS SHEAR PLATE INFORMATION BOLTS W / STANDARD
TOP & BOTTOM OF SHEAR-PLATE. BEAM W ELD
W / SHORT- 'A' W ASHERS OVER W ELD
3/8" @ W 10 & SMALLER COLS. UNO. DEPTH Lev Leh BEAM PL. DIMENSIONS COMMENTS
SLOTTED No. Ø SIZE SLOTS 'A'
1/2" @ W 12 & W 14 COLS. UNO. DEPTH W / SHORT- Lev Leh
HOLES
5/8" @ W 16 & W 18 COLS. UNO. SLOTTED HOLES No. SIZE

B W BEAM -SEE PLAN C8, W 8, W 10 PL. 3/8" x REQ'D 1 1/2" 2" 2 3/4" 1/4" B
1/2" W 8, W 10 PL. 1/4" x REQ'D 1 1/2" 2" 2 3/4" Ø 3/16" p r o j e c t # : 21.0320
1 1/2" TYP.
W 12, W 14 PL. 3/8" x REQ'D 1 1/2" 2" 3 7/8" 1/4" W 12, W 14 PL. 5/16" x REQ'D 1 1/2" 2" 3 3/4" Ø 1/4" d a t e : 02.14.2023
Leh
EQ.

W 16 PL. 3/8" x REQ'D 1 3/4" 2" 4 1" 1/4" W 16 PL. 5/16" x REQ'D 1 1/2" 2" 4 3/4" Ø 1/4" revisions :
PL. 5/16" x REQ'D
Lev

W 18 1 1/2" 2" 5 3/4" Ø 1/4"


W 18 PL. 3/8" x REQ'D 1 3/4" 2" 5 1" 1/4"
W 21 PL. 5/16" x REQ'D 1 1/2" 2" 6 3/4" Ø 1/4"
3" TYP.

W 21 PL. 3/8" x REQ'D 1 3/4" 2" 6 1" 1/4"


W 24 PL. 3/8" x REQ'D 1 1/2" 2" 7 7/8" Ø 1/4"
W 24 PL. 1/2" x REQ'D 1 3/4" 2" 7 1" 1/4" W 27 PL. 3/8" x REQ'D 1 1/2" 2" 7 7/8" Ø 1/4"
Lev

W 27 W 30 PL. 1/2" x REQ'D 1 3/4" 2" 8 1" Ø 5/16"


PL. 1/2" x REQ'D 1 3/4" 2" 7 1" 1/4"
EQ.

W 33 PL. 1/2" x REQ'D 1 3/4" 2" 9 1" Ø 5/16"


W 30 PL. 5/8" x REQ'D 2" 2 1/4" 8 1-1/8" 5/16"
W 36 PL. 1/2" x REQ'D 2" 2 1/4" 10 1-1/8" Ø 5/16"
SHORT-SLOTTED
HOLES IN SHEAR W 33 PL. 5/8" x REQ'D 2" 2 1/4" 9 1-1/8" 5/16"
PLATE
W 36 PL. 5/8" x REQ'D 2" 2 1/4" 10 1-1/8" 5/16"
title:
FACE OF COLUMN / BEAM
SHEAR PL. - SEE SCHEDULE W EB

SEE SCHED.
SCHEDULES
'A'
Leh Leh
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

1/2"
FACE OF COLUMN W EB

Lev
SHEAR PL. - SEE SCHEDULE

3" TYP.
SHORT-SLOTTED HOLES IN
A SHEAR PLATE W / W ASHER A
PER THE STRUCTURAL NOTES

Lev
W BEAM - SEE PLAN sheet:

'A'
SEE SCHED.

S012 BID SET


1 2 3 4 5 6
1 2 3 4 5 6
FOOTING & FOUNDATION NOTES :

1. SEE SHEET S001 FOR GENERAL STRUCTURAL NOTES.


2. ALL FOOTINGS SHALL BE PLACED ON SOIL W HICH HAS BEEN PREPARED FOR THE BEARING PRESSURE
SHOW N IN THE STRUCTURAL NOTES.
3. VERIFY ALL DIMENSIONS W ITH DRAW INGS AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOUND.
4. SOLID GROUT ALL MASONRY COURSES BELOW FINISHED FLOOR OR EXTERIOR GRADE (W HICHEVER IS
1 1.2 2 3 4 5 HIGHER).
5. SEE SHEET S002 FOR FOOTING SCHEDULE.
6. PROVIDE DOW ELS IN FOOTINGS / FOUNDATIONS TO MATCH VERTICAL W ALL REINFORCING U.N.O.
7. SEE SHEET S201 FOR TYPICAL FOOTING AND FOUNDATION DETAILS.
8. ALL EXTERIOR W ALL FOOTINGS TO BEAR A MINIMUM DIMENSION BELOW EXTERIOR GRADE AS NOTED
G G 9.
IN GENERAL STRUCTURAL NOTES.
FOUNDATION W ALLS ARE DESIGNED AND DETAILED FOR THE COMPLETED CONDITION. CONTRACTOR
IS RESPONSIBLE FOR MEANS AND METHODS OF CONSTRUCTION. BACKFILLED W ALLS SHALL BE
ADEQUATELY BRACED DURING CONSTRUCTION AND BACKFILLING TO PRODUCE PLUMB AND TRUE
FINISHED W ALLS.
E 10. ALL ANCHORS, HOLDOW NS, ANCHOR BOLTS, DOW ELS, EMBEDDED ITEMS, ETC. SHALL BE HELD IN E
PLACE PRIOR TO AND DURING CONCRETE AND/OR GROUT PLACEMENT. 360 west aspen avenue
11. COORDINATE ALL FOOTING DEPTHS (INTERIOR AND EXTERIOR) W ITH DRAINS, CONDUITS, ETC. THAT
MAY INTERFERE W ITH FOOTINGS.
salt lake city, utah 84101
12. EXISTING ELECTRICAL CONDUIT BOX AND LINES TO REMAIN. CONTRACTOR TO COORDINATE DEPTH 801 532 4422
AND LOCATIONS OF CONDUIT RUNS W ITH NEW FOOTINGS. STEP FOOTINGS AS REQUIRED SO THAT
CONDUIT IS RUNNING THROUGH FOUNDATION W ALL PER DETAIL 3/S201.
13. SEE SHEET S011 FOR TYPICAL MASONRY W ALL REINFORCING INFORMATION. PROVIDE MASONRY
JAMBS AND BEAMS AROUND ALL OPENINGS, PER SCHEDULE, UNLESS NOTED OTHERW ISE ON PLANS.

CONCRETE SLAB NOTES :

1. SLAB ON GRADE SHALL BE PER THE FOLLOW ING:


A. SLAB ON GRADE BETW EEN GRIDS 1 AND 4 SHALL BE 6" THICK UNREINFORCED CONCRETE. SLAB
5 SHALL BE INSTALLED ON 5" OF AGGREGATE BASE AND PROPERLY PREPARED SUBGRADE TO MEET
PROVIDE 2" GAP BETW EEN THE REQUIREMENTS FOR RIGID PAVEMENT AS OUTLINED IN THE GEOTECHNICAL REPORT.
S210
MASONRY W ALLS FC2 B. SLAB ON GRADE BETW EEN GRIDS 4 AND 5 SHALL BE 4" THICK UNREINFORCED CONCRETE. SLAB
98' - 0" SHALL BE UNDERLAIN BY FREE DRAINING MATERIAL AS PRESCRIBED IN THE GEOTECHNICAL
REPORT.
MW -8A 2. SEE SHEET S201 FOR CONTROL AND CONSTRUCTION JOINT INFORMATION.
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
PIT NOTES :
NOT INTENDED FOR CONSTRUCTION, RECORDING
FC2 PURPOSES, OR IMPLEMENTATION
1. SEE SHEET S001 FOR GENERAL STRUCTURAL NOTES.
98' - 0" 2. ALL CONCRETE REINFORCEMENT AT PITS SHALL BE FRP (FIBER REINFORCED POLYMER) BARS

MW -8A
4 CONFORMING TO ASTM D7957.
C

4
TYP.

1/

F
3. GRATING AT PIT LOCATIONS SHALL BE THE FOLLOW ING (OR AN APPROVED EQUAL).

W O
5X
S210 FC3 S110 A. 3" DEEP FIBERGRATE FRP HIGHLOAD PULTRUDED GRATING - MODEL H13730.

D GE
5X

A T J -5
SS

IN D
98' - 0"

O
W E
FC3

H
MW -12A 98' - 0"

6' - 6"
F 8
S210
F

F
W O
D GE
A T J -3
IN D
M

O
W E
4' - 0"

MW-8B
TYP. AT 7
EXISTING BUILDING FOOTING
NOTE: COORDINATE FOOTING
D AND MASONRY W ALL ELEVATOR S210 S S
DEPTH AT THIS LOCATION W /
D
PROVIDE 2" GAP BETW EEN 1 ELEVATOR PIT REQUIREMENTS
1
MASONRY W ALLS S210
S210 PROVIDE 2" GAP BETW EEN MW -8A

T.O.FOUNDATION
MASONRY W ALLS

W ALL = 100'-0"
FC4
E E

16

16
FC2 F4

5/

5/
FC3 99' - 4"

6X

6X
6X

6X
99' - 4"

S
98' - 0"
99' - 4" F6

SS

SS
MW -8B

H
S

D MW -8A 99' - 4"


D

T.O.FOUNDATION
W ALL = 102'-0"
M
M

S
C
J-

J-

BE

-2
S

3
S S

LO
S S

W
FC3 6 FC3

BE
TYP.

AM
S S 98' - 0" S210 FC3 98' - 0"
S S 9
99' - 4"
SEE FOOTING AND S S

8
S210

3/
FOUNDATION NOTE 12 FC2

5X
SEE FOOTING AND

5X
99' - 4" S S FOUNDATION NOTE 12

SS
4
MW -8A

H
1/
4X
S S

4X
SS
H
MW -8A S S
FC3

MW -8B
NOTE: INSTALL FOOTING
F5.5 AT THIS LOCATION 98' - 0"
FC2 TYP. AT INTERIOR -- THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
FC2 F3 BELOW EXISTING
98' - 0" MASONRY W ALLS CONDUIT RUN ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
99' - 4" 6 99' - 0" MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
6 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
S210

8
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS

3/
S210

5X
TYP. AT INTERIOR WRITTEN PERMISSION FROM METHOD STUDIO INC.

5X
C MASONRY W ALLS C

SS
H
FC3 project:
99' - 4"

TYP.
4
S210 F6
USU EVR
3 99' - 0"
EXPANSION
MW -12A

9 TYP.
SEE PIT NOTE 3 FOR S210

8
3/
8
GRATING INFO.

5X
S210 10

3/
6X

5X
TYP.
2

2
X7

X7

X7

6X

SS
F358 S210
12

12

12

SS

H
W

H
95' - 0"

C 11 C
S210

F5 F5
F6 F6
98' - 0" TYP. AT INTERIOR 99' - 0" C
99' - 0" 99' - 4"
GRATING SUPPORT
M

S301
(REMOVABLE BEAM)
J-
5

MW -8A
13
HSS8X8X3/8

S210
TYP. AT PIT FC3
2 98' - 0"
12 TYP. 670 EAST 1550 NORTH, LOGAN, UT
12

8
SEE PIT NOTE 3 FOR S210

3/
A S210 TYP. 84341

5X
GRATING INFO. S210

5X
S301

SS
H
15 AT BEAM 8
SUPPORT
3/
S210
6X
2

2
X7

X7

X7

6X
M

B F6 B
C

12

12

12

SS
-1

p r o j e c t # : 21.0320
H

99' - 0"

B B d a t e : 02.14.2023
F7
98' - 0"
F7.5
99' - 0"
revisions :
F358
F6 95' - 0"

8
3/
99' - 0"

5X
5X
9

SS
H
S210
A
TYP. AT 5 S110
OPENING S210
F6
99' - 0"
5

title:
J-
M

FOOTING
16

14
5/
5X

S210
5X

FC2
SS

2
-2

AND
J-
C

98' - 0"
H

M
M
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

A A
MW -12A
FC2
MW -8A

FC3
FOUNDATION
4 F5.5 10
S210
TYP.
98' - 0"
98' - 0"
MW -12A MW -8A
98' - 0"
S210 PLAN
A B T.O.FOUNDATION T.O.FOUNDATION A
1 2 3 S301
4 W ALL = 100'-0" W ALL = 102'-0"
5

sheet:

FOOTING AND FOUNDATION PLAN


SCALE : 1/8" = 1'-0"
A
S101
S101 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

FLOOR FRAMING NOTES :

1. SEE SHEET S001 FOR GENERAL STRUCTURAL NOTES


2. CONCRETE FLOOR SLABS SHALL CONSIST OF A CONCRETE SLAB ON METAL DECK AS INDICATED IN
THE GENERAL STRUCTURAL NOTES. SLAB THICKNESS IS TOTAL FROM BOTTOM OF DECK TO TOP OF
1 1.2 2 3 4 5 CONCRETE. THE W ELDED W IRE FABRIC SHALL BE PLACED AT THE APPROXIMATE CENTERLINE OF THE
CONCRETE DEPTH OVER THE TOP FLUTE OF THE FORMLOK DECK.
3. ( ) DENOTES QUANTITY OF 3/4" DIAMETER X 4 1/2" LONG HSA ALONG BEAM TOP FLANGE.
4. c = DENOTES AMOUNT OF CAMBER IN W F BEAM AT MIDSPAN.
5. PROVIDE TYPICAL SLAB CLOSURE AT ALL OPENINGS AND SLAB EDGES AS PER DETAIL 8/S220. TYPICAL
G G 6.
UNLESS NOTED OTHERW ISE. SEE DETAIL 3/S202 FOR TYPICAL FRAMING AT SLAB OPENINGS.
SEE ARCHITECTURAL DRAW INGS FOR FINISHED FLOOR ELEVATIONS.
7. SEE S003 FOR MASONRY BEAM/LINTEL SCHEDULE.
8. W HERE STEEL FLOOR DECK RUNS PERPENDICULAR TO BEAMS W ITH HSA, HSA SHALL BE FIELD
W ELDED TO BEAMS THRU DECK MATERIAL.
9. W HERE STEEL FLOOR DECK RUNS PARALLEL TO BEAMS W ITH HSA, A 2-1/2" X CONTINUOUS EXPOSED
BEAM FLANGE SURFACE IS REQUIRED FOR CONCRETE COVER OF HSA.
E 10. DO NOT PROVIDE CONTROL JOINTS IN SUSPENDED CONCRETE SLABS. E
11. CONSTRUCTION JOINTS IN SLABS ON DECK SHALL NOT BE CLOSER THAN 12" TO HSA. 360 west aspen avenue
12. AT NON-COMPOSITE BEAMS AND JOISTS AND W HERE HSA’S ARE SPACED AT MORE THAN 12” O.C., salt lake city, utah 84101
W ELD DECK TO SUPPORT W ITH 3/4" DIAMETER PUDDLE W ELDS AT 12" O.C.
13. INDICATES LOCATION OF EXTERIOR FLOOR SYSTEM CONSISTING OF EITHER GRAVEL OR PAVER 801 532 4422
NOTE: AT PARAPET ALONG EXTERIOR OF SYSTEM W ITH MAXIMUM W EIGHT = 25psf. SEE ARCHITECTURAL DRAW INGS FOR ADDITIONAL
ROOF TERRACE, PROVIDE (2) #4 BARS AT INFORMATION.
TOP OF W ALL. PLACE BARS AT FACE OF
HSS2X2X1/4 INTERIOR W ALL TO ALLOW FOR GUARDRAIL TO BE CRANE NOTES :
CANOPY FRAMING, TYP. INSTALLED BETW EEN BARS. SEE ARCH
5 TYP. AT DRAW INGS FOR ADD. INFO. 1. COLUMNS AND RAIL SUPPORTS HAVE BEEN DESIGNED FOR THE FOLLOW ING:
HSS8X2X3/16 PERIMETER S220 BEAM A. 5 TON CRANE HOIST CAPACITY
CANOPY FRAMING, TYP. SEE DETAIL 4/S220 FOR CONCRETE B. RAIL SUPPORTS W ITH W EIGHT LESS THAN 100 PLF
SLAB CONDITION ALONG W ALL. C. BRIDGE CRANE BEAM W ITH MAXIMUM W EIGHT = 5000#
COORDINATE ROOFING SYSTEM 2. SEE DETAILS 12 AND 13/S220 FOR RAIL SUPPORT STRUCTURE ITEMS TO BE INSTALLED NOW AND
NOTE: SEE DETAIL ABOVE DECKING W / ARCH REQUIRED IN FUTURE.
17/S230 FOR CANOPIES DRAW INGS
MB-8B
SEE DETAIL 5/S220 FOR CONCRETE
SLAB CONDITION ALONG THIS W ALL.
COORDINATE ROOFING SYSTEM UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
ABOVE DECKING W / ARCH NOT INTENDED FOR CONSTRUCTION, RECORDING

W 12X14

W 12X14

W 12X14
DRAW INGS PURPOSES, OR IMPLEMENTATION

SHIPS LADDER TO ROOF C


ABOVE - SEE ARCH S110
2"BUILDING SEPARATION
JOINT ALONG EXISTING
W ALL W 16X36
F INFILL EXISTING OPENING
F
IN MASONRY W ALL PER
DETAIL 7/S202 14 8
S220 TYP.
W 12X14 S220

W 12X19
15
S220

W 14X26

W 14X26

W 14X26

W 14X26

W 21X57
D D
W 12X19
SEE FLOOR FRAMING
NOTE 13
4 5 TYP. AT
TYP.
E E

MB-8B
BEAM W 12X19 (8)
S220 S220

MB-8C
D D
16 MC-2 ABOVE 2nd FLOOR

(2) EQ SPACES
S220

W 14X26 (10)
W 14X22 (12) W 14X22 (10)
1
W 12X19 (10)

W 12X19 (10)

W 12X19 (10)

W 12X19 (10)

W 12X19 (10)

W 12X19 (10)

W 12X19 (10)
TYP.
S220
3
TYP.
S202

3
TYP. W 14X22 (12) W 14X22 (10)
S220

TYP. 4 6
BETW EEN TYP.

(2) EQ SPACES
BEAMS S220

W 14X26 (10)
S220
5 TYP. AT 1
TYP. D W 14X22 (12) W 14X22 (10)
S220 BEAM S220
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
S110 ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
(8) EQ SPACES MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C W 14X26 (15) W 14X22 (10) C
TYP. AT 5
BEAMS S220 1 2 3 4 project:

(2) EQ SPACES
USU EVR

W 14X26 (10)
W 14X22 (10) W 14X22 (12)

S220
4 TYP.
BETW EEN
BEAM
W 18X76 CRANE RAIL
12
S220
TYP. AT RAIL
SUPPORT W 18X76 CRANE RAIL
EXPANSION
SUPPORT BRACKET SUPPORT BRACKET

W 14X22 (10) W 14X22 (12)


C C C
FUTURE CRANE RAIL (BY OTHERS)
17 C
13
S301 TYP.
S220 W 14X22 (10) W 14X22 (12) S220

(3) EQ SPACES
W 16X36 (20)
W 14X22 (10) W 14X22 (12)
W 18X40

5 TYP. AT
A S220 BEAM
S301 670 EAST 1550 NORTH, LOGAN, UT
84341
W 14X22 (10) W 14X22 (12)

W 18X76 CRANE RAIL W 18X76 CRANE RAIL


7
6 SUPPORT BRACKET SUPPORT BRACKET
S220 TYP.
S220
W 14X22 (10) W 14X22 (12) FUTURE CRANE RAIL (BY OTHERS)

(3) EQ SPACES
B B
W 16X36 (20)

B B B p r o j e c t # : 21.0320

B d a t e : 02.14.2023
13 12
S110 W 14X22 (10) W 14X22 (12)
S220
TYP. TYP. AT RAIL
SUPPORT
revisions :
S220

8
TYP. W 14X22 (10) W 14X22 (12)
S220
W 21X57 (32)

W10X22

W 10X22

W 14X22 (10) W 14X22 (12)


CRANE FRAMING PLAN B

(3) EQ SPACES
W 16X36 (20)

W 10X22 SCALE : 1/8" = 1'-0"


S102
W10X22

W 14X22 (10) W 14X22 (12) title:


10' - 0"
SECOND
A A FLOOR
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

MB-8B

3
S220
TYP.
FRAMING
B PLAN
A 1 2 3 S301
4 5 A

sheet:
SECOND FLOOR FRAMING PLAN A
S102
S102
SCALE : 1/8" = 1'-0"

BID SET
1 2 3 4 5 6
1 2 3 4 5 6

ROOF FRAMING NOTES :

1. SEE SHEET S001 FOR GENERAL STRUCTURAL NOTES.


2. GENERAL CONTRACTOR SHALL VERIFY MECHANICAL EQUIPMENT W EIGHTS, DIMENSIONS, AND
LOCATIONS W / MECHANICAL AND REFRIGERATION CONTRACTORS PRIOR TO ORDERING/FABRICATING
JOISTS.
3. ( ### / ### ) DENOTES APPLIED TOTAL AND LIVE UNIFORMLY DISTRIBUTED LOADS IN POUNDS PER
LINEAR FOOT OF JOIST, RESPECTIVELY.
4. JOISTS SUPPORTING MECHANICAL EQUIPMENT SHALL BE DESIGNED FOR ADDITIONAL LOADS
INDICATED.
1 1.2 2 3 4 5 5. W HERE JOIST AXIAL LOADS ARE SHOW N ON THE PLANS (XX.X(W )) OR (XX.X(E)), LOADS ARE ASD LEVEL
LOADS
6. SNOW DRIFT LOADS INDICATED ON FRAMING PLANS SHALL BE APPLIED IN ADDITION TO UNIFORMLY
DISTRIBUTED LOADS INDICATED PER NOTE 3.
7. PROVIDE ADDED HORIZONTAL AND VERTICAL JOISTS LOADS W HERE INDICATED ON PLAN OR DETAILS.
G 8.
9.
JOISTS AND GIRDERS SHALL BE DESIGNED FOR 11 PSF NET W IND UPLIFT.
SEE ROOF DECK SCHEDULE FOR REQUIRED DECK AND ATTACHMENTS.
E 10. SEE SHEET S201 FOR OPENINGS IN ROOF DECK. SEE MECHANICAL AND ARCHITECTURAL DRAW INGS E
FOR EXACT LOCATIONS. 360 west aspen avenue
11. CONTRACTOR SHALL ERECT AND MAINTAIN ADEQUATE TEMPORARY BRACING UNTIL ALL ROOF salt lake city, utah 84101
FRAMING AND DECK ATTACHMENTS ARE COMPLETE.
12. CONCENTRATED LOADS FROM EQUIPMENT, PIPING, ETC., SHALL NOT BE HUNG FROM JOISTS EXCEPT 801 532 4422
AT PANEL POINTS AND AS APPROVED BY THE ENGINEER.
13. JOIST BRIDGING DESIGN AND LOCATION BY JOIST MANUFACTURER.
14. ANY CONCENTRATED LOAD ON JOIST CHORDS (INCLUDING FRAMING ANGLES) NOT LOCATED W ITHIN 6"
OF A PANEL POINT REQUIRE (2) L 2" X 2" X 1/4" FROM THE POINT LOAD TO THE NEAREST OPPOSITE
CHORD PANEL POINT (CONTRACTOR SUPPLIED AND INSTALLED).
15. ANY ROOF SUPPORTED PIPING 6" OR LARGER RUNNING PARALLEL TO JOIST SHALL BE SUPPORTED BY
TW O OR MORE JOISTS.
16. ALL JOISTS TO HAVE 5" JOIST BEARING SEAT.
17. 'SS' INDICATES SEISMIC STRAP LOCATIONS. SEE DETAIL 11/S230.

