KT800R Paperless Recorder Manual
KT800R Paperless Recorder Manual
Manual
KT800R
USER’S MANUAL
IM01C82R01-01E
First Edition
FOREWORD
Thank you for purchasing our paperless recorder!
This manual is about the functions, settings, wiring methods, methods of
operation, failure of treatment methods of the paperless recorder. To ensure correct
use, please read this manual carefully and use properly before operation and keep this
manual in a safe place for quick reference.
Notice
The contents of this manual are subject to change without prior notice as a result
of continuing upgrades to the instrument’s performance and functions.
Every effort has been made in the preparation of this manual to ensure the
accuracy of its contents. However, if you have any questions or find any errors,
please feel free to contact us.
Copying or reproducing all or any part of the contents of this manual without our
permission is strictly prohibited.
Revisions
February, 2012, First edition
I IM01C82R01-01E
SAFETY PRECAUTIONS
For your safe use of this instrument be sure to comply with the following safety
precautions. If the instrument is used in a manner not specified in this manual, the
protection provided by the instrument may be impaired. We assume no responsibility
for the customer’s failure to comply with these requirements.
WARNING
Power Supply
Before connecting the power cord, ensure that the power supply voltage matches the
voltage rating for the instrument.
Protective Grounding
Make sure to connect the protective grounding to prevent electric shock before
turning on the power.
Necessity of Protective Grounding
Never cut off the internal or external protective grounding wire or disconnect the
wiring of the protective grounding terminal. Otherwise, it will pose a potential shock
hazard.
Defect-Free Protection
Do not operate the instrument when the protective grounding might be defective. Also,
make sure to check them before operation.
Do Not Operate in Explosive Atmosphere
Do not operate the instrument in the presence of flammable, explosive gas or vapors.
In such circumstances the use of this instrument is very dangerous.
Do Not Remove Covers
Please do not tear down part of the front screws and open the front panel, because
some areas inside the instrument have high voltages .The cover should be removed by
our qualified personnel only.
External Connection
Connect the protective grounding before connecting to the items under measurement
or external control circuit connections.
Damage to the protection
Using the instrument in a manner not specified in this manual can damage the
instrument’s protection.
IM01C82R01-01E II
CHECKING THE CONTENTS OF THE PACKAGE
Unpack the wrapping box and check the contents before operating the instrument. If
some of the contents are not correct or missing or if there is any physical damage,
contact our company or the sales network from which you purchased it.
Accessories
The following accessories are supplied with the instrument. Make sure that all items
are present and undamaged.
III IM01C82R01-01E
Accessories (Sold Separately)
The following optional accessories are available for purchase separately. When
ordering, make sure whether there is a shortage or damage. For information about
ordering accessories, please contact us.
IM01C82R01-01E IV
HOW TO USE THIS MANUAL
This user's manual consists of the following 16 chapters:
Chapter Title and Contents
1 Overview of Functions
Describe the functions of the instrument
2 Before Using the Instrument
Describe the installation and wiring connection
3 Names of All Parts/ Mode of Usage/Common Operations
Describe the names of each part of the instrument, how to
use the storage medium drive, run mode, and common
key operations.
4 Switching Operation Screens
Describe how to use the operation screen such as the
trend display and digital display. Describes the
operations that can be performed using the arrow keys,
page key and the enter key on the front panel.
5 System Configuration and Its Function
Describe the related parameters of running system and its
functions
6 Record Configuration
Set the related parameters of the recording data
7 Input Configuration
Set the relevant parameters measured input channels
8 Output configuration
Set the relevant parameters of output transmitted
channel
9 Alarm Configuration
Set relevant parameters of alarms and relays.
10 Display configuration
Set related parameters of channel combinations and
display
11 Report Configuration
Set related parameters of channel accumulation and report
12 Print Configuration
Set related parameters of print function
13 Communication Configuration
Set parameters related to communications
14 Check System Information
Check system information, and AD board running
15 Import and Export Configuration File
Describe the import and export of configuration file
16 Specifications
List the specifications of the Paperless Recorder
V IM01C82R01-01E
Symbols Used in this Manual
Unit
K Denotes”1024”
k Denotes”1000”
M Denotes“1024K”
G Denotes“1024M”
B “Bytes”
Operation of Marks
The following symbols are used during the explanation of operation
[ ] : represents key’s name. Example: [Page] [En]
『』: represents a reference item. Example: 『Input Channel』
【】 : indicates screen element .Example: 【Device Name】
IM01C82R01-01E VI
FOREWORD ..........................................................................................................I
SAFETY PRECAUTIONS ................................................................................... II
CHECKING THE CONTENTS OF THE PACKAGE ........................................ III
HOW TO USE THIS MANUAL .......................................................................... V
CHAPTER 1 OVERVIEW OF THE FUNCTIONS ...................................................... 1
1.1 OVERVIEW OF THE INSTRUMENT ........................................................... 1
1.2 FUNCTIONS OF THE INPUT SECTION ...................................................... 2
1.3 DISPLAY FUNCTION .................................................................................... 4
1.4 STORAGE FUNCTION. ................................................................................. 6
1.5ALARM FUNCTION ....................................................................................... 7
1.6 REPORT FUNCTIONS (ADDITONAL SPECIFICATIONS) ........................ 8
1.7 OUTPUT FUNCTIONS (ADDITIONAL SPECIFICATIONS) ...................... 9
1.8 COMMUNICATION FUNCTIONS (ADDITIONAL FUNCTIONS) .......... 10
1.9 OTHER FUNCTIONS ................................................................................... 11
CHAPTER 2 INSTALLATION AND WIRING .......................................................... 12
2.1 INSTRUMENT SITE .................................................................................... 12
2.2 INSTALLING THE INSTRUMENT ............................................................. 13
2.3 THE ARRANGEMENT OF VARIOUS TERMINALS ................................ 15
2.4 INPUT AND OUTPUT SIGNAL WIRING .................................................. 16
2.5 ALARM OUTPUT WIRING (OPTION) ...................................................... 19
2.6 CONNECT POWER SUPPLY ...................................................................... 21
2.7 CONNECT SWITCHING VALUE ............................................................... 22
2.8 24VDC TRANSMITTER POWER WIRING(OPTION) ......................... 23
2.9 RS232C/RS485 COMMUNICATION WIRING ........................................... 24
2.10 CONNECT SPECIAL SERIAL PRINTER ................................................. 25
CHAPTER 3 NAMES OF PARTS/RUN MODE/COMMON KEY OPERATIONS .. 26
3.1 NAMES OF PARTS AND FUNCTIONS ...................................................... 26
3.2 INSERTING/REMOVING THE EXTERNAL STORAGE MEDIUM ........ 27
3.3 RUN MODE .................................................................................................. 28
3.4 CONFIGURING THE FUNCTIONS ............................................................ 29
3.5 COMMON KEY OPERATIONS................................................................... 30
CHAPTER 4 DISPLAY SCREENS AND ITS FUNCTION ....................................... 37
4.1 SWITCHING OPERATION SCREENS. ...................................................... 37
4.2 EXPLANATION OF THE STATUS DISPLAY SECTION .......................... 38
4.3 DIGTAL DISPLAY SCREEN ....................................................................... 39
4.4 BAR GRAPH DISPLAY ............................................................................... 41
4.5 REAL-TIME TREND SCREEN ................................................................... 43
4.6 HISTORY TREND SCREEN ........................................................................ 45
4.7 Function screen .............................................................................................. 49
4.8 FILE LIST ...................................................................................................... 50
4.9 STORAGE OPERATIONS ............................................................................ 51
4.10 DATA BACKUP .......................................................................................... 52
4.11 DATA PRINTING ........................................................................................ 54
4.12 ALARM SUMMARY .................................................................................. 55
4.13 ACCUMULATIVE REPORT ...................................................................... 56
4.14 POWER-DOWN RECORD......................................................................... 57
4.15 SYSTEM LOG............................................................................................. 58
4.16 LOG CONFIGURATION ............................................................................ 59
CHAPTER 5 SYSTEM CONFIGURATIONS AND ITS FUNCTION ...................... 60
5.1 SETTING THE DATE AND TIME ............................................................... 60
VII IM01C82R01-01E
5.2 SETTING THE DEVICE NAME .................................................................. 61
5.3 SETTING THE SYSTEM PASSWORD ....................................................... 62
5.4 SET SYSTEM LANGUAGE......................................................................... 63
5.5 SET REFERENCE JUNCTION COMPENSATION .................................... 64
5.6 IMPLEMENTATION OF THE FACTORY SETTINGS ............................... 65
5.7 IMPLEMENTION OF PURGING DATA ..................................................... 68
CHAPTER 6 SET RECORDS OF THE CONFIGURATION ..................................... 69
6.1 SET THE RECORD INTERVAL .................................................................. 69
6.2 SET UP RECORD TYPE .............................................................................. 70
6.3 SET UP AUTOMATIC BACKUP ................................................................. 71
6.4 SET RECORD MODE................................................................................... 72
6.5 SET TRIGGER CONDITIONS ..................................................................... 73
6.6 PURGE HISTORY DATA ............................................................................. 74
CHAPTER 7 SET THE INPUT CONFIGURATION ................................................. 75
7.1 SET INPUT TYPE AND SCALING ............................................................. 80
7.2. SET CHANNEL TAG ................................................................................... 81
7.3 SET THE CHANNEL UNIT ......................................................................... 82
7.4 SET THE CHANNEL ADJUSTMENT ......................................................... 83
7.5 SET BURNOUT TREATMENT.................................................................... 84
7.6 SET SQUARE ROOT COMPUTATIONS .................................................... 85
7.7 SET THE PARAMETERS OF CHANNEL FILTER .................................... 86
7.8 SET THE REMOVAL OF SMALL SIGNAL................................................ 87
7.9 COPY CHANNEL CONFIGURATION ........................................................ 88
CHAPTER 8 SET OUTPUT CONFIGURATIONS .................................................... 89
8.1SET THE OUTPUT CHANNEL .................................................................... 90
8.2 SET THE OUTPUT ADJUSTMENT ............................................................ 91
CHAPTER 9 SET ALARM CONFIGURATION ........................................................ 92
9.1 SET THE ALARM AND RELAY CONTRACT ........................................... 94
9.2 SET THE DELAY PERIOD OF RELAY OUTPUT ...................................... 95
9.3 SET THE HYSTERESIS OF ALARM LIMIT .............................................. 96
9.4 SET THE VARIATION OF ALARM TIME .................................................. 97
CHAPTER 10 SET THE DISPLAY CONFIGURATION ........................................... 98
10.1 SET BACKGROUND COLOR ................................................................... 98
10.2 SET SCREEN BRIGHTNESS AND FIRST SCREEN ............................... 99
10.3 SET THE DIRECTION OF CURVES ON THE PAPER .......................... 100
10.4 SET THE COMBINATION AND COLOR OF THE CHANNELS .......... 101
CHAPTER 11 SET THE REPORT CONFIGURATION .......................................... 102
11.1 SET THE CHANNEL ACCUMULATION, THE INITIAL VALUE,
MAGNIFICATION, DECIMAL DIGITS AND SETTLING TIME ................. 102
11.2 SET THE NUMBER OF THE SHIFT REPORTS, TIME AND DISPLAY
NUMBER .......................................................................................................... 104
CHAPTER 12 SET PRINTING CONFIGURATION ............................................... 105
12.1 SET KEY TRIGGER PRINT ..................................................................... 105
12.2 SET TIMER PRINGTING AND THE TIME ............................................ 106
CHAPTER 13 SET COMMUNICATIONS CONFIGURATION ............................. 107
13.1 SET ADDRESS.......................................................................................... 107
13.2 SET COMMUNICATION BAUD RATE .................................................. 108
13.3 SET COMMUNICATION CHECK........................................................... 109
13.4 SET THE ORDER OF BYTE-SWAPPING .............................................. 110
CHAPTER 14 CHECK SYSTEM INFORMATION ................................................ 111
IM01C82R01-01E VIII
14.1 CHECK SYSTEM INFORMATION ......................................................... 111
14.2 CHECK AD BOARD ................................................................................ 112
CHAPTER 15 IMPORT AND EXPORT CONFIGURATION FILES ...................... 113
15.1 EXPORT CONFIGURATION FILE ......................................................... 113
15.2 IMPORT CONFIGURATION FILE .......................................................... 114
CHAPTER 16 SPECIFICATIONS ............................................................................ 115
16.1 SIGNAL INPUT AND ALARM ................................................................ 115
16.2 DISPLAY FUNCTION .............................................................................. 117
16.3 DATA STORAGE FUNCTION ................................................................. 119
16.4 OTHER STANDARD FEATURES ........................................................... 120
16.5 CHOOSE ACCESSORIES ........................................................................ 121
16.6 GENERAL SPECIFICATIONS ................................................................. 123
16.7 EXTERNAL DIMENSIONS ..................................................................... 127
IX IM01C82R01-01E
CHAPTER 1 OVERVIEW OF THE FUNCTIONS
1.1 OVERVIEW OF THE INSTRUMENT
Unlike conventional record that record data on charts, the Instrument displays the
measured data in a LCD. Moreover, the measured data can also be saved to external
storage media such as U Disk (additional specifications).
