Installation and Operation Manual - Growatt - MOD 3 15KTL3 X - Inverters - 2021 - ENG
Installation and Operation Manual - Growatt - MOD 3 15KTL3 X - Inverters - 2021 - ENG
&
Operation Manual
Growatt New Energy
Download
Manual
2 Safety
2.1 Product description and features
2.2 Qualification of skilled person
2.3 Safety instruction
3 Product overview
3.1 Appearance overview
3.2 Dimensions
3.3 Storage environment
4 Unpacking inspection
5 Installation
5 . 1 Basic installation requirements
5.2 Mounting wall mount
5.3 Installing the inverter
6 Inverter wiring
6.1 Security
6.2 AC side wiring
6.3 DC side wiring
6.4 Connect the signal cable
6.5 Grounding the inverter
6.6 Active power control with smart
meter,CT or ripple control signal
receiver
6.7 Inverter demand response modes
(DRMS)
6.8 AFCI(Optional)
7 Debugging 13 Troubleshooting
13 . 1 Error message
13 . 2 Syetem error
19 Contect us
1 Notes on this manual
1.1 Validity
This manual will provide detailed product information and installation instructions for CAUTION indicates a hazardous situation which, if not avoided,
users of model TL3-X series photovoltaic inverter of Shenzhen Growatt new energy Co., could result in minor or moderate injury.
CAUTION
Ltd. (hereinafter referred to as Growatt new energy). Please read this manual carefully
before using this product. Growatt new energy will not inform users of any changes to
this manual.
MOD 3000TL3-X NOTICE is used to address practices not related to personal injury.
MOD 4000TL3-X NOTICE
MOD 5000TL3-X
MOD 6000TL3-X Information that you must read and know to ensure optimal
MOD 7000TL3-X operation of the system.
MOD 7000TL3-X-AU Information
MOD 8000TL3-X
MOD 8000TL3-X-AU
MOD 9000TL3-X
MOD 9000TL3-X-AU
1.3.2 Markings on this product
MOD 10KTL3-X
MOD 10KTL3-X-AU Symbol Explanation
MOD 11KTL3-X
MOD 11KTL3-X-AU
MOD 12KTL3-X Danger: Electricity!
MOD 13KTL3-X
MOD 15KTL3-X
Danger:Flame!
1.2 Applicable personnel
The inverter must be installed by professional electricians who are certified by relevant
departments. By reading this manual in detail, the installer can install the MOD TL3-X Danger:Hot surface!
series inverter correctly and quickly, and can carry out troubleshooting and
communication system construction.
Operation after 5 minutes
If there are any problems during the installation process, the installer can log on to
www.growatt.com to leave a message on the website or call our 24-hour service
phone: +86 755 2747 1942 . Point of connection for grounding protection
3 4
2.2 Qualification of skilled person 2.3.2 Electrical Connection Warnings
This grid-tied inverter system operates only when properly connected to the AC
distribution network. Before connecting the MOD TL3-X to the power distribution grid,
contact the local power distribution grid company. This connection must be made only Ø The components in the inverter are live. Touching live components
by qualified technical personnel to connect, and only after receiving appropriate can result in serious injury or death.
approvals, as required by the local authority having jurisdiction. Ÿ Do not open the inverter except the wire box by qualified persons.
Ÿ Electrical installation, repairs and conversions may only be carried
2.3 Safety instructions out by electrically qualified persons.
1.Please read this manual carefully before installation.If you fail to install according Ÿ Forbid live line work.
to the instructions in this manual,or ignore the warnings in the manual and the Ø Danger to life due to high voltages in the inverter
equipment is damaged,our company reserves the right not to guarantee the quality; Ÿ There is residual voltage in the inverter after the device shutdown.
2.All operations and wiring should be finished by the professional electrical or mechanic- The inverter need to take 20 minutes to discharge for safety.
al engineers; DANGER
Ø Persons with limited physical or mental abilities may only work
3.During installation,except for the wiring terminals,please do not move other parts with the Growatt inverter following proper instruction and under
inside the chassis; constant supervision. Must keep the Growatt inverter away from
4.All electrical installations must comply with local electrical safety standards; children.
5.If the machine needs maintenance,please contact the local designated system
installation and maintenance personnel;
6.The use of this machine for grid-connected power generation requires permission
from the local power supply department; Ø Make all electrical connections (e.g. conductor termination,
7.When installing photovoltaic modules during the day,use opaque materials to fuses, PE connection, etc.) in accordance with prevailing
cover the photovoltaic modules,otherwise the voltage at the module terminals will regulations. When using the inverter to provide the power,
be high in the sun,which may cause personal danger. adhere to all prevailing safety regulations to minimize risk of
accidents.