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
EXISTING ROOF JOISTS NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

(4) EQ SPACES

5 TYP. AT 2 CONTINUE BEAM REINFORCING


TYP.
S220 BEAM S230 AROUND CORNER AND MAKE
BEAMS INTEGRAL
ROOF HATCH - SEE ARCH
MB-12C
F

W8X10

MB-8C
W8X10 8

W8X10

W8X10
D TYP. D
S230

W 12X14
15 W12X14
TYP.
S230
W 8X10 ELEVATOR HOIST BEAM

W 12X19

W 12X14
W 12X19
SIM. AT W BEAM METAL STUD W ALL FRAMING - BELOW - COORDINATE ELEVATION
SEE ARCH AND STRUCTURAL AND LOCATION W / ELEVATOR
13 13 NOTES (DEFERRED MANUF. ATTACH BEAM TO
S230 2" BUILDING SEPARATION JOINT S230 SUBMITTAL) MASONRY W ALLS PER DETAIL 5/S220

TYP.

W 10X12
15
E

MB-8B
1
S230
S230

W 18X35 D

61 PSF
C12X20.7 14
17 S230
S220

12' - 4"
200# ADD 200# ADD 1
TYP.
S230

0 PSF
3000# ADD (BID ALT. #1)
1500# ADD
(BELOW ROOF) 2 TYP. AT SNOW DRIFT - SEE ROOF
S230 JOIST (HIGH) FRAMING NOTE 6
HSS12X2X3/16 PERIMETER
CANOPY FRAMING, TYP. 32LH (330/180) THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &

(9) EQ SPACES
32LH (535/390)

32LH (380/235)

32LH (340/195)

32LH (465/320)
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
11 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
TYP.
26K (E)

26K (E)
S201 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
NOTE: SEE DETAIL 2 TYP.
17/S230 FOR CANOPIES
S230
BETW EEN project:
4 FRAMING
S230
2000# ADD TYP. AT LOW
ROOF
USU EVR
TYP.
S230
4 2
S230
TYP. BETW EEN
FRAMING (HIGH)
EXPANSION
HSS2X2X1/4 INTERIOR
CANOPY FRAMING, TYP. 2000# ADD 750# ADD

11
TYP.
S230 2500# ADD
SS

SS

W 21X57 W 21X57 W 21X57


12 C
S230
C

32LH (330/180)
17 S301
5
TYP. 750# ADD S220
S230
HSS8X2X3/16 PERIMETER
CANOPY FRAMING, TYP. 2000# ADD 11 3 TYP. AT
TYP.
670 EAST 1550 NORTH, LOGAN, UT
JOIST

(6) EQ SPACES
S230
S201 84341
W 18X46
26K (E)

26K (E)

22K (330/180)
MB-12C

A 11
S301 TYP.
S201 750# ADD
2000# ADD
HSS2X2X1/4 INTERIOR
B CANOPY FRAMING, TYP. 10 TYP. AT
B
p r o j e c t # : 21.0320
S230 JOIST
NOTE: SEE DETAIL 11 d a t e : 02.14.2023
17/S230 FOR CANOPIES TYP.
S230
revisions :
SS

SS

W 18X46 W 18X46 W 18X46


12 B
S230

5 6
TYP.
S230 S230
200# ADD

7 TYP. BETW EEN


MB-12C

JOISTS ALONG
S230 GRID 4

(6) EQ SPACES
W 18X46
26K (E)

26K (E)

26K (330/180)

title:
3000# ADD (BID ALT. #1)
ROOF
FRAMING
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

PLAN
A
3 2 TYP.
TYP. AT 4
BETW EEN B
A S230 JOIST S230 FRAMING S230 A
S301
(5) EQ SPACES (5) EQ SPACES (5) EQ SPACES TYP. BETW EEN
GRIDS 4 AND 5

sheet:
ROOF FRAMING PLAN A
SCALE : 1/8" = 1'-0"
S103
S103 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

STAIR NOTES :

4 4 1. SEE SHEET S001 FOR GENERAL STRUCTURAL NOTES.


2. COORDINATE FRAMING SIZES AND LAYOUTS SHOW N W ITH ARCHITECTURAL DRAW INGS.
3. UNLESS NOTED OTHERW ISE, MEMBERS TO BE CONNECTED TOGETHER W ITH 3/16" FILLET W ELD ALL
AROUND.
4. SEE DETAIL 3/S110 FOR TYPICAL BROKEN STRINGER INFORMATION.

F3 F3 5

4
1/

1/
99' - 0" 99' - 0"

4X

4X
4X

4X
3

SS

SS
H

H
HSS12X3X3/16 LANDING BEAM
2 4
E TYP. TYP. E
PROVIDE HSS12X3X3/16 S110 S220 360 west aspen avenue
ATTACHED TO PERIMETER EDGE salt lake city, utah 84101

HSS12X3X5/16 BROKEN STRINGER

HSS12X3X5/16 BROKEN STRINGER


ANGLE AT EDGE OF LANDING 1 801 532 4422
CONSTRUCT LANDING OF 4" F F S110
HSS8X4X5/16 SLAB ON 20 GA. COMPOSITE
SEE FLOOR FRAMING NOTES FOR PROVIDE CANTILEVERED BEAM
B-DECK
DECKING AT THIS LOCATION W 10X22 MOMENT CONNECTIONS AT
HSS12X3X3/16 STRINGER
D D
THESE LOCATIONS, PER DETAIL CONSTRUCT LANDING OF

HSS12X3X3/16 STRINGER
CONCRETE FILLED 5/S202 4" SLAB ON 20 GA.
4 METAL PAN TREAD COMPOSITE B-DECK
SEE A/S110 FOR CONTINUATION

HSS12X3X3/16 BROKEN STRINGER


S110 OF STAIR FRAMING

HSS8X4X5/16 LANDING BEAM


1
TYP. 5
S110 HSS12X3X3/16 STRINGER TYP.
CONCRETE FILLED S110
METAL PAN TREAD

HSS12X3X3/16 STRINGER

HSS12X3X3/16 BROKEN STRINGER


W 10X22
SEE B/S110 FOR CONTINUATION HSS12X3X3/16 STRINGER UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND

HSS12X3X3/16 STRINGER
HSS12X3X5/16 BROKEN STRINGER

HSS12X3X5/16 BROKEN STRINGER


OF STAIR FRAMING PRECAST TREADS ON BENT 3 DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
PLATE STEEL SUPPORTS - TYP. NOT INTENDED FOR CONSTRUCTION, RECORDING
S220 PURPOSES, OR IMPLEMENTATION
SEE ARCH FOR ADD. INFO.
1
TYP.
S110
HSS12X3X3/16 STRINGER
HSS8X4X5/16

5
S110

CONCRETE FILLED
HSS8X4X3/16 METAL PAN TREAD
2
D A A A A TYP.
S110
D
5
2
TYP.
3
CONSTRUCT LANDING OF
5 S110
S110 S220 4" SLAB ON 20 GA. HSS8X4X3/16
COMPOSITE B-DECK

STAIR B FIRST LEVEL FRAMING PLAN C


4
4 SCALE : 1/4" = 1'-0"
S110

STAIR A FIRST LEVEL FRAMING PLAN A STAIR A SECOND LEVEL FRAMING PLAN B
SCALE : 1/4" = 1'-0"
S110 SCALE : 1/4" = 1'-0"
S110
3

MEZZANINE STAIR FRAMING PLAN D


SCALE : 1/4" = 1'-0"
S110 THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

USU EVR
EXPANSION
1/4 1/4
HSS STRINGER - SEE PLAN
STAIR STRINGER - SEE PLAN
CJP
HSS GIRT - SEE PLAN MASONRY W ALL - SEE PLAN CJP BEARING & CAP PLATE 1/4"
CONNECTION ANGLE W / 3/4" DIA. x 6"
EXPANSION ANCHOR IN 1 1/2" OR ELEVATION x REQ'D
SLOTTED HOLE - SEE STRUCTURAL
NOTES FOR ANCHOR INFO. HSS STRINGER - SEE PLAN
1/4
(2) #4 BARS x CONT.

L3x3x1/4 x CONT.

670 EAST 1550 NORTH, LOGAN, UT


8"

CHANNEL EMBED
AT 8" DEEP HSS USE C12 x 20.7 x 1'-0" CJP 84341
W / (4) 3/4" DIA. x 5" HSA
AT 12" DEEP HSS USE C15 x 33.9 x CONCRETE SLAB ON
1'-0" W / (6) 3/4" DIA. x 5" HSA METAL DECK AT LANDING HSS HEADER OR BROKEN-
16" NOTE: LENGTH OF THICKENED
SLAB = DISTANCE BETW EEN HSS STRINGER - SEE PLAN BEARING AND CAP BACK STAIR STRINGER -
STAIR STRINGER + 12" PLATE 1/4" x REQ'D SEE PLAN

B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :
THICKENED SLAB @ STAIR 1 DETAIL 2 DETAIL 3 DETAIL 4 DETAIL 5
SCALE : NONE
S110 SCALE : NONE
S110 SCALE : NONE
S110 SCALE : NONE
S110 SCALE : NONE
S110

title:

STAIR
FRAMING
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

PLANS

A A

sheet:

S110 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

12" MIN. d1 L d2

4" MIN.
CONCRETE OR CMU
(2) #6 DOW ELS (AT FOUNDATION W ALL UTILITY TRENCHES
CONCRETE FOUNDATION

SLEEVE
BACK FILL AND COMPACT

24
DIAMOND PLATE DOW ELS W ALLS ONLY) (1) #5 x REQ'D ABOVE & BELOW PER GEOTECHNICAL REPORT

"M
POUR #1 / #2 AT 18"o.c. SLEEVE IN FOUNDATION W ALLS

IN
30"

.
24"
DIAMOND A CONCRETE FLOOR SLAB
TYP. FOUNDATION
BLOCKOUT REINFORCEMENT
T = FOOTING THICKNESS
AT COLUMNS
SAW N OR FORMED JOINT H = FOOTING STEP HEIGHT
PIPE TO CLEAR SLEEVE

MIN.
'T'

6"

24" MAX. (U.N.O.)


BY 1" ALL AROUND

t/4
CONCRETE FLOOR SLAB

'T'
TYP. FOUNDATION
POUR #3 18" 18" NO PIPES ALLOW ED TO
E REINFORCEMENT E

'H'

SLEEVE
PASS THROUGH FTGS.

T
OR GRADE BEAMS
360 west aspen avenue
salt lake city, utah 84101
NOTE: THICKENING OF SLAB ' . 4" MIN.
T = SLAB THICKNESS 1 'T . 801 532 4422
NOT REQUIRED FOR SLABS IN 24" MAX. 18"
POUR #1 / #2 B W ITH T = 6" OR GREATER T = SLAB THICKNESS 1 M
FOOTING REINFORCING 2
CONTROL JOINT

5"
(TOP STEEL W HERE BOTTOM OF FOOTING 1
CONSTRUCTION JOINT B
SCALE : NONE
A SCALE : NONE OCCURS)
2 x 'H' 12" 12"
NOTES: FOOTING OUTLINE THICKEN FOOTING W HERE
1. JOINTS SHALL OCCUR AT MAIN COLUMN / GRID LINES PIPE IS LESS THAN 24"
NOTES : NO DIGGING FOR PIPE TRENCH
W / 10'-0" MAX. SPACING BETW EEN JOINTS AT 4" SLABS; BELOW BOTTOM OF FOOTING
1. TYP. FOUNDATION W ALL REINFORCING NOT SHOW N FOR PARALLEL TO FOOTING W ITHIN
12'-0" MAX. AT 5" SLABS, AND 15'-0" MAX. AT 6" SLABS.
CLARITY. THIS BOUNDARY
2. SEE PLAN FOR SLAB THICKNESS 'T' AND REINFORCING NOTES : 2. FOR OPENINGS LARGER THAN 12" IN ANY DIRECTION. SEE
SIZE AND SPACING. 1. FOUNDATION REINFORCING NOT SHOW N FOR CLARITY. STRUCTURAL NOTE E-7.
2. SEE FOOTING SCHEDULE FOR FOOTING W IDTH AND 3. DETAIL IS SIMILAR AT MASONRY FOUNDATION W ALLS.
REINFORCING SIZE AND LOCATION. ALL FOOTING 4. DISTANCE 'L' SHALL BE THE GREATER OF (d 1 +d 2 )/2 OR 4".
REINFORCING REFERENCED IN THE SCHEDULE OR
SHOW N IN THE DETAILS MUST RUN CONTINUOUS PIPE PARALLEL TO FOOTING UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
THROUGH THE FOOTING STEP. DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
PIPE CROSSING FOOTING / FOUNDATION W ALL NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

TYPICAL CONCRETE SLAB JOINTS 1 TYPICAL STEPPED FOOTING 2 ALLOW ABLE PIPING LOCATIONS AT FOOTING DETAIL 3
SCALE : NONE
S201 SCALE : NONE
S201 SCALE : NONE
S201
NOTES: NOTES :
1. ℓs = LAP SPLICE LENGTH - SEE REBAR LAP SCHEDULE. 1. ℓs = LAP SPLICE LENGTH - SEE REBAR LAP SCHEDULE.
2. VERTICAL BARS NOT SHOW N. CAULK JOINT AT EXTERIOR
2. VERTICAL BARS NOT SHOW N.
3. THIS DETAIL IS APPLICABLE AT ALL FOOTINGS AND 3. THIS DETAIL IS ALSO APPLICABLE W HERE THE MASONRY W ALL
FOUNDATION W ALLS. ABUTS A CONCRETE FOUNDATION W ALL AT THE FOUNDATION
LEVEL. IN THIS CASE, THE BOND BEAM REINFORCING SHALL BE (3) VERTICAL BARS MIN. - SIZE
TO MATCH VERTICAL
ℓs

ℓs ℓs EPOXIED 5" INTO THE CONCRETE FOUNDATION W ALL.


REINFORCING IN MASONRY -
TYP. AT CORNERS

ℓs
ℓs ℓs
D D
BREAK SHELL FOR (2) VERTICAL BARS TO MATCH RAKE JOINT AT INTERIOR
FLOW OF GROUT, TYP. VERTICAL W ALL REINFORCING
EACH SIDE OF JOINT NON-SHRINK GROUT - 1" MIN.
CONT. VERTICAL CONTROL
VERIFY THICKNESS
JOINT
ℓs

CORNER COLUMN NUT THICKNESS

VERIFY
OPEN ENDED BRICK

4" MIN.
ℓs
DOUBLE MAT STOP HORIZONTAL REINFORCING AT
OPEN ENDED BRICK INTERMEDIATE BOND BEAMS BASE PLATE THICKNESS -
BREAK SHELL FOR FLOW SEE APPROPRIATE
NOTES:
OF GROUT, TYP. INTERMEDIATE BOND BEAM REINFORCING SCHEDULE OR DETAIL
1. ALL VERTICAL REINFORCING SHALL HAVE
INTERSECTION CORNER MATCHING DOW ELS CAST INTO FOUNDATIONS /
FOOTINGS. CAULK JOINT AT EXTERIOR EMBEDMENT LENGTH -
INTERSECTION DOUBLE MAT CORNER 2. HORIZONTAL REINFORCING NOT SHOW N FOR SEE DETAILS FOR MIN.
ALTERNATE BENDS, TYP. TOP OF FOUNDATION / EMBEDMENT LENGTH
CLARITY.
(4) VERTICAL BARS MIN. - PIER / FOOTING
3. TYP. W ALL, VERTICAL REINFORCING NOT SHOW N -
ℓs ℓs SIZE TO MATCH VERTICAL BOLT HEADS / NUT THICKNESS
SEE PLAN FOR SIZE AND SPACING
ALTERNATE REINFORCING IN MASONRY -
BENT, TYP. TYP. AT INTERSECTIONS
1 THREAD MIN.
ℓs ℓs
3" MIN. CLEAR
(2) VERTICAL BARS TO RAKE JOINT AT INTERIOR GRADE
MATCH VERTICAL W ALL DOUBLE NUT
BREAK SHELL FOR
FLOW OF GROUT, TYP. REINFORCING EACH SIDE CONT. VERTICAL CONTROL
ℓs

OF JOINT JOINT HEADED ANCHOR BOLT THREADED ROD


SINGLE MAT
OPEN ENDED BRICK OPEN ENDED BRICK INTERSECTION CONTINUE HORIZONTAL REINFORCING
ℓs

THROUGH JOINT AT ROOF, FLOOR AND


BREAK SHELL FOR FLOW OF TOP OF W ALL BOND BEAMS
GROUT, TYP. SINGLE MAT
INTERSECTION CORNER FLOOR, ROOF, AND TOP OF W ALL BOND BEAM REINFORCING
SINGLE MAT
TYP. REINFORCING AT INTERSECTIONS IN INTERSECTION CORNER TYPICAL ANCHOR BOLT EMBEDMENT THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
CONCRETE DETAIL 4 TYP. REINFORCING AT INTERSECTIONS IN TYPICAL VERTICAL REINFORCING DETAIL 6 TYP. JOINT REINFORCING DETAIL 7 DETAIL 8 MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
SCALE : NONE
S201 MASONRY DETAIL 5
SCALE : NONE
S201 SCALE : NONE
S201 SCALE : NONE
S201 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
SCALE : NONE
S201 project:
NOTE: W ELD SHALL BE FIELD W ELDED NOTE: W ELD SHALL BE FIELD W ELDED NOTE: W ELD SHALL BE FIELD W ELDED
AT MASONRY AND CONCRETE
EMBEDS AND SHOP W ELDED AT STEEL
TO STEEL CONNECTIONS.
AT MASONRY AND CONCRETE
EMBEDS AND SHOP W ELDED
AT STEEL TO STEEL CONNECTIONS.
AT MASONRY AND CONCRETE EMBEDS
AND SHOP W ELDED AT STEEL TO
STEEL CONNECTIONS.
18 GA. PLATE W / SHEET METAL
USU EVR
5/16
SCREW S AT 6"o.c. EACH W AY
EXPANSION
5/16
'LH' SERIES JOIST - SEE PLAN 3/4" PLATE x 6" x 1'-0" 14 GA. STEEL SHEET 12" MIN.
1/4 ROOF DECK BEYOND OPENING EACH W AY
42" SQ. 18" DIA. MAX.
ALL SIDES
'K' SERIES JOIST - SEE PLAN
36" SQ. 12" DIA. MAX.
#12 TEK SCREW S AT 6"o.c.
PIPE SLEEVE EACH W AY
24" SQ. 8" DIA. MAX.
BOLTING AS REQ'D. BY
12"

BOLTING AS REQ'D. BY
BOLTING AS REQ'D. BY JOIST MANUFACTURER 5/16 JOIST MANUFACTURER 12" SQ. 4" DIA. MAX.
JOIST MANUFACTURER

3/4" PLATE x REQ'D. - USE


(2) PLATES ALIGNED W ITH
COLUMN W ALLS AT HSS 1" DECK PENETRATION
COLUMNS - USE (1) PLATE 670 EAST 1550 NORTH, LOGAN, UT
L5 x 5 x 3/8 x 0'-6" W / 3/8" STIFFENER IN OTHER CONDITIONS
84341
PLATE AND BOLT HOLES W HEN REQ'D. NOTES :
L6 x 6 x 1/2 x 0'-8" W / 1/2" 1. USE DETAIL FOR THE FOLLOW ING CONDITIONS : NOTES :
IF REQUIRED BOTTOM CHORD STIFFENER PLATE AND BOLT - NO ADDED LOAD NOTED ON PLANS 1. USE DETAIL FOR FOLLOW ING CONDITIONS :
EXTENSION AND STABILIZER PLATE HOLES W HEN REQ'D. GIRDER - SEE PLAN - (1) TO (3) DECK FLUTES ARE PENETRATED - NO ADDED LOAD NOTED ON PLANS.
INFORMATION AND REQUIREMENTS 2. FOR OPENINGS GREATER THAN THREE FLUTES (18"), - (1) TO (3) DECK FLUTES ARE PENETRATED.
ARE TO BE PROVIDED BY THE JOIST IF REQUIRED BOTTOM CHORD IF REQUIRED BOTTOM CHORD SEE TYPICAL DETAIL FOR ADDITIONAL FRAMING. 2. FOR OPENINGS GREATER THAN THREE FLUTES (18") -
MANUFACTURER. EXTENSION AND STABILIZER PLATE EXTENSION AND STABILIZER PLATE SEE TYP. DETAIL.
INFORMATION AND REQUIREMENTS INFORMATION AND REQUIREMENTS PLAN
B FACE OF COLUMN / W ALL
ARE TO BE PROVIDED BY THE JOIST ARE TO BE PROVIDED BY THE JOIST B
MANUFACTURER. MANUFACTURER p r o j e c t # : 21.0320
d a t e : 02.14.2023
FACE OF COLUMN / W ALL FACE OF COLUMN / W ALL
revisions :
TYP. 'K'-'LH'-'GIRDER' SERIES JOIST BEARING SEAT (U.N.O.) 9 TYP. FRAMING @ SMALL ROOF OPENINGS DETAIL 10
SCALE : NONE
S201 SCALE : NONE
S201
TYP. AT
TYP. AT PERIMETER
PERIMETER METAL DECK - SEE PLAN OF
OF 3/4 6"
3/4 6" OPENING
OPENING
METAL DECK - SEE PLAN TYP.
2 1/2"

L TO 3/16 L TO
SEE ARCH. / FRAMING SEE ARCH./ FRAMING
1/4 3" MIN. TYP. 1/4 3" MIN TYP.
MECH. PLAN MECH. PLAN
B B B C B

A title:

B B

B B

A
1" MAX. IF 'H' < 2 1/2" GROUT
ANGLE (TYP.) ALL AROUND
OPENING - SEE SCHEDULE TYP.
1" MAX.
CHANNEL - SEE SCHEDULE
3/16
TYP. 4"
COURSE CONTAINING
REBAR AND COURSE
ABOVE REBAR SOLID
TYPICAL

'H' ≥ 2 1/2"
3/16"
BENT PLATE 3/8" x 4" x 6" x 0'-8" (LLV)
TYPICAL 8" OPEN-END BOND BEAM CMU TYPICAL 8" OPEN-END CMU DETAILS
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

SUPPORT MEMBER - SEE PLAN

'H'
SUPPORT MEMBER - SEE PLAN (FOR USE IN CMU BEAMS) (FOR USE IN ALL CMU BEAMS)
ABOVE BOTTOM COURSE ABOVE BOTTOM COURSE, U.N.O.

B B
SPAN LENGTH 'L'= JOIST SPACING OR LENGTH OF OPENING SPAN LENGTH 'L'= JOIST SPACING OR LENGTH OF OPENING
2 1/2"

PARALLEL WITH JOISTS, WHICHEVER IS GREATER PARALLEL WITH JOISTS, WHICHEVER IS GREATER HORIZONTAL BOND BEAM
REINFORCEMENT - SEE
PLANS AND SCHEDULES B C B
SPAN ANGLE SIZE SPAN CHANNEL NOTES:
1. ALL 8" OPEN-END AND BOND-BEAM CMU UNITS A A
L ≤ 6'-0" L4 x 4 x 1/4 L ≤ 8'-0" C6 x 8.2 SHALL MEET THE MINIMUM DIMENSIONS SHOW N.
A L ≤ 8'-0" L4 x 4 x 3/8 L ≤ 10'-0" C8 x 11.5 2. STANDARD 8" CMU UNITS MAY BE CUT, CHIPPED, TYPE SBP-1 TYPE SBP-2 TYPE SBP-3 A
L ≤ 10'-0" L5 x 5 x 3/8 OR MODIFIED TO CREATE OPEN-END OR BOND
BEAM UNITS, PROVIDED THE FINAL CONFIGURATION
NOTES : MEETS THE MINIMUM DIMENSIONS SHOW N. TYPICAL BOND BEAM GROUTING ALTERNATE BOND BEAM GROUTING
1. THIS DETAIL APPLIES TO ROOF OPENINGS LARGER THAN 18" IN EITHER DIRECTION. 4" A = 1/2" MIN.
2. MECHANICAL CURB ATTACHMENT TO STRUCTURE IS BY OTHERS. W HEN 'H' ≤ 2 1/2"
3. THIS DETAIL OCCURS UNDER THE CURB AND AROUND THE OPENING. W HERE NO B = 1 1/2"
OPENING OCCURS, FRAME OCCURS BELOW CURB ONLY. TYPICAL 8" BOND BEAM CMU ("H" BLOCK) C = 3" MIN.
sheet:
4. W HERE FRAME CONNECTS TO JOISTS MORE THAN 6" FROM A PANEL POINT, SEE DETAIL
(FOR USE IN ALL BOND BEAMS, U.N.O.)
1/S202 FOR REQUIRED JOIST UPGRADE INFORMATION.

