ID-TUN-NG-SME-010301 Rev C - FINAL - Approved PJT
ID-TUN-NG-SME-010301 Rev C - FINAL - Approved PJT
ID-TUN-NG-SME-010301
COMMISSIONING – OPERATIONAL TEST PROCEDURE
SAFETY AND FIRE & GAS SYSTEM Revision : C Doc. Class : 1
TABLE OF CONTENTS
3. TEST REQUIREMENT 8
3.1. PRECOMMISSIONING STATUS 8
3.2. COMMISSIONING STATUS 8
3.3. STATUS OF OTHER SUBSYSTEM 9
3.4. SPECIAL TOOLS AND TEST EQUIPMENT 10
3.5. CONSUMABLE 10
3.6. COMMISSIONING SPARE PART 10
3.7. SAFETY 10
4. TEST PREPARATION 11
4.1. JUMPERS LIST 11
4.2. PROCESS 11
4.3. MECHANICAL 11
4.4. ELECTRICAL 11
4.5. INSTRUMENT 11
5. TEST PROCEDURE 11
5.1. OPERATIONAL TEST REPORT FORM 11
5.2. STEP BY STEP DEMONSTRATION TESTS 11
5.3. MAINTENANCE INHIBITS 12
5.4. START-UP INHIBITION 12
5.5. ESD LEVEL DEMONSTRATION 12
5.6. HIPS 13
5.7. AUTO-RESET 13
5.8. INTERLOCK 13
• All hardware and software which are inhibited during the test will be noted in the " OTP
hardware/software list of inhibit" attached to this OTP.
1.3. PROCESS SIMULATION
As far as feasible the installation shall be in real operating conditions: pumps running, ESDV
open, BDV closed, systems energized
All the instruments will be simulated from field using pressure test equipment, level using water,
temperature simulated with temperature calibrator .
The valves will be operated minimum one time during the test.
Actuation of CH4 gas detectors will be done using 50% LEL gas sample.
When voting, only 2 out of 3 detectors selected at random will be used to initiate the shut down.
Actuation of heat detectors will be done using the RE6T testing unit and smoke detectors with
RE6 testing unit.
Actuation of fire detectors will be done using G.M UV/IR test lamp.
FLARE/DRAIN/CORROS.INHIB.
SD 3.40.4A/SD 3.40.4B/SD 3.40.4A & B
FW CASE
SD 3.40.4A/SD 3.40.4B/SD 3.40.4A & B
AFTCOOLER TRAIN A
SD 3.40.1A.2A/SD 3.40.1A.2B/SD 3.40.1A
LP SCRUBBER TRAIN A
SD 3.40.2A.1/SD 3.40.2A
AFTCOOLER TRAIN B
SD 3.40.1B.2A/SD 3.40.1B.2B/SD 3.40.1B
LP SCRUBBER TRAIN B
SD 3.40.2B.1/SD 3.40.2B
NCP2
SD 2/ ESD 1.5 / ESD1.4 / ESD1.3/ ESD 1.2/
ESD 1.0/ESD1.1/ESD1.1.1/ESD1.1.2
NMP3
HIPS LOGIC
INLET MANIFOLD
SD 3.10 /SD 3.11/ SD 3.12/SD 3.13/ SD 3.14 /SD 3.15/SD 3.16/SD 3.17
HPU
SD 3.18
SLUG CATCHER
SD 3.20 /SD 3.21 / SD 3.22
NMP3
SD 2
ESD 1.3/ESD 1.4/ESD 1.5/ ESD 1.6/ESD 1.7/ESD 1.8/ ESD 1.9 /ESD 1.10/ ESD 1.11/ ESD
1.12/ESD 1.13 ESD 1.2/ ESD 1.1/ ESD 1
NCP2
ESD 1.1.0/F&G BATTERY ROOM
TECHNICAL BUILDING FIRE DETECTION
PROCESS & UTILITIES FIRE DETECTED
PROCESS & UTILITY GAS DETECTED
TRAIN A&B GAS DETECTION
TRAIN A&B FIRE DETECTION
EDG GAS & FIRE DETECTION
NCP2 TECHNICAL BUILDING GAS DETEC.
NMP3
PLTF FIRE DETECTED
PLTF GAS DETECTED
EXISTING
NPU ESD1.2/ESD1.4/ESD2.11/ESD2.13/ESD2/1.0A
NCP ESD3.7.4B/ESD3.7.2B/3.8.2B/ ESD2B/ESD 1.2B/ESD1.3B
NCP/OWT ESD1.0B/1.0C/1.02B/ESD1.B/ESD1.C
OWT ESD 3.71.1C/ESD3.70.1C/ESD2C
NCP FW CASE
• For the existing location all the logic modifications will be checked as per the attached
test sheets until marshalling cabinet or peer to peer communication system during the
October 2008 shutdown.
(refer to document COMMISSIONING & OPERATIONAL TEST PROCEDURE
NPU/OWT/NCP ICSS MODIFICATION)
PERSONNEL MANHOURS
PJC/CMS Instrument SPDT 5 days 50 h
One PJC/CMS Electrical Technician 5 days 50 h
3 PJC/CMS Instrument Technicians 5 days 150 h
One NPU Safety Rep. 5 days 50 h
One NPU Electrical Technician 5 days 50 h
One NPU Instrument Technician 5 days 50 h
One Production Operator at N.C.R 5 days 50 h
One Production Operator on Field 5 days 50 h
One NPU CS Technician 5 days 50 h
TOTAL MANHOUR 550 h
Instrument PJC/CMS:
• To conduct the OTP
• To coordinate with operator people prior to and during the OTP
Instrument MNT/INS:
• To witness and perform complementary test on the existing
installation.
• To troubleshoot / repair the existing installation.
Electrical MNT/ELEC:
• To witness
Panel Operator:
• To monitor and send remote commands from NCR.
3. TEST REQUIREMENT
• Verify that the Commissioning Dossier is completed (except section related with OTP).
• OTP is approved by Commissioning Team and Field Operation.
NMP3 PLTF
• 10301 ESD and F&G
• 10503 Emergency Lighting & small power
• 10702/703 Instrument air & distribution
• 10704/705 Hydraulic power unit and distribution
• 10801 Telephone
• 10802 Public address / General alarm
• 16201 Normal Lighting & small power
NCP2 PLTF
• 20202 Technical building protection INERGEN
• 20301 ESD and F&G
• 20302
• 20401 PCS
• 20501 Emergency diesel generator.
• 20502 Emergency power distribution
• 20503 Emergency Lighting & small power
• 20601 230vac UPS Power supply & distribution.
• 20603 48vdc UPS Power supply & distribution.
• 20701/702 Air compressor & distribution.
• 20801 Telephone
• 20802 Public address / General alarm
• 20901 HVAC.
• 26102 Normal power distribution
• 26201 Normal Lighting & small power
OFFSITE
• 30101 ESD and F&G
• 30503 Emergency Lighting & small power
• 30702/703 Instrument air & distribution
• 30802 Public address / General alarm
• 36201 Normal Lighting & small power
EXISTING PLANT
• 40301 Modification for new PSDV
• 40302 Modification for new ESDV and BDV.
• 40301 Modification for new safety link.
• 40304 Removal of ESD 0 and others software modifications.
• 40601 Electrical supply to new ICSS/Telecom equipment in NCR
• 40802 Public address / General alarm
3.5. CONSUMABLE
• Not required.
3.6. COMMISSIONING SPARE PART
• Not required.
3.7. SAFETY
4. TEST PREPARATION
5. TEST PROCEDURE
• Make sure that ESD level “n-1” is not activated and is reset on
the ESD display
• Make sure that all level “n” inputs are in normal condition: tag
steady green
• Check on ESD display that the corresponding ESD lines
(horizontal and vertical) are steady green
• In all concern cases, activate the start-up inhibit when the point
is in alarm
• Check if that were able to reset the ESD level.
• Wait for automatic deactivation after time-out fixed by operator
• Check if ESD level trip
• Initiate again Start-up Inhibit and simulate normal status on the
point.
• Reset ESD level
• Check Start-up Inhibit automatic deactivation
• Check if ESD level still normal
IMPORTANT:
ALL CAUSES OF THE SAME ESD LEVEL HAVE TO BE
TESTED SYSTEMATICALLY BUT WITHOUT RESETTING
ALL EQUIPMENT WHICH WAS ALREADY OPERATED BY A
PREVIOUS TEST.
5.6. HIPS
For the ESDV and PSDV connected to the HIPS the test will be
perform at the same time from the HIPS and safety shutdown
system. The interlock will be tested as per P&ID and ESD logic
notes.
5.7. AUTO-RESET
Will be tested as per ESD logic diagram.
5.8. INTERLOCK
Will be tested as per P&ID indication.
7. REFERENCE DOCUMENTS
• ID-TUN-NM-SME-159402 /403/404/405/406
NCP2 GENERAL SHUTDOWN ESD LOGIC DIAGRAM
• ID-TUN-NM-SME-159302/303/305
NCP/NMP2/NPU/NMP/OWT ESD LOGIC DIAGRAM
• ID-TUN-NM-SME-159501 to 159513
NORTH MANIFOLD PLT NMP3 P&ID
• ID-TUN-NM-SME-119401 to 119422
NMP3 SAFE CHART
• ID-TUN-NC-SME-159013
NORTH COMPRESSION PLTF NCP2 P&ID
• ID-TUN-NM-SME-129301 to 129333
NCP2 & NMP3 FIRE & GAS CAUSES AND EFFECTS MATRIX
• ID-TUN-NG-SME-289204
NCP2 SAFE CHART
• ID-TUN-NC-SME-159011
EXISTING INSTALLATION AND TIE IN
• ID-TUN-NO-MEI-129501 to 129521 and 129531
NCP2 F&G DETECTOR AND ESD PB LAYOUT
• ID-TUN-NC-SME-289061
NORTH COMPRESSION NCP2 TSLD
• ID-TUN-NC-SME-709009
NORTH OFFSITES EPSC13 TSLD
• ID-TUN-NO-MEI-709012
• OT ACCEPTANCE CERTIFICATE
To be completed after successful test
APPENDIX 1
HARD WARE :
INERGEN SYSTEM :
Actuator and booster dismantled from main and reserve rack.
DELUGE SYSTEM :
Deluge valve 12-XV-011100/200 AND 12-XV-012100/200 to be isolated up
stream and by pass line closed if water supply connected to the existing
installation.
