Fiber Optic Cable Datasheet

This document provides specifications for barpa Distribution Cables that are perfect for building backbones and horizontal distribution applications. The cables have an easy strippable tight buffer and can be used indoors and/or outdoors. They meet various international standards and are available with different fiber counts and fiber types. The document also lists the cable's mechanical, ambient, and ordering information.

Uploaded by

sermmys
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views2 pages

Fiber Optic Cable Datasheet

This document provides specifications for barpa Distribution Cables that are perfect for building backbones and horizontal distribution applications. The cables have an easy strippable tight buffer and can be used indoors and/or outdoors. They meet various international standards and are available with different fiber counts and fiber types. The document also lists the cable's mechanical, ambient, and ordering information.

Uploaded by

sermmys
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TIGHT BUFFER - DISTRIBUTION CABLE OR MINI BREAKOUT

GLASS YARN DIELECTRIC ARMOURING

DESCRIPTION

• The barpa Distribution Cables are


perfect for building backbones and
horizontal distribution applications;
• To use in structured cabling
installations: data centers, LANs,
SANs and longer length backbones;
• Easy strippable tight buffer;
• For indoor and/or outdoor.
Outer Jacket

Tight-buffered
STANDARDS
• ISO/IEC 11801; • EN 50173-1; • EN50575; • IEC 60794-2-20; Strength Member

• IEC 60332-1-2; • IEC 60332-3-24; • IEC 61034-[1,2];


• EN 50399; • ANSI/TIA-568-C; • ITU G652; • ITU G657;
• IEC 60793-2-50; • IEC 60793-2-10; • IEC 60794-1-21;
• IEC 60794-1-22.

INDOOR OUTDOOR CONDUCT CABLE FLAME


TRAY RETARDANT

CABL E PRO PE RT IES


1 - red 1 - red with mark

2 - green 2 - green with mark

3 - blue 3 - blue with mark

4 - yellow 4 - yellow with mark

5 - white 5 - white with mark

6 - grey 6 - grey with mark


Coating Fiber Color
7 - brown 7 - brown with mark

8 - violet 8 - violet with mark

9 - turquoise 9 - turquoise with mark

10 - black 10 - black with mark

11 - orange 11 - orange with mark

12 - pink 12 - pink with mark

Water blocking (Only in Dca) Sweallable tape

Strength member Material Glass Yarns as strength members and rodent protection

Material Halogen free, flame retardant, UV stabilised

Cor OM2 - orange; OM3 - aqua; OM4 - purple; OS2 - yellow.


Sheath
(code) barpa FO Distribution w Glass (CPR class) (fiber type) (No of fibers)F
Marking
(batch no.) Made in EU (meters)m

VDE 888 U-VQ(ZN)H

This document is authored and owned by barpa . It is forbidden to reproduce in whole or in part without mentioning its authorship ,
as well as modification of its content or context. All specifications are subject to change without notice. The pictures/drawings are
merely illustrative.
More information: [email protected] or in www.barpa.eu 1/2
datasheet n° b40_3
TIGHT BUFFER - DISTRIBUTION CABLE OR MINI BREAKOUT
GLASS YARN DIELECTRIC ARMOURING

CA RAC T E R Í ST I CAS M ECÂNICAS E AMBIENTAIS

Method
Dca Limits Cca Limits
IEC 60794-1-21/22

2 4 8 12 24 2 4 8 12 24

Tensile Strength (Long Term) N 160 220 340 450 700 280 280 280 340 400 E1

Tensile Strength (Short Term - Installation) N 325 440 680 900 1400 560 560 560 680 800 E1

Impact J 10 10 10 10 10 20 20 20 20 20 E4

Torsion 5 cycles ± 1 turn E7

Crush N/10cm 2000 2000 2000 2000 2000 3000 3000 3000 3000 3000 E3

Min. Bend radius (permanent - unloaded) mm 50 50 50 50 60 53 57 68 78 86 E11

Installation Temperature ºC -20 a +60 -20 a +70 F1

Operation Temperature ºC -40 a +70 -20 a +70 F1

Storage Temperature ºC -40 a +70 -40 a +70 F1

Water Penetration No water on free end F5C

Cable Diameter mm 4,6 5,2 6 7 8,5 5,3 5,7 6,8 7,2 8,6 -

Nominal Cable Weight kg/km 19 27 36 48 73 35 35 35 80 80 -

OR DER INFO RMAT IO N

Number of Fibers

2 4 8 12 24

OM3 81114101502 81114101504 81114101508 81114101512 81114101524

OM4 81115101602 81115101604 81115101608 81115101612 81115101624

OS2 G652D 81112101102 81112101104 81112101108 81112101112 81112101124

OS2 G657A2 81112101202 81112101204 81112101208 81112101212 81112101224

Bien que la norme ITU G652 soit présente, nous ne parvenons pas à identifier :
- La longueur d'onde ,
- L'atténuation max en dB/Km
- Et la dispersion chromatique max
qui sont des caractéristiques recommandées par la
B16.2.27-STG-Spécification Technique Générale Référentiel Câblage Telecom
This product is developed and produced in Europe.

To order in Dca-s2, d2, a1 add to the code “D1” at the end of the code. To order in Cca add to the code “C1” at the end of the code.
Without any CPR add to the code “S” at the end of the code. Available in different CPR class.
Please specify in your request.

As part of our goal to achieve quality excellence, our barpa System Warranty can give you 25 years products and solution assurance of
compliance with the industry performance standard comparing with the class installed. This warranty applies to network infrastructure
installations that was made by an approved barpa Partner using an barpa solution (end-to-end). For more informations go to our website.

This document is authored and owned by barpa . It is forbidden to reproduce in whole or in part without mentioning its authorship ,
as well as modification of its content or context. All specifications are subject to change without notice. The pictures/drawings are
merely illustrative.
More information: [email protected] or in www.barpa.eu 2/2
datasheet n° b40_3