Measured/ operational data can be used as displayed data stored in the memory, or
you can also insert the external storage to save it in the external storage media through
automatic or manual backup.
Displayed data is shown as curves and other data on meter screen. It is the data filter
out from the samples by the instrument. A datum is equivalent to a point on the curve
of the screen. The time of a datum is determined by recorded meter intervals.
Historical data is equivalent to the original recording paper, which is very suitable for
long-time observation.
1 IM01C82R01-01E
1.2 FUNCTIONS OF THE INPUT SECTION
Number of Measurement Channels/Scan Interval
The number of measurement channels can be selected from 1~48.
The scan interval of measurement is 1 second.
IM01C82R01-01E 2
Burnout
When measuring temperature with a thermocouple / thermal resistence /4-20mA/1-5V
signal, the instrument provides check burnout function. You can specify the
measurement result to be set to maximum of measurable range, minimum of
measurable range, last value or Error Flag*1. For the setting procedure, see section
『Burnout』
*1 when the burnout setting is Error Flag, the measured value is indicated as “-.--”.
Filter
The filter is used to suppress the disturbance that is curbing the signal. Filtering is
provided by the standard products. The filter can be set on each channel. For the
setting procedure, see section 『set filter parameter』.
3 IM01C82R01-01E
1.3 DISPLAY FUNCTION
Common items related to the display
TFT Color LCD and the Screen Configuration
The instrument has a 10.4 TFT color LCD (800-by-600 dot resolution).
The screen consists of the status display section and the data display section.
Group Display
The data displayed on the curve displays are the data of measurement or computation
channels that are assigned to the group. Up to 8 channels can be assigned to a single
group. For the procedure used to assign channels to groups, see section『configuration
display 』.
Up to 8 sets of combinations can be used in the digital screen, bar graph screen,
real-time curve screen and historical curve screen effectively.
IM01C82R01-01E 4
Run Mode
This mode is entered when the power is turned on.
Display various operation screens such as signal’s digital, alarm status, trend,
historical trend, alarm summary, data print (option), and data backup display (option).
Configuration screen
This instrument is in Configuration mode to set various functions.
Under Configuration mode, this screen is used to set system configuration, recording
configuration, input configuration, output configuration, alarm configuration, display
configuration, report configuration, print the configuration and communication
configuration parameters.
5 IM01C82R01-01E
1.4 STORAGE FUNCTION.
The instrument can save measured data and computed data, which are first acquired to
the instrument’s internal memory as display data. Then, the data are saved to the
external storage medium on paper. For detail, see sections『data backup 』 and
『recording configuration』 .
IM01C82R01-01E 6
1.5ALARM FUNCTION
Real-time data alarm can be set or alarm relay output (additional specifications). For
details, see section 『Setting Alarms』.
Number of Alarms
You can set up to four alarms for each channel.
High alarm (H)
An alarm occurs when the measured value is greater than or equal to the alarm value.
Low alarm (L)
An alarm occurs when the Measured value is less than or equal to the alarm value.
Incremental alarm (I)
An alarm occurs when increased measured value of the time point is greater than or
equal to the value of alarm value.
Reduction alarm (D)
An alarm occurs when reduced measured value of the time point is greater than or
equal to alarm value.
Alarm Accessibility
Use the following auxiliary functions
Functional Content
Transfinite alarm Hysteresis Set any hysteresis within the range
Setting the length of incremental alarm
Incremental Alarm Time
time
Setting the length of reduced alarm
Reduced alarm time
time
Alarm relay output When alarm occurs, output contacts
(additional specifications) signal
Alarm display
Show alarm state in the digital display screen, bar screen and real-time curves of
screen, and display the icon of output relay in the System Column.
7 IM01C82R01-01E
1.6 REPORT FUNCTIONS (ADDITONAL
SPECIFICATIONS)
The Accumulation computation and reports can be performed, but the monthly
cumulative maximum value is no more than 999,999,999, otherwise the report is
invalid.
Accumulation Computation
The accumulation computation is performed every second.
The accumulation computation can be performed on each measurement channel.
For detail, see section『Report Setting』
Report function
Based on total accumulated data to show generated shift reports, hourly reports, daily
and monthly reports and to keep the data up to 410 days.
Class report: According to the number of class and time settings to show the
cumulative amount of each shift.
Horly report: Show the cumulative amount generated per hour.
Daily report: Shows the cumulative amount generated every day.
Monthly report: Shows the cumulative amount generated per month.
IM01C82R01-01E 8
1.7 OUTPUT FUNCTIONS (ADDITIONAL
SPECIFICATIONS)
Measured and Computed data can be transmitted and output as an analog signal.
Transmitter Output
The signal type of transmitter output is 4-20mA.
The instrument provides 8 channels transmitter output.
The maximum load of each channel is 750Ω.
For detail, see section『 Output Configuration Setting』
9 IM01C82R01-01E
1.8 COMMUNICATION FUNCTIONS (ADDITIONAL
FUNCTIONS)
The instrument can communicated with PC via serial cable(RS232C/RS485) . And
also can print data by micro printer.
RS232C/RS485 Communications
RS232C or RS485 can be select when the instrument communicates with PC.
By using the wired network (485 networks), radio, GPRS, Modem and other methods,
connect to the computer.
The Instrument adopts the international common standards: MODBUS-RTU
communication protocol.
The OPC software also provides for users, you can use it to connect the he
configuration software.
IM01C82R01-01E 10
1.9 OTHER FUNCTIONS
24 VDC Power Supply for Transmitter (Option)
The instrument provides 6 channels power supply of 24 VDC. The maximum current
of each channel can be provided is 60mA.
This instrument supports 2-wire 4-20mA current input. For the wiring method, please
refer to 『24VDC Power Supply for Transmitter』
11 IM01C82R01-01E
CHAPTER 2 INSTALLATION AND WIRING
2.1 INSTRUMENT SITE
Installation location
Install the instrument in a location that meets the following conditions.
Instrument panel
The instrument is designed for panel mounting.
Location of installation
To prevent rain and direct heat, install the instrument indoors.
Well-ventilated location
To prevent overheating, install the instrument in a well-ventilated location.
Minimum mechanical vibrations
Choose an installation location with the minimum mechanical vibration.
Horizontal
Install the instrument horizontally (However, the instrument can be inclined up to 30
degrees backwards for panel mounting).
Note
Condensation may occur if the instrument is moved to another
place where both the ambient temperature and humidity are higher,
or if the temperature changes rapidly. In addition, measurement
errors will result when using thermocouples. In this case, let the
instrument adjust to the new environment for at least one hour
before using the instrument.
The lifetime of the LCD may be shortened (lower picture quality,
etc.) if the instrument is used in a high-temperature environment
over a long period of time. When installing the instrument in a
high-temperature environment (greater than 40°C), please don not
do it.
IM01C82R01-01E 12
2.2 INSTALLING THE INSTRUMENT
Warning
In order to prevent electric shock, be sure to turn off the power
before the installation.
Installation Procedure
The instrument should be mounted on a steel panel of thickness 1 mm to 10 mm.
1. Insert the instrument from the front side of the panel.
2. As shown in the figure below, mount the instrument to the panel using the mounting
brackets that came with the package.
●Use two brackets under the cover of the instrument
●The screws of instrument panel mounting bracket are the standard M4 screws.
Installation diagram
Positioning
13 IM01C82R01-01E
IM01C82R01-01E 14
2.3 THE ARRANGEMENT OF VARIOUS TERMINALS
Due to different configurations, the arrangement of every instrument for the wiring
terminal in various channels is different. Please refer to the terminal graph on the
terminal cover.
When relay loop number is more than 24, signal terminal 4 will function as the alarm
terminal.
15 IM01C82R01-01E
2.4 INPUT AND OUTPUT SIGNAL WIRING
Precautions to be taken while wiring
Take the following precautions when wring the input signal cables.
