Product data sheet
Specifications
Harmony, Modular timing relay, 8 A,
2 CO, 0.05 s…300 h, multifunction,
24...240 V AC/DC
RE22R2MYMR
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Harmony Timer Relays
Product or component type Multifunction relay
Discrete output type Relay
Device short name RE22
Nominal output current 8A
Complementary
Contacts type and composition 1 C/O timed or instantaneous contact, cadmium free
2 C/O timed contact, cadmium free
Time delay type Power on-delay
Off-delay
Symmetrical flashing
Interval
Star-delta
Time delay range 3...30 min
30...300 min
0.3...3 s
3...30 h
10...100 s
1...10 s
0.05...1 s
30...300 s
30...300 h
3...30 s
Control type Rotary knob
Diagnostic button
Potentiometer external
[Us] rated supply voltage 24...240 V AC/DC 50/60 Hz
Release input voltage <= 2.4 V
Voltage range 0.85...1.1 Us
Supply frequency 50...60 Hz +/- 5 %
Connections - terminals Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque 0.6…1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Aug 25, 2022 1
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Control signal pulse width 100 ms with load in parallel
30 ms
Insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1
Recovery time 120 ms on de-energisation
Immunity to microbreaks 10 ms
Power consumption in VA 3 VA at 240 V AC
Power consumption in W 1.5 W at 240 V DC
Switching capacity in VA 2000 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 8A
Maximum switching voltage 250 V AC
Electrical durability 100000 cycles, 8 A at 250 V, AC-1
100000 cycles, 2 A at 24 V, DC-1
Mechanical durability 10000000 cycles
Rated impulse withstand 5 kV for 1.2…50 µs conforming to IEC 60664-1
voltage
Power on delay 100 ms
Creepage distance 4 kV/3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data B10d = 160000
MTTFd = 171.2 years
Mounting position Any position
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Status LED LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (fast flashing) for timing in progress and output relay de-energised
LED yellow (slow flashing) for timing in progress and output relay energised
Width 22.5 mm
Net weight 0.105 kg
Environment
Dielectric strength 2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation
conforming to IEC 61812-1
Standards UL 508
IEC 61812-1
Directives 2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
Product certifications RCM
CE
EAC
CSA
CCC
UL
GL
Ambient air temperature for -20…60 °C
operation
Ambient air temperature for -40…70 °C
storage
IP degree of protection IP40 housing: conforming to IEC 60529
IP20 terminals: conforming to IEC 60529
IP50 front panel: conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
2
Aug 25, 2022
Vibration resistance 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn not operating for 11 ms conforming to IEC 60068-2-27
5 gn in operation for 11 ms conforming to IEC 60068-2-27
Relative humidity 95 % at 25…55 °C
Electromagnetic compatibility Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC
61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1
GHz) conforming to IEC 61000-4-3
Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 116.0 g
Package 1 Height 2.6 cm
Package 1 width 8.2 cm
Package 1 Length 9.5 cm
Unit Type of Package 2 S02
Number of Units in Package 2 40
Package 2 Weight 5.153 kg
Package 2 Height 15.0 cm
Package 2 width 30.0 cm
Package 2 Length 40.0 cm
Unit Type of Package 3 P06
Number of Units in Package 3 640
Package 3 Weight 74.24 kg
Package 3 Height 75.0 cm
Package 3 width 60.0 cm
Package 3 Length 80.0 cm
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is
known to the State of California to cause cancer and birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
Aug 25, 2022 3
Product data sheet RE22R2MYMR
Dimensions Drawings
Dimensions
4
Aug 25, 2022
Product data sheet RE22R2MYMR
Connections and Schema
Wiring Diagram
Aug 25, 2022 5
Product data sheet RE22R2MYMR
Technical Description
Function A: Power On-Delay
Description
On energisation of power supply, the timing period T starts. After timing, the output(s) R close(s).The second output (R2) can be either timed
(when set to "TIMED") or instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
6
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function At: Power On-Delay with Pause / Summation Control
Description
On energisation of power supply, the timing period T starts.Timing can be interrupted / paused each time X1 energizes.Except for RE17*,
RE22R2AMU, RE22R2MMW, RE22R2MMU, RE22R2MJU, timing can be interrupted / paused each time Y1 energizes.When the cumulative
total of time periods elapsed reaches the pre-set value T, the output(s) R close(s).The second output (R2) can be either timed (when set to
"TIMED") or instantaneous (when set to "INST").
