D I E S E L

G E N E R A T I N G S E T

Exclusively from your Caterpillar® dealer

GEP150 (3-Phase)
50 HZ
 STANDBY 150 kVA / 120 kW
PRIME 135 kVA / 108 kW
60 HZ
 STANDBY 165 kVA / 132 kW
 PRIME 150 kVA / 120 kW

FEATURES
GENERATING SET exhaust SYSTEM
l Complete system designed and built at ISO9001 l Heavyduty industrial capacity exhaust silencer
certified facility (approximately 10 dB reduction) supplied loose
l Factory tested to design specifications at full load
COOLING SYSTEM
conditions
l Standard ambient temperatures up to 50° C (122° F)
l Fully engineered with a range of options and
l Fan, fan drive and charging alternator fully guarded
accessories
l Antifreeze protection coolant
ENGINE
l Industrial water cooled diesel engine CIRCUIT BREAKER
l Governor, l 3-pole miniature circuit breaker (mcb) < 160 amps
electronic
l Electrical system, 12 VDC and 3-pole molded case circuit breaker (mccb)
l Cartridge type fuel and oil filters
>= 160 amps
l Vibration isolated sheet steel enclosure with
l Air filter
removable cover plate
l Battery(ies), rack and cables
l Outgoing cable stub-up area directly below circuit
GENERATOR breaker
l Self excited brushless generator AUTOMATIC VOLTAGE REGULATOR
l Insulation system, class H l Voltage regulation ±0.5 %
l Drip proof generator air intake (IP23)
l Provides fast recovery from transient load changes
l Electrical design in accordance with BS5000 Part‑99,
IEC60034-1, VDE0530, UTE51100 EQUIPMENT FINISH
l Allelectroplated hardware
CONTROL SYSTEM l Anticorrosive paint protection
l PowerWizard 1.0 control panel l High gloss polyurethane paint for durability and
l Vibrationisolated sheet steel enclosure with hinged scuff‑resistance
lockable door
QUALITY STANDARDS
MOUNTING ARRANGEMENT l BS4999, BS5000, BS5514, IEC60034, VDE0530
l Heavy-duty fabricated steel base with lifting points
l Anti-vibration pads to ensure vibration isolation DOCUMENTATION
l Engine coupled to generator with flexible l Operation and maintenance manuals provided
disc‑coupling l Wiring diagrams included
l Baseframe incorporates heavy-duty fabricated steel
fuel tank, 8 hours running capacity WARRANTY
l All equipment carries full manufacturer's warranty

LEHF1193-09 (08/06)
5 0 H z S T A N D B Y 1 5 0 k V A / 1 2 0 k W
P R I M E 1 3 5 k V A / 1 0 8 k W
6 0 H z S T A N D B Y 1 6 5 k V A / 1 3 2 k W
P R I M E 1 5 0 k V A / 1 2 0 k W

Exclusively from your Caterpillar® dealer


OPTIONAL Equipment*
Engine Lube oil drain
Lube oil drain valve
Lube oil drain pump
High lube oil temperature shutdown
Generator Anti-condensation heater
Quadrature droop upgrade
Permanent magnet generator (PMG)
AREP Excitation system
Cooling System Coolant heater
Low coolant temperature alarm
Low coolant level shutdown
Radiator transition flange
Coolant drain
Fuel System Extended capacity metal basetank
Manual fuel pump
Low fuel level shutdown
Low fuel level alarm
High fuel level alarm
Remote fuel systems
Manual Bypass Valve
Silencer System — Open Unit Level 2 silencer with mounting kit (approximately 25 dB reduction)
Level 3 silencer with mounting kit (approximately 35 dB reduction)
Overhead mounting kit for level 1 silencer
Level 1, 2 and 3 silencer installation kits
Enclosures Sound attenuated (EC) canopy
Handling/Trailers Oil field skid
Controls Baseframe mounted terminal box instead of control panel
6000 Series digital synchronising control panels
PowerWizard 2.0 control panel
Remote Annunciators PowerWizard 2.0 annunciator
Circuit Breaker Upgrades from 3-pole to 4-pole breaker
Transfer Switches TM Series manual load transfer panels
TC Series automatic load transfer panels
ATI Series load transfer panels
Certification European CE certification (not available on 60 Hz models)
*Some options may not be available on all models.
*Not
Somealloptions
optionsmay
are listed.
not be available on all models.
Not all options are listed.