S201
5. UNLESS NOTED OTHERW ISE, USE THE ANGLE FRAMES W HERE JOIST SPACING IS LESS
THAN OR EQUAL TO 10'-0" AND EQUIPMENT W EIGHS 1,000 POUNDS OR LESS. W HERE
EQUIPMENT W EIGHT IS GREATER THAN 1,000 POUNDS, USE CHANNEL FRAMES.

TYP. FRAMING AT ROOF OPENINGS AND ROOFTOP EQUIPMENT DETAIL 11 TYPICAL CMU BLOCK 12 TYP. BOND BEAM GROUTING 13 TYPICAL BASE PLATE 14
SCALE : NONE
S201 SCALE : NONE
S201 SCALE : NONE
S201 SCALE : NONE
S201 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

SEE PLAN HSA - SEE PLAN AND


24" MAX. NOTES
LOCATION OF NEW POINT LOAD 4 1/2" MIN.

PROVIDE NEW L2 x 2 x 1/4 BOTH SIDES ≥ 6"


OF JOIST - EXTEND TO NEAREST 18" o.c. CONCRETE SLAB ON
PANEL POINT ON OPPOSITE CHORD FILLER PIECE FULL LENGTH CONCRETE SLAB OVER METAL DECK
3/16 2" MIN. SPACING
OF BEAM W HEN DECK TOP METAL DECK - SEE NOTES
FLUTE COINCIDES W ITH FOR SLAB THICKNESS AND PLAN (SINGLE ROW ) BEAM TOP FLANGE
BEAM DECK SIZE AND GAUGE

7/8" MIN.
HSA - SEE PLAN AND SEE PLAN 5/16" MIN FLANGE
NOTES 24" MAX. THICKNESS
4 1/2" MIN.
CONDUIT CONDUIT
W BEAM - SEE PLAN
E E
SLAB REINFORCING - HSA - SEE PLAN AND 360 west aspen avenue

MIN.
3"
SEE STRUCTURAL NOTES salt lake city, utah 84101
NOTES
W BEAM - SEE PLAN
801 532 4422

7/8" MIN.
2" MIN.

SEE STRUCTURAL NOTES


HSA - SEE PLAN AND
NOTES
PLAN (DOUBLE ROW )
CONCRETE SLAB OVER
METAL DECK - SEE NOTES

1 1/2" MIN
1/2" MIN.
FOR SLAB THICKNESS AND
BEAM TOP FLANGE DECK SIZE AND GAUGE NOTES:
CLOSURE ZEE PLATE CONCRETE SLAB OVER 1. 1" OUTSIDE DIAMETER MAXIMUM CONDUIT SIZE.
≥ 6" 2. CONDUIT SHALL NOT CROSSOVER.

2" MIN
LOCATION OF NEW POINT LOAD METAL DECK - SEE NOTES
FOR SLAB THICKNESS AND 3. CONDUIT SHALL HAVE 3/4" MINIMUM CONCRETE COVER.
3/16 2" DECK SIZE AND GAUGE 4. MAINTAIN 1" CLEAR BETW EEN THE CONDUIT AND THE DECK.
5. CONDUIT SHALL NOT BE PLACED IN DECK FLUTES W ITH
EXISTING ROOF JOIST REINFORCING STEEL OR HSA's.
HSA - SEE PLAN AND
NOTES SECTION 6. CONDUIT SHALL NOT BE PLACED IN CONCRETE SLABS USED
TO OBTAIN A FIRE RATING. UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
W BEAM - SEE PLAN NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

TYPICAL JOIST UPGRADE DETAIL 1 COMPOSITE FLOOR DETAIL 2


SCALE : NONE
S202 SCALE : NONE
S202
METAL ROOF DECK
TYP.
TYP.
METAL ROOF DECK 3/4 __
3/4 __
(OPP. DIRECTION)
10 GA. x CONT. BENT
METAL ROOF DECK
SHIM - TYP.
NOTE: W HERE OPENING OCCURS ADJACENT 10 GA. x CONT. BENT
TO MASONRY W ALL PROVIDE C8 x 11.5 x 0'-8" "L" CHANNEL METAL ROOF DECK SHIM - TYP.
EMBED W / (2) 3/4" DIA. x 5" HSA IN W ALL AT (OPP. DIRECTION)
D FRAME SUPPORT LOCATIONS. L ≤ 6'-0" C6 x 8.2 D
SHIM TO SHIM TO
CONCRETE SLAB L ≤ 10'-0" C8 x 11.5 FLANGE FLANGE
CHANNEL - SEE SCHEDULE 1/8 2"-12" TYP. 1/8 2"-12" EACH SIDE
OVER METAL DECK
TYP.
CONCRETE SLAB OVER 3/16 BEAM - SEE PLAN BEAM - SEE PLAN
SEE ARCH. PLANS SEE ARCHITECTS 4" METAL DECK
TYP.
1/4" PLAN

DETAIL C DETAIL D

TYP. 10 GA. x CONT. TYP.


3/4 __ BENT SHIM - TYP. 3/4 __
4" TYP. 10 GA. x CONT. BENT
3/16 SHIM - TYP.
1/2" MAX. METAL ROOF DECK METAL ROOF DECK
BENT PLATE OR ANGLE (t=1/4" MIN.)
BENT PLATE OR ANGLE (t=1/4" MIN.) TYP. AROUND ALL OPENINGS SHIM TO
TYP. AROUND ALL OPENINGS METAL ROOF DECK METAL ROOF DECK FLANGE
(OPP. DIRECTION) (OPP. DIRECTION) 1/8 2"-12" TYP.
1/4" PLATE x 3" x 0'-10" 3/16
FLOOR FRAMING - SEE PLAN
COPE ANGLE VERTICAL LEG FLOOR FRAMING - SEE PLAN
SHIM TO
W HERE W IDTH OF OPENING "L" NOTE: W HEN LOW FLANGE
PERPENDICULAR TO DECK SPAN IS LESS CORRUGATION DOES NOT 1/8 2"-12" EACH SIDE
THAN 30", USE L4 x 4 x 1/4 SUPPORT OCCUR OVER BEAM, ADD BEAM - SEE PLAN
FOR OPENINGS GREATER THAN 24", ANGLE FRAMING BETW EEN FLOOR FOR OPENINGS PERPENDICULAR TO DECK SPAN CONT. PLATE - PLATE TO
BUT ≤ TO 4'-0" BEAMS, OTHERW ISE USE C6 x 8.2 GREATER THAN 4'-0" AND ≤ 8'-0" MATCH METAL DECK GA.

BEAM - SEE PLAN


DETAIL A DETAIL B
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
FLOOR OPENING DETAIL 3 TYP. ROOF METAL DECK SHIM DETAILS 4 MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
SCALE : NONE
S202 SCALE : NONE
S202 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

'A' 'A' USU EVR


HSS COLUMN - SEE PLAN
HSS COLUMN - SEE PLAN
(W HERE OCCURS)
EXPANSION
COVER PLATE (FY = 50ksi) x
COVER PLATE (FY = 50ksi) x (W HERE OCCURS)
BEAM 8" REQ'D THICKNESS = BASE PLATE W / (4) 3/4" DIA.
BEAM REQ'D THICKNESS = COVER PLATE (FY = 50ksi) x REQ'D BASE PLATE W / (2) 3/4" DIA.
8" FLANGE MIN. CANTILEVER BEAM BOLTS THICKNESS = Tf OR 1/2"
FLANGE CANTILEVER BEAM FLANGE 8" THICKNESS = CANTILEVER BEAM BOLTS THICKNESS = Tf OR 1/2"
BEAM THICKNESS FLANGE THICKNESS + 1/8" - MIN. W IDTH = Bf OR (COLUMN AT HSS COLUMN ABOVE USE
THICKNESS MIN. THICKNESS + 1/8" - W IDTH = FLANGE THICKNESS + 1/8" - TYP.
FLANGE MIN. W IDTH = CANTILEVER MIN. W IDTH = Bf OR (COLUMN W IDTH + 1" MIN.) LENGTH = A + (4) STIFFENER PLATES
- 1/16" CANTILEVER BEAM FLANGE W IDTH = CANTILEVER BEAM - 1/16" 1/4
A W IDTH - 1"
THICKNESS
FLANGE W IDTH - 1" BEAM FLANGE W IDTH - 1" W IDTH + 1" MIN.) LENGTH = A + 6" (W HERE OCCURS) THICKNESS = Tf/2 OR 3/8" MIN.
TOP COVER PLATE - 1/16" 3" (W HERE OCCURS)
BOLTED CONNECTION BOLTED CONNECTION PLATE - BOLTED CONNECTION
PLATE - PER SCHEDULE (2) STIFFENER PLATE TYP.
PLATE - PER SCHEDULE PER SCHEDULE W HERE COLUMN ABOVE
CANTILEVER BEAM - BEAM W BEAM W / CANTILEVER DOES NOT EXIST
SEE PLAN FLANGE MOMENT CONNECTION - THICKNESS = Tf/2 OR 3/8" MIN.
W BEAM W / CANTILEVER W BEAM W / CANTILEVER THICKNESS SEE PLAN
MOMENT CONNECTION - MOMENT CONNECTION - - 1/16"
SEE PLAN SEE PLAN CAP PLATE W / (2) 3/4" DIA. BOLTS
KNIFE PLATE, BOTH SIDES
BOTTOM COVER THICKNESS = Tf OR 1/2" MIN.
KNIFE 8" OF GIRDER, (FY=50ksi) STEEL BEAM W / FLANGE CAP PLATE W / (4) 3/4" DIA. STEEL BEAM W / FLANGE
PLATE OR KNIFE 8" W IDTH = Bf OR (COLUMN W IDTH +
BOTTOM COVER PLATE (FY = 50 ksi) PROVIDE W ELD PLATE TO MATCH THICKNESS OF W IDTH Bf & FLANGE BOLTS THICKNESS = Tf OR 1/2" W IDTH Bf & FLANGE 670 EAST 1550 NORTH, LOGAN, UT
PLATE (W HERE MIN. 3/16 MIN. 1" MIN.) LENGTH = B + 3 1/2"
MATCH THICKNESS OF CANTILEVER ACCESS HOLES IN BEAM W EB CANTILEVER BEAM 1/2" 1 1/2" THICKNESS Tf MIN. W IDTH = Bf OR (COLUMN 1 1/2" THICKNESS Tf
OCCURS)
W IDTH = BEAM FLANGE + 1" CANTILEVERED BEAM
CJP BOTTOM FLANGE. W IDTH W IDTH + 1" MIN.) LENGTH = B + 6" 84341
(ALTERNATIVELY, USE FULL-PEN W ELDED = BEAM FLANGE + 1"
SECTION A CONFIGURATION #2 W BEAM - SEE PLAN HSS COLUMN - SEE PLAN HSS COLUMN - SEE PLAN
CONNECTION AT BOTTOM FLANGE - W BEAM - SEE PLAN
SIM. TO CONFIG. #1, OPTION #1 ABOVE) CONFIGURATION #1, OPTION #2 'B' 'B'
CONFIGURATION #1, OPTION #1

W BEAM - SEE PLAN


TYPICAL CONDITION W HEN TYPICAL CONDITION
BEAM DOES NOT EXTEND W HEN BEAM EXTENDS
B BEYOND COLUMN BEYOND COLUMN B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :
TYPICAL CANTILEVERED BEAM MOMENT CONNECTION DETAIL 5 TYPICAL CAP PL. / BASE PL. @ FRAMING CONNECTIONS 6
SCALE : NONE
S202 SCALE : NONE
S202

EPOXY ALL NEW VERTICAL


REINFORCING 6" INTO EXISTING
MASONRY. ALL CELLS
RECEIVING EPOXY DOW ELS
SHALL BE GROUTED SOLID

title:
EXISTING MASONRY W ALL

TYPICAL
EPOXY ALL NEW HORIZONTAL
REINFORCING 8" INTO EXISTING
DETAILS
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

MASONRY. ALL CELLS


RECEIVING EPOXY DOW ELS
SHALL BE GROUTED SOLID

NEW MASONRY INFILL W / #5


AT 24"o.c. VERTICAL AND (2) #4
A AT 32"o.c. HORIZONTAL SOLID A
GROUT INFILL. AT MINIMUM,
PROVIDE VERTICAL AND
HORIZONTAL REINFORCING
AT EACH EDGE OF OPENING

sheet:

TYPICAL MASONRY INFILL DETAIL


SCALE : NONE
7
S202
S202 BID SET
1 2 3 4 5 6
1 2 3 4 5 6
2" GAP BETWEEN BASE PLATE SCHEDULE
MASONRY WALLS
COLUMN SIZE BASE PLATE SIZE
PROVIDE (2) #5 IN SOLID GROUTED
CELL AT END OF NEW W ALL CONCRETE SLAB (INTERIOR) -
8"SQ, 10"Ø PL. 3/4" x 14" x 1'-2" BASE PLATE SCHEDULE SEE PLAN / NOTES FOR
CONSTRUCTION JOINT - THICKNESS AND REINFORCING
TERMINATE HORIZONTAL 7" SQ PL. 3/4" x 13" x 1'-1" COLUMN SIZE BASE PLATE SIZE DIMENSION 'A' DIMENSION 'B' A.B. SIZE
MASONRY W ALL REINFORCING
6"SQ , 8"Ø PL. 3/4" x 12" x 1'-0" CONCRETE SLAB #4 DOW ELS AT 24"o.c.
EXISTING MASONRY W ALL AT CONSTRUCTION JOINT W 12x72 3/4"x14"x1'-2" 3" 4" 3/4" MASONRY W ALL - SEE PLAN
DOW EL TO MATCH AND SCHEDULE FOR SIZE AND (EXTERIOR, W HERE 24"
VERTICAL W ALL OCCURS) REQ'D
5" SQ PL. 3/4" x 12" x 1'-0" REINFORCING
NEW MASONRY W ALL - SEE PLAN REINFORCING
AND SCHEDULE
4" SQ PL. 5/8" x 10" x 0'-10"
CONCRETE SLAB - SEE PLAN /
EXISTING SLAB ON GRADE

6"
3"Ø, 3" SQ PL. 1/2" x 9" x 0'-9" NOTES FOR THICKNESS AND
SEE ARCH FOR REVEAL REINFORCING
5/16" REQ'D AT W HERE REQ'D
E FOUNDATION W ALL REINFORCING -
SEE STRUCTURAL NOTES AND STEEL PIPE OR HSS COLUMN 5/16" REQ'D AT
W COLUMN - SEE PLAN BASE PLATES 2' - 0" E
1/4 THICKER THAN 3/4" 360 west aspen avenue
SCHEDULE. DRILL AND EPOXY ALL BASE PLATES
HORIZONTAL REINFORCING TO (4) 3/4" DIA. x REQ'D HEADED 1/4 THICKER THAN 3/4"
(4) HEADED ANCHOR BOLTS
STEP CONT. TOP BARS
salt lake city, utah 84101
ANCHOR BOLTS W / NUT AND W / NUT AND W ASHER W / 8" 801 532 4422
EXISTING FOUNDATION W / 6" MIN. SEE BASE PLATE SCHEDULE BELOW RECESS
W ASHER W / 8" MIN. EMBED - SEE BASE PLATE SCHEDULE MIN. EMBED - SEE TYP.
EMBED FOR PLATE SIZE
SEE TYP. DETAIL FOR PLATE SIZE DETAIL
CONCRETE FOUNDATION W ALL -
CONCRETE SLAB - CONCRETE FOUNDATION SEE PLAN AND STRUCTURAL
BLOCKOUT BLOCKOUT W ALL - SEE PLAN AND
CONCRETE SLAB - SEE PLAN / SEE PLAN FOR THICKNESS NOTES FOR SIZE AND
NOTES FOR THICKNESS AND AND REINFORCING STRUCTURAL NOTES FOR REINFORCING
EXISTING FOUNDATION 1 1/2" NON-SHRINK GROUT REINFORCING 1 1/2" NON-SHRINK GROUT A SIZE AND REINFORCING
CONCRETE FOOTING -
W ALL AND FOOTING CONCRETE FOOTING - SEE PLAN SEE PLAN AND SCHEDULE
AND SCHEDULE FOR SIZE AND FOR SIZE AND REINFORCING
REINFORCING
1" MIN.
TYP. 'A' 'A'

CONCRETE FOOTING -

1" MIN.
TYP.
SEE PLAN AND SCHEDULE
FOR SIZE AND REINFORCING

'B'
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
TYP. FOOTING AND FOUNDATION INTO SECTION A
PURPOSES, OR IMPLEMENTATION

EXISTING FOOTING AND FOUNDATION 1 LEVELING NUT - TYP.


CONCRETE FOOTING - LEVELING NUT - TYP.
CONCRETE FOOTING -
SEE PLAN AND SCHEDULE
CONCRETE FOUNDATION AT OPENING 5
SEE PLAN AND SCHEDULE
SCALE : NONE
S210 FOR SIZE AND REINFORCING
FOR SIZE AND REINFORCING SCALE : NONE
S210
TYP. MASONRY ON CONCRETE
COLUMN TO SPOT FOOTING 2 COLUMN TO SPOT FOOTING 3 FOUNDATION W ALL DETAIL 4
SCALE : NONE
S210 SCALE : NONE
S210 SCALE : NONE
S210
3/4" BASE PLATE x REQ'D W / (4) 3/4" DIA.
MASONRY W ALL - SEE PLAN CONCRETE SLAB - SEE PLAN HEADED ANCHOR BOLTS W / 8" MIN.
AND SCHEDULE FOR SIZE / NOTES FOR THICKNESS EMBED - SEE DETAIL 14/S201 FOR BASE
D AND REINFORCING AND REINFORCING PLATE CONFIGURATION. PROVIDE
DOW EL TO MATCH MASONRY W ALL - SEE PLAN D
VERTICAL W ALL AND SCHEDULE FOR SIZE AND
SBP-2
(1) #4 BAR x CONT. SEE ARCH REINFORCING REINFORCING
HSS COLUMN - SEE PLAN W OR HSS COLUMN -
CONCRETE SLAB - SEE PLAN / SEE DETAILS 2 AND 3/S210 SEE PLAN

6"
EXISTING CONCRETE NOTES FOR THICKNESS AND FOR BASE PLATE AND CONCRETE SLAB - SEE PLAN /
#4 DOW ELS AT 24"o.c. T.O.W ALL
SLAB REINFORCING ANCHOR BOLT INFO. CONCRETE SLAB (EXTERIOR) NOTES FOR THICKNESS AND
SEE PLAN REINFORCING
DOW EL TO MATCH VERTICAL 24"
MASONRY W ALL - SEE PLAN 18" 2' - 0"
W ALL REINFORCING AND SCHEDULE FOR SIZE SEE ARCH FOR REVEAL
AND REINFORCING W HERE REQ'D

8"
GROUT CELLS SOLID #5 BARS x CONT. AT 12"o.c.,
BELOW GRADE TOP AND BOTTOM 5" MAX. FOR FIRST (3) 18" x 18" CONCRETE PIER W /
TIES, TYP. ALL PIERS (8) #5 VERTICAL BARS AND #3
8" CONCRETE FOUNDATION HORIZ. TIES AT 8"o.c.
#4 STIRRUP AT 24"o.c. 8" CONCRETE FOUNDATION
W ALL - SEE STRUCTURAL EXISTING CONCRETE
NOTES FOR REINFORCING FOUNDATION W ALL W ALL - SEE PLAN AND
REQ'D STRUCTURAL NOTES FOR
EXISTING CONCRETE CONCRETE FOOTING - SIZE AND REINFORCING
#4 DOW ELS AT 18"o.c. CONCRETE FOOTING -
FOOTING 8" SEE PLAN AND SCHEDULE SEE PLAN AND SCHEDULE

12"
FOR SIZE AND REINFORCING FOR SIZE AND REINFORCING
SEE ARCH. FOR W ATERPROOF
REQUIREMENTS 18"

EXISTING
MATCH
CONCRETE FOOTING -
SEE PLAN AND SCHEDULE #5 BARS AT 14"o.c.
FOR SIZE AND REINFORCING EACH W AY 8"
SEE ARCH
NEW CONCRETE FOOTING - #5 BARS AT 12"o.c., TOP AND
SEE PLAN FOR SIZE SEE PLAN
BOTTOM - EPOXY DOW EL INTO
12" MIN.
EXISTING CONCRETE W / 6 5/8"
MIN. EMBED
TYP. MASONRY ON CONCRETE THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MASONRY W ALL ON FOOTING 6 DETAIL 8 CONCRETE PIER 9 FOUNDATION W ALL DETAIL 10 MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
SCALE : NONE
S210 (1) #4 BAR x CONT. SCALE : NONE
S210 SCALE : NONE
S210 SCALE : NONE
S210 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
SECTION AT ELEVATOR PIT 7 project:
SCALE : NONE
S210
REQ'D
?
24"
FRP GRATING - SEE NOTES USU EVR
FRP EZ ANGLE (OR MASONRY W ALL - SEE PLAN HSS COLUMN - SEE PLAN
APPROVED EQUIVALENT)

FRP GRATING - SEE NOTES


#4 FRP BENT DOW EL AT 16"o.c.

CONCRETE SLAB - SEE NOTES


AND SCHEDULE FOR SIZE
AND REINFORCING CONCRETE SLAB - SEE PLAN /
NOTES FOR THICKNESS AND PROVIDE BEAM POCKET THAT
EXPANSION
CONCRETE SLAB - SEE NOTES IS 1/2" W IDER THAN BEAM
EXTERIOR GRADE REINFORCING

FRP GRATING - SEE NOTES 1/4" CAP PLATE CONCRETE SLAB - SEE PLAN /
EXTEND REINFORCING A (2) #4 FRP BARS x CONT., TOP #5 FRP VERTICAL
NOTES FOR THICKNESS AND
MIN. OF 16" INTO AND BOTTOM OF W ALL DOW ELS AT 16"o.c. FRP GRATING - SEE NOTES REINFORCING
8"

SURROUNDING SLAB FRP EZ ANGLE (OR


APPROVED EQUIVALENT) NOTE: A MAX. 8" HOLE MAY BE #4 FRP HORIZONTAL
#4 FRP BAR x CONT.
LOCATED AT BOTTOM OF W ALL BAR AT MID-HEIGHT
8" CONCRETE W ALL SEE NOTES AND GEOTECH FOR ELECTRICAL W IRING ACCESS OF W ALL CONCRETE FOUNDATION CONCRETE BLOCKOUT

8"
REPORT FOR AGGREGATE AS REQ'D (HOLES MAY NOT BE W ALL - SEE PLAN AND
(2) #4 FRP BARS x CONT., TOP AND BASE REQUIREMENTS CLOSER THAN 36" TO EACH 8" CONCRETE W ALL STRUCTURAL NOTES OR BASE PLATE (SBP-2), PER
SEE ARCH AND BOTTOM OF W ALL BELOW SLAB OTHER) STEP BOTTOM SCHEDULE FOR SIZE AND DETAIL 14/S201 W / (4) 3/4" DIA.
REINFORCING ABOVE OPENING REINFORCING HEADED ANCHOR BOLTS W /
#4 FRP BAR x CONT.
#4 FRP BARS AT 24"o.c. EACH 8" MIN. EMBED
W AY AT TOP OF MAT SLAB 1' - 6"
REMOVABLE HSS BEAM - FRP EZ ANGLE (OR
1 SEE PLAN FOR SIZE AND 3" APPROVED EQUIVALENT)
8" MIN.

1
LOCATION 670 EAST 1550 NORTH, LOGAN, UT
SEE NOTES AND (2) #4 FRP x 36" BELOW
1 CONCRETE W ALL - SEE PLAN POCKET
84341
GEOTECHNICAL REPORT FOR
#4 FRP BENT BAR AT 12"o.c. 1 AGGREGATE AND BASE AND SCHEDULE FOR SIZE
REQUIREMENTS BELOW SLAB AND REINFORCING

#4 FRP BARS AT 12"o.c.