SOFTWARE:
APPENDIX 2
TAG N° FUNCTION ESD LEVEL DESIGN TIME DELAY MEASURED TRAVEL TIME COMMENTS
12‐PSDV‐111101 SLUG CATCHER GAS MANIF. TO NCP2 PSDV SD 3.20 <= 30 SEC
12‐PSDV‐101009 LP INLET FROM GTS Y PSDV SD 3.11/ HIPS <= 6 SEC
12‐PSDV‐101015 LP INLET FROM GTS L, LX, I, IX PSDV SD 3.12/ HIPS <= 16 SEC
12‐PSDV‐101021 LP INLET FROM GTS K, KX PSDV SD 3.13/ HIPS <= 6 SEC
12‐PSDV‐101027 LP INLET FROM GTS M PSDV SD 3.14/ HIPS <= 6 SEC
12‐PSDV‐101033 LP INLET FROM GTS P&K PSDV SD 3.15/ HIPS <= 6 SEC
12‐PSDV‐101039 LP INLET FROM GTS J, I & L PSDV SD 3.16/ HIPS <= 16 SEC
12‐PSDV‐101045 LP INLET FROM GTS N, M & Q PSDV SD 3.17/ HIPS <= 6 SEC
12‐ESDV‐101005 LP INLET FROM GTS Y ESDV ESD 1.4/ HIPS <= 6 SEC
12‐ESDV‐101007 LP INLET FROM GTS L, LX, I, IX ESDV ESD 1.5/ HIPS <= 16 SEC
12‐ESDV‐101011 LP INLET FROM GTS K, KX ESDV ESD 1.6/ HIPS <= 6 SEC
12‐ESDV‐101013 LP INLET FROM GTS M ESD 1.7/ HIPS <= 6 SEC
12‐ESDV‐101017 LP INLET FROM GTS P&K ESDV ESD 1.8/ HIPS <= 6 SEC
12‐ESDV‐101019 LP INLET FROM GTS J, I & L ESDV ESD 1.9/ HIPS <= 16 SEC
12‐ESDV‐101023 LP INLET FROM GTS N, M & Q ESDV ESD 1.10/ HIPS <= 6 SEC
12‐ESDV‐312100 NMP3 GAS MANIFOLD TO LP COMP INLET MANIF. ESD 1.3 <= 30SEC
12‐ESDV‐312200 LP COMP AFTER COOL. TO MNP2 MP MANIF. ESD 1.5 <= 24 SEC
APPENDIX 3
SUMMARY
SUMMARY
MATRIX FORM
1 NCP2 FUEL GAS
2 NCP2 FLARE DRAIN C0RROS.INHIB.
3 NCP2 FCW CASE
4 NCP2 INLET COOLER TRAIN A
5 NCP2 AFT COOLER TRAIN A
6 NCP2 LP SCRUBBER TRAIN A
7 TRAIN A TRIP W.O BLOWDOWN (1)
8 TRAIN A TRIP W.O BLOWDOWN (2)
9 TRAIN A TRIP WITH BLOWDOWN
10 NCP2 INLET COOLER TRAIN B
11 NCP2 AFT COOLER TRAIN B
PAGE
12 NCP2 LP SCRUBBER TRAIN B
13 TRAIN B TRIP W.O BLOWDOWN (1)
14 TRAIN B TRIP W.O BLOWDOWN (2)
15 TRAIN B TRIP WITH BLOWDOWN
16 NCP2 SD 2
17 NCP2 ESD 1.5_1.4_1.3
18 NCP2 ESD 1.2
19 NCP2 ESD 1.1_1.1.1_1.0_1.1.2
20 HIPS LOGIC
21 HIPS LOGIC (2)
22 MNP3 DRAINS SD 3
23 NMP3 INLET MANIFOLD SD 3
24 NMP3 INLET MANIFOLD & HPU SD 3
25 NMP3 SLUG CATCHER SD 3
26 NMP3 SD 2
27 NMP3 SD 2 (2)
28 NMP3 ESD 1.3 to 1.8
29 NMP3 ESD 1.9 to 1.13
30 NMP3 ESD 1.2 FIRE DETECTED
31 NMP3 ESD 1.2 FIRE DETECTED (2)
32 NMP3 ESD 1.1 GAS DETECTED
33 F&G NCP2 BATTERY ROOM
34 NCP2 TEC.BUIDING FIRE DETEC.(1)
35 NCP2 TEC.BUIDING FIRE DETEC (2)
36 NCP2 PROCESS FIRE DETECTION
37 NCP2 PROC.& UTIL. FIRE DETECTION
38 NCP2 PROC.UTIL. GAS DETECTION
39 NCP2 TURBCOMP A GAS DETECTION
40 NCP2 TURBCOMP B GAS DETECTION
41 NCP2 TURBCOMP FIRE DETECTION
42 NMP3 PROCESS FIRE DETECTION (1)
43 NMP3 PROCESS FIRE DETECTION (2)
PAGE
44 NMP3 PROCESS AREA GAS DETECTION
45 NCP2 TEC.BUIDING GAS DETECTION
46 NPU ESD 1.2-1.4-2.11-2.13
47 NPU ESD 2
48 NPU ESD 2 (2)
49 NPU ESD 1.2-1.4-2.11-2.13
50 NPU ESD 1.0.X & 1.1X
51 NPU ESD 1.1
52 NPU ESD 1
53 NPU ESD 1.0A
54 NCP SD 3.7.4B & 3.7.2B & 3.8.2B
55 NCP FCW CASE 4_5_6 & ESD 2.1B
56 NCP ESD 2B
57 NCP ESD 1.6B & 1.7B
58 NCP_ESD 1.2B & 1.3B
59 OWT ESD 2C & 3.70.1C & 3.71.1C
60 NCP_OWT ESD 1.B & 1.C & 1.X.C
61 NCP_OWT ESD 1.0B & 1.0C & 1.02B
OPERATIONAL TEST SHEET TUNU 11N
SUBSYSTEM 10301/20301/30301/40303 EPSC 11, 12 & 14
MATRIX NCP2 & NMP3
ESD
C O S T X
VALVE TAG
TRAVEL TIME
SD 3.51/3.52/3.53/3.54
HP FG SCRUB.LIQU/OUT
FG to NCP2 PURGE
12-PSDV-7021A00
12-PSDV-7021B00
12-PSDV-702105
12-PSDV-702103
TRAIN A INLET
TRAIN B INLET
12-US-7021A01
12-US-7021B01
Alarm in NCR
12-HE-7021A
12-HE-7021B
DCS
TAG NUMBER SETTING
C X
NCP2 SD2 VALVE TAG 12-PSDV-702105
SD 3.54
FUEL GAS TO NCP2 C X TIME BEFORE
12-PAHH-702116 MOVING
X C
NCP2 SD2 TRAVEL TIME
SD 3.51
VALVE TAG 12-PSDV-702103 See note: 3
X S C TIME BEFORE
NCP2 SD2 MOVING
FG HEATER TRAIN A X S C
TRAVEL TIME
12-TAHH-7021A06
SD 3.52
FG HEATER TRAIN A X S C
VALVE TAG 12-PSDV-7021A00
12-LAHH-7021A13
FG HEATER TRAIN A X S C TIME BEFORE
MOVING
See note: 2
12-FALL-7021A00B
X S C
NCP2 SD2 TRAVEL TIME
FG HEATER TRAIN B X S C
VALVE TAG 12-PSDV-7021B00
SD 3.53 12-TAHH-7021B06
FG HEATER TRAIN B X S C TIME BEFORE
12-LAHH-7021B13 MOVING
FG HEATER TRAIN B X S C
TRAVEL TIME See note: 2
12-FALL-7021B00B
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
2- Start up inhibit to be tested.
3- Auto reset PSDV 702103 to be tested.
SD 3.61/3.62/3.63
12PR7521B 12-US-7521B01
STOP OPEN DRAIN PUMP
CLOSE LIQUID OUTLET
PA2821A 12-US-2821A07
12PA2822 12-US-2821A07
PA2821B 12-US-2821B07
12-PSDV-282200
Alarm in NCR
DCS
TAG NUMBER SETTING
S S C X
NCP2 SD2 VALVE TAG 12-PSDV-282100 See note: 2
SD 3.61
CLOSED DRAIN DRUM S S C X TIME BEFORE
MOVING
See note: 2
12-LALL-282100
TRAVEL TIME See note: 3
X C S
NCP2 SD2 VALVE TAG 12-PSDV-282200 See note: 3
SD 3.62
NCP2 OPEN DRAIN X C S TIME BEFORE
12-LALL-282201 MOVING
TRAVEL TIME
X S S
NCP2 SD2
CORROSS.INHIBITOR X S S
SD 3.63
12-PAHH-752107
CORROS.INHIB.TANK X S S
12-LALL-752103
ALARM IN NCR
FCW CASE 1
FCW CASE 2
12-US-03225
12-US-03226
TAG NUMBER SETTING
I CPA.2 X X
SD 3.40.4A
12-US-3121A32
I CPB.2 X X
SD 3.40.4B
12-US-3121B32
X X
12-US-3121A32 & 12-
SD 3.40.4A & B
US-3121B32
ALARM IN NCR
12-US-3121A100
12-US-3121A200
12-US-3121A300
12-US-3121A400
12-US-3121A500
12-US-3121A600
TAG NUMBER SETTING
SD 3.40.1A S X
SD 3.40.1A.1A
12-VAHH-3121A100 S X
HH VIBRATION COOLER A1
SD 3.40.1A S X
SD 3.40.1A.1B
12-VAHH-3121A200 S X
HH VIBRATION COOLER A2
SD 3.40.1A S X
SD 3.40.1A.1C
12-VAHH-3121A300 S X
HH VIBRATION COOLER A3
SD 3.40.1A S X
SD 3.40.1A.1D
12-VAHH-3121A400 S X
HH VIBRATION COOLER A4
SD 3.40.1A S X
SD 3.40.1A.1E
12-VAHH-3121A500 S X
HH VIBRATION COOLER A5
SD 3.40.1A S X
SD 3.40.1A.1F
12-VAHH-3121A600 S X
HH VIBRATION COOLER A6
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
AFT/COOLER EA3122A2
AFT/COOLER EA3122A1
AFT/COOLER EA3122A2
ALARM IN NCR
12-US-3122A100
12-US-3122A200
SD 3.40.1A21
SD 3.40.1A22
SD 3.40.1A1
SD 3.40.1A2
SD 3.40.1A3
SD 3.40.1A4
SD 3.40.1A5
SD 3.40.1A6
OCS
TAG NUMBER SETTING
SD 3.40.1A S X
SD 3.40.1A.2A
12-VAHH-3122A100 S X
HH VIBRATION COOLER A1
SD 3.40.1A S X
SD 3.40.1A.2B
12-VAHH-3122A200 S X
HH VIBRATION COOLER A2
I CPA.2 X X X X X X X X X
SD 3.40.1A
12-US-3121A32
SD 3.40.2A.1/SD 3.40.2A
12-PSDV-3121A10
ALARM IN NCR
12-US-3121A10
12-US-3121A20
SD 3.40.2A.1
OCS
TAG NUMBER SETTING
SD 3.40.2A S S X
See note: 3
12-PALL-3121A13 S S X
SD 3.40.2A.1 See note: 3
DISCH/PRESS COND PUMPS
12-LALL-3121A13A S S X
See note: 3
LL LEVEL LP SCRUBBER
I CPA.2 X C X
SD 3.40.2A See note: 2
12-US-3121A32
TRAVEL TIME
I CPA.3/I CPA.2
LP COMP TURBINE
INL/COMP BYPASS
12-PSDV-3121A00
12-PSDV-3122A00
12-PSDV-3121A01
SD 3.40.1A/2A/4A
12-ESDV-702112
ALARM IN NCR
12-FV-3121A23
12-US-3121A32
I CPA.3
OCS
TAG NUMBER SETTING
I CPA.2 C X
VALVE TAG 12-PSDV-3121A00
TRIP W/O BLOWDOWN
I CPA.3
12-PDAHH-3121A00B C X TIME BEFORE
INL/COMP PSDV-3121A00 MOVING
12-PB-3121A35 X C C C X O X
TRAVEL TIME
TRIP W/O BLOWDOWN
I CPA.1 X C C C X O X
VALVE TAG 12-PSDV-3122A00
TRIP WITH BLOWDOWN
12-PAHH-3121A20B X C C C X O X TIME BEFORE
COMPR.INLET PRESS. MOVING
12-TAHH-3121A20B X C C C X O X
TRAVEL TIME
COMPR.INLET TEMP.
