0 ratings0% found this document useful (0 votes) 69 views6 pagesPole Barn Foundations
pole barn foundations in farm buildings
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
Poce 24M BES ign)
A section which meets these requirements and is in accordance with
industry standard depths and widths measu =28.1ind
indsty a Pt veastres 3X9, A= 28.1 in.
2. Check for combined stresses.
P_ 57,600
050 psi
210 psi
15 (030(2.000,000)
° [3.390129]
F, = 2,800 psi > 2,190 psi
190 psi
2,190 psi
Use Ft =
_ 57,600,
(28.1)(2, 190)" (42.2)(2,740)
Try aShX 12, A = 97.5 ine, $= 75.0ind
5 (0.8)(2,000,000)
1 [3.8)(12y 127
2. Use Fy!
__57,600
67.5)(2,300)
986+0.440=1.376>1 NG.
F,
900 psi
W916 <1 OK,
5: Gheck for radial stess. Moment is tending to decrease the radius,
therefore, radial stress is compressive and allowable radial stress —
Fe =410 pai
(860,900)
Hena2ye
Use a $4X 12 glued laminated top chord.
QI2psi< 470 OK.
4. Une pottom cnora Is GesigHeu wr wiLeLe eeNsON Yin, HILL CHIL ae
no ceiling loads, The center panel is critical.
Required 4 =
‘A. 31xc7h section would be adequate to meet this requirement. How-
ever, the section size reduced by the projected area of the fastenings
at that section must meet net section requirements (see page 8-13)
If ceiling loads are present, bending is induced in the member, and
the bottom chord must be designed for combined loading.
‘The complete design of 2 truss includes other factors noted in the
general design procedure beginning on page 4-88,
POLE-TYPE FRAMING
Pole-type frame structures employ preservatively treated timber poles or
sawn timber posts set in the ground as'main structural members. Usually,
the hole in which the pole or post is set furnishes both vertical and hori-
zontal support for the pole in supporting the structure, Setting the pole
in the ground tends to’ prevent rotation of the bottom of the pole and
thereby provides some or all of the required ‘bracing. Preservative treat-
ment of poles should be in accordance with the American Wood-Preservers’
Association Standards Gl and C4,
General Considerations
General considerations, which are applicable to all pole-type frame
structures include the following
1. A bracing system can be provided at the top of a pole in orde¥ to re-
duce bending moments at the base of the pole and to distribute loads, The
design of buildings supported by poles without bracing requires good
knowledge of soil conditions in order to eliminate excessive deflection or
sidesway.
2, Bearing values under butt ends of poles should be checked. It is
common practice to backfill holes around the pote with well-tamped native
soil, sand, or gravel. Backfilling with concrete or soil-cement can develop
a more effective pole diameter; consequently, it can be used as a means of
reducing required depth of embedment, Concrete backfill also increases
the area of the pole for skin friction and thus increases the bearing capacity.
Skin friction is also effective where uplift due to wind may act on a pole
through its connections to the roof framing.
3. In order to increase bearing capacity under pole butts, concrete foot
ings may be used, If they are used, they should be designed to withstand
the punching shear of the pole and bending moment due to the pole load.
Thickness of concrete footings should never be less than 12 in. and may
need to be greater, depending on the loads. Concrete footings should be
considered even in firm soils such as dry hard clay, coarse firm sand, or
gravel.The intended use of the structure largely determines such general
features as height, overall length and width, spacing of poles, height at
aves, type of roof framing, and the kind of flooring to be used, as well as
any special features such as wide bays, unsymmetrical layouts, or the
possible suspension of particular loads from the roof framing. These
General design features having been determined, the following procedure
may be used.
Design procedure.
1, Determine loads. The principal load on a pole-type frame is generally
the horizontal wind load; therefore, the wind load value required by the
governing building code or, in the absence of a governing code, as deter-
mined from Section 3 of this Manual, should be used. In addition to dead
load and other loads, roofs will transmit vertical components of wind load
to poles. When wind loads are involved, allowable unit stress values may
be increased one-third for the duration of loading,
2 Determine soil values. If soil tests are not available, visual inspection
and a careful estimate of the bearing value of samples of the soil should be
made, Building codes contain allowable design values for direct bearing
assigned to various sol classifications.
