Vickers®
Amplifier Cards
Power Plugs for Proportional Valves
EHH-AMP-702-D/J/K; 2* Series
For use with valve types: Features and Benefits                                                         F Adjustable dither
KDG4V-3(S)-H*-6*                                                                                        F EMC to latest European standards
KTG4V-3(S)-H*-6*                                  F Integral amplifier provides essential               F Protection to IP67
KDG4V-5-H*-3*                                         functions for control of proportional
KTG4V-5-H*-3*                                         valves                                            Application
KCG-3/6/8-H1-1*                                   F   Adjustable ramp time (types D and K),
                                                      gain, deadband compensation and                   Primary applications are in the control of
KX(C)G-6/8-H1-1*                                                                                        directly operated, non-feedback
KDG5V-5/7/8-H1-1*                                     dither
                                                  F   Ease of installation, with reduced cost           proportional valves where the cost of
CMX***-E-G                                                                                              more sophisticated electronic controls
EPV**-12D-1*                                      F   Fully short-circuit and reverse-polarity
                                                      protected                                         can be avoided.
ERV1/2**-12D-1*
EPFR1**-12D-1*                                    F   Differential voltage command signal               Type J is for closed-loop applications.
                                                      (types D and J)
General Description
Three types of plugs, conforming to
ISO 4400/DIN 43650 interface, with
                                                  Electrical Block Diagram
integral amplifiers and necessary                 EHH-AMP-702-D/J/K-2*
adjustment potentiometers, are
                                                  Power input    1
designed for use with non-feedback                24V DC +                                    Dither                                       X1
hydraulic valves.
                                                        0V   –
                                                                 2                                        Max.               Power
This plug/valve combination offers very                                                       Gain        limiter    PWM     amp.
                                                                                                                                           Solenoid
low cost solutions to many hydraulic                             3                J                                                         X2
control problems requiring proportional                      +                  Ramp
control.                                          Command
                                                  signal                                     Deadband
Type D is controlled with a 0-10V                            –
command signal, and has adjustable                               4
gain, ramp, deadband compensation
and dither.                                       J Type J does not have the ramp function.
Type J, designed for closed-loop
applications, is controlled with a 0-10V
command signal, and has no ramp                   Model Code
function.                                         EHH-AMP-702- * - 2*
Type K is controlled with a 4-20 mA
command signal, and has an adjustable                                            1       2
ramp time of 50 ms to 5s.
                                                   1 Adjustment range                                    2 Design number, 20 series
                                                  D = Proportional plug: 50 ms to 5s                    Subject to change. Installation
                                                  J = Proportional plug without ramp                    dimensions unaltered for design
                                                      function                                          numbers 20 to 29 inclusive.
                                                  K = Proportional plug: 4-20 mA
              This product has been designed and tested to meet specific standards outlined in the European Electromagnetic Compatibility
              Directive (EMC) 89/336/EEC, amended by 91/263/EEC, 92/31/EEC and 93/68/EEC, article 5. For instructions on installation
              requirements to achieve effective protection levels, see this leaflet and the Installation Wiring Practices for Vickers Electronic
              Products leaflet 2468. Wiring practices relevant to this Directive are indicated by       Electromagnetic Compatibility (EMC).
August 1996                                                                                                                                GB-2115E
Operating Data
Electrical
                                           Types D and J                                Type K
Connections
 1                                         24V DC
 2                                         0V (power and signal)
 3                                         Positive command signal
 4                                         Negative command signal
Power (input) supply                       20-30V DC including "10% maximum ripple (peak-to-peak)
                                           24V DC nominal
Absolute maximum voltage                   40V
Max. power consumption incl. solenoid      35W
Reverse polarity protected                 Yes
Short circuit protected                    Yes
Maximum output current                     1,6A
Max. output voltage typical (1,6A output   Typically 1,5V below supply voltage
current)
Command signal                             0-10V (10 kohms)                             4-20 mA (250 ohms)
Deadband triggering                        200 mV                                       4 mA
For output (LED ON)                        200 mV to 10V                                4-20 mA
For no output (LED OFF)                    0 mV to 100 mV                               0-4 mA
Deadband adjustment range                  100 to 1000 mA
Gain adjustment range                      0.02 A/V to 0.16 A/V                         0.01 A/mA to 0.08 A/mA
Dither adjustment range                    0 to 500 mA
Ramp time (types D and K only)             50 ms to 5s
PWM frequency                              1200 Hz "10%
Dither frequency                           120 Hz "10%
Protection                                 IEC 529: IP67 (when correctly installed with interface seal in place)
                                           Fully short-circuit and reverse-polarity protected
Isolation to VDE 0110                      Group “B”
Electromagnetic compatibility (EMC):
 Emission                                  EN 50081-2
 Immunity                                  EN 50082-2
Mechanical
Housing                                    PA6 glass-reinforced plastic (conforming to UL-94HB). Color: gray
Mounting interface                         ISO 4400 (DIN 43650)
Cable clamp                                Pg9 screw type
Cable diameter                             Ø 5 to 10 mm (0.197 to 0.394I dia)
Wire section                               0,5 to 1,0 mm2 (20 AWG-17 AWG)
Temperature, ambient range                 –20_ to +70_C (–4_ to +158_F)
Mass                                       0,07 kg (0.154 lb)
                                                                2
Input/Output Characteristics
Types D and K                                                Type J
Command                                                      Command
signal                                                       signal
Type K Type D                                                voltage Us
20 mA      10V                                                         10V
            8V                                                          8V
12 mA       6V                                                          6V
            4V                                                          4V
            2V                                                          2V
4 mA                                                  Time                                                    Time
        Output                  Ramp                                 Output
        current                 setting                              current
                                US                                                      US
                                Gain setting                                            Gain setting
                          Deadband compensation                                Deadband compensation
                                                      Time                                                    Time
Installation Dimensions in mm (inches)                                                     3rd angle
                                                                                           projection
                                          88 (3.52)
                                                          22
                                                        (0.87)
                39
              (1.54)
                                                                                 Solenoid Connections
                            34 (1.34)
                                                                                                   No connection
                                                                                      1 (or 2)
                               2
                   38
                  (1.5)
                               1
                                                                                      2 (or 1)
                                                                 3
Installation Data
Adjustments                                      Ramp time:                                       Terminal 1:
                  Gain        Deadband
                                                 Turn clockwise to increase ramp time.            Power supply 20V-30V DC, positive.