12-PALL-3121A23B X C C C X O X
VALVE TAG 12-PSDV-3121A01
I CPA.2 COMPR.INLET PRESS.
12-PAHH-3121A27B X C C C X O X TIME BEFORE
COMPR.OUTLET PRESS. MOVING
12-TAHH-3121A22B X C C C X O X
TRAVEL TIME
COMPR.OUTLET TEMP.
12-PALL-3121A28B X C C C X O X
VALVE TAG 12-FV-3121A23 VALVE TAG 12-ESDV-702112
COMPR.OUTLET PRESS.
12-US-3121A34 X C C C X O X TIME BEFORE TIME BEFORE
SD 3.41A MOVING MOVING
12-LAHH-3121A12B X C C C X O X
TRAVEL TIME TRAVEL TIME
LP SCRUBBER
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
LP COMP TURBINE
INL/COMP BYPASS
12-PSDV-3122A00
12-PSDV-3121A01
12-PSDV-3121A00
12-ESDV-702112
ALARM IN NCR
12-FV-3121A23
12-US-3121A32
12-US-3121A34
12-US-31207A
12-US-31207B
TO ICPA2
I CPA.3
ICPA.2
ICPB.2
OCS
TAG NUMBER SETTING
12-PAHH-TP386A X C C C X O X
FUEL GAS PACKAGE
12-TAHH-RT389A X C C C X O X
FUEL GAS PACKAGE
I CPA.2
12-US-31207A X C C C X O X
SD 3.42
COMPR. PRESS. TRIP X C C C X O X
See note: 3
SKID
NCP2 SD 2 C C C C X X
12-TAHH-3121A02 C C C C X X
OUT PRECOOLER TEMP
12-PAHH-702119 C C C C X X
FUEL GAS LINE
SD 3.41A
12-PB-3121A34 C C C C X X
NCR PUSH BUTTON
12-TAHH-3122A01 C C C C X X
AFT COOLER TEMP
12US-3121A39 C C C C X X
120 VDC CHARG.FAULT
12-PALL-312201 X X X
See note: 2
COMMON OUT COMP.
SD 3.42
12-PALL-742106 X X X
N2 GENERATION
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
2- Start up inhibit to be tested.
3-will be tested during compressor OTP
SD 3.40A/I CPA.1
ALARM IN NCR
12-US-3121A33
TO ICPA.1
I CPA.2
OCS
TAG NUMBER SETTING
12-PB-3121A33 X X
SD 3.40A
NCR TRIP PB
12-US-3121A33 X C OT X
See note: 3
NCR TRIP WITH BLOWDOWN
12-PB-3121A37 X C OT X
See note: 3
SKID
12-PB-3121A36 X C OT X
I CPA.1 See note: 3
HMI
12-PB-3121A38 X C OT X
See note: 3
SKID
COMP DEPRESS.TRIP X C OT X
See note: 2 & 3
SKID
VALVE TAG 12-ESDV-702108
TIME BEFORE
MOVING
TRAVEL TIME
TRAVEL TIME
4- 12-ESDV-702108 SEAL GAS TO COMPRESSOR start to close when suction pressure below 0.7 Barg COMMISSIONING AND ACCEPTANCE
PIT-3121A24 (COMP.LOGIC)
PJC / CMS AMT / NPU / MNT
ALARM IN NCR
12-US-3121B100
12-US-3121B200
12-US-3121B300
12-US-3121B400
12-US-3121B500
12-US-3121B600
TAG NUMBER SETTING
SD 3.40.1B S X
SD 3.40.1B.1A
12-VAHH-3121B100 S X
HH VIBRATION COOLER B1
SD 3.40.1B S X
SD 3.40.1B.1B
12-VAHH-3121B200 S X
HH VIBRATION COOLER B2
SD 3.40.1B S X
SD 3.40.1B.1C
12-VAHH-3121B300 S X
HH VIBRATION COOLER B3
SD 3.40.1B S X
SD 3.40.1B.1D
12-VAHH-3121B400 S X
HH VIBRATION COOLER B4
SD 3.40.1B S X
SD 3.40.1B.1E
12-VAHH-3121B500 S X
HH VIBRATION COOLER B5
SD 3.40.1B S X
SD 3.40.1B.1F
12-VAHH-3121B600 S X
HH VIBRATION COOLER B6
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
2- Maintenance inhibit to be tested.
AFT/COOLER EA3122B1
AFT/COOLER EA3122B2
AFT/COOLER EA3122B1
AFT/COOLER EA3122B2
INLET COOLER EA3121B1
ALARM IN NCR
12-US-3122B100
12-US-3122B200
SD 3.40.1B21
SD 3.40.1B22
SD 3.40.1B1
SD 3.40.1B2
SD 3.40.1B3
SD 3.40.1B4
SD 3.40.1B5
SD 3.40.1B6
OCS
TAG NUMBER SETTING
SD 3.40.1B S X
SD 3.40.1B.2A
12-VAHH-3122B100 S X
HH VIBRATION COOLER A1
SD 3.40.1B S X
SD 3.40.1B.2B
12-VAHH-3122B200 S X
HH VIBRATION COOLER A2
I CPB.2 X X X X X X X X X
SD 3.40.1B
12-US-3121B32
SD 3.40.2B.1/SD 3.40.2B
12-PSDV-3121B10
ALARM IN NCR
12-US-3121B10
12-US-3121B20
SD 3.40.2B.1
OCS
TAG NUMBER SETTING
SD 3.40.2B S S X
See note: 3
12-PALL-3121B13 S S X
SD 3.40.2B.1 See note: 3
DISCH/PRESS COND PUMPS
12-LALL-3121B13A S S X
See note: 3
LL LEVEL LP SCRUBBER
I CPB.2 X C X
SD 3.40.2B See note: 2
12-US-3121B32
TRAVEL TIME
I CPB.3/I CPB.2
LP COMP TURBINE
INL/COMP BYPASS
12-PSDV-3121B00
12-PSDV-3122B00
12-PSDV-3121B01
12-ESDV-702113
ALARM IN NCR
12-FV-3121B23
12-US-3121B32
I CPB.3
OCS
TAG NUMBER SETTING
I CPB.2 C X
VALVE TAG 12-PSDV-3121B00
TRIP W/O BLOWDOWN
I CPB.3
12-PDAHH-3121B00A C X TIME BEFORE
INL/COMP PSDV-3121B00 MOVING
12-PB-3121B35 X C C C X O X
TRAVEL TIME
TRIP W/O BLOWDOWN
I CPB.1 X C C C X O X
VALVE TAG 12-PSDV-3122B00
TRIP WITH BLOWDOWN
12-PAHH-3121B20B X C C C X O X TIME BEFORE
COMPR.INLET PRESS. MOVING
12-TAHH-3121B20B X C C C X O X
TRAVEL TIME
COMPR.INLET TEMP.
12-PALL-3121B23B X C C C X O X
VALVE TAG 12-PSDV-3121B01
I CPB.2 COMPR.INLET PRESS.
12-PAHH-3121B27B X C C C X O X TIME BEFORE
COMPR.OUTLET PRESS. MOVING
12-TAHH-3121B22B X C C C X O X
TRAVEL TIME
COMPR.OUTLET TEMP.
12-PALL-3121B28B X C C C X O X
VALVE TAG 12-FV-3121B23 VALVE TAG 12-ESDV-702112
COMPR.OUTLET PRESS.
12-US-3121B34 X C C C X O X TIME BEFORE TIME BEFORE
SD 3.41B MOVING MOVING
12-LAHH-3121B12B X C C C X O X
TRAVEL TIME TRAVEL TIME
LP SCRUBBER
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
3- Auto reset PSDV 3121B10 to be tested.
LP COMP TURBINE
INL/COMP BYPASS
12-PSDV-3122B00
12-PSDV-3121B01
12-PSDV-3121B00
12-ESDV-702113
ALARM IN NCR
12-FV-3121B23
12-US-3121B32
12-US-3121B34
12-US-31207A
12-US-31207B
TO ICPB2
I CPB.3
SD3.42
SD3.42
OCS
TAG NUMBER SETTING
12-PAHH-TP386B X C C C X O X
FUEL GAS PACKAGE
12-TAHH-RT389B X C C C X O X
FUEL GAS PACKAGE
I CPB.2
12-US-312107B X C C C X O X
SD 3.42
COMPR. PRESS. TRIP X C C C X O X
See note: 2
SKID
NCP2 SD 2 C C C C X X
12-TAHH-3121B02 C C C C X X
OUT PRECOOLER TEMP
12-PAHH-702120 C C C C X X
FUEL GAS LINE
SD 3.41B
12-PB-3121B34 C C C C X X
NCR PUSH BUTTON
12-TAHH-3122B01 C C C C X X
AFT COOLER TEMP
12-US-3121B39 C C C C X X
120 VDC CHARG.FAULT
SD 3.40B/I CPB.1
ALARM IN NCR
12-US-3121B33
TO I CPB.1
I CPB.2
OCS
TAG NUMBER SETTING
12-PB-3121B33 X X
SD 3.40B See note: 3
NCR TRIP PB
12-US-3121B33 X C OT X
See note: 3
NCR TRIP WITH BLOWDOWN
12-PB-3121B37 X C OT X
See note: 3
SKID
12-PB-3121B36 X C OT X
I CPB.1 See note: 3
HMI
12-PB-3121B38 X C OT X
See note: 3
SKID
COMP DEPRESS.TRIP X C OT X
See note: 2 & 3
SKID
VALVE TAG 12-ESDV-702108
TIME BEFORE
MOVING
TRAVEL TIME
TRAVEL TIME
4- 12-ESDV-702109 SEAL GAS TO COMPRESSOR start to close when suction pressure below 0.7 Barg COMMISSIONING AND ACCEPTANCE
PIT-3121B24 (COMP.LOGIC)