2.3.1 Assembly Warnings WARNING Ø Systems with inverters typically require additional control (e.g.,
Ø Before installation, pleae check the unit to ensure that there is no switches, disconnects) or protective devices (e.g., fusing circuit
transportation or handling damage, which may affect the breakers) depending upon the prevailing safety rules.
insulation integrity or safety clearances; otherwise, it may cause
safety hazards.
Ø Follow the instructions in this manual to assemble the inverter.
Note that select the suitable mounting location and comply with
the specified requirements of cooling.
Ø Unauthorized removal of necessary protections, improper use,
incorrect installation and operation may lead to serious safety and
WARNING
shock hazards and/or equipment damage.
Ø In order to minimize the possibility of shock hazards due to
dangerous voltages, cover the entire solar array with dark colored
materials before connecting the array to any equipment.
5 6
2.3.3 Operation Warnings
Product overview 3
3.1 Appearance overview
7 8
Unpacking inspection 4
3.2 Dimensions Before opening the inverter package,please check whether the outer package is
damaged.After unpacking,please check whether the appearance of the inverter is
428
178 damaged or lack of accessories.If there is damage or missing parts,please contact the
dealer.
A B C D E
392
F G H I J K L M N O P Q
Fig 3.2
J Expansion screw 3
K Security screw 1
9 10
5 Installation
5.1 Basic installation requirements
Ø The wall on which the inverter is mounted must be sturdy and can withstand the
weight of the inverter for a long time (refer to the specifications in Chapter 12 for the
weight of the inverter);
Ø The installation location must match the size of the inverter;
Ø Do not install the inverter on a building constructed of flammable or heat-resistant
materials;
Ø Install the inverter in an eye-view orientation to facilitate inspection of the OLED
display and maintenance work;
Ø The machine's degree of protection is IP66 and can be installed indoors and outdoors;
Ø It is not recommended to expose the inverter directly to strong sunlight to prevent
overheating and cause power derating;
Ø The humidity of the installation environment should be between 0 and 90%;
Ø The ambient temperature around the inverter should be between -25 ° C ~ 60 ° C;
Ø The inverter can be mounted on a plane that is tilted vertically or backwards.
Please refer to the following figure:
Fig 5.2 Installation dimensions for one inverter
Ø In order to ensure the normal operation of the machine and the convenience of
personnel operation, please pay attention to provide sufficient clearance for the inverter.
Please refer to the figure below:
Above 500
Fig 5.3 Installation dimensions for multiple inverters
Under 500
Ø Do not install the inverter on the TV antenna, other antennas or antenna cables;
Both sides 300
Ø Do not install the inverter in the living area;
Forward 300 Ø Do not install the inverter where children can reach it;
Ø The inverter should be installed in a sheltered and protected location such as cool,
rain-proof;
11 12
5.2 Install the wall mount
5.2.1 Install the wall mount
Fig 5.4 Installation Environment Secure the wall mount as shown, do not let the screws flush with the wall, instead expose
2 to 4 mm.
Ø Make sure that the inverter is installed in a suitable place and is not allowed to be
installed in a closed box;
Ø In order to reduce the inverter load and extend the life of the inverter due to direct
sunlight, we recommend installing a awning. The distance between the awning and the
inverter is as follows:
13 14
Inverter wiring 6
6.1 Security
There may be a high voltage in the conductive part of the inverter,
which may cause electric shock.Therefore, when installing the
inverter,make sure that the AC and DC sides of the inverter are
Danger
powered off.
Fig 5.9 Schematic diagram of inverter wall mounting 6.2 AC side wiring
Before making electrical connections, please make sure that the
DC switch of the inverter is in the "OFF" state and disconnect the
AC side MCB, otherwise the high voltage of the inverter may
Danger
cause death.
15 16
Preparation before wiring: AC connection steps:
Connect the protective ground wire (PE) 1.Pass the 5 wires (A,B,C,N and PE wires) through the AC shield,connect them to the
Connect the inverter to the grounding bar through the protective earth (PE) to achieve power grid,and then crimp the O/U terminal.
grounding protection.
c
Fig 6.1 Grounding diagram Fig 6.2 AC output wiring diagram
Ø Disconnect the inverter DC switch,AC side circuit breaker or switch.
