Koc Standard FOR Process Flow Measurement: Standards Publication
Koc Standard FOR Process Flow Measurement: Standards Publication
KOC STANDARD
FOR
STANDARDS TEAM
DOC. NO. KOC-I-026 Page 2 of 74 Rev. 0
TABLE OF CONTENTS
PAGE NO.
FOREWORD 4
1.0 INTRODUCTION 5
2.0 SCOPE 6
3.0 APPLICATION 6
4.0 TERMINOLOGY 6
4.1 Definitions 6
4.2 Abbreviations 9
ACKNOWLEDGEMENT 74
DOC. NO. KOC-I-026 Page 4 of 74 Rev. 0
FOREWORD
This document “KOC Standard for Process Flow Measurement” (KOC-I-026 Rev. 0) is
intended to provide the minimum requirements for the design, selection, construction, installation
and testing of Flowmeters to be installed at KOC Facilities within Kuwait.
This Standard has been approved by the Standards Team in consultation with the ESTC
Sub-Committee (Technical) for use throughout the Engineering and Operational functions of
Kuwait Oil Company (K.S.C.).
a) To provide technical guidance and establish a base document for developing project
specifications for flowmeters to achieve uniformity, safety, quality, reliability and efficiency
in an economical manner.
c) To set out minimum features required, typical data sheets have been included to ensure
that all the minimum requirements for design and construction of flowmeters &
accessories are covered.
d) To maintain the Health, Safety and Environment (HSE), including Process Safety
Management (PSM), requirements for the safety, integrity & protection of personnel,
environment and assets.
Feedback as well as any comments or suggestions derived from the application of this
Standard at any stages of the projects are invited and should be directed to:
1.0 INTRODUCTION
1.1 Currently in KOC, the design, selection, construction, installation and testing
requirements of flowmeters meant for process flow measurement have been
covered in the following documents:
1.2 The contents related to the flowmeters design, selection, construction, installation
and testing etc. requirements from the above documents are updated and
amalgamated into this document “KOC Standard for Process Flow Measurement” to
avoid duplications and likely differences of interpretations between these
documents.
2.0 SCOPE
2.1 This Standard specifies the minimum requirements for the design, selection,
construction, installation and testing of flowmeters to be installed at various KOC
Facilities within Kuwait.
2.2 Fiscal / Custody transfer and allocation flow metering systems are not covered in this
Standard.
3.0 APPLICATION
3.1 The design, selection, construction, installation and testing of flowmeters shall fully
comply with all relevant requirements specified in this Standard and the reference
Standards / Codes mentioned herein.
3.2 Any exceptions or deviations from this Standard, along with their merits and
justifications shall be brought to the attention of KOC Controlling Team for their
review, consideration and amendment by the Standards Team (if required).
3.3 Compliance with this KOC Standard does not of itself confer immunity from legal or
statutory obligations.
4.0 TERMINOLOGY
4.1 Definitions
4.1.1 Accuracy
It is the ratio of the orifice (primary element) bore diameter (d) to the pipeline inner
diameter (D).
4.1.3 Calibration
Set of operations which establish, under specified conditions, the relationship between
values of quantities indicated by a flowmeter and the corresponding values indicated
by a standard of reference.
4.1.4 Deadband
4.1.5 Density
Difference between the (static) pressures measured at the wall pressure tappings,
one of which is on the upstream side and the other of which is on the downstream
side of a primary device (pressure differential device), inserted in a straight pipe
through which flow occurs, when any difference in height between the upstream and
downstream tappings has been taken into account.
4.1.7 Error
Element of the flow measurement that performs the flow computation and flow
integration.
Note: A flow computer is a tertiary device and is usually a fiscal element in the
measurement system.
The ratio of gas volume flow rate to the total liquid volume flow rate at any point,
expressed at standard conditions, usually in standard cubic feet per barrel (scf / bbl)
or standard cubic meters of gas per cubic meter of total liquid (m3 / m3).
The ratio of gas volume flow rate to the liquid hydrocarbon volume flow rate at any
point, expressed at standard conditions, usually in standard cubic feet per barrel (scf
/ bbl) or standard cubic meters of gas per cubic meter of liquid hydrocarbon (m3 / m3).
The fraction of the total volumetric flow rate at actual conditions in the pipe that is
attributable to gas flow, often expressed as a percentage.
4.1.12 K- Factor
The KOC Team authorised and responsible for the execution and overall control
of the Project.
The fraction of the total volumetric flow rate at actual conditions in the pipe that is
attributable to liquid flow, often expressed as a percentage.
DOC. NO. KOC-I-026 Page 8 of 74 Rev. 0
4.1.16 Multiphase
Flow of a composite fluid that includes natural gas, hydrocarbon liquids, water and
injected fluids or any combination of these.
Region, between the extreme lower and upper range-values, outside which
irreversible change in the performance of the flowmeter will occur.
4.1.18 Rangeability
Dimensionless parameter expressing the ratio between the inertia and viscous forces.
A digital computer that processes the data from one or more flow computers for
producing reports, graphic displays and communicating with the process control
network.
It is the ratio of the maximum flow rate to minimum flowrate of the measuring
range.
4.1.23 Watercut
The water volume flow rate, relative to the total liquid volume flow rate (oil and
water), both converted to volumes at standard pressure and temperature.
Watercut generally expressed in percentage.
The water volume flow rate, relative to the total liquid volume flow rate (oil and
water), at the actual conditions (operating pressure and temperature), expressed
as a percentage.
DOC. NO. KOC-I-026 Page 9 of 74 Rev. 0
4.2 Abbreviations
DP Differential Pressure
FT Flow Transmitter
HP High Pressure
ID Internal Diameter
IP Ingress Protection
LP Low Pressure
OD Outer Diameter
PD Positive Displacement
PT Pressure Transmitter
QA Quality Assurance
QC Quality Control
DOC. NO. KOC-I-026 Page 11 of 74 Rev. 0
TT Temperature Transmitter
VA Variable Area
WC Water Cut
WG Water Gauge
5.1 Conflicts
In the event of conflict between this Standard and the latest editions of standards /
codes referred herein or other purchase or contractual requirements, the most
stringent requirement shall apply.