Consult your Olympian representative for more information

LEHF1193-09 (08/06) 
5 0 H z S T A N D B Y 1 5 0 k V A / 1 2 0 k W
P R I M E 1 3 5 k V A / 1 0 8 k W
6 0 H z S T A N D B Y 1 6 5 k V A / 1 3 2 k W
P R I M E 1 5 0 k V A / 1 2 0 k W

Exclusively from your Caterpillar® dealer


specifications
Piston speed — m/sec (ft/sec)
50 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 (20.8)
GENERATOR 60 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.6 (25.0)
Make.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Olympian Maximum power at rated rpm — kW (hp)
Model.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LL3014F Standby
Type.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Self-excited, brushless 50 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146 (196)
60 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 (219)
Voltage regulation. . . . . . . . . . . . . . . . ±0.5% at steady state from
Prime
from no load to full load
50 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135 (181)
Frequency.. . . . . . . . . . . . . . . . . . . . ±0.25% for constant load from 60 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150 (201)
no load to full load
BMEP — kPa (psi)
Waveform distortion.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . THD <4% Standby
Radio interference. . . . . . . . . . . . . . . Compliance with EN61000-6 50 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1949 (283)
Telephone Interference.. . . . . . . . . . . . . . . . . . . . TIF <50, THF <2% 60 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1822 (264)
Overspeed limit.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2250 rpm Prime
Insulation.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class H 50 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1800 (261)
Temperature rise.. . . . . . . . . . . . . . . . . . . . . . . Within Class H limits 60 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1671 (242)
Deration.. . . . . . . . . . . . . . . . Consult factory for available outputs Regenerative power — kW (hp)
50 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12.6 (16.9)
60 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16.2 (21.7)
ENGINE Governor
Manufacturer.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Perkins Type.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electronic
Class.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ISO 8528 G2
Model.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1006TAG
Type.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-Cycle
Aspiration.. . . . . . . . . . . . Turbocharged air to air charge cooled
Cylinder configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . In-line 6
Displacement — L (cu in).. . . . . . . . . . . . . . . . . . . . . . . . . . . 6.0 (366)
Bore/stroke — mm (in).. . . . . . . . . . . . . . . . . . . . . . 100/127 (3.9/5.0)
Compression ratio.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17.0:1
Engine speed — rpm
50 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
60 Hz.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1800

GENERATING SET DIMENSIONS AND WEIGHTS

L W

Length Width Height Weight* Note:‑General configuration not to be


Model mm (in) mm (in) mm (in) kg (lb) used for installation. See general
dimension drawings for detail.
GEP150 2675 (105) 900 (35.4) 1460 (57.5) 1480 (3263)
*Includes oil and coolant

Consult your Olympian representative for more information

LEHF1193-09 (08/06) 
5 0 H z S T A N D B Y 1 5 0 k V A / 1 2 0 k W
P R I M E 1 3 5 k V A / 1 0 8 k W
6 0 H z S T A N D B Y 1 6 5 k V A / 1 3 2 k W
P R I M E 1 5 0 k V A / 1 2 0 k W

