CL-NG-6460-002-023 Checklist For CT Rev02
CL-NG-6460-002-023 Checklist For CT Rev02
Substation
Bay/Panel
Equipment Serial No
2. Visual Inspection
Item Description Done Remarks
1. Inspect for physical damage or defects.
2. Check the current transformer insulation type is as per the Table-
1 in the standard 50-TMSS-01 as per its voltage class and
indoor/outdoor installations.
3. Nameplate:
a. Check that the CT nameplate is provided outside the switchgear
enclosure in addition to CT nameplate with the equipment.
b. Ensure that the nameplate material is stainless steel and it is
fastened to the equipment by stainless steel screws or rivets.
c. Ensure that the nameplate contains the information for all taps
from the highest tap up to the lowest tap including the specified
tap with the following additional information:
i. The words " ***kV Current transformer"
ii. National Grid SA Purchase Order Number and contract No.
/Job Order No. 50-TMSS-01 Rev.**.
d. Check nameplate and information with drawings and
specifications as specified in the Data Schedule.
4. Check the accuracy class for metering application CT as per the
approved design is 0.2 IEC or 0.3 ANSI unless otherwise
specified in the Data Schedule.
5. Ensure that Metering Cores of conventional have Instrument
Security Factor (ISF) less than or equal to 5.
6. For Metal-enclosed Air Insulated and Metal-Clad Gas Insulated
Switchgear 11 kV through 34.5 kV switchgear:
a. Ensure that CTs for bus bar differential and restricted earth fault
(REF) relays are of single-ratio type. Other relaying CTs are of
dual-ratio or multi-ratio as per protection requirement.
7. For Metal-enclosed Air Insulated Switchgear 11 kV through 34.5
kV switchgear:
a. Ring type CT on cable and as part of Circuit breaker spout or
mounted on breaker truck is not acceptable.
8. For Oil-Immersed CT, ensure the followings with the Contractor:
a. The insulating Oil is polychlorinated biphenyls (PCB).
b. The mineral insulating oil conforms to 54-TMSS-01 or 54-
TMSS- 02.
9. a. Check color-coding of secondary wiring is Red, Yellow, Blue, and
Black.
NATIONAL GRID SA
b. Ensure that the wire color code for CT circuits wiring between
GIS equiment and LCC (Local control cubicle) are identified with
RED, YELLOW, BLUE & BLACK color with necessary ferrules.
c. Ensure that that in GIL(Gas Insulated Line), power transformer,
and in the relay and control panels, the CT circuits wiring color-
coding is as per latest revision of 01-TMSS-01
10. Terminals:
a. Check the degree of protection of enclosure for the secondary
terminal box is as per 01-TMSS-01.
b. Check that Removable cable gland plate is provided on the
terminal box.
c. Ensure that the CT secondary terminals are of non-captive pan
head screw type and accept copper cable of adequate size as
determined by CT sizing calculation with a minimum of 4 mm².
d. The internal Current secondary circuits wiring size in all
relay/control panels shall be 2.5 mm2. The cable sizing
selection of external wiring shall meet the requirements of the
latest revision/amendment of TES-P-119.29 and the project
technical specification requirements PTS.
e. Ensure that the Facility is provided for shorting and grounding of
secondary terminals inside the CT terminal box.
f. Check primary and secondary terminals and polarity are marked
as per applicable standards and protection requirement.
g. Ensure that all wiring are heat and flame retardant, rated 90 °C
maximum operating temperature, rated 600/1000 V, with PVC
insulated, tinned, stranded annealed copper conductor.
h. Check proper lugs have been used on terminations as following:
i. Wires for screw-type with spring-loaded terminal block have
solderless “O” ring tin-plated copper type terminal. Spade/fork
type terminals is not used.
ii. The terminal blocks for CT secondary wiring are of shorting
type, sliding link type (isolating link) type and clearly marked
to indicate the CT's phase and ratio in use. CT's shorting
type terminal blocks provide a ground connection when CT
shorting is applied.
iii. Bypass facility is used whenever CT is wire for more than one
IED.
iv. Short and isolate facility is provided in all CT terminals.
v. Instruction labels are provided for short before isolate.
vi. A clear note in the scheme is provided for short/isolate
arrangements description
i. In the relay panels, shrouds are fitted to all current circuits’
terminal blocks.
j. Check that in the control and relay panels for each CT circuits
nine (9) terminals and proper shorting and isolating
arrangement
NATIONAL GRID SA