PJC / CMS AMT / NPU / MNT
SD 2
CORROSION INHIBITOR
TRIP W/O BLOWDOWN
INLET HP SCRUBBER
FUEL GAS PACKAGE
TRAIN B SD 3.41B
CLOSED DRAIN
ALARM IN NCR
12-PSDV-702102
OPEN DRAIN
FCW CASE 2
12-US-03226
SD 3.54
SD 3.51
SD 3.52
SD 3.53
SD 3.61
SD 3.62
SD 3.63
OCS
TAG NUMBER SETTING
ESD1.2 X X X X X X C X X X X X
NCP2
ESD1.3 X X X X X X C X X X X X
NCP2
NCR X X X X X X C X X X X X
12-PB-03002
12-US-03212 X X X X X X C X X X X X
NPU ESD 2
12-US-03227 X X X X X X C X X X X X
NCP ESD 2B
12-PALL-072200A/B/C X X X X X X C X X X X X
See note: 2
NCP2 SD 2 INST/AIR/RECEIVER
12-PAHH-702104 X X X X X X C X X X X X
HP F/G SCRUBBER
12-LAHH-702103 X X X X X X C X X X X X
HP F/G SCRUBBER
12-PALL-702104 X X X X X X C X X X X X
HP F/G SCRUBBER
VALVE TAG 12-PSDV-702102
TIME BEFORE
MOVING
TRAVEL TIME
12-ESDV-702100
12-ESDV-312100
12-ESDV-102000
ALARM IN NCR
NCP2 SD 2
NCP2
OCS
TAG NUMBER SETTING
ESD 1.2 C X
NCP2 NCP2
ESD 1.5 NCP ESD 1.2B C X
12-US-03216
ESD 1.2 C X
See note: 2
NCP2 NCP2
ESD 1.4 NPU ESD 1.2 C X
12-US-03215
ESD 1.2 X C C X
NCP2 NMP3
ESD 1.3 ESD 1.2 X C C X
NCP2
VALVE TAG 12-ESDV-312200
TRAVEL TIME
ESD 1.2
HYDRAU.PUMP 12-DG0521
OUTLET COMPRESSION
AIR COMP UA-0921A/B
STOP N2 PRODUCTION
INLET COMPRESSION
OPEN 12-BDV-312101
OPEN 12-BDV-312202
OPEN 12-BDV-702116
12-US-0721A01/B01
12-US-0721A02/B02
12-US-0721A03/B03
12-US-7421A01/B01
12-BDV-3121A22
COMPRESSOR.A
12-BDV-3121B22
COMPRESSOR.B
12-ESDV-053200
12-ESDV-702108
12-ESDV-702109
HP F/G SYSTEM
ALARM IN NCR
FLARE STATUS
12-US-052100
12-US-052101
NPU ESD 1.4
12-US-03214
12-XA03201
ESD 1.5
ESD 1.4
ESD 1.3
ESD 1.2
NMP3
NCP2
NCP2
NCP2
NCP2
SD 2
OCS
TAG NUMBER SETTING
ESD 1.1 X X X X X S S S S S S X T T T C C T C T X
See note: 3
NCP2
NCR X X X X X S S S S S S X T T T C C T C T X
See note: 3 & 4
12-PB-03001
FIRE DETECTION X X X X X S S S S S S X T T T C C T C T X
See note: 2 7 3
NCP2
12-US-O3231 X X X X X S S S S S S X T T T C C T C T X X
See note: 3
LL VOLT UPS 230VAC
12-US-O3233 X X X X X S S S S S S X T T T C C T C T X X
See note: 3
LL VOLT UPS 48VDC
NCP2
ESD 1.2
VALVE TAG 12-ESDV-053200
TRAVEL TIME
ESD 1.0/ESD1.1/ESD1.1.1/ESD1.1.2
LV BREAK INCOM B
12-US-03294 A/B
12-US-03295 A/B
12-US-03260 A/B
12-US-03272 A/B
ALARM IN NCR
12-US-03270A
12-US-03270B
12-US-3271A
12-US-3271B
12-US-03250
12-US-03251
12-US-03252
12-US-03291
12-US-03296
12-US-03261
ESD 1.2
ESD 1.1
ESD 1.1
NMP3
NCP2
OCS
TAG NUMBER SETTING
ESD 1.0 X O O X X X
See note: 7
NCP2
12-PB-03003 X O O X X X
See note: 7 & 8
NCR
NCP2 12-PB-03200 X O O X X X
See note: 7 & 8
ESD 1.1 ACCES WAY
12-PB-03203 X O O X X X
See note: 7 & 8
ACCES WAY
NCP2 GAS DETECTED X O O X X X
See note: 5 & 7
PROCESS AREA
12-PB-03000 O O X X X X X T T X X
See note: 3, 7 & 8
NCR
NCP2 12-PB-03201 O O X X X X X T T X X
See note: 3, 7 & 8
ESD 1.0 TECHN. BUILDING
NCP2 GAS DETECTED O O X X X X X T T X X
See note: 3, 7
TEC.BUIL.1ST or 2ND FLOOR
12-US-3206 X X X
See note: 7
NCP2 FROM NCP ESD 1.0B
ESD 1.1.2
HIPS LOGIC
BY-PASS PSDV-101009
BY-PASS PSDV-101016
BY-PASS PSDV-101021
BY-PASS PSDV-101027
BY-PASS PSDV-101033
BY-PASS PSDV-101039
BY-PASS PSDV-101045
LP INLET GTS N/Q/M
LP INLET GTS K/KX
TO LP MANIFOLD
TO LP MANIFOLD
TO LP MANIFOLD
TO LP MANIFOLD
TO LP MANIFOLD
TO LP MANIFOLD
TO LP MANIFOLD
LP INLET GTS P/K
LP INLET GTS M
LP INLET GTS Y
12-ESDV-101001
12-ESDV-101005
12-ESDV-101007
12-ESDV-101011
12-ESDV-101013
12-ESDV-101017
12-ESDV-101019
12-ESDV-101023
ALARM IN NCR
12-PSDV-101003
12-PSDV-101004
12-PSDV-101009
12-PSDV-101010
12-PSDV-101015
12-PSDV-101016
12-PSDV-101021
12-PSDV-101022
12-PSDV-101027
12-PSDV-101028
12-PSDV-101033
12-PSDV-101034
12-PSDV-101039
12-PSDV-101040
12-PSDV-101045
12-PSDV-101046
OCS
TAG NUMBER SETTING
12-PAHH-101051A/B/C C C C C C C C C C C C C C C C C C C C C C C C C X
See note: 2
LP MANIFOLD PRESS.
PDAHH (DORMANT) X Y Z Voting 2OO3 applied
INTERLOCK TO BE TESTED
VALVE TAG 12-ESDV-101001 VALVE TAG 12-PSDV-101003 VALVE TAG 12-PSDV-101004
as per note 2 / 3 / 4 / 5
12-PDAHH-101005 TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING
12-PDAHH-101017 TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING
HIPS LOGIC
INTERLOCK TO BE TESTED
PDAHH (DORMANT) X Y Z as per note 2 / 3 / 4 / 5
VALVE TAG 12-ESDV-101011 VALVE TAG 12-PSDV-101021 VALVE TAG 12-PSDV-101022
12-PDAHH-101023 TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING
12-PDAHH-101035 TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING
HIPS LOGIC
INTERLOCK TO BE TESTED
PDAHH (DORMANT) X Y Z as per note 2 / 3 / 4 / 5
VALVE TAG 12-ESDV-101019 VALVE TAG 12-PSDV-101039 VALVE TAG 12-PSDV-101040
12-PDAHH-101041 TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING
SD PUMP 12-PA2811A
SD PUMP 12-PA3611B
SD PUMP 12-PA2811B
SD PUMP 12-PA2812
SD PUMP 12-PA8511
12-PSDV-361100
12-PSDV-281100
12-PSDV-281200
12-US-3611A07
12-US-2811A07
12-PSDV-36104
12-PSDV-36105
12-PSDV-85112
12-US-3611B07
12-US-2811B07
12-US-281207
12-US-851107
TAG NUMBER SETTING
SD 2 C S S
VALVE TAG 12-PSDV-361100 VALVE TAG 12-PSDV-281100 See note: 2 & 3
MNP3 SD NMP3
3.40
TIME BEFORE MOVING TIME BEFORE MOVING
SD 2 C S S
TRAVEL TIME TRAVEL TIME See note: 4
MNP3 SD NMP3
3.41 12-LALL-281100 C S S
VALVE TAG 12-PSDV-281200 See note: 4
CLOSED DRAIN DRUM
SD 2 C S
MNP3 SD
TIME BEFORE MOVING See note: 5
NMP3
3.42 12-LALL-281201 C S
TRAVEL TIME See note: 5
OPEN DRAIN DRUM
SD 2 C S
VALVE TAG 12-PSDV-36104
MNP3 SD NMP3
3.43 12-PAHH-361003 C S
TIME BEFORE MOVING
F/G SUPPLY T0 FLARE
SD 2 C S
TRAVEL TIME See note: 6
MNP3 SD NMP3
3.44 12-LALL-851102 C S
VALVE TAG 12-PSDV-85112 See note: 6
UTILITY WATER DRUM
TIME BEFORE MOVING
TRAVEL TIME
5- Interlock to be tested between 12-PSDV-281200 and pumps PJC / CMS AMT / NPU / MNT
TRUNKLINE GTS K
ALARM IN NCR
12-PSDV-101003
12-PSDV-101009
12-PSDV-101015
12-PSDV-101021
FCW CASE 3
12-US-03114
OCS
TAG NUMBER SETTING
SD 2 C X X
MNP3 SD MNP3
3.10 12-PAHH-101001A/B/C C X X
See note: 2
NMP2 PIGGING MANIF.
