0% found this document useful (0 votes)
102 views130 pages

Manual Ttr310

This document is an instruction manual for the Megger AVTMTTR310 Three-Phase Transformer Turn Ratio Test Set. It contains information about safety, specifications, descriptions of the device and its components, setup and connection instructions for various transformer configurations, operating instructions, and service information. The device is used to test the turn ratios of single-phase and three-phase transformers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
102 views130 pages

Manual Ttr310

This document is an instruction manual for the Megger AVTMTTR310 Three-Phase Transformer Turn Ratio Test Set. It contains information about safety, specifications, descriptions of the device and its components, setup and connection instructions for various transformer configurations, operating instructions, and service information. The device is used to test the turn ratios of single-phase and three-phase transformers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 130

AVTMTTR310

Rev 8
May 2016

Instruction Manual AVTMTTR310

for

Three-Phase TTR
Transformer Turn Ratio Test Set
Catalog No. TTR310, TTR310-47, TTR310E

High-Voltage Equipment
Read the entire manual before operating.

Aparato de Alto Voltaje


Antes de operar este producto lea este manual enteramente.

M
Valley Forge Corporate Center
2621 Van Buren Avenue
Norristown, PA 19403 U.S.A.

610-676-8500

www.megger.com
Three-Phase TTR 310
Transformer Turn Ratio Test Set
Instruction Manual
Copyright Notice
Copyright 1999-2016 by Megger. All rights reserved.

Disclaimer Notice
The information contained in this manual is believed to be adequate for the intended use of the product.
If the product or its individual instrument are used for purposes other than those specified herein,
confirmation of their validity and suitability must be obtained from Megger. Refer to the warranty
information included at the end of this instruction manual. Specifications are subject to change without
notice.

Warranty
Products supplied by Megger are warranted against defects in material and workmanship for a period of
one year following shipment. Our liability is specifically limited to replacing or repairing, at our option,
defective equipment. Equipment returned to the factory must be shipped prepaid and insured. This
warranty does not include batteries, lamps, or other expendable items, where the original manufacturer's
warranty shall apply. We make no other warranty. The warranty is void in the event of abuse (failure to
follow recommended operating procedures) or failure by the customer to perform specific maintenance
as indicated in this manual.
TABLE OF CONTENTS
1 INTRODUCTION .....................................................................................................................................................1
2 SAFETY ....................................................................................................................................................................5
3 SPECIFICATIONS ....................................................................................................................................................9
Input Power .................................................................................................................................................9
Pollution Degree..........................................................................................................................................9
Protective Devices.......................................................................................................................................9
Output Test Voltage and Current .............................................................................................................9
Test Frequency ............................................................................................................................................9
Loading of Test Transformer ................................................................................................................. 10
Measuring Ranges..................................................................................................................................... 10
Accuracy .................................................................................................................................................... 10
Measurement Method .............................................................................................................................. 10
Transformer Winding Phase Relationship............................................................................................ 11
Measuring Time ........................................................................................................................................ 11
Display ....................................................................................................................................................... 11
Memory Storage ....................................................................................................................................... 11
Interface ..................................................................................................................................................... 11
4 DESCRIPTION ...................................................................................................................................................... 15
5 SETUP AND CONNECTIONS............................................................................................................................... 19
Single-Phase, Two-Winding Transformers........................................................................................... 19
Current Transformers (CTs) ................................................................................................................... 25
Unmounted CTs ....................................................................................................................................... 25
Bushing Current Transformer (BCT) Mounted on Single-Phase, Two-Winding Transformer ... 27
BCTs Mounted on Three-Phase Transformers ................................................................................... 28
T-Type Transformers .............................................................................................................................. 31
Connections and Vector Voltage Diagrams ......................................................................................... 32
Notes to Table 5-4 ................................................................................................................................... 35
Notes to Table 5-5 ................................................................................................................................... 47
Notes to Table 5-6 ................................................................................................................................... 58
6 OPERATION......................................................................................................................................................... 67
MAIN MENU Screen (Figure 6-1) ....................................................................................................... 68
QUICK TEST SETUP Screen (Figure 6-2)......................................................................................... 70
Quick Test Result Screens (Figure 6-3 and Figure 6-4) ...................................................................... 71
FULL TEST SETUP 1 Screen (Figure 6-5) ......................................................................................... 73
FULL TEST SETUP 2 Screen (Figure 6-6) ......................................................................................... 75
FULL TEST SETUP 3 Screen (Figure 6-7) ......................................................................................... 77
Transformer Test Result Screens (Figure 6-8 and Figure 6-9).................................................. 79
Main Menu Screen When a Custom Transformer Setting Recalled (Figure 6-10) ......................... 82
SYSTEM SETUP Menu (Figure 6-11) ................................................................................................. 83
LANGUAGE Screen (Figure 6-12) ...................................................................................................... 84
SAVED DATA Screen (Figure 6-13) ................................................................................................... 85
Recall (or Save) Custom Transformer Settings (Figure 6-14) ............................................................ 86
Error Messages ......................................................................................................................................... 87

AVTMTTR310 Rev 8 May 2016 i


M

7 TTR 300 SERIES POWERDB LITE USER MANUAL .........................................................................................91


Operating Instructions for the Multiple Quick Test Form.............................................................. 105
Operating Instructions for the Simple 3PH TTR Form .................................................................. 106
Operating Instructions for the 3PH TTR with TAP Changer Form ............................................. 107
8 SERVICE ............................................................................................................................................................. 109
Voltage Selection .................................................................................................................................... 111
Troubleshooting ..................................................................................................................................... 115
Repair ....................................................................................................................................................... 116
GLOSSARY ............................................................................................................................................................. 117

AVTMTTR310 Rev 8 May 2016


ii
Table of Contents

LIST OF ILLUSTRATIONS

TTR310 Transformer Turn Ratio test set .............................................................................................................1


Figure 4-1. Three-Phase TTR310 Test Set Block Diagram ...................................................................... 16
Figure 4-2. Three-Phase TTR310 Control Panel ....................................................................................... 17
Figure 5-1. Setup for Testing Single-Phase Transformer.......................................................................... 20
Figure 5-2. Setup for Testing Single-Phase Autotransformer .................................................................. 20
Figure 5-3. Setup for Testing Single-Phase, Type A (Straight Design) Step Voltage Regulator ......... 21
Figure 5-4. Setup for Testing Single-Phase, Type B (Inverted Design) Step Voltage Regulator ........ 22
Figure 5-5. Setup for Testing Unmounted Current Transformer............................................................ 26
Figure 5-6. Setup for Testing Taps on Multiple Tap CT .......................................................................... 26
Figure 5-7. Setup for Testing BCT Mounted on Single-Phase Two-Winding Transformer ............... 27
Figure 5-8. Setup for Testing BCT Mounted on Delta Winding on a Three-Phase Power
Transformer................................................................................................................................. 29
Figure 5-9. Setup for Testing BCT Mounted on Wye Winding of a Three-Phase Transformer ........ 30
Figure 5-10. Winding Connections and Phase Relationship ...................................................................... 34
Figure 6-1. Main Menu Screen ...................................................................................................................... 68
Figure 6-2. Quick Test Setup Screen ........................................................................................................... 70
Figure 6-3. Initial Quick Test Result Screen ............................................................................................... 71
Figure 6-4. Final Quick Test Result Screen ................................................................................................ 72
Figure 6-5. FULL TEST SETUP 1 Screen ................................................................................................. 73
Figure 6-6. FULL TEST SETUP 2 Screen ................................................................................................. 75
Figure 6-8. FULL TEST SETUP 3 Screen ................................................................................................. 77
Figure 6-8. Three-Phase Transformer Test Result Screen........................................................................ 79
Figure 6-9. Phase A Test Result Screen ....................................................................................................... 80
Figure 6-10. The Main Menu Screen After Selection of a Custom Transformer Setting ...................... 82
Figure 6-11. SYSTEM SETUP Screen .......................................................................................................... 83
Figure 6-12. Language Screen ......................................................................................................................... 84
Figure 6-13. SAVED DATA Screen .............................................................................................................. 85
Figure 6-14. Recall (or Save) Custom Settings Screen ................................................................................. 86
Figure 6-15a. Sample Test Report Header ........................................................................................................ 89
Figure 6-15b. Sample Single Phase Test Report .............................................................................................. 89
Figure 6-15c. Sample Three-Phase Test Report ............................................................................................... 90

AVTMTTR310 Rev 8 May 2016


iii
M

LIST OF TABLES

Table 5-3. T-type Transformer Winding Phase Relationship ..................................................................31


Table 5-4. ANSI Transformer Winding Phase Relationship ...................................................................37
Table 5-5. CEI/IEC 76-1:1993 Transformer Winding Phase Relationship ..........................................49
Table 5-6. Transformer Winding Phase Relationship (Australian Std. 2374, Part 4 - 1982) ...............60
Table 7-1. Troubleshooting Guide ........................................................................................................... 115

AVTMTTR310 Rev 8 May 2016


iv
PROPRIETARY INFORMATION NOTICE
This document contains information proprietary to Megger. All rights are
reserved.

No part of this document may be reproduced, transmitted, processed or


recorded by any means or form, electronic, mechanical, photographic or
otherwise, nor be released to any third party without the express written consent
of Megger.

Megger Software End User License Agreement


NOTICE TO USER: THIS IS A CONTRACT. BY INSTALLING/USING
THIS PRODUCT YOU ACCEPT ALL TERMS AND CONDITIONS OF
THIS AGREEMENT. If you do not agree with the terms and conditions of this
Agreement, return the software, unused, along with the rest of the package, to
Megger. This package contains software and related explanatory written
materials. The term Software shall also include any upgrades, modified versions,
updates, additions and copies of the Software licensed to you by Megger. Megger
grants you a nonexclusive license to use the Software and Documentation,
provided you agree to the following:

Use of the Software – You may –

Install the software on any computer within your company.

Make one backup copy of the Software.

Copyright – The Software is owned by Megger, and its structure, organization


and code are the valuable trade secrets of Megger. The Software is also protected
by United States Copyright Law and International Treaty provisions. You must
treat the Software just as you would any other copyrighted material, such as a
book. You may not copy the Software or the Documentation, except as set forth
in the Use of the Software section. Any copies that you are permitted to make
pursuant to this Agreement must contain the same copyright and other
proprietary notices that appear on or in the Software. You agree not to modify,
adapt or translate the software. You also agree not to reverse engineer,
decompile, disassemble or otherwise attempt to discover the source code of the
Software.

Transfer – You may not rent, lease, sublicense or lend the Software or
Documentation. You may, however, transfer all of your rights to use the
Software to another person of legal entity provided that you transfer this
Agreement, the Software, including all copies, updates and prior versions, and all
Documentation to such person or entity, and that you retain no copies, including
copies stored on a computer.

AVTMTTR310 Rev 8 May 2016 v


M

Limited Warranty – Megger warrants that the SOFTWARE will perform


substantially in accordance with the accompanying written materials for a period
of one year from date of receipt. Any implied warranties on the SOFTWARE are
limited to one year.

Customer Remedies – Megger and its suppliers’ entire liability and your
exclusive remedy shall be, at Megger option, either (a) return of the price paid, or
(b) repair or replacement of the SOFTWARE that does not meet this Limited
Warranty and which is returned to Megger with proof of purchase. This Limited
Warranty is void if failure of the SOFTWARE has resulted from accident, abuse,
or misapplication. Any replacement SOFTWARE will be warranted for the
remainder of the original warranty period or thirty (30) days, whichever is longer.

No Other Warranties – To the maximum extent permitted by applicable law,


Megger and its suppliers disclaim all other warranties, either express or implied,
including, but not limited to implied warranties of merchantability and fitness for
a particular purpose, with regard to the SOFTWARE, the accompanying written
materials, and any accompanying hardware.

No Liability for Consequential Damages – To the maximum extent


permitted by applicable law, in no event shall Megger or its suppliers be liable for
any damages (including without limitation, special, incidental, consequential, or
indirect damages for personal injury, loss of business profits, business
interruption, loss of business information, or any other pecuniary loss) arising
out of the use of or inability to use this product, even if Megger has been advised
of the possibility of such damages. In any case, Megger and its suppliers’ entire
liability under any provision of this agreement shall be limited to the amount
actually paid by you for the SOFTWARE.

Megger Technical Support

In the event that the PowerDB Lite software appears defective or if you need
assistance in the operation of the PowerDB Lite software, call the MEGGER
SUPPORT DEPT at (610) 676-8500. The Megger Support Dept will determine
the necessary support to correct the problem.

AVTMTTR310 Rev 8 May 2016


vi
Proprietary Information Notice

CUSTOMER FEEDBACK
We listen to our customers very seriously when they express interest in or
suggest new or modified features. Please feel free to call, e-mail, fax, or write
with any comments or suggestions you may have. We can be contacted at the
following:

By Phone: 610-676-8500

By Fax: 610-676-8610

By Website: www.megger.com

By Mail:
Megger
Valley Forge Corporate Center
2621 Van Buren Avenue
Norristown, PA 19403 U.S.A.
IMPORTANT!

Megger periodically provides updates of software. See our web site www.megger.com
to obtain these download updates.

SEE ALL OF OUR PRODUCTS, APPLICATION NOTES, FAQ’s BY


PRODUCT, AND LOCAL REP INFORMATION ON THE WEB AT:
www.megger.com

AUDIENCE
This manual is written for technical personnel who are familiar with the various
measurements performed by a TTR and have a general understanding of their use and
operation. Such personnel should also be thoroughly familiar with the hazards associated
with the use of this equipment and should have received proper safety training.

AVTMTTR310 Rev 8 May 2016


vii
M

MANUAL CONVENTIONS
This manual uses the following conventions:

Bold indicates emphasis or a heading.

Arial Bold denotes the use of a screen button (i.e. click the TTR button).

Ctrl+Enter indicates that to perform the function, press both keys


simultaneously (i.e. Ctrl+Enter indicates that you hold-down the Control (Ctrl)
key while simultaneously striking the Enter key).
NOTE: is used to set off important information from the rest of the text.

A WARNING symbol alerts you to a hazard that may result in


equipment damage, personal injury, or death. Carefully read the
instructions provided and follow all safety precautions.

A CAUTION symbol alerts you that the system may not operate
as expected if instructions are not followed.

AVTMTTR310 Rev 8 May 2016


viii
1
Introduction
Upon Receipt of Product
Check the equipment received against the packing list to ensure that all materials
are present. Notify Megger of any shortage. Telephone 610-676-8500.

Examine the instrument for damage received in transit. If any damage is


discovered, file a claim with the carrier at once and notify Megger or its nearest
authorized sales representative, giving a detailed description of the damage.

This instrument has been thoroughly tested and inspected to meet rigid
specifications before being shipped. It is ready for use when set up as indicated
in this manual.

TTR310 Transformer Turn Ratio test set

AVTMTTR310 Rev 8 May 2016 1


M

General Information
The Three-Phase TTR®310 Test Set is fully automatic, self-checking, self-
calibrating, menu-driven unit. The test set measures the turn ratio, phase shift,
and excitation current of power, distribution, and instrument transformers. A
“-47” suffix added to the catalog number denotes a 230-V, 50 Hz input power
supply, rather than the standard 120-V supply. The test set is a portable
instrument housed in a sturdy plastic case with lid and carrying strap. The inside
bottom half of the case is nickel coated. A canvas carrying bag is supplied to hold
all accessories.

The test set can be used to test single-phase and three-phase transformers, both
with and without taps in accordance with the requirements of the IEEE
C57.12.90 – 2013, IEC 60076-1 and CIGRE TB 445 standards. For three-phase
measurements, the test set is connected to all Three-Phases of the transformer to
be tested. The TTR310 lead selection circuitry permits automatic measurement
of all phases without changing connections. This feature eliminates the need to
refer to hook-up charts when testing three-phase transformers. Turn ratio, phase
shift and excitation current readings are displayed on a large LCD. Transformer
excitation current as well as phase shift angle helps to detect transformer shorted
turns or an unequal number of turns connected in parallel. Operating condition
(error) messages identify incorrect test connections, abnormal operating
condition, or winding problems. Test results can be saved, printed out on an
optional printer, or uploaded to a personal computer (PC).

Features include:
ƒ Fully automatic operation.
ƒ Self-checking at power-up.
ƒ Self-calibration at each measurement.
ƒ User-friendly, menu-driven operation.
ƒ Test turn ratio, phase shift (in both degree and centiradian), and excitation
current.
ƒ Easy measuring of regular windings, tertiary windings, and CTs.
ƒ Storage capacity for up to 200 tests for retrieving, printing out, or uploading
to a PC.
ƒ Saving up to 9 custom transformer settings for faster and easier testing.
ƒ Checking reverse polarity at start of each test.
ƒ External printer records test data.
ƒ External PC or laptop can be connected instead of a printer to transfer test
results and to provide full transformer test report.
ƒ Quick test mode provides the fastest testing of a transformer.

AVTMTTR310 Rev 8 May 2016


2
M

ƒ Three excitation test voltages: 80 V, 40 V, and 8 V.


ƒ Testing to ANSI, IEC, and Australian standards.
ƒ Leads marked to ANSI, IEC, and Australian standards.
ƒ Choice of six languages.
ƒ Large, easy-to-read LCD shows alphanumeric data
ƒ Meets the requirements of both the European EMC and Low Voltage
Directives.
ƒ Trouble-free operation in switchyards under electrostatic and magnetic
interference conditions.

AVTMTTR310 Rev 8 May 2016


3
M

AVTMTTR310 Rev 8 May 2016


4
2
Safety
The test set and the specimen to which it is connected are a possible source of
high-voltage electrical energy and all persons making or assisting in tests must
use all practical safety precautions to prevent contact with energized parts of the
test equipment and related circuits. Persons actually engaged in the test must
stand clear of all parts of the complete high-voltage circuit, including all
connections, unless the test set is de-energized and all parts of the test circuit are
grounded. Persons not directly involved with the work must be kept away from
test activities by suitable barriers, barricades, or warnings.