ANSI B16.36 Steel Orifice Flanges Class 300, 600, 800, 1500 & 2500
6.1 The environmental conditions in Kuwait are severe and shall be considered
carefully while design, selection, construction, installation and testing of
flowmeters. The atmosphere shall be considered to be dusty, corrosive and may
contain traces of hydrogen Sulphide (H2S), SOx / NOx gases & airborne chemical
contaminants.
6.2 For detailed information regarding the environmental, site and utility supply
conditions prevailing throughout the KOC Facilities, KOC-G-007 “KOC Standard
for Basic Design Data” shall be referred.
7.1 General
7.1.1 The flowmeters are normally installed in the field / open areas and it shall be
suitable for environmental conditions mentioned in Clause 6.0 of this Standard for
operation under the temperature from -3˚ C to 55˚ C & Relative Humidity 100 %,
unless otherwise specified in the Project Documents / Datasheet.
DOC. NO. KOC-I-026 Page 16 of 74 Rev. 0
7.2.2 The flowmeters to be installed in hazardous area shall be certified for use in those
areas by a testing authority of an international recognition. The list of testing and
certifying agencies acceptable to KOC are given in “KOC Recommended Practice
for Selection, Installation and Maintenance of Electrical Equipment in Hazardous
Areas” (Doc. No.: KOC-E-004 Part 2).
7.2.3 The copies of hazardous area certification documents shall be submitted to KOC
for review and approval.
8.1 Relevant KOC HSE requirements, including PSM requirements and specifically the
procedure for Inherently Safer Design (ISD), shall be adhered to while designing,
engineering and material selection so as to safeguard personnel, environment and
assets during the use of the flowmeters. Materials containing asbestos shall not
utilised in the assembly / manufacture or during installation of flowmeters.
8.2 The Vendor / Contractor shall ensure compliance with KPC HSSE Policy and all
applicable KOC HSE procedures to protect personnel, property and surrounding
environment during on-site field activities and while performing any work within
KOC areas at all times.
8.3 Appropriate Permit to Work (PTW) with applicable Job Safety Analysis (JSA)
document for the work to be carried out shall be prepared by the Contractor in line
with the relevant KOC HSE Procedures and submitted to KOC Controlling Team
for approval prior to commencement of any work within KOC areas. The PTW and
JSA documents shall address all relevant HSE requirements as per KOC “Permit
to Work Procedure” (KOC.SA.004) and “Job Safety Analysis Procedure”
(KOC.SA.024).
8.4 All personnel engaged in site works shall have successfully undergone all the
applicable trainings and awareness courses as per the “Matrix of identified
categories of personnel identified under ‘HSE Training’ and ‘HSE Awareness’ for
Contractors’ Employees” in the KOC HSE procedure “HSE Training, Awareness
and Continued HSE Learning Process” (KOC.GE.028).
DOC. NO. KOC-I-026 Page 17 of 74 Rev. 0
8.5 All personnel carrying out site works, including Supervisors, shall use appropriate
Personal Protective Equipment (PPE) during the execution of works as identified
by the job requirement and in line with the requirements of KOC “Procedure for
Personal Protective Equipment” (KOC.SA.010) and KOC Standard for “Personal
Protective Equipment” (KOC-L-010).
8.6 The Contractor shall ensure the safe handling of equipment during the
construction works. The tools and equipment used for the works shall be
periodically inspected and certified for safe use in all KOC areas. Contractor’s
mobile plant / equipment entering KOC areas shall be certified “Fit for Service” by
Third Party Inspector and shall obtain clearance certificate as per KOC “Mobile
Equipment Procedure” (KOC.SA.013).
8.7 The Contractor personnel shall take all necessary precautionary measures to
ensure safe handling of loads during the work as per KOC “Safety Procedure for
Mechanical Handling of Loads” (KOC.SA.029) and “Manual Handling of Loads”
(KOC.SA.003).
8.8 All personnel carrying out site works shall comply with KOC.SA.025 “Procedure
for Handling of Explosive Materials, Substances and EOD”. No site work in KOC
area shall be carried out without ensuring explosive ordinance disposal clearance
for that location as per KOC.SA.025. In addition, it is mandatory for Company &
Contractor employees to attend EOD awareness / training session in line with
KOC.GE.028 “HSE Training, Awareness and Continued HSE learning Process”.
8.9 All wastes (hazardous / non-hazardous) arising out of all activities shall be
managed in a safe and environment friendly manner in accordance with the KOC
“Waste Management Procedure” (KOC.EV.008). All personnel engaged at site
work in KOC areas shall be fully aware of the need for good housekeeping and
shall adhere to KOC “Housekeeping Procedure” (KOC.GE.034) during all work
activities.
9.1 General
9.1.2 The flowmeters and related accessories design shall be suitable for the
environmental conditions as mentioned in Clause 6.0 of this Standard.
9.1.3 The flowmeters body ratings and connections shall confirm to the project piping
material class specification.
9.1.4 Different types of flowmeters are available for measuring both volumetric and mass
flowrates, which are detailed in the following Clauses.
DOC. NO. KOC-I-026 Page 18 of 74 Rev. 0
9.2.1 The common flow measuring devices are generally classified into three (3)
categories i.e. head type or differential pressure flowmeters, volumetric flowmeters
and mass flowmeters.
9.2.2 The head type / differential pressure flowmeters include orifice plates, venture
tube, averaging pitot tube, flow nozzle, v-cone, etc.
9.2.4 The above mentioned categories of flowmeters are most commonly used to
measure the flow rate of liquids and gases flowing through pipes, which are
described in the following sub-clauses.
9.3.1 There are various types of flowmeters available and each type having its own
advantages and disadvantages. Hence, the selection of flowmeter for a particular
application is an important task.
9.3.2 The basis of a good flowmeter selection is a clear and thorough understanding of
the requirements of the particular application that the flow sensor is intended for.
To successfully select a flowmeter that will be able to operate in the desired manner,
the design engineers shall analyse the properties and flow characteristics of the fluid,
the piping requirements and many other factors. The factors which shall be
considered carefully include, but not limited to the following:
d) Chemical compatibility
f) Is the fluid corrosive, does the fluid contain slurry or large solids
i) Uni-directional or bi-directional
o) Flow turndown
t) Maintenance issues
u) Operating costs
x) Versatility (like can the meter be easily re-ranged, can the meter be used in
other applications, etc.)