               Ramp             Dither
                                                 (Only types D/K)
                                                                                                  Terminal 2:
                                                 Gain:                                            Power supply 0V.
                                                 Turn clockwise to increase gain.
                                                                                                  Terminal 3:
                                                 Deadband compensation:                           Command signal positive (see
                                                 Turn clockwise to increase deadband              “Operating Data”).
                                                 compensation current.
                                                                                                  Terminal 4:
      LED                                        Dither:                                          Command signal negative (see
                                                 Turn clockwise to increase the dither            “Operating Data”).
                                                 current.
                      4 3 2 1
Installation Wiring Options
Positive Command Voltage                                                   Bi-polar Command Voltage for Operating
                                                                           Two Solenoids from One Signal
 +10V                                   EHH-AMP-702-D/J-20                                                             EHH-AMP-702-D/J-20
                                                        4 3 2 1
                                                                                                                                           4 3 2 1
         24V                                                                               24V
          0V                                                                                0V
            0V                                                                              0V
                                                                               +10V
Negative Command Voltage
                                       EHH-AMP-702-D/J-20                                                               EHH-AMP-702-D/J-20
                                                                                                                                           4 3 2 1
                                                        4 3 2 1
 –10V    24V                                                                   –10V        24V
          0V                                                                                0V
          0V                                                                                0V
4-20 mA Command Signal                                                     Connections when replacing –10 design power plug
                                         EHH-AMP-702-K-20                  with –20 design and only 3 wires exist
                                                                                                                     EHH-AMP-702-D/J/K-20
                                                        4 3 2 1
         24V
          0V
                                                                                                                                           4 3 2 1
                                                                                           24V
     4-20 mA                                                                                0V
          0V                                                                                0V
                                                                                                                           Link pin 2 to pin 4
   Customer’s protective ground connection.
            Warning: Electromagnetic Compatibility (EMC)
            Screened cables should be used and particular attention paid to the grounding of the screens as shown in the above diagrams.
                                                                       4
Installation Data
Assembly Showing Wiring Connection Points
                                                                                          Warning
                                                                             F Ensure cable clamp nut is adequately
                                                                                tightened to secure the cable.
                                                                             F Do not connect, or disconnect, the
                                                                                plug while power is on.
                                                                             F Do not mount, or dismount, the plug
                                                                                while power is on.
                                                          Wiring Preparation
                                                          4 0,5-1,0 mm2
                                                          (20 AWG-17 AWG)
                                                                            Ø5-10
                                                5 (0.2)                     (0.197-0.394 dia)
                                                              40 (1.6)
 J All seals must be fitted correctly at plug
   installation to provide protection to IP67
   (IEC 529).
                                                                    5
Start-Up Procedure                          Spare Parts
F Correctly wire the plug and, before       The only spare part available is the
  mounting it on the valve solenoid,        interface seal, part number 732100.
  apply 24V DC (20 to 30V limits) to the
  “power input” terminals.                  Ordering Procedure
F Check for correct plug function by        Order plug by full model code, and spare
  illumination/non-illumination of the      interface seals by part number 732100.
  LED. The LED should illuminate when
  the demand applied to the “signal
  input” terminal is between 200 mV and
  10V (or 4 mA and 20 mA) and should
  not be illuminated when the applied
  demand is less than 100 mV (4 mA). If
  there is a malfunction a new plug must
  be fitted.
F Switch off power supply and
  command/input signal and then install
  plug on solenoid. Ensure that all seals
  are fitted correctly and clamped as the
  retaining screw is tightened: this is
  essential in providing IP67 protection.
F Ensure that the hydraulic system will
  not cause any erratic movement of
  actuators, then:
  – Switch on power supply again.
  – Repeat LED/function check as in 2.
  An LED malfunction now indicates a
  short circuit at the load.
F Successful completion of these
  checks means that the plug and load
  are ready for use.