Ø Measure the voltage and frequency of the public grid (voltage:AC 230V;
frequency:50Hz) 2.Lock the AC cable to the corresponding AC terminal.
Ø
The recommended specifications of the AC output switch are as follows:
6mm² 30m
8 mm² 40m
19 20
Moisture and dust penetration can damage the inverter Connect DC terminal
Ø Make sure that the waterproof cable gland is firmly tightened.
Ø If the cable connector is not installed correctly,the inverter may be Positive connector
Cables Positive metal terminal
damaged due to the penetration of moisture and dust.All warranty claims
Note are void. 4~6mm²
4~6mm²
The MOD series inverter has two independent inputs, as shown in the figure below:
Cables
Negative metal terminal
Negative connector
Fig 6.9
3 4
1 2
21 22
2.Push the threaded sleeve into the socket and tighten the waterproof gland. 6.5 Grounding the inverter
Inverter side The inverter must be connected to the AC grounding conductor of the power distribution
grid via the ground terminal (PE) .
Fig 6.12
3.Connect the client to the inverter plug until both are tightly locked on the inverter.
6.6 Active power control with smart meter , CT or ripple control
signal receiver
Fig 6.16
Fig 6.14
Active power control with a Radio Ripple Control Receiver(RRCR).
2. Insert the H-shaped tool and pull it out of the socket.
23 24
6.7 Inverter demand response modes (DRMS) 6.7.3 Using the Power Control Interface for EU
This series inverter has the function of demand response modes, We use 16-Pin socket as RRCR
inverter DRMS connection.
6.7.2 Method of asserting demand response modes 6.8.3.2The inverter is preconfigured to the following RRCR power levels:
Socket asserted DRM Socket DRM Socket DRM Socket DRM Socket
Mode Function Active power Cos(φ)
by shorting pins Pin 9 Pin 10 Pin 11 Pin 12
DRM 0 14 13 Operate the disconnection device. Short circuit
0% 1
with Pin 13
DRM 5 9 13 Do not generate power.
Short circuit
30% 1
DRM 6 10 13 Do not generate at more than 50% of rated power. with Pin 13
Do not generate at more than 75% of rated power and Short circuit 1
DRM 7 11 13 60%
reduce the reactive power as far as possible. with Pin 13
Increase power generation (subject to constraints from Short circuit
DRM 8 12 13 100% 1
other active DRMs). with Pin 13
Active power control and reactive power control are enabled separately.
25 26
Debugging 7
6.8 AFCI(Optional) 1.Close the DC switch on the inverter.As long as the input DC voltage is greater
6.8.1 Arc-Fault Circuit Interrupter (AFCI) than 140V,the inverter display will show the following information:No mains
In accordance with the National Electrical Code R, Article 690.11, the inverter has a connection error,the inverter LED will turn red.
If other information is displayed,please refer to Chapter 8.If you encounter any
system for the recognition of electric arc detection and interruption. An electric arc
problems during the debugging process and cannot solve it,please contact customer
with a power of 300 W or greater must be interrupted by the AFCI within the time service.
specified by UL 1699B. A tripped AFCI can only be reset manually. You can deactivate 2.Close the circuit breaker or switch between the inverter and the grid, the inverter
the automatic arc fault detection and interruption (AFCI) via a communication product will start a countdown to the self-check,and after the self-check is normal,it will be
connected to the grid.
in "Installer" mode if you do not require the function. The 2011 edition of the National 3.In normal operation,the leaves of the inverter indicator window will turn green.
Electrical Code R, Section 690.11 stipulates that newly installed PV systems attached to 4.Finish debugging.
a building must be fitted with a means of detecting and disconnecting serial electric
arcs (AFCI) on the PV side.
If an "Error 200" message is displayed, the buzzer alarms, an electric arc occurred in
the PV system. The AFCI has tripped and the inverter is in permanent shutdown.
The inverter has large electrical potential differences between its conductors. Arc
flashes can occur through air when high-voltage current flows. Do not work on the
product during operation.
When the inverter error 200, please follow the steps:
Fig 6.19
Wait for the screen be off.
6.8.3.2 Perform troubleshooting on the PV system:
Check the PV strings' open circuit voltage is normal or not.
6.8.3.3 After the fault is rectified, restart the inverter:
Turn the DC & AC Switch to position "ON".