Treat all terminals of high-voltage power equipment as a potential electric shock


hazard. There is always the possibility of voltages being induced at these
terminals because of proximity to energized high-voltage lines or equipment.
Always disconnect test leads from power equipment before attempting to
disconnect them at the test set. The ground connection must be the first made
and the last removed. Any interruption of the grounding connection can create
an electric shock hazard.

This instrument operates from a single-phase power source. It has a three-wire


power cord and requires a two-pole, three-terminal, live, neutral, and ground type
connector. The voltage to ground from the live pole of the power source must
be within the following rated operating voltage:

For Cat. No. TTR310/ TTR310E 120 V 10%, single phase, 60 2 Hz

For Cat. No. TTR310-47/ TTR310E-47 230 V 10%, single phase, 50 2 Hz

The neutral pole must be at ground potential. Before making connection to the
power source, determine that the instrument rating matches the voltage of the
power source and has a suitable two-pole, three-terminal grounding type
connector.

The power input plug must be inserted only into a mating receptacle with a
ground contact. Do not bypass the grounding connection. Any interruption of
the grounding connection can create an electric shock hazard. Determine that the
receptacle is properly wired before inserting the plug.

For test sets energized with 230 V input, the neutral terminal of the input supply
cord (white or blue lead) must be connected to the neutral pole of the line power
source. The ground terminal of the input supply cord (green or yellow/green

AVTMTTR310 Rev 8 May 2016 5


M

lead) must be connected to the protective ground (earth) terminal of the line
power source. The black or brown cord lead is the live (hot) lead.

To avoid electric shock hazard, operating personnel must not remove the
instrument from the case. Any repair or component replacement must be
performed by qualified service personnel.

The control circuits of the instrument are protected by two mains circuit fuses.
These fuses are replaceable by the operator. To avoid electric shock and fire
hazard, use only the fuse specified in Section 3, Specifications, that is identical in
respect to type, voltage rating and current rating. Refer to the Fuse Replacement
procedure in the Service section.

WARNING
Before replacing the fuses, disconnect the power input plug from
the live power source.

Megger has made formal safety reviews of the initial design and any subsequent
changes. This procedure is followed for all new products and covers areas in
addition to those included in applicable standards. Regardless of these efforts, it
is not possible to eliminate all hazards from electrical test equipment. For this
reason, every effort has been made to point out in this instruction manual the
proper procedures and precautions to be followed by the user in operating this
equipment and to mark the equipment itself with precautionary warnings where
appropriate. It is not possible to foresee every hazard which may occur in the
various applications of this equipment. It is therefore essential that the user, in
addition to following the safety rules in this manual, also carefully consider all
safety aspects of the test before proceeding.
ƒ Safety is the responsibility of the user.
ƒ Follow your company’s safety procedures.
ƒ Misuse of this high-voltage equipment can be extremely dangerous.
ƒ The purpose of this equipment is limited to use as described in this manual.
Do not use the equipment or its accessories with any device other than
specifically described.
ƒ Never connect the test set to energized equipment.
ƒ Do not use the test set in an explosive atmosphere.
ƒ Corrective maintenance must only be performed by qualified personnel who
are familiar with the construction and operation of the test set and the
hazards involved.
ƒ Refer to IEEE 510 - 1983, IEEE Recommended Practices for Safety in High-
Voltage and High-Power Testing, for additional information.

AVTMTTR310 Rev 8 May 2016


6
SAFETY

If the test equipment is operated properly and all grounds correctly made, test
personnel need not wear rubber gloves. As a routine safety procedure, however,
some users require that rubber gloves be worn, not only when making
connections to the high-voltage terminals, but also when manipulating the
controls. Megger considers this an excellent safety practice.

Users of equipment should note that high-voltage discharges and other sources
of strong electric or magnetic field may interfere with the proper functioning of
heart pacemakers. Persons with heart pacemakers should obtain expert advice on
the possible risks before operating this equipment or being close to the
equipment during operation.

F
WARNING

No user serviceable parts inside!


Refer all servicing to the factory or a qualified
authorized service company!

G
CAUTION

Use only factory supplied mains cord!


Mains cord shall not be substituted!

AVTMTTR310 Rev 8 May 2016


7
M

AVTMTTR310 Rev 8 May 2016


8
3
Specifications
Electrical
Input Power
Cat. No. TTR310/TTR310E: 120 V ac ±10%, single phase, 60 ±2 Hz, 100 VA
IEC 1010-1 installation category II

Cat. No. TTR310-47/ TTR310E-47: 230 V ac ±10%, single phase, 50 ±2 Hz, 100 VA
IEC 1010-1 installation category II

Pollution Degree
TTR310 is designed for Pollution Degree II

Protective Devices
Fuses (2)*:

Cat. No. T TTR310/TTR310E:: Type T, 250 V, 1A (IEC 127 designation)

Cat. No. TTR310-47/ TTR310E-47:: Type T, 250 V, 0.5 A (IEC 127 designation)

High voltage and low voltage measurement circuit shorting relays


Heavy duty varistors and transient voltage suppressors
* Two spare fuses are included with each TTR310 as spare parts

Output Test Voltage and Current

3 test voltages: 80 V rms, 40 V rms, 8 V rms.

Current: up to 500 mA

Test Frequency
Same as line frequency.

AVTMTTR310 Rev 8 May 2016 9


M

Loading of Test Transformer


Less than 0.2 VA

Measuring Ranges

Turn ratio: 80 V ac: 0.8 to 45,000, 5 digit resolution


40 V ac: 0.8 to 25,000, 5 digit resolution
8V ac: 0.8 to 8,000, 5 digit resolution

Excitation Current: 0 to 500 mA, 3 digit resolution (±2% of reading +1 digit)

Phase Angle ± 90 degrees, 1 decimal point for the minutes display, 2


Deviation: decimal points for the degree display
Accuracy: ±0.05 degrees
Limit of Ratio: (0.8:1 to 2000:1)

Accuracy
Turn ratio:

80 V ac: ±0.1% (0.8 to 2000)


±0.15% (2001 to 4000)
±0.25% (4001 to 10000)
±0.3% (10001 to 45000)

40 V ac: ±0.1% (0.8 to 2000)


±0.15% (2001 to 4000)
±0.3% (4001 to 10000)
±0.35% (10001 to 25000)

8 V ac: ±0.1% (0.8 to 2000)


±0.25% (2001 to 4000)
±0.35% (4001 to 8000)

Excitation Current (rms): ±(2% of reading + 1 digit)

Phase Angle Deviation: ±3 minutes


(limit of ratio) (0.8:1 to 2000:1)

Measurement Method
In accordance with ANSI/IEEE C57.12.90 -2013

AVTMTTR310 Rev 8 May 2016


10
SPECIFICATIONS

Transformer Winding Phase Relationship


ANSI C57.12.70-2011

CEI/IEC 76-1:2011

AS-2374, Part 4 2003 (Australian Standard)

Measuring Time
8 to 20 seconds depending on mode of operation and type of transformer

Display
5.7 Inch, color display, text on-screen view, numeric keypad

Memory Storage
Up to 200 data sets of complete 3 phase results

Up to 9 custom transformer settings


Interface
RS-232C: PC control, data download and printer output
USB 2.0 Host: Data download to memory stick
Ethernet: PC Control and data download

Environmental Conditions
Operating temperature range: 23 to 122 F (-5 to 50 C)
Storage temperature range: -22 to 140 F (-30 to 60 C)
Relative humidity: 0 to 90% noncondensing (operating)
0 to 95% noncondensing (storage)

AVTMTTR310 Rev 8 May 2016


11
M

Physical Data
Dimensions:
Instrument: 8.5 H x 21.5 W x 13 D in (216H x 546.1 W x 330.2 D
mm)
Case:
25 H x 19 W x 26 D in. (635 H x 483 W x 660 D
mm)
Weight (test set):
Instrument with standard 25 lbs (11.3 kg)
provided accessories
Instrument with Optional Leads 47 lbs (21.3 kg)
30 ft (9.1 m)
Instrument with Standard 62 lbs (28.1 kg)
accessories and Transit Case
Instrument with Optional Leads 84 lbs (38.1 kg)
and Transit Case

Transit Case: Black ABS case with lid


37 lb (16.7 kg)

Accessories Supplied
Item (Qty) Cat. No.

Three-Phase TTR®310 Test Set, fully automatic, self-


checking, self-calibrating, menu-driven unit

120 V ac ±10%, single phase, 60 ±2 Hz, 100 VA TTR310/TTR310E


IEC 1010-1 installation category II

230 V ac ±10%, single phase, 50 ±2 Hz, 100 VA TTR310-47/TTR310E-47


IEC 1010-1 installation category II

Included Accessories

Canvas carrying bag for test leads 2005-265

Power supply cord, 8 ft (2.5 m) (120 version units) 17032-4

Power Supply cord, 8 ft (2.5 m) (230 version units) 17032-13

Ground lead, 15 ft (4.6 m) 4702-7

AVTMTTR310 Rev 8 May 2016


12
SPECIFICATIONS

Item (Qty) Cat. No.

Ethernet cable for connecting to a PC 36798 (TTR310E only)

RS-232C serial cable for connecting to a PC CA-RS232

Hand-held TEST switch assembly for remote 30915-220 (TTR310 only)


operation

Transformer Vector Voltage Diagrams


ANSI Standards 35298
IEC Standards 35299
AS (Australian) Standards 35300

PowerDB LITE Software DB0001

Instruction Manual TTR310_UG (from website)


AVTMTTR310 (paper)

1:1 test jig (instrument self test) 2005-249

Replacement Parts List and Optional Accessories


Item (Qty) Cat. No.

3-ø Universal shielded test lead set compatible with MTO3XX,


MWA3XX and TTR3XX series of instruments (up to 10A max),
complete with color coded Kelvin clamps:

3-ø Universal 30 ft (9 m), H and X, Lead Set 2008-30-KIT

3-ø Universal 60 ft (18 m), H and X, Lead Set 2008-60-KIT

3-ø Universal 100 ft (30 m), H and X, Lead Set 2008-100-KIT

3-ø Universal 30 ft (9 m), H Lead Set 2008-113-30

3-ø Universal 30 ft (9 m), X Lead Set 2008-114-30

3-ø Universal 60 ft (18 m), H Lead Set 2008-113-60

3-ø Universal 60 ft (18 m), X Lead Set 2008-114-60

3-ø Universal 100 ft (30 m), H Lead Set 2008-113-100

3-ø Universal 100 ft (30 m), X Lead Set 2008-114-100

AVTMTTR310 Rev 8 May 2016


13
M

Item (Qty) Cat. No.

3-ø Universal 33 ft (10 m), X Extension Lead Set 36486-7

3-ø Universal 33 ft (10 m), H Extension Lead Set 36486-8

3-ø Universal 33 ft (10 m), H and X Extension Lead Set 36486-9

Replacement/spare battery pack for printer 37077

Bushing Clips (each) MC7144

TTR Check Box 550555

TTR Calibration Standard Y550055

Transit case for instrument, leads and accessories 2005-340

Printer (includes battery/line powered serial thermal printer,


printer interface cable)

120 V, 60 Hz 1001-390

230 V, 50 Hz 1001-401

Optional Replacement Lead Sets for older style TTR C/N


550503

3-ø 'H' lead, 30 ft (9.1m) with old style H connector 2008-115-30

3-ø 'X' lead, 30 ft (9.1m) with old style X connector 2008-116-30

AVTMTTR310 Rev 8 May 2016


14
4
Description
Principle of Operation
The TTR310 test set provides accurate measurements of transformer input and
output voltages and the, calculates a transformer turn ratio. The TTR310 also
measures phase shift between primary and secondary windings of a transformer
and transformer excitation current.

A block diagram of the TTR310 test set is shown in Figure 4-1. The excitation
voltage transformer converts the main voltage into the test excitation voltage of a
transformer. The excitation voltage transformer outputs three test voltages: 80 V,
40 V, and 8 V. The transformer under test excitation current is measured by the
excitation current measurement circuitry. The test excitation voltage is applied to
a transformer under test through the H winding lead select circuitry. This
circuitry automatically excites the transformer windings depending on winding
connections. The same excitation voltage is applied to the reference conditioning
circuitry.

The transformer under test output voltage is connected to the X winding lead
select circuitry. This circuitry automatically connects the transformer winding
being tested to the range conditioning circuitry.

AVTMTTR310 Rev 8 May 2016 15


M

Figure 4-1. Three-Phase TTR310 Test Set Block Diagram

The range and reference conditioning circuitries isolate a transformer under test
from the TTR310 measurement circuitry and provide conditioning of the input
and output measurement signals. The programmable gain amplifier is used for
additional conditioning of the transformer output signals.

Both the reference A/D converter and the range A/D converter are used to
convert the analog measurement signals to their digital replica. The converted
output digital signals are applied to the microprocessor.

The microprocessor orchestrates all steps of the TTR310 test set operation. It
provides proper sequence of operation, gathers and calculates the test results,
provides interfacing with the display, RS232/printer port, and the control
circuitry. The control circuitry interfaces with virtually all function blocks
described, providing proper control sequence of the TTR310 test set operation.

AVTMTTR310 Rev 8 May 2016


16
DESCRIPTION

Controls, Indicators, and Connectors


TEST VOLTAGE Red indicator lamp indicates when lit that test voltage is being
ON supplied to a transformer.

EMERGENCY This red push button interrupts testing. When pressed, the
TEST OFF switch is locked in off position. To reset the switch, twist the
button in the direction indicated by the arrows.

DISPLAY Color LCD shows menus and test information.


SCREEN

KEYPAD 16-button keypad for entering menu selections and navigating


through the various screens. In addition to numbered keys
1 through 9, plus 0, there is a CLR (clear) button, R (raise or
right) button, L (lower or left) button, an ENT (enter) button,
a decimal point button, and an * (asterisk) button. An audible
tone confirms that you have successfully pressed a button.

Figure 4-2. Three-Phase TTR310 Control Panel

GROUND Wing-nut terminal allows connection of test set to earth


ground.

CABLE H Plug receptacle for connecting test leads to the high-voltage


(H) winding of a transformer

AVTMTTR310 Rev 8 May 2016


17
M

CABLE X Plug receptacle for connecting test leads to the low-voltage


(X) winding of a transformer.

AC POWER On/off power switch and input power receptacle provides


120 V 50/60 Hz power to the test set.
100 VA MAX

FUSE IEC 127 T 1 Fuse receptacle and rating.


A/250 V

RS232/PRINTER Plug receptacle for connecting a printer or connecting to a


PC.

ETHERNET PORT Port for PC communication and data download


(TTR310E)

AVTMTTR310 Rev 8 May 2016


18
5
Setup and Connections
General Instructions
When testing high-voltage transformers, caution must be used at all times and all
safety precautions followed. Read and understand all safety information
contained in Section 2, Safety.

WARNING
Ensure that the transformer to be tested is completely de-
energized. Check every winding. Ensure that all terminals of the
transformer are disconnected from line or load at the transformer.
Connections to ground may be left in place.

The following setup and connection instructions pertaining to ratio, polarity, and
phase relation assume that the transformer under test, connections, and terminal
markings comply with the requirements of ANSI C57.12.70-2011 American
National Standards Terminal Markings and Connections for Distribution and Power
Transformers. The H test leads of the test set are the exciting (high voltage) leads
(8 V, 40 V, or 80 V).

Single-Phase, Two-Winding Transformers

WARNING
Never interchange connections between the high- and low-
voltage transformer terminals. Failure to observe proper
connections will result in a safety hazard and may result in
damage to the test set or transformer.

Perform the following setup procedure for single-phase, two-winding


transformers:
1. Connect the wing-nut ground terminal of the test set to a low-impedance
earth ground using the 15-ft (4.6 m) ground lead supplied.
2. Connect the H and X test cables to the respective H and X receptacles of the
test set. Make sure that the connectors are screwed tight to the receptacles.
3. Connect the heavy-duty clips marked H1 and H2 of the test lead to the
corresponding (high-voltage winding) terminals of the transformer under
test.

AVTMTTR310 Rev 8 May 2016 19


M

4. Connect the heavy-duty clips marked X1 and X2 of the test lead to the
corresponding (low-voltage winding) terminals of the transformer under test.
Figures 5-1 and 5-2 show test setups for single-phase transformers. Figures
5-3 and 5-4 show test setups for regulators.
NOTE: When using a three-phase cable set, connect heavy-duty clips marked
H1, H2 and X1, X2 to the corresponding terminals of the transformer under
test. The unused clips should be kept clear of ground and personnel.

Figure 5-1. Setup for Testing Single-Phase Transformer

Figure 5-2. Setup for Testing Single-Phase Autotransformer

To test windings other than H1 – H2 and X1 – X2, ensure that the heavy-duty
clip marked H1 is connected to the lower numbered terminal and H2 to the
higher numbered terminal of the high-voltage winding. Similarly, X1 and X2
should be connected to the low-voltage winding. Test lead markings for the
ANSI, CEI/IEC, and Australian standards are as shown in Table 5-1.

AVTMTTR310 Rev 8 May 2016


20
SETUP AND CONNECTIONS

Table 5-1. Test Lead Markings for Single-Phase Transformers

Test Lead Marking Transformer Heavy-Duty Test Lead


Clip

ANSI CEI/IEC Australian Terminal Boot Color Color


Voltage Band

H1 1U A2 High Red Red

H2 1V A1 High Red Yellow

X1 2U a2 Low Black Red

X2 2V a1 Low Black Yellow

Figure 5-3. Setup for Testing Single-Phase, Type A (Straight Design) Step Voltage Regulator

AVTMTTR310 Rev 8 May 2016


21
M

Figure 5-4. Setup for Testing Single-Phase, Type B (Inverted Design) Step Voltage Regulator

Three-Phase, Two-Winding Transformers


Perform the following setup procedure for three-phase, two-winding
transformers:
1. Connect the wing-nut ground terminal of the test set to a low-impedance
earth ground using the 15 ft (4.6 m) ground lead supplied.
2. Connect the three-phase test cables to the respective H and X receptacles of
the test set. Make sure that the connectors are screwed tight to the
receptacles.
3. Connect the heavy-duty clips marked H0, H1, H2, and H3 of the test lead to
the corresponding (high-voltage winding) terminals of the transformer under
test.
4. Connect the heavy-duty clips marked X0, X1, X2 , and X3 of the test lead to
the corresponding (low-voltage winding) terminals of the transformer under
test.