12" THICK CONCRETE MAT


#5 FRP BARS AT 12"o.c. 12" THICK CONCRETE SLAB - SEE DETAIL 12/S210 CONCRETE FOOTING - SEE 1 1/2" NON-SHRINK GROUT
B EACH W AY AT BOTTOM MAT SLAB FOR REINFORCING PLAN AND SCHEDULE FOR B
OF MAT SLAB REQUIRMENTS SIZE AND REINFORCING p r o j e c t # : 21.0320
#5 FRP VERTICAL
DOW ELS AT 16"o.c. d a t e : 02.14.2023

revisions :
DETAIL 11 DETAIL 12 DETAIL 13 DETAIL 14 DETAIL 15
SCALE : NONE
S210 SCALE : NONE
S210 SCALE : NONE
S210 SCALE : NONE
S210 SCALE : NONE
S210

title:

FOUNDATION
DETAILS
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

A A

sheet:

S210 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

#4 DOW ELS AT 24"o.c.

24" 16"
CONCRETE SLAB OVER #4 DOW ELS AT 24"o.c.
METAL DECK - SEE NOTES ALTERNATE BENDS CONCRETE SLAB OVER
CONCRETE SLAB OVER 2" MIN. A325 BOLTS AS PER
FOR SLAB THICKNESS AND METAL DECK - SEE NOTES
METAL DECK - SEE NOTES GAP MASONRY W ALL - SEE SCHEDULE W / W ASHERS
DECK SIZE AND GAUGE 24" 1/4 6" FOR SLAB THICKNESS AND
FOR SLAB THICKNESS AND 16" PLAN AND SCHEDULE THAT COMPLETELY COVER
DECK SIZE AND GAUGE
DECK SIZE AND GAUGE FOR SIZE AND THE SLOTS PER THE
REINFORCING STRUCTURAL NOTES
#4 DOW ELS AT 24"o.c.
MASONRY W ALL - SEE #4 DOW ELS AT 24"o.c.
24" PLAN AND SCHEDULE CONT. BOND BEAM W BEAM - SEE PLAN
MASONRY W ALL - SEE 16" FOR SIZE AND 24" REINFORCING. LOCATE
E PLAN AND SCHEDULE REINFORCING 16" W ITHIN 8" OF TOP OF E
FOR SIZE AND
STEEL BEAM
360 west aspen avenue
REINFORCING
salt lake city, utah 84101
2" MIN. BEARING NOTE : PROVIDE 2" MIN.
BEARING DO NOT RUN CONCRETE BOND BEAM 801 532 4422
DECKING CONT. OVER W ALL. REINFORCING CONCRETE BOND BEAM
CONCRETE SLAB OVER METAL REINFORCING
DECK - SEE NOTES FOR SLAB
THICKNESS AND DECK SIZE
MASONRY W ALL - SEE C8 x 13.75 x 0'-8" AT AND GAUGE
PLAN AND SCHEDULE W / (2) 3/4" DIA. x 5" HSAs
FOR SIZE AND AT 6'-0"o.c. MAX. SPACING NOTE: AT CONTRACTORS OPTION
MASONRY W ALL - SEE L 4 x 3 x 1/4 (LLV)
REINFORCING AND A MINIMUM OF 1'-4" PROVIDE TEMPORARY SHORING
PLAN AND SCHEDULE FOR
FOR SLAB POUR AT DECK EDGE

8" MAX.
2" MIN.
SIZE AND REINFORCING FROM END OF W ALL SEE TYP. SCHEDULE FOR
(NOTE: AT 6" W ALL RUNNING PARALLEL TO W ALL
BEAM CONNECTION
RECESS LOCATIONS USE
3/4" DIA. x 3" HSA) CHANNEL EMBED H.S.A.'s -
SEE SCHEDULE

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

DECK ON MASONRY 1 DECK ACROSS MASONRY 2 CONCRETE DECK INTO MASONRY 3 CONCRETE DECK INTO MASONRY 4 BEAM INTO CMU 5
L L L L
SCALE : NONE
S220 SCALE : NONE
S220 SCALE : NONE
S220 SCALE : NONE
S220 SCALE : NONE
S220

8" OR 12" MASONRY ABOVE


RECESS - SEE ELEVATIONS
/ PLANS FOR LOCATIONS

EXTEND VERTICAL W ALL PROVIDE MASONRY BEAM


HSS COLUMN - SEE PLAN BENT PLATE TO BENT PLATE TO DBA TO BENT REINFORCING INTO MASONRY REINFORCING ABOVE
BEAM
D 1/4 2"-12" MATCH SLAB
THICKNESS
BEAM 1/4 2"-12" PLATE ABOVE A MIN. OF 16" RECESS - SEE TYP. SCHEDULE D
CONCRETE SLAB OVER ON S011 FOR INFO.
CONCRETE SLAB OVER METAL METAL DECK - SEE NOTES
DECK - SEE NOTES FOR SLAB CONCRETE SLAB OVER REQ'D
FOR SLAB THICKNESS AND DECK SUPPORT - SEE TRANSITION
ℓd

1" CLEAR
THICKNESS AND DECK SIZE AND DECK SIZE AND GAUGE STRUCTURAL NOTES METAL DECK - SEE NOTES 1/2" DIA. x REQ'D DBA AT MATCH SLAB ELEVATION
SEE

MAX.
SEE TYP. SCHEDULE FOR GAUGE FOR SLAB THICKNESS AND BENT PLATE 1/4" x REQ'D x REQ'D - 24"o.c. U.N.O. W ELDED REQ'D THICKNESS
BEAM CONNECTION ARCH. TYP. AT SLAB EDGES. EDGE OF BENT SEE ARCH
DECK SIZE AND GAUGE TO BENT PLATE
PLATE TO OCCUR 5/8" FROM BEAM
CENTERLINE TO ALLOW FOR STUD BENT PLATE 1/4" x REQ'D x CONT. -
ATTACHMENT (ANGLE CAN BE USED SHORE PLATE UNTIL CONCRETE
AT CONTRACTOR'S OPTION.) CURES. EDGE OF BENT PLATE TO (1) #5 BAR x CONT.
OCCUR 5/8" FROM BEAM CENTERLINE
HSA - SEE PLAN FOR MORE INFO. TO ALLOW FOR STUD ATTACHMENT 6" OR 10" MASONRY W ALL
2" MIN. DECK BEARING - CONCRETE SLAB OVER 17" MAX. (ANGLE CAN BE USED AT RECESS - SEE W ALL
SEE STRUCTURAL NOTES 8" MAX. METAL DECK - SEE NOTES CONTRACTOR'S OPTION) ELEVATIONS FOR LOCATIONS
FOR ATTACHMENT FOR SLAB THICKNESS AND
DECK SIZE AND GAUGE VERTICAL REINFORCING -
W BEAM - SEE PLAN SEE SCHEDULE
2" MIN. DECK BEARING - HSA - SEE PLAN FOR
SEE STRUCTURAL NOTES MORE INFO.
FOR ATTACHMENT HORIZONTAL REINFORCING -
W BEAM - SEE PLAN SEE SCHEDULE
W BEAM - SEE PLAN
W BEAM - SEE PLAN SEE TYP. SCHEDULE FOR #5 BARS x CONT. IN BOTTOM
BEAM CONNECTION (2) COURSES

T.O.OPENING
SEE ARCH

FOR SLAB OVERHANGS ≤ 8" FOR SLAB OVERHANGS GREATER THAN 8" ≤ 17" PROVIDE 90° HOOK AT
BOTTOM OF VERTICAL BARS
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
BEAMS INTO GIRDER 6 BEAM INTO COLUMN 7 TYPICAL SLAB EDGE DETAIL 8 DETAIL 9 MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
SCALE : NONE
S220 SCALE : NONE
S220 SCALE : NONE
S220 SCALE : NONE
S220 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:
16"

B.O.OPENING
SEE ARCH
FUTURE TIE BACK PLATE AND
CONNECTION TO COLUMN BY
REQ'D USU EVR
16"
CRANE SUPPLIERS (W HERE
REQ'D)

#4 BAR x CONT.
#3 BENT DOW EL AT 16"o.c.
EXPANSION
(2) #5 BARS x CONT.
EXTEND MIN. OF 24" PAST PROVIDE OPEN ENDED 8" OR 12" MASONRY JAMB W COLUMN - SEE PLAN W COLUMN - SEE PLAN CONCRETE SLAB OVER
EDGE OF RECESS BLOCK AT TRANSITION EACH SIDE OF RECESS - FUTURE CRANE BEAM W / ROOFING AND PAVER METAL DECK - SEE NOTES
BETW EEN BLOCK SIZES SEE ELEVATIONS AND CAP CHANNEL (OR GRAVEL) FOR SLAB THICKNESS AND
CONCRETE SLAB OVER FUTURE 3/4" DIA. BOLT, TYP. SYSTEM - SEE ARCH DECK SIZE AND GAUGE
6" RECESSED MASONRY - SCHEDULE 3" MIN.
METAL DECK - SEE NOTES FUTURE TIE BACK ANGLES -
SEE ELEVATIONS FOR INTALL VERTICAL BAR AT
FOR SLAB THICKNESS AND SEE DETAIL 13/S220
LOCATIONS AND SCHEDULE PERIMETER OF RECESS, TYP.
DECK SIZE AND GAUGE
FOR REINFORCING TYP.
FUTURE L3 x 3 x 1/4 TIE BACK
ANGLE

TYP. L3 x 3 x 1/4 x CONT.


SEE DETAIL 3/S220 FOR HORIZONTAL W ALL
CONDITION AT FLOOR REINFORCING - SEE SCHEDULE.
EXTEND ALL REINFORCING MIN. 1/2" STIFFENER PLATE
VERTICAL REINFORCING - OF 24" PAST EDGE OF RECESS HORIZONTAL REINFORCING - 6" OR 10" MASONRY W ALL 670 EAST 1550 NORTH, LOGAN, UT
SEE SCHEDULE SEE SCHEDULE. EXTEND MIN. RECESS - SEE W ALL TYP.
CONCRETE SLAB OVER W BEAM - SEE PLAN 84341
OF 24" INTO ADJACENT W ALL ELEVATIONS FOR LOCATIONS 5/16
PROVIDE 90° HOOK AT BOTTOM CRANE BEAM, PER FUTURE BEAM FLANGE, TYP. METAL DECK - SEE NOTES
AND SCHEDULE FOR
OF ALL VERTICAL BARS SUPPLIER FOR SLAB THICKNESS AND
REINFORCING
CRANE BRACKET - SEE PLAN DECK SIZE AND GAUGE
(2) #5 BARS x CONT. 9" 9"
EXTEND MIN. OF 24" PAST
EDGE OF RECESS TYP. 3 SIDES
5/16 W 18 x 76 BRACKET
T.O.OPENING 3/16 3"-12"
B SEE ARCH TYP. B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :
DETAIL 10 DETAIL 11 DETAIL 12 DETAIL 13 DETAIL 14
SCALE : NONE
S220 SCALE : NONE
S220 SCALE : NONE
S220 SCALE : NONE
S220 SCALE : NONE
S220

BUILDING SEPARATION JOINT -


SEE PLAN AND ARCH
DRAW INGS FOR ADD. INFO.

ROOFING AND PAVER METAL STUD FRAMING AND


(OR GRAVEL) FINISHES - SEE ARCH
SYSTEM - SEE ARCH
ROOFING AND PAVER
(OR GRAVEL)
HSS COLUMN - SEE PLAN
PROVIDE 1/4" CAP PLATE
AT TOP OF COLUMN
title:
SYSTEM - SEE ARCH
W BEAM - SEE PLAN 3" (4) 3/4" DIA. DBAs x 36" LONG

6"
FLOOR
EXISTING MASONRY FRAMING
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

W ALL PROVIDE BEND IN DBA


TO ALLOW FOR 4" MIN
CONCRETE SLAB OVER
METAL DECK - SEE NOTES
FOR SLAB THICKNESS AND 5/16
GAP BETW EEN BARS
DETAILS
DECK SIZE AND GAUGE
EDGE ANGLE - SEE CONCRETE SLAB OVER
DETAIL 8/S220 METAL DECK - SEE NOTES SEE DETAIL 3/S220 FOR MASONRY BOND BEAM
FOR SLAB THICKNESS AND CONDITION AT SLAB EDGE REINFORCING
CONCRETE SLAB OVER
A DECK SIZE AND GAUGE
METAL DECK - SEE NOTES 3/8" x REQ'D PLATE A
MASONRY W ALL - SEE PLAN W / (2) 3/4" DIA. MASONRY W ALL - SEE
W BEAM - SEE PLAN FOR SLAB THICKNESS AND
AND SCHEDULE FOR SIZE ERECTION BOLTS PLAN AND SCHEDULE FOR
DECK SIZE AND GAUGE
AND REINFORCING SIZE AND REINFORCING
SEE DETAIL 4/S220 FOR
SLAB EDGE

SEE DETAIL 5/S220 FOR BEAM 5/16 sheet:


CONNECTION BELOW SLAB
(W HERE OCCURS)

DETAIL
SCALE : NONE
15
S220
DETAIL
SCALE : NONE
16
S220
DETAIL
SCALE : NONE
17
S220
L
S220 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

1/4 6"

SEE DETAIL --/S---- FOR SEE ROOF DECK


(2) #4 BARS x CONT. DECK BEARING INFORMATION SCHEDULE
SEE ROOF DECK AT TOP OF W ALL, TYP.
TYP. W ALL REINFORCING -
SCHEDULE ROOF DECK - SEE SCHEDULE SEE STRUCTURAL NOTES JOIST BRIDGING PER MANUF.
3/16 6" 1/4" x 2 1/2" AT LH
FOR SIZE AND ATTACHMENT
(2) #5 BARS - THESE BARS 1/8" x 2 1/2" AT K
1/8" x 2 1/2" AT 'K'
MAY BE CUT AT JOIST ROOF DECK - SEE SCHEDULE
1/4" x 3" AT 'LH'
POCKETS W HERE REQ'D L 3 x 2 x 1/4 x CONT. (LLH) CONT. BOND BEAM FOR SIZE AND ATTACHMENT
VERTICAL LEG UP, FULL PEN REINFORCING - SEE ROOF DECK - SEE SCHEDULE
W ELD AT SPLICES SCHEDULE. STEP BOND BEAM ROOF JOIST - SEE PLAN FOR SIZE AND ATTACHMENT
1/4" PLATE x 6" x CONT. W / 1/2" TO MATCH SLOPE OF ROOF
DIA. x 5" HSA AT 24"o.c. (PLATE CONT. BOND BEAM
E TO BE CONT. BETW EEN JOIST REINFORCING (THESE
3/16 E
BARS SHALL NOT BE CUT) SOLID GROUT JOIST POCKET
360 west aspen avenue
POCKETS W HERE JOISTS
BEAR ON W ALL) MC12 x 10.6 x 0'-8" AT 4'-0"o.c.
salt lake city, utah 84101
ROOF DECK - SEE SCHEDULE
NOTE: AT SLOPING DECK
FOR SIZE AND ATTACHMENT W / (2) 3/4" DIA. x 5" HSAs 801 532 4422
CONDITIONS PROVIDE BENT SHIM MASONRY W ALL - SEE
PLATE ON TOP OF W ALL EMBED PLAN AND SCHEDULE FOR 1/2" PLATE x 6" x 1'-2"
FOR DECK ATTACHMENT, SIM. TO MC12 x 10.6 x 0'-8" BETW EEN W / (2) 3/4" DIA. x 8" HSA
SIZE AND REINFORCING
DETAIL 4/S202 JOISTS (6'-0" MAX. SPACING) W /
TYP. W ALL REINFORCING - (2) 3/4" DIA. x 5" HSAs (NOTE: AT
TYP. W ALL REINFORCING - SEE STRUCTURAL NOTES CONT. BOND BEAM
6" W ALL RECESS LOCATIONS
SEE STRUCTURAL NOTES REINFORCING - SEE
USE 3/4" DIA. x 3" HSA)
SCHEDULE. STEP BOND L4 x 4 x 1/4 x CONT. BOLTS REQ'D FOR ALL
BEAM AS REQ'D TO (VERTICAL LEG DOW N) JOISTS W / SPANS > 40' - 0"
MATCH ROOF SLOPE 5/8" DIA. ANCHORS
W / 5" MIN. EMBED
L3 x 3 x 1/4 x 0'-6" JOIST SUPPORT GIRDER /
W BEAM - SEE PLAN
'LH' SERIES JOISTS TO BEAR 6" MIN.
TYP. *
ON EMBED. 'K' SERIES JOISTS TO 3/16 2"
BEAR 4" MIN. ON EMBED

TYP. W ALL REINFORCING - UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


SEE STRUCTURAL NOTES DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOTE: * = BRIDGING CONNECTIONS MAY BE BOLTED OR W ELDED NOT INTENDED FOR CONSTRUCTION, RECORDING
AS PER JOIST MANUFACTURERS RECOMMENDATIONS. PURPOSES, OR IMPLEMENTATION

DECK ACROSS MASONRY 1 DECK TO MASONRY 2 JOIST INTO MASONRY 3 JOIST BRIDGING INTO MASONRY 4 JOISTS ON BEAM 5
L L
SCALE : NONE
S230 SCALE : NONE
S230 SCALE : NONE
S230 SCALE : NONE
S230 SCALE : NONE
S230

BEARING PLATE
PER TYP. DETAIL
CAP PLATE 3/8" x REQ'D BOLTS - PER JOIST MANUF.
D D
1/8" x 2 1/2" AT 'K'
SEE ROOF DECK 1/4 6"
ROOF DECK - SEE SCHEDULE TYP. 1/4" x 2 1/2" AT 'LH'
FOR SIZE AND ATTACHMENT 1/4 SCHEDULE
TYP. W ALL REINFORCING -
SEE STRUCTURAL NOTES
SEE ROOF DECK
SCHEDULE 1 1/2"

CONT. BOND BEAM ROOF DECK - SEE SCHEDULE


REINFORCING - SEE FOR SIZE AND ATTACHMENT

HSS 5 x 5 x 3/16 SCHEDULE. STEP BOND BEAM


NOTE: SEE DETAIL 7/S230
3/16 2"-12" TO MATCH SLOPE OF ROOF
BETW EEN JOISTS FOR CONDITIONS
AT BEAMS ON
GRID 4 BETW EEN JOISTS
1/4
L4 x 4 x 1/4 x CONT.
W BEAM - SEE PLAN
(VERTICAL LEG DOW N)
W BEAM - PER PLAN ROOF JOIST - PER PLAN
HSS COLUMN - SEE PLAN W BEAM - SEE PLAN EMBED - SEE DETAIL 4/S230 ROOF JOIST - SEE PLAN
HSS COLUMN - SEE PLAN SEE --/--- FOR INFO.
SEE TYP. SCHEDULE FOR NOTE: BOLTS REQ'D FOR ALL JOISTS
BEAM CONNECTION W HERE JOISTS BEARING ON BEAM W / SPANS ≥ 40'-0", TYP.
HAVE 2 1/2" END BEARING DEPTH,
SEE TYP. DETAIL FOR USE HSS 5 x 2 1/2 x 3/16 x REQ'D IN W BEAM - SEE PLAN
STABILIZER PLATE INFO. LIEU OF HSS 5 x 5

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
BEAMS & JOISTS INTO HSS COLUMN 6 DETAIL 7 DETAIL 8 BEAM TO COLUMN ON SEAT CONNECTION 9 BEAMS & JOIST ON BEAM 10 MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
L L COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
SCALE : NONE
S230 SCALE : NONE
S230 SCALE : NONE
S230 SCALE : NONE
S230 SCALE : NONE
S230 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
SEE ARCH 1/4" BENT PLATE x CONT. x CONT.
AT TRANSITION LOCATION project:
NOTE: AT SIM. CONDITION, JOISTS (COORDINATE W / ARCH
5/16" x 4" x 2'-0" SEISMIC STRAP BEAR ON TOP OF STEEL BEAM DRAW INGS)
(SS) W HERE NOTED ON
DRAW INGS
1/4
1/4
4" 4" SEE DETAIL 1/S230 FOR W ALL
CONDITION BETW EEN JOISTS
USU EVR
4"
ROOF DECK - SEE SCHEDULE
FOR SIZE AND ATTACHMENT
3/8" CAP PLATE x REQ'D
(U.N.O.) ROOF DECK - SEE SCHEDULE
FOR SIZE AND ATTACHMENT
EDGE ANGLE - SEE
DETAIL 4/S230
4"
ROOF DECK - SEE SCHEDULE
FOR SIZE AND ATTACHMENT
EXPANSION
2" MIN. JOINT BETW EEN
BUILDINGS - SEE ARCH
EXISTING MASONRY W ALL FOR ADD. INFO.
1/4 8"
4" 1/4" BENT PLATE x CONT. 1/4 3"
CHANNEL - SEE PLAN
CONNECTION PLATE - SEE
SCHEDULE FOR PLATE
THICKNESS AND BOLT VARIES
REQUIREMENT
1/4
3/16" BENT PLATE x REQ'D

A
C12 x 20.7 x 3'-0" W / (10)
W BEAM - SEE PLAN W BEAM - SEE PLAN 3/4" DIA. x 5" HSA
CENTERED ON COLUMN 670 EAST 1550 NORTH, LOGAN, UT
W BEAM - SEE PLAN C15 x 33.9 x 2'-0" W /
3/16 2"-12" 4" 1' - 0" MIN. 84341
FULL DEPTH STIFFENER PLATE - CONNECTION PLATE - SEE 3/16 (12) 3/4" x 5" HSA
SEE STRUCTURAL NOTES SCHEDULE FOR PLATE FULL DEPTH STIFFENER PLATE -
THICKNESS AND BOLT SEE STRUCTURAL NOTES MASONRY W ALL - SEE PLAN
JOIST TOP CHORD AND SCHEDULE FOR SIZE
REQUIREMENT EXTENSION AND REINFORCING
W COLUMN - SEE PLAN MASONR W ALL - SEE PLAN
W COLUMN - SEE PLAN AND SCHEDULE FOR SIZE JOIST TOP CHORD EXTENSION
1/2" EMBED PLATE x 6" x 1'-2"
3/8" BENT PLATE x 1'-0" x AND REINFORCING W / (2) 3/4" DIA. x 8" HSA
16" REQ'D EACH SIDE OF
B COLUMN W / 1/4" STIFFENER SECTION A
CONT. BOND BEAM ROOF JOIST - SEE PLAN B
6" AT MID HEIGHT OF PLATE p r o j e c t # : 21.0320
REINFORCING - SEE SCHEDULE
MASONRY W ALL - SEE PLAN d a t e : 02.14.2023
AND SCHEDULE FOR SIZE
AND REINFORCING revisions :
DETAIL 11 DETAIL 12 DETAIL 14
L
SCALE : NONE
S230 SCALE : NONE
S230 DETAIL 13
SCALE : NONE
S230
SCALE : NONE
S230 1 1/2" 6" 1 1/2"

1 1/2"
1/2" PLATE x REQ'D
CANOPY NOTES:

8"
1. SEE PLANS FOR CANOPY LOCATIONS.
2. ALL EXPOSED W ELDS TO BE GROUND SMOOTH.

1 1/2"
3. SEE ARCH. DRAW INGS FOR CANOPY DIMENSIONS,
ROD LOCATIONS AND OTHER INFO.

BENT PLATE TO
SECTION A title:
BEAM 3/4" DIA. ROD W / CLEVIS W /
3/16 2"-12" 3000# MIN CAPACITY (ASD)

BENT GUTTER TO A (2) #4 x CONT.


ROOF
HSS
SEE ROOF DECK
SEE ARCH.
15" MAX.
3/16 3"-12"
3/16 FRAMING
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

SCHEDULE
1/4" BENT GUTTER PLATE - MASONRY W ALL - SEE PLAN

BENT PLATE 1/4" x CONT. ROOF DECK - SEE SCHEDULE


SEE ARCH FOR ADD. INFO.

