CHISAGE ESS www.chisagess.
com
Technical Data
Model Mars-5G1-LE Mars-6G1-LE Mars-8G1-LE Mars-10G1-LE Mars-12G1-LE Mars-14G1-LE
Battery Input
Battery Type Lead-acid or Li-Lon
Battery Voltage Range (V) 40-60
Triple Phase
Max. Charge Current (A) 120 130 200 220 250 280
Max. Discharge Current (A) 120 130 200 220 250 280
Charging Curve 3 Stages/Equalization
External Temperature Sensor Yes
Hybrid Inverter
Charging Strategy for Li-Ion Battery Self-Adaption to BMS
PV String Input
Max. DC Input Power (W) 7,500 9,000 12,000 15,000 18,000 20,000
PV Input Voltage (V) 650(160~800)
MPPT Range (V) 200~700
Full Load DC Voltage Range (V) 260~650
Start-up Voltage (V) 160
PV Input Current (A) 17+17 17+17 17+17 26+17 26+17 26+17
Max. PV Isc (A) 20+20 20+20 20+20 34+20 34+20 34+20
No. of MPPT Trackers 2
Mars-5/6/8/10/12/14G1-LE No. of Strings per MPPT Trackers
AC Output
1+1 1+1 1+1 2+1 2+1 2+1
Rated AC Output and UPS Power (W) 5,000 6,000 8,000 10,000 12,000 14,000
Max. AC Output Power (W) 6,000 7,200 9,600 12,000 13,200 15,400
Peak PoWer(off grid) 2 times of rated power, 10s 1.8 times of rated power, 10s
AC Output Rated Current (A) 7.6/7.3 9.1/8.7 12.1/11.6 15.2/14.5 18.2/17.4 21.1/20.3
Max. AC Current (A) 11.4/10.9 13.6/13 18.2/17.4 22.7/21.7 27.3/26.1 27.6/26.4
Max. Continuous AC Passthrough (A) 30 30 30 50 50 50
Power Factor 0.8 leading to 0.8 lagging
Output Frequency and Voltage (V) 50/60Hz, 380/400Vac(Triple phase)
Grid Type Three phase
Current Harmonic Distortion THD<3%(Linear load<1.5%)
Efficiency
Max. Efficiency 96.60%
Euro Efficiency 96.00%
Product Features MPPT Efficiency
Protection
99.00%
PV Input Lightning Protection, Anti-islanding Protection, PV String Input Reverse Polarity Protection, Insulation
Integrated
Resistor Detection, Residual Current Monitoring Unit, Output Over Current Protection, Output Shorted Protection
Support different power inverters parallel connection
PV ARC Fault Detection Optional
Unlimited quantity inverters parallel for on-grid and off-grid operation Output Over Voltage Protection DC Type II/AC Type III
Certifications and Standards
100% unbalanced output, each phase max. output up to 50% rated power Grid Regulation CEI 0-21, VDE-AR-N 4105, NRS 097, IEC 61727, G99, G98, VDE 0126-1-1, RD 1699,C10-11
Safety Regulation IEC/EN62109-1, IEC/EN62109-2
Support on/off grid mode switch, EPS output EMC IEC/EN 61000-6-1,IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61000-6-4
General Data
Colorful 7-inch touch LCD, IP65 protection degree Operating Temperature Range (℃) -45~60, >45 Derating
Cooling Smart Cooling
Support battery charging/discharging according to the time setting
Noise (dB) ≤45
Independent AC input port for diesel generator Communication with BMS CAN, RS485
Weight (kg) 38 40 42 44 44 45
Support storing energy from diesel generator Dimensions (mm) 510W×630H×290D
Protection Degree IP65
ARC fault detection optional Installation Style Wall-mounted
Warranty 5 Years
51 52