LWEB-900

Building Management System

User Manual

LOYTEC electronics GmbH


Contact

LOYTEC electronics GmbH


Blumengasse 35
1170 Vienna
AUSTRIA/EUROPE
[email protected]
http://www.loytec.com

Version 2.2

Document № 88081507

LOYTEC MAKES AND YOU RECEIVE NO WARRANTIES OR CONDITIONS,


EXPRESS, IMPLIED, STATUTORY OR IN ANY COMMUNICATION WITH YOU,
AND
LOYTEC SPECIFICALLY DISCLAIMS ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. THIS
PRODUCT IS NOT DESIGNED OR INTENDED FOR USE IN EQUIPMENT
INTENDED FOR SURGICAL IMPLANT INTO THE BODY OR OTHER
APPLICATIONS INTENDED TO SUPPORT OR SUSTAIN LIFE, FOR USE IN
FLIGHT CONTROL OR ENGINE CONTROL EQUIPMENT WITHIN AN
AIRCRAFT, OR FOR ANY OTHER APPLICATION IN WHICH IN THE FAILURE
OF SUCH PRODUCT COULD CREATE A SITUATION IN WHICH PERSONAL
INJURY OR DEATH MAY OCCUR. LOYTEC MAKES NO REPRESENTATION
AND OFFERS NO WARRANTY OF ANY KIND REGARDING OF ANY
THIRDPARTY COMPONENTS MENTIONED IN THIS MANUAL.

No part of this publication may be reproduced, stored in a retrieval system, or transmitted,


in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise,
without the prior written permission of LOYTEC.

LC3020, L-Chip, L-Core, L-DALI, L-GATE, L-INX, L-IOB,


LIOB-Connect, LIOB-FT, L-IP, LPA, L-Proxy, L-Switch, L-Term,
L-VIS, L-WEB, L-ZIBI and ORION™ stack are trademarks of LOYTEC
electronics GmbH.

LonTalk®, LONWORKS®, Neuron®, LONMARK®, LonMaker®, i.LON®, and LNS® are


trademarks of Echelon Corporation registered in the United States and other countries.
LWEB-900 User Manual 3 LOYTEC

Contents

1 Introduction .................................................................................................. 9
1.1 Overview .............................................................................................................. 9
1.2 Operating and Monitoring ............................................................................... 10
1.3 Device Configuration ........................................................................................ 11
1.4 Global Connections ........................................................................................... 11
1.5 Parameter View ................................................................................................. 11
1.6 Alarming ............................................................................................................ 11
1.7 Scheduling .......................................................................................................... 11
1.8 Trending ............................................................................................................. 12
1.9 Reporting ........................................................................................................... 12
1.10 Multiuser System ............................................................................................... 12
1.11 Event Log ........................................................................................................... 13
1.12 Licensing ............................................................................................................ 13
1.13 Supported Devices ............................................................................................. 13
1.14 Scope................................................................................................................... 16
2 What’s New in LWEB-900 ........................................................................ 17
2.1 New in LWEB-900 2.2.0.................................................................................... 17
2.2 New in LWEB-900 2.1.0.................................................................................... 18
2.3 New in LWEB-900 2.0.0.................................................................................... 22
2.4 New in LWEB-900 1.3.0.................................................................................... 28
3 Installation .................................................................................................. 32
3.1 Software Installation ......................................................................................... 32
3.2 Product Activation ............................................................................................ 32
3.3 Firewall Configuration ..................................................................................... 35
4 System Tray Icon ........................................................................................ 36
5 LWEB-900 Server ...................................................................................... 37
5.1 Manage Projects ................................................................................................ 37
5.2 Password Protection.......................................................................................... 39
5.3 Network Settings ............................................................................................... 39
5.4 Certificate Management ................................................................................... 40
5.5 Proxy Settings .................................................................................................... 42
5.6 Backup/Restore ................................................................................................. 42
5.6.1 Manual Backup ........................................................................................ 42
5.6.2 Scheduled Backup .................................................................................... 43
5.6.3 Restore ..................................................................................................... 44

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 4 LOYTEC

5.7 Database Engines .............................................................................................. 45


5.8 Communication Statistics ................................................................................. 47
6 LWEB-900 Client ....................................................................................... 49
6.1 Login .................................................................................................................. 49
6.1.1 Default user ............................................................................................. 50
6.1.2 Kiosk Mode ............................................................................................. 51
6.1.3 Command Line Options ........................................................................... 51
6.2 User Interface Overview .................................................................................. 51
6.3 Navigation View ................................................................................................ 53
6.4 Object List View ............................................................................................... 55
6.5 BACnet Configuration ..................................................................................... 59
6.6 Add Devices ....................................................................................................... 64
6.7 Configure LOYTEC Devices ........................................................................... 72
6.8 Identification Key ............................................................................................. 74
6.9 Advanced Search and Search View ................................................................. 78
6.10 Watch View ....................................................................................................... 80
6.11 Graphical View ................................................................................................. 83
6.11.1 Operate Graphical View .......................................................................... 84
6.11.2 Configure Graphical View....................................................................... 86
6.11.3 Graphical View Templates ...................................................................... 89
6.11.4 Graphical Views in LWEB-900 Server and in LOYTEC device ............ 90
6.12 Parameter View ................................................................................................ 92
6.12.1 Operate Parameter View.......................................................................... 92
6.12.2 Configure Parameter View ...................................................................... 94
6.12.3 Parameter View Templates ...................................................................... 96
6.13 Web View .......................................................................................................... 97
6.14 Alarming ............................................................................................................ 98
6.14.1 Alarm View ............................................................................................. 99
6.14.2 System Alarms ....................................................................................... 103
6.14.3 Alarm Notification................................................................................. 104
6.14.4 Alarm Log ............................................................................................. 107
6.15 Scheduling ....................................................................................................... 108
6.15.1 Device Schedulers ................................................................................. 108
6.15.2 LWEB-900 Server Schedulers............................................................... 108
6.15.3 Master Scheduler View ......................................................................... 110
6.16 Trending .......................................................................................................... 124
6.16.1 Trend Log Size Limitation .................................................................... 125
6.16.2 Device Trend Logs ................................................................................ 126
6.16.3 LWEB-900 Server Trend Logs ............................................................. 128

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 5 LOYTEC

6.16.4 Trend Log View ..................................................................................... 131


6.16.5 Trend Chart View .................................................................................. 135
6.17 Reporting ......................................................................................................... 141
6.17.1 Report View ........................................................................................... 141
6.17.2 Configure Reports .................................................................................. 142
6.17.3 Trigger a report manually....................................................................... 147
6.17.4 Report Templates ................................................................................... 148
6.18 E-Mail Notification ......................................................................................... 156
6.19 Event View ....................................................................................................... 157
6.20 Global Connections ......................................................................................... 161
6.21 File Objects ...................................................................................................... 165
6.22 Device Management View .............................................................................. 167
6.22.1 Device Overview.................................................................................... 169
6.22.2 Firmware Update.................................................................................... 171
6.22.3 Device Configuration ............................................................................. 177
6.22.4 Program Files ......................................................................................... 181
6.22.5 LWEB-800/802 files .............................................................................. 184
6.22.6 Backup and Restore ............................................................................... 187
6.22.7 File Selection Dialog.............................................................................. 191
6.22.8 Manage Files .......................................................................................... 192
6.23 Perspectives...................................................................................................... 193
6.24 Device Communication Profiles ..................................................................... 195
6.25 System Registers .............................................................................................. 197
6.26 Offline Mode .................................................................................................... 197
6.27 User Management ........................................................................................... 198
6.28 Access Rights ................................................................................................... 202
6.29 L-Studio Projects ............................................................................................. 205
7 WEB Access .............................................................................................. 207
7.1 Navigation Menu and System Menu .............................................................. 209
7.2 Global Settings ................................................................................................. 210
7.3 Project Settings ................................................................................................ 210
7.4 Error Handling ................................................................................................ 213
7.5 Statistics ........................................................................................................... 213
7.6 System Log ....................................................................................................... 213
8 Interfaces ................................................................................................... 214
8.1 Trend Log CSV File ........................................................................................ 214
8.2 Alarm Log CSV File ........................................................................................ 215
8.3 Identification Key CSV File ........................................................................... 215
8.4 Database Interface .......................................................................................... 216

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 6 LOYTEC

8.4.1 Datalog Configuration Table (DatalogConfig) ...................................... 216


8.4.2 Log Information Table (LogInfo) .......................................................... 216
8.4.3 Log Item Information Table (LogItemInfo)........................................... 217
8.4.4 Trend Log Table (TrendLog) ................................................................ 217
8.4.5 Alarm Log Table (AlarmLog) ............................................................... 218
8.5 Report Template ............................................................................................. 220
8.5.1 Report Template XML file .................................................................... 220
8.5.2 Microsoft Report File Definition ........................................................... 224
8.5.3 Image File .............................................................................................. 226

9 Troubleshooting ........................................................................................ 227


9.1 Technical Support ........................................................................................... 227
9.2 Bug Reports ..................................................................................................... 228
10 Specifications ............................................................................................ 230
10.1 System requirements ...................................................................................... 230
11 References ................................................................................................. 232
12 Revision History ....................................................................................... 233

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 7 LOYTEC

Abbreviations

100Base-T ........................... 100 Mbps Ethernet network with RJ-45 plug


Aggregation ......................... Collection of several CEA-709 packets into a single CEA-852
packet
APDU.................................. Application Protocol Data Unit
AST ..................................... Alarming, Scheduling, Trending
BACnet ............................... Building Automation and Control Network
BOOTP ............................... Bootstrap Protocol, RFC 1497
CA ....................................... Certification Authority
CAT .................................... Composite Automation Type
CEA-709 ............................. Protocol standard for LONWORKS networks
CEA-852 ............................. Protocol standard for tunneling CEA-709 packets over IP
channels
CN ....................................... Control Network
COV .................................... change-of-value
CR ....................................... Channel Routing
CS........................................ Configuration Server that manages CEA-852 IP devices
DA ....................................... Data Access (Web service)
DHCP .................................. Dynamic Host Configuration Protocol, RFC 2131, RFC 2132
DIF, DIFE ........................... Data Information Field, Data Information Field Extension
DL ....................................... Data Logger (Web service)
DNS .................................... Domain Name Server, RFC 1034
DST ..................................... Daylight Saving Time
GMT.................................... Greenwich Mean Time
HDD .................................... Heating Degree Days
IP ......................................... Internet Protocol
IP-852.................................. logical IP channel that tunnels CEA-709 packets according
CEA-852
LSD Tool ............................ LOYTEC System Diagnostics Tool
MAC ................................... Media Access Control
MD5 .................................... Message Digest 5, a secure hash function, see Internet
RFC 1321
M-Bus ................................. Meter-Bus (Standards EN 13757-2, EN 13757-3)
MS/TP ................................. Master/Slave Token Passing (this is a BACnet data link layer)
NAT .................................... Network Address Translation, see Internet RFC 1631
NV ....................................... Network Variable
OPC ..................................... Open Process Control
PLC ..................................... Programmable Logic Controller
RNI...................................... Remote Network Interface
RSTP ................................... Rapid Spanning Tree Protocol (Standard IEEE 802.1D-2004)
RTT ..................................... Round-Trip Time
RTU .................................... Remote Terminal Unit
SCPT ................................... Standard Configuration Property Type
SHA..................................... Secure Hash Algorithm

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 8 LOYTEC

SL ....................................... Send List


SMTP ................................. Simple Mail Transfer Protocol
SNTP .................................. Simple Network Time Protocol
SSH..................................... Secure Shell
SSL ..................................... Secure Socket Layer
STP ..................................... Spanning Tree Protocol (Standard IEEE 802.1D)
TLS ..................................... Transport Layer Security
UCPT .................................. User-defined Configuration Property Type
UI ........................................ User Interface
UTC .................................... Universal Time Coordinated
VIF, VIFE ........................... Value Information Field, Value Information Field Extension
XML ................................... eXtensible Markup Language

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 9 LOYTEC

1 Introduction

1.1 Overview
LWEB-900 is an innovative and comprehensive solution for building management. The
software covers the whole sequence of activities, from installation of the building
management system through configuring the devices, all the way to daily operation of the
facilities. Thus, a common user interface is available at all phases of the project.

Figure 1: LWEB-900 Client User Interface

The central component is the LWEB-900 Server, which stores all configuration data in a
database and communicates with the devices of the building management system in real
time. The LWEB-900 Client is the user interface of the building management system. When
a user starts the client, he has to log on to the server before receiving access. Client and
server exchange data using web services only. Due to this system architecture, remote
access is easily possible through firewalls and NAT routers. In addition, differences
between the various field bus technologies (CEA-709, BACnet, DALI, MBus, Modbus,
KNX, etc.) are compensated and the user is presented with a consolidated view of the
separate systems.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 10 LOYTEC

Figure 2: LWEB-900 System Architecture

To operate and monitor the building technical equipment a standard web browser can be
used. In this way it is possible to quickly check the status of the building automation system
while travelling. It makes no difference, whether a smart phone, tablet, or PC is used.
Compared to the LWEB-900 Client, the functionality of the web application is limited to
the daily operation of the building and does not include the functionality to install and
configure the system.

Figure 3: Graphical View on a Mobile Device

1.2 Operating and Monitoring


In LWEB-900, all areas of a building are visualized and operated using installation
schematics. Each schematic can consist of a large number of dynamic display elements
which reflect the current status of the facilities. These display elements also include
complex elements like alarms, trend logs and schedules.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 11 LOYTEC

The configuration software to design the graphical representation of the installation is built
directly into LWEB-900. It allows users to easily create dynamic graphics without requiring
any programming knowledge.

1.3 Device Configuration


LWEB-900 manages and configures all LOYTEC devices based on a central database. The
set-up of the devices can be changed very comfortably because the required configuration
software is built directly into LWEB-900. It is also easily possible to update the firmware of
all devices and to perform backups.

1.4 Global Connections


With LWEB-900 it is easy to connect data points of different LOYTEC devices. For this
purpose, a global connection can simply be created and drag&drop can be used to add input
and output data points. LWEB-900 configures all devices which are part of the global
connection accordingly. After the connection has been configured, the devices exchange
data directly over TCP/IP.

1.5 Parameter View


The parameter view allows configuring operational parameters, which are distributed over
multiple devices, efficiently. For example, parameters for room temperature control, light
control, or sunblind control can be organized in different parameter views. Each parameter
view is a matrix where each cell represents a parameter. Parameters can be organized freely
in the matrix depending on space layout and function. In this way, it is possible to e.g.
adjust the running periods of sun blinds across many rooms with a few mouse clicks and
write the new values reliably into the corresponding automation devices.

1.6 Alarming
With LWEB-900, alarms from different sources can be visualized and managed in a
uniform manner. For example, an L-DALI device can generate alarms in case of a ballast
failure or if the emergency light test fails. On the other hand, a L-INX device controls the
air handling unit and triggers an alarm if the V-belt is torn or if the air filter is dirty. In
LWEB-900, these alarms are presented in a common view and the user can acknowledge or
disable them.

When an alarm occurs, one or multiple receivers can be notified via e-mail. A scheduler can
be used to control who is notified about alarms at a specific date and time. If the alarm is
not acknowledged within a configurable amount of time, an alternative action can be
triggered.

1.7 Scheduling
Schedules can be either executed in LOYTEC devices or directly in the LWEB-900 Server.
To optimize the reliability of the system, create schedulers at the same location as the
corresponding control logic. For example, an occupancy scheduler should be executed by
the L-INX automation controller which primarily uses this information, whereas a scheduler
determining which people are notified about alarms should be executed by the LWEB-900
Server.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 12 LOYTEC

LWEB-900 offers the unique possibility of organizing schedules in a hierarchical way,


independently of where they are executed. The resulting tree structure permits defining
entries which apply to all schedulers or only a subset. For example, a standard occupancy
schedule can be defined for a whole building. This global schedule can be modified for
certain areas of the building. The area specific entries can in turn be supplemented by room
specific entries.

After the schedule hierarchy has been defined, LWEB-900 calculates the resulting
configurations. If a scheduler is executed by in a LOYTEC device, LWEB-900 downloads
the configuration.

1.8 Trending
LOYTEC devices can record the value of data points over time. However, the memory
available on a device is limited. LWEB-900 overcomes this restriction by reading out the
trend data from the devices periodically and storing everything in the database.

A user can also create ad-hoc trend logs directly in LWEB-900. This is the fastest way to
create a trend log. One simply selects a data point and activates trending using the context
menu. LWEB-900 periodically polls the data point value from the device and stores the
value in the database.

Trend logs can be viewed either as tables or as charts. Especially for trend charts, a large
number of customization options are available.

1.9 Reporting
LWEB-900 can create reports based on trend logs. Reports can be used, for example, to
document the energy consumption in a building. The generation of a report can be trigger in
one of the following ways:

 Periodically: Reports can be generated daily, weekly, monthly, or yearly.

 Event: The change of a data point value can trigger a report.

 Manually: A report can be triggered manually by the user.

Reports can be generated in PDF, Excel, or Word format. They can be automatically
distributed via e-mail.

1.10 Multiuser System


LWEB-900 provides a separate work environment for each user. A user has to log on to the
system and is presented with a perspective tailored to his individual requirements. A
perspective defines which windows are open and how they are arranged. In this way, a user
can define separate perspectives which are optimized for different tasks and quickly switch
between them.

LWEB-900 uses access control lists to define which operations a user can perform on a
certain object (e.g. folder, data point, graphical view, parameter view, trend chart). To
speed up the access right configuration, access control lists can be inherited from parent to
child objects.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 13 LOYTEC

1.11 Event Log


All events are logged by LWEB-900 in the database. Events include alarms, alarm
acknowledgements, log-in and log-out of users, change of operational parameter, change of
device configuration, system messages, etc. The event log view offers a large variety of
filters to efficiently analyze all activities in LWEB-900.

1.12 Licensing
The license limits the number of devices which can be managed by LWEB-900. Different
license options are available starting with 10 devices up to an unlimited number of devices.
The license also restricts the maximum number of concurrent LWEB-900 Clients and
LWEB-802/803 Clients (access for end user via web browser or Windows application). The
standard license includes 5 LWEB-900 Clients and 20 LWEB-802/803 Clients.

1.13 Supported Devices


The LWEB-900 Server supports the LOYTEC devices shown in Table 1. Devices from
other manufacturers can be integrated if they support BACnet.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 14 LOYTEC

Product code OPC BACnet Comment

LINX-100 + - Full support.


LINX-101 + - Full support.
LINX-102 + - Full support.
LINX-103 + - Full support.
LINX-110 + - Full support.
LINX-111 + - Full support.
LINX-112 + - Full support.
LINX-113 + - Full support.
LINX-200 + + Full support.
LINX-201 + + Full support.
LINX-202 + + Full support.
LINX-203 + + Full support.
LINX-210 + + Full support.
LINX-211 + + Full support.
LINX-212 + + Full support.
LINX-213 + + Full support.
LINX-215 + + Full support.
LINX-120 + - Full support.
LINX-121 + - Full support.
LINX-150 + + Full support.
LINX-151 + + Full support.
LINX-153 + + Full support.
LINX-154 + + Full support.
LINX-220 + + Full support.
LINX-221 + + Full support.
LIP-ME201 - + The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-ME201C - + The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-ME202C - + The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-ME204 - + The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-ME204C - + The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-xECTB - - The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-xxECTB - - The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-xxxxECTB - - The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-xxECRB - - The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-xECTC - - The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-xxECTC - - The device has no OPC XML-DA server. Therefore
data point values cannot be displayed in LWEB-900.
LIP-xxxxECTC - - The device has no OPC XML-DA server. Therefore

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 15 LOYTEC

data point values cannot be displayed in LWEB-900.


LROC-100 + + Full support.
LROC-101 + + Full support.
LROC-102 + + Full support.
LROC-400 + + Full support.
LROC-401 + + Full support.
LROC-402 + + Full support.
LGATE-900 + + Full support.
LGATE-902 + + Full support.
LGATE-950 + + Full support.
LGATE-951 + + Full support.
LGATE-952 + + Full support.
LDALI-E201-U, + + Full support.
LDALI-ME201-U
LDALI-ME204, + + Full support.
LDALI-ME204-U
LDALI-3E101, + - Full support.
LDALI-E101-U,
LDALI-3E101-U
LDALI-3E102, + - Full support.
LDALI-3E102-U
LDALI-3E104, + - Full support.
LDALI-3E104-U
LDALI-PLC4 + + Full support.
LVIS-3E100 + - Full support.
LVIS-100-RE + - Full support.
LVIS-ME200 + + Full support.
LVIS-3E112 + - Full support.
LVIS-3E115 + - Full support.
LVIS-ME212 + + Full support.
LVIS-ME215 + + Full support.
LVIS-3ME7-G1, + + Full support.
LVIS-3ME7-G2
LVIS-3ME12-A1 + + Full support.
LVIS-3ME15-A1, + + Full support.
LVIS-3ME15-G1,
LVIS-3ME15-G2,
LVIS-3ME15-G3
LIOB-100 - - The device is connected to a LINX-xxx via
LIOB-CONNECT.
LIOB-101 - - The device is connected to a LINX-xxx via
LIOB-CONNECT.
LIOB-102 - - The device is connected to a LINX-xxx via
LIOB-CONNECT.
LIOB-103 - - The device is connected to a LINX-xxx via
LIOB-CONNECT.
LIOB-131 - - The device is connected to a LINX-xxx via
LIOB-CONNECT.
LIOB-150 - - The device is connected to a LINX-xxx via LIOB-FT.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 16 LOYTEC

LIOB-151 - - The device is connected to a LINX-xxx via LIOB-FT.


LIOB-152 - - The device is connected to a LINX-xxx via LIOB-FT.
LIOB-153 - - The device is connected to a LINX-xxx via LIOB-FT.
LIOB-154 - - The device is connected to a LINX-xxx via LIOB-FT.
LIOB-450 - - Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-451 - - Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-452 - - Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-453 - - Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-454 - - Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-480 + - Full support.
LIOB-481 + - Full support.
LIOB-482 + - Full support.
LIOB-483 + - Full support.
LIOB-484 + - Full support.
LIOB-550 + + Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-551 + + Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-552 + + Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-553 + + Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-554 + + Supported as stand-alone device in LonMark Mode
or connected to a LINX-xxx via LIOB-IP.
LIOB-580 + + Full support.
LIOB-581 + + Full support.
LIOB-582 + + Full support.
LIOB-583 + + Full support.
LIOB-584 + + Full support.
LIOB-586 + + Full support.
LIOB-AIR1 + + Full support.
LIOB-AIR2 + + Full support.
LIOB-AIR13 + + Full support.
L-STAT - - This device is connected to a L-INX or L-ROC via
Modbus.
Table 1: Supported LOYTEC Devices.

1.14 Scope
This document covers the LWEB-900 software. The LOYTEC devices and their
configuration software are beyond the scope of this manual. Please refer to the device
specific user manuals for additional information.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 17 LOYTEC

2 What’s New in LWEB-900

2.1 New in LWEB-900 2.2.0


This section describes the major changes and new features. For a full list of changes, refer
to the Readme file.

Parameter View

In the previous version of LWEB-900 the parameter view could contain only data points of
LOYTEC devices which were marked as parameters in the device configuration software.
The new parameter view in LWEB-900 version 2.2.0 can contain any data point of
LOYTEC devices or BACnet properties of third party devices.

The workflow to create and edit multiple parameter views from templates was improved:
You can select multiple parameter view templates and drag them to a folder in the
navigation view to instantiate them. It is also possible to select multiple parameter view
instances and edit their properties together.

Master Device Manager

The master device management view was reworked completely:

 It is now possible to configure which columns are displayed in the device list.

 Multiple master device management views can be saved as objects in the


navigation view.

 The device backup schedules have been moved from the master device manager to
the folder "System/Backup Schedules".

 Support for firmware update of L-STAT devices has been added.

 Firmware ZIP archives which support multiple firmware files are supported.

Object Properties

Instead of displaying properties of objects (e.g. properties of chart views) in modal dialogs,
they are now displayed in separate views. This allows opening multiple properties views
side-by-side and copying values between them.

Object List view

The object list view is no longer split into multiple pages. Instead the object list view is an
endless list and objects are loaded only when needed.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 18 LOYTEC

Filter

Several views (e.g. alarm view, event view, master device manager view) support custom
filters. It is now possible to save and edit multiple custom filters.

Project management

The upgrade procedure for old LWEB-900 versions has been improved. Because the
upgrade can take a long time for large data bases, detailed progress information has been
added. Before the upgrade is performed, a backup is performed automatically.

Trending

A possibility to add corrections for trend log values has been implemented. This feature is
useful when trending energy consumption and the energy meter needs to be replaced. The
new energy meter will start with a counter value which is different from the last value of the
replaced meter. To correct the value, right click on the first value of the new energy counter
in the trend log view and add a log correction. In the trend log view, you can display both
the raw values of the energy counter and the corrected values. Chart views, graphical views,
and reports use the corrected values.

The custom filter for trend log views has been improved. It is now possible to filter by log
item.

Chart view templates

Chart view templates are useful if you need to create multiple chart views with identical
settings but which display different trend logs. They can be created in the folder
“Library/Chart View Templates”. The concept is similar to graphical view templates.

2.2 New in LWEB-900 2.1.0


This section describes the major changes and new features. For a full list of changes refer to
the Readme file.

File objects

LWEB-900 allows you to store files on the server and to link them to other objects or to
alarms. File objects can be added below the folder “Library/Files”. Files can be organized in
user defined folders. Refer to Section 6.21 for details.

Windows authenticated users

LWEB-900 can now connect to an Active Directory server which performs the user
authentication. Refer to Section 6.27 for details.

BACnet custom objects

The BACnet standard defines standard objects and their properties. However, many
BACnet vendors extend those standard objects with custom properties. Other vendors
define new object types with a complete new set of properties. When LWEB-900 scans a
BACnet device and its objects, it gathers all available information and creates a new object
type definition if it does not yet exist. All object types can be modified using the Types &
Properties editor. To access the object type definitions, select Properties from the context
menu of the project node in the navigation view, switch to the BACnet tab, and select
Types & Properties.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 19 LOYTEC

Figure 4: Types & Properties Editor

Favorites

Each user has his own Favorites folder in the navigation view. You can drag and drop any
view into the Favorites folder to speed up access to frequently used views. The Favorites
folder can be organized using sub-folders.

Figure 5: Favorites

Client Notification Alarm Receiver

The alarm notifier can now be configured to display a pop-up message when an alarm
occurs. Figure 6 shows an example. Refer to Section 6.14.3 for details.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 20 LOYTEC

Figure 6: Alarm Notification Pop-Up

Parameter view improvements

The parameter view can now check if parameter values are different on the device and in
LWEB-900. It highlights these differences and allows resolving the conflicts.

Figure 7: Parameter Merge

A parameter view can be based on a template. Use parameter view templates to create
multiple parameter views with the same parameter names but different paths. The parameter
view template defines the parameter view columns and specifies a search pattern for each
column. Refer to Section 6.12.3 for more details.

Chart view improvements

Several improvements have been implemented for the chart view. The chart view does no
longer require a size configuration in pixels. Instead it automatically adjusts to the available
view size. A new option to scale the range of the y-axis automatically depending on the
displayed values is available.

Reporting improvements

A number of improvements have been made to reports:

 It is now possible to configure the colors used in the report for the trend logs.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 21 LOYTEC

 A new build-in report template has been added. The generic report template
contains one data group. It allows specifying what charts and tables are used to
display data.

 New parameters have been added to existing templates to make them even more
flexible. It is now possible to decide which part of the reports should be visible and
which should be hidden. It is also possible to add a company logo to the reports.

 The dialog to select a report template has been improved. It now displays a
preview of the report templates.

 When triggering a report manually, it is now possible to specify if an e-mail should


be sent to the configured e-mail receivers or not.

Limit number of parallel file transfers

The device communication profile (see Section 6.24) has a new configuration option to
limit the maximum number of parallel file transfers. Files need to be transferred to/from a
device for firmware upgrades, backup, restore, parameter download/upload, global
connections download/upload, etc. The new WLAN device communication profile has been
added. The number of concurrent file transfers has been set to 1 for this profile to limit the
traffic on wireless networks.

Communication statistics

The LWEB-900 server UI provides detailed communication statistics. To display the


statistics select the menu File  Statistics. The following information is provided:

 OPC Server: To provide data updates to clients, the LWEB-900 Server acts as
OPC XML-DA server. This tab displays the statistics for the communication
between LWEB-900 Server and clients.

 OPC Client: To get data updates from the devices, the LWEB-900 Server acts as
OPC XML-DA client. This tab displays the statistics for the communication
between LWEB-900 Server and devices.

 Connected Clients: This tab displays the clients which are currently connected to
the LWEB-900 Server.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 22 LOYTEC

Figure 8: Communication Statistics

Certificate management

The certification management for secure communication has been improved and has moved
to a separate tab in the LWEB-900 Server UI preferences. LWEB-900 now supports the
SHA-2 hash algorithm.

Licensing

The licensing now also takes the number of connected clients into account. The license
restricts the maximum number of concurrent LWEB-900 Clients and LWEB-802/803
Clients (access for end user via web browser or Windows application). The standard license
includes 5 LWEB-900 Clients and 20 LWEB-802/803 Clients.

Device management

The following new LOYTEC devices are now supported: LDALI-3E102-U, LDALI-3E104-
U, LDALI-ME204-U, LDALI-ME201-U, LDALI-3E101-U, LROC-101, LROC-400,
LROC-401, LROC-402, LIOB-AIR2, LIOB-AIR13, LIOB-586

The master device manager can now import .zip archives containing the firmware for
multiple devices.

2.3 New in LWEB-900 2.0.0


This section describes the major changes and new features. For a full list of changes refer to
the Readme file.

BACnet

LWEB-900 implements the BACnet communication protocol. The BACnet technology


offers a standardized interface to devices from other manufacturers. LWEB-900 supports
the following BACnet functionality:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 23 LOYTEC

 Scan BACnet network to find BACnet devices and their objects.

 Monitor and modify the value of all BACnet object types, including all required
and optional properties.

 Display and acknowledge BACnet alarms in alarm view.

 Configure BACnet scheduler and calendar objects using the master schedule
configurator.

 Display BACnet trend logs in list view, chart view, or report.

 Distribute time into the BACnet network as BACnet time master.

 Reset BACnet devices.

 Backup and restore the configuration of BACnet devices.

Refer to Section 6.5 for details.

Print

The toolbar of the different LWEB-900 views allows printing the current content.

Figure 9: Print LWEB-900 Client View

Kiosk mode

The LWEB-900 Client now supports a kiosk mode with the following properties:

 LWEB-900 Client is displayed in full screen mode

 The Windows task bar is not visible

Default user

LWEB-900 allows defining a default user which has no password and no auto-logout. If no
username and password is specified in the login-in dialog, the LWEB-900 Client logs in the
default user. If a standard user logs out (auto-logout or manual logout), the default user is
automatically logged in.