Fig 6.20
27 28
8 Working Mode OLED display and touch button 9
8.1 Normal mode The OLED display can display the running status of the inverter, as well as various
In this mode, the inverter works normally. parameters information, and the display interface of the inverter can be switched and
Ø When the DC voltage is greater than 250V, the energy is sufficient, and the grid the inverter parameters can be set by touching the button.
voltage frequency meets the grid-connected requirements, the inverter will convert
the energy of the solar panels into AC power and export to the grid, and the green Mark Describe Explain
LED will light up.
Switch the display interface or
Ø When the DC voltage is lower than 140V, the inverter will automatically disconnect Single touch
the current number plus 1
from the grid and exit the normal operation mode. When the input voltage reaches
Enter the setting state or
the requirement again and the grid voltage and frequency return to normal, the Double touch
confirm
inverter will automatically connect to the grid. Touch mark
Return to the previous display
Triple touch
interface
8.2 Failure mode The current data returns to the
The inverter controls the chip monitors and adjusts the state of the system in real time. Long press for 5s
default value
When the inverter monitors any unexpected conditions,such as system failure and
inverter failure,the display will show the fault information.In the failure mode,the 9.1 Boot display
inverter will indicate The leaves of the window will turn red and the inverter output will
be disconnected from the grid. When the inverter is turned on, the OLED display interface is as follows:
FW Ver:AK1.0
8.3 Shutdown mode
When the sunlight is weak or there is no sunlight,the inverter will automatically stop
Model:S03B00D
running.When in shutdown mode,the inverter basically does not consume energy from Growatt
00T00P00U00M0
the grid or solar panels,and at the same time,the inverter's display screen and LED lights PV inverter
000
will be turned off.
Connect in
More Info
30S
Power PV1
XXXXw XXXvXXXXw
Etoday PV2
XXXkWh XXXvXXXXw
Etotal Grid
XXXXw XXXvXXXHz
Fig 9.1
Exporlimit Meter
Set OK Set Comaddr Set Comaddr Language Language Set
OFF ON CT Set OK
1 2 Chinese English successfully
The factory setting of the inverter is CQC standard regulations. Customers can choose
different voltage protection levels according to the actual situation; a single touch
switches the voltage level, and two consecutive touches confirm the setting. Reset factory
Set Date
2018-12-14
0
Set
Voltage level 1
successfully
2 Set Time
Exportlimit
12:30:00
Fig 9.3
Set Comaddr
AUTO TEST
0 standard 1
31 32
Communication and Monitoring 10
Set Language 10.1 RS485
Set paramerter This series of inverters provide two RS485 ports. You can monitor one or more inverters
English
via RS485. The other RS485 port is used to connect a smart meter (stand-alone anti-
Double touch backflow function).
No. Description Remarks
Set Country Set Date
VDE0126 2018-12-14
1 +12V Dry junction : external relay
coil interface, power is not
2 COM more than 2W
Set Time
Exporlimit 3 RS485A1 Fig 10.1
12:30:30
RS485 communication port
4 RS485B1
Fig 10.3
33 34
11 Maintenance and Cleaning Troubleshooting 13
11.1 Checking Heat Dissipation 13.1 Error message
If the inverter regularly reduces its output power due to high temperature, please When a malfunction occurs, an error message will be displayed on the OLED screen.
improve the heat dissipation condition. Maybe you need to clean the heat sink. Faults include system faults and inverter faults.
In some cases, you may be advised to contact Growatt, please provide the following
information.
11.2 Cleaning the Inverter Information about the inverter::
●Serial number
If the inverter is dirty, turn-off the AC breaker and DC switch ,waiting the inverter shut
●Model
down ,then clean the enclosure lid, the display, and the LEDs using only a wet cloth. Do
●Error message on OLED
not use any cleaning agents (e.g. solvents or abrasives).
●A short description of the problem
●Grid voltage
11.3 Checking the DC Disconnect ●DC input voltage
●Can you reproduce the failure? If so, how?
Check for externally visible damage and discoloration of the DC Disconnect and the
●Has this problem occurred in the past?
cables at regular intervals.If there is any visible damage to the DC Disconnect, or visible
●What were the environmental conditions when the problem occurred?
discoloration or damage to the cables, contact the installer.
Ø Once a year, turn the rotary switch of the DC Disconnect from the On position to the Information about photovoltaic panels:
Off position 5 times in succession. This cleans the contacts of the rotary switch and ●PV panel manufacturer's name and model
prolongs the electrical endurance of the DC Disconnect. ●Panel output power
●Voc of the panel
●Vmp of the panel
●Imp of the group
●The number of panels in each string
●If you need to replace the device, please ship it to the original box.