It is recommended that crimp-on lugs (designed for 4 mm screws) with insulation
sleeves be used on the lead wire ends.
crimp-on lugs (designed for 4 mm screws) with
insulation sleeves be used on the lead wire ends.
When using the thermocouple input, take measures to stabilize the temperature
at the input terminal.
Always use the input terminal cover.
Do not use thick wires which may cause large heat dissipation (cross sectional
area 0.5mm2 or less recommended).
Make sure that the ambient temperature remains reasonably stable. Large
temperature fluctuations can occur if a nearby fan turns ON or OFF.
Connecting the input wires in parallel with other devices can cause signal
degradation, affecting all connected devices.
If you need to make a parallel connection, then
Ground the instruments to the same point.
Do not turn ON or OFF another instrument during operation. This can have
adverse effects on the other instruments.
RTD cannot be wired in parallel.
Current signal cannot be wired in parallel.
WARNING
To prevent electric shock, ensure the main power supply is turned OFF
IM01C82R01-01E 16
Wiring Method
1. Turn OFF the instrument and remove the input terminal cover.
2. Connect the input/output signal wires to the input/output terminals.
3. Fit with the rear terminal cover and supply electricity.
17 IM01C82R01-01E
Wiring diagram
IM01C82R01-01E 18
2.5 ALARM OUTPUT WIRING (OPTION)
WARNING
To prevent electric shock, ensure the main power supply is turned
OFF.
If a voltage of more than 30 VAC or 60 VDC is to be applied to the
alarm output terminal, use ring-tongue crimp-on lugs with
insulation sleeves on all terminals to prevent the wires from
slipping out when the screws become loose. Furthermore, use
double-insulated wires (dielectric strength of 2300 VAC or more)
for the signal wires on which a voltage of more than 30 VAC or 60
VDC is to be applied. For all other wires, use basic insulated wires
(dielectric strength of 1350 VAC). To prevent electric shock, attach
the terminal cover after wiring and make sure not to touch the
terminals.
Wiring Procedure
1. Turn OFF the instrument and remove the cover for the rear terminal.
2. Connect the alarm output cables to the terminal.
3. Replace the terminal cover and fasten it with screws.
CAUTION
Remove the rear terminal cover to wire easily. In order to prevent poor
contact, tighten the screws after wiring
.
Relay Specifications
Item Content
Output Relay transfer contact ( switchable)
Output capacity 250VAC/3A
30VDC/3A
Dielectric 500VAC/one minute
19 IM01C82R01-01E
The contact arrangement of alarm relay ( e.g. the maximum channel number
36-way)
* Note
When the relay way is more than 24, signal terminal 4 will function as alarm terminal.
Wiring diagram
IM01C82R01-01E 20
2.6 CONNECT POWER SUPPLY
Here explains power wiring method. Be sure to read this part before connecting
power.
WARNING
To prevent electric shock, ensure the main power supply is turned
OFF.
To prevent fire, use doubled-insulated wire
Make sure to earth ground the protective earth terminal through a
grounding resistance less than 10Ω before turning ON the power.
Use crimp-on lugs (designed for 4mm screws) for power and
ground wiring termination.
Make sure to provide a power switch (double-pole type) on the
power supply line in order to separate the instrument from the main
power supply. Put an indication on this switch as the breaker on the
power supply line for the instrument.
Switch Specification Rated current: 3A or more
Connect a fuse (between 2A and 15A) to the power line.
Wiring Procedure
1. Connect the power supply wires and the protective ground wire to the power
terminals.
2. Turn on the power.
Relay Specifications
Item AC supply
Input voltage 85VAC ~ 265VAC
Input frequency 50Hz
21 IM01C82R01-01E
2.7 CONNECT SWITCHING VALUE
Switching value (digital) input can be used as the trigger conditions of the batch
records. As for the related settings, please see "record configuration" section. Be sure
to read this section before connecting input signal line of switching value.
Wiring
1. Turn off the power and remove the rear terminal cover.
2. Connect digital input signal line and the switching value input terminal line.
3. Install the rear terminal cover, and turn on the power
Contact specification
Item Content
external Connect electrical level input terminal and
signal line termianl2 D+ terminal, and connect ground wire
and 2D- terminal。
Set the trigger of instrument record as “ on-off”.
When the electrical level input terminal is high
level ( more than 4 V and less than 24V), the
instrument stops recording; if it is low level
( less than 2 V), the instrument starts recording.
IM01C82R01-01E 22
2.8 24VDC TRANSMITTER POWER WIRING(OPTION)
Transmitter power output
CAUTION
●Never short-circuit the power supply terminals or apply an external
voltage, otherwise damage to the instrument may result.
Wiring Procedure
1. Turn OFF the instrument and remove the cover of the rear terminal.
2. Connect the power line of transmitter to the output terminal.
3. Fit with the terminal cover and turn on the power.
Wiring diagram
23 IM01C82R01-01E
2.9 RS232C/RS485 COMMUNICATION WIRING
This instrument provides a serial interface, and type ( RS 232C/ RS 485 ) can be
ordered according to the specification
RS232C interface
Pin
Signal Name Description
number
Receive data from the RS232 interface,
2 RXD
and the instrument input signal
Send data to the RS232 interface, and the
3 TXD
instrument output signal
RS485 interface
Communication Specifications
Item Content
Speed(baud 1200/2400/4800/9600/19200/38400/57600/115200
rate)
Data format Eight data bits,One stop bit
Optional checkout code(None/odd/even)
IM01C82R01-01E 24
2.10 CONNECT SPECIAL SERIAL PRINTER
This section will explain how to connect serial printer. Be sure to read it before
connecting.
Wiring method
The terminal arrangement of serial printer interface
Explanation
The instrument and printer is connected through the printer special interface.
The instrument doesn’t need to set any parameter, so it can print when connected
to the printer.
25 IM01C82R01-01E
CHAPTER 3 NAMES OF PARTS/RUN
MODE/COMMON KEY OPERATIONS
3.1 NAMES OF PARTS AND FUNCTIONS
Front Panel
IM01C82R01-01E 26
3.2 INSERTING/REMOVING THE EXTERNAL
STORAGE MEDIUM
This section describes the procedures to insert and remove the external storage
medium.
USB disk and SD card can be used as external storage medium.
For the handling procedure of the storage medium, see section 『back up history
data』.
Procedure
Inserting the storage medium
1. Open the front cover. Insert the U disk and SD card into the USB port.
2. The instrument detects the U disk and SD card in the drive automatically.
3. Enter Backup screen, and prepare to back up data.
CAUTION
Keep the front cover closed during operation except when
accessing the external storage medium. This will protect the storage
medium and the drive from particles such as dust.
Keep the metal face upper when inserting the U disk, otherwise the
U disk can’t be inserted.
If you are using a commercially available U disk or SD card, be
careful of static electricity.
It is recommended using our company's products.
CAUTION
The access lamp is lit while the storage medium is being accessed.
A message “Data are being saved to the medium.” is displayed
while data are being saved to the medium.
Description
Formatting external storage media
Use the external storage medium which has been formatted.
Please use the PC to carry on the formatting for the USB flash drives and choose
FAT 32 system, because this product doesn’t provide the formatted function.
Specification
Item Content
USB port Support the USB 2.0 protocol. The maximum
capacity is 4GB
SD card port Standard SD card, support SDHC [Link]
maximum capacity is 4GB
27 IM01C82R01-01E
3.3 RUN MODE
There are two run modes: operating and setting. This section describes the functions
and relationships of the two modes.
Mode Types
IM01C82R01-01E 28
3.4 CONFIGURING THE FUNCTIONS
Setting Mode
The configuration mode is used to set the various parameters of the running
system.
Note
Change some system parameters will affect the data acquisition. We
Suggest backing up data before the change.
Setting Items
User can carry out the following content in configuration mode:
Setting system parameters
Setting display parameters
Setting signal input parameters
Setting analog output parameters
Setting alarm parameters
Setting accumulation and reports parameters
Setting print parameters
Setting communication parameters
Clearing data in the instrument
Checking instrument hardware information and firmware
29 IM01C82R01-01E
3.5 COMMON KEY OPERATIONS
This section describes common key operations which are often used.
[Left and right key] [Left key] [Right key]
[Up and down key] [Up key] [Down key]
In the run mode, press the [PAGE] to switch to the function screen
Select Function screen
1. Use the[up and down ] button and [left and right] button to move the cursor
2. Use the [Enter] to enter the corresponding screen
IM01C82R01-01E 30
Function key operation
Click the corresponding function button below the screen to perform the
operation.
31 IM01C82R01-01E
Key operations in the configuration mode
Entering the configuration mode
1. Under the running mode, Press [Page] and [Enter] to enter the configuration
screen.
2. Move the cursor and press the [Enter] to enter in the function screen
3. Move the cursor and press the [Enter] to enter different configuration screens.
Confirming operation
Press [Enter] to enter the target operation screen
IM01C82R01-01E 32
Modifying the parameter
There are three types of the revisable parameters, namely, to adjust the input
parameters, edit the input parameters and select input parameters.
Move the cursor to the parameters which need editing, then an input panel will
pop up after pressing [Enter], and the user can input.
33 IM01C82R01-01E
Procedure
[Left][Right][Up][Down] :Move the cursor to the soft key area (including
character soft key input and Pinyin Chinese character selection).
[En]: Input the character to the input field, which under the place of cursor.
[Function Key]: the related operation in the corresponding function soft key:
[F1] : switch the input method( switching input method)
[F2]: 【Delete】(delete the last character in the input window)
[F3]和[F4]: no operation;
[F5]: 【Cancel】( canel all the editing operation and exit the inout panel);
[F6] : 【Finish】( finish the editing content and exit the input panel)
IM01C82R01-01E 34
Input Chinese characters
Used in inputting unit, tag, etc.
Operation
1. Use the [left] [right] to move the cursor to the alphabet ‘z’, use the [En],the
phonetic show bar display” z”, It is the same case with the operation of
alphabet 'i'.
2. Use the [Page Down] to jump the cursor to columns “selecting Chinese
characters” (also can use the [left and right key] and [up and down key])
3. Use the [up and down keys] to accented characters, which show icon
characters.
4. Use the [left and right button] to move the cursor to the character "Zi", use the
[En] to select.
5. Use the [Up] and [Down] to jump the cursor to the [En] (can also use the [left
and right button]), and use [En] to confirm exit.