LWEB-900 Client command line options

Using the LWEB-900 Client command line options it is now possible to start the LWEB-
900 Client automatically (see Section 6.1.3).

Navigation view

The navigation view now displays all objects. For example, data points which were
previously visible only in an object list view are now displayed also in the navigation view.
A single click on an object in the navigation view no longer switches the context of the
active view in the document area. Use the bread crumb navigation bar instead. It is also
possible to drag a folder from the navigation view to the bread crumb navigation bar.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 24 LOYTEC

Display values for all data points

LWEB-900 can now display the values of all data points. Only OPC data points and
BACnet properties are refreshed automatically. Use the refresh button to update the values
of other data points.

Reorder objects in object list view and watch view

Objects in the object list view and watch view can be reordered using drag-and-drop.

Search

The search dialog has been improved. It allows now to search for all object types. In
addition it is possible to combine search parameters using AND, OR, and NOT operators.
Refer to Section 6.9 for details.

Identification key

The identification key can be assigned based on data point names or descriptions (see
Section 6.8). The identification key can be displayed as a column in the event view (see
Section 6.19).

Graphical views

Using a Show page action, it is possible to create buttons in a graphical view which link to
other views. Figure 10 shows how to drag a view and drop it on the action object in the tree
view of the L-VIS Configurator.

Note The Show page action works inside the LWEB-900 Client. When using a web browser to
display a graphical view, only links to other graphical views or chart views are supported.

Figure 10: Show Page Action

Alarming

The project settings contain a new Alarming tab which allows configuring that users have
to enter a comment when acknowledging alarms with a priority higher than a certain value.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 25 LOYTEC

Figure 11: Alarming Configuration

The subject of alarm notification e-mails is now freely configurable. Two new timing
parameters have been added to the alarm notifier object:

 Aggregation time: This parameter defines the time period in which LWEB-900
collects alarm notifications before it sends an e-mail. All alarm notifications
occurring during this time are included in the e-mail. Use this setting to receive
related alarm notifications in a single e-mail.

 Min. send time: This parameter defines the minimum time that elapses between
two e-mail notifications. If alarm notifications occur more often, they are
postponed and sent after the minimum send time. Use this setting to limit the e-
mail transmission rate.

Master scheduler

The configuration of the default preset has been changed. The master schedule configurator
now uses the new features of the current LOYTEC device firmware to set a default preset
instead of using a default event with low priority.

Trending

The properties of chart views allow configuring a scale factor for data records. The data
records are multiplied with this factor before displaying them. Example: To convert Wh into
kWh enter, configure the scale factor 0.001.

A server trend log can be temporarily disabled using the Disable Trend Log option in the
context menu. When the trend log is disabled, the LWEB-900 Server does not record the
attached data points. A disabled trend log can be enabled with the Enable Trend Log menu
entry.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 26 LOYTEC

To search for specific records in the trend log view, click on the Filter Log Data button in
the toolbar. The filter dialog allows you to combine multiple conditions with AND and OR
operators. The example in Figure 12 finds all data records of the data point
“nvoHCroomTemp” with a value less than 20.

Figure 12: Trend Log Filter

Reporting

The new energy signature report template gives a quick overview of the energy performance
of a building. It shows the correlation between energy consumption and heating degree
days. Heating degree days (HDD) are calculated from the outside temperature and are a
measure of how much the outside air temperature was below a certain base temperature.

Figure 13: Energy Signature

The stacked column chart report template has been updated to include a pie chart.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 27 LOYTEC

Figure 14: Stacked Column Chart

L-Studio support

LWEB-900 can import L-Studio projects (see Section 6.29).

Localization

The LWEB-900 user interface was localized in French and Chinese. It now supports the
following languages:

 English

 German

 French

 Chinese (Traditional)

Client user interface

Most LWEB-900 views have a toolbar and bread crumbs navigation. You can hide those
bars using the context menu of the tab.

Figure 15: Hide Toolbar and Bread Crumbs Navigation

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 28 LOYTEC

Web access

The LWEB-900 web access can now display chart views in addition to graphical views. The
dialog to select the view was improved to shows the tree structure of the LWEB-900
project.

Figure 16: Graphical View List

2.4 New in LWEB-900 1.3.0


This section describes the major changes and new features. For a full list of changes refer to
the Readme file.

Reporting

LWEB-900 can now create reports based on trend logs. Reports can be used, for example,
to document the energy consumption in a building. Figure 17 shows an example report.
Refer to Section 6.17 for details.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 29 LOYTEC

Figure 17: Example Report

LWEB-900 Server Schedulers

It is now possible to create schedulers which are executed by the LWEB-900 Server. They
should be used to schedule LWEB-900 Server user registers which trigger a report or enable
an alarm receiver. Refer to Section 6.15 for details.

Alarming

A number of features have been added to alarm management in LWEB-900:

 It is now possible to configure the priority of LWEB-900 system alarms.

 A custom filter can be configured for alarm notifiers.

 It is now possible to specify an enable data point for alarm receivers. By using a
user register which is controlled by a scheduler it is possible to configure different
receivers based on a time table.

 A column for the identification key of the data point which triggered the alarm has
been added to the alarm view. The identification key can also be added as a place
holder in an alarm notification template.

Create L-VIS project from LWEB-900 Server graphical view

It is now possible to simply copy an LWEB-900 graphical view to an L-VIS device. Refer
to Section 6.11.4 for details.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 30 LOYTEC

Allow wildcards in search expressions

You can now use the percent sign (%) as a wild card character in the search string. It
matches zero or more characters. For example, the search string “nvi%Fb” finds all data
points which have names starting with “nvi” and ending with “Fb”.

Hide folders to which a user has no access

The new option Show objects on which the user has no read access has been added to the
user configuration dialog. If this checkbox is enabled, the user sees objects (e.g. folders) to
which he has no read access. They are displayed with a lock icon. If this option is disabled,
those objects are not visible in the navigation and object list view.

Import and export Identification key schema

It is now possible to export the identification key schema from one LWEB-900 project and
import it in a different LWEB-900 project.

Data point details

A double-click on a data point displays detailed information about the data point (see Figure
18). The Links section shows where the data point is used. Click on a link to open the
corresponding view.

Figure 18: Data Point Details

Chart view improvements

A number of improvements have been made to the chart view:

 Support a secondary y-axis.

 Dynamic scaling of y-axis.

 Support configuration of line width for trend curves.

 Allow to display chart view description as header of the trend graph.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 31 LOYTEC

 Improve trend zooming: If cursor is active, zoom relative to current cursor position
else relative to center.

 Support linear interpolation for trend log charts.

 Support limit lines: It is now possible to display limit lines in the trend graph. A
horizontal line with the configured color and value is drawn across the entire
graph.

Manage files in master device manager

A new dialog was added to the master device manager which displays all files imported or
uploaded from LOYTEC devices. This dialog allows removing unused files quickly. Refer
to Section 6.22.8 for details.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 32 LOYTEC

3 Installation

3.1 Software Installation


The LWEB-900 software can be downloaded from the LOYTEC Web site
http://www.loytec.com. The LWEB-900 setup file includes the LWEB-803 installer as a
prerequisite. LWEB-803 is used by LWEB-900 as an add-in to display graphical views and
chart views. After the LWEB-803 setup finishes, the LWEB-900 installation is started.
When asked for the type of installation, there are two options to choose from (see Figure
19). Select LWEB-900 Server and Client to install both server and client on the same PC.
Select LWEB-900 Client to install the client only. This option is useful, if the server is
installed on a different PC.

Figure 19: LWEB-900 Installation Options

3.2 Product Activation


After LWEB-900 has been installed, the server has to be activated:

1. Start the LWEB-900 Server user interface by selecting Windows Start  Programs
 LOYTEC LWEB-900  LWEB-900 Server.

2. Select Help  Register… to open the registration dialog (see Figure 20).

3. Select the required license from the Select feature drop-down list. The following kinds
of licenses are available for the LWEB-900 Sever:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 33 LOYTEC

a. LWEB-900: License for 10 LOYTEC devices. If this number is insufficient,


one or more extension licenses (LWEB-900-ADD10 or
LWEB-900-ADDMAX) can be added later. The license support 5 LWEB-900
Clients and 20 LWEB-802/803 Clients.

b. LWEB-900-MAX: License for unlimited number of LOYTEC devices. The


license support 5 LWEB-900 Clients and 20 LWEB-802/803 Clients

c. LWEB-900-ADD10: One or multiple LWEB-900-ADD10 licenses can be


added to the LWEB-900 license to increase the number of supported devices.
Each license adds 10 devices.

d. LWEB-900-ADDMAX: The LWEB-900-ADDMAX license can be added to


the LWEB-900 license to support an unlimited number of LOYTEC devices.
The combination of LWEB-900 and LWEB-900-ADDMAX licenses is
equivalent to the LWEB-900-MAX license.

e. LWEB-900-CL-5: The LWEB-900-CL-5 license can be added to the


LWEB-900 or LWEB-900-MAX license to increase the number of concurrent
LWEB-900 Clients. Each license adds 5 LWEB-900 clients.

f. LWEB-900-80x-50: The LWEB-900-80x-50 license can be added to the


LWEB-900 or LWEB-900-MAX license to increase the number of concurrent
LWEB-802/803 Clients. Each license adds 50 LWEB-802/803 Clients.

g. LWEB-900-80x-100: The LWEB-900-80x-100 license can be added to the


LWEB-900 or LWEB-900-MAX license to increase the number of concurrent
LWEB-802/803 Clients. Each license adds 100 LWEB-802/803 Clients.

h. LWEB-900-80x-MAX: The LWEB-900-80x-50 license can be added to the


LWEB-900 or LWEB-900-MAX license to support an unlimited number of
concurrent LWEB-802/803 Clients.

i. LWEB-900-DEMO: The demo license has the same features as the


LWEB-900 license but will work only for 30 days.

j. LWEB-900-CP: LWEB-900 license for LOYTEC competence partners.

4. If you have already purchased the license, enter your serial number (shipped with the
LWEB-900 product). If you have not yet purchased the license, click on the Not
purchased yet button. No serial number is required for the demo license.

5. Click on Request activation file by e-mail to request the activation file. Alternatively,
write an e-mail to [email protected] with both the Target ID and the Serial Number
in the subject.

6. You will receive a LOYTEC activation file, which you import by clicking on Add
activation file....

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 34 LOYTEC

Figure 20: LWEB-900 Registration

The activation files determine the maximum number of LOYTEC devices which can be
added in LWEB-900. Exceptions are the following devices which do not add to the total
count:

 L-IOB devices attached to other LOYTEC devices

 L-IP devices

The LWEB-900 Server user interface displays the limit determined by the activation files
and how many devices are currently used for each project (see Figure 21). Only projects
which have the status Running count for the total limit.

Figure 21: LWEB-900 Device License

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 35 LOYTEC

3.3 Firewall Configuration


If you want to access the LWEB-900 Server with an LWEB-900 Client from a remote PC,
you need to add the following firewall rule for inbound traffic on the server:

 Protocol: TCP

 Port: Specify the port configured in the LWEB-900 Server preferences (File 
Preferences, Network tab). If you have enabled secure connection, configure the
HTTPS port (default 8443) else configure the HTTP port (default 8080).

The exact procedure how to add the rule depends on the firewall you are using. If you are
using the Windows 7 firewall, execute the following procedure:

1. Open Windows Firewall by opening the Windows Control Panel and clicking
Windows Firewall.

2. In the left pane, click Advanced settings. If you are prompted for an administrator
password or confirmation, type the password or provide confirmation.

3. In the Windows Firewall with Advanced Security dialog box, in the left pane, click
Inbound Rules. In the right pane, click New Rule.

4. Follow the instructions in the New Inbound Rule wizard.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 36 LOYTEC

4 System Tray Icon

The status of the LWEB-900 Server is indicated by a system tray icon (see Figure 22). The
systray icon is not present, if only the LWEB-900 Client is installed on the PC.

Figure 22: LWEB-900 System Tray Icon

The color of the systray icon reflects the status of the LWEB-900 Server (refer to Table 2).
Moving the mouse pointer over the systray icon displays detailed information in a tooltip.

Color Condition

Green LWEB-900 Server is running without errors and warnings


Red Fatal error (e.g. database error)
Orange One or more LOYTEC devices are not responding
Grey No LWEB-900 project is running
Table 2: LWEB-900 System Tray Icon Color

The context menu of the systray icon allows starting the LWEB-900 Server user interface
and the LWEB-900 Client. A double-click on the systray icon opens the LWEB-900 Client.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 37 LOYTEC

5 LWEB-900 Server

The LWEB-900 Server runs as a service which is started automatically when the PC boots.
The user interface for the service is shown in Figure 23. It can be started from the Windows
start menu (Start  Programs  LOYTEC LWEB-900  LWEB-900 Server) or from
the context menu of the LWEB-900 system tray icon.

Figure 23: LWEB-900 Server User Interface

5.1 Manage Projects


When starting the LWEB-900 Server user interface for the first time, you will notice, that a
project with the name “Default LWEB-900 Project” has already been created. You can edit
the project by selecting Edit project… from the context menu. The project properties are
displayed and can be edited as shown in Figure 24.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 38 LOYTEC

Figure 24: Edit LWEB-900 Project

 Project name: The project name has to be specified when connecting with the
LWEB-900 Client.

 Project location: Folder in which project related data is stored.

 Description: Project description.

 Startup mode: The startup mode determines if the project is started automatically
when the PC boots:

o Automatic: The project is started automatically when the PC boots. This


is the default setting.

o Manual: The project has to be started manually.

 Database type: LWEB-900 supports different database engines (refer to Section


5.7).

The LWEB-900 Server can manage multiple independent projects. A new project can be
added by clicking on the Add project… button. Projects can be removed by selecting
Remove project… from the context menu. A double-click on the project starts the
LWEB-900 Client.

Each project can be in the state running or stopped. After a reboot of the PC, the project
state is determined by startup mode. The project state can be changed using the context
menu of the project. To be able to connect with the LWEB-900 Client, the project has to be
running. A running project can be in online or offline mode. In offline mode, the
LWEB-900 Server does not communicate with the LOYTEC devices (see Figure 25).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 39 LOYTEC

Figure 25: LWEB-900 Project Status

5.2 Password Protection


Per default the LWEB-900 Server user interface is not protected by a password. The
password protection can be activated in the Login Tab of the menu File  Preferences
(see Figure 26).

Note Do not confuse the server login with the client login. The LWEB-900 Server user interface
can be started on the server PC only and is used to manage multiple projects. The
LWEB-900 Client can be started on a remote PC and connects to a specific project. The
user name and password specified in the client login is part of the project.

Figure 26: LWEB-900 Server, Activate Login

5.3 Network Settings


The LWEB-900 Server provides web services for the LWEB-900 Client. The
communication parameters are defined in the Network tab of the File  Preferences
menu.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 40 LOYTEC

Figure 27: LWEB-900 Server Network Settings

 Enable HTTP: Allow a client to connect to the LWEB-900 server using HTTP.

 HTTP port: Server port used for HTTP communication between client and server.

 Enable HTTPS: Allow a client to connect to the LWEB-900 server using HTTPS.
In order to enable HTTPS a certificate is required (see Section 5.4)

 HTTPS port: Port used for SSL (Secure Sockets Layer) communication.

5.4 Certificate Management


Certificates are part of Secure Socket Layer (SSL) encryption. The server certificate enables
the user to confirm the identity of the LWEB 900 Server. The Certificate management tab
allows you to create a self-signed certificate, import a certificate, or create a certification
request which can be sent to a certification authority.

Figure 28: LWEB-900 Server Certificate Management

Enable secure connection using a self-signed certificate

1. Start the LWEB-900 Server UI and select the Network tab of the File  Preferences
menu.

2. Activate the Enable HTTPS checkbox.

3. Select the Certificate management tab and click on the button Create Self-Signed
Certificate.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 41 LOYTEC

4. Switch to the Network tab and activate the Enable HTTPS checkbox.

When you connect with the LWEB-900 Client to the LWEB-900 Server for the first time, a
warning will be displayed because the certificate was not issued by a trusted certification
authority (see Figure 29). If you set the checkbox Do not show this warning again, the
certificate will be accepted without warning in the future.

Figure 29: Server Certificate Warning

Enable secure connection using a certificate issued by a public certification


authority

1. Start the LWEB-900 Server UI and select the Network tab of the File  Preferences
menu.

2. Activate the Enable HTTPS checkbox.

3. Select the Certificate management tab and click on the button Create new
Certificate Request.

4. In the certificate request dialog fill out the following data:

 Common Name: The name through which LWEB-900 Server will be accessed
(usually the fully-qualified domain name).

 Organization: The legally registered name of your organization/company.

 Organizational unit: The name of your department within the organization.

 City/Locality: The city in which your organization is located.

 State/Province: The state in which your organization is located.

 Country/Region: Enter your two-digit country code (e.g. AT: Austria, DE


Germany, US United States).

 Bit Length: In the drop-down box, select a bit length for the RSA encryption
algorithm.

5. Specify the path where the certification request should be set or use the browser button
(…) and press OK.

6. Send the request to a public certification authority (CA).

After you received a response from the public certification authority, perform the following
actions to install the certificate:

1. Start the LWEB-900 Server UI and select the Certificate management tab of the File
 Preferences menu.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 42 LOYTEC

2. Click on the Complete Certificate Request button.

3. Select the certificate signed by your certification authority and click on Install
Certificate.

5.5 Proxy Settings


Per default the LWEB-900 Server does not use a proxy as show in Figure 30. If the radio
button Automatically detect settings is enabled, the LWEB-900 Server uses the proxy
settings of the user which runs the LWEB-900 service (usually the local system account).

Figure 30: LWEB-900 Server Proxy Settings

5.6 Backup/Restore
5.6.1 Manual Backup
To create a system backup including the LWEB-900 Server configuration and all
LWEB-900 projects, select File  System backup.

Figure 31: System Backup

 Backup location: Folder in which the backup file will be stored

 Backup type: This drop-down field specifies the contents of the backup. A Full
system backup contains all data. A Configuration system backup contains
configuration data, but no historic data other than the event log (no alarm logs and
no trend logs). Therefore the file size of this type of backup will be much smaller.

It is also possible to backup only a specific project. This is useful to e.g. transfer a project
from one LWEB-900 Server to another. To execute a project backup, right click on the
project and select Backup project… from the context menu. Refer to Table 3 for a
description of the different backup types.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 43 LOYTEC

Type Sub-Type Contents

System Full system backup Configuration of LWEB-900 server


Configuration of all LWEB-900 projects
Historic data of all LWEB-900 projects
Configuration system backup Configuration of LWEB-900 server
Configuration of all LWEB-900 projects
Project Full project backup Configuration of selected LWEB-900 project
Historic data of selected LWEB-900 project
Configuration project backup Configuration of selected LWEB-900 project
Backup datalogs Historic data of selected LWEB-900 project
Table 3: Backup Types

5.6.2 Scheduled Backup


Periodic backup schedules can be defined in the menu File  Scheduled backups (see
Figure 32).

Figure 32: Scheduled Backups

 Name: Name of the backup schedule.

 Description: Description of the backup schedule.

 Backup type: This drop-down field specifies the contents of the backup (refer to
Table 3).

 Backup location: Folder in which the backup files will be stored.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 44 LOYTEC

 Interval: Definition of the backup schedule. Note, that the times of the last and the
next scheduled backup are displayed in the project list (see Figure 33).

 Max backups: Maximum number of stored backups. When this number is


exceeded the oldest backup file is removed.

 Projects: This section defines which projects will be included in the backup.
System backups contain all projects and this section is therefore disabled. For
project backups, move one or more projects from the list Available projects to the
list Projects to backup.

Figure 33: Last Backup and Next Scheduled Backup

5.6.3 Restore
The LWEB-900 Server offers different ways to restore a backup:

 Restore System: To restore a complete LWEB-900 Server configuration with all


projects, select File  Restore system from the menu. The complete system can
be restored only from a system backup.

 Restore Project: To restore a single project without affecting other projects on the
server, right click on the project and select Restore project… from the context
menu. A project can be restored from a system backup or from a project backup.

 Import Project: To create a new LWEB-900 project from a backup, click on the
button Import project above the project list. A project can be imported from a
system backup or from a project backup.

Figure 34 shows the dialog to restore the LWEB-900 system. The dialogs to restore or
import a single project are similar.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 45 LOYTEC

Figure 34: Restore System Backup

 Restore from file: Select this option to restore a backup created by a different
LWEB-900 Server.

 Restore from existing system backup: All system backups performed by the
LWEB-900 Server are displayed in the list. Select one of the available backups.

 Delete backup: To free up space on the hard drive, select one of the available
backups and click on the Delete backup button.

 System backup content: The projects contained in the selected backup are listed.

 Type of system restore: Use the radio button to define which part of the backup
to restore.

o Restore full system: Restore everything contained in the backup.

o Restore system configuration: Restores the system configuration, but no


historic data (alarm log, trend log, event log). This option is useful, if you
want to restore an old configuration but keep the latest log data.

5.7 Database Engines


LWEB-900 supports different database engines:

 SQLite

 Microsoft SQL Server

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 46 LOYTEC

 MySQL

When creating a new project, the database engine is selected. Per default SQLite is selected
as shown in Figure 35. SQLite is a light-weight database implementation which is included
in LWEB-900.

Figure 35: New SQLite Project

If you want to use a Microsoft SQL or MySQL server (not included in LWEB-900), you
can select the appropriate database type in the New Project dialog and configure the
connection parameters shown in Figure 36.

Figure 36: New Microsoft SQL Server Project

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 47 LOYTEC

 Server: Database server (e.g. “.\SQLSERVER” for Microsoft SQL Server or IP


address of the MySQL server).

 Database: Name of the database which will be created for LWEB-900.

 User: Name of the user that will be created to access the database.

 Password: Password for the created user.

 Confirm password: Password confirmation to ensure that the password was


entered correctly.

 Admin user: Admin user for database server (e.g. “sa” for Microsoft SQL Server
or “root” for MySQL server); necessary to create the database.

 Admin Password: Password for admin user; necessary to create the database.

5.8 Communication Statistics


To display communication statistics select the menu File  Statistics. The following
information is provided:

 OPC Server: To provide data updates to clients, the LWEB-900 Server acts as
OPC XML-DA server. This tab displays the statistics for the communication
between LWEB-900 Server and clients.

 OPC Client: To get data updates from the devices, the LWEB-900 Server acts as
OPC XML-DA client. This tab displays the statistics for the communication
between LWEB-900 Server and devices.

 Connected Clients: This tab displays the clients which are currently connected to
the LWEB-900 Server.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 48 LOYTEC

Figure 37: Communication Statistics

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 49 LOYTEC

6 LWEB-900 Client

The LWEB-900 Client is the primary user interface for the server. It can be started on the
same PC as the server or on a remote PC. Multiple clients can access the server
concurrently.

6.1 Login
When the LWEB-900 Client is started, the login dialog is displayed (see Figure 38).

Figure 38: LWEB-900 Client Login

The Connection drop-down list allows to choose between different LWEB-900 projects.
To open the Manage Project Connections dialog, click on the Edit button (see Figure 39).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 50 LOYTEC

Figure 39: Manage Project Connections

 Connection name: The name entered in this text field, will appear in the
connection drop-down list of the login dialog.

 Host name or IP address: Host name or IP address of the LWEB-900 Server.

 Use secure connection: Activate this checkbox to connect to the LWEB-900


Server using SSL (Secure Socket Layer).

 Port: Port of the LWEB-900 Server (see Section 5.3).

 Project name: Name of the project. To obtain a list of projects, press on the
button “…”. If the server is protected by a password (see Section 5.2), the server
user name and password are requested.

Each LWEB-900 project has its own set of users and access rights (see Sections 6.27 and
6.28). A new project has an administrator user with the following default credentials:

 Username: admin

 Password: loytec4u

6.1.1 Default user


LWEB-900 allows defining a default user (see Section 6.27 for user management). The
default user has the following special properties:

 The default user has no password.

 If user name and password is left empty in the login dialog, the LWEB-900 client
logs in the default user.

 If the current user logs out (auto-logout or manual logout), the default user is
automatically logged in.

 Only the admin user can define/remove the default user.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 51 LOYTEC

6.1.2 Kiosk Mode


The LWEB-900 Client can be started in kiosk mode using the command line option
“Kiosk”. The admin user can switch between kiosk and normal mode using the keyboard
combination Ctrl+Enter. For other users the ability to switch between kiosk mode and
normal mode can be enabled as part of the user properties (Section 6.27 for user
management).

The kiosk mode has the following features:

 LWEB-900 Client is displayed in full screen mode

 The Windows task bar is not visible

6.1.3 Command Line Options


Using the LWEB-900 client command line options it is possible to start the LWEB-900
client automatically.

Option Description

Connection=<connection name> Name of a predefined connection. The connection defines


host, port, project and connection method (HTTP/HTTPS)
Host=<host name or IP address> Host name or IP address of the LWEB-900 Server
Port=<port> Port of the LWEB-900 Server
Project=<project name> Project name
UseSSL Use secure connection (HTTPS) to LWEB-900 Server
Username= <user name> User name for automatic login. To login the default user,
do not specify a user name.
Password=<password> Password for automatic login. To login the default user, do
not specify a password.
Perspective=<perspective name> Name of the perspective which will be loaded after login.
If no perspective is specified, the previous view layout will
be restored.
Kiosk Start LWEB-900 Client in kiosk mode
Table 4: LWEB-900 Client Command Line Options

6.2 User Interface Overview


The LWEB-900 Client user interface is highly customizable. You can arrange views inside
the workspace in the layout that best suits your working style. An example is shown in
Figure 40.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 52 LOYTEC

Figure 40: LWEB-900 Client User Interface

A pane displays one or multiple views. If a pane contains multiple views, they are displayed
as tabs. To move the entire pane, grab the caption bar and drag it. To move only a single
view from a pane, grab the tab and drag it.

While dragging a pane, docking indicators are displayed to make it easy to choose the
destination. You can drop the pane over a docking indicator (see Figure 41) or leave it
floating in a separate window above the application window. Floating windows are very
useful if you have a secondary monitor.

Another very useful feature that allows conserving space on your monitor is auto-hiding of
panes. To control this feature there is a pinup button in the upper right corner of each pane.
If you unpin it, the pane will automatically hide when it loses focus.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 53 LOYTEC

Figure 41: Docking Indicators

Most LWEB-900 views have a toolbar and bread crumbs navigation. You can hide those
bars using the context menu of the tab.

Figure 42: Hide Toolbar and Brad Crumbs Navigation

6.3 Navigation View


The navigation view displays the contents of the LWEB-900 project in a tree view. Figure
43 shows the navigation view of a new project.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 54 LOYTEC

Figure 43: Navigation View for New Project

 Favorites: Each user has his own Favorites folder. You can drag and drop any
view into the Favorites folder to speed up access to frequently used views. The
Favorites folder can be organized using sub-folders.

 Home: This folder contains a sub-folder for each user. When adding a new user
(refer to Section 6.27), a corresponding user folder is created automatically.

o admin: A new project contains an admin user per default.

 Library: This folder can contain templates for graphical views (refer to Section
6.11, parameter views (refer to Section 6.12), and reports (refer to Section 6.17).
Those templates can be instantiated multiple times. It also contains file objects
which can be linked to other objects or alarms (refer to Section 6.21).

 System: This folder contains LWEB-900 system items.

o Perspectives: Views are organized in the application window in an


arrangement called a perspective. These perspectives can be made
available for other users by placing them in the System/Perspectives
folder. Refer to Section 6.23 for details.

o Alarming: This folder contains the LWEB-900 alarm server and alarm
log. LWEB-900 monitors all devices and creates an alarm if a device is
not responding (refer to Section 6.14).

o System Registers: This folder contains data points which describe the
status of the LWEB-900 Server. Refer to Section 6.25 for details.

o User Registers: This folder contains user defined LWEB-900 registers.


They can be used in combination with LWEB-900 schedulers. Refer to
Section 6.15 for details.

o Scheduler: This folder contains schedulers which are executed by the


LWEB-900 Server. Refer to Section 6.15 for details.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 55 LOYTEC

o Trending: This folder contains LWEB-900 Server trend logs. Refer to


Section 6.16 for details.

 Network: This folder contains items related to the building automation network.

o Devices: This folder contains all LOYTEC devices. Refer to Section 6.5
for details.

o Communication Parameters: This folder contains settings for the


communication between the LWEB-900 Server and the LOYTEC
devices. Refer to Section 6.24 for details.

o Global Connections: This folder contains connections between input and


output data points of LOYTEC devices. After the connections have been
configured by LWEB-900, the devices exchange data directly over
TCP/IP. Refer to Section 6.20 for details.

6.4 Object List View


The object list view shows all items in a folder (see Figure 44).

Figure 44: Object List View

To open a new object list view, double click on a folder in the navigation view or select
Open  Open in new object list view from the context menu. Use the breadcrumb
navigation bar as shown in Figure 45 to navigate in the object list view. You can also drag
folders from the navigation view and drop them on the bread crumb navigation bar.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 56 LOYTEC

Figure 45: Breadcrumb Navigation Bar

Configure Columns

The columns of the object list view can be customized. Per default the Name, Type, and
Description columns are displayed. To add columns or to change the column order, click
on the Configure columns toolbar button.

Figure 46: Configure Columns

The column configuration is stored for each folder separately. To change the column
configuration for the current folder only, deactivate the Apply to all ‘Datapoints folder’
objects checkbox and click the Apply button. To save the configuration for all data point
folders, activate the checkbox and press the Apply button.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 57 LOYTEC

Column Description

Name Name of object


Type Object type
Description Object description
Path Complete path
Referenced If the object is a link, this column displays the referenced object
Value If the object is a data point, this column displays the value
Object ID Unique identifier for the object
Referenced ID If the object is a link, this column displays the unique identifier of
the referenced object
Identification Key (IK) Refer to Section 6.8
IK.<field name> The identification key consists of user defined fields. Each field
can be displayed as a separate column
Table 5: Object List View Columns

Note If the Value column is displayed, LWEB-900 does not refresh the values automatically.
Click on the Refresh values toolbar button to update the object list view. If you want to see
periodic updates, drag the data point into a watch view.

Sorting

If no sort order is defined, object in the object list view can be reordered using drag and
drop.

You can sort the list of objects by clicking one of the column headings - Name or Type, for
example. The first click sorts the objects in ascending order, the second click in descending
order, and the third click removes the sort order.

To sort by a second column, hold down the [Shift] key and click the column heading that
represents the secondary sort group.

Search

To find objects, type the name or part of the name in the search box (see Figure 47). The
search includes the folder and all its subfolders. To access additional search options, click
on the Advanced search button. Refer to Section 6.9 for details.

Figure 47: Search Tool Bar

Show Related Objects

Objects can be related to each other. In the example shown in Figure 48, the selected data
point is linked with the following views:

 Graphical view: The data point is member of the data point interface of the
graphical view.