35 36
Warning Warning
Description Suggest Description Suggest
message message
1Unplug the U disk;
1.Check whether the meter is turned on;
U S B o v e r c u r r e n t 2.Reconnect the U disk after shutdown;
Warning 207 Warning 401 The meter is abnormal 2.Check whether the connection between the
protection 3.If the fault message still exists,contact the
machine and the meter is normal.
manufacturer.
1.Check the fuse after shutdown; Optimizer and inverter 1.Check if the optimizer is open;
Warning 208 DC fuse is broken 2.If the fault message still exists,contact the Warning 402 communication 2.Check whether the connection between the
manufacturer. abnormal optimizer and the inverter is normal.
1.Disconnect the DC switch immediately and 1.Check the string board wiring after shutdown;
String communication
Panel voltage is too confirm the voltage; Warning 403 2.If the fault message still exists,contact the
Warning 209 abnormal
high 2.fter the normal voltage is restored, if the fault manufacturer.
message still exists,contact the manufacturer. 1.Restart the inverter;
1.Check the panel input; Warning 404 Memory exception 2.If the fault message still exists, contact the
Warning 210 Panel reverse 2.If the fault message still exists,contact the manufacturer.
manufacturer. The firmware version
1.Please confirm whether the power grid is lost; of the control board 1.Check the firmware version;
Warning 300 No mains connection 2.If the fault message still exists,contact the Warning 405 and the 2.If the fault message still exists, contact the
manufacturer. communication board manufacturer.
1.Check whether the AC voltage is within the do not match
Mains voltage is out of specification range of the standard voltage; 1.Restart the inverter;
Warning 301
range 2.If the fault message still exists,contact the Warning 406 Boost circuit failure 2.If the fault message still exists,contact the
manufacturer. manufacturer.
1.Check whether the frequency is within the
Mains frequency is out range;
Warning 302
of range 2.If the fault message still exists, contact the
manufacturer.
Warning 303 Output overload 1.Reduce output power;
2.If the fault message still exists, contact the
manufacturer.
Warning 304 Open current 1.Check whether the current transformer is
transformer connected well;
2.If the fault message still exists, contact the
manufacturer.
Warning 305 Reverse connection of 1.Check whether the current transformer is
current transformer connected reversely;
2.If the fault message still exists,contact the
manufacturer.
Warning 306 Communication failure 1.Please check the communication line;
of current transformer 2.If the fault information still exists,contact the
manufacturer.
Warning 307 Wireless CT pairing 1.Please check the communication line;
timeout 2.If the fault information still exists,contact the
manufacturer.
Warning 400 Fan function is 1.Check the fan wiring after shutdown;
abnormal 2.Replace the fan;
3.If the fault information still exists,contact the
manufacturer.
37 38
13.3 System error Error code Description Suggest
Error code Description Suggest 1.Restart the machine;
Abnormal DC
1.Check the panel terminal wiring after shutdown; Error 400 2.If the fault information still exists,contact the
component offset
2.Restart the inverter; manufacturer.
Error 200 DC arc abnormal
3.If the fault message still exists,contact the The output
manufacturer. 1.Restart the machine;
voltage DC
Error 401 2.If the fault information still exists,contact the
1.Restart the machine; component is too
Leakage current is manufacturer.
Error 201 2.If the fault information still exists,contact the high
too high
manufacturer. The output
1.Restart the machine;
1.Disconnect the DC switch immediately and confirm the current DC
Error 402 2.If the fault information still exists,contact the
Panel voltage is voltage; component is too
Error 202 manufacturer.
too high 2.After the normal voltage is restored,if the fault high
message still exists,contact the manufacturer. 1.Check whether the output current is unbalanced after
Unbalanced shutdown;
1.After shutting down, check whether the panel shell is Error 403
Low panel output current 2.If the fault message still exists, contact the
reliably grounded;
Error 203 insulation manufacturer.
2.If the fault message still exists,contact the
resistance
manufacturer. B u s v o l t a g e 1 Restart the machine
1.Check the grid voltage; Error 404 s a m p l i n g i s 2: If the fault information still exists, contact the
The mains voltage 2.If the grid voltage has recovered to the allowable range abnormal manufacturer
Error 300
is abnormal and the fault information still exists,contact the
manufacturer. 1.Restart the machine;
Error 405 Relay abnormal 2.If the fault information still exists, contact the
1.Please check the mains terminal;
manufacturer.