Exclusively from your Caterpillar® dealer


GEP150 (3-Phase)
50 Hz 60 Hz
Generator Set Technical Data Standby Prime Standby Prime
Package Performance
Power rating kVA (kW) 150 (120) 135 (108) 165 (132) 150 (120)
Lubricating System
Type: Oil pump & lubrication sump
Oil filter: Spin-on, full flow
Oil cooler: Water
Oil type required: API CD 15W-40
Total lube system capacity L (U.S. Gal) 19.0 (5.0) 19.0 (5.0)
Oil pan capacity L (U.S. Gal) 16.0 (4.2) 16.0 (4.2)
Fuel System
Fuel Tank Capacity L (U.S. Gal) 290 (76.6) 290 (76.6)
Generator set fuel consumption**
100% load L/hr (U.S. g/hr) 34.4 (9.1) 31.2 (8.2) 41.5 (11.0) 38.2 (10.1)
75% load L/hr (U.S. g/hr) 26.5 (7.0) 24.2 (6.4) 32.5 (8.6) 30.0 (7.9)
50% load L/hr (U.S. g/hr) 18.9 (5.0) 17.4 (4.6) 23.4 (6.2) 21.7 (5.7)
Engine Electrical System
Voltage/ground: 12 vDC/negative
Battery charging alternator ampere rating amps 55 55
Cooling System
Water pump type: Centrifugal
Cooling system capacity L (U.S. Gal) 37.2 (9.8) 37.2 (9.8)
Maximum coolant static head m H2O (ft H2O) 6.8 (22.3) 9.8 (32.2)
Coolant flow rate L/hr (U.S. gal/hr) 8400 (2219) 10320 (2726)
Minimum temperature to engine °C (°F) 76.0 (169) 76.0 (169)
Temperature rise across engine °C (°F) 8.0 (14.4) 8.0 (14.4)
Heat rejected to coolant at rated power kW (Btu/min) 72.9 (4146) 66.4 (3776) 82.5 (4692) 70.1 (3987)
Total heat radiated to room at rated power kW (Btu/min) 39.1 (2224) 25.3 (1439) 50.9 (2895) 31.2 (1775)
Radiator fan load kW (hp) 4.5 (6.0) 8.0 (10.7)
Air Requirements
Combustion air flow m3/min (cfm) 9.8 (346) 9.2 (325) 31.2 (466) 12.7 (448)
Maximum air cleaner restriction kPa (in H2O) 5.0 (20.1) 5.0 (20.1)
Radiator cooling air m /min (cfm) 192 (6780) 244 (8617)
3

External restriction to cooling airflow Pa (in H2O) 125 (0.5) 125 (0.5)
Generator cooling air m3/min (cfm) 22.2 (784) 26.4 (932)
Exhaust System
Maximum allowable backpressure kPa (in Hg) 6.0 (1.8) 6.0 (1.8)
Exhaust flow at rated power m3/min (cfm) 28.2 (996) 26.2 (925) 36.3 (1282) 34.5 (1218)
Exhaust temperature at rated power
(dry exhaust) °C (°F) 570 (1059) 560 (1039) 522 (971) 514 (957)
Generator Set Noise Rating*
(without attenuation) at 1 m (3.28 ft) dBA 95.4 99.0
**dBA levels are for guidance only
**Fuel consumption data at indicated load with diesel fuel with a specific gravity of 0.85 and conforming to BS2869:1998 Class A2.
50 Hz 60 Hz
Generator Technical Data 415/240V 400/230V 380/220V 220/127V 480/277V 440/254V 208/120V 230/115V 380/220V
230/115V 220/110V 240/139V 220/127V 208/120V 220/110V
200/115V
Motor Starting Capability:
Self Excited (kVA) 329 309 283 362 360 311 263 264 241
AREP Excited*** (kVA) 429 404 370 472 469 406 370 346 316
PM Excited**** (kVA) 429 404 370 472 469 406 370 346 316
Full Load Efficiency
Standby % 92.2 92.3 92.1 92.0 93.0 92.9 92.6 92.3 91.9
Prime % 92.5 92.6 92.5 92.1 93.2 93.1 92.9 92.6 92.3
Reactances (per unit) Xd 2.94 3.16 3.50 2.40 2.90 3.45 3.86 4.17 4.63
Saturated X'd 0.10 0.11 0.12 0.08 0.10 0.12 0.13 0.14 0.16
Reactances X"d 0.0610.066 0.073 0.050 0.060 0.072 0.080 0.087 0.096
are shown Xq 1.76 1.90 2.10 1.44 1.74 2.07 2.32 2.50 2.78
applicable to the X"q 0.0720.078 0.086 0.059 0.071 0.085 0.095 0.103 0.114
standby rating X2 0.0670.072 0.080 0.055 0.066 0.079 0.088 0.095 0.106
X0 0.0050.005 0.006 0.004 0.005 0.006 0.006 0.007 0.008
t'd t"d t'do ta
Time Constants:
100 ms 10 ms 2865 ms 15 ms
****With AREP Excited Option AR20A/AR21A
****With PMG Excited Option AR18A/AR19A
Consult your Olympian representative for more information