 Trend Chart View: The data point is recorded by a trend log displayed in the chart
view.

 Watch View: The data point is shown in the watch view.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 58 LOYTEC

 Trend Log: The data point is recorded by the trend log.

Click on the link in the context menu to open the related view.

Figure 48: Show Related Objects

Data Point Details

A double-click on a data point displays detailed information about the data point (see Figure
49). The Links section shows where the data point is used. Click on a link to open the
corresponding view.

Figure 49: Data Point Details

Print

Use the print button in the toolbar to print the object list view. The print dialog allows
adjusting the page margins and the font size.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 59 LOYTEC

Figure 50: Print Object List View

6.5 BACnet Configuration


The BACnet technology offers a standardized interface to devices from other
manufacturers. LWEB-900 supports the following BACnet functionality:

 Scan BACnet network to find BACnet devices and their objects.

 Monitor and modify the value of all BACnet object types, including all required
and optional properties.

 Display and acknowledge BACnet alarms in alarm view.

 Configure BACnet scheduler and calendar objects using the master schedule
configurator.

 Display BACnet trend logs in list view, chart view, or report.

 Distribute time into the BACnet network as BACnet time master.

 Reset BACnet devices.

 Backup and restore the configuration of BACnet devices.

Activate BACnet communication

1. Select Properties from the context menu of the project node in the navigation view and
switch to the BACnet tab.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 60 LOYTEC

2. Active the Enable BACnet checkbox.

3. Select the Network Adaptor which the BACnet stack will use.

4. Configure the BACnet/IP address and BACnet/IP port. If the BACnet/IP network
uses a non-default UDP port number other than 47808/0xBAC0, enter this port in the
BACnet/IP port field. Press the Default button for switching back to the default setting.

5. The BACnet Instance Number corresponds to the instance number of the BACnet
device object for the LWEB-900 project. It must be a unique ID on the BACnet
internetwork.

6. Configure the APDU parameters:

 APDU timeout: Time the LWEB-900 Server waits for an answer before
retrying or giving up on a request.

 APDU segment timeout: Timeout allowed between segments.

 APDU retries: The number of times the LWEB-900 Server will try to re-send
a packet before giving up on a request.

 APDU length accepted: The maximal size of an APDU (Application Protocol


Data Unit) accepted by the LWEB-900 Server. The value of this property is
487 if only BACnet MS/TP is used and 1476 if BACnet/IP is used.

7. Configure the default value for write priority. LWEB-900 allows writing
commandable properties using one of the following methods (see Figure 52):

 Use default priority: Directly set the value of the commandable property.

 Use a specific priority: Change an entry in the corresponding priority array.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 61 LOYTEC

Figure 51: BACnet Configuration

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 62 LOYTEC

Figure 52: BACnet Write Priority

Register as Foreign Device with BACnet Broadcast Management Device


(BBMD)

The LWEB-900 Server can register with an existing BBMD in the BACnet/IP network as a
foreign device. This functionality is used if the LWEB-900 Server is located as a single
BACnet/IP device on a remote IP subnet or behind a NAT router. If operated as a foreign
device behind a NAT router, port forwarding to the BACnet/IP port must be setup in the
NAT router.

1. Enable the Register as Foreign Device with BACnet/IP Broadcast Management


Device (BBMD) checkbox.

2. Configure the IP address and port of the remote BBMD.

Configure BACnet time synchronization

The LWEB-900 Server can serve as a BACnet time master.

1. Enable the Use BACnet Time Synchronization checkbox.

2. Configure the time synchronization parameters:

 Time syn. interval: This value specifies the time interval in which periodic
time synchronization events are created. If set to zero, no periodic time
synchronization events are generated.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 63 LOYTEC

 Align time sync. interval to the top of the hour: The checkbox determines
whether or not periodic time synchronization events shall be anchored at the
start of a day or hour.

 Offset by: This value determines the point of time within this time
synchronization interval at which the time synchronization event is actually
triggered. The default value of this property is 0.

3. Add BACnet devices which should receive UTC time to the UTC time sync.
recipients list and devices which should receive local time to the Time sync.
recipients list. LWEB-900 allows to add the following types of recipients:

 Existing BACnet device from the data base

 BACnet device identified by BACnet instance number (the object ID of its


Device object)

 BACnet device identified by BACnet address (Network number and MAC


address/IP address)

 Local broadcast

 Foreign broadcast

 Global broadcast

BACnet custom objects and properties

The BACnet standard defines standard objects and their properties. However, many
BACnet vendors extend those standard objects with custom properties. Other vendors
define new object types with a complete new set of properties. When LWEB-900 scans a
BACnet device and its objects, it gathers all available information and creates a new object
type definition if it does not yet exist. All object types can be modified using the Types &
Properties editor.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 64 LOYTEC

Figure 53: Types & Properties Editor

6.6 Add Devices


Devices are added in the folder Network/Devices. To manage a large number of devices,
they can be grouped in subfolders. The LWEB-900 Server can communicate with LOYTEC
devices using one of the following modes:

 Web Service: This is the default communication mode enabling LWEB-900 to


access the full functionality of the device. The LWEB-900 Server uses web
services only (HTTP or HTTPS) for all communications with the device.
LOYTEC devices represent process data as data points. At the data point level, the
specific technological restrictions are abstracted and hidden from the user.
Therefore it makes no difference whether a LOYTEC device is connected to a
BACnet, CEA709, DALI, Modbus, Mbus, etc. network or has local I/Os.

 TCP/IP: This communication mode should be used for devices with old firmware
versions which do not yet support web services for device management. It requires
that LWEB-900 can access the device using web services for real time data and
FTP/Telnet (or SCP/ SSH) to manage the device.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 65 LOYTEC

 E-Mail: Most LOYTEC devices can send an e-mail with a trend or alarm log in
CSV format in the attachment when a configurable fill level is reached. The
LWEB-900 Server can fetch these e-mails from a mail box and process the
contained data. This communication mode is a good option, if the device is behind
a firewall and cannot be accessed directly. Only history data (trend and alarm logs)
can be received from the device.

 BACnet: BACnet communication can be enabled if Web Service or TCP/IP is


selected as communication mode. If the BACnet option is enabled, LWEB-900
displays the native BACnet objects and their properties as well as the abstracted
data points.

LWEB-900 allows adding devices from other manufacturers if they support BACnet
communication.

Add a device with communication mode “Web Service”

1. Select the folder Network/Devices or a subfolder and choose New  New device
from the context menu.

2. In the New Device dialog (see Figure 54) enter the following data:

 Family: Select the LOYTEC device family from the drop-down list.

 Type: Select the LOYTEC device type from the drop-down list.

 Name: User defined name to identify the device.

 Description: Description of the device.

 Communication: Select Web Service.

 BACnet: This checkbox is available only if the LOYTEC device supports BACnet
communication. If this option is enabled, LWEB-900 will display the native
BACnet objects of the device.

 State: If the device is online, select Enabled, else select Disabled.

 IP address: IP address or DNS name of the device.

 Operator password: Enter the operator password which has been configured via
the Web UI of the device. The default password is “operator”.

 Admin password: Enter the admin password which has been configured via the
Web UI of the device. The default password is “loytec4u”.

 Communication profile: Select one of the available communication profiles from


the drop-down list. Per default the communication profiles LAN, WAN, and
WLAN are available. The LAN setting ensures fast response times, the WAN
setting saves bandwidth; the WLAN setting limits the number of parallel file
transfers. Refer to Section 6.24 for details.

 HTTP port: HTTP port of the device.

 HTTPS port: Some LOYTEC devices (LINX-12x, LINX-22x, LINX-15x,


LVIS-3E11x, LVIS-ME21x, L-ROC) support HTTPS. For those devices the Use
secure connection checkbox can be activated and the HTTPS port can be
configured.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 66 LOYTEC

Figure 54: Add Device with Communication Mode Web Service

3. Press the button Test connection to verify that LWEB-900 can communicate with the
device correctly.

4. In the next dialog you are offered the following options:

 Upload device configuration: Choose this option if the device is already


configured. LWEB-900 will upload the configuration of the device and display the
data points.

 Assign device configuration: Choose this option to assign the configuration of a


different device. This option is useful if you have multiple devices with identical
configuration.

 Start the configurator: Open the device configuration view. Refer to Section 6.7
for details.

 Cancel: Perform none of the above actions. You can execute any of the actions
later from the context menu of the device.

5. The new device is displayed in the navigation view. If you have uploaded the device
configuration or assigned a configuration, you now have access to all data points of the
device (see Figure 55).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 67 LOYTEC

Figure 55: Device Data Points

Add a device with communication mode “TCP/IP”

If a device does not support the Web Service communication mode, use TCP/IP instead.
The following additional parameters need to be configured:

 FTP port and Telnet port: Those ports are fixed and cannot be changed.

 SSH port: Some LOYTEC devices (LINX-12x, LINX-22x, LINX-15x,


LVIS-3E11x, LVIS-ME21x, L-ROC) support SSH. For those devices the Use
secure connection for device management checkbox can be activated and the
SSH port can be configured.

Add a device with communication mode “E-mail”

1. Before mails can be received, the incoming mail server has to be configured. Select
Properties from the context menu of the project node in the navigation view and select
the Incoming mails tab.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 68 LOYTEC

Figure 56: Incoming Mail Configuration

 Incoming server: IP address of the incoming mail server.

 Server type: The LWEB-900 Server supports POP3 and IMAP.

 Port number: Incoming mail server port.

 Use secure connection (SSL)

 Username: User name for mail box access.

 Password: Password for mail box access.

 Check incoming mail period: The LWEB-900 Server checks the mail box
periodically for new mail. This value defines how often the mail box will be
checked.

 Keep mails on server after reading: The LWEB-900 Server can either remove
the processed e-mails from the server or leave them on the server.

 Store attached files locally: If this option is selected, the attached CSV log files
from the processed e-mails will be stored on the hard disk in the directory <project
directory>\MailInputBox\AttachedFiles.

2. Select the folder Network/Devices or a subfolder and choose New  New device
from the context menu.

3. In the New Device dialog (see Figure 57) enter the following data:

 Family: Select the LOYTEC device family from the drop-down list.

 Type: Select the LOYTEC device type from the drop-down list.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 69 LOYTEC

 Name: User defined name to identify the device.

 Description: Description of the device.

 Communication: Select E-mail.

 State: If the device is online, select Enabled, else select Disabled.

 Serial number: Serial number of the LOYTEC device. The serial number is part
of the CSV log files which are transmitted by LOYTEC devices.

Figure 57: Add Device with Communication Mode E-mail

4. The new device is displayed in the navigation view. After the first data has been
received via e-mail, the trend logs and alarm logs will be displayed in the
corresponding folders (see Figure 58).

Figure 58: Device Trend and Alarm Logs

rd
Add 3 party BACnet devices using network scan

LWEB-900 Server supports an online network scan on the BACnet network. In this scan the
LWEB-900 server searches for other devices on the BACnet network and pulls in the
BACnet object information of these devices.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 70 LOYTEC

1. Select the folder Network/Devices or a subfolder and choose Scan BACnet Network
from the context menu. This opens the BACnet network scan dialog as shown in Figure
59.

Figure 59: BACnet Network Scan

2. Click on the Scan Network button to start a network scan. The results are put in the
device list below.

3. Select one or multiple devices in the device list and click the Add Selected Devices…
button.

4. The new devices are displayed in the navigation view. You have access to all BACnet
objects and their properties (see Figure 60).

Figure 60: BACnet Objects

rd
Add a 3 party BACnet device offline

If the BACnet device is not yet online, it is possible to add it as follows:

1. Select the folder Network/Devices or a subfolder and choose New  New device
from the context menu.

2. In the New Device dialog (see Figure 61) enter the following data:

 Family: Third-party device.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 71 LOYTEC

 Type: BACnet/IP.

 Name: User defined name to identify the device.

 Description: Description of the device.

 State: If the device is online, select Enabled, else select Disabled.

 BACnet instance: Instance number of BACnet device object. The instance


number must be unique in the BACnet network.

 BACnet address: The BACnet address consists of BACnet network number and
BACnet MAC address. For a BACnet/IP device the BACnet MAC address is
defined by its IP address and UDP port.

 Management password: Enter the password required for device management


functions (reset, backup/restore). For LOYTEC devices the default password is
“loytec4u”.

 Communication profile: Select one of the available communication profiles from


the drop-down list. Per default the communication profiles LAN, WAN, and
WLAN are available. The LAN setting ensures fast response times, the WAN
setting saves bandwidth; the WLAN setting limits the number of parallel file
transfers. Refer to Section 6.24 for details.

Figure 61: Add 3rd Party BACnet Device

3. Press the button Test connection to verify that LWEB-900 can communicate with the
device correctly.

4. In the next dialog you are offered the following options:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 72 LOYTEC

 Upload device configuration: Choose this option if the BACnet device is online.
LWEB-900 will upload the BACnet object information of the device.

 Import device configuration: Choose this option if the device is offline. You can
either import an EDE file and the corresponding state text file or assign the
configuration of a different device (see Figure 62). The latter option is useful if
you have multiple devices with identical configuration.

 Cancel: Perform none of the above actions. You can execute any of the actions
later from the context menu of the device.

Figure 62: Import BACnet Device Configuration

5. The new device is displayed in the navigation view. If you have uploaded the device
configuration or imported a configuration, you now have access to all BACnet objects
of the device (see Figure 60).

Organize devices

To keep track of a large number of devices, it is recommended to organize them in folders.


To create a folder, select Add folder from the context menu. Devices can easily be moved
between folders using drag-and-drop.

6.7 Configure LOYTEC Devices


Configuration Software

LOYTEC devices can be configured very comfortably because the required software can be
started directly in LWEB-900. The L-VIS, L-INX, and L-DALI Configurators are separate
software packages which can be downloaded from the LOYTEC homepage. When the
LWEB-900 Client is started, it checks which Configurators are installed on your PC and
displays any missing components (see Figure 63).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 73 LOYTEC

Figure 63: Device Configuration Software Not Installed

If the corresponding configuration software is installed, you can right-click on a device in


the navigation view and select Configure device.

Figure 64: L-VIS Configuration Software in LWEB-900

The configuration software of the different LOYTEC devices is outside the scope of this
document. It is described in the corresponding product manuals instead (see Table 6).
Figure 65 shows the part of the device configuration toolbar which is independent of the
product type.

Figure 65: Common Button for Device Configuration

 Save Configuration: Save the current configuration in the LWEB-900 database.


The navigation view will be updated with the objects created in the device
configuration software.

 Upload Configuration: If the configuration on the device is newer than the


configuration in the LWEB-900 database, use this button to upload it. It will

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 74 LOYTEC

upload the entire configuration from the device, including data points, NVs,
registers, client mappings, schedules, etc.

 Download Configuration: To download the configuration, the device must be


online. Before downloading the configuration, it will be saved in the LWEB-900
database.

Device Family Configuration Software

L-VIS L-VIS devices are configured with the L-VIS Configurator. Refer
to the L-VIS User Manual [1] for details.
L-INX, L-GATE L-INX and L-GATE devices are configured with the L-INX
Configurator. Refer to the L-INX/L-GATE User Manual [2] for
details.
L-IOB L-IOB devices are configured with the L-INX Configurator. Refer
to the L-IOB User Manual [3] for details.
L-DALI LDALI-3E10x devices are configured with the L-DALI
Configurator. LDALI-ME20x devices are configured using the
web interface and do not need a separate configuration software.
Refer to the L-DALI User Manual [5] for details.
Table 6: Device Configuration Software

Note: If you are using a network management tool based on LNS, do NOT configure the devices
in LWEB-900, but start the device configuration software from the network management
tool in plug-in mode.

Note: The device configuration software accesses the device directly and does not go through the
LWEB-900 Server.

Access Web UI of device

The web UI of a LOYTEC device can be accessed easily by selecting Open device web UI
from the context menu. There is no need to remember the password of each device.
Depending on your access rights (see Sections 6.17.4 and 6.28) to the device, you will be
automatically logged in as admin user or as operator user.

6.8 Identification Key


In LWEB-900 each data point is uniquely identified by its path and name. Optionally, you
can define your own identification key schema and assign identification keys to each data
point. Figure 66 shows an example.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 75 LOYTEC

Figure 66: Identification Key Example

Define identification key schema

1. Select Properties from the context menu of the project node in the navigation view and
select the Identification key tab (see Figure 67).

2. An identification key consists of a number of fields which have fixed length. To add a
new field, click on the Add field button.

3. Specify a name and the length of the field.

4. Each field can have a number of predefined values. Define the values and optionally
add a description.

5. Click on the Apply button to save the field configuration.

Figure 67: Identification Key Schema

Assign identification keys to data points

1. In the object list view, click on the toolbar button Configure columns and add the
Identification Key (IK) column.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 76 LOYTEC

2. Click on the identification key which you want to change. The identification key is split
into its fields as shown in Figure 68. For each field you can select one of the predefined
values or enter a new value.

Figure 68: Assign Identification Key

Multi-edit identification key fields

1. In the object list view, click on the toolbar button Configure columns and add the
identification key fields which you want to change.

2. Select multiple data points in the object list view.

3. Click on the identification key field of the first data point and change it (see Figure 69).
The identification key of all selected data points is changed.

Figure 69: Multi-Edit Identification Keys

Assign identification keys from data point name or description

The name or description of a data point can be used as part of the identification key.

1. In the navigation, click with the right mouse button on a device or a device folder and
select Identification Keys  Assign Identification Keys… from the context menu.

2. The Assign Identification Keys dialog allows the definition of a Constant Part which
is assigned to the identification keys of all data points in the folder and a Dynamic
Part which is derived either from the data point name or description. In the example

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 77 LOYTEC

shown in Figure 70, the first two fields of the identification key will be set to the
constant value “VIE BG35” for all data points in the folder. The rest of the
identification key, starting with the field “Level” and ending with the field “Data Point
Idx”, will be set to the name of the data points.

Figure 70: Assign Identification Key

Change identification key schema

If you need to change the length of an identification key field or add a new field, all existing
identification keys will be affected. LWEB-900 can give you a preview of the effect of the
change.

1. Select Properties from the context menu of the project node in the navigation view and
select the Identification key tab

2. Change the identification key definition.

3. Click on the button Select datapoint for preview to see the effects of your change.

4. If you do not set the checkbox Change existing identification keys, the existing
identification key strings will be left unchanged. In the example shown in Figure 71, the
length of the field “Location” has been increased from three to four characters. Because
the field boundaries change, the values of all fields change. If you activate the
checkbox, the configuration key strings will be modified as shown in Figure 72. Note,
that the configured Fill character is used to bring the length of the field “Location”
from 3 characters up to 4 characters.

Figure 71: Do Not Change Existing Identification Keys

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 78 LOYTEC

Figure 72: Change Existing Identification Keys

Export identification keys

1. Right click on a data point folder in the navigation view and select Identification Keys
 Export Identification keys to CSV file from the context menu.

2. Select a destination folder and filename.

The format of the exported file is documented in Section 8.3.

Import identification keys

1. Right click on a data point folder in the navigation view and select Identification Keys
 Import Identification keys from CSV file from the context menu.

2. The identification keys are imported relative to the selected folder.

Export identification key schema

1. Select Properties from the context menu of the project node in the navigation view and
select the Identification key tab.

2. Click on the Export schema… button.

3. Select a destination folder and filename.

Import identification key schema

1. Select Properties from the context menu of the project node in the navigation view and
select the Identification key tab.

2. Click on the Import schema… button.

3. Select the identification key schema file.

6.9 Advanced Search and Search View


Advanced Search

To access additional search options in the object list view, click on the Advanced search
button. The following search parameters can be configured:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 79 LOYTEC

 Search options: Select whether you want to search in the identification key, name,
description, or path.

 Search string: An object satisfies the search condition if its identification key,
name, description, or path contains the specified search string.

Note: To search for a specific field of a structured data point or BACnet property, use the “.”
separator in the data point name (e.g. nviSBstateFb.pos).

You can use the asterisk (*) and question mark (?) as a wild card characters in the search
string. The asterisk matches zero or more characters, the question mark matches any single
character. For example, the search string “nvi*Fb” finds all data points which have names
starting with “nvi” and ending with “Fb”.

 Object type: This drop-down box allows limiting the search to certain object
types.

Figure 73: Search in Name

Figure 74: Search in Identification Key

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 80 LOYTEC

The Advanced tab allows you to combine multiple conditions with AND and OR
operators.

Figure 75: Advanced Search Condition

Save search parameters in search view

If you regularly search for a certain type of objects, it might be useful to save your search. If
you click on the Save Search View button, a new search view with the current search
parameters is created in your home directory. The next time you want to execute the search,
just double click it, and you will see the current objects that match the original search. To
modify the search parameters, click on the Properties button in the search view toolbar.

Figure 76: Search View Icon

To create a search view in another folder than your home directory, right click on the folder
and select New  New search view from the context menu.

6.10 Watch View


The watch view allows observing data point values in real time. Per default each user has
his own watch view stored in his home directory (see Figure 77). Double click on the watch
view to open it. To monitor data points, drag them from an object list view to the watch
view.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 81 LOYTEC

Figure 77: Watch View in Home Directory

Create new watch view

1. Right click on a folder in the navigation view and select New  New Watch View
from the context menu. A watch view can be created in root folder (the project node),
in the home folder of the user, or in any user defined folder.

2. Enter a name and a description for the watch view and click on OK.

3. The new watch view is created and displayed in the navigation view. Double click the
watch view to open it. A new watch view does not contain any data points.

Add data points to watch view

1. Select the data points you want to monitor in the object list view and drag them to the
watch view as shown in Figure 78.

2. Save your changes to the watch view by clicking on the Save button in the toolbar.

Figure 78: Add Data Points to Watch View

Note: OPC data points and BACnet properties are refreshed automatically in the watch view.
They are marked with a small “O” in the top right corner of the data point symbol. To
expose a data point via OPC, the corresponding checkbox has to be activated in the
LOYTEC device configuration software. Other data points of LOYTEC devices can also be
added to the watch view. Their values are refreshed when clicking the refresh button in the
toolbar.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 82 LOYTEC

Change data point values

1. Click on the value of a data point. Depending on the data point type, a drop down list, a
number input, or a text input box is displayed (see Figure 79).

2. Enter the new value and press the Enter key.

Figure 79: Change Data Point Value in Watch View

Column Configuration

The columns of the watch view can be customized. Per default the Polled, Name, and
Value columns are displayed. To add columns or to change the column order, click on the
Configure columns toolbar button.

The column configuration is stored for each watch view separately. To change the column
configuration for the current watch view only, deactivate the Apply to all ‘Watch view’
objects checkbox and click the Apply button. To save the configuration for all watch views,
activate the checkbox and press the Apply button.

Column Description

Polled If this checkbox is set, the data point value is updated periodically.
Name Name of data point
Value Current value of the data point
Timestamp Timestamp of last value change
Type Data point type
Description Data point description
Referenced Referenced data point including the path
Identification Key (IK) Refer to Section 6.8
IK.<field name> The identification key consists of user defined fields. Each field
can be displayed as a separate column.
Table 7: Watch View Columns

Sorting

If no sort order is defined, data points in the watch view can be reordered using drag and
drop.

You can sort the watch view by clicking one of the column headings. The first click sorts
the data points in ascending order, the second click in descending order, and the third click
removes the sort order.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 83 LOYTEC

Print

Use the print button in the toolbar to print the watch view. The print dialog allows adjusting
the page margins and the font size.

Figure 80: Print Watch View

6.11 Graphical View


Graphical views are schematics to visualize and operate areas of a building. Each graphical
view can consist of a large number of dynamic display elements which reflect the current
status of the facilities. Figure 81 shows an example graphical view for an air handling unit.

Figure 81: Graphical View

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 84 LOYTEC

6.11.1 Operate Graphical View


A graphical view is displayed in the navigation view and in the object list view with a
special icon (see Figure 82) and can be opened with a double-click.

Figure 82: Graphical View Icon

Interact with schematics

When you move the mouse pointer over an element of the schematics which allows user
interaction, the form of the pointer changes from arrow to hand. Depending on the nature of
the element, clicking the element with your left mouse button will trigger an action (e.g.
switch to another page, hide or show parts of the schematic) or allow to change the value of
an underlying data point.

View data point details

You can easily access information about data points visualized in the graphical view. Click
with your right mouse button on the value of a data point to open a context menu. Select the
name of the data point for which you want to inspect the properties as shown in Figure 83
and Figure 84.

Figure 83: Graphical View Context Menu

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 85 LOYTEC

Figure 84: Data Point Properties

Error handling

If LWEB-900 cannot read the value of a data point from a LOYTEC device, the
corresponding visualization element is grayed out. The OPC error message will be
displayed when hovering over the control as shown in Figure 85.

Figure 85: Error Display in Graphical View

Navigation menu

The navigation menu can be opened by a click with the right mouse button on an empty area
in the schematics. If the right-click is executed over a control, a context menu is displayed
which allow to either open the navigation menu or to inspect the data point properties.

Zoom levels

The zoom level can be configured in the tool bar of the graphical view. If the zoom level is
set to Auto-scale, the schematics will be scaled to fit completely into the pane.

Print graphical view

Use the print button in the toolbar to print the graphical view. The print dialog allows
adjusting the page margins and the scale factor.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 86 LOYTEC

Figure 86: Print Graphical View

6.11.2 Configure Graphical View


In order to configure graphical views, the L-VIS Configurator has to be installed on your
PC. This software can be downloaded from the LOYTEC homepage. When the LWEB-900
Client is started, it checks which Configurators are installed on your PC and displays any
missing components (see Figure 63).

Create new graphical view

1. Right click on a folder in the navigation view and select New  New Graphical View
from the context menu. A graphical view can be created in the root folder (the project
node), in the home folder of a user, or in any user defined folder.

2. Enter a name and description for the graphical view and click on OK.

3. The new graphical view is created and displayed in the navigation view. Note, that a
data point interface folder is created below the graphical view.

Define data point interface

The data point interface folder contains all data points which can be used in the graphical
view. After creating a new project, the data point interface is empty. You can add data point
in one of the following ways:

 Pull data points from an object list view into the interface. A link to the original
data point is created.

 Drag a complete folder into the interface. In this case, a link to the folder is
created. If the contents of the original folder change (e.g. data point configuration
of a device is modified), the interface changes accordingly.

 Press the [CTRL] key while dragging a folder into the interface. The folder
including all its sub-folders is created in the interface and populated with data
point links.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 87 LOYTEC

You can create folders to organize data point and folder links by selecting New  New
Folder from the context menu.

Figure 87: Data Point Interface of Graphical View

Note Only OPC data points can be added to the interface of a graphical view. They are marked
with a small “O” in the top right corner of the data point symbol. To expose a data point
via OPC, the corresponding checkbox has to be activated in the device configuration
software.

Design graphics

To design the graphics, click with the right mouse button on the graphical view icon and
select Configure Graphical View from the context menu. The graphical design tool is
outside the scope of this document. It is described in the L-VIS User Manual [1].

Note If you dock an object list view showing the data point interface to the graphical design tool,
you can quickly attach data points to controls using drag-and-drop (see Figure 88).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 88 LOYTEC

Figure 88: Design Graphics

Broken Links

A data point link breaks if the referenced data point is removed (e.g. data point
configuration of the device is modified). If a graphical view contains a broken link, it is
marked with an asterisk in the navigation view to warn you. In the object list view, broken
links are marked with a special icon (see Figure 89). They can be easily fixed by dragging a
new data point on the broken link.

Figure 89: Broken Link

Show Page Actions

Using a Show page action, it is possible to create buttons in a graphical view which link to
other views. Figure 90 shows how to drag a view and drop it on the action object in the tree
view of the L-VIS Configurator.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 89 LOYTEC

Note The Show page action works inside the LWEB-900 Client. When using a web browser to
display a graphical view, only links to other graphical views or chart views are supported.

Figure 90: Show Page Action

Import Graphical View from LWEB-800/802 project

1. Right click on a folder in the navigation view and select New  New Graphical View
from the context menu.

2. Activate the checkbox Initialize from file and select the LWEB-800/802 project file.

Figure 91: Import LWEB-800 Project

3. The graphical view is created and displayed in the navigation view. The data point
interface contains a link to the device in the imported project (see Figure 92). If a
matching device with the same IP address exists in the LWEB-900 project, the link is
resolved automatically, else a broken link is displayed. To fix the broken link, simply
drag a device from the Devices folder and drop it on the broken link.

Figure 92: Navigation View after Import of LWEB-800 Project

6.11.3 Graphical View Templates


Use graphical view templates to create multiple graphical views with the same graphics but
referencing different data points. For example, you can create a graphical view template
which visualizes a room. This template can then be instantiated for each room in your
building. If you modify the template, all instances of the template will be updated.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 90 LOYTEC

Create new graphical view template

1. Right click the folder Library in the navigation view and select New  New
Graphical View Template from the context menu.

2. Enter a name and description for the graphical view template and click on OK.

3. Create the data point interface and the graphics in the same way as for a normal
graphical view (see Section 6.11.2).

Instantiate Template

1. Right click on a folder in the navigation view and select New  New Graphical View
from the context menu.

2. Enter a name and description for the graphical view.

3. Select the option Initialize from template and press the browser button to choose the
template. Click on OK.

4. Replace folder/data point links: Drag a folder/data point from a device in the Network
folder onto the folder/data point link in the data point interface for the template
instance.

Note Wherever possible, use folder links instead of data point links. A folder which contains
multiple data points can be relinked much faster than multiple separate data point links.

6.11.4 Graphical Views in LWEB-900 Server and in LOYTEC device


There are two types of graphical views:

 Graphical view in LWEB-900 Server: Graphical views of this type can be located
in any user folder in the navigation view. In order to display real-time data, the
graphical view communicates with the LWEB-900 Server using OPC XML-DA.
The LWEB-900 Server in turn communicates with LOYTEC devices using OPC
XML-DA. This approach has the advantage that it relieves the communication load
of the LOYTEC devices. For the LOYTEC devices it makes no difference whether
a graphical view is displayed only on one PC or on multiple PCs. The server
fetches the data only once from the LOYTEC devices and distributes it to multiple
graphical views (see Figure 94).

 Graphical view in LOYTEC device: These views are located in the Graphical
Views folder below a LOYTEC device (see Figure 93). In order to display real-
time data, the graphical view communicates directly with the LOYTEC devices
using OPC XML-DA. This approach has the advantage that it offers faster
response times. However, value changes cannot be logged by the server, because
the communication bypasses the LWEB-900 Server.

Figure 93: Graphical View in LOYTEC Device

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 91 LOYTEC

Figure 94: Comparison of Graphical View Types

Move graphical view from LWEB-900 Server to device

1. Right click on the LWEB-900 Server graphical view in the navigation view and select
Copy from the context menu.

2. Select the Graphical Views subfolder of the device to which you want to move the
graphical view and select Paste from the context menu.

