EDC-DTS-MV001 - Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
EDC-DTS-MV001 - Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
ELECTRICITE DU CAMBODGE
TECHNICAL SPECIFICATION
EDC-DTS-MVOO1
Pole Mounted Three-Phase and Two-
Phase Outdoor Distribution Transformers
August 2019
Version 2.0
EDC-DTS-MVOO1- Pole Mou nted Three-Phase and Two-Phase Outdoor Distribution Transformers
ELECTRICITE DU CAMBODGE
Page 3/ 70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
Draft 1
DRAFT2 AD
FINAL AD
Appro AD/EDC
V 2.0
Version 2.0: Main modifications from version 1.0 (February 2017) are below:
Page 4/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
Content
1 Scope 9
2 Standards 9
3 Definitions 9
4.1 GeneralNotesforTest 9
5 Quality Management 10
6 Technical Requirements 10
6.1 General 10
7 Performance Characteristics 11
8 Technical Characteristics 13
8.2 Core 14
8.3 Winding 14
8.5 lmpedanceVoltage(Uk%) 15
8.7 Losses
8.8 Regulation
Page5/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
9.1 TankandCover 19
9.2 Sealing 19
9.4 Cooling 20
9.8 Earthing 21
9.10 Accessories 21
10 Bushings 22
10.1.1 General 22
10.1.2 Location 22
10.1.5 Construction 23
10.1.6 Terminals 23
10.2.1 General 23
.2 Location 23
4t?31ctrical Characteristics 24
ic)
Page6/70 LL
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
10.2.5 Construction 24
10.2.6 Terminals 25
12 Oil 27
13 Delivery 27
15 ANNEX 70
[Blank]
1 Scope
This specification covers the design, manufacturing, testing, supply, delivery and performance
requirements of 2-phase and 3-phase, oil immersed, hermetically sealed outdoor pole mounted type
distribution transformers for 22 kV and 35 kV levels to be used on the Power Distribution networks of
EDC with a life expectancy of at least 25 years without any maintenance.
2 Standards
IEC : International Electrotechnical Commission
IEC 60296 : Fluids for electro technical applications - Unused mineral insulating oils for
transformers and switchgear
ISO/IEC 17025 : General requirements for the competence of testing and calibration
laboratories
Unless if standard year is specified, the latest version of the above standards apply.
The supplier may propose alternative standards, provided it is demonstrated that they give an
equivalent degree of quality as the referenced standard. Acceptability of any alternative standard is at
the discretion of the EDC.
3 Definitions
The definition of the relevant IEC standards applies to this technical specification.
The inspection and routine tests shall be carried out in accordance withh9'pro
I 4q / ,
IEC 60076 recommendations. / '
\ , \
\c\\.
Page 9 / 70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
All type tests required by the IEC 60076 shall be carried out.
Type test reports shall be carried out by internationally recognized electrical testing laboratories.
Full copies of type test reports shall be submitted within the bid of the manufacturer/supplier. Type
test reports older than 10 years will not be accepted.
If the manufacturer is certified by EDC, it is not necessary to submit type test reports for the considered
eq uipment.
Nevertheless, in case the testing laboratory is not internationally recognized, the testing laboratory
shall be mandatorily accredited ISO/IEC 17025 by an international or national accreditation body
specialized in testing laboratories accreditation/acceptance. In that case, the testing laboratory shall
prove mandatorily its capability/capacity to carry out all type tests mentioned in the type tests reports
by supplying: Full description of all tests the laboratory can carry out, list of testing equipment with
full characteristics, drawing of testing rooms with location of testing equipment, ...etc., supported by
pictures and copy of the ISO/IEC 17025 accreditation certificate.
The routine tests requested by IEC 60076 shall carried out on all transformers. Routine test reports
shall be sent to [DC prior the shipment for [DC acceptance.
The routine test report shall be also attached to each transformer in a fully waterproof pocket or under
the form of an indelible plastic sheet.
The routine testing procedure to be carried out during EDC approval inspection shall be sent to [DC
for approval.
Oil will be routine tested and analyzed to prove PCB free and the routine test report shall be sent to
[DC prior the shipment for acceptance.
5 Quality Management
Design, development and production of the proposed equipment shall be ISO 9001 certified. The ISO
9001 certificate shall be submitted within the bid.