Normally, building codes do not give established allowable passive soil
pressure values, in which case the values may be determined by using
Rankine’s formula
—ltsing
oT sing
where p = allowable passive soil pressure, psf per ft of depth
$= angle of internal friction of soll, degrees
w= weight of soil, pef
d= depth below grade, ft
Allowable soil pressure values for various classes of soil are also given in
‘Table 4.8. For most soils suitable for foundations, a value of p = 250 psf is
conservative.
8. Estimate the size of pole required. The American National Standards
Institute (ANSI) has established certain pole classes. Table 4.9 tabulates the
size requirements corresponding to ANSI Classes H-6 through 10 for
Douglas fir and for Southern pine poles.
Poles of a given class and length are selected to have approximately the
same load carrying capacity regardless of species. The minimum circum-
ferences specified at 6 ft from the butt in Table 4.9 are based on the maxi-
mum fiber stress in bending that will occur at the groundline due to a
given horizontal load applied 2 ft from the top of the pole. The horizontal
loads used in the calculations for separating the 15 classes given in Table 4.9
Class Horizontal Load, Ib
TABLE 48
ALLOWABLE LATERAL PASSIVE SOIL PRESSURE,
Maximum
Allowable
Values, psf
Allowable Values per
Foot of Depth Below
(Class of Material Natural Grade, p, psf
© Sempac,well-graded sand
and gravel
Hard cay
Well graded fine and coarse
tand
{all drained, so water wil
ntsc)
aver
‘Gompactfine sand
Medium day
Compactsandy loam
Loose sand and gravel
{Alldrained, so water il
notstand)
Poor
Softlay
hay oa
Poorly compacted
Glays containing large
amounts of st
{Water stands during wet
season)
400 8,000
200 2,600
100 1,500
‘ing lateral bearing ves
olted poles, such as flagpoles or signs, maybe designed using
tuled these tabulated values.vougias nr or poutnern pine are given m Lapie 4.av. Ar 1wo1eS 4.9 anu nay
are used, the load to be supported by the poles is known and an estimate of
the size of pole required can be made.
TABLE 4.10
SAFE CONCENTRIG COLUMN LOADS ON
DOUGLAS FIR AND SOUTHERN PINE POLES
Safe Concentric Column Load, Ib
Minimum Top Diameter
|
1972 by American National Seandaras om
Unsupported
g Sate eng ———
g {above Groundline), Bin Tin. | Gin. bin.
2 — ANSI Pole Gas
He Zz 2 8
é é 0 | 2500.) 3800 | 26000
i e ° Shawo | 2800 |, 14000
é é 12 36.500 | 20,500 |" 10,000
: € it rsnd-| issn | 3000
i § i Zao | 12500 | 6200
a 3 18 17,500 | 10,000 | 5,000
tI 3 20 15,000. | 8500 | 4,500
i % tomo’ | 6000
5 % 300
i ss He
&
;
Circumferences at points other than those tabulated in Table 4.9 may be
determined assuming an average taper of 0.25 in, circumference per Foot
of length of pole for Douglas firand Southern pine,
mt and Dimers
4, Determine required embedment of pole. The following formula may
be used in determining required embedment depth where no constraint
(euch as a rigid floor or surface pavement) is provided at the ground sur-
face. Note that this procedure requires the assumption of an initial embed-
E olges ment depth,
| iste a4 36h) cured a( Tae
(| be) G85 4 (4 I ) Geerigureszy d= 5 (hie
a7 se a where d= depth of embedment, ft
“lege A=234P|S,B
gees P = applied horizontal force on pole, Ib
5, = pdiS (see Table 4.8 for p)
‘h= height above groundline at which force P is applied, ft
B butt diameter of pole or diameter of concrete casing, ft(wth no restrair
with restrain
Grounding
1 2 (oth sl beck
Le B (th concrete fi
Figure 424, DEPTH OF EMBEDMENT.
If the post is restrained at the groundline such as by a rigid concrete
floor, the following formula is used
fe
pd (see Table 4.8 for p; note that S, values may not exceed the
‘maximum values specified in Table 4.8)
where 5,
and other terms are as previously defined,
For poles having some degree of fixity or restraint at the eave line, such
as provided by knee braces, the point at which the applied horizontal force,
P, acts is at the point of inflection of the pole. For round, tapered poles,
the point of inflection is assumed to be at two-thirds the distance from the
groundiine to the point of restraint. For poles with no restraint, the height
to the top of the pole is used as the value for h.
