Voltronic Inverter Connection Manual

1. The document provides instructions for upgrading the firmware of a Voltronic inverter to version V16.04.06_PN01_220924_9600 and setting the communication protocol and baud rate. 2. It describes how to set the LIb pattern for 485 communication with a BMS using address switches on the inverter. Addresses can be set from 1000 0000 to 1111 1111 for up to 15 inverters in parallel. 3. The pin definitions for the 485 communication port and guidelines for connecting multiple inverters in parallel are also summarized.

Uploaded by

hi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views4 pages

Voltronic Inverter Connection Manual

1. The document provides instructions for upgrading the firmware of a Voltronic inverter to version V16.04.06_PN01_220924_9600 and setting the communication protocol and baud rate. 2. It describes how to set the LIb pattern for 485 communication with a BMS using address switches on the inverter. Addresses can be set from 1000 0000 to 1111 1111 for up to 15 inverters in parallel. 3. The pin definitions for the 485 communication port and guidelines for connecting multiple inverters in parallel are also summarized.

Uploaded by

hi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Voltronic Inverter

1、V16 Board upgrade program (note the latest board on V16) as follows:

CAN1101[V16.04.06_PN01_220924_9600].ehex

Use the host upgrade program (refer to the host upgrade method, upgrade the port rate
19200, after upgrading the moon program, connect the upper machine to use 9600 wave
rate)
Inverter Settings

1) push Enter the setting——choose 05(LIb)——The LIb pattern uses the

protocol name is:Voltronic Inverter and BMS 485 communication protocol 20180911

2) push Enter the Setup interface

3) press to 05,then press to setting,then press choose LIb,press to


confirm。
4、The pins of the conventional inverters are defined as follows:

BMS Communication port definition:

Connecting communication wire pin Note: inverter end pin 3 to BMS end 1 or 8; inverter
pin 5 to BMS end 2 or 7

5、Connect the inverter

Single-machine use of the address settings:1000 0000


Connect the inverter via the RS485
Address setting: the definition of dial switch refers to the following
table
If 2 parallel machine: the first dial 1000 0000 the second dial 0100 0000
through RS485 connection inverter
3 parallel machine: the first dial 1000 0000 the second dial 0100 0000
the third dial 1100 0000 through RS485 inverter

Set up from the machine(1)


地址 拨码开关位置 说明
 #1 #2 #3 #4 #5 #6 #7 #8
1 ON OFF OFF OFF 预留 预留 预留 预留 Pack1
2 OFF ON OFF OFF 预留 预留 预留 预留 Pack2
3 ON ON OFF OFF 预留 预留 预留 预留 Pack3
4 OFF OFF ON OFF 预留 预留 预留 预留 Pack4
5 ON OFF ON OFF 预留 预留 预留 预留 Pack5
6 OFF ON ON OFF 预留 预留 预留 预留 Pack6
7 ON ON ON OFF 预留 预留 预留 预留 Pack7
8 OFF OFF OFF ON 预留 预留 预留 预留 Pack8
9 ON OFF OFF ON 预留 预留 预留 预留 Pack9
10 OFF ON OFF ON 预留 预留 预留 预留 Pack10
11 ON ON OFF ON 预留 预留 预留 预留 Pack11
12 OFF OFF ON ON 预留 预留 预留 预留 Pack12
13 ON OFF ON ON 预留 预留 预留 预留 Pack13
14 OFF ON ON ON 预留 预留 预留 预留 Pack14
15 ON ON ON ON 预留 预留 预留 预留 Pack15

6、Connecting mode: connect the inverter through RS485 connection (the address starts
from PACK 1)
The example of the parallel connection is as follows:
7、 Notice:
When connecting to the inverter, do not use the upper computer for communication, which
will cause interference