Oil Drain Valve UHF PD Sensor
UHF PD sensor for transformer oil drain valves for PD measuring or monitoring systems
Transformers are an essential, critical and expensive part of electric power transmission and distribution
systems. Failure of a transformer will unavoidably lead to power outage, damage, and costly repair or
replacement. A continuous partial discharge (PD) monitoring of transformers detects deterioration of its
insulation system at an early stage and allows to take measures before insulation breakdown and failure
happens. A partial discharge monitoring system (PDMS) also helps to understand the health of
transformers and supports maintenance and asset management.
Within the PDMS hardware infrastructure, the sensors for picking up the electromagnetic PD signals from
within the oil-filled transformer housing play a crucial role in detecting PD. Usually, transformers do not
have integrated PD sensors, in particular in older installations. The oil drain valve ultra-high frequency
(UHF) sensor can be retrofitted into any transformer with a standard oil drain valve, even adaptation to
non-standard valves is possible. Using oil drain valve sensors, the transformer tank acts as shielding
against external electromagnetic interference, thus the UHF measurement has high sensitivity and a good
signal to noise ratio.
Features:
Decoupling of PD signals from the inside of oil-immersed components in power transformers
Easy and leak free installation into oil-filled transformers and reactors
Standard designs for DN 50 and DN 80 drain valves
Online installation of the sensor, no power-down necessary
No infringement of critical sections of the transformer
Suitable for permanent and temporary installation
Technical Data:
Electrical
Frequency Range 100 MHz – 2 GHz
Impedance 50 Ω
Mechanical
Maximum
450 mm
Penetration
Weight 3 kg (depending on diameter)
Operation
Max. Oil 120°C (248°F)
Temperature
Max. Pressure 5 bar (0.5 MPa)
8526 Virginia Meadows Drive | Manassas, Virginia 20109 | USA
T: +1-703-365-2330 | F: +1-703-365-2331 |
[email protected] | www.hvtechnologies.com
Scope of Supply:
Transformer oil drain valve sensor
Fastener set
Installation instruction
Application Example:
Oil drain valve UHF PD sensors can be used in combination with the PDMS partial discharge monitoring
system.
Example: Transformer PDMS using bushing and oil drain valve UHF PD sensors.
8526 Virginia Meadows Drive | Manassas, Virginia 20109 | USA
T: +1-703-365-2330 | F: +1-703-365-2331 |