WARNING
Never interchange connections between the high- and low-
voltage transformer terminals. Failure to observe proper
connections will result in a safety hazard and may result in
damage to the test set or transformer.

AVTMTTR310 Rev 8 May 2016


22
SETUP AND CONNECTIONS

The unused H0 and X0 terminals should be kept clear of ground and personnel
because they could become energized during the test. Refer to Table 5-2 for test
lead markings.

With delta connected windings, H0 or X0 is not used. With wye connected


windings, a neutral connection is normally available.

Table 5-2. Test Lead Markings for Three-Phase Transformers

Test Lead Marking Transformer Heavy-Duty Clip Test Lead

ANSI CEI/IEC Australian Terminal Boot Color Color Band


Voltage

H0 1N N Neutral Red White

H1 1U A2/A4 High Red Red

H2 1V B2/B4 High Red Yellow

H3 1W C2/C4 High Red Blue

X0 2N N Neutral Black White

X1 2U a1/a2/a4 Low Black Red

X2 2V b1/b2/b4 Low Black Yellow

X3 2W c1/c2/c4 Low Black Blue

Note: According to Australian standard, wye and delta transformer winding


connections have a numerical suffix of 1 and 2. The zigzag transformers have a
numerical suffix of 4. See Table 5-6.

AVTMTTR310 Rev 8 May 2016


23
M

Three-Phase, Three-Winding Transformers


This type of transformers has primary, secondary and tertiary windings. Primary
and secondary windings are tested as a regular three-phase, two-winding
transformer. To test tertiary winding, perform the following setup procedure:
1. Connect the wing-nut ground terminal of the test set to a low-impedance
earth ground using the 15 ft (4.6 m) ground lead supplied.
2. Connect the three-phase test cables to the respective H and X receptacles of
the test set. Make sure that the connectors are screwed tight to the
receptacles.
3. Connect the heavy-duty clips marked H0, H1, H2, and H3 of the test lead to
the corresponding (high-voltage winding) terminals of the transformer under
test.
4. Connect the heavy-duty clips marked X0, X1, X2 , and X3 of the test lead to
the corresponding tertiary (low-voltage winding) terminals (Y0, Y1, Y2, and
Y3) of the transformer under test.

WARNING
Never interchange connections between the high- and low-
voltage transformer terminals. Failure to observe proper
connections will result in a safety hazard and may result in
damage to the test set or transformer.

The unused H0 and X0 terminals should be kept clear of ground and personnel
because they could become energized during the test. Refer to Table 5-2 for test
lead markings.

With delta connected windings, H0 or X0 is not used. With wye connected


windings, a neutral connection is normally available.

AVTMTTR310 Rev 8 May 2016


24
SETUP AND CONNECTIONS

Current Transformers (CTs)


Connections to CTs are made backwards compared to power or potential
transformers. The H terminals on the test set must be connected to the X
terminals on the CT; and the X terminals on the test set must be connected to
the H terminals on the CT.
NOTE: Dots on the housing of the transformer are commonly used to identify
terminals of the same polarity.

WARNING
Failure to observe proper connections will result in a safety
hazard and may result in damage to the test set or CT. Failure to
observe voltage rating of low-current X winding may result in
damage to the CT.

CAUTION
Never use AUTO mode of operation when testing the current
transformers with the rated voltage below 80 V ac.

Most of the CTs are tested at 8 V ac excitation voltage.

NOTE: Most of the current transformers are tested at 8 V ac excitation


voltage. Some current transformers with turn ratio of 100:5 and less get
saturated at 8V ac. They require lower excitation voltage for testing and
therefore can not be tested with the Cat. No TTR310. Use the TTR100 or
TTR25.

Unmounted CTs
1. Connect the wing-nut ground terminal of the test set to a low-impedance
earth ground using the 15-ft (4.6 m) ground cable supplied.
2. Use the TTR310 H and X test leads and connect as follows and as shown in
Figure 5-5.
3. Connect the heavy-duty clips marked H1 and H2 of the test lead to the
respective X1 and X2 terminals of the CT.
4. Connect the heavy-duty clips marked X1 and X2 of the test lead to the
respective H1 and H2 terminals of the CT. Ensure correct polarity.

AVTMTTR310 Rev 8 May 2016


25
M

Figure 5-5. Setup for Testing Unmounted Current Transformer


Figure 5-6 shows the setup for testing the taps on a multiple-tap CT.

Figure 5-6. Setup for Testing Taps on Multiple Tap CT

AVTMTTR310 Rev 8 May 2016


26
SETUP AND CONNECTIONS

Bushing Current Transformer (BCT) Mounted on Single-Phase,


Two-Winding Transformer
A turn-ratio test can be performed on a BCT after it has been mounted on a
circuit breaker or power transformer entrance bushing. The test can be
performed without removal of the BCT from the equipment. Proceed as follows
and as shown in Figure 5-7.
1. Connect the wing-nut ground terminal of the test set to a low-impedance
earth ground using the 15-ft (4.6 m) ground cable supplied.
2. Use the TTR310 two or four conductor H and X test leads.
3. Short-circuit the winding on the opposite voltage side of the power
transformer core, using jumper leads.
4. Connect the heavy-duty clips marked H1 and H2 of the test leads to the
respective X1 and X2 terminals of the BCT.
5. Connect the heavy-duty clip marked X1 to the power transformer terminal
on which the BCT is mounted and the X2 heavy-duty clip to the terminal on
the opposite side of the power transformer winding (H2 side of BCT). Check
to make sure that the BCT is mounted with proper polarity with respect to
power transformer entrance bushing and that connection polarities are
correct.

Figure 5-7. Setup for Testing BCT Mounted on Single-Phase Two-Winding Transformer

AVTMTTR310 Rev 8 May 2016


27
M

BCTs Mounted on Three-Phase Transformers


A turn-ratio test can be performed on all three BCTs using a single setup. Figure
5-8 shows how to make the proper connections when the BCTs are mounted on
a typical delta winding and Figure 5-9 when mounted on a typical wye winding.
1. Use four conductor H and X test leads.
2. Short-circuit all windings on the opposite voltage side of the power
transformer core using jumper leads.
3. Check to make sure that all BCTs are mounted with proper polarity with
respect to the power transformer entrance bushing. Ensure that all
connection polarities are correct.

AVTMTTR310 Rev 8 May 2016


28
SETUP AND CONNECTIONS

Figure 5-8. Setup for Testing BCT Mounted on Delta Winding on a Three-Phase Power Transformer

AVTMTTR310 Rev 8 May 2016


29
M

Figure 5-9. Setup for Testing BCT Mounted on Wye Winding of a Three-Phase Transformer

AVTMTTR310 Rev 8 May 2016


30
SETUP AND CONNECTIONS

T-Type Transformers
T-type transformers represent the special type of thee-phase transformers. This
transformer may be tested as a single phase transformer. In this case, the jumpers
indicated in Table 5-3 should be applied to the appropriate terminals of the T-
type transformers. The TTR310 measured turn ratio should be compared to the
calculated turn ratio indicated in Table 5-3.
Table 5-3. T-type Transformer Winding Phase Relationship
Winding Connection Winding Tested
IEC External Phase High- Low-
Vector High-Voltage Low-Voltage jumpers tested Voltage Voltage Calculated
Group Winding (H) Winding (X) Winding Winding Turn Ratio Remarks

VH
- A H1 - H 2 X 1 - X2 VX
T-T
0 H1 -H2 VH
X1 -X2 B H1 – H3 X1 – X3 VX

VH 3
H2 -H3 A H1 – H3 X 1 - X2 v
VX 2
T-T
30 VH 2
lag B H2 – H3 X 1 – X3
VX 3
X1 -X2

VH 3
H2 -H3 A H1 – H3 X1 – X3 v
VX 2
T-T
30 VH 2
lead X1 –X3 B H2 – H3 X2 – X1
VX 3

NOTE: When testing T-type transformer, the diagram number 1 should be


entered at the Quick Test Setup screen (See Figure 6-3) or at the Full Test
Setup 1 screen (See Figure 6-6).

AVTMTTR310 Rev 8 May 2016


31
M

Connections and Vector Voltage Diagrams


When testing three-phase transformers, it is necessary to understand the phase
relationships, vector diagrams, and winding connection diagrams for these
transformers. A detailed description of phase relationships, vector diagrams, and
terminal markings is contained in specification ANSI C57.12.70 – 2011 American
National Standard Terminal Markings and Connections for Distribution and Power
Transformers.

Refer to specification CEI/IEC 76-1:2011 and Publication 616:1978 for


International Standard terminal and tapping markings for power transformers.
Refer to specification AS-2374, Part 4-2003 for Australian standard tappings and
connections for power transformers.

Table 5-4 shows winding diagrams for standard transformers and nonstandard
transformers for power and distribution transformers marked in accordance with
the ANSI standard. Table 5-5 shows winding diagrams for power transformers
marked in accordance with the CEI/IEC standard, and Table 5-6 shows winding
diagrams for power transformers marked in accordance with the Australian
standard.

To make a measurement on a three-phase power transformer, match the vector


diagram from the transformer nameplate to the corresponding winding
connection diagram from Table 5-4 through 5-6, then enter the corresponding
diagram number (column 1 of table) in the appropriate setup menu of the
instrument.

The tables show the windings tested for each of the three-phases. The tables also
show the relationship between the measured turn ratio and the actual line-to-line
voltage ratio. For the ANSI specification, the rated voltage on the high-voltage
winding is represented by VH; VX represents rated voltage on the low-voltage
winding.

The TTR310 is also capable of measuring the turn ratio on three-phase


transformers with an inaccessible neutral point. In this case, the TTR310
automatically shorts an appropriate transformer winding, listed in the winding
shorted column of the table. An inaccessible neutral point on the high-voltage or
low-voltage transformer winding is designated by the symbol *.

For many utilities, different manufacturer nameplate diagrams make it impossible


to always find a corresponding diagram on Tables 5-4 to 5-6. To help determine
the correct connection and to test any transformer, the following explanation will
help self-check your work.

Figure 5-10 (a) shows the relationship in a typical delta-wye connected


transformer with accessible neutral connection point. The delta winding is the
high-voltage winding and the terminals are marked H1, H2, and H3. The wye
winding is the low-voltage winding and the terminals are marked X0, X1, X2, and

AVTMTTR310 Rev 8 May 2016


32
SETUP AND CONNECTIONS

X3. Determine which windings (lines) are parallel to each other. In the diagram,
winding H1 – H3 is parallel to X1 – X0 as illustrated by the two solid straight
arrows. Only H1 – H3 will ratio against X1 – X0. Also H2 – H1 is parallel to X2 –
X0, and H3 – H2 is parallel to X3 – X0. All ratio measurements are made between
parallel windings. The phase polarity must also be observed and is designated by
the order of terminal mention, i.e., H1 - H3 is of the same phase polarity as X1 –
X 0.

Note that the phase displacement for Figure 5-10 (a) diagram is 30 and has an
IEC vector group coding of Dyn1. Refer to the notes to Tables 5-4 through 5-6
for an explanation of vector group coding. For phase displacement between
windings the vector relating to the HV winding is taken as the vector of origin
(dotted line on delta winding, H1 on wye winding). The vector relating to the
low-voltage wye winding is taken as X1 (dotted line on a delta winding) and is
expressed in counterclockwise rotation of low-voltage winding in 30 clock-hour
figure increments. The low-voltage winding lag may be from 0 to 330 in steps of
30 .

The TTR310 test set is capable of measuring the turn ratio of three-phase
transformers where the windings are rotated or are connected in various phase
displacements from standard. Figure 5-10 (b) vector diagram is an example of a
typical case where the phase is displaced 150 from that of Figure 5-10 (a)
diagram. Vector group coding for this diagram is Dyn5.

Figure 5-10 (c) is an example of a nameplate vector diagram drawn differently


from that of Figure 5-5 (a). Although a corresponding figure cannot be found in
Table 5-4, the transformer and its testing is identical to that for Figure 5-10 (a).

Figure 5-10 (d) vector diagram is an example of a typical wye-delta connected


transformer winding which has a phase displacement of 210 . H1 is the high-
voltage winding vector of origin and the dotted line on the delta winding is the
low-voltage winding reference. Vector group coding for this diagram is YNd7.

AVTMTTR310 Rev 8 May 2016


33
M

IEC VECTOR GROUP CODING


Dyn1
PHASE DISPLACEMENT
30 LAG

(a)

IEC VECTOR GROUP CODING


Dyn5
PHASE DISPLACEMENT
150 LAG

(b)

IEC VECTOR GROUP CODING


Dyn1
PHASE DISPLACEMENT
30 LAG

(c)

IEC VECTOR GROUP CODING


YNd7
PHASE DISPLACEMENT
210 LAG

(d)
Figure 5-10. Winding Connections and Phase Relationship

AVTMTTR310 Rev 8 May 2016


34
SETUP AND CONNECTIONS

Notes to Table 5-4


Transformer terminal markings for distribution and power transformers marked
in accordance with requirements of American National Standard Institute, Inc
(ANSI) standard C57.12.70 – 2011.

Definition of Symbol Designations

H1, H2, H3 External terminals on HV transformer winding.

X1, X2, X3 External terminals on LV transformer winding.

H0 External neutral terminal on HV transformer winding.

X0 External neutral terminal on LV transformer winding.

* Inaccessible neutral point on HV or LV transformer winding.

VH Nameplate voltage rating (line-to-line) of HV transformer winding.

VX Nameplate voltage rating (line-to-line) of LV transformer winding.

A, B, C Winding tested on HV side of transformer.

a, b, c Winding tested on LV side of transformer.

IEC Vector Group Coding

The letters indicate the three-phase winding connections; D, Y, and Z designate


the HV side winding; d, y, and z designate the LV side winding. D and d
represent a delta connection, Y and y represent a wye connection, and Z and z
represent a zigzag connection. N and n indicate that the neutral point of a star or
zigzag connected winding is accessible on the respective HV or LV side winding.
The number indicates the phase displacement (lag) of the LV winding with
respect to the HV winding in units of 30º.

For example, 0 = 0º lag, 1 = 30º lag, 2 = 60º lag, 6 = 180º lag, 11 = 330º lag.

AVTMTTR310 Rev 8 May 2016


35
M

Additional Transformer Winding Identification

External terminal markings for three-phase power transformers with more than
two windings are as follows:

Y1, Y2, Y3 Third winding (if any).

Z1, Z2, Z3 Fourth winding (if any).

If unable to find a corresponding diagram for a transformer with, for example,


accessible neutral winding but can find the corresponding diagram for the same
transformer with no neutral accessible winding, follow the test procedure for the
transformer with no neutral accessible winding. In this case, specify the diagram
number for the transformer with no neutral accessible winding and do not
connect H0 or X0 lead to the neutral. Note that on the print out of the results,
the vector designation and the corresponding diagram will not be EXACT, but
will be close to the actual transformer configuration.

As an example, if transformer winding connection is identical to Table 5-4


Diagram No. 26 except the wye winding has an accessible neutral winding,
perform test per Diagram 26. Do not connect H0 lead to the wye winding
neutral terminal. The test results are identical and do not require any corrections.
Note that on the print out of the results, the vector designation and the
corresponding diagram will not be EXACT, but will be close to the actual
transformer configuration.

