SC7010BVA Specs
SC7010BVA Specs
COMBO
ALARM
SC7010BV 120V AC, 60Hz Wire-in
CAT.
The BRK Model No. SC7010BV is a wire-in, 120V AC 60Hz single and/or multiple
station combination smoke and carbon monoxide alarm specifically designed for
residential and institutional applications including sleeping rooms of hospitals, ho-
tels, motels, dormitories and other multi-family dwellings as defined in standard
10YR CO SENSOR NFPA 101. Model SC7010BV complies with UL217 and UL2034, CSFM, NFPA 72
10YR ALARM LIFE and NFPA 720, HUD, FHA and other agencies that model their codes after the
above agencies. It meets building codes where AC/DC photoelectric smoke and
carbon monoxide alarms with and without voice are required.
SMOKE & CO COMBO The BRK SC7010BV is a state-of-the-art hardwired with battery backup smoke/
Electrochemical CO sensor; Photoelec- CO combo alarm that features a photoelectric smoke sensing chamber, an elec-
tric smoke sensor. trochemical CO sensor, an End of Life signal and voice warning with location. This
exclusive feature incorporates a voice that will speak one of 11 pre-programmed
VOICE WARNING locations and the danger detected. The Spread Spectrum Horn Tone has a lower
and varying frequency that makes it easier for the elderly with normal age related
WITH LOCATION hearing loss to hear the horn. This alarm features two latching features and two
Exclusive! A voice will tell you the pro- silence features. Alarm Latch: Easily identifies initiating alarm even after alarm
condition has subsided. Low Battery Latch: Identifies which unit is in low battery
grammed location of the unit and danger condition by blinking the green power light. Low Battery Silence: Temporarily si-
detected. lence the low battery chirp for up to eight hours. Alarm Silence: Silence alarm for
several minutes. Other features include an 85dB horn and silence. OptiPath 360
Technology provides 360 degrees of direct access to the smoke sensor. Two lock-
SILENCE FEATURE ing features are provided to prevent battery theft and/or theft of the unit. Connec-
Silences nuisance alarms. tion to AC power is made with a Quick-Connect wiring harness.
SPREAD SPECTRUM
HORN TONE
Easier for elderly with normal age
related hearing loss to hear the horn.
OPTIPATH 360
TECHNOLOGY TM
Provides 360 degrees of direct access
to the smoke sensing chamber.
SC7010BV
CAT.
TECHNICAL SPECS
Alarm Dimensions: 5.0”dia. x 2.0”H
Weight: 9.3 oz
TOP VIEW SIDE VIEW
MOUNTING Operating Voltage: 120V AC 60Hz with 3V alkaline battery backup (two 1.5V)
BRACKET
Operating Current: 0.05 amps (standby/alarm)
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
5.0” Voice Output: Choice of 11 pre-programmed locations warns of smoke
or CO danger and location of danger
Test/Silence: Electronically simulates smoke or CO condition, causing the
unit to alarm. Press and hold test/silence button.
Alarm Reset: Automatic when smoke or CO clears
2.0” Interconnections: Up to 18 units of First Alert or BRK Smoke, CO and Heat
Alarms. Maximum of 12 smoke alarms.