35 IM01C82R01-01E
Examples
Revise unit to "wan m3 / h"
Enter "3"
Select a “special Input Method”: Move the cursor with [Left and right] button,
[Enter] to select.
Select special character "3": [left and right button] to move the cursor, [Enter]
to select.
IM01C82R01-01E 36
CHAPTER 4 DISPLAY SCREENS AND ITS
FUNCTION
4.1 SWITCHING OPERATION SCREENS.
This chapter describes the screen (operation screen) used to display the measured /
computed data.
The operation screens are composed of digital display, bar, real-time trend, history,
function screen.
Alarm summary, data print (additional function) and backup (additional function), the
cumulative report (additional specification) , power-down recording and system logs
and other screens enter through the data query screen.
37 IM01C82R01-01E
4.2 EXPLANATION OF THE STATUS DISPLAY
SECTION
The following information is displayed in the status display section during the
operation mode and the configuration mode.
1 2 3 4 5 6 7 8
A C
B D
IM01C82R01-01E 38
4.3 DIGTAL DISPLAY SCREEN
The digital displays measured / computed data. On the way of display, please refer
to the section 『switch to run the screen』.
Use [up and down keys] to switch displayed combinations .It can display up to 8
[Link] display of combinations don’t show configuration, skip this display
combinations.
The order to switch combination is shown in the following picture:
Use [Enter] to start or stop the automatic switching function of display combinations,
every 5 seconds automatically switch to the next combination curve, with a status bar
icons.
Screen dispays as follows:
1. Show combination numbers in the title bar, all channels show 【Device name】
2. Channel tag, can be set. With regard to setting method, See section『Channel Tag
and Unit Setting』
3. Measurement of channel /computed data. Blue is Normal, red is alarming
Note
Measure the channel’s data display
When measuring data of measurement channel anomalies (see below), the
screen shows measurements for -.--.
Data exception
4-20 mA : signal is bellow2 mA.
1-5V: measured signal is bellow 0.5V, and the [burnout] display an error flag
The thermocouple burnout, and the [burnout set] display an error flag.
The thermal resistence burnout, and the [burnout set] display an error flag.
39 IM01C82R01-01E
4. Channel accumulation value. It displays when the user selects [channel
accumulated] function.
5. Channel unit can be set. With regard to setting method, see section『Channel Tag
and Unit Setting』
6. Alarm symbol. 4-channel alarm can be set up, Green is normal, red is alarm.
IM01C82R01-01E 40
4.4 BAR GRAPH DISPLAY
Bar graph displays the measured / operated data. On the way to show, please refer to
『switch running screen』
Using [up and down keys] to switch combinations of display. It can display up to 8
[Link] display of combinations don’t show configuration, skip this display
combinations.
The order to switch combination is shown in the following picture:
Use [Enter] to start or stop the automatic switching function of display combinations,
every 5 seconds automatically switch to the next combination curve, with a status bar
icons.
Example of screen display is shown in the following picture:
41 IM01C82R01-01E
When measuring data of measurement channel anomalies (see below), the
screen shows measurements for -.--.
Data exception
4-20 mA : signal is bellow2 mA.
1-5V: measured signal is bellow 0.5V, and the [burnout] display an error flag.
The thermocouple burnout, and the [burnout set] display an error flag.
The thermal resistence burnout, and the [burnout set] display an error flag.
5. Channel unit can be set. With regard to setting method, see section『Channel Tag
and Unit Setting』
6. Alarm symbol. 4-channel alarm can be set up, green is normal, red is alarm. The
place in which the warning signs are located in the bar is where the alarm sets
limits in the range of the position, which is only effective against H/L alarm.
IM01C82R01-01E 42
4.5 REAL-TIME TREND SCREEN
The waveform displays measured / operated data. On the way to show, please refer to
『switch running screen』
Using [up and down keys] to switch combinations of display. If display of
combinations don’t show configuration, skip this display combinations.. When all the
combinations show no configuration, each 8-channel has circular display according to
the order of combination of channels.
Combined mode of curve cycle
Use [Enter] to start or stop the automatic switching function of display combinations,
every 5 seconds automatically switch to the next combination curve, with a status bar
icons.
An example of Real-time curve show (vertical)
43 IM01C82R01-01E
An example of Real-time curve show (horizontal)
9. Channel unit can be set. With regard to setting method, see section『Channel Tag
and Unit Setting』
10. Scale. Display the percentage of the trend.
Curve refresh: every pixel in the timeline of LCD screen timeline represents a record
of each interval. Each interval in the curve moves once.
IM01C82R01-01E 44
4.6 HISTORY TREND SCREEN
Display the measured / operated data stored in the memory with historical curve.
On the way to show, please refer to 『switch running screen』
There exist two methods to search historical data. One is continuous and the other is
fixed point. Historical Curves show no alarm.
Curve direction on paper is according to the configuration display, with horizontal or
vertical two options.
45 IM01C82R01-01E
Procedure:
Cursor searching state
Switching curve combination
Using [up and down keys] to switch combinations of display. If display of
combinations don’t show configuration, skip this display [Link] all
the combinations show no configuration, each 8-channel has circular display
according to the order of combination of channels.
Searching mode
Searching mode operation
Use [left and left button] to move the cursor to the searching time, use the [up and
down keys] to set the date and time to the required searching time, then press
[Enter key], the trend will be automatically moved to the set point in time, and the
searching point is at the far right of the screen.
Scaling curve
Use [Left] [Right] to move the cursor to the curve of cycles, and use [Up] [Down]
to adjust zoom curve.
IM01C82R01-01E 46
Show or hide a curve
Use [Left] [Right] to move the cursor to the curve show / hide, press [Up] or
[down], you can hide or show the curve.
Procedure:
Cursor state
Switching curve combination
Using [up and down keys] to switch combinations of display. If display of
combinations don’t show configuration, skip this display [Link] all
the combinations show no configuration, each 8-channel has circular display
according to the order of combination of channels.
47 IM01C82R01-01E
Non-combined cycle mode of curve
Cursor state
Uses [Up] and [Down] to move cursor so that forward or backward searching is
available. Long press [up and button] can accelerate continuous mode.
Scaling curve
Use [Left] [Right] to move the cursor to the curve of cycles, and use [Up] [Down]
to adjust zoom curve.
IM01C82R01-01E 48
4.7 FUNCTION SCREEN
This section describes the screen entrance for the instrument internal data (historical
data, alarm list, accumulation, accumulative statements, power-down recording and
system logs) to back up, print, view, etc.
Operation:
Use [left and right button] to move the cursor
Use [Enter key] to enter the corresponding screen
49 IM01C82R01-01E
4.8 FILE LIST
This section shows file storage and file storage status information.
On the display method, see the section『switch run screen』
1. Number: Records arranged by time, the nearer it occurs, the farther it is arranged.
2. Starting time: the starting time of data record in the file.
3. End time: the end time of data record in the file.
4. Status: Display the current state of file records, and the file state is as follows:
Being recorded: the file is recording data;
Manually stopped: because of changes in the configuration data or manually key
operation, file stops recording;
Power-down stop: due to power down, file stops recording;
Alarm stop: due to alarm cancellation, the file stops recording;
Switch stop: because the external switching device is disconnected , the file stops
recording;
Time stop: because the file reaches the set time for the end, it stops recording.
5. Key operation: Use the [up an down keys] to move the arrow to the file number
you want to view;
Press [F1] ( [trend] )to the historical trend screen for viewing the historical trend
data, and then use the [Page] to return to the file list screen;
press [F2 ] ([backup] )to the history data backup screen for a single file to back up
it . Then, use the [Page ] to return to the file list screen;
press [F3 ] ([print] )to data print screen . Then, use the [Page] to return to the file
list screen;
Press [Page] or [F6] ([Exit] key )to return to the current file list screen.
IM01C82R01-01E 50
4.9 STORAGE OPERATIONS
This section displays record configuration information and file storage, for the
recording configuration, please refer to the section『record configuration
setting』 .
On the display method, please refer to『switch run screen』
51 IM01C82R01-01E
4.10 DATA BACKUP
This section describes how to use the U disk and SD card to backup historical data.
On the way to show, please see the section and 【Switching the running screen 】
Procedures:
1. Properly connect U disk or SD card, then there is a corresponding connection
icon display in the system column.
2. Use [up and down keys] to select the backup contents, including all historical
data, historical data for single file, alarm recording, power-down record, the
IM01C82R01-01E 52
system log, accumulative shift report, the accumulative daily report,
accumulative monthly and accumulative annual report.
3. When backing up historical data for single files, use the [up and down keys]
to modify the file index, and make sure the backup start time and end time.
4. Modify the folder name or file name, use the [up and down keys] to adjust the
file number, use the [Enter key] to edit the file name.
5. Back up data, move the cursor to 【Backup (USB)】 or 【Backup (SD)】
button, press [Enter key] to back up data.
6. Back up all the historical data, the file storage path is / DATA /】 【Device
name】 / folder name; back up other data, the file storage path is / DATA /
【Device name】 / file name, for the【Device name】, Please check the system
configuration screen.
7. Use the [Page key] to return to data query screen.
53 IM01C82R01-01E
4.11 DATA PRINTING
This section describes how to use the mini-printer to print historical data.
On the way to display, please see the section 『switching the running screen』
Steps:
1. Connect mini-printer properly.
2. Set the start time and end time.
3. Set print channel (or combination) and print interval.
4. Printing curves or data.
5. Use [Page ] to return to data query screen.
Description
Connect the instrument and the printer through the special interface.
IM01C82R01-01E 54
4.12 ALARM SUMMARY
Display channel alarm information and relay output state. It can save up to 256 pieces
alarm information.
On the way to display, please see the section and 『switching the running screen』
1. Channel sequence number:Records are arranged according to the stack, the closer
time of occurrence is, the more pre-arranged it is.
2. Status: Displays the current record status, alarm, or report cancel
3. Channel: Displays the channels of current record
4. Alarm type. Display the alarm type. Figures represent the 4-way alarm in the
number of (1-4), the letter on behalf of alarm type (H, L, I, D).
5. Alarm time. Displayed the alarm occur
6. Relay state. Display current relay output state.
7. Menu: Use the [Enter key] to enter: Press [backup key] to the backup screen for
the alarm record backup; Press [Exit] to return to the current alarm record screen.
8. Use [left or right button] or [up and down keys] to inquire next page
9. Use [Page] to return to data query screen
55 IM01C82R01-01E
4.13 ACCUMULATIVE REPORT
According to the related setting of report configuration and current query range,
display accumulative report ( yearly report+ monthly report+ daily report and monthly
report+ shift report).