AVTMTTR310 Rev 8 May 2016


36
SETUP AND CONNECTIONS

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks

1 VH Single-phase
1 1ph0 1 H1 - H2 X1 - X2 VX transformer

1 VH Single-phase
2 1ph6 1 H1 - H2 X 2 - X1 VX transformer

A H1 - H3 X1 - X3 VH
3 Dd0 B H2 - H1 X2 - X1 VX
C H3 - H2 X3 - X2

A H1 - H3 X3 - X1 VH
4 Dd6 B H2 - H1 X1 - X2 VX
C H3 - H2 X2 - X3

Neutral
5 Dyn1 A H1 - H3 X1 - X0 accessible
VH v 3
B H2 - H1 X2 - X0 on wye
C H3 - H2 X3 - X0 VX winding

A H1 - H3 X0 - X1 Neutral
VH v 3
6 Dyn7 B H2 - H1 X0 - X2 accessible
C H3 - H2 X0 - X3 VX on wye
winding

A H1 - H0 X1 - X0 VH Neutral
7 YNyn0 B H2 - H0 X2 - X0 VX accessible
C H3 - H0 X3 - X0 both wye
windings

AVTMTTR310 Rev 8 May 2016


37
M

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks

A H1 - H0 X0 - X1 VH Neutral
8 YNyn6 B H2 - H0 X0 - X2 VX accessible
C H3 - H0 X0 - X3 both wye
windings

A H1 - H0 X1 - X2 VH Neutral
9 YNd1 B H2 - H0 X2 - X3 accessible
C H3 - H0 X3 - X1 VX v 3 on wye
winding

VH Neutral
10 YNd7 A H1 - H0 X2 - X1 accessible
B H2 - H0 X3 - X2 VX v 3 on wye
C H3 - H0 X1 - X3 winding

VH v 3 No
11 Dy1 A H3 - H2 H1-(H3-H2) X1 - X3 accessible
B H1 - H3 H2-(H1-H3) X2 – X1 VX neutral on
C H2 - H1 H3-(H2-H1) X3 – X2 wye winding

Neutral
A H1 - H3 X3 - X0 VH v 3 accessible
12 Dyn5 B H2 - H1 X1 - X0 on wye
C H3 - H2 X2 - X0 VX winding

No
A H3 - H2 H1-( H3-H2) X3 – X2 VH v 3 accessible
13 Dy5 B H1 – H3 H2-( H1-H3) X1 – X3 neutral on
C H2 – H1 H3-( H2-H1) X2 – X1 VX wye winding

AVTMTTR310 Rev 8 May 2016


38
SETUP AND CONNECTIONS

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks

A H3 - H2 H1-(H3-H2) X3 - X1 VH v 3 No
14 Dy7 B H1 - H3 H2-(H1-H3) X1 - X2 accessible
C H2 - H1 H3-(H2-H1) X2 - X3 VX neutral on
wye winding

H1 - H3 X0 - X3 VH v 3 Neutral
15 Dyn11 A H2 - H1 X0 - X1 accessible
B H3 - H2 X0 - X2 VX on wye
C winding

No
A H3 - H2 H1-(H3-H2) X2 - X3 VH v 3 accessible
16 Dy11 B H1 - H3 H2-(H1-H3) X3 - X1 neutral on
C H2 - H1 H3-(H2-H1) X1 - X2 VX wye winding

A+C H1 - H3 X1 - X3 VH No
17 Dz0 B+A H2 - H1 X2 - X1 VX accessible
C+B H3 - H2 X3 - X2 neutral

A+C H1 - H3 X 3 - X1 VH No
18 Dz6 B+A H2 - H1 X1 - X2 VX accessible
C+B H3 - H2 X2 - X3 neutral

No
A H2 - H0 H1-(H2-H0) X1 – X2 VH accessible
19 YNy0 B H3 - H0 H2-(H3-H0) X2 – X3 VX neutral on
C H1 - H0 H3-(H1-H0) X3 – X1 low-voltage
winding

AVTMTTR310 Rev 8 May 2016


39
M

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks

No
A+C H1 - H3 X1 - X3 VH accessible
20 Yyn0 B+A H2 - H1 X2 - X1 VX neutral on
C+B H3 - H2 X3 - X2 high-voltage
winding

No
A H1 - H3 X1 - X3 VH accessible
21 Yy0 B H2 - H1 X2 - X1 VX neutral both
C H3 - H2 X3 - X2 wye windings

No
A H2 - H0 H1-(H2-H0) X2 - X1 VH accessible
22 YNy6 B H3 - H0 H2-(H3-H0) X3 - X2 VX neutral on
C H1 - H0 H3-(H1-H0) X1 - X3 low-voltage
winding

No
A+C H1 - H3 X3 - X1 VH accessible
23 Yyn6 B+A H2 - H1 X1 - X2 VX neutral on
C+B H3 - H2 X2 - X3 high-voltage
winding

No
A+C H1 - H3 X3 - X1 VH accessible
24 Yy6 B+A H2 - H1 X1 - X2 VX neutral on
C+B H3 - H2 X2 - X3 both wye
windings

No
A H1 - H3 X1 - X0 VH v 3 accessible
25 Yzn1 B H2 - H1 X2 - X0 neutral on
C H3 - H2 X3 - X0 VX wye winding

AVTMTTR310 Rev 8 May 2016


40
SETUP AND CONNECTIONS

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks

A+B H3 - H2 H1-(H3+H2) X1 - X2 VH 3 No
26 Yz1 B+C H1 - H3 H2-(H1+H3) X2 - X3 v accessible
C+A H2 - H1 H3-(H2+H1) X3 - X1 VX 2 neutral

No
A H1 - H3 X3 - X0 VH v 3 accessible
27 Yzn5 B H2 - H1 X1 - X0 neutral on
C H3 - H2 X2 - X0 VX wye winding

A+B H3 - H2 H1-(H3+H2) X3 - X1 VH 3 No
28 Yz5 B+C H1 - H3 H2-(H1+H3) X1 - X2 v accessible
C+A H2 - H1 H3-(H2+H1) X2 - X3 VX 2 neutral

No
A H1 - H3 X0 - X1 VH v 3 accessible
29 Yzn7 B H2 - H1 X0 - X2 neutral on
C H3 - H2 X0 - X3 VX wye winding

A+B H3 - H2 H1-(H3+H2) X2 - X1 VH 3 No
30 Yz7 B+C H1 - H3 H2-(H1+H3) X3 - X2 v accessible
C+A H2 - H1 H3-(H2+H1) X1 - X3 VX 2 neutral

No
A H1 - H3 X0 - X3 VH v 3 accessible
31 Yzn11 B H2 - H1 X0 - X1 neutral on
C H3 - H2 X0 - X2 VX wye winding

AVTMTTR310 Rev 8 May 2016


41
M

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks

A+B H3 - H2 H1-(H3+H2) X1 - X3 VH 3 No
32 Yz11 B+C H1 - H3 H2-(H1+H3) X2 - X1 v accessible
C+A H2 - H1 H3-(H2+H1) X3 - X2 VX 2 neutral

No
A+C H1 - H0 X3 - X1 VH accessible
33 ZNy5 B+A H2 - H0 X1 - X2 neutral on
C+B H3 - H0 X2 - X3 VX v 3 wye winding

A+C H3 - H2 H1-(H3+H2) X3 - X1 VH 1.5 No


34 Zy5 B+A H1 - H3 H2-(H1+H3) X1 - X2 v accessible
VX 3
C+B H2 - H1 H3-(H2+H1) X2 - X3 neutral

No
A+B H1 - H0 X1 - X3 VH accessible
35 ZNy11 B+A H2 - H0 X2 - X1 neutral on
C+B H3 - H0 X3 - X2 VX v 3 wye winding

A+C H3 - H2 H1-(H3+H2) X1 - X3 VH 1.5 No


36 Zy11 B+A H1 - H3 H2-(H1+H3) X2 - X1 v accessible
VX 3
C+B H2 - H1 H3-(H2+H1) X3 - X2 neutral

No
A H3 - H2 H1-(H3+H2) X1 - X2 VH 1.5 accessible
37 Yd1 B H1 - H3 H2-(H1+H3) X2 - X3 v neutral on
VX 3
C H2 - H1 H3-(H2+H1) X3 - X1 wye winding

AVTMTTR310 Rev 8 May 2016


42
SETUP AND CONNECTIONS

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks

Neutral
A H1 - H0 X3 - X1 VH accessible
38 YNd5 B H2 - H0 X1 - X2 on wye
C H3 - H0 X2 - X3 VX v 3 winding

No
A H3 - H2 H1-(H3+H2) X3 - X1 VH 1.5 accessible
39 Yd5 B H1 - H3 H2-(H1+H3) X1 - X2 v neutral on
VX 3
C H2 - H1 H3-(H2+H1) X2 - X3 wye winding

No
A H3 - H2 H1-(H3+H2) X2 - X1 VH 1.5 accessible
v
40 Yd7 B H1 - H3 H2-(H1+H3) X3 - X2 VX 3 neutral on
C H2 - H1 H3-(H2+H1) X1 - X3 wye winding

A H1 - H0 X1 - X3 VH Neutral
41 YNd11 B H2 - H0 X2 – X1 accessible
C H3 - H0 X3 – X2 VX v 3 on wye
winding

No
A H3 - H2 H1-(H3+H2) X1 - X3 VH 1.5 accessible
42 Yd11 B H1 - H3 H2-(H1+H3) X2 - X1 v neutral on
VX 3
C H2 - H1 H3-(H2+H1) X3 - X2 wye winding

AVTMTTR310 Rev 8 May 2016


43
M

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks
S

L
43 1 VH
VREG _ S-SL L-SL _
_ VX
SL

A H1 – H3 X0 – X2 VH v 3 Neutral
44 Dyn3 B H2 – H1 X0 – X3 accessible
_ C H3 – H2 X0 – X1 VX on wye
winding

X1
A H3 - H2 H1-(H3+H2) X1 - X2 VH v 3 No
45 Dy3 X2 B H1 - H3 H2-(H1+H3) X2 - X3 accessible
C H2 - H1 H3-(H2+H1) X3 – X1 VX neutral on
wye winding

X3

X3
Neutral
A H1 - H3 X2 - X0 VH accessible
46 Dyn9 X0 B H2 - H1 X3 - X0 on wye
X2 VX v 3
C H3 - H2 X1 - X0 winding

X1

X3
No
A H3 - H2 H1-( H3+H2) X2 – X1 VH v 3 accessible
47 Dy9 B H1 – H3 H2-( H1+H3) X3 – X2 neutral on
X2 * C H2 – H1 H3-( H2+H1) X1 – X3 VX wye winding

X1

Neutral
A H1 - H3 X1 - X0 VH v 3 accessible
48 YNzn1 B H2 - H1 X2 - X0 on wye
C H3 - H2 X3 - X0 VX winding

AVTMTTR310 Rev 8 May 2016


44
SETUP AND CONNECTIONS

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks

Neutral
A H1 - H3 X0 - X1 VH v 3 accessible
49 YNzn7 B H2 - H1 X0 - X2 on wye
C H3 - H2 X0 - X3 VX winding

Neutral
A H1 - H3 X0 - X3 VH v 3 accessible
50 YNzn11 B H2 - H1 X0 - X1 on wye
C H3 - H2 X0 - X2 VX winding

Neutral
A H1-H0 X3-X2 VH accessible
51 YNd3 B H2-H0 X1-X3
__ VX v 3 on wye
C H3-H0 X2-X1
winding

Neutral
A H1-H0 X2-X3 VH accessible
52 YNd9 B H2-H0 X3-X1
__ VX v 3 on wye
C H3-H0 X1-X2
winding

H3-H2 VH 1.5 No
A H1-(H2+H3) X3-X2 v
H1-H3 VX 3 accessible
53 Yd3 B H2-(H3+H1) X1-X3
H2-H1 neutral on
* C H3-(H1+H2) X2-X1
wye winding

54 Yd9
No
A H3-H2 H1-(H2+H3) X2-X3 VH 1.5
v accessible
B H1-H3 H2-(H3+H1) X3-X1
* C H2-H1 H3-(H1+H2) X1-X2
VX 3 neutral on
wye winding

55 YNyn2
Neutral
XO A H1-H0 X0 – X2 VH accessible
B H2-H0 X0 – X3
C __ H3-H0 X0 – X1
VX both wye
windings

AVTMTTR310 Rev 8 May 2016


45
M

Table 5-4. ANSI Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (H) Winding (X) Tested By TTR Winding Winding Turn Ratio Remarks
56 YNyn8
Neutral
A H1-H0 VH
X2 - X0 accessible
B H2-H0
XO
C __ H3-H0 X3 - X0 VX both wye
X1 - X0 windings

AVTMTTR310 Rev 8 May 2016


46
SETUP AND CONNECTIONS

Notes to Table 5-5


Transformer terminal markings for power transformers marked in accordance
with requirements of International Standard CEI/IEC 76-1:2011.

Definition of Symbol Designations

1U, 1V, 1W External terminals on HV transformer winding


(alternate notation U, V, W).

2U, 2V, 2W External terminals on LV transformer winding


(alternate notation u, v, w).

1N External neutral terminal on HV transformer winding


(alternate notation N).

2N External neutral terminal on LV transformer winding


(alternate notation n).

* Inaccessible neutral point on HV or LV transformer winding.

U1 Nameplate voltage rating (line-to-line) of HV transformer


winding.

U2 Nameplate voltage rating (line-to-line) of LV transformer


winding.

U, V, W Phase tested.

IEC Vector Group Coding

The letters indicate the three-phase winding connections; D, Y, and Z designate


the HV side winding; d, y, and z designate the LV side winding. D and d
represent a delta connection, Y and y represent a wye connection, and Z and z
represent a zigzag connection. N and n indicate that the neutral point of a star or
zigzag connected winding is accessible on the respective HV or LV side winding.
The number indicates the phase displacement (lag) of the LV winding with
respect to the HV winding in units of 30º.

For example, 0 = 0º lag, 1 = 30º lag, 2 = 60º lag, 6 = 180º lag, 11 = 330º lag.

AVTMTTR310 Rev 8 May 2016


47
M

Additional Transformer Winding Identification

External terminal markings for three-phase power transformers with more than
two windings are as follows:

3U, 3V, 3W Third winding (if any).

4U, 4V, 4W Fourth winding (if any).

If unable to find a corresponding diagram for a transformer with, for example,


accessible neutral winding but can find the corresponding diagram for the same
transformer with no neutral accessible winding, follow the test procedure for the
transformer with no neutral accessible winding. In this case, specify the diagram
number for the transformer with no neutral accessible winding and do not
connect 1N or 2N lead to the neutral.

As an example, if transformer winding connection is identical to Table 5-5


Diagram No. 43 except the wye winding has an accessible neutral winding,
perform test per Diagram 43. Do not connect 1N lead to the wye winding
neutral terminal. The test results are identical and do not require any corrections.

AVTMTTR310 Rev 8 May 2016


48
SETUP AND CONNECTIONS

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

1 U1 Single-phase
1 1ph0 1 1.1-1.2 2.1-2.2 U2 transformer

1 U1 Single-phase
2 1ph6 1 1.1-1.2 2.2-2.1 U2 transformer

U 1U-1V 2U-2V U1
3 Dd0 V 1V-1W 2V-2W U2
W 1W-1U 2W-2U

U 1U-1V 2W-2V U1
4 Dd2 V 1V-1W 2U-2W U2
W 1W-1U 2V-2U

U 1U-1V 2W-2U U1
5 Dd4 V 1V-1W 2U-2V U2
W 1W-1U 2V-2W

U 1U-1V 2V-2U U1
6 Dd6 V 1V-1W 2W-2V U2
W 1W-1U 2U-2W

U 1U-1V 2V-2W U1
7 Dd8 V 1V-1W 2W-2U U2
W 1W-1U 2U-2V

U 1U-1V 2U-2W U1
8 Dd10 V 1V-1W 2V-2U U2
W 1W-1U 2W-2V

AVTMTTR310 Rev 8 May 2016


49
M

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

U 1U-1V 2N-2V U1 v 3 Neutral


9 Dyn1 V 1V-1W 2N-2W accessible
W 1W-1U 2N-2U U2 on wye
winding

U 1V-1W 1U-1V 2W-2V U1 v 3 No neutral


10 Dy1 V 1W-1U 1V-1W 2U-2W accessible
W 1U-1V 1W-1U 2V-2U U2 on wye
winding

U 1U-1V 2N-2U U1 v 3 Neutral


11 Dyn5 V 1V-1W 2N-2V accessible
W 1W-1U 2N-2W U2 on wye
winding

No neutral
U 1V-1W 1U-1V 2V-2U U1 v 3 accessible
12 Dy5 V 1W-1U 1V-1W 2W-2V on wye
W 1U-1V 1W-1U 2U-2W U2 winding

Neutral
U 1U-1V 2V-2N U1 v 3 accessible
13 Dyn7 V 1V-1W 2W-2N on wye
W 1W-1U 2U-2N U2 winding

DH1109
No neutral
U 1V-1W 1U-1V 2V-2W U1 v 3 accessible
14 Dy7 V 1W-1U 1V-1W 2W-2U on wye
W 1U-1V 1W-1U 2U-2V U2 winding

AVTMTTR310 Rev 8 May 2016


50
SETUP AND CONNECTIONS

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

Neutral
U 1U-1V 2U-2N U1 v 3 accessible
15 Dyn11 V 1V-1W 2V-2N on wye
W 1W-1U 2W-2N U2 winding

No neutral
U 1V-1W 1U-1V 2U-* U1 v 3 accessible
16 Dy11 V 1W-1U 1V-1W 2V-* on wye
W 1U-1V 1W-1U 2W-* U2 winding

Neutral
U 1V-1W 1U-(1V+1W) 2U-2N 1.5U1 accessible
17 Dzn0 V 1W-1U 1V-(1W+1U) 2V-2N on zigzag
U2
W 1U-1V 1W-(1U+1V) 2W-2N winding

No neutral
U 1U-1V 2U-2V U1 accessible
18 Dz0 V 1V-1W 2V-2W U2 on zigzag
W 1W-1U 2W-2U winding

Neutral
U 1V-1W 1U-(1V+1W) 2N-2V 1.5U1 accessible
19 Dzn2 V 1W-1U 1V-(1W+1U) 2N-2W on zigzag
U2
W 1U-1V 1W-(1U+1V) 2N-2U winding

U 1U-1V 2W-2V U1 No neutral


20 Dz2 V 1V-1W 2U-2W U2 accessible
W 1W-1U 2V-2U on zigzag
winding

AVTMTTR310 Rev 8 May 2016


51
M

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

U 1V-1W 1U-(1V+1W) 2W-2N 1.5U1 Neutral


21 Dzn4 V 1W-1U 1V-(1W+1U) 2U-2N U2 accessible
W 1U-1V 1W-(1U+1V) 2V-2N on zigzag
winding

No neutral
U 1U-1V 2W-2U U1 accessible
22 Dz4 V 1V-1W 2U-2V U2 on zigzag
W 1W-1U 2V-2W winding

Neutral
U 1V-1W 1U-(1V+1W) 2N-2U 1.5U1 accessible
23 Dzn6 V 1W-1U 1V-(1W+1U) 2N-2V U2 on zigzag
W 1U-1V 1W-(1U+1V) 2N-2W winding

No neutral
U 1U-1V 2V-2U U1 accessible
24 Dz6 V 1V-1W 2W-2V U2 on zigzag
W 1W-1U 2U-2W winding

Neutral
U 1V-1W 1U-(1V+1W) 2V-2N 1.5U1 accessible
25 Dzn8 V 1W-1U 1V-(1W+1U) 2W-2N U2 on zigzag
W 1U-1V 1W-(1U+1V) 2U-2N winding

No neutral
U 1U-1V 2V-2W U1 accessible
26 Dz8 V 1V-1W 2W-2U U2 on zigzag
W 1W-1U 2U-2V winding