6 Technical Requirements
6.1 General
D1stit J j 41ai sformers shall be 3-phase or 2-phase transformers, 2 windings, oil immersed, 50 Hz
and thaU 1av5ffjrcuit tapings mounted in the primary winding The type of cooling shall be oil
naturaIir natt(biAN).
;jn
Version 2.0 Page 10/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
- 35(22) kV Transformers (two primary voltages): Un: 35(22) kV, Urn: 38/40.5(24) kV
7 Performance Characteristics
The transformers shall be suitable to operate in the ambient conditions described hereafter:
Climate Tropical
Average 27.5°C
Minimum 13.3°C
Maximum 40.5°C
Wind Velocity:
\ '4*---.
Page 11/70 M on 2.0
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
230V
35kV 25
2 LV bushings
230/460 V
35 kV 50, 75, 100
3 LV bushings
230V
(22) kV 25
Two-phase 2 LV bushings
Transformers 230/460V
35(22)kV 50, 75, 100
3 LV bushings
230V
22 kV 25, 30
2 LV bushings
230/460V
22kV 50
3 LV bushings
All transformers shall be of outdoor type, designed for pole mounted and platform substations.
Each transformer shall be capable of supplying its rated capacity continuously for all tap positions with
rated voltage on the secondary winding and continuous, steady load, a maximum temperature
gradient of 21 °C and maximum winding hot spot of 98 °C. The transformers shall also be capable of
delivering rated current at an applied voltage equal to 110 % of the rated voltage.
Likewise, each transformer shall be capable of supplying its rated capacity continuously under ambient
temperature conditions without the temperature rise of the top oil exceeding 55 °C and without the
temperature rise of the windings as measured by resistance exceeding 60 °C. The ambient temperature
conditions will be as follows:
150% 98 65
The supplier shall include calculations demonstrating that these requirements are met. These
calculations shall disregard the effect of winding thermal capacity.
Importance is attached to overload capacity and transformers incapable of meeting the performance
specified shall not be considered and accepted.
8 Technical Characteristics
The high voltage windings shall be provided with off-load tap changer for voltage adjustment.
The lever(s) for operating the off-load tap changer and primary voltage changer (if any) shall be of
externally operated type.
Each transformer shall be fitted with 5 taps giving provision for off circuit changing of voltage ratio;
Generally, the tap settings shall be +5%, +2.5%, 0%, -2.5%, -5%. Nevertheless, for transformer located
in remote rural area, the tap setting shall be: +2.5 %, 0, -2.5%, -5 %, -7.5 %.
-.5---..
.' I
Page 13 / 70 t vp 2.0
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
Tap changing shall be carried out with the transformer off circuit. An externally operated self-
positioning tapping switch shall be provided. The handle shall give visual indication of the tapping
position, and it shall be rotated in clockwise direction from a high tap to lower tap "1" to "5". Switch
position No.1 shall correspond to the primary voltage that gives the highest voltage ratio.
For two primary voltage transformers, the changing between 2 primary voltage levels shall be carried
out with an externally operated self-positioning tapping switch on the top of transformer without aid
from another device. The handle shall give visual indication of the voltage position, and it shall be
rotated in clockwise direction from a high tap to lower tap 35 kV to 22 kV.
The tap position shall be indelibly marked by embossing or engraving and with weather proof paint
and in color which shall present distinctive contrast to the surrounding material. The operating handles
shall be made by non-corrosive metal.
Provision shall be made for pad-locking of the tapping switch handles in any desired position, with a
6 mm standard diameter padlock to be provided by [DC.
Tap change switches shall be fitted with gaskets and covers in order to make the sealing of the
transformer independent of the switch shaft gland under normal conditions.
8.2 Core
Core shall be made of low loss; high permeability material and the core construction shall avoid static
discharge and development of short-circuit paths within itself or to the ground. The core design shall
ensure no hot sections due to over fluxing or circulating currents. The flux density at any point shall be
designed to meet 1.55 to 1.65 tesla.
8.3 Winding
MV and LV Windings shall be made with high conductivity copper and shall be designed and
manufactured to resist, without suffering damage, the thermal and mechanical effects caused by
external short-circuit. The insulation material of windings shall be suitable for the specified
temperature rise and shall be thermally stabilized.