SD 2 C X X
MNP3 SD MNP3
3.11 12-PAHH-101007A/B/C C X X
See note: 2
TRUNKLINE GTS-Y
SD 2 C X X
MNP3 SD MNP3
3.12 12-PAHH-101013A/B/C C X X
See note: 2
TRUNKLINE GTS L/I
SD 2 C X X
MNP3 SD MNP3
3.13 12-PAHH-101019A/B/C C X X
See note: 2
TRUNKLINE GTS K
SD PUMP 12-PA0711A
TRUNKLINE GTS-P/K
SD PUMP 12-PA0711B
TRUNKLINE GTS-M
ALARM IN NCR
12-PSDV-101027
12-PSDV-101033
12-PSDV-101039
12-PSDV-101045
12-US-0711A07
12-US-0711B07
FCW CASE 3
12-US-03114
OCS
TAG NUMBER SETTING
SD 2 C X X
MNP3 SD MNP3
3.14 12-PAHH-101025A/B/C C X X
See note: 2
TRUNKLINE GTS-M
SD 2 C X X
MNP3 SD MNP3
3.15 12-PAHH-101031A/B/C C X X
See note: 2
TRUNKLINE GTS-P/K
SD 2 C X X
MNP3 SD MNP3
3.16 12-PAHH-101037A/B/C C X X
See note: 2
TRUNKLINE GTS J/I/L
SD 2 C X X
MNP3 SD MNP3
3.17 12-PAHH-101043A/B/C C X X
See note: 2
TRUNKLINE GTS N/Q/M
ESD 1.2 S S X
MNP3
12-PALL-071123 S S X
See note: 3
MNP3 SD HPU OUTLET
3.18 12-PAHH-071123 S S X
HPU OUTLET
12-LALL-0711B02 S S X
HPU SUPPLY RESERVOIR
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset, Trunk line arrival ESDV and PSDV interlock refer to HIPS matrix
discrepancy, override and stroking (if appropriate)
2- Voting 2OO3 applied
3- STARTUP INHIBIT to be tested
CONDENSATE OUTLET
SD PUMP 12-PA1211A
SD PUMP 12-PA1211B
SD PUMP 12-PA1211C
12-PSDV-1111A10
ALARM IN NCR
12-PSDV-111101
12-PSDV-121000
12-US-1211A07
12-US-1211B07
12-US-1211C07
OCS
TAG NUMBER SETTING
SD 2 C X
MNP3 SD MNP3
3.20 12-PDAHH-111101 C X
ACROSS PSDV-111101
SD 2 C X
See note: 3
MNP3
12-US-03124/03125 C X
See note: 3
MNP3 SD OWT SD 3.70.1C/3.71.1C
3.21
SD 2 S S S C X
See note: 4 & 5
MNP3
12-PALL-121103 S S S C X
See note: 4 & 5
COND.TRAN.PUMPS DISCH
12-US-03122/03123 S S S C X
See note: 2& 4 & 5
MNP3 SD NCP SD 3.7.2B/3.8.2B
3.22
5- Auto reset PSDV by 12-LALL-1111A01 AND 12-LALL-1111B01 to be tested. PJC / CMS AMT / NPU / MNT
SD 2
BY PASS PSDV-101009
BY PASS PSDV-101015
BY PASS PSDV-101021
BY PASS PSDV-101027
BY PASS PSDV-101033
BY PASS PSDV-101039
BY PASS PSDV-101045
BY PASS PSDV-111101
TRUNKLINE GTS-J/I/L
TRUNKLINE GTS-P/K
TRUNKLINE GTS-L/I
TRUNKLINE GTS-M
TRUNKLINE GTS-K
TRUNKLINE GTS-Y
ALARM IN NCR
12-PSDV-101004
12-PSDV-101010
12-PSDV-101016
12-PSDV-101022
12-PSDV-101028
12-PSDV-101034
12-PSDV-101040
12-PSDV-101046
12-PSDV-111102
12-PSDV-101025
NMP2 PIGGING
SD 3.10
SD 3.11
SD 3.12
SD 3.13
SD 3.14
SD 3.15
SD 3.16
SD 3.17
SD 3.20
SD 3.21
SD 3.22
SD 3.40
SD 3.41
SD 3.42
SD 3.43
SD 3.44
OCS
TAG NUMBER SETTING
ESD 1.2 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NMP3
12-PB-03101 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NCR
12-PALL-071102A/B/C X C X C X C X C X C X C X C X C X X X C C X X X X X X
See note: 2 & 3
INSTR AIR RECEIVER
ESD 1.3 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NMP3
ESD 1.4 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NMP3
ESD 1.5 X C X C X C X C X C X C X C X C X X X C C X X X X X X
MNP3 NMP3
SD 2 ESD 1.6 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NMP3
12-PAHH-101049A/B/C X C X C X C X C X C X C X C X C X X X C C X X X X X X
MANIFOLD TRUNK.ARRIVAL
See note: 2
ESD 1.7 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NMP3
ESD 1.8 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NMP3
ESD 1.9 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NMP3
ESD 1.10 X C X C X C X C X C X C X C X C X X X C C X X X X X X
NMP3
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset, Trunk line arrival ESDV and PSDV interlock refer to HIPS matrix
discrepancy, override and stroking (if appropriate)
2- Voting 2OO3 applied
3- Start up inhibit to be tested
SD 2
BY PASS PSDV-101009
BY PASS PSDV-101015
BY PASS PSDV-101021
BY PASS PSDV-101027
BY PASS PSDV-101033
BY PASS PSDV-101039
BY PASS PSDV-101045
BY PASS PSDV-111101
TRUNKLINE GTS-J/I/L
TRUNKLINE GTS-P/K
TRUNKLINE GTS-L/I
TRUNKLINE GTS-M
TRUNKLINE GTS-K
TRUNKLINE GTS-Y
ALARM IN NCR
12-PSDV-101004
12-PSDV-101010
12-PSDV-101016
12-PSDV-101022
12-PSDV-101028
12-PSDV-101034
12-PSDV-101040
12-PSDV-101046
12-PSDV-111102
12-PSDV-101025
NMP2 PIGGING
SD 3.10
SD 3.11
SD 3.12
SD 3.13
SD 3.14
SD 3.15
SD 3.16
SD 3.17
SD 3.20
SD 3.21
SD 3.22
SD 3.40
SD 3.41
SD 3.42
SD 3.43
SD 3.44
OCS
TAG NUMBER SETTING
12-PALL-111102 X C X C X C X C X C X C X C X C X X X C C X X X X X X
See note: 3
SLUG CATC DISCH MAN
12-LAHH-1111A00A/B/C X C X C X C X C X C X C X C X C X X X C C X X X X X X
See note: 2
SLUG CATCHERAB
12-LAHH-1111B00A/B/C X C X C X C X C X C X C X C X C X X X C C X X X X X X
See note: 2
SLUG CATCHER B
12-LAHH-361102A/B/C X C X C X C X C X C X C X C X C X X X C C X X X X X X
See note: 2
HP FLARE KO DRUM
MNP3
SD 2
TRUNKLINE GTS-P/K
TRUNKLINE GTS-M
TRUNKLINE GTS-Y
12-ESDV-101001
12-ESDV-101005
12-ESDV-101007
12-ESDV-101011
12-ESDV-101013
12-ESDV-101017
ALARM IN NCR
NMP3
NMP3
NMP3
NMP3
NMP3
NMP3
NMP3
SD 2
SD 2
SD 2
SD 2
SD 2
SD 2
SD 2
OCS
TAG NUMBER SETTING
ESD 1.2 X C X
MNP3 NMP3
ESD 1.3 12-PALL-101001A/B/C X C X
See note: 2 & 3
NMP2 PIGGING MANIF.
ESD 1.2 X C X
MNP3 NMP3
ESD 1.4 12-PALL-101007A/B/C X C X
See note: 2 & 3
TRUNKLINE GTS-Y
ESD 1.2 X C X
MNP3 NMP3
ESD 1.5 12-PALL-101013A/B/C X C X
See note: 2 & 3
TKLINE GTS L/I/LX/IX
ESD 1.2 X C X
MNP3 NMP3
ESD 1.6 12-PALL-101019A/B/C X C X
See note: 2 & 3
TRUNKLINE GTS K/KX
ESD 1.2 X C X
MNP3 NMP3
ESD 1.7 12-PALL-101025A/B/C X C X
See note: 2 & 3
TRUNKLINE GTS-M
ESD 1.2 X C X
MNP3 NMP3
ESD 1.8 12-PALL-101031A/B/C X C X
See note: 2 & 3
TRUNKLINE GTS-P/K
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset, Trunk line arrival ESDV and PSDV interlock refer to HIPS matrix
discrepancy, override and stroking (if appropriate)
2- Voting 2OO3 applied
3- START-UP INHIBIT to be tested.
12-ESDV-1111A00
12-ESDV-101019
12-ESDV-101023
12-ESDV-361003
12-ESDV-111000
NMP3
NMP3
SD 2
SD 2
TAG NUMBER SETTING
ESD 1.2 X C
MNP3 NMP3
ESD 1.9 12-PALL-101037A/B/C X C
See note: 2 & 3
TRUNKLINE GTS J/I/L
ESD 1.2 X C
MNP3 MNP3
ESD 1.10 12-PALL-101043A/B/C X C
See note: 2 & 3
TRUNKLINE GTS N/Q/M
ESD 1.2 C
MNP3 NMP3
ESD 1.11 12-US-03112 C
NPU ESD 1.2
ESD 1.2 C
MNP3 NMP3
ESD 1.12 12-US-03111 C
NCP ESD 1.3.B
ESD 1.2 C
MNP3 NMP3
ESD 1.13 12-US-03110 C
OWT ESD 1.C
ESD 1.2
TRUNKLINE GTS-P/K
TRUNKLINE GTS-M
TRUNKLINE GTS-M
TRUNKLINE GTS-Y
TRUNKLINE GTS Y
SLUG CATCHER A
SLUG CATCHER B
12-BDV-1111A09
12-BDV-1111B09
ALARM IN NCR
12-BDV-101002
12-BDV-101006
12-BDV-101008
12-BDV-101012
12-BDV-101014
12-BDV-101018
12-BDV-101020
12-BDV-101024
12-BDV-101000
12-BDV-111104
LP MANIFOLD
NMP3 HPU
ESD 1.10
ESD 1.11
ESD 1.12
ESD 1.13
ESD 1.3
ESD 1.4
ESD 1.5
ESD 1.6
ESD 1.7
ESD 1.8
ESD 1.9
ESD 1.3
SD 3.18
NMP3
NMP3
NMP3
NMP3
NCP2
SD 2
OCS
TAG NUMBER SETTING
12-PB-3006 X X X X X X X X X X X X X X OT OT OT OT OT OT OT OT OT OT OT OT X
See note: 2
NCR PB
FIRE DETECTED X X X X X X X X X X X X X X OT OT OT OT OT OT OT OT OT OT OT OT X
See note: 2 & 3
MNP3
ESD1.1 X X X X X X X X X X X X X X OT OT OT OT OT OT OT OT OT OT OT OT X
See note: 2
NMP3 GAS DETEC.
NCP2 12-US-03231 X X X X X X X X X X X X X X OT OT OT OT OT OT OT OT OT OT OT OT X
See note: 2
LL VOLT UPS 230VAC
NCP2 12-US-O3233 X X X X X X X X X X X X X X OT OT OT OT OT OT OT OT OT OT OT OT X
See note: 2
LL VOLT UPS 48VDC
NCP2 FRIRE DETEC X X X X X X X X X X X X X X OT OT OT OT OT OT OT OT OT OT OT OT X
See note: 2 &4
MNP3 TECHN BUILDING
ESD 1.2
ESD 1.2
SLUG CATCHER B
12-BDV-1111A09
12-BDV-1111B09
12-BDV-101000
12-BDV-111104
LP MANIFOLD
TAG NUMBER SETTING
VALVE TAG 12-BDV-101002 VALVE TAG 12-BDV-101006 VALVE TAG 12-BDV-101008 VALVE TAG 12-BDV-101012
TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING
VALVE TAG 12-BDV-101014 VALVE TAG 12-BDV-101018 VALVE TAG 12-BDV-101020 VALVE TAG 12-BDV-101024
TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING
MNP3
ESD 1.2
TRAVEL TIME TRAVEL TIME TRAVEL TIME TRAVEL TIME
VALVE TAG 12-BDV-101000 VALVE TAG 12-BDV-1111A09 VALVE TAG 12-BDV-1111B09 VALVE TAG 12-BDV-111104
TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING TIME BEFORE MOVING
ESD 1.1
ALARM IN NCR
12-US-01211A07
12-US-01211B07
12-US-01211C07
12-US-0711A07
12-US-2811A07
12-US-3611A07
12-US-0711B07
12-US-2811B07
12-US-3611B07
12-US-281207
12-US-03184
12-US-03185
12-US-03186
12-US-03193
ESD 1.2
NMP3
OCS
TAG NUMBER SETTING
MNP3
ESD 1.1
12-XL-222161C/D BAT/ROOM
12-XL-222161A/B SW/ROOM
LCP BATT.ROOM.INERG RELEASED
FIRE DAMP. 1ST BATT.ROOM
12-XL-222161E/F OUTDOOR
FIRE DAMP. 1ST FLOOR
12-US-03248 INHIBIT
12-US-03249 INHIBIT
12-SOV-22161A OR B
HVAC SHUTDOWN
PA/GA ALL AREA
ALARM IN NCR
12-XL-222162C
12-XL-222163C
12-XL-222164C
NCP2 ESD1.1.0
12-US-03204
12-US-03239
12-US-3243
12-US-3244
12-US-3245
12-US-3246
ESD 1.1.1
ESD 1.2
ESD 1.2
NMP3
NCP2
NCP2
OCS
TAG NUMBER SETTING
12-US-03239 X X X X
NCP2 BATTERY ROOM VENT FAIL
ESD 1.1.0
12-US-03240 HVAC X X X
FAILURE BATTERY ROOM
NCP2
12-US-03241 AIR SUPPLY X X X
BATTERY ROOM
DAMP.NOT FULLY OPEN.
VENT FAIL
12-GDAHH-03203A/B/C X X X
See note: 2
H2 DETECTED BATT ROOM
12-XAHH-03223 X X X X C C C X X X X X X X T X
NCP2 BATTERY See note: 3 & 4
SW/ROOM CEILING
ROOM SMOKE &
HEAT DETECT.