On the way to display, please see the section 『switching the running screen』
Operation instruction:
Channel: use the [Up and down keys] to modify the channel.
Type: Use the [Up and down keys] to select the display type of report
combinations, and use the [Enter] key to start the query.
Time: Use the [Up and down keys] to select the time for report query.
Function keys: Press the [last month], or [the next month] to switch the month;
press [ backup ] to skip to data backup screen for accumulative shift report
backup; press [Print], using the mini-printer to print the screen display content;
press [Exit] or [page] to return to the function screen.
IM01C82R01-01E 56
4.14 POWER-DOWN RECORD
Display time of power-down and power-on records, including the power-down and
power-on time, power-down frequency and the total time of power-down. It can save
up to 512 power-down record.
On the way to display, please see the section 『switching the running screen』
1. Channel sequence number:Records are arranged according to the stack, the closer
time of occurrence is, the more pre-arranged it is.
2. Power-down time: Power-down time of the Instrument.
3. Power-on time: power-on time of the Instrument.
4. Total power-down: the total number of power-down, accumulate each
power-down time for display.
5. Menu: Use the [Enter key] to enter: Press [backup key] to the backup screen, for
the power-down record backup; Press [Exit] to return to the current power-down
record screen.
6. Use [left or right button] or [up and down keys] to inquire on next page
7. Use [Page] to return to data query screen.
57 IM01C82R01-01E
4.15 SYSTEM LOG
Display related log of instrument operation.
On the way to display, please see the section 『switching the running screen』
Operation:
Use [left and right button] or [up and down keys] to inquire on next page
Use [Page] to return to data query screen.
IM01C82R01-01E 58
4.16 LOG CONFIGURATION
This section describes how to log configuration.
Operation
Press the [next page] plus [En] to enter the login screen, enter the password, If the
password is correct then display configuration entry, select the appropriate
configuration entry to set the configuration; password error could not enter.
Press 【Quit】 button to exit configuration and enter the running screen.
59 IM01C82R01-01E
CHAPTER 5 SYSTEM CONFIGURATIONS AND
ITS FUNCTION
5.1 SETTING THE DATE AND TIME
Set the date and time of the instrument.
Procedure
Enter 【system configuration】screen, the method to enter please see “log
configuration”.
Date Time: This field is to set meter’s current date and time.
1. Use the [left and right button] to move the cursor to the【System time】
column.
2. Use the [up and down keys] to modify date and time.
3. Confirming operation
After the parameter setting, select 【Exit】there is a Frame.
Select 【Yes】 to save setting content, and exit [System] screen.
Select 【No】 to cancel setting content, and exit [System] screen.
Select 【Cance】 to continue setting parameters in [System] screen.
Caution
After setting system date / time, those historical data stored in
instrument is invalid.
New and effective data begins after setting system date / time.
Before setting system date / time, please back up history data.
After setting the system date / time, it is recommended that the
instrument should purge the data.
IM01C82R01-01E 60
5.2 SETTING THE DEVICE NAME
Set the device name; display it on the title bar.
Use that name to create the directory of data backup and automatic backup .
Operation
Enter 【System configuration screen】, the method to enter please see “log
configuration”.
61 IM01C82R01-01E
5.3 SETTING THE SYSTEM PASSWORD
System password is used to modify configuration parameters and prevent the system
parameters from being accidentally modified.
System password is six digits.
Operation
Enter 【System configuration screen】 , the method to enter please see “log
configuration”.
NOTE
The system password is the only password which can enter the system
configuration to modify parameters. If it is lost, modification is
unavailable.
The initial password is 000000, after the purchase please change
password as soon as possible, and properly preserve it.
IM01C82R01-01E 62
5.4 SET SYSTEM LANGUAGE
Display language (Chinese and English).
Operation
Enter 【System configuration screen】 , the method to enter please see “log
configuration”.
63 IM01C82R01-01E
5.5 SET REFERENCE JUNCTION COMPENSATION
Reference junction compensation can tune compensation temperature value of
thermocouple
Operation
Enter 【System configuration screen】 , the method to enter please see “log
configuration”.
IM01C82R01-01E 64
5.6 IMPLEMENTATION OF THE FACTORY SETTINGS
This section describes the instrument functions of the factory settings and parameters
of reset value.
This will clear all stored data in memory of the instrument, including historical data,
the total cumulative amount, cumulative reports, alarm list, power-down records, but
the system log is not cleared.
Operation
Enter 【System configuration screen】 , the method to enter please see “log
configuration”.
65 IM01C82R01-01E
Reset instrument of configuration parameter values, please see the following table:
IM01C82R01-01E 66
Automatic
30 No
backup
Trigger
31 Power-down
condition
32 Relay delay 4s
33 Alarm hysteresis 0.00
34 I alarm time 1s
Alarm
35 R alarm time 1s
configuration
36 Alarm type None
37 Alarm value 0.00
38 relay None
39 Digit precision 2
40 Settle time 00:00
Number of shift
41 3
report
First shift
42 Display tag Second shifr
Third shift
Report
00:30~08:30
configuration
43 Starting time 08:30~16:30
16:30~00:30
44 Accumulation Close
Initial value of
45 0.00
accumulation
Accumulative
46 1.00
ratio
47 Key print No
Print
48 Time print No
configuration
49 Time interval 00:02(H:M)
Communication
50 001
Address
Communication
51 Bytes exchange 2-1 4-3
configuration
52 Baudrate 115200
53 Parity None
67 IM01C82R01-01E
5.7 IMPLEMENTION OF PURGING DATA
This section describes the instrument functions of purging data.
Clear all stored data in memory of the instrument, including historical data, the total
cumulative amount, cumulative reports, alarm list, power-down records, but the
system log is not cleared.
Operation
Enter 【System configuration screen】 , the method to enter please see “log
configuration”.
1. Use the [ F2] to move the cursor to the 【Purge data】 button.
2. Use the [En] to clear data function.
3. Pop up a confirmation dialog box.
Select【Yes】, implement data- clearing.
Select【Cancel】or【No】, give up clearing data.
IM01C82R01-01E 68
CHAPTER 6 SET RECORDS OF THE
CONFIGURATION
6.1 SET THE RECORD INTERVAL
This section describes the settings of historical data records interval. Optional
recording interval: 1 second, 2 seconds, 5 seconds, 10 seconds, 30 seconds, 1 minute,
2 minutes, 5 minutes, 10 minutes, 30 minutes.
Operation
Enter 【record configuration screen】 ,the method to enter please see “log
configuration”.
69 IM01C82R01-01E
6.2 SET UP RECORD TYPE
This section describes setting and recording methods of historical data in the
instrument.
When the recording interval is more than 1 second, depending on the recording
method to select and calculate real-time value and record the calculated values.
Optional Recordings are: real-time values, average, maximum and minimum values.
Real-time value: Direct take the records of time corresponding to real-time value.
Average: take the average of real-time data before and after the recording points.
Maximum: Take the maximum real-time value before and after the recording data
points
Minimum: Take the minimum real-time value before and after the recording data
points
Operation:
Enter 【Record configuration screen】 , the method to enter please see “log
configuration”.
Recording type: This column is used to set recording method. ( It can choose
real-time value, maximum value, minimum value, and average value)
1. Use the [left and right button] to move the cursor to the 【Record type】
column.
2. Use the [up and down keys] to select recording method.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 70
6.3 SET UP AUTOMATIC BACKUP
This section describes the principle and setting methods of historical data automatic
backup.
Automatic backup: every day at 0:00 the instrument will automatically back up the
history data to SD card; when stop recording or reach the trigger conditions set by the
user, the instrument will automatically back up historical data to the SD card.
Automatic backup file storage directory:
1. Every day at 0:00 backup file storage directory: DATA / 【Device Name】/
instrument date (year _month) / AUTO_ date (day). RDZ
2. Other automated file storage directory: DATA /【Device Name】/ instrument date
(month _year) / day / instrument time (hours _ minutes_ second). RDZ
Operation
Enter 【record configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to 【Auto backup】 column.
2. Use the [left and right keys] to open or turn off the automatic backup
function.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
71 IM01C82R01-01E
6.4 SET RECORD MODE
This section describes the method of instrument record mode setting.
There are 2 types of recording modes: circular and non-circular.
Circular: When the record in the last file of the instrument is full, it will continue to
record from the first file, the file will record historical data circularly according to the
way in which the new file replaces the old.
Non-circular: When the instrument records at the last file is full, and then it will stop
recording automatically
Operation
Enter 【Record configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to 【Record type】 column.
2. Use the [left and right keys] to select record type: circular or non-circular.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [Configuration] screen.
Select【No】to cancel setting content, and exit [Configuration] screen.
Select【Cancel】to continue setting parameters in [Configuration] screen.
IM01C82R01-01E 72
6.5 SET TRIGGER CONDITIONS
This section describes the method of trigger conditions setting.
Trigger conditions include: manual trigger, alarm, relay, switch, timing, power.
Manual: enter the instrument storage interface, you can manually start or stop data
storage recording.
Alarm: can be set only when one channel occurs alarm, then start recording data
storage; when the alarm stops, then stop recording.
Relay: can be set only when one channel’s alarm occurs, then start recording data
storage; when the relay stops alarm, then stop recording.
Switch: Meter is connected to an external switch equipment, when the switch is on,
the began recording data storage, and when switch is off , then stop recording data
storage.
Timing: Timing cycles is fixed at 24 hours. Set start time and end time so that the
instrument only records the data storage in the set time every day.
Power: when the instrument is powered on, it will automatically create a new file and
start recording data.
Operation
Enter 【Record configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to 【Trigger condition】 column.
2. Use the [up and down keys] to select trigger condition.
3. Confirming operation
After the parameter setting, select [Exit] there is a Frame.
Select【Yes】to save setting content, and exit [Configuration] screen.
Select【No】to cancel setting content, and exit [Configuration] screen.
Select【Cancel】to continue setting parameters in [Configuration] screen.
73 IM01C82R01-01E
6.6 PURGE HISTORY DATA
This chapter describes the method for purging recording data.
It only purge the history data in the memory , the total accumulation, accumulative
reports, alarm list, power-down record,but the system log is not cleared.
Operation
Enter 【Record configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [ F1] to move the cursor to the【Purge History record】 button.