Two-phase Transformers
25 to 100 li-U
Three-phase Transformers
50 to 1600 Dyn 11
Page 14 / 70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
Voltage Voltage (Um) withstand voltage (50Hz/i mn) withstand voltage (1.2/50 i.ts)
22 kV 24 kV 50 kV 125 kV
0.4 kV 1 kV 3 kV
0.23 kV 1 kV 3 kV
The windings shall be fully insulated and the neutral point shall be insulated for full voltage.
The impedance on the principal tap (nominal voltage) of 35 kV transformers shall be:
25 kVA 2.2%
50kVA 2.4%
The impedance voltage shall be subject to the tolerance specified in lEC 60076.
8.5.1.2 22 kV transformers
The impedance on the principal tap (nominal voltage) of 22 kV transformers shall be:
up to 30 kVA 2%
50 kVA 2.2%
The impedance voltage shall be subject to the tolerance specified in IEC 60076.
8.5.2.1 35 kVTransformers
The impedance on the principal tap (nominal voltage) shall be:
Page 15 / 70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
4% 50, 75
6% 1250, 1600
The impedance voltage shall be subject to the tolerance specified in IEC 60076.
Transformers shall have corresponding impedance per tap characteristics such that transformers of
the same rating can be operated in parallel.
8.5.2.2 22 kVTransformers
The impedance voltage shall be subject to the tolerance specified in IEC 60076.
Transformers shall have corresponding impedance per tap characteristics such that transformers of
the same rating can be operated in parallel.
The transformer shall be capable of sustaining a three-phase symmetrical short circuit on the low
voltage side with power maintained on the high voltage side without damage or distress for 3 seconds.
8.7 Losses
According to Cambodia and [DC Standards for 35 kV and 22 kV distribution transformers, maximum
values of losses accepted shall be as follows:
25 ~120 ~430
50 ~160 ~679
75 ~175 ~730
100 ~250 ~1260
Page 16 I 70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
2-phase 22 kV Transformers
25 ~115 ~430
30 ~120 ~500
50 ~150 ~670
50 ~170 ~950
75 ~230 ~1250
3-phase 22 kV Transformers
50 ~160 ~950
75 ~220 ~1250
250 ~500
315 ~600
400 ~720
Page 17 / 70 /
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
3-phase 22 kV Transformers
The losses shall be stated and guaranteed in the offer. The guaranteed losses including IEC tolerances
are to be maximum values and shall not be exceeded.
If at delivery, the tested losses exceed the guaranteed losses, the transformer will be rejected.
8.8 Regulation
The supplier shall guarantee that the regulation of each transformer from no load to continuous rated
output at 1.0 power factor and at 0.85 lagging power factor shall be as stated in the technical data
schedules.
The transformer shall be capable of operating continuously with rated current and with system
maximum voltage applied to the secondary winding at a frequency of 96 % of rated frequency without
exceeding the temperature rise specified before.
For all transformers, the limit of flux density at any point in the magnetic circuit shall be subject to the
requirements for losses, harmonics and noise suppression.
The acoustic sound level shall be measured according to the IEC 60076 requirements.
2-phase transformers
35 kV and 35(22) kV 22 kV
25 45 45
30 45 45
50 46 46
75 47 47
100 48 48
3 -phase transformers
35 kV and 35(22) kV 22 kV
50 47 47
75 48 48
100 49 49
160 52 52
200 53 53
250 55 55
315 56 56
400 58 58
500 59 59
630 60 60
800 61 61
1000 63 63
1250 64 64
1600 66 66
Tank and cover shall be constructed of welded steel sheets. The joints between tank and cover shall
be provided with suitable flanges bolted together with gaskets.
The cover shall be formed of steel sheet and electrically bonded to the tank. It shall be designed in
such manner the tank/cover gasket remains in correct position during assembly and all along the
transformer lifespan.
Nevertheless, for two-phase transformers, as they are allowed to be of gas cushion oil preservation
system, the cover can be welded to the tank for this type of transformers.
The transformer tank shall be designed in such a manner that the completed transformer can be lifted
and transported without permanent deformation or oil leakage.
The tank and cover shall be designed in such a manner to prevent external pockets in which water can
lodge.
All pipes, fins or corrugation shall be externally welded to the tank wall.
All bolts used on transformers shall be made of stainless steel and be of metric size.