Function: 1 Output with Pause / Summation Control
T = t1 + t2 +…
Function: 2 Outputs with Pause / Summation Control
T = t1 + t2 +…
Function: 1 Output with Retrigger / Restart Control
T = t1 + t2 +…
Function: 2 Outputs with Retrigger / Restart Control
T = t1 + t2 +…
Aug 25, 2022 7
Product data sheet RE22R2MYMR
Technical Description
Function Aw : Power On-Delay With Retrigger / Restart Control
Description
On energisation of power supply, the timing period T starts.At the end of the timing period T, the output(s) R close(s).Energization of Y1 makes
the output(s) R open(s).Deenergization of Y1 restarts timing period T.At the end of timing period T, the output(s) R close(s).The second output
(R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST")
Function: 1 Output
Function: 2 Outputs
8
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function C: Off-Delay Relay with Control Signal
Description
After energisation of power supply and energization of Y1 causes output(s) R close(s). When Y1 deenergizes, timing T starts.At the end of
this timing period T,the output(s) R revert(s) to its/their initial position.The second output (R2) can be either timed (when set to "TIMED") or
instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
Aug 25, 2022 9
Product data sheet RE22R2MYMR
Technical Description
Function Ct: Off-Delay Relay with Control Signal & With Pause / Summation Control
Description
After energisation of power supply and energization of Y1 cause output(s) R close(s).When Y1 deenergizes, timing starts and the timing can
be interrupted / paused each time X1 energizes. When the cumulative total of time periods elapsedreaches the pre-set value T, the output(s) R
revert(s) to its/their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 1 Output
T = t1 + t2 +…
Function: 2 Outputs
T = t1 + t2 +…
10
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function D: Symmetrical Flashing Relay (Starting Pulse Off)
Description
On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for
the same timing duration T.This cycle is repeated indefintely until power supply removal.Specially for RE17*, RE22R2AMU, RE22R2MMW,
RE22R2MMU, RE22R2MJU,this D function can only be initiated by energizing Y1 permanently.The second output (R2) can be either timed
(when set to "TIMED") or instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
Function: 1 Output with Retrigger / Restart Control
Function: 2 Output with Retrigger / Restart Control
Aug 25, 2022 11
Product data sheet RE22R2MYMR
Technical Description
Function Dt: Symmetrical Flashing Relay (Starting Pulse Off) & With Pause / Summation Control
Description
On energisation of power supply, output(s) R starts at its/their initial state for timing duration T and the timing can be interrupted / paused each
time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, then changes to output(s) R close(s).The
output(s) R close state will remain for the same timing duration T and the timing can be interrupted / paused each time X1 energizes.When
the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state.This cycle is repeated
indefintely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 1 Output
T = t1 + t2 +…
T = t'1 + t'2 +…
Function: 2 Outputs
T = t1 + t2 +…
T = t'1 + t'2 +…
12
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function DW: Symmetrical Flashing Relay (Starting Pulse Off) & With Retrigger / Restart Control
Description
On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for
the same timing duration T.This cycle is repeated indefintely until power supply removal.Specially for RE17*, RE22R2AMU, RE22R2MMW,
RE22R2MMU, RE22R2MJU,this D function can only be initiated by energizing Y1 permanently.The second output (R2) can be either timed
(when set to "TIMED") or instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
Aug 25, 2022 13
Product data sheet RE22R2MYMR
Technical Description
Function Di: Symmetrical Flashing Relay (Starting Pulse On)
Description
On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T then revert(s) to its/their initial state for the
same timing duration T.This cycle is repeated indefintely until power supply removal.The second output (R2) can be either timed (when set to
"TIMED") or instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
14
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function Dit: Symmetrical Flashing Relay (Starting Pulse On) & With Pause / Summation Control
Description
On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T and the timing can be interrupted / paused each
time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, then revert(s) to its/their initial state.The
output(s) R at initial state will remain for the same timing duration T and the timing can be interrupted / paused each time X1 energizes.When
the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R change(s) to close state.This cycle is repeated
indefintely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 1 Output
T = t1 + t2 +…
T = t'1 + t'2 +…
Function: 2 Outputs
T = t1 + t2 +…
T = t'1 + t'2 +…
Aug 25, 2022 15
Product data sheet RE22R2MYMR
Technical Description
Function Diw: Symmetrical Flashing Relay (Starting Pulse On) & With Retrigger / Restart Control
Description
On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T then revert(s) to its/their initial state for the same
timing duration T.This cycle is repeated indefintely until power supply removal.At any state of the output(s) R when Y1 energizes, the output(s)
R will revert to its/their initial state and followed by Y1 deenergizes then restarts the same operation as described at the beginning.The second
output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
16
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function H: Interval Relay
Description
On energisation of power supply, output(s) R close(s) and timing period T starts.At the end of the timing period T, the output(s) R revert(s) to its/
their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
Aug 25, 2022 17
Product data sheet RE22R2MYMR
Technical Description
Function Ht: Interval Relay & With Pause / Summation Control
Description
On energisation of power supply, output(s) R close(s) and timing period T starts.
The timing can be interrupted / paused each time X1 energizes.
When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state Reenergization of
X1 will also cause output(s) R close(s) if the time has elapsed and restart the same operation as described at the beginning.