3. If the new graphical view is working properly, remove the original LWEB-900 Server
graphical view.

Move graphical view from device to LWEB-900 Server

1. Right click on the device graphical view in the Graphical Views folder of the device
view and select Copy from the context menu.

2. Select the user folder to which you want to move the graphical view and select Paste
from the context menu.

3. If the new graphical view is working properly, remove the original device graphical
view.

Creating an L-VIS project from a LWEB-900 Server graphical view

1. Right click on the LWEB-900 Server graphical view in the navigation view and select
Copy from the context menu.

2. Use the right mouse button to click on the target L-VIS device in the navigation view
and select Paste from the context menu.

3. The L-VIS Configurator is opened and automatically converts the graphical view to an
L-VIS project.

4. Click on the Download Configuration button.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 92 LOYTEC

6.12 Parameter View


The parameter view allows to efficiently configure operational parameters which are
distributed over multiple devices. Figure 95 shows an example parameter view for room
temperature control. Each cell of the matrix represents a parameter. Parameters can be
organized freely in the matrix depending on space layout and function.

Figure 95: Parameter View

6.12.1 Operate Parameter View


A parameter view is displayed in the navigation view and in the object list view with a
special icon (see Figure 96) and can be opened with a double-click.

Figure 96: Parameter View Icon

Edit parameters

1. Parameter values can be edited in one of two ways:

 Edit single parameters: Click on the corresponding value field and enter a new
value.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 93 LOYTEC

 Edit multiple parameters: Select multiple parameters and select Edit from the
context menu (see Figure 97) and enter a new value.

Figure 97: Edit Multiple Parameters

2. Parameters which have been modified in the parameter view but have not yet been
saved yet are highlighted in green.

3. Press the Download Parameters button in the toolbar. A dialog showing the progress
is displayed.

Upload Parameters

To upload the currently configured parameters from the device(s) and save them in the
database, click on the Upload Parameters button in the toolbar.

Upload Parameters and Merge

1. Press the Upload Parameter and Merge… button in the toolbar. All parameters which
are different on the device and in the parameter view are highlighted in orange. Hover
the mouse over the value to see the different values.

Figure 98: Parameter Merge

2. Using the toolbar buttons you can choose between displaying the device values or the
view values.

3. To resolve the conflict for a single parameter, right click on the value and choose
between Resolve conflicts of selected parameters with view values and Resolve
conflicts of selected parameters with device values.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 94 LOYTEC

4. To resolve the conflict for all parameters in the same way, use the toolbar buttons
Resolve all conflicts with view values and Resolve all conflicts with device values.

5. Press the Download Parameters button in the toolbar. A dialog showing the progress
is displayed.

Print

Use the print button in the toolbar to print the parameter view. The print dialog allows
adjusting the page margins and the font size.

Figure 99: Print Parameter View

6.12.2 Configure Parameter View


To configure the parameter view, you have to switch from operating mode to configuration
mode. You can switch between the two modes using the toolbar buttons shown in Table.

Button Description

Change from operating mode to configuration mode


Change from configuration mode to operating mode
Table 8: Buttons to Switch between Operating and Configuration Mode

Create new parameter view

1. Right click on a folder in the navigation view and select New  New Parameter View
from the context menu. A parameter view can be created in the root folder (the project
node), in the home folder of a user, or in any user defined folder.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 95 LOYTEC

2. Enter a name and description for the parameter view and click on OK.

3. The new parameter view is created and opened in configuration mode.

Add parameters

Parameters can be added to the view by pulling them from an object list view to the
parameter list. You can also perform a search operation and then select the results and drop
them on the parameter list. The advanced search dialog, offers the possibility to filter for
objects of type Parameter (see Figure 100 and Figure 101).

Figure 100: Search for Object Type Parameter

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 96 LOYTEC

Figure 101: Add Data Points to Parameter View

Note Only parameters can be added to a parameter view. They are marked with a small gear
wheel in the top left corner of the data point symbol. To expose a data point as parameter,
the corresponding checkbox has to be activated in the device configuration software.

Assign column and row

When adding a new parameter, it is automatically assigned to a default row and column:
The parameter name determines the column and the path determines the row. To change the
default row, select one or multiple parameter and choose Change row of selected
parameters from the context menu. The default column can be changed by selecting the
option Change column of selected parameters.

Order rows and columns

The upper part of the parameter view displays a preview of the parameter matrix. To change
the column order, grab a column header and drag it to the desired new position. Rows can
be reordered in the same way.

6.12.3 Parameter View Templates


Use parameter view templates to create multiple parameter views with the same parameter
names but different paths. The parameter view template defines the parameter view columns
and specifies a search pattern for each column.

Create new parameter view template

1. Right click the folder Library/Parameter View Templates/User Parameter View


Templates in the navigation view and select New  New Parameter View Template
from the context menu.

2. Enter a name and description for the parameter view template.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 97 LOYTEC

3. Add a new column by pressing on the plus icon for columns. Configure the following
properties:

Property Description

Column Name Name of the column displayed in the parameter view


Description The description is displayed as tooltip for the column name
Read only If this checkbox is set, parameter values in this column cannot be
changed
Width Width of the column in pixels. If 0 is configured, the width of the
parameter column is adjusted automatically depending on the
values.
Table 9: Column Properties in Parameter View Template

4. Add parameters to the column by pressing on the plus icon for parameters. Configure
the following properties:

Property Description

Search pattern The search pattern specifies the path and name of the parameter(s)
which are displayed in the column. Up to 9 wild card characters (*
and ?) can be used to define the search pattern.
Row name This property defines in which row(s) the parameter(s) defined by
the search pattern should be displayed. The following placeholders
can be used:
\1, \2, … \9: replaced by content matched by first, second, … ninth
wildcard character
\d: replaced by name of the device
Table 10: Parameter Properties in Parameter View Template

Note Instead of configuring the properties from scratch it is often easier to use the search icon
and select a single parameter. The search pattern and row name can then be modified to
include wildcard characters.

5. Define the default search order of the rows in the parameter view. This step is optional.

Instantiate parameter view templates

1. Right click on a folder in the navigation view and select New  New Parameter View
from the context menu.

2. Enter a name and description for the parameter view.

3. Select the option Initialize from template and press the browser button to choose the
template.

4. Select one or multiple base objects. The base object is the starting point for searching
parameters which match the search patterns of the template. Examples for base objects
are the whole Network/Device folder, a specific device, or a data point folder.

6.13 Web View


Web views display the contents of a web page. They are useful to e.g. integrate web cams
into your LWEB-900 project. A web view is displayed in the navigation view and in the
object list view with a special icon and can be opened with a double-click (see Figure 102
and Figure 103).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 98 LOYTEC

Figure 102: Web View Icon

Figure 103: Web View

Create new web view

1. Right click on a folder in the navigation view and select New  New Web View from
the context menu. A web view can be created in the root folder (the project node), in
the home folder of a user, or in any user defined folder.

2. Enter a name, description, and an URL for the web view and click on OK.

3. The new web view is created and displayed in the navigation view.

6.14 Alarming
In the bottom right corner of the LWEB-900 client window, the status bar displays an icon
reflecting the current alarm state. To see the alarm details, double click on the icon and the
alarm view is opened.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 99 LOYTEC

Figure 104: LWEB-900 Client Status Bar

Icon Description

At least one active, not acknowledged alarm


At least one active, acknowledged alarm
At least one inactive, not acknowledged alarm
No alarms
Table 11: Alarm Icons in LWEB-900 Status Bar

6.14.1 Alarm View


The alarm view displays the currently pending alarms. It can be opened by clicking on the
alarm icon in the LWEB-900 status bar or by selecting Show Alarms from the context
menu of a folder. An example is shown in Figure 105.

Figure 105: Alarm View

Alarm path

LWEB-900 receives alarms from a number of different sources which are called alarm
servers. Each LOYTEC device can have one or multiple alarm servers. System alarms
originate from the LWEB-900 alarm server in the folder System/Alarming (see Section
6.14.2). The alarm view displays only alarms from alarm servers which are inside the path
set in the breadcrumb navigation bar. To see all alarms, select the top folder. To see alarms
of a single device only, select the corresponding device folder. To see system alarms only,
select the System folder.

Alarm filter

The alarm filter lets you drill down to the specific alarms you want to see. The alarm view
offers a number of predefined filters described in Table 12 or you can use the powerful
custom filter.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 100 LOYTEC

Column Description

All Enabled Alarms Display alarms which are not disabled and have one of the
following states:
 Active, not acknowledged
 Active, acknowledged
 Inactive, not acknowledged
Not Acknowledged Alarms Display alarms which are not disabled and have one of the
following states:
 Active, not acknowledged
 Inactive, not acknowledged
Active Alarms Display alarms which are not disabled and have one of the
following states:
 Active, not acknowledged
 Active, acknowledged
Disabled Alarms Display all disabled alarms.
Table 12: Predefined Alarm Filters

Figure 106 shows an example of a custom filter definition. As you can see, the custom filter
allows to combine multiple conditions with AND and OR operators.

Figure 106: Custom Filter

Acknowledge alarms

To acknowledge alarms, select one or multiple alarms and choose Acknowledge selected
alarms from the context menu. Or alternative, you can use the corresponding toolbar
button.

In the project settings, you can configure that users have to enter a comment when
acknowledging alarms with a priority higher than a certain value (see Figure 107).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 101 LOYTEC

Figure 107: Alarming Configuration

Disable alarms

To disable alarms, select one or multiple alarms and select Disable selected alarms from
the context menu. When you disable an alarm, you can enter a comment explaining the
reason why you disabled the alarm. The disabled alarms disappear from the current alarm
view. To see the disabled alarms, select Disabled Alarms from the alarm filter drop-down
box. Disabled alarms can be enabled again, by selecting Enable selected alarms from the
context menu.

Multiple occurrences of the same alarm

If the same alarm is triggered multiple times, only the last alarm entry is displayed. This
alarm entry can be expanded to see the previous occurrences of the alarm (see Figure 108).

Figure 108: Multiple Occurrences of the Same Alarm

Column Configuration

The columns of the alarm view can be customized. To add columns or to change the column
order, click on the Configure columns toolbar button.

The column configuration is stored for each alarm view separately. To change the column
configuration for the current alarm view only, deactivate the Apply to all ‘Alarm view’

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 102 LOYTEC

objects checkbox and click the Apply button. To save the configuration for all alarm views,
activate the checkbox and press the Apply button.

Column Description

Id Unique alarm ID
Alarm Time Date and time when the alarm occurred.
Clear Time Date and time when the alarm condition was cleared. If the alarm
is still active, this field is empty.
Ack. Time Data and time when the alarm was acknowledged. If the alarm has
not yet been acknowledged, this field is empty.
Ack. Source Name of the user who acknowledged the alarm. If the alarm has
not yet been acknowledged, this field is empty.
State An alarm undergoes a number of state changes during its life-
cycle. When the alarm occurs, it is Active, not acknowledged.
The alarm can be acknowledged by a user. Then it becomes
Active, acknowledged. Alarms can also become inactive, but an
acknowledgement is still required. Then they become Inactive,
not acknowledged. When an alarm is inactive and was
acknowledged it disappears from the alarm view.
Type An alarm can be of different alarm types. The alarm type specifies
the class of the alarm. The following alarm types exist:
 Off-Normal: This alarm type is a generic alarm class. It
indicates that the alarmed data point is on an off-normal
operating condition that triggered the alarm. An alarm value
is supplied, if the technology supports it.
 High/Low Limit: This alarm type is typical for analog alarm
conditions. It applies when the alarmed value is over or under
the defined alarm limits. An alarm value is supplied, if the
technology supports it.
 Fault: This alarm type is indicating that the monitored data
point or device is in a fault state.
Value Value of the data point at the time the alarm occurred.
Description Description of the alarm condition. The description is configured
in the device configuration software.
Priority Priority of the alarm.
Source  Device: The alarm was generated by a LOYTEC device.
 Server: The alarm was generated by the LWEB-900 Server.
Device Name of the device which was the source of the alarm.
Alarm Server Name of the alarm server which was the source of the alarm
Alarm Server Path Path to alarm server.
Source Name Name of the data point which was the source of the alarm.
Identification Key (IK) Identification key of the data point which was the source of the
alarm. Section 6.8 describes how to assign identification keys to
data points.
Disable Source Name of the user who disabled the alarm. If the alarm is not
disabled, this field is empty.
Comment This text is entered by the user when he disables an alarm and
specifies the reason. If the alarm is not disabled, this field is
empty.
XAID On a LOYTEC device, each alarm is uniquely identified by the
XAID. The XAID is used in the acknowledgement to identify the
alarm.
Table 13: Alarm View Columns

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 103 LOYTEC

Save alarm view

If you regularly need to filter for certain alarms, it might be useful to save your alarm view.
A new alarm view with the current path and filter settings is created in your home directory.
The next time you want access the alarm view, just double click it, and you will see the most
current alarms matching your path and filter.

Figure 109: Alarm View Icon

Print alarm view

Use the print button in the toolbar to print the alarm view. You can print all alarms or only
alarms which occurred during a configurable time interval. The print dialog allows adjusting
the page margins and the font size.

6.14.2 System Alarms


LWEB-900 monitors all LOYTEC devices. If a device is not responding, the device icon in
the navigation view turns red and a fault alarm is generated in the LWEB-900 alarm server
which is located in the folder System/Alarming.

Figure 110: LWEB-900 Alarm Server

Configure priority of system alarms

1. Right click on the LWEB-900 Alarm Server and select Properties from the context
menu.

2. Select the priority for system alarms. The highest priority is 0, the lowest priority is
255.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 104 LOYTEC

Figure 111: LWEB-900 Alarm Server Properties

6.14.3 Alarm Notification


When an alarm occurs, LWEB-900 can notify one or multiple users via e-mail or log the
alarm in a text file. The target of the notification is called an alarm receiver. Primary alarm
receivers are notified as soon as the alarm occurs. Secondary alarm receivers are notified
only if the alarm is not acknowledged in time. A prerequisite to sending e-mails is the
configuration of the outgoing e-mail server as described in Section 6.18.

Create new alarm notifier

The alarm notifier determines which alarms are notified to which alarm receivers. It also
defines the format of the notification.

1. Right click on a folder in the navigation view and select New  New Alarm Notifier
from the context menu. An alarm notifier can be created in the root folder (the project
node), in the home folder of a user, or in any user defined folder.

2. Enter a name and description for the new alarm notifier.

3. Define notification properties:

 Acknowledge timeout: An alarm is sent to the primary receivers first. If it is not


acknowledged after the acknowledgement timeout, the alarm is sent to the
secondary alarm receivers. To disable the acknowledge timeout, set it to 0.

 Notify alarm state changes: If this checkbox is active, the alarm receivers will be
notified when the state of an alarm changes (e.g. alarm condition cleared, alarm
acknowledged).

 Aggregation time: This parameter defines the time period in which LWEB-900
collects alarm notifications before it sends an e-mail. All alarm notifications
occurring during this time are included in the e-mail. Use this setting to receive
related alarm notifications in a single e-mail.

 Min. send time: This parameter defines the minimum time that elapses between
two e-mail notifications. If alarm notifications occur more often, they are
postponed and sent after the minimum send time. Use this setting to limit the e-
mail transmission rate.

4. Define one or more notification templates. In case of an e-mail receiver, the template is
used for the subject and message body. If the alarm is logged to a text file, the template
specifies the format of the log entry. You can easily add any column of the alarm view
(see Table 13) to the template body using the context menu.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 105 LOYTEC

Figure 112: Alarm Notifier, Properties

5. Switch to the Alarm Servers tab and specify a folder as the Base object. The base
object serves the same function as the path in the alarm view: the alarm notifier applies
only to alarms from alarm servers which are inside the base folder.

6. Enable custom filter: If you enable this checkbox, only alarms will be notified which
pass through the configured filter. This filter has the same functionality as the custom
filter for the alarm view.

7. Switch to the Alarm Receivers tab to define who should be notified of the alarm. The
primary alarm receivers are notified as soon as the alarm occurs. Secondary alarm
receivers are notified only if the alarm is not acknowledged in time. To add an alarm
receiver, click on the corresponding plus icon.

8. Enter a name for the alarm receiver and select the type. LWEB-900 supports the
following alarm receiver types:

 E-Mail Alarm Receiver: This alarm receiver sends an e-mail notification to one
or multiple e-mail addresses.

 File Alarm Receiver: This alarm receiver logs alarms in a text file.

 Client Notification Alarm Receiver: This alarm receiver displays a pop-up


message inside the LWEB-900 Client when an alarm occurs.

9. Configure the properties of the alarm receiver as described in the following tables.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 106 LOYTEC

Property Description

Alarm Template This template is used for the e-mail body when an alarm occurs.
Alarm State Changes This template is used for the e-mail body when the alarm changes
Template its state. You have to assign this template only if you have selected
the option Notify alarm state changes.
Enable Per default this parameter is set to Always. When you click on this
parameter, you can select an enable data point and specify the
enable condition. Use an LWEB-900 Server scheduler to control
the enable data point (see Section 6.15)
E-Mail addresses Select the e-mail addresses which should be notified about the
alarm. The list of available e-mail addresses contains all users for
which an e-mail address has been specified (see Section 6.27). If
you want to send alarm notification to an e-mail address which
does not belong to an LWEB-900 user, you can add this e-mail
address in the project properties: Select Properties from the
context menu of the project node in the navigation view and
switch to the Outgoing mails tab.
Table 14: E-Mail Alarm Receiver Properties

Property Description

Alarm Template This template defines the format of a log entry in the text file when
an alarm occurs.
Alarm State Changes This template defines the format of a log entry in the text file when
Template the alarm changes its state. You have to assign this template only if
you have selected the option Notify alarm state changes.
Enable Per default this parameter is set to Always. When you click on this
parameter, you can select an enable data point and specify the
enable condition. Use an LWEB-900 Server scheduler to control
the enable data point (see Section 6.15)
File name Specify the name of the log file. The file is stored on the server in
the directory <project directory>\AlarmReceiverFiles\
Table 15: File Alarm Receiver Properties

Property Description

Alarm Template This template is used to display alarm information in the popup
message when an alarm occurs.
Alarm State Changes This template is used to display alarm information in the popup
Template message when the alarm changes its state. You have to assign this
template only if you have selected the option Notify alarm state
changes.
Enable Per default this parameter is set to Always. When you click on this
parameter, you can select an enable data point and specify the
enable condition. Use an LWEB-900 Server scheduler to control
the enable data point (see Section 6.15)
Users & Groups Select the users and groups which should be notified.
Popup Message Enter a text which will be displayed as part of the popup window.
Sound Select a sound which is played for notification. This property is
optional.
View The popup message can contain links to views (e.g. graphical
view, alarm view). This property is optional
Table 16: Client Notification Alarm Receiver Properties

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 107 LOYTEC

6.14.4 Alarm Log


The alarm view contains a live list of currently active and acknowledge-pending alarms. As
soon as an alarm becomes inactive and has been acknowledged, it disappears from the alarm
view. To store a historical log of alarm transitions, the alarm log in the folder
System/Alarming is utilized. This alarm log records transitions of the LWEB-900 alarm
server and all device alarm servers.

LOYTEC devices can have their independent alarm logs. Those device alarm logs are part
of the device configuration and displayed in the Alarm logs sub folder of the device.

Figure 113: Alarm Log Icon

An alarm log can be viewed by double clicking on the alarm log icon in the navigation or
object list view.

Figure 114: Alarm Log

The contents of the alarm log can be exported as a comma separated value list (CSV
export). The alarm log window can be refreshed by hitting the [F5] function key or pressing
the Refresh value toolbar button. If the log contains a large number of entries, the log is

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 108 LOYTEC

split into multiple pages and the buttons at the bottom can be used to navigate through the
pages. Alternatively, the Go to date button can be used to jump to a specific date and time.

Note Alarms are a special kind of events. Therefore, you can also use the event view (see Section
6.17.4) to investigate alarm transitions. The event view is often more convenient, because
its filters let you drill down to the specific alarm transitions you want to see.

Filter alarm log

To search for specific records in the alarm log, click on the Filter Log Data button in the
toolbar. The filter dialog allows you to combine multiple conditions with AND and OR
operators. The example in Figure 146 finds all alarm log records with priority higher than
128 and the state “Active, not acknowledged”.

Figure 115: Alarm Log Filter

Print alarm log

Use the print button in the toolbar to print the alarm log. You can print all alarm log records
or only alarm events which occurred during a configurable time interval. The print dialog
allows adjusting the page margins and the font size.

6.15 Scheduling
Schedulers are objects that schedule values of data points on a timely basis. LWEB-900
distinguishes between two kinds of schedulers:

 Device scheduler: The scheduler is executed on a LOYTEC device. Device


schedulers should be used to schedule data points on the device.

 LWEB-900 Server scheduler: The scheduler is executed by the LWEB-900


Server. LWEB-900 Server scheduler should be used to schedule an LWEB-900
user register. The scheduled user register can in turn be used to trigger a report or
to enable/disable an alarm receiver.

Both scheduler types can be configured using the master schedule configuration view in
LWEB-900.

6.15.1 Device Schedulers


Device schedulers are part of the device’s data point configuration. Therefore, they are
created using the device configuration software. How to create device schedulers is outside
the scope of this document. Refer to the device specific manuals (see Table 6).

6.15.2 LWEB-900 Server Schedulers


LWEB-900 Server schedulers are located in the System/Scheduler folder. Per default a
new LWEB-900 project includes 10 schedulers which schedule LWEB-900 user registers of

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 109 LOYTEC

type Binary. Those user registers are located in the folder System/User Registers. If
necessary, additional user registers and schedulers can be created.

Figure 116: Default LWEB-900 Server Schedulers

Create new LWEB-900 user registers

1. Right click on the folder System/User Registers and select New  New Register…
from the context menu. This opens the register creation dialog as shown in Figure 117.

Figure 117: New LWEB-900 Server User Register

2. Enter a Name and Description for the register.

3. Select the Type of the register. The following types are available:

 Analog: An analog data point typically represents a scalar value.

 Binary: A binary data point contains a Boolean value. The State text defines
human-readable labels for the two Boolean states. Select one of the existing state
texts from the drop-down list or create a new one by clicking on the plus icon.

 Multistate: A multi-state data point represents a discrete set of states. The State
map defines the possible states and the human-readable labels. Select one of the
existing state maps from the drop-down list or create a new one by clicking on the
plus icon.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 110 LOYTEC

4. Select the Default value.

5. If you want to use the register in a Parameter view, select the Parameter checkbox.

6. Click OK.

Create a new LWEB-900 Server scheduler

1. Right click on the folder System/Schedulers and select New  New Scheduler… in
the context menu.

2. Enter a name for the schedule and a description.

3. Select the tab Datapoints (see Figure 118).

4. Click the Add… button. This opens a data point selector window.

5. Select the LWEB-900 Server user register to attach and click OK. For each of the
attached data points, one line appears in the list below the Add… button.

6. Data points can be removed from the scheduler by clicking Remove.

7. Select the default value for the attached data point.

8. Click OK.

Figure 118: New Scheduler, Datapoints Tab

6.15.3 Master Scheduler View


LWEB-900 offers the unique possibility of organizing schedules in a hierarchical way,
independently of whether they are executed. The resulting tree structure permits defining
entries which apply to all schedulers or only a subset. For example, a standard occupancy
schedule can be defined for a whole building. This global schedule can be modified for
certain areas of the building. The area specific entries can in turn be supplemented by room
specific entries (see Figure 119).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 111 LOYTEC

Figure 119: Schedule Hierarchy

6.15.3.1 Using the Master Scheduler View


To open the master schedule view, double click on any object in the schedule hierarchy.
The master schedule view is linked to the navigation view. Whenever a different hierarchy
level is selected in the navigation view, the master schedule view is updated. The current
hierarchy level is displayed on the top right (see Figure 120). The toolbar buttons shown in
Table 17 select the information which is displayed in the master schedule view.

Button Description

Display the schedule for a complete week from Monday to Sunday. The week is
selected in the calendar on the left.
Display the schedule details of a single day. The day is selected in the calendar on
the left.
Display all events in a list.
Display the calendar configuration.
Table 17: View Selection Buttons

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 112 LOYTEC

Figure 120: Master Scheduler View

Week view

Week view gives a quick overview of the scheduled events for one week. The week can be
selected in the calendar on the left. All events which are defined on the current hierarchy
level are displayed and can be modified. Events which are defined on higher hierarchy
levels are also displayed, but are greyed out and cannot be edited. Figure 121 shows an
example schedule for a specific meeting room. Figure 122 shows the same schedule for a
higher hierarchy level which applies to all meeting rooms.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 113 LOYTEC

Figure 121: Master Schedule Week View Example 1

Figure 122: Master Schedule Week View Example 2

The color of the timeline bar depends on the level of hierarchy on which the event is
defined. The color of the timeline bar corresponds with the color of the icons in the
navigation view (see Table 18).

Hierarchy Level Symbol in Timeline Bar Color


Navigation View

Master schedule level Green


User defined folder level 1 Brown
User defined folder level 2 Red
User defined folder level 3 Purple
Scheduler level Blue
Table 18: Schedule Hierarchy Levels

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 114 LOYTEC

If an event is overridden by events defined on lower hierarchy levels, the corresponding part on
the timeline is hatched. You can right click on the hatched part and select Show overriding
events… to see the list of events which override the event at that time (see Figure 122).

If you have defined a default value for the schedule, it is displayed at the top of the week
view.

Day view

The left side of the day view shows a preview similar to the week view. The right part shows the
details of all defined events. Lower priority events are displayed to the left and higher priority
events are displayed further to the right and partly cover the lower priority events (see Figure
123).

Events with higher priority override events with lower priority. There are three priority
levels:

 Low

 Normal

 Override

If two events have the same priority, the event on the lower hierarchy level overrides the
event on the higher hierarchy level.

Figure 123: Master Schedule Day View

Event List

The event list displays the events defined in the master schedule (see Figure 124). Events of the
current hierarchy level can be edited. Events which are defined on higher hierarchy level are
greyed out and cannot be edited. To see events defined on lower hierarchy levels, activate
the checkbox Show events defined at lower hierarchy levels.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 115 LOYTEC

Figure 124: Master Schedule Event List

Calendar

Events can reference a calendar pattern which defines on which days the event will be
active. Each calendar pattern is a collection of date entries (see Figure 125). Calendar
patterns can be defined on any hierarchy level. If you define a calendar patterns at the level
of the master schedule folder, it will apply to all master schedules.

Calendar patterns of the current hierarchy level can be edited. Calendar patterns which are
defined on higher hierarchy levels are greyed out and cannot be edited. To see calendar
pattern defined on lower hierarchy levels, activate the checkbox Show calendar patterns
defined at lower hierarchy levels.

If you select a calendar pattern or a date entry, the corresponding days are highlighted in the
calendar pane on the left.

Figure 125: Master Schedule Calendar

Configure presets

Presets define the set of values which can be scheduled. Each master schedule has its own
presets.

1. Double click on a master schedule in the navigation view.

2. Click on the toolbar button Define presets.

3. Click on the Create button to add a new presets (see Figure 126).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 116 LOYTEC

Figure 126: Preset Definition

4. For each preset, the following parameters can be changed:

 Name of the preset

 Color: The color is used to display the preset in week view and day view.

 Value

5. To set a default preset, right-click on the input field and select a preset from the context
menu. The default preset will be scheduled when no event is active.

Note The buttons Rename and Delete become active if the name of a preset is selected in the
table header.

Add events

1. Double click on a schedule hierarchy level in the navigation view.

2. Right click anywhere in the week view, day view, or event list and select Add event…
from the context menu.

3. Figure 127 shows an example for the event definition dialog. The following parameters
can be configured:

 Name: Each event is given a name. The name has to be unique.

 Value: Select a preset.

 Priority: If two events are scheduled at the same time, the priority defines which
event takes precedence. The following priority levels are supported:

o Low: Lowest priority

o Normal

o Override: Highest priority

If two events have the same priority, the event defined on the lower hierarchy level
takes precedence.

 Start, End, Duration: Define start and end time of an event. At the end of an
event, the value is withdrawn. This means that the event with the next highest
priority can take over and set a different value. If there is no lower priority event,

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 117 LOYTEC

the default preset will be sent out. If no default preset is defined, no value update
will be sent out.

 Event Type: The event type defines on which days an event will be active. The
following event types are supported:

o One-time: The event is active only on one specific date.

o Daily: The event is executed daily, starting at a specific date and ending
on another date or never.

o Weekly: The event is active on a specific weekday (e.g. every Monday).

o Monthly: Monthly events are repeated every month or only every


odd/even month.

o Yearly: Yearly events are repeated every year.

o Calendar: The days on which the event is active is defined by a calendar


pattern.

o Special: The special event type is available for compatibility reasons.

Figure 127: Event Definition

Add calendar patterns and date entries

1. Double click on a schedule hierarchy level in the navigation view. If you want to add a
calendar pattern which applies to all schedulers, select the master schedule folder.

2. Switch to the calendar view by clicking the corresponding button on the tool bar.

3. Right click anywhere in the calendar view and select Add calendar pattern… from the
context menu.

4. Specify a name for the new calendar pattern and click OK.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 118 LOYTEC

Figure 128: New Calendar Pattern

5. Right click on the new calendar pattern and select Add date entry… from the context
menu.

6. The dialog is very similar to the lower part of the event definition dialog. You can
define One-time, Daily, Weekly, Monthly, Yearly, or Special date entries.

Figure 129: New Calendar Date Entry

7. To add additional date entries to the same calendar pattern, repeat Step 5 and 6.

Note Calendar patterns can be defined on any hierarchy level. A calendar pattern will be visible
only at the hierarchy level it was defined and in lower hierarchy levels.

It is possible to add date entries on different hierarchy levels. Date entries are visible only
in the hierarchy on which they were defined and below. In this way, a calendar pattern can
be composed of different date entries in different hierarchy levels.

Download master schedules

After you have configured the schedules in LWEB-900, you have to download them to the
LOYTEC devices. The schedules are executed decentralized in the devices to increases
reliability of the system.

1. The download to the LOYTEC devices is triggered by pressing one of the buttons
shown in Table 19.

Button Description

Download schedulers in or below the currently selected hierarchy level.


Download all schedulers.

Table 19: Schedule Download Buttons

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 119 LOYTEC

2. The download dialog is shown in Figure 130. If the checkbox Process only modified
items is selected, only the schedulers which have been modified since the last
download will be downloaded. This is useful to speed up the download if you have a
large number of schedulers. If this checkbox is not active, all schedulers displayed in
the list below will be downloaded. This is useful to override any potential changes of
the schedulers on the devices.

Figure 130: Master Schedule Download

3. Press the Start download button.

Note Events which are in the past and unused calendar patterns will not be downloaded to the
LOYTEC device to save resources.