As option expressed in the tender documents, transformers shall be fitted with special cross arm for
supporting surge arresters on the upper part of the transformer located on MV bushing transformer
side.
9.2 Sealing
Page 19 / 70 A-
Ii '*1
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
The tank cover shall be removable for core and coils access. Transformer parts inside the tank shall be
able to remove upward in one piece with the lift of the tank cover.
All gaskets shall be made of resilient material which will not deteriorate under the action of hot oil and
will remain oil-tight for the life expectancy of the transformer.
All gaskets and sealing devices shall be able to maintain the seal for extreme operating temperatures
of the transformer.
The oil preservation system of the transformers shall be of the following type according the
requirement of IEC 60076-1 paragraph 8.2.
Sealed, completely filled system in which the expansion of the oil is taken up by elastic
movement of the permanently sealed, usually corrugated tank.
• Sealed, completely filled system in which the expansion of the oil is taken up by elastic
movement of the permanently sealed, usually corrugated tank or;
• Sealed tank system with gas cushion, in which a volume of gas above the liquid surface
in a stiff tank accommodates the liquid expansion under variable pressure.
9.4 Cooling
The tank shall be designed for natural cooling (ONAN) with a corrugated wall tank (radiator for 2-phase
Sealed tank system with gas cushion) if additional cooling is required.
Each transformer shall be provided with a minimum of two closed lifting lugs located on the
transformer cover (one for two-phase transformers). The minimum diameter of the hole shall be 25
mm. The two lifting lugs shall be located such that there will be a minimum of 50 mm between the
lifting chain and the nearest part of the bushings.
Three-phase Transformer shall be fitted with an under frame suitable for bolting the transformer to a
pole mounted platform.
Two-phase transformers shall be fitted with a single hole fixing bracket and a steady bracket to enable
the transformers to be mounted on a single pole. The upper fixing bracket must be located sufficiently
near the top of the tank to ensure stable hanging.
A-ftWns$.uwith an inner diameter of at least 25mm shall be placed at the top of the cover.
¶?atsfQrm&s tiall have a 25mm minimum diameter BSP oil drain plug placed at the bottom of the
;. . r*t
itank. -
Page2O/70 /i4
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
9.8 Earthing
In addition, the two lifting lugs shall be also fitted with one 10 mm diameter hole each.
The core construction shall avoid static discharge and development of short-circuit paths within itself
or to the ground.
The windings shall be designed and manufactured to resist, without suffering damage, the thermal and
mechanical effects caused by external short-circuit.
9.10 Accessories
The transformer shall be supplied with the thermometer pocket filled with oil and the thermometer
installed shall be of 2 pointers with the maximum temperature indicator of resettable type with
horizontal reading scale graduated in °C.
Accuracy ±2%
Page 21/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
All other transformer necessary accessories shall be supplied with the transformer.
Transformers and smaller parts such as brackets, etc. shall be preferably powder painting with Dark
Grey colour-RAL 7033 or 7036.
As an alternative to powder painting the exterior of the tank of the transformers may be painted with
a primer coat and not less than two-finish epoxy or acrylic paint provided the manufacturer prove a
surface treatment lifespan that meet the lifespan of the transformer (25 years without maintenance)
by providing salt spray test.
The inner surfaces of the tank and radiators shall be coated by an oil resistant paint.
Before painting the interior and exterior of the tank in a dismantled condition shall be abrasive blast
cleaned to white metal. All surfaces (except those in direct contact with oil) immediately after cleaning
and not less than four hours after cleaning shall be coated with the powder painting.
Before any top coats are applied i.e. before assembly, the coating is to be primed in accordance with
the paint manufacturer's recommendations.
The interior of the tank in contact with the oil shall be given at least one coat of non-chipping oil and
acid resisting paint or varnish after cleaning as above.
The details of the paint system to be used, including the brand and type of paint to be used shall be
included in the Bid documents.
10 Bushings
10.1.1 General
All winding leads shall be brought out through porcelain bushings. All bushings shall be so designed
that there will be no excessive stressing of any parts due to temperature changes and adequate means
shall be provided to accommodate conductor expansion.
10.1.2 Location
The insulation levels for bushing shall be at least equal to those specified for the windings.