Error 301 AC wiring error 2.If the fault message still exists,contact the
manufacturer. 1.Reset mode;
Initialization
Error 406 2.If the fault message still exists,contact the
1.Check the AC side line connection after shutdown; mode exception
No mains manufacturer.
Error 302 2.If the fault message still exists,contact the
connection 1.Restart the machine;
manufacturer. Automatic
1.Check the ground wire after shutting down to ensure Error 407 2.If the fault information still exists,contact the
detection failed
Zero ground that the ground wire is connected reliably; manufacturer.
Error 303 1.Check the temperature after shutdown,restart the
detection anomaly 2 . I f t h e f a u l t m e s s a g e s t i l l e x i s t s , c o n t a c t t h e
manufacturer. Temperature is too inverter after normal;
Error 408
1.Detect grid frequency and restart; high 2.If the fault message still exists,contact the
Abnormal mains manufacturer.
Error 304 2.If the fault message still exists,contact the
frequency 1.estart the machine;
manufacturer. Abnormal bus
Error 409 2.If the fault information still exists, contact the
1.Check output load, reduce load power; voltage
Output overload manufacturer.
Error 305 2.If the fault information still exists,contact the
protection Inconsistent
manufacturer 1.Restart the machine;
insulation
Reverse 1.Check the connection direction of the current Error 410 2.If the fault information still exists,contact the
resistance
connection of transformer after shutdown; manufacturer.
Error 306 sampling
current 2.If the fault information still exists,contact the
transformer manufacturer. 1.Check the wiring of the communication version after
Internal
shutdown;
C o m m u n i c a t i o n 1.Please check the communication line; Error 411 c o m m u n i c a t i o n
2.If the fault message still exists, contact the
Error 307 failure of current 2.If the fault information still exists,contact the abnormal
manufacturer.
transformer manufacturer. 1.Check whether the temperature sampling module is
Temperature
1.The pairing of the machine and the current transformer properly connected after shutdown;
Error 412 sensor connection
is overtime, re-pair; 2.If the fault message still exists,contact the
Error 308 Pairing timeout abnormal
2.If the fault information still exists,contact the manufacturer.
manufacturer;
39 40
Manufacturer warranty 14
Error code Description Suggest Please refer to the warranty card.
1.Restart the machine;
Error 413 Drive exception 2.If the fault information still exists,contact the
manufacturer.
1.Restart the machine;
Error 414 Memory exception 2.If the fault information still exists,contact the
manufacturer. Decommissioning 15
Abnormal 1.Restart the machine; 15.1 Dismantling the Inverter
Error 415 a u x i l i a r y p o w e r 2.If the fault information still exists,contact the
supply manufacturer. 1. Disconnect the inverter as described in section8.
2. Remove all connection cables from the inverter.
1.Restart the machine;
Overcurrent
Error 416 2.If the fault information still exists,contact the
protection Danger of burn injuries due to hot enclosure parts!
manufacturer.
Wait 20 minutes before disassembling until the housing has cooled down.
The grid voltage 1.Restart the machine;
Error 417 sampling is 2.If the fault information still exists,contact the CAUTION
inconsistent manufacturer.
3. Screw off all projecting cable glands.
The firmware 4. Lift the inverter off the bracket and unscrew the bracket screws.
version of the
control board and 1.Restart the machine;
Error 418 the 2.If the fault information still exists,contact the 15.2 Packing the Inverter
c o m m u n i c a t i o n manufacturer. If possible, always pack the inverter in its original carton and secure it with tension belts.
board do not If it is no longer available, you can also use an equivalent carton. The box must be
match capable of being closed completely and made to support both the weight and the size of
Inconsistent 1.Restart the machine; the inverter.
Error 419 leakage current 2.If the fault information still exists,contact the
sampling manufacturer. 15.3 Storing the Inverter
L e a k a g e c u r re n t 1. Restart the machine; Store the inverter in a dry place where ambient temperatures are always between -25°C
Error 420 module is 2.If the fault information still exists,contact the and +60°C.
abnormal manufacturer.
