0% found this document useful (0 votes)
49 views

03 - System Components

The document discusses the components needed to build an energy automation system called SICAM PAS. It describes communication components like Ethernet switches, routers, and time synchronization modules. It also discusses PC equipment like servers, clients, and engineering PCs. Finally, it provides examples of Ethernet switches from RuggedCom and Hirschmann that are compatible with SICAM PAS, including their port configurations and redundancy capabilities.

Uploaded by

sandi anugraha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views

03 - System Components

The document discusses the components needed to build an energy automation system called SICAM PAS. It describes communication components like Ethernet switches, routers, and time synchronization modules. It also discusses PC equipment like servers, clients, and engineering PCs. Finally, it provides examples of Ethernet switches from RuggedCom and Hirschmann that are compatible with SICAM PAS, including their port configurations and redundancy capabilities.

Uploaded by

sandi anugraha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 35

Energy Automation

SICAM PAS
System Components

Unrestricted © Siemens AG 2014 All rights reserved. siemens.com/answers


SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 2 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 3 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - application example -

Control Center

WAN

Ethernet RJ45
Ethernet FO
RS485
Unrestricted © Siemens AG 2014 All rights reserved.
Page 4 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - application example -

Ethernet RJ45
Ethernet FO
RS485

Unrestricted © Siemens AG 2014 All rights reserved.


Page 5 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - PRP / HSR Redundancy-

PRP-A PRP-B
Control Room
… …
ring 1…n ring 1…n

up to 50 devices
Room 1 split over two string

up to 50 devices
Room n split over two stings

Non Non
HSR HSR
device device

Unrestricted © Siemens AG 2014 All rights reserved.


Page 6 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches – IEC 61850 limits -

 The communication standard for the station bus based on Ethernet


 Recommended max. number of IED’s per IEC 61850 system: 500
=> SICAM PAS system limits needs also to be considered (max. 350 IED’s)

 Recommended max. number of GOOSE massages per system: 1.000


 Recommended max. Number of GOOSE send per IED: 16
 Recommended max. Number of GOOSE received per IED: 128
 We recommend the use of Ethernet components from Ruggedcom,
Hirschmann and Siemens Scalance X EEC

Inter-bay communication independent of the station unit via IEC 61850-


GOOSE mechanism (e.g. for inter-bay interlocking)

Unrestricted © Siemens AG 2014 All rights reserved.


Page 7 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - RuggedCom -

 IEC 61850 compliant , KEMA certificate


 Integrated redundant-/managed switch functions
 Tested together with Siprotec IED‘s
RSG2100
19 ports modular managed switch with Gigabit ports (LC)
Up to 3 Gbit ports
Up to 16 Fast Ethernet ports

RSG900 RS900
10-port managed switch 9-port managed switch
2x Gigabit FO- ports (LC) 2x FO- ports (ST)
8x Fast Ethernet (RJ45) 6x RJ45

Unrestricted © Siemens AG 2014 All rights reserved.


Page 8 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - RuggedCom -

RS8000H-HI-MMST-MS

RS1600T-HI-HI-MM-MS
RS1600-xx-xx-MM-MS

RS900-xx-D-MTMT00
RS8000T-HI-MM-MS
RS80000-x-MM-MS
Interfaces / Type of Device

RSG2100
RS8000H
RS8000T

RS1600T

RS1600F

RSG900
RS8000

RS1600

RS900
FO-ports
2 3
1 G-Bit

FO-ports
8 2 4 2 2 16 3
100 M-Bit

FO-ports
12 16
10 M-Bit

RJ45-ports
10/100BaseTX 6 4 14 6 8 16
max. 20m
http://www.ruggedcom.com
Unrestricted © Siemens AG 2014 All rights reserved.
Page 9 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - Hirschmann -

 Tested with SIPROTEC


 IEC 61850 compliant, KEMA certificate
Config
Type RS20/30/40 RSR20/30 and MS20/30/4128 (Firmware 5.0)
 Compact
 max. 8 Ethernet ports

Type Mach 1020/1030/1040 (Firmware 5.0)


 Modular USB port V24 port
Flexible configuration

Mixed
Other vendors Diagnostic LEDs
8 x FE fiber SC MM/SM
8 x FE RJ45
4 x FE SFP slot
 Moxa, Garettcom claim to be 2 x FE ST MM/SM
2 x FE MTRJ MM/SM

compliant to IEC 61850-3 with some product lines


 NOT tested with SIPROTEC devices

Unrestricted © Siemens AG 2014 All rights reserved.


