NC202A
MCB 2P 10kA C-2A 2M
Technical properties
Architecture
Number of protected poles 2
Number of poles 2P
Type of pole 2P
NC202A
Curve C
Functions
Concurrently switching N-neutral No
Configuration
Number of modules 2
Connectivity
Top connection alignement for modular
devices Aligned terminal
Bottom connection alignement for modular
devices Aligned terminal
Main electrical features
Rated short circuit breaking capacity Icn AC
according IEC60898-1 10 kA
Rated operational voltage Ue 230 / 400 V
Frequency 50/60 Hz
Voltage
Rated insulation voltage 500 V
Rated impulse withstand voltage 4000 V
Electric current
Rated current 2A
Rated service breaking capacity Ics AC
according IEC 60898-1 7.5 kA
min/maxi threshold value of the AC thermal
operation 1.13 / 1.45 In
Magnetic regulating currrent 5 / 10 In
min/maxi threshold value of the DC
magnetic operation 5 / 15 In
min/maxi threshold value of the DC thermal
operation 1.13 / 1.45 In
Breaking capacity on 1 pole for IT 400V NF
60947-2 3 kA
Rated short circuit breaking capacity Icn
under 400V AC according IEC60898-1 10 kA
Subject to technical modifications
Rated ultimate short-circuit breaking
capacity Icu under 230V AC IEC 60947-2 15 kA
Rated ultimate short-circuit breaking
capacity Icu under 415V AC IEC 60947-2 15 kA
Electric current / temperature
Rating current -25°C 2.3 A
Rating current -20°C 2.3 A
Rating current -15°C 2.2 A
Rating current -10°C 2.2 A
Rating current -5°C 2.2 A
Rating current 0°C 2.2 A
Rating current 5°C 2.1 A
Rating current 10°C 2.1 A
Rating current 15°C 2.1 A
Rating current 20°C 2.1 A
Rating current 25°C 2A
Rating current 30°C 2A
Rating current 35°C 2A
Rating current 40°C 1.9 A
Rating current 45°C 1.9 A
Rating current 50°C 1.9 A
Rating current 55°C 1.9 A
Rating current 60°C 1.8 A
Rating current 65°C 1.8 A
Rating current 70°C 1.8 A
Current correction factors
Correction factor of rating current for 2
devices placed side-by-side 1
Correction factor of rating current for 3
devices placed side-by-side 0.95
Correction factor of rating current for 4 and
5 devices placed side-by-side 0.9
Correction factor of rating current for 6
devices placed side-by-side 0.85
Correction factor of magnetic tripping with
100 Hz 1.1
Correction factor of magnetic tripping with
200 Hz 1.2
Correction factor of magnetic tripping with
400 Hz 1.5
Correction factor of magnetic tripping with
60 Hz 1
Dimensions
Depth of installed product 70 mm
Height of installed product 83 mm
Width of installed product 35 mm
Frequency
Frequency 50 to 60 Hz
Subject to technical modifications
Power
Total power loss under IN 2.8 W
Power loss per pole at In 1.41 W
Endurance
Electric endurance in number of cycles 10000
Number of mechanical operations 20000
Installation, mounting
Type of top connection for modular devices with screw
Tightening torque 2,8Nm
Type of top rail clip for modular devices NA
Type of bottom rail clip for modular devices metallic
Type of Bottom Connection for modular
devices BIconnect
Top removability for modular devices No
Bottom removability for modular devices No
Connection
Connection cross-section of input and
output with screws, for massive conductors 1 / 35 mm²
Connection cross section of access and exit
with screws, for flexible conductor 1 / 25 mm²
Type of connection with screw
Equipment
With transparent product label holder No
Standards
Standard text EN 60898-1
European directive WEEE not concerned
Use conditions
Operating temperature -25…70 °C
Degree of pollution according to IEC 60664 /
IEC 60947-2 2
Class of energy limitation I²t 3
Altitude 2000 m
Air humidity protection for all climates
Storage/transport temperature -25…80 °C
Subject to technical modifications