Distance
The creepage ditnces for the bushings and the insulators shall not be less than 25 mm/kV for the
considered highes\(oltage:
24kV 600mm
38kV 950mm
10.1.5 Construction
The porcelain shall be tested according to lEC Publication 60137 or equivalent standard respectively.
The glaze shall be brown and shall cover all exposed parts of the insulator. Between the porcelain and
surrounding metal, gaskets or cement are to be interposed. All porcelain clamping surfaces in contact
with gaskets shall be accurately grounded and free from glaze.
Each porcelain bushing shall be marked with manufacturer's identification mark, indicating the year of
manufacturing and other marks necessary for the tests. The marking shall be clearly legible and visibJe
after assembly of the fittings.
Connections from the windings to the bushings shall have necessary flexibility.
Clamps and similar details made of steel or malleable iron shall be galvanized.
Copper or copper alloy terminals shall be tinned to a thickness of minimum 50 tm. Copper alloys shall
not be sensitive to cracking.
The bushings shall be so installed that they are easy to be checked and removed without removing the
tank cover.
10.1.6 Terminals
External terminals shall comply with the requirements of High Voltage Terminals and shall be suitable
to received bi-metallic aluminum/copper crimped lugs with a hole of 13 mm diameter.
10.2.1 General
Distribution transformer shall be supplied with porcelain bushings on LV side. Secondary bushings
include porcelain insulator and copper terminal.
10.2.2 Location
10.2.5 Construction
The porcelain shall be tested according to lEC Publication 60137 or equivalent standard respectively.
The glaze shall be brown and shall cover all exposed parts of the insulator. Between the porcelain and
surrounding metal, gaskets or cement are to be interposed. All porcelain clamping surfaces in contact
with gaskets shall be accurately grounded and free from glaze.
Each porcelain bushing shall be marked with manufacturer's identification mark, indicating the year of
manufacturing and other marks necessary for the tests. The marking shall be clearly legible and visible
after assembly of the fittings.
Connections from the windings to the bushings shall have necessary flexibility.
Page 24 / 70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
10.2.6 Terminals
External terminals shall be suitable to received bi-metallic pre-insulated aluminum/copper lugs for
Aluminum ABC with a hole of 13 mm diameter.
Transformer
Type of terminals
capacity (kVA)
Page 25 / 70 IL
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
Flexibles and UV weather resistant terminal insulating covers shall be provided for wildlife protection.
The insulation withstand of insulating cover shall not be less than 24 kV per 1 minute (power frequency
voltage).
The terminal markings shall be clearly and permanently displayed. Painted markings are not
acceptable.
• Primaryvoltage: A,B,C
• Secondary voltage: a, b, c and n
• Primary voltage: A, B
• Secondary voltage:
- a,b for 25 and 30 kVA transformers
- a,n,b for 50, 75 and 100 kVA transformers
Labels, plates, markings and instructions shall be clear and indelible and both in English and Khmer
language. Case-in or molded-in words which are not English words shall be covered with permanently
fixed non-ferrous labels inscribed in English.
A weatherproof rating plate shall be provided in accordance with IEC 60076 and showing the following
items, indelibly marked by engraving or embossing:
Type of transformer,
Manufacturer's name,
Serial number,
Year of manufacturing,
Number of phases,
Rated capacity,
Rated frequency,
Rated voltages,
Rated currents,
Vector group,
Page 26 / 70 IL
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
Type of cooling,
Total weight,
Volume of oil,
Connection diagram.
It shall be possible to fix this plate on all side of the transformer with exception of the LV bushing side.
In addition, a second plate or paint marking mentioning kVA rating in numerals 70 mm height shall
appear on the tank and below the LV bushing. These numerals shall be applied by stenciling or by other
suitable means.
12 Oil
All transformers shall be filled to the required level with new, unused, clean, standard mineral oil in
compliance with [C 60296 and shall be free from all traces of polychlorinated biphenyl (PCB)
compounds.
The oil shall be PCB free; [DC will refuse the delivery of the transformers that are not proved to comply
with this requirement.
Oil suppliers' coordinates, oil type, reference and detailed characteristics shall be provided in the offer.
13 Delivery
Transformers shall be delivered suitably protected for transport and storage on a strong enough non-
returnable wooden case pallet.
30 kVA LI
50 kVA LII
1 Country to be specified
2 Manufacturer to be specified
General
1. Tank
Page28/70 it.,
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
2. Sealing
Page 29 / 70 .