Upload schedules from device

After a schedule has been downloaded by LWEB-900 to a LOYTEC device, it can be


changed locally on the device (e.g. using the Web UI). LWEB-900 detects these changes
and marks changed schedulers with an asterisk. Changes are detected because LWEB-900
periodically polls the devices. The poll cycle is configured as part of the communication
profile (see Section 6.24).

LWEB-900 can upload local schedule changes only if they do not affect other schedulers.
This means that e.g. a change to the start or end time of an event, which was defined on the
scheduler level, can be uploaded. However, if an event is changed, which is defined on a
higher hierarchy level, it will not be uploaded because it might affect other schedulers.

1. The upload of schedules is trigged by pressing one of the buttons shown in Table 20.

Button Description

Upload schedulers in or below the currently selected hierarchy level.


Upload all schedulers.
Table 20: Schedule Upload Buttons

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 120 LOYTEC

2. The upload dialog is shown in Figure 131. If the checkbox Process only modified
items is selected, only the schedulers which have been detected as modified will be
uploaded. This option is useful to speed up the process if you have a large number of
schedulers. However, if schedulers have been changed since the last poll cycle of
LWEB-900, these changes will not be taken into account. If the checkbox is not active,
all schedulers displayed in the list below will be uploaded. Use this option to get the
most current scheduler configuration from the devices.

Figure 131: Master Schedule Upload

3. If the changes cannot be uploaded into the master schedule configuration, an error will
be displayed as shown in Figure 132. In this example the preset values were changed
using the Web UI. Because the presets affect all other schedulers under the same master
schedule node, the modified presets will not be uploaded to the master schedule
configuration.

Figure 132: Master Schedule Upload Error

4. To find out more about why the upload did not work, double click on the scheduler in
the upload dialog. The pop-up window shows on the left side the scheduler as
configured in LWEB-900 and on the right side the changes made on the device (see
Figure 133).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 121 LOYTEC

Figure 133: Schedule Comparison

Note If you have a master schedule which contains only a single scheduler, define the events on
the scheduler level. This gives you the possibility to upload any local changes.

Print master scheduler view

Use the print button in the toolbar to print the currently displayed view of the master
scheduler. The print dialog allows adjusting the page margins and the scale factor.

Figure 134: Print Master Scheduler View

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 122 LOYTEC

6.15.3.2 Configure Master Schedule View


Create new master schedule

1. Right click on the master schedule folder and select New  New Master Schedule
from the context menu. If no master schedule folder exists yet, right click on the project
node instead. The master schedule folder is created automatically when creating the
first master schedule.

2. Enter a name and description for the new master schedule and click on OK.

3. The new master schedule is displayed in the navigation view. Double click the master
schedule to open the master schedule view.

Configure scheduler hierarchy

1. To add a hierarchy level select New hierarchical folder from the context menu. Each
hierarchy level can contain further hierarchy levels. Up to three nested hierarchy levels
can be created under the master schedule node. All events defined on a specific
hierarchy level affect all schedulers attached to the same or lower hierarchy levels.

2. To add schedulers to a hierarchy level select Add scheduler… from the context menu.
Device schedulers as well as LWEB-900 Server schedulers can be added. All
schedulers which are added under a master schedule node must be compatible. This
means that the number and type of the scheduled data points must be identical.

Figure 135: Add Scheduler

Note LWEB-900 takes over the presets from the first scheduler which is added to a master
schedule node. Presets can be edited any time.

Scheduler naming rules

Per default a new scheduler is displayed using the name of the scheduler data point. This
can be a problem if multiple schedulers have identical names. You can either rename the
scheduler in LWEB-900 or define a new naming rule which can include the path
information. To define a naming rule right click on a node in the master scheduler and select
Define Schedules Naming Rules from the context menu. Scheduler naming rules are

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 123 LOYTEC

inherited from a node to all lower hierarchy levels. Figure 136 shows an example naming
rule. Right click in the Schedule name format field to add placeholders as defined in Table
21.

Figure 136: Scheduler Naming Rules

Placeholder Description

[Scheduler Name] Name of the scheduler data point


[Device Name] Name of the device
[PathParent(n)] The path of the scheduler consists of a sequence of folders. The
[PathParent(n)] placeholder is replaced with the n-th folder
starting from the right.
[PathFolder(n)] The path of the scheduler consists of a sequence of folders. The
[PathFolder (n)] placeholder is replaced with the n-th folder
starting from the left.
Table 21: Placeholders for Scheduler Naming Rule

Scheduler and calendar limitations

Each LOYTEC device has only a limited amount of resources. LWEB-900 knows about
these limitations and checks every time a preset, event, or calendar pattern is added whether
there are enough resources available. Figure 137 shows an example error message which is
caused by adding too many presets.

Figure 137 Too Many Presets Defined

For CEA-709 devices, the number of available daily schedule, calendar patterns, etc. can be
configured in the configuration software. Open the menu Settings  Project Settings …
and select the CEA709 AST tab as shown in Figure 138.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 124 LOYTEC

Figure 138: Project Settings, CEA709 AST Tab

For the master schedule view, the following settings are relevant:

 Number of calendar patterns: Influences the number of calendar patterns which


can be created in a master schedule. However, there is no one-to-one mapping of
calendar patterns in a master schedule and in a device. Depending on the
configuration, LWEB-900 sometimes has to split a calendar pattern into multiple
calendar patterns before downloading it into the device.

 Total number of date entries: This parameter specifies the total number of date
entries for all calendar patterns on a device.

 Number of daily schedules: Defines how many events can be created.

 Entries in Time/Value table: Also limits the maximum number of events. Each
event consists of 2 time/value pairs.

 Number of value templates: Defines the maximum number of presets.

Note: Every change of the CEA709 AST settings changes the static network interface of the
device.

6.16 Trending
Trending refers to the ability to log values of data points over time. LWEB-900
distinguishes between two kinds of trend logs:

 Device trend log: The data points are logged by a LOYTEC device. The
LWEB-900 Server reads out the stored data periodically (e.g. once a day). This

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 125 LOYTEC

approach has the advantage, that data points are logged even if the LWEB-900
server is offline. Moreover, the traffic between LWEB-900 server and LOYTEC
devices is kept to a minimum.

 LWEB-900 Server trend log: The data points are logged directly by the
LWEB-900 server. This approach has the advantage that you do not need to
change the configuration of the LOYTEC device. However, the LWEB-900 Server
has to access the device much more frequently. Therefore, the LWEB-900 Server
trend log is recommended only for temporary trends.

Trend logs can be visualized using a chart view. One chart view can reference multiple
trend logs.

6.16.1 Trend Log Size Limitation


Even on a server with a large hard drive, the disk space is limited. Therefore, you need to
configure for how long the LWEB-900 Server keeps old trend log records.

Configure default values for log size limitations

1. Select Properties from the context menu of the project node in the navigation view and
switch to the Database Log Limitations tab.

2. The trend and alarm log size is limited by the following parameters (see Figure 139):

 Size limit: Trend and alarm logs are organized as ring buffers. As soon as the
maximum number of log items has been reached, new log entries will overwrite the
oldest entries.

 Duration limit: This parameter defines the maximum time span for which old data
is kept before deleting it from the database.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 126 LOYTEC

Figure 139: Database Log Limitations

New trend logs are assigned the configured default values. These initial values can be
changed any time by editing the properties of an individual trend log.

6.16.2 Device Trend Logs


Device trend logs are part of the device’s data point configuration. Therefore, they are
created using the device configuration software. How to create device trend logs is outside
the scope of this document. Refer to the device specific manuals (see Table 6).

LWEB-900 automatically detects new records in trend logs of LOYTEC devices. Before the
trend log buffer on the device can overrun, LWEB-900 reads out the trend log data and
stores it in the LWEB-900 database on the PC. The trend log poll cycle is configured as part
of the communication profile (see Section 6.24). Thus, memory limitations on the devices
can be overcome.

All trend logs of a device are stored in the folder Trend logs below the device (see Figure
140). Double click on the trend log to open it.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 127 LOYTEC

Figure 140: Device Trend Log

Edit device trend log properties

1. Right-click on a device trend log and select Properties from the context menu.

2. The properties dialog is opened (see Figure 141). You can only modify the Database
Log Limits (refer to Section 6.16.1) parameters. The other parameters are defined by
the device configuration and cannot be edited.

Figure 141: Device Trend Log Properties

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 128 LOYTEC

Note: It is possible to select multiple trend logs and select Properties from the context menu to
change the size limits. To find specific trend logs, select the object type Trend Log in the
advanced search (see Section 6.9).

6.16.3 LWEB-900 Server Trend Logs


Server trend logs can record one or multiple data points and operate in one of the following
modes:

 Interval Mode: In this mode a snapshot of all trended data points is logged
periodically.

 COV Mode: In this mode, each of the trended data points is logged separately if
and only if its value changes. For analog data points, a specific COV increment can
be configured.

 Trigger Mode: In this mode a snapshot of all trended data points is logged each
time a trigger condition fires. The trigger condition is applied to a trigger data
point.

Create a new server trend log

1. Right click on the folder System/Trending in the navigation view and select New 
New Trend Log from the context menu.

2. Enter a name and description for the new trend log.

Figure 142: LWEB-900 Server Trend Log Properties

3. Select the desired Trend mode.

4. If necessary, change the Log size and Log duration parameters (refer to Section
6.16.1).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 129 LOYTEC

5. For trend logs of type Interval, select the Log interval.

6. Select Starting date and time. For trend logs of type Interval, LWEB-900 aligns the
log interval to this time.

7. The trending can be enabled/disabled by attaching an enable data point. This data point
should be of type binary. If the value of that enable data point is TRUE, the trend logs
data as defined by the trend mode. If the value of the enable is FALSE, trending is
disabled. If no enable data point is configured, the trend log is always enabled. Click
the … button to select a data point.

8. To remove the enable data point, click the Remove button.

9. Click OK to store the basic configuration of the trend. The new trend log appears in the
navigation view.

Configure trended data points

When an LWEB-900 Server trend log has been created, it needs to be configured, which
data points it shall log. This is done by attaching data points to the trend log. Only simple
data points can be attached for trending, i.e. analog, binary, or multi-state.

1. Right click on the LWEB-900 Server trend log and select Properties from the context
menu. The same dialog which appears when a new trend object is created is shown and
allows configuring the trend.

Note Of course, this step can also be done directly when the object is created.

2. Switch to the Datapoints tab.

Figure 143: LWEB-900 Server Trend Log Datapoints

3. Add data points to be trended. Click on Add… to open a data point selector window.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 130 LOYTEC

4. Select the data points and click OK. For each of the attached data points, a line appears
in the list below the add button.

Note: Data points can also be attached to a trend by selecting a data point in the object list view
and dragging it onto a trend log.

Only OPC data points can be added to LWEB-900 Server trend logs. They are marked with
a small “O” in the top right corner of the data point symbol. To expose a data point via
OPC, the corresponding checkbox has to be activated in the device configuration software.

5. Data points can be removed from the trend by clicking Remove.

6. If COV mode was selected, the COV increment is displayed in the COV Delta column.
This value can be increased to generate less trend data.

7. If the trended value of the data point shall be aggregated over the log interval, select the
desired aggregation in the Type column. Available options are Min, Max, Avg.

Note To create multiple curves with min, average, and maximum values, add the same data point
three times and select the different aggregation types.

8. When done with the data point setup, click OK to leave the dialog.

Configure trigger data points

In trigger mode, one or more trigger data points cause the generation of a snapshot
containing the values of the trended data points at the time instant the trigger is activated.
For a trend log, one or more trigger conditions can be defined.

1. Right-click on the LWEB-900 Server trend log and select Properties from the context
menu.

Note Of course, this step can also be done directly when the object is created.

2. Switch to the Triggers tab.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 131 LOYTEC

Figure 144: Trend Log Trigger

3. Click the Add… button. A data point selection dialog opens.

4. Select one or more data points and click OK.

5. The triggers appear now in the list.

6. In the Manage Trigger Conditions you can refine the trigger condition depending on
the trigger data point class.

7. When done with the data point setup, click OK to leave the dialog.

Disable server trend logs

A server trend log can be temporarily disabled using the Disable Trend Log option in the
context menu. When the trend log is disabled, the LWEB-9S00 Server does not record the
attached data points. A disabled trend log can be enabled with the Enable Trend Log menu
entry.

6.16.4 Trend Log View


To view a trend log, double click on it in the navigation view or object list view.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 132 LOYTEC

Figure 145: Trend Log View

The contents of the trend log can be exported as a comma separated value list (CSV export).
The trend log view can be refreshed by hitting the [F5] function key or pressing the Refresh
value toolbar button. If the log contains a large number of entries, the log is split into
multiple pages and the buttons at the bottom can be used to navigate through the pages.
Alternatively, the Go to date button can be used to jump to a specific date and time.

Column Configuration

The columns of the trend log view can be customized. To add columns or to change the
column order, click on the Configure columns toolbar button.

The column configuration is stored for each trend log view separately. To change the
column configuration for the current trend log view only, deactivate the Apply to all ‘Log’
objects checkbox and click the Apply button. To save the configuration for all trend log
views, activate the checkbox and press the Apply button.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 133 LOYTEC

Column Description

Sequence No. The log record sequence number. This is a monotonously


increasing number, which is unique for each log record.
Record Type Data records:
 Bool
 Real
 Enum
 Unsigned
 Signed
 Null: This element is included if the logged data point has no
value.
System records:
 Error: This element is included if a communication error has
occurred. The value of the error is technology-specific.
 Purge: This element is included if a purge action is logged.
In this case, no value is logged.
 Log Enable: This element is included if a log enable (TRUE)
or log disable (FALSE) action is logged.
 Time Change: This element is included, if a change in the
device’s clock has been logged. The integer value specifies
the number of seconds the clock was put forward or
backward.
Timestamp The date/time of the log record.
Item (Index) Name of logged data point and index.
Value Logged value.
Value Type Data type of the Value field.
Aggregation Mode Value: No aggregation.
Min.: Minimum value during log interval.
Max.: Maximum value during log interval.
Avg.: Average value during log interval.
Path Complete path of logged data point (if available).
Table 22: Trend Log View Columns

Filter trend log

To search for specific records in the trend log view, click on the Filter Log Data button in
the toolbar. The filter dialog allows you to combine multiple conditions with AND and OR
operators. The example in Figure 146 finds all data records of the data point
“nvoHCroomTemp” with a value less than 20.

Figure 146: Trend Log Filter

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 134 LOYTEC

Clear trend log

1. Click on the Clear Trend Log button in the toolbar.

2. To clear all data, activate the checkbox Remove all data, else specify a date.

Figure 147: Clear Trend Log

Note In case of a device trend log, only data in the LWEB-900 database is cleared. Data logged
by the LOYTEC device is left unchanged. You can clear the trend log data on the device
using its web UI.

Note Clearing trend log data is recorded in the event log.

Edit trend log records

1. Select one or multiple trend log records and open the context menu

Note Only data records, no system records can be edited.

2. The context menu allows to remove the selected records or to change the recorded
value.

Figure 148: Edit Trend Log Records

Figure 149: Edit Trend Log Record

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 135 LOYTEC

Note Editing trend log records is recorded in the event log.

Print trend log

Use the print button in the toolbar to print the trend log. You can print all trend log records
or only data logged during a configurable time interval. The print dialog allows adjusting
the page margins and the font size.

6.16.5 Trend Chart View


One or multiple trend logs are visualized using a chart view. Figure 150 shows the chart
icon in the navigation view. Double click on the icon to open the chart view (see Figure
151).

Figure 150: Chart View Icon

Figure 151: Chart View

Create a new chart view

1. Right click on a folder in the navigation view and select New  New Chart View
from the context menu. A trend chart can be created in the root folder (the project
node), in the home folder of a user, or in any user defined folder.

2. Enter a name and description for the new chart view.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 136 LOYTEC

Figure 152: Chart View Properties

3. Line Width: Sets the line width for all curves drawn in this trend control.

4. Draw grid: This option enables a grid which allows easier readout of the displayed
data. The checkbox defines the initial state of the grid when you open the chart view.
You can enable/disable the grid any time using the corresponding toolbar button.

5. Display description in the view: If this option is enabled, the description of the chart
view is displayed as title of the chart.

6. Configure the X Axis Properties:

 Label: Text displayed as label for the x-axis.

 Time Span: Select a suitable time span which is displayed initially when you open
the chart view. You can zoom in and zoom out any time using the corresponding
toolbar buttons of the char view.

 Date Format: Format string used to display date labels on the time axis. Date
labels are shown at midnight of each day which has a label drawn. If the user
zooms out further, date labels will be shown only for every other day, every start of
the week, or every month, as space allows.

 Time Format: Format string used to display time labels on the time axis. Time
labels are displayed only when there is more than one label for one day. Otherwise,
time labels will not be used.

 Tick marks: Enables drawing of tick marks for the time axis.

 Scale labels: Enables drawing of scale labels.

7. Configure the Y Axis Properties:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 137 LOYTEC

 Label: Text displayed as label for the primary y-axis.

 Range: Value range for the primary value axis drawn on the left end of the trend
graph. This is the default range for the standard zoom setting and may be changed
during runtime when the option Y-Scaling is enabled.

 Label 2: Text displayed as label for the secondary y-axis.

 Range 2: Value range for the secondary value axis. If enabled, the secondary scale
is drawn on the right end of the graph.

 Tick Marks: Enables drawing of tick marks for the value axis.

 Scale Labels: Enables drawing of scale labels. Note that scale labels should
always be enabled for controls which have the Y-Scaling option set.

 Y-Scaling: Enables navigation buttons for the value axis.

 Y-Autoscale: The range of the Y-axis automatically scales to the displayed values.

 Second. Scale: Activates the secondary Y-axis.

8. Configure the chart view Colors:

Color Name Description

Labels Labels of the value scale (x-axis) and the time scale (y-axis).
Horizontal Grid Horizontal grid lines (if the grid is enabled).
Vertical Grid Vertical primary grid lines (if the grid is enabled).
Second. Grid Vertical secondary grid lines (if the grid is enabled).
Axis Tick marks and axis for value and time.
Container Background of the graph area, which is the rectangular area
spawned by the value and time axis.
Background Color of the background outside the graph.
Table 23: Colors of Trend Chart View

9. Click OK to store the basic configuration of the chart view. The new chart view
appears in the navigation view.

Attach trend logs

When a chart view has been created, it needs to be configured, which trend logs it shall
display. This is done by attaching trend logs to the chart view. Device trend logs as well as
LWEB-900 Server trend logs can be attached.

1. Right-click on the chart view and select Properties from the context menu. The same
dialog which appears when a new char view is created is shown and allows configuring
the chart view.

Note Of course, this step can also be done directly when the object is created.

2. Switch to the Datapoints tab.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 138 LOYTEC

Figure 153: Chart View Datapoints

3. Click on Add… to add a trend log to the chart view. A trend log selector window is
opened.

4. Select the trend log and click OK. The trend log and the logged data point(s) appear in
the list below the add button.

5. Trend logs can be removed from the chart view by clicking Remove.

6. For each logged data point the following parameters can be configured:

 Name: Name displayed in the chart view legend. If you leave this field empty,
the data point name will be displayed per default.

 Color: Color used to draw the trend curve.

 Y-Axis: Select First to display the data point on the primary y-axis or Second
to display the data point on the secondary y-axis.

 Interpolation: If you select None, the current value will be drawn


horizontally until the next recorded value is available, causing the trend graph
to show a vertical step to the new value. This setting is suitable to record
binary or multi state values like window state or room occupancy. Selecting
Linear will draw straight lines between the recorded values, which is suitable
for temperatures or other analog values which do not represent a small set of
discrete values.

 Scale Factor: The data records are multiplied with this factor before
displaying them. Example: To convert Wh into kWh enter the value 0.001.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 139 LOYTEC

7. When done with the data point setup, click OK to leave the dialog.

Define limit lines

A limit line draws a value as a horizontal line across the entire graph. The value can either
be constant or fetched from a data point.

1. Right-click on the chart view and select Properties from the context menu. The same
dialog which appears when a new char view is created is shown and allows configuring
the chart view.

Note Of course, this step can also be done directly when the object is created.

2. Switch to the Limit Lines tab.

Figure 154: Chart View Limit Lines

3. To add a constant value limit line, click on the Add a Constant Value… button. The
limit line appears in the list.

4. To add a limit line based on a data point value, click on the Add Datapoint button. A
data point selector window is opened. Select the data point and click OK. The limit line
appears in the list.

5. Limit lines can be removed from the chart view by clicking Remove.

6. For limit lines the following parameter can be configured:

 Color: Color used to draw the limit line.

 Y-Axis: Select First to display the limit line on the primary y-axis or Second
to display the limit line on the secondary y-axis.

 Value: Value displayed for constant value limit lines.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 140 LOYTEC

7. When done with the data point setup, click OK to leave the dialog.

Shortcut to create a new trend log and chart view

A shortcut to creating a LWEB-900 Server trend log and a corresponding chart view is to
select a data point in the object list view, right click on it and choose Show the Datapoint
in a new Chart View (see Figure 155) . The trend log is created with default settings in the
folder System/Trending and the chart view is placed in the home directory of the user (see
Figure 156).

Figure 155: Create Chart View Directly From Data Point

Figure 156: LWEB-900 Trend Log and Chart View Created in Home Directory

Print Trend Chart

Use the print button in the toolbar to print the trend chart. The print dialog allows adjusting
the page margins and the scale factor.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 141 LOYTEC

6.17 Reporting
LWEB-900 can create reports based on trend logs. Reports can be used, for example, to
document the energy consumption in a building. Figure 157 shows an example report.

Figure 157: Example Report

6.17.1 Report View


A report is displayed in the navigation view and in the object list view with a special icon
(see Figure 158). Each time a report is triggered, for example on the first day of each
month, the generated data is stored as child object of the report. Double-clicking on the
report data opens the report view with the selected data. If you double-click on the report
itself, the report view opens with the latest generated data. The report view includes a
toolbar that provides navigation, search, and print functionality. The report can be exported
to an Excel, PDF, or Word file.

Figure 158: Reports in Navigation View

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 142 LOYTEC

6.17.2 Configure Reports


Create a new report

Right click on a folder in the navigation view and select New  New Report from the
context menu. A report can be created in the root folder (the project node), in the home
folder of the user, or in any user defined folder.

Define report properties

When creating a new report, the report properties dialog (see Figure 159) is opened. To
change the properties of an existing report, right click on the report and select Properties
from the context menu.

Figure 159: Report Properties

1. Enter a name and a description for the report.

2. Select a report template from the drop-down list. The report template defines how the
data from the trend logs is presented. Refer to section 6.17.4 for details.

3. Configure the report schedule: The report schedule defines when LWEB-900 generates
a report. LWEB-900 offers the following options:

 Periodic report: The report is generated automatically each day, week, month, or
year.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 143 LOYTEC

 Triggered report by datapoint: The report is generated if the attached data point
changes to a value other than zero. This feature is useful to e.g. generate a report
when an alarm occurs.

 Manual report: The report is generated only when the user triggers it manually.

4. Configure how the generated report will be distributed. The report can be generated in
PDF, Excel, or Word format. If the E-mail report checkbox is active, the report will be
distributed via e-mail. A prerequisite to sending e-mails is the configuration of the
outgoing e-mail server as described in Section 6.18. The following parameters need to
be specified for e-mail distribution:

 E-mail to: Select the e-mail addresses which should receive the generated reports.

Note The list of available e-mail adresses contains all users for which an e-mail address has
been specified (see Section 6.27). If you want to send a report to an e-mail address which
does not belong to an LWEB-900 user, you can add this e-mail address in the project
properties: Select Properties from the context menu of the project node in the navigation
view and switch to the Outgoing mails tab.

 E-mail subject: The e-mail subject can contain the place holders described in
Table 24. To add a place holder, use the right mouse button and select the place
holder from the context menu.

 E-mail body: The body can contain the same place holders as the e-mail subject.

5. Configure the folder and file name for the generated report:

 Base folder: Base folder for all generated report files.

 Report folder: Subfolder for generated report files. The report folder can contain
the place holders described in Table 25. To add a place holder, use the right mouse
button and select the place holder from the context menu.

 Report filename: The report filename can contain the place holders described in
Table 24. To add a place holder, use the right mouse button and select the place
holder from the context menu.

 Date & time format: The date and time format can contain the format specifier
described in Table 26. To add a format specifier, use the right mouse button and
select the format specifier from the context menu.

6. Configure how many generated reports the LWEB-900 Server stores:

 Max. reports: If a value different from 0 is specified, the LWEB-900 Server will
delete the oldest report when this number is exceeded.

 Store for a period of: If a value different from 0 is specified, the LWEB-900
Server deletes reports which have been generated before the specified period.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 144 LOYTEC

Place holder Description

ReportName Name of the Report


ReportType Type of the report:
 Periodic: Report was generated based on a periodic schedule
 Triggered: Report was triggered by a data point
 Manual: Report was generated by manual request
TriggerName The value of this place holder depends on the trigger type:
 Periodic: “System”
 Triggered: Name of the data point which triggered the report
 Manual: Name of the user who requested the report
ReportTime Date and time when the report was generated
ReportIndex The report index starts with 1 and is incremented for each
generated report
Table 24: Place Holders for E-Mail Subject, E-Mail Body, and Report File Name

Place holder Description

ReportName Name of the Report


ReportType Type of the report:
 Periodic: Report was generated based on a periodic schedule
 Trigger: Report was triggered by a data point
 Manual: Report was generated by manual request
TriggerName The value of this place holder depends on the trigger type:
 Periodic: “System”
 Triggered: Name of the data point which triggered the report
 Manual: Name of the user who requested the report
Year Year when the report was generated
Month Month when the report was generated
Table 25: Place Holders for Report Folder

Format Specifier Description

%Y Year
%m Month
%d Day
%H Hour
%M Minute
%S Second
Table 26: Format Specifiers for Date and Time

Define report data

Figure 160 shows the Datalogs tab of the report properties dialog. This dialog allows you to
configure the data source for your report. Depending on the report template, you can have
one or multiple data groups. The template “Stacked Column Chart“, for example, has the
following two data groups:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 145 LOYTEC

 Group 1: All trend logs in group 1 are displayed on the primary y-axis as stacked
column chart. Typically trend logs which represent energy meters are added to
group 1.

 Group 2: All trend logs in group 2 are displayed on the secondary y-axis as line
chart. Group 2 can be used to display data which influences the energy
consumption reported by group 1 (e.g. outside temperature, solar irradiation).

Figure 160: Report Properties, Datalogs Tab

For each data group the following information needs to be configured:

1. Define the time period: All data records with a timestamp inside the time period will be
selected for the report. You have to specify a start date (From) and an end date (To).
Both can be absolute or relative:

 Absolute: An absolute date and time is independent of the time when the report is
generated.
Example: 1.1.2014 at 12:00 AM

 Relative: If you want to create a periodic report or a triggered report, the time
period should be relative to the time when the report is generated.
Example: Relative to start of current month, 1 month ago at 12:00 AM

If the report template has multiple data groups, you can link the time periods of the
different groups by using the Identical to option. For example, after you have defined
the time period for group 1, you can select Identical to Group 1 for the time period of
group 2.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 146 LOYTEC

2. Define step interval: The step interval defines the resolution of the report. All data
during the step interval will be aggregated. The aggregation algorithm can be
configured for each data point separately (see Table 27).
Example: To report the daily energy consumption, set the step interval to 1 day and the
aggregation mode to “Delta”.

3. Click on Add… to attach a trend log to the chart view. A trend log selector window is
opened.

4. Select the trend log and click OK. The trend log and the logged data point(s) appear in
the list below the add button.

5. Trend logs can be removed from the chart view by clicking Remove.

6. For each logged data point the following parameters can be configured:

 Report legend: Name displayed in the report. If you leave this field empty, the
data point name will be displayed per default.

 Color: Color used to display the logged data point in the report.

 Aggregation Mode: The aggregation mode defines how a value for the step
interval is calculated (see Table 27).

 Scale Factor: Each calculated value is multiplied with the scale factor.
Example: To convert Wh to kWh, enter a scale factor of 0.001.

Aggregation Mode Description

Average Average value during the step interval


First value First value in the step interval
Last value Last value in the step interval
Min value Minimum value in the step interval
Max value Maximum value in the step interval
Sum Sum of all values in the step interval
Delta Calculate the difference between the last value of the current step
interval and the last value of the previous step interval. This
aggregation mode is used for energy counters. To take a
wraparound of the energy counter into account, specify the
parameter Max counter value
On counter Counts how often the value changed from zero to non-zero during
the step interval.
Off counter Counts how often the value changed from non-zero to zero during
the step interval.
Pulse counter Count how many occurrences of the following sequence is
detected during the step interval: change from zero, to non-zero
and then change back to zero.
Running time Time during which the value is non-zero
Down time Time during which the value is zero
Availability RunningTime/(RunningTime+DownTime) in percent
Table 27: Aggregation Mode

Configure report template specific parameters

Figure 161 shows the Parameters tab of the report properties dialog. This dialog allows
configuring report template specific parameters. Each report template can be customized

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 147 LOYTEC

using parameters. The parameters for the different built-in report templates are described in
Section 6.17.4.

Figure 161: Report Properties, Parameters Tab

6.17.3 Trigger a report manually


To trigger a report manually, right-click on the report and select Generate report from the
context menu. When you trigger the report generation manually, you can override the
standard values for time period and step interval. The default values are determined by the
report properties (see Figure 162). Set the checkbox Send E-mail if you want to send the
report to the configured e-mail addresses.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 148 LOYTEC

Figure 162: Trigger Report Manually

6.17.4 Report Templates


Reports are based on report templates which are displayed in the Library/Report
Templates folder. Standard report templates are provided by LOYEC.

Figure 163: Built-In Report Templates

The following sections describe the standard report templates provided by LOYTEC. For
information on how to create your own custom user report templates refer to Section 8.5.

Stacked Column Chart

The stacked column chart template contains two data groups. If the second data group is
used, the time period and the step interval for group 2 should be set identical to group 1.

The stacked column chart contains the following report items:

 Header: The report header displays the report name, description, the time period
for group 1, the date and time when the report was created, and the page number.

 Column Chart: All trend logs in group 1 are displayed on the primary y-axis as
stacked column chart. All trend logs in group 2 are displayed on the secondary y-
axis as line chart.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 149 LOYTEC

Figure 164: Stacked Column Chart, Column Chart

 Pie Chart: The pie chart is displayed only if more than one trend logs are added to
group 1. It displays the sum of values for each trend log.

Figure 165: Stacked Column Chart, Pie Chart

 Step table: The step table contains the same information as the line chart in tabular
form. Each row contains the aggregated data for the corresponding step interval.
The minimum and maximum values are highlighted in bold.

 Statistics table: The statistics table provides a summary of the report data.