Except for RE17*, RE22R2MMW, RENF22R2MMW, RE22R2MMU and RE22R2MJU, timing can be interrupted / paused each time Y1
energizes.
The second output (R2) can be either timed (when set to “TIMED” or instantaneous (when set to “INST”).
Function: 1 Output
T = t1 + t2 +...
Function: 2 Outputs
T = t1 + t2 +...
Function: 1 Output with Retrigger / Restart Control
T = t1 + t2 +...
Function: 2 Outputs with Retrigger / Restart Control
T = t1 + t2 +...
18
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function Hw: Interval Relay & with Retrigger / Restart Control
Description
On energisation of power supply, output(s) R close(s) and timing period T starts.At the end of the timing period T, the output(s) R revert(s)
to its/their initial state.At any state of the output(s) R when Y1 energizes followed by deenergizes, the output(s) R close(s) then restarts the
same operation as described at the beginning.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to
"INST").
Function: 1 Output
Function: 2 Outputs
Aug 25, 2022 19
Product data sheet RE22R2MYMR
Technical Description
Function Qg: Star-Delta Relay (2 CO with same Common)
Description
On energisation of power supply, the output R3 closes such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T
starts (STAR connection time duration starts).At the end of the timing period T, the output R3 reverts to its initial state such that deenergizes
STAR CONTACTOR and causes t transition time starts.At the end of the transition time, the output R4 closes such that energizes DELTA
CONTACTOR. Diagnostic feature not available.
Function: 2 Outputs
t : 20, 40, 60, 80, 100, 120, 140 ms
20
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function Qgt: Star-Delta Relay (2 CO with same common) with Pause / Summation Control
Description
On energisation of power supply, the output R3 closes such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts
(STAR connection time duration starts).During STAR connection time, the timing can be interrupted / paused each time X1 energizes.When the
cumulative total of time periods elapsed reaches the pre-set value T, R3 reverts to its initial state such that deenergizes STAR CONTACTOR
and causes t transition time starts.At the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. Diagnostic
feature not available.
Function: 2 Outputs
T = t1 + t2 +…
NOTE: RE22R2MYMR is with fixed transition time, t: 50ms
Aug 25, 2022 21
Product data sheet RE22R2MYMR
Technical Description
Function Qt: Star-Delta Relay (2 CO with Split Common)
Description
On energisation of power supply, the output R3 & R4 initializes at its initial state such that energizes STAR CONTACTOR + MAIN
CONTACTOR and the timing T starts (STAR connection time duration starts).At the end of the timing period T, the output R3 closes such that
deenergizes STAR CONTACTOR and causes t transition time starts.At the end of the transition time, the output R4 closes such that energizes
DELTA CONTACTOR. Diagnostic feature not available.
Function: 2 Outputs
t : 20, 40, 60, 80, 100, 120, 140 ms
22
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function Qtt: Star-Delta Relay (2 CO with same common) with Pause / Summation Control
Description
On energisation of power supply, the output R3 & R4 initializes at its initial state such that energizes STAR CONTACTOR + MAIN
CONTACTOR and the timing T starts (STAR connection time duration starts).During STAR connection time, the timing can be interrupted /
paused each time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output R3 closes such that
deenergizes STAR CONTACTOR and causes t transition time starts.At the end of the transition time, the output R4 closes such that energizes
DELTA CONTACTOR. Diagnostic feature not available.
Function: 2 Outputs
T = t1 + t2 +…
NOTE: RE22R2MYMR is with fixed transition time, t: 50ms
Aug 25, 2022 23
Product data sheet RE22R2MYMR
Technical Description
Function W: Interval Relay with Control Signal Off
Description
After energisation of power supply and on energization of Y1 following by denergization of Y1, the output(s) R close(s) and starts the timing T.At
the end of the timing period, the output(s) R revert(s) to its/their initial state.The second output (R2) can be either timed (when set to "TIMED")
or instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
24
Aug 25, 2022
Product data sheet RE22R2MYMR
Technical Description
Function Wt: Interval Relay with Control Signal Off & with Pause / Summation Control
Description
After energisation of power supply and on energization of Y1 following by denergization of Y1, the output(s) R close(s) and starts the timing
T.Timing can be interrupted / paused each time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T,
the output(s) R revert(s) to its/their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to
"INST").
Function: 1 Output
T = t1 + t2 +…
Function: 2 Outputs
T = t1 + t2 +…
Legend
Relay de-energised
Relay energised
Output open
Output closed
U- Supply
R1/R2 - 2 timed outputs
Ta - Adjustable On-delay
Tr - Adjustable Off-delay
X1 - Pause / Summation control
Y1 - Retrigger / Restart control
X2 - Function Selection
R2 inst. - The second output is instantaneous if the right position is selected
T- Timing period
R4 - Delta contact output
t- Delay to switch ON Delta contact output
R3 - Star-Delta contact output
Aug 25, 2022 25