9.3.3 To select right flowmeter technology from a variety of technologies available, Table
provided in Appendix-A of this Standard and below mentioned points shall be
referred for usage and guidance.
b) Pipe taps shall be used where back-flushed chemical seals are required,
for services such as viscous, corrosive or particulate service.
c) Corner tappings with corner tapping assembly shall be used for clean fluids
and vapors or for liquefied gases within the calculation requirements of
IS0 5167.
g) Fabricated metering runs shall be used for line sizes 2 in. and below. Sizes
smaller than 2 in. shall only be used if it can be shown that swaging up to
2 in. is not viable. Vent and drain holes shall not be used on orifice plates
fitted into metering runs.
h) Where low pressure loss is essential, venturi or flow tube (Dall) type meters
shall be used. Venturi nozzles shall be used only if the flow remains
sub-sonic throughout the measurement section; the pipe Reynolds No. is
greater than 10,000 for pipe sizes greater than 2 inches.
j) For small rates of flow and where high accuracy is not required such as
samples for analysers, variable area meters shall be used. For purging flow,
variable area meters with a constant flow regulator and a low-flow alarm
shall be used.
m) For slurries, chemical effluent and fluids which are electrically conductive,
magnetic flowmeter shall be used.
n) For wet gas flows with single phase measurement, a venture, V-cone or
orifice plate shall be used.
o) Sight glasses shall only be used at atmospheric pressure on oil and water
flows to machinery, where the lack of a flow will cause an alarm from
another measurement before any injurious result could arise.
9.4.1 General
i) The flowmeters electronic housing shall be certified for intrinsically safe (IS)
for the hazardous area classification as specified in project documents /
datasheets. The use of flameproof certified flowmeters shall be restricted
for the application where it is inevitable and shall require KOC approval.
j) All the flowmeters shall be suitable for outdoor installation and shall be
weatherproof to IP 65 as a minimum in accordance with IEC 60529, unless
otherwise specified in the project documents and approved by KOC.
m) The use of 110 V AC UPS power supply and other form of output signals
(digital communication, pulse output, etc.) shall be as per project
documents / datasheet and subject to KOC approval.
q) All the flowmeter transmitters (integral or remote mounted) shall have LCD
display local indicators and display shall be in engineering units.
u) Where specified, the separate cable entry connections shall be provided for
input, output and power supply as applicable.
aa) The Manufacturer shall calibrate (latest calibration methods) the flowmeters
at minimum five-points (10 %, 25 %, 50 %, 75 % and 100 %) of the
maximum flow for each flowmeter and has to submit the calibration report
to the KOC. Calibration to be performed with a fluid viscosity as close as
possible to the actual process.
ac) The Manufacturer shall provide the pressure drop across the flow element
/ meter based on selected flowmeter size.
ad) The Manufacturer shall specify the straight length of pipes required on
upstream and downstream of flowmeter based on the type of meter being
used and referring to the applicable National / International standards. The
Appendix-B of this Standard shall be referred for straight piping requirements
for flowmeters installation.
ae) If the transmitter output is used to assist the local operation of a control
valve with hand-wheel or valved bypass, a local indicator with display in
engineering units shall be installed near the control valve.
af) For the remote mounted type flowmeters, the transmitters shall be suitable
for 2 inch. pipe mounting and mounting accessories shall be minimum
SS 316 / SS 316 L supplied by Manufacturer.
ah) All flowmeters shall have a permanent marking with an arrow indicating the
flow direction.
DOC. NO. KOC-I-026 Page 24 of 74 Rev. 0
aj) All flowmeters associated equipment and calibration software needed for
maintaining / changing input data shall be provided by the Manufacturer.
am) The flow elements shall be engraved with the following information as
minimum:
an) All the flowmeters shall be supplied with embossed stainless steel (SS 316
/ SS 316 L) manufacturer labels. The label shall be permanently attached
using stainless steel screws or stainless steel bolts riveted. Each nameplate
shall include as minimum, the following information:
ao) Where applicable, painting and coating of flowmeters shall conform to KOC
Standards unless otherwise approved by KOC.
a) Alarms
c) In case of dual DP type orifice meters, the same orifice plate and flange set
shall be used for all transmitters, but each instrument shall have its own
isolation valve and tubing hook-up connections.
b) VA meters fitted with constant flow regulators may only be used for fixed
rate flows such as flushing and purging. The flow alarm signal shall be
provided from VA meters.
c) The material selected for orifice plates and other wetted parts shall be
compatible with the fluid handled and shall be as per project piping material
specifications. The standard orifice plate material shall be SS 316 /
SS 316 L. This selection shall be varied when process conditions require
an alternative material.
e) Generally, Concentric Orifice plates and flange tappings shall be used for
all installations unless otherwise specified by the KOC. Dual tappings to be
used in applications requiring a shutdown function plus a control or alarm
function.
f) The sections of pipe to which the orifice flanges are attached shall be
cylindrical, smooth and free from splatters, burrs and scales. Mill finish of
the inside wall shall be satisfactory. All welding slag and excessive metal
projections shall be removed by grinding after the flanges are installed.
DOC. NO. KOC-I-026 Page 26 of 74 Rev. 0
g) The calculated d / D ratio (Beta ratio) for square-edged orifice plates shall
be within the range 0.4 to 0.70 (typically around 0.6) for new equipment.
For plant modification or exceptional cases, both subject to approval by
KOC, ratios between 0.25 and 0.75 are acceptable. If the initially calculated
beta ratio exceeds 0.7 for a 500 mbar (200 ins WG) DP transmitter range,
the line shall be swaged up for the metering length as necessary. In normal
operating range DP shall be around 75 % of the maximum flow.
h) The beta ratio for conical entrance plates shall not exceed 0.3, and for
quarter circle shall not exceed 0.6. The usage of conical entrance and
quarter circle orifice plates shall be made only if it is proved that a square
edged orifice plate cannot be installed for measurement.
j) The flange material, rating, facing and type of gasket shall be as per
relevant piping material class specification.
k) Where RTJ gaskets are specified, flange or corner taps shall not be used.
Alternatives such as pipe taps (D and D / 2 or 2.5D and 8D), orifice carriers
or alternative instruments shall be considered. For difficult cases, fabricated
spool inserts with integrally machined orifice may be offered for approval by
KOC.