AVTMTTR310 Rev 8 May 2016


52
SETUP AND CONNECTIONS

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

Neutral
U 1V-1W 1U-(1V+1W) 2N-2W 1.5U1 accessible
27 Dzn10 V 1W-1U 1V-(1W+1U) 2N-2U U2 on zigzag
W 1U-1V 1W-(1U+1V) 2N-2V winding

No neutral
U 1U-1V 2U-2W U1 accessible
28 Dz10 V 1V-1W 2V-2U U2 on zigzag
W 1W-1U 2W-2V winding

Neutral
U 1U-1N 2U-2N U1 accessible
29 YNyn0 V 1V-1N 2V-2N U2 on HV & LV
W 1W-1N 2W-2N winding

No neutral
U 1V-1N 1U-1N 2U-2V U1 accessible
30 YNy0 V 1W-1N 1V-1N 2V-2W U2 on LV
W 1U-1N 1W-1N 2W-2U winding

No neutral
U+V 1U-1V 2U-2V U1 accessible
31 Yyn0 V+W 1V-1W 2V-2W U2 on HV
W+U 1W-1U 2W-2U winding

No neutral
U+V 1U-1V 2U-2V U1 accessible
32 Yy0 V+W 1V-1W 2V-2W U2 on HV & LV
W+U 1W-1U 2W-2U windings

AVTMTTR310 Rev 8 May 2016


53
M

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

Neutral
U 1U-1N 2N-2U U1 accessible
33 YNyn6 V 1V-1N 2N-2V U2 on HV & LV
W 1W-1N 2N-2W windings

U 1V-1N 1U-1N 2V-2U U1 No neutral


34 YNy6 V 1W-1N 1V-1N 2W-2V U2 accessible
W 1U-1N 1W-1N 2U-2W on LV
winding

U+V 1U-1V 2V-2U U1 No neutral


35 Yyn6 V+W 1V-1W 2W-2V U2 accessible
W+U 1W-1U 2U-2W on HV
winding

U+V 1U-1V 2V-2U U1 No neutral


36 Yy6 V+W 1V-1W 2W-2V U2 accessible
W+U 1W-1U 2U-2W on HV & LV
windings

With or
U 1U-1V 2N-2V U1v 3 without
37 Yzn1 V 1V-1W 2N-2W accessible
U2
W 1W-1U 2N-2U neutral on
wye winding

No neutral
U 1V-1W 1U-(1V+1W) 2U-2V U1 3 accessible
38 Yz1 V 1W-1U 1V-(1W+1U) 2V-2W v on HV & LV
U2 2
W 1U-1V 1W-(1U+1V) 2W-2U winding

AVTMTTR310 Rev 8 May 2016


54
SETUP AND CONNECTIONS

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

With or
U 1U-1V 2N-2U U1v 3 without
39 Yzn5 V 1V-1W 2N-2V accessible
W 1W-1U 2N-2W U2 neutral on
wye winding

No neutral
U 1V-1W 1U-(1V+1W) 2W-2U U1 3 accessible
40 Yz5 V 1W-1U 1V-(1W+1U) 2U-2V v on HV & LV
W 1U-1V 1W-(1U+1V) 2V-2W U2 2 windings

U 1U-1V 2V-2N U1 v 3 Neutral


41 Yzn7 V 1V-1W 2W-2N accessible
U2
W 1W-1U 2U-2N on wye
winding

No neutral
U 1V-1W 1U-(1V+1W) 2V-2U U1 3 accessible
42 Yz7 V 1W-1U 1V-(1W+1U) 2W-2V U2
v
2 on HV & LV
W 1U-1V 1W-(1U+1V) 2U-2W windings

With or
U 1U-1V 2U-2N without
43 Yzn11 V 1V-1W 2V-2N U1 v 3 accessible
W 1W-1U 2W-2N U2 neutral on
wye winding

No neutral
U 1V-1W 1U-(1V+1W) 2U-2W accessible
U1 3
44 Yz11 V 1W-1U 1V-(1W+1U) 2V-2U v on HV & LV
W 1U-1V 1W-(1U+1V) 2W-2V U2 2 windings

AVTMTTR310 Rev 8 May 2016


55
M

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

U 1U-1N 2U-2V Neutral


45 YNd1 V 1V-1N 2V-2W U1 accessible
W 1W-1N 2W-2U on wye
U2 v 3 winding

U 1V-1W 1U-(1V+1W) 2U-2V No neutral


46 Yd1 V 1W-1U 1V-(1W+1U) 2V-2W U1 * 1.5 accessible
W 1U-1V 1W-(1U+1V) 2W-2U on wye
U2 v 3 winding

U 1U-1N 2W-2U Neutral


47 YNd5 V 1V-1N 2U-2V U1 accessible
W 1W-1N 2V-2W on wye
U2 v 3 winding

U 1V-1W 1U-(1V+1W) 2W-2U No neutral


48 Yd5 V 1W-1U 1V-(1W+1U) 2U-2V U1*1.5 accessible
W 1U-1V 1W-(1U+1V) 2V-2W on wye
U2 v 3 winding

U 1U-1N 2V-2U Neutral


49 YNd7 V 1V-1N 2W-2V U1 accessible
W 1W-1N 2U-2W on wye
U2 v 3 winding

U 1V-1W 1U-(1V+1W) 2V-2U No neutral


50 Yd7 V 1W-1U 1V-(1W+1U) 2W-2V U1*1.5 accessible
W 1U-1V 1W-(1U+1V) 2U-2W on wye
U2 v 3 winding

AVTMTTR310 Rev 8 May 2016


56
SETUP AND CONNECTIONS

Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship


Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (U1) Winding (U2) Tested By TTR Winding Winding Turn Ratio Remarks

U 1U-1N 2U-2W Neutral


51 YNd11 V 1V-1N 2V-2U U1 accessible
W 1W-1N 2W-2V on wye
U2 v 3 winding

U 1V-1W 1U-(1V+1W) 2U-2W No neutral


52 Yd11 V 1W-1U 1V-(1W+1U) 2V-2U U1*1.5 accessible
W 1U-1V 1W-(1U+1V) 2W-2V on wye
U2 v 3 winding

AVTMTTR310 Rev 8 May 2016


57
M

Notes to Table 5-6


Transformer terminal markings for power transformers marked in accordance
with requirements of Australian Standard 2374, Part 4-2003.

Definition of Symbol Designations

A2, B2, C2 External terminals on HV transformer winding (Ax, Bx, Cx).

a2, b2, c2 External terminals on LV transformer winding (ax, bx, cx).

N External neutral terminal on HV transformer winding.

n External neutral terminal on LV transformer winding.

* Inaccessible neutral point on HV or LV transformer winding.

HV Nameplate voltage rating (line-to-line) of HV transformer


winding.

LV Nameplate voltage rating (line-to-line) of LV transformer


winding.

A, B, C Winding tested on HV side of transformer.

a, b, c Winding tested on LV side of transformer.

IEC Vector Group Coding

The letters indicate the three-phase winding connections; D, Y, and Z designate


the HV side winding; d, y, and z designate the LV side winding. D and d
represent a delta connection, Y and y represent a wye connection, and Z and z
represent a zigzag connection. N and n indicate that the neutral point of a star or
zigzag connected winding is accessible on the respective HV or LV side winding.
The number indicates the phase displacement (lag) of the LV winding with
respect to the HV winding in units of 30º.

For example, 0 = 0º lag, 1 = 30º lag, 2 = 60º lag, 6 = 180º lag, 11 = 330º lag.

AVTMTTR310 Rev 8 May 2016


58
SETUP AND CONNECTIONS

Additional Transformer Winding Identification

External terminal markings for three-phase power transformers with more than
two windings are as follows:

3A, 3B, 3C Third winding (if any).

4A, 4B, 4C Fourth winding (if any).

If unable to find a corresponding diagram for a transformer with, for example,


accessible neutral winding but can find the corresponding diagram for the same
transformer with no neutral accessible winding, follow the test procedure for the
transformer with no neutral accessible winding. In this case, specify the diagram
number for the transformer with no neutral accessible winding and do not
connect N or n lead to the neutral.

As an example, if transformer winding connection is identical to Table 5-6


Diagram No. 23 except the wye winding has an accessible neutral winding,
perform test per Diagram 23. Do not connect N lead to the wye winding neutral
terminal. The test results are identical and do not require any corrections.

AVTMTTR310 Rev 8 May 2016


59
M

Table 5-6. Transformer Winding Phase Relationship (Australian Std. 2374, Part 4 - 2003)
Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (HV) Winding (LV) Tested By TTR Winding Winding Turn Remarks
Ratio

HV
1 1 1 A2 - A1 a2 - a1 LV Single-phase
1ph0 transformer

HV
2 1 1 A2 - A1 a1 - a2 LV Single-phase
1ph6 transformer

3 Dd0 A A2 - B2 a2 - b2 HV
B B2 - C2 b2 - c2 LV
C C2 - A2 c2 - a2

A A2 - B2 b1 - a1 HV
4 Dd6 B B2 - C2 c1 - b1 LV
C C2 - A2 a1 - c1

A A2 - B2 n - b2 HV v 3 Neutral
5 Dyn1 B B2 - C2 n - c2 accessible
C C2 -A2 n - a2 LV on wye
winding

A B2 - C2 A2 - B2 c2 - b2 HV v 3 No neutral
6 Dy1 B C2 - A2 B2 - C2 a2 - c2 accessible
C A2 - B2 C2 - A2 b2 - a2 LV on wye
winding

A A2 - B2 a2 - n HV v 3 Neutral
7 Dyn11 B B2 - C2 b2 - n accessible
LV
C C2 - A2 c2 - n on wye
winding

AVTMTTR310 Rev 8 May 2016


60
SETUP AND CONNECTIONS

Table 5-6. Transformer Winding Phase Relationship (Australian Std. 2374, Part 4 - 2003)
Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (HV) Winding (LV) Tested By TTR Winding Winding Turn Remarks
Ratio

A B2 - C2 A2 - B2 a2 - b2 HV v 3 No neutral
8 Dy11 B C2 - A2 B2 - C2 b2 - c2 accessible
LV
C A2 - B2 C2 - A2 c2 - a2 on wye
winding

Neutral
A+C B2 - C2 A2 - (B2+C2) a4 - n 1.5 HV accessible
9 Dzn0 B+A C2 - A2 B2 - (C2+A2) b4 - n LV on zigzag
C+B A2 - B2 C2 - (A2+B2) c4 - n winding

A+C+A+B No neutral
B+A+C+B A2 - B2 a4 - b4 accessible
HV
10 Dz0 C+B+C+A B2 - C2 b4 - c4 on zigzag
LV
C2 - A2 c4 - a4 winding

Neutral
A+C B2 - C2 A2 - (B2+C2) n - a3 1.5 HV accessible
11 Dzn6 B+A C2 - A2 B2 - (C2+A2) n - b3 LV on zigzag
C+B A2 - B2 C2 - (A2+B2) n - c3 winding

No neutral
A+C+A+B A2 - B2 b3 - a3 HV accessible
12 Dz6 B+A+C+B B2 - C2 c3 - b3 on zigzag
C+B+C+A LV
C2 - A2 a3 - c3 winding

Neutral
A A2 - N a2 - n HV accessible
13 YNyn0 B B2 - N b2 - n LV on HV & LV
C C2 - N c2 - n windings

AVTMTTR310 Rev 8 May 2016


61
M

Table 5-6. Transformer Winding Phase Relationship (Australian Std. 2374, Part 4 - 2003)
Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (HV) Winding (LV) Tested By TTR Winding Winding Turn Remarks
Ratio

No
A B2 - N A2 - N a2 - b2 HV accessible
14 YNy0 B C2 - N B2 - N b2 - c2 LV neutral on LV
C A2 - N C2 - N c2 - a2 winding

No neutral
A+B A2 - B2 a2 - b2 HV accessible
15 Yyn0 B+C B2 - C2 b2 - c2 LV on HV
C+A C2 - A2 c2 - a2 winding

No neutral
A+B A2 - B2 a2 - b2 HV accessible
16 Yy0 B+C B2 - C2 b2 - c2 LV on HV & LV
C+A C2 - A2 c2 - a2 windings

Neutral
A A2 - N n - a1 HV accessible
17 YNyn6 B B2 - N n - b1 LV on HV & LV
C C2 - N n - c1 windings

No neutral
A B2 - N A2 - N b1- a1 HV accessible
18 YNy6 B C2 - N B2 - N c1- b1 LV on LV
C A2 - N C2 - N a1- c1 winding

No neutral
A+B A2 - B2 b1 - a1 HV accessible
19 Yyn6 B+C B2 - C2 c1 - b1 LV on HV
C+A C2 - A2 a1 - c1 winding

AVTMTTR310 Rev 8 May 2016


62
SETUP AND CONNECTIONS

Table 5-6. Transformer Winding Phase Relationship (Australian Std. 2374, Part 4 - 2003)
Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (HV) Winding (LV) Tested By TTR Winding Winding Turn Remarks
Ratio

No neutral
A+B A2 - B2 b1 - a1 HV accessible
20 Yy6 B+C B2 - C2 c1 - b1 LV on HV & LV
C+A C2 - A2 a1 - c1 windings

With or
without
A+B A2 - B2 n - b4 HV v 3 neutral
21 Yzn1 B+C B2 - C2 n - c4 accessible
C+A C2 - A2 n - a4 LV on wye
winding

No neutral
A+C+A+B B2- C2 A2- (B2 +C2) a4 - b4 HV 3 accessible
22 Yz1 B+A+C+B C2 - A2 B2 - (C2+A2) b4 - c4 v on HV & LV
C+B+C+A A2 - B2 C2 - (A2+B2) c4 - a4 LV 2 windings

With or
without
A+B A2 - B2 a4 - n HV v 3 neutral
23 Yzn11 B+C B2 - C2 b4 - n accessible
LV
C+A C2 - A2 c4 - n on wye
winding

No neutral
A B2 - C2 A2 - (B2+C2) a4 - c4 HV 3 accessible
24 Yz11 B C2 - A2 B2 - (C2+A2) b4 - a4 v on HV & LV
C A2 - B2 C2 - (A2+B2) c4 - b4 LV 2 windings

Neutral
A A2 - N a2 - b2 HV accessible
25 YNd1 B B2 - N b2 - c2 on wye
LV v 3
C C2 - N c2 - a2 winding

AVTMTTR310 Rev 8 May 2016


63
M

Table 5-6. Transformer Winding Phase Relationship (Australian Std. 2374, Part 4 - 2003)
Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (HV) Winding (LV) Tested By TTR Winding Winding Turn Remarks
Ratio

No neutral
A B2 - C2 A2 -(B2+C2) a2 - b2 HV v 1.5 accessible
26 Yd1 B C2 - A2 B2 -(C2+A2) b2 - c2 LV v 3 on wye
C A2 - B2 C2 -(A2+B2) c2 - a2 winding

Neutral
A A2 - N a2 - c2 HV accessible
27 YNd11 B B2 - N b2 - a2 on wye
LV v 3
C C2 - N c2 - b2 winding

No neutral
A B2 - C2 A2 -(B2+C2) a2 - c2 HV v 1.5 accessible
28 Yd11 B C2 - A2 B2 -(C2+A2) b2 - a2 LV v 3 on wye
C A2 - B2 C2 -(A2+B2) c2 - b2 winding

Neutral
A B4 - C4 A4 - N a2 - b2 HV accessible
29 ZNd0 B C4 - A4 B4 - N b2 - c2 1.5 LV on zigzag
C A4 - B4 C4 - N c2 - a2 winding

No neutral
A B4 - C4 A4 - (B4 - C4) a2 - b2 HV accessible
30 Zd0 B C4 - A4 B4 - (C4 - A4) b2 - c2 LV on zigzag
C A4 - B4 C4 - (A4 - B4) c2 - a2 winding

Neutral
A B4 - C4 A4 - N b1 - a1 HV accessible
31 ZNd6 B C4 - A4 B4 - N c1 - b1 1.5 LV on zigzag
C A4 - B4 C4 - N a1 - c1 winding

AVTMTTR310 Rev 8 May 2016


64
SETUP AND CONNECTIONS

Table 5-6. Transformer Winding Phase Relationship (Australian Std. 2374, Part 4 - 2003)
Copyright 2009 Megger
Winding Connection Winding Tested
IEC Winding High- Low-
Diag Vector High-Voltage Low-Voltage Phase Shorted Voltage Voltage Measured
No. Group Winding (HV) Winding (LV) Tested By TTR Winding Winding Turn Remarks
Ratio

No neutral
A B4 - C4 A4 - (B4 - C4) HV accessible
32 Zd6 B C4 - A4 B4 - (C4 - A4) LV on zigzag
C A4 - B4 C4 - (A4 - B4) winding

No
C+A A4 - N a2 - b2 HV accessible
33 ZNy1 A+B B4 - N b2 - c2 neutral on LV
LV v 3
B+C C4 - N c2 - a2 winding

No neutral
C+A B4 - C4 A4 -(B4+C4) a2 - b2 VH 1.5 accessible
34 Zy1 A+B C4 - A4 B4 -(C4+A4) b2 - c2 v on HV & LV
VX 3
B+C A4 - B4 C4 -(A4+B4) c2 - a2 windings

No
A+C A4 - N a2 - c2 HV accessible
35 ZNy11 B+A B4 - N b2 - a2 neutral on LV
LV v 3
C+B C4 - N c2 - b2 winding

No neutral
A+C B4 - C4 A4 -(B4+C4) a2 - c2 VH 1.5 accessible
36 Zy11 B+A C4 - A4 B4 -(C4+A4) b2 - a2 v on HV & LV
VX 3
C+B A4 - B4 C4 -(A4+B4) c2 - b2 windings

Neutral
n A+C A4 - N a2 - c2 HV accessible
37 ZNyn11 B+A B4 - N b2 - a2
__ LV v 3 on HV & LV
C+B C4 - N c2 - b2
windings

AVTMTTR310 Rev 8 May 2016


65
M

AVTMTTR310 Rev 8 May 2016


66
6
Operation
General Operating Procedure
Proceed only after reading and fully understanding Section 2, Safety, and setting
up the test set as described. An operator who is familiar with the contents of this
manual, the test setup, and the operation of the test set may follow the
condensed operating instructions in the lid of the test set.