ARCHITECTURAL AND ENGINEERING SPEC Smoke Sensor: Photoelectric
The combination smoke and carbon monoxide alarm shall be a BRK Model SC7010BV and CO Sensor: Electrochemical
shall provide at a minimum the following features and functions:
1. A photoelectric smoke sensing chamber and an electrochemical CO sensor both with Indicator Lights/Sounds:
a 10 year service life. AC Power: Constant Green LED
2. Powered by 120V AC, 60Hz and have a monitored battery backup and a solid state DC Power: Intermittent Green LED
piezo horn rated at 85dB at 10 ft. and shall be capable of self restoring.The horn Local Alarm: Red LED flashes, Voice: “Smoke” or “CO” with location
shall have a lower and varying horn frequency to to make it easier for the elderly with
normal age related hearing loss to better hear the horn. Remote Alarm: Red LED off, Voice: “Smoke” or “CO” without location
3. A Voice Warning of Smoke or Carbon Monoxide detected in addition to speaking 11 Latching Alarm: Red LED flashes every 5 seconds after local alarm
pre-programmed locations, e.g. “Warning, Evacuate, Smoke in Basement” Low Battery Latch: “Power” LED flashes green on for 2 sec, off for 2 sec
4. The unit shall have an “End of Life” signal (5 chirps). This signal should be capable of
temporarily being silenced for up to 2 days. After about 2 days, the signal will resume. Listing: Listed to UL217 and UL2034 Standards
After about 2-3 weeks the signal cannot be silenced. SHIPPING SPECS
5. A visual power-on indicator to confirm unit is receiving AC power or has switched to
battery backup mode. Separate LED ‘s to indicate a smoke or CO alarm. Individual Carton Dimensions 5.13”L x 2.38”W x 5.13”H
6. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not alarm Weight 0.74 lbs.
when exposed to constant levels of 30 PPM for 30 days. It will alarm at the following
levels: 400 PPM CO between 4 and 15 minutes, 150 PPM CO between 10 and 50 Cube 0.04 ft3
minutes and 70 PPM CO between 60 and 240 minutes. UPC 0 29054 00229 7
7. Two Latching features: Alarm Latch to easily identify initiating alarm after alarm
condition has subsided. Low battery latch: to visually identify which unit is in low Master Carton Dimensions 10.75”L x 7.88”W x 11.06”H
battery condition. Two Silence Features: Alarm Silence to temporarily silence nuisance Master Pack 12
alarms. Low Battery Silence to silence low battery chirp for up to 8 hours.
8. Two Locking features - tamper resistant locking pins that lock battery drawer and/or Weight 9.4 lbs.
alarm to mounting bracket. Cube: 0.54 ft3
9. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and
relative humidity between 10% and 95%. I2of5: 100 29054 00229 4
10. The unit shall have a plug in connector and be capable of interconnection of up to 18 Pallet Information
alarms, 12 of which can be smoke alarms.
11. The unit shall at a minimum meet the requirements of UL217 and UL2034, CSFM, Cases per Layer 22
NFPA 72 and 720 and the ICC. Number of Layers: 4
INSTALLATION OF ALARM B Cases per Pallet: 88
Installation of this smoke alarm must conform to all local Units per Pallet: 1,056
}
678
electrical codes and Article 760 of the National Electrical Code Cube: 54.0 ft3
(NFPA 70) and NFPA 72. Interconnected units must meet the
following requirements: Total length of wire interconnecting Weight: 892 lbs.
units should be less than 1000 feet, be #18 gauge or larger
and be rated at least 300V. It is recommended that all units BATTERY DRAWER LOCK
be on the same fuse or circuit breaker. If local codes do not Remove Pin from Close Door. Insert Pin in Holes
permit, be sure the neutral wire is common to both phases. Mounting Bracket through alarm and Battery Drawer
THE PARTS OF THIS ALARM
5 43 1
1 1. Mounting bracket
2
2 2. Mounting Slots
3. Locking Pins
4. Hot (Black) AC Wire
5. Nuetral (White) AC Wire
3 6 6. Interconnect (Orange) Wire
7. Pull-out battery drawer
5
8. Quick-Connect Plug
4
}
A 5 43 2 1
A. Unswitched 120VAC 60 Hz source
©2016 BRK Brands, Inc. a subsidiary of Newell Brands
B. To additional units; Maximum = 18 total
(NYSE: NWL) 3901 Liberty Street Road, Aurora, IL 60504-
7 (Maximum 12 Smoke Alarms)
8122, All rights reserved. First Alert is a registered trade-
1. Smoke /CO Alarm 5. Junction Box mark of the First Alert Trust. BRK is a registered trademark
2. Ceiling or Wall 6. Neutral Wire (White) of BRK Brands, Inc.
3. Power Connector 7. Interconnect Wire (Orange) CM3235
4. Wire Nut 8. Hot Wire (Black)
8 brkelectronics.com