Note: Information ii, v, vi and viii to be stamped on the orifice paddle plate
on upstream facing side.
b) The averaging pitot tubes (Annubar) used for flow measurement shall be
based on differential pressure principle.
e) The process connection for the sensor assembly shall be flanged type with
flange size, rating, facing and surface finish in accordance with piping
material class specification as indicated in datasheet.
g) Based on the process data provided, the Manufacturer shall submit sizing
calculations for KOC review and approval.
c) The construction of venturi tube shall be in accordance with the ISO 5167.
d) The differential pressure shall be measured over the throat of the venturi.
e) Venturi shall have permanent marking with an arrow indicating the flow
direction.
f) The end connections for venturi shall be flanged connection which shall
comply with project piping material specification.
c) Differential pressure transmitters shall have a minimum 100 bar (1450 psi)
rated stainless steel body. All wetted parts shall be 316 stainless steel as
minimum with superior alternative materials to suit service conditions.
f) Square root extraction shall be carried-out in the flow transmitter and where
flow compensation is required, it shall be carried-out in the control system.
g) If the output is used to assist the local operation of a control valve with hand
wheel or valved bypass, a local indicator with display in engineering units
shall be installed near the control valve.
DOC. NO. KOC-I-026 Page 29 of 74 Rev. 0
k) The tappings for all instruments used for handling viscous or corrosive fluids
or slurries shall be sealed. Seals shall be the liquid type employing seal
pots or the chemical type (diaphragm seal) utilizing a diaphragm with silicon
oil (or other fluid) between the diaphragm and the pressure element of the
instrument.
l) Diaphragm seals are the preferred method for these applications within the
temperature limitations for this type of seal. The transmitters shall be
supplied with the capillary tubes fitted and tested as a unit. The low and
high pressure transmitter chambers shall be of equal volume when these
seals are fitted. Connecting capillary tubing shall be 3 mm (1/8 in.) stainless
with spiral-wound stainless steel armour.
d) VA meters of the tapered tube and float type shall be used where
appropriate.
DOC. NO. KOC-I-026 Page 30 of 74 Rev. 0
g) The tube and float shall be renewable without recalibration being required.
c) The flowmeter body and wetted parts material shall be SS 316 (as a
minimum) and electrodes shall be platinum or hastelloy unless otherwise
specified in the project document / datasheet.
e) Flowmeter shall be with flanged end connections and it shall be as per ASME
B16.5 / B16.47 as applicable. Flange rating and facing shall be as specified
in the instrument datasheet.
h) The flowmeter shall have multiline LCD display with facility to show flow rate
indication with engineering units and flow totaliser.
b) The turbine flowmeter shall be with flanged end connections and it shall be
as per ASME B16.5 / B16.47 as applicable. Rating and facing shall be as
specified in project documents / datasheet.
c) The body rating shall be suitable for the service conditions specified in
datasheet. The connection flanges shall be ANSI 300 lb minimum .
e) The turbine flowmeter shall meet the accuracy requirements as per project
documents / datasheet.
i) The upstream strainers and air vapor separator shall be provided to protect
turbine flow meter where applicable and specified in project documents.
m) The flowmeter enclosure and terminal box shall be rated for use in the
required hazardous area classification.
n) The meter shall exhibit linear relationship between the meter output and
flowrate.
o) The flowmeter shall be provided with LCD display for flowrate and totaliser
indications. The meter shall have totaliser reset facility (from key pad or
remote pulse).
f) The flowmeter end connections shall comply with the standard of the
pipework in which the flowmeter is installed.
i) The flowmeter shall be provided with LCD display for local indication.
f) For applications like flare gas metering, the meters shall be able to operate
in the conditions like varying flare gas temperature, pressure, composition
and unsteady flow. The requirements like meter range, access platforms
for maintenance of sensors online needs to be considered in flowmeter
design.
DOC. NO. KOC-I-026 Page 34 of 74 Rev. 0
i) The meters shall provide a pulse output in addition to 4-20 mA HART signal
at 24 V DC, where specified in project documents / datasheets.
j) The meters shall provide diagnostics over an RS485 serial or Modbus TCP
connection to a host system where specified in project documents /
datasheets.
k) The flowmeter shall be easily programmable and provided with auto zeroing
facility. The calibration of the flowmeter shall be carried out at the specified
operating conditions viz. viscosity, temperature and density for the fluid
mentioned in the specifications.
l) The Manufacturer shall submit sizing calculations for KOC review and
approval.
j) The Manufacturer shall submit sizing calculations for KOC review and
approval.
k) Flow transmitter shall have provision for accepting temperature and density
input signals for compensation.
m) The local transmitter LCD display shall provide indications mass flowrate,
flow direction, temperature, density, diagnostic messages, etc. as
applicable.
e) Flowmeter body and all wetted parts material shall be SS 316 / SS 316L as
a minimum unless otherwise specified in project documents / datasheets.
All the process wetted parts materials in sour service shall comply with
requirements of NACE MR-0175 / ISO 15156.
h) The flowmeter shall be provided with local LCD display. The local display
shall provide raw mass flowrate as a minimum along with diagnostic
messages.
b) PD meters shall be of the nutating disk type, rotary vane type or oval gear
type as specified in project documents and datasheets.
c) The meter body and wetted parts material shall be SS 316 / SS 316L (as a
minimum) unless otherwise specified in the project document / datasheet.
a) Where specified in the project documents, the flow switches shall be used
to continuously monitor the flow rate and provide output signal to
corresponding system as per project documents.
b) The flow switches shall be suitable to adjust the set point values where
required.
c) Flow switches shall be modular in design and switch body housing and
internal parts material shall be SS 316 as minimum unless otherwise
specified in project documents.
a) The local visual sight flow indicators shall be provided to monitor or indicate
the presence of fluid flow where applicable.
b) The viewing glass shall be toughened glass suitable for chemical attacks
and abrasions. The window shall be suitable for replacement and servicing.
c) The body, process connections and other materials shall be as per project
documents and datasheet.
DOC. NO. KOC-I-026 Page 38 of 74 Rev. 0
a) For reducing or eliminating flow swirl and for accurate measurement, flow
conditioners can be used subject to KOC approval.
b) The location of flow conditioners shall comply with ISO 5167, API MPMS
and / or AGA standards requirements.
c) The pressure drop across the flow conditioner shall be minimum and the
Manufacturer shall submit pressure drop calculations for KOC approval.