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
4.1 Primary
e Frequency Hz 50
Page 30 I 70 F
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
4.2 Secondary
a. Service voltage
a. 25and30kVA 2%
b. 50kVA 2.2%
6. Short-circuit performance
7. Tap changer
i-f
Page3l/70 ilc
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
8. Losses To be specified
a. 25kVA
• Noload W • ~115
b. 30kVA
• Noload W • ~120
• Load (75°C) • ~ 500
c. 50 kVA
• Noload W • ~150
• Load (75°C) • ~ 670
10. Accessories
Page 32 / 70 /./
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. 25and30kVA 2
b. 50kVA 3
c. Rated voltage 1 kV
Page 33 I 70 6, I
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
• Type of transformer,
• Manufacturer's name,
Yes
• Serial number,
• Year of manufacturing,
• Numberofphases,
• Rated capacity,
• Rated frequency,
• Rated voltages,
• Rated currents,
• Vector group,
• Type of cooling,
• Total weight,
• Volumeofoil,
• Connection diagram.
• Property of ELECTRICITE DU
CAM BODGE and EDC logo
• nHJ$nfl
107 Oil
Page34/70 ijt
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. 25kVA mm HxLxW
b. 30kVA mm HxLxW
c. 50kVA mm HxLxW
a. 25 kVA kg To be specified
b. 30 kVA kg To be specified
c. 50 kVA kg To be specified
Supplier's offer column must be properly filled with the right figures. "compliant, Yes, ", V 1 etc..." are not accepted.
Bidder signature:
Page35/70 /
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
50 kVA LII
75 kVA LII
1 Country to be specified
2 Manufacturer to be specified
4 Standard [C 60076
General
1. Tank
Page36/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
2. Sealing
Page37/70 tk
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
h. Vectorgroup li-O
a Servicevoltage(Un) kV 35(22)
Page 38 / 70 4t
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
e. Frequency Hz 50
4.3 Secondary
-25kVA kV 0.230
-50,75and100kVA kV 0.230/0.460
b. RatedMaximumVoltage(Um) kV 1
c. Powerfrequencywithstandvoltage(lmn) kV 3
a. 25 kVA 2.2%
b. 50kVA 2.4%
7. Tap changer
Page 39/70 N-
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
8. Losses To be specified
a. 25 kVA
• Noload W • ~120
• Load (75°C) • ~ 430
b. 50kVA
• Noload W • ~160
• Load (75°C) • ~ 679
c. 75 kVA
• Noload W • ~175
• Load (75°C) • ~ 730
d. 100 kVA
• Noload W • ~250
• Load (75°C) • ~ 1260
10 Accessokes
Page4O/70 M
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
-25kVA 2
a. Primary: A, B Yes
b. Secondary: (2 bushings) : a, b Yes
(3 bushings) : a, n, b Yes
• Manufacturer's name,
• Serial number,
• Year of manufacturing,
• Number of phases,
• Rated capacity,
• Rated frequency,
• Rated voltages,
• Rated currents
Vector group
\'è) Percentage impedance voltage at
\ rated current
Page 42 / 70 /J
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
• Type of cooling,
• Continuous ambient temperature at
which ratings apply,
• Top oil temperature rises at rated
load,
• Total weight,
• Volumeofoil,
• Weight of core and wind ings,
• Table of primary voltages at the 5
tapping positions,
• Connection diagram.
• Property of ELECTRICITE DU
CAM BODGE and [DC logo
•
10.7 Oil
a. New, unused, clean, standard mineral oil in
compliance with IEC 60296 and free from all Yes
traces of polychlorinated biphenyl (PCB)
com pounds.
a. 25kVA mm HxLxW
b. 50kVA mm HxLxW
c. 75kVA mm HxLxW
d. 100kVA mm HxLxW
a. 25 KVA kg To be specified
b. 50 kVA kg To be specified
c. 75 kVA kg To be specified
V
)
/
\
Page 43/70 /U ç1 2.0
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
Supplier's offer column must be properly filled with the right figures. "compliant, Yes, ", V, etc..." are not accepted.
Bidder signature:
Page44/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
1 Country to be specified
2 Manufacturer to be specified
I. General
1. Tank
Page45/70 1W
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
2. Sealing
Page46/70 1e
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
4.1 Primary
a. Servicevoltage(Un) kV 22
Page47/70 Ik L9 ..