It may be desirable to repeat the procedure for determining embedment
with the first determination of embedment as the basis for recalculating the
parameter S;,
5. Check pole bending stress, The actual bending stress in the pole at
the point of maximum bending moment may be determined by the formula
32mm _ 32M
f M
Gab
where f= actual bending stress, psi
(C= pole circumference at point of maximum moment, in
ole diameter at point of maximum moment, in.
naximum moment, in-lb, which, for a round, tapered pole,
is assumed to occur at one-fourth the depth of embedment
below groundline; it may be determined if P and A, as previously
defined, are known,
creased one-third for wind duration ot ioaaing.
TABLE 4.11
STRESS VALUES FOR TREATED®
ANSI POLE
(Normal Duration of Loading)
SPECIES
Modulus of | Extreme
Rupture,” | Fiberin |Modulus of] Compression
lextreme Fiber| Bending,*| Elasicity,® | Parallel to Grain‘
inBending, | Fe. BE Fe
Species ai al psi pal
Cedar, Northern white] 4,000 1,540 | 600,000 40
Cedar, Western red 6,000 1850 | 900,000, 1,030
Douglas fir 8,000 2,700 | 1,500,000 1,360
‘Hemlock, Western "7400 21880 | 1,800,000 1.250
Larch, Western 8,400 140 | 1,500,000 1,500
Pine, jack 6,600 100 | 1,100,000, 1,100
Pine, lodgepole 6,600 1820 | 1,100,000, ‘980
Pine, ponderosa 6,000 1.710 | 1,000,000 920
Pine, red or Norway 6,600 2,100 | 1,300,000 4,020
Pine, Southern 8,000 2.749 | 1,500,000 1,360
*Ain-dried prior to treatment.
‘Based on Utmerican National Standard Speifcations and Dimensions for Wood Pele, ANSI 05.1
1972,
‘Baned on ASTM D 2890-707, Tetatoe Method for Bstelishing Design Streit for Round Timber
Piles
‘Above the pole’s point of inflection, the bending moment reaches a
maximum at the bottom of the roof bracing. The bending stress at this
point should also be checked to make sure that it does not exceed the
allowable bending stress.
6. Check the pole compression stress. The vertical loads on one pole
include, in addition to applied live loads and/or snow loads and dead load
of the supported structure, the vertical component of wind load and one-~
third the weight of the pole
“The allowable unit stress for a round column may be determined by
the formula
ay
for Iid ratio, psi
3.68 _ 0.2258
Dy
where F,! = allowable unit stress in compression parallel to grai
adjusted
E = modulus of elasticity of pole species, psi (see Table 4.11)
= unsupported length of pole, in.
the top, in. (= D4/16)
least radius of gyration of pole at one-third the length fromand maximum diameters, but in no case shall it be assumed as
‘more than I} times the minimum diameter,
‘The ratio ID should not exceed 44 for round columns. The unsupported
length of long poles may be reduced by providing bracing in both direc-
tions at approximately the inflection point of the pole. The actual com.
pression. parallel to grain stress at the top, or small end, of the pole should
be checked, and it should not exceed the allowable unit stress for a short
column, Actual compressive stress j. may be determined by the formula
-
fn q
where P = total vertical load on the pole, Ib
4
ross-sectional area at the top of the pole, in,
7. Determine footing requirements, The pole footing requirements can
be determined if the kind of soil, the vertical load on the pole, and the size
of pole required are known. Soil beating
i§ load, in pounds per square foot,
can be determined by the formula
‘| siae
Soil bearing load = 144
where P = total vertical load on pole, Ib
4 = area of butt of pole, in?
If this load exceeds the allowable bearing capacity, Sq, for the type of soil
in question, a concrete footing is required.
The required area, 4c, in square feet, of a concrete footing may be deter-
mined by the formula
A=P
Se
Concrete footings should be designed in acrordance with the recom-
mendations of the American Concrete Institute.
Example. Design the poles for the illustrated typical bent of a pole-type
building to meet the stated conditions:
Six
ee Ged
laminteg
‘eam
ing
areatiog
Grounding
Bent spacing = Y= 15
= 1,500,000 pst
Determine loads.