2. Use the [Enter key] to purge the data function
3. Confirming operation
Select【Yes】to purge data
Select【Cancel】or【No】to give up purging data
IM01C82R01-01E 74
CHAPTER 7 SET THE INPUT CONFIGURATION
This chapter describes the channel type, signal type, the relationship between the
signal range and range display, and the computing part of the channel involved
Note: The thermal resistance and thermocouple signal range can not be changed;
project quantity is the directly measured temperature.
Linear operation
Semaphore transforms to project quantity according to the signal range and
practical range of linear
100℃
10mA
4mA
0℃
0mA 0mA 0℃
75 IM01C82R01-01E
Ordinary vacuum operation
Semaphores and vacuum degree of logarithm has a linear relationship, signal
range in the overall signal is free to set, the project range is expressed by 10 of the
index form, ranging from 10E-9.999 to 10E9.999.
Sub-vacuum operation
According to the vacuum degree of order , divide it into a number of sections , the
corresponding signal of endpoint in every section and the vacuum degree has
a linear relationship, at the same time, corresponding signal in the same section
and the vacuum have a linear relationship too. Signal range in the overall signal
is free to set; the project range is expressed by 10 of the index form, ranging from
10E-9.999 to 10E9.999.
IM01C82R01-01E 76
20mA 100℃
50℃
8mA
4mA 0℃
(8 - 4)
50℃ = (100 - 0)* +0
(20 - 4)
Filtering operation
Filter parameters range from 0.0 seconds to 9.9 seconds .Take an example when
the filter parameters is1.0 seconds
f * S0 + S1
Result
1+f
= 7.5mA
Line Regulation
Quantities according to the formula x = K * x + B linear adjustment.
Burnout treatment,
The project quantity approach to deal with signal even break off, options are:
maximum, minimum, to maintain the data, error markers, error markers. When
choose error markers, collected data is the marked value.
77 IM01C82R01-01E
Channel types and the computation relationship
Reference Removal of Filter Square Specific Adjust treatment
junction small-signal root calculation linear of burnout
compensation
Current Linear
operation
voltage Linear
operation
Resistance Linear
operation
frequency Linear
operation
Thermal
Resistance
Thermocouple
Ordinary General
vacuum Vacuum
IM01C82R01-01E 78
Signal Type Measurement Range
Type Range
0-20mA -20mA ~ 20mA
4-20mA 4mA ~ 20mA
0-10mA -10mA ~ 10mA
0-5V -5V ~ 5V
1-5V 1V ~ 5V
0-10V -10V ~ 10V
20mV -20mV ~ 20mV
100mV -100mV ~ 100mV
400Ω 0 ~ 400Ω
175Ω 0 ~ 175Ω
Fr 0 ~ 10KHz
Fr. 0.0~3000.0Hz
PT100 -200℃ ~ 650℃
PT100. --50℃ ~ 150℃
Cu50 -50℃ ~ 150℃
Cu53 -50℃ ~ 150℃
BA1 -200℃ ~ 650℃
BA2 -200℃ ~ 650℃
S -50℃ ~ 1768℃
R -50℃ ~ 1768℃
B 250℃ ~ 1817℃
K -200℃ ~ 1372℃
N -200℃ ~ 1300℃
E -200℃ ~ 1000℃
J -210℃ ~ 1200℃
T -200℃ ~ 385℃
WRE5-26 0℃ ~ 2310℃
WRE3-25 0℃ ~ 2310℃
F1 700℃ ~ 2000℃
F2 700℃ ~ 2000℃
Note:
Channel tag: 15 characters in length mixed in English and Chinese
Channel unit: Not involved in operations, only display, 7 characters in length,
support mixed English and Chinese symbols and special characters.
Channel decimal point: The calculation and display precision, 0 to 3
decimals.
Signal range: Within the entire range of signal, it is free to set signal
acquisition range.
Project Range: According to the project need, it is to be set free, -9999 ~
30000, the decimal point 0 to 3.
79 IM01C82R01-01E
7.1 SET INPUT TYPE AND SCALING
This section describes the channel type and range setting method.
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Channel close】, use the
[up and down keys] to open or close the channel.
2. Use the [left and right button] to move the cursor to the 【Channel type】, use the
[up and down keys] to select channel type.
3. Use the [left and right button] to move the cursor to the 【Signal type 】, use the
[up and down keys] to select signal types.
4. Use the [left and right button] to move the cursor to the 【Precision】, use the [up
and down keys] to adjust channel decimal point.
5. Use the [left button] to move the cursor to the 【Signal scale】, use the [En] to edit
data, use the [up and down keys] to tune the data.
6. Use the [left and right button] to move the cursor to the【Display scale】,
use the [En] to edit data, use the [up and down keys] to tune the data.
7. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
Note: The thermal resistance and thermocouple signal range cannot be changed.
IM01C82R01-01E 80
7.2. SET CHANNEL TAG
This section describes how to set the channel tag.
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the【Tag 】
2. Use the [En] to edit bit number.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
Note: The channel tag, 15 characters in length, mixed in English and Chinese.
81 IM01C82R01-01E
7.3 SET THE CHANNEL UNIT
This section describes how to set the channel engineering units.
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Unit】.
2. Use the [up and down keys] to select a common unit.
3. Use the [En] to edit a custom unit.
4. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
Note: The channel unit is not involved in operations, only display, 7 characters in
length, supporting mixed English and Chinese symbols and special characters.
IM01C82R01-01E 82
7.4 SET THE CHANNEL ADJUSTMENT
This section describes the channel linear adjustment.
Formula: project quantities= k × Quantities + b.
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the linear【Adjust(kX+b)】.
2. Use the [up and down keys] to tune data; use the [En] to edit data.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
83 IM01C82R01-01E
7.5 SET BURNOUT TREATMENT
This section describes how to deal with burnout. Burnout treatment is effective on the
III type signal, thermal resistance and thermocouple signal.
Treatment methods: minimum, maximum, maintaining, -. -- (error flag).
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Burnout 】
2. Use the [up and down keys] to choose approach.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 84
7.6 SET SQUARE ROOT COMPUTATIONS
This section describes set the square root computations of channels. To operational
principle please see 『set the channel type and range』 .
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to 【Channel type】
2. Use the [up and down keys] to choose the square root for the channel type.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
85 IM01C82R01-01E
7.7 SET THE PARAMETERS OF CHANNEL FILTER
This section describes the channel filtering settings. Setting theory of filtering
operation please see 『6.1』” channel types and range”.
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Filter】.
2. Use the [up and down keys] to adjust the filter time parameter, ranging from 0.0
seconds ~ 9.9 seconds.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 86
7.8 SET THE REMOVAL OF SMALL SIGNAL
This section describes the setting of channel small-signal removal function. Resection
of the small-signal operation principles please refer to 『6.1』”set the channel type
range”.
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Cut】.
2. Use the [up and down keys] to adjust removal, general signal is 0.0% ~ 9.9%, the
frequency signal is frequency value: 0 ~ 99Hz.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
87 IM01C82R01-01E
7.9 COPY CHANNEL CONFIGURATION
This section describes the channel configuration replication.
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Channel】.
2. Use the [up and down keys] to select the source- channel.
3. Use the [F1] to execute【Copy xx】key, and copy the configuration parameter in the
current channel.
4. Use the [up and down keys] to select the source channel.
5. Use the [F2] to execute 【Paste】key, and copy the source channel configuration to
the current channel configuration.
IM01C82R01-01E 88
CHAPTER 8 SET OUTPUT CONFIGURATIONS
This chapter describes the principle and setting method of output transmission.
According to the source-channel project quantity and project range, to output a linear
4-20mA transmission,
Support the output kX + b adjustment, the source input channel can be set freely. Up
to 8-channel can perform transmission output.
20mA 20mA
100℃
K*x+B
0℃
4mA 4mA
89 IM01C82R01-01E
8.1SET THE OUTPUT CHANNEL
This section describes the setting method of transmission output channel.
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Channel】.
2. Use the [up and down keys] to select the output source channel or turn off the
output.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 90
8.2 SET THE OUTPUT ADJUSTMENT
This section describes the setting methods of transmission output adjustment.
The formula: new output current = k × original output current+ b.
e.g
If the original channel scale is 0 ~ 100℃, and the current scale is 25℃, adjust K=2.00
and b = 3.00, then
Before adjusting, output = (25 / (100 - 0) * (20 – 4) + 4) mA = 8mA
After adjusting, output= = K × output + b = 2.00 * 8mA + 3.00 = 19mA
Operation:
Enter 【Input configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Channel】.
2. Use the [up and down keys] to tune data, and use [En] to edit data
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
91 IM01C82R01-01E
CHAPTER 9 SET ALARM CONFIGURATION
This chapter describes the alarm principle, relay contacts and set methods.
The amount of channel project within a certain range of values performs alarm and
relay output. Optional alarm types are: H, L, I, D. 4-way alarm for each channel.
H Alarm:
When the project is greater than or equal to alarm value which has been set, alarm
occurred. After alarm generated, the project is less than the amount or equal to (alarm
value - hysteresis), then eliminate alarm.
H alarm
hysteresis
alarm value
L Alarm:
When the project is less than the amount equal to the alarm value, the alarm occurred.
After alarm generated, the project is greater than or equal to (alarm value + hysteresis),
then eliminate alarm.
L alarm
hysteresis
alarm value
I alarm:
The project difference (V2 - V1) of a specific time interval point (t2 and t1) is greater
than or equal to alarm value which has been set, alarm occurred.
I alarm
t1 t2 t
IM01C82R01-01E 92
D Alarm:
The project difference (V2 - V1) of a specific time interval point (t2 and t1) is greater
than or equal to alarm value which has been set, alarm occurred.
D alarm
V1
set changed value
t1 t2 t
Relay Delay: Relay delay time after the occurrence of an alarm, 0-10 seconds
(optional). (Valid for all alarms)
Hysteresis: hysteresis range of H/L‘s eliminating alarms (All channels is uniform)
I Alarm Time: Alarm interval time of I. (All channels is uniform)
D Alarm Time: Alarm interval time of D. (All channels is uniform)
Relay Output: corresponding relay to alarm. Optional 1-12 or 1-8, when multiple
alarms use the same one relay output, Use the stack output.
Each alarm action and eliminating actions will have reported alarm information to
form a warning list. The maximum of alarm list is 256.
93 IM01C82R01-01E
9.1 SET THE ALARM AND RELAY CONTRACT
This section describes the setting methods of alarm parameters and relay contacts.
Operation:
Enter 【Alarm configuration screen】 ,the method to enter please see “log
configuration”.
1. Use [left and right button] to move the cursor to the 【Channel】,use the [up and
down keys] to select channel configuration.