L2 x 2 x 3/16, W ELDED TO
AND SCHEDULE FOR SIZE
AND REINFORCING
TYP.
HSS 2 x 2 x 1/4 CROSS
MEMBER AT INTERIOR ROD
LOCATIONS. SLOPE
DETAILS
? FOR SIZE AND ATTACHMENT BENT PLATE ANCHOR ACCESS HOLE 3/16 MEMBER TO FOLLOW
4" PROFILE OF DECKING AND 3/4" DIA. EPOXY ANCHORS
2" MIN. DECK BEARING ROOFING
REQ'D. 3/4" DIA. EPOXY ANCHOR AT W / 6 3/4" MIN. EMBED - SEE
REQ'D. 3'-0"o.c. MAX. SPACING (NOTE: STRUCTURAL NOTES FOR
A BENT PLATE TO BEAR AT MASONRY RECESS MASONRY W ALL - SEE PLAN EPOXY INFO. A
LOCATIONS PROVIDE ANCHOR AND SCHEDULE FOR SIZE
ON BEAM FLANGE 2" MIN. AND REINFORCING
L2 x 2 x 3/16, TYP. ON EACH SIDE OF RECESS)
W BEAM - SEE PLAN
HSS BEAM - SEE PLAN L1 1/2 x 1 1/2 x 3/16 x HSS BEAM - SEE PLAN HSS BEAM - SEE PLAN 3/4" DIA. ROD AND CLEVIS
CONT. W / 3000# CAPACITY (ASD)
L1 1/2 x 1 1/2 x CONT.,
GRATING - SEE ARCH W ELDED TO HSS 1/2" CONNECTION PLATE x REQ'D sheet:

TYPICAL DECK EDGE ON BEAM


SCALE : NONE
15
S230
CANOPY DETAIL
SCALE : NONE
TYP. CANOPY SECTION CANOPY CONDITION AT INTERIOR
ROD SUPPORT LOCATION
ROD CONNECTION DETAIL

17
S230
S230 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

E D C B A
4 MECH OPENING IN W ALL ABOVE DOORS. COORDINATE
LOCATIONS W / ARCH / MECH DRAW INGS. DO NOT
W ALL SHADING SCHEDULE
TYP.
S230 PLACE IN MASONRY BEAM / JAMBS. PROVIDE
REINFORCING AROUND MECHANICAL OPENINGS PER 6" MASONRY W ALL, RECESSED (MW -6A)
STRUCTURAL NOTES / SCHEDULES.
MASONRY JAMB, TYP. - SEE
SCHEDULE ON SOIL FOR 10" MASONRY W ALL, RECESSED (MW -10A)
ROOF
SIZE AND REINFORCING

MASONRY JAMBS AND BEAMS, PER SCHEDULE (U.N.O.)

E E
360 west aspen avenue
SEE NOTE 4 salt lake city, utah 84101
801 532 4422

MASONRY WALL NOTES:

TYP. AT 1. SEE GENERAL STRUCTURAL NOTES ON S001 FOR ADDITIONAL INFORMATION.


RECESSED 2. SEE MASONRY SCHEDULES ON SHEET S011 FOR W ALL, JAMB AND BEAM REINFORCING UNLESS NOTED
MASONRY OTHERW ISE.
MASONRY BEAM - SEE 3. NOT ALL MASONRY W ALLS ARE SHOW N ON THIS SHEET. SEE PLANS AND SCHEDULE FOR ALL W ALL
11 LOCATIONS, SIZES AND REINFORCING. THESE ELEVATIONS ARE PRIMARILY FOR IDENTIFYING
TYP. SCHEDULE ON S011
S230 LOCATIONS W HERE RECESSES AND OTHER SPECIAL CONDITIONS OCCUR.
4. AT ALL RECESSED MASONRY LOCATIONS PROVIDE MASONRY BEAM ABOVE RECESS AS IF IT W ALL AN
OPENING. SEE DETAIL 9/S220 FOR ADDITIONAL INFORMATION.

9
S220
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
TYP. AT RECESSED DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
MASONRY ABOVE NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
OPENING
4
S210

FLOOR

D W ALL ELEVATION - GRID 1 A D


SCALE : 3/16" = 1'-0"
S301
1 2 3 4 5
3 2 TYP. 4
TYP. AT TYP. AT GRIDS
BETW EEN
S230 JOIST S230 S230 4 AND 5
JOISTS

RUN MASONRY BEAM (MB-8B) ROOF


MASONRY BEAM, TYP. - CONT. OVER BOTH OPENINGS
SEE SCHEDULE ON S011 AND RECESS

MASONRY JAMB, TYP. - SEE


SCHEDULE ON SOIL FOR
SIZE AND REINFORCING
TYP. AT RECESS
BETW EEN
OPENINGS
SEE NOTE 4 SEE NOTE 4 SEE NOTE 4 10
S220

FLOOR THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


11 ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
S220 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
NOTE: SOLID GROUT W ALL WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
TYP. AT RECESSED
SEGMENT BETW EEN WRITTEN PERMISSION FROM METHOD STUDIO INC.
MASONRY
C OPENINGS AT THIS LOCATION C
9 project:
S220
TYP. AT RECESSED
MASONRY ABOVE
OPENING
10
TYP.
USU EVR
S220
4
S210
TYP. EXPANSION
FLOOR

W ALL ELEVATION - GRID A B


SCALE : 3/16" = 1'-0"
S301
A B C D E F
670 EAST 1550 NORTH, LOGAN, UT
84341

B 3 TYP. AT 2 TYP. B
BETW EEN p r o j e c t # : 21.0320
JOIST MASONRY JAMB, TYP. - SEE MASONRY BEAM - SEE
S230 S230 JOIST
SCHEDULE ON SOIL FOR TYP. SCHEDULE ON SOIL d a t e : 02.14.2023
SIZE AND REINFORCING
revisions :
ROOF
EXTEND MASONRY BEAM
REINFORCING AROUND
CORNER

PROVIDE #4 VERTICAL
TYP. AT RECESSED TYP. AT RECESSED
BARS IN (3) CELLS
MASONRY BETW EEN MASONRY BETW EEN
ADJACENT TO OPENING
OPENINGS OPENINGS
10 10
S220 TYP. AT S220 TYP. AT
5 TYP. AT RECESS 4 TYP. AT RECESS title:
S220 BEAM S220 FLOOR
10 10

FLOOR
S220 S220
ELEVATIONS
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

4
TYP.
A S210 A

FLOOR
SEE NOTE 3 IN THE MASONRY BEAM SEE NOTE 3 IN THE MASONRY BEAM
CONNECTION SCHEDULE ON S011 CONNECTION SCHEDULE ON S011
FOR EMBED REQUIREMENTS AT 6"
W ALL LOCATIONS
FOR EMBED REQUIREMENTS AT 6"
W ALL LOCATIONS
sheet:

W ALL ELEVATION - GRID 5


SCALE : 3/16" = 1'-0"
C
S301
S301 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

E E
360 west aspen avenue
salt lake city, utah 84101
801 532 4422

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

D D

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

USU EVR
EXPANSION

670 EAST 1550 NORTH, LOGAN, UT


84341

B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :

Schematic View A
SCALE : NONE
S401 title:

SCHEMATIC
REFERENCE
BIM 360://USU EVR Facility Expansion/S-21914 - USU EVR Facility - v.21.rvt

A A

sheet:
NOTE: THIS VIEW REPRESENTS A SCHEMATIC

S401
RENDERING ONLY AND IS NOT INTENDED TO
CONVEY CONSTRUCTION INFORMATION. ALL
CONSTRUCTION SHALL COMPLY W ITH
SPECIFIC NOTES AND DETAILS W ITHIN THE
STRUCTURAL DRAW INGS.
BID SET
1 2 3 4 5 6
1 2 3 4 5 6
GENERAL NOTES - SITE
1 NO CROSS SLOPES GREATER THAN 2%

2 ALL LANDINGS AT BUILDING EXITS NOT TO EXCEED 2% SLOPE IN ANY DIRECTION

3 ALL SIDEWALK CURB CUTS TO HAVE ADA ACCESSIBLE RAMP AND DETECTABLE WARNING

4 DOORS SERVING SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE SHALL SWING IN THE DIRECTION OF TRAVEL AND
SHALL BE PROVIDED WITH PANIC HARDWARE. SEE SHEET SERIES A500

5 SEE A050 SHEET SERIES FOR FOR TYPICAL SITE DETAILS


NEW 7' WIDE
SIDEWALK
1550 NORTH EXISTING GATE, RELOCATE TO
NEW 6 GENERAL CONTRACTOR TO COORDINATE WITH LANDSCAPE, AND CIVIL DRAWINGS, AND SPECIFICATIONS
E E
7 SEE CIVIL FOR FULL ACCESSIBLE ROUTES AND SLOPES 360 west aspen avenue
salt lake city, utah 84101
8 SEE LANDSCAPE PLANS FOR IRRIGATION AND PLANTING DRAWINGS. 801 532 4422

EXISTING ELECTRICAL EXISTING TEST


EQUIPMENT TO TRENCH TO NEW LANE
REMAIN, TYP. REMAIN
E

EXISTING TEST
ROADWAY
E
E
E
E
E
E

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NEW AND
RELOCATED CHAIN E
E
E
SYMBOL LEGEND NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
LINK FENCE @ SITE
BOUNDARY BOUNDARY LINE
E
E
E PUBLIC UTILITY EASEMENT
E
SETBACK LINE

TEST TRENCH
PANELS TO REMAIN
E E E E E E

1.05%
2%
STORM DRAIN E E 2%
BOXES TO REMAIN
D D
1.8%
NEW TEST TRENCH
PAVED SHOULDER
WITH ELECTRICAL
NEW PULL BOXES FOR
DUMPSTER TEST PANELS
LOCATION
EXISTING ELECTRICAL
EQUIPMENT TO
REMAIN, TYP.

700 EAST
BF

E5
________
________
A051
ELECTRIC VEHICLE AND BF E
ROADWAY RESEARCH BF

FACILITY NEW RETAINING


WALL
EXISTING TEST
TRENCH TO (BUILDING FOOTPRINT) BF
REMAIN BF

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


BF
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
BF MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C 14' - 6"
8' - 0 1/4"
C
project:
BF

USU EVR
EXPANSION
STORM DRAIN
BOXES TO REMAIN

670 EAST 1550 NORTH, LOGAN, UT


84341

B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :
1 Review Responses 03.06.2022

NEW LANE title:

EXISTING TEST ROADWAY


SITE AND
STAGING
NEW LANE
PLAN

A A

sheet:

A1 SITE PLAN
1 : 300
A001 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

FIBERGLASS GRATE
RATED FOR H-20
TRAFFIC 8" 8" 3' - 6" 8" 8"
FIBERGLASS ANGLE
GRATE SHELF.
NEW ASPHALT, RE:
CIVIL

GRAVEL

1' - 6"
SLOPE SLOPE
1/4" PER 1' 1/4" PER 1'
SLOPE 1/4" PER 1' TO DRAIN.
RE: CIVIL

E 12" CONCRETE SLAB E


& FOOTING, SLOPE 360 west aspen avenue
TO CENTER AND TO salt lake city, utah 84101
DRAIN. FIBERGLASS 801 532 4422
FRP
REINFORCEMENT RE:
CIVIL

EXTERIOR TEST TRENCH


E5 1" = 1'-0"

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

D D

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

USU EVR
EXPANSION

670 EAST 1550 NORTH, LOGAN, UT


84341

B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :

title:

SITE
DETAILS

A A

sheet:

A051 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES - FLOOR PLAN


1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
C1 CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
1.2 A301 A201 5
2 DO NOT SCALE THE DRAWINGS

D1 3 ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED

G G 4 ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE

5 SEE G000 SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
09.55 WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
E E
6 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED 360 west aspen avenue
salt lake city, utah 84101
7 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES 801 532 4422

8 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES

9 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS


A1
A301 10 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
43' - 0"

11 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT IN
ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
E5
A523 12 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CW1 CORRECTLY CENTERED BETWEEN THE SOFFITS
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
100A 13 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF NOT INTENDED FOR CONSTRUCTION, RECORDING
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE PURPOSES, OR IMPLEMENTATION
OF JAMB UNLESS NOTED OTHERWISE

13' - 4"
VESTIBULE
100A
B2 198 SF
A561
SF1
SF6
F F
100B

UP
STAIRS A5
ENTRY/RECEPTION 100C
3' - 10" A401
100B
18' - 4"

183 SF
D B3
707 SF
B3 D
A301
E1 A413
A301 KEYED NOTES
E5 07.32
SIM.
A523
C4 03.30 TRENCH SUMP W/ FIBERGLASS BAR GRATE COVER. NO SLOPE OR DRAIN AT BOTTOM OF TRENCH
A401 ELEVATOR 05.01 STEEL COLUMN, TYP. PAINT. RE: STRUCTURAL
E ELECTRICAL EQUIPMENT
CLEARANCE
A1 E1 A4 A3 100D E 05.23 36" TALL 6" PAINTED ROUND CONCRETE FILLED STEEL BOLLARD WITH ROUND TOP CONDITION, FLANGE MOUNTED TO
FOOTING BELOW SLAB
5' - 0"

A412 A542 A542 64 SF


108 100C A542 07.32 CONTINUOUS SEISMIC SEPARATION JOINT BETWEEN EXISTING AND NEW CONSTRUCTION
108 05.23 IHM1
263 SF 100E 09.55 PATCH & REPAIR WALL AND FISNISHES AS REQUIRED AFTER INSTALLATION OF PIPING
D D

8 3/8"
UP 10.77 CAST IN PLACE TEST TRENCH W/ FIBERGLASS GRATING COVER RATED FOR H-20 TRAFFIC. REINFORCE W/ FIBERGLASS
114a
10.78 CAST IN PLACE CABLE TRENCH W/ FIBERGLASS GRATING COVER RATED FOR H-20 TRAFFIC. REINFORCE W/ FIBERGLASS
1' - 4"

114b
WITHIN 4' OF TEST TRENCH
D.1 IHM4 OFFICE SF1 D.1 22.05 ADA HI / LOW DRINKING FOUNTAIN WITH BOTTLE FILLER, RE: PLUMBING
1.2 113
22.28 EMERGENCY EYE WASH & SHOWER STATION. RE: PLUMB
SOLDERING C2 IHM2 23.02 MECHANICAL EQUIPMENT, RE: MECHANICAL
113 121 SF
110D A402
CUTTING / GRINDING

20' - 4"
CONCRETE & EPOXY POURING 230 SF
110A 110B
110Aa
353 SF 437 SF 115
LARGE CONFERENCE
114 SF1
OFFICE
110C 819 SF IHM5
IHM3 115
COMPRESSOR
121 SF
110C 05.23
110A 110B 16 SF 110D

E4 A413 D1
48' - 8"

22.28 THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


SF1 ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
110 IHM6 OFFICE MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
IHM4
E2 117 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
121 SF WRITTEN PERMISSION FROM METHOD STUDIO INC.
117
C C
FLEXIBLE WORK 119
project:
114c SF1
110 A413 OFFICE

A201 A1
SF1
3,086 SF
A413 A1 CUSTODIAL STORAGE
122
STORAGE
120
F2
COFFEE
118
IHM5 119
121 SF
C1 A201
USU EVR
48 SF D2

SF1 D5 122
61 SF
120
92 SF
EXPANSION
E1 SF1
A511 A7
100Ea A411 OFFICE A312
IHM4 127
124 126 HALLWAY
TYP.
C E4 10.78 10.78
22.05 100E 121 SF C
827 SF 127
A511
F1 RESTROOM RESTROOM PRINT/COPY
05.23 124 126 128 D3 A413
05.23 129
92 SF 84 SF 29 SF
OFFICE SF1
IHM5 129
10.77 121 SF
D1 112Ab D1
A301 A301
30' - 0"

670 EAST 1550 NORTH, LOGAN, UT


112a TRUCK BAYS SIM 84341
03.30 112 E5
10.77 A511
SIM. 4,933 SF OFFICE - DIRECTOR / EXEC
E4 D5 ELECTRICAL IT / MDF
112A 130 131 SF1
A511 A511
201 SF 210 SF 201 SF
IHM7 IHM4

23.02 131
130
B 112Aa B
p r o j e c t # : 21.0320
05.23
B 05.23
10.78 133
B d a t e : 02.14.2023
05.01
SF1
revisions :
MECHANICAL IHM5
E4 112B OFFICE - DIRECTOR / EXEC 1 Review Responses 03.06.2022
112B
A511 326 SF 133
248 SF

STAIRS
112b 03.30
100F
234 SF IHM7 135
33' - 4"

C2

BREAK / KITCHENETTE
title:
A413
05.23 DYNAMOMETER 135
05.23 (N.I.C.)
734 SF
SF1 OVERALL
112

100F
A5
135a
PLAN LEVEL
A A402 135b
A
SF1 SF1 SF1 SF1 SF1 SF1 SF2 SF1 SF2
1
29' - 0" 28' - 0" 29' - 0" 46' - 0"
132' - 0"

B2
A C1 A1
A
1 A301
2 3 A201
4 A301
5

sheet:
LEVEL 1 FLOOR PLAN
A1
A101
1/8" = 1'-0"

BID SET
1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES - FLOOR PLAN


1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
C1 A1 CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
1 1.2 A301 2 3 A201 4 A301 5
2 DO NOT SCALE THE DRAWINGS

D1 3 ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED

G 4 ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE

5 SEE G000 SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
E E
6 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED 360 west aspen avenue
salt lake city, utah 84101
7 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES 801 532 4422

8 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES

9 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS

10 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION

11 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT IN
ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS

05.37 07.33 12 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
13 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF NOT INTENDED FOR CONSTRUCTION, RECORDING
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE PURPOSES, OR IMPLEMENTATION
OF JAMB UNLESS NOTED OTHERWISE

A3
A551
B1
A511 SF1 CW3

F
DEMO EXISTING WINDOW & PATCH TO ROOF ACCESS
200A 200A CW2 C5
MATCH EXSTING CMU WALL. ALSO REFER STAIRS
TO STRUCTURAL DRAWINGS ROOF TERRACE 24 SF A401
200C
- SF3
07.32 170 SF
671 SF
D B3 B3 D
A301 DN A301 KEYED NOTES
E5 sim. C5 A201 D4 201
A523 02.34 EXISTING ROOF ACCESS LADDER TO BE REMOVED. COORDINATE SALVAGE OR DISPOSAL WITH OWNER
C4 05.01 STEEL COLUMN, TYP. PAINT. RE: STRUCTURAL
LANDING AREA
05.04 STEEL GUARDRAIL, PAINTED
200B A401
C1
233 SF
E 05.37
07.32
STAINLESS STEEL GUARDRAIL, RE: DETAILS
CONTINUOUS SEISMIC SEPARATION JOINT BETWEEN EXISTING AND NEW CONSTRUCTION
A411
02.34 07.33 PRECAST CONCRETE PARAPET CAP
05.01 IHM4
7" 4' - 0" 200E
STORAGE
D
D1
201 201
22 SF
STORAGE
204
RESTROOM
202 PERSONAL CARE A414 SF1 D.1
05.04 127 SF 70 SF 203
203
111 SF D2
HALLWAY
MEZZANINE STORAGE 204 202 200E
209 D3
213 273 SF
C2
1,037 SF GROUP WORK
A402 209 SF1
206 208 A414
151 SF
PRINT / COPY IHM8
DN
RESTROOM 210 D4
RESTROOM 40 SF
206
D1 208
63 SF
A532 97 SF
05.04 D5 A414
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
C1 SF1 ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
A414 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
B1
C A1 C
A411 A411
project:
SF1

A413 A1
C1 A201
USU EVR
EXPANSION
SF1
A7
A312

C
B4

B1 A414 C2
SF1

D1 D1
A301 SF7 A301
OPEN WORK AREA
670 EAST 1550 NORTH, LOGAN, UT
212
3,420 SF
84341

SF1

B B
p r o j e c t # : 21.0320

B d a t e : 02.14.2023

SF1
revisions :
1 Review Responses 03.06.2022

STAIRS
200F
200F
234 SF IHM10 IHM11 IHM11
212C 212B 212A
GROUP WORK GROUP WORK GROUP WORK title:
212B 212A
212C
178 SF

A1 A414 A2 A3
138 SF

A414 A4 A5
136 SF

A414
SF1 OVERALL
PLAN LEVEL
A
SF1 SF2 SF1 SF2 SF2
2
9

C1 C5 A1
B2 A604
A A301 A402 A301 A
A201

sheet:
LEVEL 2 FLOOR PLAN
A1 1/8" = 1'-0"

A102 BID SET


1 2 3 4 5 6
1 2 3 4 5 6
GENERAL NOTES - ROOF PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
C1 A1
1 1.2 A301 2 3 4 A301 5 2 DO NOT SCALE DRAWINGS

29' - 0" 28' - 0" 29' - 0"


3 CRICKET AT ALL MECHANICAL ITEMS, SKYLIGHTS, ROOF HATCHES; 1/4" PER FOOT BACKSLOPE MINIMUM

G 4 SEE BUILDING AND WALL SECTIONS FOR ADDITIONAL ROOF DETAILS; SEE SHEET SERIES AE500 FOR ROOF ASSEMBLY
CONSTRUCTION

5 ROOF/OVERFLOW DRAIN LOCATIONS SHOWN ARE APPROXIMATE; EXACT LOCATIONS SHALL BE DETERMINED IN FIELD.
ROOF/OVERFLOW DRAINS TO BE PLACED TO ONE SIDE OF STRUCTURAL ELEMENT (IF EXISTS) AND INSTALLED AT LOWEST
POINT
E E
360 west aspen avenue
6 ALL GIVEN DECK BEARING POINTS ARE AT GRID LINE LOCATIONS UNLESS NOTED OTHERWISE
salt lake city, utah 84101
7 PROVIDE ROOFTOP WALKING PAD PATHWAY TO ALL AIR HANDLER UNITS, EXHAUST FANS, AND SPLIT UNITS ON ROOF 801 532 4422

8 ALL DRAIN COVERS OR SCREENS ARE TO BE CAST IRON

EXISTING EVR FACILITY


DRAINAGE TO REMAIN UNCHANGED 15' - 10 3/4" 29' - 11 1/4"

4' - 0"
EL. 112' - 5 7/8"
KEYED NOTES
EL. 112' - 5 7/8" 05.36 STEEL HANDRAIL MOUNTED TO CMU WALL THROUGH MEMBRANE AND INSULATION UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
07.31 CONTINUOUS SELF ADHERING SHEET WATERPROOFING, TYP. NOT INTENDED FOR CONSTRUCTION, RECORDING
08.11 ROOF ACCESS HATCH WITH INTEGRATED GUARDRAIL AND TELESCOPING SAFETY POLE PURPOSES, OR IMPLEMENTATION
08.12 ROOFTOP SOLAR TUBE LIGHT, SOLATUBE SKYVAULT B.O.D.