YL(DL+SL)
2
Vertical load on one pole = ¥ =
1 = ONEDLO 9
Ib
(wt = GEIE2829) 15) — 2.9201
‘Wind load at top of pole
Soil values.
Soil is compact, well-graded sand (good soil)
Allowable passive pressure = p= 400 pst (from Table 4.8)
Allowable bearing capacity = Sp = 8,000 psf
Concrete fill not required
Estimate size of pole required.
From Table 4.10, for an unsupported pole length of 15 ft carrying a
11,250 Ib load, select an ANSI Class 5 pole.
Assuming a 12 ft depth of embedment, from Table 4.9.2 30 ft Class
5 pole has a minimum top circumference of 19in. and a minimum
circumference 6 ft from the butt of 27.5 in.
Determine required embedment,
Distance from groundline to point of inflection =k = # unsupported
pole length = §(15) = 10ft
Diameter 6 ft from butt =8.75in.
27.5-+ (60.25) _
Butt diameter = B 9.28in, = 0.769 ft
td _ (40090120)
= 3
1,600 psf
3
AP _ 3N2320 4 44
SB (1,600)(0.769)
Depth of embedment = ¢
aaA(ts 8)
Al CIID) _
BC Yi 2) - gs 8
49. uneck venaing stress,
Maximum moment = M= 1» (v4)
1=a2yea2y (19042) 262006
j
1. Gircumference at depth of embedment
st_@y
34 (0102) 69 istance rom but .
= 215~(0-6,0.25) = 265m
nM _ 32%
[oa (26.75)>
} ‘Try a Class 2 pole~ circumference 6 ft f
' y ‘umference 6 ft from butt = 34,
i Circumference at tdepth of embedment
970 psi > 3,590 N,
C= 34.0~(9-6)(0.25) =
fo $222(862,000)
° (33.25)?
Use a Class 2 pole
Upper maximum moment occurs at the knee brace-
tio, oF 5 feabovethe pointofinflction nn mnconnee
Upper maximum M = 12P(5) = (12)(2,320)(6
(M= 139,200 in.-lb 7
Circumference at knee brace connection = C
Top circumference for Class 2 pole = 25 in,
Knee brace connection occurs 3 ft below top
C= 25+ (3)(0.25) = 95.75in.
2m?M _ $2*(139,200
Cc (25.75)*
090 psi < 3,590 OK.
fe = 2,570 psi < 3,590 OK.
Check compression stress.
‘Weight of 30 ft Class 2 pole = W = 725 Ib (approx.)
735
Axial load = P = 1,250-+ 725
Ww
w+
P=11,4901b
Diameter at pole length
=108) rom top =
[
Diameter at top =
25+ (103(0.25)
a 8.75 in
0.2258 _ (0.225)(1 500,000)
py (20.6)
Fe 95 Psi
es oper
Perot soetaets Ths
7. Determine footing requirements.
Area of pole butt
40+ 6,025)
tr
A= 100in#
P
Soil bearing load = 1447 = 490) — 16,850 psf > 8,000; there-
fore, a footing is required
Required area of concrete footing = Ae
436 ft
TIMBER PILES
Recommendations for the use of timber piles in foundations may be
found in Pressure Treated Timber Foundation Piles for Permanent Structures,
of the American Wood Preservers Institute The American Society for
Testing and Materials publication, Standard Specifications for Round Timber
Piles, ASTM D25~70, clasifies round timber piles according to the manner
in which their load carrying capacity is developed. There are two classes:
1. Friction Piles, Friction piles are specified when pile capacity is deter-
mined by the friction developed in contact with the surrounding soil, along
with the compressive strength of the timber piles used.
2. End-Bearing Piles. End:bearing piles are specified when pile capacity
is determined primarily by the end-bearing capacity of the soil at the pile
tip, along with the compressive strength of the timber piles used.
‘Table 4.12 lists size requirements for piles in accordance with ASTM Speci-
fication D25-70.
FALSEWORK AND CENTERING
Framing employing either glued laminated or sawn material is often
economically used as falsework to support formwork for large poured-io-
place concrete structures or as centering for placing precast concrete,
stone, and steel structures which are assembled in place.
Falsework is the temporary structure erected to support work in the
process of construction. It may be composed of structural units such as
‘columns, beams, trusses, arches, and bracing designed by standard engin-
ering procedure. The type and/or combination of structural units used