2. Use the [left and right button] to move the cursor to the 【Type】, use the [up and
down keys] to select alarm type and shut down alarm.
3. Use the [left and right button] to move the cursor to the 【Alarm value】, use the
[up and down keys] tune data; use the [En] to edit data.
4. Use the [left and right button] to move the cursor to the 【Relay】,use the [up and
down keys] to select relay contact number, OFF stands for closure; R1 ~ 12 stands
for the corresponding relay output.
5. Confirming operation
Press [F6] to execute【Exit】, and select [Exit] there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 94
9.2 SET THE DELAY PERIOD OF RELAY OUTPUT
This section describes the time delay settings method of relay.
Operation:
Enter 【Alarm configuration screen】 ,the method to enter please see “log
configuration”.
1. Use [left and right button] to move the cursor to the 【Relay delay】.
2. Use the [up and down keys] to adjust the output delay time, ranging from 0 to 10
seconds.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
95 IM01C82R01-01E
9.3 SET THE HYSTERESIS OF ALARM LIMIT
This section describes the setting method of hysteresis of alarm limit; hysteresis
parameters are only valid for HL alarm.
Operation:
Enter 【Alarm configuration screen】,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the【Hysteresis】.
2. Use the [up and down keys] tune data; use the [En] to edit data.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 96
9.4 SET THE VARIATION OF ALARM TIME
This section describes setting method of the changes in the amount of alarm hysteresis.
Incremental alarm periods is effective to I alarm, reduced alarm time is effective to D
alarm.
Operation:
Enter 【Alarm configuration screen】,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【I Alarm Time】, use the
[up and down keys] to adjust the alarm time, the scope is 1 ~ 32 seconds.
2. Use the [left and right button] to move the cursor to the 【Reduced Alarm Time】,
use the [up and down keys] to adjust the alarm time, the scope is 1 ~ 32 seconds.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
97 IM01C82R01-01E
CHAPTER 10 SET THE DISPLAY
CONFIGURATION
This chapter describes the applications of channel combination.
According to the channel combinations, Digital display screen, Bar graph screen,
real-time curve screen and the historical curve screen have data or curves display;
default settings without channel combinations, digital screen and bar diagram show in
full-screen channel, real-time curve screen and the historical curve screen are in
accordance with 4-way channel to display as a set of cycles. Details please refer to the
screen description.
Operation
Enter the 【Display configuration】 screen , For the methods to enter, please refer
to the section『 log configuration』 .
1. Use the [left and right button] to move the cursor to the【Background color】.
2. Use the [up and down keys] to select direction: white or black;
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [Configuration] screen.
Select【No】to cancel setting content, and exit [Configuration] screen.
Select【Cancel】to continue setting parameters in [Configuration] screen.
IM01C82R01-01E 98
10.2 SET SCREEN BRIGHTNESS AND FIRST SCREEN
This section describes the setting method of the startup screen brightness and the first
screen display when the instrument starts.
Operation
Enter the 【Display configuration】 screen , For the methods to enter, please refer
to the section『 log configuration』 .
1. Use the [left and right button] to move the cursor to the【Screen brightness】, and
use the [up and down keys] to adjust the screen brightness, range from 0 to 10.
2. Use the [left and right button] to move the cursor to the 【The first screen】, and
use [the up and down keys] to select the first screen display when the meter starts.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [Configuration] screen.
Select【No】to cancel setting content, and exit [Configuration] screen.
Select【Cancel】to continue setting parameters in [Configuration] screen.
99 IM01C82R01-01E
10.3 SET THE DIRECTION OF CURVES ON THE PAPER
This section describes the setting method of curve direction on the paper.
Operation
Enter the 【Display configuration】 screen , For the methods to enter, please refer
to the section『 log configuration』 .
1. Use the [left and right button] to move the cursor to the【Direction】.
2. Use the [up and down keys] to choose the direction, horizontal or vertical
(optional).
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 100
10.4 SET THE COMBINATION AND COLOR OF THE
CHANNELS
This section describes the setting methods of combination of channels.
Operation
Enter the 【Display configuration】 screen , For the methods to enter, please refer
to the section『 log configuration』 .
1. Use the [left and right button] to move the cursor to the 【Group】, use the [up and
down keys] to choose serial number.
2. Use the [left button] to move the cursor to the 【Channel】, use the [up and down
keys] to select open or close channel.
3. Use the [left and right button] to move the cursor to the 【Color】, optional colors:
red, green, blue, yellow, blue, [Link] the [up and down keys] to select channel
color.
4. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
101 IM01C82R01-01E
CHAPTER 11 SET THE REPORT
CONFIGURATION
11.1 SET THE CHANNEL ACCUMULATION, THE
INITIAL VALUE, MAGNIFICATION, DECIMAL DIGITS
AND SETTLING TIME
This section describes the setting method of cumulative channel, the cumulative initial
value, cumulative magnification and settling time.
Accumulative Initial value: initial value of accumulation begins to accumulate.
Accumulative Rate: According to the normal rate of a cumulative accumulation to
multiply.
Purge accumulation: Clear the accumulated amount of the current channel.
Decimal digits: set the decimal digits for the accumulative value of all channels.
Settle time: from the setting settler time to the next one, which can be regarded as one
day accumulation when starting the accumulation function.
Operation:
Enter 【Report configuration screen】,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【decimal digits】., use the
[up and down keys] to adjust, range from 0 to 2.
2. Use the [left and right button] to move the cursor to the【Settle time】 , use the [up
and down keys] to adjust settle time, range from 00 to 23.
3. Use the [left and right button] to move the cursor to the 【Channel 】. Use the [up
IM01C82R01-01E 102
and down keys] to select the channel.
4. Use the [left and left button] to move the cursor to 【Accumulation】. Use the [up
and down keys] to select to open or close the accumulative function.
5. Use the [left and right button] to move the cursor to the【Initial 】, use the [up and
down keys] to tune data, use the [En] to edit data, ranging from 0 to 999999.00.
6. Use the [left and right button] to move the cursor to the【Magnification】, use the
[up and down keys] to tune data, use the [En] to edit data, ranging from 0.00 ~
999999.00.
7. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
103 IM01C82R01-01E
11.2 SET THE NUMBER OF THE SHIFT REPORTS,
TIME AND DISPLAY NUMBER
This section describes the number of shift reports and time and setting methods.
The number of shift report: the number of classes per day, range from 2 to 5.
Shift: start time and end time of every class, 24-hour clock.
Operation:
Enter 【Report configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to 【Shift number】, use the [up
and down keys] to choose the number of shift reports, five shifts are the largest.
2. Use the [left and right button] to move the cursor to the 【Display number】, and
use the Enter button to edit the shift report to show the display number.
3. Use the [left and right button] to move the cursor to the 【Start time】, use the [up
and down keys] to adjust the frequency of time.
4. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 104
CHAPTER 12 SET PRINTING CONFIGURATION
12.1 SET KEY TRIGGER PRINT
This section describes the key trigger printing functions and settings methods.
Key trigger print: In the digital display screen, Bar graph screen, real-time curve
screen, using the [Left] to trigger button printing, and then print the real-time data and
cumulative amount.
Operation:
Enter 【Print configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the 【Key trigger print】, use
the [up and down keys] to open or close button printing functions.
2. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
105 IM01C82R01-01E
12.2 SET TIMER PRINGTING AND THE TIME
This section describes the timer printing functions and settings methods.
Timer Print: each day, choose 00: 00:00 as the starting time and print real-time data
and accumulation according to time intervals.
Operation:
Enter 【Print configuration screen】 ,the method to enter please see “log
configuration”.
1. Use the [left and right button] to move the cursor to the【Timer Print】, use the [up
and down keys] to close to open timing printing functions.
2. Use the [left and right button] to move the cursor to the【Interval】, use the [up and
down keys] to adjust the print interval time in the format X/hour, X/minute.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 106
CHAPTER 13 SET COMMUNICATIONS
CONFIGURATION
13.1 SET ADDRESS
This section describes the setting method of ModbusRTU mailing address.
Operation:
Enter 【Communication configuration screen】 ,the method to enter please see
“log configuration”.
1. Use the [left and right button] to move the cursor to the 【Address】.
2. Use the [up and down keys] to modify the mailing address, ranging from 0 to 247.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
107 IM01C82R01-01E
13.2 SET COMMUNICATION BAUD RATE
This section describes the setting method of serial communication baud rate.
Baud rate: 1200,2400,4800,9600,19200,38400,57600,115200. The default value is
115200.
Operation:
Enter 【Communication configuration screen】 ,the method to enter please see
“log configuration”.
1. Use the [left and right button] to move the cursor to the【Baud rate】.
2. Use the [up and down keys] to select communication baud rate.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 108
13.3 SET COMMUNICATION CHECK
This section describes the setting method of serial communication check.
Parity: no parity, odd parity, even parity.
The default value is no check
Operation:
Enter 【Communication configuration screen】 ,the method to enter please see
“log configuration”.
109 IM01C82R01-01E
13.4 SET THE ORDER OF BYTE-SWAPPING
This section describes the setting method of ModbusRTU 32-bit data byte-swapping.
In order to be suitable for ModbusRTU communication protocol, it provides
byte-swapping functions.
Byte-swapping: 1-2, 3-4, 2-1 4-3, 3-4 1-2, 4-3 2-1. The default value is 2-14-3.
Operation:
Enter 【Communication configuration screen】 ,the method to enter please see
“log configuration”.
1. Use the [left and right button] to move the cursor to the 【Byte swap】.
2. Use the [up and down keys] to choose byte-swapping method.
3. Confirming operation
After the parameter setting, select【Exit】there is a Frame.
Select【Yes】to save setting content, and exit [System] screen.
Select【No】to cancel setting content, and exit [System] screen.
Select【Cancel】to continue setting parameters in [System] screen.
IM01C82R01-01E 110
CHAPTER 14 CHECK SYSTEM INFORMATION
14.1 CHECK SYSTEM INFORMATION
This section describes how to check system information, and instrument setting.
Operation:
Enter 【System configuration screen】 ,the method to enter please see “log
configuration”.
111 IM01C82R01-01E
14.2 CHECK AD BOARD
This section describes the methods to check the status of AD board.
Operation:
Enter 【System configuration screen】 ,the method to enter please see “log
configuration”.
Blue Text (1: R7A8C: 8) is the inherent information in AD, black text (R7A8C: 8)
is the current AD board information, if there is any difference between them, this
shows that AD board failure, please contact the manufacturer for maintenance.