41 42
16 EU Declaration of conformity Specification 17
With the scope of EU directives: 17.1 Parameter
•2014/35/EU Low Voltage Directive (LVD)
MOD MOD MOD MOD MOD MOD
•2014/30/EU Electromagnetic Compatibility Directive (EMC) Model
3000TL3- 4000TL3- 5000TL3- 6000TL3- 7000TL3- 8000TL3-
•2011/65/EU RoHS Directive and its amendment (EU)2015/863 Specifications
X X X X X X
Shenzhen Growatt New Energy Technology Co. Ltd confirms that the Growatt inverters
and accessories described in this document are in compliance with the above mentioned Input data(DC)
EU directives. The entire EU Declaration of Conformity can be found at www.ginverter.com. Max. recommended PV
4500W 6000W 7500W 9000W 10500W 12000W
power(for module STC)
Max. DC voltage 1100V
Start voltage 200V
Nominal voltage 580V
MPP voltage range 140-1000V
Full-load voltage range 250-800V 320-850V
No. of MPP trackers 2
No. of PV strings per MPP
1/1 1/1 1/1 1/1 1/1 1/1
trackers
Max. input current per
13/13A 13/13A 13/13A 13/13A 13/13A 13/13A
MPP trackers
Max. short-circuit current
16/16A
per MPP trackers
Backfeed current to PV
0A
array
Output data(AC)
AC nominal power 3000W 4000W 5000W 6000W 7000W 8000W
Max. AC apparent 3300VA 4400VA 5500VA 6600VA 7700VA 8800W
Nominal AC voltage/range 230/400V
50/60 Hz
AC grid frequency/range
45~55Hz/55-65 Hz
Max. output current 5.0A 6.7A 8.3A 10.0A 11.7A 13.3A
AC inrush current 30A
Max. output fault current 24.6A 44.5A
Max. output overcurrent
24.6A 44.5A
Protection
Power factor(@nominal
>0.99
power)
Adjustable power factor 0.8Leading ...0.8Lagging
THDi <3%
AC grid connection type 3W+PE /3W+N+PE
Efficiency
Max. efficiency 98.3% 98.6%
Euro-eta 97%
43 44
MOD MOD MOD MOD MOD MOD
Model Model MOD MOD MOD MOD MOD MOD
3000TL3- 4000TL3- 5000TL3- 6000TL3- 7000TL3- 8000TL3-
Specifications Specifications 9000TL3-X 10TL3-X 11TL3-X 12TL3-X 13TL3-X 15TL3-X
X X X X X X
Protection devices Input data(DC)
DC reverse-polarity
YES Max. recommended PV
protection 13500W 15000W 15000W 18000W 19500W 22500W
power(for module STC)
DC switch YES
Max. DC voltage 1100V
DC Surge protection typeII OPT
Start voltage 200V
Insulation resistance
YES Nominal voltage 580V
monitoring
MPP voltage range 140-1000V
AC surge protection typeII OPT
Full-load voltage range 320-850V 400-850V 480-850V 520-850V
AC short-circuit
YES
protection No. of MPP trackers 2
Grid monitoring YES No. of PV strings per MPP
1/1 1/1 1/1 1/1 1/2 1/2
trackers
Anti-islanding protection YES Max. input current per
13/13A 13/13A 13/13A 13/13A 13/26A 13/26A
Residual-current MPP trackers
YES Max. short-circuit current
monitoring unit 16/16A 16/16A 16/16A 16/16A 16/32A 16/32A
per MPP trackers
String Fuse protection YES
Backfeed current to PV
0A
String monitoring OPT array
AFCI protection OPT Output data(AC)
AC nominal power 9000W 10000W 11000W 12000W 13000W 15000W
General data
Max. AC apparent 9900VA 11000VA 12100VA 13200VA 14300VA 165000VA
Dimensions (W / H / D) in
425*381*138mm 425*381* 178mm
mm Nominal AC voltage/range 230/400V
Weight 13.5kg 15kg 50/60 Hz
AC grid frequency/range
Operating temperature -25°C ... +60°C 45~55Hz/55-65 Hz
range (>45°CDerating) Max. output current 15A 16.7A 18.3A 20.0A 21.7A 25A
Noise emission (typical) 35dB(A) AC inrush current 30A
Altitude 4000m Max. output fault current 44.5A 58.4A
Internal consumption at Max. output overcurrent
1W 44.5A 58.4A
night Protection
Topology Transformerless Power factor(@nominal
>0.99
power)
Cooling Natural heat dissipation Adjustable power factor 0.8Leading ...0.8Lagging