To be able to get optimum performance and better accuracy, the design engineers
shall ensure that straight piping runs at the upstream and downstream of the flow
element / flowmeter. The following minimum guidelines and requirements shall be
adhered to install flowmeters:
b) Where it is not practical to meet the required straight pipe runs for the
flowmeter, suitable flow conditioner for flow straightening can be installed
subject to KOC approval.
d) Ensure that the correct direction of flow as indicated by the arrow on the
flowmeter body.
m) Where there is vortex or corkscrew flow, increase inlet and outlet sections or
install flow straighteners.
n) Install two or more meters in parallel if the flow rate is too great for one meter.
p) Make sure there is sufficient clearance for installation and maintenance work.
10.2 The Appendix-B of this Standard shall be referred for straight piping requirements
for flowmeters installation.
a) Piping isolation block valves shall be supplied for all differential pressure
installations. Transmitters may share isolation valves (e.g., in the case of
high turndown applications where two transmitters are used) but
instruments on shutdown service shall have individual locked open block
valves.
f) Process line tappings shall be fitted with line class isolating valves of
roddable type. lnstruments shall be close coupled whenever possible. The
use of condensate pots and vent chambers shall be minimised by use of
respective elevations of the tappings and the instrument, to provide
self-draining for dry gases and self-venting / wet leg filling for liquids and
condensates.
h) Horizontal metering runs are preferred for liquid flow and are mandatory for
eccentric orifices. Vertical runs may be used with downward flow for steam
and condensates and upward flow for liquids close to their boiling
(vaporisation) point.
a) The connecting pipe shall be the same size but, in no case, more than or
less than one pipe size different than the meter connection size. Standard
meters, which use gravity to return the float to the rest position, shall be
installed within 5° of vertical.
b) Metal tube meter shall be installed in a location, which is free from vibration.
c) Metal tube meters shall be installed away from strong magnetic fields.
d) Fluids which may contain solids shall be adequately filtered upstream of the
VA meters.
e) VA meters shall be located with sufficient clearance to permit tube and float
removal without removing the meter body from the line.
DOC. NO. KOC-I-026 Page 41 of 74 Rev. 0
f) If the flow must not be interrupted during plant operations, line size block
and bypass valves shall be provided. The meter shall normally be fitted in
the bypass leg to avoid line stresses being imposed on the meter.
c) For liquid measurement, pipes shall be fully filled with liquids. It is essential
that pipes shall be fully filled with liquids, otherwise flowrate indications may
be effected and measurement errors will occur.
e) The location shall be selected such that, it allows regular inspection and
maintenance.
e) The gaskets material shall be compatible with the process fluid and
operating conditions. Metallic / spiral-wound gaskets are not recommended
with some liners. For the details of gaskets materials and other
requirements, KOC-MP-010 “KOC Standard for Piping Material Classes”
shall be referred.
DOC. NO. KOC-I-026 Page 42 of 74 Rev. 0
g) The flowmeter location shall be away from the strong magnetic fields or
other major sources of electrical interference.
a) The minimum distance that the flowmeter shall be installed from the pumps,
valves, elbows etc., shall be as per Manufacturer’s instructions.
d) The flowmeter when mounted in horizontal pipes should always have the
transducers mounted in horizontal plane.
e) Deposits (like wax, dirt and sand) if any in pipeline will reduce the accuracy of
meter. Accumulation of deposits should be avoided by providing proper
filtration equipment.
a) A double block and bleed assembly (with spectacle blind) shall be provided
downstream of the flowmeter, to facilitate accurate zeroing under line
pressure, unless otherwise approved by KOC.
b) Ensure that the gas bubbles or solids are not allowed to accumulate in the
flowmeter. The strainers, filters, air / vapour eliminators etc. as necessary to
remove solids / liquids shall be placed upstream from the flowmeter.
e) Coriolis flowmeters should not be installed close to valves that will regularly
open and close which can cause pulsations / vibrations in the flow and lead
to errors in the measurement.
h) To avoid flowmeters damage during plant start-up, the flowmeter and air
eliminator shall be installed after final flushing.
a) The flowmeter shall be installed so that the body is not subject to pipe strain.
The pressure drop across the PD and Turbine meter shall not cause
cavitation or flashing.
d) Turbine meters are normally installed in horizontal lines but can be in the
vertical as well. Usually the flowmeter shall be installed in same position as
they were calibrated.
e) Turbine meters shall have an upstream strainer to prevent rotor and bearing
damage.
f) Turbine and PD meters shall be mounted in the pipelines that are always
full of the fluid to be measured.
h) To avoid flowmeters damage during plant start-up, the flowmeter and air
eliminator shall be installed after final flushing.
11.1 The flare gas flow measurement is significant in point of view mass balance, energy
conservation, emissions reduction, local environmental regulatory perspectives, etc.
However, measurement of flow to flares remains particularly different from traditional
flow measurement for plant or custody transfer applications.
DOC. NO. KOC-I-026 Page 45 of 74 Rev. 0
11.2 The flowmeters selected or used for flare gas flow metering shall be suitable to
operate and perform under the following conditions:
f) Density variations
11.3 Multi-path transit-time ultrasonic type flowmeters shall be used in flare gas flow
measurement application. Subject to project specific requirement and KOC
approval, the thermal mass or other type flowmeter can be used for flare gas flow
measurement.
11.4 Flowmeter sensor shall be retractable online under pressure without any
requirement of shutdown. All necessary arrangement shall be supplied by
Manufacturer.
11.5 A process stream data sheet shall be developed for the flare meter, which captures
the most likely composition and flow rate scenarios at minimum, normal and
maximum (upset) conditions. The reliable and detailed process stream information
is critical to flowmeter sizing.
11.6 The potential for two-phase or liquid flow through the meter should be avoided if
possible by locating the meter downstream of knock-out drums.
11.7 The accuracy shall be in the range of ± 2.5 to 5 % full scale and turndown ratio 1:20
to 1:1000 unless otherwise approved by KOC.
11.8 Flare flowmeters are expected to operate over a wide range of velocities. The meter
Manufacturer shall be consulted on how the meter handles flow in these condition
and the effect on metering performance.
11.9 The flowmeters outputs shall be available to the plant DCS / ICSS, PLC or other data
acquisition device, according to common industry protocols. The output signal shall
be two (2) wire 4 - 20 mA HART. Where applicable and specified in project
documents, the modbus serial RS485 also to be provided.
11.10 Depending upon flowmeter technology, outputs other than flow rate may also be
provided. Examples are pressure, temperature, velocity, speed of sound, inferred
density and inferred molecular weight.