1/4" / 1'-0"
23.09 ADD ALTERNATE MECHANICAL EQUIPMENT, RE: MECHANICAL

EL. 112' - 2 15/16"


EL. 128' - 9 15/16"

F
D4
RF2 A532
07.31
08.11
B3 B3
D A301 A301 D
RF1

E5 TYP.
A523

1/2" / 1'-0"

1/2" / 1'-0"
1/4" / 1'-0" EL. 120' - 4 1/2" 1/4" / 1'-0" EL. 112' - 5 7/8" EL. 112' - 5 7/8"

D
EL. 128' - 6 7/16" EL
.1
D.1
27
'-
10

3/4" / 1'-0"
INSULATION OVERBUILD 1/2
"

15' - 6" 9' - 2" 26' - 2"


8' - 0" 3/8" / 1'-0"
23.09
EL. 126' - 4 3/4"

RF1 THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


RF1 Sim
D2 D2 ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
A532 A532 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
08.12 08.12 08.12
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
D6
C C
D1 A522
project:
24' - 2"

A532
1 13/16" / 1'-0"

05.36

USU EVR
20' - 7"

EXPANSION

3/4" / 1'-0"
EL. 127' - 10 1/2"
2' - 6"

EL. 127' - 10 1/2" EL. 127' - 10 1/2"


C
4' - 0"

4' - 0" EL. 127' - 10 1/2"


9/16" / 1'-0"

9/16" / 1'-0"

08.12 ROOF LEGEND


D1 D1
A301 A301

TAPERED RIGID INSULATION, SEE BELOW FOR CRICKET DESIGN


670 EAST 1550 NORTH, LOGAN, UT
12' - 6"

REQUIREMENTS 84341

SLOPED ROOF STRUCTURE, RE: A501 FOR ASSEMBLY


11/16" / 1'-0" 5/8" / 1'-0" 3/8" / 1'-0" TYPES AND STRUCTURAL DRAWINGS
08.12
6' - 3"

RF1
11/16" / 1'-0"
B ROOFTOP WALKING PADS, 3' WIDE MIN. B
51' - 4"

p r o j e c t # : 21.0320
EL. 126' - 4 3/4" EL. 126' - 4 5/8"
RF1
B d a t e : 02.14.2023
6' - 3"

revisions :
1 Review Responses 03.06.2022
08.12

7' - 2"
23.09
CRICKET DESIGN REQUIREMENTS
ROOF SURFACE SLOPE

CRICKET WIDTH
LOPE

SURF
A LLEY S

CRIC
V
KET

ACE
CRIC

KET
20.89°

SLOP
ANGLE

E
title:
9/16" / 1'-0"

CRICKET LENGTH

EL. 127' - 10 1/2"


ROOF PLAN
EL. 127' - 10 1/2"
EL. 127' - 10 1/2"

A
1 TO 1 1.73 TO 1 2 TO 1 3 TO 1 4 TO 1
LENGTH TO LENGTH TO LENGTH TO LENGTH TO LENGTH TO
WIDTH RATIO WIDTH RATIO WIDTH RATIO WIDTH RATIO WIDTH RATIO
C1 A1 45° ANGLE 30° ANGLE 27° ANGLE 19° ANGLE 14° ANGLE
A A301 A301 A
THE ABOVE CRICKET VALLEY SLOPES AND ANGLES ARE APPROXIMATE AND ARE INTENDED TO SHOW THE RELATIONSHIP BETWEEN
THE LENGTH TO WIDTH RATIOS AND VALLEY SLOPES. THIS INFORMATION IS NOT A RECOMMENDATION, IT IS RATHER A FACTUAL
REPRESENTATION TO HELP INDUSTRY PROFESSIONALS PROPERLY SIZE CRICKETS FOR COMMERCIAL ROOFING.

THE INFORMATION CLEARLY SHOWS THE NEED FOR WIDER CRICKETS WHEN USING LOW "ROOF SURFACE SLOPES" IN ORDER TO
ACHIEVE ADEQUATE VALLEY SLOPES. PROJECTS THAT UTILIZE THE SAME CRICKET WIDTH ALL OVER THE ROOF WILL HAVE VALLEY sheet:
SLOPES THAT VARY CONSIDERABLE. WHILE THIS APPROACH MAY BE EASIER TO INSTALL, IT DOES NOT ACHIEVE CONSISTENT
DRAINAGE.

A1 OFFICE ROOF DECK


1/8" = 1'-0"
THE SAME LENGTH TO WIDTH RATIO SHOULD NOT BE USED FOR DIFFERENT ROOF SURFACE SLOPES WITHOUT FIRST REALIZING
THE EFFECT ON VALLEY SLOPE. FOR EXAMPLE, A CRICKET WITH A LENGTH TO WIDTH RATIO OF 4 TO 1 INSTALLED ON 1/4" PER
FOOT ROOF SURFACE SLOPE HAS A VALLEY SLOPE OF APPROX. 2/33" PER FOOT (1/16" PER FOOT). THE SAME CRICKET INSTALLED
ON 1/8" PER FOOT ROOF SURFACE SLOPE HAS A VALLEY SLOPE OF APPROX. 1/33" PER FOOT. THIS IS WHY EACH UNIQUE ROOF
SURFACE SLOPE SHOULD HAVE ITS OWN UNIQUE LENGTH TO WIDTH RATIO FOR CRICKETS.

ONE FINAL NOTE, INCREASING THE CRICKET SURFACE SLOPE HAS NO EFFECT ON THE VALLEY SLOPE.
A103 BID SET
1 2 3 4 5 6
1 2 3 4 5 6
GENERAL NOTES - SLAB
1 COORDINATE SLAB EDGE PLANS WITH STRUCTURAL DRAWINGS FOR REQUIRED REINFORCING, ESPECIALLY AT ALL
PENETRATIONS

1.2
1.2 2 5 2 COORDINATE SLAB EDGE PLANS WITH MECHANICAL DRAWINGS FOR HOUSEKEEPING PADS, SIZE(S), AND EXACT
LOCATION(S)

3 COORDINATE SLAB EDGE PLANS WITH WALL TYPES FOR ACOUSTIC ISOLATION TREATMENTS

G G G G 4 COORDINATE SLAB EDGE PLANS WITH MANUFACTURER FOR DEPTHS AND DIMENSIONS OF ALL ELEVATOR PITS AND
WHEELCHAIR LIFT SLAB RECESSES

5 MAJOR SLAB PENETRATIONS SHOWN ON THIS PLAN. MINOR PENETRATIONS, SUCH AS FOR INDIVIDUAL PIPES AND
CONDUITS TO BE COORDINATED WITH MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE DESIGNS. LOCATIONS TO BE
E PROVIDED TO ARCHITECT FOR APPROVAL BY CONTRACTOR PRIOR TO COMMENCING WORK E
360 west aspen avenue
6 THE MINIMUM SLOPE FOR ANY DRAINING SURFACE IS 1/4" PER 1'-0" salt lake city, utah 84101
801 532 4422
7 DRAIN PENETRATIONS SHOWN ARE FOR COORDINATION PURPOSES ONLY, VERIFY SIZE AND PLACEMENT WITH PLUMBING
AND MANUFACTURERS

12' - 5 3/8"
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

29' - 4 3/8" 10 5/8"

1' - 2 5/8"
F F

D D

23' - 4"
3' - 9 3/4"
E E E 8' - 5 3/8" E
1' - 4" 5' - 0"

11' - 10 5/8"

D D

1' - 4"
10 5/8"

5' - 0"
D.1 D.1
1.2
1.2 2

20' - 4"
7 5/8"
48' - 8"

48' - 8"
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
1' - 2 5/8" 6' - 0" 8' - 4" 6' - 4" 8' - 4" 16' - 4" 4' - 0" 7' - 11 5/8" ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:
03.31 F2
EL. 100' - 0" USU EVR
1' - 1'2"- 4" 9' - 8" 1' - 4" 5' - 10"
EXPANSION

136' - 8"
1' - 8"

C C
5' - 6"
118' - 4"

F1

EL. 98' - 6" EL. 100' - 0" 03.31


12' - 0"

F4
30' - 0"

30' - 0"
20' - 6"

670 EAST 1550 NORTH, LOGAN, UT


4' - 2 5/8"
84341

18' - 2" EL. 98' - 6"


4' - 11"

F4
4' - 0 1/2"

B B
5' - 10"

p r o j e c t # : 21.0320
B B d a t e : 02.14.2023
1' - 11 1/2"

revisions :
5' - 10" 17' - 2" 1' - 4" 23' - 2"
20' - 6"
33' - 4"

33' - 4" title:

LEVEL 1
10' - 4"
1' - 2 5/8"

SLAB PLAN
10 5/8"

A A
5/8" 8" 10 5/8"
1' - 2 5/8"
29' - 0" 28' - 0" 29' - 0" 46' - 0"

132' - 0"

A 1 2 3 4 5 A

sheet:

A1 LEVEL 1 SLAB PLAN


1/8" = 1'-0"
A111 BID SET
1 2 3 4 5 6
1 2 3 4 5 6
GENERAL NOTES - SLAB
1 1.2
1.2 2 3 42 5 1 COORDINATE SLAB EDGE PLANS WITH STRUCTURAL DRAWINGS FOR REQUIRED REINFORCING, ESPECIALLY AT ALL
PENETRATIONS

2 COORDINATE SLAB EDGE PLANS WITH MECHANICAL DRAWINGS FOR HOUSEKEEPING PADS, SIZE(S), AND EXACT
G G G LOCATION(S)

3 COORDINATE SLAB EDGE PLANS WITH WALL TYPES FOR ACOUSTIC ISOLATION TREATMENTS

4 COORDINATE SLAB EDGE PLANS WITH MANUFACTURER FOR DEPTHS AND DIMENSIONS OF ALL ELEVATOR PITS AND
WHEELCHAIR LIFT SLAB RECESSES

5 MAJOR SLAB PENETRATIONS SHOWN ON THIS PLAN. MINOR PENETRATIONS, SUCH AS FOR INDIVIDUAL PIPES AND
CONDUITS TO BE COORDINATED WITH MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE DESIGNS. LOCATIONS TO BE
E PROVIDED TO ARCHITECT FOR APPROVAL BY CONTRACTOR PRIOR TO COMMENCING WORK E
360 west aspen avenue
6 THE MINIMUM SLOPE FOR ANY DRAINING SURFACE IS 1/4" PER 1'-0" salt lake city, utah 84101
801 532 4422
7 DRAIN PENETRATIONS SHOWN ARE FOR COORDINATION PURPOSES ONLY, VERIFY SIZE AND PLACEMENT WITH PLUMBING
AND MANUFACTURERS

16' - 0" 4' - 9 7/8"

12' - 8"
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
10' - 1 1/16" 14' - 5 15/16"

6' - 4 1/4"
SEE ROOF PLAN 7"
FOR DECK
BEARING

6' - 7 3/8"
ELEVATIONS

23' - 2 5/8"
D D

10' - 0 1/2"
E E
8' - 7" 7 5/8"
E
1' - 6 1/4"
D

7 5/8"
1.2 2 D.1

15' - 10 3/8"
F3 EL. 111' - 0"

3' - 10"
27' - 5 1/8" 34' - 1 1/4"

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
project:

F3
USU EVR
EXPANSION
C

EL. 114' - 0"

670 EAST 1550 NORTH, LOGAN, UT


84341

B
B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

revisions :
1 Review Responses 03.06.2022
5' - 8"
7' - 10 1/2"

title:
10' - 1"

LEVEL 2
7 5/8"

A
SLAB PLAN

A A

sheet:

A1 LEVEL 2 SLAB PLAN


1/8" = 1'-0"
A112 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES
C1 A1 A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
1 1.2 A301 2 3 4 A301 5 UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK

B. DO NOT SCALE THE DRAWINGS

C. ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED


G D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE

E. SEE G000 SHEET SERIES FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT

F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
E INSTALLED
E
360 west aspen avenue
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES salt lake city, utah 84101
801 532 4422
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES

I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS

J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION

K. VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES AE400. CONTRACTOR TO VERIFY AND MAXIMIZE
CEILING HEIGHT IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS

L. ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION
EM8a OF THE DROPPED SOFFITS HAVE BEEN DETERMINED.THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE
30' - 0"
CENTERED ARE CORRECTLY CENTERED BETWEEN THE SOFFITS.

M. SEMI-FLUSH LIGHT FIXTURE TO BE CENTERED OVER UNIT KITCHEN ISLANDS & CENTERED WITHIN FIXED
DINING ROOMS AT UNITS. SEE AE400 UNIT SHEET SERIES FOR LOCATIONS.
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
N. DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING

EM8a
LENGTH OF WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. PURPOSES, OR IMPLEMENTATION
ASSUME CENTERED IN FACE OF JAMB UNLESS NOTED OTHERWISE.

13' - 4"
O. ALL PANEL MOLDING TO HAVE MITERED CORNERS AND CONSISTANT MOUNTING HEIGHT AND SPACING
WITHIN THE SAME SPACE.
EM12a

F LEGEND: INT. PARTITION HEAD CONDITIONS

EM8a
TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF

PS3a

14' - 6 1/4"
a - PARTITION EXTENDS FROM FLOOR TO 6" ABOVE CEILING
B3 ENTRY/RECEPTION B3
D A301
100B
A301 b - ACOUSTIC PARTITION D

23' - 4"
PS2a
707 SF PS2a

27' - 4 1/16"
8' - 3 3/4"
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION

8' - 9 3/4"
PS3a
E
EM8a

7"
5' - 0"

1' - 10 1/2" 17' - 3 1/2" 8' - 0" 4' - 8" WALL TYPE HEAD CONDITION LEGEND
IF NULL = TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
D a= PARTITION EXTEND FROM FLOOR TO 6" ABOVE CEILING
UP D.1 b= ACOUSTIC PARTITION
EM8
EM8a EM8 PS3a
7' - 2"

OFFICE

11' - 7"
19' - 0" 24' - 0" 12' - 0 1/2" PS2a

EM8 PS2a
113

14' - 8"
CONCRETE & EPOXY POURING CUTTING / GRINDING SOLDERING 121 SF FIRE RATED WALL TAG (description)

10' - 0"
LARGE CONFERENCE

EM8
EM8
EM8

110A 110B 110D 114


20' - 4"

353 SF 437 SF 230 SF 819 SF CORE MATERIAL (SEE LEGEND BELOW)


2' - 9 5/8"
8' - 0"

1' - 4" 3' - 0" LAYERS (REF PARTITIONS SHEET)

PS8b
OFFICE
1SA6a

10' - 8"
PS3b 115

10' - 0"
PS3b

121 SF
PS3b

PS3b
13' - 5" HEAD CONDITION MODIFIER (IF APPLICABLE)
11' - 6"

CORE SIZE (ROUNDED; SEE LEGEND)


EM8

20' - 1 3/4"

PS3b
EM8 FIRE RATING (IF APPLICABLE)
50' - 0"

50' - 0"
PS3b THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
OFFICE

10' - 8"
6' - 0" 14' - 8" 7' - 1 3/8" 17' - 6 5/8" 11' - 4" ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
117 NON-FIRE RATED WALL TAG (description) MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE

10' - 0"
121 SF COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
CORE MATERIAL (SEE LEGEND)
7' - 6"

PS6b WRITTEN PERMISSION FROM METHOD STUDIO INC.


LAYERS (SEE LEGEND)
C C
PS3b
SA6a project:
3' - 4"

EM12a

FLEXIBLE WORK CUSTODIAL STORAGE STORAGE OFFICE

10' - 8"
PS6b
8' - 6 1/2"
USU EVR

10' - 0"
110 122 120 119
HEAD CONDITION MODIFIER (IF APPLICABLE)
3,086 SF 61 SF 92 SF 121 SF
CORE MATERIAL LEGEND CORE SIZE (ROUNDED; SEE LEGEND)

EM8a
PS6b
PS6b
7' - 4"

HALLWAY C= CONCRETE WALLS, MASONRY


EXPANSION

136' - 8"
7' - 6 1/2" 11' - 6 1/4" 100E S= STEEL STUDS
6' - 2 1/2"

PS8b 827 SF W= WOOD STUDS


9' - 4" 9' - 7 1/4" 3' - 8" PS3b OFFICE

10' - 8"
127

12' - 7 15/16"
CORE SIZE LEGEND
9' - 1 1/4"

121 SF
C STEEL STUDS WOOD STUDS MASONRY (WIDTH) BCONCRETE (WIDTH)

PS8b
1= A7/8"
RESTROOM RESTROOM
F1
10' - 7"

124 126 2= 1 5/8" 1 1/2"

PS12b
3= 2 1/2" 2 1/2"
113' - 4"

92 SF 84 SF PS3b 4= 3 5/8" 3 1/2" MASONRY SIZE 4"


1 FS6b PS6b OFFICE 5=

10' - 8"
129 6= 6" 5 1/2" MASONRY SIZE 6" CONCRETE 6"
8= 8" 7 1/4" MASONRY SIZE 8" CONCRETE 8"
4"

121 SF
D1 D1 10 = 9 1/4" MASONRY SIZE 10" CONCRETE 10"

12' - 8"
PS3b
12 = 11 1/4" MASONRY SIZE 12" CONCRETE 12"
A301 ELECTRICAL IT / MDF A301 14 = CONCRETE 14"
30' - 0"

30' - 0"
112A 130 16 = MASONRY SIZE 16"
670 EAST 1550 NORTH, LOGAN, UT
22' - 8"

PS3b
201 SF 210 SF
84341

PS8b
SUPERSCRIPT NOTES -
17' - 9 3/4"

PS3b
1 FS8b

A - HAT CHANNEL FURRING IN LIEU OF METAL STUD


OFFICE - DIRECTOR / EXEC B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES

13' - 9"
10' - 6 3/4" 11' - 4" 131
201 SF
1 FS3b

TRUCK BAYS

12' - 8"
PS3b
112
4,933 SF 1 FS6b
B B
1' - 8 1/2"
3' - 4 3/4"

p r o j e c t # : 21.0320

21' - 10 3/4"
B d a t e : 02.14.2023

revisions :
1 FS8b

16' - 10"
MECHANICAL
15' - 1"

112B
16' - 8"
326 SF
22' - 8"

1 FS6b
PS3b OFFICE - DIRECTOR / EXEC
133
248 SF
33' - 4"

33' - 4"
PS2a

BREAK / KITCHENETTE title:

17' - 10"
135
734 SF
LEVEL 1
7' - 4"

DIMENSION
2' - 0"

A
EM12a
EM8a
PLAN
A1
C1 A301
A 1 A301
2 3 4 5 A

9' - 4" 7' - 4" 11' - 4" 7' - 4" 11' - 4" 7' - 4" 24' - 0" 8' - 0" 10' - 0" 3' - 4" 3' - 4" 8' - 8" 16' - 8" 4' - 0"

29' - 0" 28' - 0" 29' - 0" 46' - 0"


86' - 0" 46' - 0" sheet:

A1 LEVEL 1 DIMENSION PLAN


1/8" = 1'-0"
A121 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES
C1 A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
1 1.2 A301 2 3 4 5 UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK

B. DO NOT SCALE THE DRAWINGS

C. ALL EXPOSED INTERIOR COLUMNS TO BE PAINTED


G D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE

E. SEE G000 SHEET SERIES FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT

F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
E INSTALLED
E
360 west aspen avenue
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES salt lake city, utah 84101
801 532 4422
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES

I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS


A1 J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
A301
K. VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES AE400. CONTRACTOR TO VERIFY AND MAXIMIZE
CEILING HEIGHT IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS

L. ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION
OF THE DROPPED SOFFITS HAVE BEEN DETERMINED.THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE
CENTERED ARE CORRECTLY CENTERED BETWEEN THE SOFFITS.

M. SEMI-FLUSH LIGHT FIXTURE TO BE CENTERED OVER UNIT KITCHEN ISLANDS & CENTERED WITHIN FIXED
DINING ROOMS AT UNITS. SEE AE400 UNIT SHEET SERIES FOR LOCATIONS.
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
N. DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
LENGTH OF WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. PURPOSES, OR IMPLEMENTATION
ASSUME CENTERED IN FACE OF JAMB UNLESS NOTED OTHERWISE.
25' - 0 3/4"
O. ALL PANEL MOLDING TO HAVE MITERED CORNERS AND CONSISTANT MOUNTING HEIGHT AND SPACING
5' - 8 3/4" 19' - 4" WITHIN THE SAME SPACE.
EM12a

F LEGEND: INT. PARTITION HEAD CONDITIONS

PS3c
TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF

PS3b
a - PARTITION EXTENDS FROM FLOOR TO 6" ABOVE CEILING

18' - 4"
B3 B3
D PS3b b - ACOUSTIC PARTITION D

ES6
A301 A301

11' - 0 1/4"
PS2a EM8
1-HR FIRE RATED PARTITION

EM8a
2-HR FIRE RATED PARTITION

EM8a

5' - 0"
ES6 PS2a WALL TYPE HEAD CONDITION LEGEND

SS6
IF NULL = TYPICAL PARTITION FLOOR TO FLOOR/CEILING/ROOF
D a= PARTITION EXTEND FROM FLOOR TO 6" ABOVE CEILING

PS6b
b= ACOUSTIC PARTITION

4' - 2"
PS8b
5' - 6" PS3a
D.1

10' - 4"
10' - 9"
EM8

PS6b
PS6b
PS6b 15' - 5 3/8"
PS6b FIRE RATED WALL TAG (description)

EM8a
CORE MATERIAL (SEE LEGEND BELOW)

10' - 0"
13' - 5" 8' - 6"

5' - 4 1/2"

4' - 9 1/4"
LAYERS (REF PARTITIONS SHEET)
PS3b

10' - 5 3/4"
PS6b 15' - 7 3/4"

1SA6a

PS6b
PS6b PS6b
DN
HEAD CONDITION MODIFIER (IF APPLICABLE)

10' - 8"

10' - 0"
CORE SIZE (ROUNDED; SEE LEGEND)

PS12b

PS3b
D1
A532 FIRE RATING (IF APPLICABLE)

50' - 0"
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
NON-FIRE RATED WALL TAG (description) MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
PS6b WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
CORE MATERIAL (SEE LEGEND)
WRITTEN PERMISSION FROM METHOD STUDIO INC.