LCP EMERG.EXIT.INHIB.MODE
LCP MAIN ENTR.INERG RELEASED
INERG.SYSTEM INHIBITED
LCP BATT.ROOM.AUTO MODE
12-XL-222161E/F OUTDOOR
ALARM PA/GA ALL AREA
INERG.SYSTEM AUTO
INERGEN .RELEASED
12-SOV-22161A OR B
12-XL-222160D F&G
HVAC SHUTDOWN
ALARM IN NCR
12-XL-222162A
12-XL-222163A
12-XL-222164A
12-XL-222162B
12-XL-222163B
12-XL-222164B
12-XL-222162C
12-XL-222163C
12-XL-222164C
12-US-3204
12-US-3243
12-US-3244
12-US-3245
12-US-3246
ESD 1.1.1
ESD 1.2
ESD 1.2
NMP3
NCP2
NCP2
OCS
TAG NUMBER SETTING
LCP EMERG.EXIT.INHIB.MODE
LCP MAIN ENTR.INERG RELEASED
INERG.SYSTEM INHIBITED
ALARM PA/GA ALL AREA
INERG.SYSTEM AUTO
INERGEN .RELEASED
12-SOV-222261A OR B
12-XA-222261A/B ITR
12-XL-222260D F&G
HVAC SHUTDOWN
ALARM IN NCR
12-XL-222262A
12-XL-222263A
12-XL-222262B
12-XL-222263B
12-XL-222262C
12-XL-222263C
12-US-3204
12-US-3243
12-US-3244
12-US-3245
12-US-3246
ESD 1.1.1
ESD 1.2
ESD 1.2
NMP3
NCP2
NCP2
OCS
TAG NUMBER SETTING
HVAC SHUTDOWN
ALARM IN NCR
12-PAH-12203B
12-PAH-12303B
12-SOV-12200
12-SOV-12300
12-US-03290
12-US-3204
12-US-3243
12-US-3244
12-US-3245
12-US-3246
ESD 1.1.1
ESD 1.2
ESD 1.2
NMP3
NCP2
NCP2
OCS
TAG NUMBER SETTING
12-FDAHH-3222 X X O O X X C C C X X
PROC & UTILITY FIRE DETEC.
See note: 2
12-PALL-03205 X X O O X X C C C X X
FP SCRUBBER AREA
12-PALL-03206 X X O O X X C C C X X
FP SCRUBBER AREA
12-PALL-03212 X X O O X X C C C X X
FP CLOSED OPEN DRAIN
12-PALL-03631A04 X X X X
FP NCP2 ESDV PLTF
NCP2 12-PB-012203A X X O O X C C C X X
PROCESS & NCR F&G MATRIX
UTILITIES FIRE 12-PB-012203B X X O X C C C X X
DETECTED DEL.RELEASED AREA 1
12-PSH-12203 X X X C C C X X X
DEL.RELEASED AREA 1
12-PB-012303B X X O X C C C X X
DEL.RELEASED AREA 2
12-PSH-12303 X X X C C C X X X
DEL.RELEASED AREA 2
ALARM IN NCR
12-PAH-12203B
12-PAH-12303B
F&G MATRIX
12-XL-22203C
12-XL-22203B
12-SOV-12200
12-SOV-12300
12-XL-22203F
12-US-03290
12-US-3204
12-US-3243
12-US-3244
12-US-3245
12-US-3246
ESD 1.1.1
ESD 1.2
ESD 1.2
NMP3
NCP2
NCP2
NCR
OCS
TAG NUMBER SETTING
12-PAL-012202 X
NCP2 DELUGE AREA 1
12-UZ-0122 OPEN
12-PAL-012302 X
NCP2 DELUGE AREA 2
12-UZ-0123 OPEN
12-PALL-012000 X X
NCP2 FIRE WATER
MAIN RING LL PRESS.
12-MAC-03202 X
NCP2 M. CALL POINT
WALKWAY PROCESS
12-MAC-03204 X
NCP2 M. CALL POINT
WALKWAY UTILITIES
12-FAH-3216 X
See note: 2
NCP2-EDG FIRE TROUBLE ALARM
DETECTION 12-FAHH-3216 X
See note: 3
FIRE DETEC.CONFIRMED
12-XL-22203F X X
INHIBIT MODE SELECTED
NCP2-EDG 12-XL-22203C X X
WATER MIST AUTO MODE SELECTED
12-XL-22203B X X
WATER/MIST RELEASED
ALARM IN NCR
12-GDSHH-3204
12-GDSH-03204
F&G MATRIX
12-XL-22203C
12-XL-22203B
12-XL-22203F
12-US-03290
12-US-3204
12-US-3205
12-US-3243
12-US-3244
12-US-3245
12-US-3246
EDG UCP
ESD 1.1.1
ESD 1.1
ESD 1.2
ESD 1.2
NMP3
NCP2
NCP2
NCP2
NCP2
NCR
OCS
TAG NUMBER SETTING
12-GDAHH-03207 X X X X C C C X X
BETWEEN PROCESS / UTILITIES
See note: 2
NCP2
12-GDAHH-03208 X X
PROCESS AREA See note: 2
PLTF NORTH RIVER SIDE
GAS DETECTION
12-GDAHH-03209 X X
See note: 2
PLTF EAST RIVER SIDE
NCP2-UTILITIES 12-GDAHH-03205A/B/C X X X X C C C X X
AIR INTAKE COMP.A
AIR
12-GDAHH-03206A/B/C X X X X C C C X X
COMPRESSORS
AIR INTAKE COMP.B
12-GDAH-03204A/B/C X X
See note: 3
NCP2-EDG GAS EDG AIR INTAKE
DETECTION 12-GDAHH-03204A/B/C X X X X C C C X X X
See note: 4
EDG AIR INTAKE
12-US-3121A42A
12-US-3121A42B
ALARM IN NCR
12-US-3121A40
12-US-3121A41
12-US-03290
12-US-3204
12-US-3205
12-US-3243
12-US-3244
12-US-3245
12-US-3246
ESD 1.1.1
ESD 1.1
ESD 1.2
ESD 1.2
NMP3
NCP2
NCP2
NCP2
NCP2
OCS
TAG NUMBER SETTING
12-GDAH-03121A61 X X X
TURB.ENCLOS.VENT OUTLET
See note: 2
12-GDAHH-03121A61 X X X X C C C X X X X
TURB.ENCLOS.VENT OUTLET
See note: 3
12-GDAH-03121A62 X X X
See note: 2
INSIDE TURB.ENCLOSURE
12-GDAHH-03121A62 X X X
See note: 3
INSIDE TURB.ENCLOSURE
NCP2 12-GDAH-03121A63 X X X
See note: 2
COMPRESSOR DT TURB.AIR COMB INLET
3121A GAS 12-GDAHH-03121A63 X X X X C C C X X X X
See note: 3
DETECTION TURB.AIR COMB INLET
12-GDAH-03121A64 X X X
See note: 2
ABOVE COMPRE. AREA
12-GDAHH-03121A64 X X X X C C C X X X X
See note: 3
ABOVE COMPRE. AREA
12-US-3121A43 X X
GAS DETECTED ITR
12-US-3121B42A
12-US-3121B42B
ALARM IN NCR
12-US-3121B40
12-US-3121B41
12-US-03290
12-US-3204
12-US-3205
12-US-3243
12-US-3244
12-US-3245
12-US-3246
ESD 1.1.1
ESD 1.1
ESD 1.2
ESD 1.2
NMP3
NCP2
NCP2
NCP2
NCP2
OCS
TAG NUMBER SETTING
12-GDAH-03121B61 X X X
TURB.ENCLOS.VENT OUTLET
See note: 2
12-GDAHH-03121B61 X X X X C C C X X X X
TURB.ENCLOS.VENT OUTLET
See note: 3
12-GDAH-03121B62 X X X
See note: 2
INSIDE TURB.ENCLOSURE
12-GDAHH-03121B62 X X X X C C C X X X X
See note: 3
INSIDE TURB.ENCLOSURE
NCP2 12-GDAH-03121B63 X X X
See note: 2
COMPRESSOR DT TURB.AIR COMB INLET
3121B GAS 12-GDAHH-03121B63 X X X X C C C X X X X
See note: 3
DETECTION TURB.AIR COMB INLET
12-GDAH-03121B64 X X X
See note: 2
ABOVE COMPRE. AREA
12-GDAHH-03121B64 X X X X C C C X X X X
See note: 3
ABOVE COMPRE. AREA
12-US-3121B43 X X
GAS DETECTED ITR
ALARM IN NCR
F&G MATRIX
F&G MATRIX
12-XL-22200C
12-XL-22200B
12-XL-22202C
12-XL-22202B
12-XL-22200F
12-XL-22202F
NCR
NCR
OCS
TAG NUMBER SETTING
12-HDAH-3121A61 X
SOLAR See note: 2
FIRE ALARM
COMPRESSOR DT 12-HDAHH-3121A61 X
See note: 3
3121A FIRE FIRE DETEC.CONFIRMED
DETECTION
12-XL-22200F X X
SOLAR INHIBIT MODE SELECTED
COMPRESSOR DT 12-XL-22200C X X
3121A WATER AUTO MODE SELECTED
MIST 12-XL-22200B X X
WATER/MIST RELEASED
12-HDAH-3121B61 X
SOLAR See note: 2
FIRE ALARM
COMPRESSOR DT 12-HDAHH-3121B61 X
See note: 3
3121B FIRE FIRE DETEC.CONFIRMED
DETECTION
12-XL-22202F X X
INHIBIT MODE SELECTED
SOLAR
12-XL-22202C X X
COMPRESSOR DT
AUTO MODE SELECTED
3121B WATER MIST
12-XL-22202B X X
WATER/MIST RELEASED
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
2- Voting 1OO4 applied for alarm. Fire confirmed voting 2OO4 is applied for UV/flamme detectors or
3- Fire confirmed voting 2OO4 is applied for UV/flamme detectors or ROR heat detectors. Inhibit mode
to be tested. COMMISSIONING AND ACCEPTANCE
12-SOV-011100 MNP3
12-SOV-011200 MNP3
NCR 12-032-CP-01
NCR 12-032-CP-01
12-PAH-011103B
12-PAH-011203B
ALARM IN NCR
12-US-03113
12-US-3204
ESD 1.2
NMP3
OCS
TAG NUMBER SETTING
12-PALL-011000 X X
NMP3 FIREWATER RING
12-FDAHH-03111 X X X O O X
See note: 2
FIRE DET.NMP3 PLTF
12-PALL-03108 X X X O O X
FP SLUG CATCHER A
12-PALL-03109 X X X O O X
FP SLUG CATCHER B
12-PALL-03117 X X X O O X
FP CLOS/OPEN DRAIN
12-PALL-03118 X X X O O X
NMP3 FP PSDV PLTF & LP MANIF
FIRE DETECTED 12-PALL-03120 X X X O O X