DOC. NO. KOC-I-026 Page 46 of 74 Rev. 0
11.11 Pressure and Temperature measurements can be connected directly to the flow
meter for compensation in the meter electronics unless otherwise specified in the
project documents / datasheets.
11.12 A generally accepted minimum number of header diameters are 20 pipe diameters
upstream and 10 diameters downstream. However, these minimum numbers can
vary depending upon upstream and downstream piping configuration and Flowmeter
technology. The Manufacture recommendation shall be followed for exact straight
pipe length requirements.
11.13 The probes of meters (which require only single phase metering) shall be above flare
centre line piping on account of water / other liquids present.
11.14 The flowmeter, piping and other metering components shall be designed so that they
can be removed, as necessary, for inspection, cleaning, replacement or other testing
in the course of performing periodic verifications or other maintenance.
11.15 The flowmeters shall have diagnostic software capabilities, which can be used to
monitor / check the operation of the flowmeter while it is in service. Use of this
capability shall be considered during meter selection and when developing operating
and maintenance procedures.
11.16 The Manufacturer shall provide a detailed periodic verification procedure. This
procedure shall be written specifically for individual flare meter applications, as
necessary and shall be maintained by the KOC.
12.1 General
c) The use of multiphase flowmeters shall be limited to lines where the fluid
shall not be subsequently separated into different phases in any equipment
within a Facility.
e) All the interconnecting cables (from PT, DPT, FT, TT, etc.) inside the skid
shall be terminated up to the skid mounted junction boxes by the
Manufacturer.
DOC. NO. KOC-I-026 Page 47 of 74 Rev. 0
f) The flow computers, DAU and HMI shall be located in the instrument
auxiliary room unless otherwise specified in project documents.
h) All the process wetted parts materials in sour service shall comply with
requirements of NACE MR-0175 / ISO 15156.
i) Inline Meters
ii) Separation type meters (compact or partial separation)
k) Non-nucleonic type design flowmeters for gas, oil and water fraction
calculation shall be used unless otherwise specified in project documents.
o) The flow computer shall be rack mounted type and shall be able to perform
following functions as minimum:
Flow calculations
Instantaneous measurement of inline oil, gas and water flowrates
Gas Volume Fraction (GVF)
Gas Oil Ratio (GOR)
Water cut %
Pressure and Temperature
Data storage.
q) The DAU shall be dual redundant and shall be able to perform / provide the
following as minimum:
s) The DAU shall have printer for alarm reports, diagnostic messages, etc.
DOC. NO. KOC-I-026 Page 49 of 74 Rev. 0
u) Separate connections shall be provided for power supply, input and output
as applicable.
w) The Manufacturer shall ensure that the presence of sand in the well fluids
shall not affect the flowmeter functionality and accuracy.
x) The selected flowmeter model shall have been through a series of third
party verification tests and Manufacturer shall submit associated test
reports prior to its approval.
y) The Factory Acceptance Test (FAT) shall check that all hardware confirms
to the approved drawings / specifications and shall include a full three
phase dynamic / wet functional test for each multiphase flowmeter unless
otherwise approved by KOC.
13.1 The flowmeter and components shall be designed and manufactured, such that,
under normal operating conditions, the instrument shall be unaffected by
electromagnetic disturbances likely to be encountered and shall not radiate Radio
Frequency Interference (RFI) which shall affect the normal operation of other
electronic devices. The flowmeter shall meet EMC requirements of IEC 61800-3.
14.1 The Contractor shall operate a quality system to ensure that the requirements of this
Standard are achieved. The quality system shall be preferably based on ISO 9001
series of standards (latest version), certified by internationally reputed inspection
agencies.
14.2 Verification of the Contractor’s quality system is normally part of the pre-qualification
procedure and therefore not detailed in this Standard.
14.3 For details of quality requirements, KOC-Q-014 “KOC Standard for Project QA / QC
General Requirements” shall be referred.
15.1 All inspection and testing shall be carried-out as per approved “Inspection and Test
Plan” (ITP). Inspection and testing of flowmeters shall include Factory Acceptance
Test (FAT), Site Acceptance Test (SAT) etc. as specified in the project documents
and approved by KOC.
15.2 Flow transmitters shall be factory calibrated to the range as specified in the instrument
datasheet.
15.3 FAT procedure shall be submitted for KOC review and approval. The FAT shall be
performed at the vendor works, where the flowmeters are engineered and
assembled.
15.5 The KOC reserves the right to witness the FAT in full or to witness selected tests. The
flowmeters shall not be delivered until all applicable tests have been verified and
tested successfully.
15.6 Except for DP type flowmeters, for other types of flowmeters shall be provided with
suitable piping connections, with isolation valves and fittings for onsite calibration,
functional checking, carrying-out “Site Acceptance Test” (SAT) etc.
15.7 Where applicable, the “Integrated Factory Acceptance Test” (IFAT) shall be
conducted at ICSS Manufacturer’s works, for checking communication between the
flowmeter system with other systems (like DCS, SCADA, PLDS).
15.8 While performing the inspection at Manufacturer’s works, the following minimum
checks shall be carried-out:
e) Full functional check of flowmeter. If water is used for testing purpose, water
shall be clear from suspended particles and chlorides. The quality of water
shall be as per KOC-G-011. After calibration, the meter shall be blown dry
and preserved.
g) Check size, rating, flange finish and material of construction of the flowmeter
in accordance with this document, drawings and datasheet approved by
KOC.
15.9 Where applicable, SAT procedure shall be submitted for KOC review and approval
and SAT shall be conducted as per approved SAT procedure.
16.1 General
16.1.1 All correspondences, drawings, instructions, data sheets, sizing calculations or any
other written information shall be in English language. In the case of dual languages,
one (1) language shall be English.
16.1.2 All dimensions, units of measurement, physical constants, etc. shall be in SI units,
unless otherwise specified in the Project Documents.
16.1.3 For details of packing, marking and shipping documentation, "KOC Standard for
Packing, Marking and Documentation" (KOC-G-004) shall be referred.
16.2 Packing
16.2.1 All openings shall be properly sealed by proper covering plates or other methods to
ensure against ingress of dirt and transportation hazard.
16.2.2 After completion of testing, the components especially body cavities shall be
thoroughly dried and preserved prior to packing and shipping.