Vrsior2
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
e. Frequency Hz 50
4.2 Secondary
a. Servicevoltage(Un) kV 0.23/0.40
7. Tap changer
Page48/70 !&-
EDC-DTS-MVOO1- Pole Mou nted Three-Phase and Two-Phase Outdoor Distribution Transformers
8. Losses To be specified
a. 50kVA
• Noload W • ~160
• Load (75°C) • ~ 950
b. 75 kVA
• Noload W • ~220
• Load (75°C) • ~ 1250
c. 100 kVA
• Noload W • ~250
• Load (75°C) • ~ 1550
d. 160 kVA
• Noload W • ~360
• Load (75°C) • ~ 2100
e. 200 kVA
• Noload W • ~450
• Load (75°C) • ~ 2500
f. 250 kVA
• Noload W • ~500
• Load (75°C) • ~ 2950
g. 315 kVA
• Noload W • ~600
• Load (75°C) • ~ 3500
h. 400 kVA
• Noload W • ~720
• Load (75°C) • ~ 4150
i. 500 kVA
• Noload W • ~860
• Load (75°C) • ~ 4950
j. 630 kVA
• Noload W • ~1010
• Load (75°C) • ~ 5850
9. Acoustic sound Level To be specified
a. 50 kVA dB(A) ~ 47
100 kVA
d 160 kVA dB(A) ~52 4
/ \Z4 \*
Page49/70 j1L
LQ
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
10. Accessories
Page5O/70 ,
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. Rated voltage 1 kV
Page5l/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. Rated voltage 1 kV
Page 52 / 70 4t.
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
• Type of transformer,
• Specification to which standard it
was manufactured,
• Manufacturer's name,
• Serial number,
• Yearofmanufacturing,
• Numberofphases,
• Rated capacity,
• Rated frequency,
• Rated voltages,
• Rated currents,
• Vector group,
• Percentage impedance voltage at
rated current,
• Type of cooling,
• Continuous ambient temperature at
which ratings apply,
• Top oil temperature rises at rated
load,
• Total weight,
• Volume of oil,
• Weight of core and wind ings,
• Table of primary voltages at the 5
tapping positions,
• Connection diagram.
• Property of ELECTRICITE DU
CAM BODGE and [DC logo
• nHiJ$nfl
Page 53/70 gk
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
10.6 Oil
a. New, unused, clean, standard mineral oil in
compliance with IEC 60296 and free from all To be specified
traces of polychlorinated biphenyl (PCB)
com pounds.
a. 50kVA mm HxLxW
b. 75kVA mm HxLxW
c. 100kVA mm HxLxW
d. 160kVA mm HxLxW
e. 200kVA mm HxLxW
f. 250kVA mm HxLxW
g. 315kVA mm HxLxW
h. 400kVA mm HxLxW
i. 500kVA mm HxLxW
j. 630kVA mm HxLxW
a. 50 kVA kg To be specified
b. 75 kVA kg To be specified
Supplier's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc..." are not accepted.
Page 55 / 70 iL
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
100 kVA
160 kVAL1
200 kVAL
250 kVAL1
315 kVALI1
400 kVA
500 kVALI
630 kVA
800 kVA
1000 kVAL1
1250 kVALI
1600 kVALI1
1 Country to be specified
2 Manufacturer to be specified
I. General
Page56/70 i&
EDC-DTS-MVOO1- Pole Mou nted Three-Phase and Two-Phase Outdoor Distribution Transformers
1. Tank
2. Sealing
Page57/70 4t
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. Thecoreand coilassemblyhavethecore
and coils rigidly connected to the tank and
Yes
shall not shift in any direction during
shipping, transportation, installation and
operation.