EMERGENCY SHUTDOWN
Press red EMERGENCY TEST OFF push button or switch power
off.

Description of Menus and Test Screens


Data shown on the menus and test screens in Figures 6-1 through 6-16 are for
illustrative purposes only. The TTR310 test set menus and test screens are
operated by using the keypad on the front panel. On power up, a beep sounds,
the test set performs a self-test check, and all hardware and software variables are
initialized.

AVTMTTR310 Rev 8 May 2016 67


M

MAIN MENU Screen (Figure 6-1)


After a successful self-test check, the main menu screen (Figure 6-1) appears.

MAIN MENU
DATE (M/D/Y) : 06/15/1998 14:15

1 QUICK TEST SETUP TEST WINDING:


2 FULL TEST SETUP
3 RECALL CUSTOM SETTINGS * 7 H-X
4 SYSTEM SETUP MENU 8 H-Y
5 SAVED DATA MENU 9 CT
6 PRINT HEADER

TEST:002 ID nnnnnnnnnnnn DIAG 1ph0


01
TEST VOLTAGE: AUTO
H NAMEPLATE VOLTAGE (L-L): 250000
X NAMEPLATE VOLTAGE (L-L): 50000

ENTER SELECTION FROM KEYPAD

Figure 6-1. Main Menu Screen

DATE (M/D/Y): This line shows the current date and time. Date
format is month/day/year. To change date/time,
select 4 (SYSTEM SETUP MENU) and then
select 2 (SET DATE(M/D/Y)/TIME) on the
SYSTEM SETUP menu (see Figure 6-11).

1 QUICK TEST SETUP: This setup provides a quick path for transformer
testing. It requires minimum transformer nameplate
information to be entered before testing. The test
results displayed do not include the calculated ratio
and ratio deviation values.

2 FULL TEST SETUP: This setup requires entering main transformer


nameplate information. The FULL TEST SETUP is
used for obtaining full test information of a
transformer. This setup may be saved and recalled
later for future testing of the same or similar type
transformers. In this case (RECALL CUSTOM
SETTINGS), no additional information needs to be
entered to start testing, other than the transformer
serial number (TRANSFOMER ID) if desired.

AVTMTTR310 Rev 8 May 2016


68
OPERATION

3 RECALL CUSTOM This option permits saving up to nine custom


SETTINGS: transformer settings. These saved custom transformer
settings may be recalled and used for testing the same
or similar type of transformer.

4 SYSTEM SETUP MENU: This menu permits choice of language, transformer


standard, test voltage, phase display units and setting
of date and time.

5 SAVED DATA MENU: The TTR310 saves up to 200 test results. This menu
allows these readings to be recalled for viewing and
uploading to a PC.

6 PRINT HEADER: This option will print out a test report header to the
printer, if connected.

TEST WINDING: Selection 7, 8, and 9 allow an operator to choose the


windings to be tested. Asterisk (*) indicates last
selection used. See description of the following
screens for more details.

Test parameters shown on the bottom of the main menu screen are from the last test
performed.

AVTMTTR310 Rev 8 May 2016


69
M

QUICK TEST SETUP Screen (Figure 6-2)


If 1 (QUICK TEST SETUP) is selected on the main menu, the QUICK TEST
SETUP screen (Figure 6-2) appears.
QUICK TEST SETUP

1 TRANSFORMER ID: nnnnnnnnnnnn

2 TRANSFORMER TYPE: DIAG 01 1ph0

3 START TEST

4 MAIN MENU

ENTER SELECTION FROM KEYPAD

Figure 6-2. Quick Test Setup Screen

1 TRANSFORMER ID: This selection allows you to enter up to a 12-character


alphanumeric identification of a transformer. Skip this
step if you do not want to enter this information. When
selected, the screen appears the same as Figure 6-2
except for a message at bottom of screen: ENTER UP
TO 12 CHARACTER ID. USE * TO SELECT
LETTER. A cursor will blink on the line next to
TRANSFORMER ID.

2 TRANSFORMER This selection is used to enter the diagram number


TYPE: (vector group) of the transformer to be tested. This
diagram number must be entered for testing any
transformer windings (see selections 7, 8, 9 on the Main
Menu screen). When 2 (TRANSFORMER TYPE) is
selected, the screen appears the same as Figure 6.2
except for message at bottom of screen: ENTER
TRANSFORMER DIAGRAM NUMBER. REFER TO
TABLE ON INSTRUCTION CARD. Cursor will blink
on the line next to TRANSFORMER TYPE (in place of
“DIAG 01 1ph0”).

3 START TEST: This selection initiates testing of a transformer. See


Figure 6-3 for the next screen displayed (Initial Quick
Test Result Screen).

4 MAIN MENU: This selection returns you to the main menu screen,
Figure 6-1.

AVTMTTR310 Rev 8 May 2016


70
OPERATION

Quick Test Result Screens (Figure 6-3 and Figure 6-4)


If 3 (START TEST) is selected on the QUICK TEST SETUP menu, Figure 6-2,
the initial quick test result screen shown in Figure 6-3 appears. This screen is
displayed during testing of a transformer.

THREE PHASE TRANSFORMER TEST


TEST: nnn ID:A13579CV0246 DIAG NN Ddnnn

TEST VOLTAGE: 80V


A B C
RATIO

PHASE (min)
Iexc (mA)

TEST IN PROGRESS
PRESS EMERGENCY TEST OFF BUTTON
TO STOP TEST

Figure 6-3. Initial Quick Test Result Screen

The TEST IN PROGRESS message indicates that the TTR310 test set is
performing a test. The test may be interrupted by pressing the EMERGENCY
TEST OFF button, located on the front panel. When pressed, the
EMERGENCY TEST OFF switch is locked in the off position. To reset the
switch, twist the button in the direction indicated by the arrows. When the test is
completed, the final quick test result screen shown in Figure 6-4 appears.

If abnormal operating conditions occur during testing phase B or C of a three-


phase transformer, an error message (refer to Error Messages section) will appear
on the bottom of the screen followed by the message “PRESS ANY KEY TO
CONTINUE.” In this case, if any key is pressed, the following message will
appear on the bottom of the screen:

“Select 1 – REPEAT TEST 2 – CONTINUE 3 – ABORT TEST”

If REPEAT TEST is selected, the test set will re-test phase B or C.

If CONTINUE is selected, the test set will start testing of phase C (if an error
message appeared during phase B testing).

If ABORT TEST is selected, the Main Menu screen will appear. If one of these
error messages appears, verify the abnormal condition by taking a repeat
measurement before attempting to take any corrective action. If an error message
appears during phase A testing, and repeat measurement is still bad, it is
impossible to continue testing of the transformer, and troubleshooting procedure
should be started by testing each phase of the three-phase transformer separately
as a single phase transformer.

AVTMTTR310 Rev 8 May 2016


71
M

THREE PHASE TRANSFORMER TEST


TEST: nnn ID:A13579CV0246 DIAG nn Ddnnn

TEST VOLTAGE: 80V


A B C
RATIO 12.379 12.354 12.287

PHASE (min) 4.8 5.1 2.3

Iexc (mA) 2.6 2.9 2.2

SELECT: 1-PRINT 2-STORE 3-NEXT TEST


4-REPEAT TEST 5-MAIN MENU

Figure 6-4. Final Quick Test Result Screen

1 PRINT: This selection allows the test result to be printed out (on
an optional printer or uploaded to PC.

2 STORE: This selection allows the test result to be saved in


memory for future viewing and/or printing and/or
uploading to PC.

3 NEXT TEST: When selected, the QUICK TEST SETUP screen,


Figure 6-2, appears. You may change connections and
continue testing with the same transformer (for example,
with a different tap of the high voltage winding) or you
may start testing a new transformer.

4 REPEAT TEST: This selection allows you to repeat the last test.

5 MAIN MENU: This selection brings back the MAIN MENU screen
(Figure 6-1).

AVTMTTR310 Rev 8 May 2016


72
OPERATION

FULL TEST SETUP 1 Screen (Figure 6-5)


If 2 (FULL TEST SETUP) is selected on the main menu, the FULL TEST
SETUP 1 screen (Figure 6-5) appears.
FULL TEST SETUP 1

1. CONTINUE
2. TRANSFORMER ID: nnnnnnnnnnnn
3. TRANSFORMER TYPE: DIAG nn Ddnnn
4. H NAMEPLATE VOLTAGE (L-L): 250000
5. NO. OF H TAPS: 5
6. NOMINAL VOLTAGE H TAP NO: 3
7. HIGH VOLTAGE H TAP NO: 1
8. % DIFFERENCE/TAP 2.5
9. MAIN MENU

ENTER SELECTION FROM KEYPAD

Figure 6-5. FULL TEST SETUP 1 Screen


The last tested transformer information (previously entered) is displayed on the
screen.

1 CONTINUE: This selection brings up the FULL TEST SETUP 2


screen (Figure 6-6).

2 TRANSFORMER ID: This selection allows you to enter up to a 12 character


alphanumeric identification of a transformer. Skip this
step if you do not want to enter this information. When
selected, the screen appears the same as Figure 6-5
except for a message at bottom of screen: ENTER UP
TO 12 CHARACTER ID. USE * TO SELECT
LETTERS. A cursor will blink on the line next to
TRANSFORMER ID.

3 TRANSFORMER This selection is used to enter the diagram number


TYPE: (vector group) of the transformer to be tested. This
diagram number must be entered for testing a
transformer. Diagram numbers for the most common
types of transformers are included on the instruction
cards in the lid of the TTR310 test set. When selected,
the screen appears the same as Figure 6-5, except for the
message at bottom of screen: ENTER
TRANSFORMER DIAGRAM NUMBER, REFER TO
TABLE ON INSTRUCTION CARD. A cursor will
blink on the line next to TRANSFORMER TYPE.

AVTMTTR310 Rev 8 May 2016


73
M

4 H NAMEPLATE This selection is used to enter the nameplate high voltage


VOLTAGE (L-L): (H) rating of the transformer to be tested (L-L stands for
line to line). The transformer under test nameplate high
voltage is used to calculate the transformer turn ratio when
test winding 7 (H-X) or 8 (H-Y) is selected on the Main
Menu screen (see Figure 6-1). When test winding 9 CT is
selected on the Main Menu screen (see Figure 6-1), entry 4
H NAMEPLATE VOLTAGE (L-L) is replaced by 4
PRIMARY CURRENT (A), and selections 5, 6, 7, 8 of the
FULL TEST SETUP 1 screen will go off. In this case
selection 4 PRIMARY CURRENT (A) is used to enter the
nameplate primary current of a current transformer tested.

5 NO. OF H TAPS: This selection is used to enter the number of taps on the
high side (H) of the transformer to be tested. If the high
side winding does not have any taps, enter 0 (selections 6,
7, and 8 will go off.)

6 NOMINAL This selection is used to enter the tap number of the


VOLTAGE H TAP NO: nominal voltage of the high side (H) of the transformer.

7 HIGH VOLTAGE H This selection is used to enter the tap number of the
TAP NO: highest input voltage of the transformer.

8 This selection is used to enter the high voltage difference


% DIFFERENCE/TAP (in percent) per tap. Use the following formula to calculate
this parameter:
V H max V H min
s 100% ,
V Hnameplate s n 1
Where: n = number of H taps,
VHMAX = maximum voltage at H winding taps,
VHMIN = minimum voltage at H winding taps,
VHNAMEPLATE = nominal voltage at H winding taps.
If a nameplate has information on total change of voltage
in percent (for example, +/- 10% from nominal voltage),
the following formula may be used to calculate the %
difference per tap:
(Total % of voltage change) (n – 1),
Where n = number of H taps.
Note: The aforementioned calculations are true only
if a transformer has the same voltage change per tap.

9 MAIN MENU: This selection returns you to the MAIN MENU screen,
Figure 6-1.

AVTMTTR310 Rev 8 May 2016


74
OPERATION

FULL TEST SETUP 2 Screen (Figure 6-6)


If 1 is selected on the FULL TEST SETUP 1 screen, the FULL TEST SETUP 2
screen (Figure 6-6) appears.
FULL TEST SETUP 2

1 CONTINUE
2 X NAMEPLATE VOLTAGE (L-L): 5000
3 NO. OF H TAPS: 33
4 NOMINAL VOLTAGE X TAP NO: 17
5 HIGH VOLTAGE X TAP NO: 33 OR 16R
6 % DIFFERENCE/TAP 0.625
7 PAUSE BETWEEN PHASES: NO
8 SAVE CUSTOM SETTINGS
9 PREVIOUS MENU
10

ENTER SELECTION FROM KEYPAD

Figure 6-6. FULL TEST SETUP 2 Screen


The previously entered information from the last transformer tested is displayed
on the screen.

1 CONTINUE: This selection brings up the FULL TEST SETUP 3


screen shown in Figure 6-7.

2 X NAMEPLATE This selection is used to enter the nameplate low voltage


VOLTAGE (L-L): rating of the transformer to be tested (L-L stands for
line to line). The transformer-under-test nameplate low
voltage is used to calculate the transformer turn ratio.
When test winding 8 (H-Y) is selected on the Main
Menu screen (see Figure 6-1), entry 2 X NAMEPLATE
VOLTAGE (L-L) is replaced by 2 Y NAMEPLATE
VOLTAGE (L-L). In this case this selection is used to
enter the tertiary (Y) nameplate low voltage rating of the
transformer to be tested (L-L stands for line to line).
When test winding 9 CT is selected on the Main Menu
screen (see Figure 6-1), entry 2 X NAMEPLATE
VOLTAGE (L-L) is replaced by 2 SECONDARY
CURRENT (A), and selections 3, 4, 5, 6, of the FULL
TEST SETUP 2 screen will go off. In this case selection
2 SECONDARY CURRENT (A) is used to enter the
nameplate secondary current of a current transformer
tested.

AVTMTTR310 Rev 8 May 2016


75
M

3 NO. OF X TAPS: This selection is used to enter the number of taps on the
low side (X) of the transformer. If the low side winding
does not have any taps, enter 0 (selections 4, 5, and 6 will
go off).
4 NOMINAL VOLTAGE This selection is used to enter the tap number of the
X TAP NO: nominal output voltage of the low side (X) of the
transformer.
5 HIGH VOLTAGE X This selection is used to enter the tap number of the
TAP NO: highest output voltage of the transformer.
6 % DIFFERENCE/TAP This selection is used to enter the low voltage difference
(in percent) per tap. Use the following formula to
calculate this parameter:
V XMAX V XMIN
s100% ,
V XNOMINAL s n 1
Where n = number of X taps,
VXMAX = maximum voltage at X winding taps,
VXMIN = minimum voltage at X winding taps,
VXNAMEPLATE = nominal voltage at X winding taps.
If a nameplate has information on total change of voltage
in percent (for example, +/- 10% from nominal voltage),
the following formula may be used to calculate the %
difference per tap:
(Total % of voltage change) (n – 1),
Where n = number of X taps.
Note: The aforementioned calculations are true only
if a transformer has the same voltage change per tap.
7 PAUSE BETWEEN For this selection, there are two choices NO or YES.
PHASES: If NO is chosen, the TTR310 will test all three windings
and display the test results as shown in Figure 6-8
(THREE PHASE TRANSFORMER TEST result
screen). If YES is chosen, the TTR310 will test the first
phase of a transformer and display the test results as
shown in Figure 6-9 (Phase A Test Result Screen).

8 SAVE CUSTOM This selection allows you to save up to nine custom


SETTINGS: transformer settings. See Figure 6-14, Recall (or Save)
Custom Transformer Settings Screen.

9 PREVIOUS MENU: This selection returns you to the FULL TEST SETUP 1
screen (Figure 6-7).

AVTMTTR310 Rev 8 May 2016


76
OPERATION

FULL TEST SETUP 3 Screen (Figure 6-7)


If 1 is selected on the FULL TEST SETUP 2 screen, the FULL TEST SETUP 3
screen appears (Figure 6-7).
FULL TEST SETUP 3
TEST: nnn ID:A13579CV0246 DIAG nn Ddnnn

1 H TAP TO BE TESTED: 3

2 X TAP TO BE TESTED: 3

3 START TEST

4 PREVIOUS MENU

5 MAIN MENU

ENTER SELECTION FROM KEYPAD

Figure 6-8. FULL TEST SETUP 3 Screen

The test number, ID and diagram are shown on the first line.

Selections 1 and 2 allow you to test any pairs of H and X taps. If the transformer
under test does not have any taps, only selections 3, 4, and 5 will be displayed on
the screen.
If 3 (START TEST) is selected, see Figure 6-3 for the next screen displayed.
The % DEVIATION heading will also be shown on the screen.

1 H TAP TO BE This selection is used to enter the H tap number to be


TESTED: tested when test winding 7 H-X or 8 H-Y is selected on
the Main Menu screen (see Figure 6-1).
When test winding 9 CT is selected on the Main Menu
screen this entry will go off.

2 X TAP TO BE This selection is used to enter the X tap number to be


TESTED: tested when test winding 7 H-X is selected on the Main
Menu screen (see Figure 6-1). When test winding
8 (H-Y) is selected on the Main Menu screen, entry 2 X
TAP TO BE TESTED is replaced by 2 Y TAP TO BE
TESTED. When test winding 9 CT is selected on the
Main Menu screen (see Figure 6-1), this entry will go off.

3 START TEST: This selection initiates testing of a transformer. If


selected, the screen shown in Figure 6-3 will appear.