FP FLARE KO DRUM
12-PALL-1031A03 X X X O O X
FP NMP3 ESDV PLTF
12-PALL-4531A02 X
FP FLOW LINE NMP/NMP2
12-PB-011103A RELEASE DELUGE X X X O O X
NCR 12-032-CP-01
12-PB-011103B RELEASE DELUGE X X X O X
LOCAL PANEL
12-PSH-011103 X X X X X
DEL.RELEASED AREA 1
12-SOV-011100 MNP3
12-SOV-011200 MNP3
NCR 12-032-CP-01
NCR 12-032-CP-01
12-PAH-011103B
12-PAH-011203B
ALARM IN NCR
12-US-03113
12-US-3204
ESD 1.2
NMP3
OCS
TAG NUMBER SETTING
X
MNP3 12-MAC-03101
MANUAL CALL
X
POINT 12-MAC-03101
ALARM IN NCR
12-US-03113
12-US-3204
12-US-3205
ESD 1.1
NMP3
OCS
TAG NUMBER SETTING
12-GDAHH-03101A/B/C X X X X X
See note: 2
TRANSFER PUMPS AREA
12-GDAHH-03103 X X
NMP3 PLATFORM NORTH RIVER SIDE
GAS DETECTION 12-GDAHH-03104 X X
WEST RIVER SIDE
12-GDAHH-03105 X X
EAST RIVER SIDE
ISOLT.INDOOR TELEPHONE
HVAC SHUTDOWN
ALARM IN NCR
12-US-03204
12-US-03205
12-US-03298
12-US-03243
12-US-03244
12-US-03245
12-US-03246
ESD 1.0
NCP2
OCS
TAG NUMBER SETTING
12-GDAHH-3201A/B/C X X X X C C C X X
See note: 2
NCP2 GAS DETEC. AIR LOCK 1ST FLOOR
12-GDAHH-3202A/B/C X X X T T X C C C X X
TECHNICAL See note: 2 & 3
AIR LOCK 2ND FLOOR
BUILDING
12-GDAHH-3200A/B/C X X X X C C C X X
See note: 2
HVAC AIR INTAKE
US-3201 X X
NCP/ OWT NCP PROCESS GAS DETECTION
GAS DETEC. US-3203 X X
OWT TECH.BUILD.GAS DETECT
NPU ESD2.12/ESD3.15/ESD3.10
ALARM IN NCR
ESDV-10A01
ESDV-10A02
ESDV-1022
ESDV-1809
HV-10A02
ESD3.11
NPU
OCS
TAG NUMBER SETTING
NPU C X
ESD 1.2
PSHH-1027 C X X
NPU
ESD 3.10 PSLL-1024 C X X
ESD 1.2B C X
NCP
PB-10A01 C C C X
PSLL-10A06 C C C X
NPU PSHH10A03 C C C X
ESD 3.15
ESD 3.7.4B C C C X
FROM NCP
ESD 3.16 C C C X
NPU
5-US-0242 C X
NCP ESD 2.1B
NPU 5-US-0246 C X
ESD 2.12 NCP ESD 3.18B or 23B
ESD 2.1 C X
NPU
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
NPU ESD2
NPU HP CONTACTOR
NPU HP SEPARATOR
NPU HP SEPARATOR
GAS EXPORT NMP
NPU HP KO DRUM
NPU HP KO DRUM
ALARM IN NCR
COND. EXPORT
ESD 3.16TN-M1
TO NCP2 SD 2
ESD 2B NCP
ESD 3.30/31
PSDV-1804
PSDV-1602
PSDV-1104
PSDV-1111
PSDV-1108
PSDV-1110
PSDV-1107
PSDV-1113
PSDV-1109
PSDV-1115
5-US0020
ESD 3.11
ESD 2.11
ESD 3.20
ESD 3.21
ESD 3.26
ESD 3.36
US-3212
ESD 3.2
ESD 3.5
ESD 3.2
ESD 3.8
TN-M1
NPU
NPU
NPU
OCS
TAG NUMBER SETTING
ESD1.0.X X X X X X X C C X X X C C C C X X X C C C C C X X
FIRE
LOSS OF PEER TO PEER X X X X X X C C X X X C C C C X X X C C C C C X X
SEE NOTE 2
US-03202
PB-0201 X X X X X X C C X X X C C C C X X X C C C C C X X
NCR ESD CP-01
PB-0206 X X X X X X C C X X X C C C C X X X C C C C C X X
NPU ITR
PB-0203 X X X X X X C C X X X C C C C X X X C C C C C X X
NPU ESCAPE WAY
PB-0204 X X X X X X C C X X X C C C C X X X C C C C C X X
NPU NPU ESCAPE WAY
ESD 2 PB-0205 X X X X X X C C X X X C C C C X X X C C C C C X X
NPU ESCAPE WAY
PSHH-1007 X X X X X X C C X X X C C C C X X X C C C C C X X
MANIFOLD
PSLL-1007 X X X X X X C C X X X C C C C X X X C C C C C X X
MANIFOLD
HS-207 X X X X X X C C X X X C C C C X X X C C C C C X X
PSLL-1801 X X X X X X C C X X X C C C C X X X C C C C C X X
GAS EXPORT
PSLL-1601 X X X X X X C C X X X C C C C X X X C C C C C X X
COND. EXPORT
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
2- LOSS OF P2P with NCP / OWT / NCP2 to be tested.
NPU ESD2
NPU HP CONTACTOR
NPU HP SEPARATOR
NPU HP SEPARATOR
GAS EXPORT NMP
NPU HP KO DRUM
NPU HP KO DRUM
ALARM IN NCR
COND. EXPORT
ESD 3.16TN-M1
TO NCP2 SD 2
ESD 2B NCP
ESD 3.30/31
PSDV-1804
PSDV-1602
PSDV-1104
PSDV-1111
PSDV-1108
PSDV-1110
PSDV-1107
PSDV-1113
PSDV-1109
PSDV-1115
5-US0020
ESD 3.11
ESD 2.11
ESD 3.20
ESD 3.21
ESD 3.26
ESD 3.36
US-3212
ESD 3.2
ESD 3.5
ESD 3.2
ESD 3.8
TN-M1
NPU
NPU
NPU
OCS
TAG NUMBER SETTING
LSHH-2603 X X X X X X C C X X X C C C C X X X C C C C C X X
HP FLARE KO DRUM
PSLL-2203A/B/C X X X X X X C C X X X C C C C X X X C C C C C X X
SEE NOTE 2
INSTRUM.AIR
2-XA-1073 &1074 X X X X X X C C X X X C C C C X X X C C C C C X X
UPS 220 VAC
2-XA-1076 &1077 X X X X X X C C X X X C C C C X X X C C C C C X X
UPS 24 VAC
NPU
ESD 2
NPU ESD1.2/ESD1.4/ESD2.11/ESD2.13
BLOWDOWN STATUS
GTS Y TRUNKLINES
BDV1114/1304/1313
TO NMP3 ESD 1.11
NPU-FCW CASE 5
COND. TO NMP2
ALARM IN NCR
FLARE STATUS
12-ESDV 703200
12-ESDV 103100
START INHIBIT
FUEL GASGAS
EDG 2-XS2406
12-XA03205
ESDV-1011
ESDV-0156
ESDV 1801
ESDV 1601
GAS EXP.
US-………
US-03112
US-03215
BDV1009
BDV1805
BDV2811
5US-9901
ESD 3.10
ESD 2.13
ESD 3.1
ESD 3.4
ESD 3.7
ESD 1.4
NPU
NPU
NPU
NPU
NPU
NPU
NPU
OCS
TAG NUMBER SETTING
ESD 1.1 X X X X X C C X X X X OT OT OT OT OT X X
SEE NOTE 2, 3 & 5
NPU
ESD 1.2 ESD 1 X X X X X C C X X X X OT OT OT OT OT X X
SEE NOTE 2, 3 & 5
NPU NPU
PB-0122 X X X X X C C X X X X OT OT OT OT OT X X
SEE NOTE 2, 3 & 5
ESD 1.2 5-CP-O3
ESD 1.2 C X
ESD 1.4 NCP
NPU US-3214 C X
FROM NCP2 SD 1.2
ESD 2 C C X X
ESD 2.11 NPU
NPU US-3214 C C X X
FROM NCP2 SD 1.2
ESD 2.11 C X X
ESD 2.13 NPU
NPU 12-FP-4531A02 C X X Fusible plug loop will activate
FUSIBLE PLUG LOOP ESD 1.1X
US-……… X
FCW CASE 5 VALVE TAG 12-ESDV 703200 VALVE TAG 12-ESDV 103100 SEE NOTE4
FCW CASE 5 FROM NCP
TIME BEFORE TIME BEFORE
MOVING MOVING
START/STOP INHIB.
ELECT ISOLATION
ELECT ISOLATION
ELECT ISOLATION
ELECT ISOLATION
ELECT ISOLATION
ELECT ISOLATION
LV-SB 100 CB 14D
DELUGE VALVE
DELUGE VALVE
ALARM IN NCR
TO FWP LOGIC
START ORDER
XV2404
XV2406
ESD 2.1
ESD 2
EDG
NPU
NPU
OCS
TAG NUMBER SETTING
5-US-0207 X X X X X X X X X
NPU FROM NCP ESD 1.0B
ESD 1.0.X X
US-03290 X X
FROM NCP2 F&G
US-03113 X X
FROM NMP3 F&G
5-US-0206 NCP F&G X
FROM NCP F&G
PSL-2401 X
NPU X
NPU ESD 1
ESD 1.1.X NPU X
ESD 1.1
ESDV-103100 X
FP-4531A02
HS-2406B X O See note : 2
NCR
HS-2404B X O X See note : 2
NCR
FIRE DETECTION FKP X See note : 2
& NEW DRAIN PLANT
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
2- Only the link to be checked .
ALARM IN NCR
NCP ESD 1.6B
5-US-4041
ESD 1.1X
DELUGE
DELUGE
DELUGE
DELUGE
DELUGE
XV-2404
XV-2401
XV-2402
XV-2403
XV-2405
ESD 1.2
NPU
NPU
OCS
TAG NUMBER SETTING
PSL-2435 X X X O O O O X
PSL-1210 X X X O O O O O X
DELUGE
NPU FIRE DETECTION X X X O O O O X
ESD 1.1 5.5KV NPU TRANSFO.
HS-2401A X X X O O O O X
ESCAPE WAY
HS-2401B X X X O O O O
NCR
NPU ESD 1
ELECTRICAL ISOLATION
ELECTRICAL ISOLATION
XS-6011/12/13/14/15
AIR COMPRESSOR
ALARM IN NCR
ESD 1.1X
ESD 1.2
NPU
NPU
OCS
TAG NUMBER SETTING
NPU X X X X X
ESD 1.0A
PB-103 X X X X X
SEE NOTE 4
NPU ESCAPE WAY
PB-104 X X X X X
SEE NOTE 4
NPU ESCAPE WAY
PB-105 X X X X X
SEE NOTE 4
NPU ESCAPE WAY
PB-102 X X X X X
SEE NOTE 4
NPU NCR 5-00-CP-03
ESD 1 12-XS-2210A/B X X X X X
LV-SB-100/200 UND.VOLT.