10' - 0"
PS2a LAYERS (SEE LEGEND)
C C
EM8

SA6a project:

22' - 9 1/2"
CORE MATERIAL LEGEND
HEAD CONDITION MODIFIER (IF APPLICABLE)
CORE SIZE (ROUNDED; SEE LEGEND)
USU EVR

10' - 0"
C=
S=
W=
CONCRETE WALLS, MASONRY
STEEL STUDS
WOOD STUDS
EXPANSION
CORE SIZE LEGEND
C STEEL STUDS WOOD STUDS MASONRY (WIDTH) BCONCRETE (WIDTH)

12' - 8"
1= A7/8"

2= 1 5/8" 1 1/2"
3= 2 1/2" 2 1/2"
4= 3 5/8" 3 1/2" MASONRY SIZE 4"
5=
6= 6" 5 1/2" MASONRY SIZE 6" CONCRETE 6"
8= 8" 7 1/4" MASONRY SIZE 8" CONCRETE 8"
D1 D1 10 = 9 1/4" MASONRY SIZE 10" CONCRETE 10"
12 = 11 1/4" MASONRY SIZE 12" CONCRETE 12"
A301 A301 14 = CONCRETE 14"

30' - 0"
16 = MASONRY SIZE 16"

12' - 8"
670 EAST 1550 NORTH, LOGAN, UT
SUPERSCRIPT NOTES - 84341
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES
2' - 8 1/32"

B B
PS8b

12' - 8"
p r o j e c t # : 21.0320
B d a t e : 02.14.2023

revisions :
17' - 11 1/2"

33' - 4"
23' - 4"
PS3b

17' - 7 1/8" 13' - 11 1/4" 13' - 9 3/8" title:


11' - 8 1/2"

11' - 8 1/2"

LEVEL 2
PS6b

PS6b

4' - 8"

A
DIMENSION
18' - 0" 6' - 8" 12' - 0" 13' - 4" 4' - 0" PLAN
86' - 0" 46' - 0"

A 1 2 3 4 5 A

C1 A1
A301 A301

sheet:

A1 LEVEL 2 DIMENSION PLAN


1/8" = 1'-0"
A122 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES - CEILING


1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
C1 A1
1
1 A301 2
2 3
3 42
4 A301 5
5
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION

3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
G
G MECHANICAL PLANS

4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
E E
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500 360 west aspen avenue
salt lake city, utah 84101
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE 801 532 4422
7 SEE SHEET SERIES A600 FOR FINISH MATERIAL SPECIFICATIONS

8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS

9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS

4' - 0"
EXISTING CEILING
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
KEYED NOTES NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
TR 18'-6"
VESTIBULE
07.32 CONTINUOUS SEISMIC SEPARATION JOINT BETWEEN EXISTING AND NEW CONSTRUCTION
100A A2 10' - 0" 10.76 ADD ALTERNATE: 5-TON TOP RIDING SINGLE GIRDER HOIST CRANE, W/ W16X67 MAIN GIRDER AND W14X61 CRANE BEAMS
10.77 CAST IN PLACE TEST TRENCH W/ FIBERGLASS GRATING COVER RATED FOR H-20 TRAFFIC. REINFORCE W/ FIBERGLASS

2' - 11 3/4"
EQ EQ EQ
A2 12' - 4" RS-01 SINGLE ROLLER WINDOW SHADE, MANUAL; RE: FINISH SCHEDULE
F
F
07.32 Sim
E2
A561
S S STAIRS

6' - 4"
100C
B3 B3
D A301 A301 D
C CI C1 7' - 8"

M1
ENTRY/RECEPTION
100B
S S S C4
A2 10' - 0"
A401
EQ A4 E
E CEILING LEGEND

CR
A542

ES
CP
CI
EQ

EQ
D
D NOTE :
ALL DROPS NEED TO BE NON-COMBUSTABLE METAL FRAMING OR LIGHT GUAGE METAL FRAMING AND MEET L/360 STANDARD

EQ
FOR ALLOWABLE DEFLECTION
C ST TYP
CONCRETE & EPOXY POURING CUTTING / GRINDING D4
110A 110B A591
2 OFFICE RS-01 ACP-01:
S S 113
TYPE A1 2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
A1 10' - 0"
CP

M2
ACP-02:
TYPE A2 2' x 4' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
ST TYP
D4
SP
SOLDERING A591
RS-01 ACP-03:
110D OFFICE TYPE A3
S S A2 10' - 0" 2' x 4' VINYL LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
COMPRESSOR 115
110C M4
A1 10' - 0"
TYPE B1 5/8" GYPSUM BOARD (PAINTED PNT-01b UNLESS NOTED ON PLAN) ON METAL STUD
S LARGE CONFERENCE
W TYP
114 D4
CP

HALLWAY
A2 9' - 0" A591 THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
J 100E RS-01
FLEXIBLE WORK
S S OFFICE TYPE B2 5/8" GYPSUM BOARD (PAINTED PNT-02) ON METAL SUSPENSION SYSTEM ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE

TP1
110 117 COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
E1 20' - 0"

CP

CP
A1 10' - 0" WRITTEN PERMISSION FROM METHOD STUDIO INC.
C ST C
C W W TYPE B3 5/8" GYPSUM BOARD (PAINTED PNT-03) ON METAL SUSPENSION SYSTEM
C
S S

EQ
M2 M2 TYP
ST D4
project:

M5
COFFEE

EQ 4' - 0" EQ
CUSTODIAL STORAGE RS-01 A591 5/8" GYPSUM BOARD (PAINTED PNT-01b UNLESS NOTED ON PLAN) ON UNDERSIDE OF FLOOR
STORAGE 118 TYPE C1

CL
PLATE STRUCTURE. PROVIDE BRACING AS NECESSARY
USU EVR
122 OFFICE
120 C
B1 10' - 0" 119

CL
R R R R R R R R R R B1 10' - 0" A1 10' - 0" EXPOSED STRUCTURE, PAINTED PNT-01b RE: FINISH SCHEDULE
E1 13' - 6" TYPE E1
D4
TYP
EXPANSION
RS-01 A591
ST ST RECESSED LINEAR STRIP LIGHTING, RE: ELECTRICAL
10.77 10.77 OFFICE
C
127 C
C

EQ
EQ

B5
SUSPENDED LINEAR PENDANT LIGHT FIXTURE, RE: ELECTRICAL

M5
CL

CL
A591 A1 10' - 0"

5' - 0"
5' - 0"

10.77 B1 9' - 0" B1 9' - 0" C DOWNLIGHT FIXTURE, RE: ELECTRICAL


B3 7' - 0"
RESTROOM RESTROOM TYP
PRINT/COPY D4
CL

CL
124 126
128 A591 DOWNLIGHT FIXTURE, RE: ELECTRICAL

EQ
EQ

OFFICE RS-01

10.76 129
D1 ST ST D1 SUPPLY DIFFUSER, RE: MECHANICAL
A1 10' - 0"
A301 A301

M5
ELECTRICAL
112A RETURN GRILLE, RE: MECHANICAL 670 EAST 1550 NORTH, LOGAN, UT
OFFICE - DIRECTOR / EXEC
C IT / MDF CP 84341
131 TYP
E1 13' - 6" 130 D4
E1 13' - 6" RS-01 A591 2'x4' LIGHT FIXTURE, RE: ELECTRICAL

A1 10' - 0"
10.77 10.77 10.77 ST C ST

M5
2'x4' LIGHT FIXTURE, RE: ELECTRICAL
B B
p r o j e c t # : 21.0320

C
OFFICE - DIRECTOR / EXEC
TYP
B
B d a t e : 02.14.2023
133 D4 LINEAR WALL MOUNT FIXTURE, RE: ELECTRICAL
A1 9' - 0"
RS-01 A591 revisions :
MECHANICAL
RECESSED LIGHT FIXTURE, RE: ELECTRICAL
C 112B
E1 13' - 6" HIGH BAY FIXTURE, RE: ELECTRICAL
ST CP ST
TRUCK BAYS M5
112 HIGH BAY FIXTURE, RE: ELECTRICAL
5 3/4"
E1 20' - 0"
B2 7' - 0"
B1 9' - 4" 2' - 4 3/8"
TURF PLATE ACOUSTICAL CEILNG CLOUD, RE: FINISH SCHEDULE
D5
CP
SP

SP

SP

B5 C
BREAK / KITCHENETTE A591
STAIRS A591 135 EXIT SIGN - PENDANT, RE: ELECTRICAL
1"
PTZ

12' - 1

100F
EXIT SIGN - WALL, RE: ELECTRICAL
title:
C
W ST ST ST
M4
M4

TYP
RS-01 D4
LEVEL 1 RCP
M4

A2 10' - 0" A591


J
1' - 0 1/32"

A
RS-01 RS-01 RS-01

C1 A1 12' - 7" 1' - 0 7/8"


A301 A301

A A

sheet:
LEVEL 1 REFLECTED CEILING PLAN
A1 1/8" = 1'-0"

A131 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES - CEILING


1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
C1 A1
1
1 A301
22 33 42
4 A301 5
5
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION

3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
G MECHANICAL PLANS

4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
TR TR
E E
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500 360 west aspen avenue
salt lake city, utah 84101
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE 801 532 4422
7 SEE SHEET SERIES A600 FOR FINISH MATERIAL SPECIFICATIONS

8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS

9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS

EXISTING CEILING
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND

KEYED NOTES DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS


NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

07.32 CONTINUOUS SEISMIC SEPARATION JOINT BETWEEN EXISTING AND NEW CONSTRUCTION
09.72 ACOUSTICAL CEILING CLOUD, RE: FINISH SCHEDULE
10'-6"
09.76 TECTUM CEILING PANEL; RE: FINISH SCHEDULE
RS-01 SINGLE ROLLER WINDOW SHADE, MANUAL; RE: FINISH SCHEDULE

F
F
D4
CI @ ROOF HATCH
07.32 A532
TR TR
STAIRS
B3 200C B3
D A301 TR TR A301 D

A2 10' - 0"

LANDING AREA C4
200B A401
TR
STORAGE
TR E
E CEILING LEGEND
C 201
22 SF

TR B1 9' - 0"
D
D NOTE :
ALL DROPS NEED TO BE NON-COMBUSTABLE METAL FRAMING OR LIGHT GUAGE METAL FRAMING AND MEET L/360 STANDARD
STORAGE FOR ALLOWABLE DEFLECTION
TYP
204 D4
RESTROOM
2 TR 202 A2 10' - 0" PERSONAL CARE TR RS-01 A591
TR ACP-01:
B1 10' - 0" HALLWAY 203 TYPE A1 2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
B1 10' - 0" 200E A2 9' - 0"

GROUP WORK ACP-02:


TYPE A2 2' x 4' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
209
C TYP
RS-01 D4
B5 ACP-03:
A591
A591
TYPE A3 2' x 4' VINYL LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
A1 10' - 0"
RESTROOM RESTROOM PRINT / COPY
206 208 210
B2 7' - 0" TYPE B1 5/8" GYPSUM BOARD (PAINTED PNT-01b UNLESS NOTED ON PLAN) ON METAL STUD
B1 10' - 0" B1 10' - 0" B3 7' - 0"
D2
A532 RS-01
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
C ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
TYPE B2 5/8" GYPSUM BOARD (PAINTED PNT-02) ON METAL SUSPENSION SYSTEM MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
B5 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C D6 A591 09.76 TYP.
C TR TYPE B3 5/8" GYPSUM BOARD (PAINTED PNT-03) ON METAL SUSPENSION SYSTEM C
A522
project:

TYP. TYP.
EQ
RS-01
5/8" GYPSUM BOARD (PAINTED PNT-01b UNLESS NOTED ON PLAN) ON UNDERSIDE OF FLOOR

EQ
TYPE C1
EQ 8' - 0"
S
8' - 6" 8' - 0" 8' - 6"
S
8' - 0" EQ
PLATE STRUCTURE. PROVIDE BRACING AS NECESSARY
USU EVR
R R R R R R R R R R TYP. TYP.
TYPE E1 EXPOSED STRUCTURE, PAINTED PNT-01b RE: FINISH SCHEDULE
EXPANSION
TYP. TYP.
RS-01
EQ

RECESSED LINEAR STRIP LIGHTING, RE: ELECTRICAL


EQ

C
TR
EQ 8' - 0" 12' - 5" 8' - 0" EQ C
C

M5
SUSPENDED LINEAR PENDANT LIGHT FIXTURE, RE: ELECTRICAL
TYP. 8' - 0"
2' - 0" 8' - 0"
2' - 0" DOWNLIGHT FIXTURE, RE: ELECTRICAL
S S
TYP. TYP.
EQ EQ

TR
TR RS-01
DOWNLIGHT FIXTURE, RE: ELECTRICAL
11' - 3" 11' - 3"
D1 D1 SUPPLY DIFFUSER, RE: MECHANICAL
3' - 0"

3' - 0"
A301 09.72 09.72 A301

M5
1/2" 1/2"
2' - 0" 1/2" 1/2" 2' - 0" 670 EAST 1550 NORTH, LOGAN, UT
2' - 0" 2' - 0" E1 14' - 0" 2' - 0" 2' - 0" RETURN GRILLE, RE: MECHANICAL
84341
1' - 6" 1' - 6" 1' - 6" 1' - 6" TYP
1/2" S
1/2" S
1/2" 1/2" D4
1' - 6" 1' - 7" 1' - 7" 1' - 6" RS-01 2'x4' LIGHT FIXTURE, RE: ELECTRICAL
RS-01 1/2" 1/2" 1/2" 1/2" A591
11" 11"
C

M5
B 2'x4' LIGHT FIXTURE, RE: ELECTRICAL B
p r o j e c t # : 21.0320
B
B d a t e : 02.14.2023
LINEAR WALL MOUNT FIXTURE, RE: ELECTRICAL
RS-01
revisions :
C C S S RECESSED LIGHT FIXTURE, RE: ELECTRICAL

HIGH BAY FIXTURE, RE: ELECTRICAL


M5
HIGH BAY FIXTURE, RE: ELECTRICAL

TURF PLATE ACOUSTICAL CEILNG CLOUD, RE: FINISH SCHEDULE

EXIT SIGN - PENDANT, RE: ELECTRICAL


GROUP WORK
212C
GROUP WORK
212B C
GROUP WORK
212A
title:
EXIT SIGN - WALL, RE: ELECTRICAL

TR
CP
CP
CP
TR RS-01
LEVEL 2 RCP
A1 10' - 0" A1 10' - 0" A1 10' - 0"
EQ

A
RS-01 RS-01 RS-01 RS-01 EQ ACOUSTICAL CEILING LEGEND
TYP TYP TYP
D4 D4 D4
A591 A591 A591
C1 A1 ACP-04 ACOUSTIC BAFFLE CLOUD
A301 A301
A A
ACP-05 ACOUSTIC BAFFLE CLOUD

ACP-06 ACOUSTIC BAFFLE CLOUD


sheet:
LEVEL 2 REFLECTED CEILING PLAN
A1 ACP-07 ACOUSTIC TECTUM PANEL

A132
1/8" = 1'-0"

* RE: FINISH SCHEDULE SHEET FOR MORE INFORMATION *

BID SET
1 2 3 4 5 6
1 2 3 4 5 6
GENERAL NOTES - EXTERIOR ELEVATIONS
1 ALL EXPOSED STRUCTURAL EXTERIOR STEEL SHALL BE GALVANIZED WITHOUT CHROMATE COATING, SHOP PRIMED WITH
HIGH PERFORMANCE COATING

4 3 2 1.2 1 F B3 E D
5 A1
C1
07.30 A301 2 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
07.04 07.04 A301
A301 3 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
07.12 T.O. OFFICE WALL T.O. OFFICE WALL
130' - 0" 130' - 0" 4 SEE SHEET SERIES A500 FOR ARRISCRAFT AND EIFS CORNICE PROFILES

OFFICE ROOF DECK 07.12 OFFICE ROOF DECK 5 SEE SHEET SERIES A500 FOR EXTERIOR RAILING TYPES
07.24 128' - 0" 128' - 0"
D6
________
________
A523 6 SEE SHEET A600 WINDOW SURROUND TYPES (WS - #)
E E
360 west aspen avenue
05.37 EXISTING EVR ROOF DECK PAINT TO MATCH BLACK salt lake city, utah 84101
SF1 05.37
120' - 7 1/2" CMU HONED 801 532 4422
A3
07.32 SF3
CW3 A551 201

LEVEL 02 LEVEL 02
TYP.
05.40
114' - 0" 114' - 0" KEYED NOTES
02.11 REMOVE EXISTING WINDOW FOR CLEAN PATCH AT CMU WALL, RE: STRUCTURAL. MATCH TO EXISTING CMU WALL
EXISTING EVR FACILITY AT EXTERIOR & INTERIOR.
04.03 6" CMU, RECESS 2" FROM ADJACENT BLOCK
SF1
04.04 10" CMU, RECESS 2" FROM ADJACENT BLOCK
CW1 05.37 STAINLESS STEEL GUARDRAIL, RE: DETAILS
05.39 ADD ALTERNATE: VERTICAL WINDOW SHADE
05.40 ROD AND CLEVIS SUPPORT FOR EXTERIOR CANOPY. RE: STRUCTURAL
LEVEL 01 LEVEL 01 UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
07.02 PRE-FINISHED METAL FLASHING WITH DRIP EDGE
100' - 0" 100' - 0" DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
07.04 PRE-FINISHED METAL CAP FLASHING TO MATCH ADJACENT WALL FINISH. COLORS TO BE CHOSEN BY ARCHITECT NOT INTENDED FOR CONSTRUCTION, RECORDING
22.20 FROM PHYSICAL SAMPLES SELECTED FROM MANUFACTURER'S FULL RANGE OF COLORS PURPOSES, OR IMPLEMENTATION
07.12 ACM WALL PANEL
07.24 ACM PANEL JOINT
EXTERIOR ELEVATION - NORTH PARTIAL ELEVATION - WEST
D1 1/8" = 1'-0" D4 1/8" = 1'-0"
07.30
07.32
PRE-FINISHED METAL CAP FLASHING
CONTINUOUS SEISMIC SEPARATION JOINT BETWEEN EXISTING AND NEW CONSTRUCTION
22.20 ROOF DRAIN DOWNSPOUT, FINISH TO MATCH CANOPY, RE: PLUMBING
23.02 MECHANICAL EQUIPMENT, RE: MECHANICAL
26.25 EXTERIOR LIGHT FIXTURE TO BE DEMOLISHED. RE: ELEC.
A B C D.1 D E F G D E F G
D1 A7 TYP. @ EAST B3
A301 A312 STACKED WINDOWS A301
07.02
D D
07.02 T.O. OFFICE WALL T.O. OFFICE WALL
130' - 0" 130' - 0"

E6 TYP. OFFICE ROOF DECK OFFICE ROOF DECK


________
________
A523 128' - 0" B3 B1
128' - 0"
A301 A511

EXISTING EVR FACILITY 07.32 EXISTING EVR ROOF DECK


SF1 SF1 SF1 SF1 SF1 SF1 SF1 SF1 SF1 EXISTING EVR FACILITY 120' - 7 1/2"
05.39 05.39 05.39 05.39 05.39 05.39 05.39 05.39 05.39 05.37
CW2 26.25 26.25

LEVEL 02 LEVEL 02
04.03 04.03 04.03 04.03 04.03 04.03 04.03 04.03 04.03 04.03 114' - 0" 114' - 0"
D3 TYP.
A551
02.11

SF1 SF1 SF1 SF1 SF1 SF1 SF1 SF1 SF1

E4
A511
LEVEL 01 LEVEL 01
100' - 0" 100' - 0"
CONCRETE STEM WALL
TO 2'-0" THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C EXTERIOR ELEVATION - EAST PARTIAL ELEVATION - EAST C
C1 1/8" = 1'-0" C5 1/8" = 1'-0" project:
C1 A1
A301 A301
USU EVR
1 1.2 2 3 4 5
07.02 07.02
LEGEND: ELEVATION FINISHES EXPANSION
T.O. OFFICE WALL
130' - 0"
HONED EXTERIOR SURFACE ACM PANEL; COLOR:
ARCHITECTURAL CONCRETE ALUCOBOND "DUSTY
OFFICE ROOF DECK BLOCK; COLOR: SUNROC CHARCOAL". FINAL COLOR TO
E2 E1 C E1 E 128' - 0" "WHITE" OR SIMILAR BE SELECTED BY ARCHITECT
A551 A551 A551 APPROVED BY ARCHITECT FROM FULL RANGE OF
MANUFACTURER'S COLORS
HONED EXTERIOR SURFACE
ARCHITECTURAL CONCRETE
E2 SF1 SF2 SF1 SF2 04.03 SF2 BLOCK; COLOR: SUNROC CONTROL JOINT
E1 B E1 B E1 B "BLACK" OR SIMILAR
A551 APPROVED BY ARCHITECT
A551 A551 A551

04.03 HONED EXTERIOR SURFACE CONCRETE STEM WALL


LEVEL 02 ARCHITECTURAL CONCRETE
04.04 04.04 04.04 04.04 04.04 04.04 SF5
E2
04.03 04.03 E1 D E1
670 EAST 1550 NORTH, LOGAN, UT
C 114' - 0" BLOCK; COLOR: SUNROC
A551 A551 "NATURAL" OR SIMILAR 84341
A551
APPROVED BY ARCHITECT

SF1 SF1 SF1 SF1 SF1 SF1 SF2 SF1 SF2

135b
B SF4 B
LEVEL 01 p r o j e c t # : 21.0320
100' - 0" d a t e : 02.14.2023
D4
________
________
A522
revisions :
EXTERIOR ELEVATION - SOUTH
B2 1/8" = 1'-0"
A
G F E D D.1 C B
B3 D1
A301 A301

07.02 07.02

T.O. OFFICE WALL


130' - 0" title:
OFFICE ROOF DECK
23.02
C3
A511
23.02
128' - 0"
EXTERIOR
EXISTING EVR ROOF DECK
C2
A511 05.40 TYP. ELEVATIONS
120' - 7 1/2"
A2
04.04 A511

A1 LEVEL 02
04.04 04.04 114' - 0"
A511
A EXISTING EVR FACILITY
112a 112b A

SF1 SF1

110Aa
108 110 112
sheet:
LEVEL 01
100' - 0"

A1 EXTERIOR ELEVATION - WEST


1/8" = 1'-0"
B3
A301
22.20 22.20 D1
A301
22.20 22.20

A201 BID SET


1 2 3 4 5 6
1 2 3 4 5 6

5
GENERAL NOTES - SECTIONS
1 1.2 C1
A301
2 3 A2 4 A301
A1 A3
A311 1 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
A311
T.O. OFFICE WALL 2 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
130' - 0"

OFFICE ROOF DECK


128' - 0"
A1
A311

EXISTING EVR ROOF DECK


E 10.76
120' - 7 1/2" E
360 west aspen avenue
salt lake city, utah 84101
LEVEL 02
05.38 801 532 4422
114' - 0"

KEYED NOTES
TRUCK BAYS ELECTRICAL IT / MDF HALLWAY OFFICE
D5
________
________ 112 112A 130 100E 129 02.11 REMOVE EXISTING WINDOW FOR CLEAN PATCH AT CMU WALL, RE: STRUCTURAL. MATCH TO EXISTING CMU WALL
A511 4,933 SF 201 SF 210 SF 827 SF 121 SF AT EXTERIOR & INTERIOR.
05.04 STEEL GUARDRAIL, PAINTED
LEVEL 01
05.37 STAINLESS STEEL GUARDRAIL, RE: DETAILS
100' - 0"
05.38 PROVIDE FULLY-WELDED WIDE FLANGE SHELF FOR FUTURE HOIST CRANE BEAMS
10.76 ADD ALTERNATE: 5-TON TOP RIDING SINGLE GIRDER HOIST CRANE, W/ W16X67 MAIN GIRDER AND W14X61 CRANE
BEAMS
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
E5 E6 TYP. DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
A511 A511 NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

BUILDING SECTION - GRID C


D1 1/8" = 1'-0"

B3 D1
G F A301
E D D.1 D6
A522
C A301 B A A6
A311
T.O. OFFICE WALL
D 130' - 0" D
OFFICE ROOF DECK
A5 128' - 0"
A311

EXISTING EVR ROOF DECK


120' - 7 1/2"
B1
A511 02.11 05.04
TYP 10.76
A4 LEVEL 02
A511 05.37 114' - 0"

20' - 4 1/2"
EXISTING BUILDING
E2
ELECTRICAL EQUIPMENT CONCRETE & EPOXY POURING FLEXIBLE WORK TRUCK BAYS
CLEARANCE A511
110A 110 112
108 353 SF

LEVEL 01
100' - 0"

THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING


BUILDING SECTION - GRID 2
C1 1/8" = 1'-0"
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS

A3
5 WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
C1 A1 A2 A312
1 1.2 A301 2 3 4 A301 A312 project:
EL. 134' - 0"
T.O. OFFICE WALL
130' - 0"
USU EVR
A1
OFFICE ROOF DECK
128' - 0"
EXPANSION
A312

EXISTING EVR ROOF DECK


ROOF TERRACE 120' - 7 1/2"
-
671 SF

LEVEL 02
114' - 0"
EXISTING BUILDING

670 EAST 1550 NORTH, LOGAN, UT


ENTRY/RECEPTION 84341
STAIRS
100B
100C
707 SF
183 SF
LEVEL 01
100' - 0"

B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023

BUILDING SECTION - GRID F revisions :


B3 1/8" = 1'-0"

F E D D.1 C D1
B A
D4 B3 C4
A301
A532 A301 A401 A6
EL. 134' - 0" A5
A312
A312
T.O. OFFICE WALL
130' - 0"
OFFICE ROOF DECK
128' - 0"
title:

A4
BUILDING
EXISTING EVR ROOF DECK
A312
SF3
201
ROOF TERRACE STORAGE
HALLWAY
200E
GROUP WORK
212C
120' - 7 1/2"
SECTIONS
- 204

LEVEL 02
114' - 0"

A A
VESTIBULE ENTRY/RECEPTION LARGE CONFERENCE STORAGE HALLWAY RESTROOM ELECTRICAL MECHANICAL BREAK / KITCHENETTE
100A 100B 114 120 100E 124 112A 112B 135
I T
NCE
ROM ON
ZO NE 1 L I E
NF A L
UT

Z O E
NCA
L L

I T
NCE
ROM ON
ZO NE 2
L I E
NF A L
UT
Z O E NCAL L

P US H RE L E
A S E I T
NCE
ROM ON
O
T O
T ZO NE 3 L I E
NF A L
UT
T A L
K L I S
T E
N
Z O E
NCA
L L

P OW E
RON

I T
NCE
ROM ON
ZO NE 4
L I E
NF A L
UT
RE S
E T A
L L O
Z E
NS Z O E NCAL L

LEVEL 01
100' - 0" sheet:

A1 BUILDING SECTION - GRID 4


1/8" = 1'-0" A301 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES - SECTIONS


1 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES

2 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES

E ASSEMBLY TYPES E
360 west aspen avenue
ROOF R1 MAIN ROOF salt lake city, utah 84101
R2 PAVER TERRACE 801 532 4422

FLOOR F2 SLAB ON GRADE


F3 SLAB ON STRUCTURE

NOTE: SEE AE500 SHEET SERIES FOR COMPLETE ASSEMBLY TYPES

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

1 4 5

D D
E6 SIM./OPP.
E6 A521 E6 SIM./OPP.
A521 A521

T.O. OFFICE WALL T.O. OFFICE WALL T.O. OFFICE WALL T.O. OFFICE WALL
130' - 0" 130' - 0" 130' - 0" RF1 130' - 0"
RF1 C5
RF1
RF1 A521
C5
C5 A521
OFFICE ROOF DECK OFFICE ROOF DECK OFFICE ROOF DECK OFFICE ROOF DECK
A521
128' - 0" 128' - 0" 128' - 0" 128' - 0"

