0% found this document useful (0 votes)
22 views3 pages

NC202A

The document provides technical specifications for the NC202A miniature circuit breaker. It is a 2-pole, 2-module circuit breaker rated for 10kA with a C-curve. Key specifications include a rated operational voltage of 230/400V, rated current of 2A, rated short circuit breaking capacity of 10kA, and dimensions of 70mm depth, 83mm height, and 35mm width. It has a rated operational temperature range of -25°C to 70°C.

Uploaded by

Rushabh Kasrung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views3 pages

NC202A

The document provides technical specifications for the NC202A miniature circuit breaker. It is a 2-pole, 2-module circuit breaker rated for 10kA with a C-curve. Key specifications include a rated operational voltage of 230/400V, rated current of 2A, rated short circuit breaking capacity of 10kA, and dimensions of 70mm depth, 83mm height, and 35mm width. It has a rated operational temperature range of -25°C to 70°C.

Uploaded by

Rushabh Kasrung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

NC202A

MCB 2P 10kA C-2A 2M

Technical properties

Architecture

Number of protected poles 2

Number of poles 2P

Type of pole 2P
NC202A
Curve C

Functions

Concurrently switching N-neutral No

Configuration

Number of modules 2

Connectivity

Top connection alignement for modular


devices Aligned terminal

Bottom connection alignement for modular


devices Aligned terminal

Main electrical features

Rated short circuit breaking capacity Icn AC


according IEC60898-1 10 kA

Rated operational voltage Ue 230 / 400 V

Frequency 50/60 Hz

Voltage

Rated insulation voltage 500 V

Rated impulse withstand voltage 4000 V

Electric current

Rated current 2A

Rated service breaking capacity Ics AC


according IEC 60898-1 7.5 kA

min/maxi threshold value of the AC thermal


operation 1.13 / 1.45 In

Magnetic regulating currrent 5 / 10 In

min/maxi threshold value of the DC


magnetic operation 5 / 15 In

min/maxi threshold value of the DC thermal


operation 1.13 / 1.45 In

Breaking capacity on 1 pole for IT 400V NF


60947-2 3 kA

Rated short circuit breaking capacity Icn


under 400V AC according IEC60898-1 10 kA

Subject to technical modifications


Rated ultimate short-circuit breaking
capacity Icu under 230V AC IEC 60947-2 15 kA

Rated ultimate short-circuit breaking


capacity Icu under 415V AC IEC 60947-2 15 kA

Electric current / temperature

Rating current -25°C 2.3 A

Rating current -20°C 2.3 A

Rating current -15°C 2.2 A

Rating current -10°C 2.2 A

Rating current -5°C 2.2 A

Rating current 0°C 2.2 A

Rating current 5°C 2.1 A

Rating current 10°C 2.1 A

Rating current 15°C 2.1 A

Rating current 20°C 2.1 A

Rating current 25°C 2A

Rating current 30°C 2A

Rating current 35°C 2A

Rating current 40°C 1.9 A

Rating current 45°C 1.9 A

Rating current 50°C 1.9 A

Rating current 55°C 1.9 A

Rating current 60°C 1.8 A

Rating current 65°C 1.8 A

Rating current 70°C 1.8 A

Current correction factors

Correction factor of rating current for 2


devices placed side-by-side 1

Correction factor of rating current for 3


devices placed side-by-side 0.95

Correction factor of rating current for 4 and


5 devices placed side-by-side 0.9

Correction factor of rating current for 6


devices placed side-by-side 0.85

Correction factor of magnetic tripping with


100 Hz 1.1

Correction factor of magnetic tripping with


200 Hz 1.2

Correction factor of magnetic tripping with


400 Hz 1.5

Correction factor of magnetic tripping with


60 Hz 1

Dimensions

Depth of installed product 70 mm

Height of installed product 83 mm

Width of installed product 35 mm

Frequency

Frequency 50 to 60 Hz

Subject to technical modifications


Power

Total power loss under IN 2.8 W

Power loss per pole at In 1.41 W

Endurance

Electric endurance in number of cycles 10000

Number of mechanical operations 20000

Installation, mounting

Type of top connection for modular devices with screw

Tightening torque 2,8Nm

Type of top rail clip for modular devices NA

Type of bottom rail clip for modular devices metallic

Type of Bottom Connection for modular


devices BIconnect

Top removability for modular devices No

Bottom removability for modular devices No

Connection

Connection cross-section of input and


output with screws, for massive conductors 1 / 35 mm²

Connection cross section of access and exit


with screws, for flexible conductor 1 / 25 mm²

Type of connection with screw

Equipment

With transparent product label holder No

Standards

Standard text EN 60898-1

European directive WEEE not concerned

Use conditions

Operating temperature -25…70 °C

Degree of pollution according to IEC 60664 /


IEC 60947-2 2

Class of energy limitation I²t 3

Altitude 2000 m

Air humidity protection for all climates

Storage/transport temperature -25…80 °C