Page 10 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - Siemens Scalance X -
EEC Version (IEC 61850 and IEEE 1613)
 Compact and modular housing
 Hardware-based time synchronization IEEE 1588
 Simple device swap due to C-Plug (Configuration Plug,
stores device‘s parameters)
 Technical support from local Siemens consultants
 Fast qualified support via Hotline (24h) worldwide
 Delivery from stock – available worldwide
 System tested with SIPROTEC / SICAM (Firmware V3.3.0)

Scalance X-300 EEC (compact): Scalance XR-300 EEC (modular):


 9 Ethernet interfaces  Up to 24 Ethernet interfaces
 7 x RJ45 & 2 x FX with LC  16 x RJ45 fixed integrated
 2 x RJ45 & 7 x FX with LC  4 Ethernet modules (FX or RJ45)
 Single or redundant Power Supply  Single or redundant Power Supply
 DC 24 V  DC 24 V
 DC 60 to 250 / AC 100 to 240 V  AC 230 V
Unrestricted © Siemens AG 2014 All rights reserved.
Page 11 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - Siemens Scalance X204 RNA EEC -

SOFTNET – IE RNA V12


PRP-Driver for PC
Substation Controller
using two Ethernet-Cards
6GK1711-1EW12-0AA0

PRP-A PRP-B
HSR Networks
6GK5204-0BS00-2NA3
PRP Networks
6GK5204-0BS00-3LA3
Up to 50
PRP&HSR Networks
SIPROTEC 6GK5204-0BS00-3PA3
devices per ring
.

 RNA: Redundant Network Access


HSR  2 X 100MBit/s RJ45 Ports
 2 X 100MBit/s Combo-Port
 LED-Diagnostics
 Redundant PS 24 VDC
 Network Management
Unrestricted © Siemens AG 2014 All rights reserved.
Page 12 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet switches - Siemens Scalance X204 RNA EEC -

The SCALANCE X204RNA EEC (PRP/HSR)


- has four RJ-45 jacks and
- two slots for SFP modules (order separately).

The SFP modules (LC connectors)


= > alternatives to RJ-45 jacks A/H1 and B/H2
to connect networks:
- PRP: LAN A and LAN B or
- HSR: HSP-ring

End devices or network segments w/o


Compatible with EN100 O/O+ & ETH-BB-2FO PRP or HSR: use RJ-45 jacks 1|1/B and 2|2/B.

Unrestricted © Siemens AG 2014 All rights reserved.


Page 13 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 15 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Serial Hub - application example -

Control Center

modem

COM 1 COM 1
COM 2 COM 2

COM 2
modem

Ethernet RJ45
Ethernet FO
COM1
RS485
RS232
Unrestricted © Siemens AG 2014 All rights reserved.
Page 16 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Serial Hub - tested components -

Tunneling of serial protocols


 IEC 60870-5-103
 IEC 60870-5-101 (Master & Slave)
 DNP V3.00
 Modbus

Moxa:
 NPort 5410 (4 x RS 232 serial device server)
 NPort 5430i (4 x RS 485 serial device server)
 NPort 5650-16 (16 x RS 232/485 serial device server)
 NPort 6450 (4 x RS 232/485 secure terminal server)

RuggedCom:
 RS400 (4 x RS 232/485 interfaces)

EA PRO:
 7XV5655-0BA00 (1 x RS 232/485; 1 x FO interfaces)

Unrestricted © Siemens AG 2014 All rights reserved.


Page 17 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 18 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet router / firewall - application example -

Control Center
Engineering Office

WAN

WAN

Ethernet RJ45
Ethernet FO
RS485
Unrestricted © Siemens AG 2014 All rights reserved.
Page 19 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Ethernet router / firewall - Cisco / RuggedCom -

Cisco ASA 5510

Router/Firewall RX1000
 IEC 61850-3
 industrially hardened Cyber Security Appliance
 up to 4 Ethernet ports, WAN Ports
 Input voltage range of 9-59VDC, 88-300VDC, and 85-264VAC for worldwide
operability
 -40°C to +85°C operating temperature (no fans)

Unrestricted © Siemens AG 2014 All rights reserved.


Page 20 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 21 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Modem Splitter - application example -

Control Center

modem

modem

Ethernet RJ45
Ethernet FO
RS485
RS232
Unrestricted © Siemens AG 2014 All rights reserved.
Page 22 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Modem Splitter - components -

Modem splitter: Order number:


 2 x RJ45 20690249
 RS232-25 male

Connection Cable: Order number:


 RJ45 male 20690252
 RS232-9 female

Adapter: Order number:


 RS232-9 male -> 25 female 20690251

Patch Panel: Order number:


 19’’ 20690250
 2U

Unrestricted © Siemens AG 2014 All rights reserved.