The following parameters can be configured for the stacked column chart template:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 150 LOYTEC

Parameter Description

Chart title Title displayed in the chart


Group 1 name Text used for the primary y-axis in the chart and as table header in
the step and statistics tables
Group 1 decimal digits Number of decimal digits used to display values of group 1
Group 2 name Text used for the secondary y-axis in the chart and as table header
in the step and statistics tables
Group 2 decimal digits Number of decimal digits used to display values of group 2
Show stacked column This checkbox defines if the stacked column chart is displayed or
chart not
Show pie chart This checkbox defines if the pie chart is displayed or not.
Show step table This checkbox defines if the step table is displayed or not.
Show statistics This checkbox defines if the statistics table is displayed or not.
Image file (*.jpg/*.png) The report can be customized with a custom bitmap
Select logo position This parameter defines the position of the image file in the report
Table 28: Parameters of Report Template Stacked Column Chart

Line Chart

The line chart contains the following report items:

 Header: The report header displays the report name, description, the time period,
the date and time when the report was created, and the page number.

 Line Charts: Depending on the time period, the data of the attached trend logs is
displayed in one or multiple line charts. The following screenshot shows an
example of the electric power for the time period of one month. Each line chart
shows one complete week starting with Monday. Therefore, data from
corresponding weekdays is displayed above each other.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 151 LOYTEC

Figure 166: Line Chart Template, Chart

 Step table: The step table displays the same information as the line chart in tabular
form. Each row contains the aggregated data for the corresponding step interval.
The minimum and maximum values are highlighted in bold.

 Statistics table: The statistics table provides a summary of the report data.

The following parameters can be configured for the line chart template:

Parameter Description

Chart title Title displayed in the chart


Y-Axis label Text used for the y-axis in the chart
Decimal digits Number of decimal digits used to display values in the step table
and statistics table
Show chart This checkbox defines if the line chart is displayed or not
Show step table This checkbox defines if the step table is displayed or not.
Show statistics This checkbox defines if the statistics table is displayed or not.
Image file (*.jpg/*.png) The report can be customized with a custom bitmap
Select logo position This parameter defines the position of the image file in the report
Table 29: Parameters of Report Template Line Chart

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 152 LOYTEC

Compare

This report template is intended to compare two groups of trend logs during different time
periods. It can be used to e.g. compare the energy consumption in the current time period
with a baseline. It is possible to add multiple trend logs to each data group. The report
template compares the total of group 1 will the total of group 2. Additionally, each pair of
trend logs is compared separately.

The compare report template contains the following report items:

 Header: The report header displays the report name, description, the time periods
for group 1 and for group 2, the date and time when the report was created, and the
page number.

 Gauge: The gauge displays the difference between the sum of all data in group 1
and group 2 in percent.

Figure 167: Compare Template, Gauge

 Summary table: This table compares each pair of trend logs (trend log n in group 1
and trend log n in group 2). For each pair of trend logs the following information is
displayed: sum of values for trend log in group 1, sum of values for trend log in
group 2, absolute delta, and delta in percent.

 Line chart: This chart displays a pair of trend logs (trend log n in group 1 and trend
log n in group 2) over time. The x-axis labels display the timestamp of group 1.
Data from group 2 is displayed with a time offset so that both data lines start at the
same x-axis position.

Figure 168: Compare Template, Chart

 Step table: The step table displays the same information as the line chart in tabular
form. Each row contains the aggregated data for the corresponding step interval.

The following parameters can be configured for the compare template:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 153 LOYTEC

Parameter Description

Y-Axis label Text used for the y-axis in the chart


Group 1 name Name for data in group 1
Group 2 name Name for data in group 2
Unit Unit displayed in chart view and in tables
Decimal digits Number of decimal digits used to display values in the tables
Show compare gauge This checkbox defines if the compare gauge is displayed
Show summary table This checkbox defines if the summary table is displayed
Show total line chart This checkbox defines if the line chart is displayed for the total of
all trend logs
Show total step table This checkbox defines if the step table is displayed for the total of
all trend logs
Show separate line charts This checkbox defines if the line chart is displayed for each pair of
trend logs
Show separate step tables This checkbox defines if the step table is displayed for each pair of
trend logs
Image file (*.jpg/*.png) The report can be customized with a custom bitmap
Select logo position This parameter defines the position of the image file in the report
Table 30: Parameters of Report Template Compare

Energy Signature

The energy signature report gives a quick overview of the energy performance of a building.
It shows the correlation between energy consumption and heating degree days. Heating
degree days (HDD) are calculated from the outside temperature and are a measure of how
much the outside air temperature was below a certain base temperature.

Figure 169: Energy Signature

The heating degree days are calculated using the following formula:

HDDTIndoor/TBase = ∑ If (TOutdoor < TBase, TIndoor –TOutdoor, 0)

TIndoor: Average room temperature

TBase: Outside temperature below which the building needs heating

TOutdoor: Outdoor temperature

The values TIndoor and TOutdoor are parameters for the calculation, the values TOutdoor
are the measured values.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 154 LOYTEC

The energy signature report performs a simple linear regression and shows the following
parameters:

Energy Consumption ≈ a + b*HDD

a: Energy consumption for HDD=0

b: Slope

r: The product-moment correlation coefficient r is a measure of the linear dependence


between the energy consumption and heating degree days. The value 1 is total positive
correlation, 0 is no correlation, and −1 is total negative correlation.

The energy signature report template contains two data groups. Group 1 contains the energy
meter data. Figure 170 shows an example configuration. If multiple energy meter trend logs
are added, a separate chart is displayed for each energy meter. Group 2 contains the trend
log for the outside temperature (see Figure 171). The step interval for Group 2 has to be set
to 1 day for calculation of the heating degree days.

Figure 170: Energy Signature Report, Group 1 Configuration

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 155 LOYTEC

Figure 171: Energy Signature Report, Group 2 Configuration

The following parameters can be configured for the energy signature template:

Parameter Description

Chart title Text used for the chart title


Group 1 name Label displayed on y axis of chart and for table header
Group 2 name Label displayed on x axis of chart and for table header
Group 1 decimal digits Number of decimal digits used to display values of group 1
(energy consumption)
Group 2 decimal digits Number of decimal digits used to display values of group 2
(outside temperature)
Base Temperature The base temperature of a building is the temperature below which
that building needs heating
Indoor Temperature Average indoor temperature
Show total chart This checkbox defines if the compare gauge is displayed
Show separate charts This checkbox defines if the line chart is displayed for the total of
all trend logs
Show step table This checkbox defines if the summary table is displayed
Show statistics This checkbox defines if the step table is displayed for the total of
all trend logs
Image file (*.jpg/*.png) The report can be customized with a custom bitmap
Select logo position This parameter defines the position of the image file in the report
Table 31: Parameters of Energy Signature Report Template

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 156 LOYTEC

Generic

The generic report template contains one data group. It allows specifying what charts and
tables are used to display data. The following parameters can be configured for the generic
report template:

Parameter Description

Chart title Text used for the chart title


Y-Axis label Text used for the y-axis in the chart
Decimal digits Number of decimal digits used to display values in the step table
and statistics table
Show line chart This checkbox defines if the line chart is displayed or not
Show stacked column This checkbox defines if the stacked column chart is displayed or
not
Show pie chart This checkbox defines if the pie chart is displayed or not
Show vertical bar This checkbox defines if the vertical bar chart is displayed or not
Show horizontal bar This checkbox defines if the horizontal bar chart is displayed or
not
Show scatter chart This checkbox defines if the scatter chart is displayed or not
Show step table This checkbox defines if the step table is displayed or not.
Show statistics This checkbox defines if the statistics table is displayed or not.
Image file (*.jpg/*.png) The report can be customized with a custom bitmap
Select logo position This parameter defines the position of the image file in the report
Table 32: Parameters of Generic Report Template

6.18 E-Mail Notification


The LWEB-900 Server can send e-mail notification in case of an alarm (see Section 6.14.3)
or if a report is generated (see Section 6.17). The prerequisite to sending e-mails is the
configuration of the outgoing e-mail server. Select Properties from the context menu of the
project node in the navigation view and open the Outgoing mails tab.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 157 LOYTEC

Figure 172: Configure Outgoing Mails

 E-mail address: Enter the e-mail address of the LWEB-900 server’s e-mail
account.

 SMPT server: SMTP server of your Internet provider.

 Port number: Typically, the SMTP server port can be left at 25.

 User secure connection (SSL): Enable secure socket layer.

 Username and Password: If the provider’s SMTP server requires authentication,


specify the user name and password.

 E-Mail addresses: The list automatically contains all users for which an e-mail
address has been specified (see Section 6.27). If you want to add e-mail addresses
which do not belong to LWEB-900 users, you can add them explicitly to the list by
pressing the plus icon.

6.19 Event View


The event view helps you to keep track of what is going on in LWEB-900. It can be opened
by selecting Show Events from the context menu of a folder. An example is shown in
Figure 173.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 158 LOYTEC

Figure 173: Event View

Event path

Each event is associated with an LWEB-900 object. LWEB-900 objects are organized
hierarchically and can be explored using the navigation view and the object list view. The
event view displays only events related to objects which are inside the path set in the
breadcrumb navigation bar. To see all events, select the top folder. Select a specific folder
to see only events which are associated with objects inside this folder.

Event filter

The event filter lets you drill down to the specific events you want to see. The event view
offers a number of predefined filters described in Table 33 or you can use the powerful
custom filter.

Column Description

All Events Display all events.


Alarm Events Display alarm events only.
Configuration Events Display configuration events only. Configuration events include
the creation and deletion of objects and the modification of their
properties.
Set Value Events Display events which change the value of an object. This includes
modification of a data point value, modification of schedulers
(scheduler events, calendar patterns, date entries), and
modification of trend logs (edit trend log records, clear trend log)
done by LWEB-900 users.
Device Management Display events related to device management. This includes the
Events upload and download of files from/to the device.
User Management Events Display user management events. This includes login and logout
events, configuration of users and groups, and setting access
rights.
System Events System events are generated by the LWEB-900 Server if an
LWEB-900 project is started or stopped, a project backup or
restore operation is executed, or if an error occurs.
Table 33: Predefined Event Filters

Figure 174 shows an example of a custom filter definition. As you can see, the custom filter
allows to combine multiple conditions with AND and OR operators.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 159 LOYTEC

Figure 174: Custom Filter

Column Configuration

The columns of the event view can be customized. To add columns or to change the column
order, click on the Configure columns toolbar button.

The column configuration is stored for each event view separately. To change the column
configuration for the current event view only, deactivate the Apply to all ‘Event view’
objects checkbox and click the Apply button. To save the configuration for all event views,
activate the checkbox and press the Apply button.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 160 LOYTEC

Column Description

Timestamp Date and time when the event occurred.


Category Event main category:
 Alarm: Alarm events.
 Set Value: Object value changed.
 Configuration: Object created, deleted, or properties
modified.
 User Management: User management related events.
 System: System events like project start/stop, project
backup/restore, and error events.
 Device Management: Upload and download of files from/to
the device.
Type Type of event inside the main category.
Description Description of the event.
Object Name of the object associated with the event.
Object Type Type of the object associated with the event.
Object Identification Key Identification key of the object associated with the event. Section
6.8 describes how to assign identification keys to data points.
Path Path of the object.
User If the event was triggered by a user, this field contains the user
name.
Access Level User access level required to trigger the event.
Comment For some events (e.g. disable alarms, edit trend log records), the
user can enter a comment.
Item (Index) Some objects contain sub items (e.g. a graphical view object has
data point items in its data point interface, a trend log has attached
data points). If such a sub item is affected by the event, the Item
(Index) field contains its name.
Item Identification Key Identification key of the sub item associated with the event.
Section 6.8 describes how to assign identification keys to data
points.
Item Path Path of the sub item.
Value New value of the object after the event.
Old Value Old value of the object before the event.
State In case of an alarm event, this field contains the alarm state:
 Active, not acknowledged
 Active, acknowledged
 Inactive, not acknowledged
 Inactive acknowledged
Priority In case of an alarm event, this field contains the priority.
Alarm Time Date and time when the alarm occurred.
Clear Time Date and time when the alarm condition was cleared. If the alarm
is still active, this field is empty.
Ack. Time Data and time when the alarm was acknowledged. If the alarm has
not yet been acknowledged, this field is empty.
XAID On a LOYTEC device, each alarm is uniquely identified by the
XAID. The XAID is used in the acknowledgement to identify the
alarm.
Table 34: Event View Columns

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 161 LOYTEC

Save event view

If you regularly need to filter for certain events, it might be useful to save your event view:
click the Save event view button, enter the view name and its optional description. A new
event view with the current path and filter settings is created in your home directory. The
next time you want access the event view, just double click it, and you will see the most
current events matching your path and filter.

Figure 175: Event View Icon

Print event view

Use the print button in the toolbar to print the event view. You can print all event records or
only events logged during a configurable time interval. The print dialog allows adjusting the
page margins and the font size.

Event log size limitation

Even on a server with a large hard drive, the disk space is limited. Therefore, you need to
configure for how long the LWEB-900 Server keeps old events.

1. Select Properties from the context menu of the project node in the navigation view and
switch to the Database Log Limitations tab.

2. The event log size is limited by the following parameters:

 Size limit: The event log is organized as a ring buffer. As soon as the maximum
number of log items has been reached, new log entries will overwrite the oldest
entries.

 Duration limit: This parameter defines the maximum time span for which old data
is kept before deleting it from the database.

6.20 Global Connections


Global connections are an easy way to connect data points from different LOYTEC devices.
The data is transferred over an IP-based network. Global connections are especially useful
to distribute certain global data (e.g. weather station data, wind alarms, global on/off) in a
system.

To configure such communication, all devices need to be member of a CEA-852 channel.


The configuration of the CEA-852 channel is done by adding devices to a configuration
server using the web UI. Refer to device specific manuals for more details.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 162 LOYTEC

Figure 176: CEA-852 Channel List Setup

Create a global connection

1. Use your right mouse button to click on the Global connections folder in the
navigation view and select New  New Global Connection from the context menu.

Note You can organize global connections in sub folders. To create a sub folder, right click on
the Global connections folder and select New  New Folder from the context menu.

Figure 177: Global Connections Folder

2. Define a name and description for the global connection. The name is required to be
unique.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 163 LOYTEC

Figure 178: Global Connection Properties

3. Define timing parameters for the global connection:

 Max Send Time: This timing parameter of the global connection specifies a
time in seconds, in which a value update is transmitted into the connection,
even if the value has not changed. This is typically used for heartbeat
functions.

 Min Send Time: This timing parameter of the global connection specifies a
time in seconds, for which transmissions will be delayed after sending out a
value into the connection. This setting can be used to limit the transmission
rate to the connection.

4. Switch to the Datapoints tab

Figure 179: Global Connection Datapoints

5. Add data points to the global connection. Click on Add… to open a data point selector
window.

6. Select the data points and click OK. For each of the attached data points, a line appears
in the list below the add button.

7. Data points can be removed from the global connection by clicking Remove.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 164 LOYTEC

8. As a default, output data points will be added with the direcction Send, input data
points with the direction Receive. Change the direction by modifying Send or Receive.

9. When done with the global connection setup, click OK to leave the dialog. The global
connection is displayed in the navigation view. All datapoints which are member of the
connection are displayed in the object list view.

Figure 180: Global Connections in Object List View

Download global connections

After the connections have been created in LWEB-900, the LOYTEC devices need to be
configured accordingly. This is done by downloading the connection information to the
devices.

1. Use your right mouse button to click on the Global connections folder in the
navigation view and select Download Global Connections from the context menu.

2. Select the devices to which the global connection information should be downloaded.
Per default only devices for which the global connnection configruation changed since
the last download are selected. You can change the selection by activating/deactivating
the checkboxes beside the devices (see Figure 181).

Figure 181: Download Global Connections

3. Click on the Download button

Upload global connections

If global connections have been configured using a different tool (e.g. device configuration
software), those existing global connections can be uploaded into LWEB-900:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 165 LOYTEC

1. Use your right mouse button to click on the Global connections folder in the
navigation view and select Upload Global Connections from the context menu.

2. The existing global connections of all devices are checked and the current status is
displayed. You can select from which devices you want to upload the global
connections and import them into LWEB-900.

6.21 File Objects


LWEB-900 allows you to store files on the server and to link them to other objects or to
alarms. File objects can be added below the folder Library/Files. Files can be organized in
user defined folders.

Figure 182: File Objects

File objects support the following types of links:

 Direct link: The file object can be linked directly to any other object in the
navigation view. The file object appears as related object in the context menu of
the linked object.

 Object filter: The file object can be linked to multiple other objects in the
navigation view by specifying an object filter condition. The file object appears as
related object in the context menu of any object which passes the filter condition.

 Alarm filter: The file object can be linked to alarms by specifying an alarm filter
condition. The file object appears as related object in the context menu of any
alarm in the alarm view which passes the filter condition.

Create new file object

1. Right click on a folder in the navigation view and select New  New File from the
context menu. A file object can be created in Library/Files folder or any user defined
subfolder.

2. Enter a name, description, and select a file by clicking on the browse button.

3. After clicking the OK button, the new file object is created and displayed in the
navigation view.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 166 LOYTEC

Link file object using a direct link

1. Right click on the file object and select Properties from the context menu.

2. Click on the New Link… icon.

3. Give the link a name, select the Link Type “Direct Link to Object” and press on the
Browse button to select the object to which you want to link.

4. You can create multiple links for a file object.

Figure 183: Create Direct Link

Note An alternative way to create a direct link is to drag the file object and drop it on the object
to which you want to link it.

Link file object using an object filter

1. Right click on the file object and select Properties from the context menu.

2. Click on the New Link… icon.

3. Give the link a Name, select the Link Type “Link Filter to Object” and define a filter
condition. You can combine multiple parameters using AND, OR, and NOT operators.

Figure 184: Create Link Using Object Filter

Link file object using an alarm filter

1. Right click on the file object and select Properties from the context menu.

2. Click on the New Link… icon.

3. Give the link a Name, select the Link Type “Link Filter to Alarm” and define a filter
condition. You can combine multiple parameters using AND, OR, and NOT operators.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 167 LOYTEC

Figure 185: Create Link Using Alarm Filter

Edit file object

1. Right click on the file object and select Download for editing from the context menu.

2. Edit the local version of the file

3. Right click on the file object and select Upload new version from the context menu.

6.22 Device Management View


The device management view provides functionality to upgrade the firmware of multiple
LOYTEC devices in parallel. It checks periodically if a new firmware has been published
on the LOYTEC web site and informs the user if an update is available.

Using the device management view, the configuration and parameterization of LOYTEC
devices can be managed. In a typical installation multiple devices have the same data point
configuration but are parameterized differently. LWEB-900 can assign configuration and
parameter files to devices and download them in parallel. Furthermore, LWEB-900 can
manage program (logi.CAD) files.

The backup feature allows defining regular backup schedules for LOYTEC devices. It is
also possible to backup selected devices on request.

To open the device management view, right click on the Network/Devices folder in the
navigation view and select Open in Device Management View (see Figure 186).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 168 LOYTEC

Figure 186: Device Management View

Current hierarchy level:

The device management view is linked to the navigation view. The selected folder in the
navigation view determines which devices are displayed. If you select the Network/Devices
folder, you see all devices in the project. If you select a sub-folder all devices in or below
this folder are displayed.

Device list:

The device list displays all devices which are in or below the currently selected folder in the
navigation view. Each line in the device list describes one device. If a line is displayed in
red, the LWEB-900 Server cannot communicate with the device.

The first three columns in the device list always show the device name, IP address, and
device type. The remaining columns are depending on the selected tab. By clicking on the
column header, the list can be sorted. It is possible to filter the list to display only a certain
device type by right-clicking on the Type column header as shown in Figure 187.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 169 LOYTEC

Figure 187: Filter Device List

One or multiple devices can be selected in the list view. The buttons above the device list
(e.g. Download all files, Upload all files) execute actions on all selected devices.
Additional actions are available in the context menu of the selected devices.

Property view

The property view displays the properties of the device(s) selected in the device list. Which
properties are displayed depends on the selected tab.

Tab selection

Each tab provides different information about the devices. The following tabs are available:

 Overview: On the overview tab you can see the complete status of the devices at
one glance. It combines the most important information of the Firmware file,
Configuration file, and Program file tabs.

 Firmware file: This tab allows upgrading the firmware of LOYTEC devices
including L-IOB devices attached to programmable controllers. A detailed
description is given in Section 6.22.2.

 Configuration file: This tab allows managing configuration and parameter files.
Refer to Section 6.22.3 for a detailed description.

 Program file: This tab is used to manage logi.CAD files for programmable
controllers. See Section 6.22.4 for more information.

 Backup/Restore: This tab is used to backup and restore LOYTEC devices. It is


also possible to define periodic backup schedules. The backup and restore features
are described in Section 6.22.6

6.22.1 Device Overview


Figure 188 shows the overview tab which displays the status of LOYTEC devices at one
glance. On this tab you can see if the device firmware, L-IOB firmware, configuration file,
parameter file, program file, and LWEB-800/802 projects are up-to-date. The following
sections describe each of those configuration elements in detail.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 170 LOYTEC

Figure 188: Overview Tab

The columns of the device list are described in Table 35. The property view contains
detailed information about the selected device(s). This information is described in the
following sections (see Table 36).

Column Description

Device Name of the device as configured in LWEB-900 navigation view.


IP address IP address of the device.
Type Device type (e.g. LINX-120).
FW Status of device firmware. Refer to Table 38 for a list of possible
status symbols.
L-IOB FW Status of L-IOB firmware. Refer to Table 38 for a list of possible
status symbols.
Configuration Status of configuration file. Refer to Table 42 for a list of
possible status symbols.
Parameter file Status of parameter file. Refer to Table 42 for a list of possible
status symbols.
Program file Status of program file. Refer to Table 45 for a list of possible
status symbols.
L-Web project Status of LWEB-800/802 projects. Refer to Table 47 for a list of
possible status symbols.
Location Location of the device in the tree view using the format
Devices/<folder>/…
Table 35: Device List on Overview Tab

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 171 LOYTEC

Property View Header Description

Firmware file Refer to Section 6.22.2


L-IOB firmware(s) Refer to Section 6.22.2
Configuration file Refer to Section 6.22.3
Parameter file Refer to Section 6.22.3
Program file Refer to Section 6.22.4
LWEB-800/802 projects Refer to Section 6.22.5
Table 36: Property View on Overview Tab

6.22.2 Firmware Update


A special tab is available to manage the firmware as shown in Figure 189. Some devices
(LINX-12x, LINX-22x, LINX-15x, and LINX-11x) can be extended by attaching one or
multiple I/O modules (L-IOB devices). The device management view allows upgrading the
firmware of the base device and of the attached L-IOB devices.

Figure 189: Firmware File Tab

The columns of the device list are described in Table 37. The status of the firmware (up-to-
date, new on web, etc.) is visualized in the column FW status. If L-IOB devices are
attached to the base device, the column L-IOB FW status displays the summary status of
the connected L-IOB devices. The status of device firmware and L-IOB firmware is
visualized using the symbols described in Table 38.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 172 LOYTEC

Column Description

Device Name of the device as configured in LWEB-900 navigation view.


IP address IP address of the device.
Type Device type (e.g. LINX-120).
Version in LWEB-900 Firmware version assigned to the device.
Build date in LWEB-900 Build date of the firmware assigned to the device.
FW status Status of device firmware. Refer to Table 38 for a list of possible
status symbols.
L-IOB FW Status Status of L-IOB firmware. Refer to Table 38 for a list of possible
status symbols.
Location Location of the device in the tree view using the format
Devices/<folder>/…
Table 37: Device List on Firmware Tab

Symbol Name Description

Up-to-date The firmware of the device is up to date.


New on web There is a new firmware version available on the LOYTEC
web site.
Download The firmware version assigned to the device is newer than
the firmware which is currently installed on the device. The
firmware needs to be downloaded to the device.
New on device The firmware in the device is newer than the firmware in
the database. This happens if the firmware of the device is
updated with a different tool or if a new device is added to
the database and no firmware is assigned yet.
New in database There is a new firmware version available in the database
which is not yet assigned to the device. You should
consider assigning the new firmware version to the device.
File missing This is an error state. The device is assigned a firmware file
which no longer exists on the server.
Status symbols for L-IOB firmware only
Undefined This status symbol is only used for the L-IOB firmware in
the device list. It is displayed if there are multiple L-IOB
devices connected to the L-INX device and the L-IOB
firmware status is not the same for all attached devices.
Not available This status symbol is displayed if the device does not
support L-IOB devices.
- No L-IOB devices This status symbol is displayed if no L-IOB devices are
attached to the L-INX device.
Table 38: Firmware Status

The property view contains detailed information about the selected device(s). Table 39
describes the information displayed in the Firmware file section of the property view. A
new firmware can be assigned to the selected device(s) by clicking on the button Select new
firmware file.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 173 LOYTEC

Line Description

Type List of device types which are supported by the firmware file.
Latest version in database Version and timestamp of the newest firmware file in the
database which fits the selected device.
Version in database for Version and timestamp of the firmware file which is assigned to
this device the device.
Version on device Version and timestamp of the firmware installed on the device.
Table 39: Device Firmware Properties

If the device supports L-IOB devices, the property view contains a L-IOB firmware
section. This section displays a list of all connected L-IOB devices. For each L-IOB device,
the information described in Table 40 is displayed.

A new L-IOB firmware can be assigned by clicking on the button Select new L-IOB
firmware files. The same L-IOB firmware file will be assigned to all connected L-IOB
devices which are compatible with this firmware. Before downloading a new L-IOB
firmware, it is recommended to click on the button Check for new L-IOB devices. This
ensures that all L-IOB devices (even devices which are not yet configured) are detected.

Line Description

Bus x, Device y This line displays the firmware status symbol for the individual
L-IOB device (refer to Table 38) and live status of the device
(e.g. online, offline, not detected, etc.). The last contact
timestamp informs the user when this information has been
updated by LWEB-900.
Name Name of the L-IOB bus and of the L-IOB device in the format
<L-IOB bus name>, <L-IOB device name>.
Latest version in database Version and timestamp of the newest L-IOB firmware file in the
database.
Version in database for Version and timestamp of the L-IOB firmware file which is
this device assigned to the device.
Version on device Version and timestamp of the firmware installed on the L-IOB
device.
Table 40: L-IOB Firmware Properties

6.22.2.1 Upgrade Device Firmware


Firmware updates can be done either in the Overview tab or in the Firmware file tab.

Upgrading the device firmware is done in two steps: First a new firmware has to be assigned
to the devices. Different device types require different firmware files. This means that you
need to assign a different firmware file to e.g. an LVIS-3E100 device or a LINX-100
device. In a second step the firmware is downloaded to the devices. This can be done in
parallel for all devices independent of the device type.

Assign new device firmware

1. In the device list, select one or more devices which you want to upgrade. All selected
devices have to belong to the same product family. To select all devices of a product
family, right click on a device and choose Select devices with compatible firmware
from the context menu.

2. Click on the Select new firmware file button in the property view.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 174 LOYTEC

Note: An alternative method is to choose Select firmware file from the context menu in the list
view.

3. The Select Firmware dialog opens as shown in Figure 190. The dialog displays a list
of compatible firmware files available in the LWEB-900 database. If the desired
firmware version is already available in the list, select it and press OK. You can either
import a new firmware file from the hard disk or check if a new firmware is available
on the LOYTEC web site:

 Hard disk: If you have the firmware file available on your hard disk, click on the
Import new file… button, which opens a file selection dialog.

 LOYTEC web-site: You can download the newest released firmware directly
from the LOYTEC web-site by clicking on the Check for new version on
LOYTEC web-site… button. If a new firmware version is available, LWEB-900
downloads it from the web-site and displays the Readme file.

4. Repeat the previous steps for other devices which require a different firmware file.

Figure 190: Select Firmware Dialog

Download device firmware file

1. In the device list, select all devices. Press the button Download device firmware on
the top of the Firmware file tab.

Note: An alternative method is to choose Download device firmware from the context menu in
the list view.

2. The Download firmware file dialog opens as shown in Figure 191. This dialog
displays a list of devices and the firmware files which will be downloaded. To start the
download, press the Start download button.

3. During the download, the Status column is updated with current information.
LWEB-900 first checks if the firmware in the devices is already up-to-date. If this is the
case, the status “Up-to-date” is displayed and the firmware will not be downloaded.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 175 LOYTEC

Figure 191: Download Firmware File Dialog

6.22.2.2 Upgrade L-IOB Firmware


Upgrading the L-IOB firmware is very similar to upgrading the device firmware described
in the previous section.

Assign new L-IOB firmware

1. In the device list, select one or more L-INX devices with attached L-IOB devices.

2. Click on the button Check for new L-IOB devices. This ensures that all L-IOB
devices (even devices which are not yet configured) are detected.

3. Click on the Select new L-IOB firmware files button in the property view.

Note: An alternative method is to choose Select L-IOB firmware files from the context menu in
the list view.

4. The Select Firmware dialog opens as shown in Figure 192. The dialog displays a list
of available L-IOB firmware files. The list is split into separate sections for L-IOB
devices which require different firmware files. If the desired L-IOB firmware version is
already available in the list, select it and press OK. You can either import a new L-IOB
firmware file from the hard disk or check if a new firmware is available on the
LOYTEC web site:

 Hard disk: If you have the L-IOB firmware file available on your hard disk, click
on the Import new file… button, which opens a file selection dialog.

 LOYTEC web-site: You can download the newest released firmware directly
from the LOYTEC web-site by clicking on the Check for new version on
LOYTEC web-site… button. If a new L-IOB firmware version is available,
LWEB-900 downloads it from the web-site and displays the Readme file.

The selected firmware is assigned to all L-IOB devices which are attached to the
selected L-INX device(s).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 176 LOYTEC

Figure 192: Select Firmware for L-IOB Devices Dialog

Download L-IOB firmware file

1. In the device list, select all devices. Press the button Download L-IOB firmware files
on the top of the Firmware file tab.

Note: An alternative method is to choose Download L-IOB firmware files from the context menu
in the list view.

2. The Download L-IOB firmware files dialog opens as shown in Figure 193. This
dialog displays a list of L-INX devices and the L-IOB firmware files which will be
downloaded. To start the download press the Start download button.

3. During the download, the Status column is updated with current information.
LWEB-900 downloads the L-IOB firmware to the L-INX device and then tells the
L-INX device to upgrade the attached L-IOB devices with this firmware.

Figure 193: Download L-IOB Firmware File Dialog

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 177 LOYTEC

6.22.3 Device Configuration


A special tab is available to manage the configuration of LOYTEC devices as shown in
Figure 194. The configuration of a LOYTEC device is defined by the following two files:

 Configuration file: The configuration file defines the data points on the device
(e.g. user registers, CEA-709 network variables, BACnet server objects and client
mappings, M-Bus registers, Modbus registers, etc.). The configuration file is
created by the configuration software of the device.

 Parameter file: In the configuration file some data points are marked as
parameters. The parameter file defines the values of these parameters. Not all
LOYTEC devices have a parameter file.