Electronics protection THDi <3%
Ip66
degree
AC grid connection type 3W+PE /3W+N+PE
Relative humidity 0~100%
Efficiency
DC connection H4/MC4(OPT)
Max. efficiency 98.6%
AC connection Waterproof PG head+OT terminal or quick connect terminal Euro-eta 97%
Interfaces
Display OLED+LED
USB/RS485 YES
WIFI/GPRS/4G/RF/LAN OPT
45 46
Model MOD MOD MOD MOD MOD MOD
Australian models
Specifications 9000TL3-X 10KTL3-X 11KTL3-X 12KTL3-X 13KTL3-X 15KTL3-X MOD MOD MOD MOD MOD MOD
Model
3000TL3- 4000TL3- 5000TL3- 6000TL3- 7000TL3- 8000TL3-
Specifications
Protection devices X X X X X-AU X-AU
DC reverse-polarity Input data(DC)
YES
protection
Max. recommended PV
DC switch YES 4500W 6000W 7500W 9000W 10500W 12000W
power(for module STC)
DC Surge protection typeII OPT Max. DC voltage 1100V
Insulation resistance Start voltage 200V
YES
monitoring
Nominal voltage 580V
AC surge protection typeII OPT
MPP voltage range 140-1000V
AC short-circuit
YES Full-load voltage range 250-800V 320-850V
protection
Grid monitoring YES No. of MPP trackers 2
No. of PV strings per MPP
Anti-islanding protection YES 1/1 1/1 1/1 1/1 1/2 1/2
trackers
Residual-current Max. input current per
YES 13/13A 13/13A 13/13A 13/13A 13/26A 13/26A
monitoring unit MPP trackers
String Fuse protection YES Max. short-circuit current
16/16A 16/32A
per MPP trackers
String monitoring OPT Backfeed current to PV
0A
array
AFCI protection OPT
Output data(AC)
General data
AC nominal power 3000W 4000W 5000W 6000W 7000W 8000W
Dimensions (W / H / D) in
425*381* 178mm Max. AC apparent 3000VA 4000VA 5000VA 6000VA 7000VA 8000W
mm
Weight 15kg 16.5kg Nominal AC voltage/range 230/400V
Noise emission (typical) 35dB(A) Max. output current 4.5A 6.0A 7.6A 9.1A 10.6A 12.1A
AC inrush current 30A
Altitude 4000m
Max. output fault current 24.6A 44.5A
Internal consumption at
1W Max. output overcurrent
night 24.6A 44.5A
Protection
Topology Transformerless
Power factor(@nominal
>0.99
Cooling Natural heat dissipation power)
Electronics protection Adjustable power factor 0.8Leading ...0.8Lagging
Ip66
degree THDi <3%
Relative humidity 0~100% AC grid connection type 3W+PE /3W+N+PE
DC connection H4/MC4(OPT) Efficiency
AC connection Waterproof PG head+OT terminal or quick connect terminal Max. efficiency 98.3% 98.6%
Interfaces Euro-eta 97%
Display OLED+LED
USB/RS485 YES
WIFI/GPRS/4G/RF/LAN OPT
47 48
MOD MOD MOD MOD MOD MOD MOD MOD MOD
Model Model MOD MOD MOD
3000TL3- 4000TL3- 5000TL3- 6000TL3- 7000TL3- 8000TL3- 9000TL3- 10TL3-X- 11TL3-X-
Specifications Specifications 12TL3-X 13TL3-X 15TL3-X
X X X X X-AU X-AU X-AU AU AU
Protection devices Input data(DC)
DC reverse-polarity
YES Max. recommended PV
protection 13500W 15000W 15000W 18000W 19500W 22500W
power(for module STC)
DC switch YES
Max. DC voltage 1100V
DC Surge protection typeII OPT Start voltage 200V
Insulation resistance Nominal voltage 580V
YES
monitoring
MPP voltage range 140-1000V
AC surge protection typeII OPT
Full-load voltage range 320-850V 400-850V 480-850V 520-850V
AC short-circuit
YES
protection No. of MPP trackers 2
Grid monitoring YES No. of PV strings per MPP
1/2 1/2 1/2 1/2 1/2 1/2
trackers
Anti-islanding protection YES Max. input current per
13/26A 13/26A 13/26A 13/26A 13/26A 13/26A
Residual-current MPP trackers
YES Max. short-circuit current
monitoring unit 16/32A 16/32A 16/32A 16/32A 16/32A 16/32A
per MPP trackers
String Fuse protection YES
Backfeed current to PV
0A
String monitoring OPT array
53 54