LEHF1193-09 (08/06) 
5 0 H z S T A N D B Y 1 5 0 k V A / 1 2 0 k W
P R I M E 1 3 5 k V A / 1 0 8 k W
6 0 H z S T A N D B Y 1 6 5 k V A / 1 3 2 k W
P R I M E 1 5 0 k V A / 1 2 0 k W

Exclusively from your Caterpillar® dealer


RATINGS AT AVAILABLE Voltages
50 Hz
Standby Prime
Voltage
Code Voltage kVA kW kVA kW
VOPT502 415/240 150.0 120.0 135.0 108.0
VOPT503 400/230 150.0 120.0 135.0 108.0
VOPT504 380/220 150.0 120.0 135.0 108.0
VOPT506 230/115 150.0 120.0 135.0 108.0
VOPT507 220/127 138.0 110.4 125.0 100.0
VOPT508 220/110 150.0 120.0 135.0 108.0
VOPT510 200/115 150.0 120.0 135.0 108.0

60 Hz
Standby Prime
Voltage
Code Voltage kVA kW kVA kW
VOPT601 480/277 165.0 132.0 150.0 120.0
VOPT603 440/254 165.0 132.0 150.0 120.0
VOPT605 380/220 165.0 132.0 150.0 120.0
VOPT606 240/120 165.0 132.0 150.0 120.0
VOPT607 230/115 165.0 132.0 150.0 120.0
VOPT608 220/127 165.0 132.0 150.0 120.0
VOPT609 220/110 165.0 132.0 150.0 120.0
VOPT610 208/120 165.0 132.0 150.0 120.0
VOPT611 240/139 165.0 132.0 150.0 120.0
Ratings at 27° C (80° F), 152.4 m (500 ft), 60% humidity, 0.8 pf

RATING DEFINITIONS
Standby Prime Power
These ratings are applicable for supplying These ratings are applicable for supplying
continuous electrical power (at variable load) in continuous power (at variable load) in lieu of
the event of a utility power failure. No overload commercially purchased power. There is no
is permitted on these ratings. When used limitation to the annual hours of operation and
at standby rating the alternator will be peak this model can supply 10% overload power for
continuous rated (as defined in ISO8528-3). 1 hour in 12 hours.

Consult your Olympian representative for more information

LEHF1193-09 (08/06) 
5 0 H z S T A N D B Y 1 5 0 k V A / 1 2 0 k W
P R I M E 1 3 5 k V A / 1 0 8 k W
6 0 H z S T A N D B Y 1 6 5 k V A / 1 3 2 k W
P R I M E 1 5 0 k V A / 1 2 0 k W

Exclusively from your Caterpillar® dealer

Information contained in this publication may be considered confidential. www.CAT-ElectricPower.com


Market: International Discretion is recommended when distributing.
Materials and specifications are subject to change without notice. © 2006 Caterpillar
LEHF1193-09 (08/06) CAT, CATERPILLAR, their respective logos and "Caterpillar Yellow", as well as corporate and product All rights reserved.
identity used herein, are trademarks of Caterpillar and may not be used without permission. Printed in U.S.A.
278-687

You might also like