Page 23 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 24 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Media Converter

Converters fibre optic to cupper 7XV565*


 Fibre optic/RS485 (for bus topology) 7XV5650-0BA00
 Fibre optic/RS485 (for ring topology) 7XV5651-0BA00
 Fibre optic/RS232 7XV5652-0BA00

Optical mini-star coupler 7XV5450-0BA00


 Max. 1.5km
 Cascadable
RS232 Interface
Fibre optic- Interface
Converter RS232/RS485 (2 ports) (4 output; 1 income)
 Meilhaus: IRK-100 (http://www.meilhaus.com)

RuggedCom IEC 61850 media Converter


 RJ45 <-> FO (e.g. for 7SS52 central unit): RMC series

Unrestricted © Siemens AG 2014 All rights reserved.


Page 25 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 26 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
COM-port expander - application example -

Control Center

modem
PCI module

COM 2; COM3; COM 4; COM 5

COM 5
COM 2
modem

COM 4
COM 3

Unrestricted © Siemens AG 2014 All rights reserved.


Page 27 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
COM-port expander - tested components -

PCI module for PC


Comtrol: Rocket Ports , Com Port expander (RS232)
 4x ports PCI (RS232)
 8x ports PCI (RS232)
 16x ports PCI (RS232)

COM- interfaces

Moxa: Com Port expander


 Industrio CP-114 PCI express board (4 x RS232/48)

SICAM PAS Station Unit


=> Per MLFB option

Unrestricted © Siemens AG 2014 All rights reserved.


Page 28 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 29 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS Communication components
Profibus communication - application example -

Profibus FMS and DP communication


 PCI-card 6GK1561-3AA01
 Profibus FMS for SIPROTEC 4 (software package 6GK1713-5FBxx-3AA0)
 Profibus DP e.g. ET200, SIMEAS P (software package 6GK1713-5DBxx-3AA0) CP5613

 Max. 2 Profibus modules CP5613 in each station unit


Repeater
 Max. 30 devices (100 data points per unit) on each CP5613
 Use of Profibus components from A&D (e.g. OLM)

FO double bus
RS485 line OLM

! no inter bay interlocking


during local control !
Unrestricted © Siemens AG 2014 All rights reserved.
Page 30 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 31 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS PC equipment ! continuous operation !
Hardware and System Requirements

Always to consider:
 Interoperability lists I-op
 Hardware requirements

SICAM PAS
 Station Unit
 I-PC (industrial PC)
 “normal” PC (not recommended)

SICAM SCC
 I-PC (industrial PC)
 “normal” PC (not recommended)

Engineering PC
 I-PC (industrial PC)
 “normal” PC (not recommended)

Unrestricted © Siemens AG 2014 All rights reserved.


Page 32 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Components needed to build a SICAM PAS system
 Communication components
 Ethernet switches
 Ethernet serial hubs
 Ethernet Router (with Firewall)
 Modemsplitter
 Media converter
 Com-Port expander
 Profibus communication equipment

 PC equipment
 SICAM PAS PC’s (instead of Station Unit)
 SICAM PAS CC PCs - Server; Client –
 Engineering PC

 Time synchronization
 Internal PCI-module
 External NTP time server
Unrestricted © Siemens AG 2014 All rights reserved.
Page 36 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Time synchronization module

GPS PCI card FG6039GPS


 Time synchronization of the SICAM PAS station unit
 All connected IEDs and HMI- PCs are synchronized
 Fa. Hopf (http://www.hopf-time.com)

antenna SICAM
PAS CC
Ethernet (TCP/IP)
Station Unit

Time master
Receiver
module

Time.-

/-server

IEC 61850 IEC101

Profibus FMS
IEC 103

Unrestricted © Siemens AG 2014 All rights reserved.


Page 37 2014-05 M. Zapp / EA PRO S PROM
SICAM PAS
Time synchronization device

Central time server


 Used in IEC 61850 stations
 All connected devices (SIPROTEC 4, SICAM PAS, PCs,)
connected with Ethernet are synchronized directly via SNTP protocol.
 SICLOCK TM, Meinberg or Hopf FG6842-G31/TS1-Lx
antenna
Station Unit

SICAM
PAS CC

(Time-) Time
SNTP master
Master clock -Client /-server
SNTP-Server
by Meinberg
or Siclock

IEC 61850 IEC101


Ethnernet (TCP/IP)
Profibus FMS
IEC 103

Unrestricted © Siemens AG 2014 All rights reserved.


Page 38 2014-05 M. Zapp / EA PRO S PROM
M Fatkhur Rokhim
EM DG SYS
Siemens Indonesia
Jl Jend A Yani Kav B.67-68
Pulomas JAKARTA 13210
Phone: +62 (21) 24555-581
Fax: +62 (21) 472-9244
Mobile: +62 (81) 11026380
E-mail:
[email protected]

siemens.com/answers

Unrestricted © Siemens AG 2014 All rights reserved.


Page 39 2014-05 F Rokhim/EM DG SYS

You might also like