Page 58 / 70 &
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
h. Vectorgroup Dynli
(IEC 60076)
a. Servicevoltage(Un) kV 35
e. Frequency Hz 50
a. Servicevoltage(Un) kV 35(22)
e. Frequency Hz 50
4.3 Secondary
a. Servicevoltage(Un) kV 0.230/0.400
/
b. Rated Maximum Voltage(Um) kV 1 'f A
It 'I
c. Power frequency withstand voltage (rms) kV 3
Page 59 / 70 j11L
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. 50and75kVAtransformers 4%
6. Short-circuit performance
7. Tap changer
Page 60/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. 50kVA
• Noload W • ~170
• Load (75°C) • ~ 950
b. 75 kVA
• Noload W • ~235
• Load (75°C) • ~ 1250
c. 100 kVA
• Noload W • ~260
• Load (75°C) • ~ 1550
d. 160 kVA
• Noload W • ~370
• Load (75°C) • ~ 2100
e. 200 kVA
• Noload W • ~460
• Load (75°C) • ~ 2500
f. 250 kVA
• Noload W • ~520
• Load (75°C) • ~ 2550
g. 315 kVA
• Noload W • ~630
• Load (75°C) • ~ 3500
h. 400 kVA
• Noload W • ~75L
• Load(75 C) • ~4150 t
*
Page 61/70 /U ji
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
i. 500 kVA
• Noload W • ~900
• Load (75°C) • ~ 4950
j. 630 kVA
• Noload W • ~1050
• Load (75°C) • ~ 5850
k. 800 kVA
• Noload W • ~1270
• Load (75°C) • ~ 9900
I. 1000 kVA
• Noload W • ~1300
• Load (75°C) • ~ 12150
m. 1250 kVA
• Noload W • ~1530
• Load (75°C) • ~ 14850
n. 1600 kVA
• Noload W • ~1850
• Load (75°C) • ~ 17850
10 Accessories
Page 62 / 70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
-Brown color
c. Ratedmaximumvoltage(Um) kV 38or40.5
-Brown color
b Rated voltage 1 kV
Page64/70 h-
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. Rated voltage 1 kV
• 800,1000kVA :Fourcablesforeach
phase and two cables for neutral Yes /
I *
Page 65 / 70 I-
EDC-DTS-MVO01- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
a. Primary:A,B,C Yes
• Type of transformer,
• Specification to which standard it
was manufactured,
• Manufacturer's name,
• Serial number,
Yes
• Yearofmanufacturing,
• Numberofphases,
• Rated capacity,
• Rated frequency,
• Rated voltages,
• Rated currents,
• Vector group,
• Percentage impedance voltage at
rated current,
-.-Tpe of cooling,
4' ' • CoftiYuous ambient temperature at
whicii ratings apply
• Top oil temperature rises at rated
Ioad
Page 66 / 70 M-
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
• Total weight,
• Volume of oil,
• Weight of core and wind ings,
• Table of primary voltages at the 5
tapping positions,
• Connection diagram.
• Property of ELECTRICITE DU
CAM BODGE and [DC logo
•
10.7 Oil
a. 50kVA mm HxLxW
b. 75kVA mm HxLxW
c. 100kVA mm HxLxW
d. 160kVA mm HxLxW
e. 200kVA mm HxLxW
f. 250kVA mm HxLxW
g. 315kVA mm HxLxW
h. 400kVA mm HxLxW
i. 500kVA mm HxLxW
j. 630kVA mm HxLxW
k. 800kVA mm HxLxW
/
I. 1000 kVA mm H x L x W: ,
\_ 1
Page67/70 /1i,
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
m. 1250kVA mm HxLxW
n. 1600 kVA mm H xL xW
a. 50 kVA kg To be specified
b. 75 kVA kg To be specified
.ciiJer's offer column must be properly filled with the right figures. "Compliant, Yes, ", V, etc..." are not accepted.
4;5
Page 68/ 70 4L
EDC-DTS-MV001- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
The bidder shall list point after point and explain here in after all deviation from the requested
technical specification.
Bidder signature:
Page 69/70
EDC-DTS-MVOO1- Pole Mounted Three-Phase and Two-Phase Outdoor Distribution Transformers
15 ANNEX
The distribution transformers will be evaluated as the sum of the capital cost (adjusted for deviations
as necessary) plus the capitalized value of the losses, as guaranteed in the Technical data sheet using
the following formula:
Where: G is the capitalized value of the guaranteed losses, in accordance with the bidder offered
technical data sheets.
A is capitalized cost of one kW of load loss and B is the capitalized cost of one kW of no-load loss.
There will be no credit for losses less than the guarantee. If transformers exceed the maximum losses
requested values, the offer shall be rejected for non-responsiveness.
Page 70 I 70