AVTMTTR310 Rev 8 May 2016


77
M

4 PREVIOUS MENU: This selection will return you to the FULL TEST
SETUP 2 screen (Figure 6-6).

5 MAIN MENU: This selection returns you to the MAIN MENU screen
(Figure 6-1).

AVTMTTR310 Rev 8 May 2016


78
OPERATION

Transformer Test Result Screens (Figure 6-8 and Figure 6-9)


When test is completed with NO pauses between phases chosen (selection 7,
Figure 6-6) the test results are displayed as in Figure 6-8 (Three-Phase
Transformer Test Results Screen).
THREE PHASE TRANSFORMER TEST
TEST: nnn ID:A13579CV0246 DIAG nn Ddnnn
TAPS TESTED: 3 - 16R
HIGH VOLTAGE: 25000 X VOLTAGE: 5000
CALCULATED TURNS RATIO: 5.000
TEST VOLTAGE: 80V
A B C
RATIO 5.102 5.015 4.986
% DEVIATION 2.04 0.24 0.30
PHASE (min) 1.2 2.4 1.8
Iexc (mA) 20.6 10.5 7.78

SELECT: 1-PRINT 2-STORE 3-NEXT TEST


4-REPEAT TEST 5-MAIN MENU

Figure 6-8. Three-Phase Transformer Test Result Screen

1 PRINT: This selection prints out the test results.

2 STORE: This selection stores the test results.

3 NEXT TEST: This selection brings up the FULL TEST SETUP 3


screen (Figure 6-7). At this point you may specify
another pair of transformer taps to be tested.

4 REPEAT TEST: This selection repeats the last test. If the transformer
under test does not have any taps the Main Menu screen
appears.

5 MAIN MENU: This selection displays the MAIN MENU (Figure 6-1).

When test is completed with pauses between phases selected (YES chosen on
selection 7, Figure 6-6), the screen shown in Figure 6-9 (Phase A Test Result
Screen) appears after phase A test is complete.

If abnormal operating conditions occur during testing phase B or C of a three-


phase transformer, an error message (refer to Error Messages section) will appear
on the bottom of the screen followed by the message “ PRESS ANY KEY TO
CONTINUE.” In this case, if any key is pressed, the following message will
appear on the bottom of the screen:

AVTMTTR310 Rev 8 May 2016


79
M

“Select 1 – REPEAT TEST 2 – CONTINUE 3 – ABORT TEST”

If REPEAT TEST is selected, the test set will re-test phase B or C.

If CONTINUE is selected, the test set will start testing of phase C (if an error
message appeared during phase B testing).

If ABORT TEST is selected, the Main Menu screen will appear.

If one of these error messages appears, verify the abnormal condition by taking a
repeat measurement before attempting to take any corrective action. If an error
message appears during phase A testing, and repeat measurement is still bad, it is
impossible to continue testing of the transformer, and troubleshooting procedure
should be started by testing each phase of the three-phase transformer separately as
a single phase transformer.

THREE PHASE TRANSFORMER TEST


TEST: nnn ID:A13579CV0246 DIAG nn Ddnnn
TAPS TESTED: 3 - 16R
H VOLTAGE: 25000 X VOLTAGE: 5000
CALCULATED TURNS RATIO: 5.000
TEST VOLTAGE: 80V
A B C
RATIO 5.102
% DEVIATION 2.04
PHASE (min) 1.2
Iexc (mA) 20.6

SELECT: 1-REPEAT TEST 2 CONTINUE

Figure 6-9. Phase A Test Result Screen

1 REPEAT TEST: This selection allows repeat testing of the same phase
(last phase tested, A,B, or C). Refer to following
paragraphs.

2 CONTINUE: This selection will initiate testing of the next phase.


Refer to following paragraphs.

You may repeat testing of the phase (select 1 REPEAT) or continue testing the
transformer (select 2 CONTINUE). If 2 is selected, phase B will be tested. After
completion of the phase B testing, the test result will be displayed next to phase
A test results. The same two selections (1 REPEAT and 2 CONTINUE) are
shown on the screen. Selection 1 allows repeating of the phase B testing.
Selection 2 starts the phase C testing.

After completion of the phase C testing, the test result will be displayed next to
phase B test results. The same two selections are shown on the screen. Selection

AVTMTTR310 Rev 8 May 2016


80
OPERATION

1 allows repeating of the phase C testing. Selection 2 will bring up the five
selections shown in Figure 6-8.

If abnormal operating conditions occur during testing a transformer, an error


message will appear on the screen. Refer to Error Messages section. If one of
these messages appears, verify the abnormal condition by taking a repeat
measurement before attempting to take any corrective action.

AVTMTTR310 Rev 8 May 2016


81
M

Main Menu Screen When a Custom Transformer Setting Recalled


(Figure 6-10)
After selection of a custom transformer setting, the MAIN MENU will appear as
shown in Figure 6-10. It will display the main parameters of the saved custom
settings, including the H and X nameplate voltages, the diagram number and the
test set voltage. The ID number will be blank. The test number shows the
number of the next test to be run.

MAIN MENU
DATE (M/D/Y) : 06/15/1998 14:15

1 QUICK TEST SETUP TEST WINDING:


2 FULL TEST SETUP
3 RECALL CUSTOM SETTINGS * 7 H-X
4 SYSTEM SETUP MENU 8 H-Y
5 SAVED DATA MENU 9 CT
6 PRINT HEADER

TEST:002 ID nnnnnnnnnnnn DIAG 01 1ph0


TEST VOLTAGE: AUTO
H NAMEPLATE VOLTAGE (L-L): 250000
X NAMEPLATE VOLTAGE (L-L): 50000

ENTER SELECTION FROM KEYPAD

Figure 6-10. The Main Menu Screen After Selection of a Custom Transformer Setting

Full Test Setup 1, 2, and 3 screens will display the custom transformer setting
recalled.

AVTMTTR310 Rev 8 May 2016


82
OPERATION

SYSTEM SETUP Menu (Figure 6-11)


When selection 4 (SYSTEM SETUP MENU) on the MAIN MENU is chosen,
the SYSTEM SETUP MENU screen appears as shown in Figure 6-11.

SYSTEM SETUP

1 LANGUAGE: ENGLISH

2 SET DATE (M/D/Y)/TIME: 03/16/1998 11:45

3 STANDARD: ANSI

4 TEST VOLTAGE: AUTO

5 PHASE DISPLAY: DEGREES

6 MAIN MENU

ENTER SELECTION FROM KEYPAD

Figure 6-11. SYSTEM SETUP Screen

1 LANGUAGE: This selection allows a choice of six languages. See


Figure 6-12 for LANGUAGE screen.

2 SET DATE/TIME: This selection is for entering the date and time. Year has
four-digit representation (mm/dd/yyyy).

3 STANDARD: This selection is for entering the desired transformer


standard. Three transformer standards are available to
select from: ANSI, IEC, or AS (Australia Standard).

4 TEST VOLTAGE: This selection is for entering the desired test voltage.
There are four selections available:
AUTO the TTR310 will automatically test at the
highest allowable excitation voltage (80 V, 40 V, or 8 V),
depending on the transformer excitation current
measured.
80 V the test voltage is 80 Volts.
40 V the test voltage is 40 Volts.
8V the test voltage is 8 Volts.

AVTMTTR310 Rev 8 May 2016


83
M

5 PHASE DISPLAY: This selection allows a choice of the phase display units:
DEGREES, CENTIRADS or NONE. If DEGREES is
selected, any phase test results below 1 degree will be
displayed in minutes. If CENTIRADS is selected, the
phase test results will be displayed in centiradians (1
centiradian = 0.573 degrees). If NONE is selected, the
phase test results will not be displayed.

6 MAIN MENU: This selection returns you to the MAIN MENU screen.

LANGUAGE Screen (Figure 6-12)


Use this screen to select a language. Text on all screens except for the opening
display screen will appear in the language chosen.

LANGUAGE

1 ENGLISH

2 FRANCAISE

3 ESPANOL

4 PORTUGUESA

5 DEUTSCH

6 ITALIANA

ENTER SELECTION FROM KEYPAD

Figure 6-12. Language Screen

AVTMTTR310 Rev 8 May 2016


84
OPERATION

SAVED DATA Screen (Figure 6-13)


When 5 (SAVED DATA MENU) is selected on the MAIN MENU screen
(Figure 6-1), the SAVED DATA screen appears as shown in Figure 6-13.

SAVED DATA

1 VIEW READINGS

2 DELETE LAST READING

3 DELETE ALL READINGS

4 TRANSFER READINGS TO PC

5 MAIN MENU

ENTER SELECTION FROM KEYPAD

Figure 6-13. SAVED DATA Screen

Use this menu to view, delete, or transfer to a PC the saved test results.

1 VIEW READINGS: This selection allows you to specify the first test number
to view and then (on prompt) the number of tests to
view. The test results will be displayed on the screen. A
prompt line will show three prompts: 0 NEXT, 1
PRINT, and 2 EXIT. Select NEXT to view the next
reading in numerical order; select PRINT to print test
results; Select EXIT to return to SAVED DATA screen.

2 DELETE LAST This selection deletes from memory the last reading
READING: saved.

3 DELETE ALL This selection deletes all readings from memory.


READINGS:

4 TRANSFER This selection allows you to select which test results to


READINGS TO PC: transfer to a PC.

5 MAIN MENU: This selection returns you to the MAIN MENU screen
(Figure 6-1).

AVTMTTR310 Rev 8 May 2016


85
M

Recall (or Save) Custom Transformer Settings (Figure 6-14)


If 3 (RECALL CUSTOM SETTINGS) is selected on the MAIN MENU screen
(Figure 6-1), the RECALL CUSTOM SETTINGS screen appears as shown in
Figure 6-14.

If 8 (SAVE CUSTOM SETTINGS) is selected on the FULL TEST SETUP 2


menu (Figure 6-6), the screen appears the same as in Figure 6-14 except that the
headline will be changed to SAVE CUSTOM SETTINGS.
RECALL CUSTOM SETTINGS

DIAG TYPE H VOLTAGE X VOLTAGE


1 03 Dd0 250000 20000
2
3 12 Dyn5 67000 12000
4
5
6
7
8
9

0 PREVIOUS MENU
ENTER SELECTION FROM KEYPAD

Figure 6-14. Recall (or Save) Custom Settings Screen

The following message will be displayed if a selection without data is recalled:

NO DATA IN SELECTED CUSTOM SETTING, PRESS ANY KEY TO


CONTINUE.

The following message will be displayed if your selection to save data already
contains data:

CUSTOM SETTING 1 (i.e.) HAS DATA! OVERWRITE? 0 = YES, 1 = NO

Saved data will be overwritten by selecting YES.

Selecting NO will return you to the SAVE CUSTOM SETTINGS screen.

AVTMTTR310 Rev 8 May 2016


86
OPERATION

Error Messages
When an error message appears in the transformer test result screen indicating an
abnormal operating condition, verify the condition by taking a repeat
measurement before attempting to take any corrective action. Also, refer to the
Troubleshooting section for malfunctions and possible causes.
Open connections, wrong connections, open windings, shorted windings, high
resistance windings, other abnormal transformer problems, or a combination of
these may cause a large deviation from normal turn ratio or indicate an unusual
message. The unusual operating conditions may be caused by an abnormal
leakage reactance or capacitive coupling within the transformer windings. If
abnormal operating conditions occur during transformer testing, the following
error messages will appear on the quick test result screen and the transformer
test result screen, accompanied by three short beeps.
CHECK CONNECTIONS
This message indicates that the transformer is not connected to the test set. The
message may be caused by poor connection of one of the test leads, as well.
PHASE A (or B, or C) EXCITATION CURRENT TOO HIGH
This message indicates that excitation current exceeds 500 mA. Excitation
current can be reduced by using lower test voltages (40 V or 8 V).
TURNS RATIO TOO LOW, <0.8
This message shows that a transformer under test turn ratio is less than 0.8. The
TTR310 is not designed to test a transformer turn ratio under 0.8.
PHASE A (or B, or C) TURNS RATIO TOO HIGH
This message shows that a transformer under test turn ratio is higher than 10,000
(if 80 V or 40 V is used) or is higher than 4,000 (if 8 V is used). The message may
be caused by poor connection of one of the test leads, as well.
CHECK PHASE A (or B, or C) CONNECTIONS, REVERSED
This message is caused by incorrect connection of the H and X leads. The H and
X leads have either been reversed or the test transformer connections or
markings do not comply with the requirements of ANSI, IEC, or the Australian
standard. The message may be caused by wrong diagram number specified, as
well.

AVTMTTR310 Rev 8 May 2016


87
M

CHECK PHASE A (or B, or C) POLARITY


This message shows that the H or X test leads are incorrectly connected or the
test transformer connections or markings do not comply with the requirements
of ANSI, IEC, or the Australian standard.
If self-test fails, one of the following error messages will appear on the opening
display screen and you should return the test set to Megger for repair. Refer to
Repair section for instructions.
ANALOG OFFSET VOLTAGE HIGH
ANALOG GAIN OUT OF TOLERANCE
CAN NOT DETECT FLASH RAM
FAILED PROGRAM CODE CHECK
PLEASE SHUT DOWN AND CHECK THE MANUAL
CHECKING ALTERA: GOOD (BAD)
CHECKING DISPLAY: GOOD (BAD)
CHECKING RAM: GOOD (BAD)

AVTMTTR310 Rev 8 May 2016


88
OPERATION

Use with the Optional Printer


If you are using the optional printer, plug the printer cable into the
RS232/PRINTER receptacle on the TTR310 test set and turn it on. A separate
manual is supplied with the printer. Refer to it for specific information about
how to connect, operate, and care for the printer.

Select 6 PRINT HEADER on the main menu to print out a test report header.
Select 1 PRINT on the final quick test result screen or the three-phase
transformer test result screen to print out test results. A sample printout is
shown in Figure 6-15a, 6-15b, and
6-15c.
M
AUTOMATIC TRANSFORMER TURN RATIO TESTER
CATALOG NO. TTR310
________________________________________________

TRANSFORMER TEST REPORT


COMPAMY:______________________________________
SUBSTATION:____________________________________
MANUFACTURER:________________________________
TRANSFORMER RATING:________________kVA/MVA
AMBIENT TEMPERATURE:________________________
RELATIVE HUMIDITY:____________________________
TTR S/N:__9901245_______________________________
OPERATOR (S):___________________________________
_________________________________________________
COMMENTS/NOTES:

Figure 6-15a. Sample Test Report Header


DATE (M/D/Y) : 06/01/1999 12:25
TEST: 002
TRANSFORMER ID: 12A-76M/2
TYPE: SINGLE PHASE TRANSFORMER 1ph0
TAPS TESTED: 3 – 17
H VOLTAGE: 10000
X VOLTAGE: 10000
CALCULATED TURNS RATIO: 1.0000
TEST VOLTAGE: 8V

RATIO 1.0013
% DEVIATION 0.13
PHASE(min) -14.7
Iexc(ma) 0.03

Figure 6-15b. Sample Single Phase Test Report

AVTMTTR310 Rev 8 May 2016


89
M

DATE (M/D/Y) : 06/01/1999 1:25


TEST: 003
TRANSFORMER ID: CHQ12-5899D
TYPE: THREE PHASE TRANSFORMER Dd6
TAPS TESTED: 3 - 16L
H VOLTAGE: 250000
X VOLTAGE: 50000
CALCULATED TURNS RATIO: 5.0000
TEST VOLTAGE: 80V
A B C
RATIO 5.006 4.998 5.011
% DEVIATION 0.12 -0.04 0.22
PHASE(min) 5.3 6.5 7.9
Iexc(ma) 8.5 9.1 7.6

Figure 6-15c. Sample Three-Phase Test Report

AVTMTTR310 Rev 8 May 2016


90
7
TTR 300 Series PowerDB Lite User Manual
Introduction
PowerDB Lite is a free, but limited capability, version of the PowerDB software
tool that is designed specifically to control and/or extract data from Megger
instruments. The primary difference between PowerDB Lite and PowerDB is
that PowerDB is designed to work with all manufacturers’ equipment and has
field and office synchronization capabilities. PowerDB Lite will present your test
data into a professional looking data form that can be sent to a printer or .pdf file
distiller such as PDF995.

PowerDB Lite allows you to use a sub-set of the standard PowerDB forms that
are appropriate for specific Megger instruments. PowerDB Lite detects the
instrument and enables the appropriate form(s). Data can be entered on-screen
or captured directly while using the test instrument. Completed data forms can
be saved as files to your computer.

Minimum Recommended System


ƒ Operating System: Windows 2000 or later
ƒ RAM: 64 MB RAM minimum, 512+ MB RAM recommended
ƒ Processor: 300 MHz Pentium Class processor minimum, 1 GHZ or better
recommended

For information about the features of the full version of PowerDB please visit
our website at www.powerdb.com.

AVTMTTR310 Rev 8 May 2016 91


M

Software Installation
To install PowerDB Lite, load the PowerDB Lite CD into your CD-ROM drive
and follow the on-screen instructions.

1. Accept the terms of the License agreement.

2. Choose the destination location for the PowerDB Lite files.

AVTMTTR310 Rev 8 May 2016


92
TTR 300 Series PowerDB Lite User Manual

3. Select Default Settings.

4. InstallShield Wizard will complete the installation of PowerDB Lite. Click


Finish to close the installation program.

AVTMTTR310 Rev 8 May 2016


93
M

Using PowerDB Lite


1. Home
1. Select your Instrument from the Instrument Setup screen.

a. You can always view the Instrument Setup screen from the Tools
menu or F3.
b. Choose the appropriate selection from the screen below.

c. The TTR310E uses RS232 OR Ethernet communications (user


selectable).

a. Then Click OK on the Instrument Setup Screen to finish (Ethernet


only provided on TTR310E)

AVTMTTR310 Rev 8 May 2016


94
TTR 300 Series PowerDB Lite User Manual

2. Open a New Form


a. Select the File>New menu item, or type CTRL+N, or press the New
toolbar button.
b. The forms associated with the detected instrument will be shown in
the Select a Form screen.
c. Choose a form by double-clicking or by navigating with the arrow
keys and pressing the OK key.
d. See Specific Form Help Instructions for further instruction on test
steps. You can view the Form Help by pressing the F1 key once the
form is loaded.