DOC. NO. KOC-I-026 Page 52 of 74 Rev. 0
16.2.3 Easily damageable parts such as machines faces, shall be fitted with caps, plates etc.
for proper protection.
16.3 Documentation
16.3.1 The following drawings / documents shall be submitted by Manufacturer for KOC’s
review / approval, record and use as a minimum:
b) Instrument datasheets
q) Packing details
16.4 The Manufacturer shall submit all drawings, documents, in hard copies and in
electronic files.
16.5 For more details on packing, marking and shipping documentation, KOC-G-004
“KOC Standard for Packing, Marking and Documentation” shall be referred.
17.1 The Manufacturer shall supply all spare parts and consumables required for pre-
commissioning, commissioning and testing activities.
17.2 The Manufacturer shall submit the list of spare parts and consumables required for
commissioning and 2 years operation and maintenance.
17.3 For more details on spare parts and maintenance requirements, KOC-G-009
“KOC Standard for Spare Parts and Maintenance Data” shall be referred.
DOC. NO. KOC-I-026 Page 54 of 74 Rev. 0
Accuracy Rangeability
Flowmeter Recommended Service
(Note 1)
Clean Liquids
Dirty Liquids
Gas
Orifice Corrosive Fluids
Plates Steam ±2% 3:1 to 5:1
Cryogenic Services
High Temperature
Clean Liquids
Dirty Liquids
Clean Gases
V-Cone Slurries ± 0.5 % 10:1
High Temperature
Cryogenic Services (normally applicable)
Clean Liquids
Clean Gases
Corrosive Fluids
Turbine Flowmeter Low Viscous Liquids ± 0.25 % 10:1
High Temperature
Cryogenic Services
Dirty Liquids
Ultrasonic Flowmeter Viscous Liquids ±1% 10:1
(Doppler) Corrosive Fluids
Slurries
Clean Liquids
High / Low Viscous Liquids
Ultrasonic Flowmeter Gases ± 0.2 to 0.5 % 10:1
(Transit Time) Corrosive Liquids
Cryogenic Services
Clean Liquids
Viscous Liquids
Positive Displacement Clean Gases ± 0.2 % 10:1
Corrosive Fluids
High Temperature Services
Clean Liquids
Dirty Liquids
Viscous Liquids
Coriolis ± 0.25 %
Gas 10:1
High Temperature Services
Cryogenic Services
Clean Liquids
Dirty Liquids
Slurries
Thermal Mass Flowmeter Corrosive Fluids ±1% 10:1
Viscous Liquids
Gas
High Temperature Services
Note 1: The accuracies mentioned in above table are percentage (%) of full scale for DP
meters and variable area meters and percentage (%) of actual flow reading for other types of
flowmeters.
DOC. NO. KOC-I-026 Page 56 of 74 Rev. 0
V-Cone 3D 1D
Electromagnetic 5D 2D
Vortex 10D 5D
Positive Displacement - -
Coriolis - -
Note: The upstream and downstream straightrun lengths provided in above table are for
guidance and indicative only. The respective National / International standards and
Manufacturer recommendation shall be followed for exact straight pipe length requirements.
DOC. NO. KOC-I-026 Page 57 of 74 Rev. 0
2 P&ID No.
3 Pipe Line No. Pipe Class
4 Pipe Line Size Line Sch. Wall Thickness
5 Pipe Line Internal Diameter (I.D)
6 Process Fluid
7 Fluid Phase Fluid State
8 @ Min. Flow @ Nor. Flow @ Max. Flow
9 Flow Rate (m3 / hr)
10 Operating Pressure (bar g)
Process Data
11 Operating Temperature °C
12 Design Pressure (bar g) Max. / Min.
13 Design Temperature °C Max. / Min.
14 Density (kg / m3)
15 Viscocity (cP)
16 Vapour Pressure (bar g) / psi a
17 Molecular Weight (g / mol)
18 Maximum Allowable Pressure Drop (bar g)
19 Orifice Type
20 Plate Material Plate Thickness (mm)
21 Sizing Calculation Standard
Orifice Plate
22 Dimensional Details
23 Flowmeter Range (m3 / hr) Max. / Min.
24 Differential Pressure @ Meter Range
25 Orifice Bore Diameter (inch / mm)
26 Beta Ratio (d / D)
27 Drain Hole dia. Vent Hole dia. (mm)
28 Permanent Pressure Loss (bar / psi)
29 Flange Size
30 Flange Material Rating, Facing & Finish
Orifice Flanges
31 Gasket Material
32 Bolt, Nut & Screw Material
33 Pressure Taps Type
34 Pressure Taps Size No. of Taps per Flange
35 Pressure Taps Orientation
36 Construction Details
37 NACE Compliance
38 Manufacturer
Purchase
39 Model Number
Note: This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement”
(Doc. No.: KOC-I-026, Rev. 0).
DOC. NO. KOC-I-026 Page 58 of 74 Rev. 0
22 Flange Material
23 DP @ Maximum Flow bar-g (psig)
24 Maximum Allowable Pressure Drop (bar g)
25 Meter Range
26 Accuracy
27 NACE Compliance
28 Valve Type
Insert / 29 Valve Material
Retract 30 Size, Rating, Facing & Finish
Assembly 31 Model
32 Other Accessories (if any)
33 Manufacturer
Purchase
34 Model Number
Note: This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement”
(Doc. No.: KOC-I-026, Rev. 0).
DOC. NO. KOC-I-026 Page 59 of 74 Rev. 0
Data Sheet
DATA SHEET FOR FLOW NOZZLE
No.:
1 Tag Number
2 P&ID No.
3 Pipe Line No. Pipe Class
General
Data Sheet
DATASHEET FOR V-CONE
No.:
1 Tag Number
2 P&ID No.
3 Pipe Line No. Pipe Class
General
24 Accuracy
25 Body & Cone Material Flange Material
26 Process End Conn. Size, Rating, Facing & Finish
27 Pressure Taps Type No. of Tappings
28 Pressure Taps Material
29 Pressure Taps Size, Rating, Facing & Finish
30 Face to Face Dimensions
31 NACE Compliance
32 Manufacturer
Purchase
33 Model Number
Note: This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement”
(Doc. No.: KOC-I-026, Rev. 0).