Figure 194: Configuration File Tab

The columns of the device list are described in Table 41. The status of the configuration file
(up-to-date, download, etc.) is visualized in the column Config. status. If the device
supports a parameter file, the column Parameter file status displays the status of the
parameter file. The status of configuration and parameter file is visualized using the
symbols described in Table 42.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 178 LOYTEC

Column Description

Device Name of the device as configured in LWEB-900 navigation view.


IP address IP address of the device.
Type Device type (e.g. LINX-120).
Configuration File name of the configuration file assigned to the device.
Config. date Modification date of the configuration file assigned to the device.
Config. Status Status of configuration file. Refer to Table 42 for a list of
possible status symbols.
Parameter file File name of the parameter file assigned to the device.
Parameter file date Modification date of the parameter file assigned to the device.
Parameter file status Status of parameter file. Refer to Table 42 for a list of possible
status symbols.
Location Location of the device in the tree view using the format
Devices/<folder>/…
Table 41: Device List on Configuration File Tab

Symbol Name Description

Up-to-date The configuration/parameter file on the device is up to


date. This is the case if the configuration/parameter file on
the device is identical to the file assigned to the device in
the database.
Download A new configuration/parameter file has been assigned to
the device but has not yet been downloaded. The
configuration/parameter file needs to be downloaded to the
device.
New on device The configuration/parameter file has changed on the device
since the last download.
Configuration file: The “New on device” symbol is
displayed if the configuration is updated with a different
tool (e.g. the device configuration software) or if a new
device is added to the database and no configuration is
assigned yet.
Parameter file: The parameter file will change during
normal operation of the device whenever the value of a
parameter is modified using e.g. the Web UI of the device
or by sending an update via the fieldbus interface.
File missing This is an error state. The device is assigned a
configuration/parameter file which no longer exists on the
server.
Not available This status symbol is displayed if the device does not
support a configuration/parameter file.
- No file This status symbol is displayed if the device is not
configured/has no parameter file.
Table 42: Configuration/Parameter File Status

The property view contains detailed information about the selected device(s). Table 43
describes the information displayed in the Configuration file and Parameter file sections
of the property view. A new configuration can be assigned to the selected device(s) by
clicking on the button Select new configuration file. A new parameter file is assigned by
clicking on the button Select new parameter file.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 179 LOYTEC

Line Description

Configuration Name/File Name of the configuration/parameter file


name Configuration file: Name given to the configuration in the
configuration software. This name is different from the file name.
Parameter file: File name of the parameter file
File date in database Timestamp of the configuration/parameter file which is assigned
to the device.
File date on device Timestamp of the configuration/parameter file installed on the
device.
Table 43: Configuration File and Parameter File Properties

6.22.3.1 Upload a configuration file


To upload the current configuration file from one or more devices perform the following
steps:

1. In the device list, select one or more devices for which you want to upload the
configuration file.

2. Press the button Upload configuration on the top of the Configuration file tab.

Note: An alternative method is to choose Upload configuration from the context menu in the list
view.

3. The Upload configuration file dialog opens as shown in Figure 195. This dialog
displays a list of devices and the configuration files which will be uploaded. To start
the upload, press the Start upload button.

4. During the upload, the Status column is updated with current information. The
uploaded configuration files get default names. Default names for configuration files
have the following format:

[<device name>_<date>_<time>]_config.zml

The configuration file name can be changed in the Select Configuration File dialog
(see Section 6.22.7).

Figure 195: Upload Configuration File Dialog

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 180 LOYTEC

6.22.3.2 Assign a configuration file


To assign a new configuration file to one or more devices, perform the following steps:

1. In the device list, select one or more devices to which you want to assign the same
configuration. To select all devices which have identical configuration assigned, right-
click on a device and choose Select devices with identical configuration from the
context menu.

2. Click on the Select new configuration file button in the property view.

Note: An alternative method is to choose Select configuration file from the context menu in the
list view.

3. The Select configuration dialog opens as shown in Figure 196. The dialog displays a
list of compatible configuration files available in the LWEB-900 database. If the
desired configuration file is already available in the list, select it and press OK.

To get a configuration file into LWEB-900 you have two possibilities:

 Upload the configuration from a device as described in Section 6.22.3.1.

Note: Uploading a configuration file from one device and then assigning this configuration to
multiple other devices is a quick way to copy the configuration of a device to other devices.

 If you have the configuration file available on your hard disk, click on the Import
new file… button which opens a file selection dialog.

Note: Configuration files can be exported from the device configuration software.

Figure 196: Select Configuration Dialog

6.22.3.3 Downloading a configuration file


To download a configuration file to one or more devices, perform the following steps:

1. In the device list, select the devices to which you want to download the assigned
configuration. Press the button Download configuration on the top of the
Configuration file tab.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 181 LOYTEC

Note: An alternative method is to choose Download Configuration from the context menu in the
list view.

2. The Download configuration file dialog opens. This dialog displays a list of devices
and the configuration files which will be downloaded. To start the download, press the
Start download button.

6.22.3.4 Parameter files


Parameter files can be uploaded, assigned, and downloaded in the same way as
configuration files (see Section 6.22.3.1, 6.22.3.2, and 6.22.3.3).

6.22.4 Program Files


The LOYTEC LINX-11x, LINX-21x, LINX-12x, LINX-15x, LROC-100, and LIOB-48x
device families are programmable controllers. Those devices contain a program file which
is created using the logi.CAD software supplied by LOYTEC. A special tab is available to
manage program files as shown in Figure 197.

Figure 197: Program File Tab

The columns of the device list are described in Table 44. The status of the program file (up-
to-date, download, etc.) is displayed in the column Status. The status of the program file is
visualized using the symbols described in Table 45.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 182 LOYTEC

Column Description

Device Name of the device as configured in LWEB-900 navigation view.


IP address IP address of the device.
Type Device type (e.g. LINX-120).
Program file File name of the program file assigned to the device.
Server timestamp Modification date of the program file assigned to the device.
Device timestamp Modification date of the program file installed on device.
Status Status of program file. Refer to Table 45 for a list of possible
status symbols.
Location Location of the device in the tree view using the format
Devices/<folder>/…
Table 44: Device List on Program File Tab

Symbol Name Description

Up-to-date The program file on the device is up-to-date. This is the


case if the program file on the device is identical to the file
assigned to the device in the database.
Download A new program file has been assigned to the device but has
not yet been downloaded. The program file needs to be
downloaded to the device.
New on device The program file has changed on the device since the last
download. The “New on device” symbol is displayed if the
program is updated with a different tool (e.g. the device
configuration software).
File missing This is an error state. The device is assigned a program file
which no longer exists on the server.
Not available This status symbol is displayed if the device does not
support a program file.
- No file This status symbol is displayed if the device has no
program file.
Table 45: Program File Status

The property view contains detailed information about the selected device(s). Table 46
describes the information displayed in the Program file sections of the property view. A
new program file can be assigned to the selected device(s) by clicking on the button Select
new program file.

Line Description

File name File name of the program file.


File date in database Timestamp of the program file which is assigned to the device.
File date on device Modification date of the program file on the device.
Table 46: Program File Properties

6.22.4.1 Upload a program file


To upload the current program file from one or more devices perform the following steps:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 183 LOYTEC

1. In the device list, select one or more devices for which you want to upload the program
file.

2. Press the button Upload program file on the top of the Program file tab.

Note: An alternative method is to choose Upload program file from the context menu in the list
view.

3. The Upload program file dialog opens as shown in Figure 198. This dialog displays a
list of devices and the program files which will be uploaded. To start the upload, press
the Start upload button.

4. During the upload, the Status column is updated with current information. The
uploaded program files get default names. Default names for program files have the
following format:

[<device name>_<date>_<time>]_program.so

The program file name can be changed in the Select Program File dialog (see Section
6.22.7).

Figure 198: Upload Program File Dialog

6.22.4.2 Assign a program file


To assign a new program file to one or more devices perform the following steps:

1. In the device list, select one or more devices to which you want to assign the same
program file. To select all devices which have identical program files assigned, right-
click on a device and choose Select devices with identical program from the context
menu.

2. Click on the Select new program file button in the property view.

Note: An alternative method is to choose Select program file from the context menu in the list
view.

3. The Select program dialog opens as shown in Figure 199. The dialog displays a list of
program files available in the LWEB-900 database. If the desired program file is
already available in the list, select it and press OK.

To get a program file into LWEB-900 you have two possibilities:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 184 LOYTEC

 Upload the program from a device as described in Section 6.22.3.1.

Note: Uploading a program file from one device and then assigning this program to multiple
other devices is a quick way to copy the program of a device to other devices.

 If you have the program file available on your hard disk, click on the Import new
file… button, which opens a file selection dialog.

Note: The program file can be exported from the L-INX Configurator by pressing the Restore to
Disk button on the LogiCAD Files tab.

Figure 199: Select Program File Dialog

6.22.4.3 Downloading a program file


To download a program file to one or more devices perform the following steps:

1. In the device list, select the devices to which you want to download the assigned
program. Press the button Download program file on the top of the Program file tab.

Note: An alternative method is to choose Download program file from the context menu in the
list view.

2. The Download program file dialog opens. This dialog displays a list of devices and
the program files which will be downloaded. To start the download, press the Start
download button.

6.22.5 LWEB-800/802 files


The device families LINX-10x, LINX-20x, LINX-12x, LINX-15x can contain
LWEB-800/802 projects for visualization. They can be managed on the overview tab.

The status of the LWEB-800/802 projects is visualized in the column L-Web project using
the symbols described in Table 47. Note that multiple projects can be stored on a single
device.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 185 LOYTEC

Symbol Name Description

Up-to-date The LWEB-800/802 projects on the device are up-to-date


Download The LWEB-800/802 projects assigned to the device do not
exist on the device or are newer than the corresponding
versions on the device. The LWEB-800/802 projects needs
to be downloaded to the device.
New on device The LWEB-800/802 projects on the device are newer than
the projects in the database. This happens if the
LWEB-800/802 projects are updated with a different tool.
File missing This is an error state. The device is assigned a
LWEB-800/802 project, but the file no longer exists on the
server.
Undefined This status symbol is displayed if there are multiple
LWEB-800/802 projects on the same device and the status
is not the same for all projects.
Not available This status symbol is displayed if the device does not
support LWEB-800/802 projects.
- No This status symbol is displayed if the device supports
LWEB-800/802 LWEB-800/802 projects, but no project is stored on the
project devices device.
Table 47: LWEB-800/802 Status

The property view contains detailed information about the selected device(s). Table 48
describes the information displayed in the LWEB-800 projects section of the property
view. New LWEB-800/802 projects can be assigned to the selected device(s) by clicking on
the button Select new LWEB-800 project files.

Line Description

File name File name of LWEB-800/802 project.


File date in database Timestamp of the LWEB-800/802 file which is assigned to the
device.
File date on device Modification date of the LWEB-800/802 file on the device.
Table 48: LWEB-800/802 Project Properties

6.22.5.1 Upload LWEB-800/802 projects


To upload the LWEB-800/802 projects stored on one or more devices perform the
following steps:

1. In the device list, select one or more devices for which you want to upload the
LWEB-800/802 project files.

2. Choose Upload LWEB-800 projects from the context menu in the list view of the
Overview tab.

3. The Upload LWEB-800 projects dialog opens as shown in Figure 200. This dialog
displays a list of devices and the LWEB-800/802 projects which will be uploaded. To
start the upload, press the Start upload button.

4. During the upload the Status column is updated with current information. Uploaded
LWEB-800/802 files get a prefix containing the name of the device and the upload
timestamp:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 186 LOYTEC

[<device name>_<date>_<time>]_<LWEB-800 project file name>.lweb


or
[<device name>_<date>_<time>]_<LWEB-802 project file name>.lweb2

This prefix is internal to LWEB-900. When downloading a LWEB-800/802 project to a


device the prefix is removed and the file gets the original name.

The LWEB-800/802 file name can be changed in the Select L-Web projects dialog
(see Section 6.22.7).

Figure 200: Upload LWEB-800 Projects Dialog

6.22.5.2 Assign LWEB-800/802 projects


To assign LWEB-800/802 projects to one or more devices perform the following steps:

1. In the device list, select one or more devices to which you want to assign the same
LWEB-800/802 project files. Usually you will assign a certain LWEB-800/802 project
only to a single device.

2. Click on the Select new LWEB-800 project files button in the property view.

Note: An alternative method is to choose Select LWEB-800 project files from the context menu in
the list view.

3. The Select L-Web projects dialog opens as shown in Figure 201. The dialog displays
a list of LWEB-800/802 projects available in LWEB-900. Use the checkboxes to
assign LWEB-800/802 projects to the device(s) and press OK.

To get LWEB-800/802 projects into LWEB-900 you have two possibilities:

 Upload the program from a device as described in Section 6.22.5.1.

 If you have the LWEB-800/802 project file (extension .lweb or .lweb2) available
on your hard disk, click on the Import new file… button, which opens a file
selection dialog.

Note: The LWEB-800/802 project file can be exported from the L-INX Configurator by pressing
the Export… button on the L-Web Projects tab.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 187 LOYTEC

Figure 201: Select LWEB-800 Projects Dialog

6.22.5.3 Downloading LWEB-800/802 projects


To download LWEB-800/802 projects to one or more devices perform the following steps:

1. In the device list, select the devices to which you want to download the assigned
LWEB-800/802 projects. Select Download LWEB-800 projects from the context
menu in the list view of the Overview tab.

2. The Download LWEB-800 projects dialog opens. This dialog displays a list of
devices and the LWEB-800/802 project files which will be downloaded. To start the
download press the Start download button.

6.22.6 Backup and Restore


Figure 202 shows the Backup/Restore tab. Using this tab, you can perform manual
backups, define backup schedules, and restore LOYTEC devices.

Figure 202: Backup/Restore Tab

6.22.6.1 Manual Backup


To backup one or more devices manually perform the following steps:

1. In the device list select the devices which you want to backup.

2. Press the button Backup selected devices.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 188 LOYTEC

3. Enter a backup description and press Continue. The description helps you later to
identify a certain backup.

4. The Backup devices dialog opens (see Figure 203). To start the process, press the
Start backup button. During the backup the Status column is updated with current
information.

Figure 203: Backup Devices Dialog

6.22.6.2 Backup Schedules


The lower part of the Backup/Restore tab (see Figure 204) allows to define backup
schedules. Table 49 describes the columns of this table.

Figure 204: Backup Schedules Table

Column Description

Active This checkbox allows to activate/deactivate a backup schedule.


Name User defined name for backup schedule.
Folder The backup schedule contains all devices inside this folder.
Type Type of schedule: Daily, Weekly, Monthly, or Yearly.
Date Configured backup date.
Daily: Empty
Weekly: Weekday
Monthly: Day in month
Yearly: Date
Time Configured backup time.
Next backup Date and time when the backup schedule will be executed next.
Last backup Date and time when the backup schedule was executed last.
Table 49: Backup Schedule Properties

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 189 LOYTEC

Create a new backup schedule:

1. In the navigation view select a folder. The device list displays all devices below the
selected hierarchy level. These devices will be included in the backup schedule.
Because the backup schedule references a hierarchy level (folder) and not individual
devices, devices which are added later below this level will be included in the backup
automatically.

2. Click on the New backup schedule button.

3. Configure the name in the Edit backup schedule dialog (see Figure 205) and select
when the backup will be executed.

Figure 205: Edit Backup Schedule

Edit Backup Schedule

1. Select a backup schedule.

2. Right click and select Edit selected backup schedule from the context menu, or
double click on the selected backup schedule.

3. Change the schedule settings in the Edit backup schedule dialog (see Figure 205)

Remove Backup schedule

1. Select a backup schedule.

2. Right click and select Delete selected backup schedule from the context menu.

6.22.6.3 Restore
Perform the following steps to restore one or more devices from a backup:

1. Select the devices you want to restore in the device list

2. Click on the button Restore selected devices.

3. The Restore devices dialog (see Figure 206 and Table 50) allows selecting the backups
which will be restored. Per default the latest backup is selected for each device. You
can select a different backup using one of the following methods:

 Select specific backup: Select a single device and right-click on the date column.
A context menu appears which allows you to select one of the available backups
for the selected device.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 190 LOYTEC

 Select backup before a certain date: Select multiple devices, right-click on the date
column and select Backup before date…. The following dialog allows you to
specify a date.

 Select latest backup: Select multiple devices, right-click on the date column, and
select Latest backup.

4. Press the button Restore devices.

5. The Restore backup files dialog opens (see Figure 207). To start the restore process,
press the Start download button. During the restore operation, the Status column is
updated with current information.

Figure 206: Restore Devices Dialog

Column Description

Device Name and IP address of the device.


No of backups Number of available backups for this device.
Date Date of the currently selected backup.
Description Description of the currently selected backup.
Backup Type of the currently selected backup:
 Manual: The currently selected backup was created
manually.
 Automatic: The currently selected backup was created by a
backup schedule.
Table 50: Columns of Restore Device Dialog

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 191 LOYTEC

Figure 207: Restore Backup Files Dialog

6.22.7 File Selection Dialog


The dialog to assign a file to a device looks similar for all devices types. Figure 208 shows
the Select Firmware dialog as an example. All dialogs have the following columns in
common:

 File name

 Original path: Files are uploaded from an LWEB-900 client to the LWEB-900
server. The original path shows where the file was originally stored:

[localhost]<path>
The file was stored on the same PC where the LWEB-900 server is running in the
specified path.

[<IP address or host name>]<path>


The file was stored on the PC with the specified IP address in the specified path.

<device name>
File was uploaded from the specified device.

www.loytec.com
File was downloaded from the LOYTEC homepage (for firmware files only).

 Use: This number indicates how many devices the file is assigned to. A file can be
deleted only if the use count is 0.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 192 LOYTEC

Figure 208: File Selection Dialog

The dialog allows the following actions:

 Import new file: Import a new file from the hard disk. If a file with the same name
already exists in the database, you have the option to overwrite or to rename the
existing file.

 Remove file: A file can be removed only if it is not assigned to any device (use
count must be zero).

 Rename file: Existing files can be renamed. The new name must be unique.

 Check for new version on LOYTEC web-site: This action applies only to
firmware files. LWEB-900 checks if a new firmware version has been published on
the LOYTEC web site. If this is the case, LWEB-900 can download the new
firmware and assign it to the selected device.

6.22.8 Manage Files


The manage files dialog displays all files which have been imported into the master device
manager or uploaded from LOYTEC devices. The dialog is opened by pressing the
Manage files button on the Overview tab.

Figure 209: Open Manage Files Dialog

The list of files can be filtered using the checkboxes on the top (see Figure 210).

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 193 LOYTEC

Figure 210: Manage Files Dialog

The dialog allows the following actions:

 Import new file: Import a new file from the hard disk. If a file with the same name
already exists in the database, you have the option to overwrite or to rename the
existing file.

 Remove file: A file can be removed only if it is not assigned to any device (use
count must be zero).

 Remove unused file: Only files which appear in the list above (filter is applied)
and which have a use count of 0 are removed.

 Rename file: Existing files can be renamed. The new name must be unique.

6.23 Perspectives
Views are organized in the application window in an arrangement called a perspective. You
can create and customize your own perspectives by arranging views in the layout that best
suits your working style for specific tasks.

Figure 211: Perspectives Toolbar

Create a new perspective

1. Open the relevant views and arrange them on your screen in the way it suits you best.

2. Press on the New perspective toolbar button.

3. Define a name and description for the perspective.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 194 LOYTEC

Figure 212: New Perspective

4. Select the initial perspective configuration:

 From current perspective: The new perspective is based on your current view
arrangement. This is the default.

 From default perspective: The new perspective is based on your default


perspective. The default perspective is defined for each user in the user
management dialog (see Section 6.27).

5. Click OK to save the perspective. The perspective is created in your home directory. It
is now available in the perspective selection drop-down list.

Save and reset perspectives

After you have created a new perspective, you will open new views and change the
arrangement of existing views. Your current layout is automatically saved when you log out.
Therefore, when you start the LWEB-900 client, you will find it in the same state as when
you left it. To return to the initial layout of your perspective, click on the Reset Perspective
toolbar button. To override the initial layout with your current layout, click on the Save
Perspective toolbar button.

Make perspective available to other users

When you create a new perspective, it is stored in the Perspectives folder of your home
directory. Objects in your home directory cannot be accessed by other users. To make a
perspective available to other users, drag it to the System/Perspectives folder (see Figure
213). Per default all user have access to this folder and its contents. You can change the
access rights as described in Section 6.28. The perspective selection drop-down box shows
all perspectives to which you have at least Read access. To save a perspective, you need to
have Configure access.

Figure 213: Make Perspective Available to Other Users

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 195 LOYTEC

6.24 Device Communication Profiles


Communication profiles define how LWEB-900 accesses LOYTEC devices. When adding
a new device, the communication profile is assigned to the device (see Section 6.5). In the
object list view the communication profiles can be expanded to see all devices which are
member of the profile (see Figure 214). You can use drag-and-drop to re-assign a device
from one communication profile to another.

Figure 214: Communication Parameters Folder

Create a new communication profile

1. Right click on the folder Network/Communication Parameters and select New 


New Web Service Communication Profile from the context menu.

2. Define name and description for the communication profile.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 196 LOYTEC

Figure 215: Device Communication Profile

3. Define the maximum number of parallel file transfers: Files need to be transferred
to/from a device for firmware upgrades, backup, restore, parameter download/upload,
global connections download/upload, etc. To limit the traffic on the network the
number of concurrent file transfer can be limited by this setting.

4. Define OPC communication parameters: The LWEB-900 Server uses the OPC
XML-DA communication standard to access data points on LOYTEC devices. The
standard defines two data access modes:

 Polling: The data points are polled periodically using the interval defined by Poll
cycle.

 Delayed response: Delayed response is a more efficient alternative to polling. In


this mode, a LOYTEC device delays the poll response until one of the requested
data points has changed. The parameter Hold time specifies the minimum time the
LOYTEC holds off until it responds. Set this value based on the maximum update
rate needed. The parameter Wait time instructs the LOYTEC device to wait the
specified duration after the hold time is reached before responding even if no data
points have changed.

5. Define BACnet communication parameters: The LWEB-900 Server uses COV


subscriptions to access properties of BACnet objects. If a device does not support COV
subscriptions, the properties are read periodically using the poll cycle parameter.

6. Define status polling properties: The LWEB-900 Server monitors all LOYTEC devices
to detect if a device is not responding or if the configuration has changed. A web

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 197 LOYTEC

service is used to check LOYTEC devices and a BACnet service is used for devices of
other manufacturers. The Polling status properties define how often the device is
checked.

7. Define trend and alarm log polling properties: These settings specify how often device
trend and alarm logs are read from the device. This poll cycle has to be configured so
that LWEB-900 reads out the data before the device runs out of memory and overwrites
old data. Usually the devices have enough memory to store log data for several days.
Therefore, it is sufficient to read out log data once a day. A web service is used to
access LOYTEC devices and a BACnet service is used for devices of other
manufacturers.

Note: Using the Starting date and time parameter, you can define at what times a poll cycle is
started.

6.25 System Registers


The LWEB-900 server provides internal information as system registers in the folder
System/System Registers. These registers can be used in a graphical view or added to a
watch view.

Folder System/System Registers

Name Description

Server Version Version of LWEB-900 Server and build date


Server Time Server Time (UTC) in seconds since January 1, 1970 00:00:00
Server TZ Offset Server time zone offset in seconds, positive east of GMT
Server CPU Load CPU load in % of PC hosting the LWEB-900 Server
Server Free Memory Free RAM in MBytes of PC hosting the LWEB-900 Server
Project Status XML description of the contents of the LWEB-900 project.

Folder System/System Registers/Alarm

Name Description

Active Unack Alarm Total number of active unacknowledged alarms


Count
Active Ack Alarm Count Total number of active acknowledged alarms
Inactive Unack Alarm Total number of inactive unacknowledged alarms
Count
Disabled Alarm Count Total number of disabled alarms
Table 51: LWEB-900 System Registers

6.26 Offline Mode


The LWEB-900 Server can be set into offline mode. In this mode there is no
communication with the LOYTEC devices. Therefore, no current data point values can be
displayed in graphical view, watch view, and object list view. No alarms are displayed in
the alarm view. The trend chart view, trend log view, and alarm log view display only data
which has already been stored in the database before switching to offline mode.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 198 LOYTEC

In offline mode all functionalities which require communication with the device are
disabled (upload/download device configuration and parameters, refresh data point values,
device backup, firmware update, etc.).

Switch to offline mode

1. Press on the Set Project Offline toolbar button.

2. The LWEB-900 client status bar indicates the project is now in offline mode.

Switch to online mode

1. Press on the Set Project Online toolbar button.

2. The LWEB-900 client status bar indicates the project is now in online mode.

6.27 User Management


When the LWEB-900 client is started a login is required. There is a default admin user
(user name: “admin”, password: “loytec4u”) who has full access rights. New users can be
created in the user management dialog. Users can be assigned to user groups. User groups
are the basis to define detailed access rights on objects.

Figure 216: User Management Toolbar

LWEB-900 supports two types of user authentication:

 LWEB-900 Authentication: The user name and password are stored in the LWEB-
900 data base. The LWEB-900 Server performs the authentication.

 Windows Authentication: The LWEB-900 Server is connected to an Active


Directory server which performs the authentication.

Crate a new LWEB-900 authenticated user

1. Click on the User Management toolbar button.

2. To add a new user, click on the New user button.

3. Select the radio button LWEB-900 Authentication.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 199 LOYTEC

Figure 217: New LWEB-900 Authenticated User

4. Specify the user properties:

 User name: Login name.

 Access level: This drop-down box defines the default access rights of the user. It is
used to define a role for a user. The following access levels are defined:

o No access: The user cannot log-in. This setting is used to temporarily


disable a user.

o Read: The user can start the LWEB-900 client, but he is not allowed to
modify anything. He can monitor data points in watch views, graphical
views, etc., but he is not allowed to change the values of the data points.
He can see the current parameter values in a parameter view, but he is not
allowed to set the parameters. The user is notified about alarms, but he
does not have the right to acknowledge them. Master schedules can be
viewed but not modified. The user is allowed to open chart and trend log
views, but he cannot edit trend log records.

o Read/Write: The user is allowed to change data point values using e.g.
watch views and graphical views. He can modify and download
parameters using parameter views. The events and calendars of a master
schedule can be configured. The user is allowed to acknowledge and
disable alarms. He can edit trend log records.

o Configure: In addition to access level Read/Write, the user is allowed to


create/edit/remove objects in the navigation view. The user is not allowed
to open the user management dialog or change access rights.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 200 LOYTEC

o Full Control: The user has unrestricted access. He is allowed to


create/edit/remove users and groups and can define detailed access rights
on objects.

 Password: Password for login.

 Password confirmation: Enter password a second time for confirmation.

 Full name: Optional input field for full user name.

 Description: Optional input filed for user description.

 E-Mail address: Optional input field for user e-mail address. If an e-mail address
is specified, an alarm receiver is created automatically for the user (see also
Section 6.14.3).

 Auto logout time: If the user performs no activity for the specified amount of
time, he is automatically logged out. Set this value to zero to disable the auto
logout function.

 Default perspective: This drop-down box configures the perspective which is


loaded when the user logs in for the first time.

 Show objects on which the user has no read access: If this checkbox is enabled,
the user sees objects (e.g. folders) to which he has no read access. They are
displayed with a lock icon. If this option is disabled, those objects are not visible in
the navigation and object list view.

 Can switch between normal and kiosk mode: If this checkbox is enabled, the
user can switch between normal and kiosk mode using the keyboard combination
Ctrl+Enter or the File menu.

 Is the default user: The default user has no password and no auto-logout. If no
username and password is specified in the login-in dialog, the LWEB-900 client
logs in the default user. If a standard user logs out (auto-logout or manual logout),
the default user is automatically logged in. Only the admin user can define/remove
the default user.

Note: The admin user is a special user with the following properties:
 The user name of the admin user cannot be changed .
 The admin user has access level Full Control and this cannot be changed.
 The admin user cannot be assigned to groups.
 Access rights do not apply to the admin user.
 The admin user cannot be the default user.

Create a new Windows authenticated user

1. Click on the User Management toolbar button.

2. To add a new user, click on the New user button.

3. Select the radio button Windows Authentication.

4. Click on the Browse icon beside the Usename. The following dialog allows you to
search for users and groups in the Active Directory.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 201 LOYTEC

Figure 218: New Windows Authenticated User

Note: LWEB-900 allows adding a whole Windows group as a Windows authenticated user. This
way it is possible to define the access rights for members of the Windows group in
LWEB-900 and manage the user in Active Directory.

Create a new user group

1. Click on the User Management toolbar button and switch to the User Groups tab.

2. To add a new group, click on the New group button.

Figure 219: User Groups

3. Specify a group name. The description is optional.

4. Define the group members: The list on the left side of the dialog displays the available
users; the list on the right displays the group members. To add a user to the group,
select the user in the left list and click on the -> button. To remove a user from the
group, select the user on the right side and press the <- button.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 202 LOYTEC

Edit personal information

Each user can change his full name, description, e-mail address, and password by clicking
on the Edit personal information toolbar button.

Figure 220: Edit Personal Information

6.28 Access Rights


The global access level specified for each user defines the default access rights. These
default access rights can be further refined by defining access rights to the individual
objects in the navigation tree. The effective access rights can never exceed the user access
level.

LWEB-900 uses access control lists (ACL) to define which operations a user can perform
on a certain object (e.g. folders, data points, visualization view, parameter view, trend
charts). Figure 221 shows the default access control list for objects outside the user’s home
directory.

Figure 221: Default Access Control List

The access control contains only a single entry: Allow full control to everyone. This ACL
entry is inherited from the parent object. Because full control is the highest access level, the
effective access level for a specific user is determined by the access level settings in the user
management dialog.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 203 LOYTEC

Change access right of an object

1. Right-click on an object (e.g. folder) in the navigation or object list view and select
Access rights from the context menu.

Figure 222: Edit Access Rights

2. Per default an object inherits the access rights from its parent. To remove the inherited
permissions, clear the checkbox Inherit permissions from parent.

3. To add a new ACL entry, click on the button New permission entry. Because the
permission entry is created specifically for this object, this type of entry is called an
explicit permission entry.

Figure 223: New Permission Entry

4. Select the Group/User for which the permission entry applies. Everyone is a special
group which contains all users.

5. Specify the Access Level (see Table 52). Deny permissions take precedence over allow
permissions.

6. To remove an ACL entry, select it and click Delete. Inherited permission entries cannot
be deleted. Disable the Inherit permissions from parent checkbox instead.

