Foundation Report

This document contains the results of analyzing the pad/pile footings for columns C13 and C12 of a 1-storey semi-detached self-contained apartment building. The footings were designed with dimensions of 1200mm x 1200mm x 300mm and reinforced with 600 mm^2/m of steel in both directions. Various checks were performed to validate the design, including moment capacity, shear stress, and punching shear, and all checks were passed for both column footings.

Uploaded by

Okechukwu Nwaewo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
29 views2 pages

Foundation Report

This document contains the results of analyzing the pad/pile footings for columns C13 and C12 of a 1-storey semi-detached self-contained apartment building. The footings were designed with dimensions of 1200mm x 1200mm x 300mm and reinforced with 600 mm^2/m of steel in both directions. Various checks were performed to validate the design, including moment capacity, shear stress, and punching shear, and all checks were passed for both column footings.

Uploaded by

Okechukwu Nwaewo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Project: 1_STOREY_SEMI_DETACHED_SELF_CONTAIN_APARTMENT - BMH MEDICAL SCHOOL WT (*14Y-ZWPG-ZZ6N-JZDA)

PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-1

PAD/PILE FOOTING RESULTS

F13
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C13 1 -165.6 0.3 -15.8 G+Q *F
2 -117.3 0.2 -11.2 G+Q
3 -154.6 0.3 -15.0 (G+Q)P1 *F
4 -123.6 0.1 -11.3 (G+Q)P2 *F
5 -140.1 2.7 -13.4 G+Q+Nx
6 -141.3 -2.3 -13.4 G+Q-Nx
7 -139.4 0.2 -10.7 G+Q+Ny
8 -142.1 0.2 -16.1 G+Q-Ny
Column: 1C13
bx = 225.0 mm by = 225.0 mm
Effects:
N = -117.3 kN Mx = 0.2 kN.m
My = -11.2 kN.m
Footing Dimensions:
Lx = 1200.0 mm Ly = 1200.0 mm
h = 300.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 140.736 kN/m2 S-min = 61.570 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
168.000 kN/m2
As-min (Both Dir's) = 600.00 mm2/m
X Dir: Footing Design: M = 16.7 kN.m/m
K/K' = 0.06 < 1.0
As = 600.00 mm2/m Y12-175
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.27 N/mm2 < v-max = 4.38 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.13 N/mm2 < vc = 0.48 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 140.5 kN V-eff = 157.9 kN
v = 0.71 N/mm2 < v-max = 4.38 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 50.7 kN V-eff = 51.0 kN
v = 0.05 N/mm2 < vc = 0.48 N/mm2
Y Dir: Footing Design: M = 15.5 kN.m/m
K/K' = 0.06 < 1.0
As = 600.00 mm2/m Y12-175
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.28 N/mm2 < v-max = 4.38 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.14 N/mm2 < vc = 0.49 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 140.5 kN V-eff = 157.9 kN
v = 0.71 N/mm2 < v-max = 4.38 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 50.7 kN V-eff = 68.0 kN
v = 0.07 N/mm2 < vc = 0.49 N/mm2

F12
--------------------------------------------------------------------------------
Columns/Loadings:
Column Cmb N Mx My
1C12 1 -166.3 -0.3 -15.9 G+Q *F
2 -117.7 -0.2 -11.2 G+Q
3 -155.1 -0.4 -15.1 (G+Q)P1 *F
4 -123.9 -0.1 -11.3 (G+Q)P2 *F
5 -141.9 2.3 -13.5 G+Q+Nx
6 -140.7 -2.8 -13.5 G+Q-Nx
7 -139.9 -0.2 -10.7 G+Q+Ny
8 -142.7 -0.3 -16.2 G+Q-Ny
Column: 1C12
bx = 225.0 mm by = 225.0 mm
Effects:
N = -117.7 kN Mx = -0.2 kN.m
My = -11.2 kN.m
Footing Dimensions:
Lx = 1200.0 mm Ly = 1200.0 mm
h = 300.0 mm h-Tap = 0.0 mm
Soil Stresses:
S-max = 141.014 kN/m2 S-min = 61.847 kN/m2
Allowable Soil Stress will be amplified by the factor (x1.4) =
168.000 kN/m2

Project: 1_STOREY_SEMI_DETACHED_SELF_CONTAIN_APARTMENT
Project: 1_STOREY_SEMI_DETACHED_SELF_CONTAIN_APARTMENT - BMH MEDICAL SCHOOL WT (*14Y-ZWPG-ZZ6N-JZDA)
PAD/PILE FOOTING RESULTS Orion Building Design System 18.0 (04.2012) / Page: FTG-2

As-min (Both Dir's) = 600.00 mm2/m


X Dir: Footing Design: M = 16.7 kN.m/m
K/K' = 0.06 < 1.0
As = 600.00 mm2/m Y12-175
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.27 N/mm2 < v-max = 4.38 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.13 N/mm2 < vc = 0.48 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 140.9 kN V-eff = 158.3 kN
v = 0.71 N/mm2 < v-max = 4.38 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 50.8 kN V-eff = 51.1 kN
v = 0.05 N/mm2 < vc = 0.48 N/mm2
Y Dir: Footing Design: M = 15.5 kN.m/m
K/K' = 0.06 < 1.0
As = 600.00 mm2/m Y12-175
Shear Check (At Column Face): (BS8110-Cl.3.4.5.2)
v = 0.28 N/mm2 < v-max = 4.38 N/mm2
Shear Check (At 'd' from Column): (BS8110-Cl.3.4.5.2)
v = 0.14 N/mm2 < vc = 0.49 N/mm2
Punching Check (At Column Face): (BS8110-Cl.3.7.6.4)
Vt = 140.9 kN V-eff = 158.3 kN
v = 0.71 N/mm2 < v-max = 4.38 N/mm2
Punching Check (At '1.5d'): (BS8110-Cl.3.7.6.4)
Vt = 50.8 kN V-eff = 68.2 kN
v = 0.07 N/mm2 < vc = 0.49 N/mm2

Project: 1_STOREY_SEMI_DETACHED_SELF_CONTAIN_APARTMENT