BERMAD Fire Protection
400 Series
Hydraulically Controlled,
On-Off Deluge Valve
Model: FP 400E-5D
Typical Applications Features and Benefits
■ Local release HRV ־Quick opening for long hydraulic
Petrochemical facilities remote control piping lines
■ Remote reset ־Shut-off on remote command
■ One-piece molded elastomeric moving part –
No maintenance required
Tunnels ■ Simple design ־Cost effective
■ Obstacle-free full bore ־Uncompromising reliability
■ Factory pre-assembled trim ־Out-of-box quality
■ In-line serviceable ־Minimal down time
Power plants & transformers
Optional Features
■ Alarm pressure-switch (option code: P or P7)
Flammable material storage ■ Seawater service (add FS as prefix to model)
■ Valve Position Single/Double Limit Switches
Gas storage tanks
Hydraulic remote controlled systems
BERMAD Fire Protection
Model: FP 400E-5D 400 Series
Operation
The BERMAD Model FP 400E־5D is suitable for systems that include wet pilot lines with closed fusible plugs
(thermal releases), and piping systems with a wide variety of open nozzles. The typical wet pilot line, is installed in the
covered area and connected to the valve trim. Providing boosted local pressure release from its control chamber, the
Model FP 400E־5D is recommended for systems with remote and/or elevated pilot line fusible plugs.
In the SET position line-pressure, which is supplied to both the main valve’s control chamber [1] and a Hydraulic Relay
Valve (HRV-2) [2] by the priming line [3], through a Check Valve [4], an Accelerator [5] with priming restriction and the
wet pilot line [6] restriction [7], is trapped by the Check Valve, by the closed HRV-2, by the closed wet pilot line and by
a closed Manual Emergency Release [8]. The trapped pressure holds the main valve’s diaphragm and plug against the
valve seat [9], sealing it drip-tight and keeping the system piping dry. The HRV-2 is held closed by the pressure
in the wet pilot line.
Under FIRE or TEST conditions, a pilot line hydraulic pressure drop opens the HRV-2 causing water to exit through the
Accelerator faster than it can be supplied. Pressure is then released from the main valve’s control chamber through the
opened HRV-2, or the Manual Emergency Release, allowing the main valve to fully open and water to flow into the
system piping and to the alarm device (if mounted).
[6]
[7]
[2]
[4] [5]
[3] 15B
[8]
[1] to drain
[9]
D 1 to alarm
Valve Closed (set position) Valve Open (operating condition)
Engineer Specifications
■ The On-Off deluge valve shall be a UL-Listed, hydraulically controlled, elastomeric type globe valve with a
rolling-diaphragm.
■ The valve shall have an unobstructed flow path, with no stem guide or supporting ribs.
■ Valve actuation shall be accomplished by a fully peripherally supported, one-piece balanced rolling-diaphragm,
vulcanized with a rugged radial seal disk. The diaphragm assembly shall be the only moving part.
■ The valve shall have removable cover for quick in-line service enabling all necessary inspection and servicing.
■ The control trim materials shall be S.S.316 tubing and fittings and plated brass accessories, including Y strainer,
Accelerator, Hydraulic Relay Valve (HRV-2), and Manual Emergency Release.
■ The control trim shall be supplied as an assembly, pre-assembled and hydraulically tested at an
ISO 9000 and 9001 certified factory.
■ The Hydraulically Controlled, On-Off Deluge Valve shall fully open in response to a wet pilot line hydraulic pressure drop.
BERMAD Fire Protection
Model: FP 400E-5D 400 Series
System Components
1 - Main Valve, BERMAD FP 400E Series
2B - Accelerator with Priming Restriction
3B - Orifice Assembly
4B - Priming Strainer
7B - Check Valve
15B - Manual Emergency Release
18B - Priming Ball Valve
26B - Hydraulic Relay Valve (HRV-2)
Optional
S - Valve Position Limit Switch / Switches
4B 7B 3B 2B
18B To Remote
Control
26B
15B
Hydraulic
UL Listed Atmosphere
The BERMAD Model FP 400E-5D is UL-Listed.
The installation shall include Indicating and Drain Components.
BERMAD Fire Protection
Model: FP 400E-5D 400 Series
Technical Data
Th
Tb
L1, L4
Inlet Inlet
Tw
1½” 2” 2½” 3” 4” 6” 8” 10” 12”
Size
mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch
L1 (1) 205 8 1/16 205 8 1/16 205 8 1/16 257 10 2/16 320 12 10/16 415 16 5/16 500 19 11/16 607 23 14/16 725 28 9/16
Dimensions
L4 (2) 205 8 1/16 205 8 1/16 N/A N/A 257 10 2/16 320 12 10/16 N/A N/A 500 19 11/16 N/A N/A N/A N/A
Tw 255 10 /16 255 10 /16 255 10 /16 255 10 /16 255 10 /16 255 10 /16 255 10 1/16 255 10 1/16 255 10 1/16
1 1 1 1 1 1
Tb 64 2 8/16 78 3 1/16 89 3 8/16 100 3 15/16 115 4 8/16 140 5 8/16 172 6 12/16 204 8 1/16 242 9 8/16
Th 289 11 /16 289 11 /16 301 11 /16 325 12 /16 345 13 /16 420 16 /16 471 18 /16 471 18 /16 588 23 2/16
6 6 14 13 9 9 9 9
Notes:
1. L1 is for flanged ANSI #150 and ISO PN16. 3. Provide adequate space around valve for maintenance.
2. L4 is for grooved end connections (Ductile Iron Only). 4. Data is for envelope dimensions, specific component positioning may vary.
Connection Standard Available Sizes
• Flanged: ANSI B16.42 (Ductile Iron), • 1½, 2, 2½, 3, 4, 6, 8, 10 & 12"
B16.5 (Steel & Stainless Steel), • UL-Listed for sizes 1½, 2, 2½, 3, 4, 6, 8 & 10”
B16.24 (Bronze)
Pressure Rating
• ISO PN16
• Max. working pressure: 250 psi (17 bar)
• Grooved: ANSI/AWWA C606 for 2, 3, 4, 6 & 8”
Water Temperature
• 0.5 – 50°C (33 – 122°F)
Manufacturers Standard Materials Optional Materials
Main valve body and cover Main valve body
• Ductile Iron ASTM A-536 • Carbon Steel ASTM A-216 WCB
Main valve internals • Stainless Steel 316
• Stainless Steel 304 & Cast Iron • Ni-Al-Bronze ASTM B-148
Control Trim System Control Trim
• Brass control components/accessories • Stainless Steel 316
• Stainless Steel 316 tubing & fittings • Monel) and Al-Bronze
Elastomers • Hastalloy C-276
• Nylon fabric reinforced polyisoprene NR Elastomers
Coating • NBR
• Electrostatic Powder Coating Polyester, • EPDM
Red (RAL 3002) Coating
• High Build Epoxy Fusion-Bonded
with UV Protection, Anti-Corrosion
The information herein is subject to change without notice. BERMAD shall not be held
liable for any errors. All rights reserved. © Copyright by BERMAD. PE4PE-5D 11