7. To edit an ACL entry, select it and click Edit. Inherited permission entries cannot be
edited.

8. If you want to apply the access level settings to all child objects, click on the button
Replace all child explicit permissions by inherited permissions.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 204 LOYTEC

Access Level Description

Allow Read The user is allowed to see the value of the object (e.g. data point
value, parameter value).
Allow Write In addition to the permissions granted by Allow Read, the user is
allowed to change the value of the object (e.g. data point value,
parameter value).
Allow Configure In addition to the permissions granted by Allow Read, the user is
allowed to change the configuration of the object (e.g. change
graphical view, add object in folder).
Allow Full Control In addition to the permissions granted by Allow Configure, the
user is allowed to edit the access rights of the object.
Deny Full Control The user is denied to change the access rights of the object.
Deny Configure In addition to the permissions denied by Deny Full Control, the
user is denied to change the configuration of the object (e.g.
change graphical view, add object in folder).
Deny Write In addition to the permissions denied by Deny Configure, the
user is denied to change the value of the object (e.g. data point
value, parameter value).
Deny Read In addition to the permissions denied by Deny Write, the user is
denied to see the value of the object (e.g. data point value,
parameter value).
Table 52: Access Levels

Algorithm to determine effective access rights

LWEB-900 uses the following algorithm to determine if a user is allowed to perform a


certain action on an object:

1. If the action is not allowed due to the access level set in the user management dialog
(see Section 6.27), the algorithm stops and the action is denied.

2. If the ACL of the object contains an explicit Deny entry for the requested action, the
algorithm stops and the action is denied.

3. If the ACL of the object contains an explicit Allow entry for the requested action, the
algorithm stops and the action is allowed.

4. If the ACL of the object contains a Deny entry inherited from the parent object, the
algorithm stops and the action is denied.

5. If the ACL of the object contains an Allow entry inherited from the parent object, the
algorithm stops and the action is allowed.

6. Step 4 and 5 are repeated for entries inherited from the next higher hierarchy level until
the top level is reached.

7. If the evaluation has made it to the top of the tree and the action does not have an
Allow or Deny permission, the action is denied.

Note: It is possible to deny a user read access to a folder but allow him access to lower-down
objects. For example, you can setup the access rights to allow Write access to the folder
Network/Devices, but deny access to the folder Network. In this case, the user cannot use
the navigation and object list view to browse the data points on the devices. However, the
user can use a graphical view to modify the referenced data points.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 205 LOYTEC

6.29 L-Studio Projects


LWEB-900 can import the following data from L-Studio projects:

 LOYTEC devices and their data point configuration: Because the devices are
engineered using L-Studio, LWEB-900 does not allow modifying them with the
device configuration software.

 Global connections: Global connections are configured in L-Studio. LWEB-900


displays them but does not allow changing them.

 Graphical views: Graphical views can be imported to a user folder. For graphical
views imported from L-Studio, no data point interface is displayed and they cannot
be modified in LWEB-900.

Add L-Studio Project

1. Build the project in L-Studio. The compilation generates the configuration files of the
devices and the graphical views.

2. In LWEB-900, select the folder Network/Devices or a subfolder and choose New 


New L-Studio Project from the context menu.

3. In the New L-Studio Project dialog (see Figure 224) enter the following data:

 Name: User defined name which will be displayed in the navigation view.

 Description: Optional description of the L-Studio project.

 L-Studio project file: Select the solution file (.sln) of the L-Studio project.

 Global graphical views: Select the destination folder for global graphical views.
Global graphical views can display information from multiple devices. If this field
is left empty, global graphical views are not imported as server graphical views.

 Device graphical views: Select the destination folder for device graphical views.
Device graphical views are created in L-Studio for each device instance from the
device CAT (Composite Automation Type). If this field is left empty, device
graphical views are not imported as server graphical views.

Figure 224: Add L-Studio Project

4. The imported devices are displayed in the navigation view and you have access to all
data points.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 206 LOYTEC

Figure 225: Navigation View after L-Studio Import

Update L-Studio Project

If you have changed your L-Studio project and compiled it, then the project needs to be
updated in LWEB-900.

1. In LWEB-900, select the L-Studio project and choose Update L-Studio Project from
the context menu.

Note The Update L-Studio project context menu item is displayed only if LWEB-900 finds the L-
Studio solution file. If the menu item is missing, select Properties from the context menu
and check the file path.

2. The L-Studio Project Update View displays the changes in the L-Studio project.
Select Update project to import the new files.

Figure 226: L-Studio Project Update

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 207 LOYTEC

7 WEB Access

The graphical views defined in an LWEB-900 project can be accessed with a standard web
browser. In this way it is possible to quickly check the status of the building automation
system while travelling. It makes no difference, whether a smart phone, tablet, or PC is
used.

Open graphical view in web browser

1. Open the web browser an enter the following URL:

http://<IP address of server>:<port>/lweb900/

Note: The port is configured in the network settings of the LWEB-900 server (see Section 5.3).
The default port is 8080.

2. Specify the name of the LWEB-900 project. If the LWEB-900 Server is password
protected, you have to enter the name in a text field, else you are presented with a drop-
down list of the available projects.

3. Enter your user name and password and press OK to login.

LWEB-900 Web Login

4. The web browser displays a list of all graphical views and chart views of the
LWEB-900 project to which you have at least Read access.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 208 LOYTEC

Figure 227: Graphical View List

5. Click on the name of a graphical view to open it.

Figure 228: Graphical View in Web Browser

Create home screen icon on Android devices

1. Bookmark the graphical view in your browser.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 209 LOYTEC

2. Android 4.x: Tap on the app panel (six squares) in the upper right of the home screen.
Switch to Widgets and long press on Bookmark.

Older Android versions: Long press on the home screen. From Add to Home Screen,
select Shortcuts and then select Bookmark.

3. Select the bookmark of your graphical view.

Create home screen icon on iOS devices

When the graphical view is displayed, just hit + and select Add to Home Screen.

7.1 Navigation Menu and System Menu


The navigation menu is opened by one of the following actions in the main window:

 Left click and hold: The left click and hold operation opens the navigation menu
after the time configured in the L-VIS/L-WEB Configurator. Please note that for
correct operation, the left click and hold action should be executed on a free spot
on the display. If the area of an input control is clicked, the control enters input
mode and all further input is processed by the control.

 Right click: A right click has the same effect than a left click and hold operation. It
is not available on touch displays.

Figure 229 shows an example of the navigation menu.

Figure 229: Navigation Menu

The navigation menu displays the menu items which were defined in the L-VIS/L-WEB
Configurator and and the “System” entry to open the menu shown in Figure 230.

Figure 230: System Menu

The system menu give access to the following functionality:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 210 LOYTEC

 Project list: Display a list of graphical views in the LWEB-900 project.

 Global settings: Refer to section 7.2.

 Project settings: Refer to section 7.3.

 Edit connection: Edit the connection parameters.

 Statistics: Refer to section 7.4.

 Show log: Refer to section 7.6.

 Refresh values: This icon is displayed only if manual only is selected as


update method in the global settings. Clicking on this icon performs a manual
update of the data point values.

7.2 Global Settings


Global settings apply to all graphical views.

Figure 231: Global Settings

The Global settings dialog as shown in Figure 231 contains the following settings:

 Show error tooltips: If this checkbox is set, a tooltip is displayed showing the
OPC error when hovering over a grayed-out control.

 Update control: This setting defines how often data point values are updated. The
default setting is use project settings.

 Language: This drop down box allows changing the display language. The new
setting takes effect after reloading the application (CTRL+r).

7.3 Project Settings


This dialog contains settings which are specific to a graphical view.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 211 LOYTEC

Figure 232: Project Settings

 Default page: If the graphical view contains multiple pages, the default page
which is displayed when opening the view can be selected from this drop-down
list.

 Lock project settings: If this checkbox is enabled, a PIN code will be required
before opening the project settings dialog. In addition, no menu entries will be
displayed in the navigation menu. This feature can be used for example to setup a
project with multiple pages where each page controls an office room. The default
page for each user is set to the room in which he is located and then the menu is
disabled. This way each user can control only the own room.

The PIN codes can be configured in the L-VIS/L-WEB Configurator using the
menu File  Project Settings. Press the Button Setup Pin Codes… to open the
Access Codes Dialog and set the PIN code for Level 15.

 Context menu for data points: If this checkbox is enabled, you can click with
your right mouse button on a control to view data point details. A context menu is
displayed listing the attached data points (see Figure 233). Select the name of the
data point for which you want to inspect the properties as shown in Figure 234.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 212 LOYTEC

Figure 233: Data Point Context Menu

Figure 234: Data Point Details

 Occupancy timeout: LWEB-802 has an internal system data point called PC


Active. If enabled, this data point is 1 as long as there is activity inside the browser
window. LWEB-802 cannot detect activity outside the browser window.

 Mute sound: This option allows disabling sound output for the project.

 Automatically check for new project version: If this option is enabled,


LWEB-802/803 automatically checks in the background if a new version of the
project is available. This check is done once every hour. If a new version is
detected, it is reloaded automatically

 Autoscale: This option is only available in LWEB-802. The user can always
change the zoom level manually using pinch-zoom or CTRL + mouse wheel. The
autoscale operation is performed for each project load, orientation change, or
resize event. The drop down box contains the following settings:

o None: No autoscale is performed and the zoom level is persistent.

o Fit in Window: The graphical view is scaled to completely fit into the
browser window.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 213 LOYTEC

o Cover Window: The graphical view is scaled to fit either the width or the
height of the browser window so that the whole browser window is
covered.

o Fit Width: The graphical view is scaled to fit the width of the browser
window.

o Fit Height: The graphical view is scaled to fit the height of the browser
window.

7.4 Error Handling


If a control does not receive data from the LOYTEC device or the LWEB-900 server, the
control will be grayed out. If tooltips for error messages are enabled the OPC error message
will be displayed when hovering over the control as shown in Figure 235.

Figure 235: Tooltip to report error

7.5 Statistics
The Statistics dialog displays the connection status with the LWEB-900 Server (see
Figure 236).

Figure 236: Connections Dialog

7.6 System Log


The system log records all activities. When reporting a problem with the LWEB-900 web
access, it is recommended to include a screenshot of the system log. This will speed-up
problem analysis.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 214 LOYTEC

8 Interfaces

8.1 Trend Log CSV File


The CSV file format for a trend log is defined in this section. The CSV file starts with a
header, containing at least the first line, which specifies the CSV format (log_csv_ver). The
current version is 2. The next line contains the field log_device. It has trailing fields that
specify the vendor, product code, firmware version and device ID string. The Device ID
String contains the host name of the LWEB-900 Server.

The log_info line specifies the ID and name of the trend log object. The line log_create has
two fields specifying the date and time when this CSV log was generated. The line
log_capacity has two fields: the current number of log entries in the file and the log
capacity.

Following are one or more lines of log_item. Each line specifies a trended data point. The
first field is the index, the second the ID of the logged data point, the third the data point
name. The data point name can be augmented by engineering units in square brackets. Log
entries in the CSV refer to the item index to identify the data point, for which the entry was
logged.
#log_csv_ver,2
#log_device;LOYTEC;Product Code;Firmware Version;Device ID String
#log_info;Log-ID;Log Name
#log_create;YYY-MM-DD;HH:MM:SS
#log_capacity;filled;capacity
#log_item;index;UID;data point name [units]

After those lines any number of comment lines starting with a hash character ‘#’ are
allowed. One line contains the column headings. Lines that are not comments specify one
log record per line, using the column information as described below. The columns are
separated by commas ‘,’ or semi-colons ‘;’. If commas are used as a separator, the decimal
point must be a point ‘.’. If semi-colons are used, the decimal point must be a comma ‘,’.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 215 LOYTEC

Column Field Example Description

A Sequence Number 50 The log record sequence number. This is the


monotonously increasing sequence number, which is
unique for each log record.
B Source 0 Data point source identifier. Indexes into logger_entry
header. For value lines in a multi-column CSV, this
field indexes the first column, which has a value. For the
ERROR record type, the field indexes the data source
that caused the error. For LOGSTATE, TIMECHANGE
records this field is not applicable and set to 255.
C Record Type 2 The record type: LOGSTATE (0), BOOL (1), REAL
(2), ENUM (3), UNSIGNED (4), SIGNED (5), NULL
(7), ERROR (8), TIMECHANGE (9)
D Error/Time 1 This field is valid for records of type ERROR,
Change/Log TIMECHANGE, and LOGSTATUS.
Status
E Date/Time 2007-11-02 15:34:22 The date/time of the log record. This is in the format
YYYY-MM-DD HH:MM:SS.
F Value 0 24,5 Logged value from source 0 or empty
G Value 1 200 Logged value from source 1 or empty
… …
… Value n – 1 5000 Logged value from source n – 1 or empty
Table 53: Columns of the Trend Log CSV File.

There are as many value columns as value sources specified in the header. If at a given
date/time more values are logged, all of them appear in the same line. If at that given time
some sources did not log values, those columns are left empty. The “Source” column in a
multi-value CSV refers to the first data source that supplied a value in a given line.

8.2 Alarm Log CSV File


The historical alarm logs can also be exported as CSV-formatted files. The CSV format of
the alarm log CSV file is identical to the trend log CSV format as described in Section 8.1.

8.3 Identification Key CSV File


Identification keys can be exported and imported via CSV files. Figure 237 shows and
example.
Path,Name,IK,Type,Description
./LI/I1/,nvoLIvalue,VIEBG35O401LIRCT00ZON01LIF00CMD00,DP User Output,
./LI/I1/,nviLIvalueFb,VIEBG35O401LIRCT00ZON01LIF00CMF00,DP User Input,
./LI/I1/,nviLIOvrValue,VIEBG35O401LIRCT00ZON01LIF00OVR00,DP User Input,
./LI/I1/,nvoLIovrValue,VIEBG35O401LIRCT00ZON01LIF00OVR00,DP User Output,
./LI/I1/,nvoLIvalFb,VIEBG35O401LIRCT00ZON01LIF00CMF00,DP User Output,
./LI/I1/,nviLIlux,VIEBG35O401LIRCT00ZON01SEL00VAL00,DP Analog Input,
./LI/I1/,nviLIoccup,VIEBG35O401LIRCT00ZON01SEO00VAL00,DP Multistate Input,
Figure 237: Example of Identification Key CSV File

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 216 LOYTEC

Column Field Description

A Path Path of the object relative to the folder from which the file was exported
B Name Name of object
C IK Identification key assigned to the object
D Type Object type
E Description Object description
Table 54: Columns of the Identification Key CSV File.

8.4 Database Interface


To allow 3rd party applications access to historical data, trend and alarm logs are stored in a
dedicated database. When creating a new LWEB-900 project, you can decide which
database engine to use (see Section 5.7). The following sections describe the tables used to
store trend and alarm log information.

8.4.1 Datalog Configuration Table (DatalogConfig)


This table contains global data log parameters stored as (key, value) pairs. The "key" is the
unique identifier of the parameter, its "value" is a string.

Name Type Description

Id int64 Id of the parameter:


DATABASE_VERSION (0)
Value text Value of the parameter.
Table 55: DatalogConfig Table

8.4.2 Log Information Table (LogInfo)


This table contains global information on log objects.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 217 LOYTEC

Name Type Description

Id int64 Unique identifier of the log


Type int16 Type of the log:
 Device trend log (0)
 Device alarm log (1)
 Server trend log (2)
 Server alarm log (3)
SourceName varchar(64) Name of the source for this log:
 Name of a device in case of a device log
 Name of an LWEB-900 project in case of a server log
AbsolutePath text Path of the log in the form /<log source name>/…/<log
name>
SourceTotalCnt Int64 Total count of records ever logged on the log source (e.g.,
device). Some of these records might no longer be on the
log source due to log size limitation or user deletion.
ServerTotalCnt Int64 Total count of records ever logged on the LWEB-900
Server. Some of these records might no longer be in the
database due to log size limitation or user deletion.
ServerRecCnt Int64 Actual count of records stored in this log on the
LWEB-900 Server
FirstTimestamp Int64 Date/time in seconds since 1.1.1970 of the oldest record
in this log
LastTimestamp Int64 Date/time in seconds since 1.1.1970 of the newest record
in this log
Table 56: LogInfo Table

8.4.3 Log Item Information Table (LogItemInfo)


This table contains a description of the items for which trend log records are stored into the
database.

Name Type Description

LogId int64 Identifier of the log this log item is attached to


ItemId Int64 Internal identifier of the log item in the LWEB-900
configuration database
ItemIndex int16 Index of this item within the set of log items attached to
the same log
AbsolutePath text Absolute path to the log item, in the form /<root object
name>/…/<log name>
Unit varchar(20) Unit to interpret the values logged for this log item
AggregationMode int16 Aggregation mode used when logging values for this
item:
 val (0) : no aggregation
 min (1)
 max (2)
 average (3)
Table 57: LogItemInfo Table

8.4.4 Trend Log Table (TrendLog)


This table contains the records forming the trend logs.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 218 LOYTEC

Name Type Description

RecordType int16 The record type: LOGSTATE (0), BOOL (1), REAL
(2), ENUM (3), UNSIGNED (4), SIGNED (5), NULL
(7), ERROR (8), TIMECHANGE (9)
LogId int64 Identifier of the log this data log record belongs to
ItemIndex int16 Index of the item of the log
SeqNum int64 Sequence number assigned to this record when logged
on the server
Value Nvarchar(1024) Logged value, depending on the record type:
 Data record (BOOL, REAL, ENUM,
UNSIGNED, SIGMNED): value of the item
 Log state record (LOGSTEATE): 1 (log enabled)
or 0 (log disabled)
 Error record (ERROR): error code
 Time change record (TIME CHANGE): Number
of seconds to clock was put forward or backward
 Other: 0
Timestamp int64 Date and time when the record was logged in seconds
since 1.1.1970
Table 58: TrendLog Table

8.4.5 Alarm Log Table (AlarmLog)


This table contains the records forming the alarm logs.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 219 LOYTEC

Name Type Description

LogId int32 Identifier of the log this alarm log record is attached to
ItemIndex Int16 0
RecordType int16 The record type: LOGSTATE (0), BOOL (1), REAL (2),
ENUM (3), UNSIGNED (4), SIGNED (5), NULL (7),
ERROR (8), TIMECHANGE (9)
Timestamp int32 Date and time the record was logged in seconds since
1.1.1970
SeqNum int64 Sequence number assigned to this record when logged on
the server
XAID Varchar(30) Extended alarm identifier; this identifier is used to
acknowledge the alarm on its source
State Int16 State of the alarm in case the event is an alarm event:
 1: active, not acknowledged
 2: acknowledged, but still active
 3: inactive, but not acknowledged
 4: acknowledged and inactive
 5: inactive, no acknowledgement required
AlarmType Int16 Type of the alarm:
 0: normal
 1: off-normal
 2: low-limit
 3: high-limit
 4: fault
 5: buffer
Priority Int16 Priority of the alarm
AlarmTime Int64 Date and time in seconds since 1.1.1970 when the alarm
occurred
ClearTime Int64 Date and time in seconds since 1.1.1970 when the alarm
condition was cleared
AckTime Int64 Date and time in seconds since 1.1.1970 when the alarm
was acknowledged
AckSource text Name of the user who acknowledged the alarm
DisableSource text Name of the user who disabled the alarm
AckRequired Boolean True when acknowledgement is required for the alarm,
else False
Description text Textual description associated to the alarm
ValueType int16 Type of the value column:
 double (0)
 integer (1)
 boolean (2)
Value text Value of the data point when the alarm condition was
triggered
PointName text Name of the data point which triggered the alarm
condition
UserId int64 Internal ID of the user who acknowledged or disabled the
alarm.
Comment Text Comment entered by the user when he disables an alarm
Table 59: AlarmLog Table

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 220 LOYTEC

8.5 Report Template


LWEB-900 can create reports based on trend logs. Reports can be used, for example, to
document the energy consumption in a building. The LWEB-900 Server is delivered with a
set of built-in report templates which cover most use cases for building automation. This
section describes how to create your own custom user report templates.

A user report template is a Zip archive with the (*.rep) file extension. The archive contains
the following files:

 An XML file which describes the template to the LWEB-900 Server

 A Microsoft Report File Definition file (*.rdlc)

 An optional (*.png) file

To create or modify the RDLC file you need the software Microsoft Report Builder. This
software is an Add-on for Microsoft Visual Studio.

You could find Microsoft Visual Studio Express 2012 here:

https://www.microsoft.com/en-us/download/details.aspx?id=34673

To get Microsoft Report Builder you can either download the Microsoft SQL Server
Express 2012 with Advanced Services here:

https://www.microsoft.com/en-us/download/details.aspx?id=43351

Or download Microsoft SQL Server 2012 SP1 Report Builder:

https://www.microsoft.com/en-us/download/details.aspx?id=35576

Create a user defined Report Template

1. Select the build-in report template which is most similar to the report template which
you want to create. Right click on the build-in report template and select Export report
template from the context menu.

2. Change the extension of the exported file from .rep to .zip and unzip it.

3. Modify the files as described in the following sections.

4. Create a .zip archive and rename the file extension to .rep.

5. Click with the right mouse button on the folder Library/Report Templates/User
Report Templates and select Import report template from the context menu.

8.5.1 Report Template XML file


This xml file contains all information required by the LWEB-900 Server to create data for
the report.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 221 LOYTEC

Figure 238: Example of report template XML file with two data groups

The XML file consists of the following main sections:

 TemplateDesc: This xml tag contains the description of the report template

 CommonParams: Each report template can be customized using parameters. This


xml tag contains common parameters which apply to the whole report.

 DataSet: Each report template operates on a data set. A data set can contain one or
two groups. This section defines also the parameters which apply to a specific
group.

Common Params

Common parameters are displayed in the report properties on the Parameters tab as shown
in the following screenshot.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 222 LOYTEC

Figure 239: Common report parameters as seen in LWEB-900 Client

Each common parameter can have the following attributes:

 paramName: Name of the parameter. This name has to match the name of the
parameter in the .rdlc file.

 paramLabel: Label displayed in the Parameters tab of the report properties. If this
attribute is not specified, the parameter is not displayed.

 paramValue: Default value of the parameter.

 paramType: Parameters can have the special types shown in Table 60. If this
attribute is not specified, the parameter is a generic parameter.

 paramDataType: Data type of the parameters as described in Table 61. If this


attribute is not specified, the type is Text.

 paramStateMap: If paramDataType is Integer, a state map can be provided. The


state map is a comma separated list of values.

paramType Description

ReportDesc Parameter contains the description of the report as defined in the report
properties
ExecutionTime Parameter contains the date and time when the report was created
Image Parameter to select an image which should be displayed in the report
Generic Any other parameters
Table 60: Attribute paramType for common report template parameters

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 223 LOYTEC

paramDataType Type Description

Text VarChar Text input field


Integer Int32 If the attribute paramStateMap is provided, a combo
box with the available states is displayed.
Boolean Boolean Checkbox
Table 61: Attribute paramDataType for common report template parameters

Data Set

The DataSet element contains one or two DataSetParam elements. The DataSetParam
elements correspond to the groups on the Datalogs tab as shown in Figure 240. The
groupName attribute define the display name for a group.

Figure 240: DataSet element as seen in LWEB-900 Client

The DatalogSourceParam element has the following attributes:

 maxItems: Maximum number of trend log items in this group. If the value is set to
0, an unlimited number of trend log items can be attached.

 userInstructions: Text displayed in user dialog.

The ValueMethod element allows defining the default aggregation mode. The following
values are allowed:

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 224 LOYTEC

periodValueMethod Description

Average Average value during the step interval


FirstValue First value in the step interval
LastValue Last value in the step interval
Min Minimum value in the step interval
Max Maximum value in the step interval
Sum Sum of all values in the step interval
Delta Calculate the difference between the last value of the current step
interval and the last value of the previous step interval. This aggregation
mode is used for energy counters.
OnCounter Counts how often the value changed from zero to non-zero during the
step interval.
OffCounter Counts how often the value changed from non-zero to zero during the
step interval.
PulseCounter Count how many occurrences of the following sequence is detected
during the step interval: change from zero, to non-zero and then change
back to zero.
RunningTime Time during which the value is non-zero
DownTime Time during which the value is zero
Availability RunningTime/(RunningTime+DownTime) in percent
Table 62: Attribute periodValueMethod for data group

The ReportParam elements define parameters which apply to a specific data group. They
can have the following type:

paramType Description

PeriodFrom Parameter contains the start of the time period for which the report was
created.
PeriodTo Parameter contains the end of the time period for which the report was
created.
StepInterval Parameter contains the step interval of the report.
Color This parameter contains the colors configured for each trend log item in the
data group. A default color palette can be provided in the paramValue
attribute. The colors are encoded in hexadecimal in a RGB color space
(value between: #000000 – black and #FFFFFF - white) and separated by
commas. There should be no space between any characters and the latest
color shall not be followed by a comma.
Table 63: Attribute paramType for data group parameters

8.5.2 Microsoft Report File Definition


A Report Definition Language Client-side is a type of file used to create reports with
Microsoft Reporting technology. To create, preview or modify a RDLC file you will need
the Report Designer from Microsoft Visual Studio 2012 or later.

Note RDLC files are encoded using XML. However, we do not recommend modifying the file
using a text editor as you could easily break the report file.

You can create an RDLC file from scratch or export a build-in report template as starting
point.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 225 LOYTEC

Figure 241: RDLC file as viewed with Microsoft Report Builder

RDLC parameters

Each of the parameters defined in the Report Template XML file has to correspond to a
parameter in the RDLC file.

You can add new parameters in Microsoft Report Builder using the Report Data view
(CTRL + ALT +D when you have a RDLC file open). Name and Data type of RDLC
parameters have to match with the attributes paramName and paramDataType in your
Report Template XML file.

Figure 242: RDLC Parameters as seen with Microsoft Report Builder

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 226 LOYTEC

8.5.3 Image File


The image file for a user-defined report template is optional but strongly recommended. It
provides a preview when selecting a report template. If no image file is provided, a default
image will be displayed. Size minimal recommended: 150*250 pixels

Figure 243: Example of report template with and without (Compare v2) image file

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 227 LOYTEC

9 Troubleshooting

9.1 Technical Support


LOYTEC offers free telephone and e-mail support for the L-WEB product series. If none of
the above descriptions solves your specific problem please contact us at the following
address:

LOYTEC electronics GmbH


Blumengasse 35
A-1170 Vienna
Austria / Europe

e-mail : [email protected]
Web : http://www.loytec.com
tel : +43/1/4020805-100
fax : +43/1/4020805-99

or

LOYTEC Americas Inc.


N27 W23957 Paul Road
Suite 103
Pewaukee, WI 53072
USA

email: [email protected]
web: http://www.loytec-americas.com
tel: +1 (512) 402-5319
fax: +1 (262) 408 5238

or

LOYTEC Asia Corporation Ltd.


16F.-3, No. 155, Zhongyang Rd
Xindian District
New Taipei City 23150
Taiwan

email: [email protected]
tel: +886 (2) 8913 7838
fax: +886 (2) 8913 7830

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 228 LOYTEC

9.2 Bug Reports


When you report a bug, you can speed-up the problem analysis a great deal if you include
the right information. These guidelines explain how to write such reports.

Before you report a bug, make sure your software is up to date. A good bug report includes
the following items:

 Description how to reproduce the problem. This is the most important part of the
bug report. The developer has to be able to reproduce the bug on his or her own
computer. Include screenshots to document the steps to reproduce the problem.

 System Log: The system log can give useful information about what was
happening at the time when the problem occurred.

 Project backup: Sometimes the problem cannot be reproduced without a backup of


your setup. There might be something unusual about your configuration which is
necessary to reproduce the bug.

Save system log to CSV file

1. Start LWEB-900 Server UI

2. Select File  Display System Log from the menu bar.

3. Press on the button Save to CSV file.

Figure 244: LWEB-900 Server System Log

Create a project backup

1. Start LWEB-900 Server UI

2. Right click on the project and select Backup project from the context menu.

3. To minimize the size of the project, select the option Configuration project backup.

4. Click on the button Make backup.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 229 LOYTEC

Figure 245: Project Backup

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 230 LOYTEC

10 Specifications

10.1 System requirements

The LWEB-900 Server requires a Windows PC with the following minimum requirements:
 2 GHz 32-bit or 64-bit processor
 4 GB main memory
 50 GB free hard disk space (for program installation and database)
 Ethernet access
 Operating System:
o Windows 7
o Windows 8
o Windows 10
o Windows Server 2008
o Windows Server 2012

The LWEB-900 Client requires a Windows PC with the following minimum requirements:
 2 GHz 32-bit or 64-bit processor
 2 GB main memory
 1 GB free hard disk space
 Ethernet access
 Operating System:
o Windows 7
o Windows 8
o Windows 10
o Windows Server 2008
o Windows Server 2012
 Minimum display resolution: 1280x720

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 231 LOYTEC

For the LWEB-900 web access one of the following browsers is required:
 Google Chrome (recommended)
 Firefox
 Internet Explorer 10-11, Microsoft Edge
 Android web browser 4.x and later
 iOS web browser

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 232 LOYTEC

11 References

[1] L-VIS User Manual, LOYTEC electronics GmbH,


Document № 88068520, February 2015.
[2] L-INX/L-GATE User Manual, LOYTEC electronics GmbH,
Document № 88073019, January 2015.
[3] LIOB-10X/X5X User Manual, LOYTEC electronics GmbH,
Document № 88078510, April 2014.
[4] LIOB-X8X User Manual, LOYTEC electronics GmbH,
Document № 88080306, April 2014.
[5] L-DALI User Manual, LOYTEC electronics GmbH,
Document № 88077109, August 2014.
[6] L-IP User Manual, LOYTEC electronics GmbH,
Document № 88065911, September 2012.
[7] LWEB-800/802 User Manual, LOYTEC electronics GmbH,
Document № 88074215, March 2015.

Version 2.2 LOYTEC electronics GmbH


LWEB-900 User Manual 233 LOYTEC

12 Revision History

Date Version Author Description

2012-12-14 1.0 AD Initial revision for LWEB-900 1.0.0


2012-05-24 1.1 AD Update for LWEB-900 Version 1.1.0:
 License model based on number of devices
 Support secure communication (SSL) between server
and client
 Use web services for all communication between
server and LOYTEC devices
 Support graphical view templates
 Support graphical views in devices
 Support upload global connections
 Group multiple occurrences of the same alarm
 Search in object path
 Search in fields of structured data points
 Navigation view: additional hierarchy level added to
context menu options
 Import of LWEB-900 project: renaming of the
imported project is now possible
2014-03-02 1.3 AD Update for LWEB-900 Version 1.3.0:
 Reporting
 LWEB-900 Server schedules
 Alarming improvements
 Create L-VIS project from LWEB-900 Server
graphical view
 Allow wildcards in search expressions
 Hide folders to which user has no access
 Import and export Identification key schema
 Datapoint details
 Chart view improvements
 Manage files in master device manager
2015-03-30 2.0 AD Update for LWEB-900 Version 2.0.0
2015-04-11 2.1 AD Update for LWEB-900 Version 2.1.0
2017-06-03 2.2 AD Update for LWEB-900 Version 2.2.0