23.02 EM8a
E D D.1

EM12a
E1

E1 A521
A511
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
RF1
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
EM12a WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
EXISTING EVR ROOF DECK
120' - 7 1/2" project:

USU EVR
C2
A511
C3
A511
EXPANSION

C3
A541 EM8

LEVEL 02 LEVEL 02 LEVEL 02 LEVEL 02 LEVEL 02


114' - 0" 114' - 0" 114' - 0" 114' - 0" 114' - 0"

670 EAST 1550 NORTH, LOGAN, UT


84341
F3 E4
A551

B B
A1 10' - 0" p r o j e c t # : 21.0320
d a t e : 02.14.2023
E2
revisions :
A541

112a
SF1

112Ab
title:
B4
2"
A551

A3 D4 EM12a
WALL
A5 Sim B3
A521
F1 F1 F2
F2 A522
A521
F1
A511
F1
A2 SECTIONS
A521
LEVEL 01 LEVEL 01 LEVEL 01 LEVEL 01 LEVEL 01
100' - 0" 100' - 0" 100' - 0" 100' - 0" 100' - 0"

A A

sheet:

A1 Wall Section (Grid C-1)


1/2" = 1'-0" A2 Wall Section (Grid C-4)
1/2" = 1'-0" A3 Wall Section (Grid C-5)
1/2" = 1'-0" A5 Wall Section (Grid D-2)
1/2" = 1'-0" A6 Wall Section (Grid A-2)
1/2" = 1'-0"
A311 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES - SECTIONS


1 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES

2 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES

E ASSEMBLY TYPES E
360 west aspen avenue
ROOF R1 MAIN ROOF
salt lake city, utah 84101
801 532 4422
R2 PAVER TERRACE

FLOOR F2 SLAB ON GRADE


F3 SLAB ON STRUCTURE

NOTE: SEE AE500 SHEET SERIES FOR COMPLETE ASSEMBLY TYPES

UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND


DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS

5 NOT INTENDED FOR CONSTRUCTION, RECORDING


PURPOSES, OR IMPLEMENTATION

E4
E6 SIM./OPP.
A521
A521

D D.1 A 5

D D

E4 Sim E6 E6
A521 A521 A521
EM8a
RF1 RF1
T.O. OFFICE WALL T.O. OFFICE WALL T.O. OFFICE WALL T.O. OFFICE WALL
130' - 0" 130' - 0" 130' - 0" 130' - 0"
C5
RF1 RF1
Sim A521
B5
A521 B5 Sim
OFFICE ROOF DECK OFFICE ROOF DECK OFFICE ROOF DECK OFFICE ROOF DECK OFFICE ROOF DECK
A521
128' - 0" 128' - 0" 128' - 0" 128' - 0" 128' - 0"
ES6

4 C5 C5
A521 A521
E2
A551
EM8a

ES6

E1 E4
A521 A551

A2 10' - 0" A1 10' - 0"


THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
E3 MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
A551 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
EXISTING EVR ROOF DECK EXISTING EVR ROOF DECK EXISTING EVR ROOF DECK
120' - 7 1/2" 120' - 7 1/2" 120' - 7 1/2" SF2 project:

USU EVR
A5
A511
B4
EXPANSION
A551

B4 SIM.
A551

E2 B1
B4
A521 A521 A521
RF2 2" TYP., RE: EXT. ELEVATIONS
RF2 RF2
RF2
E1
LEVEL 02 LEVEL 02 LEVEL 02 LEVEL 02 LEVEL 02 LEVEL 02 LEVEL 02
A511
114' - 0" 114' - 0" 114' - 0" 114' - 0" 114' - 0" 114' - 0" 114' - 0"

EM8a 670 EAST 1550 NORTH, LOGAN, UT


84341
E4
A551

E4
A551
B B
A2 10' - 0" p r o j e c t # : 21.0320
A2 10' - 0" C2 C3 A2 10' - 0" A2 10' - 0"
A511 A511 d a t e : 02.14.2023

E6
A551 A3
A2 9' - 0" revisions :
A541

SF2

100A 114a B4
A551

B4
title:
SIM.
A551

Sim./Opp. A1 C4
EM8a A2
WALL
Sim A2 F2
A5
A521 F2
F2 F2
A521 A541 A541

F2
A2
A521
A521
SECTIONS
F2
LEVEL 01 LEVEL 01 LEVEL 01 LEVEL 01 LEVEL 01 LEVEL 01 LEVEL 01
100' - 0" 100' - 0" 100' - 0" 100' - 0" 100' - 0" 100' - 0" 100' - 0"

A A

sheet:

A1 Wall Section (Grid F-4)


1/2" = 1'-0" A2 Wall Section (Grid F-4.5)
1/2" = 1'-0" A3 Wall Section (Grid F-5)
1/2" = 1'-0" A4 Wall Section (Grid F.5-4)
1/2" = 1'-0" A5 Wall Section (Grid D-4)
1/2" = 1'-0" A6 Wall Section (Grid A-4)
1/2" = 1'-0" A7 Wall Section (Grid C-D.5)
1/2" = 1'-0"
A312 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

KEYED NOTES
05.03 STEEL HANDRAIL, PAINTED, EXTEND 1'-0" PAST LAST TREAD/RISER TYP.
05.04 STEEL GUARDRAIL, PAINTED
05.24 STEEL ELEVATOR PIT LADDER
05.31 SHIPS LADDER
05.41 1-1/2" DIA. METAL PIPE GUARDRAIL PAINTED TO MATCH STAIR STRINGERS. CORE DRILL AND GROUT AT CONCRETE SLAB.
07.34 BENTONITE WATERPROOFING MEMBRANE, ENCOMPASSING ENTIRE ELEVATOR PIT. LAP UNDER FOOTINGS, SLAB, AND UP
FOUNDATION WALLS. EXTEND PAST JOINTS BY 2FT MIN. (TYP.)
08.11 ROOF ACCESS HATCH WITH INTEGRATED GUARDRAIL AND TELESCOPING SAFETY POLE

E E
A2 360 west aspen avenue
A513 05.24 salt lake city, utah 84101
A4
801 532 4422
TYP.
A513

5
C4
A401

ELEVATOR SHAFT
8' - 4" CLEAR
RF1 UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
HOIST BEAM, RE: STRUCTURAL 07.34 NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

OFFICE ROOF DECK


128' - 0"
SS6 7' - 3 13/16"
(6'-11" CLEAR REQ'D)
BENTONITE WATERPROOFING
EXTEND PAST JOINT 2' (TYP.)

MIN. OVERHEAD CLEARANCE


A2 10' - 0"
EM8a

12' - 11"
D D

LANDING AREA ENLARGED PLAN @ ELEVATOR PIT


4'-0" O.C. MAX. SPACING 200B D2 1/2" = 1'-0"

5/8" x 2" FLAT STEEL BAR VERTICAL SUPPORT.


C4 5
WELD TO TOP BAR & GRIND SMOOTH, PAINTED A513
LEVEL 02
114' - 0"

32' - 0 1/16"
A EM12a
A2
A401
5/8" x 2" FLAT STEEL BAR
TOP RAIL, PAINTED A2 10' - 0" F

TRAVEL DISTANCE
1 1/2" DIA. STL.

14' - 0"
HANDRAIL, PAINTED
3 1/2"
MAX.

PS3b
FRAME AT PERIMETER,
BASIS OF DESIGN: UP 05.03
MCNICHOLS U-EDGING, ENTRY/RECEPTION A4
42" T.O. GUARDRAIL

7' - 0"
3' - 0" T.O. HANDRAIL

CARBON STEEL, COLD

PS3c
PS3c
100B A401 05.04
ROLLED, 18 GA., TYPE
A2
403 U-EDGING

LANDING
B2 05.03

12' - 4"
A513
F2 A521
1/8" x 1" PERFORATED THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
SLOTTED HOLE PANEL, LEVEL 01 05.03 ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
EM8a
VERTICALLY ORIENTED, 100' - 0" MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE

5' - 2" CLEAR


CARBON STEEL. BASIS COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
3 1/2"
MAX.

5' - 8"
A1

4' - 0" PIT


OF DESIGN: MCNICHOLS WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
DN WRITTEN PERMISSION FROM METHOD STUDIO INC.
ITEM NO. 16890016M2 B4 D2 A401
C A513 A401
C
05.03
2-1/2" PRECAST TREAD
PAINTED STRINGER,
RE: STRUCTURAL
project:
METAL RISER AND B6
________
________ CORE DRILL AND 1' - 0"
TREAD SUPPORT, RE:
SECTION DETAIL
A513 GROUT LEVEL 01
100' - 0"
REFER TO SECTIONS FOR A1 & A2 ON SHEET A401 FOR LOW
PROFILE CANE DETECTION UNDER STAIRS A4 05.04
TYP. D4 USU EVR
07.34 A513 6' - 5"

SECTION A-A 1' - 0"


A ELEVATION A513
LANDING
EXPANSION
NORTH STAIR ENLARGED GUARDRAIL & HANDRAIL DETAIL 3D AXON - STAIR NORTH SECTION @ ELEVATOR LEVEL 2 NORTH STAIR PLAN
C1 3/4" = 1'-0" C2 C4 1/4" = 1'-0" C5 1/4" = 1'-0"

5 F 5
5
D4
A532 12' - 10" 6' - 5"
(14) EQUAL TREADS @ 11" MIN. LANDING
08.11 670 EAST 1550 NORTH, LOGAN, UT
D4 84341
A532

3" GAP @ WALL


A2
EM12a A401
TYP. D4
A513 F
OFFICE ROOF DECK OFFICE ROOF DECK OFFICE ROOF DECK
B 128' - 0" 128' - 0" 128' - 0" B
05.03 p r o j e c t # : 21.0320
1' - 0"
1' - 0"

5' - 2" CLEAR


d a t e : 02.14.2023

5' - 8"
UP
A4 05.04 TYP. revisions :
05.31 A401 1 Review Responses 03.06.2022

12' - 4" LANDING


05.03 TYP.
A2 10' - 0"

GAP
6"
AC PLYWOOD ONE
SIDE, PAINT A SIDE
PER FINISH PLAN. RE: PS3c EM8a

5' - 2" CLEAR


FINISH SCHEDULE

5' - 8"
A1
1' - 0" A401
A1 A4 A2
A2 A401 A401 A401
0° PS2a
A401 10.0
1
05.03
title:

3" GAP @ WALL


LEVEL 02 LEVEL 02 LEVEL 02 B2
05.04
114' - 0" 114' - 0" D4 114' - 0" A513
2 9/16" TYP.
VERTICAL
TYP. C4
A513
A401

ELEVATOR SHAFT
8' - 4" CLEAR
1' - 0" A2 12' - 4"
E
C6
CIRCULATION
3' - 0"
1' - 0"
A513 A606
24 EQ. RISERS @ 7" MAX.

C1 10'
0' --0"0"
A2 10' - 0" LANDING EL. 108' - 6 1/2" A2 10' - 0"
D2
________
________ 11"
ENLARGED
(24) EQ. RISERS

A513 3
EM8 SS6
14' - 0"

14' - 0"

7"

PLANS AND
8' - 0" CLEAR

C1 7' - 8"
C1 7' - 8"
C1 7' - 8" C1 0' - 0"
D

(15) EQUAL RISERS


D6
A513
A A
SECTIONS
8' - 9"
B6
GYPSUM BOARD AT UNDERSIDE OF
OPEN TO LOBBY STAIR, PAINT PER FINISH SCHEDULE A513 6' - 11" CLEAR
6' - 8"

ELEVATOR SHAFT
C1 TYP. GUARDRAIL 1' - 0"
3' - 0"

3' - 0"

A401 DTL. C1 0' - 0" 05.41


(HEIGHT VARIES)
sheet:
9"
9"

9"

LEVEL 01 LEVEL 01 LEVEL 01


100' - 0" 100' - 0" 100' - 0"
05.41 05.41 A6
1' - 0" PROVIDE CANE DETECTION < 80" A.F.F.

A401
A513 .
12' - 10"
(14) EQUAL TREADS

NORTH STAIR SECTION 02 NORTH STAIR CROSS SECTION NORTH STAIR SECTION 01 LEVEL 1 NORTH STAIR & ELEVATOR PLAN
A1 1/4" = 1'-0" A2 1/4" = 1'-0" A4 1/4" = 1'-0"
A5 1/4" = 1'-0" BID SET
1 2 3 4 5 6
1 2 3 4 5 6

D.1 D
D2
KEYED NOTES
A402
D 05.01 STEEL COLUMN, TYP. PAINT. RE: STRUCTURAL
3 05.02
05.03
STEEL BEAM, RE: STRUCTURAL
STEEL HANDRAIL, PAINTED, EXTEND 1'-0" PAST LAST TREAD/RISER TYP.

11"
05.04 STEEL GUARDRAIL, PAINTED
D.1 05.23 36" TALL 6" PAINTED ROUND CONCRETE FILLED STEEL BOLLARD WITH ROUND TOP CONDITION, FLANGE MOUNTED TO
05.23 FOOTING BELOW SLAB
05.41 1-1/2" DIA. METAL PIPE GUARDRAIL PAINTED TO MATCH STAIR STRINGERS. CORE DRILL AND GROUT AT CONCRETE SLAB.

E EXISTING EVR ROOF DECK E


120' - 7 1/2" 360 west aspen avenue
salt lake city, utah 84101
801 532 4422

E1

HEAD CLEARANCE
A513
05.04 05.04

7' - 7"
LEVEL 02

GUARDRAIL HT.
114' - 0" A4

3' - 6"
A511
EL. 111' - 0"

TOP LANDING
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
SUPPORT, RE: STRUCT.
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
6' - 0" PURPOSES, OR IMPLEMENTATION

(18) EQUAL RISERS


BOLLARD @ LVL 1 - RE: FLOOR PLANS
11' - 0"
1' - 6 1/4"
FLEXIBLE WORK
110 3D AXON - STAIR MEZZANINE 4
3,086 SF d3
B1
EL. 100' - 0"
A513
CORE DRILL &
10' - 6" 3"
LEVEL 01 GROUT
LANDING
100' - 0" 05.03

D A1
05.04 A1 D
A513 A2
A402 A402

E1 05.04
A513

SECTION @ STAIR - LVL1/MEZZANINE


D2

< 4" GAP

LANDING
A3
1/4" = 1'-0"

6' - 5"
05.04 A402

TOP LANDING, RE: STRUCT.

1' - 0"
3' - 10"
DN

EL. 111' - 0" TYP. D4


A513

11 EQ. TREADS @ 11" MIN.


05.04
TYP. D4

10' - 1"
05.04 EL. 100' - 0"
(RE: STRUCTURAL FOR A513
MOUNTING DTLS) 4' - 7" 05.03
DN
C2

1' - 0"

1' - 0"
TOP LANDING, RE: STRUCT. 05.23
05.04 A413
6' - 1" 05.03

BOLLARD @ LVL 1 - RE: FLOOR PLANS THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &

1' - 0"

1' - 0"
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
ENLARGED FLOOR PLAN @ STAIR - LVL 1/MEZZANINE 05.03 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS

C2 WRITTEN PERMISSION FROM METHOD STUDIO INC.

LANDING
DN

5' - 8 1/2"

5' - 8 1/2"
4' - 6" CLEAR
C 1/2" = 1'-0" C
project:
5' - 0" 6" 5' - 0" 3"

USU EVR
A
EXPANSION
3D AXON - STAIR SOUTH LEVEL 2 SOUTH STAIR PLAN
C4 C5 1/4" = 1'-0"

A A
A3 4
A402 A2 A1

T.O. OFFICE WALL A3


A402 A402
4 670 EAST 1550 NORTH, LOGAN, UT
130' - 0" A402 10' - 6" 84341
OFFICE ROOF DECK
LANDING
128' - 0"
OFFICE ROOF DECK OFFICE ROOF DECK
128' - 0" 128' - 0" A1 A2
A402 A402
05.01 05.41 05.01

B B
p r o j e c t # : 21.0320
d a t e : 02.14.2023
EXISTING EVR ROOF DECK

6' - 6 1/4"
EXISTING EVR ROOF DECK
11' - 3 1/4" 6' - 0"
EXISTING EVR ROOF DECK
120' - 7 1/2"
A3 revisions :
A402
120' - 7 1/2" 120' - 7 1/2" 1 Review Responses 03.06.2022
E1
05.04
D1 A513

1' - 0"
A513

05.04 05.04
1' - 2" 05.03

(7) EQ. TREADS


LEVEL 02

6' - 5"
D2
________
________ 114' - 0" 05.03
LEVEL 02 LEVEL 02 05.41

(11) EQ. TREADS


A513
(4) EQ. RISERS
3' - 6"

114' - 0" 114' - 0"


3' - 0"

3' - 0"

10' - 1"
E2
2' - 4"

05.04
05.02 05.02
A513
05.41 05.03
title:

1' - 0"

1' - 0"
UP
05.04

VERTICAL
(12) EQ. RISERS

05.03 05.03 4' - 6" CLEAR


C1
TYP.
7' - 0"

A513

CIRCULATION
5' - 0" 6" 5' - 0" 3" GAP @ WALL
B1
A513
05.04 GAP ENLARGED
(8) EQUAL RISERS

05.01
05.01
05.41 PLANS AND
4' - 8"

C1
05.41
3' - 0"

A513
A A
SECTIONS

9"
LEVEL 01
100' - 0"
A
9"

9"

LEVEL 01 LEVEL 01
100' - 0" 100' - 0"
CORE DRILL & GROUT B1 05.41 PROVIDE CANE DETECTION
1' - 0"
A513 < 80" A.F.F.
PROVIDE CANE DETECTION A1
BENEATH STAIRS < 80" A.F.F. A513 PROVIDE CANE DETECTION sheet:
BENEATH STAIRS < 80" A.F.F.

A1 SOUTH STAIR SECTION 01


1/4" = 1'-0" A2 SOUTH STAIR SECTION 02
1/4" = 1'-0" A3 SOUTH STAIR CROSS SECTION
1/4" = 1'-0" A5 LEVEL 1 SOUTH STAIR PLAN
1/4" = 1'-0"
A402 BID SET
1 2 3 4 5 6
1 2 3 4 5 6

GENERAL NOTES - INTERIOR ELEVATIONS


3 FULL TILE 1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
FULL TILE FULL TILE FULL TILE CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK

124 126
2 DO NOT SCALE DRAWINGS

RESTROOM RESTROOM 26.16


3 SEE SHEET SERIES G000 FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
124 126 TL-02 10.03
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
92 SF 84 SF 22.10
10.04 4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
10.02 10.05

8"
ST-01
10.07
10.11 10.06 PL-03 5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
E2 A411 E4 E4 A411 E2 10.09 10.01
E

3'-4"
E

6"
TYP 22.03
C1 TYP 10.10 6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED 360 west aspen avenue
MIR. C4
E3 E3 A571 HORIZONTALLY salt lake city, utah 84101

34"
A571

8" 8"
801 532 4422
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES

FULL TILE
TYP TYP
C4 TYP C4
C1 A1
________
________ 8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
A571 1' - 10" 2' - 2" A571
A571 A581
1' - 10" 9 1/2" 2'-2 3/8" 5'-3 3/4" 1'-6" 1'-0" 9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
CL CL
CL CL CL CL CL 10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE

11 CONTRACTOR TO PROVIDE RESTROOM ACCESSORIES; SEE ACCESSORY SCHEDULE


RESTROOM 113 &114 - ENLARGED PLAN RESTROOM 113 & 114 - INT. ELEVATION 2 RESTROOM 113 & 114 - INT. ELEVATION 3 RESTROOM 113 & 114 - INT. ELEVATION 4
E1 1/4" = 1'-0" E2 1/4" = 1'-0" E3 1/4" = 1'-0" E4 1/4" = 1'-0" 12 SEE AF600 SERIES FOR MATERIAL SPECIFICATIONS

13 SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES


UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
14 SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION

15 SEE SHEET SERIES A500 FOR CASEWORK DETAILS

D3

FRP-01
D2 A411

FRP-01 KEYED NOTES


CUSTODIAL STORAGE

5'-1"

5'-1"
10.01 TOILET PAPER DISPENSER, RE: ACCESSORY SCHEDULE
D 122
10.02 BABY CHANGING STATION, RE: ACCESSORY SCHEDULE
D
61 SF
22.01 10.03 MIRROR, RE: ACCESSORY SCHEDULE
122 10.04 WALL MOUNT SOAP DISPENSER, RE: ACCESSORY SCHEDULE
10.05 18" GRAB BAR, RE: ACCESSORY SCHEDULE
2'-4" 22.01 2'-9"
10.06 36" GRAB BAR, RE: ACCESSORY SCHEDULE
10.07 42" GRAB BAR, RE: ACCESSORY SCHEDULE
10.09 PAPER TOWEL DISPENSER, RE: ACCESSORY SCHEDULE
CUSTODIAL STORAGE 116 - ENLARGED PLAN CUSTODIAL STORAGE 116 - INT. ELEVATION 1 CUSTODIAL STORAGE 116 - INT. ELEVATION 2 10.10 SANITARY NAPKIN DISPOSAL, RE: ACCESSORY SCHEDULE
D1 1/4" = 1'-0" D2 1/4" = 1'-0" D3 1/4" = 1'-0"
10.11
22.01
SANITARY NAPKIN DISPENSER, RE: ACCESSORY SCHEDULE
MOP SINK, RE: PLUMBING
22.03 TOILET FIXTURE, RE: PLUMBING
22.10 UNDERMOUNT SINK, RE: PLUMBING
26.16 LIGHT FIXTURE, RE: ELECTRICAL
FRP-01 FIBER-GLASS REINFORCED PANEL, FRP-01; RE: FINISH SCHEDULE
PL-03 PLASTIC LAMINATE, PL-03, RE: FINISH SCHEDULE
FULL TILE
FULL TILE ST-01 QUARTZ, ST-01; RE: FINISH SCHEDULE
EQ FULL TILE EQ TL-02 TILE, TL-02, RE: FINISH SCHEDULE

FULL TILE
RESTROOM
202 26.16
70 SF 10.03 TL-02

4'-0"
C4
22.10
10.04
10.05

FULL TILE
C3 A411 C2 ST-01
10.07
10.11 PL-03 THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
10.06 10.01
10.09 TYP ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &

6"
C1 22.03 10.10 TYP MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
C1

4'-0"
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
A571 A571 WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS

34"
WRITTEN PERMISSION FROM METHOD STUDIO INC.
C C
202
2'-2" 1'-8" C4
TYP
A1
C4
TYP
C4
TYP project:
________
________
A571 A581 A571 A571

USU EVR
CL CL
1'-0" 1'-6" 4'-6 1/4" 2' - 4 5/8" 9 1/2"

CL CL CL CL

RESTROOM 204 - ENLARGED PLAN RESTROOM 204 - INT. ELEVATION 1 RESTROOM 204 - INT. ELEVATION 3 RESTROOM 204 - INT. ELEVATION 4 TILE LEGEND EXPANSION
C1 1/4" = 1'-0" C2 1/4" = 1'-0" C3 1/4" = 1'-0" C4 1/4" = 1'-0"
TL-02 WALL TILE

TL-03 WALL TILE


CL FULL TILE 2 FULL TILE
2' - 6"
FULL TILE FULL TILE TL-04 WALL TILE
EQ FULL TILE FULL TILE
EQ
206
EQ

* SEE INTERIOR ELEVATIONS + FINISH SCHEDULE SHEET FOR MORE INFORMATION *


RESTROOM
4'-0"

26.16
206 TL-02 670 EAST 1550 NORTH, LOGAN, UT
63 SF
10.03
22.10
84341
FULL TILE

10.05
10.04 10.07
10.11 ST-01 10.10
B2 A411 B3 PL-03 10.06 10.01
10.09
6"

TYP 22.03 TYP


C1 C1
B B4 A571 A571 B
34"

p r o j e c t # : 21.0320
EQ

d a t e : 02.14.2023
TYP