IM01C82R01-01E 112
CHAPTER 15 IMPORT AND EXPORT
CONFIGURATION FILES
15.1 EXPORT CONFIGURATION FILE
This section describes the instrument configuration file export functions and operation
methods.
Configuration file export, you can set up the information of the current instrument
channel, including input configuration, recording configuration, alarm configuration,
and export it to root directory of the external storage media .
Operation
Enter 【System configuration】 screen, for the method to enter, please refer to
the section『 log configuration 』.
1. Use the [left and right button] to move the cursor to 【Device 】, use the [up and
down keys] to select the connected backup storage media U disk / SD card; use
the [left and right button] to move the cursor to the 【File name】 ,and use the [up
and down keys] or [Enter button] to modify the file name; use the [left and right
button] to move the cursor to 【Export configuration】,use the [Enter key] to
export configuration.
2. Show the configuration file export situation.
3. Use the [left and right button] to move the cursor to the 【Exit】,and use [Enter key]
to exit the configuration file screen
113 IM01C82R01-01E
15.2 IMPORT CONFIGURATION FILE
This section describes the import meaning and operation method of configuration file.
Import the configuration file: To set the configuration of multiple models of the same
configuration, you can only configure one of the instrument configuration . You can
export the configuration file of this instrument, for the configuration file export ,
please refer to the section 『configuration file export 』,and for the remaining
instrument , they only need to import configuration file ,which makes multi-channel
configuration simplier.
Operation
Enter 【system configuration 】, the method to enter , please refer to the section
『 log configuration』.
1. Use the [left and right button] to move the cursor to the 【Device】, use the [up and
down keys] to select the connected backup storage media U disk / SD card; use
the [left and right button] to move the cursor to the 【File name】, and use the [up
and down keys] to confirm the imported file name; use the [left and right button]
to move the cursor to the 【Import configuration】, and use the [Enter key] to
import the configuration.
2. Show the configuration file import situation.
3. Use the [left and right button] to move the cursor to the 【Exit】,and use [Enter
key] to exit the configuration file screen.
IM01C82R01-01E 114
CHAPTER 16 SPECIFICATIONS
16.1 SIGNAL INPUT AND ALARM
Measurement input
Item Specifications
The number of simultaneously measuring up to 48 input channels
input channels
Measurement 1 second
period
Signal type DC current (I), DC voltage (V), thermocouple (TC), thermal
resistance (RTC), frequency (FR)
Input measurement range and the measurable range
Type Range Measurable range
Current 4-20mA 4.00mA ~ 20.00mA
0-20mA -20.00mA ~ 20.00mA
0-10mA -10.00mA ~ 10.00mA
Voltage 1-5V 1.000V ~ 5.000V
0-5V -5.000V ~ 5.000V
0-10V -10.00V ~ 10.00V
20mV -20.00mV ~ 20.00mV
100mV -100.00mV ~ 100.00mV
resistence 400Ω 0.0Ω ~ 400.0Ω
175Ω 0.0Ω ~ 175.0Ω
Digital signal FR 0Hz ~ 10000Hz
FR. 0.0Hz~3000.0Hz
RTD PT100 -200.0℃ ~ 650.0℃
PT100. -50℃ ~ 150.0℃
Cu50 -50.0℃ ~ 140.0℃
Cu53 -50.0℃ ~ 150.0℃
BA1 -100℃ ~ 600℃
BA2 -100℃ ~ 600℃
Thermocouple S -50℃ ~ 1768℃
R -50℃ ~ 1768℃
B 250℃ ~ 1820℃
K -50℃ ~ 1300℃
N -200℃ ~ 1300℃
E -100℃ ~ 1000℃
J -100℃ ~ 1000℃
T -200℃ ~ 400℃
WRE5-26 0℃ ~ 2310℃
115 IM01C82R01-01E
WRE3-25 0℃ ~ 2315℃
F1 600℃ ~ 2000℃
F2 600℃ ~ 2000℃
Measuring current: I = 0.25mA (resistance, heat resistance)
Thermocouple Choose the maximum, minimum, error flag or keeping the former
burnout displayed value
check current: About 2.5uA
Item Specifications
Thermocouple Using internal cold junction compensation, the compensation
cold junction accuracy :±0.5 ℃
compensation
Digital filter 0 ~ 9.9 seconds inertia filter
Vacuum
operation
General LOG curve is used in the whole range
algorithm
Sub-algorithm linear operation is used in every section
Alarm
Item Specifications
The number of Each channel has 4 alarm
alarms
alarm type High highalarm type , high alarm, I alarm , D alarm
Alarm delay 0-10s
time
Alarm output Alarm outputs to the internal relay
Internal relay number: 36 Or 24 ( If the channel number is more
than 36, it is 24, otherwise, it is 36)
Internal relay operations: OR operation
Display When alarm occurs, the corresponding screen displays the alarm
status; the status display section displays the alarm icon.
Alarm Display alarm log in the alarm list
information
IM01C82R01-01E 116
16.2 DISPLAY FUNCTION
Display
Item Specifications
Display * 10.4-inch TFT color LCD display (800× 600 points)
Display color 256 colors
Display Information
Item Specifications
Display channel Channels will be allocated to real-time curve and historical curve
group show and then display
group Number 8
the number of channels which an be allocated to each group
≤8
Real-time curve
display
Renewal rate 1 record interval
Waveform 1 pixel
width
Display method Display perpendicular axes with timeline (T) and the
measurement axis (Y)
Layout: horizontal, vertical
Div Curve cycle: recording interval × 60 div
Scale To display each channel (0% ~ 100%)
Digital Display Display measured values with digital
Update Rate 1 second
Bar graph Display measurement on the bar graph
display
Update Rate 1 second
ruler 0% ~ 100%
Historical curves Display stored data in the memory
show
Timeline can enlarge one times / 2 times / 4 times / 8 times / 16 times / 32
operation times
Alarm list Display up to 256 alarm records
display
117 IM01C82R01-01E
Other displayed information
Item Specifications
Channel-bit 7 Chinese characters or 15 letters(numbers)
Channel units Three Chinese characters 7 letters (numbers)
Status display Show the status of this instrument in the upper part of the display
section screen
Display content Searching status、 Display screen name, card status, alarm status,
SD card status, USB device status, circular display status, year,
month, day, hour, minute, seconds
Automatic At the specified time interval to switch display groups
switch of Show Time interval: 5 seconds
group
Language Simplified Chinese, English
System Show the number of input and output card channels, relay output
information channels, instrument additional features, firmware version,
display production date and released date
IM01C82R01-01E 118
16.3 DATA STORAGE FUNCTION
Setting
Item Specifications
External storage Back up the record data in the device
media
Media U Disk, SD card
Capacity Up to 4GB( U disk), 4 GB (SD card)
File format FAT32
Data type
Item Specifications
Data Size
Sampled data 2 bytes/ data values
Cumulative 8 bytes/ data values
amount
Data Format Binary Data
The sampling Equal to recording interval
period
Recording Always recording
method
Recording type Intermittent storage
119 IM01C82R01-01E
16.4 OTHER STANDARD FEATURES
Time-related functions
Item Specifications
Clock Can operate in 2000 ~ 2099
Clock Accuracy ±10ppm (0 ~ 50 ℃), does not include the delay caused by the
error when the power is on(less than 1 second )
Life of Clock About 10 years ( under room temperature)
battery
IM01C82R01-01E 120
16.5 CHOOSE ACCESSORIES
Alarm output relay
Item Specifications
Action Output relay contacts signal from the back panel of the terminal
when alarm occurs
Output points Normally open contact :
36 (input channel ≤ 36)
36 (input channels> 24)
Relay electric 250VAC(50/60Hz)/3A,250VDC/3A((load resistance))
shock rating
Output Type Normal open or closed
Relay Operation OR operation
RS232C/RS485
Item Specifications
Physic level RS-232、RS485(option)
Protocol MODBUS-RTU
Communication 1200/2400/4800/9600/19200/38400/57600 bps
rate
Byteswap 2-1 4-3、1-2 3-4、4-3 2-1、3-4 1-2
Data length 8bits
Stop bit 1bit
Parity bit 1bit
parity None/ odd/ even parity
24VDCPower Distribution
Item Specifications
Loop 6
Output voltage 24VDC±10%
Maximum output 60mADC(overload protection current: approximately 90mADC)
current
Allowed ≤ 750Ω
impedance
121 IM01C82R01-01E
USB Function
Item Specifications
USB port Compatible with USB2.0 protocol
Number of ports 1
Capacity Maximum: 4 GB
Power Supply 5V±10%,100mA
Devices can be U disk
connected
SD card function
Item Specifications
SD card port Compatible with SD protocol( NOT SDHC)
Number of ports 1
Capacity Maximum: 4 GB
Devices can be SD card
connected
IM01C82R01-01E 122
16.6 GENERAL SPECIFICATIONS
Frame
Item Specifications
Installation Embedded instrument panel installation (vertical plane)
Angle Allow for a maximum of 30 degrees after the tilt from horizontal
Plate thickness 2 ~ 10mm
of installation
Material Panels and Terminal Material: ABS plastic
Shell: Aluminum alloy
External 288(W)×288(H)×245(D)(D:the length from the installation panel
dimensions to terminal)
Weight About 9 Kg(cluding configuration)
Power
Item Specifications
Rated supply 220VAC
voltage
Allowed voltage 85VAC ~ 220VAC
range
Rated power 47-63Hz
frequency
Power ≤20W(including the matching function)
consumption
123 IM01C82R01-01E
Insulation
Item Specifications
Resistance Measurement input terminals:: 400V
voltage Between protective ground and measured terminal: 1000V
Grounding Grounding resistance ≤ 10Ω
resistance
IM01C82R01-01E 124
Electrical characteristic
125 IM01C82R01-01E
Frenquency input board
Item Specification
Channel number 8 channel/ per board
Low level Minimum:-5V,Maximun2V
High level Minimum:4V,Maximun26V
Duty ratio 10%-90%
Drive current Minimum:1.5mA
Other standard
Item Specification
Data storage About 10 year
limit
Safty agency EN61010-1:2001
approval
Electromagnetic EN61326-1:2006
compatibility EN61000-3-2:2006
EN61000-3-3:2008
Protection grade Front panel IP50,complete machine:IP40
IM01C82R01-01E 126
16.7 EXTERNAL DIMENSIONS
Unit: mm
127 IM01C82R01-01E
Dimensions of Instrument installation
Unit: mm
Hole size of Instrument
IM01C82R01-01E 128
[Link]
2012.02
Print in China