0% found this document useful (0 votes)
172 views2 pages

Catalogue tr-7578

TR-7578 is a transformer protection relay that: 1. Monitors up to 8 temperature points on medium voltage transformers using PT-100 sensors and controls cooling fans and provides alarms. 2. Provides three user-settable temperature set points to control cooling fans, warn of high temperatures, and trip the transformer. 3. Displays temperature readings and stores maximum temperatures even after power interruptions.

Uploaded by

arupamguria05
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
172 views2 pages

Catalogue tr-7578

TR-7578 is a transformer protection relay that: 1. Monitors up to 8 temperature points on medium voltage transformers using PT-100 sensors and controls cooling fans and provides alarms. 2. Provides three user-settable temperature set points to control cooling fans, warn of high temperatures, and trip the transformer. 3. Displays temperature readings and stores maximum temperatures even after power interruptions.

Uploaded by

arupamguria05
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Transformer Protection Relay

TR-7578 / TR-7578-C
(FOR RESIN CAST / DRY TYPE TRANSFORMERS)

Transformer Protection Relay


TR - 7578

RS-485
A B G
.
8 123
Temperature C

8
Func Set

7
Esc Reset

Auto Max

6
Manual

5
4
3
2
1

Standard Features:
* Single scanner unit for eight temperature monitoring points.
* Four output relays for Alarm, Trip, Fan on/off (Fan) & to warn against sensor open or
wrong sensor connection (Fault).
* Bright digital display offers accurate and unambiguous reading even in poor lighting
conditions.
* Better vibration withstanding capability.
* C and solid state design offers high reliability.
* Memorizes max. temperature.
Doc no. : 1 1 0 1 2 5 0 2

* Low power requirement.


* Extremely high noise immunity.
* Analog output (4-20mA) for Remote Indication (Provided in TR-7578 & TR-7578-C).
* Isolated RS-485 computer communication with MODBUS RTU Slave Protocol
(Provided in TR-7578-C)

Power Electronics & Control


145/2, G.I.D.C. Estate, Naroda, Ahmedabad - 382 330 INDIA
Tel: + 91 (79) 2281 3432, 2281 7892 Fax: +91 (79) 2282 1397
Em ai l : pec o n @ vs n l .c o m W ebs ite : www. p ec o n - i nd i a.c om
TR-7578 is designed for safe operation of medium voltage cast resin / dry type transformers. It is suitable for
control room as well as marshalling box installation and is built for long and trouble-free operation under
extreme conditions of service associated with transformer.
Three numbers of user settable set-points are provided - i) to control the cooling fan, ii) to warn the user of
high temperature and iii) to shut down the transformer in case of excessive heating. TR-7578 can accept upto
eight numbers of Pt-100 RTD sensors to allow the user to monitor eight critical temperature parameters on the
transformer. These can be like, three windings and core (as in case of TR-7570) or 6 winding points (either 3
from primary and 3 from secondary or 3 from top and 3 from the bottom of the three phase windings). This can
be achieved using TR-7576 also. However, to monitor additional temperature points in addition to six winding
temperature points like core temperature or enclosure temperature, TR-7578 is the solution.
TR-7578 is programmed to note and store maximum temperature of these points. Facility extends to recall this
information and to clear it for fresh recording. The maximum Temperature is saved such that it can be recalled
even after the power for TR-7578 is interrupted.
TR-7578-C is provided with facility for computer communication using RS-485 with MODBUS RTU Slave
Protocol in addition of 4-20mA output signal.
Technical Specifications
Inputs : 8 RTDs (Pt-100, IEC 751)
No. of Set-points : Three (Alarm, Trip & Cooling Fan On.)
O O
Temperature indication range: - 25 C to 225 C
O
Set point range : 1 to 225 C
O
Accuracy : ± 1 C (sensor inaccuracy not included)
O
Dead Band (relay differential) : User settable (range: 1 - 25 C)
Display Speed : User Settable (range 1 - 60 secs)
Display : 3 Seven Segment 1/2" red LEDs for displaying temperature
1 Seven segment 1/2" red LED for displaying channel no.
Mechanical
Overall Dimensions : 330 (H) x 275 (W) x 135 (D) mm
Mounting : Wall mounting by 3 nos. M6 Screws
Weight : 4 kg approx. unpacked
Enclosure : M.S. Sheet Box, powder coated, with acrylic viewing window (IP-52)
Electrical
Supply Voltage : 90-270 VAC/DC (Optionally 20-50 VAC/DC)
Outputs : Four relay contacts (1 C/O for each relay - Fault, Fan, Alarm & Trip).
One 4-20mA analog output in TR-7578 & TR-7578-C (correspondence
to 0-200 °C, max. load 300 ohms, linearity 0.5% of F.S.).
1KVDC Isolated RS-485 communication with MODBUS RTU Slave
Protocol in TR-7578-C.
Contact Rating : For resistive load, 5A @ 230VAC & 0.5A @ 125VDC
For inductive load, 5A@230VAC(cos¢ = 0.4) & 0.3A@125VDC(L/R=7msec)
Relay operations : Fault : To de-energize on detecting a fault condition.
Alarm : To energize if any one Channel has crossed Alarm set point
Trip : To energize if any one Channel has crossed Trip set point
Fan : To energize to start the cooling fan.
2
Terminals : Screwed Caged suitable for 2.5 mm solid conductors.
Insulation : Insulation resistance shall be 100 Mohm or more when 500VDC
is applied between each terminal in turn and enclosure.
Controller will withstand 2 KV rms at 50 Hz. for 1 min., applied
between all terminals shorted together and enclosure.
Power consumption : Max. 5VA
O O
Operating conditions : Temp. : -20 C to 50 C. R.H.: 95% Max non-condensing.
o
Test Conditions : 60% ±20% R.H., Amb. Temp. 27 ±5 C.

Due to continual development & change in technology, specifications are subject to change.