GAS DETECTION X X X X X
SEE NOTE 3
AIR COMPRESSOR
GAS DETECTION X X X X X
SEE NOTE 2
EDG
GAS FIRE DETECTION X X X X X
SEE NOTE 2
TELECOM CABINE
GAS DETECTION X X X X X
SEE NOTE 2
FIRE WATER PLTF
ISOLA.BATT.CH.33-BC-21
ISOL.BATT.UNIT 30BC31 A/B
ISOLA.BATT.30-UPS.33BC A/B
XS-6003 / 4 NPU
XS-6005 / 6 NPU
XS-………. NPU
XS-………. NPU
XS-………. NPU
XS-………. NPU
XS-………. NPU
XS-………. NPU
XS-………. NPU
ALARM IN NCR
XS-………. NPU
XS-………. NPU
XS-6007 NPU
XS-2601 NPU
ESD 1
NPU
OCS
TAG NUMBER SETTING
12-PB-0004 X X X X X X X X X X X X X X X X X X
SEE NOTE 5
NCR 5-00-CP-03
5-US-…………… X X X X X X X X X X X X X X X X X X
SEE NOTE 2
GAS DETECT. 1ST FLOOR TB
ESD 1.0 A
5-US-………… X X X X X X X X X X X X X X X X X X
SEE NOTE 2
GAS DETECT. 2ND FLOOR TB
5-US-…………… X X X X X X X X X X X X X X X X X X
SEE NOTE 2
GAS DETECT. HVAC INTAKE
NCP ESD3.7.4B/ESD3.7.2B/3.8.2B
TO NMP3 SD 3.22
ALARM IN NCR
12-PSDV-113100
12-PSDV-113101
NPU ESD 3.15
FCW CASE 7
ESD 3.7.10B
ESD 3.7.10B
8-US-0034B
ESD 3.7.6 B
ESD 3.8.4 B
PSDV-0145
PSDV-0155
US-……….
ESD 3.7.4B
ESD 3.8.6B
ESD 3.8.6B
5-US0133
US-03122
US-03123
INLET
INLET
OCS
NCP
NCP
NCP
NCP
NCP
NCP
NCP
TAG NUMBER SETTING
ESD 3.8.5 B
PAHH-0157 X X X X
8-US-0034A X X X
ESD 3.8.7 B OWT ESD 3.70.4C
NPU CONDEN.NMP/NMP2
TO NPU-FCW CASE 5
ALARM IN NCR
ESDV-103100
FCW CASE 4
FCW CASE 6
ESD 3.11.2B
ESD 3.9.3 B
ESD 3.9.4 B
ESDV-1011
PSDV-1053
PSDV-0132
PSDV-1063
PSDV-0112
PSDV-1073
PSDV-0121
PSDV-0162
ESD 3.1.2B
ESD 3.2.2B
ESD 3.3.2B
ESD 3.4.2B
ESD 3.5.2B
ESD 3.6.2B
US-………
US-………
US-………
ESD 2.11
ESD 2.12
NPU
NPU
OCS
NCP
NCP
NCP
NCP
NCP
NCP
NCP
NCP
NCP
TAG NUMBER SETTING
NCP ESD2B
ALARM IN NCR
NMP2 GTS I/J/L
TO NCP2 SD2
5-US0236/239
NMP2 GTS M
NMP2 GTS K
NMP2 GTS Y
ESD 3.11B
ESD 3.29B
ESD 3.30B
ESD 3.24B
ESD 3.25B
ESD 3.26B
ESD 3.27B
ESD 3.28B
8-US9709
US-03227
ESD 2.1B
ESD 3.1B
ESD 3.2B
ESD 3.3B
ESD 3.4B
ESD 3.5B
ESD 3.6B
ESD 3.7B
ESD 2.3B
ESD 3.8B
NCP
NCP
NCP
NCP
NCP
NCP
NCP
NCP
NCP
NCP
NCP
OCS
TAG NUMBER SETTING
5-US0020 X X X X X X X X X X X X X X X X X X X X X X X
ESD 2 NPU
ESD 1.3B X X X X X X X X X X X X X X X X X X X X X X X
NCP
PB-010 X X X X X X X X X X X X X X X X X X X X X X X
NCR
PB-011 X X X X X X X X X X X X X X X X X X X X X X X
ITR
LOSS OF PEER TO PEER X X X X X X X X X X X X X X X X X X X X X X X
See note: 2
US-03207
PALL-0181 X X X X X X X X X X X X X X X X X X X X X X X
NCP ESD GAS OUTLET
2.B PAHH-0180 X X X X X X X X X X X X X X X X X X X X X X X
PALL-0142 X X X X X X X X X X X X X X X X X X X X X X X
GAS OUTLET
PALL-0147 X X X X X X X X X X X X X X X X X X X X X X X
LIQUID EXP PUMP OUTLET
PALL-0152 X X X X X X X X X X X X X X X X X X X X X X X
GAS OUTLET
LAHH4810A/B/C X X X X X X X X X X X X X X X X X X X X X X X
CLOSED DRAIN DRUM
LAHH4610A/B/C X X X X X X X X X X X X X X X X X X X X X X X
HP FLARE KO DRUM
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
2- LOSS OF P2P with NPU / OWT /NCP2 to be tested.
8-US-9719 CB 5B
ALARM IN NCR
5-US-4045
5-US-4039
5-US-4040
5-US-4046
8-US-9716
8-US-9717
8-US-9720
8-US-9721
OCS
TAG NUMBER SETTING
5-US-4041 X X X X X
NCP ESD FROM NPU ESD 1.1
1.6B
8-US-0115 X X X X X X X
NCP ESD FROM OWT ESD 1.0C
1.7B
DISCHARGE SCRUBBER A
STOP AIR COMPRESSORS
DISCHARGE SCRUBBER B
STOP N2 UNIT 5X-9500A/B
BLOWDOWN STATUS
NMP2 MP MANIFOLD
HP MANIFOLD NCP
SLUG CATCHER A
SLUG CATCHER B
ALARM IN NCR
FLARE STATUS
5-US9500A/B
12-XA03203
5-US03111
BDV-0341
BDV-0241
BDV-0205
BDV-0143
BDV-0150
BDV-0153
BDV-0133
5-US9701
5-US3216
5-US0161
ESD 1.3B
ESD 1.5B
ESD 2.1
ESD 2B
ESD 2
NPU
NPU
OCS
NCP
NCP
NCP
TAG NUMBER SETTING
ESD 1.B X X X X X X OT OT OT OT OT OT OT X
See note: 2 & 3
NCP
5-US-0115 X X X X X X OT OT OT OT OT OT OT X See note: 2 & 3
FIRE DETEC. NMP2
NCP 5-US-0136 X X X X X X OT OT OT OT OT OT OT X See note: 2 & 3
ESD 1.2B NCP LOW VOLT 230 V UPS
5-US-0135 X X X X X X OT OT OT OT OT OT OT X
See note: 2 & 3
NCP LOW VOLT 48 V UPS
5-US116 X X X X X X X
NCP T.B FIRE DETEC
PB-007 X X X X X X X
NCP NCR
ESD 1.3B PALL-4242A/B/C X X X X X X X
INST/AIR
ESD 1.2B X X X X X X X
OWT
TO NMP3 SD3.21
ALARM IN NCR
PSDV-18110
PSDV-18112
PSDV-18120
PSDV-18122
ESD 3.70.4C
ESD 3.70C
ESD 3.71C
US-03124
US-03125
OWT
OWT
OWT
OCS
TAG NUMBER SETTING
8-US-0116 X X X
OWT TEC.BUILD FIRE DET
8-US-9709 NCP X X X
ESD 2.B NCP
8-US-9711 X X X
230V UPS LL VOLTAGE
8-US-9712 X X X
OWT 48 VDC UPS LL VOLTAGE
ESD 2.C PB-008 X X X
PB-009 X X X
NCR
LOSS OF PEER TO PEER X X X
SEE NOTE 5
US-……………
ESD 1C X X X
OWT
ESD 3.70 C X X C C X
SEE NOTE 3
OWT OWT
ESD 3.70.1C LAHH-18114 X X C C X
SEE NOTE 3
OWT
ESD 3.71 C X X C C X
SEE NOTE 4
OWT OWT
ESD 3.71.1C LAHH-18124 X X C C X
SEE NOTE 4
OWT
REMARK : COMMENTS DURING OT :
1 - All animation & alarm of safety valves to be tested regarding the reset,
discrepancy, override and stroking (if appropriate)
5- LOSS OF P2P with NCP / NPU / NCP2 to be tested. PJC / CMS AMT / NPU / MNT
ALARM IN NCR
NCP ESD 3.8.7B
ESD 3.70.1C
ESD 3.70.2C
ESD 3.70.3C
ESD 3.71.1C
ESD 3.71.2C
ESD 3.71.3C
ESD 3.76.1C
8-US-0034A
OWT
OWT
OWT
OWT
OWT
OWT
OWT
OCS
TAG NUMBER SETTING
8-US-0034B X X X X
NCP ESD 3.8.5B
PAHH-18111 X X X X
OWT
ESD 3.70C PALL-18116 X X X X
ESD 2.C X X X X
OWT
8-US-0034B X X X X
NCP ESD 3.8.5B
PAHH-18121 X X X X
OWT
ESD 3.71C PALL-18126 X X X X
ESD 2.C X X X X
OWT
ESD 3.82.C X X X
OWT OWT
ESD 3.70.4C X X X
ESD 3.70.1C AND 3.71.1C
ELECT.ISOL.48VDC CB 21A
24VDC ELECT.ISOL.FOR PDCS
HVAC ELECT ISOL 220V UPS
ELECT.ISOL.48VDC CB 21B
ELECT.ISOL.48VDC CB 21C
8-US-3201 NCP TO
ALARM IN NCR
8-US-3110 NCP
8-US-9703 NCP
8-US-9600A
8-US-9600B
8-US-9600C
8-US-9708
ESD 1.2B
ESD 2C
OWT
OCS
NCP
NCP
TAG NUMBER SETTING
5-US-0130 X X X X X X X
NCP PROCESS GAS
ESD 1.0B X X X X X X X
NCP
ESD 1.0C X X X X X X X
OWT
5-PB0002 X X X X X X X
See note: 1
NCP & OWT ESD ESCAPE WAY
1.B OR 1C 5-PB0004 X X X X X X X
See note: 1
ESCAPE WAY
5-PB0005 X X X X X X X
See note: 1
ESCAPE WAY
5-PB0006 X X X X X X X
See note: 1
NCP ITR
5-PB0003 X X X X X X X
See note: 1
NCR 5-CP-03
8-US-9710 X X X X X
FROM NCP ESD1.0.B
OWT ESD 1.X.C
NCP/OWT ESD1.0B/1.0C/1.02B
ISOLT.CRITICAL SOURCES
ISOLATION OF TELECOM
8-US-……….. OWT
8-US-……….. OWT
8-US-……….. OWT
5-US-……….. NCP
5-US-……….. NCP
5-US-……….. NCP
8-US-9715 OWT
8-US-3203 OWT
ALARM IN NCR
NCP2 ESD 1.1.2
5-US4052/4053
5-US4050/4054
5-US4049/4051
OWT ESD 1. C
OWT ESD 1.0
ESD 1.0.2 B
12-US-3206
5-US-0207
8-US-9710
8-US-0115
ESD 1.B
ESD 1.C
OCS
NCP
NCP
NCP
TAG NUMBER SETTING
5-PB-0001 X X X X X X T X X X
See note: 2 & 3 & 5 & 6
NCR 5-00-CP-03
ESD 1.0 B
5-US-0114 X X X X X X T X X X
See note: 3
TECH BUILDING GAS DETEC.
5-PB-0001 X X X T T T X X X X
See note: 2 & 4 & 5
NCR 5-00-CP-03
ESD 1.0 C
12-US-0114 X X X T T T X X X X
OWT TECH BUILD. GAS DETEC.
See note: 4
A20000758
Company
Commissioning
Certifying Authority