Calculations for wind load on individual members
1. Site Information
Project Location : Delhi
2. Basic Design Criterion :
Self-Weight of Structure : The structure self-weight is calculated automatically
by the software used for the analysis.
Earthquake Zone : Zone IV As per Bureau of Indian Standards
Basic Wind Speed : 47 Meters per Second (169.2Km/h)
3. Unit of Measurements
Units of measurements used in analysis are SI Units.
4. Wind Load (As per IS 875: part-3, 2015)
Basic wind speed = 47 meter per sec.
Risk Coefficient factor K1 = 0.90 (As per IS 875: part-3:2015, Table-1 For 47 m/s basic
wind speed & 25 years probable design life of Structure).
Terrain & Height Factor K2 = 0.91 (As per IS 875: part-3:2015, Table-2 for category 3,
Height- 10 Meters)
Topography Factor K3 =1
Design wind speed, Vz = Vb*K1 * K2 * K3
Design wind speed, Vz = 47 *0.90 * 0.91 * 1.0
= 38.5 M/s
Design Wind Pressure, Pz = 0.6*(38.5) ^2
= 0.89 KN/M^2
Design Wind Pressure (Pd) = Kd*Ka*Kc*Pz
Kd=Wind Directionality Factor = 0.9
Ka=Area Averaging Factor = 1.00 (As per IS 875: part-3:2015, Table-4 )
Kc=Combination Factor = 1.00
Design Wind Pressure (Pd) = 0.89 * 0.9 * 1 * 1
Page 1 of 2
= 0.8 KN/ sq. mtrs
4.1 Wind Forces in Lateral Direction on Member:
Force Calculation as per Table 28, 29 - IS 875:Part 3:2015
Members Section
Length Width Depth
S.No Item Section
mm mm mm
1 L Angle 65 x 65 x 6 10000 65 65
2 RHS 50 x 25 x 2.9 500 50 25
Normal Force Fn = Cfn x Pd x K x lxb
Transverse Force Ft = Cft x Pd x K x lxb
Sections L/b K Cfn/Cft Fn/Ft
L Angle 153.85 1 2.10 0.109
RHS 50 MM Side 10 0.69 2.00 0.072
RHS 25 MM Side 20 0.81 2.00 0.065