DOC. NO. KOC-I-026 Page 62 of 74 Rev. 0
Data Sheet
DATA SHEET FOR DIFFERENTIAL PRESSURE (DP) FLOWMETER
No.:
1 Tag Number P&ID No.
2 Pipe Line No. Pipe Class
General
22 Cable Entry
23 Power Supply Power Consumption
24 Output Signal
25 Local Indication (LCD Display)
26 Accuracy Repeatability
27 Housing Material Painting
28 Certification Ingress Protection (IP)
29 SIL Certification
30 Location of Square Root Extraction Transmitter Control System
31 NACE Compliance
32 Mounting Kit (SS 316)
33 Process Conn. Size & Rating HP LP
Diaphragm Seal
25 Meter Factor
26 Meter Scale Length & Type
27 Housing Material
28 Ingress Protection (IP)
29 Accuracy
30 Rangeability
31 Hazardous Area Certification
32 NACE Compliance
33 Transmitter Output Signal
Options 34 Transmitter Ingress Protection (IP)
35 Transmitter Range
36 Manufacturer
Purchase
37 Model Number
Note: This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement”
(Doc. No.: KOC-I-026, Rev. 0).
DOC. NO. KOC-I-026 Page 64 of 74 Rev. 0
Data Sheet
DATA SHEET FOR ELECTRO MAGNETIC FLOWMETER
No.:
1 Tag Number
2 P&ID No.
General
32 Cable Entry
33 Local Indication (LCD Display)
34 Housing Material
35 Transmitter Mounting (Integral with Meter / Remote)
36 Mounting Kit (SS 316)
37 IP Rating
38 Hazardous Area Certification
39 Self Diagnostics
40 Manufacturer
Purchase
41 Model Number
Note: This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement”
(Doc. No.: KOC-I-026, Rev. 0).
DOC. NO. KOC-I-026 Page 65 of 74 Rev. 0
Data Sheet
DATA SHEET FOR TURBINE FLOWMETER
No.:
1 Tag Number
2 P&ID No.
General
31 Cable Entry
32 Local Indication (LCD Display)
33 Housing Material
34 Transmitter Mounting (Integral with Meter / Remote)
35 Mounting Kit (SS 316)
Hazardous Area
36 Ingress Protection (IP)
Certification
37 Self Diagnostics
38 Manufacturer
Purchase
39 Model Number
Note: This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement”
(Doc. No.: KOC-I-026, Rev. 0).
DOC. NO. KOC-I-026 Page 66 of 74 Rev. 0
Data Sheet
DATA SHEET FOR VORTEX FLOWMETER
No.:
1 Tag Number
2 P&ID No.
General
34 Output Signal
35 Cable Entry
36 Local Indication (LCD Display)
37 Transmitter Housing Material
38 Mounting Kit (SS 316)
Ingress Protection Hazardous Area
39
(IP) Certification
40 Internal Self Diagnostics
41 Manufacturer
Purchase
42 Model Number
Note: This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement”
(Doc. No.: KOC-I-026, Rev. 0).
DOC. NO. KOC-I-026 Page 67 of 74 Rev. 0
Data Sheet
DATA SHEET FOR ULTRASONIC FLOWMETER
No.:
1 Tag Number
2 P&ID No.
General
37 Output Signal
38 Cable Entry
39 Local Indication (LCD Display)
40 Housing Material
41 Transmitter Mounting (Integral with Meter / Remote)
42 Mounting Kit (SS 316)
43 Ingress Protection (IP)
44 Hazardous Area Certification
45 Self Diagnostics
DOC. NO. KOC-I-026 Page 68 of 74 Rev. 0
46 Flow Conditioner
47 Transmitter Mounting Kit (SS 316)
Accessories
48 Sensor Mounting Accessories
49 Retraction Tool
Purchase 50 Manufacturer Model Number
Note: This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement”
(Doc. No.: KOC-I-026, Rev. 0).
DOC. NO. KOC-I-026 Page 69 of 74 Rev. 0
Data Sheet
DATA SHEET FOR CORIOLIS MASS FLOWMETER
No.:
1 Tag Number
2 P&ID No.
General
39 Cable Entry
40 Local Indication (LCD Display)
41 Transmitter Housing Material Surface Finish
42 Process Connection & Wetted Parts Material
43 Transmitter Mounting
44 Ingress Protection (IP)
45 Hazardous Area Certification
46 Self Diagnostics
47 Mounting Integral Display
DOC. NO. KOC-I-026 Page 72 of 74 Rev. 0
48 Housing Material
Flow 49 Power Supply
Computer 50 Serial Communication Protocol (Redundant)
51 Hazardous Area Certification Ingress protection
52 Accuracy
Performance
53 Repeatability
54 Reporting Computer
Accessories
55 Flow Straightener Material
and Others
56 Tubing And Fittings Material
57 MPFM Manufacturer Model Number
Purchase
58 Transmitter Manufacture Model Number
Notes: 1) This Datasheet shall be read in conjunction with “KOC Standard for Process Flow Measurement” (Doc.
No.:KOC-I-026, Rev. 0).
2) This is only typical datasheet. The process data (minimum flow, maximum flow, operating and design
conditions, etc.) shall be provided for summer and winter cases at different water cut levels (as per project
specific water cut design requirements ex. 80 % water cut & 20 % water cut) as an attachment to this
datasheet.
3) For the fields which is not relevant / applicable, those fields can be filled with “Not Applicable”.
DOC. NO. KOC-I-026 Page 73 of 74 Rev. 0
Body
Rotating Element
23 Materials
Shaft Blades
Outer Housing
24 Accuracy Repeatability
25 Bearing Type & Material
26 Packing Type of Coupling
27 Register Type
Counter 28 Totaliser Reset
29 Capacity
30 Power Supply Power Consumption
31 Output Signal
Transmitter 32 Cable Entry
33 Hazardous Area Certification IP Rating
34 LCD (Local Indication) Housing Material
35 Shutoff Valve
Accessories
& Options
ACKNOWLEDGEMENT
The Draft of this document “KOC Standard for Process Flow Measurement”
(Doc. No. KOC-I-026, Rev. 0) has been circulated to KOC User Teams for review
& comments and the responses received were suitably resolved and incorporated into the
document.
The Team Leader Standards / Chairman ESTC Sub-Committee (Technical) would like to
thank the KOC User Teams, ESTC Sub-Committee (Technical) Members and Task Force
Members for providing technical inputs and valuable comments for the successful
development of this Standard.