AVTMTTR310 Rev 8 May 2016


95
M

3. Enter Test Data


a. Header and nameplate information can be manually typed into a
form.
b. Form fields with automation will now be colored cyan. Right-clicking
these fields will start the test.

c. To change the settings of the TTR place the mouse on the form and
right-click. Then select “TTR Settings”.

d. This dialog box allows you to change the TTR settings.


4. Comments and Deficiencies
AVTMTTR310 Rev 8 May 2016
96
TTR 300 Series PowerDB Lite User Manual

When imported into the full version of PowerDB, the comments and
deficiencies on each form are used to generate summary reports. These summary
reports repeat the notations and lists the page number where reported. This
allows the user to scroll to a particular page to view a reported anomaly. For
more information on features of PowerDB visit us at our website at
www.PowerDB.com.
5. Save the Data
a. Select the File>Save menu item, or press CTRL+S, or press the Save
toolbar button.
b. The Save As screen will allow you to specify a location and file name
for your PowerDB Lite XML file.

AVTMTTR310 Rev 8 May 2016


97
M

6. Opening an Existing File


a. Select the File> Open menu item.

b. Browse to the file you would like to open.


c. Press the Open dialog button.
d. If the file contains multiple test dates, select the date that you would
like to open for editing or select New to append a new set of results
to the file. To remove a set of results, click on the selected file and
press the delete button.

AVTMTTR310 Rev 8 May 2016


98
TTR 300 Series PowerDB Lite User Manual

7. Loading Data Files


When testing with the TTR 320 or TTR 330 you may load files saved on the
instrument’s USB drive. Refer to Step 7 for instructions on selecting and opening
files.
8. Setting the Logos
a. Select the Tools>Options menu item.
b. The Logos section specifies paths to the left and right logos files to
use.
c. To change the left logo press the “…” button by the left logo path.
d. The Open screen allows you to browse to a file location, select a
.JPG or .BMP file, and press the Open button.
e. Repeat steps (c) and (d) for the right logo path.
f. Note that a logo will not be shown if the logo file path is blank or the
file does not exist.
g. Note after specifying the logo files the image will not be shown until
the next time a form is opened (File>Open, or the File>New menu
items).
h. Note that the logos will look the best if the resolution of the file is
pixels wide by 240 pixels high. DPI is not important.

AVTMTTR310 Rev 8 May 2016


99
M

9. How to change Languages


a. Select the Tools>Options menu item.
b. Select the appropriate language in the dropdown menu.

10. How to change units of measurement


a. Select the Tools> Options menu item.
b. Select the units in the drop down Default Units under Measurements.

AVTMTTR310 Rev 8 May 2016


100
TTR 300 Series PowerDB Lite User Manual

11. Additional Notes


a. Additional forms can be filled out by repeating steps 2, 3 and 6.
b. Forms can be printed with the File>Print menu item, or type
CTRL+P, or press the Print toolbar button.
c. A help guide may be found in the Help>PowerDB Lite Help menu
item.

AVTMTTR310 Rev 8 May 2016


101
M

Specific Form Help Instructions


Operating Instructions for the Multiple Quick Test Form
a. Type in the asset ID and then press the Enter key.
b. Use the left and right arrow keys to select the high-side winding
configuration.
c. Press the Enter or Tab key.
d. Use the left and right arrow keys to select the low-side winding
configuration.
e. Press the Enter or Tab key.
f. Select the test voltage from the dropdown menu, then press Enter or
Tab.
g. Type in the high side tap number and press the Enter key.
h. Type in the high side voltage and press the Enter key.
i. Type in the low side tap number and press the Enter key.
j. Type in the low side voltage and press the TEST key (F2) or right
click on the blue highlighted fields.
k. Hit the Enter key and repeat for each tap you would like to test.

AVTMTTR310 Rev 8 May 2016


102
TTR 300 Series PowerDB Lite User Manual

Operating Instructions for the Simple 3PH TTR Form


This form can be used for testing a two or three winding transformer with
multiple taps on one or more of the windings.

If you are testing a three winding transformer please check the “Has Tertiary”
checkbox.

Next select the winding configuration by using the left and right arrow keys.
Press the Enter or Tab key to move to the next field.

The default total number of tests is defined as follows:

1. Test for each secondary (or tertiary) tap tested with the primary nominal tap.

2. Test for each primary tap with the nominal secondary (or tertiary) tap.

If you do not wish to test all of the secondary or tertiary taps you can reduce the
“# tests” field for each category of tests (primary, secondary, tertiary).

Once the total number of taps and the # tests field are entered the form will
display the correct number of rows to perform testing.

Once the voltage is entered for the first and last tap values (from the
transformer’s nameplate tap voltage table), the ratios for all taps will
automatically be calculated and populated. Please note that the calculated values
can be over written.

Right click on each of the blue highlighted fields in each table to run the tests.

AVTMTTR310 Rev 8 May 2016


103
M

Operating Instructions for the 3PH TTR with TAP Changer Form
The procedure for this form is the same as the Simple TTR form. The only
difference is that it allows the user to enter additional nameplate information.

AVTMTTR310 Rev 8 May 2016


104
TTR 300 Series PowerDB Lite User Manual

Specific Form Help Instructions


Operating Instructions for the Multiple Quick Test Form
a. Type in the asset ID and then press the Enter key.
b. Use the left and right arrow keys to select the high-side winding
configuration.
c. Press the Enter or Tab key.
d. Use the left and right arrow keys to select the low-side winding
configuration
e. Press the Enter or Tab key.
f. Select the test voltage from the dropdown menu, then press Enter or
Tab.
g. Type in the high side tap number and press the Enter key.
h. Type in the high side voltage and press the Enter key.
i. Type in the low side tap number and press the Enter key.
j. Type in the low side voltage and press the TEST key (F2) or right
click on the blue highlighted fields.
k. Hit the Enter key and repeat for each tap you would like to test.

AVTMTTR310 Rev 8 May 2016


105
M

Operating Instructions for the Simple 3PH TTR Form


This form can be used for testing a two or three winding transformer with
multiple taps on one or more of the windings.

If you are testing a three winding transformer please check the “Has Tertiary”
checkbox.

Next select the winding configuration by using the left and right arrow keys.
Press the Enter or Tab key to move to the next field.

The default total number of tests is defined as follows:


1. Test for each secondary (or tertiary) tap tested with the primary nominal tap.
2. Test for each primary tap with the nominal secondary (or tertiary) tap.

If you do not wish to test all of the secondary or tertiary taps you can reduce the
“# tests” field for each category of tests (primary, secondary, tertiary).

Once the total number of taps and the # tests field are entered the form will
display the correct number of rows to perform testing.

Once the voltage is entered for the first and last tap values (from the
transformer’s nameplate tap voltage table), the ratios for all taps will
automatically be calculated and populated. Please note that the calculated values
can be over written.

Right click on each of the blue highlighted fields in each table to run the tests.

AVTMTTR310 Rev 8 May 2016


106
TTR 300 Series PowerDB Lite User Manual

Operating Instructions for the 3PH TTR with TAP Changer Form
The procedure for this form is the same as the Simple TTR form. The only
difference is that it allows the user to enter additional nameplate information.

AVTMTTR310 Rev 8 May 2016


107
M

AVTMTTR310 Rev 8 May 2016


108
8
Service
Maintenance
Maintenance should be performed only by qualified persons familiar with the
hazards involved with high-voltage test equipment. Read and understand Section
2, Safety, before performing any service.
The TTR310 test set is sturdily constructed and requires no periodic
maintenance. Routine maintenance is all that is required for the TTR310 test sets.
Inspect the cable assemblies occasionally to ensure they are in good condition.
The appearance of the TTR310 test set can be maintained by occasionally
cleaning the case, panel and cable assemblies. Clean the outside of the carrying
case with detergent and water. Dry with a clean, dry cloth. Clean the control
panel with a cloth dampened with detergent and water. Do not allow water to
penetrate panel holes, because damage to components on the underside may
result. An all-purpose, household spray cleaner can be used to clean the panel.
Polish with a soft, dry cloth, taking care not to scratch the display screen cover.
Clean the cables and mating panel receptacles with isopropyl or denatured
alcohol applied with a clean cloth.

Fuse Replacement
The TTR310 is protected by two mains fuses. Fuse replacement is indicated if
the electronic circuits do not function. Refer fuse replacement to qualified
personnel only. To avoid electric shock and fire hazard, use only the fuses
specified on Instrument panel. Note that 2 spare fuses are included with each
TTR.

F WARNING
Before replacing the fuses, disconnect the power input plug
from the live power source.

To replace fuse(s), proceed as follows:

1. Remove power cord.

2. Pry door open at socket.

3. Lift and swing door into socket.

4. Lift fuse holder out of housing.

AVTMTTR310 Rev 8 May 2016 109


M

5. Install one (1) AG fuse or two (2) metric fuses*.

6. Replace fuse holder into housing.

7. Swing and snap door back in place.

*Install fuses on one side only, do not install both AG and metric fuses at the
same time

AVTMTTR310 Rev 8 May 2016


110
Service

Voltage Selection
To change selected voltage: open cover, using small blade screwdriver or similar
tool; set aside cover/fuse block assembly; pull voltage selector card straight out
of housing, using indicator pin; orient selector card so that desired voltage is
readable at the bottom; orient indicator pin to point up when desired voltage is
readable at bottom (note that when indicator pin is fixed, successive voltages are
selected by rotating the card 90° clockwise); insert voltage selector card into
housing, printed side of card facing forward toward IEC connector and edge containing the
desired voltage first; replace cover, and verify that indicator pin shows the desired
voltage.

Voltage Selector Card Orientation

3. Insert a pocket screwdriver at point “X” as shown. Gently lift UP until the
entire door lifts up approximately 1/4" (minimum).

Gently lift UP until the entire door lifts up approximately ¼-inch (minimum).

4. Once lifted, the door will pivot on its hinges and expose the fuse holder.

AVTMTTR310 Rev 8 May 2016


111
M

5. When the fuse holder is installed in the single fuse position, apply the
screwdriver as shown and gently pry up. Use screwdriver as shown, do not
use fingers.

When the fuse holder is installed in the dual fuse position, it would normally
release as soon as the door is open.

Calibration
A complete performance and calibration check should be made at least once
every year. This will ensure that the TTR310 test set is functioning and calibrated
properly over the entire measurement range. The 3-phase TTR310 calibration is
performed on each new or repaired unit before sending it to a customer. There is
a special 3-phase TTR310 final calibration procedure which requires a NIST-
traceable test equipment to be used. As a result of such calibration procedure,
each TTR310 test set may be NIST certified.

To check the 3-phase TTR310 calibration at a customer site or in the field, the
Megger TTR Check Box (Catalog No. 550555) or equivalent standard should be
used.

To perform a quick simplified calibration check, the Megger TTR Check Box
(Catalog No. 550555) may be used. The last standard has eleven switchable turns
ratio settings which cover the turns ratio range from 0.8:1 to 2000:1. Using these
Calibration Standards will confirm proper calibration of TTR310 test set.

AVTMTTR310 Rev 8 May 2016


112
Service

3-Phase TTR310 Test Set Functional Test


A customer may want to make sure that the test set is functioning properly
before testing a transformer. Traditionally, for the transformer turns ratio testers,
a customer performed this test by connecting H1-X1 and H2-X2 test leads. The
1:1 turns ratio was expected to be measured. Additionally, the displayed test
results were interpreted as a test set calibration check.

The 3-phase TTR310 test set is designed and optimized for the transformer turns
ratio testing. It uses a mixed analog-digital technique to provide the high accurate
readings of the tested transformer turns ratio. The test set measurement
approach is based on high impedance input and output transformer voltage
monitoring circuits. The high impedance of the monitoring circuits is optimized
for the accurate transformer turns ratio testing.

When performing a 3-phase TTR310 functional test, the H and X test leads
interconnect the input and output monitoring circuits without a transformer
being connected. Such connection cause an impedance mismatch and, as a result
of the mismatch, the displayed turns ratio reading is not exactly 1:1 as it may be
expected. A customer should be aware that a functional test is not a real
transformer turns ratio test. Due to the intrinsic and inevitable impedance
mismatching, the 3-phase TTR310 functional test readings may be from 0.9980
to 1.0020. The TTR310 functional test readings do not represent its calibration.
It simply shows that the TTR310 test set circuitry functions properly. To check
the 3-phase TTR310 calibration, a customer should use the Calibration Standards
mentioned in Calibration section of the manual.

To perform a 3-phase TTR310 functional test proceed as follows:


1. Turn TTR310 test set power off.
2. Connect H1 lead to X1 lead, H2 lead to X2 lead, H3 lead to X3 lead, and H0
lead to X0 lead. Make sure the leads are properly connected.
3. Turn TTR310 test set power on.
4. After self-test is complete and the main menu screens appear, select 4, and
then select 4 and enter 80 V. On the same menu select 6.
5. When the Main menu appears, select 1.
6. When the Quick test setup menu appears, select 2 and enter 7. The
transformer type entry displays DIAG 07 YNyn0.

WARNING
Do not continue functional test if the QUICK TEST SETUP menu
does not display DIAG 07 YNyn0 transformer type.
Keep the leads, which are energized, clear of ground, and
personnel.

7. Select 3, START TEST on QUICK TEST SETUP menu.

AVTMTTR310 Rev 8 May 2016


113
M

8. The readings for phases A, B, and C should be:

RATIO: 1.0000 ±0.0020

PHASE(min): 0 ±5

Iexc (mA): 0.0 to 0.5

If needed, perform the test according to steps 1 through 8 for the excitation
voltage 40 V, and then for the excitation voltage 8 V. The readings should be the
same as shown in step 8.

AVTMTTR310 Rev 8 May 2016


114
Service

Troubleshooting
The Troubleshooting Guide, Table 7-1, is arranged to help you evaluate the
reasons for TTR310 test set malfunction. The table lists possible test set
malfunctions which may be encountered during operation and lists possible
causes. Electronic circuit repairs should not be attempted in the field. Refer to
Repair section. Refer to Section 8 for a list of spare parts.
Table 7-1. Troubleshooting Guide
MALFUNCTION POSSIBLE CAUSE
ƒ No service power.
ƒ Defective line cord.
Display stays blank after POWER switch is turned
ƒ Defective fuse(s).
on.
ƒ CONTRAST potentiometer not adjusted.
ƒ Defective display or electronics.
Error message:
ANALOG OFFSET VOLTAGE HIGH
Out of tolerance condition(s) in measurement
and/or
circuit.
ANALOG GAIN OUT OF TOLERANCE
appears after self-test is complete.
ƒ Defective lamp.
Red TEST VOLTAGE ON lamp does not light on ƒ EMERGENCY TEST OFF switch is not
start of testing. released.
ƒ Problem in measuring circuit.
One of the following messages appear on the test
result screen.
ƒ Abnormal operating condition.
ƒ CHECK CONNECTIONS
ƒ Incorrect setting of TRANSFORMER TYPE in
ƒ PHASE A (or B, or C) EXCITATION
the quick test setup or the full test setup 1
CURRENT TOO HIGH;
menus.
ƒ TURNS RATIO TOO LOW, <0.8; or
ƒ Incorrect connection of leads.
PHASE A (or B, or C) TURNS RATIO
ƒ Defective test leads.
TOO HIGH;
ƒ Incorrect marking of a transformer.
ƒ CHECK PHASE A (or B, or C)
ƒ Problem in test specimen.
CONNECTIONS, REVERSED;
ƒ Problem in measuring circuit.
ƒ CHECK PHASE A (or B, or C)
POLARITY
ƒ Defective test leads (open circuit, poor
connection).
RATIO and/or Iexc (mA) readings erratic. ƒ Severe abnormal transient in service power.
ƒ Problem in test specimen (poor connection).
ƒ Problem in measuring circuit.
ƒ Printer power not turned on.
Cannot obtain printout when printer is connected. ƒ Printer battery discharged.
ƒ Problem in measuring circuitry.

AVTMTTR310 Rev 8 May 2016


115
M

Repair
Megger offers a complete repair and calibration service and recommends that its
customers take advantage of this service in the event of equipment malfunction.
Contact your MEGGER representative for instructions and a return
authorization (RA) number. Equipment returned for repair should be shipped
prepaid and insured and marked for the attention of the Repair Department.
Please indicate all pertinent information including problem symptoms and
attempted repairs. The catalog number and serial number of the test set should
also be specified. Pack the TTR310 test set, including all cables, in a carton
(original shipping carton if available) with adequate dunnage in accordance with
best commercial practice. Seal the carton with waterproof tape.

Ship to: M
Valley Forge Corporate Center
2621 Van Buren Avenue
Norristown, PA 19403 U.S.A.

AVTMTTR310 Rev 8 May 2016


116
Glossary

Use only in accordance with instruction manual.

Protective ground (earth) terminal is the wing nut for connecting the test
set to earth ground.

ANSI American National Standards Institute

BCT Bushing current transformer

CEI/IEC The initials of the official French name, Commission Electrotechnique


Internationale, of the International Electrotechnical Commission.

Centiradian Phase display option in SYSTEM SETUP screen. 1 centiradian =


0.573 degrees.

CT Current transformer

LCD Liquid crystal display

LTC Load tap changer. A selector switch device used to change transformer
taps with the transformer energized and carrying full load.

Safety ground An insulated stick (sometimes called a hot stick) with a hook type
stick electrode connected to ground via an insulated cable. In some
discharge sticks, a resistor is connected between the electrode and the
ground cable. Both are used to discharge capacitive specimens by
providing a low-impedance path to ground. They must be suitable
rated for the voltage and capacitance of the specimen to be discharged.

transient A change in the steady-state condition of voltage or current, or both.

TTR Transformer turn ratio; a registered trademark of Megger.

turn ratio The ratio of the number of turns in a higher voltage winding to that in
a lower voltage winding.

AVTMTTR310 Rev 8 May 2016 117


M

AVTMTTR310 Rev 8 May 2016


118

You might also like